TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 2 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

A) Test results for Paragraph 3 of Appendix II of FSD Circular Letter No. 1/2006, reference to PPA/104(A) (4th Revision)

TEST ITEM TITLE REMARK NOTE PASS FAIL

a.

Parts of insulating material retaining current-carrying parts in position shall comply with the Needle Flame Test according to Section 13.3.1 of BS EN / EN / IEC 60598-1

X

b.

Parts of insulating material which do not retain live parts in position, but which provide protection against electric shock, and parts of insulating material retaining SELV, parts in position shall comply with the Glow Wire Test at 650°C according to Section 13.3.2 of BS EN / EN / IEC 60598-1

X

c. The enclosures of the emergency lighting luminaire are subjected to the Glow Wire Test at 850°C according to Section 13.3.2 of BS EN / EN / IEC 60598-1

X

d.

The external parts (including lighting fittings, lamp cover, connecting tube between lamp and the enclosure, switch, external fuse holder, etc) of the emergency lighting luminaire are subjected to the Glow Wire Test at 850°C according to Section 13.3.2 of BS EN / EN / IEC 60598-1

X

Conclusion : PASS

Page 3: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 3 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

B) Test results for Paragraph 4 of Appendix II of FSD Circular Letter No. 1/2006, reference to PPA/104(A) (4th Revision)

All power cables extended outside the enclosure of a self-contained emergency lighting luminaire, other than the wiring connecting the luminaire to normal supply, shall be provided with certificate, test reports or relevant document to demonstrate the compliance with the following condition(s):

Standard / conditions: Findings:

BS6387 Cat CWZ, or N.A.

BS6207 or BS EN 60702, or N.A.

Other international standards acceptable to the Director of Fire Services, or N.A.

Specification complying with criteria for exemption in F.S.D.

circular letter no. 1/2003 N.A.

Conclusion: Not applicable

Page 4: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 4 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

C) Test results for Paragraph 5 of Appendix II of FSD Circular Letter No. 1/2006,

reference to PPA/104(A) (4th Revision)

An automatic trickle charger fitted with pilot lights or other indicating device shall be provided for battery ..: YES

Type of rechargeable battery .............................. (V) : Ni-Cd

Maximum voltage obtained Vmax ....................... (V) : 4,21

No. of cells in the battery (n) .....................................: 3

End point voltage per cell Uf ................................................. (V) : 1.00

End point voltage n Uf .......................................... (V) : 3,00

Voltage of battery under load (after discharging through the lamp of SUT but before charging) ................. (V) :

3,00 (0.95n Uf ≤ V ≤ n Uf)

Discharge current Isd ........................................... (A) : 0,52

Rated duration provided by client (T) ................... (h) : 1

Voltage of battery after discharging T hours......... (V) : 3,68

Voltage shall not be less than End point voltage n Uf Volts

Conclusion : PASS

Page 5: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 5 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

D) Test results for Paragraph 6, 7 of Appendix II of FSD Circular Letter No. 1/2006,

reference to PPA/104(A) (4th Revision)

Table of measurement

Maximum lux level within 1 hour operation (L max) ................ (Lux) : 9,56

Lux level after operating for 5 seconds (L 5s ) ....................... (Lux) : 9,56

Lux level after operating for 1 hour (L 1hr ) ............................ (Lux) : 6,87

Conclusion

The emergency light is considered to pass the requirement of maintaining lighting level with reference to Paragraph 6 of Appendix II of FSD Circular Letter No. 1/2006, reference to PPA/104(A)

(Passing criteria: L 1hr ≥ 50% of L max)

PASS

The emergency light is considered to pass the requirement of response time with reference to Paragraph 7 of Appendix II of FSD Circular Letter No. 1/2006, reference to PPA/104(A)

(Passing criteria: L 5s ≥ 90 % of L 1hr)

PASS

Plotting:

Page 6: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 6 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

E) Test results for Paragraph 8 of Appendix II of FSD Circular Letter No. 1/2006,

reference to PPA/104(A) (4th Revision)

‘TEST’ switch and charge monitor light shall be provided..................................................................... : YES

A low voltage cut out shall be provided to disconnect the batteries when fully discharged .......................... : YES

Conclusion : PASS

Page 7: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 7 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

HISTORICAL OF SAMPLE RECEIVED

LABORATORY RECORDED N° Arrival date SPECIAL REMARKS

HK -- September 29, 2008 Component list provided HK 80728073, 80728074 July 28, 2008 -- HK 80606018, 80606019 June 6, 2008 --

PICTURES OF THE SAMPLES TESTED:

Page 8: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 8 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

NONE

Page 9: TEST REPORT N°: CMF-08-JU-H0859-LTHP - chun … · test report n°: cmf-08-ju-h0859-lthp bureau veritas hong kong limited – kwai chung office lcie electrical division unit 1611,

TEST REPORT N°: CMF-08-JU-H0859-LTHP

BUREAU VERITAS HONG KONG LIMITED – KWAI CHUNG OFFICE LCIE ELECTRICAL DIVISION

Unit 1611, 1614 & 1615, 16/F, VANTA INDUSTRIAL CENTRE 21-33, TAI LIN PAI ROAD, KWAI CHUNG, N.T. HONG KONG

Tel: +852 2494 4676 Fax: +852 2426 0613 Email: [email protected]

Page 9 of 9 TEST REPORT FOR FSD 01/2007 VER. 1

COMPONENT LIST

Object / part No. Manufacturer/ trademark Type / model Technical data Standard Mark(s) of

conformity External parts

Test switch 栢雨電子有限公司 -- 6mm x 6mm x 5mm EN 60598-2-22 Tested with appliance

Sleeve 栢雨電子有限公司 -- Dia. 5mm EN 60598-2-22 Tested with appliance

Charging unit

PCB 長深電子有限公司 S8-2C Not identified EN 60598-2-22 Tested with appliance

Material of connectors 栢雨電子有限公司 301-29 Not identified EN 60598-2-22 Tested with

appliance Other

Transformer 夏榮電子有限公司 JUSP-30411U-1

INPUT: AC230V/50Hz

OUTPUT: AC9V/0,15V FUSE: 125ºC

EN 60598-2-22 Tested with appliance

Terminal block 鏵科電子有限公司 3A2C -- EN 60598-2-22 Tested with appliance

Fuseholder 夏榮電子有限公司 AD-02 -- EN 60598-2-22 Tested with appliance

LEDs 興隆光電有限公司 LED-7 Dia. 3mm x 5mm EN 60598-2-22 Tested with appliance

Battery 江門市蓬江區東松電

池有限公司 -- 3,6V, 600mAh, Ni-Cd battery EN 60598-2-22 Tested with

appliance

EQUIPMENT FOR TESTING

Testing Equipment

Type Serial №.

Next Calibration Date(yyyy-mm-dd)

Digital Multimeter A1240003HK 2009/06/11

Data Acquisition Unit A7440015HK 2009/02/28

Electronic Load A7150009HK --

Light meter B5080003HK 2009/08/12

Needle Flame Tester G2000002HK 2009/01/21

Glow-wire Tester G2000014HK 2008/12/26

*** End of Report ***