TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 1 of 22 ALTER TECHNOLOGY TÜV NORD, S.A.U. Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja 41092 SEVILLA, SPAIN TÜV NORD GROUP ATNF310.C ALTER TECHNOLOGY TÜV NORD, S.A.U.– V.A.T.: ES A 41990490 – R.M. Sevilla, Tomo 3.892 de Sociedades, Folio 98, Hoja nº SE-37.807, inscripción 30ª REPORT Nr.: 2016901145-EMC ALTER TECHNOLOGY TÜV NORD, S.A.U. LABORATORIO DE EQUIPOS Y CERTIFICACIÓN C/ de la Majada, 3. 28760 TRES CANTOS Madrid (Spain) Telf.: +34 918041893 Fax: +34 918041664 Rec. date: 22/09/2016 Start date: 29/09/2016 Final date: 14/10/2016 TEST: EMC PRODUCT: MONSOL-1000/1500V MODEL: MONSOL 1000/1500V-H ORDERED BY: SMART SOLAR SOLUTIONS, S.L. ADDRESS: Creative Tower, P.O. Box 442 Fujairah, UAE (United Arab Emirates) TEST SPECIFICATIONS: EN 61326-1:2013 REFERENCE DOCUMENTS: ATN-Q-IO-22-98 Ed. 2 The results of this report are only representative of the sample/s tested PERFORMED BY: APPROVED BY: G. Blázquez M. González Laboratory Technician Laboratory Manager Partial copy of this document is not permitted without written authorization

TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

  • Upload
    others

  • View
    16

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

TEST REPORT

(*).-Marked tests or documents are not covered by ENAC accreditation

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 1 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U. Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja 41092 SEVILLA, SPAIN

TÜV NORD GROUP

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

REPORT Nr.:

2016901145-EMC

ALTER TECHNOLOGY TÜV NORD, S.A.U.

LABORATORIO DE EQUIPOS Y CERTIFICACIÓN C/ de la Majada, 3. 28760 TRES CANTOS Madrid (Spain)

Telf.: +34 918041893 Fax: +34 918041664

Rec. date: 22/09/2016

Start date: 29/09/2016

Final date: 14/10/2016

TEST: EMC

PRODUCT: MONSOL-1000/1500V

MODEL: MONSOL 1000/1500V-H

ORDERED BY: SMART SOLAR SOLUTIONS, S.L.

ADDRESS: Creative Tower, P.O. Box 442 Fujairah, UAE (United Arab Emirates)

TEST SPECIFICATIONS:

EN 61326-1:2013

REFERENCE DOCUMENTS:

ATN-Q-IO-22-98 Ed. 2

The results of this report are only representative of the sample/s tested

PERFORMED BY: APPROVED BY:

G. Blázquez M. González

Laboratory Technician Laboratory Manager

Partial copy of this document is not permitted without written authorization

Page 2: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 2 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

CHANGES RECORD

EDITION / REVISION DATE REVISED EDITION REASON FOR

CHANGE

2016901145-EMC 17/10/2016 - Initial Version

- - - -

- - - -

NOTE.- The following editions of the test reports cancel and replace all the content of the previous ones.

Page 3: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 3 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

INDEX

1 OBJECT ........................................................................................................................................... 4

2 SUMMARY OF RESULTS ................................................................................................................ 4

3 ACRONYMS AND ABBREVIATIONS ............................................................................................... 4

4 EUT IDENTIFICATION AND EUT CONDITIONS .............................................................................. 5

4.1 EUT IDENTIFICATION .............................................................................................................. 5

4.2 GENERAL EUT CONDITIONS .................................................................................................. 6

5 TESTS AND RESULTS .................................................................................................................... 7

5.1 RADIATED EMISSION TEST .................................................................................................... 7

5.2 CONDUCTED EMISSION TEST................................................................................................ 9

5.3 ELECTROSTATIC DISCHARGES IMMUNITY TEST .............................................................. 13

5.4 RADIATED IMMUNITY TEST .................................................................................................. 14

5.5 EFT IMMUNITY TEST ............................................................................................................. 16

5.6 SURGES IMMUNITY TEST ..................................................................................................... 17

5.7 CONDUCTED IMMUNITY TEST ............................................................................................. 19

5.8 POWER FREQUENCY MAGNETIC FIELD ............................................................................. 20

6 UNCERTAINTIES ........................................................................................................................... 20

7 COMPETENCE AND WARRANTIES.............................................................................................. 20

8 EQUIPMENT USED DURING THE TESTS .................................................................................... 21

9 ENVIRONMENTAL CONDITIONS IN THE LABORATORY ............................................................ 22

Page 4: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 4 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

1 OBJECT

The purpose of these tests is to verify emission levels of electromagnetic disturbances emitted by the EUT and its immunity to electromagnetic radiation according to the criteria applied by the test specifications.

