THE TOWNSHIP OF SOUTH ORANGE VILLAGE, SOUTH ORANGE, NEW JERSEY SPECIFICATION ADDITIONS AND RENOVATIONS TO THE BAIRD COMMUNITY CENTER VOLUME II MEP, FIRE PROTECTION, CIVIL SPECIFICATIONS FEBRUARY 10, 2020 The Biber Partnership AIA Architecture Planning Interior Design 480 Morris Avenue, Summit, NJ 07901 908.273.8877 FAX 908.273.0978 TBP: 18010

THE TOWNSHIP OF SOUTH ORANGE VILLAGE, SOUTH ......2020/02/10  · 092216 NON-STRUCTURAL METAL FRAMING 8 PAGES 092300 GYPSUM PLASTERING 7 PAGES 092400 PORTLAND CEMENT PLASTERING 7 PAGES

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • THE TOWNSHIP OF SOUTH ORANGE VILLAGE,

    SOUTH ORANGE, NEW JERSEY

    SPECIFICATION

    ADDITIONS AND RENOVATIONS TO

    THE BAIRD COMMUNITY CENTER

    VOLUME II MEP, FIRE PROTECTION, CIVIL SPECIFICATIONS

    FEBRUARY 10, 2020

    The Biber Partnership AIA Architecture Planning Interior Design

    480 Morris Avenue, Summit, NJ 07901

    908.273.8877 FAX 908.273.0978 TBP: 18010

  • SPECIFICATIONS FOR THE LABOR AND MATERIAL REQUIRED FOR: PROJECT: ADDITIONS AND RENOVATIONS TO

    THE BAIRD COMMUNITY CENTER

    LOCATION: 5 MEAD STREET

    SOUTH ORANGE, NEW JERSEY OWNER THE TOWNSHIP OF SOUTH ORANGE VILLAGE ARCHITECT: THE BIBER PARTNERSHIP AIA ARCHITECTURE PLANNING INTERIOR DESIGN _____________________________________________ PETER I. BIBER, AIA

    NEW JERSEY AI 05025 480 MORRIS AVENUE SUMMIT, NEW JERSEY (908) 273-8877 TBP PROJECT NUMBER: 18010 DATE: February 10, 2020

  • TBP18010 Table of Contents The Baird Community Center Page 1 of 8 Additions & Renovations

    TABLE OF CONTENTS

    TITLE SHEET TABLE OF CONTENTS INDEX OF DRAWINGS PART I - GENERAL DOCUMENTS DIVISION 0 - BIDDING AND CONTRACT REQUIREMENTS (VOLUME I) PAGES BIDDING INFORMATION NOTICE TO BIDDERS 1 PAGE STATEMENT OF THE WORK 3 PAGES GENERAL INSTRUCTIONS TO BIDDERS 16 PAGES BID FORMS BID FORM 10 PAGES BID DOCUMENT CHECKLIST 1 PAGE STATEMENT OF OWNERSHIP DISCLOSURE 2 PAGES NON-COLLUSION CERTIFICATION 1 PAGE BID GUARANTEE STATEMENT 1 PAGE PUBLIC WORKS CONTRACTOR REGISTRATION 1 PAGE CONSENT OF SURETY (PERFORMANCE BOND 1 PAGE AFFIRMATIVE ACTION INSTRUCTIONS 2 PAGES AFFIRMATIVE ACTION QUESTIONNAIRE 1 PAGE AMERICAN WITH DISABILITY ACT 2 PAGES NEW JERSEY BUSINESS REGISTRATION 1 PAGE BIDDER QUALIFICATION FORM 2 PAGES ACKNOWLEDGEMENT OF RECEIPT OF ADDENDA 1 PAGE CONTRACT FORMS NOTICE OF AWARD 1 PAGE NOTICE TO PROCEED 1 PAGE PERFORMANCE-PAYMENT BOND 2 PAGES HOLD HARMLESS INDEMNIFICATION AGREEMENT 1 PAGE INSURANCE CERTIFICATES 1 PAGE SUBCONTRACTORS CERTIFICATION 2 PAGES AIA GENERAL CONDITIONS FOR CONSTRUCTION CM EDITION 41 PAGES AIA STANDARD FORM OF AGREEMENT OWNER & CONTRACTOR CM EDITION 13 PAGES MEETING FEDERAL LABOR STANDARDS FOR COMMUNITY DEVELOPMENT BLOCK GRANT (CDBG) 45 PAGES PREVAILING WAGE RATES (General Decision #NJ20190031 10/04/19) 22 PAGES SPECIAL CONDITIONS 20 PAGES

  • TBP18010 Table of Contents The Baird Community Center Page 2 of 8 Additions & Renovations

    PART II - TECHNICAL SPECIFICATIONS SECTION TITLE DIVISION 01 - GENERAL REQUIREMENTS (VOLUME I) 010550 BORING LOGS 1 PAGE SOILS REPORT 22 PAGES 012100 ALLOWANCES 3 PAGES 012200 UNIT PRICES 4 PAGES 012300 ALTERNATES 2 PAGES 012600 CONTRACT MODIFICATION PROCEDURES 3 PAGES 012900 PAYMENT PROCEDURES 5 PAGES 013100 PROJECT MANAGEMENT AND COORDINATION 3 PAGES 013300 SUBMITTAL PROCEDURES 11 PAGES 014000 QUALITY REQUIREMENTS 7 PAGES 014200 REFERENCES 2 PAGES 014339 MOCKUPS 2 PAGES 016000 PRODUCT REQUIREMENTS 7 PAGES 017329 CUTTING AND PATCHING 4 PAGES 017400 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL 6 PAGES 017700 CLOSEOUT PROCEDURES 5 PAGES 017823 OPERATION AND MAINTENANCE DATA 8 PAGES DIVISION 02 – EXISTING CONDITIONS (VOLUME I) 024119 SELECTIVE STRUCTURE DEMOLITION 7 PAGES DIVISION 03 – CONCRETE (VOLUME I) 033000 CAST-IN-PLACE CONCRETE 12 PAGES DIVISION 04 – MASONRY (VOLUME I) 042000 UNIT MASONRY 23 PAGES DIVISION 05 – METALS (VOLUME I) 051200 STRUCTURAL STEEL FRAMING 7 PAGES 053100 STEEL DECKING 5 PAGES 054000 COLD-FORMED METAL FRAMING 11 PAGES 055000 METAL FABRICATIONS 11 PAGES 055100 METAL STAIRS 8 PAGES 055213 PIPE AND TUBE RAILINGS 14 PAGES 057300 DECORATIVE METAL RAILINGS 16 PAGES DIVISION 06 - WOOD AND PLASTICS (VOLUME I) 061000 ROUGH CARPENTRY 18 PAGES 061053 MISCELANEOUS ROUGH CARPENTRY 11 PAGES 061500 COMPOSITE DECKING 5 PAGES

  • TBP18010 Table of Contents The Baird Community Center Page 3 of 8 Additions & Renovations

    061600 SHEATHING 14 PAGES 062013 EXTERIOR FINISH CARPENTRY 11 PAGES 062023 INTERIOR FINISH CARPENTRY 12 PAGES 064023 INTERIOR ARCHITECTURAL WOODWORK 11 PAGES 066400 PANELING 3 PAGES 066500 SIMULATED WOOD TRIM 10 PAGES DIVISION 07 - THERMAL AND MOISTURE PROTECTION (VOLUME I) 071113 BITUMINOUS DAMPPROOFING 5 PAGES 071326 SELF-ADHERING SHEET WATERPROOFING 12 PAGES 071353 ELASTOMERIC SHEET WATERPROOFING 10 PAGES 071413 HOT FLUID-APPLIED RUBBERIZED ASPHALT WATERPROOFING 9 PAGES 071416 COLD FLUID-APPLIED WATERPROOFING 6 PAGES 072100 THERMAL INSULATION 8 PAGES 073113 ASPHALT SHINGLES 12 PAGES 074600 FIBER CEMENT SIDING AND TRIM 7 PAGES 075323 ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 16 PAGES 076200 SHEET METAL FLASHING AND TRIM 14 PAGES 077100 ROOF SPECIALTIES 14 PAGES 078400 FIRESTOPPING 5 PAGES 079200 JOINT SEALANTS 9 PAGES DIVISION 08 – OPENINGS (VOLUME I) 081113 HOLLOW METAL DOORS AND FRAMES 11 PAGES 081416 FLUSH WOOD DOORS 7 PAGES 081433 STILE AND RAIL WOOD DOORS 5 PAGES 083113 ACCESS DOORS AND FRAMES 4 PAGES 083323 OVERHEAD COILING DOORS 13 PAGES 084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 10 PAGES 085200 WOOD WINDOWS 12 PAGES 086200 UNIT SKYLIGHTS 7 PAGES 087100 DOOR HARDWARE 8 PAGES 088000 GLAZING 11 PAGES 088300 MIRRORS 5 PAGES 089000 LOUVERS AND VENTS 7 PAGES DIVISION 09 – FINISHES (VOLUME I) 092216 NON-STRUCTURAL METAL FRAMING 8 PAGES 092300 GYPSUM PLASTERING 7 PAGES 092400 PORTLAND CEMENT PLASTERING 7 PAGES 092900 GYPSUM BOARD 9 PAGES 093000 TILING 8 PAGES 095123 ACOUSTICAL TILE CEILINGS 9 PAGES 096466 INDOOR WOOD ATHLETIC FLOORING 4 PAGES 096513 RESILIENT BASE AND ACCESSORIES 6 PAGES 096516 RESILIENT SHEET FLOORING 5 PAGES

