Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.rosemount.com

Mounting and Installation Advicefor Resistance Thermometers

and Thermocouple Assemblies

NOTICE

Read this manual before working with the product. For personal and system safety, and foroptimum product performance, make sure you thoroughly understand the contents beforeinstalling, using, or maintaining this product.

For further details please contact your local Rosemount representative.

The products described in this document are NOT designed for nuclear-qualifiedapplications. Using non-nuclear qualified products in applications that requirenuclear-qualified hardware or products may cause inaccurate readings.

For information on Rosemount nuclear-qualified products, contact your local EmersonProcess Management Sales Representative.

Page 4: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 4/26

Page 5: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 5/26

Page 6: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 6/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

TOC-2

Page 7: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 7/26

Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.emersonprocess.com/rosemount

Section 1 Introduction

How to Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1

HOW TO USETHIS MANUAL

This manual provides installation, configuration, troubleshooting, and otherprocedures for the use of the Rosemount1075 Series. Specifications andother important information are also included.

Section 2: Temperature Measurement with Resistance Thermometers

Contains information on description and measuring principle, structure,methods of connection and areas of application.

Section 3: Temperature Measurement with Thermocouples

Contains information on description and measurement principle, installation ofprotective tubes, leads and connections, and areas of application.

Section 4: Assembly of Housing

Contains information on rules and regulations for the Rosemount 1075

Series.

Appendix A: Limit Tolerances of Basic Values

Provides a chart with the limit tolerances of the basic values according to DINIEC 751 and DIN 43760.

Appendix B: Limit Tolerances for Thermocouples

Provides a chart for limit tolerances for thermocouples according to DIN IEC584-2.

SAFETY MESSAGES Procedures and instructions in this manual may require special precautions toensure the safety of the personnel performing the operations. Refer to thesafety messages, listed at the beginning of each section, before performingany operations.

Page 8: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 8/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

1-2

Page 9: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 9/26

Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.rosemount.com

Section 2 Temperature Measurement withResistance Thermometers

Description and Measuring Principle . . . . . . . . . . . . . . . .page 2-1

Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1

Methods of Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3

Areas of Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4

DESCRIPTION ANDMEASURING PRINCIPLE

Temperature measurement with resistance thermometers is based on theproperty possessed by all conductors and semiconductors, namely that theirresistance varies as a function of temperature. This property is more or lesspronounced, depending on the particular material. The relative change in theresistance as a function of temperature (dR/dt) is known as the temperaturecoefficient, the value of which is usually not constant over the range oftemperature of interest, but is itself a function of temperature. The result isthat the mathematical relationship between resistance and temperature takesthe form of a high-order polynomial.

Figure 2-1 shows the change in resistance as a function of temperature for aPt 100 resistance thermometer.

Figure 2-1. Pt 100 characteristiccurve

STRUCTURE The resistance temperature detector is made up of a platinum coil wound on a

suitable support. The wire coil is either fused into glass or embedded inceramic. To meet today’s requirements for more compact dimensions andhigher resistance values, extremely thin platinum layers are applied to aceramic substrate instead of wires (see Figure 2-2).

0

100

-200

200

300

400

2000 400 600 800

R

t

Page 10: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 10/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

2-2

Figure 2-2. Glass wire-wound,ceramic wire-wound andthin-film resistancethermometers

To protect them against mechanical damage (pressure of flowing liquid) thesemeasuring elements are usually installed into suitable protective tubes(measuring inserts). This also ensures easy replacement without the need toreplace the complete fitting. As resistance thermometers are contact-makingtemperature sensors (i.e. the sensor has to reach the temperature of themedium in which measurement is to be performed) the housing has to beadapted to the application (see Figure 2-3).