2 SUMMARY OF RESULTS

TEST RESULT

Radiated emission, electric field SATISFACTORY

Conducted emission SATISFACTORY

Electrostatic Discharges (ESD) SATISFACTORY

Radiated immunity, electric field SATISFACTORY

Electrical Fast Transients (EFT) SATISFACTORY

Surges SATISFACTORY

Conducted immunity SATISFACTORY

Power frequency magnetic field NOT APPLICABLE(1)

REMARKS:

The EUT belongs to Group 1 and Class A for emission test according to the test specification.

The EUT is an equipment intended to be used in an industrial electromagnetic environment so it must comply with the immunity requirements specified in table 2 of the test specification.

(1) According to the manufacturer, the EUT has not any element sensitive to magnetic field.

Table 1

3 ACRONYMS AND ABBREVIATIONS

AC: Alternating Current.

AP max.: Maximum Atmospheric Pressure.

AP min.: Minimum Atmospheric Pressure.

AVG: Average.

CDN: Coupling/Decopuling Network.

DC: Direct current.

EFT: Electrical Fast Transients.

EMC: Electromagnetic Compatibility.

ESD: Electrostatic Discharges.

EUT: Equipment Under Test.

HCP: Horizontal Coupling Plane

HW: Hardware.

Page 5: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 5 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

P/N: Part Number.

Rec. date: Reception date of the EUT.

RH max.: Maximum Relative Humidity.

RH min.: Minimum Relative Humidity.

S/N: Serial Number.

SW: Software.

T max.: Maximum Temperature.

T min.: Minimum Temperature.

VCP: Vertical Coupling Plane.

4 EUT IDENTIFICATION AND EUT CONDITIONS

4.1 EUT IDENTIFICATION

The EUT is a strings monitoring hardware for photovoltaic plants.

The EUT tested in the laboratory has the following identification:

MANUFACTURER: Smart Solar Solution (Monsol)

PRODUCT: MONSOL-1000/1500V

MODEL: MONSOL 1000/1500V-H

SERIAL NUMBER: Muestra 001 (defined by Laboratory)

SW VERSION: 1403

HW VERSION: s0003c

Table 2

Photographs 1 and 2

Page 6: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 6 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

Photograph 3

4.2 GENERAL EUT CONDITIONS

According to the manufacturer, the EUT is always supplied by a dedicated power supply and its cable cannot be longer than 30 meters. The EUT is supplied with VDC = 24 V ± 10% (2 wires).

During the tests, the RS485 port of the EUT was connected to an auxiliary PC through a RS485-USB converter and unshielded cable.

During the tests:

o An auxiliary power supply was set to 7 ADC, approximately.

o the “Busbar port” of the EUT was connected to the negative pole of the auxiliary power supply

o The positive pole of the auxiliary power supply was connected to a S3 port of the EUT.

o The DIN1 port was connected to an unshielded cable.

According to the manufacturer, the cables connected to these ports cannot be longer than 3 meters.

See the following figure for the EUT connection:

Figure 1. EUT connection diagram.

EUT

RS485-USB CONVERTER PC RS485

24 VDC

DIN1

BUSBAR S3

AUX. POWER

- SUPPLY +

Page 7: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 7 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

During the tests, a SW application, provided by the manufacturer, was running in the auxiliary PC (see photograph 4). Through this application:

o The EUT was in continuous communication with the auxiliary.

o The states of the each port of the EUT was monitored in the auxiliary PC.

The measurement of the S3 port was 7 A. approximately.

The DIN state was ON or OFF depending on if it is short-circuited or open-circuited.

Photograph 4

CONTROL:

o The communications with the auxiliary PC

o The states and the measurements of the ports of the EUT (in S3 port must be appear the same current as in the auxiliary power, approximately 7 A).

5 TESTS AND RESULTS

5.1 RADIATED EMISSION TEST

5.1.1 Procedure

The test is carried out according to the standard EN 61326-1.

The EUT is measured as a tabletop equipment.

The horizontal distance from the boundary of the EUT and the receiver antenna is three meters.

