49
TP48200A-D15A1 & H15A3 & H15A5 V300R001 Quick Installation Guide Issue 06 Date 2013-07-23 HUAWEI TECHNOLOGIES CO., LTD.

TP48200A-D15A1 & H15A3 & H15A5 V300R001 Quick Installation Guide 06

Embed Size (px)

Citation preview

  • TP48200A-D15A1 & H15A3 & H15A5 V300R001

    Quick Installation Guide

    Issue 06

    Date 2013-07-23

    HUAWEI TECHNOLOGIES CO., LTD.

  • Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    i

    Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.

    No part of this document may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    Trademarks and Permissions

    and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

    All other trademarks and trade names mentioned in this document are the property of their respective

    holders.

    Notice

    The purchased products, services and features are stipulated by the contract made between Huawei and

    the customer. All or part of the products, services and features described in this document may not be

    within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

    information, and recommendations in this document are provided "AS IS" without warranties, guarantees or

    representations of any kind, either express or implied.

    The information in this document is subject to change without notice. Every effort has been made in the

    preparation of this document to ensure accuracy of the contents, but all statements, information, and

    recommendations in this document do not constitute a warranty of any kind, express or implied.

    Huawei Technologies Co., Ltd.

    Address: Huawei Industrial Base

    Bantian, Longgang

    Shenzhen 518129

    People's Republic of China

    Website: http://www.huawei.com

    Email: [email protected]

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide About This Document

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    ii

    About This Document

    Purpose

    This document describes the TP48200A-D15A1 & H15A3 & H15A5 in terms of its structure,

    components, installation, and commissioning.

    Intended Audience

    This document is intended for:

    Installation and commissioning engineers

    Technical support engineers

    Symbol Conventions

    The symbols that may be found in this document are defined as follows.

    Symbol Description

    Indicates a hazard with a high level or medium level of risk

    which, if not avoided, could result in death or serious injury.

    Indicates a hazard with a low level of risk which, if not

    avoided, could result in minor or moderate injury.

    Indicates a potentially hazardous situation that, if not avoided,

    could result in equipment damage, data loss, performance

    deterioration, or unanticipated results.

    Provides a tip that may help you solve a problem or save time.

    Provides additional information to emphasize or supplement important points in the main text.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide About This Document

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    iii

    Change History

    Changes between document issues are cumulative. The latest document issue contains all the

    changes made in earlier issues.

    Issue 06 (2013-07-23)

    Modified section 7.1.1 UIM02C.

    Issue 05 (2013-04-28)

    Optimized the content of the document, including standardizing the terminology and

    improving the accuracy of the description.

    Issue 04 (2013-02-28)

    Add the installation dimensions for the cabinet installation holes.

    Issue 03 (2013-01-09)

    This issue is the third official release, which incorporates the following changes:

    Chapter 6 Installing Components

    Modify the picture of Install a temperature and humidity sensor.

    Chapter 8 Powering On and Commissioning

    Set battery fuse break alarm "Enable/Disable" status is added.

    Issue 02 (2012-11-12)

    This issue is the second official release, which incorporates the following changes:

    Port description is modified.

    Issue 01 (2012-07-28)

    This issue is used for first office release.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide Contents

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    iv

    Contents

    About This Document .................................................................................................................... ii

    1 Safety Precautions ......................................................................................................................... 1

    1.1 Health and Safety ............................................................................................................................................. 1

    1.1.1 Overview ................................................................................................................................................. 1

    1.1.2 Electrical Safety ...................................................................................................................................... 3

    1.1.3 Inflammable Environment ...................................................................................................................... 4

    1.1.4 Battery ..................................................................................................................................................... 4

    1.1.5 Working at Heights ................................................................................................................................. 6

    1.1.6 Using Ladders ......................................................................................................................................... 7

    1.1.7 Mechanical Safety ................................................................................................................................... 7

    1.1.8 Bundling Signal Cables ........................................................................................................................... 8

    1.2 Equipment Safety ............................................................................................................................................. 9

    1.2.1 Electricity Safety ..................................................................................................................................... 9

    1.2.2 Electrostatic Discharge............................................................................................................................ 9

    1.2.3 Laying Cables ....................................................................................................................................... 10

    2 Installation Preparations ........................................................................................................... 11

    2.1 Tools ............................................................................................................................................................... 11

    2.2 Installation Clearance Requirements .............................................................................................................. 12

    2.3 Prepare Cables ................................................................................................................................................ 12

    3 Configuration ............................................................................................................................... 14

    4 Installing the Cabinet ................................................................................................................. 18

    5 Installing a PGND Cable ........................................................................................................... 21

    6 Installing Components............................................................................................................... 22

    6.1 Installing Rectifiers ........................................................................................................................................ 22

    6.2 Installing a Smoke Sensor(Optional) ............................................................................................................. 23

    6.2.1 Securing the Smoke Sensor ................................................................................................................... 23

    6.2.2 Connecting the Smoke Sensor .............................................................................................................. 23

    6.3 Installing a Temperature and Humidity Sensor(Optional) .............................................................................. 24

    6.3.1 Securing the Temperature and Humidity Sensor ................................................................................... 24

    6.3.2 Connecting the Temperature and Humidity Sensor ............................................................................... 24

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide Contents

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    v

    6.4 Installing a Water Sensor(Optional) ............................................................................................................... 25

    6.4.1 Securing the Water Sensor .................................................................................................................... 25

    6.4.2 Connecting the Water Sensor ................................................................................................................ 25

    7 Installing Cables ......................................................................................................................... 27

    7.1 Installing Signal Cables and Communication Cables ..................................................................................... 27

