27
2 THE ULT IMATE MCB 48 Technologically advanced range of MCB based distribution equipment Incorporates many unique features of benefit to all of our customers Satisfies the diverse requirements of the user, contractor, specifier, OEM and distributor Incorporates the revolutionary RCBO Distribution boards accept both MCBs to BSEN60898 & BS1361 HRC fuses Memshield 2 MCBs and ancillary devices can be DIN-rail mounted and connected with comb busbar Memshield 2 type A and type B distribution boards of equal width can be vertically stacked and interlinked to provide additional outgoing ways. SP HRC fuse carriers can be fitted to any Memshield 2 distribution board and incorporate an MEM BS1361 HRC fuse fitted plus facility for a spare fuse contained in the carrier. Memshield 2 devices are suitable for DIN-rail mounting and can be inter-connected with comb busbar. Memshield 2 MCBs are rated at 10kA Icn to BSEN60898 & BSEN60947-2. MCBs comply with Lloyds Register of Shipping. MCBs and RCCBs have positive contact indication. REVOLUTIONARY... The unique RCBO pod can be fitted to any SP or SPSN MCB offering hundreds of possible combinations of circuit and earth fault protection. A wide choice of incoming devices are available including direct connection, switch- disconnector, MCB, MCCB, RCCB or fused combination switch.Top or bottom cable entry.

THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

  • Upload
    doannga

  • View
    222

  • Download
    2

Embed Size (px)

Citation preview

Page 1: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

2

T H E U L T I M A T E M C B

48

■ Technologically advanced range of

MCB based distribution equipment

■ Incorporates many unique features

of benefit to all of our customers

■ Satisfies the diverse requirements of

the user, contractor, specifier, OEM

and distributor

■ Incorporates the revolutionary

RCBO

■ Distribution boards accept both

MCBs to BSEN60898 & BS1361

HRC fuses

■ Memshield 2 MCBs and ancillary

devices can be DIN-rail mounted and

connected with comb busbar

Memshield 2 type A and type B

distribution boards of equal width can be

vertically stacked and interlinked to

provide additional outgoing ways.

SP HRC fuse carriers can be fitted to

any Memshield 2 distribution board and

incorporate an MEM BS1361 HRC

fuse fitted plus facility for a spare fuse

contained in the carrier.

Memshield 2 devices are suitable

for DIN-rail mounting and can be

inter-connected with comb busbar.

Memshield 2 MCBs are rated at 10kA

Icn to BSEN60898 & BSEN60947-2.

MCBs comply with Lloyds Register of

Shipping. MCBs and RCCBs have

positive contact indication.REVOLUTIONARY...

The unique RCBO pod can be

fitted to any SP or SPSN MCB

offering hundreds of possible

combinations of circuit and

earth fault protection.

A wide choice of incoming

devices are available including

direct connection, switch-

disconnector, MCB, MCCB,

RCCB or fused combination

switch.Top or bottom cable entry.

Memshield 2 P47-91 1/8/02 10:01 Page 5

Page 2: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

49

D I S T R I B U T I O N S Y S T E M

11129

5

4

1613

10

8

36

7

2

1

15

14

9

6

5

4

2

1

8

7

11

3

12

10

THE FEATURE PACKED, REVOLUTIONARY MEMSHIELD 2 RCBO

1 Earth fault sensitivity pod can be fitted to any standard SP or SPSN

Memshield MCB

2 Unique revolutionary design means that an RCBO within a SP (18mm) module

can be achieved

3 SP configuration allows a far greater number of devices to be fitted in a

distribution board

4 Use of the standard Memshield 2 MCB means that there are hundreds of possible

RCBO combinations providing an incredible choice

5 Standard features of the MCB are retained but with the added flexibility of earth

fault protection

6 Memshield 2 RCBOs are suitable for use in any Memshield 2 distribution board

or ideally suited to OEM applications

7 Four choices of sensitivity to meet the requirements of any installation

8 Time delay versions available to allow correct function of any downstream

residual current devices

9 The Memshield 2 RCBO complies with BSEN61009

10 An RCBO can be ordered simply by selecting the most suitable MCB for an

application and then adding the appropriate sensitivity suffix

11 The all new British design developed using state-of-the-art CAD equipment gives

you the assurance of quality, safety and performance

12 Earth fault protection is maintained even if the neutral connection is lost

13 Version suitable for use on 110V 50/60Hz systems

THE FEATURE PACKED MEMSHIELD 2 MCB

1 Any SP or SPSN MCB can be factory or site fitted with an RCBO pod providing

hundreds of possible combinations allowing you even more flexibility

2 Magnetic Type characteristics to BSEN60898 B, C, D for wide choice

of applications

3 Foolproof positive contact indication gives you the assurance of isolation function

4 Breaking capacities of up to 10kA (BSEN60898) allow increased

installation opportunities

5 Five pole configurations (SP, SPSN, DP, TP, with FP) and 14 current ratings (1,

2, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A) for increased flexibility

6 Quality trip free mechanism prevents MCBs from being held ‘ON’

7 Optional padlock dolly for positive locking ‘ON’ or ‘OFF’

8 High performance current limiting design for safer installations

9 Optional screw and terminal shields for full shrouding of MCBs

10 All new ‘easy fit’ British design using state-of-the-art CAD equipment gives you

the assurance of quality, safety and performance

11 Generous, wire-in, wire-out, box type terminals for cables up to 25mm2, and fork

type comb busbar facilities on line and load side for OEM installations

12 Terminals clamp cable and fork type comb busbar simultaneously

13 Mounting on standard 35mm DIN-rail to BS5584/EN50 022 for individual and

OEM installations

14 Finger protected combination head screws to increase safety and allow

easier installation

15 Optional rear connectors to allow cables up to 50mm2 to be terminated where

space is limited

16 Thermally calibrated to 40ºC with 50ºC option to cover a wider range of

ambient temperatures

Memshield 2 P47-91 1/8/02 10:02 Page 6

Page 3: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

1 Easy fit, DIN-rail mounting, incoming devices simply slot

into place easing installation

2 HRC fuse modules can be fitted in place of outgoing MCBs

increasing flexibility

3 Attractive two-tone grey finish over rust protected steel

enclosure for lasting durability

4 Main earth stud allows earth to be terminated inside or

outside the enclosure

5 Type A distribution boards comply with BS5486:Pt 12 & 13

and BSEN60439-3; type B with BS5486:Pt 12 and

BSEN60439-3

6 Heavy guage removable gland plates are provided top and

bottom for ease of installation

7 Shrouded neutral bar for increased safety

8 Fully shrouded busbar for increased safety

9 Busbar design eliminates risk of ‘hot spots’

10 Earth and neutral bars can accommodate up to

25mm2

cables

11 Modular sizes and removable gland plates allow distribution

boards to be stacked vertically

12 Optional connecting kits can be used to electrically connect

two distribution boards together vertically. TPN boards can

also be linked horizontally (not shown)

13 Covers fit within enclosure dimensions allowing

adjacent mounting

50

M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM E M S H I E L D 2 F E A T U R E S A N D B E N E F I T S

4

1011

18

15

8

2

24

23

26

16

7

21

20

9

125

3

27

65

THE FEATURE PACKED MEMSHIELD 2 TYPE A SPN DISTRIBUTION BOARD

13

14

Memshield 2 P47-91 1/8/02 10:02 Page 7

Page 4: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

14 The door can be closed when MCBs are padlocked ‘ON’

or ‘OFF’ to increase safety (not shown)

15 Unique blanking modules can be used to blank off

unused outgoing ways. The blanking module is the

profile of an MCB, so that it shrouds the busbar stab as

well for increased safety

16 Generous cable space is provided. Space behind the pan

assembly, on type A boards, allows bottom entry/exit

of cables

17 Optional adjustable flush mounting kits provide the

solution even where the mounting surface is uneven;

non-adjustable on type A (not shown)

18 All distribution boards have dished keyhole mounting

slots for easy surface installation even when the

mounting surface is uneven

19 Optional busbar connecting blocks for type A boards

allow the installer to fit DIN-rail mounted control

devices onto the pan assembly providing protection and

control for additional flexibility with economy and

compact size (not shown)

20 Pan assembles are fully removable to ease installation

21 Neutral links can be removed

for testing purposes

22 An optional clean earth kit can

be site installed for computer

installations - standard on TPN

distribution boards (not shown)

23 The door, when locked, covers

all devices and front cover

screws to prevent unwanted

access (not shown)

24 Doors can be site fitted with

either door barrel lock kits or

padlocking kits. Padlocking

kits allow the user to

standardise on all padlocking

arrangements for an

installation (not shown)

25 All incomers (except direct

connection) have positive

contact indication

26 Distribution boards can be fitted

with a wide range of extension

boxes including glazed door

types so the user can easily

identify the status of the fitted

control devices (not shown)

27 Modern styling allows the

range to discreetly blend in

with both industrial and

commercial premises

28 Dual earth and neutral bars on TPN distribution boards

for ease of installation

29 TPN and TPSN incoming device options include a 125A

fuse combination switch to give a compact solution to

discrimination problems at high current levels

30 TPN incomer options allow the fitting of MCCBs from

16A up to 200A

31 Split load, dual tariff and double pole distribution

boards are available as standard

32 Double pole boards can be fitted with SPSN MCBs

and SPSN RCBOs

33 Top entry distribution boards available.

51

THE FEATURE PACKED MEMSHIELD 2 TYPE B TPN DISTRIBUTION BOARD

23 14

13

27

7

5

21125

4

2

3

266

1831

11

20915

8

2810

2930

24

Memshield 2 P47-91 1/8/02 10:02 Page 8

Page 5: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

52

M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D S P N T Y P E A A N D D P V E R S I O N S - T Y P E A F O R M A T

Standard SPN type A distribution boards are available in six

sizes with a choice of 2, 4, 7, 10, 13, or 16 outgoing ways. DP

versions of type A distribution boards are also available having

5 or 8 DP outgoing ways. A wide range of incomers can be

fitted to allow for the flexibility needed in modern installations.