The receiver antenna scans continuously in height from one meter up to four meters, changing from vertical to horizontal polarization, in order to find maximum meter reading at each test frequency.

The EUT is rotated continuously to find the maximum field strength readings.

The interference is weighted with quasi-peak indication.

The uncertainty measurement, for k = 2, is ± 5 dB.

5.1.2 Conditions

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration in the following photographs.

Page 8: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 8 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

Photographs 5 and 6

5.1.3 Acceptance Criterion

The EUT must comply with the limits specified in the following table:

LIMITS (d = 3 meters)

FREQUENCY RANGE QUASI-PEAK

30 MHz – 230 MHz 50 dBV/m

230 MHz – 1000 MHz 57 dBV/m

Table 3

5.1.4 Result

The measurement results FULFIL with the specified limits. See the test results in the following graph(s) and/or table(s).

Page 9: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 9 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

Graph 1. Band 30 MHz to 1 GHz

QUASI-PEAK VALUES

FREQUENCY MHz

LEVEL dBµV/m

LIMIT dBµV/m

MARGIN dB

HEIGHT cm

AZIMUTH deg

POLARIZATION

33.542500 44.3 50.0 5.7 99.0 155.0 VERTICAL

35.522500 44.3 50.0 5.7 112.0 170.0 VERTICAL

37.262500 44.1 50.0 5.9 113.0 211.0 VERTICAL

37.412500 44.9 50.0 5.1 99.0 152.0 VERTICAL

40.202500 44.1 50.0 5.9 105.0 117.0 VERTICAL

48.332500 33.3 50.0 16.7 189.0 180.0 VERTICAL

REMARKS:

Uncertainty measurement: 5 dB

Table 4

5.2 CONDUCTED EMISSION TEST

The EUT is not connected to a DC power distribution network. According to the manufacturer, the EUT is supplied by a dedicated power supply so this test should be not applicable. This test is performed by costumer requirement.

5.2.1 Procedure

The test is carried out according to the standard EN 6326-1.

The EUT is measured as a tabletop equipment.

10 15

20 25 30

35 40 45 50 55 60 65

30M 50 60

80 100M 200 300 400 500 800 1G

Level in

dB

µV

/m

Frequency in Hz

Preview Peak Measurement Final Quasi-peak Measurement Class A QUasi-peak Limit

Page 10: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 10 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

a. Power port

The EUT is connected to power supply through an artificial mains network with a nominal

impedance of (50 /50 H).

Both lines are measured between the lead and GND reference plane.

The interference is weighted with average and quasi-peak indication.

The uncertainty measurement, for k = 2, is ± 3.4 dB.

5.2.2 Condition

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration in the following photograph.

Photograph 7

5.2.3 Acceptance criterion

The EUT must comply with the limits specified in the following tables:

POWER PORT LIMITS

FREQUENCY RANGE AVERAGE QUASI-PEAK

150 kHz – 500 kHz 66 dBV 79 dBV

5 MHz to 30 MHz 60 dBV 73 dBV

Table 5

Page 11: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 11 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.2.4 Result

The measurement results FULFIL with the specified limits. See the test results in the following graphs and/or table(s).

Graph 2. Positive line

AVERAGE VALUES

FREQUENCY MHZ

LEVEL dBµV/m

LIMIT dBµV/m

MARGIN dB

LINE PE

0.510000 59.3 60.0 0.7 + GND

0.852000 59.5 60.0 0.5 + GND

1.194000 58.8 60.0 1.2 + GND

1.873500 57.9 60.0 2.1 + GND

2.206500 55.1 60.0 4.9 + GND

2.553000 53.5 60.0 6.5 + GND

2.890500 54.8 60.0 5.2 + GND

3.219000 54.8 60.0 5.2 + GND

3.565500 58.2 60.0 1.8 + GND

3.907500 55.3 60.0 4.7 + GND

REMARKS:

Uncertainty measurement: 3.4 dB

Table 6

- 10

0

10

20

30

40

50

60

70

80

150k 300 400 500 800 1M 2M 3M 4M 5M 6 8 10M 20M 30M

Le

vel i

n d

BµV

Frequenc y in Hz

Page 12: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 12 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

