249
Products, services and controls for integrated air-conditioning and refrigeration solutions in commercial and industrial markets Systems Guide PROD-PRC014-E4

Train Instrument's

Embed Size (px)

DESCRIPTION

all about train instruments

Citation preview

Page 1: Train Instrument's

Products, services and controls for integrated air-conditioning and refrigeration solutions in commercialand industrial markets

Systems Guide

PROD-PRC014-E4

Page 2: Train Instrument's

Ph

oto

gra

ph

ic c

red

its

: Get

ty Im

ages

- B

anan

aSto

ck

Cooling-only system

Heat pump (or reversible cooling/heating) system

Heat recovery system

Free cooling system

R134a refrigerant

R407C refrigerant

Cooling-only and gas burner

Cooling-only and electric heater

Tracer Summit™ compatibility

Conforms to the BACnet™ standard

Conforms to the applicableLonMark® profiles

Plant control applications

Water terminal and scroll chiller systems applications

Air handling unit and air distribution system applications

Rooftop and VAV applications

Interoperability and integration

Factory-mounted controller

Eurovent certification

PRODUCT CHARACTERISTICS

©American Standard Inc. 2006

Throughout this catalogue, “Option” refers to a factory-mounted device. “Accessory” refers to a device that is to be installed on the job site

COMMUNICATION

Page 3: Train Instrument's

1

Our business is a business of providing

energy-efficient and environmentally

responsible systems that sustain high

performance for life...

By doing so, we make it possible for buildings and

industrial processes to operate at world-class levels...

Trane systems do more than make chilled water or

warm and cool air.

Our systems ensure process reliability, energy effi-

ciency, as well as superior indoor air quality.

And these results are realized by carefully looking at

how everything works together - before we put any-

thing together…

So whether the challenge is creating sophisticated

Integrated Comfort™ Systems for luxury hotels…

enterprise services for high-performance working

environments… control systems for critical, regulated

processes…

Trane has the committed team with

the technical know-how and expertise

to help your building or your process

perform at its utmost ability...

TRANE BRINGS VALUE TO YOUR BUSINESS

Page 4: Train Instrument's

Trane is a leading global provider of energy efficient HVAC systems service

and parts support, building controls and solutions designed to meet

the specific needs of our commercial, institutional, industrial and process

application customers.

Trane generates $6.0 billion in global sales, employs over 26,000 people,

has sales and service operations around the world and conducts its

manufacturing activities through 27 plants in 10 countries.

American Standard is a global diversified manufacturer of high quality,

brand-named products in three major business segments.

Air-conditioning systems and services, sold under the Trane® and American

Standard® brands for commercial, institutional and residential buildings;

Bath and kitchen fixture and fittings, sold under such brands as American

Standard®, Ideal Standard®, Ceramica Dolomite®, Armitage Shanks®, Porcher®,

Børma®, Sottini®, JADO® and Absolute;

Vehicle control systems, including electronic braking and air suspension sys-

tems, sold under the WABCO® name to the world's leading manufacturers of

heavy-duty trucks, buses, SUVs and luxury cars.

American Standard is one of the largest providers of products in each of its

three major business segment; the company employs approximately 60,000

people, operates in 50 countries and conducts its manufacturing activities

through 103 plants in 28 countries.

2PROD-PRC014-E4

Page 5: Train Instrument's

Driven by our commitment to provide high quality products and services, American Standard and its businesses pay close attention to quality every step of the way… from development to sales.Trane was the first company in its industrial sector to obtain ISO 9001 certification in December 1987. The manufacturing sites of Charmes, Golbey and Colchester have been certified ISO 9001: 2000 process-basedQuality Management System.Product quality is also achieved through processes led by DFT (Demand Flow Technology) and Six Sigmaefforts, making Trane a responsive, flexible and demand-driven organization.

Trane’s environmental commitment is to provide state-of-the-art HVAC systems that are good for our customers, for our businesses, and that are environmentally responsible.Trane’s responsibility is to keep a comprehensive view of what affects our planet’s health, remain accountablefor our actions, and preserve engineering excellence so as to further improve the environmental benefits of ourproducts and services.The global environmental policy goes even deeper, as Trane pro-actively participates by anticipating regulatorychanges and by integrating environmental impact reduction in all projects.While Trane’s environmental commitments and policies are global, the environmental priorities of customersmay vary locally. Trane invites you to contact your local sales office for the most updated information for yourregion.Trane manufacturing sites in Charmes and Golbey were certified ISO 14001 in July 2004.

TRANE AND THE ENVIRONMENT

TRANE QUALITY

TRANE COMPLIANCE

Trane participates in the Eurovent certification programmes where product performance and construction dataare validated by independent laboratories. The added value to you is a guarantee to performance complianceand the peace of mind knowing that Trane puts forth continuous efforts ensure we are meeting the needs of ourcustomers.

As a business of American Standard, Trane has a company-wide mission to create a safe and healthy work envi-ronment. This is accomplished by creating individual ownership and responsibility and by building processes that help prevent injury and illness.This mission also encompasses the safety of our customers, anticipating and helping to solve our customers'safety problems to ensure a safer future for all.

3PROD-PRC014-E4

TRANE AND SAFETY

A TRUE GLOBAL COMPANY WITH LOCAL PRESENCE

Trane has offices and service operations around the world. About 130 locations in Trane EMAIR (Europe, MiddleEast, Africa and India Region) are staffed by a team of the industry's most experienced sales engineering pro-fessionals and are organized to provide uniform local support capabilities such as engineering expertise, appli-cation assistance, service, parts and financial solutions.In addition, Trane offices provide the benefits that come with a working knowledge of local business practices,building codes, languages and currencies.

Page 6: Train Instrument's

TRANE BRINGS VALUETO YOUR BUSINESS.

4PROD-PRC014-E4

Trane has decades of experience working with the lodging industry allowing hotel owners to achieve a highlevel of consistency from location to location, from economy motels to upscale hotels and resorts, with increasing expectations at each level.Guest comfort and energy savings have significant relevance this industry.With intelligent building design and quality equipment, it is possible to achieve both energy efficiency andunimpeachable guest comfort in all its dimensions, including acoustics, temperature, humidity, absence of odors, and precise control. Guest comfort deals with indoor air quality (IAQ) and this goes beyond good housekeeping. It requires intelligent system design, use of the right equipment, good HVAC maintenance practices, and training support for facility teams.

Trane can help to achieve and maintain the highest quality air by installing humidity control systems, providing ample ventilationwith filtered and conditioned outdoor air, and working with your building staff to meet or exceed IAQ standards.Energy is the second-highest operating cost component in the lodging industry. With the use of Trane heat recovery solutions you cansave energy on both airside and waterside capturing energy that would otherwise be lost.

LODGING

- reliability- energy efficiency- environmental responsibility- cost efficiency

- technological expertise- state-of-the-art equipment- meeting or exceeding environmental standards- meeting the individual business needs of a client, no matterhow simple or complex

Equipment systems are the tip of the iceberg.

Whether we work with you directly or as a contributing partner, we can serve you in a variety of ways, like evaluating the equipmentyou have and upgrading it if necessary, or integrating your system with advanced controls.We can train your facilities department in the intricacies of heating, ventilating and air conditioning (HVAC) equipment systems,controls, and industry standards and issues.We can also service and maintain your systems, and provide emergency assistance, parts and supplies to keep your system operatingat peak efficiency.

The bottom line.

We have the best people, the best equipment and the best service in the industry. Which all comes down to this: Trane has the kno-wledge and resources to turn building systems into business advantages for you.

A Trane system can have a measurable impact on your business, no matter what your business is. It’s been proven time after timethat Trane can positively influence not only your working environment but your bottom line and even your production and designtimetables.

What we do.

Trane manufactures, manages and services HVAC equipment systems or controls for buildings and industrial processes all over theworld. We’re the industry leader in R&D, as well as manufacturing.Our projects are large and small but all have these in common:

Page 7: Train Instrument's

5PROD-PRC014-E4

The best facilities promote customer comfort, increase brand competitiveness and drive revenue, all at the lowest life-cycle cost.From simple stores to modern shopping complexes, Trane has experience in the retail business. Trane offers aportfolio of building support tools, services, and expertise that optimize the facility throughout its life cycle. We know that the temperature, humidity and ventilation management needs of stores are different than forother buildings. Leveraging our experience, we can help identifying specific areas for energy and comfortimprovement. Trane can provide the knowledge to keep buildings operating at their design levels.

With our equipment and controls technicians, we can help to reduce the risk of sales lost due to comfort system failure. Trane equipment has a worldwide reputation for the highest quality and reliability.Trane offers proven systems to help your project succeed and thousands of trained service technicians with superior knowledge to serve you, with all systems you chose.Trane can supply the systems you need, applying our range of industry proven, high-efficiency comfort equipment and digital building controls for all sizes of installations.

RETAIL

Trane provides solutions for facilities devoted to research, development, manufacturing, and product stabilityacross the life sciences industry. Our integrated systems provide tightly controlled environments for pharmaceuticals, genome projects, medical devices, and a full range of biotechnology products.Applying superior engineering expertise, Trane provides integrated HVAC and building management systemsthat allow you to take command of the environmental conditions in your facilities.Trane can be your knowledge partner, keeping abreast of changing regulations and bringing you the technology to meet these challenges.Our strong relationships with the specialized firms most capable of successfully designing and constructing lifesciences facilities also help ensure the seamless success of this entire critical process. Trane HVAC and buildingmanagement systems make a major contribution to your speed to market — the most hotly pursued success

factor in the life sciences industry.We provide validation documentation templates that streamline the entire process for your in-house or external engineering teams.Together we perform installation, operational, and performance qualification, ensuring all systems, processes, functions, and documentation can be validated for your specific environment.Trane offers the products and expertise to make your HVAC systems a point of absolute reliability in this equation.

LIFE SCIENCES

The commercial office market is a highly competitive one. Owners have the onerous responsibility of not only attracting prestigious and desirable tenants but also retaining them with excellentservices.Trane offers superior air conditioning comfort as a means of attracting new tenants and as a source of differentiating the building from the rest of the crowd.Research has proven that comfort significantly impacts productivity. More than half of all tenants in commercial office properties find their offices “too hot” or “too cold”. Most tenants who complain about dis-

comfort end up moving out of their premises when their lease ends and this, of course, affects profitability.In addition to supplying superior comfort, Trane’s energy efficient equipment will help in electricity savings while our automation soft-ware and direct digital controlled terminal units can help generate revenue from your tenants’ use of air conditioning facilities afteroffice hours.Trane makes buildings work better and creates an optimum working environment while controlling operating costs for office buildings.

COMMERCIAL OFFICES

Page 8: Train Instrument's

6PROD-PRC014-E4

84

86

88

90

92

94

96

98

Air handling units700-108 000 m3/h

Air handling units1 000-132 000 m3/h Air handling units1 000-140 000 m3/hAir handling units1 000-18 000 m3/h

Air handling units1 200-86 000 m3/h

Air handling units1 800-120 000 m3/h

Variable air volume systems

Linear and cassette diffusers

CLCE

CCEA

CCTA

CCH

CCVA

CCSA

VariTrane™

VDLE-VRLE-Cassette

TABLE OF CONTENTS

AIR SYSTEMS

102

110

112

120

126

136

Axial fans, scroll compressor19-61 kW

Remote hydraulic module

Axial fans, scroll compressor, heat pump50-270 kW

Axial fans, scroll compressor, heat pump285-465 kW

Axial fans, helical rotary compressor250-650 kW

Axial fans, helical rotary compressor400-1500 kW

CGA/VGA/CXA/CXA

HDM

AquaStream2™ CGAN/CXAN

AquaStream2™ CGAN/CXAN

RTAD

RTAC

OUTDOOR CHILLERS

50

58

64

70

76

Fan coil units1-12 kW

Fan coil units for office applications2-7 kW

Fan coil units for lodging applications1-5 kW

Ductable units4-30 kW

Cassettes1-12 kW

UniTraneTM FCC-FCK-FVC

Slim Line HFO-HFR

Slim Line HFH

FWD

CWS

CHILLED WATER TERMINALS

10

18

26

32

Domains

Functions

Applications

Products and accessories

BUILDING MANAGEMENT SYSTEMS

144

150

156

164

166

170

172

Scroll compressor, packaged and condenserless chillers51-153 kW

Scroll compressor, packaged and condenserless chillers180-350 kW

Helical rotary compressor, packaged and condenserless chillers200-700 kW

Remote condenser215-600 kW

Helical rotary compressor500-1500 kW

Centrifugal compressor1400-3800 kW

Single-stage absorption400-1630 kW

CGWH/CCUH

AquaStream2™ CGWN/CCUN

RTWB/RTUB

RTCA

RTHD

CVGF

ABSC

INDOOR CHILLERS

Page 9: Train Instrument's

7PROD-PRC014-E4

238

239

240

241

242

243

244

245

EvoluTrane

Trane Select Contracts

Chemical analysis

Eddy current tube analysis

Vibration analysis

Remanufactured compressors

Equipment enhancement

Parts and supplies

SERVICE SOLUTIONS

218

220

222

Split system3-15 kW

Split system19-31 kW

Condensing unit55-218 kW

TTK/TWK + MCD/MWD

TTA/TWA + MWD

RAUL

SPLIT SYSTEMS AND CONDENSING UNITS

228

230

Technology and comfort applications5-20 kW

High tech applications22-63 kW

Jupiter

Mercury

CLOSE CONTROL UNITS

234Variable frequency drives0.37-400 kW

VarioTrane TR1

VARIABLE FREQUENCY DRIVES

188

196

204

212

213

Reversible17-62 kW

Cooling-only18-143 kWGas-fired

17-143 kWLight commercial building supervisor

Variable air volume systems

Voyager™ WSD/WSH-WKD/WKH

Voyager™ TSD/TSH-TKD/TKH

Voyager™ YSD/YSH-YKD/YKH

Tracker™

VariTrac™ II

ROOFTOPS

174

176

178

180

184

Single-stage absorption2000-4800 kW

Two-stage absorption1300-6000 kW

Direct-fired absorption350-3900 kW

Centrifugal fans, scroll compressor49-150 kW

Centrifugal fans, helical rotary compressor130-170 kW

Horizon™ ABSD

Horizon™ ABTF

ABDL

CGCL

RTRA

INDOOR CHILLERS

Page 10: Train Instrument's

8PROD-PRC014-E4

BUILDING MANAGEMENT SYSTEMS

Page 11: Train Instrument's

Trane Building Management Systems

Full BMS offer: Trane has developed a full range ofcommunicating controllers and components that canaddress all the needs of customers looking forcomfortable, and efficient environments related to HVACBuilding Management Systems. Trane also has taken carethat the teams serving this activity are structured so thatcustomer can get the right support at the right time.

Open Systems: Trane has adopted the latest openprotocols standard and built them as native services intoits BMS offer. BACnetTM and LonTalk® are native withinTrane BMS panels. Thus several ways of integration andinteroperability are offered to users as to free them upfrom brands.

Factory-mounted Controls: Every piece ofequipment leaving the factory is equipped with acontroller which is mounted, wired up, configured andtested before the unit ships to the site. This ensures thatequipment is easy to commission and ready to run.

Domains: IndustryLarge buildingsMedium buildingsLight commercial buildings

Functions: Water plant systemsVariable air systemsWater terminal systemsPackaged unit systems

Applications: Water terminal unit controlVAV unitsAHU Technical lotsBuilding Management SystemsCommunication gateway

Products: ZN familyAHU controllerFreely programmable controllerI/O controllersNetwork controllerWeb serverVAV controllerBMS software

PROD-PRC014-E4

9

BU

ILD

ING

MA

NA

GE

ME

NT

SY

ST

EM

S

OperatorInterface

BuildingControls

Site installedUnit Controls

Field devices Control, measure,monitoring

HVACEquipmentwith Factory-MountedControlsRTHD HFO/HFR VariTracTM CGAN/CXAN CLCE Voyager TM

Lightingcontrol

Power panel control

Energy metering

Building information monitoring

Alarm control and

monitoring

3rd party equipment

control

Tracer Summit TM LCD Touch ScreenWeb Server

BCU Field Server

EX2

MP581

MP501/MP503

Inte

gra

tio

n

WWWInteroperability

Field level

Automation level

▲▲ Management

level

PICZSM

MP583ZN523

Page 12: Train Instrument's

10PROD-PRC014-E4

Utilities and HVAC process control

Domain: Industry

Trane already has a wide experience of industrial controlapplications, starting from simple chiller plantmanagement, up to highly technical systems, such asunderground water source heat pumps, or condenseroptimization for improving chillers efficiency.

Reliability: One of the highest priority of Traneengineers when designing an industrial application is toensure a system that is reliable. As an exampleinstallation operation continuity is being focused on atdesign and commissioning stages. Trane proposessystems that can revert to a safe stand alone runningmode should any issue such as communication troublesarise, offering cooling capacity until the issue has beenanalyzed and fixed.

Ease of use: On top of that reliability, Trane systemallows for ease of system operation. Whatever theproposed solution is, Trane always proposes simple touse user interfaces. These ones always offer pertinentinformation about system status and running conditions.Since every piece of equipment is hooked up to anetwork, the user can access at any time many systemand units information, allowing for easy diagnosis, andeasy understanding of system reactions.

Ease of commissioning: Pre-engineeredchiller plant management function are implemented onthe system so that commissioning time can be asreduced as possible.

Optimization: Trane also focuses on savings.Thisobjective is focused on since the beginning of the project.Piping arrangement, chiller technology, unit sizesarrangement are being studied so that customer can getthe best result of their installation, according to theirsystem load profile. Chiller Plant sequencing is apowerful pre-engineered function that only requiresparameters for being able to drive the installation withhigh level of optimization.

Dedicated BMS teams: From here, Trane isable to propose the BMS products adapted to the solutionthat the customer has chosen. At this point of time, BMS

project fulfillment teams take over the project. BMSproject fulfillment teams follow a complete process:building clear and fully detailed project specifications,proposing clear project development and fulfillmentschedule, and project management.

Page 13: Train Instrument's

BM

S:

Do

main

sIn

du

stry

11PROD-PRC014-E4

Consulting services: Trane also has developedthe capacity of offering full support to its customers,beginning with customer's technical service.Traneproposes its simulation and solution evaluation software.Using this tool, customers can easily evaluate the bestalternative for solving their problem, by being able toview the solutions from different angles, such aseconomical aspects, technical aspects, safety andreliability etc…

Single source responsibility: Customerscan have access to project info from a single sourcewithin the Trane organization. After the project has beenfulfilled, it is also easy for customers to get assistancefrom Trane in concluding a maintenance and servicecontract including HVAC and BMS equipment / softwares.This way, system fluctuations, fine tuning etc … can bedone by people working in sync with those teams thathave developed originally the application. This by essenceensures service continuity as well as efficiency inanswering any request of system improvement oradaptation.

1 = Critical Systems monitoring:Electrical Power: MP581

2 = System Water Flow Control:Variable frequency pump Control:VarioTrane VFD

3 = Chiller condenser operation:Cooling towers control: MP581

4 = Chiller Plant Control:3 RTHD with factory mounted CH530

Twin pump control for each chiller: BCU

5 = System monitoring and Control:Supervision: Tracer SummitTM

1

5

2

3

4

Page 14: Train Instrument's

12PROD-PRC014-E4

Building control

Domain: Small/medium size office

The know-how gained while sharing experiences with itscomfort process customer has led Trane to develop BMSsolutions dedicated to these applications.

Comfort is a key in these projects, but not the only one.Having a look at the entire project process, as well asoffering a system capable of handling the overall buildingcontrol functions has also been taken into account inorder to offer packaged solutions.

The packages Trane offers allow for several advantages:

Comfort: All Trane HVAC equipment are shipped withfactory-mounted/factory-programmed controls, offeringeasy-to-install equipment, and reduced commissioningtime. All building equipment is fully compatible with eachother thanks to use of LonTalk® protocol. All comfortcontrol functions, such as scheduling, heating/coolingchange over management, timed overrides, chiller plantmanagement, boiler plant management, indoor air qualitycontrol are built in the system. The system also ensuresacoustic performance, by having FCU using the lowestfan speed possible.

Energy savings: Trane's package includes severalfunctions dedicated to energy savings, such aschiller/boiler plant optimization, allowing for pumpingenergy savings, as well as equipment starts and stopsoptimization. It also includes automatic watertemperature compensation, occupied / stand by /unoccupied modes for FCU etc…

Ease of use: Trane's solution offers a VGA display,presenting data as graphics. The entire system can beaccessed by an intuitive navigation tree system. Dailyoperators can easily access information such as ambienttemperatures, setpoint settings, timed override on anyzone, not being forced to understand HOW comfort isbeing maintained. For more advanced users or technicalpersonnel, the system also offers capability to access todetails about equipment such as various runningconditions for chillers, boilers, and AHU, or optimizationparameters for plant controls. System however integratesadvanced event logging and trending, and very powerfulsystem access protection through password strategies.

Page 15: Train Instrument's

BM

S:

Do

main

s

Off

ices

13PROD-PRC014-E4

Ease of installation: Trane's delivered packagecan come as a predefined kit including all components,control panels and so on, so that very little amount ofcoordination is requested for on site installation, wiringand commissioning. It is also possible to get the parts asindividual pieces, would the contractor, or wouldtechnical constraints such as clearance etc … not allowfor using the full 'kit'.

Flexibility: Trane's system is capable not only ofhandling Trane equipment, but also extending its domainto integration of non-HVAC functions, such as externallighting systems, grass watering, intrusion system oreven alarms from ancillaries such as power systems,circuit breakers etc…

Ease of doing business with: Choosing thissolution means having only one company handling theoverall comfort process. Trane is the contact for anyadvice concerning either the HVAC equipment or theassociated BMS. System optimization will be done bypeople who perfectly understand the HVAC equipment,and BMS components.

Thus Trane's offer is a solution that allows for better

building performances and optimized project

management, answering all concerns.

1 = Chilled Water Plant: 2 CGAN with factorymounted CH532: BCU

2 = Fresh air control: AHU: MP581

3 = Lighting control: EXL

4 = Open space comfort: HFO with factory mountedZN controller

5 = Tenant interface: Setpoint and room conditionsinformation: Web Server

6 = System monitoring and control: Supervision: Tracer SummitTM

7 = Intrusion system: Access control systemmonitoring: BACnetTM

8 = Critical Systems monitoring: Electrical Power:MP581

9 = Hot water plant: Boiler Plant Control: BCU

12

3

45

6

7

98

Page 16: Train Instrument's

14PROD-PRC014-E4

Building management control

Domain: Large office building

In addition to HVAC application solutions for large scalebuilding projects, Trane has developed one of the most

open Building Management System solutions availableon the market. This range of solutions, completelydeveloped and manufactured by Trane, is the sum ofdecades of expertise, hundreds of HVAC system designs,thousands of operating and maintenance experts. It is theway a reliable and renowned manufacturer helps hiscustomer get the best out of his products.

Large building comfort application have been carefullystudied by Trane and fully optimized functions have beenimplemented within Trane's BMS. These functions offerseveral unique advantages to Trane's contacts along theproject cycle.

Flexibility: Trane's BMS is a highly flexible systemthat offers ease of (re) configuration. This allows thesystem to be adapted at every step of a project. It hasalso been considered that large buildings require changesquite regularly in the levels layout (open space) andTrane's system is fully organized as to allow for space

reconfiguration, thanks to advanced master/slavecapabilities of terminal units controller, perfectly fitted inthe global BMS.

Flexibility is also at first priority when consideringBuilding Operations. Trane's BMS integrates graphicaluser interfaces, either based on HTML pages handled in adedicated environment, called Tracer Summit™, or from asimple and standard PC Web browser for dailyoperations.

Another important point is about the ability of Trane'ssolution to offer equipment integration and systeminteroperability. Since 1995, Trane has adopted the mostadvanced standard protocols, such as BACnetTM, LonTalk®or MODBUS, and has implemented them as nativefeatures of its BMS.

Reliability: Trane's BMS takes advantage of Trane'sexperience in HVAC equipment, as well as in BMS, asTrane has been active in this domain for the last 25 years.Building its own electronic component was a choice thatTrane made as to perfectly master the complete productlife cycle, from development, engineering, manufacturing,up to maintenance, support and upgrade. This means thatevery piece of BMS component is well-known by Trane'sBMS personnel, and, would the project engineer require aspecific piece of information for assisting his customer,he can find it easily within Trane's organization.

Page 17: Train Instrument's

BM

S:

Do

main

s

Lar

ge

Off

ices

15PROD-PRC014-E4

Efficiency: Trane has developed pre-engineeredfunction within Tracer Summit™ that allow a high level ofsystem efficiency which can be seen from differentangles.

Efficiency of commissioning: Minimum programmingis required to set up these functions and the BASproject engineers can spend more time in fine-tuningthe system rather than developing the applicationsfrom scratch.Perfect equipment coordination:Trane's HVACequipment comes with its factory-mounted controller.All these controllers have been developed keeping inmind their possible association within a system andthus, their interactions have been envisaged andimplemented within Trane's BMS. This way, it is quiteeasy for Trane's BAS engineers to associate thecontrollers and get the best of the equipment, simplyby telling the system how these controllers are linkedtogether.Fine-tuning:Trane's BMS integrates a unique reportgeneration system that allows operations managersto get a report of the current system status, by thesimple click of a mouse. This operation can be doneon ANY equipment integrated in the system, and doesnot require any programming. Should the operationmanager want a specific report, a specific layout, aspecific trend, Trane's BMS integrates a very simplereport template editor that allows creation of any

report, just by dragging/dropping any piece ofinformation available in the BMS database.

Comfort: Trane's core business is about developingHVAC equipment. As to reach the unquestionable level ofequipment quality, reliability and efficiency, Trane'sengineers have had to consider the equipment in theirglobal environment. This means that on top of ensuringequipment safeties and running condition efficiency carehas been taken ensure performance around acoustics,energy savings, etc. Through the use of Trane's BMS,these aspects of equipment running conditions are evenimproved. As an example, a VAV box can be drivenaccording to pressures and running conditions of theAHU that is serving it. The equipment exchanges data inorder to align the respective working conditions to deliverthe optimum service to the end user.

1 = Weather information: MP503

2 = Chilled water plant: 2 RTAC with factorymounted CH530: BCU

3 = Fresh air control: AHU with factorymounted MP581

4 = Open Space comfort: HFO with factorymounted ZN523 controller

5 = Environmental comfort: Lighting control:EXL, Sunblinds control: EXB

6 = Tenant interface: Setpoint androom conditions information: Web

Server

7 = Workstation: Building SystemsManagement, operation and diagnosis:Tracer SummitTM

8 = Variable Air flow control AHU + VAVvalves: MP581 + VV550

9 = Hot water plant: Boiler Plant Control: BCU

10 = Electrical Power monitoring: MP581

11 = Interoperability: Access Control systemmonitoring: BACnetTM + LonTalk®

1

23

456

7

8

10 911

Page 18: Train Instrument's

16PROD-PRC014-E4

Building control

Domain: Light commercial

Trane has developed a Building Management Systemwhose capabilities perfectly match context of rooftop/airdistribution applications. Trane's BMS, for lightcommercial applications presents many advantages:

Delivered System: Trane's light commercial BMSonly requires a few settings to be implemented on anapplication. Thanks to the capability of any Trane HVACequipment to communicate over a network, the BMSmanages to identify these equipment linked together,builds the corresponding database and automaticallyoffers to the end user predefined functions such as time-of-day schedule, automatic setpoint reset, zonemanagement or alarming menu, with almost no laborrequired. If the customer wants to customize his interface,a convenient software interface is available to changezones that have been automatically created, changingalarms menus, and so on.

The system is compact and very convenient to install and

wire up.Trane's equipment uses an open standard

protocol, called LonTalk®, which is often present in thistype of building, and contractors perfectly master thiskind of bus topology installation.

Trane's delivered system offers an additional perspective,since every piece of the puzzle comes from the samemanufacturer. It is far easier to have coordination onequipment delivery, commissioning and fine tuning, sinceonly one contact is involved for this. On top of this, Tranepersonnel are well trained for the entire systemcomponents, ensuring efficiency in commissioning, andfast response should the customer require anyinformation.

Page 19: Train Instrument's

BM

S:

Do

main

s

Co

mm

erci

al

17PROD-PRC014-E4

Energy savings: Various pre-engineered tactics,such as setpoint reset, time-of-day scheduling, duty cycle,have been implemented in the system and can beassociated together to improve system energy efficiency,and almost not touch system comfort managementcapability.

Trane's system is easy to install, set up and use. Thismeans that system updates, system daily operations andsystem maintenance can be done by operation personnelvery easily, requiring almost no specific training.

Trane's system also has the capability to control ancillaryequipment, such as lights, parking lots, energy meters,and any equipment that must be controlled according toa time-of-day schedule, through simple interface such asrelay contacts.

Saying this, Trane's delivered BMS for commercialapplications is a powerful answer to customers who wanta very easy-to-use system, capable of simplifying their lifeall along the project life cycle.

1 = Space temperature and humidity control: Rooftopunits with factory mounted control: ReliaTelTM

2 = Lighting control: MP581

3 = Tenant interface: Setpoint and room conditionsinformation: Zone Sensor (THP-THS)

3

2

1

Page 20: Train Instrument's

18PROD-PRC014-E4

Water plant systems

Function

Chillers are one of the main focuses for Trane. Theirenvironment is perfectly known by Trane engineers. Thishas led up Trane developing advanced Chiller Plant

Control applications within its Building ManagementSystem. Trane also has taken this opportunity to make itssystem fully capable of handling boiler plants.

Various aspects of boiler/chiller plant operations havebeen studied and very smart functions have beenimplemented within Trane's Water System Management.Trane's systems are able to handle many hydrauliclayouts.

Most efficient results can be achieved with well-preparedpiping arrangement. However, Trane always studiespiping arrangement that is either existing or consideredfor the installation. Trane specialists in hydraulics andchillers application always review the system drawingsbefore any proposal is made. This helps Trane to clearlypoint out what the installation is really capable ofdelivering, and to position these capabilities regardingwhat is expected.

Once this is clear, Water System Management addsadvanced capabilities to the customer's installation:

Flexibility: Water System Management offersflexible interfaces to operate chiller plant. By a few mouseclicks, chillers can be turned into maintenance, sequencenumbers can be adjusted and rotation can be initiated.The same interface also helps operation personnelexactly know what the installation has been doing, iscurrently doing and will be doing in the near future. Atany time, the operator can anticipate system reactions.System graphics for plant operation can be monitoredfrom an Intranet, using a web browser.

Energy savings: Water System Managementalways ensures that chillers are used in their mostefficient operation conditions. Unit technology andenvironment conditions are monitored by Water SystemManagement, which adjusts parameters according tochanges in the system running conditions. Parameterssuch as unit size, compressor technology, condensertemperatures are controlled. The number of chillers isautomatically adapted according to the system load.Should there be a change, the system anticipates andadds/removes chillers accordingly. The system alsocontrols all ancillaries such as pumps, cooling towers, drycoolers etc.

Page 21: Train Instrument's

BM

S:

Fu

nctio

ns

Ch

ille

r

19PROD-PRC014-E4

Reliability: It is obvious that chilled water productionis crucial for customer's process and the Trane systemmaintains a high level of reliability so that chilled watercan be maintained at all times. Every chiller is equipped with its own electroniccontroller, and each controller embeds an adaptivecontrol algorithm. Each controller is fully compatible withthe Building Management System, It communicates withit over a standard protocol, sharing all its runningconditions. This allows the management system to notonly turn on/off chillers according to temperatures ortemperatures differences, but also consider currentrunning conditions of chillers, such as maximum capacityreached, limit conditions, and so on, in order to knowsystem capacity at all times.

Interoperability/integration: Trane systemsare fully capable of communicating with any equipmentand/or management system through the use of openstandard protocols, such as BACnetTM, or LonTalk®.Modbus is also supported allowing for a wide range ofintegration and data sharing with ancillaries, such aspumps, sensors or PLC's. Trane systems are capable ofintegrating either standard LonTalk® profiles (SCC, DAC)or Generic Lon Devices (GLD).

Protection: Trane systems offer a high security levelthat protects against any unexpected system operation.Operators can be authorized to monitor data only, writesetpoint and other parameters, create graphics or justview them, modify system layout, and so on. Every actionon the system is recorded in an event log. Events canthen be monitored, filtered by date/operator/device, etc.Events can be seen either at the PC level, or from a localtouch screen available in the plant room.

Assistance: Trane systems allow for system remotemonitoring. After commissioning, Trane personnel canget connected to the system and monitor/fine tuneparameters to adapt the overall system performance.Alarms can also be forwarded to that remote workstation.If an IP address is available, a web server can be installedand allow for remote access to the system through asimple web browser. Trends, event log, system status canbe accessed this way from any location where an accessto the Internet/intranet is possible.

1 = Network Management: BCU

2 = Ancillaries control (Pumps): MP581

3 = Power control panel monitoring: MP581 + EX2

4 = Variable Flow control: VarioTrane VFD

5 = Workstation: Tracer SummitTM

6 = Chiller: RTHD with factory mounted CH530

2

1

3

4

5

6

Page 22: Train Instrument's

20PROD-PRC014-E4

Variable air systems

Function

In buildings where environmental comfort is a key,variable air systems are the best alternative. Trane BMSintegrates the capability of driving such systems througha pre-defined engineered function called Variable AirSystems. By the use of VAS, building owners get a state-of-the-art system capable of offering many differentadvantages.

System approach: Every piece of equipment of aTrane air system is equipped with an optimised controller,which locally ensures that the equipment is used the bestway. Trane air system management uses controllercommunication capability to handle all the equipmentfrom a global standpoint. Every running condition hasbeen modelled in a global function. Ancillaries, such aslights, power supply, shadows can be associated with theair system and all these components can be coordinatedtogether.

Comfort: Thanks to a common communicationstandard protocol, all equipment serving the system isexchanging data with an application server which takesdecisions. If most VAV boxes are fed with too much air, itwill reset static pressure setpoint as to avoid unnecessarynoise. If boxes are fully opened and call for more air, thesetpoint is adjusted upward. Since VAV boxes are equipped with communicatingcontrollers, master/slaving can easily be used forhandling large zones avoiding fights between cooling andheating areas, as well as allowing for optimumtemperature control. Indoor Air Quality (IAQ) is alsoperfectly managed by such a system. Trane equipmentcan monitor indoor air conditions and drive the AHUfresh air dampers dynamically, by measuring the fresh airvolume sent into the building.

Page 23: Train Instrument's

BM

S:

Fu

nctio

ns

Air

Sys

tem

s

21PROD-PRC014-E4

Savings: Dynamically adjusting airflow in the ductsystem leads to energy savings by the reduction of fanconsumption. Occupancy schedules also participate inenergy savings.Start/stop optimisation, done through the monitoring ofoutdoor air conditions, building inertia and occupancyprofiles are also a very powerful tool. Control of IAQ alsois an important asset for energy savings. Only the rightamount of fresh air is handled by the system reducingunnecessary ventilation.

Ease of use: Trane systems can be run through anintuitive web-style user interface, as well as from touchscreens displays at every level of the system. The use of anadvanced password system allows the use of filteringscreens so that users only have access to what they reallyneed. End users can also use their standard PC to operatethe system, by surfing on their dedicated web pages forsetpoint adjustment, for example. Alarms are alsomonitored by the system and can be forwarded to theappropriate recipient via e-mail. Reports are accessiblethrough couple of mouse clicks, no engineering, noprogramming being required. Time of day schedules,setpoints and system statuses can be accessed, for readingand reading/writing, depending on the password given.

1 = Open space Comfort: AHU with factory-mounted control MP581

2 = Variable air volume damper: VariTraneTM

+ VV550

1

2

Page 24: Train Instrument's

22PROD-PRC014-E4

Water terminal units systems

Function

Water terminal units and chillers are Trane core products.Understanding how this equipment is being usedtogether, is part of Trane know-how that has beenconverted into a Management System. Other equipmentserving building comfort system is also under Tranesystem, control such as air handling units, exhaust fans,water treatment, but also ancillaries such as lights, powerdistribution panels, and so on.The system that Trane offers covers key points for aproject to be successful.

Comfort: Trane has developed advanced electroniccontrollers that offer individual comfort at each terminalunit level. This comfort is offered several ways• Temperatures are being monitored and controlled to

stay within limits each user can adjust, either byindividual wall sensors, or by the use of web pages.

• Sound level is maintained at its minimum value and airmovement reduced as much as possible by the controlof fan speed, which is maintained at the lowest value aspossible.

• Comfort is maintained year-round, cooling/heating modeis controlled automatically and intelligently, change overbeing totally transparent to the occupant.

• Comfort for the operation manager is also ensured.Master/Slaving is now very easy to set up andreconfigure. Open space re-design can be done in veryshort period of time.

• Indoor Air Quality (IAQ) is also one of the advantages ofa Trane system which is capable of monitoring andmaintaining IAQ within optimum limits, by collectingIAQ data from terminal units and givingrecommendation to the AHU, thanks to communicationbuses.

Ease of use: Trane systems communicate throughopen protocols (LonTalk® BACnetTM) as a core means ofdata sharing. In addition to this data sharing, the systemhandles several types of user interfaces, so that everyuser can have access to the information he needs, whilenot being overwhelmed with inappropriate data.• Terminal units can be equipped with wall sensors

embedding indications such as setpoint, timed override,and temperature values. This information can beadjusted within pre-determined limits.

• Operation managers can have access to system statusby using an advanced graphical interface running on aPC. This status can be filtered and organized accordingto the use. Software interfaces integrate a user-friendlygraphical interface allowing authorized users tochange/create graphics to optimized them for theirown use.

Page 25: Train Instrument's

BM

S:

Fu

nctio

ns

Wat

er S

yste

ms

23PROD-PRC014-E4

• Operation engineers can have access to systeminformation in the different technical locations in thebuilding by the use of VGA touch screens, on which localdata are presented.

• Time-of-day (TOD) scheduling is integrated in thesystem and offers a very convenient interface for TODadjustment, group/zone creation or modifications.

• Every single piece of equipment in the system can befocused on. It can be overridden in any state as formaintenance or test purposes. A trend can also begenerated for it, and automatic reporting is available,not requiring any specific programming.

• Equipment or system alarms can be monitored andbroadcasted on the system so that the best recipient canget a notice for this particular event and react in themost efficient manner. If a recipient does not reactwithin a pre-defined period of time, the alarm isforwarded to another level of recipients until the alarmis acknowledged.

• The addition of a web server allows for systemperformances monitoring from a PC equipped with asimple browser. Graphics and trends are converted toHTML pages and are available from any location on theintranet/internet, through the use of an IP address.

Savings: Through the coordination of all equipmentwithin the building, it is quite simple for the managementsystem to optimize energy consumption. Savings also areavailable at system design and system commissioningphases.• Water system management can be organized, so that

either chilled water or hot water production is handledin the most efficient way. Hot water can be generatedeither by boilers, reversible units or a combination ofthe two.

• Equipment schedules integrate an optimization function,which determines building inertia and adjusts start/stoptime according to temperatures/relative humidity andbuilding occupancy.

• Each Trane piece of equipment is delivered with factory-mounted controls which are ready to work when theequipment leaves the factory. No extra work on site isrequired for it to control the equipment it is associatedwith.

Coordination of production (cooling/heating) and use(FCU, AHU…) is one of the best approaches to optimizesystem operation. Communication is the key factor forthis to be efficient and Trane equipment all integrate astandard protocol interface.

1 = Open Space comfort:HFO with factory mounted ZN controller

2 = Ancillaries control:Lighting control: EXL, Sunblinds control: EXB

3 = Open Space comfort:UniTraneTM II with factory-mounted ZN523 controller

4 = Tenant interface: Setpoint and room conditionsinformation: Zone Sensor (ZSM-10, ZSM-31)

4

3

1

2

Page 26: Train Instrument's

24PROD-PRC014-E4

Office building management solution

Packaged systems

Ideal working conditions foroccupants• Air movement and noises eliminated thanks to

intelligent ventilation control• A healthy environment through air quality control with

air handling devices• Comfort at the right time thanks to advanced comfort

scheduling function• Lights and blinds automatic control

Freedom to occupants• Individual temperature adjustment capability (wall

interface)• Individual ventilation mode adjustment capability• Timed override for extended occupancy periods.

Total building control from oneoperator graphical interface• Controls and coordinates HVAC equipment• Drives and schedules technical lots, such as lighting,

exhaust fans, central ventilation, etc.• Interfaces with anti-intrusion, fire and safety systems,

tracking their running mode and failures• Reports power station and power distribution system

failures and status• Centralizes the whole building control and optimizes

energy use• Manual override of all equipment from its graphical

touch screen

Easy building optimization• Measures and displays electric energy consumption• Measures and displays all other fluid energy data• Tracks all crucial information for efficient business

operation

Zenith

Page 27: Train Instrument's

BM

S:

Fu

nctio

ns

Pac

kag

e sy

stem

s

25PROD-PRC014-E4

Powerful control system, easy to useand understand• A state-of-the-art touch screen user interface to display

pertinent data• Easy browsing through the building areas• Fast and simple time-of-day scheduling

Straightforward, eye-pleasing controls• Representative graphics on HVAC equipment• Graphical interface for every function (scheduling, timed

override, alarm display...)

