Upload
alanedwards7282
View
234
Download
0
Embed Size (px)
Citation preview
8/12/2019 The Risk Assessment of Fire Damper Installations
1/43
The risk assessment
of
fire damper installations
June 2010
Paul White
8/12/2019 The Risk Assessment of Fire Damper Installations
2/43
OVERVIEW
The purpose of this presentation is to highlightthat fire dampers form a key part of the
passive fire protection within a building, but
are at best often overlooked, but at worst not
even recognised for the job that they might be
called on to do in the event of fire.
It seeks to clarify the regulatory requirements
and fill in the gaps left by the guides to the
RRFSO where fire dampers are installed in a
building
OVERVIEW
2 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
3/43
What is this?
FIRE DOORS
Everyone knows what a fire door is and most people see one every day
3 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
4/43
What is this?
FIRE DAMPERS
This is a fire damper and they are generally hidden above ceilings and
mounted in a ductwork run, most people dont know that they exist
4 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
5/43
Ad hoc testing to BS476-20/22
FIRE
DAMPERS
BS476 -20/22
This shows a fire damper during the old style of ad hoc testing to BS 476
5 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
6/43
Test setup for EN 1366-2
FIRE
DAMPERS
BS EN1366-2
The fire damper is subjected to a 300pa pressure difference for the whole
of the test and the leakage recorded as a pass failure criteria
6 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
7/43
Fire and Leakage Rated Fire Dampers
FIRE
DAMPERS
BS EN 1366-2
Fire damper tests to EN 1366-2 in practice
7 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
8/43
Fire Dampers
Application and test detailsFor use in normal ventilation ducts at fire boundaries to maintaincompartmentation in the case of fire
Generally tested for Integrity (E), Insulation (I) (if required) andReduced Leakage (S) (again, if required)
Also considered are horizontal, vertical, fire from inside tooutside, fire from outside to inside, symmetry etc
Units are mounted in a supporting partition, such that would beused in practice.
During the test, the damper must close, and is then subjected toa300Papressure differential.
E Integrity damper must not leak more than 360 m3/hr/m2
I Insulation thermocouples record temperature rise(140/180C max)
S Leakage rating damper must not leak more than 200m3/hr/m2, at ambient and during the fire test. The smallestexample must also not leak more than 200 m3/hr/m2
FIRE DAMPERS
APPLICATION
AND TEST
DETAILS
8 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
9/43
Fire Damper Standards
Product standardEN 15650: 2010 Fire dampers
Published (CEN TC156 WG9)
Test standard
EN 1366-2:1999: Fire resistance tests for service installations: Fire dampers
Published, but under review (CEN TC127 WG2 TG4)
Classification standardEN 13501-3:2005: Fire classification of construction products and buildingelements - part 3: classification using data from fire resistance tests on
components of normal building service installations
Published (CEN TC127 WG7)
Extended field of application standard
prEN 15882-2: Extended applications of test results for fire resistance tests
for service installations : DampersUnder development (CEN TC127 WG2 TG4)
FIRE DAMPERS
-2
STANDARDS
9 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
10/43
Regulation - ADB
The following slides give asnapshot of the requirementsin Approved Document B
It is strongly recommendedthat anyone making riskassessments carefully
considers the requirements inthis document and does notrely purely on the informationgiven here
It is available as a freedownload from
http://www.planningportal.gov.uk/-search on approveddocuments
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS10
APPROVED
DOCUMENT B
(1)
8/12/2019 The Risk Assessment of Fire Damper Installations
11/43
Regulation - ADB
Mechanical ventilation andair-conditioning systems Page 60 5.47 Para 2
Where the ductworksystem serves more thanone part of a sub-divided
escape route, a firedamper should beprovided where the ductwork enters each sectionof the escape routeoperated by a smokedetector or suitable fire
detection system. The firedampers should closewhen smoke is detected
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS11
APPROVED
DOCUMENT B
(2)
8/12/2019 The Risk Assessment of Fire Damper Installations
12/43
Regulation - ADB
Mechanical ventilation andair-conditioning systems
Page 60 - 5.48 Note
Fire dampers activatedonly by fusible links arenot suitable for protectingescape routes. Howeveran ES classified fire andsmoke damper which isactivated by a suitable fireprotection system may beused
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS12
APPROVED
DOCUMENT B
(3)
8/12/2019 The Risk Assessment of Fire Damper Installations
13/43
Regulation - ADB
Ventilation ducts, flues etc. Page 86 - 10.9
Where air handling ductspass through fire separatingelements the integrity ofthose elements should bemaintained
There are 3 basic methodsand these are:
Method 1: protection usingfire dampers;
Method 2: protection usingfire resistant enclosures;
Method 3: protection usingfire-resisting ductwork
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS13
APPROVED
DOCUMENT B
(5)
8/12/2019 The Risk Assessment of Fire Damper Installations
14/43
Regulation - ADB
Ventilation ducts, flues etc.Page 86 - 10.10
Method 1 (e.g. Dampers) isnot suitable for extractductwork serving kitchens.
