48
CHAPTER 1. SPECIFICATION [1] SPECIFICATION ........................................... 1-1 [2] EXTERNAL DIMENSION .............................. 1-2 [3] WIRING DIAGRM ......................................... 1-3 [4] ELECTRICAL PARTS ................................... 1-3 CHAPTER 2. EXPLAMATION OF CIRCUIT AND OP- ERATION [1] BLOCK DIAGRAMS ...................................... 2-1 [2] MICROCOMPUTER CONTROL SYSTEM ........ 2-3 [3] FUNCTION.................................................... 2-8 CHAPTER 3. FUNCTION AND OPERATION OF PRO- TECTIVE PROCEDURES [1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS ............................................... 3-1 [2] AIR CONDITIONER OPERATION IN THERMISTOR ERROR ................................ 3-3 [3] THERMISTOR TEMPERATURE CHAR- ACTERISTICS .............................................. 3-5 [4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY ............................... 3-6 [5] GENERAL TROUBLESHOOTING CHART ........ 3-6 [6] MALFUNCTION (PARTS) CHECK METH- OD ................................................................. 3-8 [7] OUTDOOR UNIT CHECK METHOD........... 3-10 [8] TROUBLESHOOTING GUIDE .................... 3-13 CHAPTER 4. REFRIGERATION CYCLE [1] FLOW FOW REFRIGERANT ........................ 4-1 [2] STANDARD CONDITION .............................. 4-1 [3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE ...................... 4-1 [4] PERFORMANCE CURVES........................... 4-2 REPLACEMENT PARTS LIST SERVICE MANUAL CONTENTS Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the safety and performance of the set. This document has been published to be used for after sales service only. The contents are subject to change without notice. TopPage AYXP9FRN SPLIT TYPE ROOM AIR CONDITIONER INDOOR UNIT AY-XP9FR-N OUTDOOR UNIT AE-X9FR-N MODELS In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used.

TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

CHAPTER 1. SPECIFICATION[1] SPECIFICATION............................................ 1-1[2] EXTERNAL DIMENSION............................... 1-2[3] WIRING DIAGRM .......................................... 1-3[4] ELECTRICAL PARTS .................................... 1-3

CHAPTER 2. EXPLAMATION OF CIRCUIT AND OP-ERATION[1] BLOCK DIAGRAMS....................................... 2-1[2] MICROCOMPUTER CONTROL SYSTEM........ 2-3[3] FUNCTION..................................................... 2-8

CHAPTER 3. FUNCTION AND OPERATION OF PRO-TECTIVE PROCEDURES[1] PROTECTION DEVICE FUNCTIONS AND

OPERATIONS................................................ 3-1[2] AIR CONDITIONER OPERATION IN

THERMISTOR ERROR ................................. 3-3[3] THERMISTOR TEMPERATURE CHAR-

ACTERISTICS ............................................... 3-5

[4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY ...............................3-6

[5] GENERAL TROUBLESHOOTING CHART........3-6[6] MALFUNCTION (PARTS) CHECK METH-

OD .................................................................3-8[7] OUTDOOR UNIT CHECK METHOD...........3-10[8] TROUBLESHOOTING GUIDE ....................3-13

CHAPTER 4. REFRIGERATION CYCLE[1] FLOW FOW REFRIGERANT ........................4-1[2] STANDARD CONDITION..............................4-1[3] TEMPERATURE AT EACH PART AND

PRESSURE IN 3-WAY VALVE ......................4-1[4] PERFORMANCE CURVES...........................4-2

REPLACEMENT PARTS LIST

SERVICE MANUAL

CONTENTS

Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining thesafety and performance of the set.

This document has been published to be used forafter sales service only.The contents are subject to change without notice.

TopPage

AYXP9FRN

SPLIT TYPEROOM AIR CONDITIONER

INDOOR UNIT

AY-XP9FR-NOUTDOOR UNIT

AE-X9FR-N

MODELS

In the interests of user-safety (Required by safety regulations in somecountries) the set should be restored to its original condition and onlyparts identical to those specified should be used.

Page 2: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

AYXP9FRN Service Manual CHAPTER 1. SPECIFICATION

[1] SPECIFICATION

1. AY-XP9FR-N – AE-X9FR-N

NOTE: The condition of star”✩” marked item are ‘ISO5151’ : 1994(E), contition T1.

MODEL INDOOR UNIT OUTDOOR UNITITEMS AY-XP9FR-N AE-X9FR-NCooling capacity(Min. > Max.) kW 2.50 (0.9 - 3.0)Heating capacity(Min. > Max.) kW 3.20 (0.9 - 5.0)Moisture removal(at cooling) Liters/hElectrical dataPhase SingleRated frequency Hz 50Rated voltage V 230Rated current ✩(Min - Max.)

Cool A 2.8 (0.8 - 3.8)Heat A 3.4 (0.7 - 5.9)

Rated input ✩(Min - Max.)

Cool W 540 (150 - 750)Heat W 700 (130 - 1300)

Power factor ✩ Cool % 84Heat % 90

Compressor Type Hermetically sealed rotary typeModel 5RS092XDFOil charge 320cc (RB68A or Freil Alphc 68M)

Refrigerant system Evaporator Louver Fin and Grooved tube typeCondenser Corrugate Fin and Grooved tube typeControl Expansion valveRefrigerant (R410A) 1000gDe-lce system Micro computer controled reversed systems

Noise level(at cooling)

High dB(A) 42 46Low dB(A) 37 –Soft dB(A) 26 –

Fan systemDrive Direct driveAir flow quantity(at cooling)

High m3/min. 10.3 28.1Low m3/min. 8.2 –Soft m3/min. 5.1 –

Fan Cross flow fan Propeller fanConnectionsRefrigerant coupling Flare typeRefrigerant tube size Gas, Liquid 3/8", 1/4"Drain piping mm O.D φ18OthersSafety device Compressor: Thermal protector

Fan motors: Thermal fuseFuse, Micro computer control

Air filters Polypropylene net (Washable)Net dimensions Width mm 790 780

Height mm 278 540Depth mm 198 265

Net weight kg 10 37

1 – 1

Page 3: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[2] EXTERNAL DIMENSION

1. Indoor unit

2. Outdoor unit

278

198790

22.0

58 18.5

175

INVERTER AIR CONDITIONER

265

780

540

14

165

540

299

72

58

37.512 4.5

324

135

81 136

1 – 2

Page 4: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[3] WIRING DIAGRM

1. Indoor unit

2. Outdoor unit

[4] ELECTRICAL PARTS

1. Indoor unit

2. Outdoor Unit

DESCRIPTION MODEL REMARKSIndoor fan motor MLB084 DC MotorIndoor fan motor capacitor – –Transformer – –FUSE1 – QFS-GA062JBZZ (250V, 3.15A)FUSE2 – QFS-GA063JBZZ (250V, 2A)

DESCRIPTION MODEL REMARKSCompressor 5RS092XDF D.C. brush-less motorOutdoor fan motor ML-A902 DC MotorOutdoor fan motor capacitor – –Fu4 – QFS-GA064JBZZ(250V, 1A)Fu3 – QFS-GA051JBZZ(250V, 2A)Fu2 – QFS-GA052JBZZ(250V, 3.15A)Fu1 – QFS-CA001JBZZ(250V, 20A)Fu5, 6 – QFS-CA002JBZZ(250V, 15A)

1 – 3

Page 5: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

AYXP9FRN Service Manual CHAPTER 2. EXPLAMATION OF CIRCUIT AND OPERATION

[1] BLOCK DIAGRAMS

1. Indoor unit

Louvre motor drive circuit(upper)

Louvre motor drive circuit(lower)

LED drive circuit

Flow direction control (louver motor upper)

Flow direction control (louver motor lower)

LED display

AC powerRectification circuit

CPU

SubCPU

3.15AFuse

Serial signals

2AFuse

DC power supply circuit

Fan motor PWM control circuit

Rotation pulse input circuit

AC clock circuit

Remote controller signal reception circuit

Buzzer drive circuit

CPU reset circuit

CPU oscillator circuit

Room temp. detect circuit

Heat exchanger pipe thermo circuit

EEPROM

Select circuit

Serial I/O circuit

Power supply relay drive circuit

Auto restart circuit

Test run circuit

Auxiliary mode

Power on circuit

Cluster generator drive circuit

Indoor fan motor

Fan motor pulse detect

Wireless remote control operation

Audible operation confirmation

Room temp. thermistor

Heat exchanger pipe thermistor

Louvre angle, fan speed

Wireless, preheat, Model select

Indoor/outdoor control signal I/O

Outdoor unit power supply on/off control

Test run (forced operation)

Auxiliary mode button ON/OFF

Self diagnostics, fault diagnosis

Cluster generator

Unit-unit wiring(AC power andserial signals)

2 – 1

Page 6: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2. Outdoor unit

CPU

20Aprotection

15Aprotection

Expansion valve drive circuit Expansion valve

Suction temp. thermo. circuit Suction pipe thermistor

2-way valve temp. thermo. circuit 2-way valve thermistor

3.15Aprotection

15Aprotection

Power supply circuit

CPU oscillator circuit

DC overvoltage detection circuit

Outdoor fan drive circuit

4-way valve relay drive circuit

Power transistor module drive circuit

Serial I/O circuit

CPU reset circuit

Position detection circuit

AC overcurrent detection circuit

Compressor thermo circuit

Heat exchanger pipe thermo circuit

Outdoor temp. thermo. circuit

LED drive circuit

Test mode circuit

Power factorconverter circuit

Filtercircuit

Smoothingcircuit

Pulse amplitube modulation circuit

EEPROM

AC clock circuit

DC overcurrent detection circuit

IGBT

Unit-unit wiring (AC powerand serial signals)

Outdoor fan

4-way valve

Power transistor module

Compressor

Current transformer

Compressor thermistor

Heat exchanger pipe thermistor

Outdoor temperature thermistor

LED

2 – 2

Page 7: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[2] MICROCOMPUTER CONTROL SYSTEM

1. Indoor unit

1.1. Electronic control circuit diagram

0.1μC 50

V

JPF

54

21

54

21

4.7KRN

2.4K5V 10.0KFR96

JPT

9 10 11 12

CIR

CU

ITD

IAG

RAM

DIS

PLAY

PWB

LOU

VER

MO

TOR

TOP

LOU

VER

MO

TOR

BOTT

OM

DR

AIN

PAN

ASS'

Y

MO

TOR

FAN

DC

AUX.

SW1

(TES

TR

UN

)

PIPE

THER

MO

TEM

PTH

ERM

O

POW

ERO

N

10K

R52

(HA

CIR

CU

IT)

AUTO

RES

TAR

T

PREH

EAT

WIR

ELES

S

HO

TKE

EP

FLAS

H

TEST

SUB

MIC

RO

CO

MPU

TER

PWB

REC

EIVE

RPW

B7

-SEG

LED

&

REM

OTE

CO

NTR

OLL

ER SIG

NAL

SER

IAL

SIG

NAL

S

OF

SER

IAL

ERR

OR

SIG

NAL

SUB

MIC

RO

CO

MPU

TER

POW

ERSU

PPLY

OF

12V

LIN

EG

ND

for

GN

Dfo

r5V

LIN

E

CO

NN

ECTO

RO

FJO

INT

(DR

AIN

PAN

)

CO

NN

ECTO

RO

FJO

INT

(FAN

MO

TOR

)

33

98

76

101

23

45

8

R4156k

5V

23 1

4 32

R38100k

C1835V100μ

R39

ZD2HZ24-2

41 4.7k

D1N60D7

R37 RD

4

21

30.

1μC42

25V

12V

R44

1.8k

1/4W

C2116V47μ

R70

Q3

KRC

108S

4.7k

4.7k

(SER

IAL

I/OC

IRC

UIT

)

KRA1

01S

Q11

5V

5VJP

H

R53

JPO

10K

ACC

LOC

K

25V

R90

R55

FU1

3.15

A-2

50V

C57

R85

10K

50V

1000

p

C20250V0.01μ

5V

JPS

470μ

D2S

6M

MQ

R27

10K

10k

R71 1k

1k

R336.8k

8.2k

680

PC5

R34

6.8k

89

5V

12V

87654321

86

75

43

21

1 3 5 7 9

2 4 6 8 10

1112

1 3

5VVs

VccPG

GN

DVm

3 12577 5 2 13

3 1257

PC3

BCN

5

BCN

1 PC81

716P

1210

111

23

45

67

89 9

87

65

43

21

1110

1210

111

23

45

67

899

87

65

43

21

1110

7654321

BCN

7

KRC

102S

Q15

PC1

PC81

7XP3

C16

50V

0.01

μ

10K

R16

275V

0.01

μ

C23

2.7K

RH

RE

R76

100

1W

SSR

12V

2W11K

2W11K

PC2

PC85

3HXP

2W680

680 2W

2W680

680 2W

2W680

D8

D1N

60R

GR

40R

BR

CR

A

C14275V0.1μ

NF1

NR1

200K

200K 39

K

D3

D1N

60

1/2WR26

1/2WR25 R24

C45275V0.1μ

E25

0V47

00p

C53

~C56

C54

C53

C56

C55

CN

801

23

4

BUSY

7654321 8

VPP

VCC

SCL

SDA

OE

RES

ET

9VS

S

5V

321

C90

HAJ

P

4

CN

90R

92

R91

100kR93

1000

p50

V

5V

5V

100μ

C350V

R95

4.7K

R69100K

R684.7K

100μ

DC

15V

D2S

BA60

5V

C2425V

0.1μR

46

DB1

C1

3.3

450V120μ

1M

R2 RF1/2W

1M1/2W

4 321

5V

PC81

7XP3

3.3KR66

100KR73

35VC46

25VC50

0.1μ

0.1μ50VC47

R28

R31

56k

2A-2

50V

142

3

14

5V

FU2

5WR1

47kR67

10kR50

0.1μC

5225

VC

37

0.1μ25

V

5V

JPW

JPP

R87

R86

10K

10K

C26

4.7μ

IC2

RES

ET

0V

ZD1

ST03

D-2

00

5V

1/4W

100

R561/4W

100

R51

C39

16V

0.01

μ

C36

0.01

μ16

V

10K

10K

10K

CN

4

R58

R54

R59

10.0KF

16V10μC31

R61

16V10μC30

R60

34TH

1

12TH

2

321

5V

21

4 3

D1F

S4

0.1μ50

VC4

C44

220μ

10V

C7

470μ

10V

25V

C43

12V IC9

10μHL1

D14 D

1

TR1

6 5 4 3 2 1 4

34

12

IC108

765

EEPR

OM

R97

5V

R47

3

3.3k 2

R29

PC4

R32

C17

0.01μ16V

IC1

64636261605958575655545352515049 P37

P36P35P34P33P32P31P30VCC

VRVSSP67P66P65P64P63

P00

P01

P02

P03

P04

P05

P06

P07

P10

P11

P12

P13

P14

P15

P16

P17

3348 47 46 45 44 43 42 41 40 39 38 37 36 35 34

P20P21P22P23P24P25P26P27VSSXOUXINP40P41RSTVSSP42

20212223242526272829303132

191817

P43

P44

P45

P46

P47

P50

P51

P52

P53

P54

P55

P56

P57

P60

P61

P62

161 2 3 4 15141312111098765

R35

10k 5V

R36

C22

PC81

7XP3

R30

16V0.01μ

4.7K

1000

p50

VC

32

5V

KRC

102S

Q19

C2510V

100μ

C27

16V

0.01

μ4.

