The Risk Assessment of Fire Damper Installations

Embed Size (px)

Citation preview

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    1/43

    The risk assessment

    of

    fire damper installations

    June 2010

    Paul White

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    2/43

    OVERVIEW

    The purpose of this presentation is to highlightthat fire dampers form a key part of the

    passive fire protection within a building, but

    are at best often overlooked, but at worst not

    even recognised for the job that they might be

    called on to do in the event of fire.

    It seeks to clarify the regulatory requirements

    and fill in the gaps left by the guides to the

    RRFSO where fire dampers are installed in a

    building

    OVERVIEW

    2 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    3/43

    What is this?

    FIRE DOORS

    Everyone knows what a fire door is and most people see one every day

    3 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    4/43

    What is this?

    FIRE DAMPERS

    This is a fire damper and they are generally hidden above ceilings and

    mounted in a ductwork run, most people dont know that they exist

    4 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    5/43

    Ad hoc testing to BS476-20/22

    FIRE

    DAMPERS

    BS476 -20/22

    This shows a fire damper during the old style of ad hoc testing to BS 476

    5 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    6/43

    Test setup for EN 1366-2

    FIRE

    DAMPERS

    BS EN1366-2

    The fire damper is subjected to a 300pa pressure difference for the whole

    of the test and the leakage recorded as a pass failure criteria

    6 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    7/43

    Fire and Leakage Rated Fire Dampers

    FIRE

    DAMPERS

    BS EN 1366-2

    Fire damper tests to EN 1366-2 in practice

    7 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    8/43

    Fire Dampers

    Application and test detailsFor use in normal ventilation ducts at fire boundaries to maintaincompartmentation in the case of fire

    Generally tested for Integrity (E), Insulation (I) (if required) andReduced Leakage (S) (again, if required)

    Also considered are horizontal, vertical, fire from inside tooutside, fire from outside to inside, symmetry etc

    Units are mounted in a supporting partition, such that would beused in practice.

    During the test, the damper must close, and is then subjected toa300Papressure differential.

    E Integrity damper must not leak more than 360 m3/hr/m2

    I Insulation thermocouples record temperature rise(140/180C max)

    S Leakage rating damper must not leak more than 200m3/hr/m2, at ambient and during the fire test. The smallestexample must also not leak more than 200 m3/hr/m2

    FIRE DAMPERS

    APPLICATION

    AND TEST

    DETAILS

    8 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    9/43

    Fire Damper Standards

    Product standardEN 15650: 2010 Fire dampers

    Published (CEN TC156 WG9)

    Test standard

    EN 1366-2:1999: Fire resistance tests for service installations: Fire dampers

    Published, but under review (CEN TC127 WG2 TG4)

    Classification standardEN 13501-3:2005: Fire classification of construction products and buildingelements - part 3: classification using data from fire resistance tests on

    components of normal building service installations

    Published (CEN TC127 WG7)

    Extended field of application standard

    prEN 15882-2: Extended applications of test results for fire resistance tests

    for service installations : DampersUnder development (CEN TC127 WG2 TG4)

    FIRE DAMPERS

    -2

    STANDARDS

    9 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    10/43

    Regulation - ADB

    The following slides give asnapshot of the requirementsin Approved Document B

    It is strongly recommendedthat anyone making riskassessments carefully

    considers the requirements inthis document and does notrely purely on the informationgiven here

    It is available as a freedownload from

    http://www.planningportal.gov.uk/-search on approveddocuments

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS10

    APPROVED

    DOCUMENT B

    (1)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    11/43

    Regulation - ADB

    Mechanical ventilation andair-conditioning systems Page 60 5.47 Para 2

    Where the ductworksystem serves more thanone part of a sub-divided

    escape route, a firedamper should beprovided where the ductwork enters each sectionof the escape routeoperated by a smokedetector or suitable fire

    detection system. The firedampers should closewhen smoke is detected

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS11

    APPROVED

    DOCUMENT B

    (2)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    12/43

    Regulation - ADB

    Mechanical ventilation andair-conditioning systems

    Page 60 - 5.48 Note

    Fire dampers activatedonly by fusible links arenot suitable for protectingescape routes. Howeveran ES classified fire andsmoke damper which isactivated by a suitable fireprotection system may beused