Graph 3. Negative line

AVERAGE VALUES

FREQUENCY MHZ

LEVEL dBµV/m

LIMIT dBµV/m

MARGIN dB

LINE PE

0.510000 59.6 60.0 0.4 – GND

0.852000 59.2 60.0 0.8 – GND

1.189500 57.6 60.0 2.4 – GND

1.536000 54.1 60.0 5.9 – GND

1.869000 55.9 60.0 4.1 – GND

2.553000 57.9 60.0 2.1 – GND

2.895000 57.1 60.0 2.9 – GND

3.232500 53.1 60.0 6.9 – GND

3.574500 53.8 60.0 6.2 – GND

4.258500 55.6 60.0 4.4 – GND

REMARKS:

Uncertainty measurement: 3.4 dB

Table 7

- 10

0

10

20

30

40

50

60

70

80

150k 300 400 500 800 1M 2M 3M 4M 5M 6 8 10M 20M 30M

Le

vel i

n d

BµV

Frequenc y in Hz

Page 13: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 13 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.3 ELECTROSTATIC DISCHARGES IMMUNITY TEST

5.3.1 Procedure

The test is carried out according to the standard EN 61326-1.

Number of discharges applied at each point: 10.

Single discharges applied and at least one second between discharges.

The EUT is tested as a tabletop equipment.

Only indirect discharges are applied because, according to the manufacturer, the EUT is only accessible to qualified personnel and, during the normal operation, the EUT is located inside a closed box.

In the following tables, the ESD application points are described.

INDIRECT DISCHARGES

HCP & VCP TEST LEVEL 2 : ± 4 kV POLARITY : Positive y negative.

POINTS DESCRIPTION RESULT

A Front side HCP OK

B Left side HCP OK

C Right side HCP OK

D Rear side HCP OK

E Front side VCP OK

F Left side VCP OK

G Right side VCP OK

H Rear side VCP OK

REMARKS:

N.A. = Not applicable.

OK. = Satisfactory. The equipment complies with performance criteria

NOK. = Not satisfactory. The equipment does not comply with performance criteria

HCP Applicable only for table-top equipment.

Table 8

5.3.2 Conditions

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration and some application points in the following photographs.

Page 14: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 14 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

VCP HCP

Photographs 8 and 9

5.3.3 Acceptance Criterion

The EUT must comply with the performance criterion B specified in the clause 6.4.3 of the standard EN 61326-1.

5.3.4 Result

ESD STANDARD CRITERION

OBSERVED CRITERION

RESULT

Direct contact discharges B - NOT APPLICABLE

Direct air discharges B - NOT APPLICABLE

Indirect contact discharges B A SATISFACTORY

REMARKS:

During the test, the EUT operated correctly, maintaining the communication and without loss of function or degradation of performance.

(1) Not applicable due to the EUT is only accesible toqualified personnel

Table 9

5.4 RADIATED IMMUNITY TEST

5.4.1 Procedure

The test is carried out according to the standard EN 61326-1.

The frontal and rear faces of the EUT were tested due to the small size of the EUT.

The transmitter antennas are placed in horizontal and vertical polarization. The distance between the EUT and the transmitter antenna is three meters for the frequencies below 1 GHz and a meter for the upper frequencies.

For frequencies above 1 GHz, the windows test method is used. In this case, the Windows 1, 2 and 3 have been used.

Page 15: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 15 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

SEVERITY LEVEL

DWELL TIME

RATE OF SWEEP

FREQUENCY RANGE

MODULATION

10 V/m 3 s 1 % 80 – 1000 MHz 1 kHz, 80% AM

3 V/m 3 s 1 % 1.4 – 2 GHz 1 kHz, 80% AM

1 V/m 3 s 1 % 2 – 2.7 GHz 1 kHz, 80% AM

Table 10

5.4.2 Conditions

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration in the following photographs.

Photographs 10 and 11

5.4.3 Acceptance Criterion

The EUT must comply with the performance criterion A specified in the clause 6.4.2 of the standard EN 61326-1.

5.4.4 Result

RADIATED IMMUNITY ELECTROMAGNETIC FIELD

STANDARD CRITERION

OBSERVED CRITERION

RESULT

Enclosure A A SATISFACTORY

REMARKS:

During the test, the EUT operated correctly, maintaining the communication and without loss of function or degradation of performance.

Table 11

Page 16: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 16 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.5 EFT IMMUNITY TEST

5.5.1 Procedure

The test is carried out according to the standard EN 61326-1.

Rise time of the individual pulse: 5 ns. 30%.

Impulse duration: 50 ns. 30%.

Burst period: 300 ms 20%.

The test was applied during 2 minutes. During this period 400 burst were applied.

Coupling in common mode.

Both polarities were tested.