7kR

45

R94

5V

10k

R48

C331

3

2OSC

1 8MH

z

KRC

108S

Q1

10.0KF

1 N1 3 65

N S

321

5 6

CN

A

3112

V

IN

RY1

(CLU

STER

)C

ON

NEC

TOR

OF

JOIN

TO

UT

N12

R191/2W470K

R19A1/2W470K

3W11

K3W 11K

C98

C99

1KV

1000

pC

98,C

99

KID

6500

4AF

12V

C1950V0.047μ

IC6

BZ

GEN

ERAT

OR

CLU

STER

4.7K

33p

2KV

RM

1500

p

10KF

15V

100p

F

15KF

1.5KR10

1000

0pM

R17

12

680

PC81

7XP3

PC9

4.7K

R4

3.3KR75

910

1/4WR20

1/4WR23

910

R22

R3

R65

R5

ZD5

C12

50VC5

50VC2

100μ

D2

D1F

L20U

D1F

L20U

C35

IC3

1 2

5 34

R7 10

00p

50VC40

10K

D1F

L20UD

15

D21

KRA1

06S

IC7

R57

D20

D1F

L20U

Q9

PC81

7XP3

1KR81

2.4K

FR8

2.4K

FR11

R80

PC6

1KR9

PC817XP3

R6

100K

PC81

7XP3

R13

100K

PJ43

1CT

250VC48

PC6

PC7

R17

1K

R984.7K

R89 1K

100V

1.2K

C49

11KF

30KF

L2KI

A781

5API

1SR

139D

2 – 3

Page 8: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

1.2. Display circuit diagram

12V

KID

6500

4AF

M5V

M5V

M5V

M5V

7654321

10 111 2 3 4 5 6 7 8 9

12V

12V

5V

KID

6500

4AF

CN

103

CN

102

IC10

5

IC10

6

CN

101

IC10

4

13

28M

Hz

P30

19P3

120

P32

21P3

322

P34

23P3

524

P36

25P3

726

P00

27P0

128

P02

29P0

330

P04

31P0

532

P06

33P0

734

P10

35P1

136

Vss

18Xo

ut17161 2 3 4 15141312111098765

P12

P13

P14

P20

P21

P22

P23

P24

P25

P26

P27

Vref

RES

ETC

NVs

sVc

cXi

n

IC10

1M

3754

2

OSC

101

0.1μ25

VC

101

C10

2

4.7μ

IC10

2

0.1μ25V

C10

3

C10

416

V47

μ

IC10

3

KID

6578

3AF

R10

1

R10

2

R10

3

R10

4

R10

5

R10

6

R10

71W18

0*7

FLASH

4.7KR115

4.7K

R10

8

R11

810

KR

116

100K

KRA1

06S

KRC

106S

KRA1

06S

R109

R113R110

R114

1/4W

1.2K

*4

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

101

102

103

104

105

106

107

108

109

110

PC

CN

105A

CN

104B

CN

104A

a b c d e f g

SG20

1

Q10

2Q

101

Q10

4

KRC

106S

Q10

3

CN

105B

CN

105C

1 2 3

25V

R20

147

IC20

1

REC

EIVE

RC

IRC

UIT

SUB

MIC

RO

CO

MPU

TER

PWB

CIR

CU

ITD

AIG

RAM

12345

LOU

VER

MO

TOR

BOTT

OM

LOU

VER

MO

TOR

TOP

SER

IAL

SIG

NAL

S

REM

OTE

CO

NTR

OLL

ERSI

GN

ALS

ERR

OR

SIG

NAL

OF

SER

IAL

POW

ERSU

PPLY

OF

SUB

MIC

RO

CO

MPU

TER

5VLI

NE

GN

Dfo

r

12V

LIN

EG

ND

for

7-S

EGLE

D&

REC

EIVE

RPW

B

GN

Dfo

r12

VLI

NE

GN

Dfo

r5V

LIN

E

12V

LIN

EG

ND

for

12V

LIN

EG

ND

for

GN

Dfo

r12

VLI

NE

12V

LIN

EG

ND

for

JP1

GN

Dfo

r5V

LIN

E

DIS

PLAY

PWB

( )B L U E

SIG

NAL

SR

EMO

TEC

ON

TRO

LLER

GP1

U26

1RK

111B

(COM)5

(COM)10

7(A1)

6(B1)

4(C1)

1(D1)

3(E1)

8(F1)

9(G1)

2(H1)

7(A2)

6(B2)

4(C2)

1(D2)

3(E2)

8(F2)

9(G2)

2(H2)

c d e f g

JP2

0.22

μ50

VC

105

KRC

106S

Q10

5

1K

5V

R11

9

25V

C20

247

μ16

VC

201 0.1μ

+

C2

C1

H2

H1

B2B1

F2F1

E2E1

D2

D1

G2

G1

A2A1

a

b

c

d

e

f

g

g

f

e

d

c

b

a

RES

ET

987654321 12111010 11 121 2 3 4 5 6 7 8 9

10 9 8 7 6 5 4 3 2 1

543211 2 3 4 5

KID

6500

4AF

12V

12V

8

7

6

5

4

3

2

1

9

1 2 3 4 5 6 7 8

12V

5V

2 – 4

Page 9: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

1.3. Printed wiring board

2 – 5

Page 10: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2. Outdoor unit

2.1. Electronic control circuit diagram

9.53

KFR84

0V

Q10

0V

15V

0.01

μ

10V

47μ

6.8K

J

R85

C77

R86

C78

2A25

0VFU3

754321

0VC

N30.1μ40

0VC29

0V

5V

R83

10K

RY1

123456

0VIC

7

Ma

b

5V

10K

10K

0V

j

0V

JP1

JP2

c

JPF

0V10

C94

10V

C95 0.1μ

0.1μ

10K

R37

1K

R38

1K

R36

1K

0VUVW

C34C35C36

1000

Px

3

D7

D6

TR1

R29

4.7K

68

18V

-PC

850.

R82

680μ

C19

IC3

R27 1W

IC4

5V 0V

R22

25V

C20

R21

22K

R24

10K

R87

150μ

C84

D14

9

35V

0V-P

35V

R93

R94

R92

D20

C98

3

2

1R

78IC

5

C33

R77

50V

R79

100

0.1μ

C32

0V

QS

T

R

Q3

R S T9

Q

JP10

1 2 3 4 5 6 7 8

8

5 6 11 10

7

1K 10K

9

8

Q9

0V

2.2KR32R31

0V

R33

IC6

875 6

124 3

CN

E

5VR

30

4 3 12

4.7K

13V

CN

12

EXPA

NSI

ON

VALV

CO

IL

MR

Y1

13V

C38

0.1μ

24272322212818161315124 1079613

10K

R45

5V

100μC47

1000

PC

42

C48

10V

0.1μ

0V

IPM

330μ

25V

C37

100μ 25

VC

490.

25V

C51

0.1μ

C54

100μ 25

VC

530.

0.1μ

0.1μ

C55

0.1μC

57

C45

0.1μ

C56

D9

D10

100μC52D

8

C50

VWFB

VUFS

VUFB W

NVNUNWP

VPI

VWFSVP

I

VPI VP

VVFS

VVFBU

P

VNC F0VNI

C41

1000

P

1000

PC40

C43

1000

P

C44

1000

PC39

1000

P

1KR46

ZD4

16V

10μ

x5

C70

~74

10K

x5

R63

~67

0V

0VC

N8

1065432 7 980.

01μ

x5

C65

~69

5V

TH2

TH3

TH4

TH5

133

0KR

100

R10

7

PC4

330

Q7 KR

C10

5S

1000

PC

59

1/2W

R51

~53

IPM

c6 58

5WR49

2 3 TLP3

51

j

M

270K

DR

126

255K

F

250V

FU5

0.02

5V

15A

470K

Fx

3

CIN

CF0

262531

35

150

R11

0

250V

FU4

1Aj

1KV

C27

220P

FC

1550

V10

μ

R17

STR

-L47

2IC2

1/2W

1M

1/2W

1M

1/2W

1M

1

D5

1/2W

1M

1/2W

1M

1/2W

1M

R8

R9

R10

R11

R12

R13

3.3K

R20

2SA1

586G

Q1

ZD1

0V

470P

C17

R14

R18 1.5K

3300

PD

4

OC

P/FB

1~

48

710

96

Sour

ceG

ND

Dra

inVc

c

C18

680

R16

R15

C16

D15

1.6

1.6

3

D3

R19

15V

PC3

234

1

0.01

μC

81

R14

610

0K

e d 5V5V

FU2

R10

5

0V

22K

3.3K

R10

6

C83

1000

P

0.01

μC

82

Q6

KRC

102S

10V

C79

R91

R14

710

K

R90

D2 1.0K

F22

2.2K

R11

1

DB2

Q5

TER

MIN

ALBO

ARD N 1

WH

WH

GR

R89

0V

BLU

E

BRO

WN

YELL

OW

GR

EEN

/

T2 T1

1 2

L3L4

13

3 4

SA1

NR

1T4

R1

1/2W

1M

275V

1μF

275V

1μF C

2

42

1μF

275V

CT1

T6

510K

1/4W

R88

1/4W

510K

C1

C3

OU

TIN

PTC

MR

Y1G

RG

R

T5

DB1

18V

-P

4700pF250V

4700pF250V

4700pF250V

4700pF250V

R4

3.3K

D1

0.1μC13

1K2W2W 1K

1K2W

4700

P25

0VC

12

+42

0V42

0V+

3.15

A25

0V

R101

R102

R103

R104

1/2W

47K

x2

R10

1,10

2

1W47

Kx

2R

103,

104

T10

T11

PC81

716N

IP

5V

0VR

55

R56

R54

C60

0.1μ25

V

R99

100

0.1μC86

15K

R11

2

C61

50V

330P

330P

50V

C62

R57

100

R58

100

R59

100

C63

330P

50V

12

678910

0.1μC64

25V

114

35

IC8

KIA3

39

1

5V0V

0.01

μC

97

UV

NW5V

0VC88

1000

P

N1KR11

6

RY1

120

1/2W

0.03

NR

2

275V

CN

4

C26

R28

3 1de

D24

2R

EDT3

R12

910

K

T12 T13

250V 20A

FU1

R34

R35

JP16

5V

5V

0.1μC93

100μ10V

C30

5V

0V

JP9

JP8

JP7

32313029282726252423222120

1011

1213

1415

1617

1819

12

34

56

89

7

52535455565758596061626364

5150

4948

4746

4544

4342

4140

3938

3736

3534

33

P07

P10

P11

P12

P13

P14

P15

P16

P17

P20

P21

P22

P23

P24

P25

P26

P27

VSS

P30

(U)

P44

P45

P46

P50

P51

P52

P53

P54

P55

P56

P57

AVCC

AVR

AVSS

P60

P61

P62

P63

MD0

(B)

(O)

(Y)

(W)

IC1

RST

MD

1

MD

2

X1X0 VSS

P00

P01

P02

P03

P04

P05

P06

P31

P32

P33

P34

P35

VCC

CP36

P37

P40

P41

P42

P43

(X)

(V)

(Y)

(W)

(Z)

(U)

(V)

(W)

R13

310

0

R13

210

0

R13

710

0

R13

610

0

R13

510

0R

134

100

5V

5V

2.2K

R73

LED

1

10K

R15

510

KR

154

5V

(CN

)

41 2 3O

SC1

4MH

z

0V10

K10

K

20

JP17

N35

VNO

20.5

KF

20.5

KF

20.5

KF

0V

PS21

563

or21

564

FU6

250V

15A

1000

PC

46

0V

0V

C4A

C5A

C7A

C6A

R41

R42

R43

102W

2K

680P

6.8K

6.8K

270

270

15V

D11

6.8K

Fx

5R

68~

72

R47

,48

33x

21/

4W

1/4W

33x

2R

47A,

48A

5V

C (R)

S

(C)

R

FC3

FC4

YELL

OW

GR

EEN

/EA

RTH

U32

V33

W34

T7 T8 T9

N

FC1

FC2

FB

D12

D13

R611.8K

R601.8K

R621.8K

1.8KR115

R11

41M

14132

0V-P

D23

D22

D21

15V

0V0.

022μ

C58

ZD3

R50

1.8K

F

VALV

CO

IL

4-W

AY

PC1

PC81

7XP3

3 1

2.7K

R75

b

R74

a

1000

PC

75 0V

4.7K5V

R76

56K

41 2 4 3

2

PC85

3HXP

PC2

4.64

KFR26

R23

68K

C21

0.03

1.65

KFR25

1.5K

150μ

10K

10K

C23

0.1μ

7805

R81

10K

R14

4

C76

1000

P

5VQ

4

23.7

KF

23.7

KFR6

R7

R12

813

KFR

127

13KF

P0.

33μ

C14

630V

270K

D1/

2W

R12

51/

2WR

21/

2W 300K

F1/

2WR

5

750μ

C10

C9

750μ

(TH

ERM

ISTO

RC

IRC

UIT

)(T

HER

MIS

TOR

)

(SER

IAL

I/OC

IRC

UIT

)

(PAM

OVE

RC

UR

REN

TC

IRC

UIT

)

(EEP

RO

MC

IRC

UIT

)

(4-W

AYVA

LVE

CIR

CU

IT)

(FAN

MO

TOR

CIR

CU

IT)

(FAN

MO

TOR

)

(RES

ETC

IRC

UIT

)(S

WIT

CH

ING

POW

ERSU

PPLY

CIR

CU

IT)

KID

6500

4AP

PST9

93D

KRA1

06S

KRC

105S

KRC

105S

KRA1

06S

(DC

OVE

RC

UR

REN

TC

HEC

KC

IRC

UIT

)

MO

NIT

OR

(FO

RD

EBU

G)

CN

D

(FR

ASH

WR

ITER

CO

NN

ECTO

R)

(LED

CIR

CU

IT)

DET

ECT

CIR

CU

IT)

(RO

TOR

POSI

TIO

N

+

C4

C5

C7

C6

2.7k

F

6.8K

F

13V

0.1μC31

C

19.1

KFR

113

2 – 6

Page 11: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2.2. Printed wiring board

2 – 7

Page 12: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[3] FUNCTION

1. Function

1.1. Startup controlThe main relay remains off during the first 45 seconds (first safetytime) immediately after the power cord is plugged into an AC outlet inorder to disable outdoor unit operation and protect outdoor unit electriccomponents.

1.2. Restart controlOnce the compressor stops operating, it will not restart for 180 sec-onds to protect the compressor.

Therefore, if the operating compressor is shut down from the remotecontrol and then turned back on immediately after, the compressor willrestart after a preset delay time.

(The indoor unit will restart operation immediately after the ON switchis operated on the remote control.)

1.3. Cold air prevention controlWhen the air conditioner starts up in heating mode, the indoor unit fanwill not operate until the temperature of the indoor unit heat exchangerreaches about 23°C in order to prevent cold air from blowing into theroom.

Also, the indoor unit fan operates at low speed until the temperature ofthe indoor unit heat exchanger reaches about 38°C so that people inthe room will not feel chilly air flow.

1.4. Odor prevention controlWhen the air conditioner starts up in cooling mode, the discharged airtemperature is lowered slightly, and for the reduction of unpleasantodors the operation of the indoor unit fan is delayed 60 seconds if theautomatic fan speed mode in cooling mode is set.