    7.1.1 UIM02C ................................................................................................................................................ 27

    7.1.2 Installing Dry Contacts and Boolean Values Signal Cables .................................................................. 29

    7.1.3 Installing Sensor Cables ........................................................................................................................ 29

    7.1.4 Installing Communications Cables ....................................................................................................... 30

    7.2 Installing Power Cables .................................................................................................................................. 30

    7.2.1 Installing DC Output Cables ................................................................................................................. 31

    7.2.2 Installing Storage Batteries and Copper Bars ....................................................................................... 32

    7.2.3 Installing AC Output Cables ................................................................................................................. 34

    7.2.4 Installing AC Input Cables .................................................................................................................... 35

    8 System Commissioning ............................................................................................................. 38

    8.1 Installation Verification .................................................................................................................................. 38

    8.2 Powering On and Commissioning .................................................................................................................. 38

    8.2.1 Setting Parameters ................................................................................................................................ 38

    8.3 Powering On................................................................................................................................................... 42

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    1

    1 Safety Precautions 1.1 Health and Safety

    1.1.1 Overview

    Introduction

    This section describes the safety precautions you must take before installing or maintaining

    Huawei equipment.

    To ensure safety of humans and the equipment, pay attention to the safety symbols on the

    equipment and all the safety instructions in this document.

    The "NOTE", "CAUTION", and "WARNING" marks in other documents do not

    represent all the safety instructions. They are only supplements to the safety instructions.

    Installation and maintenance personnel must understand basic safety precautions to avoid

    hazards.

    When operating Huawei equipment, in addition to following the general precautions in

    this document, follow the specific safety instructions given by Huawei.

    Only trained and qualified personnel are allowed to install, operate, and maintain Huawei

    equipment.

    Local Safety Regulations

    When operating Huawei equipment, you must follow the local laws and regulations. The

    safety instructions in this document are only supplements to the local laws and regulations.

    General Requirements

    To minimize risk of personal injury and damage to equipment, read and follow all the

    precautions in this document before performing any installation or maintenance.

    Ensure that the instructions provided in this document are followed completely. This section

    also provides guidelines for selecting the measuring and testing devices.

    Installation The device (or system) must be installed in an access-controlled location.

    The device can be mounted only on concrete or non-combustible surfaces.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    2

    The device must be fixed securely on the floor or to other immovable objects such as

    walls and mounting racks before operation.

    When installing the unit, always make the ground connection first and disconnect it at

    the end.

    Do not block the ventilation while the device is operating. Keep a minimum distance of 5

    cm between the device and the wall or other objects that may block the ventilation.

    Tighten the thumbscrews by using a tool after initial installation and subsequent access

    to the panel.

    Ground Do not damage the ground conductor or operate the device in the absence of a properly

    installed ground conductor. Conduct the electrical inspection carefully.

    The device (or system) must be connected permanently to the protection ground before

    an operation. The cross-sectional area of the protective ground conductor must be at least

    10 mm2.

    Power Supply For AC-supplied models: The device applies to TN or TT power system.

    For DC-supplied models: Reinforced insulation or double insulation must be provided to

    isolate the DC source from the AC mains supply.

    For DC-supplied model: The device applies to DC power source that complies with the

    Safety Extra-Low Voltage (SELV) requirements in IEC 60950-1 based safety standards.

    Prepared conductors are connected to the terminal block, and only the appropriate

    AWG/Type of wire is secured with the lug terminals.

    Human Safety Do not operate the device or cables during lightning strikes.

    Remove the AC power connector when there is lightning. Do not use fixed terminals or

    touch terminals or antenna connectors when there is lightning.

    To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to

    telecommunication network voltage (TNV) circuits.

    Move or lift the chassis by holding its lower edge. Do not hold the handles on certain

    modules such as power supply, fans, and boards because they cannot support the weight

    of the device.

    At least two persons are required to lift the chassis. When lifting it, keep your back

    straight and move stably.

    Do not wear jewelry or watches when you operate the device.

    Operator Only qualified professional personnel are allowed to install, configure, operate, and

    disassemble the device.

    Only the personnel authenticated or authorized by Huawei are allowed to replace or

    change the device of the parts of the device (including the software).

    Any fault or error that might cause safety problems must be reported immediately to a

    supervisor.

    Only qualified personnel are allowed to remove or disable the safety facilities and to

    troubleshoot and maintain the device.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    3

    1.1.2 Electrical Safety

    High Voltage

    The high voltage power supply provides power for the device operation. Direct or indirect

    contact (through damp objects) with high voltage and AC mains supply may result in fatal

    danger.

    During the installation of the AC power supply facility, follow the local safety

    regulations. The personnel who install the AC facility must be qualified to perform high

    voltage and AC operations.

    Do not wear conductive articles, such as watches, hand chains, bracelets, and rings

    during the operation.

    When water is found in the rack or the rack is damp, switch off the power supply

    immediately.

    When the operation is performed in a damp environment, make sure that the device is

    dry.

    Non-standard and improper high voltage operations may result in fire and electric shock.

    Therefore, you must abide by the local rules and regulations when bridging and wiring AC

    cables. Only qualified personnel are allowed to perform high voltage and AC operations.

    Before powering on a device, ground the device. Otherwise, personal injury or device damage

    may be caused by high leakage current.

    Tools

    Dedicated tools must be used during high voltage and AC operations. Avoid using ordinary

    tools.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    4

    High Electrical Leakage

    Ground the device before powering it on. Otherwise, personal injury or device damage may

    be caused by high leakage current.

    If a "high electrical leakage" tag is present on the power terminal of the device, you must

    ground the device before powering it on.

