The Importance of Clean Air
Food and pharmaceutical producers today require hygienics and sanitation in their manufacturing process to help ensure safety and quality in the fi nished product. A major part of these processing environments is the air; its temperature, moisture, fi ltration and maintaining positive room pressure.
The air is in contact with the products, equipment and employees. Even a small amount of unconditioned air can adversely affect the processing room and may interrupt production, costing the manufacturer time and money. Proper sizing, features and construction are all key considerations when choosing a hygienic air handling system.
Why Use Hygienic Air Handlers?
The goals of today’s food processing facilities are simple: maximize production capacities and profi t potential while supplying safe products to consumers. However, recent product recalls and illnesses linked to unsafe food products have created several challenges for the entire food industry. Government regulations and programs such as Hazard Analysis and Critical Control Points (HACCP) and the Food Safety Modernization Act (FSMA) are designed to help ensure that food processing plants are following the necessary guidelines to provide consumers with the safest products possible.
The integrity of safe food products can be related to proper airfl ow, room pressurization, balance and maintaining appropriate room conditions.
What Does A Hygienic Air Handler Do?
During production, the unit utilizes a combination of return air and outside air to satisfy room conditions. When the process room stops production and goes into sanitation cycle, the PHOENIX™ PH unit is then switched to “clean-up” mode, introducing 100% outside air into the room.
Depending upon the ambient conditions, fresh air may require heating to maximize drying of the process room.
PH-Series Hygienic Air Handler
MODEL CFMWEIGHT
(estimated)DIMENSIONS (in)
A B C D E F G H J KPH-06-95 6,500 10,000 300 N/A N/A N/A 60 72 36 48 28 24
PH-08-95 10,000 11,500 312 N/A N/A N/A 78 72 60 48 56 24
PH-12-95 15,000 13,000 318 N/A N/A N/A 78 90 60 72 56 34
PH-18-95 20,000 16,000 324 N/A N/A N/A 90 90 72 72 66 34
PH-24-95 30,000 20,000 324 138 84 102 90 126 72 108 66 48
PH-32-95 40,000 23,000 330 138 90 102 114 126 96 108 94 48
PH-48-95 50,000 29,000 336 138 96 102 126 140 108 120 96 58
PH-62-95 60,000 31,000 360 138 102 120 126 162 108 144 96 68
PH-72-95 75,000 39,000 360 138 102 120 126 216 108 192 96 90
Typical 45°F Process Room - Production Mode
CAPACITY DETAILS - PRODUCTION MODEMODEL PH - 06 PH - 08 PH - 12 PH - 18 PH - 24 PH - 32 PH - 48 PH - 62 PH - 72
Total Air Flow (CFM) 6,500 10,000 15,000 20,000 30,000 40,000 50,000 60,000 75,000
Total Tons 15.8 24.3 36.4 48.6 72.9 97.2 121.5 145.8 182.2
Outside Air Load Tons 3.2 4.8 7.3 9.7 14.5 19.4 24.2 29.1 36.4
Unit Motor Load Tons 1.9 2.5 3.8 5.0 7.5 10.0 12.5 15.0 18.8
Room Tons (Sensible & Latent) 10.8 16.9 25.4 33.9 50.8 67.8 84.7 101.7 127.1
All Capacities based on the following: a) 45°F Room @ 85% RH b) 95°F / 78°F (WB / DB) Outside Air c) 5% Outside Air d) 33°F Leaving air temperature
ROOM SPECIFICATIONS
Approximate Room Size (Sq. Ft.) 1,100 1,650 2,500 3,300 4,900 6,500 8,200 9,800 12,500
Approximate Room Volume (Cu. Ft.) 22,000 33,000 50,000 66,000 98,000 130,000 164,000 196,000 250,000
Air Change (Min.) 3.4 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Note: All room volumes are based on 20 ft. ceiling height
Return Air Box
Return Air
Supply Air
Outside Air
Discharge Air
Supply AirDiffuser
Mixed Air
Typical 45°F Process Room - Sanitation Cycle
CAPACITY DETAILS - SANITATION CYCLEMODEL PH - 06 PH - 08 PH - 12 PH - 18 PH - 24 PH - 32 PH - 48 PH - 62 PH - 72
Total Air Flow (CFM) 6,500 10,000 15,000 20,000 30,000 40,000 50,000 60,000 75,000
Heating Capacity (MBH) 632 972 1,458 1,944 2,916 3,888 4,860 5,832 7,290
All Capacities based on the following: a) 90°F Temperature Rise with Direct Fired Gas Burner b) Listed capacities are based on burner output
ROOM SPECIFICATIONS
Approximate Room Size (Sq. Ft.) 1,100 1,650 2,500 3,300 4,900 6,500 8,200 9,800 12,500
Approximate Room Volume (Cu. Ft.) 22,000 33,000 50,000 66,000 98,000 130,000 164,000 196,000 250,000
Air Change (Min.) 3.4 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Note: All room volumes are based on 20 ft. ceiling height
INSTALLATION: Units are designed for outdoor mounting on structural steel or roof curb.