1.5. Indoor unit heat exchanger freeze prevention controlIf the temperature of the indoor unit heat exchanger remains below0°C for 4 consecutive minutes during cooling or dehumidifying opera-tion, the compressor operation stops temporarily in order to preventfreezing.

When the temperature of the indoor unit heat exchanger rises to 2°Cor higher after about 180 seconds, the compressor restarts andresumes normal operation.

1.6. Outdoor unit 2-way valve freeze prevention controlIf the temperature of the outdoor unit 2-way valve remains below 0°Cfor 10 consecutive minutes during cooling or dehumidifying operation,the compressor operation stops temporarily in order to prevent freez-ing.

When the temperature of the 2-way valve rises to 10°C or higher afterabout 180 seconds, the compressor restarts and resumes normaloperation.

1.7. Indoor unit overheat prevention controlDuring heating operation, if the temperature of the indoor unit heatexchanger exceeds the indoor unit heat exchanger overheat preven-tion temperature (about 45 to 54°C) which is determined by the operat-ing frequency and operating status, the operating frequency isdecreased by about 4 to 15 Hz. Then, this operation is repeated every60 seconds until the temperature of the indoor unit heat exchangerdrops below the overheat protection temperature.

Once the temperature of the indoor unit heat exchanger drops belowthe overheat protection temperature, the operating frequency isincreased by about 4 to 10 Hz every 60 seconds until the normal oper-ation condition resumes.

If the temperature of the indoor unit heat exchanger exceeds the over-heat protection temperature for 60 seconds at minimum operating fre-quency, the compressor stops operating and then restarts after about180 seconds, and the abovementioned control is repeated.

1.8. Outdoor unit overheat prevention controlDuring cooling operation, if the temperature of the outdoor unit heatexchanger exceeds the outdoor unit heat exchanger overheat preven-tion temperature (about 55°C), the operating frequency is decreasedby about 4 to 15 Hz. Then, this operation is repeated every 60 sec-onds until the temperature of the outdoor unit heat exchanger drops toabout 54°C or lower.

Once the temperature of the outdoor unit heat exchanger drops toabout 54°C or lower, the operating frequency is increased by about 4to 10 Hz every 60 seconds until the normal operation conditionresumes.

If the temperature of the outdoor unit heat exchanger exceeds the out-door unit heat exchanger overheat protection temperature for (120 sec: outdoor temperature ≥ 40°C • 60 sec : outdoor temperature < 40°C)at minimum operating frequency, the compressor stops operating andthen restarts after about 180 seconds, and the abovementioned con-trol is repeated.

1.9. Compressor overheat prevention controlIf the temperature of the compressor exceeds the compressor over-heat prevention temperature (110°C), the operation frequency isdecreased by about 4 to 10 Hz. Then, this operation is repeated every60 seconds until the temperature of the compressor drops below theoverheat protection temperature (100°C).

Once the temperature of the compressor drops below the overheatprotection temperature, the operating frequency is increased by about4 to 10 Hz every 60 seconds until the normal operation conditionresumes.

If the temperature of the compressor exceeds the overheat protectiontemperature (for 120 seconds in cooling operation or 60 seconds inheating operation) at minimum operating frequency, the compressorstops operating and then restarts after about 180 seconds, and theabovementioned control is repeated.

Compressor operation

ON operation onremote control

OFF operation onremote control

Compressor ON

Compressor ON Compressor canturn ONCompressor remains OFF

for 180 seconds

Indoor unit heat exchanger temperature

38

23

35

21

Set fan speed

Indoor unit fan at low speed

Indoor unit fan in non-operation

2 – 8

Page 13: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

1.10. Startup controlWhen the air conditioner starts in the cooling or heating mode, if theroom temperature is 2°C higher than the set temperature (in coolingoperation) or 3.5°C lower (in heating operation), the air conditioneroperates with the operating frequency at maximum. Then, when theset temperature is reached, the air conditioner operates at the operat-ing frequency determined by fuzzy logic calculation, then enters thenormal control mode after a while.

1.11. Peak controlIf the current flowing in the air conditioner exceeds the peak controlcurrent (see the table below), the operation frequency is decreaseduntil the current value drops below the peak control current regardlessof the frequency control demand issued from the indoor unit based onthe room temperature.

1.12. Outdoor unit fan delay controlThe compressor stops immediately after cooling, dehumidifying orheating operation is shut down, but the outdoor unit fan continuesoperation for 50 seconds before it stops.

1.13. Defrosting

1.13.1 Reverse defrostingThe defrost operation starts when the compressor operating timeexceeds 20 minutes during heating operation, as shown below, andthe outside air temperature and the outdoor unit heat exchanger tem-perature meet certain conditions. When the defrost operation starts,the indoor unit fan stops. The defrost operation stops when the out-door unit heat exchanger temperature rises to about 13C or higher orthe defrosting time exceeds 10 minutes.

1.14. ON timerThe ON timer can be activated by pressing the ON timer button. Whenthe ON timer is activated, the operation start time is adjusted based onfuzzy logic calculations 1 hour before the set time so that the roomtemperature reaches the set temperature at the set time.

1.15. OFF timerThe OFF timer can be activated by pressing the OFF timer button.When the OFF timer is set, the operation stops after the set time.

When this timer is set, the compressor operating frequency lowers forquieter operation, and the room temperature is gradually varied afterone hour (reduced 1°C three times (max. 3°C) in heating, or increased0.3°C three times (max. 1°C) in cooling or dehumidifying operation) sothat the room temperature remains suitable for comfortable sleeping.

1.16. Power ON startIf a jumper cable is inserted in the location marked with HAJP on theindoor unit control printed circuit board (control PCB), connecting thepower cord to an AC outlet starts the air conditioner in either cooling orheating mode, which is determined automatically by the room temper-ature sensor.

When a circuit breaker is used to control the ON/OFF operation,please insert a jumper as described above.

1.17. Self-diagnostic malfunction code display

1.17.1 Indoor unit1) When a malfunction is confirmed, all relays turn off and a flashing

malfunction code number is displayed to indicate the type of mal-function.

When the air conditioner is in non-operating condition, holdingdown AUX button for more than 5 seconds activates the malfunc-tion code display function.

The operation continues only in the case of a serial open-circuit,and the main relay turns off after 30 seconds if the open-circuit con-dition remains.

In the case of a serial short-circuit, the air conditioner continuesoperating without a malfunction code display, and the main relayturns off after 30 seconds if the short-circuit condition remains.

The malfunction information is stored in memory, and can berecalled later and shown on display.

2) The self-diagnostic memory can be recalled and shown on the dis-play by stopping the operation and holding down AUX button formore than 5 seconds.

3) The content of self-diagnosis (malfunction mode) is indicated by aflashing number.

(For details, refer to the troubleshooting section.)

1.17.2 Outdoor unitIf a malfunction occurs, LED1 on the outdoor unit flashes in 0.2-sec-ond intervals as shown below.

Model Peak control currentCooling operation Heating operation

AY-XP9FR-N Approx. 3.8 A Approx. 6.4 A

20 min or more 20 min or more 20 min or more

DefrostingMax. 10 min

DefrostingMax. 10 min

Start ofheatingoperation

Heating operationSet temperature

Activation ofOFF timer

1 hourlater

Max.1.5 hourslater

Max.2 hourslater

Timer settingreached

1 hourlater

Max.1.5 hourslater

Max.2 hourslater

Timer settingreached

Activation ofOFF timer

Set temperature

-1O

C

-1O

C

-1O

C

0.3O

C0.3

O

C0.3

O

CCooling/dehumidifying operation

1 sec 1 sec 0.6 sec

ON

OFF

(Example) Compressor high temperature abnormality

2 – 9

Page 14: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

1.18. Information about auto modeIn the AUTO mode, the temperature setting and mode are automati-cally selected according to the room temperature and outdoor temper-ature when the unit is turned on.

During operation, if the outdoor temperature changes, the temperaturesettings will automatically slide as shown in the chart.

1.19. Airflow controlThe airflow control holds the two upper and lower louvers at specialpositions during operation to prevent discharged air from directly blow-ing onto people in the room.

1.19.1 Cooling/dehumidifying operationWhen the airflow button is pressed the upper louver is set at anupward angle to send the air along the ceiling.

1.19.2 HeatingWhen the airflow button is pressed the lower louver is set at a down-ward angle to send the air directly toward the floor.

1.20. Difference of operation in Auto and Manual modesIn the Auto mode, the temperature setting is automatically determined based on the outside air temperature. In addition, the air conditioner operationdiffers from the operation in the Manual mode as explained below.

1.20.1 Difference relating to set temperature

1.21. Dehumidifying operation controlIf the room temperature is 26°C or higher when dehumidifying opera-tion starts, the dehumidifying operation provides a low cooling effect inaccordance with the room temperature setting automatically deter-mined based on the outside air operation. (The setting value is thesame as the set temperature for cooling operation in the auto mode.)

If the room temperature is lower than 26°C when dehumidifying opera-tion starts, the dehumidifying operation minimizes the lowering of theroom temperature.

1.22. Self Clean operationHeating or Fan operation and Cluster operation are performed simulta-neously.

The judgment of whether Heating or Fan operation is used is based onthe outside air temperature at 3 minutes after the start of internalcleaning.

The operation stops after 40 minutes. (The air conditioner shows theremaining minutes: 40 → 39 → 38 ... 3 → 2 → 1)

1.23. Plasmacluster Ion functionOperating the Plasmacluster Ion button while the air conditioner is inoperation or in non-operation allows the switching of the operationmode in the following sequence: “Air Clean operation” → “Stop”.

• “Self Clean operation” generates about equal amounts of (+)ionsand (-)ions from the cluster unit to provide clean air.

If the Plasmacluster Ion generation function is operated together withthe air conditioner operation, the indoor unit fan speed and louverdirection are in accordance with the air conditioner settings.

If the Plasmacluster Ion generation function is used without operatingthe air conditioning function, the indoor unit fan operates at a very lowspeed and the upper louver is angled upward and the lower louverremains horizontal. (The airflow volume and direction can be changedby using the remote control.)

1.24. Hot keepWhen the room temperature rises above the set temperature by 0.6°Cor more, the ON/OFF operation of the compressor and indoor unit fanis controlled in order to lower the room temperature.

(The values indicated below, such as "0.6°C" and "1.3°C," varydepending on the outside air temperature.)

1.24.1 Hot keep zone 1With the compressor frequency at the lowest, if the room temperatureis higher than the set temperature by 0.6°C but no more than 1.3°C,the following processes will be activated.

1) The compressor stops temporarily, and restarts after 2 minutes.

2) If the room temperature remains in the hot keep zone, the com-pressor is turned OFF and ON in 3-minute intervals.

3) The indoor unit fan turns OFF and ON with a delay of 30 secondsfrom the compressor OFF/ON.

4) After the above operation in 3-minute intervals is repeated fourtimes, the interval extends to 6 minutes.

1.24.2 Hot keep zone 2If the compressor ON/OFF in hot keep zone 1 fails to bring the roomtemperature within 1.3°C above the set temperature, the following pro-cesses will be activated.

1) The compressor repeats a cycle of 8-minute OFF and 6-minuteON.

2) After the second time, the compressor remains completely OFFand only the indoor unit fan repeats OFF-ON in set intervals.

3) While the compressor is completely OFF in 2), the louvers are sethorizontally to prevent cold air from blowing.

The zone transition and the end of hot keep operation (room tempera-ture lower than the set temperature) are judged when the compressorON period ends.

* This function cannot be repealed.

Modes and Temperature Settings

the figures in ( ) are temperature settings

Auto mode Manual modeCooling Heating Dehumidifying Cooling Heating Dehumidifying

Temperature setting method

Automatic temperature setting based on outside air tem-perature. Can be changed within ±2°C using remote con-trol.

Can be changed between 18 and 32°C using remote control.

Can be changed between 18 and 32°C using remote control.

Automatic setting. Can be changed within ±2°C.

Heating operation Fan operation

24OC Outside air temperature

1.3OC

0.6OC

Set temperature

2 – 10

Page 15: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

1.25. Winter coolCooling operation is available during the winter season by the built inwinter cool function.

Lower limit of outdoor temperature range is -10°C DB.

When the outside air temperature is low, the outdoor unit fan operatesat slower speed.

NOTE: Built-in protect device may work when outdoor temperaturefalls below 21°C DB., depending on conditions.

1.26. Auto restartWhen power failure occures, after power is recovered, the unit willautomatically restart in the same setting which were active before thepower failure.

1.26.1 Operating mode (Cool, Heat, Dry)• Temperature adjustment (within 2°C range) automatic operation

• Temperature setting

• Fan setting

• Air flow direction

• Power ON/OFF

• Automatic operation mode setting

• Swing louvre

• Plasmacluster mode

1.26.2 Setting not memorized• Timer setting

• Full power setting

• Internal cleaning

1.26.3 Disabling auto restart functionBy removing (cutting) jumper J (JPJ) on the printed circuit board(PCB), the auto restart function can be disabled.

2. Explanation of cluster circuitThe cluster unit generates cluster ions, which are circulated throughout the room by the air flow created by the blower fan (indoor unit fan motor) inthe air conditioner unit.

1) When microcomputer output turns "H," the IC6 output changes to "Lo," turning ON the SSR and applying 230 V to the cluster unit for the genera-tion of cluster ions (positive and negative ions).

3. Outline of PAM circuit

3.1. PAM (Pulse Amplitude Modulation)The PAM circuit varies the compressor drive voltage and controls the rotation speed of the compressor.

The IGBT shown in the block diagram charges the energy (electromotive force) generated by the reactor to the electrolytic capacitor for the inverterby turning ON and OFF.

1

3

12V

SSRC23RE RH

R20

IC6AC230VMicrocomputer output

1

5

3

6

Cluster unitR23R75 R76

PAM drive circuit block diagram

Reactor L5

[PAM drive circuit]

+

Microcomputer (IC1)

AC230V CompressorReactor L6

Noisefilter

AC clockdetection

circuit

DB1

IPM

DB2

Compressorpositiondetector

IGBTdrivecircuit

IGBT

Overvoltagedetection

circuit

2 – 11

Page 16: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

When the IGBT is ON, an electric current flows to the IGBT via the reactor (L5), (L6) and diode bridge (DB2).

When the IGBT turns OFF, the energy stored while the IGBT was ON is charged to the voltage doubler capacitor via the diode bridge (DB1).

As such, by varying the ON/OFF duty of the IGBT, the output voltage is varied.

3.2. High power factor control circuitThis circuit brings the operating current waveform closer to the waveform of commercial power supply voltage to maintain a high power factor.

Because of the capacitor input, when the PAM circuit is OFF, the phase of the current waveform deviates from the voltage waveform as shown below.

To prevent this deviation, a current is supplied during the periods indicated by "O" in the diagram.

To determine the length of period to supply a current, the zero-cross timing of the AC input voltage is input to the microcomputer via the clock circuit.

The power source frequency is also determined at the same time.

The IGBT turns ON after the time length determined by the zero-cross point to supply a current to the IGBT via the reactor.

This brings the current waveform closer to the voltage waveform in phase.

As described above, the ON/OFF operation of the IGBT controls the increase/decrease of the compressor power supply voltage (DC voltage) toimprove the compressor efficiency and maintain a high power factor by keeping the current phase closer to that of the supply voltage.

3.2.1 Detailed explanation of PAM drive circuit sequence

3.2.2 AC clock (zero-cross) judgment• The clock circuit determines the time from one rising point of the clock waveform to the next rising point.