Keeps your building running costunder control with impressiveprogrammable functions• Sub-systems control such as chiller plant system

optimization, intelligent changeover, etc.• Automatic processing of environmental conditions

(outside air temperature, building inertia, etc.),• Time-of-day scheduling allows to adapt building comfort

to its occupancy needs,• Programming of long vacant periods,• Antifreeze building protection,• Automatic cooling and heating system temperature

reset.

Reliable and affordable BuildingManagement System• A pre-engineered package that requires little

engineering• Factory-mounted controls strategy for a greater

reduction in installation and commissioning time• A single-source system means Trane takes care of your

Zenith system during the entire project lifecycle, andbeyond through service contracts options

Guaranteed results• Trane has proven knowledge of building comfort with a

comprehensive line of reliable and efficient equipment• All Trane equipment uses Trane factory-mounted controls

for full system optimization• With a reduced number of suppliers Trane efficiently

coordinates the entire project• Zenith design was based on Trane's strong experience in

building management (more than 1,500 sites overEurope)

• All Zenith equipment uses the open communicationcapability of microprocessor-based controllers

Flexible system architecture with anopen approach• Zenith uses LonTalk® open protocol for simple system

expansion and easy non-Trane device integration• Zenith also supports BACnet™ as a native open protocol

for straight interoperability.

Page 28: Train Instrument's

26PROD-PRC014-E4

Application Selection Information

Water Terminal unit controller

Description

Optimized controller for water terminal unit control application. Can drive 3 wires or hot wax valvesactuators, supports most common unit configuration and drive a solid state relay for sound levelcomfort.

Customer benefits

Reduced commissioning time: • Compact, quick connection, embedded power supply• Master / slave direct binding • Advanced comfort: Cascade zone / supply air temperature algorithm for precise temperature control

Chilled beam controllers

Application ZN523

Factory-mounted YesCommunication LonTalk®2-pipe cooling-only Yes2-pipe cooling-only + electric heater YesFunctionThermal valve actuator Yes3 wires valve actuator control YesOccupied/unoccupied mode YesWall sensor(setpoint knob, override/cancel) YesSupply air measure YesEntering water temperature measure YesMaster/Slave YesOccupied stand-by Yes

This is a short list of what can be done with these controllers. For information on other applications, contact your local Trane Sales Office.

Application ZN523

Factory-mounted Yes

Communication LonTalk®-SCC

2-pipe cooling-only x

2-pipe cooling-only + electric heater x

2-pipe heating only x

2-pipe changeover x

2-pipe changeover + electric heater x

4-pipe x

FunctionFan speed control (3 speeds) Auto

Thermal valve actuator control Yes

3 wires valve actuator control Yes

Automatic changeover Yes

Occupied/unoccupied mode Yes

Wall sensor (fan speed: low/medium/high/auto/off,setpoint knob, override/cancel) Yes

Automatic fan speed optimization Auto

Supply air measure and control Yes

Entering water temperature measure Yes

Auto changeover (2-pipe mode) Yes

Auto changeover (4-pipe mode) Yes

Dirty filter timer Yes

Master/Slave Yes

Occupied stand-by Yes

Timed override Yes

Duty cycling Yes

Frost protection Yes

Power up function Yes

Diagnosis Yes

Page 29: Train Instrument's

27

VAV Terminal units controllers

Description

Dedicated to variable air volume valves control, these controllers handle multiple application type,and integrate several diagnostic features for easy commissioning and facility management.

Customer benefits

• Application flexibility: same controller whatever the application is• Reduced communication time: multiple diagnosis at controller level• Freedom of choice: can either be tied in Trane BMS or in any LonTalk compatible BMS

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Ap

plica

tio

ns

PROD-PRC014-E4

UCM VAV III/IV VV550

Application

Factory-mounted Yes Yes

Communication Proprietary LonTalk®-SCC 8500

1 duct Yes Yes

1 duct + heating water coil Yes Yes

1 duct + heating electric coil Yes Yes

1 duct with parallel fan Yes Yes

1 duct with series fan Yes Yes

1 duct with parallel fan and water coil Yes Yes

1 duct with parallel fan and electric coil Yes Yes

1 duct with series fan and water coil Yes Yes

1 duct with series fan and electric coil Yes Yes

Function

Integrated airflow control Yes Yes

Integrated supply/extract flow differential control No Yes

Generic output No Yes

Generic binary input or occupancy sensor input Yes Yes

CO2 sensor input or auxiliary temperature sensor Yes Yes

Remote communication pins on wall sensor Yes Yes

Automatic calibration Yes Yes

Air/water balancing application No Yes

Manual test function Yes Yes

Damper position for pressure optimization Yes Yes

CO2 base demand control ventilation No Yes

Ventilation ratio to control outdoor air damper Yes Yes

This is a short list of what can be done with these controllers. For information on other applications, contact your local Trane Sales Office.

Page 30: Train Instrument's

28PROD-PRC014-E4

Air Handling Units - AHU controllers

Description

Pre-engineered or fully programmable controller for AHU applications. Support LonMark SpaceComfort Controller (SCC 8500) or Discharge Air Controller (DAC 8610) profiles.

Customer benefits

• Reduced commissioning by the use of application libraries for AH541• Reduced programming time by use of Trane Graphical Programming and re-use of existing

application library of AH541

Air Handling Units - AHU controller AH541 MP581/583

Factory-mounted Yes Yes

Communication LonTalk® LonTalk®

Analog inputs

Return / supply / outdoor air temperature sensor X / X / X X / X / X

Ambient / mixed air temperature sensor X / X X / X

Temperature setpoint adjustment X X

Duct static pressure X X

Differential pressure X X

Return / supply / outdoor air humidity sensor X / - / - X / X / X

Ambient air humidity sensor - X

Humidity setpoint adjustment - X

CO2 sensor / CO2 setpoint - / X X / X

Air quality / IAQ setpoint - / X X / X

Binary inputsFrost thermostat X X

Differential filter pressure switch X X

Low air pressure switch X X

Motor(s) default(s) X X

Electrical heater default X X

Damper end switch X X

On/off contact X X

Occupancy mode X X

Timed override X X

Communication bus terminals 2 2

Analog OutputPre-heating / cooling / heating valves X / 0-10 V/3 wires X / 0-10 V/3 wires

Signal damper X / 0-10 V/3 wires X / 0-10 V/3 wires

Electrical heater X / 0-10 V/3 wires X / 0-10 V/3 wires

Variable speed supply air / return air motor X / 0-10 V/3 wires X / 0-10 V/3 wires

Signal humidifier X / 0-10 V/3 wires X / 0-10 V/3 wires

Temperature * *

Humidity * *

Pressure * *

Position damper * *

Binary outputSupply air motor command X X

Extract air motor command X X

Damper command X X

Humidifier command X X

Default Signal X X

- Not Available * Screen Display point X Hardware point

Page 31: Train Instrument's

29

Technical lots - Input/Output controllers

Description

Field installed controllers dedicated to monitoring and control of any technical lots, such as boilerplant, point monitoring, specific algorithm control.

Customer benefits

• Open systems: LonTalk compatibility• Adapted range of product to real use: small / medium / large point count• Flexibility for programming panels

MP501 MP503 MP583 MP581

Factory-mounted No No No NoCommunication LonTalk® LonTalk® LonTalk® LonTalk®I/O capacity 4 8 > 20 > 20Application

Single loop controller X - X XMonitoring temperature - X X XMonitoring humidity - X X XMonitoring pressure - X X XControl mechanical equipment - X X XControl water pumps - - X XControl boilers - - X XControl cooling towers - - X XControl heat exchangers - - X XDisplay screen option - - X XFreely programmable - - X XLocal overrides (software) - - X XLocal overrides (LCD) - - X XLocal language - - X XMounting Cabinet Cabinet DIN rail Wall

- Not AvailableX Hardware point

This is a short list of what can be done with these controllers. For informations on other applications, contact your local Trane Sales Office.

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Ap

plica

tio

ns

PROD-PRC014-E4

Page 32: Train Instrument's

30PROD-PRC014-E4

Building Management Systems - User Interface

Description

Different interfaces that adapt to the right application: From local display for controlling a processfrom its location, to PC workstation software allowing for total building management, and to Webserver for serving pages to remote connected end users.

Customer benefits

• Consistency in function provided: scheduling, alarming, reporting, timed override, systemmonitoring, event logging

• Easy operation: custom graphics, view / control of any system point

Application

Password protected X X X

Touch screen interface X X -

Windows type navigation - X X

Time of day scheduling X X X

Event logging X X X

Trending/event graphing - X X

Pre-engineered reports - X X

Custom reports - X -

Personal computer support - X X

User friendly alarm log interface X X X

Alarms acknowledge X X -

Remote RS 232 connection X X -

Remote IP connection X X X

- Not Available

X Compatible

This is a short list of what can be done with these controllers. For informations on other applications, contact your local Trane Sales Office.

BCU Display Tracer SummitTM Web Server

Page 33: Train Instrument's

31

Protocol gateway

Description

Dedicated to MODBUS interfacing between Trane and non Trane devices, this compact interfacesoffer straight commissioning and low risk of technical issues.

Customer benefits

• Open systems: supports reliable and highly supported MODBUS RTU protocol• Straight commissioning: auto binding with LonTalk compatible units

ProtocolInterface

Controller (PIC)

BCU+

PIC

BCU+

Field Server

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Ap

plica

tio

ns

PROD-PRC014-E4

Chiller controllers Number of unit per interface

SMM 1 4 10 Max

TRACER CH532 1 4 10 Max

UCM-CLD + CSR 1 4 10 Max

UCP2 + TCI3-com3 1 - -

UCP2 + TCI3-com4 1 4 10 Max

TRACER CH.530 1 4 10 Max

Rooftop controllers

Rooftop + UCP2 + TCI-3 com3 1 4 16 Max

Rooftop + Reliatel + LCI-r 1 4 16 Max

Terminal unit controllers

ZN523 - 25 100 Max

Generic PLC's

AH541 - 4 10 Max

MP581 - 4 10 Max

MP501-503 - 4 120 Max

Generic data point - 50 500 Max

- Not Available

This is a short list of what can be done with these controllers. For information on other applications, contact your local Trane Sales Office.

Page 34: Train Instrument's

32PROD-PRC014-E4

Technical characteristics

Terminal Unit controller - ZN523

Description

Advanced compact water terminal unit controller. Flexible and optimized for comfort and energysaving control.

Customer benefits

• Optimized commissioning : compact, can come as factory-mounted option, pre-commissioned• Flexibility: same controller for several application types (hot wax / 3 wires applications, …)• Error less wall interface wiring: RJ9 connector for quick and reliable communication with wall

interface

I/O Type Index Signal type I/O Use

Binary inputs BI 1 Dry contact Occupancy

BI 2 Dry contact Window contact

AI 1 thermistor Return air temperature

Analog inputs AI 2 thermistor Entering water temperature

AI 3 thermistor Discharge air temperature

BO 1 relay 230 Vac / 3A NO High fan speed

BO 2 relay 230 Vac / 3A NO Medium fan speed

BO 3 relay 230 Vac / 3A NO Low fan speed

Binary outputs BO 4 triac 230 Vac, 5 A Heat valve open, electric heat (solid state relay)

BO 5 triac 230 Vac, 5 A Heat valve close

BO 6 triac 230 Vac, 5 A Cool valve open

BO 7 triac 230 Vac, 5 A Cool valve close

BO 8 relay 230 Vac / 10A NO Electric heat (relay)

Main features

Power 230 Vac 50/60 Hz 1phase

Operating environment 0 to +60°C

5 - 95% humidity non-condensing

Storage environment - 40 to +85°C

5 - 95% humidity non-condensing

Protection class IP 20

Dimensions (mm) 132 x 120 x 44

Agency listing / compliance Immunity (directive 89/336/EEC)

EN 50082-1: 1997 - EN 50082-2: 1995

Emissions EN 50081-1: 1992

Communication LonTalk® protocol SCC 8501 profile

Network type : FTT10-A

Diagnosis interface 3 LED / "Service pin" 1 push button

ZN523

Page 35: Train Instrument's

33

Zone Sensor for water terminal units

Description

Innovative in its design and function set, this interface offers user friendly comfort control, as wellas occupant unique features, such as occupant call, or maintenance request.

Customer benefits

• Ease of use: clear large Liquid Crystal Display and large push buttons• Reduced commissioning time: use of RJ9 type connection to the controller• Short commissioning: menu driven setup

Bu

ild

ing

M

an

ag

em

en

t S

ystem

sP

rod

uct

s

PROD-PRC014-E4

ZSM-10 ZSM-11 ZSM-31

Ambient limits

Operating temperature Temperature: 5°C to 35°C Temperature : from 0° to 60°C Temperature : from 0° to 60°C

Relative humidity: 5% to

95% NC

Relative Humidity : from 5% to 95%

NC

Relative Humidity : from 5% to 95%

NC

Storage temperatureTemperature: -40°C to

70°CTemperature : -40° to 85°C Temperature : -40° to 85°C

Relative humidity: 5% to

95% NCRelative Humidity : 5% to 95% NC Relative Humidity : 5% to 95% NC

Setpoint offset range

Setpoint offset is

adjustable from

-1°K/+1°K to -5°K/+5°K

Setpoint offset is fixed: +/- 3°K Step =

0.5K

Absolute or relative, Setpoint offset

adjustable from -1°K/+1°K to -5°K/+5°K

Enclosure Material ABS UL94V0 Material ABS UL94V0 Material ABS UL94V0

Color: White (RAL 9010) Color: White (RAL 9010) Color: light gray

Dimensions: 80 mm x

80 mm x 32 mmDimensions: 80 mm x 80 mm x 30 mm ø120 mm, 30 mm (thickness)

Interface

1 knob for fan speed

1 knob for setpoint

1 push button for timed

override

1 Led for mode indication

1 Push button +/- for changing value

1 Push button for Occupied mode

1 Push button for unoccupied mode

1 Push button for Fan speed

1 Push button for setpoint

1 Liquid Crystal Display

2 Push button +/- for changing value

1 Push button for Occupied mode

1 Push button for Timed override

1 large Liquid Crystal Display with red

foreground and white background

Display indicationsActive zone temperature, relative set-

point, occupancy status.

Active zone temperature, absolute or

relative setpoint, occupancy status,

controller fault status, active occupant

call status, window open status, main-

tenance call

CompatibilityCompatible with Trane round robin

synchronization feature.

Compatible with Trane round robin

synchronization feature.

Standards

Product security EN 60730-2-9: Temperature sensing controls

Electromagnetic Compatibility EN 50081-1: Emission, EN 50082-2: Immunity

Power supply Powered by the ZN523 controller

Degree of protection IP 30

Page 36: Train Instrument's

3434PROD-PRC014-E4

Description

These panels are to be used along with Trane ZN523 Zone controller.They allow for control of up to two independent lighting circuits (EXL)and two independent blinds (EXB).

Customer benefits

Easy installation (DIN Rail - Direct connection with Wielandconnectors). These panels are driven through ZN523 and do not useany LonTalk™ node connection.

EXB

EXL

EXB EXL

Board dimensions 95 mm height x 132 mm width x 43 mm depthMinimum clearance Front 100 mm

Each side 25 mmTop and bottom 100 mm

Operating environment Temperature : from 0° to 50°CRelative Humidity : from 20% to 90% non-condensing

Dust protection : pollution level 1Storage environment Temperature : from -20° to 70°C

Relative Humidity : from 20% to 90% non-condensingMechanical protection IP 20Power requirements 230 VAC 230 VAC

50 or 60 Hz 50 or 60 HzLoad 5A/output Load 5A/output

ProtectionThe unit controller must receive power from a dedicated circuit, it must be protected by a circuit

breaker/fuse located next to it.Recommended wire The AC-power wiring requires three-wire 230 Vac service

The recommended wire is 16 AWG (1.5mm2) copper wire.Connector Wieland connector, GST 18/3 type, maleStandards The AC-power wiring must comply with applicable local electrical codes :

89/336/EEC European directive for electromagnetic compatibility :- Immunity : 50081-1- Emission : 50082-1

73/23/EEC European directive for low voltage electrical equipment :- EN 60950

Contact type Normally OpenNominal/Max current 5A/10AMax voltage 250 VacOutputs Verify that wiring conforms to outputs specifications aboveRecommended wire Use only 18-22 AWG, twisted pair with stranded, tinned-copper conductorsConnector Wieland connector, GST 18i4 type, femaleStandards All wiring must comply with the applicable local electrical codes

Page 37: Train Instrument's

Bu

ild

ing

M

an

ag

em

en

t S

ystem

sP

rod

uct

s

35

Description

Infrared system for interfacing with ZN523 controller as well as EXBand EXL.

Customer benefits

Receiver can easily be integrated in the customer's buildingenvironment thanks to its small size and discreet aspect. The remotecontrol is design and can be installed in a receptacle installed on awall.

Infrared remote controller (IRC)

Functions Control of 2 independent lighting device groupsControl of 2 independent sunblind groupsShift of the temperature setpoint by +/- 3 programmable stepsControl of the fan speed : on/off, speed 1, 2 or 3, auto mode

Range 6m when direct aimingInfrared protocol Rc5 with error check for safetyOverall dimensions 148 mm x 58 mm x 25 mmOperating environment Temperature : from 0° to 50°C

Relative Humidity : from 20% to 90% non-condensingStorage environment Temperature : from -20° to 70°C

Relative Humidity : from 20% to 90% non-condensingMechanical protection IP 40Enclosure White plastic boxKeypad Elastomer keypad, 9 keys :

- 4 function keys : lighting, sunblind, temperature, fan speed- 3 operation keys : up arrow, down arrow, rotation arrow- 2 global keys : occupancy, unoccupancy

Display LCD screen with backlight, view area 30 x 30mm, function iconsPower supply 3 x 1.5V batteries, LR6 typeBattery life 2 years minimum, for normal use

Infrared receiver (IRR)

Dimensions 63 mm height x 22 mm width x 22 mm depthOperating environment Temperature: 0° to 50°CMechanical protection IP 65 (front face), IP20 (on RJ9 connector)Connector RJ9Cable length 6 m, 12 mRecommended cable FCC-68 : flat cable, 4 white conductors, 26 AWG

(Suitable for FCC-68 connectors and Western digital)Power supply Powered by the TracerTM EXB or TracerTM EXL to which it is attached.

IRC

IRR

PROD-PRC014-E4

Page 38: Train Instrument's

3636PROD-PRC014-E4

Two-way control valve PN16, flat sealing DN15/20

Valve type 2-wayMedium type WaterMaterials Body DN15 brass, DN20 red brass, stem stainless steel, plug brassAction to open Stem downMedia temperature 21 ... 20°CStatic pressure PN16Port connection type Flat sealing

Three-way/bypass control valve PN16, flat sealing DN15/20

Valve type 3-way mixing, bypassMedium type WaterMaterials Body red brass, stem stainless steel, plug brassAction to open Stem downMedia temperature 21 ... 20°CStatic pressure PN16Port connection type Flat sealing

DN D Kvs Stroke (mm)15 G1/2 1.6 6.520 G3/4 2.5 6.5

DN D Kvs Stroke (mm)15 G1/2 1.6 6.520 G3/4 2.5 6.5

Page 39: Train Instrument's

Protection class IP43 (IP40 for horizontal mounting)Stem force 90 NControl input signal 2-ptStroke 6.5 mmPower loss action Stem retractsCable length 2.5 mInitial current 0.7A

Actuator thermoelectric for zone control, 6.5 mm 90 N

Actuator 3-pt for zone control, 6.5 mm 180

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Acc

esso

ries

37PROD-PRC014-E4

Power supply

Vac/VA

Runtime

Min230/3 4.0

Stem force Power supplyN Vac/VA180 230/7

Protection class IP43/42Stem force 180NControl input signal 3-ptStroke 6.5 mmRuntime 150 sCable length 1.5 mInitial current 0.7APosition indication With red indicator

Page 40: Train Instrument's

38PROD-PRC014-E4

AHU Controller - AH541

Description

Field installed controller on Air Handler Units. AH541 comes with pre-engineered functions for fastcommissioning of most common units.

Customer benefits

• Flexibility: expandable controller through the use of EX2 panels• Easy operation: user-friendly optional touch screen for unit monitoring, overrides and control• Open systems: supports SCC / DAC LonTalk® profile

AH541

I/O Features Number Supported signal type

Universal input 12 Dry contact (included pulses)

0-10 Vdc - 0-20 mA

Linear variable resistor - Thermistor

Specific Pressure Input 1 Specific Input for Trane pressure sensor

Binary outputs 2 24 Vac powered contact (12 Vac 0,5A)

Analog Outputs 5 0-10 Vdc - 0-20 mA

Main Features

Power Supply 24 Vac 50/60 Hz 1 phase - 10 VA under 24 Vac

Operating environment - 40 to +70°C (0 to +50°C operator display)

10 to 90% humidity non-condensing

Storage environment - 50 to +95°C (-25 to +75°C operator display)

10 to 90% humidity non-condensing

Protection Class IP 20

Dimensions (mm) 215x385x127

Weight (kg) 1

Memory RAM 512 K ROM 2 MB flash EEPROM 256 K

Operator display (option) Touch screen resolution 320x240 pixels

Timer Included in the operator display

Battery Dynamic data/time: high capacity backup (7 days)

Agency listing / compliance Immunity (directive 89/336/EEC)

EN 50090-2-2: 1996

Emissions (directive 89/336/EEC)

EN 50090-2-2: 1996 - EN 61000-3-2: 1996 - EN 61000-3-3: 1995

Communication LonTalk® Protocol SCC or DAC profile

Network type : FTT10-A

Extension Capability 4 EX2 modules maximum

Diagnosis Assistance 9 LED - 1 "service pin"

Page 41: Train Instrument's

MP581/583

I/O Features Number Supported signal type

Universal input 12 Dry contact (included pulses)

0-10 Vdc - 0-20 mA

Linear variable resistor

Thermistor

Specific Pressure Input 1 Specific Input for Trane pressure sensor

Binary outputs 6 24 Vac powered contact (12 Vac 0,5A)

Analog Outputs 6 0-10 Vdc - 0-20 mA

Main Features

Power Supply 24 Vac 50/60 Hz 1 phase - 10 VA under 24 Vac

Operating environment - 40 to +70°C (0 to +50°C operator display)

10 to 90% humidity non-condensing

Storage environment - 50 to +95°C (-25 to +75°C operator display)

10 to 90% humidity non-condensing

Protection Class IP 20

Dimensions (mm) 215x385x127

Weight (kg) 1

Memory RAM 512 K ROM 2 MB flash EEPROM 256 K

Operator display (option) Touch screen resolution 320x240 pixels - Local language

Timer Included in the operator display

Battery Dynamic data/time: high capacity backup (7 days)

Agency listing / compliance Immunity (directive 89/336/EEC)

EN 50090-2-2/96: 1996

Emission (directive 89/336/EEC)

EN 50090-2-2: 1996 - EN 61000-3-2: 1996 - EN 61000-3-3: 1995

Communication LonTalk® Protocol SCC or DAC profile

Network type : FTT10-A

Extension Capability 4 EX2 modules maximum

Diagnosis Assistance 9 LED - 1"service pin"

Freely programmable I/O controller - AHU controller - MP581 - MP583

Description

This freely programmable controller uses a graphical programming tool that allows control softwareeasy development, applied on any HVAC and building management applications. Its use is userfriendly thanks to its local LCD touch screen.

Customer benefits

• Easy operation: user-friendly touch screen, driven by icons; expandable through the use of EX2panels

• Ease of programming: graphical interface TGP (Tracer Graphical Programming) for efficientprogramming

• Open systems: supports LonTalk® communication protocol, as a DAC, SCC or generic profile

Bu

ild

ing

M

an

ag

em

en

t S

ystem

sP

rod

uct

s

39PROD-PRC014-E4

Page 42: Train Instrument's

40PROD-PRC014-E4

EX2 - MP 581/583 I/O Expansion Module

Description

The EX2 is a field-installed expansion module for MP581 freely programmable controller. It allowsMP581 to monitor and control I/O point at remote locations, by driving these expansion panels overa simple RS485 communication bus.

Customer benefits

• Low cost expansion panels: offers 6 universal inputs, 4 binary outputs, 4 analog outputs per panel• Ease of installation: compact enclosure• Flexibility: EX2 is linked to the master panel over a communication bus for remote installation

Description

This is an intuitive LCD operator interface allowing for easy point monitoring, overriding, schedulingand troubleshooting. It consists in a high resolution graphical touch screen enclosed in a nicelooking casing for convenient installation.

Customer benefits

• Convenient interface: can be installed directly in building tenant spaces for being an interface withthem

• Ease of use: supports local languages• Ease of diagnosis: shows point overrides, in alarms, ...

MP581/583 Operator Display

I/O Features Number Supported signal type

Universal input 6 Dry contact binary - 0-20 mA - 0-10 Vdc - RTD - Thermistor

Binary outputs 4 24 Vac powered contact (12 Vac 0,5A)

Analog Outputs 4 0-10 Vdc - 0-20 mA

Main Features

Power Supply 24 Vac 50/60 Hz - 60 VA maximum

Operating environment - 40 to +70°C

5 to 90% humidity non-condensing

Storage environment - 40 to +85°C

5 to 95% humidity non-condensing

Dimensions (mm) 175 x 137 x 51

Weight (kg) 1

Agency listing / compliance Emission (directive 89/336/EEC)

EN 50081-1: 1992 - EN 50090-2-2: 1996 - EN 61326-1: 1997

Immunity (directive 89/336/EEC)

EN 50082-1: 1997 - EN 50082-2: 1995 - EN 50090-2-2: 1996- EN 61326-1: 1997

Communication Communicates with MP 581 on an IEEE-485 link

Main Features Supported signal type

Power Supply No power supply : gets its power from the panel it is connected to

Operating environment 0 to +50°C

10 to 90% humidity non-condensing

Dimensions (mm) 260 x 222 x 58

Touch screen VGA backlit crystal display with touch-screen

Viewable area : 115 mm x 86 mm

Resolution of 320 x 240 pixels

Page 43: Train Instrument's

41

I/O Panel Features

MP501 MP503

I/O Features Number Number

Analog input 1

Binary input 1

Universal input 4

Binary outputs 1 4

Analog Outputs 1

Main Features

Power Supply 24 Vac nominal, 50/60 Hz,

1 phase, 70VA max

Operating environment 0 to +70°C

5 - 95% humidity non-condensing

Storage environment -40 to +85°C

5 - 95% humidity non-condensing

Analog input Thermistor or 4-20 mA

Binary input Powered input 24Vac 0,25VA

Universal input Dry contact or 0-20mA or 0-10Vdc or 10 kohm thermistor

Binary outputs 24 Vac 12 VA powered relay

Analog Outputs 0-20mA or 0-10 Vdc

Protection class IP 20

Dimensions (mm) 175 x 137 x 51

Weight (kg) 0.22

Agency listing Immunity: EN 50082: 1997

compliance Emissions: EN 50081-1: 1992, EN 61000-3-2: 1996

Communication LonTalk® protocol

Network FTT10-A

Generic I/O controllers - MP501/503

Description

Range of I/O controllers with various capacities and built in functions, adapted to different functionssuch as point monitoring, point scheduling, simple loop control, HVAC process control orexpandable controller for flexible I/O count support.

Customer benefits

• Open systems: LonTalk® communication protocol• Application flexibility: output status feedback• Optimized cost: several panel sizes for perfect adaptation to the need

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Pro

du

cts

PROD-PRC014-E4

Page 44: Train Instrument's

42PROD-PRC014-E4

BCU - BMTX

Web Server

Description

BCU is an intelligent panel that controls integration and networking capabilities of the TracerSummitTM product suite. It handles peer to peer data base management with pre-engineeredfunctions such as Chiller Plant Control or data logging.

Customer benefits

• System that lasts: high reliability• Low risk in database management: peer to peer shared database• Open protocols, BACnetTM and Lontalk®

Description

Tracer SummitTM Web Server allows users using a web browsing application to operate a buildingcontrolled by Trane Tracer SummitTM. Schedules, areas, setpoint adjustment or data logging andrending can be accomodated among other functions.

Customer benefits

• Two network part for separation between HVAC and office Ethernet• Flexibility: any PC with web browser can serve as entry point in the system• Ease of operation: graphic interface with user friendly interface (Calendar, ….)

Main Features

Operating environment 0 to +50°C

10 - 90% humidity non-condensing

Storage environment -40 to +85°C

10 - 90% humidity non-condensing

Protection class IP 30

Dimensions (mm) 260x223x70

Weight (kg) 1.1

Agency listing / compliance CE EN 61326: 1998 - EN 61010-1: 1993

Memory RAM 32 MB ROM 256 Mo flash

Security Secure Sockets layer (SSL) protocol

Software requirement Java 2 plug in 1.4.0 or higher Web browser Internet Explorer 5.01 or higher

Netscape navigator 6.2 or higher

Network Two RJ 45 Ethernet 10/100 BaseT ports with rate auto detection

I/O Features Number Supported signal type

Binary inputs 2 Pulse meter or standard status inputs

Main Features

Power Nominal rating : 230 Vac; 50 or 60 Hz; 1 phase

Operating environment 0 to +50°C

10 - 90% humidity non-condensing

Storage environment -46 to +66°C

10 - 90% humidity non-condensing

Enclosure NEMA-1

Dimensions (mm) 418 x 373 x 140

Weight (kg) 7

Agency listing / compliance EN 61326: 1998 Class B - EN 61326: 1998 Commercial - EN 61010-1: 2001

Memory FLASH 16 MB - EEPROM 512 KB - SRAM 1 MB - SDRAM 8 MB

Battery Programs backed up by non-volatile memory

Communication Ethernet port EIA-232 BACnetTM port

Comm3, Comm4 : 2 links, and LonTalk®

Operator display (option) Monochrome VGA touch screen - 320 x 240 pixels

Modem (option) Internal 56 kbps

Page 45: Train Instrument's

43

VAV UCM III/IV

Description

VAV UCM II/IV are dedicated controllers for any VAV application type. It measures air flow andtemperature for a cascade control process allowing for accurate and precise room comfortmanagement.

Customer benefits

• Easy commissioning: factory installed control: flow (min / max / nominal) are preset at the factory• Reliable system application: perfectly integrated within Tracer SummitTM Variable Air System

pre-engineered function

I/O characteristics Number Supported signal type

Binary inputs 1 Occupancy or generic binary input

Analog inputs 8 Zone temperature Zone sensor common ground

Local setpoint CO2 sensor Pressure transducer

Auxiliary temperature or CO2 sensor

Outdoor air temperature or

Generic temperature universal 4-20 mA

Binary outputs 5 Open damper Close damper

Modulating heating valve open

Modulating heating valve close

Main Features

Power 24 Vac 50/60 Hz 1 phase - 50 VA max

Consumption 50 VA max at 24 Vac

Operating environment 0 to +60°C

10 - 90% humidity non-condensing

Storage environment -40 to +65°C

10 - 90% humidity non-condensing

Communication TRANE proprietary protocol

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Pro

du

cts

PROD-PRC014-E4

Page 46: Train Instrument's

44PROD-PRC014-E4

Description

VV550 are dedicated controllers for any VAV application type. It measures air flow and temperaturefor a cascade control process allowing for accurate and precise room comfort management. It supports LonTalk open protocol.

Customer benefits

• Easy commissioning: factory installed control: flow (min / max / nominal) is preset at the factory• Reliable system application: perfectly integrated within Tracer SummitTM Variable Air System

pre-engineered function

I/O characteristics Number Supported signal type

Binary inputs 1 Occupancy or generic binary input

Analog inputs 4 Space temperature, space setpoint, primary/discharge air

temperature, primary air flow

Binary outputs 5 Air valve close, air valve open, heat stage 1, heat stage 2,

heat stage 3/Fan on/off

Main Features

Power 18-32 Vac (24 Vac nominal) at 50/60 Hz

Operating environment 0 to +60°C

5 - 95% humidity non-condensing

Storage environment -40 to +65°C

5 - 95% humidity non-condensing

Communication LonTalk® protocol

LonMark® Space Comfort Controller profile (SCC 8500)

VV550

Page 47: Train Instrument's

PROD-PRC014-E4

Pro

du

cts

45

Field Server

Description

BACnetTM to MODBUS gateway, dedicated to Tracer SummitTM applications.

Customer benefits

• Easy commissioning: easy to set up MODBUS data table• Easy operation and diagnosis: compact device with diagnosis indicator (Leds)

I/O Features Supported signal type

Connection 1 RJ 45 IEA-232

1 screw terminal EIA-485

1 10 BaseT RJ 45 Ethernet

Main features

Power 24 Vac 50/60 Hz 1phase , 1A; 9-30 V DC, 1A

Operating environment 0 to +60°C

10 - 90% humidity non-condensing

Storage environment -46 to +66°C

10 - 90% humidity non-condensing

Protection class IP 30

Dimensions (mm) 110 x 90 x 45

Agency listing / compliance CE EN 55022 Class B

LED 9 active LED for: Transmit, receive, Ethernet link, power OK,

bridge running, configuration error, node offline, comm error,

system error

Software Software and driver compatibility: BACnetTM (Ethernet or IP)

MODBUS RTU

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Page 48: Train Instrument's

46PROD-PRC014-E4

PIC

Description

Gateway for converting Trane proprietary protocols to MODBUS/RTU, or between Trane equipmentLonTalk controllers and MODBUS/RTU.

Customer benefits

• Easy commissioning: auto commissioning / auto binding supported• Flexibility: compatible with all Trane equipment• Easy operation and diagnosis: terminal port + status light indicators

I/O Features Supported signal type

Connection 1 IEA-232

1 EIA-485

Main features

Power 230 Vac, 50/60 Hz, 1phase

Operating environment 0 to +60°C

10 - 90% humidity non condensing

Storage environment -46 to +66°C

10 - 90% humidity non condensing

Protection class IP 30

Agency listing / compliance CE 89/336/EEC

LED Active LED for : Transmit , receive, power OK,

configuration error, comm error, system error.

Software MODBUS RTU, slave mode

1200 to 57600 bps

Page 49: Train Instrument's

BMS Software:Tracer SummitTM

Description

Human interface between building manager and control system. Integrates graphical browsing ofthe application, user friendly interface for scheduling, reporting, alarms tracking and forwarding.

Customer benefits

• User friendliness: reduced training need• Reduced commissioning time: advanced LonTalk® capability allowing easy integration of non

Trane devices• Efficient building operation: auto reporting

Bu

ild

ing

M

an

ag

em

en

t S

ystem

s

Pro

du

cts

47PROD-PRC014-E4

I/O characteristics Number

Operating system Windows ME, NT4.0, 2000, XP

Hardware requirement Windows XP, Processor 233 MHz 64 MB RAM

Windows 2000, 300 MB hard drive free space

Windows NT4.0 (> SP3.0) 32x CDROM

15" SVGA display, 1280x1024 resolution minimum

Communication BACnetTM BACnetTM ASHRAE/ANSI 135 standard

10BASE-T/ 100BASE-TX dedicated Ethernet or

TCP/IP compatible network

Communication LonTalk® Based on EIA-709.1 LonTalk® standard

LonTalk® Standard Network Variable Types

FTT-10A transceivers

Twisted-pair physical media

Communication MODBUS Tracer Summit communicates with devices that support

the MODBUS Remote Terminal Unit (RTU) protocol using

the Field Server

Interface Graphical HTML pages (PC) Resolution: default: 1280 x 1024

Interface VGA monochrome display (BCU) Resolution: default: 320x240

Interface Supported operating systems languages: allLanguages: German - Polish - French -

Spanish - Portuguese - Hungarian - Greek

- English

Page 50: Train Instrument's

48PROD-PRC014-E4

CHILLED WATER TERMINALS

Page 51: Train Instrument's

1kW 2 304 12 203 5 10 15 49PROD-PRC014-E4

WA

TE

R S

YS

TE

MS

Office building, commercial and lodging applications

CHILLED WATER TERMINALS1 - 30 kW

1 12 FCK

2 7 HFR

UniTrane™

Slim Line

4 30FWD

1 5 HFHSlim Line

2 7 HFOSlim Line

1 5 FVCUniTrane™

1 12 FCKUniTrane™

1 5 FCCUniTrane™

1 5 FCCUniTrane™

1 12 CWS

max. 50 Pa in medium speed

> 50 Pa (98 to 230 Pa in medium speed)

max. 40 Pa in medium speed

max. 50 Pa in medium speed

max. 50 Pa in medium speed

Installationtype

Product range

Total capacities given at Eurovent conditions, medium speed

Page 52: Train Instrument's

FCK

50PROD-PRC014-E4

Customer benefits • Silent operation: high level of acoustic comfort• Energy efficient: low operation costs• Easy installation: saving of time and money

Main features• Very low noise levels (one of the quietest units on the

market, based on Eurovent data)• Very easy to install thanks to key holes, drain pan

supplied with flexible hose• Very easy to maintain due to accessible filter (no tool

needed) and life-lubricated fan motor• Very easy to wire due to quick connectors, without

opening the control panel• Convertible on job site (FCC and FCK) vertical <->

horizontal• Low energy consumption

Options• Several electric heater capacities per unit size and

protected by two overheat thermostats (automatic andmanual reset)

• On/off 2-way and 3-way/4-port valves• Modulating 2-way and 3-way/4-port valves• High external static pressure motor (up to 50Pa in

medium speed)• Right/left hand water connections• Factory-mounted feet• Epoxy coating water coil for aggressive atmosphere• Flange for discharge air connection• Cleanable EU3 filter• Factory-wired fan speeds combination according to

customer requirements

Accessories• On/off 3-way/4-port valve• Painted mounting feet• 0-33% manual fresh air damper• Painted return air grille• Painted rear panel• Auxiliary drain pans• Wall thermostats (L, M, N, P)• Flexible connections• Flange for return air connection• Condensate pump

Controls• Built-in on/off controls on fan, valve or/and electric

heater• Remote on/off controls on fan, valve or/and electric

heater• New factory-mounted LonMarkTM Trane ZN523 control,

providing enhanced acoustical and thermal comfort, andenergy saving solutions

• Full range of user interfaces (ZSM-10, ZSM-11) andwireless remote control (IRC)

• Trane ZN523 can be associated with Trane EXL-EXB forlight and sunblind control

• Factory-mounted BatiBUS control

Fan coil units1-12 kW

Chilled water terminals

UniTrane™

L

FCC

FVCP M/N

ZSM-10 ZSM-11 IRC

Page 53: Train Instrument's

General data

PROD-PRC014-E4

Water S

ystem

sU

niT

ran

e™

51

Unit size 01 02 03 04 06

Speed at ESP = 0 Pa 2 4 5 1 2 4 1 3 5 1 2 4 1 3 5Airflow (m3/h) 119 173 219 154 192 284 203 263 370 330 368 565 356 540 762Cooling Constant water flow method (1)Total capacity (kW) 0.8 1.0 1.0 1.2 1.3 1.6 1.6 1.8 2.1 2.6 2.8 3.5 3.0 3.9 4.7Sensible capacity (kW) 0.5 0.7 0.8 0.8 0.9 1.2 1.0 1.2 1.5 1.8 1.9 2.5 2.0 2.7 3.4Water flow (l/h) 185 278 376 621 816Cooling Constant delta T° method (2)Total capacity (kW) 0.7 0.9 1.0 1.0 1.2 1.6 1.4 1.7 2.1 2.4 2.6 3.5 2.6 3.7 4.7Sensible capacity (kW) 0.5 0.7 0.8 0.7 0.9 1.2 1.0 1.2 1.5 1.7 1.8 2.5 1.8 2.6 3.4Water flow (l/h) 121 159 185 170 205 278 238 293 376 421 457 621 459 638 816Water content (l) 0.55 0.83 1.1 1.5 1.7Heating Constant water flow method (3)Total capacity (kW) 0.9 1.0 1.1 1.0 1.1 1.3 1.5 1.6 1.8 2.0 2.1 2.4 2.4 2.8 3.2Water flow (l/h) 89 106 155 205 270Heating Constant delta T° method (4)Total capacity (kW) 0.8 1.0 1.1 1.0 1.1 1.3 1.4 1.6 1.8 1.9 2.0 2.4 2.3 2.8 3.2Water flow (l/h) 69 81 89 82 90 106 120 134 155 164 171 205 197 233 270Water content (l) 0.13 0.13 0.19 0.24 0.29Electric heaterCapacity (W) 530 530/1060 750/1500 980/1960 1530/3060Electric heater absorbedcurrent (A) 2.3 2.3/4.6 3.3/6.5 4.3/8.5 6.7/13.3Fan motor absorbed power (W) 17 25 31 20 25 36 23 30 47 30 33 63 31 50 79Maximum external staticpressure (5) (Pa) 25 30 50 20 25 50 20 25 50 50 50 50 50 50 50Water connections ½" ISO/R7 female gasSound power level (6) (dB(A)) 27 37 42 32 35 45 36 43 51 36 45 57 31 45 57Sound pressure level (7) (dB(A)) 18 28 33 23 26 36 27 34 42 27 36 48 22 36 48

08 11 12 15 20

Speed at ESP = 0 Pa 1 3 5 1 3 4 1 2 4 1 2 3 1 3 4Airflow (m3/h) 547 744 956 577 1136 1573 835 1295 1816 1390 1788 2572 1416 2155 3120Cooling Constant water flow method (1)Total capacity (kW) 4.3 5.1 5.8 4.8 7.1 8.2 7.1 9.3 11.0 9.9 11.3 13.3 10.1 12.6 14.8Sensible capacity (kW) 2.9 3.5 4.2 3.2 5.1 6.2 4.7 6.5 8.1 6.7 8.0 10.0 6.8 8.9 11.1Water flow (l/h) 1018 1458 1945 2355 2644Cooling Constant delta T° method (2)Total capacity (kW) 3.9 4.9 5.8 3.8 6.6 8.2 6.2 8.7 11.0 9.0 10.6 13.3 9.1 11.9 14.8Sensible capacity (kW) 2.7 3.5 4.2 2.8 4.9 6.2 4.4 6.3 8.1 6.4 7.7 10.0 6.3 8.6 11.1Water flow (l/h) 684 857 1018 677 1170 1458 1093 1539 1945 1583 1877 2355 1612 2122 2644Water content (l) 2.1 2.7 3.2 3.6 4.1Heating Constant water flow method (3)Total capacity (kW) 3.2 3.6 3.9 4.3 5.6 6.3 5.3 6.3 7.2 7.3 8.1 9.5 8.7 10.3 12.1Water flow (l/h) 331 525 595 782 995Heating Constant delta T° method (4)Total capacity (kW) 3.1 3.5 3.9 4.0 5.4 6.3 5.0 6.1 7.2 7.0 7.9 9.5 8.3 10.0 12.1Water flow (l/h) 261 297 331 337 452 525 423 510 595 588 658 782 688 832 995Water content (l) 0.34 0.44 0.52 0.60 0.68Electric heaterCapacity (W) 1970/3940 3060 3940 4800 4800Electric heater absorbed current (A) 8.6/17.1 13.3 17.1 20.9 20.9Fan motor absorbed power (W) 41 66 102 107 198 251 112 204 305 212 272 394 289 397 553Maximum external static pressure (5) (Pa) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50Water connections ½" ISO/R7 female gasSound power level (6) (dB(A)) 42 52 60 43 55 64 51 57 63 53 59 70 55 63 72Sound pressure level (7) (dB(A)) 33 43 51 34 46 55 42 48 54 44 50 61 46 54 63

Power supply : 230V/50Hz/1Ph(1) 2-pipe, 3-row coil, air: 27°C/19°C, water inlet : 7°C, delta T° = 5°K in high speed(2) 2-pipe, 3-row coil, air: 27°C/19°C, water: 7/12°C, constant dela T°(3) 4-pipe, 1-row coil, air: 20°C, water inlet : 70°C, delta T° = 10°K in high speed(4) 4-pipe, 1-row coil, air: 20°C, water: 70/60°C, constant delta T°(5) With High External Static Pressure motor(6) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor(7) Values calculated from sound power levels with a hypothetical acoustic attenuation of 9 dB.