  • TBP18010 Table of Contents The Baird Community Center Page 4 of 8 Additions & Renovations

    096519 RESILIENT TILE FLOORING 5 PAGES 096813 TILE CARPETING 5 PAGES 096816 SHEET CARPETING 5 PAGES 097200 WALL COVERINGS 5 PAGES 098000 ACOUSTICAL TREATMENT 2 PAGES 098413 FIXED SOUND-ABSORPTIVE PANELS 5 PAGES 099113 EXTERIOR PAINTING 8 PAGES 099123 INTERIOR PAINTING 10 PAGES 099300 STAINING AND TRANSPARENT FINISHING 5 PAGES 099600 HIGH-PERFORMANCE COATINGS 6 PAGES DIVISION 10 – SPECIALTIES (VOLUME I) 101400 SIGNAGE 6 PAGES 102113 TOILET COMPARTMENTS 5 PAGES 102226 OPERABLE PARTITIONS 7 PAGES 102800 TOILET ACCESSORIES 3 PAGES 104413 FIRE EXTINGUISHER CABINETS 5 PAGES 104416 FIRE EXTINGUISHERS 2 PAGES DIVISION 11 – EQUIPMENT 116623 GYMNASIUM EQUIPMENT 7 PAGES 116653 GYMNASIUM DIVIDERS 5 PAGES DIVISION 12 – FURNISHINGS (VOLUME I) 129300 SITE FURNISHINGS 5 PAGES DIVISION 13 - SPECIAL CONSTRUCTION (VOLUME I) 133419 METAL BUILDING SYSTEMS 37 PAGES DIVISION 14 - CONVEYING EQUIPMENT (VOLUME I) 142123 ELECTRIC TRACTION PASSENGER ELEVATORS 11 PAGES DIVISION 15 – RESERVED DIVISION 16 – RESERVED DIVISION 17 – RESERVED DIVISION 18 – RESERVED DIVISION 19 – RESERVED DIVISION 20 – RESERVED

  • TBP18010 Table of Contents The Baird Community Center Page 5 of 8 Additions & Renovations

    DIVISION 21 – FIRE SUPPRESSION (VOLUME II) 210000 FIRE-SUPRESSION SPRINKLERS 210553 IDENTIFICATION FOR FRIE-SUPRESSION PIPING AND EQUIPMENT 211119 FIRE-DEPARTMENT CONNECTIONS DIVISION 22 – PLUMBING (VOLUME II) 220500 COMMON WORK RESULTS FOR PLUMBING 220500 PLUMBING SPECIALTIES 220518 ESCUTCHEONS FOR PLUMBING PIPING 220523.12 BALL VALVE FOR PLUMBING PIPING 220523.13 BUTTERFLY VALVES FOR PLUMBING PIPING 220523.14 CHECK VALVES FOR PLUMBING PIPING 220523.15 GATE VALVES FOR PLUMBING 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220719 PLUMBING PIPING INSULATION 221116 DOMESTIC WATER PIPING 221316 SANITARY WASTE AND VENT PIPING 221516 NATURAL GAS PIPING 224000 PLUMBING FIXTURES DIVISION 23– HVAC (VOLUME II) 230300 BASIC MECHANICAL MATERIALS AND METHODS 230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT 230518 ESCUTCHEONS FOR HVAC PIPING 230519 METERS AND GAGES FOR HVAC PIPING 230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230548 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT 230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC 230713 DUCT INSULATION 230719 HVAC PIPING INSULATION 230923.12 CONTROL DAMPERS 231123 FACILITY NATURAL GAS PIPING 232300 REFRIGERANT PIPING 233113 METAL DUCTS 233300 AIR DUCT ACCESSORIES 233346 FLEXIBLE DUCTS 233413 AXIAL HVAC FANS 233423 HVAC POWER VENTILATORS 233713 REGISTERS AND GRILLES 233713.13 AIR DIFFUSERS 234100 PARTICULATE AIR FILTRATIONS 235113.16 VENT DAMPERS 236313 AIR-COOLED REFRIGERANT CONDENSERS 237413 PACKAGED ROOFTOP AIR CONDITIONING UNIT 237433.1 SEQUENCE OF OPERATION FOR DEDICATED OUTDOOR AIR UNITS

  • TBP18010 Table of Contents The Baird Community Center Page 6 of 8 Additions & Renovations

    238126 SPLIT SYSTEM AIR CONDITIONERS AND VRF SYSTEMS 238239.13 CABINET UNIT HEATERS 238240 ELECTRIC HEATING EQUIPMENT DIVISION 24 – RESERVED DIVISION 25 – INTEGRATED AUTOMATION NOT APPLICABLE DIVISION 26 – ELECTRICAL (VOLUME II) 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS 260544 SLEEVE AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260553 ELECTRICAL IDENTIFICATION 260573 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY 260923 LIGHTING CONTROL DEVICES 262413 SWITCHBOARDS 262416 PANELBOARDS 262726 WIRING DEVICES 262813 FUSES 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS 262923 VARIABLE-FREQUENCY MOTOR CONTROLLERS DIVISION 27 – COMMUNICATIONS NOT APPLICABLE DIVISION 28 – ELECTRONIC SAFETY AND SECURITY (VOLUME II) 283111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM DIVISION 29 – RESERVED DIVISION 30 – RESERVED CIVIL SPECIFICATIONS (VOLUME II) 024000 CLEARING SITE (DEMOLITION AND DISPOSAL) 030000 CONCRETE SITE WORK 101453 TRAFFIC CONTROL SIGNS 221413.10 HIGH DENSITY POLYETHYLENE (HDPE) PIPE 221413.20 POLYVINYL CHLORIDE (PVC) PIPE 265629 LIGHTING FIXTURES DIVISION 31 – EARTHWORK (VOLUME II) 311000 SITE PREPARATION 312300 BACKFILL OPERATIONS—GENERALEXCAVATION 312319 DEWATERING

  • TBP18010 Table of Contents The Baird Community Center Page 7 of 8 Additions & Renovations

    312500 EROSION CONTROL DIVISION 31 – EARTHWORK RELATIVE TO STORMWATER MANAGEMENT (VOLUME II) 311000 SITE CLEARING 312000 EARTH MOVING DIVISION 32 – EXTERIOR IMPROVEMENTS (VOLUME II) 320516 STONE—BASE/BACKFILL—LANDSCAPING—PEDESTRIAN PATH 320519 GEOTEXTILE FILTER FABRICS 321126.19 STABILIZED BASE COURSE 321216 HOT MIX ASPHALT SURFACE COURSE 321413 INTERLOCKING CONCRETE PAVERS 321613 GRANITE BLOCK CURBING 321713.19 CONCRETE CURB STOPS 321713.26 TIMBER GUIDE RAIL 321723.13 PAINT STRIPING AND PAVEMENT GRAPHICS 321726 DETECTABLE WARNING SURFACES 323113 CHAIN LINK FENCE AND GATES 323223 SEGMENTAL RETAINING WALL SYSTEMS 329000 LANDSCAPING DIVISION 33 – UTILITIES (VOLUME II) 331113.13 WATER SUPPLY SYSTEM 333000 PVC SANITARY SEWERS & APPURTENANCES 334113 REINFORCED CONCRETE PIPE (RCP) & CONCRETECULVERTS 334413 PLASTIC STORM SEWER INLET BOX-AREA DRAIN 334413.13 STORM SEWER INLET—DRAINAGE SYSTEMS 334420 ADJUST ELEVATION OF EXISTING GRATES 334913 STORM DRAINAGE MANHOLES, FRAMES & COVERS DIVISION 34 - TRANSPORTATION NOT APPLICABLE DIVISION 35 - WATERWAY AND MARINE CONSTRUCTION NOT APPLICABLE DIVISION 36 - RESERVED DIVISION 37 - RESERVED DIVISION 38 - RESERVED DIVISION 39 - RESERVED DIVISION 40 - PROCESS INTEGRATION NOT APPLICABLE DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT NOT APPLICABLE

  • TBP18010 Table of Contents The Baird Community Center Page 8 of 8 Additions & Renovations

    DIVISION 42 - PROCESS HEATING,COOLING, AND DRYING EQUIPMENT NOT APPLICABLE DIVISION 43 - PROCESS GAS AND LIQUID HANDLING, PURIFICATION, AND STORAGE EQUIPMENT NOT APPLICABLE DIVISION 44 - POLLUTION CONTROL EQUIPMENT NOT APPLICABLE DIVISION 45 - INDUSTRY-SPECIFIC MANUFACTURING EQUIPMENT NOT APPLICABLE DIVISION 46 - RESERVED DIVISION 47 - RESERVED DIVISION 48 - ELECTRICAL POWER GENERATION NOT APPLICABLE DIVISION 49 - RESERVED

  • TBP18010

    TheBairdCommunityCenter

    Additons & Renovations 21-00-00

    SECTION 210000

    FIRE-SUPPRESSION SPRINKLERS

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 1 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. This Section includes fire-suppression sprinklers, piping, and equipment for the following

    building systems:

    1. Wet-pipe, fire-suppression sprinklers, including piping, valves, specialties, and automatic

    sprinklers.