    Power Cable

    Do not install or remove power cables when the device is on. Transient contact between the

    core of the power cable and the conductor may generate electric arcs or sparks, which may

    cause fire or hurt human eyes.

    Before installing or removing the power cable, turn off the power switch.

    Before connecting a power cable, check that the label on the power cable is correct.

    1.1.3 Inflammable Environment

    Operating the electrical device in an inflammable environment can be fatal.

    Do not place the device in an environment that has inflammable and explosive air or gas. Do

    not perform any operation in this environment.

    1.1.4 Battery

    Storage Battery

    Before operating storage batteries, carefully read the safety precautions for battery handling

    and connection.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    5

    Improper handling of storage batteries causes hazards.

    When operating storage batteries, avoid short circuit and overflow or leakage of the

    electrolyte. Electrolyte overflow may damage the device. It will corrode metal parts and

    circuit boards, and ultimately damage the device and cause short circuit of circuit boards.

    Basic Precautions

    Before installing and maintaining the battery, note the following:

    Do not wear metal articles such as wristwatch, hand chain, bracelet, and ring.

    Use special insulation tools.

    Take care to protect your eyes when operating the device.

    Wear rubber gloves and a protective coat in case of electrolyte overflow.

    When handling a storage battery, ensure that its electrodes are upward. Leaning or

    reversing the storage battery is prohibited.

    Short Circuit

    Battery short circuit may cause human injuries. Although the voltage of ordinary batteries is

    low, the instantaneous high current caused by the short circuit releases a great deal of energy.

    There is danger of explosion if the battery is incorrectly replaced. Therefore, replace the

    battery only with the same or equivalent type recommended by the manufacturer.

    Keep away metal objects, which may cause battery short circuit, from batteries. If metal

    objects must be used, first disconnect the batteries in use before performing any other

    operations.

    Hazardous Gas

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    6

    Do not use unsealed lead acid storage batteries. Lead acid storage batteries must be placed

    horizontally and stably to prevent the batteries from releasing flammable gas, which may

    cause fire or erode the device.

    Lead acid storage batteries in use emit flammable gas. Therefore, ventilation and

    fireproofing measures must be taken at the sites where lead acid storage batteries are used.

    Battery Temperature

    If a battery overheats, the battery may be deformed or damaged, and the electrolyte may

    overflow.

    When the temperature of the battery is higher than 60 C, check the battery for electrolyte

    overflow. If the electrolyte overflows, absorb and counteract the electrolyte immediately.

    Battery Leakage

    When the electrolyte overflows, absorb and counteract the electrolyte immediately.

    When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte

    may hurt human bodies. When you find the electrolyte leaks, use the following substances to

    counteract and absorb the leaking electrolyte:

    Sodium bicarbonate (baking soda): NaHCO3

    Sodium carbonate (soda): Na2CO3

    Select a substance to counteract and absorb the leaking electrolyte according to the

    instructions of the battery manufacturer.

    1.1.5 Working at Heights

    Avoid object falling when you work at heights.

    When working at heights, fulfill the following requirements:

    Only trained personnel can work at heights.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    7

    Prevent the devices and tools that you carry from falling down.

    Take safety and protection measures, for example, wear a helm and safety belt.

    Wear warm clothes when working at heights in a cold region.

    Before working at heights, check that all the lifting facilities are in good condition.

    1.1.6 Using Ladders

    Checking a Ladder Before using a ladder, check whether the ladder is damaged. Only the ladder in good

    condition can be used.

    Before using a ladder, you should know the maximum weight capacity of the ladder.

    Avoid overweighing the ladder.

    Placing a Ladder

    The recommended gradient of ladders is 75 degrees. You can measure the gradient of the

    ladder with an angle square or your arms. When using a ladder, ensure that the wider feet of

    the ladder are downward, or take protection measures for the ladder feet to prevent the ladder

    from sliding. Ensure that the ladder is placed securely.

    Climbing Up a Ladder

    When climbing up a ladder, note the following:

    Ensure that the center of gravity of your body does not deviate from the edges of the two

    long sides.

    To minimize the risk of falling, hold your balance on the ladder before any operation.

    Do not climb higher than the fourth rung of the ladder (counted from up to down).

    If you want to climb up a roof, ensure that the ladder top is at least one meter higher than

    the roof.

    1.1.7 Mechanical Safety

    Drilling Holes

    Do not drill the cabinet at will. Drilling holes without complying with the requirements affects

    the electromagnetic shielding performance of the cabinet and damages the cables inside the

    cabinet. In addition, if the scraps caused by drilling enter the cabinet, the printed circuit

    boards (PCBs) may be short circuited.

    Before you drill a hole in the cabinet, wear insulated gloves and remove the internal

    cables from the cabinet.

    Wear an eye protector when drilling holes. This is to prevent your eyes from being

    injured by the splashing metal scraps.

    Ensure that the scraps caused by drilling do not enter the cabinet.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    8

    Drilling holes without complying with the requirements affects the electromagnetic

    shielding performance of the cabinet.

    After drilling, clean the metal scraps immediately.

    Sharp Objects

    Before you hold or carry a device, wear protective gloves to avoid getting injured by sharp

    edges of the device.

    Handling Fans

    When handling fans, note the following:

    When replacing a component, place the component, screws, and tools in a safe place.

    Otherwise, if any of them fall into the operating fans, the fans may be damaged.

    When replacing a component near fans, do not insert your fingers or boards into the

    operating fans until the fans are switched off and stops running.

    Lifting Heavy Objects

    When heavy objects are being lifted, do not stand or walk under the cantilever or the lifted

    object.