Page 54: Train Instrument's

5252PROD-PRC014-E4

Dimensions and weights

Z

Y

X

XY

Z

X

Y

Z

X

Y

Z

Z

Y

X

X Y Z

FCC 01 790 450 238 18 -

FCC 02 790 450 238 18 -

FCC 03 990 450 238 22 -

FCC 04 1190 450 238 25 -

FCC 06 1390 450 238 32 -

FCC 08 1590 450 238 40 -

FCK 01 530 430 217 17 470x122

FCK 02 530 430 217 17 470x122

FCK 03 730 430 217 20 670x122

FCK 04 930 430 217 23 870x122

FCK 06 1130 430 217 30 1070x122

FCK 08 1330 430 217 38 1270x122

FCK 11 1191 574 (3) 291 55 1092x203

FCK 12 1391 574 (3) 291 63 1292x203

FCK 15 1591 574 (3) 291 71 1492x203

FCK 20 1791 574 (3) 291 80 1692x203

FVC 01 790 450 228 18 -

FVC 02 790 450 228 18 -

FVC 03 990 450 228 22 -

FVC 04 1190 450 228 25 -

FVC 06 1390 450 228 32 -

FVC 08 1590 450 228 40 - (1) Without options or accessories(2) Without water content, options, or accessories(3) With discharge air flange connection option

Dimensions (1)

(mm)

Duct connection

dimensions (3)

(mm)

Operating Weight (2)

(kg)

Unit size

FCC 01-08 - verticalFCC 01-08 - horizontal FCK 01-20 - horizontal

FVC FCK 01-20 - vertical

Page 55: Train Instrument's

Performance data

PROD-PRC014-E4

Un

itsiz

e

Air

flo

w(m

3/h

)

Air

tem

pera

ture

Cooling capacities - 0Pa - 2-pipe / 4-pipe coilConstant delta T°

Water temperature flow / return in °C

5/10 5.5/11 6/12 7/12 8/13TkW SkW l/h TkW SkW l/h TkW SkW l/h TkW SkW l/h TkW SkW l/h

22/15.5°C 0.7 0.6 132 0.6 0.6 104 0.5 0.5 78 0.5 0.5 95 0.5 0.5 86

24/17.0°C 1.0 0.7 175 0.9 0.7 139 0.7 0.6 111 0.8 0.6 134 0.6 0.6 116

01 219 26/18.7°C 1.3 0.8 221 1.1 0.8 182 1.0 0.7 148 1.0 0.7 178 0.9 0.7 156

28/20.4°C 1.5 0.9 268 1.4 0.9 226 1.3 0.8 190 1.3 0.8 227 1.2 0.8 205

22/15.5°C 1.1 1.0 194 0.9 0.9 150 0.8 0.8 125 0.8 0.8 146 0.7 0.7 134

24/17.0°C 1.5 1.1 258 1.3 1.0 203 1.1 1.0 158 1.1 1.0 199 1.0 0.9 173

02 284 26/18.7°C 1.9 1.3 330 1.7 1.2 267 1.5 1.1 214 1.5 1.1 264 1.3 1.1 233

28/20.4°C 2.3 1.4 406 2.1 1.4 338 1.9 1.3 278 1.9 1.3 340 1.7 1.2 305

22/15.5°C 1.5 1.2 270 1.3 1.2 212 1.1 1.1 165 1.1 1.1 203 1.0 0.9 173

24/17.0°C 2.0 1.4 354 1.8 1.3 285 1.5 1.2 228 1.5 1.2 274 1.3 1.2 238

03 370 26/18.7°C 2.5 1.7 443 2.3 1.6 369 2.1 1.5 302 2.1 1.4 362 1.8 1.3 320

28/20.4°C 3.1 1.8 535 2.9 1.8 454 2.6 1.7 384 2.6 1.6 457 2.4 1.6 415

22/15.5°C 2.6 2.1 462 2.3 2.0 376 2.1 1.8 306 2.0 1.8 357 1.7 1.7 311

24/17.0°C 3.4 2.4 588 3.0 2.2 486 2.7 2.1 401 2.7 2.1 468 2.3 1.9 411

04 565 26/18.7°C 4.1 2.7 721 3.8 2.5 609 3.5 2.4 512 3.4 2.4 600 3.1 2.2 536

28/20.4°C 4.9 3.0 861 4.6 2.8 737 4.3 2.7 632 4.2 2.7 741 3.9 2.5 677

22/15.5°C 3.4 2.7 601 3.0 2.6 483 2.6 2.4 386 2.6 2.4 461 2.2 2.1 391

24/17.0°C 4.4 3.2 770 4.0 3.0 631 3.5 2.8 516 3.5 2.8 610 3.0 2.6 535

06 762 26/18.7°C 5.5 3.6 953 5.0 3.4 799 4.6 3.2 666 4.5 3.2 786 4.0 3.0 701

28/20.4°C 6.6 4.0 1142 6.1 3.8 974 5.7 3.6 830 5.6 3.6 978 5.1 3.4 892

22/15.5°C 4.3 3.4 760 3.9 3.2 619 3.4 3.0 504 3.3 3.0 588 2.9 2.8 514

24/17.0°C 5.5 3.9 965 5.0 3.7 798 4.5 3.5 659 4.4 3.4 769 3.8 3.2 677

08 956 26/18.7°C 6.8 4.4 1183 6.3 4.2 999 5.8 4.0 840 5.6 3.9 983 5.0 3.7 879

28/20.4°C 8.1 4.9 1413 7.6 4.7 1209 7.1 4.5 1036 6.9 4.4 1214 6.3 4.1 1109

22/15.5°C 5.9 5.1 1063 5.1 4.7 842 4.2 4.1 642 4.4 4.3 795 3.9 3.8 719

24/17.0°C 7.7 5.8 1370 6.8 5.4 1108 6.0 5.1 891 6.0 5.1 1081 5.3 4.8 950

11 1573 26/18.7°C 9.7 6.6 1715 8.8 6.2 1416 7.8 5.8 1163 7.9 5.8 1398 7.0 5.5 1243

28/20.4°C 11.8 7.3 2075 10.9 7.0 1751 10.0 6.6 1471 9.9 6.6 1758 9.0 6.2 1590

22/15.5°C 8.2 6.7 1460 7.3 6.3 1187 6.4 5.9 963 6.3 5.9 1143 5.4 5.3 987

24/17.0°C 10.4 7.6 1840 9.4 7.2 1520 8.4 6.8 1254 8.3 6.7 1478 7.3 6.3 1309

12 1816 26/18.7°C 12.8 8.5 2259 11.8 8.1 1896 10.8 7.7 1590 10.6 7.6 1872 9.4 7.2 1680

28/20.4°C 15.4 9.5 2706 14.4 9.1 2304 13.4 8.6 1962 13.1 8.5 2312 11.9 8.1 2107

22/15.5°C 9.9 8.3 1781 8.9 7.8 1460 8.0 7.4 1199 7.8 7.3 1406 6.7 6.5 1221

24/17.0°C 12.6 9.3 2236 11.4 8.9 1853 10.3 8.4 1537 10.0 8.3 1798 8.9 7.8 1597

15 2572 26/18.7°C 15.5 10.5 2746 14.3 10.0 2305 13.1 9.5 1936 12.8 9.3 2269 11.4 8.8 2035

28/20.4°C 18.7 11.6 3290 17.5 11.1 2800 16.2 10.6 2386 15.9 10.4 2807 14.4 9.9 2554

22/15.5°C 11.1 9.2 2007 10.0 8.7 1652 8.9 8.3 1365 8.7 8.1 1589 7.4 7.3 1380

24/17.0°C 14.0 10.4 2515 12.8 9.8 2087 11.5 9.3 1738 11.2 9.2 2023 9.9 8.7 1799

20 3120 26/18.7°C 17.3 11.7 3085 16.0 11.1 2594 14.6 10.5 2180 14.2 10.4 2550 12.7 9.8 2286

28/20.4°C 20.9 12.9 3691 19.5 12.3 3145 18.1 11.8 2684 17.7 11.6 3153 16.1 11.0 2872

TkW: Total cooling capacity in kW SkW: Sensible cooling capacity in kWCapacities given in high speed l/h: Water flow in liters per hour

Water S

ystem

sU

niT

ran

e™

53

Page 56: Train Instrument's

5454PROD-PRC014-E4

Correction factors

Unitsize

Totalcapacity

SensiblecapacityAirflow 2-pipe 4-pipe 2-pipe 4-pipe

Medium speed Low speed Medium speed Low speed

Cooling Heating

Sensiblecapacity

In order to determine the cooling and heating capacity of units in medium and in low speed,multiply the capacity in high speed by the correction factors given in the following table.

TotalcapacityAirflow

01 0.79 0.86 0.84 0.54 0.66 0.64 0.82 0.90 0.61 0.76

02 0.68 0.76 0.74 0.54 0.65 0.61 0.73 0.83 0.60 0.75

03 0.71 0.77 0.76 0.55 0.63 0.61 0.76 0.86 0.60 0.76

04 0.65 0.73 0.71 0.58 0.67 0.65 0.70 0.83 0.64 0.79

06 0.71 0.77 0.76 0.47 0.54 0.53 0.76 0.86 0.53 0.72

08 0.78 0.84 0.83 0.57 0.66 0.65 0.82 0.89 0.63 0.78

11 0.72 0.79 0.77 0.37 0.45 0.44 0.77 0.86 0.44 0.63

12 0.71 0.82 0.81 0.46 0.55 0.53 0.75 0.85 0.51 0.69

15 0.70 0.79 0.77 0.54 0.66 0.63 0.76 0.83 0.62 0.74

20 0.69 0.80 0.78 0.45 0.60 0.57 0.74 0.83 0.52 0.68

Standard motor 0Pa

Page 57: Train Instrument's

Water pressure drops - cooling

PROD-PRC014-E4

Water S

ystem

sU

niT

ran

e™

55

2-pipe coil /3-row

kP

akP

a

l/h

l/h

Page 58: Train Instrument's

5656PROD-PRC014-E4

Performance data

Unitsize

Airflow(m3/h)

Airflow(m3/h)

Unitsize

Heating capacities - 0Pa - Air temperature = 20°CConstant delta T°

2-pipe/3 row coil Water temperature flow / return in °C

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h

01 219 1.2 206 1.5 253 1.9 161 2.4 208 2.7 115 3.1 238 3.3 139

02 284 1.7 295 2.1 363 2.7 230 3.5 299 3.9 165 4.4 342 4.7 199

03 370 2.2 378 2.7 464 3.5 296 4.5 381 5.0 212 5.6 435 6.0 255

04 565 3.4 582 4.2 711 5.3 455 6.8 585 7.7 327 8.6 667 9.2 393

06 762 4.4 746 5.4 914 6.8 583 8.8 751 9.8 418 11.0 858 11.8 503

08 956 5.6 949 6.8 1160 8.7 742 11.2 954 12.5 533 14.0 1088 15.0 639

11 1573 9.5 1591 11.6 1953 14.6 1243 18.9 1606 20.9 889 23.7 1836 25.2 1072

12 1816 12.3 2064 14.9 2523 19.0 1618 24.4 2079 27.4 1166 30.6 2369 32.8 1398

15 2572 14.8 2479 18.0 3037 22.8 1936 29.3 2496 32.6 1387 36.8 2849 39.2 1668

20 3120 20.2 3393 24.6 4145 31.3 2659 40.1 3412 45.0 1914 50.2 3888 53.9 2294

4-pipe/1 row coil Water temperature flow / return in °C

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h TkW l/h

01 219 0.5 84 0.7 110 0.8 63 1.1 89 1.0 42 1.4 106 1.3 56

02 284 0.6 101 0.8 131 0.9 76 1.3 106 1.2 51 1.6 126 1.6 67

03 370 0.9 150 1.1 190 1.4 115 1.8 155 1.9 79 2.4 181 2.3 99

04 565 1.2 200 1.5 251 1.8 154 2.4 205 2.5 107 3.1 237 3.1 132

06 762 1.6 266 2.0 331 2.4 204 3.2 270 3.4 143 4.1 312 4.2 176

08 956 2.0 327 2.5 406 3.0 252 3.9 331 4.2 177 5.0 382 5.1 216

11 1573 3.2 513 4.0 645 4.8 394 6.3 525 6.6 274 8.0 610 8.1 339

12 1816 3.7 584 4.5 731 5.5 449 7.2 595 7.6 313 9.1 690 9.3 386

15 2572 4.8 769 5.9 959 7.3 592 9.5 782 10.0 414 11.9 904 12.2 509

20 3120 6.2 980 7.6 1220 9.3 756 12.1 995 12.8 529 15.2 1148 15.6 649

TkW: Total heating capacity in kWl/h: Water flow in liters per hourCapacities given in high speed

Page 59: Train Instrument's

Water pressure drops - heating

PROD-PRC014-E4

Water S

ystem

sU

niT

ran

e™

57

01

02

4-pipe coil /1-row

kP

a

l/h

l/h

kP

a

Page 60: Train Instrument's

58PROD-PRC014-E4

Customer benefits • Silent operation: maximum acoustic comfort• Flexibility: customized system to fit the customer's exact

requirements• Easy commissioning: saving of time and money

Main features• Unit specially designed for office applications• Use of 1 mm thick galvanized steel• High performance water coil (aluminium fins/copper

tubes)• Hot and/or chilled water coil• ½" water connections ISO R7 gas (screw connections)• Multi-speed motor with internal thermal protection• Use of plastic fan housings and large diameter wheels

for low sound levels• Quick connector for the control panel connection• Air inlet connections diameter 200 mm (HFO)• Direct inlet (HFR)• 50 Pa available for ducts and diffusers• Electric and hydraulic connections accessible on the

same side to save space• Low energy consumption

Options• Several electric heater capacities per unit size• Modulating and on/off 3-way/4-port or 2-way/2-port valve

for cooling and/or heating coils for better control• Fresh air intake diameter 100 or 125 mm with fixed

controller 30 m3/h, 45 m3/h, or adjustable controller60-130 m3/h for air renewal

• Easily accessible and cleanable EU3 or EU4 filter

• 4-pipe water coil• Right- or left-hand connections• Epoxy coating water coil for aggressive atmosphere• Fuse protection• Spigot arrangement• Factory-wired fan speeds combination according to

customer requirements

Accessories• Wall fan switch L: 3-speed fan switch• Wall thermostat M: 3-speed switch + 1-stage stat +

manual changeover for the fan• Wall thermostat N: 3-speed switch + 1-stage stat +

manual changeover for the valve• Wall thermostat P: 3-speed switch + 2-stage stat for the

valve• Flexible connections• Auxiliary drain pan• Fresh air controllers (30,45 and 60-130 m3/h)• On/off 3 way/4 port valve• Condensate pump

Control• Remote on/off controls on fan, valve and/or electric

heater• New factory-mounted LonMarkTM Trane ZN523 control,

providing enhanced acoustical and thermal comfort, andenergy saving solutions

• Full range of user interfaces (ZSM-10, ZSM-11) andwireless remote control (IRC)

• Trane ZN523 can be associated with Trane EXL-EXB forlight and sunblind control

• Factory-mounted BatiBUS control

Office applications2-7 kW

Chilled water terminals

Slim Line HFO/HFR

HFO-HFR

L P M/N

ZSM-10 ZSM-11 IRC

Page 61: Train Instrument's

General data HFO

PROD-PRC014-E4

Water S

ystem

sH

FO-H

FR

59

Unit size 04 06 08

Speed at ESP=0 Pa 2 3 6 2 3 6 3 6 7Power supply (V/Ph/Hz) 230/1/50 230/1/50 230/1/50

Airflow (m3/h) 296 373 535 555 679 887 746 1051 1095

Cooling (1)

Total capacity (2) (kW) 2.1 2.6 3.4 4.0 4.6 5.6 5.3 6.7 6.9

Sensible capacity (kW) 1.5 1.8 2.5 2.8 3.3 4.0 3.7 4.8 5.0

Water flow (l/h) 367 449 600 695 808 976 919 1173 1209

Water pressure drop (3) (kPa) 5 8 14 19 25 37 33 53 56

Water content (l) 1.5 1.7 2.1

1/2" ISO/R7 1/2" ISO/R7 1/2" ISO/R7 Water connection type

female gas female gas female gas

Heating (4)

Total capacity (5) (kW) 2.1 2.3 2.7 3.4 3.7 4.1 4.3 5.0 5.1

Water flow (l/h) 178 195 227 285 311 349 362 420 427

Water pressure drop (3) (kPa) 4 5 6 10 12 15 16 21 22

Water content (l) 0.24 0.29 0.34

1/2" ISO/R7 1/2" ISO/R7 1/2" ISO/R7Water connection type

female gas female gas female gas

Electric heater

Capacity (W) 500-750-1000-1500-2000 500-750-1000-1500-2000-3000 500-750-1000-1500-2000-3000-4000

Electric heat absorbed current (6) (A) 2.3-3.3-4.3-6.5-8.6 2.3-3.3-4.3-6.5-8.6-13.0 2.3-3.3-4.3-6.5-8.6-13.0-17.4

Fan motor power (6) (W) 30 39 69 70 85 106 76 120 145

Maximum external static pressure (Pa) 50 50 50

Sound power level (7) (dB(A)) 47 51 59 49 53 61 53 62 63

Sound pressure level (8) (dB(A)) 27 31 39 29 33 41 33 42 43

(1) 2-pipe, 3-row coil(2) Air 27°C/19°C, water 7/12°C(3) For the water coil only, without valve(4) 4-pipe, 1-row coil(5) Air 20°C, water 70/60°C(6) For 230V/1Ph/50Hz(7) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor(8) Values calculated from sound power levels with a hypothetical acoustic attenuation of 20dB.

Page 62: Train Instrument's

Unit size 04 06 08 11 12 15

Speed at ESP=0 Pa 2 3 6 2 3 6 3 6 7 1 5 7 1 4 7 1 3 5

Power supply (V/Ph/Hz) 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Airflow (m3/h) 315 390 632 375 527 866 734 1096 1206 687 1167 1375 918 1243 1500 975 1492 1985Cooling (1)Total capacity (2) (kW) 2.2 2.7 3.8 2.9 3.8 5.5 5.2 6.9 7.3 4.8 6.9 7.6 6.1 7.5 8.4 6.7 8.9 10.6Sensible capacity (kW) 1.6 1.9 2.8 2.0 2.7 4.0 3.6 5.0 5.3 3.3 5.0 5.6 4.3 5.3 6.1 4.6 6.3 7.7Water flow (l/h) 388 466 677 508 671 965 909 1206 1289 849 1213 1342 1081 1321 1488 1188 1575 1872Water pressuredrop (3) (kPa) 6 8 17 10 17 36 32 56 64 40 77 93 73 112 144 94 155 211Water content (l) 1.5 1.7 2.1 2.3 2.7 3.1

Heating (4)Total capacity (5) (kW) 2.2 2.4 2.9 2.9 3.3 4.1 4.4 5.2 5.5 4.1 5.3 5.7 5.1 5.9 6.5 5.9 7.1 8.2Water flow (l/h) 185 202 247 242 281 347 369 439 459 343 437 474 429 492 538 489 595 683Water pressuredrop (3) (kPa) 4 5 7 7 10 15 17 24 26 5 7 8 8 10 12 11 15 19Water content (l) 0.24 0.29 0.34 0.45 0.53 0.61

Electric heaterCapacity (W) 500-750-1000- 500-750-1000- 500-750-1000-1500- 2000-3000 3000-4000 3000-4500

1500-2000 1500-2000-3000 2000-3000-4000(A) 2.3-3.3- 2.3-3.3-4.3- 2.3-3.3-4.3-6.5- 8.7-13.0 13.0-17.4 13.0-19.6

4.3-6.5-8.6 6.5-8.6-13.0 8.6-13.0-17.4Fan motor power (6) (W) 37 47 85 62 79 116 80 125 158 118 182 202 127 170 214 178 244 281Maximum externalstatic pressure (Pa) 50 50 50 50 50 50Sound powerlevel (7) (dB(A)) 49 45 57 42 45 55 51 60 63 52 63 67 57 64 69 59 65 70Sound pressurelevel (8) (dB(A)) 29 25 37 22 25 35 31 40 43 32 43 47 37 44 49 39 45 50

(1) 2-pipe, 3-row coil(2) Air 27°C/19°C, water 7/12°C(3) For the water coil only, without valve(4) 4-pipe, 1-row coil(5) Air 20°C, water 70/60°C(6) For 230V/1Ph/50Hz(7) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor(8) Values calculated from sound power levels with a hypothetical acoustic attenuation of 20 dB

Water connection type

6060PROD-PRC014-E4

General data HFR

Y

X

ZZ

X

Y

Dimensions (1) Operating Weight (2) Duct connection dimensions

(mm) (kg) (mm)

Unit size X Y Z Intake Discharge (4)

HFO 04 1085 962 217 (3) 38 1 x Ø 200 1 x Ø 200 HFO 06 1285 962 217 (3) 43 2 x Ø 200 2 x Ø 200 HFO 08 1485 962 217 (3) 48 3 x Ø 200 3 x Ø 200HFR 04 1085 909 217 (3) 38 Direct inlet 1 x Ø 200HFR 06 1285 909 217 (3) 43 Direct inlet 2 x Ø 200 HFR 08 1485 909 217 (3) 48 Direct inlet 3 x Ø 200HFR 11 1307 811 235 37 Direct inlet 3 x Ø200HFR 12 1507 811 235 45 Direct inlet 3 x Ø200HFR 15 1707 811 235 63 Direct inlet 4 x Ø200

(1) Without options and including the auxiliary drain pan accessory(2) Without water content, options, or accessories(3) 224mm with the auxiliary drain pan accessory(4) Standard configuration, other configurations are possible

HFO - front view HFR - back view

Dimensions and weights

1/2" ISO/R7 female gas

1/2" ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2" ISO/R7 female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

1/2” ISO/R7female gas

Water connection type

Electric heat absorbedcurrent (6)

Page 63: Train Instrument's

Performance data HFO

PROD-PRC014-E4

Un

itsiz

e

Air

flo

w(m

3/h

)

Air

tem

pera

ture

Water S

ystem

sH

FO-H

FR

61

Cooling capacities - 3-row coil - 30PaConstant delta T°

Water temperature flow / return in °C

5/10 5.5/11 6/10 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22/15.4°C 1.1 0.8 189 1 1.0 0.8 158 1 1.0 0.8 225 2 0.8 0.8 150 1 0.8 0.7 133 1

24/17.1°C 1.3 1.0 233 2 1.2 0.9 196 2 1.4 1.0 306 4 1.1 0.8 189 1 1.0 0.8 169 1203

26/18.7°C 1.8 1.1 308 4 1.5 1.0 246 2 1.8 1.1 390 6 1.4 1.0 244 2 1.2 0.9 212 2

28/20.4°C 2.2 1.3 380 6 2.0 1.2 318 4 2.2 1.3 473 9 1.8 1.1 323 4 1.7 1.1 290 3

22/15.4°C 1.3 1.1 236 2 1.2 1.1 196 2 1.4 1.1 313 4 1.1 1.0 189 1 0.9 0.9 165 1

0424/17.1°C 1.9 1.3 327 4 1.6 1.2 254 3 1.9 1.3 416 7 1.4 1.1 246 2 1.2 1.0 211 2

28426/18.7°C 2.4 1.5 420 7 2.2 1.4 343 5 2.4 1.5 524 11 1.9 1.3 340 5 1.7 1.2 298 4

28/20.4°C 2.9 1.7 512 10 2.7 1.7 432 7 2.9 1.7 634 15 2.5 1.6 437 7 2.3 1.5 396 6

22/15.4°C 2.1 1.7 368 5 1.8 1.6 284 3 2.1 1.7 465 8 1.5 1.5 275 3 1.3 1.3 234 2

24/17.1°C 2.8 2.0 484 9 2.4 1.8 389 6 2.7 2.0 604 14 2.1 1.7 378 6 1.8 1.6 327 4443

26/18.7°C 3.5 2.3 609 14 3.2 2.1 504 10 3.4 2.2 754 22 2.8 2.0 498 10 2.5 1.9 442 8

28/20.4°C 4.2 2.5 737 21 3.9 2.4 624 15 4.2 2.5 909 31 3.6 2.3 629 15 3.3 2.1 571 13

22/15.4°C 2.5 2.0 448 8 2.2 1.8 356 5 2.5 2.0 551 12 1.9 1.7 338 5 1.6 1.6 291 3

24/17.1°C 3.3 2.3 577 13 3.0 2.1 473 9 3.2 2.3 707 19 2.6 2.0 458 8 2.3 1.8 399 6476

26/18.7°C 4.1 2.6 713 20 3.8 2.5 599 14 4.0 2.6 871 29 3.4 2.3 593 14 3.0 2.1 530 11

28/20.4°C 4.9 2.9 853 28 4.6 2.8 730 21 4.8 2.9 1042 42 4.2 2.6 736 21 3.9 2.5 674 18

22/15.4°C 3.0 2.3 523 11 2.6 2.2 420 7 2.9 2.3 641 16 2.3 2.0 400 6 1.9 1.9 346 5

0624/17.1°C 3.8 2.7 669 17 3.4 2.5 551 12 3.7 2.6 818 26 3.0 2.3 533 11 2.6 2.2 467 9

57326/18.7°C 4.7 3.0 825 26 4.4 2.9 694 19 4.6 3.0 1008 39 3.9 2.7 686 18 3.5 2.5 614 15

28/20.4°C 5.7 3.4 987 37 5.3 3.2 845 28 5.5 3.3 1206 55 4.9 3.0 851 28 4.4 2.9 778 23

22/15.4°C 3.7 2.9 648 16 3.3 2.7 526 11 3.6 2.9 789 24 2.8 2.6 502 10 2.5 2.4 439 8

24/17.1°C 4.7 3.3 822 26 4.2 3.1 679 18 4.6 3.3 1002 39 3.7 2.9 658 17 3.3 2.7 580 13752

26/18.7°C 5.8 3.8 1011 39 5.3 3.6 850 28 5.6 3.7 1234 58 4.8 3.3 839 27 4.3 3.1 752 22

28/20.4°C 6.9 4.2 1208 56 6.5 4.0 1033 41 6.8 4.1 1479 83 5.9 3.8 1038 41 5.4 3.5 948 35

22/15.4°C 3.3 2.5 575 13 2.9 2.3 466 9 3.2 2.5 696 19 2.5 2.2 441 8 2.1 2.0 381 6

24/17.1°C 4.2 2.9 730 21 3.8 2.7 606 15 4.0 2.8 886 31 3.3 2.5 585 14 2.9 2.3 514 11594

26/18.7°C 5.1 3.3 893 31 4.8 3.1 758 23 5.0 3.2 1085 46 4.3 2.9 749 22 3.8 2.7 672 18

28/20.4°C 6.1 3.6 1063 44 5.8 3.5 915 33 5.9 3.5 1294 65 5.3 3.2 922 33 4.8 3.1 846 28

22/15.4°C 4.4 3.5 782 24 4.0 3.3 640 16 4.3 3.4 942 35 3.4 3.0 609 15 3.0 2.8 533 11

0824/17.1°C 5.6 4.0 984 38 5.1 3.7 819 26 5.4 3.9 1191 55 4.5 3.5 792 25 4.0 3.2 700 19

88126/18.7°C 6.9 4.4 1202 56 6.4 4.2 1018 40 6.7 4.4 1461 82 5.7 3.9 1004 39 5.1 3.7 902 32

28/20.4°C 8.2 4.9 1432 79 7.7 4.7 1228 58 8.0 4.8 1747 117 7.1 4.4 1235 59 6.5 4.2 1131 50

22/15.4°C 4.8 3.8 847 28 4.3 3.6 696 19 4.6 3.7 1020 40 3.7 3.3 663 17 3.2 3.1 583 13

24/17.1°C 6.0 4.3 1063 44 5.5 4.1 886 31 5.8 4.2 1287 64 4.8 3.8 858 29 4.3 3.5 759 23979

26/18.7°C 7.4 4.8 1298 65 6.9 4.6 1098 47 7.2 4.7 1579 96 6.1 4.3 1083 45 5.5 4.0 974 37

28/20.4°C 8.8 5.3 1547 92 8.3 5.1 1326 68 8.6 5.2 1889 136 7.6 4.8 1332 68 6.9 4.5 1219 57

TkW: Total cooling capacity in kW kPa: Water pressure drops in kPaSkW: Sensible cooling capacity in kW l/h: Water flow in liters per hour

Page 64: Train Instrument's

6262PROD-PRC014-E4

Performance data HFO

Air

tem

pera

ture

Air

flo

w(m

3/h

)

Un

itsiz

e

Cooling capacities - 4-row coil - 30PaConstant delta T°

Water temperature flow / return in °C

5/10 5.5/11 6/10 7/12 8/13

TkWSkW l/h kPa TkWSkW l/h kPa TkWSkW l/h kPa TkWSkW l/h kPa TkWSkW l/h kPa

22/15.4°C 1.2 0.9 205 0.4 1.1 0.9 172 0.3 1.1 0.9 244 1 0.9 0.8 165 0.3 0.8 0.8 147 0.2

24/17.1°C 1.4 1.0 251 1 1.3 1.0 212 0.4 1.4 1.0 302 1 1.2 0.9 206 0.4 1.0 0.9 185 0.3203

26/18.7°C 1.7 1.1 301 1 1.6 1.1 256 1 1.8 1.2 396 1 1.4 1.0 254 1 1.3 1.0 230 1

28/20.4°C 2.2 1.3 382 1 1.9 1.2 305 1 2.2 1.3 489 2 1.8 1.1 315 1 1.6 1.1 281 1

22/15.4°C 1.5 1.2 257 1 1.3 1.1 215 0.4 1.4 1.2 308 1 1.2 1.1 208 0.4 1.0 1.0 187 0.3

0424/17.1°C 1.8 1.3 315 1 1.6 1.3 264 1 2.0 1.4 429 2 1.5 1.2 257 1 1.3 1.1 232 1

28426/18.7°C 2.4 1.6 427 2 2.1 1.4 332 1 2.5 1.6 550 3 1.9 1.4 335 1 1.6 1.3 286 1

28/20.4°C 3.1 1.8 533 3 2.8 1.7 440 2 3.1 1.8 671 4 2.6 1.6 449 2 2.3 1.5 402 2

22/15.4°C 2.1 1.8 370 1 1.8 1.6 285 1 2.2 1.8 495 2 1.5 1.5 276 1 1.4 1.4 253 1

24/17.1°C 2.9 2.1 508 2 2.4 1.9 392 1 3.0 2.1 652 4 2.2 1.8 387 1 1.8 1.7 329 1443

26/18.7°C 3.7 2.4 650 4 3.3 2.3 528 3 3.7 2.4 817 6 3.0 2.1 527 3 2.6 2.0 464 2

28/20.4°C 4.5 2.7 795 6 4.2 2.6 666 4 4.5 2.7 991 8 3.8 2.5 675 4 3.5 2.3 611 3

22/15.4°C 2.6 2.1 451 2 2.1 1.8 338 1 2.6 2.1 576 3 1.8 1.7 328 1 1.6 1.5 281 1

24/17.1°C 3.4 2.4 597 3 3.0 2.2 478 2 3.4 2.4 745 5 2.6 2.1 467 2 2.3 1.9 401 2476

26/18.7°C 4.3 2.8 747 5 3.9 2.6 621 4 4.2 2.7 924 8 3.5 2.4 617 4 3.1 2.3 549 3

28/20.4°C 5.2 3.1 902 7 4.8 2.9 766 5 5.1 3.0 1110 11 4.4 2.8 775 6 4.0 2.6 707 5

22/15.4°C 3.1 2.5 541 3 2.6 2.3 418 2 3.1 2.5 680 4 2.3 2.1 404 2 1.9 1.9 342 1

0624/17.1°C 4.0 2.9 704 5 3.6 2.7 570 3 4.0 2.8 873 7 3.2 2.5 556 3 2.7 2.3 483 2

57326/18.7°C 5.0 3.2 875 7 4.6 3.1 730 5 4.9 3.2 1079 11 4.1 2.9 725 5 3.7 2.7 647 4

28/20.4°C 6.0 3.6 1054 10 5.6 3.5 896 7 5.9 3.6 1297 15 5.2 3.3 905 7 4.7 3.1 826 6

22/15.4°C 3.9 3.2 689 4 3.4 3.0 547 3 3.9 3.2 854 7 3.0 2.8 527 3 2.5 2.5 451 2

24/17.1°C 5.0 3.6 882 7 4.5 3.4 721 5 4.9 3.6 1087 11 4.0 3.2 703 5 3.5 3.0 617 3752

26/18.7°C 6.2 4.1 1089 11 5.7 3.9 911 8 6.1 4.1 1339 16 5.1 3.6 904 7 4.6 3.4 809 6

28/20.4°C 7.5 4.6 1308 15 7.0 4.4 1112 11 7.4 4.5 1608 23 6.4 4.1 1121 11 5.8 3.9 1024 9

22/15.4°C 3.4 2.7 598 3 2.9 2.5 472 2 3.4 2.6 738 5 2.5 2.3 451 2 2.1 2.0 373 1

24/17.1°C 4.4 3.1 768 6 4.0 2.9 631 4 4.3 3.0 941 8 3.5 2.7 613 4 3.0 2.5 535 3594

26/18.7°C 5.4 3.5 947 8 5.0 3.3 797 6 5.3 3.4 1157 12 4.5 3.1 791 6 4.0 2.9 897 5

28/20.4°C 6.5 3.9 1133 12 6.1 3.7 970 9 6.4 3.8 1383 18 5.6 3.5 979 9 5.1 3.3 897 8

22/15.4°C 4.8 3.8 839 7 4.2 3.6 679 4 4.6 3.7 1023 10 3.7 3.3 650 4 3.1 3.0 547 3

0824/17.1°C 6.0 4.3 1061 11 5.5 4.1 878 7 5.9 4.3 1293 15 4.8 3.8 854 7 4.3 3.6 753 5

88126/18.7°C 7.4 4.9 1298 16 6.9 4.6 1096 11 7.2 4.8 1584 23 6.2 4.3 1085 11 5.6 4.1 976 9

28/20.4°C 8.9 5.4 1551 22 8.4 5.2 1327 16 8.7 5.3 1897 33 7.6 4.9 1335 16 7.0 4.6 1223 14

22/15.4°C 5.2 4.2 916 8 4.6 3.9 745 5 5.0 4.1 1114 12 4.0 3.7 714 5 3.4 3.3 605 4

24/17.1°C 6.5 4.7 1152 12 6.0 4.5 956 9 6.4 4.7 1403 18 5.3 4.2 930 8 4.6 3.9 823 6979

26/18.7°C 8.0 5.3 1408 18 7.4 5.0 1189 13 7.8 5.2 1719 27 6.7 4.7 1177 13 6.0 4.5 1060 11

28/20.4°C 9.6 5.9 1682 26 9.0 5.6 1438 19 9.4 5.8 2058 38 8.2 5.3 1446 19 7.5 5.0 1324 16

TkW: Total cooling capacity in kW kPa: Water pressure drops in kPaSkW: Sensible cooling capacity in kW l/h: Water flow in liters per hour

Page 65: Train Instrument's

Performance data HFO

PROD-PRC014-E4

Heating capacities - 3-row coil - 30Pa - Constant delta T° - Air temperature = 20°C

Water temperature flow / return in °C

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa

2 203 1.5 258 3 1.9 315 4 2.4 203 2 3.0 260 3 3.4 147 1 3.8 296 3 4.1 176 1

04 3 284 2.1 350 5 2.5 428 7 3.2 276 3 4.1 353 5 4.7 199 2 5.2 402 6 5.6 239 2

6 443 3.1 516 10 3.7 631 15 4.8 405 5 6.1 520 10 6.9 292 3 7.6 593 13 8.2 350 5

2 476 3.4 580 13 4.2 706 19 5.3 456 8 6.8 583 13 7.7 331 4 8.5 663 17 9.2 395 6

06 3 573 4.0 681 18 4.9 831 26 6.3 535 11 8.0 685 18 9.1 387 9 10.0 780 23 10.8 463 8

6 752 5.1 857 28 6.2 1046 41 7.9 672 17 10.1 862 28 11.3 485 11 12.6 982 36 13.6 581 13

3 594 4.2 716 16 5.1 872 23 6.6 563 10 8.4 719 16 9.5 408 6 10.5 818 21 11.4 487 8

08 6 881 5.9 1000 30 7.2 1220 45 9.2 785 19 11.8 1005 31 13.3 567 10 14.7 1144 39 15.9 678 14

7 979 6.5 1090 36 7.9 1331 53 10.0 855 23 12.9 1096 36 14.5 617 12 16.1 1248 47 17.3 738 17

2 203 1.6 275 1 2.0 336 1 2.5 217 0.4 3.3 278 1 3.7 158 0.2 4.1 316 1 4.4 190 0.3

04 3 284 2.2 379 1 2.7 462 2 3.5 299 1 4.5 383 1 5.1 217 0.4 5.6 435 2 6.1 260 1

6 443 3.4 569 3 4.1 695 4 5.3 448 2 6.7 574 3 7.6 325 1 8.4 653 4 9.1 389 1

2 476 3.7 626 4 4.5 762 5 5.8 494 2 7.4 630 4 8.4 360 1 9.2 715 5 10.0 429 2

06 3 573 4.4 741 5 5.3 902 7 6.8 584 3 8.7 746 5 9.9 425 2 10.9 848 6 11.9 507 2

6 752 5.6 942 8 6.8 1149 11 8.7 741 5 11.1 949 8 12.6 537 3 13.9 1080 10 15.0 642 4

3 594 4.6 778 6 5.5 945 8 7.2 614 4 9.1 781 6 10.5 447 2 11.4 887 7 12.4 532 3

08 6 881 6.5 1103 11 7.9 1344 16 10.2 868 7 13.0 1110 11 14.7 630 4 16.2 1262 14 17.6 752 5

7 979 7.1 1208 13 8.7 1472 19 11.1 950 8 14.2 1215 13 16.1 688 4 17.8 1382 17 19.3 822 6