Figure 2-3. Resistancethermometer modules

Connection wires

Measuring coil

Ceramic substrate

Strain relief

Connection wires

Glass

Measuring coil

Ceramic tube

Aluminum oxidepowder

Glass

Connection wires

Glass carrier

Measuring coil

Glass sheath

Connection wires

Glass carrier

Measuring coil

Glass sheath

Measuring resistance

Measuring insert

Housing

Page 11: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 11/26

Reference Manual00809-0301-2654, Rev BA

September 2009

2-3

RTD and Thermocouple

METHODS OFCONNECTION

When using resistance thermometers for temperature measurement, the factthat the measurement result is influenced by the resistance of the selectedlead wire must be taken into account.

Three circuit types are commonly used: 2-wire, 3-wire, and 4-wire circuits.

The most accurate measurements are obtained with the 4-wire circuit, as inthis case the measurement is not affected by lead wire resistance orenvironment temperature of lead wires (see Figure 2-4).

The 3-wire circuit is normally used for eliminating the lead wire resistance(Wheatstone bridge).

In the case of the 2-wire circuit, the lead wire resistance is fully measured bythe measuring bridge. By the use of modern control equipment the influenceof the lead wire resistance at 2-wire circuit can be compensated by a linecompensation resistor, which is independent of temperature.

Figure 2-4. Methods of

connection

To measuring unit

To measuring unit

To measuring unit

Page 12: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 12/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

2-4

AREAS OFAPPLICATION

Resistance thermometers can be used over a temperature range of -220 Cto +600 C.

Their advantages are:

• High temperature ranges• Resistance to vibration

• High immunity to electrical interference

• Long-term stability

• Robust design

• High accuracy

Resistance thermometers are used in the following industries:

• Chemical industries

• Petrochemical industries

• Pharmaceutical industries

• Power generation• Mechanical engineering

• Food & beverage

• Mining

Page 13: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 13/26

Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.rosemount.com

Section 3 Temperature Measurement withThermocouples

Description and Measurement Principle . . . . . . . . . . . . . page 3-1

Installation of Protective Tubes . . . . . . . . . . . . . . . . . . . . . page 3-3

Leads and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3

Areas of Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3

DESCRIPTION ANDMEASUREMENTPRINCIPLE

A thermocouple consists of two electrical conductors of different materialsconnected to one another at one end (measuring junction). The two free endsbuild a compensation point resp reference junction. The thermocouple can beextended by using an extension or a compensating cable. The extension orcompensating cables are connected to a measuring instrument, e.g. agalvanometer or electronic measuring unit (see Figure 3-1).

Figure 3-1.

The thermoelectric voltage appearing at the reference junction depends onthe thermocouple wire material and on the temperature difference betweenthe measuring junction and the reference junction. For temperaturemeasurement, the temperature of the reference junction must be keptconstant (e.g. 0 C) or must be well known, to make an appropriate correctionin mV (see Figure 3-2).

Reference junction

Extension/ compensating cable

Connection point

Measuring junction

Page 14: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 14/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

3-2

Figure 3-2.

Extension cables are manufactured of the same material as thecorresponding thermocouple, e.g. Cu-CuNi, Fe-CuNi. Compensating cablesare manufactured of special materials.

Up to 200 C compensating cables supply the same thermoelectric voltage asthe thermocouples to which they are connected, The thermoelectric voltagesof the thermocouples are laid down in so-called basic value series.

The compensating cable for a thermocouple must be make of a material tosuit the particular type of thermocouple, so compensating leads arecolor-coded. For standardized compensating cable the regulations containedin DIN EN 60584 apply.

Maximum temperatures indicated by manufacturer have to be considered.

Most thermocouples are supplied ready for operation, that is in a protectivemounting to prevent damage to the thermocouple by mechanical forces orchemical attack.

e.g. PtRh30%-PtRh6% Type B

Fe-CuNi Type J

NiCr-NiAl Type J

PtRh87/13%-Pt Type R

PtRh90/10%-Pt Type S

and others in DIN IEC 584-1

and Fe-CuNi Type L

Cu0CuNi Type U

These thermocouples are not more available for use in newplants (thermoelectric voltage according to DIN 43710) Basicvalue tables are available on request only at manufacturer site.