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS12

    APPROVED

    DOCUMENT B

    (3)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    13/43

    Regulation - ADB

    Ventilation ducts, flues etc. Page 86 - 10.9

    Where air handling ductspass through fire separatingelements the integrity ofthose elements should bemaintained

    There are 3 basic methodsand these are:

    Method 1: protection usingfire dampers;

    Method 2: protection usingfire resistant enclosures;

    Method 3: protection usingfire-resisting ductwork

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS13

    APPROVED

    DOCUMENT B

    (5)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    14/43

    Regulation - ADB

    Ventilation ducts, flues etc.Page 86 - 10.10

    Method 1 (e.g. Dampers) isnot suitable for extractductwork serving kitchens.

    This is due to the likely build

    up of grease which canadversely affect theeffectiveness of anydampers.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS14

    APPROVED

    DOCUMENT B

    (6)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    15/43

    Regulation - ADB

    Fire dampers Page 86 -10.11

    Fire damper should besituated within the thicknessof the fire separatingelement and be securely

    fixed. It is also necessary toensure that, in a fire,expansion of the ductworkwould not push the firedamper through thestructure.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS15

    APPROVED

    DOCUMENT B

    (7)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    16/43

    Regulation - ADB

    Fire dampers Page 86 -10.12

    Adequate means of accessshould be provided to allowinspection, testing andmaintenance of both the fire

    damper and its actuatingmechanism.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS16

    APPROVED

    DOCUMENT B

    (8)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    17/43

    Regulation - ADB

    Fire dampers Page 86 -10.13

    Where the use of thebuilding involves sleepingrisk, such as an hotel orresidential care home, fire

    dampers should beactuated by smokedetector-controlledautomatic releasemechanism, in addition tobeing actuated by thermallyactuated devices......... (caveatson certain types of alarm systems and abilities of

    people to leave the area) ............

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS17

    APPROVED

    DOCUMENT B

    (9)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    18/43

    Regulation - ADB

    Fire dampers Page 86 -10.13 cont.

    Note: Fire dampers actuatedonly by fusible links are notsuitable for protecting escaperoutes. However, an ES

    classified fire and smokedamper which is activated bya suitable fire detectionsystem may be used

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS18

    APPROVED

    DOCUMENT B

    (12)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    19/43

    Regulation - ADB

    Fire dampers Page 86 -10.15

    Fire dampers should betested to BS EN 1366-2:1999and be classified to BS EN13501-3:2005. They should

    have an E classificationequal to, or greater than, 60minutes. Fire and smokedampers should also betested to BS EN 1366-2:1999and be classified to BS EN13501-3:2005. They shouldhave an ES classification

    equal to, or greater than, 60minutes.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS19

    APPROVED

    DOCUMENT B

    (14)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    20/43

    Regulation - ADB

    Fire dampers Page 86 -10.15 Note 1

    Note 1: Fire dampers testedusing ad-hoc proceduresbased on BS476 may only beused be appropriate for fan-

    off situations.In all cases, fire dampersshould be installed astested.

    PW Note: You cannot get an E or

    ES classification if you test toBS476, so dampers for sleepingrisk areas and escape routes needto be tested to EN1366-2

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS20

    APPROVED

    DOCUMENT B

    (15)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    21/43

    Regulation - ADB

    ADB refers to a lot of second tierdocuments and also referencesother guides.

    This BS5588 series is referred toand is still apparently valid,although effectively withdrawn.The department forCommunities and LocalGovernment (CLG) still says thatit contains good and safeinformation. It is replaced by BS9999 and this where we getsome clear guidance onmaintenance requirements (exBS 5588-12)

    ADB also recommends the useof third party certificatedproducts

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS21

    APPROVED

    DOCUMENT B

    (1)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    22/43

    Other publications - ASFP

    ASFP Grey BookAbout to be published inits second edition

    Contains details ofregulation, standardstesting etc

    Also gives some guidance

    on project planning andinstallation

    It is planned that it will listcertificated products withapproved installationmethods