Repetition rate: 5 kHz.

APPLICATION VOLTAGE

LEVEL COUPLING/DECOUPLING

NETWORK CLAMP

Power port(1) 2 kV X

RS-485 port 1 kV X

REMARKS:

(1) Although this port is not connected to a DC power distribution network, (according to the manufacturer, the EUT is supplied by a dedicated power supply), this test was performed with a CDN because is a worst case.

Table 12

5.5.2 Conditions

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration in the following photographs.

Photographs 12 and 13

Page 17: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 17 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.5.3 Acceptance Criterion

The EUT must comply with the performance criterion B specified in the clause 6.4.3 of the standard EN 61326-1.

5.5.4 Result

EFT STANDARD CRITERION

OBSERVED CRITERION

RESULT

Power port B A SATISFACTORY

RS-485 port B A SATISFACTORY

Rest of ports B - NOT APPLICABLE(1)

REMARKS:

During the test, the EUT operated correctly, maintaining the communication and without loss of function or degradation of performance.

(1) Applicable only to cables which according to the manufacturer’s specification supports communication on cable lengths greater than 3 meters.

Table 13

5.6 SURGES IMMUNITY TEST

5.6.1 Procedure

The test is carried out according to the standard EN 61326-1.

Maximum pulse repetition rate 1 / 60 s.

Impulse duration: 1.2/50 s.

Minimum Nr. of tests: 5 pos. y 5 neg.

Positive and negative polarity.

APPLICATION VOLTAGE

LEVEL OUTPUT

IMPEDANCE

RS-485 port. Line to GND 0.5 kV and 1 kV 42

Table 14

5.6.2 Conditions

Due to the impact of the CDN, the EUT does not work properly. The EUT and the SW are in continuous communication but, the data shown by the SW do not refresh. It is necessary to remove the CDN and, to press Disconnect and Connect buttons in the SW program to verify the correct operation of the EUT.

For this test, during the test, the correct operation of the EUT is verify through the LEDS of the EUT and the command “bus monitor” in the SW.

See the test set-up configuration in the following photograph.

Page 18: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 18 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

Photograph 14

5.6.3 Acceptance Criterion

The EUT must comply with the performance criterion B specified in the clause 6.4.3 of the standard EN 61326-1.

5.6.4 Result

SURGES. COMMON & DIFFERENTIAL MODE

STANDARD CRITERION

OBSERVED CRITERION

RESULT

Power port B - NOT APPLICABLE(1)(2)

RS-485 port B B SATISFACTORY

Rest of ports B - NOT APPLICABLE(2)

REMARKS:

During the test, the EUT maintain the communication but the data in the SW were not correct due to the impact of the CDN. After the test, the CDN was removed and the EUT operated correctly (see clause 5.6.2 for more information).

(1) The EUT is not connected to a DC power distribution network. According to the manufacturer, the EUT is supplied by a dedicated power supply

(2) Applicable only to cables which according to the manufacturer’s specification supports communication on cable lengths greater than 30 meters.

Table 15

Page 19: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 19 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.7 CONDUCTED IMMUNITY TEST

5.7.1 Procedure

The test is carried out according to the standard EN 61326-1.

Direct injection.

The following coupling/uncoupling elements are used in the test:

CDN M2 on power port.

CDN T2 on RS-485 port.

Clamp for decoupling

During the test on DC power port, the CDN T2 was loaded with 50 ohms; and, during the test on the RS-485 port, the CDN M2 was loaded with 50 ohms.

SEVERITY LEVEL

DWELL TIME

RATE OF SWEEP

FREQUENCY RANGE

MODULATION

3 Vrms 3 s 1 % 0.15 to 80 MHz 1 kHz, 80% AM

Table 16

5.7.2 Conditions

There are not specific EUT conditions for these tests. See clause 4.2.

See the test set-up configuration in the following photographs.

Photographs 15 and 16

5.7.3 Acceptance Criterion

The EUT must comply with the performance criterion A specified in the clause 6.4.2 of the standard EN 61326-1.

Page 20: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 20 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

5.7.4 Result

CONDUCTED IMMUNITY (150 kHz – 80 MHz)

STANDARD CRITERION

OBSERVED CRITERION

RESULT

Power port A A SATISFACTORY

RS-485 port A A SATISFACTORY

Rest of ports A - NOT APPLICABLE(1)

REMARKS:

During the test, the EUT operated correctly, maintaining the communication and without loss of function or degradation of performance.

