Upload
avis-alexis-cain
View
230
Download
2
Tags:
Embed Size (px)
Citation preview
Electrical Test InstrumentsAnalog Or Digital• Voltmeters – Measuring Potential Difference• Ammeters – Measuring Current Flow
– Clamp On
• Ohmmeters – Measuring Resistance And Checking Continuity
• Capacitance – Check Capacitors• Multimeters – VOM/DMM - All The Above
General Awareness• Job Site Safety• Lock-Out/Tag-Out• Personal Safety• Clothing• Lifting
•Fire•Pressure•Hazardous Materials•Service Trucks•Electrical
First Line Of Safety
Trust Your Sixth Sense And When It Tells You Not To Do Something
DON’T DO IT!!!
CHECK FOR AN OPEN CIRCUIT
A break in the continuous path of an electrical circuit.1. Indicated by an infinity reading with an OHMMETER.2. Indicated by a voltage reading with a VOLT METER.
CHECK FOR A SHORT CIRCUIT
When the electrons take a path back to the source that allows its to bypass all or most of the circuit resistance.
1. Indicated by a blown fuse – read VOLTAGE across the fuse.
2. Indicated by reading INFINITE OHM across fuse.
3. Indicated by a ground (When electrons take a path back to the source that
adds additional resistance to the circuit) ZERO OHMS READING at component being checked to ground .
Check for Open and closed switches
Load120
VOLTS
0
VOLTS
Load120 vac
120 vac
Pitting will cause a voltage drop across a set of closed contacts.
ELECTRICAL INDICATING DEVICES
VoltmeterAlways used in parallel with the load or the
switch to be tested.
N
H120 v
MOTOR
Voltmeter
Emergency Switch
0 120
Voltage Drop
• When checking the voltage applied to a load such as an outdoor unit, the voltage applied should be measured in two steps: first with the load de-energized and then with the load energized
• The difference between the de-energized and the energized voltage is referred to as the voltage drop
Voltage Drop
• The voltage should not drop more than 3% of the de-energized applied voltage
• A voltage drop higher than 3% usually indicates that the gauge of the wire leading to the load is too small
• For example, if 223 volts were measured at the contactor of the outdoor unit de-energized…
Voltage Drop
• And then 220 volts were measured with the contactor energized…
• This would indicate a voltage drop of only 1.35%
This would be an acceptable voltage drop
%35.1100 x223
220223
Voltage Drop• However, if 223 volts were measured at the
contactor of the outdoor unit de-energized, and then 210 volts were measured with the contactor energized
• The voltage drop would be:
This would be an unacceptable voltage drop
223 – 210 X 100 = 5.82% 223
Troubleshooting Switches
• Switches that are closed will have no voltage drop
• Switches that are open will have line voltage across their terminals
Switches are wired in series with loads and are used to control their operation, such as a low
pressure switch
Load OHM
Load
0
OHM
Digital Meter: OL
Digital Meter: 0
120 vac
120 vac
Pitting will cause a reduced ohm reading across a set of closed contacts.
∞
N S
∞ 0
BatteriesZero adjustment
C
S R
Ω Com
Analog scale
Permanent magnet
Iron core (bobbin)
Coil
Compressor terminals
100 500 10
Never connect an Ohmmeter to an energized circuit
Ohmmeter
Always disconnect power to the circuit being tested first. Then use the Ohmmeter in parallel
with the load or the switch to be tested.
Ohmmeter120 v
N
H
MOTOR
EmergencySwitch
Ammeter
Always used in series with the load or the circuit to be tested.
Ammeter
MOTOR
120 v
N
H
Clamp-on ammeter
Alternative method is to use a clamp-on ammeter.
EmergencySwitch
6