    1.1.8 Bundling Signal Cables

    Do not bundle signal cables with high current cables or high voltage cables.

    Maintain a minimum space of 150 mm between adjacent ties.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    9

    1.2 Equipment Safety

    1.2.1 Electricity Safety

    High Electrical Leakage

    If the "high electrical leakage" tag is present on the power terminal of the device, you must

    ground the device before powering it on.

    1.2.2 Electrostatic Discharge

    The static electricity generated by human bodies may damage the electrostatic-sensitive

    components on boards, for example, the large-scale integrated (LSI) circuits.

    Human body movement, friction between human bodies and clothes, friction between shoes

    and floors, or handling of plastic articles causes static electromagnetic fields on human bodies.

    These static electromagnetic fields cannot be eliminated until the static is discharged.

    To prevent electrostatic-sensitive components from being damaged by the static on human

    bodies, you must wear a well-grounded ESD wrist strap when touching the device or handling

    boards or application-specific integrated circuits (ASICs).

    Figure 1-1 shows how to wear an ESD wrist strap.

    Figure 1-1 Wearing an ESD wrist strap

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 1 Safety Precautions

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    10

    1.2.3 Laying Cables

    When the temperature is very low, violent strike or vibration may damage the cable sheathing.

    To ensure safety, comply with the following requirements:

    Cables can be laid or installed only when the temperature is higher than 0 C.

    Before laying cables which have been stored in a temperature lower than 0 C, move the

    cables to an environment of the ambient temperature and store them at the ambient

    temperature for at least 24 hours.

    Handle cables with caution, especially at a low temperature. Do not drop the cables

    directly from the vehicle.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 2 Installation Preparations

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    11

    2 Installation Preparations 2.1 Tools

    Table 2-1 shows the tools that must be obtained before installation.

    Table 2-1 Tools

    Combination

    spanner

    Marker pen

    Rubber hammer

    Phillips

    screwdriver

    Flathead

    screwdriver

    Socket spanner

    Wire clippers

    Hydraulic pliers

    Torque spanner

    Diagonal plier

    Adjustable

    spanner

    Paper knife

    Network cable

    pliers

    Sharp-nose pliers

    Wire stripper

    RJ-45.connect

    or crimping

    pliers

    Power cable

    cutting pliers

    Power cable

    crimping pliers

    Crimping pliers

    ESD-preventiv

    e wrist strap

    Percussion

    drill

    Drill bit

    Clamp meter

    Hot air dun

    Steel tape

    Vacuum cleaner

    Multimeter

    Antistatic gloves

    Protective gloves

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 2 Installation Preparations

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    12

    2.2 Installation Clearance Requirements Figure 2-1 shows the installation clearance requirements.

    Figure 2-1 Installation clearance requirements

    2.3 Prepare Cables

    Table 2-2 lists the specification of the system cables.

    Table 2-2 The specification of the system cables

    Cable Cable Diameter and Color

    Signal cables to dry contacts,

    Boolean values, and sensor ports Not provided

    RS485, RS232 or Fast Ethernet

    (FE) cable Not provided

    DC Power cable to the primary

    load Not provided

    DC Power cable to the secondary

    load Not provided

    The PGND cable Cross-sectional area: 16 mm2 (0.02 in.2) Color: yellow green cable

    AC input power cable single-phase: Cross-sectional area: 25 mm2 (0.04 in.

    2 )

    three-phase: Cross-sectional area: 16 mm2

    (0.02 in.2

    )

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 2 Installation Preparations

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    13

    Cable Cable Diameter and Color (recommended /Not provided)

    Cut cables to a length suitable for the actual cable route, and then add OT terminals or cord

    end terminals to each end of the cables, as shown in Figure 2-2, Figure 2-3.

    Figure 2-2 Prepare OT terminals

    Figure 2-3 Prepare cord end terminals.

    The local cable colors prevail. The cable colors in the figure are for reference only.

    Cables routed along the floor should be protected with protection tubes that comply with NFPA70

    standards.

    NOTE

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 3 Configuration

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    14

    3 Configuration Specifications

    Table 3-1 Specifications

    Category Specifications

    Dimensions (H x W x D) Cabinet: 1500 mm (59.06 in.) x 650 mm (25.59 in.) x 650

    mm (25.59 in.)

    Base: 100 mm (3.94 in.) x 650 mm (25.59 in.) x 650 mm

    (25.59 in.)

    Weight 120 kg (264.6 lb) (without rectifiers or storage batteries)

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 3 Configuration

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    15

    Interior of the Cabinet

    Figure 3-1 Interior of the TP48200A-D15A1

    (1) Maintenance socket (2) AC input circuit breakers (3) Ground bar

    (4) Cable hole (5) Storage battery circuit breakers (6) Load circuit breakers

    (7) Site monitoring unit (SMU) (8) Space for rectifiers (9) Battery rack

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 3 Configuration

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    16

    Figure 3-2 Interior of the TP48200A- H15A3

    (1) Maintenance socket (2) AC input circuit breakers (3) Ground bar

    (4) Cable hole (5) Storage battery circuit breakers (6) Load circuit breakers

    (7) Site monitoring unit (SMU) (8) Space for rectifiers (9) Battery rack

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 3 Configuration

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    17

    Figure 3-3 Interior of the TP48200A-H15A5

    (1) Maintenance socket (2) AC input circuit breakers (3) Ground bar

    (4) Cable hole (5) Storage battery circuit breakers (6) Load circuit breakers

    (7) Site monitoring unit (SMU) (8) Space for rectifiers (9) Heater

    (10) Battery rack

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 4 Installing the Cabinet

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    18

    4 Installing the Cabinet To install a cabinet, perform the following steps:

    Step 1 Remove the cover of the packaging box and locate the marking-off template on the cover interior, as shown in Figure 4-1.