2 203 0.9 148 3 1.1 186 4 1.4 114 2 1.8 151 3 1.9 79 1 2.3 175 4 2.3 98 1

04 3 284 1.0 171 4 1.3 214 6 1.6 131 2 2.1 175 4 2.1 91 1 2.6 203 5 2.7 113 2

6 443 1.3 205 5 1.6 257 8 1.9 157 3 2.5 210 5 2.6 109 2 3.2 243 7 3.2 135 2

2 476 1.6 263 8 2.0 327 13 2.4 202 5 3.2 267 9 3.3 140 2 4.0 309 12 4.1 173 4

06 3 573 1.7 284 10 2.1 354 15 2.6 218 6 3.4 289 10 3.6 152 3 4.3 334 14 4.4 187 4

6 752 1.9 319 12 2.4 398 19 2.9 245 7 3.9 324 13 4.1 171 4 4.9 375 17 5.0 210 5

3 594 2.0 324 13 2.4 403 20 3.0 249 8 3.9 329 13 4.1 174 4 4.9 379 18 5.0 214 6

08 6 881 2.3 383 18 2.9 477 28 3.5 295 11 4.6 389 19 4.9 206 5 5.8 448 25 6.0 252 8

7 979 2.5 401 20 3.0 499 30 3.7 308 12 4.9 407 20 5.2 216 6 6.1 469 27 6.3 265 9

TkW: Total heating capacity in kWkPa: Water pressure drops in kPal/h: Water flow in liters per hour

Un

itsiz

e

Air

flo

w(m

3/h

)

Sp

eed

3-r

ow

co

il4-r

ow

co

il1-r

ow

co

il

63

Water S

ystem

sH

FO-H

FR

Page 66: Train Instrument's

64PROD-PRC014-E4

Customer benefits• Silent operation: maximum acoustic comfort• Flexibility: customized system to fit the customer's exact

requirements• Easy commissioning: saving of time and money

Main features • Unit specially designed for hotel applications• Use of 1 mm thick galvanized steel• High performance water coil (aluminium fins/copper

tubes) for optimized capacity• Hot and/or chilled water coil• ½" water connections ISO R7 gas (screw connections)• Multi-speed motor with internal thermal protection for

higher flexibility• Use of plastic fan housings and large diameter wheels

for very low sound levels• Repositionable control panel with quick connector to

save space• Return air direct inlet• 40 Pa external static pressure for ducts and discharge air

grille• Low energy consumption

Options• 4-pipe water coil• Several electric heater capacities per unit size• Modulating and on/off 3-way/4-port or 2-way/2-port valve

for better control• Easily accessible and cleanable EU3 air filter• Right- or left-hand connections• Controls specially suited to hotel applications• Epoxy coating water coil for aggressive atmosphere• Fuse protection• Factory-wired fan speeds combination according to

customer requirements

Accessories• Wall fan switch L: 3-speed fan switch• Wall thermostat M: 3-speed switch + 1-stage stat +

manual changeover for the fan• Wall thermostat N: 3-speed switch + 1-stage stat +

manual changeover for the valve• Wall thermostat P: 3-speed switch + 2-stage stat for the

valve• Flexible connections• Auxiliary drain pan• Fresh air intake diameter 100 or 125 mm with fixed

controller 30 m3/h, 45m3/h, or adjustable controller60-130 m3/h

• 200 mm long straight duct and hotel-specific dischargeair grille

• Condensate pump

Control• Remote on/off controls on fan, valve and/or electric

heater• New factory-mounted LonMarkTM Trane ZN523 control,

providing enhanced acoustical and thermal comfort, andenergy saving solutions

• Full range of user interfaces (ZSM-10, ZSM-11) andwireless remote control (IRC)

• Trane ZN523 can be associated with Trane EXL-EXB forlight and sunblind control

• Factory-mounted BatiBUS control

Lodging applications1-5 kW

Chilled water terminals

Slim Line HFH

HFH

L P M/N

ZSM-10 ZSM-11 IRC

Page 67: Train Instrument's

General data HFH

PROD-PRC014-E4

Water S

ystem

sH

FH

65

Unit size 02 03 04

Speed at ESP = 0 Pa 1 3 5 1 3 5 1 3 5

Power supply (V/Ph/Hz) 230/1/50

Airflow (m3/h) 158 244 313 216 273 376 322 490 672

Cooling (1)

Total capacity (kW) 1.1 1.4 1.5 1.4 1.6 2.3 2.12 3.16 4.08

Sensible capacity (kW) 0.8 1.1 1.4 1.1 1.3 1.8 1.6 2.39 3.17

Water flow (l/h) 184 238 273 250 289 404 371 552 716

Water pressure drop (2) (kPa) 0.3 0.4 0.6 0.5 0.7 1 1 3 4

Water content (l) 1.1 1.5 2.0

Water connection type 1/2" ISO/R7 female gas 1/2" ISO/R7 female gas 1/2" ISO/R7 female gas

Heating (3)

Total capacity (kW) 0.8 0.9 1.0 1.2 1.3 1.5 1.7 2.0 2.3

Water flow (l/h) 64 75 83 99 108 122 143 166 189

Water pressure drop (2) (kPa) 0.5 0.7 0.8 1 1 2 2 3 4

Water content (l) 0.13 0.19 0.24

Water connection type 1/2" ISO/R7 female gas 1/2" ISO/R7 female gas 1/2" ISO/R7 female gas

Electric heater

Capacity (W) 500 - 750 - 1000 500 - 750 - 1000 - 1500 500 - 750 - 1000 - 1500 -

2000

Electric heater absorbed

current (4) (A) 2.3 - 3.3 - 4.6 2.3 - 3.3 - 4.6 - 6.6 2.3 - 3.3 - 4.6 - 6.6 - 8.7

Fan motor absorbed power (4) (W) 20 30 41 24 30 46 36 50 75

Maximum external static

pressure (Pa) 30 40 40 30 40 40 30 40 40

Sound power level (5) (dB(A)) 34 41 48 36 41 49 37 43 50

Sound pressure level (6) (dB(A)) 22 29 36 24 29 37 25 31 38

(1) 2-pipe, 4-row coil, air 27°C/19°C, water 7/12°C(2) For the coil only, without valve(3) 4-pipe, 1-row coil, air 20°C, water 70/60°C(4) For 230V/1Ph/50Hz(5) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor(6) Values calculated from sound power levels with a hypothetical acoustic attenuation of 12 dB

Page 68: Train Instrument's

6666PROD-PRC014-E4

Dimensions and weights

XY

Z

Dimensions (1) Operating Duct connection

(mm) Weight (2) dimensions

Unit size Y X Z (kg) (mm)

HFH 02 743 908 217 (3) 22 399 x 151HFH 03 943 908 217 (3) 27 599 x 151HFH 04 1143 908 217 (3) 32 799 x 151

(1) Including the standard control panel and the auxiliary drain pan (+128 mm)(2) Without water content, options, or accessories(3) 224 mm with auxiliary drain pan (accessory)

Page 69: Train Instrument's

Performance data HFH

PROD-PRC014-E4

Un

itsiz

e

Air

flo

w(m

3/h

)

Retu

rn a

irte

mp

era

ture

Water S

ystem

sH

FH

67

Cooling capacities - 3-row coil - 0PaConstant delta T°

Water temperature flow / return in °C

5/10 5.5/11 6/11 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22/15.4°C 0.7 0.6 129 1 0.7 0.6 108 0.4 0.7 0.6 116 0.4 0.6 0.6 104 0.3 0.5 0.5 92 0.3

24/17.1°C 0.9 0.7 158 1 0.8 0.7 133 1 0.8 0.6 143 1 0.7 0.6 129 1 0.7 0.6 116 0.4158

26/18.7°C 1.1 0.8 190 1 1.0 0.7 161 1 1.0 0.7 174 1 0.9 0.7 159 1 0.8 0.6 144 0.6

28/20.4°C 1.3 0.8 226 1 1.2 0.8 192 1 1.2 0.8 209 1 1.1 0.7 192 1 1.0 0.7 176 1

22/15.4°C 0.9 0.9 167 1 0.9 0.8 140 1 0.8 0.8 151 1 0.8 0.7 136 1 0.7 0.7 125 1

24/17.1°C 1.1 0.9 202 1 1.1 0.9 170 1 1.0 0.9 184 1 0.9 0.9 167 1 0.8 0.8 151 102 244

26/18.7°C 1.4 1.0 249 1 1.3 1.0 204 1 1.3 1.0 222 1 1.1 0.9 202 1 1.0 0.9 184 1

28/20.4°C 1.9 1.2 329 2 1.6 1.1 255 1 1.7 1.1 296 2 1.5 1.1 262 2 1.3 1.0 229 1

22/15.4°C 1.1 1.0 192 1 1.0 1.0 159 1 1.0 0.9 173 1 0.9 0.9 160 1 0.8 0.8 146 1

24/17.1°C 1.3 1.1 231 1 1.2 1.1 194 1 1.2 1.1 211 1 1.1 1.0 192 1 1.0 0.9 174 1313

26/18.7°C 1.8 1.3 311 2 1.4 1.2 234 1 1.6 1.2 275 2 1.3 1.1 239 1 1.2 1.1 211 1

28/20.4°C 2.3 1.5 403 3 2.0 1.4 318 2 2.1 1.4 364 2 1.8 1.3 325 2 1.6 1.2 286 2

22/15.4°C 1.0 0.8 168 1 0.9 0.8 140 1 0.9 0.8 151 1 0.8 0.7 135 1 0.7 0.6 118 0.4

24/17.1°C 1.2 0.9 207 1 1.1 0.9 173 1 1.1 0.8 187 1 1.0 0.8 168 1 0.8 0.8 151 1216

26/18.7°C 1.5 1.0 264 2 1.3 0.9 212 1 1.3 0.9 231 1 1.2 0.9 208 1 1.1 0.8 188 1

28/20.4°C 2.0 1.2 340 2 1.7 1.1 275 2 1.8 1.1 311 2 1.6 1.0 279 2 1.4 1.0 244 1

22/15.4°C 1.1 1.0 193 1 1.0 0.9 162 1 1.0 0.9 174 1 0.9 0.8 152 1 0.8 0.8 140 1

24/17.1°C 1.4 1.1 240 1 1.2 1.0 198 1 1.2 1.0 215 1 1.1 1.0 193 1 1.0 0.9 174 103 273

26/18.7°C 1.9 1.3 328 2 1.6 1.1 253 2 1.7 1.2 291 2 1.4 1.1 252 1 1.2 1.0 215 1

28/20.4°C 2.4 1.5 415 3 2.1 1.4 339 2 2.2 1.4 380 3 2.0 1.3 343 2 1.7 1.2 304 2

22/15.4°C 1.3 1.2 233 1 1.2 1.2 196 1 1.2 1.1 211 1 1.1 1.0 189 1 1.0 0.9 174 1

24/17.1°C 1.9 1.4 327 2 1.5 1.3 246 1 1.6 1.3 284 2 1.4 1.2 244 1 1.1 1.1 205 1376

26/18.7°C 2.5 1.7 430 3 2.1 1.5 341 2 2.2 1.6 385 3 1.9 1.4 339 2 1.7 1.3 294 2

28/20.4°C 3.1 1.9 537 5 2.8 1.8 443 4 2.8 1.8 493 4 2.5 1.7 447 4 2.3 1.6 398 3

22/15.4°C 1.3 1.1 234 1 1.2 1.1 195 1 1.2 1.1 210 1 1.1 1.0 188 1 0.9 0.9 166 1

24/17.1°C 1.9 1.4 330 2 1.6 1.2 251 2 1.6 1.3 287 2 1.4 1.2 244 1 1.2 1.1 209 1322

26/18.7°C 2.4 1.6 427 3 2.2 1.5 346 3 2.2 1.5 386 3 1.9 1.4 342 2 1.7 1.3 297 2

28/20.4°C 3.0 1.8 524 5 2.8 1.7 440 4 2.8 1.7 485 4 2.5 1.6 444 4 2.3 1.5 401 3

22/15.4°C 2.0 1.7 352 3 1.7 1.5 268 2 1.7 1.5 303 2 1.4 1.4 250 2 1.2 1.2 223 1

24/17.1°C 2.7 2.0 469 4 2.3 1.8 372 3 2.4 1.8 414 3 2.0 1.7 361 3 1.8 1.6 311 204 490

26/18.7°C 3.4 2.2 596 6 3.1 2.1 490 4 3.1 2.1 541 5 2.7 2.0 482 4 2.4 1.8 425 3

28/20.4°C 4.2 3.2 725 8 3.9 2.4 611 6 3.8 2.4 671 7 3.5 2.2 616 6 3.2 2.1 557 5

22/15.4°C 2.6 2.2 456 4 2.2 2.0 358 3 2.2 2.0 398 3 1.9 1.8 334 2 1.7 1.6 301 2

24/17.1°C 3.4 2.5 594 6 3.0 2.3 478 4 3.0 2.3 528 5 2.6 2.2 464 4 2.3 2.0 405 3672

26/18.7°C 4.3 2.8 748 8 3.9 2.7 617 6 3.9 2.7 679 7 3.5 2.5 608 6 3.0 2.3 538 5

28/20.4°C 5.2 3.2 907 11 4.8 3.0 766 9 4.8 3.0 839 10 4.4 2.8 769 9 4.0 2.7 696 8

TkW: Total cooling capacity in kW kPa: Water pressure drops in kPaSkW: Sensible cooling capacity in kW l/h: Water flow in liters per hour

Page 70: Train Instrument's

6868PROD-PRC014-E4

Performance data HFHR

etu

rn a

irte

mp

era

ture

Air

flo

w(m

3/h

)

Un

itsiz

e

Cooling capacities - 4-row coil - 0PaConstant delta T°

Water temperature flow / return in °C

5/10 5.5/11 6/11 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22/15.4°C 0.8 0.7 144 0.2 0.8 0.6 121 0.1 0.7 0.6 130 0.1 0.7 0.6 117 0.1 0.7 0.7 125 0.1

24/17.1°C 1.0 0.7 175 0.2 0.9 0.7 148 0.2 0.9 0.7 160 0.2 0.8 0.7 145 0.2 0.7 0.6 130 0.1158

26/18.7°C 1.2 0.8 210 0.4 1.1 0.8 178 0.3 1.1 0.8 193 0.3 1.0 0.7 176 0.3 0.9 0.7 160 0.2

28/20.4°C 1.4 0.9 247 1 1.3 0.9 211 0.4 1.3 0.9 230 0.4 1.2 0.8 212 0.4 1.1 0.8 194 0.3

22/15.4°C 1.1 0.9 188 0.3 1.0 0.9 158 0.2 1.0 0.9 171 0.2 0.9 0.8 154 0.2 0.9 0.8 154 0.2

24/17.1°C 1.3 1.0 226 0.4 1.2 1.0 190 0.3 1.2 1.0 206 0.3 1.1 0.9 188 0.3 1.0 0.9 171 0.202 244

26/18.7°C 1.5 1.1 269 1 1.4 1.1 227 0.4 1.4 1.1 247 1 1.3 1.0 226 0.4 1.2 1.0 207 0.3

28/20.4°C 1.8 1.2 321 1 1.7 1.2 268 1 1.7 1.2 293 1 1.5 1.1 270 1 1.4 1.1 248 1

22/15.4°C 1.2 1.1 217 0.4 1.1 1.1 181 0.3 1.1 1.1 197 0.3 1.0 1.0 182 0.3 1.0 1.0 178 0.3

24/17.1°C 1.5 1.3 259 1 1.4 1.2 218 0.4 1.3 1.2 237 0.4 1.2 1.2 217 0.4 1.1 1.1 198 0.3313

26/18.7°C 1.7 1.4 306 1 1.6 1.3 259 0.5 1.6 1.3 282 1 1.5 1.3 259 1 1.3 1.2 237 0.4

28/20.4°C 2.4 1.6 413 1 1.9 1.4 304 1 2.1 1.5 368 1 1.8 1.4 322 1 1.6 1.3 283 1

22/15.4°C 1.1 0.9 196 0.3 1.0 0.9 164 0.2 1.0 0.9 177 0.3 0.9 0.8 159 0.2 0.8 0.8 142 0.2

24/17.1°C 1.4 1.0 239 1 1.3 1.0 201 0.3 1.2 1.0 217 0.4 1.1 0.9 196 0.3 1.0 0.9 177 0.3216

26/18.7°C 1.6 1.1 286 1 1.5 1.1 243 1 1.5 1.1 263 1 1.4 1.0 240 1 1.2 1.0 218 0.4

28/20.4°C 2.1 1.3 360 1 1.8 1.2 289 1 1.9 1.2 324 1 1.7 1.1 290 1 1.5 1.1 265 1

22/15.4°C 1.3 1.1 227 0.4 1.2 1.1 190 0.3 1.2 1.1 205 0.4 1.0 1.0 185 0.3 0.9 0.9 166 0.2

24/17.1°C 1.6 1.2 275 1 1.4 1.2 231 0.5 1.4 1.2 250 0.5 1.3 1.1 227 0.4 1.2 1.1 205 0.403 273

26/18.7°C 2.0 1.4 347 1 1.7 1.3 278 1 1.7 1.4 302 1 1.6 1.2 276 1 1.4 1.2 251 0.5

28/20.4°C 2.6 1.6 455 2 2.3 1.5 358 1 2.4 1.5 413 1 2.1 1.4 369 1 1.8 1.3 322 1

22/15.4°C 1.6 1.4 275 1 1.4 1.4 231 0.5 1.4 1.4 250 0.5 1.3 1.2 226 0.4 1.2 1.1 208 0.4

24/17.1°C 2.0 1.6 354 1 1.7 1.5 278 1 1.7 1.5 302 1 1.6 1.4 275 1 1.4 1.4 250 0.5376

26/18.7°C 2.8 1.9 483 2 2.3 1.7 369 1 2.4 1.8 429 2 2.1 1.7 375 1 1.8 1.5 321 1

28/20.4°C 3.5 2.2 611 3 3.1 2.0 495 2 3.2 2.1 559 3 2.9 1.9 505 2 2.6 1.8 449 2

22/15.4°C 1.5 1.3 262 1 1.4 1.2 219 0.4 1.3 1.2 236 1 1.2 1.2 212 0.4 1.1 1.0 189 0.3

24/17.1°C 1.9 1.4 327 1 1.7 1.4 268 1 1.6 1.3 290 1 1.5 1.3 262 1 1.3 1.2 236 0.5322

26/18.7°C 2.6 1.7 447 2 2.2 1.5 345 1 2.3 1.6 399 1 2.0 1.5 347 1 1.7 1.3 293 1

28/20.4°C 3.2 2.0 563 3 2.9 1.8 462 2 3.0 1.9 518 2 2.7 1.7 470 2 2.4 1.6 419 2

22/15.4°C 2.1 1.8 363 1 1.7 1.7 274 1 1.7 1.6 297 1 1.5 1.5 274 1 1.4 1.4 252 1

24/17.1°C 2.9 2.2 505 2 2.4 2.0 384 1 2.5 2.0 442 2 2.2 1.9 380 1 1.8 1.8 322 104 490

26/18.7°C 3.7 2.5 653 4 3.3 2.3 526 2 3.4 2.4 589 3 3.0 2.2 524 2 2.6 2.1 458 2

28/20.4°C 4.6 2.9 807 6 4.2 2.7 670 4 4.3 2.7 743 5 3.9 2.5 678 4 3.5 2.4 610 3

22/15.4°C 2.8 2.5 499 2 2.2 2.2 360 1 2.4 2.4 433 2 2.1 2.0 369 1 1.8 1.8 325 1

24/17.1°C 3.8 2.9 662 4 3.3 2.7 522 2 3.3 2.7 587 3 2.9 2.6 514 2 2.5 2.4 446 2672

26/18.7°C 4.8 3.3 840 6 4.3 3.1 685 4 4.3 3.1 761 5 3.9 2.9 681 4 3.4 2.8 602 3

28/20.4°C 5.9 3.7 1030 9 5.4 3.5 859 6 5.4 3.5 949 8 5.0 3.3 867 6 4.5 3.1 783 5

TkW: Total cooling capacity in kW kPa: Water pressure drops in kPaSkW: Sensible cooling capacity in kW l/h: Water flow in liters per hour

Page 71: Train Instrument's

Performance data HFH

PROD-PRC014-E4

Un

itsiz

e

Air

flo

w(m

3/h

)

Sp

eed

Water S

ystem

sH

FH

69

Heating capacities - 0Pa - Constant delta T° - Air temperature = 20°C

3-r

ow

co

il4-r

ow

co

il1-r

ow

co

il

Water temperature flow / return in °C

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa

1 158 1.0 177 1 1.3 221 1 1.6 138 1 2.1 182 1 2.3 98 0.3 2.7 209 1 2.8 121 0.4

02 3 244 1.5 257 1 1.9 320 2 2.3 200 1 3.1 263 2 3.3 141 1 3.9 303 2 4.1 174 1

5 313 1.9 316 2 2.3 392 3 2.9 245 1 3.8 322 2 4.1 173 1 4.8 371 3 5.0 213 1

1 216 1.5 253 1 1.8 311 2 2.3 198 1 3.0 257 2 3.3 142 1 3.8 293 2 4.0 172 1

03 3 273 1.8 310 2 2.2 381 3 2.8 243 1 3.7 314 2 4.1 174 1 4.6 359 3 4.9 211 1

5 376 2.4 408 3 2.9 501 4 3.7 318 2 4.8 412 3 5.3 228 1 6.1 471 4 6.5 276 2

1 322 2.2 376 3 2.7 460 4 3.5 295 2 4.4 379 3 5 213 1 5.6 432 3 6.0 256 2

04 3 490 3.2 538 5 3.9 659 7 4.9 422 3 6.3 543 5 7.1 303 2 8.0 619 6 8.5 364 3

5 672 4.1 695 7 5.0 852 10 6.4 543 5 8.2 701 7 9.1 389 3 10.3 801 9 11.0 469 4

1 158 1.1 190 0.3 1.4 238 0.4 1.7 147 0.2 2.3 197 0.3 2.4 103 0.1 2.9 227 0.4 3.0 130 0.1

02 3 244 1.7 280 1 2.1 351 1 2.6 218 0.4 3.4 289 1 3.6 153 0.2 4.3 334 1 4.5 191 0.3

5 313 2.1 348 1 2.6 434 2 3.2 270 1 4.2 358 1 4.4 189 0.3 5.3 413 1 5.5 236 0.4

1 216 1.6 267 1 1.9 330 1 2.4 209 0.4 3.2 273 1 3.5 149 0.2 4.0 312 1 4.3 183 0.3

03 3 273 1.9 330 1 2.4 407 1 3.0 258 1 3.9 336 1 4.3 184 0.3 4.9 384 1 5.3 225 0.4

5 376 2.6 437 2 3.2 539 2 4.0 342 1 5.2 445 2 5.7 244 0.5 6.5 509 2 7.0 297 1

1 322 2.4 407 1 2.9 498 2 3.7 320 1 4.8 412 1 5.4 231 0.5 6.0 469 2 6.5 278 1

04 3 490 3.5 592 3 4.2 724 4 5.4 464 2 7.0 598 3 7.8 335 1 8.8 682 4 9.4 402 1

5 672 4.6 773 5 5.6 948 7 7.1 605 3 9 781 5 10.2 435 2 11.5 892 7 12.3 524 2

1 158 0.4 59 0.4 0.5 78 1 0.5 44 0.2 0.8 64 0.5 0.7 29 0.1 1.0 76 1 0.9 39 0.2

02 3 244 0.4 70 1 0.6 92 1 0.6 53 0.3 0.9 75 1 0.8 34 0.1 1.2 89 1 1.1 47 0.3

5 313 0.5 78 1 0.6 102 1 0.7 59 0.4 1.0 83 1 0.9 38 0.2 1.3 98 1 1.2 52 0.3

1 216 0.6 96 1 0.7 122 2 0.9 73 1 1.2 99 1 1.2 50 0.3 1.5 116 2 1.5 63 0.5

03 3 273 0.6 104 1 0.8 133 2 1.0 80 1 1.3 108 1 1.3 54 0.4 1.6 126 2 1.6 69 1

5 376 0.7 118 2 0.9 150 3 1.1 90 1 1.5 122 2 1.5 62 0.5 1.9 142 2 1.9 78 1

1 322 0.8 140 2 1.0 175 3 1.3 107 1 1.7 143 2 1.8 74 1 2.1 165 3 2.2 92 1

04 3 490 1.0 163 3 1.2 204 4 1.5 125 2 2.0 166 3 2.1 87 1 2.5 193 4 2.6 108 1

5 672 1.1 185 3 1.4 232 5 1.7 142 2 2.3 189 4 2.4 99 1 2.9 219 5 2.9 122 2

TkW: Total heating capacity in kWkPa: Water pressure drops in kPal/h: Water flow in liters per hour

Page 72: Train Instrument's

70PROD-PRC014-E4

Customer benefits• Flexibility: customized system to fit the customer's exact

requirements• Single source cooling: low operating and maintenance

costs per kW• Wide product range: one supplier for various customer

applications

Main features• 3-speed direct drive centrifugal fan motor• Installation flexibility - easy installation of accessories• Air intake behind or underneath the unit• Galvanized steel structure• Aluminium fin copper tubes heat exchanger• Removable external electric panel• Self-contained condensate tray to avoid leakage• High external static pressure for ductwork

Accessories• Electric heater (additional casing)• Hot water coil (additional casing)• Circular duct adapter plenum• EU2 filter box• EU4 filter box• On/off 3-way/4-port valves• Automatic changeover for cold water and hot water

application• Centrifugal condensate pump• Diffusers (see page 92)

Control• Wall thermostat M: 3-speed switch + 1-stage stat +

manual changeover for the fan• Wall thermostat N: 3-speed switch + 1-stage stat +

manual changeover for the valve• Wall thermostat P: 3-speed switch + 2-stage stat for the

valve• New factory-mounted LonMarkTM Trane ZN523 control,

providing enhanced acoustical and thermal comfort, andenergy saving solutions (on request)

• Full range of user interfaces (ZSM-10, ZSM-11) andwireless remote control (IRC)

• Trane ZN523 can be associated with Trane EXL-EXB forlight and sunblind control

Large space applications4-30 kW

Chilled water terminals

FWDFWD

P M/N

ZSM-10 ZSM-11 IRC

Page 73: Train Instrument's

General data

PROD-PRC014-E4

Unit size 08 12 20 30 45

Speed at ESP = 0 Pa

Airflow (m3/h) 490 820 980 980 1650 1970 1400 2300 2600 1800 3000 3600 2700 4500 5400

Power supply (V/Ph/Hz) 230/1/50

Cooling (2-pipe)

Total capacity (1) (kW) 3.5 5.2 5.8 5.5 8.2 9.1 9.8 13.9 15.1 12.4 18.1 20.3 18.9 27.6 30.7

Sensible capacity (kW) 2.6 4.0 4.6 4.4 6.8 7.7 7.2 10.8 11.8 9.1 13.9 16.0 13.9 21.3 24.2

Water flow (l/h) 617 915 1043 979 1462 1646 1743 2495 2706 2244 3263 3677 3388 4919 5542

Water pressure drop (kPa) 11 22 28 14 30 38 31 62 72 17 33 41 22 42 51

Heating (2-pipe)

Total capacity (2) (kW) 7.6 11.8 13.8 13.7 20.8 23.9 21.3 32.3 35.7 27.6 42.5 49.1 41.3 63.4 73.7

Water flow (l/h) 645 1009 1168 1167 1773 2025 1805 2745 3027 2329 3591 4152 3495 5392 6235

Water pressure drop (kPa) 12 27 35 20 44 56 34 74 89 18 39 51 23 49 62

Water content (l) 1.6 2.5 3.6 4.9 7.9

Water connection type

Electric heater kit

Power supply (V/Ph/Hz) 230/1/50 230/1/50 - 400/3/50 400/3/50 400/3/50

400/3/50

Capacity (kW) 4 8 10 12 12

Absorbed current (A) 17.4 34.8 - 20 25 30 30

Fan motor power (W) 92 144 230 195 300 460 370 570 650 600 880 1040 800 1000 1510

Fan motor absorbed current (A) 0.5 0.7 1.1 0.9 1.3 2.2 1.7 2.6 3.1 2.7 4.0 4.7 3.6 4.2 6.8

Maximum external static pressure (Pa) 45 95 120 40 160 210 95 190 200 180 270 340 270 280 300

Sound power level (dB(A)) 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68

Sound pressure level (3) (dB(A)) 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58

Length X (4) (mm) 890 1090 1290 1290 1290

Depth Y (4) (mm) 600 710 820 970 1090

Height Z (4) (mm) 250 300 350 450 650

Operating weight (5) (kg) 32 46 61 76 118

(mm) 5 x ø 160 5 x ø 200 5 x ø 250 5 x ø 315 3 x ø 315 + 2 x ø 400

(1) Air temperature : 27°C/19°C, water temperature 7/12°C(2) 2-pipe system, air temperature : 20°C, water temperature: 70/60°C(3) 2.5 m from the unit at the maximum airflow and 0 Pa static pressure(4) Without options or accessories(5) Without water content(6) Accessory

Lo

w

Med

Hig

h

Lo

w

Med

Hig

h

Lo

w

Med

Hig

h

Lo

w

Med

Hig

h

Lo

w

Med

Hig

h

XZ

Y Water S

ystem

sFW

D

71

¾" ISO R7

female gas

¾" ISO R7

female gas

Circular duct adapter

plenum diameter (6)

¾" ISO R7

female gas

¾" ISO R7

female gas

¾" ISO R7

female gas

Page 74: Train Instrument's

7272PROD-PRC014-E4

Performance data FWD

Un

it s

ize

Sp

eed

Air

tem

pe-

ratu

re

Water temperature flow / return in °C

5/10 5.5/11 6/10 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22°C/15.4°C - - - - - - - - - - - - - - - - - - - -LOW 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C 3.2 2.6 568 10 2.7 2.4 450 6 2.3 2.2 350 4 2.4 2.2 433 6 2.0 1.9 370 4

08 MEDIUM 24°C/17.1°C 4.2 3.0 740 15 3.7 2.8 604 11 3.3 2.6 488 7 3.3 2.6 587 10 2.8 2.4 514 8646 m3/h 26°C/18.7°C 5.2 3.4 913 22 4.8 3.2 763 16 4.3 3.0 635 12 4.3 3.0 756 16 3.8 2.8 675 13

28°C/20.4°C 6.3 3.8 1103 31 5.9 3.6 938 23 5.4 3.4 796 18 5.4 3.4 944 24 4.9 3.2 861 2022°C/15.4°C 3.2 2.6 581 10 3.1 2.7 513 8 2.6 2.4 406 5 2.6 2.4 494 7 2.2 2.0 425 6

HIGH 24°C/17.1°C 4.6 3.3 829 19 4.1 3.1 680 13 3.6 2.9 553 9 3.6 2.9 661 13 3.2 2.7 581 10665 m3/h 26°C/18.7°C 5.7 3.8 1021 27 5.2 3.5 854 20 4.7 3.3 712 14 4.7 3.3 845 19 4.2 3.1 757 16

28°C/20.4°C 7.0 4.2 1232 38 6.5 4.0 1047 29 6.0 3.8 889 21 5.9 3.8 1053 29 5.4 3.6 961 2422°C/15.4°C - - - - - - - - - - - - - - - - - - - -

LOW 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C 4.5 4.1 828 11 3.4 3.1 585 6 3.2 2.9 495 4 3.2 2.9 608 6 2.8 2.5 530 5

12 MEDIUM 24°C/17.1°C 6.4 4.9 1142 19 5.4 4.5 883 12 4.2 3.9 649 7 4.8 4.2 871 12 4.1 3.8 749 91275 m3/h 26°C/18.7°C 8.2 5.8 1462 30 7.3 5.5 1181 20 6.2 4.8 935 13 6.5 4.9 1174 20 5.7 4.6 1032 16

28°C/20.4°C 10.3 6.3 1810 45 9.3 6.0 1504 32 8.4 5.6 1239 22 8.5 5.7 1516 33 7.6 5.6 1364 2722°C/15.4°C 6.3 5.8 1166 20 5.2 4.7 883 12 4.3 3.8 687 7 4.8 4.3 903 12 4.2 3.7 798 10

HIGH 24°C/17.1°C 8.5 6.7 1530 33 7.4 6.2 1223 22 6.3 5.8 963 14 6.6 5.9 1205 21 5.7 5.2 1060 171917 m3/h 26°C/18.7°C 10.7 7.6 1920 51 9.6 7.1 1571 35 8.5 6.7 1276 24 8.6 6.8 1560 34 7.6 6.4 1388 28

28°C/20.4°C 13.3 8.5 2355 74 12.1 8.1 1965 53 11.0 7.6 1633 37 11.0 7.6 1975 53 9.9 7.2 1784 4422°C/15.4°C 7.6 6.0 1369 20 6.7 5.6 1098 13 5.7 5.2 868 8 5.7 5.2 1050 12 4.8 4.4 888 9

LOW 24°C/17.1°C 9.9 6.9 1765 32 9.0 6.5 1456 22 8.0 6.1 1190 15 7.8 5.9 1399 20 6.9 5.6 1240 171495 m3/h 26°C/18.7°C 12.2 7.9 2164 47 11.3 7.5 1821 34 10.3 7.0 1528 25 10.1 7.0 1802 33 9.0 6.5 1617 27

28°C/20.4°C 14.8 8.8 2598 67 13.9 8.4 2221 50 12.9 8.1 1898 37 12.7 8.0 2234 50 11.6 7.5 2042 4222°C/15.4°C 10.0 8.1 1809 34 8.9 7.7 1474 23 7.8 7.2 1197 16 7.7 7.1 1417 21 6.7 6.1 1247 17

20 MEDIUM 24°C/17.1°C 12.8 9.5 2301 53 11.7 9.0 1907 37 10.5 8.5 1577 26 10.2 8.2 1854 35 9.0 7.7 1642 282156 m3/h 26°C/18.7°C 15.8 10.4 2805 77 14.6 9.9 2362 56 13.3 9.4 1989 40 13.0 9.5 2335 54 11.7 8.7 2101 45

28°C/20.4°C 19.1 11.6 3368 109 17.8 11.1 2869 80 16.6 10.6 2451 60 16.2 10.4 2880 81 14.8 9.9 2632 6822°C/15.4°C 11.7 9.8 2122 46 10.5 9.3 1741 31 9.3 8.7 1428 22 9.1 8.5 1680 29 8.0 7.4 1490 23

HIGH 24°C/17.1°C 14.9 11.1 2673 70 13.6 10.5 2224 50 12.3 10.0 1849 35 12.0 9.8 2166 47 10.6 9.3 1928 382714 m3/h 26°C/18.7°C 18.3 12.4 3252 102 16.9 11.8 2739 74 15.5 11.3 2310 53 15.1 11.1 2707 72 13.6 10.5 2439 59

28°C/20.4°C 22.1 13.8 3909 144 20.6 13.1 3321 106 19.2 12.6 2835 78 18.8 12.4 3332 106 17.1 11.8 3041 9022°C/15.4°C 11.4 9.2 2065 14 10.1 8.6 1664 10 8.7 8.0 1328 7 8.7 8.0 1596 9 7.6 6.9 1408 8

LOW 24°C/17.1°C 15.0 10.6 2687 23 13.4 9.9 2188 16 11.9 9.3 1794 11 11.8 9.3 2126 15 10.3 8.6 1872 122360 m3/h 26°C/18.7°C 18.3 12.1 3248 33 16.9 11.5 2732 24 15.4 10.7 2292 17 15.1 10.9 2693 23 13.5 9.9 2426 19

28°C/20.4°C 22.2 13.4 3904 45 20.8 12.9 3330 34 19.3 12.3 2841 26 18.9 12.1 3348 34 17.2 11.5 3059 2922°C/15.4°C 13.7 11.3 2507 20 12.2 10.7 2042 14 10.7 9.8 1658 10 10.6 9.7 1967 13 9.2 8.3 1735 11

30 MEDIUM 24°C/17.1°C 17.7 12.9 3187 32 16.0 12.5 2639 22 14.4 11.5 2181 16 14.1 11.4 2569 21 12.4 10.7 2276 173069 m3/h 26°C/18.7°C 21.8 14.5 3886 45 20.1 13.8 3271 33 18.4 13.1 2750 24 18.0 13.3 3232 32 16.1 12.2 2907 27

28°C/20.4°C 26.3 16.1 4670 63 24.6 15.4 3975 47 22.8 14.7 3391 35 22.4 14.5 3988 47 20.3 13.7 3643 4022°C/15.4°C 16.9 14.4 3071 30 15.1 13.7 2526 21 13.5 12.5 2078 15 13.2 12.2 2446 20 11.7 10.7 2179 16

HIGH 24°C/17.1°C 21.5 16.2 3857 44 19.5 15.4 3209 32 17.6 14.6 2671 23 17.2 14.4 3132 31 15.2 13.7 2794 254143 m3/h 26°C/18.7°C 26.3 18.1 4690 63 24.2 17.3 3943 46 22.2 16.5 3325 34 21.7 16.3 3900 45 19.5 15.4 3518 38

28°C/20.4°C 31.8 20.1 5639 88 29.6 19.2 4783 66 27.4 18.3 4072 49 26.9 18.1 4797 66 24.5 17.2 4379 5622°C/15.4°C 19.2 15.6 3425 23 17.1 14.7 2785 16 14.9 13.8 2251 11 14.8 13.7 2673 15 12.9 12.1 2346 12

LOW 24°C/17.1°C 24.7 18.1 4368 34 22.4 17.1 3618 25 20.1 15.8 2987 18 19.7 15.6 3516 24 17.3 14.7 3107 193999 m3/h 26°C/18.7°C 30.3 20.3 5331 48 28.0 19.3 4490 36 25.6 18.4 3777 27 25.1 18.2 4438 35 22.4 16.7 3991 29

28°C/20.4°C 36.5 22.1 6398 66 34.2 21.2 5458 50 31.8 20.2 4663 38 31.1 20.3 5481 51 28.4 19.3 5010 4422°C/15.4°C 22.3 18.5 4000 30 20.0 17.5 3275 21 17.7 16.6 2678 15 17.4 16.4 3155 20 15.3 14.3 2791 16

45 MEDIUM 24°C/17.1°C 28.5 20.9 5058 44 26.0 19.9 4202 32 23.4 18.8 3489 23 22.8 18.6 4091 31 20.2 17.5 3634 254976 m3/h 26°C/18.7°C 34.9 23.5 6157 62 32.3 22.4 5188 46 29.6 21.3 4372 34 28.9 21.0 5126 45 25.9 19.8 4617 38

28°C/20.4°C 42.1 26.0 7397 85 39.4 24.9 6294 64 36.6 23.8 5374 49 35.8 23.5 6314 65 32.6 22.3 5767 5522°C/15.4°C 25.1 21.3 4563 37 22.6 20.2 3754 27 20.1 18.6 3093 19 19.7 18.2 3634 25 17.3 15.8 3234 21

HIGH (2) 24°C/17.1°C 31.9 24.0 5728 55 29.1 22.8 4770 40 26.3 21.6 3975 29 25.6 21.3 4651 38 22.7 20.2 4150 326000 m3/h 26°C/18.7°C 39.1 26.8 6959 76 36.1 25.6 5858 57 33.1 24.4 4944 43 32.3 24.0 5792 56 28.9 22.7 5224 47

28°C/20.4°C 47.3 29.7 8365 105 44.0 28.4 7102 79 40.8 27.1 6053 60 40.0 26.8 7123 80 36.4 25.4 6503 68

(1) Unable to reach 50Pa TkW: Total cooling capacity in kW SkW: Sensible cooling capacity in kW(2) Unit operation high limit l/h: Water flow in liters per hour kPa: Water pressure drops through the coil

Cooling Capacities - Basic unit + EU2 filter box (clean filter) - ESP 50PaConstant delta T°

2-pipe / 4-pipe

Page 75: Train Instrument's

Performance data FWD

PROD-PRC014-E4

Un

it s

ize

Sp

eed

Air

tem

pe-

ratu

re

Water temperature flow / return in °C

Cooling Capacities - Basic unit + EU2 filter box (clean filter) - ESP 100PaConstant delta T°

2-pipe / 4-pipe

Water S

ystem

s

73

FWD

73

5/10 5.5/11 6/10 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22°C/15.4°C - - - - - - - - - - - - - - - - - - - -LOW 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C - - - - - - - - - - - - - - - - - - - -

08 MEDIUM 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C 2.4 1.9 459 7 2.1 1.8 356 4 1.7 1.5 274 3 1.8 1.6 343 4 1.5 1.3 294 3

HIGH 24°C/17.1°C 3.3 2.3 607 11 2.9 2.1 492 7 2.5 1.9 391 5 2.6 2.0 478 7 2.2 1.8 415 5506 m3/h 26°C/18.7°C 4.2 2.6 754 16 3.8 2.5 629 12 3.4 2.3 520 8 3.4 2.3 623 11 3.0 2.1 555 9

28°C/20.4°C 5.1 2.9 912 22 4.7 2.8 776 17 4.4 2.6 658 12 4.3 2.6 782 17 3.9 2.5 714 1422°C/15.4°C - - - - - - - - - - - - - - - - - - - -