This is due to the likely build
up of grease which canadversely affect theeffectiveness of anydampers.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS14
APPROVED
DOCUMENT B
(6)
8/12/2019 The Risk Assessment of Fire Damper Installations
15/43
Regulation - ADB
Fire dampers Page 86 -10.11
Fire damper should besituated within the thicknessof the fire separatingelement and be securely
fixed. It is also necessary toensure that, in a fire,expansion of the ductworkwould not push the firedamper through thestructure.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS15
APPROVED
DOCUMENT B
(7)
8/12/2019 The Risk Assessment of Fire Damper Installations
16/43
Regulation - ADB
Fire dampers Page 86 -10.12
Adequate means of accessshould be provided to allowinspection, testing andmaintenance of both the fire
damper and its actuatingmechanism.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS16
APPROVED
DOCUMENT B
(8)
8/12/2019 The Risk Assessment of Fire Damper Installations
17/43
Regulation - ADB
Fire dampers Page 86 -10.13
Where the use of thebuilding involves sleepingrisk, such as an hotel orresidential care home, fire
dampers should beactuated by smokedetector-controlledautomatic releasemechanism, in addition tobeing actuated by thermallyactuated devices......... (caveatson certain types of alarm systems and abilities of
people to leave the area) ............
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS17
APPROVED
DOCUMENT B
(9)
8/12/2019 The Risk Assessment of Fire Damper Installations
18/43
Regulation - ADB
Fire dampers Page 86 -10.13 cont.
Note: Fire dampers actuatedonly by fusible links are notsuitable for protecting escaperoutes. However, an ES
classified fire and smokedamper which is activated bya suitable fire detectionsystem may be used
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS18
APPROVED
DOCUMENT B
(12)
8/12/2019 The Risk Assessment of Fire Damper Installations
19/43
Regulation - ADB
Fire dampers Page 86 -10.15
Fire dampers should betested to BS EN 1366-2:1999and be classified to BS EN13501-3:2005. They should
have an E classificationequal to, or greater than, 60minutes. Fire and smokedampers should also betested to BS EN 1366-2:1999and be classified to BS EN13501-3:2005. They shouldhave an ES classification
equal to, or greater than, 60minutes.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS19
APPROVED
DOCUMENT B
(14)
8/12/2019 The Risk Assessment of Fire Damper Installations
20/43
Regulation - ADB
Fire dampers Page 86 -10.15 Note 1
Note 1: Fire dampers testedusing ad-hoc proceduresbased on BS476 may only beused be appropriate for fan-
off situations.In all cases, fire dampersshould be installed astested.
PW Note: You cannot get an E or
ES classification if you test toBS476, so dampers for sleepingrisk areas and escape routes needto be tested to EN1366-2
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS20
APPROVED
DOCUMENT B
(15)
8/12/2019 The Risk Assessment of Fire Damper Installations
21/43
Regulation - ADB
ADB refers to a lot of second tierdocuments and also referencesother guides.