The detected clock waveform is used to judge the power source frequency (50Hz).

• The zero-cross of the AC voltage is judged as the rising of the clock waveform, as shown in the diagram above.

3.2.3 IGBT ON start time (delay time B)• Based on the zero-cross of the AC voltage, the IGBT turns ON after a delay time set according to the power source frequency.

3.2.4 IGBT ON time (C)• After the above delay time, the IGBT turns ON to supply a current to the reactor.

• The ON time of the IGBT determines the amount of energy (level of DC voltage rise) supplied to the reactor.

DC voltage level in each operation mode (varies depending on external load conditions)

– Cooling operation --- 220 to 240 V

– Heating operation --- 220 to 280 V

Stored energyReactor

L5

L6

DB1

DB2

IGBT

IGBT ON

IGBT OFF

AC voltage waveform

AC voltage and current waveform when PAM is ON

AC current waveform

IGBT ON period

Zero-cross detection

AC voltage waveform

AC current waveform

AC voltage and current waveforms when PAM is OFF

AC voltage waveform

Clock

IGBT ON

A

B C

A

B

C

50Hz

1.2mS

1.2mS

0.25 2.3mS

2 – 12

Page 17: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

3.3. PAM protection circuit

To prevent excessive voltage of PAM output fromdamaging the IPM and electrolytic capacitor as wellas the control printed circuit board (PCB), this circuitmonitors the PAM output voltage and turns off thePAM control signal and PAM drive immediatelywhen an abnormal voltage output is generated. Atthe same time, it shuts off the compressor operation.

The PAM output voltage is distributed to pin (4) ofthe comparator (IC8). If this voltage exceeds the ref-erence voltage at pin (5) of the IC8, the output of thecomparator (IC8) reverses (from H to L) and it isinput to pin (38) of the microcomputer (IC1) to haltthe PAM drive.

The protection voltage level is as follows.

3.3.1 Details of troubleshooting procedure for PAM1) PAM shutdown due to error1) When the DC voltage detection circuit sends a signal exceeding the specified voltage to the microcomputer

DC voltage of 350 V or higher (detection circuit input voltage of about 9.2 V or higher) [IC8 pin (4)]

– When an error is detected

• PAM IGBT turns OFF.

• Compressor turns OFF.

• All units shut down completely when the error occurs four times.

2) When the outdoor unit clock waveform differs from the specified value immediately before the PAM IGBT turns ON

When there is no clock waveform input

When a clock signal of other than specified power source frequency (50/60 Hz) is input

– When an error is detected

• PAM IGBT does not turn ON.

• Compressor operates normally.

• Complete shutdown does not occur.

2) PAM error indicationIn case of error “1)”

– An error signal is sent to the indoor unit as soon as an error is generated.

• Malfunction No. 14-0 is indicated when the error code is called out by the indoor unit's self-diagnosis function.

– The LED on the outdoor unit flashes 14 times when an error is generated.

• The LED continues flashing in the 14-time cycle even after the compressor stops operating.

• The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.

In case of error “2)”

– An error signal is sent to the indoor unit as soon as an error is judged.

• Malfunction No. 14-1 is indicated when the error code is called out by the indoor unit's self-diagnosis function.

– The LED on the outdoor unit flashes 14 times when an error is judged.

• The LED on the outdoor unit flashes in normal pattern when the compressor stops operating.

(Compressor OFF or Thermostat OFF from remote control)

* When a user complains that the air conditioner does not provide sufficient cool air or warm air

In addition to conventional error-generating reasons, there is a possibility that the PAM IGBT does not turn ON even if the compressor is operating.

In that case, the DC voltage does not rise even though the compressor is operating, and lowers to the 180-VDC level.

– Check items

• Clock circuit check

• PAM IGBT check

• Fuse (Fu6) open-circuit check

R2255KC10C9420V

750uF R5300K

R723.7K

R823.7K

0V0V

0V

IC8

15V

R11319.1KF

R11215K

5VR1141M

R1151.8K R116

1K5

42

(Overvoltage detection)

During abnormal voltage output

IC138

2 – 13

Page 18: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

4. Explanation of IPM drive circuitThe IPM for compressor drive is made by Mitsubishi Electric.

The power supply for the IPM drive, the shunt resistance for overcurrent detection, etc., are provided outside the IPM (control PCB).

4.1. IPM drive power supply circuitThe power supply for the upper-phase IGBT (HU, HV, HW) drive employs a bootstrap system, and provides power to the upper-phase IC.

The 15-V power supply for the lower-phase IC is provided by the control printed circuit board (PCB).

4.1.1 Brief explanation of bootstrap system (single power drive system)To supply power to the upper-phase IC, the microcomputer (IC1) turns ON the lower-phase IGBT (LU, LV, LW).

This results in a charging current that flows to the electrolytic capacitor of each upper-phase IC input and charges the bootstrap capacitor with a 15-Vcurrent.

The power supply for the subsequent stages is charged while the lower-phase IGBT is ON in ordinary compressor drive control.

P(Vcc)

U,V,W,

VD

VDB

VCIN(n)

N-sideIGBT

N(GND

Bootstrap capacitor

High-voltage-withstanding,high-speed recovery diode

LVIC(LU,LV,LW)

HVIC(HU,HV,HW)

Bootstrap circuit

Initial charge period

Charging current group

2 – 14

Page 19: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

4.1.2 DC overcurrent detection circuitWhen a current of about 25 A or higher flows through the shunt resistance (R49) on the control printed circuit board (PCB), the voltage at this resis-tance is input to IPM CIN pin (26). Then, the gate voltage of the lower-phase IGBT (LU, LV, LW) inside the IPM turns OFF to cut off the overcurrent. Atthe same time, an L output of about 1.8 ms is generated from IPM Fo pin (24), and this results in an L input to overcurrent detection input pin (34) ofthe microcomputer (IC1) and turns OFF the PWM signal output (IC1 pins (51) through (56)) to the IGBT gate.

SETRESET

(About 22 A)

SC

SC reference voltage

Delay by CR time constant circuit

About 1.8 ms

a1

Protection circuit status

Output current Ic (A)

Sense voltage relativeto shunt resistance

Error output Fo

(Lower phase)Internal IGBT gate

IPM overcurrentdetection circuit

5V

0V

IC1

R49Overcurrent

Shunt resistance

P

N

CiN

FO

24

26

34

2 – 15

Page 20: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

5. 120° energizing control (digital position detection control)This control system detects the digital position detection signal and adjusts the rate of acceleration/deceleration accordingly.

The motor's induced voltage waveform is input to the comparator in the form of PWM-switched pulse waveform, and a position detection signal isgenerated as a reference voltage equaling 1/2 of 280 VDC. However, since there is no induced voltage waveform when the PWM waveform is OFF,the microcomputer performs internal processing so that detection is enabled only when it is ON. Based on the detected position signal, actual PWMwaveform output timing is determined. Since it does not use a filter circuit, the detection accuracy is high.

The microcomputer performs internal processing to cancel spike voltage during the regenerative process.

Furthermore, even if the induced voltage is low, position detection is still possible, thus allowing sensor-less operation at low rotation speed in the ini-tial stage of operation. This reduces the starting current and improves the IPM reliability.

Comparator output waveform(Position signal waveform)

Terminal voltage waveform

Reference voltage(1/2 of DC voltage)

Spike voltage(cancelled)

2 – 16

Page 21: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

AYXP9FRN Service Manual CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES

[1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS

Function Operation Self-diagnosis result display

Description Detection period Reset condition Indoor unit error

display

Indoor unit

Outdoor unit

1 Indoor unit fan lock Operation stops if there is no input of rotation pulse signal from indoor unit fan motor for 1 minute.

When indoor unit fan is in operation

Operation OFF or ON ✩2 Yes None

Indoor unit fan rota-tion speed error

Operation stops if rotation pulse signal from indoor unit fan indi-cates abnormally low speed (about 300 rpm or slower).

When indoor unit fan is in operation

Operation OFF or ON ✩2 Yes None

2 Indoor unit freeze prevention

Compressor stops if temperature remains below 0°C for 4 minutes.

When in cooling or dehumidifying opera-tion

Automatic reset when heat exchanger tem-perature rises above freeze prevention temperature (2°C or higher)

— None None

3 2-way valve freeze prevention

Compressor stops if temperature of outdoor unit 2-way valve remains below 0°C for 10 continu-ous minutes during cooling or dehumidifying operation.

When in cooling or dehumidifying opera-tion

Automatic reset when temperature of 2-way valve rises above 10°C.

None Yes Yes

4 Indoor unit heat exchanger over-heat shutdown

Operating frequency lowers if indoor unit heat exchanger tem-perature exceeds overheat tem-perature during heating operation.Compressor stops if indoor unit heat exchanger temperature exceeds overheat temperature for 60 seconds at minimum fre-quency.Overheat temperature setting value indoor unit heat exchanger thermistor temperature: about 45 to 54°C

When in heating operation

Automatic reset after safety period (180 sec).

None Yes Yes

5 Outdoor unit heat exchanger over-heat shutdown

Operation frequency lowers if out-door unit heat exchanger temper-ature exceeds about 55°C during cooling operation.Compressor stops if outdoor unit heat exchanger temperature exceeds about 55°C for 120 sec-onds at minimum frequency.

When in cooling or dehumidifying opera-tion

Automatic reset after safety period (180 sec).

None Yes Yes

6 Compressor dis-charge overheat shutdown

Operating frequency lowers if temperature of compressor chamber thermistor (TH1) falls below about 110°C.Compressor stops if temperature of compressor chamber ther-mistor (TH1) remains at about 110°C (for 120 seconds in cooling operation, or 60 seconds in heat-ing operation) at minimum fre-quency.

When compressor is in operation

Automatic reset after safety period (180 sec).

None Yes Yes

7 Dehumidifying oper-ation temporary stop

Compressor stops if outside air temperature thermistor is lower than about 16°C during dehumidi-fying operation.

When in dehumidify-ing operation

Automatic reset when outside air tempera-ture rises above 16°C.

None Yes Yes

8 DC overcurrent error

Compressor stops if electric cur-rent of about 25 A or higher flows in IPM.

When compressor is in operation

Operation OFF or ON Yes ✩1 Yes Yes

3 – 1

Page 22: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

9 AC overcurrent error

Operating frequency lowers if compressor AC current exceeds peak control current value. Com-pressor stops if compressor AC current exceeds peak control cur-rent value at minimum frequency.

When compressor is in operation

Operation OFF or ON Yes ✩1 Yes Yes

10 AC overcurrent error in compressor OFF status

Indoor and outdoor units stop if AC current exceeds about 3 A while compressor is in non-opera-tion status.

When compressor is in non-operation

Replacement of defective parts such as IPM

Yes ✩2 Yes Yes

11 AC maximum cur-rent error

Compressor stops if compressor AC current exceeds 17 A.

When compressor is in operation

Operation OFF or ON Yes ✩1 Yes Yes

12 AC current defi-ciency error

Compressor stops if operating frequency is 50 Hz or higher and compressor AC current is about 2.0 A or lower.

When compressor is in operation

Operation OFF or ON Yes ✩1 Yes Yes

13 Thermistor installa-tion error or 4-way valve error

Compressor stops if high and low values of temperatures detected by outdoor unit heat exchanger thermistor (TH2) and 2-way valve thermistor (TH5) do not match operating cycle.

3 minutes after com-pressor startup

Operation OFF or ON Yes ✩1 Yes Yes

14 Compressor high temperature error

Compressor stops if compressor chamber thermistor (TH1) exceeds about 114°C, or if there is short-circuit in TH1.

When in operation Operation OFF or ON Yes ✩1 Yes Yes

15 Outdoor unit heat exchanger ther-mistor short-circuit error

Compressor stops if there is short-circuit in outdoor unit heat exchanger thermistor (TH2).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

16 Outdoor unit outside air temperature thermistor short-cir-cuit error

Compressor stops if there is short-circuit in outdoor unit out-side air temperature thermistor (TH3).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

17 Outdoor unit suction thermistor short-cir-cuit error

Compressor stops if there is short-circuit in outdoor unit suc-tion thermistor (TH4).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

18 Outdoor unit 2-way valve thermistor short-circuit error

Compressor stops if there is short-circuit in outdoor unit 2-way valve thermistor (TH5).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

19 Outdoor unit heat exchanger ther-mistor open-circuit error

Compressor stops if there is open-circuit in outdoor unit heat exchanger thermistor (TH2).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

20 Outdoor unit outside air temperature thermistor open-cir-cuit error

Compressor stops if there is open-circuit in outdoor unit out-side air temperature thermistor (TH3).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

21 Outdoor unit suction thermistor open-cir-cuit error

Compressor stops if there is open-circuit in outdoor unit suc-tion thermistor (TH4).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

22 Outdoor unit 2-way valve thermistor open-circuit error

Compressor stops if there is open-circuit in outdoor unit 2-way valve thermistor (TH5).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

23 Outdoor unit dis-charge thermistor open-circuit error

Compressor stops if there is open-circuit in outdoor unit dis-charge thermistor (TH1).

At compressor star-tup

Operation OFF or ON Yes ✩1 Yes Yes

24 Serial signal error Power relay turns OFF if indoor unit cannot receive serial signal from outdoor unit for 8 minutes.

When in operation Operation OFF or ON(Automatic reset when less than 8 min-utes)

Yes None

Compressor stops if outdoor unit cannot receive serial signal from indoor unit for 30 seconds.

When in operation Reset after reception of serial signal

None None None

Function Operation Self-diagnosis result display

Description Detection period Reset condition Indoor unit error

display

Indoor unit

Outdoor unit

3 – 2

Page 23: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

✩1—The outdoor unit restarts four times before the indoor unit error is displayed (complete shutdown).

✩2—A single error judgment results in the display of the indoor unit error (complete shutdown).

✩3—The outdoor unit restarts eight times before the indoor unit error is displayed (complete shutdown).

[2] AIR CONDITIONER OPERATION IN THERMISTOR ERROR

1. Indoor unit

25 Compressor star-tup error

Compressor stops if compressor fails to start up.

At compressor star-tup

Operation OFF or ON Yes ✩3 Yes Yes

26 Compressor rota-tion error (at 120° energizing)

Compressor stops if there is no input of position detection signal from compressor or input is abnormal.

Compressor operat-ing at 120° energizing

Operation OFF or ON Yes ✩3 Yes Yes

27 Outdoor unit DC fan error

Operation stops if there is no input of rotation pulse signal from outdoor unit fan motor for 30 sec-onds.

When outdoor unit fan is in operation

Operation OFF or ON Yes ✩1 Yes Yes

28 PAM overvoltage error

Compressor stops if DC voltage is 350 V or higher.

When in operation Operation OFF or ON Yes ✩1 Yes Yes

29 PAM clock error When power source frequency cannot be determined (at startup), or when power source clock can-not be detected for 1 continuous second (at startup).

At compressor star-tup, when in opera-tion

Compressor contin-ues operation with-out stopping.

None Yes Yes

Item Mode Control opera-tion

When resis-tance is low (temperature judged higher than actual)

Short-circuit When resis-tance is high (temperature judged lower than actual)

Open-circuit

Room tempera-ture thermistor (TH1)

Auto Operation mode judgment

Cooling mode is activated even if room tempera-ture is low.

Cooling mode is activated in most cases.

Heating mode is activated even if room tempera-ture is high.

Heating mode is always activated.