LOW 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C 4.0 3.7 735 8 3.2 2.9 542 5 2.9 2.6 464 4 2.9 2.6 542 5 2.6 2.3 495 4

12 MEDIUM 24°C/17.1°C 5.7 4.4 1038 16 4.8 4.0 789 10 3.6 3.3 560 5 4.3 3.8 781 9 3.6 3.3 665 71134 m3/h 26°C/18.7°C 7.5 5.1 1340 26 6.6 4.7 1077 17 5.6 4.3 841 11 5.9 4.4 1071 17 5.2 4.1 937 13

28°C/20.4°C 9.4 5.8 1665 39 8.6 5.6 1381 27 7.6 5.0 1132 19 7.7 5.1 1374 28 7.0 4.8 1252 2322°C/15.4°C 5.6 5.1 1040 16 4.5 4.0 772 9 3.6 3.1 577 5 4.1 3.6 790 10 3.6 3.1 695 8

HIGH 24°C/17.1°C 7.6 5.9 1385 28 6.6 5.5 1097 18 5.5 5.0 849 11 5.8 5.2 1080 17 5.0 4.5 943 141656 m3/h 26°C/18.7°C 9.7 6.8 1748 43 8.7 6.3 1425 29 7.6 5.9 1149 19 7.8 6.0 1415 29 6.8 5.6 1254 23

28°C/20.4°C 12.1 7.6 2152 63 11.0 7.2 1793 45 9.9 6.8 1486 31 10.0 6.8 1803 45 9.0 6.4 1627 3722°C/15.4°C - - - - - - - - - - - - - - - - - - - -

LOW 24°C/17.1°C - - - - - - - - - - - - - - - - - - - -(1) 26°C/18.7°C - - - - - - - - - - - - - - - - - - - -

28°C/20.4°C - - - - - - - - - - - - - - - - - - - -22°C/15.4°C 9.1 7.3 1654 29 8.0 6.8 1342 19 7.0 6.4 1082 13 6.9 6.3 1287 18 6.0 5.4 1128 14

20 MEDIUM 24°C/17.1°C 11.7 8.5 2112 45 10.6 7.9 1749 32 9.5 7.4 1442 22 9.3 7.3 1699 30 8.2 6.9 1500 241908 m3/h 26°C/18.7°C 14.5 9.6 2580 66 13.4 9.1 2173 48 12.2 8.7 1828 34 11.9 8.6 2149 47 10.7 7.9 1931 38

28°C/20.4°C 17.5 10.6 3098 93 16.4 10.2 2644 69 15.2 9.7 2258 51 14.9 9.6 2655 69 13.6 9.1 2428 5922°C/15.4°C 10.9 9.0 1974 40 9.7 8.5 1615 27 8.6 8.0 1319 19 8.4 7.8 1555 25 7.4 6.8 1375 20

HIGH 24°C/17.1°C 13.9 10.2 2498 62 12.7 9.6 2075 44 11.4 9.1 1721 31 11.1 9.0 2019 41 9.8 8.5 1792 332441 m3/h 26°C/18.7°C 17.1 11.4 3041 90 15.8 10.9 2562 65 14.4 10.3 2159 47 14.1 10.2 2532 63 12.6 9.6 2280 52

28°C/20.4°C 20.6 12.7 3652 126 19.3 12.1 3107 93 17.9 11.6 2653 69 17.5 11.4 3118 94 15.9 10.8 2848 7922°C/15.4°C 10.3 8.2 1876 12 9.0 7.7 1502 8 7.7 7.1 1185 5 7.8 7.1 1439 8 6.7 6.1 1250 6

LOW 24°C/17.1°C 13.5 9.5 2423 19 12.2 8.9 1995 14 10.8 8.3 1627 9 10.7 8.4 1936 13 9.3 7.7 1699 102090 m3/h 26°C/18.7°C 16.7 10.9 2973 28 15.4 10.2 2498 20 14.0 9.6 2093 15 13.8 9.5 2473 20 12.3 8.9 2217 16

28°C/20.4°C 20.2 12.1 3575 39 19.0 11.6 3053 29 17.6 11.0 2603 22 17.3 10.9 3071 30 15.7 10.6 2805 2622°C/15.4°C 12.8 10.4 2348 18 11.3 9.8 1906 12 9.9 9.0 1539 9 9.8 8.9 1833 12 8.5 7.6 1611 9

30 MEDIUM 24°C/17.1°C 16.6 12.2 2993 28 15.0 11.5 2478 20 13.4 10.6 2042 14 13.2 10.5 2410 19 11.5 9.8 2130 152801 m3/h 26°C/18.7°C 20.4 13.4 3657 40 18.8 13.0 3078 30 17.2 12.4 2585 22 16.8 12.2 3041 29 15.1 11.2 2735 24

28°C/20.4°C 24.7 15.0 4395 56 23.1 14.3 3743 42 21.5 13.6 3193 32 21.0 13.4 3759 42 19.1 13.0 3434 3622°C/15.4°C 15.8 13.3 2887 26 14.1 12.6 2367 18 12.5 11.5 1939 13 12.3 11.3 2287 17 10.8 9.8 2031 14

HIGH 24°C/17.1°C 20.2 15.0 3639 40 18.3 14.3 3023 29 16.5 13.5 2510 21 16.1 13.4 2946 27 14.2 12.6 2623 223768 m3/h 26°C/18.7°C 24.8 16.8 4427 57 22.8 16.0 3723 42 20.9 15.3 3137 31 20.4 15.1 3682 41 18.3 14.2 3318 34

28°C/20.4°C 30.0 18.7 5322 79 27.9 17.9 4517 59 25.9 17.0 3850 44 25.4 16.8 4533 60 23.1 16.0 4138 5122°C/15.4°C 18.4 14.9 3296 21 16.3 14.0 2673 15 14.3 13.1 2156 10 14.1 13.0 2564 14 12.3 11.5 2248 11

LOW 24°C/17.1°C 23.7 17.3 4211 32 21.6 16.0 3486 23 19.3 15.1 2873 17 18.9 14.9 3386 22 16.6 14.0 2989 183798 m3/h 26°C/18.7°C 29.2 19.4 5142 45 27.0 18.5 4331 34 24.7 17.6 3643 25 24.2 17.4 4284 33 21.6 16.0 3850 28

28°C/20.4°C 35.2 21.5 6173 62 33.0 20.6 5269 47 30.7 19.7 4502 36 30.0 19.4 5292 48 27.4 18.4 4838 4122°C/15.4°C 21.5 17.7 3859 28 19.2 16.8 3152 20 17.0 15.8 2573 14 16.7 15.7 3037 18 14.6 13.6 2680 15

45 MEDIUM 24°C/17.1°C 27.5 20.1 4888 42 25.0 19.1 4059 30 22.5 18.0 3364 22 22.0 17.8 3950 29 19.4 16.7 3502 244724 m3/h 26°C/18.7°C 33.7 22.5 5953 58 31.1 21.5 5015 44 28.6 20.4 4227 33 27.9 20.1 4958 43 25.0 19.0 4463 36

28°C/20.4°C 40.7 25.0 7152 80 38.0 23.9 6087 61 35.4 22.8 5199 46 34.6 22.5 6110 61 31.5 21.3 5580 5222°C/15.4°C 25.1 21.3 4563 37 22.6 20.2 3754 27 20.1 18.6 3093 19 19.7 18.2 3634 25 17.3 15.8 3234 21

HIGH (2) 24°C/17.1°C 31.9 24.0 5728 55 29.1 22.8 4770 40 26.3 21.6 3975 29 25.6 21.3 4651 38 22.7 20.2 4150 326000 m3/h 26°C/18.7°C 39.1 26.8 6959 76 36.1 25.6 5858 57 33.1 24.4 4944 43 32.3 24.0 5792 56 28.9 22.7 5224 47

28°C/20.4°C 47.3 29.7 8365 105 44.0 28.4 7102 79 40.8 27.1 6053 60 40.0 26.8 7123 80 36.4 25.4 6503 68

(1) Unable to reach 100Pa TkW: Total cooling capacity in kW SkW: Sensible cooling capacity in kW(2) Unit operation high limit l/h: Water flow in liters per hour kPa: Water pressure drops through the coil

Page 76: Train Instrument's

PROD-PRC014-E4

Performance data FWD

Un

it s

ize

Sp

eed

Air

flo

w

(m3/h

)

Water temperature flow / return in °C

Heating Capacities - Basic unit + EU2 filter box (clean filter) - ESP 50Pa -Return Air Temperature 20°C - Constant delta T°

BA

SIC

UN

ITH

OT

WA

TE

R C

OIL

KIT

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa2-pipe coil

LOW (1) - - - - - - - - - - - - - - - - - - - - -08 MEDIUM 716 5.1 860 20 6.2 1048 29 7.9 676 13 10.1 865 20 11.5 490 7 12.7 984 26 13.7 585 10

HIGH 841 5.9 985 26 7.2 1202 36 9.2 774 17 11.7 991 26 13.2 559 9 14.6 1129 33 15.8 669 13LOW (1) - - - - - - - - - - - - - - - - - - - - -

12 MEDIUM 1337 8.7 1442 30 10.5 1769 43 13.4 1128 19 17.2 1456 30 19.1 809 10 21.6 1663 39 23.0 975 14HIGH 2031 12.0 1994 54 14.7 2453 80 18.5 1554 34 23.9 2015 55 26.3 1109 18 30.0 2308 71 31.7 1342 26LOW 1583 11.5 1919 38 13.9 2335 54 17.9 1510 24 22.8 1928 38 25.9 1096 13 28.4 2191 48 30.8 1307 18

20 MEDIUM 2291 15.8 2621 68 19.1 3200 99 24.5 2058 43 31.2 2637 69 35.1 1486 23 39.0 3003 87 42.0 1779 33HIGH 2865 18.9 3141 95 22.9 3841 139 29.2 2462 60 37.4 3162 96 41.9 1772 32 46.8 3604 123 50.2 2126 46LOW 2503 17.7 2959 28 21.5 3609 39 27.6 2326 18 35.2 2975 28 39.7 1684 10 43.9 3386 35 47.5 2013 14

30 MEDIUM 3240 22.1 3668 41 26.9 4479 58 34.3 2878 26 43.7 3691 41 49.1 2075 15 54.7 4204 52 58.8 2487 20HIGH 4418 28.1 4672 63 34.1 5719 90 43.4 3657 40 55.6 4706 64 62.0 2626 22 69.7 5369 81 74.4 3157 31LOW 4175 29.0 4863 41 35.1 5930 58 45.1 3818 27 57.5 4890 42 65.0 2762 16 72.0 5565 52 77.7 3302 21

45 MEDIUM 5203 34.7 5814 56 42.1 7102 79 53.8 4558 37 68.9 5851 57 77.3 3286 21 86.3 6666 71 92.7 3938 29HIGH (2) 6218 40.2 6689 71 48.9 8181 101 62.2 5237 47 79.6 6732 72 89.0 3766 27 99.7 7679 90 106.7 4522 37

4-pipe coil

LOW (1) - - - - - - - - - - - - - - - - - - - - -08 MEDIUM 641 1.8 299 5 2.3 375 7 2.8 229 3 3.6 305 5 3.8 159 2 4.6 354 6 4.7 197 2

HIGH 724 2.0 318 5 2.5 399 8 3.0 244 3 4.0 325 5 4.1 169 2 5.0 376 7 5.1 209 2LOW (1) - - - - - - - - - - - - - - - - - - - - -

12 MEDIUM 1278 3.5 544 19 4.2 676 28 5.2 419 11 6.7 551 19 7.1 294 6 8.4 635 25 8.6 359 9HIGH 1889 4.4 671 28 5.3 834 41 6.5 516 17 8.4 680 28 8.9 362 9 10.5 784 37 10.8 444 13LOW 1521 5.6 901 61 6.9 1114 90 8.4 694 38 10.9 908 62 11.7 486 19 13.7 1043 80 14.2 593 28

20 MEDIUM 2178 6.9 1093 87 8.4 1353 129 10.4 843 54 13.4 1103 89 14.3 591 28 16.8 1268 115 17.4 720 40HIGH 2720 7.9 1237 110 9.6 1532 163 11.8 953 68 15.2 1248 111 16.3 671 35 19.1 1435 144 19.7 815 51LOW 2377 5.9 918 18 7.2 1141 27 8.8 706 11 11.4 929 19 12.1 496 6 14.3 1072 24 14.7 606 9

30 MEDIUM 3073 7.0 1049 23 8.5 1304 34 10.3 808 14 13.2 1063 24 14.1 567 8 16.6 1226 31 17.1 694 11HIGH 4096 8.1 1229 31 9.9 1528 46 12.0 948 19 15.4 1245 32 16.4 664 10 19.4 1436 41 19.9 813 15LOW 4038 12.9 2096 82 15.8 2594 120 19.5 1616 51 25.3 2114 83 27.1 1132 27 31.9 2430 107 32.9 1381 38

45 MEDIUM 5003 14.7 2358 101 17.9 2919 149 22.1 1818 63 28.6 2378 103 30.7 1277 33 36.0 2735 133 37.2 1554 47HIGH (2) 6058 16.7 2626 123 20.3 3250 182 25.0 2023 77 32.2 2648 125 34.6 1424 40 40.5 3046 161 41.8 1730 58

(1) Unable to reach 50Pa TkW: Total cooling capacity in kW(2) Unit operation high limit l/h: Water flow in liters per hour kPa: Water pressure drops through the coil

74

Page 77: Train Instrument's

Water S

ystem

s

75

FWD

75

Performance data FWD

PROD-PRC014-E4

Un

it s

ize

Sp

eed

Air

flo

w

(m3/h

)

Water temperature flow / return in °C

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa2-pipe coil

LOW (1) - - - - - - - - - - - - - - - - - - - - -08 MEDIUM (1) - - - - - - - - - - - - - - - - - - - - -

HIGH 556 4.2 689 14 5.1 839 19 6.5 543 9 8.2 693 14 9.4 395 5 10.3 787 17 11.1 471 7LOW (1) - - - - - - - - - - - - - - - - - - - - -

12 MEDIUM 1191 7.9 1314 25 9.6 1610 36 12.2 1028 16 15.7 1325 25 17.4 738 9 19.7 1514 33 21.0 889 12HIGH 1788 11.0 1811 45 13.4 2226 67 16.9 1413 29 21.7 1829 46 24.0 1010 15 27.3 2093 59 28.9 1221 22

LOW (1) - - - - - - - - - - - - - - - - - - - - -20 MEDIUM 2043 14.4 2385 57 17.5 2909 82 22.3 1874 36 28.4 2398 57 32.1 1355 20 35.5 2730 73 38.3 1621 27

HIGH 2619 17.7 2928 83 21.4 3575 121 27.3 2294 53 34.9 2946 84 39.1 1654 29 43.6 3355 108 46.9 1983 40LOW 2218 16.1 2669 23 19.4 3250 33 24.9 2100 15 31.7 2682 23 36.0 1523 8 39.6 3050 29 42.9 1818 11

30 MEDIUM 2967 20.7 3414 36 25.0 4165 51 31.9 2678 23 40.8 3432 36 45.8 1935 13 50.9 3909 46 54.8 2317 18HIGH 4026 26.2 4354 55 31.9 5326 80 40.5 3409 36 51.9 4383 56 58.0 2453 20 64.9 4999 71 69.5 2946 27LOW 3976 27.8 4667 39 33.8 5689 54 43.3 3666 25 55.3 4692 39 62.4 2653 15 69.1 5337 49 74.6 3173 20

45 MEDIUM 4947 33.4 5590 52 40.5 6825 74 51.8 4383 35 66.2 5621 53 74.4 3162 20 82.9 6405 66 89.2 3788 27HIGH (2) 6218 40.2 6689 71 48.9 8181 101 62.2 5237 47 79.6 6732 72 89.0 3766 27 99.7 7679 90 106.7 4522 37

4-pipe coil

LOW (1) - - - - - - - - - - - - - - - - - - - - -08 MEDIUM (1) - - - - - - - - - - - - - - - - - - - - -

HIGH 513 1.7 268 4 2.1 335 6 2.6 205 2 3.4 273 4 3.5 141 1 4.2 316 5 4.3 176 2LOW (1) - - - - - - - - - - - - - - - - - - - - -

12 MEDIUM 1139 3.3 512 17 4.0 637 25 4.9 394 10 6.3 519 17 6.7 276 5 7.9 598 22 8.2 338 8HIGH 1611 4.1 615 23 4.9 764 35 6.0 473 14 7.7 623 24 8.2 332 7 9.7 718 31 9.9 406 11

LOW (1) - - - - - - - - - - - - - - - - - - - - -20 MEDIUM 1853 6.4 1002 74 7.8 1239 110 9.6 772 46 12.3 1010 75 13.2 541 24 15.4 1161 97 16.0 660 34

HIGH 2297 7.2 1127 92 8.8 1394 137 10.8 868 57 13.9 1136 94 14.9 610 30 17.4 1306 121 18.0 742 43LOW 2112 5.6 865 16 6.8 1074 24 8.3 665 10 10.8 875 17 11.4 467 5 13.5 1009 22 13.9 570 8

30 MEDIUM 2811 6.7 1001 21 8.1 1244 32 9.8 770 13 12.7 1013 22 13.5 541 7 15.8 1169 28 16.3 662 10HIGH 3731 7.8 1167 28 9.4 1451 42 11.4 899 17 14.7 1182 29 15.6 630 9 18.4 1363 37 19.0 772 13LOW 3818 12.6 2033 77 15.4 2517 114 19.0 1567 48 24.6 2050 78 26.3 1097 25 31.0 2358 101 32.0 1340 36

45 MEDIUM 4716 14.2 2283 95 17.4 2825 141 21.4 1759 59 27.7 2303 97 29.7 1235 31 34.8 2648 125 36.0 1504 45HIGH (2) 6058 16.7 2626 123 20.3 3250 182 25.0 2023 77 32.2 2648 125 34.6 1424 40 40.5 3046 161 41.8 1730 58

(1) Unable to reach 100Pa TkW: Total cooling capacity in kW(2) Unit operation high limit l/h: Water flow in liters per hour kPa: Water pressure drops through the coil

Heating Capacities - Basic unit + EU2 filter box (clean filter) - ESP 100Pa- Return Air Temperature 20°C - Constant delta T°

BA

SIC

UN

ITH

OT

WA

TE

R C

OIL

KIT

Page 78: Train Instrument's

76PROD-PRC014-E4

Customer benefits• Easy installation: saving of time and money• Easy commissioning: saving of time and money• Wide product range: one supplier for various customer

applications

Main features• 5-speed centrifugal fan with protection grille• Possibility to select on job site the 3 fan speeds to adapt

airflow and sound levels to each room• Built-in centrifugal condensate pump (maximum head

500 mm)• Possibility of air discharge on 3 or 4 sides• Fresh air intake facility• Additional room air discharge facility • Washable filters• Easy access to components from underneath

Options• Factory-mounted 2 kW or 3 kW electric heater

Accessories• On/off 2-way or 3-way/4-port valve• Modulating 2-way or 3-way/4-port ZN valve• Ultra-thin 30 mm-thick fascia - designed for discreet

integration in false ceilling• Automatic changeover for cold water and hot water

application• Blanking foam• Auxiliary drain pan• Fresh air spigot ∅ 100 mm for air renewal• Adjacent air spigot ∅ 150 mm• 2 kW, 3 kW, 4 kW electric heater

Control• Wall thermostat N: 3-speed switch + 1-stage stat +

manual changeover for the valve• Wall thermostat P: 3-speed switch + 2-stage stat for the

valve• New factory-mounted LonMarkTM Trane ZN523 control,

providing enhanced acoustical and thermal comfort, andenergy saving solutions (on request)

• Full range of user interfaces (ZSM-10, ZSM-11) andwireless remote control (IRC)

• Trane ZN523 can be associated with Trane EXL-EXB forlight and sunblind control

• BatiBUS control (kit)

Mid-sized space applications1-12 kW

Chilled water terminals

CWSCWS

P N

ZSM-10 ZSM-11 IRC

Page 79: Train Instrument's

General data

PROD-PRC014-E4

Unit size 025 045 065

Speed at ESP = 0 Pa (4) 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Airflow (m3/h) 432 525 620 750 920 432 525 620 750 920 432 525 620 750 920

Power supply (V/Ph/Hz) 230/1/50

Cooling 2-pipe (P) units (1)

Total capacity (kW) 1.6 1.8 1.9 2.0 2.3 2.7 3.1 3.5 3.9 4.3 3.2 3.8 4.3 5.0 5.7

Sensible capacity (kW) 1.4 1.6 1.8 2.0 2.3 1.9 2.2 2.5 2.9 3.3 2.2 2.6 3.0 3.5 4.0

Water flow (l/h) 281 310 335 360 396 472 537 601 670 749 565 663 753 864 986

Water pressure drop (kPa) 5 6 7 8 10 24 30 36 44 53 18 24 30 38 49

Water content (l) 0.6 1.0 1.5

Cooling 4-pipe (PL) units (1)

Total capacity (kW) 1.4 1.5 1.6 1.9 2.1 2.1 2.3 2.6 2.8 3.1 2.7 3.0 3.3 3.7 4.0

Sensible capacity (kW) 1.3 1.5 1.6 1.9 2.1 1.6 1.9 2.2 2.5 2.9 2.0 2.3 2.6 3.0 3.4

Water flow (l/h) 248 266 281 317 360 356 403 443 486 533 457 515 569 630 695

Water pressure drop (kPa) 20 23 25 31 38 12 14 17 20 23 4 5 5 6 8

Water content (l) 0.5 0.8 1.3

Cooling water 1/2" ISO R7 1/2" ISO R7 1/2" ISO R7connection type female gas female gas female gas

Heating 2-pipe (P) units (2)

Total capacity (kW) 2.1 2.4 2.7 3.0 3.4 2.7 3.0 3.5 4.0 4.5 3.3 3.9 4.5 5.2 6.0

Water flow (l/h) 281 310 335 360 396 472 537 601 670 749 565 663 753 864 986

Water pressure drop (kPa) 4 5 6 7 8 19 24 30 36 44 15 20 25 32 40

Water content (l) 0.6 1.0 1.5

Heating 4-pipe (PL) units (2)

Total capacity (kW) 1.6 1.8 1.9 2.1 2.4 2.6 2.9 3.2 3.6 4.0 2.5 2.8 3.1 3.5 3.9

Water flow (l/h) 137 151 166 184 205 223 252 277 310 346 216 245 270 299 335

Water pressure drop (kPa) 2 3 3 4 4 10 13 15 18 22 11 14 16 20 24

Water content (l) 0.2 0.3 0.3

Heating water 1/2"ISO R7 1/2"ISO R7 1/2"ISO R7connection type female gas female gas female gas

Sound power level (5) (dB(A)) 47 52 58 61 66 48 52 59 61 67 50 54 59 60 66

Sound pressure level (3) (dB(A)) 26 31 37 40 45 27 31 38 40 46 29 33 38 39 45

(1) Cooling: air temperature : 27/19°C, water temperature : 7/12°C(2) Heating: CWS 025P to 155P, air temperature : 20°C, entering water temperature : 50°C, cooling mode water flow

CWS 025PL to 155PL, air temperature: 20°C, water temperature: 70/60°C.(3) Sound pressure levels are calculated from results measured in anechoic conditions. Values relate to a position of 3m away from the centre line of the unit, 1m

down.(4) Factory wired speeds: 1, 2, 3; can be adjusted on jobsite(5) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor

Water S

ystem

sC

WS

77

Page 80: Train Instrument's

7878PROD-PRC014-E4

General data

CWS

Unit size 095 135 155

Speed at ESP = 0 Pa (4) 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Airflow (m3/h) 865 1190 1330 1620 1945 865 1150 1300 1620 1910 790 1080 1260 1550 1800

Power supply (V/Ph/Hz) 230/1/50

Cooling 2-pipe (P) units (1)

Total capacity (kW) 5.7 7.1 7.7 8.7 9.7 6.2 7.8 8.5 10.0 11.1 6.7 9.0 10.3 12.2 13.8

Sensible capacity (kW) 3.9 5.0 5.5 6.3 7.2 4.3 5.4 6.0 7.1 8.1 4.5 6.0 6.9 8.2 9.3

Water flow (l/h) 980 1231 1328 1501 1667 1069 1343 1469 1721 1915 1152 1541 1768 2106 2380

Water pressure drop (kPa) 21 32 37 45 55 20 30 35 46 55 19 31 40 54 67

Water content (l) 2.4 3.6 4.8

Cooling 4-pipe (PL) units (1)

Total capacity (kW) 5.4 6.7 7.2 8.0 8.8 5.6 7.4 8.0 9.3 10.2 6.3 8.2 9.2 10.8 12.1

Sensible capacity (kW) 3.8 4.8 5.2 6.0 6.9 4.0 5.0 5.5 6.5 7.3 4.2 5.5 6.3 7.4 8.3

Water flow (l/h) 932 1148 1231 1379 1516 1026 1271 1379 1595 1760 1076 1404 1591 1865 2077

Water pressure drop (kPa) 33 47 53 65 76 23 33 38 49 59 21 33 41 54 65

Water content (l) 1.8 2.4 3.6

Cooling water 3/4" ISO R7 3/4" ISO R7 3/4" ISO R7connection type female gas female gas female gas

Heating 2-pipe (P) units (2)

Total capacity (kW) 6.5 8.3 9.1 10.5 11.9 7.4 9.5 10.5 12.6 14.4 7.2 9.8 11.3 13.5 15.5

Water flow (l/h) 980 1231 1328 1501 1667 1069 1343 1469 1721 1915 1152 1541 1768 2106 2380

Water pressure drop (kPa) 18 26 30 37 44 16 24 28 37 45 15 25 32 44 54

Water content (l) 2.4 3.6 4.8

Heating 4-pipe (PL) units (2)

Total capacity (kW) 4.5 5.4 5.8 6.5 7.1 6.7 8.1 8.7 9.8 11.0 6.4 7.9 8.7 9.8 10.8

Water flow (l/h) 389 468 500 558 616 576 695 749 860 947 551 677 745 846 929

Water pressure drop (kPa) 6 9 10 10 12 3 4 5 6 8 3 4 5 6 8

Water content (l) 0.6 1.2 1.2

Heating water 1/2" ISO R7 1/2" ISO R7 1/2" ISO R7connection type female gas female gas female gas

Sound power level (5) (dB(A)) 52 57 60 63 66 53 59 61 64 68 55 60 63 65 69

Sound pressure level (3) (dB(A)) 34 39 42 45 48 35 41 43 46 50 37 42 45 47 51

(1) Cooling: air temperature : 27/19°C, water temperature : 7/12°C(2) Heating: CWS 025P to 155P, air temperature : 20°C, entering water temperature: 50°C, cooling mode water flow

CWS 025PL to 155PL, air temperature: 20°C, water temperature: 70/60°C.(3) Sound pressure levels are calculated from results measured in anechoic conditions. Values relate to a position of 3m away from the centre line of the unit, 1m

down.(4) Factory wired speeds: 1, 2, 3; can be adjusted on jobsite(5) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent Certification, standard motor

Page 81: Train Instrument's

Dimensions and weights

PROD-PRC014-E4

Z

YX

VW

Dimensions(mm) Operating

weight (kg)

Branch ductconnectiondiameter

(mm)

Electrical data

V W X Y Z (1)

CWS 025 675 675 580 580 305 19 150 100

CWS 045 675 675 580 580 305 21 150 100

CWS 065 675 675 580 580 305 24 150 100

CWS 095 967 967 883 883 314 36 150 100

CWS 135 967 967 883 883 314 40 150 100

CWS 155 967 967 883 883 314 44 150 100

(1) Not including fascia height (30 mm)

(2) Fresh air cannot exceed 10% of nominal airflow

Unit size

Fresh air inletconnectiondiameter (2)

(mm)

Unit size 025 045 065

Speed number 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Fan motor nominal capacity (kW) 0.05 0.06 0.08 0.09 0.12 0.05 0.06 0.08 0.09 0.12 0.05 0.06 0.08 0.09 0.12Fan motor absorbed current (A) 0.25 0.30 0.35 0.42 0.52 0.25 0.30 0.35 0.42 0.52 0.25 0.30 0.35 0.42 0.52Electric heater capacity (option) (kW) 1.8 1.8 1.8Absorbed current (A) 8.0 8.0 8.0

Unit size 095 135 155

Speed number 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Fan motor nominal capacity (kW) 0.07 0.10 0.12 0.14 0.20 0.07 0.10 0.12 0.15 0.20 0.07 0.10 0.12 0.15 0.20Fan motor absorbed current (A) 0.40 0.50 0.59 0.68 0.96 0.40 0.50 0.59 0.72 0.96 0.40 0.50 0.59 0.72 0.96Electric heater capacity (option) (kW) 2.8 2.8 2.8Absorbed current (A) 12.0 12.0 12.0Electric heater capacity kit 1 (kW) 1.8 1.8 1.8Absorbed current (A) 7.8 7.8 7.8Electric heater capacity kit 2 (kW) 3.7 3.7 3.7Absorbed current (A) 16.1 16.1 16.1

Values given for a 230V/1Ph/50Hz power supply

Water S

ystem

sC

WS

79

Page 82: Train Instrument's

Performance data CWS

8080PROD-PRC014-E4

Un

it s

ize

Sp

eed

nb

.

Air

flo

w

(m3/h

)

Air

tem

pe-

ratu

reWater temperature flow / return in °C

Cooling capacities - 0Pa - Constant delta T°

5/10 5.5/11 6/10 7/12 8/13

TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa TkW SkW l/h kPa

22/15.5°C 1.1 1.1 184 3 1.0 1.0 148 2 1.1 1.1 241 4 0.9 0.9 151 2 0.8 0.8 133 11 432 24/17.0°C 1.5 1.2 256 5 1.2 1.1 194 3 1.6 1.3 335 7 1.1 1.1 184 3 1.0 1.0 169 2

26/18.7°C 2.0 1.4 335 7 1.7 1.3 266 5 2.0 1.4 432 12 1.5 1.3 263 5 1.3 1.2 227 428/20.4°C 2.4 1.6 418 11 2.2 1.5 342 8 2.5 1.6 533 17 2.0 1.4 346 8 1.8 1.3 310 622/15.5°C 1.4 1.4 238 4 1.2 1.2 191 3 1.4 1.4 306 6 1.1 1.1 194 3 1.0 1.0 176 2

025P 3 620 24/17.0°C 1.8 1.6 306 6 1.5 1.5 234 4 1.9 1.7 400 10 1.4 1.4 241 4 1.3 1.3 220 326/18.7°C 2.4 1.8 407 10 2.1 1.7 320 7 2.4 1.9 522 16 1.8 1.6 313 7 1.6 1.5 266 528/20.4°C 3.0 2.0 508 15 2.7 1.9 414 11 3.0 2.1 644 23 2.4 1.8 418 11 2.2 1.7 371 922/15.5°C 1.8 1.8 306 6 1.6 1.6 252 4 1.8 1.8 396 10 1.5 1.5 256 5 1.3 1.3 227 4

5 920 24/17.0°C 2.1 2.1 364 9 1.9 1.9 302 6 2.2 2.2 464 13 1.8 1.8 313 6 1.7 1.7 284 526/18.7°C 2.8 2.4 475 14 2.4 2.3 374 9 2.8 2.4 612 21 2.1 2.1 367 9 2.0 2.0 342 828/20.4°C 3.5 2.6 601 21 3.1 2.5 490 14 3.5 2.7 760 31 2.8 2.4 486 14 2.5 2.3 428 1122/15.5°C 2.0 1.6 346 14 1.8 1.5 281 10 2.0 1.6 425 20 1.5 1.4 263 9 1.3 1.3 220 6

1 432 24/17.0°C 2.5 1.8 439 21 2.3 1.7 364 15 2.5 1.8 536 30 2.1 1.6 356 14 1.8 1.5 310 1126/18.7°C 3.1 2.0 533 30 2.9 1.9 450 22 3.0 2.0 652 43 2.6 1.8 450 22 2.4 1.7 407 1828/20.4°C 3.7 2.2 630 40 3.5 2.1 544 31 3.6 2.2 774 57 3.2 2.0 551 31 2.9 1.9 508 2722/15.5°C 2.6 2.1 443 22 2.3 2.0 356 15 2.5 2.1 540 30 1.9 1.8 331 13 1.7 1.7 288 10

045P 3 620 24/17.0°C 3.3 2.4 558 33 3.0 2.2 464 23 3.2 2.3 684 46 2.6 2.1 450 22 2.3 2.0 392 1726/18.7°C 4.0 2.6 680 46 3.7 2.5 576 34 3.9 2.6 835 65 3.3 2.4 572 34 3.0 2.2 518 2828/20.4°C 4.7 2.9 810 62 4.4 2.8 695 47 4.6 2.9 994 89 4.1 2.6 702 48 3.7 2.5 644 4122/15.5°C 3.2 2.8 554 32 2.8 2.6 443 22 3.1 2.7 673 45 2.4 2.4 418 19 2.2 2.2 382 16

5 920 24/17.0°C 4.1 3.1 702 48 3.7 3.0 580 35 4.0 3.1 857 68 3.3 2.8 562 32 2.8 2.6 486 2526/18.7°C 5.0 3.5 857 69 4.6 3.3 724 51 4.9 3.4 1051 98 4.2 3.1 716 49 3.7 3.0 644 4128/20.4°C 5.9 3.8 1019 93 5.6 3.6 871 70 5.8 3.8 1256 134 5.1 3.4 878 70 4.7 3.3 803 6022/15.5°C 2.5 1.9 425 11 2.3 1.8 353 8 2.4 1.8 511 16 1.9 1.6 331 7 1.6 1.5 281 5

1 432 24/17.0°C 3.1 2.1 529 17 2.8 2.0 446 12 3.0 2.1 641 23 2.5 1.9 436 12 2.2 1.7 385 926/18.7°C 3.7 2.4 637 23 3.5 2.2 544 17 3.6 2.3 774 32 3.2 2.1 544 17 2.9 2.0 493 1428/20.4°C 4.3 2.6 749 31 4.1 2.5 648 24 4.3 2.5 914 43 3.8 2.3 655 24 3.5 2.2 608 2122/15.5°C 3.3 2.5 565 19 3.0 2.4 464 13 3.2 2.5 680 26 2.5 2.2 436 12 2.2 2.0 371 9

065P 3 620 24/17.0°C 4.1 2.9 702 27 3.8 2.7 590 20 4.0 2.8 853 38 3.3 2.5 576 19 3.0 2.4 508 1526/18.7°C 4.9 3.2 846 38 4.6 3.0 724 29 4.8 3.1 1033 54 4.2 2.8 720 28 3.8 2.7 655 2428/20.4°C 5.8 3.5 997 51 5.5 3.3 860 39 5.7 3.4 1220 72 5.1 3.2 875 39 4.7 3.0 810 3422/15.5°C 4.3 3.4 738 30 3.9 3.2 605 21 4.2 3.4 896 42 3.3 3.0 569 19 2.8 2.8 479 14

5 920 24/17.0°C 5.4 3.9 922 44 4.9 3.7 774 32 5.2 3.8 1123 62 4.4 3.4 752 30 3.9 3.2 662 2426/18.7°C 6.5 4.3 1112 61 6.1 4.1 947 46 6.3 4.2 1357 86 5.5 3.8 947 45 5.0 3.6 857 3828/20.4°C 7.6 4.7 1310 81 7.2 4.5 1130 62 7.5 4.6 1609 116 6.6 4.2 1145 63 6.1 4.0 1055 5522/15.5°C 4.2 3.2 716 13 3.7 3.0 572 8 4.1 3.2 878 18 3.1 2.7 533 7 2.5 2.5 436 5

1 865 24/17.0°C 5.3 3.7 907 19 4.8 3.5 752 14 5.2 3.6 1116 27 4.3 3.2 731 13 3.7 3.0 637 1026/18.7°C 6.4 4.1 1105 27 6.0 3.9 936 20 6.3 4.1 1361 38 5.4 3.7 932 20 4.9 3.4 842 1628/20.4°C 7.6 4.5 1314 36 7.2 4.3 1127 28 7.5 4.5 1613 52 6.6 4.1 1141 28 6.1 3.9 1055 2422/15.5°C 5.7 4.5 976 22 5.0 4.2 781 15 5.5 4.5 1195 31 4.2 3.9 724 13 3.5 3.5 608 9

095P 3 1330 24/17.0°C 7.2 5.1 1238 33 6.6 4.9 1026 23 7.0 5.1 1516 47 5.8 4.5 994 22 5.0 4.2 864 1726/18.7°C 8.8 5.7 1508 46 8.1 5.5 1274 34 8.6 5.7 1850 66 7.4 5.1 1267 34 6.6 4.8 1141 2828/20.4°C 10.4 6.3 1789 62 9.8 6.0 1534 47 10.2 6.2 2200 89 9.0 5.7 1552 48 8.3 5.4 1426 4122/15.5°C 7.2 6.0 1231 33 6.3 5.6 986 22 7.0 5.9 1501 46 5.3 5.2 907 19 4.7 4.7 810 15

5 1945 24/17.0°C 9.1 6.8 1562 49 8.3 6.4 1296 35 8.9 6.7 1912 70 7.3 6.0 1249 33 6.3 5.6 1084 2526/18.7°C 11.1 7.5 1908 70 10.3 7.2 1609 52 10.9 7.4 2344 100 9.3 6.7 1595 50 8.3 6.3 1433 4128/20.4°C 13.2 8.2 2275 95 12.4 7.9 1940 72 13.0 8.2 2804 137 11.4 7.5 1958 72 10.4 7.1 1793 6122/15.5°C 4.5 3.5 781 12 4.0 3.3 623 8 4.4 3.5 958 17 3.3 3.0 572 7 2.7 2.7 457 5

1 865 24/17.0°C 5.8 4.0 997 18 5.3 3.8 828 13 5.6 4.0 1217 25 4.7 3.5 799 12 4.0 3.3 695 926/18.7°C 7.1 4.5 1213 25 6.6 4.3 1030 19 6.9 4.4 1483 36 6.0 4.0 1026 19 5.4 3.8 925 1528/20.4°C 8.4 5.0 1440 34 7.9 4.8 1238 26 8.2 4.9 1760 48 7.3 4.5 1253 26 6.7 4.3 1156 2322/15.5°C 6.3 5.0 1080 21 5.5 4.6 868 14 6.1 4.9 1314 29 4.6 4.2 799 12 3.9 3.9 662 9

135P 3 1300 24/17.0°C 8.0 5.7 1372 31 7.3 5.3 1141 23 7.8 5.6 1670 44 6.4 5.0 1102 21 5.6 4.6 958 1626/18.7°C 9.7 6.3 1670 44 9.1 6.0 1418 33 9.5 6.2 2034 62 8.2 5.6 1408 32 7.4 5.3 1267 2728/20.4°C 11.5 6.9 1980 59 10.9 6.7 1703 45 11.2 6.8 2419 84 10.0 6.3 1721 46 9.2 5.9 1584 3922/15.5°C 8.3 6.7 1422 33 7.3 6.3 1141 23 8.0 6.6 1721 46 6.1 5.8 1051 19 5.3 5.3 911 15

5 1910 24/17.0°C 10.5 7.6 1800 50 9.6 7.2 1498 36 10.1 7.5 2182 70 8.4 6.7 1444 34 7.3 6.3 1253 2626/18.7°C 12.7 8.5 2192 71 11.9 8.1 1858 53 12.4 8.3 2671 100 10.7 7.6 1836 51 9.6 7.2 1652 4228/20.4°C 15.1 9.3 2603 96 14.3 8.9 2232 73 14.8 9.2 3186 136 13.0 8.4 2246 73 12.0 8.0 2063 6222/15.5°C 5.1 3.8 878 12 4.7 3.6 731 9 4.9 3.6 1048 16 4.0 3.2 688 8 3.4 3.0 583 6

1 790 24/17.0°C 6.3 4.2 1084 17 5.9 4.0 918 13 6.0 4.1 1300 23 5.2 3.7 893 12 4.6 3.5 796 1026/18.7°C 7.5 4.7 1296 23 7.1 4.5 1116 18 7.3 4.6 1566 32 6.4 4.2 1109 18 5.9 4.0 1012 1528/20.4°C 8.8 5.2 1519 31 8.4 5.0 1318 24 8.6 5.1 1843 43 7.8 4.7 1336 24 7.2 4.4 1238 2122/15.5°C 7.8 5.8 1343 25 7.1 5.4 1116 18 7.5 5.6 1606 34 6.1 5.0 1051 16 5.2 4.6 893 12

155P 3 1260 24/17.0°C 9.6 6.5 1656 36 9.0 6.2 1404 27 9.3 6.3 1994 49 8.0 5.7 1372 25 7.1 5.3 1217 2026/18.7°C 11.5 7.2 1984 49 10.9 6.9 1706 37 11.1 7.1 2398 68 9.9 6.5 1703 37 9.0 6.1 1552 3128/20.4°C 13.5 7.9 2322 65 12.9 7.7 2016 50 13.1 7.8 2819 91 11.9 7.2 2045 51 11.0 6.8 1897 4422/15.5°C 10.5 7.8 1811 42 9.6 7.4 1501 30 10.1 7.6 2164 57 8.2 6.8 1415 27 7.0 6.3 1202 20

5 1800 24/17.0°C 13.0 8.9 2232 60 12.1 8.4 1890 45 12.5 8.6 2686 83 10.7 7.8 1843 43 9.5 7.3 1638 3426/18.7°C 15.5 9.8 2671 83 14.6 9.4 2293 63 15.0 9.6 3233 115 13.3 8.8 2286 62 12.1 8.3 2084 5228/20.4°C 18.2 10.8 3128 109 17.3 10.4 2711 84 17.7 10.6 3809 153 16.0 9.8 2747 86 14.8 9.2 2549 75

TkW: Total cooling capacity in kW SkW: Sensible cooling capacity in kW l/h: Water flow in liters per hour

2-pipe coil

Page 83: Train Instrument's

xxxxxxxxxxxxxxxxxxxxxxxxxxxxxx

PROD-PRC014-E4

Performance data CWS

Un

it s

ize

Sp

eed

nb

.