CASING: Each unit is suitable for hygienic applications and is constructed from 4” thick cam-lock, foam in place insulated panels. The interior liner shall be constructed of 22 gauge stainless steel and the exterior skin is constructed of 18 gauge smooth galvanized steel. The interior of the unit shall minimize the use of exposed fasteners and is designed for complete wash down. All interior seams are caulked with a USDA approved sealant. ACCESS DOORS: Each unit shall be furnished with access doors to all interior components. Construction materials to match selected unit interior and exterior. Doors are complete with thermal break and handles that can be operated from outside and inside of unit. ROOF: Each unit roof is pitched away from the service doors and shall have a 16 gauge galvanized steel or stainless steel interior liner and a 16 gauge mill galvanized exterior skin. The roof shall be insulated with rigid polyurethane board. DRAIN PANS: The entire unit shall be furnished with full cover-age, stainless steel drain pans with 1.5” MPT drain connections. All drain pans are foamed in place to ensure complete air and water seals. The entire drain pan assembly is protected with mill galva-nized steel bottom covers. UNIT FRAME: The base shall be constructed from a welded carbon steel frame. The entire base assembly shall be primed and painted with industrial grade enamel. The base is furnished with permanent lifting lugs on all section corners. DAMPERS (Fresh Air, Return Air): Motorized, opposed blade dampers are rated as low leakage (less than 5 CFM per square ft. of area at a 4” pressure differential). Blades shall be galvanized steel or stainless steel with stainless steel side seals and neoprene blade seals. Dampers are complete with mounted actuators. SUPPLY FAN: The supply blower is an unhoused, single-width, single-inlet, centrifugal plenum type with continuously welded airfoil blades. The blower has two self-aligning, 200,000 L-50 pillow block bearings. The blower shaft is ground and polished with center point drill on the drive end to accommodate a tachometer point. BLOWER MOTOR: The blower motor shall be premium effi ciency, TEFC mounted on an adjustable slide base. BLOWER DRIVE: The blower/motor drive assembly shall be belt driven with fi xed sheaves.
PRE FILTERS: Each Unit is supplied with two sets of 30% (MERV - 8) pre fi lters. Filters shall have an average effi ciency of 30% in accordance with ASHRAE Test Standard 52.1-1992. The fi lter me-dia is high performance, nonwoven, reinforced cotton and synthetic fabric. FINAL FILTERS: Each Unit is supplied with one set of 95% (MERV - 14) fi nal fi lters. Filters shall have an average effi ciency of 95% in accordance with ASHRAE Test Standard 52.1-1992. The fi lter media is water-resistant, high strength, microfi ber glass. Filters are 12” thick cartridge type and can be removed without the use of tools. Includes factory mounted magnehelic gauge located on cabinet exterior. COOLING COIL: Each unit is supplied with a cooling coil(s) specifi cally designed for this application. Coil shall have stainless steel tubes and aluminum fi ns. Other coil options are available such as aluminum tubes and fi ns and copper tubes with aluminum fi ns. CONTROLS: Each unit shall be furnished with the following controls:
• Allen Bradley MicroLogix 1400 PLC with Ethernet port and Magelis Interface (in unit mounted panel).
• NEMA 4 control panel.
• Fused disconnect switch.
• Control transformers.
• Damper controls.
• FM rated natural gas direct fi red burner controls (if applicable).
• Temperature controls for heating and cooling in process mode, heating in clean-up mode.
• Supply fan blower motor 40 HP and above with SoftStart.
• Supply fan blower motor under 40 HP with starter/overload.
• ICTD or RTD temperature sensors as required.
• All access doors shall be furnished with shut down safety switches.
• Stainless Steel Remote panel (NEMA 4X) with operational lights and switches.
• Smoke detector and ammonia detector.
• Service receptacle, 110 V. service by others.
• Interior service lights with switches, 110 V. service by others.
a can of too ma
OIL: Each unned for
f f
Unit Components
gning, block
haft h
er point.
Quotation Request
Date
Sales Representative
Contractor
Project Name
Project Location
Elevation ft
Outside Conditions DB WB
Room Conditions DB WB %RH
Room Size sq ft
Ceiling Height ft
Room Volume cu ft
Type of Unit Mixed Air Make-Up Air (100% Outside Air
Outside Air %
Room Load(Mixed Air Unit) Total Tons (Sensible & Latent)
Type of Refi gerant
Ammonia Recirculated Flooded DX
Halocarbon (DX) Type
RefrigerantTemperature °F Liquid °F Suction
Propylene Glycol Temperature % Concentration
Chilled Water Temperature
Coil Construction SS 304 Tubes & Alum. Fins Alum. Tubes & Fins Copper Tubes & Alum. Fins
Heating (Burner) Temp. Rize Direct Indirect
Heating (Other) Steam Hot Water Warm Glycol
PSI Ent. Temp. % Concentration
Ent. Temp
Cabinet Interior Mill Galv. SS 304
Type of Filters Pre Filters Intermediate Final
Merv. Rating Merv. Rating Merv. Rating
% % %
Main Blower Motor Single Speed VFD
Exhaust Fan Motors Single Speed VFD
AdditionalRequirements
To insure that we can provide a proposal for our equipment that is the correct solution for your application, the following information is required:
A I R S Y S T E M S™
© 2017 Weather-Rite LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval systems – without written permission of Weather-Rite LLC.
Phoenix Air Systems170 Landmark Drive, Suite BOwatonna, Minnesota 55060 Phone: [email protected]
PASHASGNA 0217 Orig
Phoenix Air Systems™ is a leading manufacturer of Hygienic Air Handling Systems providing a comprehensive approach for the critical process environment of the food and pharmaceutical grade production and process industries. Our team of experts helps to ensure your building’s environment meets your needs. We specialize in production room environmental control for a variety of product types and production requirements.
Phoenix Air Systems™ can work with your team of experts in each step of the process – from concept and design, proposal, manufacturing and commissioning with outstanding support after the sale. We also offer a standard control system that can be integrated with existing refrigeration controls or process automation systems for enhanced process room environmental control.
We have the knowledge and expertise to help ensure satisfaction of the systems we build. We strive to provide exceptional products at a competitive value while focusing on providing superior service that exceeds customers’ expectations.
“The Phoenix Way”
www.phoenixairsystems.com 507-451-3524
Hygienic Air HandlersPH-Series Mixed Air Systems