Urban Acoustics

Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks or the Softwood Lumber Board.

Steve(n) Thorburn, PE, LEED AP, CTS-I, CTS-D [email protected], TECHNOLOGY, AND LIGHTING DESIGNHORBURN ASSOCIATES

Page 2: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

“The Wood Products Council” is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES), Provider #G516.

Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.

This course is registered with AIA CESfor continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.

______________________________

Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Page 3: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

As with any issue of building performance, the acoustics of a mixed-use wood-frame

structure can be designed to meet or far exceed minimal requirements. It is the

responsibility of the design team to determine acoustical expectations for the project and

meet them within the available budget.

Through the use of case studies, this fast-paced, interactive session will explore how multi-

story wood systems can be used to meet acoustical privacy goals. Discussion will focus on

the detailing and construction of units, and how consideration of the construction process

can help keep acoustical costs down.

With the objective of providing implementable solutions, the session will include

construction details and photos showing what has and hasn’t worked in actual buildings.

Steve(n) Thorburn, PE, LEED AP, CTS-I, CTS-D, Thorburn [email protected]

Urban Acoustics – Course Description

Page 4: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

At the end of this program, participants will be able to:

- Evaluate the acoustical impact of ICC Building Code vs. Residential Expectations

- Develop cost effective / acoustically centric space planning ideas for wood frame design

- Produce practical and constructible acoustical isolation detailing for wood frame design

- Identify common acoustical compromises during construction

Page 5: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Copyright Materials

This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is

prohibited.

© Thorburn Associates Inc.

Page 6: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 7: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 8: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 9: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 10: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Mixed Use

Page 11: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 12: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban AcousticsThe Building Code

Page 13: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Our Goal Control the Transfer of Noise!

Page 14: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Slide 16

Acoustical Expectations

Luxury? Market Rate? Entry Level?

Page 15: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Entry Level HousingSTC 50 / IIC 50 (STC /IIC 48)*

Market Rate HousingSTC 55 / IIC 55 (STC/IIC 52)*

Luxury Rate HousingSTC 60+ / IIC 60+ (STC/IIC 55)*

IIC 60+ very hard to achieve with wood or tile surfaces

* Actual 1962 values – adjust when IBC set “50” as minimum

FHA Rules of Thumb from 1962NOTE THIS IS NOT A CODE, IT HAS BECOME the DE FACTO STANDARD BUT NOT CODE

Page 16: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

ICC G2 2010 Guideline for Acoustics

Acceptable Performance“Grade B Performance”

55 / 52(Laboratory / Field)

Airborne - STC / NNICImpact - IIC / NISR

Preferred Performance“Grade A Performance”

60 / 57 (Laboratory / Field)

Airborne - STC / NNICImpact - IIC / NISR

STILL NOT A CODE, IT IS FROM THE ICC –FROM WHAT APPEARS TO BE A RESEARCH PAPER FROM THE INTERNET!

Page 17: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Exterior to Interior

Page 18: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Land Use Compatibility For Community Noise

Exterior Day/Night Noise Levels (Ldn, dBA)Land Use Category

Single Family

Multi Family

Motel, Hotels

Outside Use

55 60 65 70 75 80

NormallyAcceptable

ConditionallyAcceptable

NormallyUnacceptable

ClearlyUnacceptable

Page 19: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Mixed Use – Bar to Housing

Page 20: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Not Addressed by Building Code- Implied at 45 dBA /Ldn

(Interior Noise Criterion)- Enforced as Nuisance Complaints- Enforced by “Local Codes”

THIS IS CHANGING – THE IgCC IS PLACING LIMITS ON

COMMERCIAL TO RESIDENTIAL

Commercial to Residential

Page 21: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban Acoustics Vocabulary

Page 22: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Terms (They Are Changing!)

SoundSTCFSTC NIC

ASTCNNIC

ImpactIIC

FIICAIICNISR

GeneralNRdBALdn

CNELOITC

NC NRC

Page 23: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban Acoustics - Vocabulary

Page 24: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Test Laboratory

Page 25: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Test Chamber

Page 26: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

STC vs ASTC (NIC, FSTC)

STC Testing ASTC Testing

Page 27: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

IIC vs AIIC (FIIC)

IIC Testing AIIC Testing

Page 28: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

How STC or IIC Rating Is Found

7 8 10 9 86 4 3

3

2

GOAL STC 50

MEASURED

Page 29: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

How STC or IIC Rating Is Found

6 7 9 8 75 3 2

2

1

NOW STC 49

MEASURED

Page 30: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

How STC or IIC Rating Is Found

5 6 8 7 64 2 1

1

NOW STC 48

MEASURED

Page 31: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

How STC or IIC Rating Is Found

4 5 7 6 5 3 1

NOW STC 47

MEASURED

Page 32: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Detailing is Systems