    Also has sister documents

    about fire rated dusts,structural steel protectionand fire seals

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS22

    ASFP

    GREY BOOK

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    23/43

    Other publications - HVCA

    HVCA DW144and DW145

    DW144 is under

    review for its

    second edition

    For dampers this

    is supported by

    DW145 which

    will be referred

    to for damper

    installations

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS23

    HVCA

    DW144 &

    DW145

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    24/43

    Other publications Dept of Health

    HTM 05-02Written to coverhealthcare premises

    Describes fire dampers interms of BS EN 1366-2classified E and ES

    Fire and smoke dampers

    classifed ESTransfer grilles should befitted with fire and smokedampers

    Where walls do not passthe ceiling, ducts throughthe ceiling should be

    protected with firedampers

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS24

    DEPARTMENT

    OF HEALTH

    HTM 02-05

    (1)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    25/43

    Other publications Dept of Health

    HTM 05-02 {cont}Fire & Smoke dampers incompartment wallsmotorised to close onsignal

    Fire & Smoke dampers insub compartment walls -

    link onlyPW Note: motorised wouldprobably be better for regulartesting

    Ducting serving firehazard rooms should beprotected with dampers, orif duct is passing through,

    no dampers, but fireresisting duct

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS25

    DEPARTMENT

    OF HEALTH

    HTM 02-05

    (2)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    26/43

    Other publications Dept of Health

    HTM 05-02 {cont}Installationrequirements are given,but unfortunately thisdoes not say usemanufacturers

    instructions, ratherwhat not to do, also arequirement for ceilings

    It requires details of alldampers to be includedin the fire strategy and

    drawings for complexbuildings

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS26

    DEPARTMENT

    OF HEALTH

    HTM 02-05

    (3)

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    27/43

    Other publications Dept of C S F

    BB100Generally as ADB

    References the ASFPGrey Book

    Product certification

    for property protectionfire dampers shouldalso satisfy LPS1162

    It requires details of alldampers to be includedin the fire strategy and

    drawings for complexbuildings

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS27

    DEPARTMENT

    OF CHILDREN,

    SCHOOLS &

    FAMILIES

    BB100

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    28/43

    Certification standard - LPCB

    The LPCB run a certificationscheme for fire dampers. TheLPS 1162 document containsall the tests that LPC requirethe product to undergo, beforecertification may be offered

    It also states that to meet it, acompany must have full BSEN ISO 9001 accreditation.The LPCB visit the factory atleast once a year to confirmby measurement that thecertificated products maintainall the tested dimensions,and confirm that the products

    still comply with anyassessments that may havebeen made

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS28

    CERTIFICATION

    STANDARD

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    29/43

    Regulatory Reform (Fire Safety) Order - RRFSO

    RRFSOThere is a series of

    published guides to meeting

    the requirements of the

    RRFSO

    Information on fire dampers

    is vague, but is generally as

    follows:1) laundry chutes (smoke and fire

    dampers)

    2) dampers in ducts should be correctly

    installed

    3) the fact that in cooking processes

    ventilation ducts and dampers shouldbe considered.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS29

    RRFSO

    -1-

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    30/43

    Regulatory Reform (Fire Safety) Order - RRFSO

    RRFSOHowever, fire dampers arereferred to indirectly asfollows:

    1) In a checklist: Are any holes orgaps in walls, ceilings and floorsproperly sealed, e.g. whereservices such as ventilation ductsand electrical cables pass throughthem?

    2) Ventilation systems: Whereventilation systems might assistthe spread of flames, smoke andhot gases from a fire it will benecessary to take steps to safe

    guard the means of escapeagainst this hazard.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS30

    RRFSO

    -3-

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    31/43

    Regulatory Reform (Fire Safety) Order - RRFSO

    RRFSOUnfortunately, fire dampers

    arenotreferred to in the

    maintenance check list

    section, which is a key area

    where they should be, or in

    the frequency of checkingsection, also key.

    Therefore we need to turn

    to BS9999 for further

    guidance

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS31

    RRFSO

    -3-

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    32/43

    Regulatory Reform (Fire Safety) Order - RRFSO

    BS9999Annex V (normative): Routineinspection and maintenance offire safety installations

    This requires smoke controlsystems and their componentsto be tested as often as

    weekly, however it is not clearwhat constitute smokedampers. This could possiblyrefer to dampers that are usedto protect escape routes andareas with sleeping risk. Thisshould be considered by thedesigner and perhaps the risk

    assessor.