Split load and dual tariff SPN type A distribution boards are

available with up to 19 outgoing ways.

They comply fully with BS5486:Pt 12 & 13 and BSEN60439-3.

INCOMING DEVICES

100A lugs; 100A SPSN switch-disconnector; 100A SPSN

RCCB. For full range of SPSN RCCBs suitable for use as

incoming devices see page 65.

Please consult our Technical Services department for details of

an even wider choice of incoming devices.

OUTGOING DEVICES

For type A distribution boards: 1-63A Memshield 2 SP MCBs.

Types B, C, D, 10kA to BSEN60898; 5-45A fuse carriers,

16kA to BS1361; 1-63A 18mm SP RCBOs

For double pole distribution boards: 1-63A Memshield 2 SPSN

or DP MCBs. Types B, C, D, 10kA to BSEN60898; 1-63A

36mm SPSN RCBOs.

FEATURES

Distribution boards of equal width can be stacked vertically

without any other accessories. They can be electrically

connected to give more outgoing ways by using a connector kit

(see page 60).

Memshield modular control devices can be fitted by using a

busbar block kit to adapt the busbar (see page 60). AM13,

AMSL64/37 and AMDT74 distribution boards can be mounted

on top of any type B distribution board. A clean earth kit can

be used for computer installations (see page 60).

DOUBLE POLE DISTRIBUTION BOARDS

Memshield 2 double pole distribution boards have been

developed for specialist applications.

They allow for single pole and switched neutral MCBs to be

fitted on all outgoing circuits which is necessary for the control

of circuits situated in hazardous areas.

SPSN or DP MCBs and SPSN RCBOs can be fitted.

For 3 phase, 4 wire systems please contact us for details of our

four pole range of Memshield 2 distribution boards.

A-SELECT DISTRIBUTION BOARD:

DESCRIPTION LIST NO.

2 way SPN type A AM2

4 way SPN type A AM4

7 way SPN type A AM7

10 way SPN type A AM10

13 way SPN type A AM13

16 way SPN type A AM16

5 way DP type A format AM5D

8 way DP type A format AM8D

B-SELECT 100A INCOMING DEVICE:

Incoming device supplied separately to distribution board.

DESCRIPTION LIST NO.

SPSN switch-disconnector (isolator) MS1001N

DP lugs (direct connection) MBT1002

SPSN 30mA RCCB AM100HE

SPSN 100mA RCCB AM100ME

SPSN 300mA RCCB AM100LE

SPSN 100mA time delayed RCCB AM100MET

SPSN 300mA time delayed RCCB AM100LET

C-EXAMPLE:

AM4 + MS1001N = 4 way SPN distribution board with 100A

switch-disconnector.

Use pages 61-64 to select outgoing devices and accessories.

Memshield 2 P47-91 1/8/02 10:02 Page 9

Page 6: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A

SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.

DESCRIPTION LIST NO.

10 way; 4 ways RCCB protected AMSL64

10 way; 7 ways RCCB protected AMSL37

13 way; 4 ways RCCB protected AMSL94

13 way; 7 ways RCCB protected AMSL67

13 way; 10 ways RCCB protected AMSL310

19 way; 10 ways RCCB protected AMSL910

N.B. AMSL910 = 2 row unit

DUAL TARIFF DISTRIBUTION BOARDS FITTED WITH 2

INCOMING SWITCH-DISCONNECTORS*

DESCRIPTION LIST NO.

7 + 4 way AMDT74

10 + 4 way AMDT104

7 + 7 way AMDT77

*Please consult our Technical Services department for other incomer

types, or configurations.

Example:

AMSL37 = 10 way SPN distribution board with main 100A switch

disconnector, and 7 RCCB protected ways.

CABLE CAPACITIES mm2

LUGS 50

SWITCH-DISCONNECTOR 50

RCCB 50

MCBs 25

EARTH BARS 25

NEUTRAL BARS 25

53

S P L I T L O A D & D U A L T A R I F F S P N T Y P E A

■ Clean earth kit available for all type Adistribution boards.

■ Any number of type A distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.

■ Consult us for even more incomer options.

■ Modular control/command devices can befitted into any SPN type A distributionboard by using the unique busbar block kit.See page 60 for details.

Memshield 2 P47-91 1/8/02 10:03 Page 10

Page 7: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

54

M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D 1 2 5 A T P N T Y P E B

A - SELECT 125A DISTRIBUTION BOARD:

DESCRIPTION LIST NO.

4 way TPN type B BM41

6 way TPN type B BM61

8 way TPN type B BM81

12 way TPN type B BM121

16 way TPN type B BM161

24 way TPN type B BM242

B - SELECT 100/125A INCOMING DEVICE:

Incoming device supplied separately to distribution board.

DESCRIPTION LIST NO.

100A TP switch-disconnector (isolator) BMS1003

100A SPSN switch-disconnector (isolator) BMS1001N4*

125A TP switch-disconnector (isolator) BMS1253

100A TPSN switch-disconnector (isolator) BMS1004

100A TP lugs (direct connection) BMBT1003

100A TPSN 30mA RCCB BMR30

100A TPSN 100mA RCCB BMR100**

100A TPSN 300mA RCCB BMR300

100A TPSN 300mA RCCB BMR300Twith time delay

63A TP Type C MCB BMCH363

100A TP switch-disconnector BMCC1003feeding 100A TP AC1 contactor c/w

control circuit fuse & terminal block,

housed in extension box.

Top entry distribution boards with factory fitted 125A TP switch-

disconnector- add suffix T125 to list no. e.g. BM41T125.Not applicable to 24 way board; BM242.

*TPN to SPN conversion kit included.

**Not suitable for BM242.

C - EXAMPLE:

BM61 + BMS1003 = 6 way TPN distribution board with 100A

switch-disconnector.

Use pages 61 - 64 to select outgoing devices & accessories.

Standard 125A and 200A TPN type B distribution boards are

available with a choice of 4, 6, 8, 12, 16 or 24 outgoing ways.

A wide range of incomers can be fitted to allow for the

flexibility needed in modern installations. They comply fully

with BS5486 : Pt 12 and BSEN60439-3.

INCOMING DEVICES, 125A MAX

100A lugs; 100A SPSN, TP, or TPSN switch-disconnectors,

125A TP switch-disconnectors, 100A TPSN RCCBs; 63A TP

MCB. Please consult our Technical Services department for

details of other incoming device types.

INCOMING DEVICES, 200A

200A lugs; 200A SPSN, or TP switch-disconnectors; and any

TP ‘F’ frame MCCB up to 200A. All standard 100A

distribution board incomers can also be fitted.

OUTGOING DEVICES

1-63A Memshield 2 SP, DP and TP MCBs Types B, C, D, 10kA

to BSEN60898; 5-45A fuse carriers, 16kA to BS1361; 1-

63A SP 18mm RCBOs.

FEATURES

Distribution boards of equal width can be stacked vertically

without any other accessories. They can be electrically

connected vertically or horizontally to give more outgoing ways

by using a connector kit (see page 60). Memshield modular

control devices can be fitted by using an extension box (see

page 60). Many SPN type A distribution boards can be

mounted on top of any type B distribution board.

A clean earth facility is standard for computer installations.

Memshield 2 P47-91 1/8/02 10:03 Page 11

Page 8: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

55

S T A N D A R D 2 0 0 A T P N T Y P E B

■ Two type B distribution boards can bepositioned side by side and electricallyinter-connected with a connector kit.

■ Any number of type B distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.

■ Clean earth facility standard within alltype B distribution boards.

■ Any TPN (type B) distribution board can

be simply converted to SPN by fitting

a conversion kit and SPSN switch-

disconnector incoming device.

■ Consult us for even more incoming options.

A - SELECT 200A DISTRIBUTION BOARD:

DESCRIPTION LIST NO.

4 way TPN type B BM42

6 way TPN type B BM62

8 way TPN type B BM82

12 way TPN type B BM122

16 way TPN type B BM162

24 way TPN type B BM242

B - SELECT INCOMING DEVICE UP TO 200A:

Incoming device supplied separately to distribution board. 200A

switch-disconnector and MCCB incoming devices are supplied with

cable entry boxes. (100A incomers from page 54 can also be used).

DESCRIPTION LIST NO.

200A TP switch-disconnector (isolator) BMS2003†

160A TP switch-disconnector (isolator) BMS1603

200A SPSN switch-disconnector (isolator) BMS2001N*

TP kit for ‘F’ frame MCCB** BMIK2003†

TP lugs (direct connection) BMBT2003

Top entry distribution boards with factory fitted 160A TP switch -

disconnector - Add suffix T160 to list no. e.g. BM42T160.Not applicable to 24 way board BM242.

*Not suitable for BM242. TPN to SPN conversion kit included.

**Select ‘F’ frame MCCB for use with BMIK2003 from following table.

† Add suffix ‘P’ when these are to be fitted to BM242.

F FRAME MCCBS

DESCRIPTION Icu Ics LIST NO.

TP 100A 25kA 100% MFL1003

TP 125A 25kA 100% MFL1253

TP 160A 25kA 100% MFL1603

TP 200A 25kA 100% MFL2003

CABLE CAPACITIES mm2

LUGS (100A) 50

SWITCH-DISCONNECTOR (100A) 50

RCCB 50

LUGS (200A) 120

SWITCH-DISCONNECTOR (125A & 160A) 70

SWITCH-DISCONNECTOR (200A) 120

MCCB (‘F’ Frame type) 120

MCBs 25

EARTH BARS 25

NEUTRAL BARS 25

Memshield 2 P47-91 1/8/02 10:03 Page 12

Page 9: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

56

M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF C S I N C O M E R S T P N T Y P E B , D P V E R S I O N S - T Y P E B F O R M A T

FUSED COMBINATION SWITCH INCOMERS

TPN type B distribution boards are also available with a choice of

fitted TP or TPSN FCS incomers. The FCS incomer uses MEM BS88

fuses, which allow the unit to be fused from 2-125A. This is a benefit

for applications where the load may increase in the future, as the FCS

can be re-fused accordingly.