Reference junction

Extension/ compensating cable

Connection point

Measuring junction

Copper wire

Page 15: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 15/26

Reference Manual00809-0301-2654, Rev BA

September 2009

3-3

RTD and Thermocouple

INSTALLATION OFPROTECTIVE TUBES

The protective tubes of thermocouples must be adapted to the particularoperating conditions. Precious metal thermocouples are always protectedwith a ceramic tube, even if the unit has a metallic protective mounting.

At high temperatures the protective tubes should be installed vertically, where

possible, i.e. suspended, to avoid damage deflection to the protective tubeand thermocouple through bending. If specific conditions on site make ahorizontal installation unavoidable, long protective tubes have to be suitablysupported.

LEADS ANDCONNECTIONS

When laying and connecting extension resp. compensating cables, care mustbe taken to connect the positive pole of the thermocouple to the positiveterminal of the indicating instrument. If extension cables or compensatingcables are used, care must be taken not to interchange positive and negativeconductors. To prevent errors, the positive and negative leads bear acorresponding marking.

All connections must be absolutely clean and firmly tightened. The

corresponding positive and negative terminals should have the sametemperature potential.

The compensating cables between the thermocouple and the indicatinginstrument should comply with the requirements for insulated leads in powersystems (VDE 0250). In exceptional cases, the regulations for insulated leadsin telecommunications systems (VDE 0810) may be applied.

AREAS OFAPPLICATION

In the negative temperature range, thermocouples can be used down to -200C. For temperatures above 1000 C, thermocouples made of platinum and aplatinum/rhodium alloys are used.

Advantages of thermocouples are:

• Very high temperature ranges

• Fast response

• Compact design

• Extremely high resistance to vibration

• Long term stability

• Robust design

Thermocouples are used in the following, and other, industries:

• Chemical industries

• Pharmaceutical industries

• Power generation

• Mechanical engineering• Food & beverage

• Mining

• Iron and steel

• Ceramics and glass

Page 16: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 16/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

3-4

Page 17: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 17/26

Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.rosemount.com

Section 4 Assembly of Housing

Rules and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

Stress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

Housing Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

Ceramic Housing Installation . . . . . . . . . . . . . . . . . . . . . . page 4-2

Connection of Transmitters . . . . . . . . . . . . . . . . . . . . . . . . page 4-2

RULES ANDINSTRUCTIONS

For housing assembly, please use the following instructions.

VDE/VDI 3511Technical temperature measurement/instruction

VDE/VDI 3512Set-up for temperature measurements

AD - instruction leaflets(1)

Working group pressure vessels

TRB - technical directions for tank construction(1)

Vd - TDV regulations(1)

Stress The stresses indicated in the drawing apply to the supplied housing. The loaddata, included in the standards for every type, are valid for housing accordingto DIN 43763 and DIN 43772.

Torque Starting torques for screw-in type threads

Applicable to screw-in type threads according to DIN 43763 and DIN 43772as well as comparable housing according to customer’s specifications.

Above starting torques are to be used as well for coupling rings with similarthreads.

Housing Assembly Assembly of housing with flange mounting

The seal is to be selected according to the requirements. During insertion ofthe seal, a good support is necessary. Fastening screws are to be tightenedevenly and crosswise.

(1) To be considered in case of weld-in type tubes. Material, weld and pressure test according 

to operating conditions 

G 3 / 8, G 1 / 2 50 Nm

G 3 / 4 100 Nm

Page 18: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 18/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

4-2

Ceramic HousingInstallation

Installation of ceramic housing in plants at operating temperature

Temperature of the plant:

• 1600 C insertion speed: 1-2 cm/min.

• 1200 C insertion speed: 10-20 cm/min.

Connection ofTransmitters

When connecting transmitter, the installation-, connection, and testinstructions of the manufacturers are to be considered.