Page 33: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban Acoustics Acoustical

Wall Systems

Page 34: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Detailing – The Givens• Walls are Full Height

(Deck to Deck)• Insulated (Unfaced Batt)

In all Stud or Joist Cavities• Sealed Air Tight• Floor Sheeting

Is Glued and Screwed

Page 35: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Wall Progression – Sound Isolation

STC 34 STC 38 STC 45

Page 36: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Wall Progression – Sound Isolation

STC 50 STC 63 STC 49

Page 37: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Metal Channels

Hat ChannelsAre Not

Acoustical Channels

Resilient ChannelsAre

Acoustical Channels

Page 38: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Slide 40

Page 39: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Hat Channel Resilient Isolators

Page 40: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Hat Channel Resilient Isolators

Page 41: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Lot Line Wall – Sound Isolation

Page 42: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban AcousticsAcoustical

Floor / Ceiling SystemsSound and Impact

Page 43: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

STC 37

Page 44: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

STC 43

Page 45: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

STC 49

Page 46: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems – Topping Slab

Gypcreteor

Light Weigh Concrete

Page 47: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

STC 56

Page 48: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

STC 62

Page 49: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

Batt insulation not show for clarity

Page 50: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

Batt insulation not show for clarity

Page 51: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

Batt insulation not show for clarity

Page 52: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Floor Systems

Batt insulation not show for clarity

Page 53: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Independently Framed Ceiling System

Page 54: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Impact Noise

Page 55: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

The Tapper

Page 56: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

The Tapper

Page 57: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Impact Isolation

• Impact noise changes as it travels in the building.• Impact noise is best controlled at the source.

Page 58: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Effects of Floor Covering on Impact Isolation

Batt insulation not show for clarity

IIC 73 IIC 64 IIC 56 IIC 43 IIC 32

STC 56

Page 59: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

70+

Page 60: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

70+

ACOUSTICALLY STILL REALLY NEW

We Need More Test Data

In absence of test data we compare to known acoustical systems

Page 61: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

"Volume generally assumed for the density of hardened concrete is

150 lb./ft3. (2400 kg/m3)“

McGraw-Hill Encyclopedia of Science and

Technology.

Page 62: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

6 inch thick 20 lb./ft3. CLTSame Mass as

1.6 inch thick Concrete

Based on AcousticsMass Law STC Rating

about 38 STC

Page 63: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

Page 64: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Cross-Laminated Timber

70+ IIC 35

Page 65: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban Acoustics Leaks - Doors and Windows

Page 66: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Slide 68

Leaks: Where air can flow... ...so will sound.

Page 67: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Air Tight Seal

Page 68: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Batt Insulation

Page 69: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Blow In Insulation

OPEN CELL FOAMCLOSED CELL FOAMCELLULOUS / FIBER

Page 70: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Rigid “Foam” Insulation

Page 71: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban Acoustics Other Issues to Consider

Page 72: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Fiction!• Fiber Board

Page 73: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Acoustical Fiction!• Trapped Channel

Page 74: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Trapped Air Space and Screws

STC 55

STC 38

Page 75: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Installation Issues - RC

Page 76: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Plumbing Isolation

Page 77: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Other Noise Issues

Page 78: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Condominium Noise

Page 79: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Now We See the Problem

Page 80: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Installation Issues - RC

Page 81: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Installation Issues - RC

Page 82: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Slide 84

Page 83: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Slide 85

Page 84: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Sprinkler Lines / Heads

Page 85: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 86: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

RESILIENT CEILING SYSTEMS

Page 87: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Duct Work

Page 88: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

HOLES IN SYSTEMS

Page 89: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Recessed Light Fixtures

Page 90: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

RESILIENT CHANNELS INSTALLATION

Page 91: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Framing Issues

Page 92: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Framing Issues … (ok Plumbing)

Page 93: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

ACOUSTICAL GYPSUM BOARD

Page 94: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

DAMPING

Page 95: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

OMG!

THIS IS VERYBAD! DO NOTBELIEVE THE INTERNET!

Page 96: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

OMG!

THIS IS VERYBAD! DO NOTBELIEVE THE INTERNET!

Page 97: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

OMG!

Page 98: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

When it comes to AcousticsOnly Believe Real Laboratory

Test Data or Someone you Pay and can Sue!

Page 99: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

This concludes The American Institute of Architects Continuing Education Systems Course

QUESTIONS?

Steve(n) Thorburn, PE, LEED AP

Thorburn Associates Inc.

[email protected]

Page 100: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962
Page 101: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962

Urban AcousticsThank You!!!