Air

flo

w

(m3/h

)

Heating capacities - 0Pa - Constant delta T° - Return air temperature = 20°C

Water temperature flow / return in °C

Water temperature flow / return in °C4-pipe coil

81

CW

S

81

Water S

ystem

s

Un

it s

ize

Sp

eed

nb

.

Air

flo

w

(m3/h

)

2-pipe coil

45/40 50/45 60/50 70/60 80/60 82/71 90/70TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa

1 432 1.8 310 5 2.2 385 8 2.8 238 3 3.7 317 5 3.9 169 2 4.7 364 6 4.8 205 2025P 3 620 2.3 396 8 2.9 493 12 3.5 306 5 4.7 403 8 5.0 212 3 5.9 464 10 6.1 263 4

5 920 2.9 508 13 3.7 630 18 4.5 389 8 6.0 515 12 6.3 274 4 7.6 594 15 7.8 335 51 432 2.2 374 13 2.7 461 19 3.4 288 8 4.4 378 12 4.7 205 4 5.6 436 15 5.8 248 6

045P 3 620 2.8 486 21 3.5 601 30 4.4 374 13 5.7 490 20 6.1 263 7 7.2 565 24 7.5 324 95 920 3.7 634 33 4.6 785 47 5.7 490 20 7.4 641 31 8.0 346 10 9.4 738 39 9.8 421 141 432 2.7 468 11 3.3 576 15 4.2 364 7 5.5 472 10 6.0 259 4 6.9 540 13 7.3 313 5

065P 3 620 3.6 626 18 4.5 770 26 5.6 486 11 7.3 634 17 8.0 346 6 9.3 727 21 9.7 418 85 920 4.9 839 31 6.0 1037 43 7.6 652 19 9.9 850 29 10.7 461 10 12.5 979 36 13.1 562 131 865 5.4 925 16 6.6 1134 23 8.3 720 10 10.8 932 15 11.9 511 5 13.6 1066 18 14.4 619 7

095P 3 1330 7.5 1300 29 9.3 1598 41 11.7 1008 18 15.2 1310 27 16.6 716 9 19.2 1501 34 20.2 868 135 1945 10.0 1717 48 12.3 2117 67 15.5 1332 29 20.1 1732 45 21.9 943 15 25.4 1991 55 26.6 1145 211 865 6.2 1062 16 7.5 1296 23 9.6 828 10 12.4 1066 15 13.8 594 5 15.5 1217 18 16.6 713 7

135P 3 1300 8.8 1512 30 10.8 1854 42 13.7 1181 19 17.7 1523 28 19.6 846 10 22.2 1739 34 23.6 1015 135 1910 12.1 2081 53 14.8 2552 74 18.8 1624 33 24.3 2095 49 26.9 1159 17 30.6 2398 61 32.5 1397 231 790 5.9 1020 12 7.2 1246 18 9.2 792 8 11.8 1012 11 13.1 565 5 14.7 1156 14 15.8 680 5

155P 3 1260 9.3 1598 28 11.3 1948 38 14.5 1249 17 18.6 1602 26 20.8 896 9 23.3 1829 31 25.0 1076 125 1800 12.8 2200 48 15.6 2689 67 20.0 1721 30 25.7 2210 45 28.8 1238 16 32.2 2524 54 34.5 1487 21

Air leaving temperature is above 60°C, risk of plastic distortion

45/40 50/45 60/50 70/60 80/60 82/71 90/70

TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa TkW l/h kPa

1 432 0.8 133 2 1.0 166 3 1.2 101 1 1.6 137 2 1.6 68 1 2.0 158 3 2.0 86 1025PL 3 620 0.9 162 3 1.2 205 5 1.4 122 2 1.9 166 3 2.0 83 1 2.5 194 4 2.5 104 1

5 920 1.2 202 4 1.5 252 6 1.8 151 3 2.4 205 4 2.4 104 1 3.0 238 5 3.0 130 21 432 1.3 220 11 1.6 274 15 2.0 169 7 2.6 223 10 2.8 119 3 3.3 259 13 3.4 148 5

045PL 3 620 1.6 274 16 2.0 338 23 2.5 209 9 3.2 277 15 3.4 148 5 4.1 320 19 4.2 180 75 920 2.0 342 23 2.5 425 33 3.1 263 14 4.0 346 22 4.3 184 7 5.1 400 27 5.3 227 101 432 1.2 212 12 1.5 263 17 1.9 166 7 2.5 216 11 2.7 115 4 3.2 248 14 3.3 140 5

065PL 3 620 1.5 263 17 1.9 328 25 2.4 205 11 3.1 270 16 3.3 144 5 4.0 310 20 4.1 176 75 920 1.9 331 26 2.4 410 37 3.0 256 15 3.9 335 24 4.1 176 8 5.0 389 30 5.1 220 111 865 2.2 382 6 2.8 475 8 3.4 295 4 4.5 389 6 4.8 205 2 5.8 450 7 5.9 252 3

095PL 3 1330 2.9 490 9 3.6 612 13 4.4 378 5 5.8 500 9 6.1 263 3 7.4 580 11 7.6 324 45 1945 3.5 605 13 4.4 752 19 5.4 464 8 7.1 616 12 7.5 324 4 9.1 713 15 9.3 400 61 865 3.3 565 3 4.1 706 5 5.1 436 2 6.7 576 3 7.1 306 1 8.5 666 4 8.8 378 2

135PL 3 1300 4.3 734 5 5.3 914 8 6.6 569 3 8.7 749 5 9.2 396 2 11.1 868 6 11.4 490 25 1910 5.4 929 8 6.7 1159 12 8.3 716 5 11.0 947 8 11.6 500 3 14.0 1098 10 14.3 619 31 790 3.2 540 3 3.9 673 5 4.9 418 2 6.4 551 3 6.8 292 1 8.1 637 4 8.4 364 1

155PL 3 1260 4.3 734 5 5.3 911 8 6.6 565 3 8.7 745 5 9.2 396 2 11.0 864 6 11.3 490 25 1800 5.3 911 8 6.6 1138 11 8.2 702 5 10.8 929 8 11.4 493 2 13.7 1073 9 14.1 605 4

TkW: Total heating capacity in kWl/h: Water flow in liters per hour

Page 84: Train Instrument's

82PROD-PRC014-E4

AIR SYSTEMS

Page 85: Train Instrument's

VARIABLE AIR VOLUME SYSTEMS

AIR DIFFUSERS

350kW 700 1 000 80 000 150 000 250 00050 000 100 000 120 000 200 000

83PROD-PRC014-E4

New

• CLCE: CO4 compliant (U.K.) version available for healthcare segment

• CCTA: Enhanced casing design and "Clean concept" version

• CCH: Improved features for easy maintenance, disinfection and control fittingA

IR S

YS

TE

MS

Office building, healthcare, lodging,retail and industrial applications

m3/h

700 108 000 CLCE

CCEA

1 000 140 000CCTA

1 000 CCH

1 200 CCVA

17 900

86 000

1 800 120 000CCSA

1 000 250 000

AIR HANDLING UNITS700 - 250 000 m3/h

Page 86: Train Instrument's

84PROD-PRC014-E4

Customer benefits • Designed to meet the most stringent quality and flexibility

needs for all commercial and hospital applications• Unit construction available with Air Leakage Class A or B

(as per DW 144) to meet your Indoor Air Qualityrequirements

• Easy on-site installation and assembly of the units viasemi-modular construction

• Easily removable components for simplified maintenance

Main features• Units manufactured from totally enclosed extruded

aluminium profile with reinforced nylon corner pieces• 25 mm or 50 mm thick CFC free foam injected double

skin panels• Galvanized steel self finish or Ivory (similar to RAL 9002)

coloured plastisol coated outer skin• 160 mm high unit base frame• Inclined drain trays on all cooling coil and humidifier

sections• Available sections: mixing box, panel filters, bag filters,

carbon filters, absolute filters (HEPA), cooling andheating coils, electric heaters, silencers, forward andbackward curved fans, run around coils, plate heatexchangers, rotary heat wheels, indirect gas fired heatmodules, steam humidifiers

• Units equipped with either plate heat exchangers orthermal wheels qualify for ECA benefits (UK)

• Tracer Summit™ capabilities

Options• CO4 & HTM 2025 compliant construction including:

- Motor out of air stream- Washed down section with either dagger plates or

isolating dampers- Low leak dampers, silencers Melinex lined

- Removable stainless steel drain pans• Thermal breaks, providing a cold bridge free construc-

tion (50 mm panels only)• Factory witness tests• Outdoor units complete with either flat or inclined

weatherproof roof, louvre or hood• Access doors fitted with three way adjustable hinges• Stainless steel (316) inner skin• Units delivered in sections or flat packed

Accessories• Manometers, differential pressure switches, magnehelic

pressure gauges• Double glazed inspection windows• Fully wired bulkhead light and switch, motors isolators• Flange or flexible connections, etc…

Controls*• Factory-Engineered Controls featuring designing,

selecting, mounting, wiring and testing of all controldevices such as damper actuators, control valves,pressure sensors, temperature sensors, relays andcontrollers

• Power wiring to all devices such as Fan Motors,Frequency Inverters, Electric Heaters and Humidifiers

• Factory Pre-Commissioning is provided on all ControlsUnits

Indoor and outdoor66 sizes - 700 -108 000 m3/h(0.2 - 30 m3/s)

Air handling units

CLCE

CLCE

Removable drain pan

* Available option in the UK. For other countries, contact your local Trane Sales Office.

Page 87: Train Instrument's

Dimensions (mm) (1)

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

sC

LCE

85

Unit size 2.5 3.0 3.5 2.5 3.0 3.5 Width Height

03 02 (2) 0.20 0.24 0.29 720 864 1044 603 588 (1)03 03 0.35 0.42 0.49 1260 1512 1764 603 763 (1)04 02 (2) 0.31 0.37 0.43 1116 1332 1548 778 588 (1)04 03 0.53 0.64 0.74 1908 2304 2664 778 763 (1)04 04 0.80 0.95 1.11 2880 3420 3996 778 938 (1)05 02 (2) 0.41 0.49 0.57 1476 1764 2052 953 588 (1)05 03 0.70 0.84 0.98 2520 3024 3528 953 763 (1)05 04 1.05 1.26 1.47 3780 4536 5292 953 938 (1)05 05 1.34 1.61 1.88 4824 5796 6768 953 1113 (1)06 03 0.88 1.06 1.23 3168 3816 4428 1128 763 (1)06 04 1.32 1.58 1.85 4752 5688 6660 1128 938 (1)06 05 1.69 2.02 2.36 6084 7272 8496 1128 1113 (1)06 06 2.05 2.46 2.87 7380 8856 10332 1128 1288 (1)07 05 2.01 2.42 2.82 7236 8712 10152 1303 111307 06 2.45 2.94 3.43 8820 10584 12348 1303 128807 07 2.89 3.47 4.04 10404 12492 14544 1303 146308 04 1.80 2.16 2.52 6480 7776 9072 1478 93808 05 2.30 2.76 3.22 8280 9936 11592 1478 111308 06 2.80 3.36 3.92 10080 12096 14112 1478 128808 07 3.30 3.96 4.62 11880 14256 16632 1478 146308 08 3.90 4.68 5.46 14040 16848 19656 1478 163809 04 2.06 2.47 2.88 7416 8892 10368 1653 93809 05 2.63 3.15 3.68 9468 11340 13248 1653 111309 06 3.20 3.83 4.47 11520 13788 16092 1653 128809 07 3.77 4.52 5.27 13572 16272 18972 1653 146309 08 4.45 5.34 6.23 16020 19224 22428 1653 163809 09 5.02 6.03 7.03 18072 21708 25308 1653 181310 05 2.97 3.57 4.16 10692 12852 14976 1828 111310 06 3.62 4.34 5.06 13032 15624 18216 1828 128810 07 4.26 5.12 5.97 15336 18432 21492 1828 146310 08 5.04 6.05 7.05 18144 21780 25380 1828 163810 09 5.68 6.82 7.96 20448 24552 28656 1828 181310 10 6.33 7.59 8.86 22788 27324 31896 1828 198811 05 3.30 3.96 4.62 11880 14256 16632 2003 111311 06 4.01 4.81 5.62 14436 17316 20232 2003 128811 07 4.73 5.68 6.62 17028 20448 23832 2003 146311 08 5.59 6.71 7.83 20124 24156 28188 2003 163811 09 6.31 7.57 8.83 22716 27252 31788 2003 181311 10 7.02 8.43 9.83 25272 30348 35388 2003 198811 11 7.74 9.29 10.84 27864 33444 39024 2003 216312 06 4.43 5.32 6.20 15948 19152 22320 2178 128812 07 5.23 6.27 7.32 18828 22572 26352 2178 146312 08 6.18 7.41 8.65 22248 26676 31140 2178 163812 09 6.97 8.36 9.76 25092 30096 35136 2178 181312 10 7.76 9.31 10.86 27936 33516 39096 2178 198812 11 8.55 10.26 11.97 30780 36936 43092 2178 216312 12 9.50 11.40 13.30 34200 41040 47880 2178 233814 07 6.11 7.33 8.55 21996 26388 30780 2528 146314 08 7.22 8.66 10.10 25992 31176 36360 2528 163814 09 8.14 9.77 11.40 29304 35172 41040 2528 181314 10 9.06 10.88 12.69 32616 39168 45684 2528 198814 11 9.99 11.99 13.99 35964 43164 50364 2528 216314 12 11.10 13.32 15.54 39960 47952 55944 2528 233814 14 12.95 15.54 18.13 46620 55944 65268 2528 268816 08 8.35 10.02 11.69 30060 36072 42084 2878 163816 09 9.43 11.31 13.20 33948 40716 47520 2878 181316 10 10.49 12.59 14.69 37764 45324 52884 2878 198816 11 11.57 13.88 16.19 41652 49968 58284 2878 216316 12 12.85 15.42 17.99 46260 55512 64764 2878 233816 14 14.99 17.99 20.99 53964 64764 75564 2878 268818 10 11.92 14.31 16.69 42912 51516 60084 3228 198818 11 13.28 15.93 18.59 47808 57348 66924 3228 216318 12 14.60 17.52 20.44 52560 63072 73584 3228 233818 14 17.21 20.65 24.09 61956 74340 86724 3228 268820 14 19.25 23.10 26.95 69300 83160 97020 3578 268822 14 21.29 25.55 29.80 76644 91980 107280 3928 2688

(1) Assumes drain pans, if no drain pans are present then base can be removed and overall hieght reduced.With 25 mm panels - to obtain dimensions with 50 mm panels, add 50 mm.

(2) Unit sizes only available as selections from the factory.

Page 88: Train Instrument's

86PROD-PRC014-E4

Customer benefits • High flexibility: customized system to fit the application

exact requirements• Clean concept: highest level of indoor air quality

unmatched in the market place• High reliability: very low maintenance costs

Main features• Modular casing construction specially designed for

hospitals, process and clean room applications• High flexibility on configuration, materials, components

and options• Eurovent certified range in accordance with EN 1886

3SE: 2A/B/F9/T4/TB3 - 5SE: 2A/B/F9/T3/TB35SET2: 2A/B/F9/T2/TB2

• Class C Air leakage in accordance with BS / DW144 andEurovent 2/2 with hygienic seals (0.42 l/s/m² at 2000 Pa)

• Bolted casing made of 30 mm or 50 mm self supportingpanels

• Panel insulation made of non-combustible (M0) and highdensity (70 kg/m3) rock wool, mechanically fixed to thepartitions

• Smooth internal walls and inclined drain pans• Units supplied with a 100 mm high sub-base• Available sections: panel and bag filters, absolute (HEPA)

filters, activated carbon filters, auto-roll filter,FC/BI/Aerofoil centrifugal fans, plug fans, water coils, DXcoil, electric heaters, steam coils, condensing coils, airwashers, steam humidifiers, evaporative humidifiers,plate heat exchangers, thermal wheels, heat pipes, runaround coils, silencers, mixing chambers, multi-zonesection.

• Tracer Summit™ capabilities

Options• ATEX certified construction; group II, category 2 and 3• Other unit sizes for air volumes up to 250 000 m3/h

(70 m3/s) upon request• Outdoor construction with hoods, louvers and roof• Panel material: PVC coating, aluminium, stainless steel• Flat packed delivery• Hygienic execution with inner parts in stainless steel,

inclined floor and anti-bacteriologic seals • Vertical units

Accessories• Inspection windows and wired lights• Manometers • Flexible connections, sand trap louvers• Motor lifting beam, adjustable legs

Controls*• Factory-mounted control including selection, fitting and

wiring of the controls components such as valves forcoils, damper actuators, temperature and pressuresensors, controller, air pressure switch, anti-frostthermostat

• Power wiring, frequency invertors• Commissioning

Indoor and outdoorUnlimited number of unit sizes1 000 - 132 000 m3/h (0.2 - 36 m3/s)*

Air handling units

CCEA

CCEA

* Available in certain countries. For information, contact your local Trane Sales Office.

Page 89: Train Instrument's

Unit size 2.5 3.0 3.5 2.5 3.0 3.5 Width Height

0.5 0.30 0.36 0.42 1 069 1 283 1 497 670 4250.75 0.49 0.59 0.69 1 774 2 129 2 483 975 4251 0.59 0.71 0.83 2 138 2 566 2 994 670 7301 F 0.70 0.84 0.98 2 515 3 018 3 521 1280 4251.5 0.99 1.18 1.38 3 548 4 257 4 967 975 7302 1.38 1.65 1.93 4 957 5 949 6 940 1280 7302.25 1.50 1.80 2.10 5 405 6 486 7 568 975 10352.5 1.77 2.12 2.48 6 367 7 640 8 913 1585 7303 2.14 2.57 3.00 7 711 9 253 10 796 1280 10353.75 F 2.75 3.30 3.85 9 904 11 884 13 865 1585 10354 2.86 3.44 4.01 10 311 12 374 14 436 1280 13404.50 F 3.35 4.02 4.69 12 058 14 470 16 881 1890 10755 3.73 4.48 5.23 13 441 16 129 18 817 1585 13806 4.55 5.46 6.36 16 365 19 638 22 911 1890 13806.25 4.64 5.57 6.50 16 718 20 062 23 406 1585 16857 F 5.42 6.50 7.58 19 494 23 393 27 292 2195 13807.5 5.74 6.89 8.04 20 671 24 805 28 940 1890 16858 F 6.21 7.46 8.70 22 367 26 840 31 314 2500 13808.75 6.84 8.21 9.58 24 624 29 549 34 474 2195 16859 6.83 8.20 9.56 24 586 29 503 34 421 1890 199010 7.85 9.42 10.99 28 253 33 903 39 554 2500 168510.5 8.16 9.79 11.42 29 363 35 235 41 108 2195 199011.25 F (2) 8.95 10.74 12.52 32 206 38 647 45 088 2845 172512 9.48 11.38 13.28 34 139 40 967 47 794 2500 199012.25 (2) 9.56 11.48 13.39 34 425 41 310 48 195 2235 233512.50 F (2) 10.04 12.05 14.06 36 158 43 390 50 622 3150 172513.5 (2) 10.81 12.97 15.13 38 915 46 698 54 481 2845 203014 (2) 11.12 13.34 15.57 40 025 48 030 56 035 2540 233515 (2) 12.14 14.56 16.99 43 691 52 430 61 168 3150 203015.75 (2) 12.67 15.21 17.74 45 625 54 750 63 874 2845 233516 (2) 12.57 15.08 17.60 45 247 54 296 63 345 2540 264016.5 (2) 13.44 16.13 18.82 48 389 58 067 67 745 3455 203017.5 (2) 14.23 17.07 19.92 51 224 61 469 71 714 3150 233518 (2) 14.16 17.00 19.83 50 992 61 191 71 389 2845 264018 F (2) 14.79 17.75 20.71 53 244 63 893 74 542 3760 203019.25 F (2) 15.76 18.91 22.06 56 732 68 079 79 425 3455 233519.50 F (2) 16.10 19.31 22.53 57 942 69 530 81 119 4065 203020 (2) 15.90 19.08 22.26 57 251 68 701 80 151 3150 264021 F (2) 17.34 20.81 24.28 62 424 74 909 87 394 3760 233522 (2) 17.61 21.14 24.66 63 407 76 088 88 770 3455 264022.75 F (2) 18.87 22.64 26.42 67 932 81 518 95 105 4065 233524 (2) 19.38 23.26 27.13 69 768 83 722 97 675 3760 264024.50 F (2) 19.20 23.04 26.88 69 120 82 944 96 768 4370 233526 (2) 21.09 25.31 29.53 75 924 91 109 106 294 4065 264026.25 F (2) 20.64 24.77 28.90 74 304 89 165 104 026 4675 233528 (2) 22.80 27.36 31.92 82 080 98 496 114 912 4370 264030 (2) 24.51 29.41 34.31 88 236 105 883 123 530 4675 264032 (2) 26.22 31.46 36.71 94 392 113 270 132 149 4980 2640

(1) Overall dimensions are given for 30 mm panels from size 0,5 to 10,5 + size 12 and for 50 mm panels from size 12,25 to 32 + 11,25(includes 100 mm high base frame)

(2) Unit size available with 50 mm self supporting panels only

Dimensions (mm) (1)

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

s

CC

EA

87

Page 90: Train Instrument's

88PROD-PRC014-E4

Customer benefits• Flexibility: adaptable system to fit the customer's exact

requirements• Easy installation via modular construction and special

breakpoint design: saving of time• Cleanable "Clean concept" unit: high level of indoor air

quality

Main features• Framework manufactured with extruded anti-corrosion

aluminium profiles, fitted together with nylon fiber glass-stiffened angles

• Exclusive panel fixing system, by panel-lock aluminiumprofile, avoiding internal screw and point where dust canaccumulate, and double panel gasket

• Panels with 2 seals for optimum airtightness• 25 or 50 mm external sandwich-type panels, made of

galvanised or pre-pained, peralluman, anodised alumini-um, stainless steel 304 or 316 metal sheet, factory insu-lated with polyurethane foam (40 kg/m3 density)

• Dampers manufactured by extruded anticorodalaluminium

• Coil mounted on rails for easy removal• Sloped drain pain made of stainless steel• Electrical motor and fan frame mounted on spring shock

absorber and provided of flexible duct connection• Electrical motor mounted on micrometric belt-tensioning

slide

• Available sections: plenum, mixing, double mixing,panel filters, soft and rigid bag filters, HEPA filters, rollfilters, water cooling and heating coils, DX and condens-er coils, electrical heaters, gas burner heaters, honey-comb through away or with pump humidification, waterthrough away or with pump nozzles humidification, aircompressed or water compressed nozzles humidificationcomplete of cabinet, steam humidification complete ofsteam generator, fan section with forward curved, back-ward inclined, airfoil blades, plug fans, plate heatexchanger, thermal wheel, run around coil loop, heatpipes, sound attenuator, multizone

Options• Framework with thermal break profile• One-piece supporting base• Panel metal sheet: thickness 1.2, 1.5, 2 mm• Panel thickness 100 mm• Panel thermal insulation by glass wool, 80 kg/m3 density• Unit delivered disassembled• Hygenic version - for applications requiring high air

quality level (hospitals, clean rooms, food and pharma-ceutical industries) provided of construction features andspecial components allowing a complete cleaning andsterilization of the unit

Accessories• Water-proof lamps with external switch and inspection

windows• Lateral technical box • Differential pressure switch and monometers• Disconnecting switch or power panel factory mounted

and wired• Damper servomotors

Indoor and outdoor30 sizes - 1 000 - 140 000 m3/h(0.2 - 38 m3/s)*

Air handling units

CCTA

CCTA

AH

U 0

3-12

-047

RA

NG

E C

CTA

"Clean concept" version design

* Available in certain countries. For information, contact your local Trane Sales Office.

Page 91: Train Instrument's

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

s

CC

TA

89

Dimensions (mm) (1)

Unit size 2.5 3.0 3.5 2.5 3.0 3.5 Width (2) Height

Single fan air handling units

004 0.30 0.36 0.42 1080 1296 1512 690 590005 0.45 0.54 0.63 1620 1944 2268 790 640007 0.63 0.76 0.88 2268 2722 3175 890 690009 0.79 0.95 1.10 2835 3402 3969 1040 790012 1.08 1.30 1.51 3888 4666 5443 1090 890015 1.28 1.54 1.80 4617 5540 6464 1240 990018 1.55 1.86 2.17 5589 6707 7825 1440 990023 1.90 2.28 2.66 6831 8197 9563 1440 1040025 2.15 2.57 3.00 7722 9266 10811 1590 1140030 2.54 3.04 3.55 9126 10951 12776 1590 1140035 3.04 3.65 4.25 10935 13122 15309 1640 1340040 3.38 4.05 4.73 12150 14580 17010 1790 1340044 3.71 4.46 5.20 13365 16038 18711 1990 1340050 4.21 5.05 5.89 15147 18176 21206 1990 1440055 4.59 5.51 6.43 16524 19829 23134 2140 1440062 5.13 6.16 7.18 18468 22162 25855 2140 1590074 6.27 7.52 8.78 22572 27086 31601 2580 1630083 6.93 8.32 9.70 24948 29938 34927 2580 1630090 7.56 9.07 10.58 27216 32659 38102 2780 1630105 8.80 10.56 12.32 31671 38005 44339 2930 1780115 9.72 11.66 13.61 34992 41990 48989 3080 1780121 10.50 12.60 14.70 37800 45360 52920 3080 1780135 11.34 13.61 15.88 40824 48989 57154 3530 1780146 12.35 14.82 17.29 44469 53363 62257 3430 1940173 14.40 17.28 20.16 51840 62208 72576 3580 2130187 15.75 18.90 22.05 56700 68040 79380 3880 2130211 17.76 21.31 24.86 63936 76723 89510 4080 2280243 20.40 24.48 28.56 73440 88128 102816 4630 2280280 23.51 28.22 32.92 84645 101574 118503 5130 2300333 27.80 33.35 38.91 100062 120074 140087 5830 2360

Double fan air handling units

004 0.30 0.36 0.42 1080 1296 1512 790 540005 0.45 0.54 0.63 1620 1944 2268 890 540007 0.60 0.72 0.84 2160 2592 3024 1090 590009 0.77 0.92 1.07 2754 3305 3856 1140 640012 1.04 1.24 1.45 3726 4471 5216 1440 640015 1.26 1.51 1.76 4536 5443 6350 1490 690018 1.50 1.80 2.10 5400 6480 7560 1540 790023 1.89 2.27 2.65 6804 8165 9526 1690 840025 2.16 2.59 3.02 7776 9331 10886 1890 840030 2.55 3.06 3.57 9180 11016 12852 1990 890035 2.97 3.56 4.16 10692 12830 14969 2090 940040 3.42 4.10 4.79 12312 14774 17237 2190 990044 3.69 4.43 5.17 13284 15941 18598 2390 990050 4.29 5.15 6.01 15444 18533 21622 2540 1040055 4.62 5.54 6.47 16632 19958 23285 2540 1140062 5.18 6.21 7.25 18630 22356 26082 2640 1190074 6.24 7.49 8.74 22464 26957 31450 2980 1280083 6.96 8.35 9.74 25056 30067 35078 3280 1280090 7.52 9.03 10.53 27081 32497 37913 3330 1380105 8.80 10.56 12.32 31671 38005 44339 3830 1380115 9.60 11.52 13.44 34560 41472 48384 3580 1530121 10.20 12.24 14.28 36720 44064 51408 3680 1530135 11.25 13.50 15.75 40500 48600 56700 4130 1530146 12.29 14.74 17.20 44226 53071 61916 4280 1580173 14.49 17.39 20.29 52164 62597 73030 4580 1730187 15.70 18.84 21.98 56511 67813 79115 4930 1730211 17.63 21.15 24.68 63450 76140 88830 5080 1830243 20.28 24.34 28.39 73008 87610 102211 5580 1880280 23.52 28.22 32.93 84672 101606 118541 5980 2030333 27.97 33.56 39.15 100683 120820 140956 6030 2330

(1) With 25 mm panels units until 062 size and 50 mm panels units for bigger units. Unit height does not include feet or continuous base frame.Height of feet or base frame is 150 mm. Overall cross dimensions can vary according to casing option and components.

(2) The width of the units can be adjusted in steps of 50 mm to suit project specifications.

Page 92: Train Instrument's

90PROD-PRC014-E4

Customer benefits • Innovative design with full side accessibility for

maintenance and disinfection• Easy power and controls wiring with purposed design

channel• Cleanable unit providing high level of indoor air quality• Saving of time with factory-mounted controls

Main features• Enhanced thermal and acoustical performances due to

50 mm self-supporting panels design.• Absence of casing structure providing a minimised

thermal bridges construction.• "Clean concept"- The smooth internal walls make interior cleaning easy

and quick.- Standard drain pans are inclined, insulated and easily

removable without removing the coils and the pipework.

- Drain pans with vertical outlet to ensure a completedrainage.

• Casing panels insulated with 40, 90 or 100 kg/m3 rockwool density

• Eurovent certified range with enhanced mechanicalcharacteristics :

- Classes D2/L2/F9/T2/TB2 as standard- Classes D2/L1/F9/T2/TB2 optionally

• Easy maintenance with full access to internalcomponents via sliding and removable side panels

• Casing construction without weld spots providing highresistance to corrosion

• All components are easily removable due to electric andhydraulic connections located in the technical channel atthe upper part of the unit.

Options• Stainless steel panels, condensate trays, fan motor

assemblies, filter frame, base frame• Panel material: stainless steel, PVC-coated steel• Polyurethane or polystyrene insulation

Accessories• Inspection windows and light inside of the section• Inclined manometer and pressostat• Flexible connections• Intake hoods

Control• Factory-mounted control featuring: valves for coils,

servomotor for dampers, temperature and pressuresensor, controller, air pressure switch, anti-frostthermostat, frequency inverter

• Power control• Commissioning by Trane experts

Indoor and outdoor6 sizes - 1 000 - 18 000 m3/h(0.2 - 5 m3/s)*

Air handling units

CCH

* Available in certain countries. For information, contact your local Trane Sales Office.

CCH

AH

U 0

1-09

-034

RA

NG

E C

CH

Airtight sliding doors

Page 93: Train Instrument's

Unit size 2.0 2.8 3.2 2.0 2.8 3.2 Width Height

05 0.39 0.55 0.62 1405 1968 2249 995 77010 0.78 1.09 1.25 2811 3935 4497 995 105515 1.17 1.64 1.87 4216 5903 6746 1315 105520 1.56 2.19 2.50 5622 7870 8995 1635 110530 2.34 3.28 3.75 8433 11806 13492 1635 137540 3.12 4.37 5.00 11244 15741 17990 1635 1695

Dimensions (mm)

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

s

CC

H

91

Page 94: Train Instrument's

92PROD-PRC014-E4

Customer benefits • Flexibility: customized system to fit the application exact

requirements• Easy installation: saving of time

Main features• Self-supporting framework in extruded aluminium

profiles assembled by die cast aluminium corners togive accurate alignment and easily cleanable corrosionresistant structure

• Sandwich type double skin panels with internal thermalinsulation of phenolic resin, polyurethane plates, mineralwool or special high density thermal and acousticinsulation

• Two panel thicknesses - 23 mm and 43 mm• External and internal sheet metal faces of the panel can

be selected from galvanized or Aluzinc steel sheet0.6 mm thick, plastic-coated galvanized steel sheet0.5 mm thick, aluminium sheet 0.7 mm thick or stainlesssteel A151 304

• External and internal faces can be made of differentmaterials

Options• "Thermal cutting profile", 50 and 60 TTC type, and

23 mm and 46 mm panels• Inspection windows• Bulkhead lights with or without external switch• Key operated safety door handles• Filter manometers

Accessories• Anti-vibration connections• Sound attenuators• Germicidal lamps section• Internal lighting system

Trane's CCVB range of air handling

units An economic series of units limited to 9 sizes (1 000 -10 000 m3/h) that, in certain cases may be a validalternative to the CCVA series. For more information,contact your local sales office.

Indoor and outdoor19 sizes - 1 200 - 86 000 m3/h(0.3 - 23 m3/s)*

Air handling units

CCVA

* Available in certain countries. For information, contact your local Trane Sales Office.

CCVA

Page 95: Train Instrument's

Unit size 2.0 2.5 3.0 2.0 2.5 3.0 Width Height (1)

13 0.28 0.36 0.43 1000 1300 1550 680 57516 0.35 0.44 0.53 1250 1600 1900 760 57520 0.44 0.56 0.67 1600 2000 2400 820 63525 0.56 0.69 0.83 2000 2500 3000 820 75530 0.69 0.83 1.06 2500 3000 3800 940 75540 0.89 1.11 1.28 3200 4000 4600 1000 81550 1.11 1.39 1.67 4000 5000 6000 1180 81560 1.39 1.67 2.08 5000 6000 7500 1260 93580 1.72 2.22 2.56 6200 8000 9200 1500 1055100 2.11 2.78 3.19 7600 10000 11500 1600 1160120 2.64 3.33 3.89 9500 12000 14000 1700 1175150 3.33 4.17 5.00 12000 15000 18000 1800 1355190 4.17 5.28 6.11 15000 19000 22000 2060 1560240 5.00 6.67 7.78 18000 24000 28000 2120 1655300 6.39 8.33 9.72 23000 30000 35000 2400 1920360 8.33 10.00 11.67 30000 36000 42000 2740 2120

Single or twin fan units

460 10.00 12.78 15.28 36000 46000 55000 3340 1940580 12.50 16.11 19.44 45000 58000 70000 3640 2180720 15.56 20.00 23.89 56000 72000 86000 4240 2300

(1) Unit height does not include feet or continuous base frame. Feet and base frame are available with height of 100 mm or 140 mm.

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

sC

CV

A

93

Dimensions (mm)

Page 96: Train Instrument's

CCSA

94PROD-PRC014-E4

Customer benefits• High flexibility : non-standard designs and dimensions

are possible to suit exact customer requirements.• Fast assembly, easy accessibility: saving of time

Main features• Modular construction for 19 models with flow rates from

1 800 m3/h to 120 000 m3/h• Framework manufactured with extruded anti-corrosion

aluminium profiles, fitted with injection moulded,rounded aluminium corner pieces with special seals addstrength and rigidity to the module frame

• Side panels are composed of film coated paintedgalvanized sheet metal exterior walls and galvanizedinterior walls (aluminium or stainless steel upon request)fully sealed in a closed structure

• Polyurethane is injected between the walls of the panel(can be filled with rockwool or glasswool upon request)in 6 different thicknesses to provide heat and soundinsulation

• The connections are made either by bolts (20-30-40-50 mm) or by special fitted joints (23-33 mm)

• Smooth internal and external surfaces (40-50 mm)• Available sections: panel and bag filters, HEPA filters,

activated carbon filters, auto roll and rotary filters,FC/BI/Airfoil and plug fans, water and DX coils, electricheaters, steam and evaporative humidifiers, plate/rotarytype heat recoveries, run around coils, heat pipes,silencers, mixing boxes

• Tracer SummitTM capabilities

Options• Panels made of PVC coated galvanized steels, anodized

aluminium or stainless steel AISI 304 or 316• Hygienic version for applications requiring high air

quality• The standard color of the frame is RAL 2002 (poppy red),

the panel is RAL 9002 (white-grey). They may be alteredupon request.

• Panel thickness of 20-23-30-33-40-50 mm

Accessories• Wired light• Inspection window• Roof for outdoor installations• Air outlet or inlet screen to prevent water entering into

the unit• Differential manometer to measure the pressure drop

across the filter • Belt and pulley system guard from galvanized sheet

metal • Disconnect switch or power panel factory-wired to the

motor

Indoor and outdoor19 sizes - 1 800 - 120 000 m3/h(0.5 - 33 m3/s)*

Air handling units

CCSA

* Available in certain countries. For information, contact your local Trane Sales Office.