Page 19: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 19/26

Page 20: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 20/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

A-2

Page 21: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 21/26

Reference Manual00809-0301-2654, Rev BA

September 2009

B-1

RTD and Thermocouple

Appendix B Limit tolerances forThermocouples

Table B-1. Limit tolerances for thermocouples according DIN IEC 584-2

Class 1 2 3(1)

(1) Thermocouples and thermocouple wires are usually supplied with limited tolerances according to the table above valid for temperature range above of -40    C. The thermocouple limit tolerances of same material at temperatures below -40    C may be exceeded as stated for tolerance class 3 according to DIN IEC 584-2. Thermocouples requested by purchaser with limit tolerances according to classes 1, 2, or 3 may be obtained by special material selection.

Limit tolerances(2)

(2) Limit tolerances for thermocouples are indicated in degrees centigrade or as percentage of the measured temperature in degrees centigrade. Whichever value is greater applies.

|t| = Temperature in degrees Centigrade 

0.5 C or 0.004 x |t| 1 C or 0.0075 x |t| 1 C or 0.015 x |t|

(a) Limit tolerances apply to following temperature ranges

Type T -40 C up to 350 C -40 C up to 350 C -200 C up to 40 C

Limit tolerances(2) 1.5 C or 0.004 x |t| 2.5 C or 0.0075 x |t| 2.5 C or 0.015 x |t|

() Limit tolerances apply to following temperature ranges

Type E -40 C up to 800 C -40 C up to 900 C -200 C up to 40 C

Type J -40 C up to 750 C -40 C up to 750 C --

Type K -40 C up to 1000 C -40 C up to 1200 C -200 C up to 40 C

Limit tolerances(2) 1 C or [1+9t-1100) x 003] C 1.5 C or 0.0025 x |t| 4 C or 0.005 x |t|

() Limit tolerances apply to following temperature rangesType R and S 0 C up to 1600 C 0 C up to 1600 C --

Type B -- 600 C up to 1700 C 600 C up to 1700 C

Page 22: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 22/26

Reference Manual00809-0301-2654, Rev BA

September 2009RTD and Thermocouple

B-2

Page 23: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 23/26

Reference Manual00809-0301-2654, Rev BA

September 2009 RTD and Thermocouple

www.rosemountnuclear.com

Numerics

2-wire circuit  . . . . . . . . . . . . . 2-33-wire circuit  . . . . . . . . . . . . . 2-34-wire circuits  . . . . . . . . . . . . 2-3

Aaccuracy  . . . . . . . . . . . . . . . . 2-4AD - instruction leaflets . . . . . . 4-1

Bbasic values  . . . . . . . . . . . . . A-1

C

ceramic 

. . . . . . . . . . . . . . . . . 2-1ceramic substrate  . . . . . . . . . 2-1ceramic tube  . . . . . . . . . . . . . 3-3chemical attack  . . . . . . . . . . . 3-2color-coded  . . . . . . . . . . . . . . 3-2compact dimensions . . . . . . . . 2-1compensating cable  . . . . . . . . 3-1Compensating cables  . . . . . . . 3-2compensating leads  . . . . . . . . 3-2conductors  . . . . . . . . . . 2-1, 3-1Considerations  . . . . . . . . . . . 2-2

Environmental  . . . . . . . . . 2-4contact-making temperature sensors 

2-2

coupling rings 

. . . . . . . . . . . . 4-1

Ddesign  . . . . . . . . . . . . . 2-4, 3-3DIN 43763 . . . . . . . . . . . . . . . 4-1DIN 43772 . . . . . . . . . . . . . . . 4-1DIN EN 60584  . . . . . . . . . . . . 3-2DIN IEC 584-2  . . . . . . . . . . . . B-1

Eelectrical interference  . . . . . . . 2-4electronic measuring unit  . . . . 3-1Environmental Considerations  . 2-4

Extension cables 

. . . . . . . . . . 3-2

FFastening screws . . . . . . . . . . 4-1function of temperature . . . . . . 2-1

G

galvanometer  . . . . . . . . . . . . 3-1glass  . . . . . . . . . . . . . . . . . . 2-1

Hhermoelectric voltage . . . . . . . 3-2higher resistance values  . . . . 2-1horizontal installation  . . . . . . . 3-3housing assembly  . . . . . . . . . 4-1