    2. Dry-pipe, fire-suppression sprinklers, including piping, valves, specialties, automatic

    sprinklers, air compressor, and accessories.

    1.3 DEFINITIONS

    A. Working Plans: Documents, including drawings, calculations, and material specifications

    prepared according to NFPA 13 for obtaining approval from authorities having jurisdiction.

    1.4 SYSTEM PERFORMANCE REQUIREMENTS

    A. Design sprinklers and obtain approval from authorities having jurisdiction.

    B. Design sprinkler piping according to the following and obtain approval from authorities having

    jurisdiction:

    1. Include 20 percent margin of safety for available water flow and pressure.

    2. Include losses through water-service piping, valves, and backflow preventers.

    3. Sprinkler Occupancy Hazard Classifications: As follows:

    a. Parking Garage: Ordinary Hazard, Group 1. (Dry)

    b. Electrical Equipment Rooms: Ordinary Hazard, Group 1.

    c. Building Service and Storage Areas: Ordinary Hazard, Group 1.

    d. Mechanical Equipment Rooms: Ordinary Hazard, Group 1.

    e. Office and Public Areas: Light Hazard.

    f. Residential Living Areas: Light Hazard.

    g. Retail: Light Hazard.

    4. Minimum Density for Automatic-Sprinkler Piping Design: As follows:

    a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area.

    b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area.

  • TBP18010

    TheBairdCommunityCenter

    Additons & Renovations 21-00-00

    5. Maximum Protection Area per Sprinkler: As follows:

    a. Light Hazard: 225 sq. ft.

    b. Ordinary Hazard Group 1: 130 sq. ft.

    C. Components and Installation: Capable of producing piping systems with 175-psig minimum

    working-pressure rating, unless otherwise indicated.

    1.5 SUBMITTALS

    A. Product Data: For the following:

    1. Pipe and fitting materials and methods of joining for sprinkler piping.

    2. Pipe hangers and supports.

    3. Piping seismic restraints.

    4. Valves, including specialty valves, accessories, and devices.

    5. Alarm devices. Include electrical data.

    6. Air compressors. Include electrical data.

    7. Fire department connections. Include type; number, size, and arrangement of inlets; caps

    and chains; size and direction of outlet; escutcheon and marking; and finish.

    8. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting,

    finish, and other pertinent data.

    B. Fire-Hydrant Flow Test Report:

    C. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that

    have been approved by authorities having jurisdiction. Include hydraulic calculations, if

    applicable.

    D. Field Test Reports and Certificates: Indicate and interpret test results for compliance with

    performance requirements and as described in NFPA 13. Include "Contractor's Material and

    Test Certificate for Aboveground Piping" and "Contractor's Material and Test Certificate for

    Underground Piping."

    E. Maintenance Data: For each type of sprinkler specialty to include in maintenance manuals

    specified in Division 1.

    1.6 QUALITY ASSURANCE

    A. Installer Qualifications: An experienced installer who has designed and installed fire-

    suppression piping similar to that indicated for this Project and obtained design approval and

    inspection approval from authorities having jurisdiction.

    B. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by

    a qualified professional engineer hired by the contractor. Base calculations on results of fire-

    hydrant flow test.

    C. Professional Engineer Qualifications: A professional engineer who is legally qualified to

    practice in jurisdiction where Project is located and who is experienced in providing

    engineering services of the kind indicated. Engineering services are defined as those performed

  • TBP18010

    TheBairdCommunityCenter

    Additons & Renovations 21-00-00

    for installations of fire-suppression piping that are similar to those indicated for this Project in

    material, design, and extent.

    D. Manufacturer Qualifications: Firms whose equipment, specialties, and accessories are listed by

    product name and manufacturer in UL's "Fire Protection Equipment Directory" and FM's "Fire

    Protection Approval Guide" and that comply with other requirements indicated.

    E. Sprinkler Components: Listing/approval stamp, label, or other marking by a testing agency

    acceptable to authorities having jurisdiction.

    F. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,

    Article 100, by a testing agency acceptable to authorities having jurisdiction.

    G. NFPA Standards: Equipment, specialties, accessories, installation, and testing complying with

    the following:

    1. NFPA 13, "Installation of Sprinkler Systems."

    END OF SECTION 21 00 00

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-1

    SECTION 210553- IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. Section Includes:

    1. Equipment labels.

    2. Warning signs and labels.

    3. Pipe labels.

    4. Stencils.

    5. Valve tags.

    6. Warning tags.

    1.3 ACTION SUBMITTALS

    A. Product Data: For each type of product.

    B. Samples: For color, letter style, and graphic representation required for each identification

    material and device.

    C. Equipment-Label Schedule: Include a listing of all equipment to be labeled and the proposed

    content for each label.

    D. Valve Schedules: Valve numbering scheme.

    PART 2 - PRODUCTS

    2.1 EQUIPMENT LABELS

    A. Metal Labels for Equipment:

    1. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    a. Brady Corporation.

    b. Carlton Industries, LP.

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-2

    2. Material and Thickness: Brass, 0.032 inch thick, with predrilled holes for attachment

    hardware.

    3. Letter Color: Red.

    4. Background Color: White.

    5. Minimum Label Size: Length and width vary for required label content, but not less than

    2-1/2 by 3/4 inch.

    6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24

    inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering

    for greater viewing distances. Include secondary lettering two-thirds to three-fourths the

    size of principal lettering.

    7. Fasteners: Stainless-steel rivets.

    8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

    B. Label Content: Include equipment's Drawing designation or unique equipment number,

    Drawing numbers where equipment is indicated (plans, details, and schedules), and the

    Specification Section number and title where equipment is specified.

    C. Equipment-Label Schedule: For each item of equipment to be labeled, on 8-1/2-by-11-inch

    bond paper. Tabulate equipment identification number and identify Drawing numbers where

    equipment is indicated (plans, details, and schedules) and the Specification Section number and

    title where equipment is specified. Equipment schedule shall be included in operation and

    maintenance data.

    2.2 WARNING SIGNS AND LABELS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    1. Brady Corporation.

    2. Carlton Industries, LP.

    B. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8

    inch thick, with predrilled holes for attachment hardware.

    C. Letter Color: Red.

    D. Background Color: White.

    E. Maximum Temperature: Able to withstand temperatures up to 160 deg F.

    F. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2

    by 3/4 inch.

    G. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2

    inch for viewing distances up to 72 inches, and proportionately larger lettering for greater

    viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal

    lettering.

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-3

    H. Fasteners: Stainless-steel rivets.

    I. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

    J. Label Content: Include caution and warning information, plus emergency notification

    instructions.

    2.3 PIPE LABELS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    1. Brady Corporation.

    2. Carlton Industries, LP.

    B. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering

    indicating service and showing flow direction according to ASME A13.1.

    C. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to partially cover circumference

    of pipe and to attach to pipe without fasteners or adhesive.

    D. Self-adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing.

    E. Pipe-Label Contents: Include identification of piping service using same designations or

    abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.

    1. Flow-Direction Arrows: Integral with piping-system service lettering to accommodate

    both directions or as separate unit on each pipe label to indicate flow direction.

    2. Lettering Size: Size letters according to ASME A13.1 for piping.

    F. Pipe-Label Colors:

    1. Background Color: Safety Red.

    2. Letter Color: White.

    2.4 STENCILS

    A. Stencils for Piping:

    1. Manufacturers: Subject to compliance with requirements, provide products by the

    following:

    a. Carlton Industries, LP.

    2. Lettering Size: Size letters according to ASME A13.1 for piping.

    3. Stencil Material: Brass.

    4. Stencil Paint: Safety Red, exterior, gloss, alkyd enamel. Paint may be in pressurized

    spray-can form.

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-4

    5. Identification Paint: White, exterior, alkyd enamel. Paint may be in pressurized spray-can

    form.

    2.5 VALVE TAGS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    1. Brady Corporation.

    2. Carlton Industries, LP.

    B. Description: Stamped or engraved with 1/4-inch letters for piping-system abbreviation and 1/2-

    inch numbers.