Page 97: Train Instrument's

Airflow (m3/s)

at coil face velocity (m/s)

Airflow (m3/h)

at coil face velocity (m/s)

General data

PROD-PRC014-E4

Air

S

ystem

sC

CS

A

95

Dimensions (mm)

Unit size 2.5 3.0 3.5 2.5 3.0 3.5 Width Height

080 X 080 0.53 0.63 0.74 1 890 2 268 2 646 762 762110 X 080 0.83 0.99 1.16 2 970 3 564 4 158 1 080 762110 X 110 1.43 1.71 2.00 5 130 6 156 7 182 1 080 1 080140 X 110 2.00 2.40 2.80 7 200 8 640 10 080 1 414 1 080140 X 140 2.83 3.39 3.96 10 170 12 204 14 238 1 414 1 414170 X 140 3.65 4.38 5.11 13 140 15 768 18 396 1 750 1 414170 X 170 4.73 5.67 6.62 17 010 20 412 23 814 1 750 1 750200 X 170 5.50 6.60 7.70 19 800 23 760 27 720 1 986 1 750200 X 200 6.50 7.80 9.10 23 400 28 080 32 760 1 986 1 986230 X 200 7.75 9.30 10.85 27 900 33 480 39 060 2 292 1 986230 X 230 8.93 10.71 12.50 32 130 38 556 44 982 2 292 2 292260 X 230 10.73 12.87 15.02 38 610 46 332 54 054 2 598 2 292290 X 230 12.15 14.58 17.01 43 740 52 488 61 236 2 904 2 292320 X 230 13.58 16.29 19.01 48 870 58 644 68 418 3 210 2 292350 X 230 15.00 18.00 21.00 54 000 64 800 75 600 3 516 2 292410 X 230 17.85 21.42 24.99 64 260 77 112 89 964 4 128 2 292440 X 230 19.30 23.16 27.02 69 480 83 376 97 272 4 434 2 292470 X 230 20.75 24.90 29.05 74 700 89 640 104 580 4 740 2 292540 X 230 23.85 28.62 33.39 85 860 103 032 120 204 5 352 2 292

Page 98: Train Instrument's

96PROD-PRC014-E4

Customer benefits • Comfort: optimal building occupant comfort• Flexibility: easy adaptation of building evolutions• High performance: low energy consumption

Main features• Capable of varying the amount of air in an unlimited

number of zones• Simple and rugged design• 0 to 3.8 m3/s• Interlocking panel design• Metal encapsulated edges• Low height units• Proven flow ring• Linear flow response in controller logic• Tracer Summit™ capabilities

Options• Series or parallel terminal fan• Hot water coil• Electric terminal reheat• Foil face insulation• Close cell insulation• Choice of factory-mounted control• Outlet plenum

Unlimited number of zones

Variable Air Volume Systems

VariTrane™

Single Duct Unit VCCF Series Fan Powered VSCF

Page 99: Train Instrument's

General data

PROD-PRC014-E4

Single and Dual Duct Units VCCF, VCWF, VCEF, VDDF

Air Valve Size 4 5 6 8 10 12 14 16 24x16

Inlet Diameter (mm) 105 127 152 203 254 305 356 406 610x406

Primary Airflow (m3/s) 0.106 0.165 0.236 0.425 0.661 0.944 1.416 1.888 3.776

Parallel Fan Powered Units VPCF, VPWF, VPEF

Unit size 06-0317 08-0317 10-0317 12-0317 08-0417 10-0417 12-0417 14-0417

Fan Airflow (m3/s) 0.425 0.425 0.425 0.425 0.535 0.535 0.535 0.535

Primary Airflow (m3/s) 0.236 0.425 0.661 0.944 0.425 0.661 0.944 1.416

Unit size 10-0517 12-0517 14-0517 12-06 14-06 16-06 14-07 16-07

Fan Airflow (m3/s) 0.565 0.565 0.565 0.685 0.685 0.685 0.836 0.826

Primary Airflow (m3/s) 0.661 0.944 1.416 0.944 1.416 1.888 1.416 1.888

Series Fan Powered Units VSCF, VSWF, VSEF

Unit size 05-01 06-01 08-01 06-02 08-02 10-02 06-0317 08-0317 10-0317 12-0317 06-0417 08-0417

Fan Airflow (m3/s) 0.2 0.2 0.2 0.275 0.275 0.275 0.445 0.445 0.445 0.445 0.635 0.635

Primary Airflow (m3/s) 0.165 0.236 0.425 0.236 0.425 0.661 0.236 0.425 0.661 0.944 0.236 0.425

Unit size 10-0417 12-0417 14-0417 10-0517 12-0517 14-0517 10-06 12-06 14-06 16-06 12-07 14-07 16-07

Fan Airflow (m3/s) 0.635 0.635 0.635 0.745 0.745 0.745 1.155 1.155 1.155 1.155 1.189 1.189 1.189

Primary Airflow (m3/s) 0.661 0.944 1.416 0.661 0.944 1.416 0.661 0.944 1.416 1.888 0.944 1.416 1.888

Series Fan Powered Series Fan Powered Parallel Fan Powered

Low Height Units LSCF, LSWF, LSEF LPCF, LPWF, LPEF

Unit size 0608 0808 0809 14RT09 14RT10 0608 0808 0810 14RT10

Fan Airflow (m3/s) 0.378 0.378 0.850 0.519 0.850 0.378 0.378 0.850 0.850

Primary Airflow (m3/s) 0.236 0.425 0.425 0.944 0.944 0.236 0.425 0.425 0.944

Air

S

ystem

sV

ariT

ran

e™

97

Page 100: Train Instrument's

98PROD-PRC014-E4

Customer benefits- Linear Diffusers• Comfort: optimal building occupant comfort• Easy installation: saving of time• Noise level: a level of acoustic comfort unmatched in the

market place

Customer benefits - Cassette Diffusers• Easy integration: saving of space• Comfort: optimal building occupant comfort

Main features - Linear Diffusers• Optimum use of the Coanda Effect

- Suitable for VAV application- Reduces the risk of dumping- High induction effect

• Internal closed cell insulation• Thermal and acoustic insulation• Removable plenum box for easy cleaning• Flexible design • Aluminium extruded profiles• Furnace-baked epoxy enamel

Main features - Cassette Diffusers• Dimensions : 600 x 600 mm• Uses existing false ceiling panels, allowing for homoge-

nous ceiling color and design• Manually adjustable airflow direction, from horizontal to

vertical• Internal thermal and acoustic insulation

- Made of melamine- Does not create dust particles

• Unpainted galvanized steel casing• Painted aluminium frame

Accessories - Linear Diffusers• Balancing damper

Linear and cassette diffusers

Variable Air Volume Systems

VDLE-VRLECassette

VDLE-VRLECassette

Page 101: Train Instrument's

General data

PROD-PRC014-E4

X

Y

X X

Y

(mm) (mm) (mm) (m3/s) (m) (Pa)

VDLE A 1 Slot 1 way 600 236 or 316 125 0.033 4.5 20

VDLE A 1 Slot 1 way 1200 236 or 316 160 0.066 4.5 37

VDLE A 1 Slot 1 way 1500 236 or 316 160 0.083 4.5 37

VDLE B 2 Slot 1 way 600 316 160 0.066 6 34

VDLE B 2 Slot 1 way 1200 316 200 0.130 6 40

VDLE B 2 Slot 1 way 1500 316 200 0.166 6 36

VDLE C 3 Slot 1 way 600 356 200 0.100 8 26

VDLE C 3 Slot 1 way 1200 356 250 0.200 8 30

VDLE C 3 Slot 1 way 1500 356 250 0.250 8 31

VDLE D 2 Slot 2 way 600 236, 316 or 356 160 0.066 4.5 24

VDLE D 2 Slot 2 way 1200 236, 316 or 356 200 0.130 4.5 29

VDLE D 2 Slot 2 way 1500 236, 316 or 356 200 0.166 4.5 30

VDLE E/F 3 Slot 2 way 600 356 200 0.100 4.5/6 (1) 20

VDLE E/F 3 Slot 2 way 1200 356 250 0.200 4.5/6 (1) 23

VDLE E/F 3 Slot 2 way 1500 356 250 0.250 4.5/6 (1) 26

VDLE G 4 Slot 2 way 600 356 200 0.130 6 20

VDLE G 4 Slot 2 way 1200 356 250 0.266 6 24

VDLE G 4 Slot 2 way 1500 356 250 0.333 6 32

Cassette Square 600 95 200 0.153 3.5 -

(1) 4.5 m on the 1-slot side, 6 m on the 2-slot side

Unit

type

Arrangement Inlet

Diameter

Maximum

Airflow

Maximum

Throw

Pressure

Drop

X Y

Air

S

ystem

s

Dif

fuse

rs

99

Page 102: Train Instrument's

100PROD-PRC014-E4

OUTDOOR CHILLERS

Page 103: Train Instrument's

50kW 100 200 400 1200 1600300 500 1000 1400

1500400

250 650 RTAD

RTAC

50 265 CGAN

19 30 VGA

19 63 CXA

PROD-PRC014-E4

New

• CGAN/CXAN ranges extended to 460 kW

• RTAD with free-cooling option

• RTAD with heat recovery option

Light Commercial, Commercial andIndustrial Applications

OUTDOOR CHILLERS19 - 1500 KW

101101

WA

TE

R S

YS

TE

MS

19 30 VXA

49 250 CXAN

19 61 CGA

280 460 CGAN

270 450 CXAN

Page 104: Train Instrument's

CGA/VGA/CXA/VXA

102PROD-PRC014-E4

Customer benefits• Packaged hydraulic module for easier installation: saving

of time• Low Sound version for sensitive environment: a high

level of acoustic comfort• Minimum maintenance requirement: saving of time and

money

Main features• Scroll compressor featuring:

- Sound-proofing- Protection of motor winding- Crankcase heater- Thermo-magnetic circuit breaker (1 compressor on

sizes 075 to 120, 2 compressors on sizes 150 to 240)• Axial fans with completely integrated low noise level

(1 fan on sizes 075 to 120, 2 fans on sizes 150 to 240)• Stainless steel water heat exchangers equipped with

heating resistors• Black epoxy-coated aluminium fins with copper tubes• Cooling circuits with:

- Thermostatic expansion valve(s)Liquid line filter drier(s)

- High and low pressure cut-outs- 1 circuit on sizes 075 to 120, 2 circuits on sizes 150 to

240- Factory oil and refrigerant charges

• Disconnect switch• Flow switch

Options• Water outlet low temperature (-5°C to -10°C)

Accessories• Low ambient speed controller (CGA only)• Remote control module• HDM hydraulic module for CGA sizes 150 to 240• High and low pressure gauges

ControlMicroprocessor control module featuring:• Control of return water temperature• Liquid crystal display indicating:

- Return water temperature- Codes of any faults

• Control of operating parameters• Possibility of remote fault signaling on 24V indicator

light• Antifreeze protection of evaporators• 24V dry contacts for remote signaling of on/off,

heating/cooling mode and general fault

Axial fans, scroll compressor19-61 kW*

Outdoor chillers

Microchiller controlinterface

* Also available with R22 for applications outside of the European Union. For information, contact your local Trane Sales Office.

CGA: Cooling-onlyVGA: Cooling-only with hydraulic moduleCXA: Heat pumpVXA: Heat pump with hydraulic module

CGA/VGA/

CXA/VXA

Page 105: Train Instrument's

General data CGA/VGA

PROD-PRC014-E4

Water S

ystem

sC

GA

/VG

A/C

XA

/VX

A

103

Unit size 075 100 120 150 200 240

CGA

Cooling capacity (1) (kW) 19.2 25.2 31.7 38.6 50.9 64

Cooling power input (2) (kW) 6.8 9.3 12.8 13.5 18.5 25.4

Cooling Energy Efficiency Ratio 2.82 2.71 2.48 2.86 2.75 2.52

VGA

Cooling capacity (1) (kW) 19.2 25.2 31.7 - - -

Cooling power input (2) (kW) 6.8 9.3 12.8 - - -

Cooling Energy Efficiency Ratio 2.82 2.71 2.48 - - -

Refrigerant R407C

Number of

refrigerant circuits 1 1 1 2 2 2

Refrigerant charge (kg) 5.0 5.2 7.5 5.3 5.5 7.8

Compressor type Scroll

Number of capacity steps 1 1 1 2 2 2

Number of compressors 1 1 1 2 2 2

Evaporator type Brazed plate

Evaporator water content (l) 2.7 3.2 3.2 4.9 6.3 6.3

Evaporator water connection type ISO R7 Male

Evaporator water

connection diameter (inches) 1¼" 1¼" 1¼" 1½" 1½" 1½"

Condenser type Copper tubes with aluminium fins

Total airflow (m3/h) 9300 12000 17000 18600 24000 34000

Number of fans 1 1 1 2 2 2

Fan speed (rpm) 650 710 710 650 710 710

Sound power level (dB(A)) 76 78 82 78 80 85

Minimum operating

outdoor air temperature (°C) +15 (-10 with low ambient option)

Maximum operating

outdoor air temperature (2) (°C) +45

Minimum leaving

water temperature (°C) -4 (-12 as option)

Maximum leaving

water temperature (°C) +12

(1) At Eurovent conditions (cooling water: 12°C/7°C - air: 35°C)(2) Cooling: water 12/7°C

Page 106: Train Instrument's

104PROD-PRC014-E4

General data CXA/VXA

Unit size 075 100 120 150 200 240

CXA

Cooling capacity (1) (kW) 19 25 30.7 38.3 50.4 63.5

Cooling power input (2) (kW) 6.8 9.2 13.2 13.3 18.2 25

Cooling Coefficient of Performance 2.79 2.72 2.33 2.88 2.77 2.54

Heating capacity (kW) 19 25.4 31.3 38.1 50.9 62.5

Heating power input (kW) 8.1 10.7 14.1 16 21.2 28

Heating Coefficient of Performance 2.35 2.37 2.22 2.38 2.4 2.23

VXA

Cooling capacity (1) (kW) 19 25 30.7 - - -

Cooling power input (2) (kW) 6.8 9.2 13.2 - - -

Cooling Coefficient of Performance 2.79 2.72 2.33 - - -

Heating capacity (kW) 19 25.4 31.3 - - -

Heating power input (kW) 8.1 10.7 14.1 - - -

Heating Coefficient of Performance 2.35 2.37 2.22 - - -

Refrigerant R407C

Number of refrigerant circuits 1 1 1 2 2 2

Refrigerant charge (kg) 5.7 5.7 8.7 12 12 18

Compressor type Scroll

Number of capacity steps 1 1 1 2 2 2

Number of compressors 1 1 1 2 2 2

Evaporator type Brazed plate

Evaporator water content (l) 2.7 3.2 3.2 4.9 6.3 6.3

Evaporator water connection type ISO R7 Male

Evaporator water connection diameter (inches) 1¼" 1¼" 1¼" 1½" 1½" 1½"

Condenser type Copper tubes with aluminium fins

Total Airflow (m3/h) 9300 12000 17000 18600 24000 34000

Number of fans 1 1 1 2 2 2

Fan speed (cooling only) (rpm) 650 710 710 650 710 710

Sound power level (dB(A) 76 78 82 78 80 85

Minimum operating outdoor

air temperature cooling (°C) +15

Maximum operating outdoor

air temperature cooling (°C) +45

Minimum operating outdoor

air temperature heating -15

Maximum operating outdoor

air temperature Heating +20

Minimum leaving water

temperature cooling (°C) -4 (-12 as option)

Maximum leaving water

temperature cooling (°C) +12

Minimum leaving water

temperature heating +30

Maximum leaving water

temperature heating (°C) +50

(1) At Eurovent conditions (cooling water: 12°C/7°C - air: 35°C)(2) Cooling: water 12/7°C

Page 107: Train Instrument's

Electrical data

Dimensions, weights and clearances

PROD-PRC014-E4

CGA/VGA 075 100 120 150 180 240

Power supply (V/Ph/Hz) 400/3/50Nominal (A) 16.5 21.0 26.7 32.5 41.5 52.9Start-up Amps (A) 101 133 142 117 153 167Recommended cable size (mm²) 4 6 6 10 10 16Max wire length (m) 90 90 75 90 75 75CXA/VXA 75 100 120 150 180 240

Power supply (V/Ph/Hz) 400/3/50Nominal (A) 16.7 21.2 26.9 32.6 41.6 53.0Start-up Amps (A) 101 133 142 117 153 167Recommended cable size (mm²) 4 6 6 10 10 16Max wire length (m) 90 90 75 90 75 75

Access control panel

X Y Z A B C

CGA 075 1061 952 1230 215 195 1000 1000 300

CGA 100 1061 952 1230 230 210 1000 1000 300

CGA 120 1261 1052 1230 246 226 1000 1000 300

CGA 150 2200 1050 1230 429 394 1000 300 1000

CGA 200 2200 1050 1230 459 424 1000 300 1000

CGA 240 2200 1050 1230 490 455 1000 300 1000

VGA 075 1061 952 1732 419 399 1000 1000 300

VGA 100 1061 952 1732 434 414 1000 1000 300

VGA 120 1261 1052 1732 450 430 1000 1000 300

CXA 075 1061 952 1230 221 201 1000 1000 300

CXA 100 1061 952 1230 236 216 1000 1000 300

CXA 120 1261 1052 1230 252 232 1000 1000 300

CXA 150 2200 1050 1230 441 406 1000 300 1000

CXA 200 2200 1050 1230 471 436 1000 300 1000

CXA 240 2200 1050 1230 503 468 1000 300 1000

VXA 075 1061 952 1732 419 405 1000 1000 300

VXA 100 1061 952 1732 434 420 1000 1000 300

VXA 120 1261 1052 1732 450 436 1000 1000 300

(1) Without options or accessories

Dimensions (1) (mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size

Weights (1)

C

B

B

A

Z

XY

Water S

ystem

sC

GA

/VG

A/C

XA

/VX

A

105

Page 108: Train Instrument's

106106PROD-PRC014-E4

Evaporator water pressure drop

Water Flow l/s

kP

a

1

10

100

0,1 1 10

075 100120

150 200240

5

20

50

2

5

0,2 0,5 2

Page 109: Train Instrument's

Water flow and manometric pump head pressure

PROD-PRC014-E4

0

2

4

6

8

10

12

14

16

18

20

0 1 2 3 4 5 6 7 8 9 100

0.1

0.2

0.3

0.4

0.5

0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.78 l/s

m3/h

Man

om

etr

ic h

ead

(m

)

Power consumption

Manometric head

Water flow

Po

wer

co

nsu

mp

tio

n (

kW

)

Water S

ystem

sC

GA

/VG

A/C

XA

/VX

A

107

VGA/VXA 075-120

Page 110: Train Instrument's

108108PROD-PRC014-E4

Performance data - CGA/VGA

Leaving ChilledWater

Temperature(°C)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Condenser Entering Air Temperature (°C)

30 35 40 45

CGA/VGA 075 19.0 5.4 17.9 6.0 16.8 6.7 15.7 7.5

CGA/VGA 100 25.0 7.4 23.6 8.3 22.1 9.4 20.5 10.5

CGA/VGA 120 31.5 9.7 29.7 10.8 27.9 12.0 25.9 13.3

5 CGA 150 38.2 10.7 36.1 12.0 33.8 13.4 31.5 14.9

CGA 200 50.5 14.9 47.6 16.7 44.6 18.8 41.4 21.1

CGA 240 63.5 19.5 60.0 21.6 56.2 24.0 52.3 26.6

CGA/VGA 075 20.3 5.5 19.2 6.1 18.0 6.8 16.8 7.6

CGA/VGA 100 26.7 7.6 25.2 8.5 23.6 9.5 21.9 10.7

CGA/VGA 120 33.6 9.9 31.7 11.0 29.7 12.2 27.6 13.6

7 CGA 150 40.8 10.9 38.6 12.2 36.2 13.6 33.7 15.1

CGA 200 53.9 15.1 50.9 17.0 47.6 19.1 44.2 21.4

CGA 240 67.8 19.9 64.0 22.1 60.0 24.5 55.8 27.1

CGA/VGA 075 21.7 5.6 20.5 6.2 19.2 6.9 17.9 7.7

CGA/VGA 100 28.5 7.7 26.9 8.6 25.2 9.7 23.4 10.8

CGA/VGA 120 35.7 10.1 33.8 11.3 31.7 12.5 29.4 13.8

9 CGA 150 43.6 11.1 41.2 12.4 38.7 13.8 36.0 15.4

CGA 200 57.4 15.4 54.2 17.3 50.8 19.4 47.1 21.7

CGA 240 72.2 20.3 68.2 22.5 63.9 24.9 59.4 27.6

(1) Compressors power input

Page 111: Train Instrument's

Performance data - CXA/VXA

PROD-PRC014-E4

Power

input (1)

(kW)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Cooling

capacity

(kW)

Power

input (1)

(kW)

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Leaving ChilledWater

Temperature(°C)

Power

input (1)

(kW)

Water S

ystem

sC

GA

/VG

A/C

XA

/VX

A

109

Cooling

Heating

Power

input (1)

(kW)

Heating

capacity

(kW)

Power

input (1)

(kW)

Heating

capacity

(kW)

Power

input (1)

(kW)

Heating

capacity

(kW)

Heating

capacity

(kW)

Leaving WaterTemperature

(C°)

Power

input (1)

(kW)

Condenser Entering Air Temperature (°C)

30 35 40 45

CXA/VXA 075 18.7 5.3 17.7 5.9 16.6 6.6 15.5 7.4

CXA/VXA 100 24.8 7.3 23.4 8.2 21.9 9.2 20.4 10.4

CXA/VXA 120 30.6 10.1 28.8 11.2 26.9 12.4 24.9 13.8

5 CXA 150 37.9 10.6 35.8 11.8 33.6 13.2 31.2 14.7

CXA 200 50.0 14.7 47.2 16.5 44.2 18.5 41.0 20.8

CXA 240 63.0 19.2 59.5 21.3 55.8 23.7 51.9 26.3

CXA 075 20.1 5.4 19.0 6.0 17.8 6.7 16.6 7.5

CXA/VXA 100 26.5 7.5 25.0 8.4 23.4 9.4 21.8 10.5

CXA/VXA 120 32.5 10.3 30.7 11.4 28.7 12.7 - -

7 CXA 150 40.5 10.8 38.3 12.0 35.9 13.4 33.5 14.9

CXA 200 53.4 14.9 50.4 16.7 47.2 18.8 43.9 21.1

CXA 240 67.2 19.6 63.5 21.7 59.5 24.1 55.4 26.8

CXA/VXA 075 21.4 5.5 20.2 6.1 19.0 6.8 17.7 7.6

CXA/VXA 100 28.2 7.6 26.6 8.5 25.0 9.5 23.2 10.7

CXA/VXA 120 34.6 10.5 32.6 11.7 30.5 13.0 - -

9 CXA 150 43.3 11.0 40.9 12.2 38.4 13.6 35.8 15.2

CXA 200 56.9 15.2 53.7 17.0 50.3 19.1 46.8 21.4

CXA 240 71.5 20.0 67.6 22.2 63.4 24.6 59.0 27.2

(1) Compressors power input

Entering Air Temperature (°C)

-4°C 0°C 7°C 15°C

CXA/VXA 075 14.7 6.7 16.0 6.7 19.2 6.7 23.4 6.7

CXA/VXA 100 19.6 8.9 21.3 8.9 25.5 8.9 31.0 9.0

CXA/VXA 120 24.3 11.0 26.2 11.1 31.5 11.2 38.4 11.6

40 CXA 150 29.4 13.3 31.9 13.3 38.3 13.3 46.8 13.3

CXA 200 39.2 17.9 42.6 17.9 51.1 17.9 62.0 18.0

CXA 240 48.5 22.1 52.4 22.2 63.0 22.5 76.7 23.0

CXA/VXA 075 14.7 7.4 15.9 7.4 19.0 7.4 23.1 7.4

CXA/VXA 100 19.8 9.9 21.3 9.9 25.4 9.9 30.7 9.9

CXA/VXA 120 24.2 12.1 26.2 12.2 31.3 12.4 37.9 12.6

45 CXA 150 29.5 14.7 31.8 14.7 38.0 14.7 46.1 14.7

CXA 200 39.5 19.7 42.7 19.7 50.9 19.7 61.4 19.7

CXA 240 48.5 24.2 52.4 24.4 62.5 24.7 75.9 25.1

CXA/VXA 075 14.8 8.2 16.0 8.2 18.9 8.2 22.8 8.2

CXA/VXA 100 19.9 11.1 21.5 11.1 25.4 11.0 30.4 11.0

CXA/VXA 120 24.3 13.4 26.1 13.5 31.0 13.7 37.4 13.9

50 CXA 150 29.7 16.4 31.9 16.4 37.8 16.4 45.6 16.4

CXA 200 39.9 22.2 42.9 22.2 50.7 22.1 60.8 22.1

CXA 240 48.5 26.9 52.2 27.0 62.0 27.3 74.8 27.7

(1) Compressors power input

Page 112: Train Instrument's

110PROD-PRC014-E4

Customer benefits • No technical room required: space saving• Outdoor or indoor use: installation flexibility and easy

maintenance• Wide range of application: flexibility to meet the

customer's exact requirements

Main features• Buffer tank• Expansion vessel: 25 liters• Drainage and filling circuit with 3 bar pressure

gauge/relief valve assembly• Strainer with removable screen• Stop valve and balancing valve• Designed for installation near Trane's CGCL, CGWH and

CCUH chillers

Options • Anti-freeze electric heater with 5m cable• Single or twin pump

Remotely installed hydraulicmodule

Outdoor chillers

HDM

HDM

Page 113: Train Instrument's

General data

PROD-PRC014-E4

Unit size HDM 1.1 HDM 2.2

Power supply (V/Ph/Hz) 400/3/50 400/3/50

Maximum water flow (l/s) 2.5 8.0

Nominal power input (kW) 1.1 2.2

Nominal amps (A) 2.7 4.9

Starting amps (A) 13.5 24.5

Expansion tank volume (l) 24 24

Water tank volume (l) 150 300

Water connection diameter (inches) 1 ½” 2 ½

Water connection type ISO R7 male

Available static pressure (1) / Water flow (kPa) 200/1.5 200/4

Dimensions

X (mm) 635 737

Y (mm) 1045 1200

Z (mm) 1300 1300

Shipping weight with single pump (kg) 250 300

Shipping weight with twin pump (kg) 280 340

(1) Single pump

Z

X

Y

Hyd

rau

lic M

od

ule

HD

M

111

Page 114: Train Instrument's

112112

CGAN/CXAN

CGAN/CXAN

PROD-PRC014-E4

Customer benefits• Packaged hydraulic module for easier installation: saving

of time• Low Sound version for sensitive environment: a high

level of acoustic comfort• Wide application flexibility for comfort and process

applications to fit the customer's exact requirements

Main features • Scroll Compressors

- Hermetic, high efficiency, low vibration, low soundlevel

- Full internal protections, internal temperature andbypass valve

- Built-in oil level sight glass and oil charging valve- Compressor sound attenuating enclosure (super quiet

units)• External sheet metal parts are galvanized and finished

with powder paint RAL 9002• Access panels are quickly removable using a square key• Disconnect switch/transformer • Waterflow switch

Options• Super quiet operation

• Integrated hydraulic module with or without buffer tank

(footprint unchanged)

• Single or double pump package• Copper fins or black epoxy-coated fins• Anti-freeze protection on waterside• 380, 400 and 415V power voltage• Phase reversal protection• High and low pressure gauges

• Soft starter up to size 300• High static pressure fans • Coil protection guards• Undersized or oversized water pump for information,

contact your local sales office• Factory-mounted LonTalk® serial link

Allowing you to:- Modify the chilled or hot water temperature setpoint- Start or stop the unit- Switch from cooling to heating mode- Monitor water temperature setpoint, ambient air tem-

perature, chiller operation, fans, water pumps, com-pressor alarms

- Trane Tracer Summit™ BMS direct compatibilityLonTalk® is an open communication protocol used on

AquaStream2 and water terminal units.

ControlMicroprocessor control module with liquid crystal displayoperator interface controlling and indicating:• Leaving water temperature• History of the last 200 defaults• Cold or hot water reset• On/off scheduling• Anti-freeze protection of evaporator, control defrost

(CXAN)• Remote control: dry contact for general fault• Inputs for external water setpoint reset, auxiliary

setpoint, and cooling/heating switch

* Also available with R22 for applications outside of the European Union. For information, contact your local Trane Sales Office.

Axial fans, scroll compressorcooling-only or heat pump models50-270 kW*

Outdoor chillers

TracerTM CH532

Page 115: Train Instrument's

General data

PROD-PRC014-E4

Unit size 200 250 300 400 450 490 500 600 700 800 900 925

Cooling capacity CGAN (1) (kW) 50.7 62.5 76.2 102.7 121.8 132.3 128.9 157.1 182.8 214.2 241.3 267.0

Cooling mode power input CGAN (1) (kW) 19.1 24.4 28.8 38.7 43.6 50.5 49.1 57.9 68.4 77.9 88.3 102.4Coefficient of Performancecooling mode CGAN (1) 2.65 2.56 2.64 2.65 2.79 2.62 2.63 2.71 2.67 2.75 2.73 2.61Cooling capacity CXAN (1) (kW) 49.2 60.8 73.6 94.5 116.4 124.8 125.9 153.1 164.4 195.1 229.0 251.9

Cooling mode power input CXAN (1) (kW) 20.3 25.4 30.1 40.0 42.8 49.7 51.1 60.7 69.8 78.2 91.6 102.0Coefficient of Performancecooling mode CXAN (1) 2.42 2.39 2.45 2.36 2.72 2.51 2.46 2.52 2.36 2.49 2.50 2.47Heating capacity CXAN (1) (kW) 48.1 59.6 72.7 99.2 112.3 120.3 119.2 145.3 171.8 198.4 228.0 251.6

Heating mode power input CXAN (1) (kW) 20.3 24.9 30.4 43.0 45.7 48.7 49.5 60.4 69.6 84.5 86.5 101.1Coefficient of Performanceheatling mode CXAN (1) 2.36 2.39 2.39 2.31 2.45 2.47 2.41 2.41 2.47 2.35 2.64 2.49Refrigerant R407CNumber of refrigerant circuit 1 1 1 1 1 1 2 2 2 2 2 2Refrigerant chargecircuit1/circuit2 CGAN (kg) 13 18 22 26 28 28 19/19 22/22 27/27 27/27 34/34 31/31Refrigerant chargecircuit1/circuit2 CXAN 13 18 22 26 40 40 21/21 24/24 29/29 30/30 37/37 41/41Compressor type ScrollNumber of capacity steps 2 2 2 2 2 2 4 4 4 4 4 4Number of compressors 2 2 2 3 2 2 4 4 6 6 6 4Oil charge circuit1/circuit2 (kg) 7.6/- 10.0/- 12.4/- 16.2/- 10.6/- 11.8/- 10/10 12.4/12.4 13.8/13.8 16.2/16.2 18.6/18.6 11.8/11.8

Evaporator type Brazed plateEvaporator water content (l) 5.3 6.8 8.2 10.5 11.3 12.6 17.2 19.8 25.6 29.0 35.7 35.7Evaporator water connection type Male Iso R7Evaporator waterconnection diameter (inches) 2" 2" 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 3" 3" 3" 3"Condenser type Copper tubes with aluminium finsTotal airflow (standard unit) (m3/h) 20200 19100 26300 37300 37100 37100 38300 52700 55400 86300 83000 79300Number of fans 2 2 3 3 3 3 4 6 6 6 6 6Fan speed 700 700 700 680 680 680 700 700 700 680 680 680Sound power level(standard unit) (dBA) 84 85 86 87 87 87 88 89 89 94 95 95Sound power level(super quiet option) (dBA) 80 80 81 84 84 84 83 84 85 88 88 88Minimum operatingoutdoor air temperature - cooling mode (°C) 10 (-10 or -18 with low ambient operation options)Minimum operatingoutdoor air temperature - heating mode (°C) -10Maximum operatingconditions (2) (°C) CGAN 43/CXAN 42Minimum leavingwater temperature (°C) -12Maximum leavingwater temperature (cooling/heating) (°C) 15/50 (3)

(1) At Eurovent conditions (cooling: water 12°C/7°C - air: 35°C/heating: water 40°C/45°C-air:DB 7°C/WB 6°C)(2) Cooling: water 12/7°C(3) Above 0°C ambient. For applications below 0°C ambient, contact your local sales office.

113113

CG

AN

/CX

AN

Water S

ystem

s

Page 116: Train Instrument's

114PROD-PRC014-E4

Dimensions, weights and clearances

B

B

B

A

Z

X

Y

Unit size 200 250 300 400 450 490 500 600 700 800 900 925

Power supply (V/Ph/Hz) 400/3/50Standard starter type Direct Start-up amps (A) 148 203 215 236 327 336 259 282 300 334 354 450Maximum amps (A) 47 57 69 89 102 111 113 136 153 188 208 225Maximum cable size (mm²) 16 35 35 50 50 50 50 95 95 95 150 150Fan motor power (1) (kW) 0.6 0.6 0.6 1.05 1.05 1.05 0.6 0.6 0.6 1.5 1.5 1.4

(1) Per fan standard unit

Accesscontrol panel

Dimensions (1) (mm)

Operatingweight

(kg)Minimum clearances

(mm)

Shipping weight

(kg)

Unit size

Weights (1)

Water tanknet weight

(kg)

Water tankadditional

height(mm)

Electrical data

Water tankcontent

(l)

X Y Z A BCGAN 200 2800 1100 1897 400 748 743 396 370 1300 1000CGAN 250 2800 1100 1897 400 842 834 396 370 1300 1000CGAN 300 3200 1100 1897 400 968 954 437 410 1300 1000CGAN 400 3200 1100 2074 400 1143 1124 437 410 1300 1000CGAN 450 3200 1100 2074 400 1267 1260 437 410 1300 1000CGAN 490 3200 1100 2074 400 1292 1284 437 410 1300 1000CGAN 500 3400 2300 1897 400 1623 1588 644 570 1300 1000CGAN 600 3400 2300 1897 400 1818 1778 644 570 1300 1000CGAN 700 3400 2300 1995 400 2087 2030 644 570 1300 1000CGAN 800 3400 2300 2100 400 2245 2181 644 570 1300 1000CGAN 900 3400 2300 2100 400 2423 2344 644 570 1300 1000CGAN 925 3400 2300 2100 400 2456 2377 644 570 1300 1000CXAN 200 2800 1100 1897 400 776 771 396 370 1300 1000CXAN 250 2800 1100 1897 400 870 862 396 370 1300 1000CXAN 300 3200 1100 1897 400 996 982 437 410 1300 1000CXAN 400 3200 1100 2074 400 1182 1163 437 410 1300 1000CXAN 450 3200 1100 2074 400 1302 1295 437 410 1300 1000CXAN 490 3200 1100 2074 400 1331 1323 437 410 1300 1000CXAN 500 3400 2300 1897 400 1677 1642 644 570 1300 1000CXAN 600 3400 2300 1897 400 1872 1832 644 570 1300 1000CXAN 700 3400 2300 1995 400 2166 2109 644 570 1300 1000CXAN 800 3400 2300 2100 400 2324 2260 644 570 1300 1000CXAN 900 3400 2300 2100 400 2502 2423 644 570 1300 1000CXAN 925 3400 2300 2100 400 2535 2456 644 570 1300 1000

(1) Without hydraulic module or buffer tank, with aluminium fins

Page 117: Train Instrument's

Evaporator water pressure drop

PROD-PRC014-E4

10

100

1 10 100

1 2 3 4 5 6 87 9 10 11

202 5

20

50

50

Water Flow l/s

kP

a

Water S

ystem

sC

GA

N/C

XA

N

115

1 = CGAN/CXAN 2002 = CGAN/CXAN 2503 = CGAN/CXAN 3004 = CGAN/CXAN 4005 = CGAN/CXAN 4506 = CGAN/CXAN 490

7 = CGAN/CXAN 5008 = CGAN/CXAN 6009 = CGAN/CXAN 70010 = CGAN/CXAN 80011 = CGAN/CXAN 900/925

Page 118: Train Instrument's

116PROD-PRC014-E4

Chiller available pressure - hydraulicmodule option

0

50

100

150

200

250

0 5 10 15 20

1

5

6

7

98

2

3

4 10

1 = CGAN/CXAN 2002 = CGAN/CXAN 2503 = CGAN/CXAN 3004 = CGAN/CXAN 4005 = CGAN/CXAN 500

6 = CGAN/CXAN 6007 = CGAN/CXAN 7008 = CGAN/CXAN 8009 = CGAN/CXAN 90010 = CGAN/CXAN 900/925

Water Flow l/s

kP

a

Page 119: Train Instrument's

Performance data - CGAN

PROD-PRC014-E4

EvaporatorLeaving WaterTemperature

(°C)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Unit

size

Water S

ystem

sC

GA

N/C

XA

N

117

Condenser Entering Air Temperature (°C)

30 35 40 43

200 50.4 15.2 47.7 17.1 44.7 19.3 42.8 20.7

250 62.3 19.7 58.9 22.1 55.2 24.9 52.9 26.7

300 75.7 23.1 71.7 25.8 67.5 28.8 64.8 30.9

400 101.3 30.5 96.0 34.1 90.3 38.2 86.7 40.9

450 121.3 34.9 114.2 39.0 106.7 43.6 102.1 46.6

490 132.1 41.1 124.2 45.7 115.9 50.9 110.7 54.2

5 500 128.4 39.7 121.3 44.6 113.6 50.1 108.7 53.8

600 155.8 46.5 147.6 52.0 138.9 58.1 133.3 62.2

700 182.0 55.3 171.8 62.1 160.9 69.8 153.9 74.9

800 211.9 60.2 200.9 67.2 189.2 75.1 181.8 80.3

900 239.3 69.3 226.6 77.4 213.1 86.5 204.6 92.5

925 266.8 82.1 250.8 91.3 233.9 101.6 223.5 108.2

200 53.6 15.5 50.7 17.4 47.6 19.6 45.6 21.0

250 66.2 20.1 62.5 22.5 58.6 25.3 56.2 27.1

300 80.4 23.5 76.2 26.2 71.7 29.3 68.9 31.4

400 107.5 31.1 101.9 34.7 95.8 38.8 92.0 41.5

450 129.2 35.7 121.8 39.9 114.0 44.5 109.1 47.6

490 140.6 42.1 132.3 46.8 123.6 51.9 118.2 55.2

7 500 136.5 40.5 128.9 45.5 120.8 51.1 115.6 54.8

600 165.8 47.5 157.1 53.0 147.8 59.2 141.9 63.3

700 193.6 56.5 182.8 63.3 171.2 71.1 163.9 76.3

800 225.8 61.3 214.2 68.3 201.7 76.3 193.9 81.6

900 254.7 70.7 241.3 78.8 227.0 88.0 217.9 94.1

925 283.9 84.0 267.1 93.3 249.5 103.6 238.5 110.1

200 56.8 15.7 53.8 17.7 50.5 19.9 48.4 21.3

250 70.0 20.5 66.2 23.0 62.1 25.8 - -

300 85.1 23.9 80.7 26.7 76.0 29.9 73.0 31.9

400 113.7 31.6 107.8 35.3 101.4 39.5 97.4 42.2

450 137.2 36.6 129.5 40.8 121.4 45.5 - -

490 149.1 43.2 140.5 47.9 131.6 53.0 - -

9 500 144.8 41.4 136.8 46.5 128.2 52.1 - -

600 176.0 48.4 166.8 54.0 156.9 60.3 150.7 64.4

700 205.5 57.7 194.1 64.6 181.8 72.5 - -

800 240.1 62.4 227.8 69.5 214.6 77.6 206.3 82.9

900 270.6 72.1 256.3 80.3 241.2 89.6 231.6 95.7

925 301.5 86.1 283.8 95.5 265.5 105.6 254.1 112.1

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C

(2) Compressors power input

Page 120: Train Instrument's

118PROD-PRC014-E4

Performance data - CXAN - cooling

EvaporatorLeaving WaterTemperature

(°C)

Unit

size

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Condenser Entering Air Temperature (°C)

30 35 40 42

200 49.1 16.3 46.3 18.2 43.4 20.4 42.1 21.3

250 60.6 20.5 57.2 23.0 53.6 25.7 52.1 26.9

300 73.2 24.4 69.3 27.1 65.1 30.1 63.4 31.4

400 93.2 31.6 88.2 35.3 82.8 39.4 80.6 41.2

450 116.2 34.5 109.3 38.1 101.9 42.3 98.9 44.1

490 125.0 40.7 117.3 44.9 109.2 49.5 105.8 51.5

5 500 125.7 42.0 118.5 46.9 110.8 52.4 - -

600 152.2 49.8 144.0 55.3 135.2 61.5 131.5 64.2

700 167.0 57.2 157.4 64.0 147.1 71.9 142.7 75.2

800 193.6 63.3 183.2 70.4 172.0 78.6 167.3 82.1

900 219.3 73.7 207.4 81.8 194.6 91.0 189.3 95.0

925 251.9 81.9 236.6 90.2 220.5 99.4 213.8 103.3

200 52.1 16.6 49.2 18.6 46.1 20.8 44.8 21.7

250 64.3 21.0 60.8 23.5 56.9 26.2 55.3 27.4

300 77.7 24.9 73.6 27.6 69.2 30.7 67.3 32.0

400 98.9 32.3 93.6 35.9 87.9 40.1 85.6 41.9

450 123.7 35.4 116.4 39.1 108.8 43.3 105.6 45.1

490 132.9 41.9 124.9 46.0 116.5 50.6 - -

7 500 133.6 43.0 125.9 48.0 117.7 53.6 - -

600 161.8 51.0 153.1 56.6 143.7 62.8 139.8 65.5

700 177.6 58.5 167.4 65.4 156.5 73.3 - -

800 206.1 64.6 195.1 71.8 183.3 80.1 178.3 83.6

900 233.4 75.5 220.7 83.7 207.1 92.9 201.5 96.9

925 268.1 84.2 252.0 92.4 235.2 101.5 228.3 105.4

200 55.3 17.0 52.2 18.9 48.9 21.2 - -

250 68.1 21.5 64.3 24.0 60.2 26.8 - -

300 82.3 25.5 77.9 28.2 73.3 31.3 71.3 32.7

400 104.6 32.9 99.1 36.6 93.1 40.8 90.6 42.7

9 450 131.3 36.5 123.8 40.2 115.8 44.3 112.6 46.1

490 141.0 43.1 132.7 47.2 124.0 51.8 - -

500 141.6 44.1 133.5 49.1 - - - -

600 171.6 52.3 162.3 57.9 152.4 64.2 - -

700 188.4 59.8 177.7 66.9 166.1 74.9 - -

800 219.0 65.9 207.3 73.3 194.8 81.6 189.6 85.2

900 247.8 77.3 234.3 85.6 220.0 94.9 - -

925 284.7 86.6 267.9 94.8 250.4 103.8 - -

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C

(2) Compressors power input

Page 121: Train Instrument's

Performance data - CXAN - heating

PROD-PRC014-E4

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Unit

size

Hot

Water

Leaving

Temperature

(°C)

Water S

ystem

sC

GA

N/C

XA

N

119

Entering Air Temperature (°C)

-4 0 7 14

200 35.2 15.5 39.2 15.5 46.9 15.4 56.8 15.4

250 43.6 19.3 48.5 19.4 58.1 19.5 70.2 19.6

300 53.3 23.0 59.3 23.1 71.0 23.4 85.7 23.6

400 72.5 31.0 80.8 31.1 97.0 31.4 117.3 31.7

450 87.0 34.5 97.1 34.8 116.6 35.1 141.1 35.4

40 490 93.6 37.5 104.1 37.3 125.9 37.4 151.7 37.9

500 87.2 38.6 97.1 38.9 116.2 39.1 140.4 39.3

600 106.6 46.0 118.6 46.2 142.0 46.8 171.4 47.3

700 125.2 54.2 139.7 54.4 167.8 54.6 203.3 54.8

800 144.9 62.0 161.5 62.2 194.0 62.8 234.6 63.4

900 161.6 69.1 179.8 69.3 215.1 69.9 259.3 70.6

925 190.5 75.0 211.8 74.6 254.0 74.8 308.5 75.8

200 35.2 17.4 39.1 17.4 46.6 17.3 56.2 17.2

250 43.8 21.5 48.5 21.6 57.8 21.7 69.6 21.8

300 - - 59.3 25.6 70.5 25.9 84.7 26.1

400 72.7 34.4 80.6 34.5 96.3 34.9 115.9 35.1

450 87.0 38.3 96.7 38.5 115.5 38.9 139.2 39.2

45 490 93.8 42.1 103.8 41.9 123.7 41.8 149.7 42.2

500 87.5 43.1 97.1 43.3 115.6 43.5 139.1 43.7

600 106.9 51.0 118.5 51.2 141.1 51.9 169.4 52.3

700 125.5 60.7 139.4 60.7 166.8 60.9 201.4 60.9

800 145.3 68.9 161.2 69.1 192.7 69.7 231.8 70.1

900 162.0 76.4 179.5 76.9 213.5 77.5 256.2 78.1

925 190.9 84.2 211.2 83.8 251.7 83.6 304.3 84.4

200 - - 39.0 19.5 46.3 19.4 55.8 19.3

250 - - 48.5 24.0 57.5 24.2 68.9 24.3

300 - - 59.3 28.5 70.1 28.7 83.7 28.9

400 - - 80.5 38.3 95.6 38.6 114.6 38.9

450 - - 96.4 42.6 114.5 43.1 137.3 43.4

50 490 - - 103.6 46.8 122.8 46.7 147.7 47.0

500 - - 97.1 48.1 115.0 48.3 137.8 48.5

600 - - 118.7 56.9 140.2 57.3 167.4 57.8

700 - - 139.2 67.8 165.7 67.8 199.4 67.8

800 - - 161.1 76.7 191.3 77.3 229.1 77.7

900 - - 179.7 85.3 212.3 85.9 253.3 86.5

925 - - 210.8 93.7 249.7 93.5 300.3 94.1

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C

(2) Compressors power input

Page 122: Train Instrument's

CGAN/CXAN

120PROD-PRC014-E4

Customer benefits • Packaged hydraulic module for easier installation: saving

of time • Super Quiet version for sensitive environments: a high

level of acoustic comfort• Wide application flexibility for comfort and process

applications to fit the customer's exact requirements

Main features• Scroll Compressors- Hermetic, high efficiency, low vibration, low sound level- Full internal protections, internal temperature and

bypass valve- Built-in oil level sight glass and oil charging valve- Compressor sound attenuating enclosure (super quiet

units)• External sheet metal parts are galvanized and finished

with powder paint RAL 9002• Access panels are quickly removable using a square key·• Disconnect switch/transformer• Electronic waterflow switch• Close spacing installation - 1.2m side clearances

Options• Super quiet operation• Integrated hydraulic module with or without buffer tank

(footprint unchanged)• Single or double pump package• Low or high manometric pump pressure package• Copper fins or black epoxy-coated fins• 380, 400 and 415V power voltage• Low ambiant operation (-18°C)

• Phase reversal protection• High and low pressure gauges• Soft starter• Coil protection guards• Full protection guards• Factory-mounted LonTalk® serial link allowing you to- Modify the chilled or hot water temperature setpoint- Start or stop the unit- Switch from cooling to heating mode- Monitor water temperature setpoint, ambient air

temperature, chiller operation, fans, water pumps,compressors alarms

- Trane Tracer Summit™ BMS direct compatibility- LonTalk® is an open communication protocol used on

AquaStream2 and water terminal units.