Iimmunity  . . . . . . . . . . . . . . . 2-4independent of temperature  . . 2-3installed vertically  . . . . . . . . . 3-3

LLimit tolerances . . . . . . . A-1, B-1load data  . . . . . . . . . . . . . . . 4-1

MMaximum temperature  . . . . . . 3-2measurement result . . . . . . . . 2-3measuring bridge  . . . . . . . . . 2-3measuring elements  . . . . . . . 2-2measuring junction  . . . . . . . . 3-1Measuring Principle  . . . . . . . . 2-1mechanical damage  . . . . . . . 2-2

mechanical forces  . . . . . . . . . 3-2metallic protective mounting  . . 3-3mV . . . . . . . . . . . . . . . . . . . . 3-1

Nnegative conductor  . . . . . . . . 3-3negative lead  . . . . . . . . . . . . 3-3

Pplatinum  . . . . . . . . . . . . . . . . 2-1platinum coil wound  . . . . . . . . 2-1platinum thermocouples  . . . . . 3-3platinum/rhodium alloys  . . . . . 3-3

positive lead  . . . . . . . . . . . . . 3-3positive pole  . . . . . . . . . . . . . 3-3positive terminal  . . . . . . . . . . 3-3Precious metal thermocouples  3-3protective mounting  . . . . . . . . 3-2protective tubes . . . . . . . .2-2, 3-3Pt 100 resistance thermometer  2-1

R

reference junction  . . . . . . . . . .3-1replacement  . . . . . . . . . . . . . .2-2Resistance . . . . . . . . . . . . . . .2-4resistance  . . . . . . . . . . . . . . .2-3resistance temperature detector 2-1Resistance thermometer modules 2-2resistance thermometers  . 2-1, 2-2response  . . . . . . . . . . . . . . . .3-3

Sscrew-in type threads  . . . . . . .4-1seal . . . . . . . . . . . . . . . . . . . .4-1semiconductors  . . . . . . . . . . .2-1

SpecificationsHART and Foundation Fieldbus 

A-1stability  . . . . . . . . . . . . . 2-4, 3-3standards . . . . . . . . . . . . . . . .4-1support  . . . . . . . . . . . . . . . . .3-3

TTemperature  . . . . . . . . . . . . .2-1temperature coefficient  . . . . . .2-1Temperature Measurement  . . .3-1Temperature measurement  . . .2-1temperature potential  . . . . . . .3-3temperature range  . . . . . . . . .2-4thermocouple  . . . . . . . . . . . . .3-1thermocouple,  . . . . . . . . . . . .3-2Thermocouples  . . . . . . . . . . .3-1TRB - technical directions for tank

construction  . . . . . . . . . . . . . .4-1

VVd - TDV regulations . . . . . . . .4-1VDE/VDI 3511  . . . . . . . . . . . .4-1VDE/VDI 3512  . . . . . . . . . . . .4-1vibration . . . . . . . . . . . . . . . . .3-3voltage  . . . . . . . . . . . . . . . . .3-1

Wwire material  . . . . . . . . . . . . .3-1

Index

Page 24: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 24/26

Reference Manual00809-0301-2654, Rev BA

September 2009

Index-2

RTD and Thermocouple

Page 25: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 25/26

Page 26: Thermo Couples

8/9/2019 Thermo Couples

http://slidepdf.com/reader/full/thermo-couples 26/26

Emerson Process Management

Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale.The Emerson logo is a trademark and service mark of Emerson Electric Co.Rosemount, the Rosemount logotype, and Hot Backup are registered trademarks of Rosemount Inc.HART is a registered trademark of the HART Communication Foundation.F OUNDATION is a trademark of the Fieldbus Foundation.PlantWeb is a registered trademark of one of the Emerson Process Management companies.

Teflon is a registered trademark of E.I. du Pont de Nemours & Co.All other marks are the property of their respective owners.

Reference Manual00809-0301-2654, Rev BA

September 2009