    1. Tag Material: Brass, 0.032 inch thick, with predrilled holes for attachment hardware.

    2. Fasteners: Brass wire-link chain.

    3. Valve-Tag Color: Safety Red.

    4. Letter Color: White.

    C. Valve Schedules: For each piping system, on 8-1/2-by-11-inch bond paper. Tabulate valve

    number, piping system, system abbreviation (as shown on valve tag), location of valve (room or

    space), normal-operating position (open, closed, or modulating), and variations for

    identification. Mark valves for emergency shutoff and similar special uses.

    1. Valve-tag schedule shall be included in operation and maintenance data.

    2.6 WARNING TAGS

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    1. Brady Corporation.

    2. Carlton Industries, LP.

    B. Description: Preprinted or partially preprinted, accident-prevention tags, of plasticized card

    stock with matte finish suitable for writing.

    1. Size: 3 by 5-1/4 inches minimum.

    2. Fasteners: Brass grommet and wire.

    3. Nomenclature: Large-size primary caption such as "DANGER," "CAUTION," or "DO

    NOT OPERATE."

    4. Color: Safety Yellow background with black lettering.

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-5

    PART 3 - EXECUTION

    3.1 PREPARATION

    A. Clean piping and equipment surfaces of incompatible primers, paints, and encapsulants, as well

    as dirt, oil, grease, release agents, and other substances that could impair bond of identification

    devices.

    3.2 GENERAL INSTALLATION REQUIREMENTS

    A. Coordinate installation of identifying devices with completion of covering and painting of

    surfaces where devices are to be installed.

    B. Coordinate installation of identifying devices with locations of access panels and doors.

    C. Install identifying devices before installing acoustical ceilings and similar concealment.

    3.3 EQUIPMENT LABEL INSTALLATION

    A. Install or permanently fasten labels on each major item of mechanical equipment.

    B. Locate equipment labels where accessible and visible.

    3.4 PIPE LABEL INSTALLATION

    A. Piping: Painting of piping is specified in Section 099123 "Interior Painting."

    B. Stenciled Pipe-Label Option: Stenciled labels may be provided instead of manufactured pipe

    labels, at Installer's option. Install stenciled pipe labels, complying with ASME A13.1, with

    painted, color-coded bands or rectangles on each piping system.

    1. Identification Paint: Use for contrasting background.

    2. Stencil Paint: Use for pipe marking.

    C. Pipe-Label Locations: Locate pipe labels where piping is exposed or above accessible ceilings

    in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and

    plenums; and exterior exposed locations as follows:

    1. Near each valve and control device.

    2. Near each branch connection excluding short takeoffs. Where flow pattern is not obvious,

    mark each pipe at branch.

    3. Near penetrations and on both sides of through walls, floors, ceilings, and inaccessible

    enclosures.

    4. At access doors, manholes, and similar access points that permit a view of concealed

    piping.

    5. Near major equipment items and other points of origination and termination.

  • TBP18010

    The Baird Community Center

    Additons & Renovations 210553-6

    6. Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in

    areas of congested piping and equipment.

    7. On piping above removable acoustical ceilings. Omit intermediately spaced labels.

    D. Directional Flow Arrows: Arrows shall be used to indicate direction of flow in pipes including

    pipes where flow is allowed in both directions.

    3.5 VALVE-TAG INSTALLATION

    A. Install tags on valves and control devices in fire-suppression piping systems. List tagged valves

    in a valve-tag schedule.

    B. Valve-Tag Application Schedule: Tag valves according to size, shape, and with captions similar

    to those indicated in "Valve-Tag Size and Shape" Subparagraph below:

    1. Valve-Tag Size and Shape:

    a. Fire-Suppression Standpipe: 1-1/2 inches, round.

    b. Wet-Pipe Sprinkler System: 1-1/2 inches, round.

    3.6 WARNING-TAG INSTALLATION

    A. Write required message on, and attach warning tags to, equipment and other items where

    required.

    END OF SECTION 210553

  • TBP18010

    The Baird Community Center

    Additions & Renovations 211119-1

    SECTION 211119 - FIRE-DEPARTMENT CONNECTIONS

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. Section Includes:

    1. Flush-type fire-department connections.

    1.3 ACTION SUBMITTALS

    A. Product Data: For each type of product.

    1. Include construction details, material descriptions, dimensions of individual components

    and profiles, and finishes for each fire-department connection.

    PART 2 - PRODUCTS

    2.1 FLUSH-TYPE FIRE-DEPARTMENT CONNECTION

    A. Manufacturers: Subject to compliance with requirements, provide products by one of the

    following:

    1. American Fire Hose & Cabinet.

    2. Guardian Fire Equipment, Inc.

    3. Potter Roemer LLC.

    B. Standard: UL 405.

    C. Type: Flush, for wall mounting.

    D. Pressure Rating: 175 psig minimum.

    E. Body Material: Corrosion-resistant metal.

    F. Inlets: Brass with threads according to NFPA 1963 and matching local fire-department sizes

    and threads. Include extension pipe nipples, brass lugged swivel connections, and check devices

    or clappers.

    G. Caps: Brass, lugged type, with gasket and chain.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 211119-2

    H. Escutcheon Plate: Rectangular, brass, wall type.

    I. Outlet: With pipe threads.

    J. Body Style: Horizontal.

    K. Number of Inlets: Two.

    L. Outlet Location: Back.

    M. Escutcheon Plate Marking: Similar to "AUTO SPKR & STANDPIPE."

    N. Finish: Polished chrome plated.

    O. Outlet Size: NPS 6.

    PART 3 - EXECUTION

    3.1 EXAMINATION

    A. Examine conditions, with Installer present, for compliance with requirements for installation

    tolerances and other conditions affecting performance of fire-department connections.

    B. Examine roughing-in for fire-suppression standpipe system to verify actual locations of piping

    connections before fire-department connection installation.

    C. Proceed with installation only after unsatisfactory conditions have been corrected.

    3.2 INSTALLATION

    A. Install wall-type fire-department connections.

    B. Install yard-type fire-department connections in concrete slab support. Comply with

    requirements for concrete in Section 033000 "Cast-in-Place Concrete."

    C. Install automatic (ball-drip) drain valve at each check valve for fire-department connection.

    END OF SECTION 211119

  • TBP18010 220500-1

    The Baird Community Center

    Additions & Renovations

    SECTION 220500 - COMMON WORK RESULTS FOR PLUMBING

    Verify that Section titles referenced in this Section are correct for this Project's Specifications; Section titles

    may have changed.

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 1 Specification Sections, apply to this Section.

    1.2 SUMMARY

    See Editing Instruction No. 3 in the Evaluations for discussion about how this Section supplements other

    Division 15 Sections.

    A. This Section includes the following:

    Adjust list below to suit Project.

    1. Escutcheons.

    2. Equipment installation requirements common to equipment sections.

    3. Painting and finishing.

    4. Concrete bases.

    5. Supports and anchorages.

    1.3 DEFINITIONS

    A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces,

    pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings,

    unexcavated spaces, crawlspaces, and tunnels.

    B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied

    spaces and mechanical equipment rooms.

    C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient

    temperatures and weather conditions. Examples include rooftop locations.

    D. Concealed, Interior Installations: Concealed from view and protected from physical contact by

    building occupants. Examples include above ceilings and in duct shafts.

    E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions

    and physical contact by building occupants but subject to outdoor ambient temperatures.

    Examples include installations within unheated shelters.

    Retain below if procedures for welder certification are retained in "Quality Assurance" Article.

  • TBP18010 220500-1

    The Baird Community Center

    Additions & Renovations

    PART 2 - PRODUCTS

    2.1 MANUFACTURERS

    See Editing Instruction No. 1 in the Evaluations for cautions about naming manufacturers and products.

    Edit this Article with other Part 2 articles in which manufacturers and products, or manufacturers only, are

    named. See Division 1 Section "Product Requirements" for an explanation of the terms "Available

    Manufacturers" and "Manufacturers" and the effect these terms have on "Comparable Product" and

    "Product Substitution" requirements.

    A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements

    apply for product selection:

    1. Available Manufacturers: Subject to compliance with requirements, manufacturers

    offering products that may be incorporated into the Work include, but are not limited to,

    the manufacturers specified.

    2. Manufacturers: Subject to compliance with requirements, provide products by the

    manufacturers specified.

    PART 3 - EXECUTION

    3.1 EQUIPMENT INSTALLATION - COMMON REQUIREMENTS

    A. Install equipment to allow maximum possible headroom unless specific mounting heights are not

    indicated.

    B. Install equipment level and plumb, parallel and perpendicular to other building systems and

    components in exposed interior spaces, unless otherwise indicated.

    C. Install mechanical equipment to facilitate service, maintenance, and repair or replacement of

    components. Connect equipment for ease of disconnecting, with minimum interference to other

    installations. Extend grease fittings to accessible locations.

    D. Install equipment to allow right of way for piping installed at required slope.

    3.2 PAINTING

    Division 9 Sections specify paint products for various surfaces (e.g., ferrous and nonferrous metals and

    insulation jackets), mechanical items to be field painted, application methods, and coating systems (number

    of prime and finish coatings and coating thicknesses). Coordinate these requirements with Architect to

    ensure that appropriate painting requirements are retained in these Division 9 Sections.