    Figure 4-1 Marking-off template

    Step 2 Fix the installation hole, as shown in Figure 4-2.

    Figure 4-2 Fixing the installation hole

    (1) Marker (2) Marking-off template (3) Installation hole

    (4) Concrete pad

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 4 Installing the Cabinet

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    19

    Step 3 Drill holes and install expansion sleeves, as shown in Figure 4-3.

    Figure 4-3 Drilling holes and install expansion sleeves

    (1) Expansion bolt(M12) (2) Spring washer (3) Flat washer (4) Expansion sleeve

    (5) Concrete pad

    Step 4 Remove the cabinet from the pallet, as shown in Figure 4-4.

    Figure 4-4 Removing the cabinet

    (1) Pallet

    The configuration prevail, the pallet in the figure is for reference only

    Step 5 Secure the cabinet on the concrete pad, as shown in Figure 4-5.

    NOTE

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 4 Installing the Cabinet

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    20

    Figure 4-5 Securing the cabinet

    ----End

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 5 Installing a PGND Cable

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    21

    5 Installing a PGND Cable The PGND cable is used to connect PGND screws on the cabinet and the ground busbar

    outside the cabinet to ensure proper grounding of the cabinet.

    Install the PGND cable as shown in Figure 5-1.

    Figure 5-1 Installing the PGND cable

    (1) Ground bar for the site (2) Ground bar for the cabinet

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 6 Installing Components

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    22

    6 Installing Components 6.1 Installing Rectifiers

    The rated output current of each rectifier is 50 A. The number of rectifiers depends on actual

    capacity requirements.as shown in Figure 6-1 and Figure 6-2.

    Figure 6-1 Removing the filler panel

    Figure 6-2 Installing rectifiers

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 6 Installing Components

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    23

    6.2 Installing a Smoke Sensor(Optional)

    6.2.1 Securing the Smoke Sensor

    Secure the smoke sensor base to the cabinet top using two M4 mm screws and fasten the

    smoke sensor to the base based on the direction shown in the smoke sensor, as shown in

    Figure 6-3.

    Figure 6-3 Installing a Smoke Sensor

    6.2.2 Connecting the Smoke Sensor

    Connect one end of the smoke sensor signal cable to the "SMOKE" port on the UIM02C and

    the other end to the port on the smoke sensor, as shown in Figure 6-4.

    Figure 6-4 Connect the smoke sensor

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 6 Installing Components

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    24

    6.3 Installing a Temperature and Humidity Sensor(Optional)

    6.3.1 Securing the Temperature and Humidity Sensor

    Secure the temperature and humidity sensor base to the cabinet top, as shown in Figure 6-5.

    Step 1 Secure the temperature and humidity sensor base to the cabinet top using two M4 mm screws.

    Step 2 Connect and secure signal cables of the temperature and humidity sensor to the cabinet base, as shown in the following figure

    Step 3 Install the top cover of the temperature and humidity sensor to the cabinet base.

    Step 4 The final installation view is as follows.

    Figure 6-5 Installing a temperature and humidity sensor

    ----End

    6.3.2 Connecting the Temperature and Humidity Sensor

    Connect one end of the temperature and humidity sensor signal cable to the "TEM-HUM"

    port on the UIM02C and the other end to the port on the temperature and humidity sensor, as

    shown in Figure 6-6.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 6 Installing Components

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    25

    Figure 6-6 Connecting the temperature and humidity sensor

    6.4 Installing a Water Sensor(Optional)

    6.4.1 Securing the Water Sensor

    Secure the water sensor to the cabinet bottom using cable ties, as shown in Figure 6-7.

    Figure 6-7 Installing a Water Sensor

    6.4.2 Connecting the Water Sensor

    Connect one end of the water sensor signal cable to the "WATER" port on the UIM02C, as

    shown in Figure 6-8

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 6 Installing Components

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    26

    Figure 6-8 Connecting the water sensor

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    27

    7 Installing Cables 7.1 Installing Signal Cables and Communication Cables

    7.1.1 UIM02C

    All ports in this manual are protected by a security mechanism.

    The user interface module (UIM02C) supports eight dry contact outputs, nine Boolean value

    inputs (including general DI1-6, smoke, water, door status), three analog signals inputs

    (ambient temperature, humidity, and battery temperature).

    Appearance

    Figure 7-1 UIM02C panel

    Port Description

    Table 7-1 UIM02C port description

    Port Type Silkscreen Description Default Mode

    Sensor

    ports

    TEM_HUM Temperature and humidity

    sensor

    -

    WATER Water sensor -

    TEMP1 Connected to environment

    temperature sensor and used

    for fan speed adjustment

    -

    NOTE

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    28

    Port Type Silkscreen Description Default Mode

    TEMP2 Reserved -

    GATE Door status sensor -

    SMOKE Smoke sensor -

    BTEMP Battery temperature sensor -

    Boolean

    value input

    ports

    DIN1 Boolean value input 1 Close: alarm

    Open: normal

    DIN2 Boolean value input 2 Close: alarm

    Open: normal

    DIN3 Boolean value input 3 Close: alarm

    Open: normal

    DIN4 Boolean value input 4 Close: alarm

    Open: normal

    DIN5 Boolean value input 5 Open: alarm

    Close: normal

    DIN6 Boolean value input 6 Close: alarm

    Open: normal

    Dry

    contact

    output

    ports

    Default

    mode

    (Close:

    alarm;

    Open:

    normal)

    can be

    modified

    as

    required.