The exclusive use of MEM fuselinks in this equipment will extend thewarranty period to 3 years.

These distribution boards comply fully with BS5486 : Pt 12 and

BSEN60439-3.

125A TP DISTRIBUTION BOARDS WITH FITTED FUSE

COMBINATION SWITCH INCOMERS.

DESCRIPTION INCOMER LIST NO.

4 way TPN type B TP FCS BMFCS4

6 way TPN type B TP FCS BMFCS6

8 way TPN type B TP FCS BMFCS8

12 way TPN type B TP FCS BMFCS12

16 way TPN type B TP FCS BMFCS16

4 way TPN type B TPSN FCS BMFCSN4

6 way TPN type B TPSN FCS BMFCSN6

8 way TPN type B TPSN FCS BMFCSN8

12 way TPN type B TPSN FCS BMFCSN12

16 way TPN type B TPSN FCS BMFCSN16

N.B. All distribution boards with FCS type incomer are supplied with

125A fuses.

DOUBLE POLE DISTRIBUTION BOARDS

Memshield 2 double pole distribution boards have been developed for

specialist applications.

Double pole distribution boards have a single pole and switched neutral

incoming circuit. They allow for single pole and switched neutral

MCBs to be fitted on all outgoing circuits which is necessary for the

control of circuits situated in hazardous areas.

SPSN or DP MCBs and SPSN RCBOs can be fitted.

For 3 phase, 4 wire systems please contact us for details of our four

pole range of Memshield 2 distribution boards.

DP DISTRIBUTION BOARDS TYPE B FORMAT WITH FITTED

100A SPSN MAIN SWITCH-DISCONNECTOR.

DESCRIPTION LIST NO.

6 way DP (5 way SPSN) type B format BM61D

12 way DP (11 way SPSN) type B format BM121D

18 way DP (17 way SPSN) type B format BM181D

24 way DP (23 way SPSN) type B format BM241D

Memshield 2 P47-91 1/8/02 10:03 Page 13

Page 10: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

SPLIT LOAD BOARDS

Split load TPN type B distribution boards are factory fitted with a

main 100A switch-disconnector and a 30mA RCCB. Please consult

our Technical Services department for details of other incoming

device options.

MODULAR ENCLOSURES

Memshield 2 modular enclosures can be used to house Memshield

2 protective and command devices. Enclosures are available to

house from 2 to 45 x 18mm modules in moulded or metal

construction up to IP55.

Up to three Memshield 2 type A pan assemblies can be fitted into

an enclosure.

To select a suitable enclosure, select the devices required and

calculate the amount of 18mm modules required, then select the

enclosure that can accommodate at least that many 18mm modules.

BMX 15 module enclosures can be mounted onto AM13 or any

Memshield 2 TPN distribution board. Distribution board accessories

e.g. door lock kit are suitable for use with BMX type enclosures.

BMXDC enclosures are fitted with earth and neutral bars as

standard. Additional earth and neutral bars for 30 and 45 way

enclosures are available for specific applications.

Metal enclosures will accommodate all modular devices, ie;

MCBs, RCCBs, RCBOs, fuse modules and command devices.

Moulded enclosures 4/6 QEL, 4EME and AM1SL will not

accept RCBOs.

4EME will accept command devices and TPSN RCCBs only.

CABLE EXTENSION BOXES

Cable extension boxes are for use with larger cables or for special

applications e.g. metering, etc. They can be fitted top and/or

bottom. All 200A type incomers include a cable extension box

where necessary.

All enclosures and extension boxes can be fitted top and/or bottom

of distribution boards in any quantity.

100A SPLIT LOAD DISTRIBUTION BOARDS WITH FITTED

100A MAIN SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.

DESCRIPTION LIST NO.12 way; 8 ways RCCB protected BMSL4812 way; 6 ways RCCB protected BMSL6612 way; 4 ways RCCB protected BMSL8416 way; 8 ways RCCB protected BMSL88

MEMSHIELD 2 ENCLOSURES - FOR MODULAR DEVICES

EARTH CAPACITYWITH DOOR TERMINAL IP RATING IN 18MM LIST NO.

PROVIDED MODULES

MOULDED ENCLOSURESNo yes IP30 2 AM1SLNo yes IP30 4 4EMEYes yes IP55 4 4QELYes yes IP55 6 6QEL

METAL ENCLOSURESYes yes IP4X 4 BMXDC4Yes yes IP4X 6 BMXDC6Yes yes IP4X 9 BMXDC9Yes yes IP4X 15 BMXDC15Yes yes IP4X 18 BMXDC18Yes yes IP4X 30 BMXDC30Yes yes IP4X 45 BMXDC45

Yes-glazed yes IP4X 6 BMXDCG6Yes-glazed yes IP4X 9 BMXDCG9Yes-glazed yes IP4X 15 BMXDCG15Yes-glazed yes IP4X 18 BMXDCG18Yes-glazed yes IP4X 30 BMXDCG30Yes-glazed yes IP4X 45 BMXDCG45

N.B. AM1SL, 4QEL, 6QEL, can be wire sealed.

ENCLOSURE ACCESSORIES

DESCRIPTION LIST NO.Blanking module for unused MBPways-metal enclosures

Additional earth bar for 30 & 45 BMXE15way BMXDC enclosures

Additional neutral bar for 30 & 45 BMXN15way BMXDC enclosures

Door barrel lock for 4, 6, 9, 15 way AMDLBMXDC enclosures

Door barrel lock for 30 & 45 way BMDLBMXDC enclosures

Padlocking kit for 4, 6, 9, 15 way AMPLBMXDC enclosures

Padlocking kit for 30 & 45 way BMPLBMXDC enclosures

Padlock for AMPL/BMPL PD1EXTENSION BOXES FOR TPN AND AM13 DISTRIBUTION BOARDS.

DESCRIPTION LIST NO.Cable spreader extension box, 162mm high BMXPC1Cable spreader extension box, 250mm high BMXPC2

57

S P L I T L O A D B O A R D S , E X T E N S I O N B O X E S A N D M O D U L A R E N C L O S U R E S

Memshield 2 P47-91 1/8/02 10:03 Page 14

Page 11: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

58

M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF L U S H M O U N T I N G K I T S & P A N A S S E M B L I E S

FLUSH KITS

Type A and type B distribution boards are suitable for flush mounting

applications by using the appropriate kit except 24 way TPN.

FEATURES

Memshield 2 type B flush mounting kits can be adjusted to

accommodate slightly uneven mounting surfaces.

Please contact our Technical Services department for other

flush mounting possibilities.

MEMSHIELD 2 FLUSH MOUNTING KITS

DISTRIBUTION BOARD TYPE LIST NO.

AM4, BMXDC6, BMXDCG6 AMFK4

AM7, BMXDC9, BMXDCG9 AMFK7

AM10, AM5D AMFK10

AM13, AMSL37, AMSL64, AMDT74, AMFK13BMXDC15, BMXDCG15

AM8D, AM16, AMDT77, AMDT104, AMFK16AMSL67, AMSL94, AMSL310

BM41, BM61D BMFK1

BM61, BM42 BMFK2

BM81, BM62, BM121D BMFK3

BM82 BMFK4

BM121, BM122, BM181D, BMFK5BMXDC45, BMXDCG45

BM161, BM162, BM241D BMFK6

BMSL48, BMSL66, BMSL84 BMFK7

BM42* BMFK21

BM62* BMFK22

BM82* BMFK23

BM122* BMFK24

BM162* BMFK25

*When fitted with BMIK2003, BMS2003, BMS2001N,or BMXPC1

PAN ASSEMBLIES

Memshield pan assemblies offer a high degree of flexibility for

custom applications.

SPN types are available with 4, 7, 10, 13, and 16 ways. DP types

with 5, 6, 8, 12, 18 and 24 ways. TPN types with 4, 6, 8, 12,16

and 24 TP ways.

Where the switching of outgoing neutrals on 3 phase pan

assemblies is required, eg: for switching circuits in hazardous

areas, please contact us.

Refer to pages 52, 54 and 55 for incoming devices.

Add suffix ‘P’ to incomer kits BMS2001N, BMS2003 and

BMIK2003 to order kit without cable box.

Refer to pages 61 and 68 for outgoing devices.

FEATURES

Memshield 2 pan assemblies are suitable for inclusion in other

factory built assemblies and as replacements for distribution board

interiors. Pan assemblies feature fully shrouded busbars. The

busbars can be connected by using a busbar connector kit. SPN

distribution boards can be adapted to take modular control devices

using a busbar kit to adapt the busbar, see page 60.

Please contact our Technical Services department for other pan

assembly types.

MEMSHIELD 2 PAN ASSEMBLIES (INTERIORS)

DESCRIPTION LIST NO.

100A 4 way SPN without incomer AMP4

100A 7 way SPN without incomer AMP7

100A 10 way SPN without incomer AMP10

100A 13 way SPN without incomer AMP13

100A 16 way SPN without incomer AMP16

100A 5 way DP without incomer AMP5D

100A 8 way DP without incomer AMP8D

200A 6 way DP main lugs fitted BMP61D

200A 12 way DP main lugs fitted BMP121D

200A 18 way DP main lugs fitted BMP181D

200A 24 way DP main lugs fitted BMP241D

125A 4 way TPN without incomer BMP41

125A 6 way TPN without incomer BMP61

125A 8 way TPN without incomer BMP81

200A 4 way TPN without incomer BMP42

200A 6 way TPN without incomer BMP62

200A 8 way TPN without incomer BMP82

200A 12 way TPN without incomer BMP122

200A 16 way TPN without incomer BMP162

200A 24 way TPN main lugs fitted BMP242L

MEMSHIELD 2 PAN ASSEMBLIES (WITHOUT EARTH AND

NEUTRAL BARS)

DESCRIPTION LIST NO.