    A. Painting of mechanical systems, equipment, and components is specified in Division 9 Section

    "Painting Consumer Line Product." Provide custom paint for RTU-1. Color as per

    Architect/Owner requirements

    B. Damage and Touchup: Repair marred and damaged factory-painted finishes with materials and

    procedures to match original factory finish.

  • TBP18010 220500-1

    The Baird Community Center

    Additions & Renovations

    3.3 CONCRETE BASES

    Coordinate concrete work in this Article with Division 3 Section "Cast-in-Place Concrete" or "Cast-in-

    Place Concrete (Limited Applications)."

    Coordinate below with Division 15 Sections specifying equipment. Indicate dowel rod quantity, size, and

    spacing on Drawings.

    A. Concrete Bases: Anchor equipment to concrete base according to equipment manufacturer's

    written instructions and according to seismic codes at Project.

    1. Construct concrete bases of dimensions indicated, but not less than 6 inches (100 mm)

    larger in both directions than supported unit.

    2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated,

    install dowel rods on 18 centers around the full perimeter of the base.

    3. Install epoxy-coated anchor bolts for supported equipment that extend through concrete

    base, and anchor into structural concrete floor.

    4. Place and secure anchorage devices. Use supported equipment manufacturer's setting

    drawings, templates, diagrams, instructions, and directions furnished with items to be

    embedded.

    5. Install anchor bolts to elevations required for proper attachment to supported equipment.

    6. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

    3.4 ERECTION OF METAL SUPPORTS AND ANCHORAGES

    A. Refer to Division 5 Section "Metal Fabrications" for structural steel.

    B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation

    to support and anchor mechanical materials and equipment.

    C. Field Welding: Comply with AWS D1.1.

    3.5 GROUTING

    A. Mix and install grout for mechanical equipment base bearing surfaces, pump and other equipment

    base plates, and anchors.

    B. Clean surfaces that will come into contact with grout.

    C. Provide forms as required for placement of grout.

    D. Avoid air entrapment during placement of grout.

    E. Place grout, completely filling equipment bases.

    F. Place grout on concrete bases and provide smooth bearing surface for equipment.

    G. Place grout around anchors.

  • TBP18010 220500-1

    The Baird Community Center

    Additions & Renovations

    H. Cure placed grout.

    END OF SECTION 220500

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 1

    SECTION 220500 - PLUMBING SPECIALTIES

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 1 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. This Section includes the following plumbing specialties:

    1. Backflow preventers.

    2. Strainers.

    3. Drain valves.

    4. Miscellaneous piping specialties.

    5. Sleeve penetration systems.

    6. Flashing materials.

    7. Cleanouts.

    8. Floor drains.

    9. Roof drains.

    B. Related Sections include the following:

    1. Division 23 Section "Meters and Gauges" for water meters, thermometers, and pressure

    gauges.

    1.3 DEFINITIONS

    A. The following are industry abbreviations for plastic piping materials:

    1. ABS: Acrylonitrile-butadiene-styrene plastic.

    2. PE: Polyethylene plastic.

    3. PUR: Polyurethane plastic.

    4. PVC: Polyvinyl chloride plastic.

    1.4 PERFORMANCE REQUIREMENTS

    A. Provide components and installation capable of producing piping systems with following

    minimum working-pressure ratings, unless otherwise indicated:

    1. Domestic Water Piping: 250 psig.

    2. Sanitary Waste and Vent Piping: 10-foot head of water.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 2

    3. Storm Drainage Piping: 10-foot head of water.

    4. Force-Main Piping: 100 psig.

    1.5 SUBMITTALS

    A. Product Data: Include rated capacities and shipping, installed, and operating weights. Indicate

    materials, finishes, dimensions, required clearances, and methods of assembly of components;

    and piping and wiring connections for the following:

    1. Backflow preventers and water regulators.

    2. Balancing valves and strainers.

    3. Thermostatic water mixing valves.

    4. Water hammer arresters, air vents.

    5. Drain valves.

    6. Outlet boxes and washer-supply outlets.

    7. Cleanouts, floor drains, open receptors, trench drains, and roof drains.

    8. Air-admittance valves, vent caps, vent terminals, and roof flashing assemblies.

    9. Sleeve penetration systems.

    B. Field test reports.

    C. Maintenance Data: For plumbing specialties to include in maintenance manuals. Include the

    following:

    1. Backflow preventers and water regulators.

    2. Thermostatic water mixing valves.

    1.6 QUALITY ASSURANCE

    A. Product Options: Drawings indicate size, profiles, and dimensional requirements of plumbing

    specialties and are based on the specific system indicated. Refer to Division 1 Section "Product

    Requirements."

    B. Plumbing specialties shall bear label, stamp, or other markings of specified testing agency.

    C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,

    Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for

    intended use.

    D. ASME Compliance: Comply with ASME B31.9, "Building Services Piping," for piping materials

    and installation.

    E. NSF Compliance:

    1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic

    domestic water piping components. Include marking "NSF-pw" on plastic potable-water

    piping and "NSF-dwv" on plastic drain, waste, and vent piping.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 3

    2. Comply with NSF 61, "Drinking Water System Components--Health Effects, Sections 1

    through 9," for potable domestic water plumbing specialties.

    1.7 EXTRA MATERIALS

    A. Furnish extra materials described below that match products installed and that are packaged with

    protective covering for storage and identified with labels describing contents.

    1. Water Filter Cartridges: Equal to 200 percent of amount installed for each type and size

    indicated.

    2. Operating Key Handles: Equal to 100 percent of amount installed for each key-operated

    hose bibb and hydrant installed.

    PART 2 - PRODUCTS

    2.1 MANUFACTURERS

    A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements

    apply for product selection:

    1. Available Manufacturers: Subject to compliance with requirements, manufacturers

    offering products that may be incorporated into the Work include, but are not limited to,

    the manufacturers specified.

    2.2 BACKFLOW PREVENTERS

    A. Manufacturers:

    1. Ames Co., Inc.

    2. B & K Industries, Inc.

    3. Cla-Val Co.

    4. CMB Industries, Inc.; Febco Backflow Preventers.

    5. Conbraco Industries, Inc.

    6. FLOMATIC Corp.

    7. IMI Cash Valve.

    8. Mueller Co.; Hersey Meters Div.

    9. Sparco, Inc.

    10. Watts Industries, Inc.; Water Products Div.

    11. Zurn Industries, Inc.; Wilkins Div.

    B. General: ASSE standard, backflow preventers.

    1. NPS 2 and Smaller: Bronze body with threaded ends.

    2. NPS 2-1/2 and Larger: Bronze, cast-iron, steel, or stainless-steel body with flanged ends.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 4

    a. Interior Lining: AWWA C550 or FDA-approved, epoxy coating for backflow

    preventers having cast-iron or steel body.

    3. Interior Components: Corrosion-resistant materials.

    4. Exterior Finish: Polished chrome plate if used in chrome-plated piping system.

    5. Strainer: On inlet, if indicated.

    C. Reduced-Pressure-Principle Backflow Preventers: ASSE 1013, suitable for continuous pressure

    application. Include outside screw and yoke gate valves on inlet and outlet, and strainer on inlet;

    test cocks; and pressure-differential relief valve with ASME A112.1.2 air-gap fitting located

    between two positive-seating check valves.

    1. Pressure Loss: 12 psig maximum, through middle 1/3 of flow range.

    D. Double-Check Backflow Prevention Assemblies: ASSE 1015, suitable for continuous pressure

    application. Include shutoff valves on inlet and outlet, and strainer on inlet; test cocks; and two

    positive-seating check valves.

    1. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range.

    E. Reduced-Pressure Detector Assembly Backflow Preventers: ASSE 1047, FM approved or UL

    listed, and suitable for continuous pressure application. Include outside screw and yoke gate

    valves on inlet and outlet, and strainer on inlet. Include test cocks; pressure-differential relief

    valve with ASME A112.1.2 air-gap fitting located between two positive-seating check valves;

    and bypass with displacement-type water meter, valves, and reduced-pressure backflow

    preventer.

    1. Pressure Loss: 12 psig (83 kPa) maximum, through middle 1/3 of flow range.

    F. Double-Check Detector Assembly Backflow Preventers: ASSE 1048, FM approved or UL listed,

    and suitable for continuous pressure application. Include outside screw and yoke gate valves on

    inlet and outlet, and strainer on inlet. Include test cocks; two positive-seating check valves; and

    bypass with displacement-type water meter, valves, and double-check backflow preventer.

    1. Pressure Loss: 5 psig (35 kPa) maximum, through middle 1/3 of flow range.

    2.3 STRAINERS

    A. Strainers: Y-pattern, unless otherwise indicated, and full size of connecting piping. Include

    ASTM A 666, Type 304, stainless-steel screens with 3/64-inch round perforations, unless

    otherwise indicated.