    ALM1 AC power failure alarm Close: alarm

    Open: normal

    ALM2 DC undervoltage alarm or DC

    overvoltage alarm

    Close: alarm

    Open: normal

    ALM3 Rectifier faults, Protect and No

    Response alarm Close: alarm

    Open: normal

    ALM4 SPD failure alarm Close: alarm

    Open: normal

    ALM5 Fuse burn-out alarm Close: alarm

    Open: normal

    ALM6 Battery or environment

    temperature alarms

    Close: alarm

    Open: normal

    ALM7 Door alarms Close: alarm

    Open: normal

    ALM8 Heater faults alarms and Fan

    faults alarms

    Close: alarm

    Open: normal

    Communic

    ation Port

    COM RS485

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    29

    7.1.2 Installing Dry Contacts and Boolean Values Signal Cables

    Install dry contacts and Boolean values signal cables, as shown in Figure 7-2.

    Figure 7-2 Installing dry contacts and Boolean values signal cables

    (1) White Contact plate (2) Dry contact

    7.1.3 Installing Sensor Cables

    Connect the sensor cable to the corresponding ports on UIM02C. The pin definitions of the

    sensor ports refer to Figure 7-3 and Table 7-2.

    Figure 7-3 Pins of sensor ports

    Table 7-2 Pin Definition

    Silk Screen Pin Pin definition

    WATER 1 12 V

    2 WATER

    3 GND

    4 -

    TEMHUM 1 12 V

    2 ENV_TEMP

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    30

    3 12 V

    4 ENV_HUM

    TEMP1 1 TEMP1

    2 GND

    TEMP2 1 TEMP2

    2 GND

    GATE 1 DIN7+

    2 JTD7

    SMOKE 1 12 V

    2 Smoke

    BTEMP 1 Btemp1

    2 12 V

    7.1.4 Installing Communications Cables

    When in-band monitoring is required, connect the RS485/RS232 port on the SMU to the

    communications equipment over a cable with an RJ45 connector, when out-of-band

    monitoring is required, connect the FE port on the SMU to the communications equipment

    over a cable with an RJ45 connector, as shown in Figure 7-4.

    Figure 7-4 Port on the SMU

    7.2 Installing Power Cables

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    31

    Before installing power cables, ensure that all circuit breakers to the OFF position.

    Do not bind the ground cable, AC power cables, DC power cales, signal cables, and

    communications cable together.

    Open the panel of power distribution unit, as shown in Figure 7-5.

    Figure 7-5 Open the panel of power distribution unit

    7.2.1 Installing DC Output Cables

    Install DC output cables, as shown in Figure 7-6

    CAUTION

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    32

    Figure 7-6 Installing DC output cables

    7.2.2 Installing Storage Batteries and Copper Bars

    Before installing storage batteries, ensure that the circuit breakers of the storage batteries

    to the OFF position.

    During the installation, avoid short circuits or reverse connections between the positive

    and negative poles of the storage batteries. All the tools used, such as a screwdriver, must

    be insulated to prevent the storage batteries from being burned and to ensure personal

    safety.

    Step 1 Installing the storage batteries, as shown in Figure 7-7.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    33

    Figure 7-7 Installing two layer storage batteries

    Install the copper bar, as shown in Figure 7-8.

    Figure 7-8 Installing the copper bar

    Step 2 Installing the power cables for storage batteries, as show in Figure 7-9.

    Connect negative power cables and then positive power cables for the batteries.

    CAUTION

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    34

    Figure 7-9 Installing the power cables for storage batteries

    ----End

    7.2.3 Installing AC Output Cables

    Install AC output cables, as shown in Figure 7-10.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    35

    Figure 7-10 Installing AC output cables

    7.2.4 Installing AC Input Cables

    Install three-phase AC input cables refer to Figure 7-11.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    36

    Figure 7-11 Installing three-phase AC input cables

    Install single-phase AC input cables, remove the copper bar from the cable bridge on the side

    panel and connect the copper bar to the AC input circuit breaker to short-circuit the breaker,

    as shown in Figure 7-12.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 7 Installing Cables

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    37

    Figure 7-12 Installing single-phase AC input cables

    Recover the panel of power distribution unit, as shown in Figure 7-13.

    Figure 7-13 Recover the panel of power distribution unit.

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    38

    8 System Commissioning 8.1 Installation Verification

    After installation, verify that:

    Step 1 The cabinet is installed properly and the cables are connected properly. (Cables fastened by screws are not easily removable.)

    Step 2 Cables are arranged neatly and bound properly by using cable ties.

    Step 3 The storage battery is connected properly.

    Step 4 Check for short circuits between the live wires, between the live wire and the ground cable, between the live wire and the neutral wire, between the RTN+ and the 48 V busbar. Rectify short circuits before powering on the power system.

    ----End

    8.2 Powering On and Commissioning

    8.2.1 Setting Parameters

    Figure 8-1 SMU panel

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    39

    (1) Running status indicator (2) Minor alarm indicator (3) Major alarm indicator

    (4) Liquid crystal display

    (LCD)

    (5) FE (6) Locking latch

    (7) Four buttons (8) USB (Reserved) (9) RS485/RS232

    (10) Hold hands

    If the Run indicator (green) on the SMU panel is blinking and the LCD is on, the SMU is powered on

    successfully.

    Button Description

    Button description of SMU panel as shown in Table 8-1

    Table 8-1 Button description of SMU panel

    Button Name Description

    or upordown Allows you to view menu items and set the value of a menu item by pressing or .

    Cancel Returns to the previous menu without saving the

    settings of the current menu item.