200A 4 way TPN main lugs fitted BMPS42

200A 6 way TPN main lugs fitted BMPS62

200A 8 way TPN main lugs fitted BMPS82

200A 12 way TPN main lugs fitted BMPS122

200A 16 way TPN main lugs fitted BMPS162

200A 24 way TPN main lugs fitted BMP242LWEN

Memshield 2 P47-91 1/8/02 10:03 Page 15

Page 12: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

59

M E M S H I E L D 2 T V S S R A N G E

The MEMSHIELD 2 Surge Protective Device has been developed

specifically for application with Memshield 2 ‘A’ Type and ‘B’ Type

single and three phase MCB distribution boards, ensuring outstanding

product performance for all sensitive, mission critical and general

purpose loads. The UL1449 Second Edition and UL1283 listed devices

provide high peak surge current ratings and exceptionally low real-

world measured limiting (let-through) voltage values, together with

outstanding durability, assuring the Memshield 2 range will provide a

lifetime of effective, maintenance free protection for all electrical and

electronic systems.

PROTECTION:Active Response Network (ARN) provides optimum suppression of

internal switching generated transients.

Threshold Response Network (TRN) provides maximum suppression

of high energy impulse generated transients.

This assures excellent protection of sensitive electronic, electro-

mechanical and micro-processor based equipment.

GENERAL SPECIFICATIONS:

DESCRIPTION: Parallel configured, hard wire connected, 80kA

per phase peak surge current Transient Voltage

Surge Suppressor.

APPLICATION: Location Categories B and A, medium and low

exposure level. General purpose, sensitive, and

mission critical loads. Small AC power service

entrances (≤ 200amps), sub and final circuit

Memshield 2 MCB distribution boards.

WARRANTY: 10-Year Free Replacement.

UNIT LISTINGS: UL1449 Second Edition, UL1283 Filter.

QUALITY: ISO 9001: 1994 Quality System Certification

BSI FM 30833.

MECHANICAL SPECIFICATIONS:

TVSS ENCLOSURE: IP23 rated steel enclosure.

MOUNTING: Conduit fitting and multi-point mounting feet.

CONNECTION: Standard products include approx. 450mm factory

fitted stranded cable #10 AWG (≈ 6mm2). Flush

mounting plate available, order list number ZPLATE-4

SHIPPING WEIGHT: 2.2kg.

TVSS MODULESEach TVSS module is supplied complete with the following:

■ TVSS unit as detailed above

■ 32A Type C MCB; SP for Type A (SPN) and TP for Type B

(TPN) distribution boards

■ Fittings to attach TVSS unit to distribution board

■ Full instructions

TVSS MODULE KIT LIST NO.

For Type A (SPN) distribution boards M2SSK1

For Type B (TPN) distribution boards M2SSK3

For full details of TVSS products refer to the Transient Voltage

Surge Suppression catalogue available on request.

Memshield 2 P47-91 1/8/02 10:04 Page 16

Page 13: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

UNIQUE BUSBAR BLOCK KIT

Memshield 2 type A SPN distribution boardsoffer the installer unique flexibility.

By using a busbar block kit a standard type Adistribution board can be adapted on site to accept Memshield 2 DIN-rail mounting control devices as well as MCBs. The kit includes ashorter busbar, to replace the standard busbar, which simply clips tothe pan assembly, plus a mounting rail for the control devices.

Use of a busbar block kit can mean that a conventional extension boxfor control devices is unnecessary - saving the installer time and spaceas well as providing the user with a neater more compact installation.

The number of ways indicated in the table are for outgoing MCBs,remaining ways in the distribution board can be fitted with control devices.

Eg:- 10 way type A board = AM10, fitted with MMBK4 willaccommodate 4 x SP MCBs plus up to 6 x SP control devices.

BUSBAR BLOCK KIT LIST NO.

4 way SP busbar block MMBK4

7 way SP busbar block MMBK7

10 way SP busbar block MMBK10

13 way SP busbar block MMBK13

60

M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SA C C E S S O R I E S

DISTRIBUTION TOTAL TOTAL TOTALBOARD LIST NO. NUMBER OF EARTH NUMBER OF EARTH NUMBER OF EARTH

TERMINALS FITTED TERMINALS IF TERMINALS IFAS STANDARD 2 OFF BMNE8 ADDED 2 OFF BMNE16 ADDED

BM41 16 28 N/ABM42 16 28 52

BM61 22 28 N/A

BM62 22 28 52

BM81 28 N/A N/A

BM82 28 N/A 52

BM121 40 N/A N/A

BM122 40 N/A 52

BM161 52 N/A N/A

BM162 52 N/A N/A

*Incoming device required for each linked distribution board.

†100A vertical kits can be uprated to 200A in order to connect 2 x 200A distribution boards by replacing suppliedcable with cable of appropriate rating.

DESCRIPTION LIST NO.Blanking module for unused way MBPBlanking module for half unused way when MCB auxiliary alarm contacts used MABP500 ml aerosol of light grey paint 2APDoor barrel lock for SPN distribution boards AMDLDoor padlocking kit for SPN distribution boards AMPLCoupling kit for 2 SPN distribution boards (vertical)* AMCKClean earth kit for SPN distribution boards 5 terminal AME5Clean earth kit for SPN distribution boards 11 terminal AME11Gland plate for AM4 MGP1Gland plate for AM7 MGP2Gland plate for AM10 MGP3Gland plate for AM13 MGP4Gland plate for AM16 MGP5IP42 gland plate for AM4, BMXDC6, BMXDCG6 MGP142IP42 gland plate for AM7, BMXDC9, BMXDCG9 MGP242IP42 gland plate for AM10 MGP342IP42 gland plate for AM13, BMXDC15, BMXDCG15 MGP442IP43 gland plate for BMXDC30/45, BMXDCG30/45 and all type B distribution boards except 24 way TPN

MGP442

IP42 gland plate for AM16 MGP542Door barrel lock for TPN distribution boards BMDLDoor padlocking kit for TPN distribution boards BMPL100A coupling kit for 2 TPN distribution boards (vertical)*†.Not suitable for BM242

BMCKV

125A coupling kit for 2 TPN distribution boards (horizontal). Not suitable for BM242

BMCKH

SPN conversion kit for TPN distribution boards BMSPNIP4X gland plate for all TPN distribution boards BMGP4Padlock for SPN and TPN distribution board padlock kits PD1

ADDITIONAL EARTH TERMINALS

Type B, TPN distribution boards aresupplied as standard with the number ofearth terminals shown in the table.

If required this can be increased byadditional earth bars List No. BMNE8 orBMNE16 - see table:

GENERAL ACCESSORIES

Distribution boards have front mounting

screws behind the door so that the cover cannot

be removed when the door is locked with a door

barrel lock or door padlocking kit providing a

high degree of security.

Keys for AMDL and BMDL are common

and will fit all.

Gland plates are available to increaseenclosure protection to IP42 on 4, 7, 10 &16 way A type enclosures; IP43 on all Btype enclosures except 24 way TPN.

Please contact our Technical Servicesdepartment for details of gland plateswithout knock-outs.

Memshield 2 P47-91 31/7/02 16:12 Page 17

Page 14: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SM I N I A T U R E C I R C U I T B R E A K E R S - T Y P E B & C 1 0 K A

61

The Memshield 2 MCB is an all new high performance

current limiting device with the ability to disconnect short

circuits of up to 10kA.

The feature packed device is both British designed and

manufactured, using the latest technology.

Memshield 2 miniature circuit breakers are available in one

of the widest ranges available in the world; over 600

different types are available.

The MCBs are suitable for use with Memshield 2 distribution

boards. In addition MCBs are suitable for a wide range of

OEM applications.

Current ratings are available in 1, 2, 4, 6, 8, 10, 13, 16, 20,

25, 32, 40, 50, and 63A. The range is available with types

B, C, and D, in single pole (SP), single pole and switched

neutral (SPSN), double pole (DP), triple pole (TP) and four

pole (FP) configurations.

On SPSN the switched neutral is unprotected, on DP and FP

all poles are protected.

SPSN MCBs are fitted with neutral contacts which make first

and break last.

FEATURES

Memshield 2 MCBs are available with a breaking capacity of

10kA to BSEN60898 & BSEN60947-2.

They are suitable for use on DC systems from 24V to 120V;

fault level at 24V = 6kA; 120V = 4kA.

NOTE: When a residual current pod is added to the MCB (see

P63) to form an RCBO, the combination is suitable for use on

240v AC systems, it cannot be used on DC systems.

The MCBs are calibrated to 40ºC.

MCBs can be supplied with 50ºC ambient calibration. To order

insert ‘X’ at the end of the MCB list number eg:- MCH 116X.Please contact our Technical Services department for details

of Memshield 2 MCBs suitable for other reference

calibration temperatures.