    1. Pressure Rating: 125-psig minimum steam working pressure, unless otherwise indicated.

    2. NPS 2 and Smaller: Bronze body, with female threaded ends.

    3. NPS 2-1/2 and Larger: Cast-iron body, with interior AWWA C550 or FDA-approved,

    epoxy coating and flanged ends.

    4. Y-Pattern Strainers: Screwed screen retainer with centered blowdown.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 5

    a. Drain: Factory- or field-installed, hose-end drain valve.

    2.4 DRAIN VALVES

    A. Hose-End Drain Valves: MSS SP-110, NPS 3/4 ball valve, rated for 400-psig minimum CWP.

    Include two-piece, copper-alloy body with standard port, chrome-plated brass ball, replaceable

    seats and seals, blowout-proof stem, and vinyl-covered steel handle.

    1. Inlet: Threaded or solder joint.

    2. Outlet: Short-threaded nipple with ASME B1.20.7, garden-hose threads and cap.

    B. Hose-End Drain Valve: MSS SP-80, gate valve, Class 125, ASTM B 62 bronze body, with

    NPS 3/4 threaded or solder-joint inlet and ASME B1.20.7, garden-hose threads on outlet and cap.

    Hose bibbs are prohibited for this application.

    C. Stop-and-Waste Drain Valves: MSS SP-110, ball valve, rated for 200-psig minimum CWP or

    MSS SP-80, Class 125, gate valve; ASTM B 62 bronze body, with NPS 1/8 side drain outlet and

    cap.

    2.5 MISCELLANEOUS PIPING SPECIALTIES

    A. Hose Bibbs: Bronze body with replaceable seat disc complying with ASME A112.18.1M for

    compression-type faucets. Include NPS 1/2 or NPS 3/4 (DN 15 or DN 20) threaded or solder-

    joint inlet, of design suitable for pressure of at least 125 psig (860 kPa); integral or field-installed,

    nonremovable, drainable hose-connection vacuum breaker; and garden-hose threads complying

    with ASME B1.20.7 on outlet.

    1. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated.

    2. Finish for Service Areas: Rough bronze.

    3. Finish for Finished Rooms: Chrome or nickel plated.

    4. Operation for Equipment Rooms: Wheel handle or operating key.

    5. Operation for Service Areas: Wheel handle.

    6. Operation for Finished Rooms: Wheel handle.

    7. Include operating key with each operating-key hose bibb.

    8. Include integral wall flange with each chrome- or nickel-plated hose bibb.

    B. Air Vents: Float type for automatic air venting.

    1. Bolted Construction: Bronze body with replaceable, corrosion-resistant metal float and

    stainless-steel mechanism and seat; threaded NPS 3/8 (DN 10) minimum inlet; 125-psig

    (860-kPa) minimum pressure rating at 140 deg F (60 deg C); and threaded vent outlet.

    2. Welded Construction: Stainless-steel body with corrosion-resistant metal float, stainless-

    steel mechanism and seat, threaded NPS 3/8 (DN 10) minimum inlet, 150-psig (1035-kPa)

    minimum pressure rating, and threaded vent outlet.

    C. Roof Flashing Assemblies: Manufactured assembly made of .060 spun Aluminum base with

    EPDM Cap. Made Weather tite with a grove & bead pressure seal, and lead flashing collar and

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 6

    skirt extending at least 6 inches (150 mm) from pipe with galvanized steel boot reinforcement,

    and counterflashing fitting.

    1. Available Manufacturers:

    2. Manufacturers:

    a. RPS Corporation

    b. Portals Plus

    D. Deep-Seal Traps: Cast-iron or bronze casting, with inlet and outlet matching connected piping

    and cleanout trap seal primer valve connection.

    1. NPS 2: 4-inch- minimum water seal.

    2. NPS 2-1/2 and Larger: 5-inch- minimum water seal.

    E. Stack Flashing Fittings: Counterflashing-type, cast-iron fitting, with bottom recess for

    terminating roof membrane, and with threaded or hub top for extending vent pipe.

    F. Vent Terminals: Commercially manufactured, shop- or field-fabricated, frost-proof assembly

    constructed of galvanized steel, copper, or lead-coated copper. Size to provide 1-inch (25-mm)

    enclosed air space between outside of pipe and inside of flashing collar extension, with

    counterflashing.

    2.6 SLEEVE PENETRATION SYSTEMS

    A. Available Manufacturers:

    B. Manufacturers:

    1. ProSet Systems, Inc.

    2. 3m Fire Protection Products

    C. Description: UL 1479, through-penetration firestop assembly consisting of sleeve and stack

    fitting with firestopping plug.

    1. Sleeve: Molded PVC plastic, of length to match slab thickness and with integral nailing

    flange on one end for installation in cast-in-place concrete slabs.

    2. Stack Fitting: ASTM A 48 (ASTM A 48M), gray-iron, hubless-pattern, wye-branch stack

    fitting with neoprene O-ring at base and gray-iron plug in thermal-release harness in

    branch. Include PVC protective cap for plug.

    a. Special Coating: Include corrosion-resistant interior coating on fittings for plastic

    chemical waste and vent stacks.

    2.7 FLASHING MATERIALS

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 7

    A. Lead Sheet: ASTM B 749, Type L51121, copper bearing, with the following minimum weights

    and thicknesses, unless otherwise indicated:

    1. General Use: 4-lb/sq. ft., 0.0625-inch thickness.

    2. Vent Pipe Flashing: 3-lb/sq. ft., 0.0469-inch thickness.

    3. Burning: 6-lb/sq. ft., 0.0938-inch thickness.

    B. Copper Sheet: ASTM B 152 (ASTM B 152M), of the following minimum weights and

    thicknesses, unless otherwise indicated:

    1. General Applications: 12 oz./sq. ft.

    2. Vent Pipe Flashing: 8 oz./sq. ft.

    C. Zinc-Coated Steel Sheet: ASTM A 653/A 653M, with 0.20 percent copper content and 0.04-inch

    minimum thickness, unless otherwise indicated. Include G90 hot-dip galvanized, mill-

    phosphatized finish for painting if indicated.

    D. Elastic Membrane Sheet: ASTM D 4068, flexible, chlorinated polyethylene, 40-mil minimum

    thickness.

    E. Fasteners: Metal compatible with material and substrate being fastened.

    F. Metal Accessories: Sheet metal strips, clamps, anchoring devices, and similar accessory units

    required for installation; matching or compatible with material being installed.

    G. Solder: ASTM B 32, lead-free alloy.

    H. Bituminous Coating: SSPC-Paint 12, solvent-type, bituminous mastic.

    PART 3 - EXECUTION

    3.1 INSTALLATION

    A. Refer to Division 23 for piping joining materials, joint construction, and basic installation

    requirements.

    B. Install backflow preventers in each water supply to mechanical equipment and systems and to

    other equipment and water systems that may be sources of contamination. Comply with

    authorities having jurisdiction.

    1. Locate backflow preventers in same room as connected equipment or system.

    2. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap

    fitting, fixed air-gap fitting, or equivalent positive pipe separation of at least two pipe

    diameters in drain piping and pipe to floor drain. Locate air-gap device attached to or under

    backflow preventer. Simple air breaks are not acceptable for this application.

    3. Do not install bypass piping around backflow preventers.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 8

    C. Install pressure regulators with inlet and outlet shutoff valves and balance valve bypass. Install

    pressure gages on inlet and outlet.

    D. Install strainers on supply side of each control valve, pressure regulator, and solenoid valve.

    E. Install cleanouts in aboveground piping and building drain piping according to the following,

    unless otherwise indicated:

    1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless

    larger cleanout is indicated.

    2. Locate at each change in direction of piping greater than 45 degrees.

    3. Locate at minimum intervals of 50 feet for piping NPS 4 and smaller and 100 feet for larger

    piping.

    4. Locate at base of each vertical soil and waste stack.

    F. Install cleanout deck plates with top flush with finished floor, for floor cleanouts for piping below

    floors.

    G. Install cleanout wall access covers, of types indicated, with frame and cover flush with finished

    wall, for cleanouts located in concealed piping.

    H. Install flashing flange and clamping device with each stack and cleanout passing through floors

    with waterproof membrane.

    I. Install vent flashing sleeves on stacks passing through roof. Secure over stack flashing according

    to manufacturer's written instructions.

    J. Install frost-proof vent caps on each vent pipe passing through roof. Maintain 1-inch (25-mm)

    clearance between vent pipe and roof substrate.

    K. Install floor drains at low points of surface areas to be drained. Set grates of drains flush with

    finished floor, unless otherwise indicated.

    1. Position floor drains for easy access and maintenance.

    2. Set floor drains below elevation of surrounding finished floor to allow floor drainage. Set

    with grates depressed according to the following drainage area radii:

    a. Radius, 30 Inches or Less: Equivalent to 1 percent slope, but not less than 1/4-inch

    total depression.

    b. Radius, 30 to 60 Inches: Equivalent to 1 percent slope.

    c. Radius, 60 Inches or Larger: Equivalent to 1 percent slope, but not greater than 1-

    inch total depression.