    Enter Enters the main menu from the standby screen,

    enters a submenu from the main menu, or saves the

    settings of a submenu item.

    Remark:

    After a menu is displayed, the standby screen is displayed and the LCD screen becomes dark if you do not press any button within 5 minutes.

    You need to log in again if you do not press any button with 8 minutes.

    The preset username is admin and the preset password is 001.

    Setting Parameters

    Step 1 Measure the voltage across the input ports of AC input circuit breakers. The voltage must range from 200 V to 240 V. The rated voltage is 220 V. If not, ask professionals to rectify the

    fault.

    Step 2 Switch the AC input circuit breaker to the ON position, measure the voltage between L wiring and N wiring terminal. The voltage must range from 200 V to 240 V. The rated voltage is 220

    V.

    Step 3 Set the NetEco Main IP, NetEco Bak IP, NetEco Port, LUI Language and Set Time Zone according to actual conditions.

    NOTE

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    40

    Step 4 Set the Qty of Battery, Rated Capacity, Set Date and Set Time according to actual conditions. (Always set Qty of Battery to 1 and set Rated Capacity to the total capacity of all

    battery strings.)

    Step 5 Set the IP Address, Subnet Mask and Default Gateway according to actual conditions.

    Table 8-2 Parameter settings

    Main Menu

    Second-Level Menu

    Third-Level Menu

    Fourth-Level Menu

    Default Value

    Settings Comm Para NetEco Main IP - -

    NetEco Bak IP - -

    NetEco Port - 31220

    Host Comm Addr 0

    Comm Baudrate 9600

    System Para LUI Language - ENGLISH

    Set Time Zone - GMT +08:00

    Quick

    Settings

    Qty of Battery - - 1

    Rated Capacity - - 150Ah

    Set Date - - -

    Set Time - - -

    IP Address - - 192.168.0.10

    Subnet Mask - - 255.255.255.0

    Default

    Gateway

    - - 192.168.0.1

    Step 6 Set battery fuse break alarm "Enable/Disable" status.

    ----End

    Table 8-3 Battery fuse break alarm "Enable/Disable" status

    Main Menu

    Second-Level Menu

    Third-Level Menu

    Fourth-Level Menu Set Value

    Settings Alarm Setting Site Summary Battery Fuse1 Break Enable battery

    fuse blown alarms

    for the branches

    with batteries, and

    disable battery

    fuse blown alarms

    for the branches

    Battery Fuse2 Break

    Battery Fuse3 Break

    Battery Fuse4 Break

    Battery Fuse5 Break

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    41

    Main Menu

    Second-Level Menu

    Third-Level Menu

    Fourth-Level Menu Set Value

    Battery Fuse6 Break without batteries.

    Battery Fuse7 Break

    Battery Fuse8 Break

    Battery Fuse9 Break

    Battery Fuse10 Break

    Battery Fuse11 Break

    Battery Fuse12 Break

    You can set parameters to modify the default mode of the Boolean value input ports and the dry contact

    output ports, as shown in Table 8-4.

    Table 8-4 Modify the default mode of the Boolean value input ports and the dry contact output ports

    Main Menu Second-Level Menu Third-Level Menu Default Value Settings Site Summary DI1Alarm Close

    DI2 Alarm Close

    DI3 Alarm Close

    DI4 Alarm Close

    DI5 Alarm Open

    DI6 Alarm Close

    DO1 Alarm Act Close

    DO2 Alarm Act Close

    DO3 Alarm Act Close

    DO4 Alarm Act Close

    DO5 Alarm Act Close

    DO6 Alarm Act Close

    DO7 Alarm Act Close

    DO8 Alarm Act Close

    You can set parameters to modify the related relay of the alarm. For example, set Battery1 Lost to DO8,

    as shown in Table 8-5.

    NOTE

    NOTE

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    42

    Table 8-5 Set Battery1 Lost to DO8

    Main Menu

    Second-Level Menu

    Third-Level Menu

    Fourth-Level Menu

    Default Value

    Set Value

    Settings Alarm Setting Batt Summ Battery1 Lost None DO8

    8.3 Powering On

    To avoid damaging storage batteries, switch the battery circuit breaker to the ON positions

    only after correctly setting the storage battery parameters on the SMU.

    Switch the AC input circuit breakers to the OFF positions.

    Step 1 Reinstall the removed copper bar or cable of the storage battery.

    Step 2 Switch the storage battery circuit breakers in the PDU to the ON positions.

    Step 3 Switch the AC input circuit breakers to the ON positions. Check whether the voltage between the RTN+ busbar and DC output terminal are the same as the storage battery voltage and the

    voltage displayed on the monitoring unit. If not, ask professionals to rectify the fault.

    Step 4 Switch the LLVD and BLVD branches to the ON positions, measure whether the voltage between RTN+ and the DC output terminal. The voltage must range from 42 V to 58 V

    (without load). The rated voltage is 53.5 V. Check whether the loads work normally. If the

    loads work abnormally, rectify the fault according to the relevant user guides.

    Step 5 Switch the circuit breakers for the Maintenance socket, AC input, battery route, BLVD switch, and LLVD switch as required.

    Step 6 Check whether the element management system (EMS) can receive the information from the power system. If not, check whether the IP address is set correctly.

    Step 7 Observe the operation of the power system for 15 minutes. If no alarms (except for door alarm) are generated, and current/voltage parameters of the storage battery and loads are set properly,

    then re-install the cover of the distribution unit, lock the door to the cabinet, give the key of

    the cabinet door to the customer, and clean the site before leaving.

    To make the system run properly, flip the switch to the Normal position.

    To power on the battery forcibly, flip the switch to the BAT On position.