MEMSHIELD 2 MCBS - TYPE B TO BSEN60898 (IEC898), 3 TO

5 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP

1 MBH101 MBH101N MBH201 MBH301 MBH401

2 MBH102 MBH102N MBH202 MBH302 MBH402

4 MBH104 MBH104N MBH204 MBH304 MBH404

6 MBH106 MBH106N MBH206 MBH306 MBH406

8 MBH108 MBH108N MBH208 MBH308 MBH408

10 MBH110 MBH110N MBH210 MBH310 MBH410

13 MBH113 MBH113N MBH213 MBH313 MBH413

16 MBH116 MBH116N MBH216 MBH316 MBH416

20 MBH120 MBH120N MBH220 MBH320 MBH420

25 MBH125 MBH125N MBH225 MBH325 MBH425

32 MBH132 MBH132N MBH232 MBH332 MBH432

40 MBH140 MBH140N MBH240 MBH340 MBH440

50 MBH150 MBH150N MBH250 MBH350 MBH450

63 MBH163 MBH163N MBH263 MBH363 MBH463

MEMSHIELD 2 MCBS - TYPE C TO BSEN60898 (IEC898), 5 TO

10 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP1 MCH101 MCH101N MCH201 MCH301 MCH401

2 MCH102 MCH102N MCH202 MCH302 MCH402

4 MCH104 MCH104N MCH204 MCH304 MCH404

6 MCH106 MCH106N MCH206 MCH306 MCH406

8 MCH108 MCH108N MCH208 MCH308 MCH408

10 MCH110 MCH110N MCH210 MCH310 MCH410

13 MCH113 MCH113N MCH213 MCH313 MCH413

16 MCH116 MCH116N MCH216 MCH316 MCH416

20 MCH120 MCH120N MCH220 MCH320 MCH420

25 MCH125 MCH125N MCH225 MCH325 MCH425

32 MCH132 MCH132N MCH232 MCH332 MCH432

40 MCH140 MCH140N MCH240 MCH340 MCH440

50 MCH150 MCH150N MCH250 MCH350 MCH450

63 MCH163 MCH163N MCH263 MCH363 MCH463

APPLICATIONS

■ SP MCBs can be used in type A distribution boards.

■ SP, DP and TP MCBs can be used in type B distribution boards.

■ SPSN and DP MCBs can be used in DP distribution boards.

■ FP MCBs are for specialist OEM applications.

Memshield 2 P47-91 31/7/02 16:12 Page 18

Page 15: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

62

M I N I A T U R E C I R C U I T B R E A K E R S - T Y P E D , 1 0 K A ;

F U S E C A R R I E R S - T Y P E B S .

FUSE CARRIERS

The Memshield 2 fuse carrier range uses high performance MEM

BS1361 type HRC fuses capable of disconnecting short circuits of up

to 16kA.

The fuse carriers and fuses are both British designed and

manufactured, using the latest technology. The protection of circuits by

Memshield 2 fuse and carriers is particularly applicable where circuits

exhibit high inrush e.g. high frequency lighting. The fuse carriers are

suitable for use with Memshield 2 SPN and TPN type distribution

boards. In addition fuse carriers are suitable for a wide range of OEM

type applications.

Current ratings are available in 5, 10, 15, 20, 30, 35, 40, and 45A

ratings. The range is available as SP devices only.

FEATURES

Memshield 2 fuse carriers feature a fully shrouded contact mechanism.

Each unit is supplied with a 240v fuse fitted, and facility for a spare

fuse, which can be contained within the fuse carrier.

For 415v applications contact us for details of suitable fuse units

and fuselinks.

Note - Memshield 2 types MFM35/40/45 units are 36mm wide and

require 2 SP distribution board ways.

MEMSHIELD 2 MCBS - TYPE D TO BSEN60898 (IEC898), 10

TO 20 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP

1 MDH101 MDH101N MDH201 MDH301 MDH401

2 MDH102 MDH102N MDH202 MDH302 MDH402

4 MDH104 MDH104N MDH204 MDH304 MDH404

6 MDH106 MDH106N MDH206 MDH306 MDH406

8 MDH108 MDH108N MDH208 MDH308 MDH408

10 MDH110 MDH110N MDH210 MDH310 MDH410

13 MDH113 MDH113N MDH213 MDH313 MDH413

16 MDH116 MDH116N MDH216 MDH316 MDH416

20 MDH120 MDH120N MDH220 MDH320 MDH420

25 MDH125 MDH125N MDH225 MDH325 MDH425

32 MDH132 MDH132N MDH232 MDH332 MDH432

40* MDL140 MDL140N MDL240 MDL340 MDL440

50* MDL150 MDL150N MDL250 MDL350 MDL450

63* MDL163 MDL163N MDL263 MDL363 MDL463

*6kA

MEMSHIELD 2 FUSES - HRC FUSE CARRIERS FOR

BS1361 FUSES (240V RATED).

UNDER VOLTAGE RELEASE LIST NO.

For remote tripping of an emergency stop loop. M2UV240240V AC

AUXILIARY AND ALARM CONTACTS

Auxiliary and alarm contact devices can be fitted together on

one MCB.

Each is incorporated in a 1/2 module (9mm) casing with terminals

protected to IP2 capable of accepting cable up to 2.5mm2 . A half

module blanking plate is available List no. MABP.

These devices are designed and manufactured to BS

EN60947.5.1.

Contact ratings: AC14 240V ac 50Hz 6A DC14 125V dc 1A

SHUNT TRIPS AND UVRS

Suitable for all Memshield 2 MCBs and RCBOs including those

with either auxiliary or alarm contacts. A shunt trip and

undervoltage release can be fitted together on one MCB.

Each is incorporated in a 1 module (18mm) casing with terminals

protected to IP2 capable of accepting cable up to 2.5mm2

Contact ratings: AC14 240V ac 50Hz 5A DC 14 125V dc 1A

AUXILIARY CONTACT DESCRIPTION LIST NO.

A changeover switch incorporating a test function to allow

remote indication of the position of the MCB contacts.

The auxiliary contact will not differentiate between an M2AUMCB that is “off” or “tripped”. The auxiliary contact

can be used in conjunction with a remote supply and signal

lamps, bells or buzzers.

The above devices are simply clipped to the left hand side of

an MCB or RCBO and have terminals at one end to allow

connection to pan assemblies and comb busbar.

RATING SPARE LIST NO.A FUSES SP5 5LC MFM0510 1510LC MFM1015 15LC MFM1520 20LC MFM2030 30LC MFM3035 35LCS MFM3540 40LCS MFM4045 45LCS MFM45

ALARM CONTACT DESCRIPTION LIST NO.

A changeover switch incorporating reset and test

function providing remote indication of an MCB M2ALwhich has tripped under fault conditions.

SHUNT TRIP DESCRIPTION LIST NO.

An open circuit shunt release for remote trippping of

an MCB offering three voltage options for AC &

DC applications

24V AC 24V DC M2STA

48V - 110V AC 48V-60V DC M2STB

240V AC 110V DC M2STC

Memshield 2 P47-91 31/7/02 16:12 Page 19

Page 16: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

STANDARD READY ASSEMBLED RCBOS - SPTYPE C

This table highlights examples of the more commonly required

RCBO units incorporating Type C Memshield 2 MCBs.

RATING A SENSITIVITY SENSITIVITY10MA LIST NO. 30MA LIST NO.

6 MCH106R10 MCH106R3010 MCH110R10 MCH110R3016 MCH116R10 MCH116R3020 MCH120R10 MCH120R3032 MCH132R10 MCH132R3040 - MCH140R30

RCBOS FACTORY ASSEMBLED TO ORDER

Any standard Memshield 2 SP or SPSN MCB can be factory

fitted with residual current protection.

To order your RCBO simply select the MCB from pages 61/62

and add the required sensitivity suffix shown in the table

below, the RCBO will be supplied as a fully fitted unit.

SENSITIVITY MA SUFFIX LIST NO.10mA, 230-240V AC R10*30mA, 230-240V AC R30100mA, 230-240V AC R100100mA time delayed, 230-240V AC R100D300mA time delayed, 230-240V AC R300D

* 10mA RC units can be fitted to MCBs up to 32A only.

FIELD FITTABLE RESIDUAL CURRENT (RC)UNITS

Any standard Memshield 2 SP or SPSN MCB can be field

fitted with a residual current unit.

To order simply select the required sensitivity suffix from the

table below, the residual current unit will be supplied for you

to fit to your MCB. Contact us for availability.

SENSITIVITY MA SUFFIX LIST NO.30mA, 110V AC MR30/110100mA, 110V AC MR100/11030mA, 230-240V AC MR30100mA, 230-240V AC MR100100mA time delayed, 230-240V AC MR100D300mA time delayed, 230-240V AC MR300D

D.C. Components in the LoadThe RCBO is capable of responding to the superimposition of components ofcurrent on the supply caused by the operation of equipment using rectifiedvoltages in compliance with BSEN 61009.

Loss of Supply NeutralUnder loss of supply neutral conditions the r.c. element of the device willcontinue to provide earth leakage protection.With these conditions and upon detection of an earth leakage current theRCBO will operate within its normal characteristics.

High Voltage SuppressionHigh voltage suppression is incorporated and the unit is therefore ideal foruse with supply equipment susceptible to such mains borne transients.

63

M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SR C B O ( C O M B I N E D M C B / R C D ) - T Y P E B , C , A N D D

REVOLUTIONARY!

The Memshield 2 RCBO combines the functions of an RCCB and an

MCB. The unique, revolutionary design allows hundreds of RCBO

possibilities within a module as little as 18mm wide. This allows a far

greater number of devices to be fitted into a distribution board.

All the features of the standard MCB are maintained but with the

added flexibility of residual current protection.

Memshield 2 SP RCBOs are suitable for use in any Memshield 2

distribution board.

Due to the unique method of construction any Memshield 2 SP orSPSN MCB can be fitted with residual current protection.

So for applications where a SP 63A type D MCB with 300mA time

delayed residual current protection is required MEM have the answer!

A new version of the residual current pod is available for use on 110V

50/60Hz systems.

ADDING EARTH FAULT PROTECTION TO YOUR MCB

There are three options each complying with BSEN61009:

1 Choose from the standard ready assembled range of RCBOs

incorporating Type C MCBs.

2 RCBOs factory assembled to order; select your MCB followed by the

earth fault sensitivity suffix from the relevant table. Remember any

SP or SPSN MCB can be fitted with earth fault protection.

Example: MDL150R100 = 50A SP Type D MCB factory

assembled with 100mA residual current protection.

3 Field fittable Residual Current (RC) Units; an RCBO can be

assembled on site. This provides two benefits: Previously installed

Memshield 2 SP & SPSN MCBs can be upgraded to include residual

current protection, also stock of SP & SPSN Memshield 2 MCBs

previously supplied can be upgraded to include earth fault protection.

Example: A field fitted MR30 will convert any SP or SPSN MCB

into an RCBO with 30mA residual current sensitivity.