    3. Install floor-drain flashing collar or flange so no leakage occurs between drain and

    adjoining flooring. Maintain integrity of waterproof membranes where penetrated.

    4. Install individual traps for floor drains connected to sanitary building drain, unless

    otherwise indicated.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 9

    L. Install roof drains at low points of roof areas according to roof membrane manufacturer's written

    installation instructions.

    1. Install roof-drain flashing collar or flange so no leakage occurs between drain and adjoining

    roofing. Maintain integrity of waterproof membranes where penetrated.

    2. Position roof drains for easy access and maintenance.

    M. Fasten wall-hanging plumbing specialties securely to supports attached to building substrate if

    supports are specified and to building wall construction if no support is indicated.

    N. Fasten recessed-type plumbing specialties to reinforcement built into walls.

    O. Install wood-blocking reinforcement for wall-mounting and recessed-type plumbing specialties.

    P. Install individual shutoff valve in each water supply to plumbing specialties. Use ball, gate, or

    globe valve if specific valve is not indicated. Install shutoff valves in accessible locations. Refer

    to Division 23 Section "Valves" for general-duty ball, butterfly, check, gate, and globe valves.

    Q. Install air vents at piping high points. Include ball, gate, or globe valve in inlet and drain piping

    from outlet to floor drain.

    R. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is

    indicated.

    S. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and within

    cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding pipe

    fittings.

    3.2 CONNECTIONS

    A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate

    general arrangement of piping, fittings, and specialties.

    B. Install piping adjacent to equipment to allow service and maintenance.

    C. Connect plumbing specialties to piping specified in other Division 22 Sections.

    D. Ground equipment.

    E. Tighten electrical connectors and terminals according to manufacturer's published torque-

    tightening values. If manufacturer's torque values are not indicated, use those specified in

    UL 486A and UL 486B.

    F. Connect plumbing specialties and devices that require power according to Division 22 Sections.

    3.3 FLASHING INSTALLATION

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 10

    A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes are

    required. Join flashing according to the following if required:

    1. Lead Sheets: Burn joints of lead sheets 6-lb/sq. ft., 0.0938-inch thickness or thicker. Solder

    joints of lead sheets 4-lb/sq. ft., 0.0625-inch thickness or thinner.

    2. Copper Sheets: Solder joints of copper sheets.

    B. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in floors and

    roofs with waterproof membrane.

    1. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 10 inches, and

    skirt or flange extending at least 8 inches around pipe.

    2. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 8 inches around sleeve.

    3. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least 8 inches

    around specialty.

    C. Set flashing on floors and roofs in solid coating of bituminous cement.

    D. Secure flashing into sleeve and specialty clamping ring or device.

    E. Install flashing for piping passing through roofs with counterflashing or commercially made

    flashing fittings, according to Division 23.

    F. Extend flashing up vent pipe passing through roofs and turn down into pipe, or secure flashing

    into cast-iron sleeve having calking recess.

    G. Fabricate and install flashing and pans, sumps, and other drainage shapes.

    3.4 LABELING AND IDENTIFYING

    A. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign

    on or near each trap seal primer system.

    1. Text: Distinguish among multiple units, inform operator of operational requirements,

    indicate safety and emergency precautions, and warn of hazards and improper operations,

    in addition to identifying unit.

    2. Refer to Division 23 Section "Basic Mechanical Materials and Methods and “Mechanical

    Identification" for nameplates and signs.

    3.5 FIELD QUALITY CONTROL

    A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-

    assembled trap seal primer systems and grease recovery units and their installation, including

    piping and electrical connections. Report results in writing.

    1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until

    no leaks exist.

  • TBP18010

    The Baird Community Center

    Additions & Renovations 220500 - 11

    2. Operational Test: After electrical circuitry has been energized, start units to confirm proper

    motor rotation and unit operation. Remove malfunctioning units, replace with new units,

    and retest.

    3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and

    equipment.

    3.6 PROTECTION

    A. Protect drains during remainder of construction period to avoid clogging with dirt and debris and

    to prevent damage from traffic and construction work.

    B. Place plugs in ends of uncompleted piping at end of each day or when work stops.

    END OF SECTION 220500

  • Section 220518

    Escutcheons for Plumbing Piping

    TBP18010 220518

    The Baird Community Center

    Addition & Renovations

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. Section Includes:

    1. Escutcheons.

    2. Floor plates.

    1.3 ACTION SUBMITTALS

    A. Product Data: For each type of product indicated.

    PART 2 - PRODUCTS

    2.1 ESCUTCHEONS

    A. One-Piece, Cast-Brass Type: With polished, chrome-plated finish and setscrew fastener.

    B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with chrome-plated finish and

    spring-clip fasteners.

    C. One-Piece, Stamped-Steel Type: With chrome-plated finish and spring-clip fasteners

    D. Split-Casting Brass Type: With polished, chrome-plated finish and with concealed hinge and

    setscrew.

    E. Split-Plate, Stamped-Steel Type: With chrome-plated finish, concealed hinge, and spring-clip

    fasteners.

    2.2 FLOOR PLATES

    A. One-Piece Floor Plates: Cast-iron flange with holes for fasteners.

    B. Split-Casting Floor Plates: Cast brass with concealed hinge.

  • Section 220518

    Escutcheons for Plumbing Piping

    TBP18010 220518

    The Baird Community Center

    Addition & Renovations

    PART 3 - EXECUTION

    3.1 INSTALLATION

    A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors.

    B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of insulated piping and

    with OD that completely covers opening.

    1. Escutcheons for New Piping:

    a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.

    b. Chrome-Plated Piping: One-piece, cast-brass type with polished, chrome-plated

    finish.

    c. Insulated Piping: One-piece, stamped-steel t

    d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast-brass

    type with polished, chrome-plated finish.

    e. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, stamped-

    steel type

    f. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, cast-brass type

    with polished, chrome-plated finish.

    g. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, stamped-steel

    type

    h. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type with polished,

    finish.

    i. Bare Piping in Unfinished Service Spaces: One-piece, stamped-steel type

    j. Bare Piping in Equipment Rooms: One-piece, cast-brass] finish.

    k. Bare Piping in Equipment Rooms: One-piece, stamped-steel type

    2. Escutcheons for Existing Piping:

    a. Chrome-Plated Piping: Split-casting brass type with polished, chrome-plated finish.

    b. Insulated Piping: Split-plate, stamped-steel type with concealed hinge

    c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-casting

    d. Bare Piping in Unfinished Service Spaces: Split-casting brass type with polished,

    finish.

    C. Install floor plates for piping penetrations of equipment-room floors.

    D. Install floor plates with ID to closely fit around pipe, tube, and insulation of piping and with OD

    that completely covers opening

    1. New Piping: One-piece, floor-plate type.

    2. Existing Piping: Split-casting, floor-plate type.

  • Section 220518

    Escutcheons for Plumbing Piping

    TBP18010 220518

    The Baird Community Center

    Addition & Renovations

    3.2 FIELD QUALITY CONTROL

    A. Replace broken and damaged escutcheons and floor plates using new materials.

    END OF SECTION 220518

  • SECTION 220523.12

    BALL VALVES FOR PUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.12-1

    PART 1 - GENERAL

    1.1 RELATED DOCUMENTS

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. Section Includes:

    1. Brass ball valves.

    2. Bronze ball valves.

    3. Steel ball valves.

    4. Iron ball valves.

    1.3 DEFINITIONS

    A. CWP: Cold working pressure.

    1.4 ACTION SUBMITTALS

    A. Product Data: For each type of valve.

    1. Certification that products comply with NSF 61 and NSF 372.

    1.5 DELIVERY, STORAGE, AND HANDLING

    A. Prepare valves for shipping as follows:

    1. Protect internal parts against rust and corrosion.

    2. Protect threads, flange faces, and soldered ends.

    3. Set ball valves open to minimize exposure of functional surfaces.

    B. Use the following precautions during storage:

    1. Maintain valve end protection.

    2. Store valves indoors and maintain at higher-than-ambient-dew-point temperature. If

    outdoor storage is necessary, store valves off the ground in watertight enclosures.

    C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use operating

    handles or stems as lifting or rigging points.

  • SECTION 220523.12

    BALL VALVES FOR PUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.12-2

    PART 2 - PRODUCTS

    2.1 GENERAL REQUIREMENTS FOR VALVES

    A. Source Limitations for Valves: Obtain each type of valve from single source from single

    manufacturer.

    B. ASME Compliance:

    1. ASME B1.20.1 for threads for threaded end valves.

    2. ASME B16.1 for flanges on iron valves.

    3. ASME B16.5 for flanges on steel valves.

    4. ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design criteria.

    5. ASME B16.18 for solder-joint connections.

    6. ASME B31.9 for building services piping valves.

    C. NSF Compliance: NSF 61 for valve materials for potable-water service.

    D. Bronze valves shall be made with dezincification-resistant materials. Bronze valves made with

    copper alloy (brass) containing more than 15 percent zinc are not permitted.