    CAUTION

    CAUTION

  • TP48200A-D15A1 & H15A3 & H15A5

    Quick Installation Guide 8 System Commissioning

    Issue 06 (2013-07-23) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    43

    ----End

    About This Document1 Safety Precautions1.1 Health and Safety1.1.1 Overview1.1.2 Electrical Safety1.1.3 Inflammable Environment1.1.4 Battery1.1.5 Working at Heights1.1.6 Using Ladders1.1.7 Mechanical Safety1.1.8 Bundling Signal Cables

    1.2 Equipment Safety1.2.1 Electricity Safety1.2.2 Electrostatic Discharge1.2.3 Laying Cables

    2 Installation Preparations2.1 Tools2.2 Installation Clearance Requirements2.3 Prepare Cables

    3 ConfigurationSpecificationsInterior of the Cabinet

    4 Installing the CabinetStep 1 Remove the cover of the packaging box and locate the marking-off template on the cover interior, as shown in Figure 4-1.Step 2 Fix the installation hole, as shown in Figure 4-2.Step 3 Drill holes and install expansion sleeves, as shown in Figure 4-3.Step 4 Remove the cabinet from the pallet, as shown in Figure 4-4.Step 5 Secure the cabinet on the concrete pad, as shown in Figure 4-5.

    5 Installing a PGND Cable6 Installing Components6.1 Installing Rectifiers6.2 Installing a Smoke Sensor(Optional)6.2.1 Securing the Smoke Sensor6.2.2 Connecting the Smoke Sensor

    6.3 Installing a Temperature and Humidity Sensor(Optional)6.3.1 Securing the Temperature and Humidity SensorStep 1 Secure the temperature and humidity sensor base to the cabinet top using two M4 mm screws.Step 2 Connect and secure signal cables of the temperature and humidity sensor to the cabinet base, as shown in the following figureStep 3 Install the top cover of the temperature and humidity sensor to the cabinet base.Step 4 The final installation view is as follows.

    6.3.2 Connecting the Temperature and Humidity Sensor

    6.4 Installing a Water Sensor(Optional)6.4.1 Securing the Water Sensor6.4.2 Connecting the Water Sensor

    7 Installing Cables7.1 Installing Signal Cables and Communication Cables7.1.1 UIM02CAppearancePort Description

    7.1.2 Installing Dry Contacts and Boolean Values Signal Cables7.1.3 Installing Sensor Cables7.1.4 Installing Communications CablesWhen in-band monitoring is required, connect the RS485/RS232 port on the SMU to the communications equipment over a cable with an RJ45 connector, when out-of-band monitoring is required, connect the FE port on the SMU to the communications equipment o...Figure 7-4 Port on the SMU

    7.2 Installing Power Cables7.2.1 Installing DC Output Cables7.2.2 Installing Storage Batteries and Copper BarsStep 1 Installing the storage batteries, as shown in Figure 7-7.Install the copper bar, as shown in Figure 7-8.Step 2 Installing the power cables for storage batteries, as show in Figure 7-9.

    7.2.3 Installing AC Output Cables7.2.4 Installing AC Input Cables

    8 System Commissioning8.1 Installation VerificationStep 1 The cabinet is installed properly and the cables are connected properly. (Cables fastened by screws are not easily removable.)Step 2 Cables are arranged neatly and bound properly by using cable ties.Step 3 The storage battery is connected properly.Step 4 Check for short circuits between the live wires, between the live wire and the ground cable, between the live wire and the neutral wire, between the RTN+ and the 48 V busbar. Rectify short circuits before powering on the power system.

    8.2 Powering On and Commissioning8.2.1 Setting ParametersButton DescriptionSetting ParametersStep 1 Measure the voltage across the input ports of AC input circuit breakers. The voltage must range from 200 V to 240 V. The rated voltage is 220 V. If not, ask professionals to rectify the fault.Step 2 Switch the AC input circuit breaker to the ON position, measure the voltage between L wiring and N wiring terminal. The voltage must range from 200 V to 240 V. The rated voltage is 220 V.Step 3 Set the NetEco Main IP, NetEco Bak IP, NetEco Port, LUI Language and Set Time Zone according to actual conditions.Step 4 Set the Qty of Battery, Rated Capacity, Set Date and Set Time according to actual conditions. (Always set Qty of Battery to 1 and set Rated Capacity to the total capacity of all battery strings.)Step 5 Set the IP Address, Subnet Mask and Default Gateway according to actual conditions.Step 6 Set battery fuse break alarm "Enable/Disable" status.

    8.3 Powering OnSwitch the AC input circuit breakers to the OFF positions.Step 1 Reinstall the removed copper bar or cable of the storage battery.Step 2 Switch the storage battery circuit breakers in the PDU to the ON positions.Step 3 Switch the AC input circuit breakers to the ON positions. Check whether the voltage between the RTN+ busbar and DC output terminal are the same as the storage battery voltage and the voltage displayed on the monitoring unit. If not, ask profess...Step 4 Switch the LLVD and BLVD branches to the ON positions, measure whether the voltage between RTN+ and the DC output terminal. The voltage must range from 42 V to 58 V (without load). The rated voltage is 53.5 V. Check whether the loads work norma...Step 5 Switch the circuit breakers for the Maintenance socket, AC input, battery route, BLVD switch, and LLVD switch as required.Step 6 Check whether the element management system (EMS) can receive the information from the power system. If not, check whether the IP address is set correctly.Step 7 Observe the operation of the power system for 15 minutes. If no alarms (except for door alarm) are generated, and current/voltage parameters of the storage battery and loads are set properly, then re-install the cover of the distribution unit, ...