(1) Applicable only to cables which according to the manufacturer’s specification supports communication on cable lengths greater than 3 meters.

Table 17

5.8 POWER FREQUENCY MAGNETIC FIELD

This test is only applicable to magnetically sensitive equipment.

6 UNCERTAINTIES

The expanded measurement uncertainty has a coverage factor k=2, which for a normal distribution corresponds to a coverage probability of approximately 95.5%.

The uncertainties are the following:

Radiated emission uncertainty (k = 2):

o Frequencies lower than 1 GHz: 5 dB

Conducted emission uncertainty (k = 2):

o Power LISN measurements: 3.4 dB

7 COMPETENCE AND WARRANTIES

This Laboratory is accredited by ENAC (Entidad Nacional de Acreditación) to carry out tests according to the conditions defined in the scope of accreditation 345/LE808.

Page 21: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 21 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

8 EQUIPMENT USED DURING THE TESTS

INSTRUMENT MARK MODEL INVENTARY

NUMBER

Termometer/Higrometer HOMFOR ETH16 LE0509.000

Termometer/Higrometer HOMFOR ETH16 LE0515.000

Power supply HP 6012B LE0651.000

Power supply HP 6032A LE21093.000

Anechoic chamber Euroshield RFDD-F/A-60 LE0454.000

Control room Ray-Proof 81R LE0454.002

EMI Receiver R&S ESIB 40 LE0698.000

EMI Receiver & Display R&S ESBI LE0486.000

Biconilog antenna EMCO 3142 LE0481.000

LISN Electro-Metrics ANS-25/2 LE0554.000

SW for Radiated and conducted disturbance tests.

R&S EMC32 LE0698.001

ESD generator Schaffner NSG438 LE0536.000

RF generator R&S SMR20 LE0561.000

Amplifier OPHIR 5127 FE LE0794.000

Amplifier OPHIR 5022 AFE LE0800.000

Amplifier AMPLIFIER RESEARCH

40S1G4 LE0959.000

Power meter BOONTON 4230 LE0717.000

Sonda 80MHz BOONTON 51011 LE0717.001

Horn antenna EMCO 3115 LE0860.000

Electric Field Probe PMM EP601 LE0801.000

SW for radiated immunity test TL Version 4.0 LE0756.000

Immunity generator EM TEST UCS 500 LE0500.000

Coupling clamp Schaffner CDN-125 LE0462.000

CDN KEYTEC CM-I/OCD LE0780.000

RF generator HP 8656B LE0447.001

Amplifiier AMPLIFIER RESEARCH

- LE0447.000

CDN FCC FCC-801-M2-16A LE0489.000

CDN FCC FCC-801-T2 LE0491.000

Decoupling clamp FCC F.2031-DCN-3mm LE0476.000

Adaptor 50-150 FCC FCC-801-150-50 LE0480.000

Adaptor 50-150 FCC FCC-801-150-50 LE0480.000

Load (50 ) BIRD 50-T-MN LE0478.000

Attenuator (6 dB) BIRD 50-A-MFN-06 LE0477.000

Probe 10 KHz BOONTON 91-12F / 952002 LE0717.005

Power meter BOONTON 9200B LE0739.000

SW for conducted immunity test TL Version 1.0 LE0755.000

Table 18

Page 22: TEST REPORT - Monsol · 2018-11-26 · TEST REPORT (*).-Marked tests or documents are not covered by ENAC accreditation ... o the “Busbar port” of the EUT was connected to the

REPORT Nr.: 2016901145-EMC DATE: 17/10/2016 PAGE: 22 of 22

ALTER TECHNOLOGY TÜV NORD, S.A.U., Tomas Alba Edison, 4, Parque Científico y Tecnológico Cartuja. 41092 SEVILLA, SPAIN

ATNF310.C

ALT

ER

TE

CH

NO

LOG

Y T

ÜV

NO

RD

, S.A

.U.–

V.A

.T.:

ES

A 4

1990

490 –

R.M

. Sev

illa,

Tom

o 3.

892

de S

ocie

dade

s, F

olio

98,

Hoj

a nº

SE

-37.

807,

insc

ripci

ón 3

9 ENVIRONMENTAL CONDITIONS IN THE LABORATORY

TEMPERATURE (ºC)

RELATIVE HUMIDITY (%)

ATMOSPHERIC PRESSURE (mBar)

T max. = 23 T min. = 21 RH max. = 43 RH min. = 33 AP max.= 951.6 AP min. = 927.7

Table 19