    E. Valve Actuator Types:

    1. Gear Actuator: For quarter-turn valves NPS 4 and larger.

    2. Handlever: For quarter-turn valves smaller than NPS 4

    F. Valves in Insulated Piping:

    1. Include 2-inch stem extensions.

    2. Extended operating handles of nonthermal-conductive material and protective sleeves that

    allow operation of valves without breaking vapor seals or disturbing insulation.

    3. Memory stops that are fully adjustable after insulation is applied.

    2.2 BRASS BALL VALVES

    1. Manufacturers: Subject to compliance with requirements,

    2. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Apollo

    b. Milwakee

    3. Description:

    a. Standard: MSS SP-110.

    b. CWP Rating: 400 psig .

    c. Body Design: One piece.

    d. Body Material: Forged brass or bronze.

  • SECTION 220523.12

    BALL VALVES FOR PUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.12-3

    e. Ends: Threaded and soldered.

    f. Seats: PTFE.

    g. Stem: Brass or stainless steel.

    h. Ball: Chrome-plated brass or stainless steel.

    i. Port: Reduced.

    B. Two-Piece, Brass Ball Valves with Full Port and Brass Trim:

    1. Manufacturers: Subject to compliance with requirements,

    2. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Apollo

    b. Milwaukee

    3. Description:

    a. Standard: MSS SP-110.

    b. CWP Rating: 600 psig.

    c. Body Design: Two piece.

    d. Body Material: Forged brass.

    e. Ends: Threaded and soldered.

    f. Seats: PTFE.

    g. Stem: Brass.

    h. Ball: Chrome-plated brass.

    i. Port: Full.

    C. Two-Piece, Brass Ball Valves with Full Port and Stainless-Steel Trim:

    PART 3 - manufacturers listed or a comparable

    1. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Apollo

    b. Milwaukee

    2. Description:

    a. Standard: MSS SP-110.

    b. CWP Rating: 600 psig .

    c. Body Design: Two piece.

    d. Body Material: Forged brass.

    e. Ends: Threaded and soldered.

    f. Seats: PTFE.

    g. Stem: Stainless steel.

    h. Ball: Stainless steel, vented.

    i. Port: Full.

    B. Two-Piece, Brass Ball Valves with Regular Port and Brass Trim:

  • SECTION 220523.12

    BALL VALVES FOR PUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.12-4

    1. Manufacturers: Subject to compliance with requirements,

    2. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Apollo

    b. Milwaukee

    3. Description:

    a. Standard: MSS SP-110.

    b. CWP Rating: 600 psig .

    c. Body Design: Two piece.

    d. Body Material: Forged brass.

    e. Ends: Threaded and soldered.

    f. Seats: PTFE.

    g. Stem: Brass.

    h. Ball: Chrome-plated brass.

    i. Port: Regular.

    C. Two-Piece, Brass Ball Valves with Regular Port and Stainless-Steel Trim:

    1. Manufacturers: Subject to compliance with requirements,

    2. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Apollo

    b. Milwaukee

    3. Description:

    a. Standard: MSS SP-110.

    b. CWP Rating: 600 psig .

    c. Body Design: Two piece.

    d. Body Material: Brass or bronze.

    e. Ends: Threaded and soldered.

    f. Seats: PTFE.

    g. Stem:

    h. Stem: Stainless steel.

    i. Ball: Stainless steel, vented.

    EXECUTION

    3.2 EXAMINATION

    A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove

    special packing materials, such as blocks, used to prevent disc movement during shipping and

    handling.

  • SECTION 220523.12

    BALL VALVES FOR PUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.12-5

    B. Operate valves in positions from fully open to fully closed. Examine guides and seats made

    accessible by such operations.

    C. Examine threads on valve and mating pipe for form and cleanliness.

    D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper

    size, length, and material. Verify that gasket is of proper size, that its material composition is

    suitable for service, and that it is free from defects and damage.

    E. Do not attempt to repair defective valves; replace with new valves.

    3.3 VALVE INSTALLATION

    A. Install valves with unions or flanges at each piece of equipment arranged to allow service,

    maintenance, and equipment removal without system shutdown.

    B. Locate valves for easy access and provide separate support where necessary.

    C. Install valves in horizontal piping with stem at or above center of pipe.

    D. Install valves in position to allow full stem movement.

    E. Install valve tags. Comply with requirements in Section 220553 "Identification for Plumbing

    Piping and Equipment" for valve tags and schedules.

    3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

    A. If valves with specified CWP ratings are unavailable, the same types of valves with higher CWP

    tings may be substituted.

    B. Select valves with the following end connections:

    End of Section 220523.12

  • SECTION 22053.13

    BUTTERFLY VALVES FOR PLUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.13-1

    SECTION 220523.13 - BUTTERFLY VALVES FOR PLUMBING PIPING

    PART 1 - GENERAL

    1.1 RELATED DOCUMENT

    A. Drawings and general provisions of the Contract, including General and Supplementary

    Conditions and Division 01 Specification Sections, apply to this Section.

    1.2 SUMMARY

    A. Section Includes:

    1. Iron, single-flange butterfly valves.

    2. Iron, grooved-end butterfly valves.

    3. Chainwheels.

    1.3 DEFINITIONS

    A. CWP: Cold working pressure.

    B. EPDM: Ethylene propylene-diene terpolymer rubber.

    C. NBR: Acrylonitrile-butadiene, Buna-N, or nitrile rubber.

    1.4 ACTION SUBMITTALS

    A. Product Data: For each type of valve.

    1. Certification that products comply with NSF 61

    1.5 DELIVERY, STORAGE, AND HANDLING

    A. Prepare valves for shipping as follows:

    1. Protect internal parts against rust and corrosion.

    2. Protect threads, flange faces, grooves, and weld ends.

    3. Set butterfly valves closed or slightly open.

    B. Use the following precautions during storage:

    1. Maintain valve end protection.

    2. Store valves indoors and maintain at higher-than-ambient-dew-point temperature. If

    outdoor storage is necessary, store valves off the ground in watertight enclosures.

  • SECTION 22053.13

    BUTTERFLY VALVES FOR PLUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.13-2

    C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use

    handwheels or stems as lifting or rigging points.

    PART 2 - PRODUCTS

    2.1 GENERAL REQUIREMENTS FOR VALVES

    A. Source Limitations for Valves: Obtain each type of valve from single source from single

    manufacturer.

    B. ASME Compliance:

    1. ASME B16.1 for flanges on iron valves.

    2. ASME B16.5 for flanges on steel valves.

    3. ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design criteria.

    4. ASME B31.9 for building service piping valves.

    C. AWWA Compliance: Comply with AWWA C606 for grooved-end connections

    D. NSF Compliance: NSF 61 for valve materials for potable-water service.

    E. Valve Pressure-Temperature Ratings: Not less than indicated and as required for system pressures

    and temperatures.

    F. Valve Sizes: Same as upstream piping unless otherwise indicated.

    G. Valve Actuator Types:

    1. Gear Actuator: For valves NPS 8 and larger.

    2. Handlever: For valves NPS 6 and smaller.

    3. Chainwheel: Device for attachment to gear, handlever, or stem; of size and with chain for

    mounting height, according to "Valve Installation" Article.

    H. Valves in Insulated Piping: With 2-inch stem extensions.

    2.2 IRON, SINGLE-FLANGE BUTTERFLY VALVES

    1. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Milwaukee

    b. DeZurik

    2. Description:

    a. Standard: MSS SP-67, Type I.

    b. CWP Rating: 200 psig

    c. Body Design: Lug type; suitable for bidirectional dead-end service at rated pressure

    without use of downstream flange.

  • SECTION 22053.13

    BUTTERFLY VALVES FOR PLUMBING PIPING

    TBP18010

    The Baird Community Center

    Additions & Renovations 220523.13-3

    d. Body Material: ASTM A 126, cast iron or ASTM A 536, ductile iron.

    e. Seat: EPDM.

    f. Stem: One- or two-piece stainless steel.

    g. Disc: Aluminum bronze.

    B. Iron, Single-Flange Butterfly Valves with Ductile-Iron Disc:

    1. Manufacturers: Subject to compliance with requirements,

    2. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Milwaukee

    b. DeZurik

    3. Description:

    a. Standard: MSS SP-67, Type I.

    b. CWP Rating: 200 psig

    c. Body Design: Lug type; suitable for bidirectional dead-end service at rated pressure

    without use of downstream flange.

    d. Body Material: ASTM A 126, cast iron or ASTM A 536, ductile iron.

    e. Seat: EPDM

    f. Stem: One- or two-piece stainless steel.

    g. Disc: Nickel-plated or coated ductile iron.

    C. Iron, Single-Flange Butterfly Valves with Stainless-Steel Disc:

    1. Basis-of-Design Product: Subject to compliance with requirements, provide comparable

    product by one of the following:

    a. Milwaukee

    b. DeZurik

    2. Description:

    a. Standard: MSS SP-67, Type I.

    b. CWP R