Cooling Frequency control Room becomes too cold.

Air conditioner operates in full power even when set temperature is reached.

Room does not become cool.

Compressor does not operate.

Dehumidifying Room tempera-ture memoryFrequency control

Normal operation. Room tempera-ture is stored in memory as 31.0°C, and com-pressor does not stop.

Normal operation. Room tempera-ture is stored in memory as 18.5°C, and com-pressor does not operate.

Heating Frequency control Room does not become warm.

Hot keep status results immedi-ately after opera-tion starts.Frequency does not increase above 30 Hz (40 Hz).

Room becomes too warm.

Air conditioner operates in full power even when set temperature is reached.

Heat exchanger thermistor (TH2)

CoolingDehumidifying

Freeze preven-tion

Indoor unit evap-orator may freeze.

Indoor unit evap-orator may freeze.

Compressor stops occasion-ally.

Compressor does not operate.

Heating Cold air preven-tion

Cold air preven-tion deactivates too soon and cold air discharges.

Compressor operates at low speed or stops, and frequency does not increase.

Cold air preven-tion deactivates too slow.

Cold air preven-tion does not deactivate, and indoor unit fan does not rotate.

Function Operation Self-diagnosis result display

Description Detection period Reset condition Indoor unit error

display

Indoor unit

Outdoor unit

3 – 3

Page 24: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2. Outdoor unit

Item Mode Control opera-tion

When resis-tance is low (temperature judged higher than actual)

Short-circuit When resis-tance is high (temperature judged lower than actual)

Open-circuit

Compressor chamber ther-mistor (TH1)

CoolingDehumidifyingHeating

Expansion valve control and com-pressor protection

Compressor operates, but room does not become cool or warm (expansion valve is open).

Compressor high temperature error indication.

Layer short-cir-cuit or open-cir-cuit may result in compressor in normal operation.

Outdoor unit ther-mistor open-cir-cuit error indication.

Heat exchanger thermistor (TH2)

CoolingDehumidifying

Outdoor unit heat exchanger over-heat prevention

Compressor operates at low speed or stops.

Outdoor unit ther-mistor short-cir-cuit error indication.

Normal operation. Outdoor unit ther-mistor open-cir-cuit error indication.

Heating Expansion valve controlDefrosting

Defrosting opera-tion is not acti-vated as needed, and frost accumu-lates on outdoor unit (expansion valve is closed).

Outdoor unit ther-mistor short-cir-cuit error indication.

Defrosting opera-tion is activated unnecessarily, and room does not become warm (expansion valve is open).

Outdoor unit ther-mistor open-cir-cuit error indication.

Outside air tem-perature ther-mistor (TH3)

Auto Operation mode judgment

Cooling mode is activated even if room tempera-ture is low.

Outdoor unit ther-mistor short-cir-cuit error indication.

Heating mode is activated even if room tempera-ture is high.

Outdoor unit ther-mistor open-cir-cuit error indication.

CoolingDehumidifying

Operation not affected

Normal operation. Outdoor unit ther-mistor short-cir-cuit error indication.

Normal operation. Outdoor unit ther-mistor open-cir-cuit error indication.

Heating Rating controlDefrosting

Defrosting opera-tion is activated unnecessarily.

Outdoor unit ther-mistor short-cir-cuit error indication.

Defrosting opera-tion is not acti-vated, and frost accumulates on outdoor unit.

Outdoor unit ther-mistor open-cir-cuit error indication.

Suction pipe ther-mistor (TH4)

CoolingDehumidifying

Expansion valve control

Compressor operates, but room does not become cool (expansion valve is open).

Outdoor unit ther-mistor short-cir-cuit error indication.

Frost accumu-lates on evapora-tor inlet section, and room does not become cool (expansion valve is closed).

Outdoor unit ther-mistor open-cir-cuit error indication.

Heating Expansion valve control

Compressor operates, but room does not become warm (expansion valve is open).

Outdoor unit ther-mistor short-cir-cuit error indication.

Frost accumu-lates on expan-sion valve outlet section, and room does not become warm (expansion valve is closed).

Outdoor unit ther-mistor open-cir-cuit error indication.

2-way valve ther-mistor (TH5)

CoolingDehumidifying

Expansion valve control

Frost accumu-lates on indoor unit evaporator and room does not become cool (expansion valve is closed).

Outdoor unit ther-mistor short-cir-cuit error indication.

Compressor operates, but room does not become cool (expansion valve is open).

Outdoor unit ther-mistor open-cir-cuit error indication.

Heating Operation not affected

Normal operation. Outdoor unit ther-mistor short-cir-cuit error indication.

Normal operation. Outdoor unit ther-mistor open-cir-cuit error indication.

3 – 4

Page 25: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[3] THERMISTOR TEMPERATURE CHARACTERISTICS

1. Indoor unit thermistor temperature characteristics

2. Outdoor unit thermistor temperature characteristics

K

100

80

60

40

20

0-10 0 10 20 30 40

Heat exchanger thermistor TH2 (orange)Resistance at 25 : 15 k

Resistance at 25 : 10 kRoom temperature thermistor TH1 (yellow)

- +

TesterTester

4 3 2 1

- +

Temperature( )

Resistance(K )

CN4

TH1 TH2

CN4

Thermistor

Room temperature

Heat exchanger

Color

Yellow

Orange

Symbol

TH1(CN4)

TH2(CN4)

TH1 Room temperature thermistorTH2 Heat exchanger thermistor

Before measuring resistance,disconnect connectors asshown above.

+ -

TH2 TH5

500K

400K

300K

200K

100K

0-20 0 20 60 80 100 120

Tester

1 10

ConnectorCN8

Resistance at 2552.76 k

5.8K

40K

30K

20K

0

10K

-20 0 20 6040

3.06K

4.17K

1.72K

2.28K

+ -

Tester

(In case of TH2 heat exchanger thermistor)

1 10

ConnectorCN8

Thermistor

Compressor thermistor

Heat exchanger thermistor

Outdoor air temperature thermistor

Suction thermistor

2-way valve thermistor

No.

TH1

TH2

TH3

TH4

TH5

Connector

No. (1) - No. (2)

No. (3) - No. (4)

No. (5) - No. (6)

No. (7) - No. (8)

No. (9) - No. (10)

Color

Red

Orange

Green

Black

Yellow

TH1 Compressor thermistor TH2 Heat exchanger thermistorTH3 Outdoor air temperature thermistorTH4 Suction thermistorTH5 2-way valve thermistor

Resistance(K ) Resistance

(K )

Temperature( ) Temperature( )

Resistance at 014.57 k

Resistance at 254.431 k

Before measuring resistance,

disconnect connectors from PWB.

3 – 5

Page 26: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY

1. Cooling in 40 Hz fixed modeTo operate the outdoor unit independently, short-circuit the sections indicated by arrows in the diagram below with an adapter, and apply 230 VACbetween (1) and (N) on the terminal board of the outdoor unit. This allows the outdoor unit to be operated in cooling mode independently.

(Do not operate the outdoor unit in this condition for an extended period of time.)

[5] GENERAL TROUBLESHOOTING CHART

1. Indoor unit does not turn on

2. Indoor unit fan does not operate

3. Indoor unit fan speed does not change

4. Remote control signal is not received

Main cause Inspection method Normal value/condition RemedyCracked PWB.(Cracked pattern)

Check visually. There should be no cracking in PWB or pattern.

Replace PWB.

Open-circuit in FU1 (250 V, 3 A), FU2 (250 V, 3 A)

Check melting of FU1, FU2. There should be no open-circuit. Replace PWB.

Main cause Inspection method Normal value/condition RemedyOpen-circuit in heat exchanger thermistor (TH2) (in heating oper-ation)

Measure thermistor resistance (dismount for check).

– 1 Replace thermistor.There should be no open-circuit or faulty contact.

Replace thermistor.

Disconnected heat exchanger thermistor (TH2) (in heating oper-ation)

Inspect connector on PWB.Check thermistor installation con-dition.

Thermistor should not be discon-nected.

Install correctly.

Main cause Inspection method Normal value/condition RemedyRemote control not designed to allow fan speed change.

Check operation mode. Fan speed should change except during dehumidifying operation, ventilation, light dehumidifying operation, internally normal oper-ation

Explain to user.

Main cause Inspection method Normal value/condition RemedyBatteries at end of service life. Measure battery voltage. 2.5 V or higher (two batteries in

series connection)Install new batteries.

Batteries installed incorrectly. Check battery direction. As indicated on battery compart-ment.

Install batteries in indicated direc-tion.

Lighting fixture is too close, or flu-orescent lamp is burning out.

Turn off light and check. Signal should be received when light is turned off.

Change light position or install new fluorescent lamp.

Use Sevick light (Hitachi). Check if Sevick light (Hitachi) is used.

Signal may not be received sometimes due to effect of Sevick light.

Replace light or change position.

Operating position/angle is inap-propriate.

Operate within range specified in manual.

Signal should be received within range specified in manual.

Explain appropriate handling to user.

Open-circuit or short-circuit in wir-ing of light receiving section.

Check if wires of light receiving section are caught.

Wires of light receiving section should not have any damage caused by pinching.

Replace wires of light receiving section.

Defective light receiving unit. Check signal receiving circuit (measure voltage between termi-nals 2 and 3 of connector BCN3B).

Tester indicator should move when signal is received.

Replace PWB.

(L2)C9C10

Connect with IC clipTest mode cooling at 40 HzConnect with IC clipTest mode cooling at 40 Hz

Short-circuit negative terminal ofcapacitor (C33) and jumper wire(JP16) using IC clip, etc.

3 – 6

Page 27: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

5. Louvers do not move

6. There is noise in TV/radio

7. Malfunction occurs

8. Compressor does not start

9. Operation stops after a few minutes and restarts, and this process repeats

CAUTION: If fuse FU1/FU4/FU5 (outdoor unit control circuit board) is blown, be careful of charging voltage in inverter electrolytic capacitor C9, C10.

To discharge stored electricity, unplug the power cord and connect the plug of a soldering iron (100VAC, 50W) between the positive andnegative terminals of inverter electrolytic capacitor C9, C10.

Dew condensation on light receiv-ing unit.

Check for water and rust. Signal should be received within range specified in manual.

Take moisture-proof measure for lead wire outlet of light receiving section.

Main cause Inspection method Normal value/condition RemedyCaught in sliding section. Operate to see if louvers are

caught in place.Louvers should operate smoothly. Remove or correct catching sec-

tion.Disconnected connector (DCNC, DCND on relay PWB, louver motor side)

Inspect connectors. Connectors or pins should not be disconnected.

Install correctly.

Contact of solder on PWB(connector section on PWB)

Check visually. There should not be solder con-tact.

Correct contacting section.

Main cause Inspection method Normal value/condition RemedyGrounding wires not connected properly.

Check grounding wire connec-tions.

Grounding wires should be con-nected properly.

Connect grounding wires prop-erly.

TV/radio is placed too close to outdoor unit.

Check distance between TV/radio and outdoor unit.

If TV/radio is placed too close, it may become affected by noise.

Move TV/radio away from outdoor unit.

Other than above. Check for radio wave interfer-ence. (See page )

Main cause Inspection method Normal value/condition RemedyMalfunction caused by noise. Check for radio wave interfer-

ence. (See page )

Main cause Inspection method Normal value/condition RemedyErroneous inter-unit connection. Check wiring between indoor and

outdoor units.Terminal board 1-N: 230 VAC, 50 HzTerminal board 2: serial signal

Correct wiring.

Damaged IPM. Check IPM continuity. See [IPM check method] on page 8-3.

Replace IPM.

Dried-up electrolytic capacitor. Check electrolytic capacitor. See [Inverter electrolytic capaci-tor (C9, C10) check method] on page 8-2.

Replace electrolytic capacitor.

Blown outdoor unit fuse. Check 20-A fuse.Check 15-A fuse.

Fuse should not be blown. Replace fuse/diode bridge.Replace fuse.Replace outdoor unit PWB assembly.

Power supply voltage is too low. Measure power supply voltage during startup.

230±10 VAC, 50 Hz Make sure that power supply volt-age is 180 V or higher.

Compressor lock. Supply current and touch com-pressor cover (sound absorbing material) to check if operation starts.

Compressor should start nor-mally.

Apply external impact to com-pressor.Replace compressor.

Main cause Inspection method Normal value/condition RemedyDried-up electrolytic capacitor. Measure 320-VDC line voltage. 250 V or higher. Replace electrolytic capacitor.Layer short-circuit in expansion valve coil.

Measure resistance. 46±3Ω in each phase (at 20°C) Replace coil.

Main cause Inspection method Normal value/condition Remedy

3 – 7

Page 28: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[6] MALFUNCTION (PARTS) CHECK METHOD

1. Procedure for determining defective outdoor unit IPM/compressor The following flow chart shows a procedure for locating the cause of a malfunction when the compressor does not start up and a DC overcurrent indi-cation error occurs.

YES

Immediatelyafter startup

YES

YES

NO

NO

NO

YES

NO

Connect power cordto AC outlet.

Normal

NO

Replace outdoor unit PWB.

Using remote control,operate air conditionerso that compressorstarts.

Is there 230 VACbetween (1) and (N)on outdoor unit PCB?

Is LED1 on outdoorunit flashing?

Compressor starts up.

Does LED1 indicateDC overcurrent error?

Does LED1 indicaterotation error?

Outdoor unit PWB.15/5 V display section.Voltage OK.

Replace compressor.

Check inter-unit wiring.Check indoor unit PWB.

Does LED1 remain lit?

Serial signal error.Check inter-unit wiring.Check indoor andoutdoor unit PWBs.

Replace outdoor unitPWB.Check compressor.2/3-way valve closed.Refrigerant shortage.

Replace outdoor unit

Is there 320 VDC betweenpins IPM (31) and (35)?

+13 V, +15 V on PWB.

+13 V on PWB.

Replace outdoor unit PWB.

Replace expansion valve.

End.

Check posistor (PTC1)(about 40 at 25 ).Check IPM.Check fan motor.Check outdoor unit PCB.Check wiring.Check PAM IGBT (Q5).

Disconnect expansionvalve connector.

Replace outdoor unit PWB.

After about20 seconds

YES

NO

NO

YES

NO

NO

YES

YES YES

No(unlit)

OK

3 – 8

Page 29: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2. Procedure for determining defective expansion valve

3. Diode bridge check methodTurn off the power and let the inverter electrolytic capacitor (C9, C10) discharge completely. Then use a tester and check continuity.

When using a digital tester, the (+) and (-) tester lead wires in the table must be reversed.

4. Inverter electrolytic capacitor (C9, C10) check methodTurn off the power, let the inverter electrolytic capacitor (C9, C10) discharge completely, and remove the capacitor from the control printed circuitboard (PWB). First, check the case for cracks, deformation and other damages. Then, using a needle-type tester, check continuity.

Determination of normal conditionThe tester needle should move on the scale and slowly returns to the original position. The tester needle should move in the same way when polarities are reversed. (When measurement is taken with the polarities reversed, the tester needle exceeds the scale range. Therefore, let the capacitor discharge before measurement.)

Measure resistance in expansion valve coil.

Normal resistance between redterminal of expansion valve

lead wire and each terminal:about 46 (at 20 )

Insert checker shown at left intoconnector (CN12) on control PWB, andoperate air conditioner.

If frost accumulates on 2-way valve after 10 to 20minutes of cooling operation, then thermistors with

yellow and black lead wires may be defective. Checkthese thermistors.