This BS5588 series is referred toand is still apparently valid,although effectively withdrawn.The department forCommunities and LocalGovernment (CLG) still says thatit contains good and safeinformation. It is replaced by BS9999 and this where we getsome clear guidance onmaintenance requirements (exBS 5588-12)
ADB also recommends the useof third party certificatedproducts
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS21
APPROVED
DOCUMENT B
(1)
8/12/2019 The Risk Assessment of Fire Damper Installations
22/43
Other publications - ASFP
ASFP Grey BookAbout to be published inits second edition
Contains details ofregulation, standardstesting etc
Also gives some guidance
on project planning andinstallation
It is planned that it will listcertificated products withapproved installationmethods
Also has sister documents
about fire rated dusts,structural steel protectionand fire seals
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS22
ASFP
GREY BOOK
8/12/2019 The Risk Assessment of Fire Damper Installations
23/43
Other publications - HVCA
HVCA DW144and DW145
DW144 is under
review for its
second edition
For dampers this
is supported by
DW145 which
will be referred
to for damper
installations
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS23
HVCA
DW144 &
DW145
8/12/2019 The Risk Assessment of Fire Damper Installations
24/43
Other publications Dept of Health
HTM 05-02Written to coverhealthcare premises
Describes fire dampers interms of BS EN 1366-2classified E and ES
Fire and smoke dampers
classifed ESTransfer grilles should befitted with fire and smokedampers
Where walls do not passthe ceiling, ducts throughthe ceiling should be
protected with firedampers
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS24
DEPARTMENT
OF HEALTH
HTM 02-05
(1)
8/12/2019 The Risk Assessment of Fire Damper Installations
25/43
Other publications Dept of Health
HTM 05-02 {cont}Fire & Smoke dampers incompartment wallsmotorised to close onsignal
Fire & Smoke dampers insub compartment walls -
link onlyPW Note: motorised wouldprobably be better for regulartesting
Ducting serving firehazard rooms should beprotected with dampers, orif duct is passing through,
no dampers, but fireresisting duct
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS25
DEPARTMENT
OF HEALTH
HTM 02-05
(2)
8/12/2019 The Risk Assessment of Fire Damper Installations
26/43
Other publications Dept of Health
HTM 05-02 {cont}Installationrequirements are given,but unfortunately thisdoes not say usemanufacturers
instructions, ratherwhat not to do, also arequirement for ceilings
It requires details of alldampers to be includedin the fire strategy and
drawings for complexbuildings
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS26
DEPARTMENT
OF HEALTH
HTM 02-05
(3)
8/12/2019 The Risk Assessment of Fire Damper Installations
27/43
Other publications Dept of C S F
BB100Generally as ADB
References the ASFPGrey Book
Product certification
for property protectionfire dampers shouldalso satisfy LPS1162
It requires details of alldampers to be includedin the fire strategy and
drawings for complexbuildings
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS27
DEPARTMENT
OF CHILDREN,
SCHOOLS &
FAMILIES
BB100
8/12/2019 The Risk Assessment of Fire Damper Installations
28/43
Certification standard - LPCB
The LPCB run a certificationscheme for fire dampers. TheLPS 1162 document containsall the tests that LPC requirethe product to undergo, beforecertification may be offered
It also states that to meet it, acompany must have full BSEN ISO 9001 accreditation.The LPCB visit the factory atleast once a year to confirmby measurement that thecertificated products maintainall the tested dimensions,and confirm that the products
still comply with anyassessments that may havebeen made
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS28
CERTIFICATION
STANDARD
8/12/2019 The Risk Assessment of Fire Damper Installations
29/43
Regulatory Reform (Fire Safety) Order - RRFSO
RRFSOThere is a series of
published guides to meeting
the requirements of the
RRFSO
Information on fire dampers
is vague, but is generally as
follows:1) laundry chutes (smoke and fire
dampers)
2) dampers in ducts should be correctly
installed
3) the fact that in cooking processes
ventilation ducts and dampers shouldbe considered.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS29
RRFSO
-1-
8/12/2019 The Risk Assessment of Fire Damper Installations
30/43
Regulatory Reform (Fire Safety) Order - RRFSO
RRFSOHowever, fire dampers arereferred to indirectly asfollows:
1) In a checklist: Are any holes orgaps in walls, ceilings and floorsproperly sealed, e.g. whereservices such as ventilation ductsand electrical cables pass throughthem?
2) Ventilation systems: Whereventilation systems might assistthe spread of flames, smoke andhot gases from a fire it will benecessary to take steps to safe
guard the means of escapeagainst this hazard.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS30
RRFSO
-3-
8/12/2019 The Risk Assessment of Fire Damper Installations
31/43
Regulatory Reform (Fire Safety) Order - RRFSO
RRFSOUnfortunately, fire dampers
arenotreferred to in the
maintenance check list
section, which is a key area
where they should be, or in
the frequency of checkingsection, also key.
Therefore we need to turn
to BS9999 for further
guidance
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS31
RRFSO
-3-
8/12/2019 The Risk Assessment of Fire Damper Installations
32/43
Regulatory Reform (Fire Safety) Order - RRFSO
BS9999Annex V (normative): Routineinspection and maintenance offire safety installations
This requires smoke controlsystems and their componentsto be tested as often as
weekly, however it is not clearwhat constitute smokedampers. This could possiblyrefer to dampers that are usedto protect escape routes andareas with sleeping risk. Thisshould be considered by thedesigner and perhaps the risk
assessor.