NOTE: SPSN RCBOs must NOT be fitted in TPN type B distribution

boards. SPSN RCBOs are limited for use in DP versions of type A and

type B distribution boards.

To guarantee discrimination with downstream residual current devices

any upstream residual current device should be time delayed. The time

delay period is between 150-400mS.

New

RESIDUAL CURRENT OPERATED CIRCUIT BREAKERS WITH INTEGRAL OVERCURRENT PROTECTION.

Memshield 2 P47-91 31/7/02 16:12 Page 20

Page 17: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SA C C E S S O R I E S

64

COMB BUSBAR END COVERS

For DP, TP and FP busbar configurations, supplied in packs of 10.

DESCRIPTION LIST NO.

For DP and TP comb busbars; MB2P, MB2F, MBEC23MB3P and MB3F

For FP comb busbars; MB4P and MB4F MBEC4

The wide range of Memshield 2 devices are complemented by a

range of dolly padlocking devices.

For MCBs, RCCBs, RCBOs, and MCCBs the device mechanism is

trip free which allows it to be padlocked ‘ON’ for security, but in

the event of a fault condition the device will still operate to

disconnect the fault. The device dolly will move to the tripped

position when the dolly lock is removed. These devices can also be

padlocked in the ‘OFF’ position.

NOTE: Distribution board doors can be closed when an MCB is

padlocked ‘ON’ or ‘OFF’.

MEMSHIELD 2 DEVICES GENERAL ACCESSORIES

DESCRIPTION LIST NO.

Dolly padlocking device for all MCBs MBL2and RCBOs

Dolly padlocking device for all SPSN RCCBs AML2

Dolly padlocking device for all 100A switches SML4

Dolly padlocking device for MCCB/BMS2003 2MFLL

Padlock for MBL2, AML2, SML4 PD2

Padlock for 2MFLL PD50

MCB terminal shroud (each) MTSH1

MCB terminal screw shield (each) MTS1

MCB terminal rear connectors, MBRC1capacity 50mm2 max. (each)

Spare 5A BS1361 fuse 5LC

Spare 10A BS1361 fuse 1510LC

Spare 15A BS1361 fuse 15LC

Spare 20A BS1361 fuse 20LC

Spare 30A BS1361 fuse 30LC

Spare 35A BS1361 fuse 35LCS

Spare 40A BS1361 fuse 40LCS

Spare 45A BS1361 fuse 45LCS

COMB BUSBAR

Comb busbar is available for specialist applications and can be

supplied in both pin and fork type formats.

Fork type comb busbar can be used with all Memshield 2 MCBs*

and TPSN RCCBs. Pin type comb busbar can be used with all

Memshield 2 MCBs, fuse modules, switch-disconnectors, terminal

blocks SPSN and TPSN RCCBs.

NOTE: Due to a height difference TPSN RCCBs cannot be

inter-connected with comb busbar when mounted in combination

with other devices.

Busbar material: Copper

Rated operational voltage: 240/415V

Rated operational current: 100A

Unused ways on comb busbar can be shielded by fitting the

Memshield 2 blanking module, it also provides a barrier in the

distribution board front cover aperture. List No. MBP.

*For incoming connections onto fork type comb busbar, MCB

terminals clamp cable and busbar simultaneously.

MEMSHIELD 2 COMB BUSBAR

Supplied in 1m lengths.

DESCRIPTION LIST NO.

16mm2 SP insulated pin type MB1P

20mm2 SP insulated fork type MB1F

16mm2 DP insulated pin type MB2P

16mm2 DP insulated fork type MB2F

16mm2 TP insulated pin type MB3P

16mm2 TP insulated fork type MB3F

16mm2 FP insulated pin type MB4P

16mm2 FP insulated fork type MB4F

Memshield 2 P47-91 31/7/02 16:13 Page 21

Page 18: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

65

M E M S H I E L D 2 C O M M A N D D E V I C E SR E S I D U A L C U R R E N T C I R C U I T B R E A K E R S ; S P S N & T P S N

Memshield 2 RCCBs offer a tremendous range for installers.

Units are available with ratings up to 100A and sensitivities

from 10mA to 300mA time delayed.

These units are the first to conform to BSEN61008.

FEATURES

The SPSN electronic unit is capable of sensing DC components

in the supply, in accordance with BSEN61008. Generous cable

capacities of up to 50mm2 (TPSN with adaptor fitted. 35mm2

without adaptor) are provided. The SPSN devices will trip to a

central position under earth fault conditions. A flag indicator

shows positive contact position via window above dolly. The

RCCBs can be installed in a variety of enclosures (see page 57).

All SPSN units are suitable for 240v 50/60 Hz applications.

All TPSN units are suitable for 415v AC applications and also

have comb busbar facilities.

Please contact our Technical Services department for details

of other voltage/frequency possibilities.

AUXILIARY CONTACT MODULE

Memshield 2 TPSN RCCBs can be supplied fitted with an

auxiliary contact module adding a half module to the four

module device.

To order add suffix HR to list no. e.g: AM254HHR.

They incorporate 1N/O + 1 N/C contact.

Nominal voltage: Max 415V

Nominal Current: 6A at 400V (Resistive)

6A at 230V

2A at 400V

Terminals will accept cables up to 2.5mm2.

Contact us for availability.

MEMSHIELD 2 RCCBS - TPSN

DESCRIPTION LIST NO.

25A 30mA TPSN RCCB AM254H

40A 30mA TPSN RCCB AM404H

63A 30mA TPSN RCCB AM634H

80A 30mA TPSN RCCB AM804H

100A 30mA TPSN RCCB AM1004H

25A 100mA TPSN RCCB AM254M

40A 100mA TPSN RCCB AM404M

63A 100mA TPSN RCCB AM634M

80A 100mA TPSN RCCB AM804M

100A 100mA TPSN RCCB AM1004M

25A 300mA TPSN RCCB AM254L

40A 300mA TPSN RCCB AM404L

63A 300mA TPSN RCCB AM634L

80A 300mA TPSN RCCB AM804L

100A 300mA TPSN RCCB AM1004L

100A 300mA TPSN RCCB time delayed AM1004LT

Adaptor kit to accept up to 50mm2 cable AMBT

MEMSHIELD 2 RCCBS - SPSN

DESCRIPTION LIST NO.

16A 10mA SPSN RCCB AM16VHE

25A 30mA SPSN RCCB AM25HE

40A 30mA SPSN RCCB AM40HE

63A 30mA SPSN RCCB AM63HE

80A 30mA SPSN RCCB AM80HE

100A 30mA SPSN RCCB AM100HE

25A 100mA SPSN RCCB AM25ME

40A 100mA SPSN RCCB AM40ME

63A 100mA SPSN RCCB AM63ME

80A 100mA SPSN RCCB AM80ME

100A 100mA SPSN RCCB AM100ME

25A 300mA SPSN RCCB AM25LE

40A 300mA SPSN RCCB AM40LE

63A 300mA SPSN RCCB AM63LE

80A 300mA SPSN RCCB AM80LE

100A 300mA SPSN RCCB AM100LE

100A 100mA SPSN RCCB time delayed AM100MET

100A 300mA SPSN RCCB time delayed AM100LET

RESIDUAL CURRENT OPERATED CIRCUIT BREAKERSWITHOUT INTEGRAL OVERCURRENT PROTECTION.

Memshield 2 P47-91 31/7/02 16:13 Page 22

Page 19: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

66

M E M S H I E L D 2 C O M M A N D D E V I C E SB E L L T R A N S F O R M E R S , T I M E S W I T C H E S , C O N T A C T O R S , I M P U L S E

R E L A Y S , T I M E D E L A Y R E L A Y S

Memshield 2 command devices allow increased flexibility for

both distribution board and OEM applications. SPN

distribution boards can accommodate command devices by

using a busbar block kit. Command devices can be

accommodated in modular enclosures. In addition all devices

are suitable for installation on ‘tophat’ symmetrical DIN-rail.

BELL TRANSFORMER

Devices can accommodate from 4-12v secondary from a 240v

AC primary supply. The AA2BT is not suitable for isolation duty.

TIME SWITCHES

Devices are available as analogue (dial) type or digital (LCD)

types. Quartz stabilised devices have a running reserve time of

150Hr and a recharge time of 70Hr. Digital time switches have a

running reserve of 150Hr, and a full recharge time of 140Hr. All

time switches have 1 c/o contact per channel and are suitable for

switching 16A resistive, 2.5A inductive loads at 240v 50Hz. For

higher rated loads time switches should be used in conjunction

with MEM Autoline heating & lighting contactors.

CONTACTORS

Memshield 2 modular contactors are available from 16A to 63A,

and from SP to FP. Devices are suitable for AC1 (general heating

& lighting loads) applications. All devices have N/O contacts.

Note; when several contactors are mounted it is advisable to fit a

blanking module, List no. MBP, every 2 contactors.

IMPULSE RELAYS

Memshield 2 modular impulse relays are available with 16A

N/O or C/O contacts. Impulse relays are often a suitable

replacement for contactors where low switching duty and low

energy consumption are important.

TIME DELAY RELAYS

Memshield 2 modular time delay relays (staircase switches)

are suitable for delay ‘OFF’ applications from 30 seconds to

15 minutes. For use on loads above 16A AC1 devices should

be used in conjunction with a suitable MEM contactor.

MEMSHIELD 2 BELL TRANSFORMERS

WIDTHDESCRIPTION PRIMARY SECONDARY IN 18MM

VOLTAGE VOLTAGE MODULES LIST NO.Non isolating 240v AC 4v 1A 2 AA2BT

8v 1A12v 0.67A

N.B. AA2BT supplied with full terminal shields & direct

mounting bracket.

MEMSHIELD 2 - TIME SWITCHES

MINIMUM WIDTHDESCRIPTION TYPE PROGRAMME IN 18MM LIST

TIME MODULES NO.