Replace control PWB.

NO

NO

YES

YES

Checker

LED(red)

ConnectorJ.S.T. XAP-06V-1

TerminalSXA-001T-P0.6

4 3 2 156

5.6K 5.6K 5.6K 5.6K

Do LEDs on checker light in orderlysequence(lighting of 1 LED => lighting of 2 LEDs)

45 B

Needle-type tester Normal resistance value

(several M )

Value in ( ) is for digital tester.

3 – 9

Page 30: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

5. IPM check methodTurn off the power, let the large capacity electrolytic capacitor (C10) discharge completely, and dismount the IPM. Then, using a tester, check leakcurrent between C and E.

When using a digital tester, the (+) and (-) tester lead wires in the table must be reversed.

Values in ( ) are for digital tester.

5.1. IPM internal circuit diagram

[7] OUTDOOR UNIT CHECK METHODAfter repairing the outdoor unit, conduct the following inspection procedures to make sure that it has been repaired completely. Then, operate thecompressor for a final operation check.

1. Checking procedures

Needle-type tester Normal resistance value(-) (+)

P N ∞(several MΩ)U

VW

Needle-type tester Normal resistance value(-) (+)

U N ∞(several MΩ)V

W

No.

Item Check method Normal value/condition Remedy

1 Preparation Disconnect compressor cords (white, orange, red: 3 wires) from compres-sor terminals, and connect simulated load (lamp used as load).Operate air conditioner in cooling or heating test operation mode.

2 Inverter DC power supply voltage check

Measure DC voltage between IPM pins (31) and (35).

320 VDC Replace control PWB.Replace diode bridge.Correct soldered section of Fas-ten tabs (T1, T2, T5 - T3) on con-trol PWB and IMP (S, C, R). (Repair solder cracks.)

3 IPM circuit check Check that 3 lamps (load) light.Check position detection voltage (+15 V, 5 V) on control PWB.

Each voltage should be normal.All 3 lamps (load) should light with same intensity.

Replace control PWB.

3 – 10

Page 31: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

2. Troubleshooting of outdoor unit electric components

4 Compressor check Measure compressor coil resistance (for each phase of U, V and W).Use multi-meter or digital tester capa-ble of displaying two digits right of the decimal point (0.01Ω).

Resistance value at 20°C --- 0.65Ω Correct connections at compres-sor terminals.Replace compressor.

5 Expansion valve check Measure expansion valve coil resis-tance.

Each phase 46±3Ω (at 20°C) Replace expansion valve.

6 Final check Turn off power, and connect compres-sor cords to compressor.Operate air conditioner.Measure DC voltage between IPM pins (31) and (35).

Compressor should operate nor-mally.200 VDC or higher.

Replace control PWB.Replace outdoor unit thermistor.Replace compressor (in case of compressor lock).

No.

Item Check method Normal value/condition Remedy

Does LED light?NO

YES

YES NO

Does LED flash?

Normal

NO

YES

NOYES

NO

YES

NO

YES

Is 230 V appliedbetween 1 andN on outdoorunit terminalboard?

Is voltage betweenIPM pins (31) and(35) 320 V orhigher?

5/ Short-circuit in DC fan motorShort-circuit in IPMShort-circuit in diode bridgeBlown fuseDefective electrolytic capacitorWire disconnection, PWB pattern damageShort-circuit in PAM IGBT (Q5)

Defective switching power supply circuitMalfunction of 3-terminal regulator IC4, IC1Short-circuit in expansion valve coilMalfunction of transistor array IC7Solder contact or other problems

Malfunction of 3-terminal regulator IC4, IC1

Microcomputer oscillator errorMalfunction of microcomputer reset ICMalfunction of microcomputer

Malfunction of serial signal circuitCheck wiring between indoor and outdoor units.

Is switching powersupply output of13 VDC, 15 VDCproduced?

Is 5 VDC outputproduced?

Check indoorunit.

3 – 11

Page 32: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

3. Caution in checking printed circuit boards (PWB)

3.1. Non-insulated control circuitThe GND terminals of the low-voltage circuits (control circuits for microcomputer and thermistors and drive circuits for expansion valve and relays) onthe control printed circuit board (PWB) are connected to the compressor drive power supply (320-VDC negative terminal). Therefore, exercise utmostcaution to prevent electric shock.

If a measuring instrument used for the test is grounded, its chassis (ground) has the same electric potential as the 0-V probe. Since non-insulated cir-cuits have the following voltage potential difference from the ground, connection of the grounding wire results in a short-circuit between the 0-V lineand the ground, thus allowing an excessive current to flow to the tester to cause damage.

If the sheaths of the thermistor lead wires or expansion valve lead wires inside the outdoor unit become damaged due to pinching by the front panelor other metal parts or contacting a pipe, a high voltage can flow and destroy the circuits. To prevent these problems, carefully conduct assemblywork.

Ground voltage

320-VDC line

0-V line

0-V line voltage (point (F))

Voltage at point (E)

320V

+ 160V

- 160V

Terminal board

Ground0-V line Point (F)

Point (E)Reactor

IPM+-

Compressor motor

2

AC230V

1

3

Outdoor unit circuits

M

ReasonThe oscilloscope (chassis ground) has the same electric potential as the 0-V probe. Theentire electronic control section of the outdoor unit has a voltage potential difference fromthe ground as shown in the above diagram. When the oscilloscope is set up, the 0-V lineand the ground voltage (ground) will be short-circuited, resulting in an excessive currentflow to cause damage to the oscilloscope or indoor electric circuits.

Do not touch thecabinet or bring metalparts into contact withthe cabinet. Danger!!

Do not connectthe groundingwire.

3 – 12

Page 33: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[8] TROUBLESHOOTING GUIDE

1. Self-Diagnosis Function and Display ModeTo call out the content of the self-diagnosis memory, hold down the emergency operation button for more than 5 seconds when the indoor unit is notoperating.

• The number of indications displayed by the LEDs on the outdoor unit differs from that for the 2001 cooling unit models (for detailed display of mal-function information).

The display of malfunction No. differs from that of the 2001 cooling unit models. To show detailed malfunction information, two types of numbersflash alternately. (example: "21" ←→ "-0")

1) The content of the self-diagnosis memory can be called out and displayed on the seven-segment display section on the indoor unit. (The errordata cannot be called out for display by the LED on the outdoor unit.)

2) If the power cord is unplugged from the AC outlet or the circuit breaker is turned off, the self-diagnosis memory loses the stored data.

a) The self-diagnosis display function of the indoor unit indicates the content of diagnosis by showing the error main category (number) and theerror sub-category (-number) alternately in 1-second intervals on the seven-segment display section of the indoor unit.

Example of self-diagnosis display on indoor unit: Compressor high-temperature error

b) The self-diagnosis display function of the outdoor unit indicates the error information by flashing LED1 on the outdoor unit according to the con-tent of self-diagnosis.

The self-diagnosis display function of the outdoor unit is active only for about 3 to 10 minutes after self-diagnosis is performed during operation,and the display returns to normal condition after this display period.

The content of self-diagnosis cannot be called out by the self-diagnosis display function of the outdoor unit.

Example of self-diagnosis display on outdoor unit: Compressor high-temperature error

c) The content of diagnosis is transferred to the indoor unit via serial communication, but it does not trigger a complete shutdown operation.

: Flashes in 2-sec intervals (normal), : On, : Off, : Flashes 3 times in 0.2-sec intervals (When LED1 on the outdoor unit flashes in 2-secintervals, the outdoor unit is in normal condition.)

Status of indoor/outdoor

units

Indication by LED1 on out-

door unit *2

Malfunction No. dis-

played on main unit

display sec-tion *1

Content of diagnosis Inspection location/method Remedy

Main cate-gory

Sub-cate-gory

Main category Sub-category

Indoor/outdoor units in operation

Nor-mal

flash-ing

0 0 Normal – –

Indoor/outdoor units in complete shutdown

1 time 1 -0 Outdoor unit thermistor short-circuit

Heat exchanger thermistor short-cir-cuit error

(1) Measure resistance of the outdoor unit thermistors.(TH2 to TH5: Approx. 4.4 kΩ at 25°C)

(1) Replace the outdoor unit thermistor assem-bly.

-1 Outside tempera-ture thermistor short-circuit error

(2) Check the lead wire of the outdoor unit thermistor for torn sheath and short-cir-cuit.

(2) Replace the outdoor unit thermistor assem-bly.

-2 Suction thermistor short-circuit error

(3) No abnormality found in above inspections (1) and (2).

(3) Replace the outdoor unit control PWB assembly.-3 2-way valve ther-

mistor short-circuit error

1 sec 1 sec 1 sec 1 sec 1 sec1 sec0.6 sec 0.6 sec0.6 sec 0.6 sec 1 secONOFF

1 sec 1 sec

3 – 13

Page 34: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

Indoor/outdoor units in complete shutdown

2 times 2 -0 Cycle tempera-ture

Compressor high-temperature error

(1) Check the outdoor unit air outlet for blockage.

(1) Ensure unobstructed air flow from the out-door unit air outlet.

(2) Check if the power supply voltage is 90 V or higher at full power.

(2) Connect power sup-ply of proper voltage.

(3) Check the pipe connec-tions for refrigerant leaks.

(3) Charge the specified amount of refrigerant.

(4) Measure resistance of the outdoor unit compressor thermistor.(TH1: Approx. 53 kΩ at 25°C)

(4) Replace the outdoor unit compressor ther-mistor assembly.

(5) Check the expansion valve for proper operation.

(5) Replace the expan-sion valve coil, expan-sion valve or outdoor unit control PWB assembly.

Indoor unit in operationOutdoor unit in tempo-rary stop

-1 Temporary stop due to compressor dis-charge overheat *3

(Temporary stop for cycle pro-tection)

-2 Temporary stop due to outdoor unit heat exchanger overheat *3

(Temporary stop for cycle pro-tection)

-3 Temporary stop due to outdoor unit heat exchanger overheat *3

(Temporary stop for cycle pro-tection)

-4 Temporary stop due to 2-way valve freeze *3

(Temporary stop for cycle pro-tection)

Indoor unit in operationOutdoor unit in tempo-rary stop

3 times 3 -0 Dry operation Temporary stop due to dehumidifying operation *3

(Temporary stop for cycle pro-tection)

Indoor/outdoor units in complete shutdown

5 times 5 -0 Outdoor unit thermistor open-circuit

Heat exchanger thermistor open-cir-cuit error

(1) Check connector CN8 of the outdoor unit ther-mistor for secure installa-tion.

(1) Correct the installa-tion.

-1 Outside tempera-ture thermistor open-circuit error

(2) Measure resistance of out-door thermistors TH1 to TH5.

(2) Replace the outdoor unit thermistor assem-bly.

-2 Suction thermistor open-circuit error

(3) Check the lead wires of thermistors TH1 through TH5 on the outdoor unit control PWB for open-cir-cuit.

(3) Replace the outdoor unit thermistor assem-bly.

-3 2-way valve ther-mistor open-circuit error

(4) No abnormality found in above inspections (1) through (3).

(5) Replace the outdoor unit control PWB assembly.

-4 Discharge ther-mistor open-circuit error

Status of indoor/outdoor

units

Indication by LED1 on out-

door unit *2

Malfunction No. dis-

played on main unit

display sec-tion *1

Content of diagnosis Inspection location/method Remedy

Main cate-gory

Sub-cate-gory

Main category Sub-category

3 – 14

Page 35: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

Indoor/outdoor units in complete shutdown

6 times 6 -0 Outdoor unit DC DC overcurrent error (1) IPM continuity check (1) Replace the outdoor unit control PWB assembly.

(2) Check the IPM and heat sink for secure installation.

(2) Correct the installa-tion (tighten the screws).

(3) Check the outdoor unit fan motor for proper rotation.

(3) Replace the outdoor unit fan motor.

(4) No abnormality found in above inspections (1) through (3).

(4) Replace the outdoor unit control PWB assembly.

(5) No abnormality found in above inspections (1) through (4).

(5) Replace the compres-sor.

-1 IPM pin level error Check the IPM is attached correctly to the outdoor unit control PWB.

Replace the outdoor unit control PWB assembly.

Indoor/outdoor units in complete shutdown

7 times 7 -0 Outdoor unit AC AC overcurrent error (1) Check the outdoor unit air outlet for blockage.

(1) Ensure unobstructed air flow from the out-door unit air outlet.

(2) Check the outdoor unit fan for proper rotation.

(2) Check the outdoor unit fan motor.

-1 AC overcurrent error in OFF status

(1) IPM continuity check (1) Replace the outdoor unit control PWB assembly.

-2 AC maximum cur-rent error

(1) Check the outdoor unit air outlet for blockage.

(1) Ensure unobstructed air flow from the out-door unit air outlet.

(2) Check the outdoor unit fan for proper rotation.

(1) Check the outdoor unit fan motor.

-3 AC current defi-ciency error

(1) Check if there is an open-circuit in the secondary winding of the current transformer of the outdoor unit control PWB.

(1) Replace the outdoor unit control PWB assembly.

(2) Check if the refrigerant volume is abnormally low.

(2) Charge the specified amount of refrigerant.

(3) Check if the refrigerant flows properly.

(3) Correct refrigerant clogs.(2-way valve, 3-way valve, pipe, expan-sion valve)

Indoor/outdoor units in complete shutdown

9 times 9 -0 Outdoor unit cooling/heating switchover

Thermistor installa-tion error or 4-way valve error

(1) Check to make sure out-door unit thermistor TH2 (heat exchanger) and TH5 (2-way valve) are installed in correct positions.

(1) Correct the installa-tion.

(2) Measure resistance of thermistors TH1 and TH5.

(2) Replace the ther-mistor assembly.

(3) Check the 4-way valve for proper operation.

(3) Replace the 4-way valve.

(4) No abnormality found in above inspections (1) through (3).

(4) Replace the outdoor unit control PWB assembly.

-3 Torque control error (1) Check if the refrigerant volume is abnormally low.

(1) Change the specified amount of refrigerant.

(2) Check the 4-way valve for proper operation.

(2) Replace the 4-way valve.

(3) check to see compressor type is correct.

(3) Replace the compres-sor with the correct part.

Status of indoor/outdoor

units

Indication by LED1 on out-

door unit *2

Malfunction No. dis-

played on main unit

display sec-tion *1

Content of diagnosis Inspection location/method Remedy

Main cate-gory

Sub-cate-gory

Main category Sub-category

3 – 15

Page 36: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

Indoor/outdoor units in complete shutdown

11times

11 -0 Outdoor unit DC fan

Outdoor unit DC fan rotation error

(1) Check connector CN3 of the outdoor unit DC fan motor for secure installa-tion.

(1) Correct the installa-tion.

(2) Check the outdoor unit fan motor for proper rotation.

(2) Replace the outdoor unit fan motor.

(3) Check fuse FU3. (3) Replace the outdoor unit control PWB assembly.

(4) Outdoor unit control PWB (4) Replace the outdoor unit control PWB assembly.

Indoor/outdoor units in complete shutdown

13times

13 -0 DC compressor Compressor startup error

(1) Check the colors (red, white, orange) of the com-pressor cords for proper connection. (PWB side, compressor side)

(1) Correct the installa-tion.(U: Red, V: White, W: Orange)

-1 Compressor rota-tion error(120° energizing error)

(2) Check if the IPM terminal resistance values are uni-form.

(2) Replace the outdoor unit control PWB assembly.