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS32

    BS9999

    -1-

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    33/43

    Regulatory Reform (Fire Safety) Order - RRFSO

    BS9999Annex W (normative): Routineinspection and maintenance ofventilation and air conditioningductwork

    This requires simple firedampers (spring operated so

    probably curtain fire dampers)to be tested every two years ormore often if conditions aresuch that they get dirty quicker.

    Both annexes should belooked at in their entiretybefore drawing anyconclusions, and consideration

    given to the rest of thedocument

    THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS33

    BS9999

    -2-

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    34/43

    Risk assessment

    Considerations/Key areasThe positioning of the product

    The application of the product (fire, or fire

    and smoke)

    The supporting construction into which the

    damper is fitted

    What testing has been undertaken?

    What assessment information is available?

    What maintenance regimes are in place?

    RISK

    ASSESSMENT

    -1-

    34 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    35/43

    Risk assessment

    Positioning of the productIs it known where all the fire, and fire and smoke, dampers are installed -schedule and drawing

    Is there clear access, both outside and inside for cleaning and maintenance

    Are there any gaps around the damper between it and the supportingconstruction?

    Is the fire damper mounted within the wall?

    The lastmightbe allowed if the duct and the joint with the wall are installed usinga tested method

    Application escape route or area with sleepingrisk

    Does the fire damper have an ES classification (or equivalency throughassessment) when mounted in the supporting construction being used e.g.masonry, dry wall, batt, other fire stopping etc?

    Has the damper been installed to the manufacturers instructions or at least to thedocumented satisfaction of the BCA?

    Note to get an ES classification, the damper must have been tested (or assessed

    for equivalency) to BS EN 1366-2, BS 476 cannot confirm the S low leakagecriteria

    RISK

    ASSESSMENT

    -2-

    35 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    36/43

    Risk assessment

    Application are the fans immediately turnedoff in the event of a fire incident

    Dampers tested ad hoc to BS 476 may be acceptable if the fans are turned

    off.

    Dampers having an E classification are, however, recommended and must

    be used if the fans are left on.

    If the fans are left on, curtain fire dampers are not recommended as theymay be held open by residual airflow

    Does the fire damper have an E classification (or equivalency through

    assessment) when mounted in the supporting construction being used e.g.

    masonry, dry wall, batt, other fire stopping etc?

    Has the damper been installed to the manufacturers instructions or at least

    to the documented satisfaction of the BCA?

    Note to get an E classification, the damper must have been tested (orassessed for equivalency) to BS EN 1366-2

    RISK

    ASSESSMENT

    -3-

    36 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    37/43

    Risk assessment

    Maintenance regimeDoes this exist for the fire dampers?

    Is the responsible person aware of thisrequirement?

    Do adequate records of testing andinspection exist?

    Do the records note any and all remedialaction to the fire damper and to the sealbetween it and the supporting construction

    Refer to Annex V and Annex W of BS9999

    RISK

    ASSESSMENT

    -4-

    37 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    38/43

    Summary

    The requirements for the risk assessment of firedampers are not clear from the RRFSO

    However, through reference to ADB and BS9999, a

    clear path can be drawn

    Additional help is given in the ASFP Grey Book and

    HVCA DW145There must be clear records of where dampers are

    positioned, that they are installed correctly and that

    they are maintained correctly, including the state of

    any seal around the damper at the interface between

    it and the supporting construction

    SUMMARY

    38 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    39/43

    WRONG

    WRONG

    -1-

    The damper is not in the plane of the wall and the duct is not protected.

    Has the damper been tested in association with batt? If fire resisting, is the

    duct supported around its outside at its joint with the wall

    39 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    40/43

    WRONG

    WRONG

    -2-

    The dampers are not in the plane of the wall, the duct is not protectedand it is unlikely that the dampers have been tested passing through a

    hole in a steel beam

    40 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    41/43

    WRONG

    WRONG

    -3-

    !

    41 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    42/43

    RIGHT

    RIGHT

    -1-

    The damper is within the plane of the wall, the installation is complete and

    without any damage to the seal around the damper.Note: However, it needs to be checked that damper has been tested in a batt

    installation, especially for ES requirements

    42 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS

  • 8/12/2019 The Risk Assessment of Fire Damper Installations

    43/43

    The risk assessment of fire

    damper installations

    THANK YOU FOR LISTENING