Non-quartz stabilised - 220/240v AC 50Hz

Analogue, 1 channel 24hr 30 mins 1 AT11SD

Analogue, 1 channel 24hr 30 mins 3 AT1SD

Analogue, 1 channel 7 day 180 mins 3 AT1SW

Quartz stabilised - 220/240v AC 50Hz

Analogue, 1 channel 24hr 30 mins 3 AT1QD

Analogue, 1 channel 7 day 180 mins 3 AT1QW

Digital quartz - 220/240v AC 50Hz single channel

Digital, 1 channel fully 1 min 1 AT11Pprog.

Digital, 1 channel fully 1 min 2 AT1Pprog.

Digital, 2 channel fully 1 min 2 AT2Pprog.

N.B. All time switches supplied with terminal shields and detachable

wall mounting bracket.

MEMSHIELD 2 CONTACTORS

WIDTHDESCRIPTION COIL IN 18MMRATING A DUTY VOLTAGE CONTACTS MODULES LIST NO.16A SP AC1 230v AC 1-N/O, 1-N/C 1 AA16125A DP AC1 230v AC 2-N/O 1 AA20240A DP AC1 230v AC 2-N/O 2 AA40225A TP AC1 230v AC 3-N/O 2 AA20340A TP AC1 230v AC 3-N/O 3 AA40363A TP AC1 230v AC 3-N/O 3 AA63325A FP AC1 230v AC 4-N/O 2 AA20440A FP AC1 230v AC 4-N/O 3 AA40463A FP AC1 230v AC 4-N/O 3 AA634

Contact us for other ratings.

MEMSHIELD 2 IMPULSE RELAYS

WIDTHDESCRIPTION COIL IN 18MMRATING A VOLTAGE CONTACTS MODULES LIST NO.

16A SP 230v AC 1-N/O 1 AA161RA16A SP 230v AC 1-N/0, 1-N/C 1 AA161RB

MEMSHIELD 2 TIME DELAY RELAYS

WIDTHDESCRIPTION COIL IN 18MMRATING A VOLTAGE TYPE MODULES LIST NO.

16A SP 230v AC delay off 1 AA7

Memshield 2 P47-91 31/7/02 16:13 Page 23

Page 20: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

M E M S H I E L D 2 C O M M A N D D E V I C E SS W I T C H - D I S C O N N E C T O R S A N D T E R M I N A L B L O C K S

67

SWITCH-DISCONNECTORS

Memshield 2 18mm modular switch-disconnectors have a similar profile to

Memshield 2 MCBs and conform to the requirements of BSEN60947-3,

100A 240/415v AC22B. Positive contact indication is also provided.

Terminals are box type allowing cable capacity up to 50mm2.

SPSN switch-disconnectors have neutral contacts which make

first - break last.

TERMINAL BLOCKS

Memshield 2 18mm modular terminal blocks are suitable for a wide

variety of uses. They can be used in outgoing circuits in place of a

Memshield 2 MCB or RCBO to tap off to other devices or boards.

Terminals are box type allowing cable capacity up to 50mm2. Suitable

for type A and B distribution boards.

MEMSHIELD 2 - SWITCH-DISCONNECTORS

For use in modular enclosures or on symetrical DIN-rail.

WIDTHDESCRIPTION IN 18MM LIST NO.

MODULES

100A SP 1 MS1001

100A SPSN* 2 MS1001N

100A DP* 2 MS1002

100A TP* 3 MS1003

100A TPSN* 4 MS1004

Padlock attachment - SML4

Padlock - PD2

*For switch-disconnectors for use as distribution board incomers refer

to pages 52, 54 and 55.

MEMSHIELD 2 - TERMINAL BLOCKS

For use in modular enclosures or on symetrical DIN-rail.

WIDTHDESCRIPTION IN 18MM LIST NO.

MODULES

100A 1P 1 MBT1001

100A DP* 2 MBT1002

100A TP* 3 MBT1003

*For terminal blocks for use as distribution board incomers refer to

pages 52, 54 and 55.

Memshield 2 P47-91 31/7/02 16:13 Page 24

Page 21: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

22

M E M S H I E L D 2 M C B O U T G O I N G D E V I C E S 6 K AM I N I A T U R E C I R C U I T B R E A K E R S ; T Y P E B , C & D

68

This Memshield 2 MCB is current limiting in design with the ability

to disconnect short circuits up to 6kA.

The feature packed device is both British designed and manufactured,

using the latest technology.

The MCBs are suitable for use in a wide range of OEM type

applications. In addition, MCBs are suitable for use in Memshield

2 SPN and TPN distribution boards.

Current ratings are available in 1, 2, 4, 6, 8, 10, 13, 16, 20, 25, 32,

40, 50, and 63A ratings. The range is available with Types B, C, and

D, for SP, SPSN, DP, TP, FP pole configurations.

On SPSN the switched neutral is unprotected, on DP and FP all

poles are protected.

SPSN MCBs are fitted with neutral contacts which make first and

break last.

FEATURES

Memshield 2 MCBs are available with a breaking capacity of 6kA

to BSEN60898 & BSEN60947-2. The MCBs are normally

calibrated to 40ºC.

MCBs can be supplied with 50°c ambient calibration. To order insert

‘X’ at the end of the MCB list number eg:- MCL116X

Please contact our Technical Services department for details of

Memshield MCBs suitable for other reference calibration temperatures.

APPLICATIONS

■ SP MCBs can be used in type A distribution boards.

■ SP, DP and TP MCBs can be used in type B distribution boards.

■ SPSN and DP MCBs can be used in DP distribution boards.

■ FP MCBs are for specialist OEM applications.

MEMSHIELD 2 MCBS - TYPE B TO BSEN60898 (IEC898),

3 TO 5 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP

1 MBL101 MBL101N MBL201 MBL301 MBL401

2 MBL102 MBL102N MBL202 MBL302 MBL402

4 MBL104 MBL104N MBL204 MBL304 MBL404

6 MBL106 MBL106N MBL206 MBL306 MBL406

8 MBL108 MBL108N MBL208 MBL308 MBL408

10 MBL110 MBL110N MBL210 MBL310 MBL410

13 MBL113 MBL113N MBL213 MBL313 MBL413

16 MBL116 MBL116N MBL216 MBL316 MBL416

20 MBL120 MBL120N MBL220 MBL320 MBL420

25 MBL125 MBL125N MBL225 MBL325 MBL425

32 MBL132 MBL132N MBL232 MBL332 MBL432

40 MBL140 MBL140N MBL240 MBL340 MBL440

50 MBL150 MBL150N MBL250 MBL350 MBL450

63 MBL163 MBL163N MBL263 MBL363 MBL463

MEMSHIELD 2 MCBS - TYPE C TO BSEN60898 (IEC898),

5 TO 10 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP

1 MCL101 MCL101N MCL201 MCL301 MCL401

2 MCL102 MCL102N MCL202 MCL302 MCL402

4 MCL104 MCL104N MCL204 MCL304 MCL404

6 MCL106 MCL106N MCL206 MCL306 MCL406

8 MCL108 MCL108N MCL208 MCL308 MCL408

10 MCL110 MCL110N MCL210 MCL310 MCL410

13 MCL113 MCL113N MCL213 MCL313 MCL413

16 MCL116 MCL116N MCL216 MCL316 MCL416

20 MCL120 MCL120N MCL220 MCL320 MCL420

25 MCL125 MCL125N MCL225 MCL325 MCL425

32 MCL132 MCL132N MCL232 MCL332 MCL432

40 MCL140 MCL140N MCL240 MCL340 MCL440

50 MCL150 MCL150N MCL250 MCL350 MCL450

63 MCL163 MCL163N MCL263 MCL363 MCL463

MEMSHIELD 2 MCBS - TYPE D TO BSEN60898 (IEC898),

10 TO 20 x IN & BSEN60947-2

RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP

1 MDL101 MDL101N MDL201 MDL301 MDL401

2 MDL102 MDL102N MDL202 MDL302 MDL402

4 MDL104 MDL104N MDL204 MDL304 MDL404

6 MDL106 MDL106N MDL206 MDL306 MDL406

8 MDL108 MDL108N MDL208 MDL308 MDL408

10 MDL110 MDL110N MDL210 MDL310 MDL410

13 MDL113 MDL113N MDL213 MDL313 MDL413

16 MDL116 MDL116N MDL216 MDL316 MDL416

20 MDL120 MDL120N MDL220 MDL320 MDL420

25 MDL125 MDL125N MDL225 MDL325 MDL425

32 MDL132 MDL132N MDL232 MDL332 MDL432

40 MDL140 MDL140N MDL240 MDL340 MDL440

50 MDL150 MDL150N MDL250 MDL350 MDL450

63 MDL163 MDL163N MDL263 MDL363 MDL463

Memshield 2 P47-91 31/7/02 16:13 Page 25

Page 22: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

69

D I S T R I B U T I O N B O A R D S A N D D E V I C E S - S P E C I F I C A T I O N

TYPE MCBS RCBOS RCCBS DP RCCBS FP FUSESStandards IEC60898, BSEN60898 BSEN61009 BSEN61008 BSEN61008 BS1361 Size 1

IEC60947-2, BSEN60947-2

Breaking Capacity toIEC60898/BSEN60898/IEC60947-2 10kA 10kA - - -BSEN60947-2 (H Type)

IEC60898/BSEN60898/IEC60947-2 6kA 6kA - - -BSEN60947-2 (L Type)

BS1361 - - - - 16kASensitivities (mA) - 10, 30, 100, 10, 30, 100, 300, 30, 100, 300, 300t.d. -

100t.d, 300t.d. 100t.d., 300t.d.

