Testing Parameters

Embed Size (px)

Citation preview

  • 8/12/2019 Testing Parameters

    1/13

    Sl. No. Test Test Method Frequencey

    IS: 4031 OPC 43 grade(IS 8112-1989)

    1 Physical Requirement IS: 4031

    I) Fineness

    Specific surface areain sq-cm/gm Not les than 2250 sq-cm/gm

    II) Soundenes IS: 4031Expansion in Lechatlier's mould Not more than 10 mm

    III) Intial setting time IS: 4031 Not less thatn 30 minutes

    IV) Final setting time IS: 4031 Not less thatn 60 minutes

    V) Compressive strength IS: 4031

    a) 3 days Not les than 23 N/sqmm

    b) 7 days Not les than 33 N/sqmm

    c) 28 days Not les than 43 N/sqmm

    VI) Consistancy of standard cement paste IS: 4031

    1 Test fo 1000 bags

    TEST FOR CEMENT

  • 8/12/2019 Testing Parameters

    2/13

    Sl. No. Test Test Method Frequency

    Grading Zone-II

    10.0 mm 100

    4.75 mm 90-100

    2.36 mm 75-100

    1.18 mm 55-90

    600 micron 35-59

    300 micron 8-30

    150 micron 0-10

    2 Silt contentAs per CPWD

    Specification1 Test for 20 cum

    3 Bulking of sandAs per CPWD

    Specification1 Test for 20 cum

    TEST FOR SAND

    Pactical size distribution1

    Shall not exceed 5

    As per CPWDSpecification

    Accepting Criter

    PercentageIS Sieve

    Designation

    1 Test for 40 cum

  • 8/12/2019 Testing Parameters

    3/13

    Grading Zone-III

    100

    90-100

    85-100

    75-100

    60-79

    Dec-40

    0-10

    %

    a

    passing for

  • 8/12/2019 Testing Parameters

    4/13

    Sl. No. Test Test Method Frequency Accepting Criteria

    1 Ph value IS:3025 Not less than 6.0

    2 Limits of Acidity IS:3025 Maximum 5.0 ml

    3 Limits of Alkanity' IS:3025 Maximum 25.0 ml

    4 Percentage of solids IS:3025Maximum 500 mg/ltr for RCC

    Maximum 2000 mg/ltr for RCC

    Sulphate Maximum 400 mg/ltr

    c) Suspended matters Maximum 2000 mg/ltr

    d) Inorganic solids Maximum3000 mg/ltr for RCC

    e) Organic solids Maximum 200 mg/ltr

    1 Test in 3 monthsa) Chlorides

    TEST FOR WATER

  • 8/12/2019 Testing Parameters

    5/13

    Sl. No. Test Test Method Frequence

    1 Slump TestAs per CPWD

    Specification

    Sl. No. Test Test Method Frequence

    1 Slump TestAs per CPWD

    Specification

    Column- 1 Test for 5 cum, Other

    RCC 1 Test fo 20 cum

    Column-1 Test for 20 cum

    7 days 28 days

    Slab, Beam- 1 Test for 20 cum 1:1:2 210 315

    1:1.5:3 175 265

    Other RCC- 1 Test for 20 cum 1:2:4 140 210

    TEST FOR PLAIN CEMENT CONCRETE 1:2:4 RICHER MIX

    TEST FOR REINFORCED CEMENT CONCRETE NOMINAL MIX

    Accepting Criteria

    Accepting Criteria

    Nominal Mix

    Compressive Strength(kg/sqcm)

