THE TELEPORT
Teleport II
Teleport I
Merrill Lynch Data Center
TELEHOUSE Center
AT&T / Globecast
Ariel view of the Teleport
Major Features:
4 Established in 1985 by the Port Authority of NY/NJ as the first TELEPORT in the world.
4 100-acre office park.
4 11 miles from Manhattan.
4 Security provided by Port Authority of NY/NJ Police Department.
4 Redundant power feeds from both Con Edison (NY) and PSE&G (NJ).
THE TELEPORTFront Entrance to the Teleport
Teleport Security Gates
TELEHOUSE CENTER
Major Features:
4 TELEHOUSE designed building.
4 162,000 square feet of space.
4 24x7 on-site TELEHOUSE security, in addition to the Teleport security.
4 3:1 redundant power system, commercial power capacity: (10,000 KVA).
4 Multiple telecom providers available.
TELEHOUSE Center
Front Entrance to TELEHOUSE Center
FOYER
LOBBYVIP
RECP
PRESENTATION
EXEC
EXECS
TH Office10
79
6
1
8 5 4
3
2
TELEHOUSE CenterFirst Floor Diagram
TELEHOUSE CENTER
Security:
4 24x7 on-site TELEHOUSE security personnel.
4 Key card access throughout.
4 Closed circuit television video surveillance.
4 Infrared motion detectors.
4 Photo ID required for access to site.
4 24x7 customer access (access lists).
TELEHOUSE CENTER
1
TELEHOUSE Center Security Desk
Loading Dock:
4 2 main docks, plus 1 sub-dock.
4 24x7 customer access, at no cost.
4 Docks are raised, eliminating need for ramps.
4 All work monitored by TELEHOUSE security personnel.
4 Large freight elevator near docks.
TELEHOUSE CENTER
2
TELEHOUSE Center Loading Dock
Customer Assistance Center (CAC):
4 Control center for all TELEHOUSE sites.
4 24x7 Communications Technicians and Infrastructure Engineers on duty.
4 All customer data and activities are handled via TIMS (TELEHOUSE Information Management System).
4 Electric Power Quality and Battery monitors in place.
TELEHOUSE CENTER
3
TELEHOUSE Center CAC
Data Signal Room (DSR):
4 AT&T, Verizon, and KDDI are available to provide service.
4 MCI and other providers available in the 2nd DSR.
4 All circuit installations monitored by TELEHOUSE.
4 Circuits are run from DSR to customer telecom closets throughout the site.
TELEHOUSE CENTER
4
TELEHOUSE Center DSR
Battery Room:
4 4 battery strings for back-up.
4 Capable of handle full center power load for up to 15 minutes.
4 Batteries designed to immediately provide power in case of commercial power loss, until generators start (8-12 seconds).
TELEHOUSE CENTER
5
TELEHOUSE Center Battery Room
UPS Room:
4 4 rotary UPSs, 660 KVA each, 3 are operational with 1 in stand-by mode.
4 Even out power source to prevent spikes and brown-outs.
4 In the event of commercial power loss, UPSs continue to generate power since rotary components spin at such a high rate of speed.
TELEHOUSE CENTER
6
TELEHOUSE Center UPS Room
Generator Room:
4 4 diesel-powered generators 1,250 KVA each, 3 are operational with 1 in stand-by mode.
4 2-day on-site underground supply of fuel, with multiple vendors on call.
4 Each generator is kept warm with crankcase heaters to avoid cold starts.
4 Generator operation is tested monthly, and once per quarter on full power load.
TELEHOUSE CENTER
7
TELEHOUSE Center Generator Room
Switchgear Room (Commercial Power):
4 Contains transformers for commercial power.
4 Main power feed from Con Edison (NY) with back-up feed provided by PSE&G (NJ).
4 Multiple feeds from local substations.
4 Power distributed to 3 system set-ups:u Critical (customers, emergency, etc.)u Essential (office lighting, A/C, etc.)u Non-essential (corridor outlets, etc.)
4 If outage occurs, power is directed to Critical and Essential systems first.
TELEHOUSE CENTER
8
TELEHOUSE Center Switchgear Room
Chiller (A/C) Room:
4 Chillers originally supported high cooling requirement of mainframe data centers. Less cooling capacity needed for equipment today so Chillers have been adapted accordingly.
4 4 water chillers, 3 are operational with 1 in stand-by mode.
4 2-day on-site underground supply of condenser water, in the event of water loss by New York City.
TELEHOUSE CENTER
9
TELEHOUSE Center Chiller Room
Colocation - Open Space (A) :
4 Shared colocation space.
4 Caged space is available.
4 Access to space from main building corridor.
4 Equipment can be moved using maintenance corridor.
TELEHOUSE CENTER
10
TELEHOUSE Center Colocation
Halon
Smoke Detector
Pre-Action Sprinklers
Colocation - Open Space (A):
4 Fire Protection:u Halon in restricted areas.u Pre-action sprinklers.u Ceiling smoke detectors measure
heat & smoke particle density before releasing water.
u Centrally monitored by CAC.
4 Raised Floor:u 2 feet of raised space.u Separate cable trays for
communications and power cables to avoid interference.
TELEHOUSE CENTERTELEHOUSE Center Fire Suppression
TELEHOUSE Center Raised Floor