(3) No abnormality found in above inspections (1) and (2).

(3) Replace the outdoor unit control PWB assembly.

(4) No abnormality found in above inspections (1) through (3).

(4) Replace the compres-sor.

Indoor/outdoor units in complete shutdown

14times

14 -0 Outdoor unit PAM

PAM over voltage errorCompressor rota-tion error

(1) Check the AC power sup-ply voltage for fluctuation.

(1) Connect stable power supply.

(2) No abnormality found in above inspection (1).

(2) Replace the outdoor unit control PWB assembly.

Indoor/outdoor units in operation

-1 PAM clock error (1) Check the PAM clock for proper input.

(1) Replace the outdoor unit control PWB assembly.

Indoor unit in operationOutdoor unit in complete shutdown

17 -0 Wires between units

Serial open-circuit (1) Check the wires between units.

(1) Connect stable power supply.

(2) Check voltage between Nos. 1 and 2 on the indoor/outdoor unit termi-nal boards.

(2) Replace the outdoor unit control PCB assembly.

Outdoor unit does not turn on due to erroneous wiring

(1) Check the wires between units.

(1) Correct the wiring.

(2) Check the outdoor unit fuse.

(2) Replace the fuse/out-door unit control PCB assembly.

(3) Check 15-V, 13-V and 5-V voltages on the PWB.Check resistance between IPM terminals.

(3) Replace the outdoor unit control PCB assembly.

(4) Check pins No. 5 and 7 of connector CN3 of the out-door unit fan motor for short-circuit.

(4) Replace the outdoor unit fan motor.

(5) Outdoor unit control PCB (5) Replace the outdoor unit control PCB board.

18 -0 Serial short-circuit (1) Check the wires between units.

(1) Correct the wiring.

-1 Serial erroneous wir-ing

(1) Check the wires between units.

(1) Correct the wiring.

Status of indoor/outdoor

units

Indication by LED1 on out-

door unit *2

Malfunction No. dis-

played on main unit

display sec-tion *1

Content of diagnosis Inspection location/method Remedy

Main cate-gory

Sub-cate-gory

Main category Sub-category

3 – 16

Page 37: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

Indoor/outdoor units in complete shutdown

19 -0 Indoor unit fan Indoor unit fan error (1) Check the indoor fan motor for proper rotating operation.(Check fan lock.)

(1) Replace the indoor fan motor.

(2) Check the lead wire of the indoor fan motor for open-circuit.

(2) Replace the indoor fan motor.

(3) Check CN1 of the indoor unit fan motor for secure installation.

(3) Correct the installa-tion of CN1 of the indoor fan motor.

(4) No abnormality found in above inspections (1) through (3).

(4) Replace the indoor unit control PWB.

Indoor/outdoor units in operation

20 -0 Indoor unit con-trol PCB

EEPROM data error (EEPROM read data error)

Replace the indoor unit control PWB.

Indoor/outdoor units in operation

88 Control and dis-play PCB

Communication error

(1) Check for disconnected connector between control PCB and display PCB, and open-circuit in lead wires.

(1) Insert connectors cor-rectly, or replace con-trol PWB.

(2) Check that control PCB outputs signals correctly.

(2) Replace control PWB.

Status of indoor/outdoor

units

Indication by LED1 on out-

door unit *2

Malfunction No. dis-

played on main unit

display sec-tion *1

Content of diagnosis Inspection location/method Remedy

Main cate-gory

Sub-cate-gory

Main category Sub-category

3 – 17

Page 38: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

Malfunction indications due to erroneous wiring during air conditioner installation

Inter-unit wiring error mode Symptom1 Indoor unit relay

Malfunction diagnosis displayTurns On momentarily, then turns Off."18-1"

2 Indoor unit relayMalfunction diagnosis display

Relays turns Off after about 30 minutes.None(Displays "18-0" when malfunction code is called out.)

3 Indoor unit relayMalfunction diagnosis display

Relays turns Off after about 30 minutes.None(Displays "18-0" when malfunction code is called out.)

4 Indoor unit relayMalfunction diagnosis display

Turns On momentarily, then turns Off."18-1"

5 Indoor unit relayMalfunction diagnosis display

Turns On momentarily, then turns Off."18-1"

Indoorunit

Outdoorunit

1

N

2

1

N

2

Indoorunit

Outdoorunit

1

N

2

1

N

2

Indoorunit

Outdoorunit

1

N

2

1

N

2

Indoorunit

Outdoorunit

1

N

2

1

N

2

Indoorunit

Outdoorunit

1

N

2

1

N

2

3 – 18

Page 39: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

AYXP9FRN Service Manual CHAPTER 4. REFRIGERATION CYCLE

[1] FLOW FOW REFRIGERANT

[2] STANDARD CONDITION

* REFRIGERANT PIPE LENGTH 5.0m

[3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE

Indoor side Outdoor sideDry-bulb Temp. (°C) Relative Humidity (%) Dry-bulb Temp. (°C) Relative Humidity (%)

Cooling 27 47 35 40Heating 20 – 7 87

Model AY-XP9FR-N

Operation model MAX. TEST RUNCool Heat Cool Heat

Hz57 more than 90 42 42

No.1 67 73 63 552 38 16 37 73 14 34 14 264 13 2 17 5

3-way valve pressure (MPaG) 1.17 3.28 1.25 2.25

s

14

C

2

Accumulator

3

Strainer

Expansionvalve

Heating Cooling

Outdoor unit

Condenser

EvaporatorIndoor unit

Reverse valve

Comp-ressor

Flare coupling Flare coupling

3-wayvalve

2-wayvalve

Silencer

Coil

4 – 1

Page 40: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[4] PERFORMANCE CURVESNOTE: 1) Indoor fan speed: Hi

2) Vertical adjustment louver "45°", Horizontal adjustment louver "front"

3) Indoor air temp. : Cooling 27°C, Heating 20°C

4) Power source : 230V, 50Hz

1. AY-XP9FR-N

1.1. At Cooling 1.2. At Heating

25 30 35 40

3.0

2.8

2.6

2.4

2.2

2.0

600

550

500

450

Coo

ling

capa

city

(kW

)

Outside air temp.(ºC)

Inpu

t(W

)

-5 0 75 10

Hea

ting

capa

city

(kW

)

Outside air temp.(ºC)

Inpu

t(W

)

4.0

3.5

3.0

2.5

2.0

750

700

650

600

550

4 – 2

Page 41: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

REPLACEMENT PARTS LIST

CONTENTS

AYXP9FRN

INDOOR UNIT

AY-XP9FR-NOUTDOOR UNIT

AE-X9FR-N

SPLIT TYPEROOM AIR CONDITIONER

MODELS

[1] INDOOR UNIT PARTS

[2] OTHER PARTS (Indoor unit)

[3] OUTDOOR UNIT PARTS

[4] OTHER PARTS

INDEX

Parts marked with " " are important for maintaining the safety of the set. Be sure to replace theseparts with specified ones for maintaining the safety and performance of the set.

This document has been published to be usedfor after sales service only.The contents are subject to change without notice.

“HOW TO ORDER REPLACEMENT PARTS”To have your order filled promptly and correctly, please furnish thefollowing information.

1. MODEL NUMBER 2. REF. No.3. PART NO. 4. DESCRIPTION

★ MARK: SPARE PARTS-DELIVERY SECTION

Page 42: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[1] INDOOR UNIT PARTS

4-8

2-36

2-46

2-43

2-42

2-41

2-29

2-10

2-24

2-21

2-32

2-18

1-14

2-44

2-45

2-40

2-34

1-10

2-302-37

1-11

2-12

2-22

2-23

1-12

1-17

1-201-15

1-191-16

1-18

2-28

2-354-3

4-9

2-9

4-2

4-4

2-4

3-3

2-6

2-7

2-5

1-3

1-21-4

2-1

2-3

4-5

3-2

3-1

1-1

2-2

4-7 4-6-1

3-1-1

4-1

2-9-1

2-9-2

2-9-3

2-10-6

2-10-9

2-10-4

2-10-8

2-10-7

2-7-1

2-7-3

2-7-2

2-5-3

2-5-32-5-1

1-1-2

1-1-3

2-5-4

2-8-1

2-8-22-3-1

2-3-2

2-5-2

2-5-2

2-10-22-10-3

2-10-1

2-10-11

2-10-11

2-10-10

1-10-3 1-10-1

1-10-2

2-10-5

2-19

2-20

2-11

2-33

2-392-38

1-13

2-13

2-16

2-17

2-15

2-14

1-21

1-8

1-51-6

1-7

1-9

2

Page 43: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

NO. PARTS CODE PRICE RANK

NEW MARK

PART RANK DESCRIPTION

[1] INDOOR UNIT PARTS1-1 CMOT-A437JBKZ BQ Fan motor sub ass'y

1-1-2 PGUMMA279JBEZ AU Motor cushion1-1-3 PGUMMA280JBEZ AU Motor cushion1-2 QW-VZE973JBZZ AH Lead wire1-3 RMOT-A116JBZZ AP Louver motor1-4 RMOT-A117JBZZ AP Louver motor1-5 QW-VZF246JBZZ AU Lead wire1-6 QW-VZF247JBZZ AU Lead wire1-7 QW-VZE970JBZZ AE Lead wire1-8 QW-VZF173JBZZ AF Lead wire1-9 RFIL-A064JBE0 AF Ferrite core1-10 FSGY-A295JBKZ BQ Hi voltage unit assy

1-10-1 CKITTA073AKKZ BE Plasmacluster unit1-10-2 QW-VZE859JBZZ AM Lead wire1-10-3 LHLD-A714JBFA AU Holder1-11 QW-VZE972JBZZ AP Lead wire1-12 DPWBFA462JBKZ BS Control board unit1-13 DPWBFA398JBKZ BL Sub control board k1-14 DPWBFA397JBKZ AU Display board unit1-15 QTANZA022JBZZ AH Terminal board1-16 QTANZA026JBZZ AK Terminal board1-17 QACC-A319JBZZ AU Power supply cord1-18 QW-VZE965JBZZ AE Lead wire1-19 QW-VZE966JBZZ AE Lead wire1-20 RH-HXA048JBZZ AP Themistor k1-21 QTANZA021JBZZ AN Terminal board2-1 PCOV-B062JBFA AH Cover2-2 CCOV-A113JBKZ BE Cabinet cover ass'y2-3 CCOV-A119JBKZ BE Cover ass'y

2-3-1 FCOV-A199JBRA AK Cover2-3-2 PCOV-B118JBFA AK Cover2-4 PGID-A127JBFZ AG Guide2-5 CDAI-A020JBKZ BE Louver base ass'y

2-5-1 MJNTPA115JBFA AH Louver link2-5-2 MLOV-A393JBFA AH Vertical louver2-5-3 MLOV-A414JBFA AH Vertical louver2-5-4 PDAI-A161JBFA AH Louver base2-6 CHLD-A112JBKZ AZ Bearing ass'y2-7 CLOV-A055JBKZ AU Louver ass'y

2-7-1 LHLD-A722JBFA AM Louver holder2-7-2 LHLD-A723JBFA AM Louver holder2-7-3 MLOV-A394JBFA AH H-louver2-8-1 HPNL-A778JBRA AZ Open panel2-8-2 HBDG-A002KKEA AE Al badge2-9 CPNL-A526JBKZ BD Cont.box cover ass'y

2-9-1 GBTN-A007JBFA AU Button2-9-2 PCOV-B068JBWZ AH Box cover2-9-3 PCOV-B215JBFA AF Cover2-10 CSRA-A647JBKZ BG Drain pan ass'y

2-10-1 CHOS-A018JBKZ AN Drain hose ass'y2-10-2 LPLT-A058JBPZ AC Hose holder2-10-3 PHOS-A044JBEZ AM Drain hose2-10-4 DSRA-A275JBKZ BE Drain pan sub ass'y2-10-5 GGAD-A063JBTA AQ Wire guard2-10-6 LPFT-A155JBFZ AG Drain joint2-10-7 MJNT-A019JBFA AM Joint2-10-8 MLOV-A395JBFA AU Air flow louver2-10-9 PGUMMA110JBE0 AD Drain plug2-10-10 LHLD-A712JBFZ AU Lead wire guide2-10-11 NBRG-A038JBFA AC Bearing c2-11 CWAK-C619JBKZ BH Front panel ass'y2-12 DCHS-A537JBKZ BC Cabinet ass'y2-13 DCOV-A261JBKZ AH Cover ass'y2-14 DDAI-A058JBKZ BA Holder ass'y2-15 LHLD-A767JBFA AH Terminal holder2-16 PCOV-B168JBWZ AL Cover2-17 PDAI-A170JBFA AQ Holder2-18 PCOV-B157JBFA AF Cover2-19 TLABCC037JBRZ AE Wiring diagram2-20 TSPC-F317JBRZ AK Name badge2-21 HDECQA130JBRA AZ Display panel2-22 LHLD-A303JBFA AD Tube cover2-23 LHLD-A711JBFZ AU Bering holder2-24 LHLD-A751JBFA AH Led holder2-28 MSPR-A168JBEZ AC Spring2-29 NFANCA103JBKZ AZ Cross flow fan2-30 PCOV-B065JBFZ AH Motor cover2-32 PCOV-B163JBFA AF Cover2-33 PDAI-A182JBFZ AH Holder2-34 PFILMA209JBEZ AQ Air filter2-35 PPLTNA083JBWZ AT Mounting angle2-36 PSEL-C885JBEZ AC Seal2-37 PSEL-C900JBEZ AF Seal2-38 PCOV-B183JBFZ AH Holder2-39 PCOV-B184JBFZ AH Holder

3

Page 44: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRNPRICE NEW PART

NO. PARTS CODE RANK MARK RANK DESCRIPTION

2-40 PCOV-B113JBFZ AM Led guide2-41 PDAI-A179JBFZ AH Terminal base2-42 PBOX-A457JBFA AP Control box2-43 PCOV-B071JBPZ AN Cont.box cover2-44 PFPFPC877JBEZ AC Insulator2-45 PFPFPC708JBEZ AC Seal2-46 LHLD-A715JBFZ AU Thermistor holder3-1 CPIPCA916JBKZ BE Inlet tube ass'y

3-1-1 PFPFPB954JBEZ AG Cabinet insulator e3-2 DEVA-A267JBKZ BZ Evaporator ass'y3-3 DCOV-A260JBKZ AM Cover-l ass'y4-1 CFIL-A108JBKZ AR Purify filter ass'y4-2 CRMC-A673JBEZ BA Remote control4-3 FFZK-A210JBKZ AN Screws kit4-4 LPFT-A029JBF0 AD Drain joint4-5 LHLD-A731JBFA AU Cord holder

4-6-1 TINS-A982JBRZ AR Installation manual14-7 TINSEA448JBRZ AR Operation manual4-8 UBATUA027JBE0 AE Battery pack4-9 TLAB-C926JBEZ AK Eu energy label

[2] OTHER PARTS (Indoor unit)2-25 LHLDW0362JBE0 AA Wire holder2-26 LHLDW0365JBE0 AA Wire holder2-27 LX-BZA075JBE0 AA Special screw4-3-1 LX-BZA357JBEZ AE Special screw4-10 TLABKE028JBRZ AF No card90-1 CPADBA085JBKZ AK Packing pad ass'y90-2 SPADBA216JBEZ AF Pad90-3 SPAKCC043JBEZ AX Packing case90-4 SSAKAA106JBEZ AE Bag