    Cube Test IS:5162

  • 8/12/2019 Testing Parameters

    6/13

    Sl. No. Test Test Method Frequence Accepting Criteria

    1 Percentage of soft/Deleterious Materials IS:2386 1 test for each source

    2 Estimation of Organic Impurites IS:2386 1 test for40 cum

    3 Surface Moisture IS:2386 1 test for 40 cum

    4 Determination of 10% Fine Value IS:2386 1 test for 40 cum

    5 Specified Gravity IS:2386 1 test for 40 cum

    6 Bulk Density IS:2386 1 test for 40 cum

    7 Crushing Strength IS:2386 1 test for 40 cum

    8 Impact Value IS:2386 1 test for 40 cum

    9 Particle Size DistributionAs per CPWD

    Specification1 test for 10 cum

    Sl. No. Test Test Method Frequence Accepting Criteria

    1 Percentage of soft/Deleterious Materials IS:2386 1 test for each source

    2 Estimation of Organic Impurites IS:2386 1 test for 40 cum

    3 Surface Moisture IS:2386 1 test for 10 cum

    4 Determination of 10% Fine Value IS:2386 1 test for 10 cum

    5 Specified Gravity IS:2386 1 test for 10 cum

    6 Bulk Density IS:2386 1 test for 10 cum

    7 Crushing Strength IS:2386 1 test for 10 cum

    8 Impact Value IS:2386 1 test for 10 cum

    9 Particle Size DistributionAs per CPWD

    Specification1 test for 40 cum

    TEST FOR STONE AGGREGATE FOR CEMENT CONCRETE/RCC

    TEST FOR STONE AGGREGATE FOR DESIGN MIX CONCRETE

  • 8/12/2019 Testing Parameters

    7/13

    Sl. No. Test Frequency Quantity Test Required Test carried o

    Limit of Acidity

    Limit s of Alkanity

    Percent of solids

    a) Chlorides

    b) Sulphate

    c) Suspanded matters

    d) Inorganic solids

    e) Organic solids

    Physical Requirement

    Fineness

    Specific surface areain sq-cm/gm

    Soundeness

    Exapnsion in Lechatlier's mould

    Intial setting time

    Final setting time

    Compressive strength

    a) 3 days

    b) 7 days

    c) 28 days

    Consistancy of standard cement pastePartice size distribution 1 Test for 40 cum

    Silt content 1 Test for20 cum

    Organic Impurities 1 Test for 20 cum

    Bilking of sand 1 Test for 20 cum

    Percentage of soft/Deleterious Materials 1 test for each source

    Estimation of Organic Impurities 1 Test for10 cum

    Surface Moisture 1 Test for10 cum

    Detemination of 10% Fine Value 1 Test for10 cum

    Specified Gravity 1 Test for10 cum

    Bulk Density 1 Test for10 cum

    Crushing Strength 1 Test for10 cum

    Impact Value 1 Test for10 cum

    Sand

    Aggregate

    PROFORMA FOR SUBMITTING TEST CARRIED OUT AS PER CTE

    1 Test in 3 monthsWater

    Cement 1 Test for 1000 bags

    Page 2 of 2

  • 8/12/2019 Testing Parameters

    8/13

    Sl. No. Test Frequency Quantity Test Required Test carr

    Particle Size Distribution As per CPWD Specification

    Percentage of soft/Deleterious Materials 1 test for each source

    Estimation of Organic Impurities 1 test for 40 cum

    Surface Moisture 1 test for 40 cum

    Detemination of 10% Fine Value 1 test for 40 cum

    Specified Gravity 1 test for 40 cum

    Bulk Density 1 test for 40 cum

    Crushing Strength 1 test for 40 cum

    Impact Value 1 test for 40 cum

    Particle Size Distribution As per CPWD Specification

    Tensile Strength A) Under 10mm diameter 1 sample for 25 T

    Retest

    Rebound Test

    Nominal Mass B) 10mm to 16mm dia. 1 sample for 35 T

    Bend Test

    Elongation Test

    Proof Test C) Over 16mm dia. 1 sample

    Dimentional Tolerance 1 Test in evary 50000 bricks (20 bricks to be selected)

    Copmressive Strength 1 Test in evary 50000 bricks (15 bricks to be selected)

    Water Absorption 1 Test in evary 50000 bricks (15 bricks to be selected)

    Efflorescene 1 Test in evary 50000 bricks (15 bricks to be selected)

    Slump Test Column- 1 Test for 5 cum, other RCC 1 Test for 20 cum

    Column- 1Test for 5 cum

    Slab, Beam - 1 Test for 20 cum

    Other RCC - 1 Test for 20 cum

    Aggregate for

    other work

    Steel

    Bricks

    Cube Test

    RCC

    mix design

    Page 2 of 2

  • 8/12/2019 Testing Parameters

    9/13

    Sl. No. Test Test Method Frequence Accepting Criteria

    1 Dimentional ToleranceAs per CPWD

    Specification

    1 Test in every 5000 bricks

    (20 bricks to be selected)

