Titel des Vortrages01/2007

The following slides explain the commissioning of a FRONIUS IG inverter.

Please note that each slide is provided with sound. Please switch on your loudspeakers and press the keys at the bottom of each slide to proceed.

Page 2: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

Mount the FRONIUS IG on the wall

First, mount the wall bracket. Hang the FRONIUS IG Inverter on it. Fix the inverter to the wall bracket

with the 2 screws on the bottom. For multiple inverter systems,

please provide an air space between

inverters of at least 6 inches.

Page 3: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

Open up the Faceplate

Open up the 4 screws of the faceplate in order to get into the connection area.

Please remove the display ribbon cable carefully.

Page 4: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

Electrical Installation - DC

Make sure that both internal disconnects are in the off (down) position.

Connect DC positive to the left and DC negative to the right on the DC Terminal block as shown.

After tightening the screws to fix the cables in place, measure to verify that the DC voltage is between 150V and 500 Volts.

Please check the polarity*

*Reverse polarity may damage the inverter.

FRONIUS warranty doesn´t cover damage caused by inappropriate installation.

Page 5: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

Electrical Installation - AC

Make sure that both internal disconnects are in the off (down) position.

Connect phase 1 to the left side of the AC disconnect as shown.

Connect phase 2 to the right side of the AC Disconnect.

After tightening the cables, please measure and verify the AC voltage* on the lower screws of the AC disconnect.

*The AC voltage should be between 215V to 260V

for the 240V units and between 185V and 225V for 208V units.

Page 6: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

Close the Faceplate

Connect the ribbon cable of the display carefully to the inverter.

Tighten the 4 screws in order to mount the faceplate.

Turn the internal DC and AC disconnects on (up). If the DC breaker trips open or if the display does not light up, turn the unit off and check for reverse polarity on the DC inputs.

Page 7: Titel des Vortrages 01/2007 The following slides explain the commissioning of a FRONIUS IG inverter. Please note that each slide is provided with sound

© Fronius 01/2006Commissioning a FRONIUS IG inverter

FRONIUS technical support

For more information please don’t

hesitate to contact

FRONIUS technical support

phone: 810 220 4414

fax: 810 220 4424

[email protected]

www.fronius-usa.com