[1] INDOOR UNIT PARTS

4

Page 45: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

[3] OUTDOOR UNIT PARTS

2-17

2-36

2-34

2-33

2-18

2-21

1-11

2-19

2-31

2-26

3-12

1-10

2-27

2-35

3-15

3-14

3-13

3-10

2-28

2-20

2-7-1

2-7-2

2-30

2-25

2-132-14

2-1

1-4

1-5

3-9

3-5

3-1

1-4

2-32

3-20

2-15

2-162-6

3-2

2-4

2-4

1-7

1-3

1-1

2-2

2-32-7

2-9

2-10

2-11

1-2-71-2-6

2-8

1-2

2-37

2-392-38

1-6

2-12

3-163-18

3-173-19

3-8

3-6

5

Page 46: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

NO. PARTS CODE PRICE RANK

NEW MARK

PART RANK DESCRIPTION

[3] OUTDOOR UNIT PARTS1-1 CMOTLB078JBEZ BL Fan moter1-2 DSGY-B834JBKZ CA Control board unit

1-2-6 RH-IXA790JBZZ BC Ipm1-2-7 VHDRBV2506+-F AL Diode bridge1-3 QW-VZF245JBZZ AP Lead wire1-4 RCILZA009JBZZ BA Reactor1-5 RTHM-A022JBE0 AN Thermistor1-6 QTANZA001JBZZ AQ Terminal board1-7 FW-VZA056JBKZ AR Lead wire1-10 RFIL-A064JBE0 AF Ferrite core1-11 RH-HXA029JBZZ AX Thermistor ass'y2-1 LANGKA157JBPZ AQ Motor angle2-2 CCAB-A408JBKZ BA Top plate ass'y2-3 TLABCC170JBRZ AC Wiring diagram2-4 LX-BZA355JBEZ AE Special screw2-6 LANG-A504JBYZ AP Reactor angle2-7 CFTA-A268JBKZ AN Cover

2-7-1 PCOV-A594JBPZ AE Terminal cover2-7-2 PFTA-A090JBFA AL Cover2-8 PRDAFA191JBEZ AR Heat sink2-9 LHLD-A684JBFA AN Holder2-10 LHLD-A685JBFA AF Holder2-11 DBOX-A049JBWZ AT Control box ass'y2-12 PDAI-A187JBWZ AH Terminal holder2-13 PCOV-A595JBFZ AE Cover2-14 PSKR-A284JBPZ AT Bulkhead2-15 GCAB-A220JBTA BC Front panel2-16 GGADPA007JBFA AS Fan gaurd2-17 JHNDPA015JBFA AD Handle2-18 LHLD-A449JBF0 AH Thermistor holder2-19 LHLD-A491JBFZ AD Cord clamp2-20 LHLD-A492JBFZ AD Cord clamp base2-21 MSPR-A026JBE0 AB Spring2-25 NFANPA118JBEZ AU Propeller fan2-26 PPLT-A375JBTA AW Side cover r2-27 PSPF-A918JBEZ AT Comp cover top2-28 PSPF-A919JBEZ AE Compressor cover2-30 CANG-A165JBKZ AH Holder ass'y2-31 TLAB-C511JBRA AC Label2-32 TLABBA160JBRA AL IVT LABEL2-33 TSPC-F318JBRZ Name badge2-34 PPLT-A195JBTA AS Side cover L2-35 PSEL-C830JBEZ AF Seal2-36 CHET-A025JBKZ BM Heater ass'y2-37 PCOV-A997JBWZ AM Cover2-38 PSEL-C685JBEZ AC Seal2-39 PSEL-C686JBEZ AC Seal3-1 CCHS-A931JBTA BB Base pan ass'y3-2 DVLV-A652JBKZ AV 3way valve unit3-5 DVLV-A572JBKZ AQ 2way valve unit3-6 CVLV-A799JBKZ BS Reverse valve ass'y3-8 CCIL-A129JBKZ AU Coil ass'y3-9 PVLVXA061JBEZ BD Reverse valve3-10 PDAI-A123JBTA AL Flare coupling base3-12 DCON-A291JBPZ BX Condenser ass'y3-13 PCMPRA430JBEZ CC Compressor3-14 GLEG-A099JBE0 AD Compressor cushion3-15 LX-NZA313JBEZ AE Special nut3-16 LX-NZA002JBE0 AA Special nut3-17 MSPR-A157JBEZ AD Protector spring3-18 PCOV-A736JBEZ AH Terminal cover3-19 PSEL-C248JBEZ AG Terminal gasket3-20 PSPF-A977JBEZ Compressor cover

[4] OTHER PARTS1-2-1 QFS-CA001JBZZ AK Fuse (20A 250V)1-2-2 QFS-GA051JBZZ AD Fuse1-2-3 QFS-GA052JBZZ AD Fuse1-2-4 QFS-CA002JBZZ AH Fuse (15A 250V)1-2-5 QFS-GA064JBZZ AF Fuse2-23 MSPR-A036JBE0 AB Thermistor spring2-24 MSPR-A143JBEZ AD Spring3-7 DVLV-A662JBKZ BL Control valve ass'y90-1 CPADBA048JBKZ AF Top pad ass'y90-2 CPADBA049JBKZ AM Bottom pad ass'y90-3 SPAKCC044JBEZ AS Packing case

6

Page 47: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

INDEX

PARTS CODE No. PRICE RANK

NEW MARK

PART RANK

[ C ]CANG-A165JBKZ 3-2-30 AHCCAB-A408JBKZ 3-2-2 BACCHS-A931JBTA 3-3-1 BBCCIL-A129JBKZ 3-3-8 AUCCOV-A113JBKZ 1-2-2 BECCOV-A119JBKZ 1-2-3 BECDAI-A020JBKZ 1-2-5 BECFIL-A108JBKZ 1-4-1 ARCFTA-A268JBKZ 3-2-7 ANCHET-A025JBKZ 3-2-36 BMCHLD-A112JBKZ 1-2-6 AZCHOS-A018JBKZ 1-2-10-1 ANCKITTA073AKKZ 1-1-10-1 BECLOV-A055JBKZ 1-2-7 AUCMOT-A437JBKZ 1-1-1 BQCMOTLB078JBEZ 3-1-1 BLCPADBA048JBKZ 4-90-1 AFCPADBA049JBKZ 4-90-2 AMCPADBA085JBKZ 2-90-1 AKCPIPCA916JBKZ 1-3-1 BECPNL-A526JBKZ 1-2-9 BDCRMC-A673JBEZ 1-4-2 BACSRA-A647JBKZ 1-2-10 BGCVLV-A799JBKZ 3-3-6 BSCWAK-C619JBKZ 1-2-11 BH

[ D ]DBOX-A049JBWZ 3-2-11 ATDCHS-A537JBKZ 1-2-12 BCDCON-A291JBPZ 3-3-12 BXDCOV-A260JBKZ 1-3-3 AMDCOV-A261JBKZ 1-2-13 AHDDAI-A058JBKZ 1-2-14 BADEVA-A267JBKZ 1-3-2 BZDPWBFA397JBKZ 1-1-14 AUDPWBFA398JBKZ 1-1-13 BLDPWBFA462JBKZ 1-1-12 BSDSGY-B834JBKZ 3-1-2 CADSRA-A275JBKZ 1-2-10-4 BEDVLV-A572JBKZ 3-3-5 AQDVLV-A652JBKZ 3-3-2 AVDVLV-A662JBKZ 4-3-7 BL

[ F ]FCOV-A199JBRA 1-2-3-1 AKFFZK-A210JBKZ 1-4-3 ANFSGY-A295JBKZ 1-1-10 BQFW-VZA056JBKZ 3-1-7 AR

[ G ]GBTN-A007JBFA 1-2-9-1 AUGCAB-A220JBTA 3-2-15 BCGGAD-A063JBTA 1-2-10-5 AQGGADPA007JBFA 3-2-16 ASGLEG-A099JBE0 3-3-14 AD

[ H ]HBDG-A002KKEA 1-2-8-2 AEHDECQA130JBRA 1-2-21 AZHPNL-A778JBRA 1-2-8-1 AZ

[ J ]JHNDPA015JBFA 3-2-17 AD

[ L ]LANG-A504JBYZ 3-2-6 APLANGKA157JBPZ 3-2-1 AQLHLD-A303JBFA 1-2-22 ADLHLD-A449JBF0 3-2-18 AHLHLD-A491JBFZ 3-2-19 ADLHLD-A492JBFZ 3-2-20 ADLHLD-A684JBFA 3-2-9 ANLHLD-A685JBFA 3-2-10 AFLHLD-A711JBFZ 1-2-23 AULHLD-A712JBFZ 1-2-10-10 AULHLD-A714JBFA 1-1-10-3 AULHLD-A715JBFZ 1-2-46 AULHLD-A722JBFA 1-2-7-1 AMLHLD-A723JBFA 1-2-7-2 AMLHLD-A731JBFA 1-4-5 AULHLD-A751JBFA 1-2-24 AHLHLD-A767JBFA 1-2-15 AHLHLDW0362JBE0 2-2-25 AALHLDW0365JBE0 2-2-26 AA

LPFT-A029JBF0 1-4-4 ADLPFT-A155JBFZ 1-2-10-6 AGLPLT-A058JBPZ 1-2-10-2 ACLX-BZA075JBE0 2-2-27 AALX-BZA355JBEZ 3-2-4 AELX-BZA357JBEZ 2-4-3-1 AELX-NZA002JBE0 3-3-16 AALX-NZA313JBEZ 3-3-15 AE

[ M ]MJNT-A019JBFA 1-2-10-7 AMMJNTPA115JBFA 1-2-5-1 AHMLOV-A393JBFA 1-2-5-2 AHMLOV-A394JBFA 1-2-7-3 AHMLOV-A395JBFA 1-2-10-8 AUMLOV-A414JBFA 1-2-5-3 AHMSPR-A026JBE0 3-2-21 ABMSPR-A036JBE0 4-2-23 ABMSPR-A143JBEZ 4-2-24 ADMSPR-A157JBEZ 3-3-17 ADMSPR-A168JBEZ 1-2-28 AC

[ N ]NBRG-A038JBFA 1-2-10-11 ACNFANCA103JBKZ 1-2-29 AZNFANPA118JBEZ 3-2-25 AU

[ P ]PBOX-A457JBFA 1-2-42 APPCMPRA430JBEZ 3-3-13 CCPCOV-A594JBPZ 3-2-7-1 AEPCOV-A595JBFZ 3-2-13 AEPCOV-A736JBEZ 3-3-18 AHPCOV-A997JBWZ 3-2-37 AMPCOV-B062JBFA 1-2-1 AHPCOV-B065JBFZ 1-2-30 AHPCOV-B068JBWZ 1-2-9-2 AHPCOV-B071JBPZ 1-2-43 ANPCOV-B113JBFZ 1-2-40 AMPCOV-B118JBFA 1-2-3-2 AKPCOV-B157JBFA 1-2-18 AFPCOV-B163JBFA 1-2-32 AFPCOV-B168JBWZ 1-2-16 ALPCOV-B183JBFZ 1-2-38 AHPCOV-B184JBFZ 1-2-39 AHPCOV-B215JBFA 1-2-9-3 AFPDAI-A123JBTA 3-3-10 ALPDAI-A161JBFA 1-2-5-4 AHPDAI-A170JBFA 1-2-17 AQPDAI-A179JBFZ 1-2-41 AHPDAI-A182JBFZ 1-2-33 AHPDAI-A187JBWZ 3-2-12 AHPFILMA209JBEZ 1-2-34 AQPFPFPB954JBEZ 1-3-1-1 AGPFPFPC708JBEZ 1-2-45 ACPFPFPC877JBEZ 1-2-44 ACPFTA-A090JBFA 3-2-7-2 ALPGID-A127JBFZ 1-2-4 AGPGUMMA110JBE0 1-2-10-9 ADPGUMMA279JBEZ 1-1-1-2 AUPGUMMA280JBEZ 1-1-1-3 AUPHOS-A044JBEZ 1-2-10-3 AMPPLT-A195JBTA 3-2-34 ASPPLT-A375JBTA 3-2-26 AWPPLTNA083JBWZ 1-2-35 ATPRDAFA191JBEZ 3-2-8 ARPSEL-C248JBEZ 3-3-19 AGPSEL-C685JBEZ 3-2-38 ACPSEL-C686JBEZ 3-2-39 ACPSEL-C830JBEZ 3-2-35 AFPSEL-C885JBEZ 1-2-36 ACPSEL-C900JBEZ 1-2-37 AFPSKR-A284JBPZ 3-2-14 ATPSPF-A918JBEZ 3-2-27 ATPSPF-A919JBEZ 3-2-28 AEPSPF-A977JBEZ 3-3-20PVLVXA061JBEZ 3-3-9 BD

[ Q ]QACC-A319JBZZ 1-1-17 AUQFS-CA001JBZZ 4-1-2-1 AKQFS-CA002JBZZ 4-1-2-4 AHQFS-GA051JBZZ 4-1-2-2 AD

PARTS CODE No. PRICE RANK

NEW MARK

PART RANK

7

Page 48: TopPage SERVICE MANUAL SPLIT TYPE ROOM AIR CONDITIONER

AYXP9FRN

QFS-GA052JBZZ 4-1-2-3 ADQFS-GA064JBZZ 4-1-2-5 AFQTANZA001JBZZ 3-1-6 AQQTANZA021JBZZ 1-1-21 ANQTANZA022JBZZ 1-1-15 AHQTANZA026JBZZ 1-1-16 AKQW-VZE859JBZZ 1-1-10-2 AMQW-VZE965JBZZ 1-1-18 AEQW-VZE966JBZZ 1-1-19 AEQW-VZE970JBZZ 1-1-7 AEQW-VZE972JBZZ 1-1-11 APQW-VZE973JBZZ 1-1-2 AHQW-VZF173JBZZ 1-1-8 AFQW-VZF245JBZZ 3-1-3 APQW-VZF246JBZZ 1-1-5 AUQW-VZF247JBZZ 1-1-6 AU

[ R ]RCILZA009JBZZ 3-1-4 BARFIL-A064JBE0 1-1-9 AF

" 3-1-10 AFRH-HXA029JBZZ 3-1-11 AXRH-HXA048JBZZ 1-1-20 APRH-IXA790JBZZ 3-1-2-6 BCRMOT-A116JBZZ 1-1-3 APRMOT-A117JBZZ 1-1-4 APRTHM-A022JBE0 3-1-5 AN

[ S ]SPADBA216JBEZ 2-90-2 AFSPAKCC043JBEZ 2-90-3 AXSPAKCC044JBEZ 4-90-3 ASSSAKAA106JBEZ 2-90-4 AE

[ T ]TINS-A982JBRZ 1-4-6-1 ARTINSEA448JBRZ 1-4-7 ARTLABBA160JBRA 3-2-32 ALTLAB-C511JBRA 3-2-31 ACTLAB-C926JBEZ 1-4-9 AKTLABCC037JBRZ 1-2-19 AETLABCC170JBRZ 3-2-3 ACTLABKE028JBRZ 2-4-10 AFTSPC-F317JBRZ 1-2-20 AKTSPC-F318JBRZ 3-2-33

[ U ]UBATUA027JBE0 1-4-8 AE

[ V ]VHDRBV2506+-F 3-1-2-7 AL

PARTS CODE No. PRICE RANK

NEW MARK

PART RANK

8