    Length=490+8cm, Width=242+4cm,

    Height= 145+4cm

    2 Compressive StrengthAs per CPWD

    Specification

    1 Test in every 5000 bricks

    (15bricks to be selected)Not less than 75M/sqmm

    3 Water AbsorptionAs per CPWD

    Specification

    1 Test in every 5000 bricks

    (15 bricks to be selected)Not less than 20%

    4 EffloreceneAs per CPWD

    Specification

    1 Test in every 5000 bricks

    (15 bricks to be selected)Not more than 'Moderate'

    TEST FOR BRICKS

  • 8/12/2019 Testing Parameters

    10/13

    Sl. No. Test Test Method

    1 Slupm TestAs per CPWD

    Specification

    1 Test per 5 m3

    per column, 1

    Test per 20 m3for

    other thatn

    column

    2

    Consistancy of

    Concrete1 Test per 20 m

    3

    3

    Weight per

    cum,Cament factor &

    Air Contest Test

    As per CPWD

    Specification1 Test per 20 m

    3

    4 Cube Test

    7 days 28 days

    Les than 5.0 1

    6.0 to 15.0 2

    15.0 to 30.0 3 Individual Strength 17.0N/sqmm Individual Strength 25.0N/sqmm

    31.0 to 50.0 4 As per Design Mix As per Design Mix

    Individual Strength 20.0 N/sqmm Individual Strength 30.0 N/sqmm

    As per Design Mix As per Design Mix

    Av. Strength 20+5=25.0 N/sqmm Av. Strength 30+5=35.0 N/sqmm

    Individual variation should not be more than + 15% of the average

    TEST FOR DESIGN MIX CONCRETE

    Compressive Strength

    M-25

    Av. Strength 17+4=21.0 N/sqmm Av. Strength 25+4=29.0 N/sqmm

    51 and above

    4 plus 1

    additional

    sample for

    each 50.0cum or part

    thereof

    M-30

    Frequence for

    IS:516

    Quantity of

    Concrete(cum)

    Number of

    Sample

    Accepting Criteria

    Slump shall be checked at the time of loading & placement location. At placement lo

    slump measure shall confirmthe design slump.

    1.6 to 4.5 for concrete transported and placed by normal methods. 0.80 to 3.5 for co

    transported and placed by pumping methods.

    As decided By Engineer- in charge

    Design Mix

  • 8/12/2019 Testing Parameters

    11/13

    40mm 20mm 12.5mm 40mm 20mm 10 mm

    75mm 100 - - 63mm 100 - -

    37.5mm 95-100 100 - 40mm 85-100 100 -

    19.0mm 30-70 95-100 20mm 0-25 85-100 -

    16mm - - 100 16mm - - -

    11.2mm - - 90-100 12.5mm - - 100

    9.5mm Oct-35 35-55 40-85 10mm -5 0-20 85-100

    4.75m 0-5 0-10 0-10 4.75mm - 0-5 0-20

    2.30mm - - 0-5

    PARTICLE SIZE DISTRIBUTION OF COARSE AGGREGATE

    GRADED STONE AGGREGATE UNGRADED STONE AGGREGATE

    IS Sieve

    Designation

    IS Sieve

    Designation

    % passing by weight fof nominal size % passing by weight fof nominal size

  • 8/12/2019 Testing Parameters

    12/13

    Sl. No. Test Test Method Frequence

    1 Tensile Strength IS:1608

    2 Retest IS:1786

    3 Rebound Test IS:1786

    4 Nominal Mass IS:1786

    5 Bend Test IS:1786

    6 Elongation Test IS:1786

    7 Proof Stress IS:1786

    Sl. No.Chemical

    Composition

    As per Is 1786 Fe

    415Sail TMT 415 TISCON TMT-42 Vizag Steel

    1 CARBON 0.3 0.25 0.17 0.20

    2 SULPHER 0.06 0.05 0.045 0.04

    3 PHOSPHORUS 0.06 0.05 0.045 0.05

    4SULPHER &

    PHOSPHORUS0.11 0.10 0.09 0.09

    TEST FOR STEEL

    A) Under 10mm

    diameter 1 sample

    for 25T B) 10mmto 16mm dia. 1

    sample for 35 T C)

    Over 16mm dia. 1

    sample for 45 T

    MECHANICAL PROPERTIES

    CHEMICAL PROPERTIES

    Accepting Criteria

    Sail - 500, Tiscon - 510, Vizag - 520

    Sail - 22, Tiscon - 20, Vizag - 20

    Sail - 415 Tiscon - 450, Vizag - 460