Current Ratings (A) 1,2,4,6,8,10,13, 1,2,4,6,8,10,13,16, 16,25,32,40,63, 25,40,63, 80, 100 5, 10, 15, 20,16, 20, 25, 32, 40, 50, 63 20, 25, 32, 40,50, 63† 80, 100 30, 35, 40, 45

Voltage Rating 50/60Hz (v)* 24V DC (6kA) to 120V DC (4kA) 240V AC 240V AC 240/415V AC 240V AC& 240V/415V AC 110V AC

DIN-rail mounting Yes Yes Yes Yes Yes

Tunnel ‘Box’ Terminals Yes Yes Yes Yes Yes

Cable Capacity 25mm2 25mm2 50mm2 35mm2 25mm2

(50mm2 with adaptor)

Terminals Suitable For -Stranded Copper Cable Top & Bottom** Top & Bottom Top & Bottom Top & Bottom** Top & BottomSolid Copper Cable Top & Bottom** Top & Bottom Top & Bottom Top & Bottom** Top & BottomComb Busbar (Fork) Top & Bottom** Bottom - Top & Bottom** -Comb Busbar (Pin) Top & Bottom Bottom Top & Bottom Top & Bottom Top & BottomAluminium Cable Consult Us Consult Us Consult Us Consult Us Consult Us

*Please consult our Technical Services department for alternative ratings.

**Terminals will clamp cable and fork type comb busbars simultaneously.

†10mA only available up to 32A inclusive.

TYPE SPN A BOARDS TPN B BOARDSStandards BS5486 - Part 12 BS5486 - Part 12

BS5486 - Part 13 BSEN60439-3BSEN60439-3

Busbar Rating 100A 200ABusbar Type Fully Shrouded Solid Copper Fully Shrouded Dual Solid CopperVoltage Rating 240V AC 240/415V AC

50/60Hz 50/60HzIP Rating to BS5420:1977 IP4X IP4XEnclosure Body Type Light grey finish over Light grey finish over

Rust Protected Sheet Steel Rust Protected Sheet SteelEnclosure Paint Type* BS4800 Shade 00A07 BS4800 Shade 00A07Knockouts - Body 4/7/10 way; 2 off 33 x 60mm Knockouts each side

13/16 way; 4 off 33 x 60mm for Busbar Connecting Kitin rear plate

Cable Capacities100A Switch-disconnector 50mm2 50mm2

125A TP Switch-disconnector - 70mm2

160A TP Switch-disconnector - 70mm2

200A Switch-disconnector - 120mm2

100A Terminal Block (Lugs) 50mm2 50mm2

200A Terminal Block (Lugs) - M8 bolt100A SPSN RCCB 50mm2 -100A TPSN RCCB - 50mm2 (with adaptor fitted)16-200A F Frame MCCB - 120mm2

125A Fuse Combination Switch - M6Enclosure Earth Stud M6 bolt M8 boltIncoming Earth Terminal 25mm2 70mm2

Incoming Neutral Terminal - 70mm2 (125A boards)M8 bolt (200A boards)

Outgoing Earth Terminals 25mm2 25mm2

Outgoing Neutral Terminals 25mm2 25mm2

*Please consult our Technical Services department for full details of non -standardpaint finishes.

Memshield 2 P47-91 31/7/02 16:13 Page 26

Page 23: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

22

M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM C B D I S T R I B U T I O N B O A R D D I M E N S I O N S

70

TYPE A 100A SPN 2 - 16 WAY, DP 5 & 8 WAY, SPLITLOAD AND DUAL TARIFF DISTRIBUTION BOARDS,1 ROW DIN-RAIL ENCLOSURES

AMSL910 SPLIT LOAD DISTRIBUTION BOARD

NOTE: For flush mounting aperture dimensions use equivalent

enclosure size. All dimensions in mm.

* Internal depth = 90mm.

TYPE B 100A TPN 4 - 24 WAY, DP 6 - 24 WAY, AND SPLIT LOAD DISTRIBUTION BOARDS, 3ROW DIN-RAIL ENCLOSURES*

LIST NO. A B C

AM2 152.0 38.5 77.0

AM4 238.0 81.5 163.0

AM7 292.0 108.5 217.0

AM5D, AM10 346.0 135.5 271.0

AM13 400.0 162.5 325.0

AM8D, AM16 454.0 189.5 379.0

AMSL37, AMSL64 400.0 162.5 325.0

AMSL67, AMSL94, AMSL310 454.0 189.5 379.0

AMSL910 346.0 135.5 271.0

AMDT74 400.0 162.5 325.0

AMDT77, AMDT104 454.0 189.5 379.0

ENCLOSURES

BMXDC4, BMXDCG4, 152.0 38.5 77.0

BMXDC6, BMXDCG6 238.0 81.5 163.0

BMXDC9, BMXDCG9 292.0 108.5 217.0

BMXDC15, BMXDCG15 400.0 162.5 325.0

125A BOARD 100/125A SWITCHDISCONNECTOR/100A RCCB

LIST NO. BMS1003, BMS1253, BMS1004, BMS1001N, BMBT1003, BMR100 OR

BMR300 OR NEOZED INCOMER

A B

BM41 403.0 497.5

BM61 457.0 551.5

BM61D 403.0 551.5

BM81 511.0 605.5

BM121D 511.0 659.5

BM81NZ 565.0 659.5

BM121, BM181D, 673.0 767.5BM121NZ

BM161, BM241D, 781.0 875.5BM81NZ

SPLIT LOAD

BMSL48, BMSL66, 727.0 821.5BMSL84

BMSL88 835.0 929.5

ENCLOSURES

BMXDC30, 457.0 551.5BMXDCG30

BMXDC45, 673.0 767.5BMXDCG45

BM241 = 1350mmH x 560mmW x 155mmD.

Memshield 2 P47-91 31/7/02 16:13 Page 27

Page 24: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

71

TYPE B 200A TPN 4-24 WAY DISTRIBUTION BOARDS

TYPE B 4-16 WAY DISTRIBUTION BOARDS WITH FCS INCOMER

200A 200A LUGS 160/200A SWITCH BOARD BMBT2003 DISCONNECTOR/F-FRAME LIST NO. MCCB,BMS2001N, BMS1603,

BMS2003 OR BMIK2003

A B C A B C

BM42 457.0 - 551.5 457.0 579.5 713.5

BM62 511.0 - 605.5 511.0 633.5 767.5

BM82 565.0 - 659.5 565.0 687.5 821.5

BM122 673.0 - 767.5 673.0 795.5 929.5

BM162 781.0 - 875.5 781.0 903.5 1037.5

BM242 = 1350mmH x 560mmW x 155mmD.

LIST NO. A B C

BMFCS4, BMFCSN4 403.0 486.0 875.5

BMFCS6, BMFCSN6 457.0 540.0 929.5

BMFCS8, BMFCSN8 511.0 594.0 983.5

BMFCS12, BMFCSN12 673.0 702.0 1145.5

BMFCS16, BMFCSN16 781.0 810.0 1253.5

NOTE: For flush mounting aperture dimensions use equivalent enclosure size including extension box.

Flush mounting kit will also cover extension box. All dimensions in mm.

Memshield 2 P47-91 31/7/02 16:14 Page 28

Page 25: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

2672

M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM C B P A N A S S E M B L Y D I M E N S I O N S

TYPE A PAN ASSEMBLIES

TYPE B PAN ASSEMBLIES

LIST NO. A B C

AMP4 218.5 147.5 109.0AMP7 272.5 201.5 163.0AMP5D, AMP10 326.5 255.5 217.0AMP13 380.5 309.5 271.0AMP8D, AMP16 434.5 363.5 325.0

LIST NO. A B C D

BMP41 307.0 369.5 109.5 38.5BMP61 361.0 423.5 163.5 38.5BMP81 415.0 477.5 217.5 38.5BMP42, BMP61D 307.0 423.5 109.5 92.5BMP62 361.0 477.5 163.5 92.5BMP82, BMP121D 415.0 531.5 217.5 92.5BMP122, BMP181D 523.0 639.5 325.5 92.5BMP162, BMP241D 631.0 747.5 433.5 92.5

All dimensions in mm.

52

LIST NO. A B

BMPS42 226 162

BMPS62 280 216

BMPS82 334 270

BMPS122 442 378

BMPS162 550 486

PAN-ASSEMBLIES WITHOUT EARTH & NEUTRAL

BMP242LWENBMP242L

6 x M6CLEARANCEHOLES

520.

552

0.5

109.

4

63.5

280.0

298.5

1168

.0

Memshield 2 P47-91 31/7/02 16:14 Page 29

Page 26: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

73

D E V I C E D I M E N S I O N S

SP MCB/RCBOS

LIST NO. A B C

4EME 39.0 49.0 89.0AM1SL 33.0 20.0 53.0

LIST NO. A B C D E

4QEL 170.0 105.0 112.0 153.0 88.06QEL 170.0 135.0 112.0 130.0 80.0

HRC FUSE CARRIERS

SWITCH-DISCONNECTORS AND TERMINAL BLOCKS

All dimensions in mm.

RCDS 2 POLE 4 POLE

MOULDED ENCLOSURES 4/6 QEL 4EME/AM1SL

SWITCH DISCONNECTORS

LIST NO. A BMS1001 17.5MS1001N 35.0MS1002 35.0 76.0MS1003 52.5MS1004 70.0

TERMINAL BLOCKSMBT1001 17.5 67.0

64.8 8.8

20.9

45.1

89.8

AUXILIARY &ALARM CONTACTS

Memshield 2 P47-91 31/7/02 16:14 Page 30

Page 27: THE ULTIMATE MCB - Voltimum · PDF fileTHE ULTIMATE MCB 48 ... fuse combination switch to give a compact solution to ... SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A SWITCH-DISCONNECTOR,

74

M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MD E V I C E D I M E N S I O N S

AA403, AA404, AA633, AA634

All dimensions in mm.

BELL TRANSFORMER

AA2BT

TIME SWITCHES AT1SD, AT1SW,

AT1QD, AT1QW, AT1P†, AT2P†

CONTACTORS AA161, AA202 AA203, AA204, AA402

IMPULSE RELAYS AA161RA, AA161RB TIME DELAY RELAY AA7

Memshield 2 P47-91 31/7/02 16:15 Page 31