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS32
BS9999
-1-
8/12/2019 The Risk Assessment of Fire Damper Installations
33/43
Regulatory Reform (Fire Safety) Order - RRFSO
BS9999Annex W (normative): Routineinspection and maintenance ofventilation and air conditioningductwork
This requires simple firedampers (spring operated so
probably curtain fire dampers)to be tested every two years ormore often if conditions aresuch that they get dirty quicker.
Both annexes should belooked at in their entiretybefore drawing anyconclusions, and consideration
given to the rest of thedocument
THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS33
BS9999
-2-
8/12/2019 The Risk Assessment of Fire Damper Installations
34/43
Risk assessment
Considerations/Key areasThe positioning of the product
The application of the product (fire, or fire
and smoke)
The supporting construction into which the
damper is fitted
What testing has been undertaken?
What assessment information is available?
What maintenance regimes are in place?
RISK
ASSESSMENT
-1-
34 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
35/43
Risk assessment
Positioning of the productIs it known where all the fire, and fire and smoke, dampers are installed -schedule and drawing
Is there clear access, both outside and inside for cleaning and maintenance
Are there any gaps around the damper between it and the supportingconstruction?
Is the fire damper mounted within the wall?
The lastmightbe allowed if the duct and the joint with the wall are installed usinga tested method
Application escape route or area with sleepingrisk
Does the fire damper have an ES classification (or equivalency throughassessment) when mounted in the supporting construction being used e.g.masonry, dry wall, batt, other fire stopping etc?
Has the damper been installed to the manufacturers instructions or at least to thedocumented satisfaction of the BCA?
Note to get an ES classification, the damper must have been tested (or assessed
for equivalency) to BS EN 1366-2, BS 476 cannot confirm the S low leakagecriteria
RISK
ASSESSMENT
-2-
35 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
36/43
Risk assessment
Application are the fans immediately turnedoff in the event of a fire incident
Dampers tested ad hoc to BS 476 may be acceptable if the fans are turned
off.
Dampers having an E classification are, however, recommended and must
be used if the fans are left on.
If the fans are left on, curtain fire dampers are not recommended as theymay be held open by residual airflow
Does the fire damper have an E classification (or equivalency through
assessment) when mounted in the supporting construction being used e.g.
masonry, dry wall, batt, other fire stopping etc?
Has the damper been installed to the manufacturers instructions or at least
to the documented satisfaction of the BCA?
Note to get an E classification, the damper must have been tested (orassessed for equivalency) to BS EN 1366-2
RISK
ASSESSMENT
-3-
36 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
37/43
Risk assessment
Maintenance regimeDoes this exist for the fire dampers?
Is the responsible person aware of thisrequirement?
Do adequate records of testing andinspection exist?
Do the records note any and all remedialaction to the fire damper and to the sealbetween it and the supporting construction
Refer to Annex V and Annex W of BS9999
RISK
ASSESSMENT
-4-
37 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
38/43
Summary
The requirements for the risk assessment of firedampers are not clear from the RRFSO
However, through reference to ADB and BS9999, a
clear path can be drawn
Additional help is given in the ASFP Grey Book and
HVCA DW145There must be clear records of where dampers are
positioned, that they are installed correctly and that
they are maintained correctly, including the state of
any seal around the damper at the interface between
it and the supporting construction
SUMMARY
38 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
39/43
WRONG
WRONG
-1-
The damper is not in the plane of the wall and the duct is not protected.
Has the damper been tested in association with batt? If fire resisting, is the
duct supported around its outside at its joint with the wall
39 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
40/43
WRONG
WRONG
-2-
The dampers are not in the plane of the wall, the duct is not protectedand it is unlikely that the dampers have been tested passing through a
hole in a steel beam
40 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
41/43
WRONG
WRONG
-3-
!
41 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
42/43
RIGHT
RIGHT
-1-
The damper is within the plane of the wall, the installation is complete and
without any damage to the seal around the damper.Note: However, it needs to be checked that damper has been tested in a batt
installation, especially for ES requirements
42 THE RISK ASSESSMENT OF FIRE DAMPER INSTALLATIONS
8/12/2019 The Risk Assessment of Fire Damper Installations
43/43
The risk assessment of fire
damper installations
THANK YOU FOR LISTENING