Accessories• Neoprene isolators• Weld sleeve connection

ControlAdaptive Control™ microprocessor featuring:• Easy-to-use DynaView operator interface panel• External Auto/Stop• Chilled water pumps control (optional)• Ice-making card (optional)• Chilled water and current-limit remote setpoint card

(optional)• LonTalk® communication card (optional)• Programmable fault card 4 relays (optional)• Anti-freeze protection of evaporator, control defrost

(CXAN)

Axial fans, scroll compressorcooling-only or heat pump models285-465 kW*

Outdoor chillers

CGAN/CXAN

TracerTM CH530

* Also available with R22 for applications outside of the European Union. For information, contact your local Trane Sales Office.

Page 123: Train Instrument's

Unit size 209 210 211 212 213 214

Cooling capacity CGAN (1) (kW) 287.7 315.4 350.2 389.2 428.1 462.1

Cooling mode power input CGAN (1) (kW) 107.4 120.4 130.2 139.4 155.8 171.5

Coefficient of Performance cooling mode CGAN (1) 2.68 2.62 2.69 2.79 2.75 2.69

Cooling capacity CXAN (1) (kW) 277.1 304.5 335.2 366.8 410.1 451.4

Cooling mode power input CXAN (1) (kW) 108.6 117.6 131.3 144.8 155.1 165.1

Coefficient of Performance cooling mode CXAN (1) 2.55 2.59 2.55 2.53 2.64 2.73

Heating capacity CXAN (1) (kW) 291.1 317.8 351.6 384.4 425.4 467.4

Heating mode power input CXAN (1) (kW) 107.2 112.6 131.4 146.4 159.2 172.0

Coefficient of Performance heatling mode CXAN (1) 2.72 2.82 2.68 2.63 2.67 2.72

Refrigerant R407C

Number of refrigerant circuit 2

Refrigerant charge circuit1/circuit2 CGAN (kg) 41/41 41/41 56/41 56/56 60/56 60/60

Refrigerant charge circuit1/circuit2 CXAN (kg) 46/46 46/46 58/46 58/58 63/58 63/63

Compressor type Scroll

Number of capacity steps 4 4 5 6 6 6

Number of compressors 4 4 5 6 6 6

Oil charge circuit1/circuit2 (kg) 12.6/12.6 12.6/12.6 18.9/12.6 18.9/18.9 18.9/18.9 18.9/18.9

Evaporator type Brazed plate

Evaporator water content (l) 26.8 29.2 35.6 35.6 42.0 42.0

Evaporator water connection type Victaulic

Evaporator water connection diameter (inches) 4"

Condenser type Copper tubes with aluminium fins

Total airflow (standard unit) (m3/h) 117300 117300 131000 144700 141900 139100

Number of fans 6 6 7 8 8 8

Fan speed rpm 915

Sound power level (standard unit) (dBA) 95 95 95 96 96 96

Sound power level (super quiet option) (dBA) 90 90 90 90 90 91

Minimum operating outdoor air temperature (°C) 43 (4)

Maximum operating conditions (2) (°C) 50

Minimum leaving water temperature CGAN/CXAN (°C) -12/-10

Maximum leaving water temperature (cooling/heating) (°C) +15

(1) At Eurovent conditions (cooling: water 12°C/7°C - air: 35°C/heating: water 40°C/45°C-air:DB 7°C/WB 6°C) (2) Cooling: water 12/7°C(3) Above 0°C ambient. For applications below 0°C ambient, contact your local sales office. (4) Except CGAN/CXAN 213-214 SQ: maximum ambient temp = +40°C

General data

PROD-PRC014-E4

Water S

ystem

s

CG

AN

/CX

AN

121

Page 124: Train Instrument's

122122

Dimensions, weights and clearances

C

B

B

A

Y

Z

X

Accesscontrol panel

Dimensions (1) (mm)

Operatingweight

(kg)Minimum clearances

(mm)

Shipping weight

(kg)

Weights (1)

Watertank

net weight (kg)

Watertank

content (l)

Unit size X Y Z A B C

CGAN 209 2230 5135 2323 2680 2650 300 240 600 1000 1200 800

CGAN 210 2230 5135 2323 2710 2680 300 240 600 1000 1200 800

CGAN 211 2230 5135 2323 3070 3030 300 240 600 1000 1200 800

CGAN 212 2230 5135 2323 3370 3330 300 240 600 1000 1200 800

CGAN 213 2230 5135 2323 3490 3450 300 240 600 1000 1200 800

CGAN 214 2230 5135 2323 3590 3550 300 240 600 1000 1200 800

CGAN 209 2230 5135 2323 2950 2930 300 240 600 1000 1200 800

CXAN 210 2230 5135 2323 2990 2960 300 240 600 1000 1200 800

CXAN 211 2230 5135 2323 3260 3230 300 240 600 1000 1200 800

CXAN 212 2230 5135 2323 3500 3470 300 240 600 1000 1200 800

CXAN 213 2230 5135 2323 3640 3600 300 240 600 1000 1200 800

CXAN 214 2230 5135 2323 3750 3700 300 240 600 1000 1200 800

(1) Without hydraulic module or buffer tank, with aluminium fins

Hydraulicmodule

net weight(kg)

Electrical data

Unit size 209 210 211 212 213 214

Power supply (V/Ph/Hz) 400/3/50 Standard starter type Direct Start-up amps standard (A) 509 531 544 551 621 654Start-up amps softstarter (A) 381 403 416 443 493 526Maximum amps (A) 247 269 282 326 359 392Maximum cable size (mm²) 240 240 240 240 240 240Fan motor power (1) (kW) 9.4 9.4 11 12.6 12.6 12.6

(1) Total all fans, standard unit

PROD-PRC014-E4

Page 125: Train Instrument's

Evaporator water pressure drop

PROD-PRC014-E4

Water S

ystem

sC

GA

N/C

XA

N

123

1 = CGAN/CXAN 2092 = CGAN/CXAN 2103 = CGAN/CXAN 211/2124 = CGAN/CXAN 213/214

l/s

kP

a

Chiller available pressure - hydraulicmodule option

1 = CGAN/CXAN 2092 = CGAN/CXAN 2103 = CGAN/CXAN 2114 = CGAN/CXAN 2125 = CGAN/CXAN 2136 = CGAN/CXAN 214

l/s

kP

a

Page 126: Train Instrument's

124124

Performance data - CGAN - standard unit

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Cooling

capacity (1)

(kW)

Unit

size

Evaporator

Leaving

Water

Temperature

(°C)

Condenser Entering Air Temperature (°C)

30 35 40 43

209 286.5 88.2 269.5 97.8 251.4 108.7 240.0 115.8

210 315.4 100.5 295.3 111.3 274.0 123.5 260.6 131.5

5 211 348.7 106.8 328.3 118.6 306.5 132.0 292.8 140.8

212 386.1 113.3 365.1 126.2 342.6 140.7 328.3 150.2

213 425.5 127.5 401.1 142.0 374.8 158.4 358.2 169.1

214 459.8 141.0 432.3 157.2 402.7 175.4 383.9 187.3

209 305.6 90.1 287.7 99.8 268.8 110.8 256.9 117.9

210 336.4 102.9 315.3 113.8 293.0 126.2 279.1 134.2

7 211 371.7 109.2 350.2 121.1 327.4 134.5 313.1 143.3

212 411.3 115.8 389.2 128.7 365.5 143.2 350.7 152.6

213 453.9 130.5 428.1 145.1 400.6 161.6 383.2 172.3

214 491.1 144.5 462.1 160.8 431.0 179.2 411.3 191.3

209 325.3 92.2 306.5 102.0 286.7 112.9 274.4 120.1

210 358.1 105.4 336.0 116.4 312.7 128.9 - -

9 211 395.5 111.7 372.9 123.7 349.1 137.2 - -

212 437.5 118.3 414.2 131.3 389.4 145.8 373.9 155.2

213 483.3 133.5 456.2 148.3 427.3 164.9 409.2 175.7

214 523.5 148.0 492.9 164.6 460.3 183.3 439.8 195.4

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C(2) Compressors power input

Power

input (2)

(kW)

PROD-PRC014-E4

Page 127: Train Instrument's

PROD-PRC014-E4

Water S

ystem

sC

GA

N/C

XA

N

125

Performance data - CXAN cooling - standard unit

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Power

input (2)

(kW)

Cooling

capacity (1)

(kW)

Cooling

capacity (1)

(kW)

Unit

size

Evaporator

Leaving

Water

Temperature

(°C)

Condenser Entering Air Temperature (°C)

30 35 40 42

209 276.1 88.1 259.7 97.9 242.3 108.9 231.3 116.2

210 304.5 96.8 285.4 107.4 265.1 119.4 252.3 127.2

5 211 334.5 107.3 314.5 119.0 293.1 132.3 279.6 141.0

212 365.5 117.9 344.6 130.8 322.1 145.4 308.0 154.9

213 408.7 127.0 384.6 140.6 358.9 156.1 342.6 166.2

214 449.2 135.7 422.6 150.2 394.2 166.6 376.2 177.5

209 294.3 90.1 277.1 99.9 258.8 111.0 247.4 118.3

210 324.6 99.2 304.6 109.9 283.3 121.9 269.9 129.9

7 211 356.3 109.9 335.2 121.7 312.8 135.0 298.8 143.7

212 388.9 120.8 366.8 133.7 343.4 148.2 328.6 157.7

213 435.5 130.2 410.1 144.0 383.1 159.4 366.1 169.5

214 479.5 139.2 451.4 153.9 421.6 170.5 402.7 181.5

209 313.0 92.1 295.0 102.0 276.0 113.2 264.1 120.4

210 345.3 101.6 324.3 112.4 302.1 124.6 288.3 132.6

9 211 378.7 112.6 356.6 124.5 333.2 137.8 318.6 146.5

212 413.1 123.8 389.9 136.8 365.4 151.2 - -

213 463.2 133.6 436.4 147.5 408.2 163.0 - -

214 510.8 142.9 481.3 157.8 449.9 174.6 430.1 185.7

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C(2) Compressors power input

Power

input (2)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Unit

size

Hot Water

Leaving

Temperature

(°C)

Performance data - CXAN heating - standard unit

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Heating

capacity (1)

(kW)

Power

input (2)

(kW)

Condenser Entering Air Temperature (°C)

-4 0 7 14

209 216.3 84.5 243.6 85.7 296.3 88.1 366.3 90.5

210 234.7 88.9 266.5 90.5 325.4 93.2 404.5 95.8

40 211 261.1 103.7 294.5 105.3 355.0 107.5 440.4 111.4

212 288.2 115.5 322.7 116.9 388.6 120.1 477.3 123.4

213 316.5 126.0 356.2 127.9 431.1 131.3 531.4 135.4

214 345.7 136.6 390.1 139.0 474.2 143.0 586.3 147.2

209 215.9 95.5 242.5 96.3 291.6 98.1 359.2 100.7

210 231.8 99.7 262.1 101.4 318.3 103.5 394.1 106.5

45 211 260.8 117.0 292.4 118.3 351.5 120.7 431.5 123.7

212 289.9 131.2 322.3 132.2 384.5 134.1 469.5 137.2

213 311.9 140.9 354.3 143.9 425.6 146.7 522.8 150.6

214 341.0 152.6 380.2 153.9 467.2 159.4 576.2 163.7

209 - - 240.3 108.3 287.4 109.8 350.7 111.5

210 - - 258.4 113.3 311.6 115.3 382.6 117.8

50 211 - - - - 346.7 134.8 422.5 136.8

212 - - - - 380.8 150.1 461.1 151.8

213 - - - - 420.5 163.9 513.3 167.1

214 - - 382.9 174.1 460.4 177.7 564.8 181.0

(1) At evaporator outlet, ratings are based on evaporator temperature drop of 5°C(2) Compressors power input

Page 128: Train Instrument's

126PROD-PRC014-E4

Customer benefits • Trane helirotor compressor - designed to perform, built

to last: superior reliability and low cost of ownership• R134a refrigerant for high performance: low energy con-

sumption• Wide operating range: flexibility to meet the customer's

exact requirements

Main features• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only four moving parts, suctiongas-cooled motor

• Competitive physical footprint• Single power connection• Low sound levels• Easy installation• Star-delta starter• Exact load matching• Application flexibility• Tracer Summit™ capabilities

Options• High ambient operation (up to 46°C) • Low ambient operation (down to -18°C)• Low noise version equipped with low-speed fans and

compressor sound attenuating enclosure• High efficiency version with oversized heat exchangers• Power disconnect switch• Coil protection for condenser only• Night noise setback -available on low noise units only• High and low pressure gauges• Free-cooling• Heat recovery

Accessories• Neoprene isolators• Counterflanges• Flow switch

ControlAdaptive Control™ microprocessor featuring:• Unit control module with Clear Language Display• External Auto/Stop• External interlock• Chilled water pump control• Alarm indication contacts• Ice-making card (optional)• Tracer communication card Comm 3 (optional)• Chilled water and current limit remote setpoint card

(optional)

Axial fans, helical rotary compressor250-650 kW

Outdoor chillers

RTAD

RTAD

UCM-CLD

Page 129: Train Instrument's

General data - Standard unit

PROD-PRC014-E4

Unit size 085 100 115 125 145 150 165 180

Cooling capacity standard efficiency units (1) (kW) 273.5 329.5 393.1 449.7 515.8 551.3 600.5 644.8

Power input standard efficiency units (2) (kW) 99.3 118.4 147.6 184.8 189.8 209.2 221.7 242.1

Coefficient of Performance

standard efficiency units (3) 2.8 2.8 2.7 2.4 2.7 2.6 2.7 2.7

Cooling capacity high efficiency units (1) (kW) 297.1 351.3 417.7 488.0 522.8 560.8 - -

Power input high efficiency units (2) (kW) 95.6 113.6 143.4 175.5 182.2 201.1 - -

Coefficient of Performance high efficiency units (3) 3.1 3.1 2.9 2.8 2.9 2.8 - -

Refrigerant R134a

Number of refrigerant circuits 2 2 2 2 2 2 2 2

Refrigerant charge circuit1/circuit2 (kg) 24/24 30/32 35/36 36/37 44/48 44/48 61/59 61/61

Compressor type Helical rotary

Number of compressors 2 2 2 2 2 2 2 2

Oil charge circuit 1/2 (8) (l) 6/6 7/7 9/9 10/10 10/10 10/10 15/11 15/15

Evaporator type Tube-in-shell/Internally finned copper tubes

Evaporator water content (l) 106 270 222 204 204 204 415 415

Evaporator water connection type Victaulic

Evaporator water connection diameter (inches) 5 6 6 6 6 6 6 6

Condenser type Internally finned copper tubes with aluminium fins

Total airflow (8) (m3/s) 23.39 28.53 26.99 27.02 37.02 39.04 44.88 46.84

Number of fans 6 6 6 6 9 10 11 12

Fan speed (rpm) 915

Sound power level (8) (dB(A)) 97 98 97 97 98 101 102 103

Sound pressure level at 10 m (4) (8) (dB(A)) 65 65 64 65 66 69 70 70

Minimum operating outdoor air temperature (5) (°C) 0

Maximum operating outdoor air temperature (6) (°C) +40

Minimum leaving water temperature (7) (°C) -12

Maximum leaving

water temperature (°C) +15

(1) At Eurovent conditions. 7°C leaving water temperature and 35°C entering condenser air temperature(2) Unit kW input(3) Including fans(4) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996(5) -18°C minimum operating outdoor air temperature with low ambient option(6) Depending on high ambient option, maximum operating outdoor air temperature is 46-50°C(7) With ethylene glycol solution(8) Standard efficiency units standard fans

Water S

ystem

sR

TAD

127

Page 130: Train Instrument's

128PROD-PRC014-E4

Dimensions, weights and clearances - Standard unit

Z

YX

A

B

B

A

Accesscontrol panel

Unit size 085 100 115 125 145 150 165 180Power supply (V/Ph/Hz) 400/3/50

Standard starter type Star-delta

Start-up amps STD (1) (A) 255 306 359 425 471 502 570 608

Start-up amps HE (1) (A) 255 315 368 443 480 511 - -

Maximum amps STD (2) 242 282 323 387 437 477 527 576

Maximum amps HE (2) (A) 242 291 332 405 446 486 - -

Maximum cable size (mm²) 2x300 2x300 2x300 2x300 2x300 2x300 2x300 2x300

Maximum cable size with disconnect switch STD (mm²) 150 240 240 240 240 2x300 2x300 2x300

Maximum cable size with disconnect switch HE (mm²) 150 240 240 240 240 2x300 - -

Disconnect switch size STD (A) 250 400 400 500 500 630 630 630

Disconnect switch size HE (A) 250 400 400 500 500 630 - -

Fan motor power (3) (kW) 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05

(1) Equals the sum of the largest compressor starting Amps, plus the second compressor maximum Amps, plus all the fans FLA, plus the control Amps(2) Maximum Compressors FLA + all fans FLA + control Amps(3) Per fan

X (2) Y Z A B

085 STD 3507 2260 2095 2554 2660 1000 1200085 HE 4426 2260 2095 2973 3240 1000 1200100 STD 4426 2260 2095 2838 3105 1000 1200100 HE 4426 2260 2095 3148 3370 1000 1200115 STD 5351 2260 2095 3333 3555 1000 1200115 HE 4426 2260 2115 3702 3905 1000 1200125 STD 4426 2260 2095 3368 3570 1000 1200125 HE 5351 2260 2115 3797 4000 1000 1200145 STD 5351 2260 2115 4057 4260 1000 1200145 HE 6370 2260 2215 4973 5390 1000 1200150 STD 5351 2260 2115 4317 4520 1000 1200150 HE 6370 2260 2215 5028 5445 1000 1200165 STD 6370 2260 2215 5023 5440 1000 1200180 STD 6370 2260 2215 5108 5525 1000 1200

(1) With aluminium fins(2) Including the disconnect switch handle, isolators and pressure gauges

Dimensions(mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size

Electrical data - Standard unit

Weight (1) (2)

Page 131: Train Instrument's

Evaporator water pressure drop -Standard unit

PROD-PRC014-E4

Water S

ystem

sR

TAD

129

1 = RTAD 085 STD2 = RTAD 100 STD & 085 HE3 = RTAD 115 STD & 100 HE4 = RTAD 125 STD, 145 STD, 150 STD, 115 HE & 125 HE5 = RTAD 160 STD, 180 STD, 145 HE & 150 HE

l/s

kP

a

Page 132: Train Instrument's

130PROD-PRC014-E4

Performance data - Standard unit

Cooling

capacity

(kW)

Evaporator

Leaving

Water

Temperature

(°C)

Unit

size

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Condenser Entering Air Temperature (°C)

30 35 40

085 STD 277.4 80.8 259.5 87.6 241.2 95.2

100 STD 333.3 98.9 311.9 106.2 289.7 114.3

115 STD 397.7 124.3 372.0 135.0 345.6 146.9

125 STD 456.0 158.0 425.8 171.6 394.9 186.5

5 145 STD 520.0 158.7 488.7 171.8 456.4 186.4

150 STD 556.9 175.0 523.2 189.2 488.7 205.0

165 STD 607.9 192.3 573.5 207.7 537.6 224.9

180 STD 652.6 210.1 616.4 226.9 578.4 245.5

085 STD 295.7 83.8 277.1 90.7 257.7 98.4

100 STD 355.1 102.8 332.6 110.1 309.1 118.4

115 STD 423.0 128.9 395.9 139.8 367.8 151.9

125 STD 483.8 164.2 451.8 177.9 401.5 181.2

7 145 STD 554.1 164.7 520.7 178.0 486.6 192.8

150 STD 592.5 181.8 556.9 196.2 520.0 212.1

165 STD 648.0 200.0 611.1 215.7 573.5 233.1

180 STD 695.1 218.7 656.4 235.7 616.4 254.7

085 STD 314.7 86.9 295.0 93.9 274.6 101.7

100 STD 377.6 106.8 353.7 114.3 329.1 122.6

115 STD 449.0 133.8 420.5 144.8 390.6 157.2

125 STD 511.9 170.6 478.5 184.6 406.8 174.8

9 145 STD 588.9 171.0 553.8 184.5 517.6 199.4

150 STD 628.7 188.9 591.0 203.4 552.0 219.5

165 STD 688.4 207.9 649.8 223.8 609.3 241.6

180 STD 738.4 227.5 697.2 244.9 654.7 264.2

Notes:(1) Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²° K/kW.(2) Power input compressors only (3) Ratings are based on an evaporator temperature drop of 5°C.(4) Interpolation betweeen points is permissible. Extrapolation is not permitted. (5) For operation above 40°C ambient, the chillers will have the High Ambient Option.

Page 133: Train Instrument's

Performance data - High efficiency unit

PROD-PRC014-E4

Cooling

capacity

(kW)

Evaporator

Leaving

Water

Temperature

(°C)

Unit

size

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Condenser Entering Air Temperature (°C)

30 35 40 46 49

85 HE 299.6 77.6 280.6 83.8 261.2 90.8 237.0 100.3 224.3 105.4

100 HE 353.4 91.1 331.6 98.4 308.7 106.5 280.9 117.6 266.5 123.5

115 HE 419.1 118.0 393.8 127.9 367.8 139.0 335.8 154.0 319.3 162.2

5 125 HE 490.8 144.1 461.7 156.3 431.4 169.8 387.8 184.3 360.4 189.2

145 HE 524.9 149.1 495.1 161.4 464.5 175.1 426.5 193.4 406.8 203.4

150 HE 563.6 164.9 531.6 178.1 498.6 192.9 457.8 212.9 436.7 223.7

85 HE 320.0 80.5 299.9 86.8 279.2 93.8 253.5 103.4 240.5 108.6

100 HE 377.3 94.3 354.1 101.7 330.2 110.0 300.6 121.2 285.9 127.2

115 HE 448.3 122.2 421.6 132.2 393.8 143.5 359.7 158.7 340.7 166.1

7 125 HE 524.2 149.2 493.3 161.6 461.3 175.3 391.7 177.6 366.0 183.2

145 HE 561.2 154.6 529.5 167.0 496.8 180.8 444.8 193.6 415.2 198.8

150 HE 601.6 171.1 567.8 184.6 532.7 199.5 477.8 213.8 447.2 219.7

85 HE 341.1 83.5 320.0 89.8 297.8 96.9 271.1 106.6 257.4 111.8

100 HE 401.9 97.6 377.6 105.1 352.3 113.5 321.4 124.9 305.5 131.1

115 HE 478.2 126.5 450.1 136.8 420.9 148.2 370.6 156.6 346.0 161.1

9 125 HE 558.7 154.6 526.0 167.1 492.6 181.0 398.7 172.2 372.3 177.4

145 HE 598.1 160.3 564.7 172.8 530.2 186.8 447.6 186.0 419.5 191.9

150 HE 640.6 177.7 604.8 191.2 567.5 206.3 483.1 206.7 453.6 213.4

Notes:(1) Ratings based on sea level altitude and fouling factor of 0.0176 m²° K/kW (2) Power input compressors only (3) Ratings are based on an evaporator temperature drop of 5°C.(4) Interpolation between points permissable. Extrapolation is not permitted.(5) For operation above 40°C ambient, chillers will have the High Ambient Option.

Water S

ystem

sR

TAD

131

Page 134: Train Instrument's

132132PROD-PRC014-E4

Free-cooling and heat recovery solutions

Partial heat

recovery

Partial and total heat recoveryUnits are equipped with an additional heat exchanger onthe discharge line to recover heat from refrigerant vapor.

Designed for applications where a limited (partial heatrecovery) or significant (total heat recovery) amount ofheat needs to be recovered and actually used in the build-ing to heat or preheat sanitary water in office or commer-cial buildings, or in kitchens and laundries in hotels andresorts.

This can also be a solution for process applications withsimultaneous cooling and heating needs.

Free-coolingUnits are equipped with an additional heat exchanger inorder to directly cool the building water loop with the out-side ambient air.

In general, the ideal situation is a building presenting amoderate remaining cooling load in winter, located in aregion where a significant number of hours below 0°C isencountered every year.

Trane provides assistance in running extensive load simulations. This will determine whether you canbenefit from the savings generated from the installation of a Trane RTAD with the partial heat recovery,total heat recovery or free-cooling option.

Total heat

recovery

Free

cooling

RTAD FC 180

RTAD PHR 125

J F M A M J J A S O N D

°C

Page 135: Train Instrument's

Unit size 085 100 115 125 145 150 165 180

Cooling Mode

Cooling capacity standard efficiency units (1) (kW) 271 316 371 435 498 528 584 623Power input standard efficiency units (2) (kW) 107.4 125.7 161.2 197.7 206 220.6 240.2 264.9Coefficient of Performance standard efficiency units (3) 2.5 2.5 2.3 2.2 2.4 2.4 2.4 2.4Cooling capacity high efficiency units (1) (kW) 289.3 346.6 405.5 427.7 513.1 546.9 - -Power input high efficiency units (2) (kW) 101.3 122.7 156.1 191.9 196.6 218.6 - -Coefficient of Performance high efficiency units (3) 14.6 12.6 19.5 12.5 14.4 12.9 - -Free-Cooling Mode

Cooling capacity standard efficiency units (9) (kW) 170 221 239 251 312 312 380 380Power input standard efficiency units (2) (kW) 15.4 14.5 14.6 20.5 21.9 25.2 26.7 30.0Coefficient of Performance standard efficiency units (3) 11.0 15.2 16.4 12.2 14.2 12.4 14.2 12.7Cooling capacity standard efficiency units (9) (kW) 213.1 257.2 376.3 315.5 383.3 385.6 - -Power input standard efficiency units (2) (kW) 14.6 20.4 19.3 25.2 26.7 30.0 - -Coefficient of Performance standard efficiency units (3) 14.6 12.6 19.5 12.5 14.4 12.9 - -Refrigerant R134aNumber of refrigerant circuits 2 2 2 2 2 2 2 2Refrigerant charge standard efficiency units circuit1/circuit2 (kg) 24/24 30/32 35/36 36/37 44/48 44/48 61/59 61/61Refrigerant charge high efficiency units circuit1/circuit2 32/34 35/36 42/45 42/45 59/61 59/61 - -Compressor type Helical rotaryNumber of compressors 2 2 2 2 2 2 2 2Oil charge circuit 1/2 (8) (l) 6/6 7/7 9/9 10/10 10/10 10/10 15/11 15/15Evaporator type Tube-in-shell/Internally finned copper tubesEvaporator water content standard efficiency units (l) 106 270 222 204 204 204 415 415Evaporator water content high efficiency units (l) 270 222 204 204 415 415 - -Evaporator water connection type VictaulicEvaporator water connection diameter standard efficiency (inches) 4 5 5 5 5 5 6 6Evaporator water connection diameter high efficiency (inches) 6 6 6 6 7 7 - -Condenser type Internally finned copper tubes with aluminium fins Total airflow (High/Low speed) (8) (m3/s) 17.9/13.0 21.6/15.7 20.4/14.7 23.5/17.2 28.4/20.6 29/21.2 34.2/24.8 34.7/25.4Number of fans 3/3 3/3 3/3 4/4 5/4 5/5 6/5 6/6Fan speed (rpm) 935/740 935/740 935/740 935/740 935/740 935/740 935/740 935/740Sound power level (High Speed) (8) (dB(A)) 101.1 101.1 100.8 102.0 103.8 104.2 105.0 105.5Sound power level (Low Speed) (8) (dB(A)) 97.7 97.9 97.0 98.2 101.3 101.8 102.7 103.4Sound pressure level at 10 m (High Speed) (4) (8) (dB(A)) 68.8 68.7 68.4 69.6 71.3 71.7 72.3 72.8Sound pressure level at 10 m (Low Speed) (4) (8) (dB(A)) 65.4 65.5 64.6 65.8 68.8 69.3 70.0 70.7Minimum operating outdoor air temperature (5) (°C) -18Maximum operating outdoor air temperature (6) (°C) +40Minimum leaving water temperature (7) (°C) -12Maximum leaving water temperature (°C) +15Length (mm) 3900 4850 4850 4850 5770 5770 6810 6810Width (mm) 2420 2420 2420 2420 2420 2420 2460 2460Height (mm) 2603 2603 2623 2623 2643 2643 2743 2743Shipping weight (10) (kg) 3300 3740 4530 4720 5560 5505 6665 6750Operating weight (10) (kg) 3685 4492 5291 5446 6296 6241 7884 7964

(1) At Eurovent conditions. 7°C leaving water temperature and 35°C entering condenser air temperature(2) Unit kW input(3) Including fans (4) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996 (5) -18°C minimum operating outdoor air temperature with low ambient option(6) Depending on high ambient option, maximum operating outdoor air temperature is 46-50°C (7) With ethylene glycol solution (8) Standard efficiency units standard fans (9) Conditions: 11°C leaving water temperature and 0°C entering condenser air temperature(10) For standard units only. For this information on high efficiency units, contact your local sales office. Weights given with aluminium fins, disconnect switch,isolators and pressure gauges.

General data - Free-cooling option

PROD-PRC014-E4

Water S

ystem

s

RTA

D

133

Page 136: Train Instrument's

134134PROD-PRC014-E4

General data - Partial heatrecovery option

Unit size 085 100 115 125 145 150 165 180

Cooling Mode

Cooling capacity standard efficiency units (1) (kW) 273.5 329.5 393.1 449.7 515.8 551.3 600.5 644.8Power input standard efficiency units (2) (kW) 99.3 118.4 147.6 184.8 189.8 209.2 221.7 242.1Coefficient of Performance standard efficiency units (3) 2.8 2.8 2.7 2.4 2.7 2.6 2.7 2.7Cooling capacity high efficiency units (1) (kW) 297.1 351.3 417.7 488 522.8 560.8 - -Power input high efficiency units (2) (kW) 95.6 113.6 143.4 175.5 182.2 201.1 - -Coefficient of Performance high efficiency units (3) 3.1 3.1 2.9 2.8 2.9 2.8 - -Partial Heat Recovery Mode

Heating capacity standard efficiency units (9) (kW) 61.0 84.6 110.0 152.0 147.2 160.3 173.4 191.1Heating capacity high efficiency units (9) (kW) 47.4 57.6 89.4 112.4 115.4 129.2 - -Refrigerant R134a Number of refrigerant circuits 2 2 2 2 2 2 2 2Refrigerant charge circuit1/circuit2 (kg) 26/26 33/35 38/39 39/40 47/51 47/51 65/63 66/65Compressor type Helical rotary Number of compressors 2 2 2 2 2 2 2 2Oil charge circuit 1/2 (8) (l) 6/6 7/7 9/9 10/10 10/10 10/10 15/11 15/15Evaporator type Tube-in-shell/Internally finned copper tubes Evaporator water content (l) 106 269 223 204 204 204 415 415Evaporator water connection type VictaulicEvaporator water connection diameter (inches) 5 6 6 6 6 6 6 6Condenser type Internally finned copper tubes with aluminium finsTotal airflow (8) (m3/s) 23.4 28.5 27 27 37 39 44.9 46.8Number of fans 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6Fan speed (rpm) 930 930 930 930 930 930 930 930Sound power level (8) (dB(A)) 97 98 97 97 98 101 102 103Sound pressure level at 10 m (4) (8) (dB(A)) 65 65 64 65 66 69 70 70Minimum operating outdoor air temperature (5) (°C) 0Maximum operating outdoor air temperature (6) (°C) +40Minimum leaving water temperature (7) (°C) -12Maximum leaving water temperature (°C) +15Length (10) (mm) 3507 4426 4426 4426 5351 5351 6370 6370Width (10) (mm) 2260 2260 2260 2260 2260 2260 2260 2260Height (10) (mm) 2095 2095 2095 2095 2115 2115 2215 2215Shipping weight (10) (kg) 2624 2898 3403 3439 4132 4392 5108 5193Operating weight (10) (kg) 2736 3176 3635 3650 4345 4605 5535 5622

(1) At Eurovent conditions. 7°C leaving water temperature and 35°C entering condenser air temperature (2) Unit kW input(3) Including fans (4) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996 (5) -18°C minimum operating outdoor air temperature with low ambient option (6) Depending on high ambient option, maximum operating outdoor air temperature is 46-50°C (7) With ethylene glycol solution(8) Standard efficiency units standard fans(9) Conditions: 40-50°C hot water temperature and 35°C entering condenser air temperature(10) For standard units only. For this information on high efficiency units, contact your local sales office. Weights are given with aluminium fins, disconnect switch,isolators and pressure gauges.

Page 137: Train Instrument's

Unit size 085 100 115 125 145 150 165 180

Cooling Mode

Cooling capacity standard efficiency units (1) (kW) - 323.5 388.2 440.6 507.7 542.5 596.7 642.7Power input standard efficiency units (2) (kW) - 120.8 151.8 189.6 195.3 216.0 229.0 249.8Coefficient of Performance standard efficiency units (3) - 2.7 2.6 2.3 2.6 2.5 2.6 2.6Cooling capacity high efficiency units (1) (kW) 295.7 348.4 413.1 480.6 519.0 556.2 - -Power input high efficiency units (2) (kW) 98.8 117.5 148.0 181.0 187.9 208.0 - -Coefficient of Performance high efficiency units (3) 3.0 3.0 2.8 2.7 2.8 2.7 - -Total Heat Recovery Mode

Heating capacity standard efficiency units (9) (kW) - 251.58 308.19 367.27 392.87 424.65 459.39 497.1Heating capacity - high efficiency units (9) (kW) 216.6 250.92 307.54 366.16 392.58 424.29 - -Refrigerant R134aNumber of refrigerant circuits 2 2 2 2 2 2 2 2Refrigerant charge circuit1/circuit2 (8) (kg) - 51 / 48 61 / 58 62 / 59 80 / 78 80 / 78 92 / 89 92 / 90Compressor type Helical rotary Number of compressors 2 2 2 2 2 2 2 2Oil charge circuit 1/2 (8) (l) - 5 / 4 8 / 7 8 / 7 8 / 7 8 / 7 13 / 7 13 / 12Evaporator type Tube-in-shell/Internally finned copper tubes Evaporator water content (l) 106 269 223 204 204 204 415 415Evaporator water connection type VictaulicEvaporator water connection diameter (inches) 5 6 6 6 6 6 6 6Condenser type Internally finned copper tubes with aluminium fins Total airflow (8) (m3/s) 23.4 28.5 27 27 37 39 44.9 46.8Number of fans 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6Fan speed (rpm) 930 930 930 930 930 930 930 930Sound power level (8) (dB(A)) 97 98 97 97 98 101 102 103Sound pressure level at 10 m (4) (8) (dB(A)) 65 65 64 65 66 69 70 70Minimum operating outdoor air temperature (5) (°C) 0Maximum operating outdoor air temperature (6) (°C) +40Minimum leaving water temperature (7) (°C) -12Maximum leaving water temperature (°C) +15Length (10) (mm) - 4426 4426 4426 5351 5351 6370 6370Width (10) (mm) - 2260 2260 2260 2260 2260 2260 2260Height (10) (mm) - 2095 2095 2095 2115 2115 2225 2225Shipping weight (10) (kg) - 3063 3588 3623 4382 4642 5358 5443Operating weight (10) (kg) - 3347 3833 3848 4615 4875 5806 5891

(1) At Eurovent conditions. 7°C leaving water temperature and 35°C entering condenser air temperature (2) Unit kW input(3) Including fans (4) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996 (5) -18°C minimum operating outdoor air temperature with low ambient option (6) Depending on high ambient option, maximum operating outdoor air temperature is 46-50°C (7) With ethylene glycol solution (8) Standard efficiency units standard fans (9) Conditions: 40-50°C hot water temperature and 35°C entering condenser air temperature(10) For standard units only. For this information on high efficiency units, contact your local sales office.

General data - Total heatrecovery option

PROD-PRC014-E4

Water S

ystem

sR

TAD

135

Page 138: Train Instrument's

136PROD-PRC014-E4

Customer benefits • Trane helirotor compressor - designed to perform, built

to last: low cost of ownership• State of the art control to guarantee superior

dependability: low cost of ownership• R134a refrigerant for high performance: low energy consumption

Main features• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only four moving parts, suction-gas-cooled motor

• Competitive physical footprint• Single power connection• Exact load matching• Low sound levels• Falling film evaporator - high COP and reduced

refrigerant charge• Factory-mounted star-delta starter panel• Close spacing installation - 1.2 m side clearances• Application flexibility• LonTalk® compatible

Options• Power disconnect switch • Low ambient (down to -18°C) operation• High ambient (up to 52°C) operation• High efficiency operation• Low noise version equipped with low-speed fans and

compressor sound attenuating enclosure

• Black epoxy-coated aluminium fins• Copper fins• Night noise setback available on low noise version• Protection grilles for condensing coils and service area• Coil protection for condenser only• High and low pressure gauges

Accessories• Victaulic connection kit • Neoprene isolators• Flow switch

ControlAdaptive Control™ microprocessor featuring:• Easy-to-use DynaView operator interface panel• External Auto/Stop• External interlock• Chilled water pump control• Ice-making card (optional)• Chilled water and current-limit remote setpoint card

(optional)• LonTalk® communication card COMM5

Axial fans, helical rotary compressor400-1500 kW

Outdoor chillers

RTAC

RTAC

TracerTM CH530

Page 139: Train Instrument's

General data

PROD-PRC014-E4

Unit size 140 155 170 185 200 250 275 300 350 375 400

Cooling capacity (1) (kW) 487.3 532.3 578.7 639.9 705.7 840.3 936.0 1063.2 1177.2 1305.1 1431.7

Power input (2) (kW) 171.8 189.7 207.9 226.7 246.3 295.8 333.4 373.2 422.3 462.2 501.8Coefficient of Performance (3) 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.8 2.8 2.9

Refrigerant R134aNumber of refrigerant circuits 2Refrigerant charge circuit1/circuit 2 (kg) 75/75 79/75 79/79 113/108 113/113 152/91 166/91 188/91 166/166 188/166 188/188

Compressor type Helical rotaryNumber of compressors 2 2 2 2 2 3 3 3 4 4 4

Oil charge circuit1/circuit 2 (l) 7.5/7.5 7.5/7.5 7.5/7.5 10/7.5 10/10 17/8 17/8 17/8 17/17 19/17 19/19

Evaporator type Tube-in-shell/Falling filmEvaporator water content (l) 112 122 127 135 147 198 223 239 264 280 294Evaporator water connection type VictaulicEvaporator water connection diameter (inches) 4 4 6 6 6 8 8 8 8 8 8

Condenser type Internally finned copper tubes with aluminium fins

Total airflow (m3/s) 35.8 39.5 43.2 47.6 51.9 61.8 69.2 77.8 86.4 95.1 103.7

Number of fans per circuit 4/4 5/4 5/5 6/5 6/6 8/6 10/6 12/6 10/10 12/10 12/12

Fan speed (rpm) 915

Sound power level (dB(A)) 98 98 98 99 100 100 101 102 101 102 103Sound pressure level at 10 m (4) (dB(A)) 65 66 66 67 67 67 68 69 68 69 70Minimum operating outdoor air temperature (5) (°C) 0Maximum operating outdoor air temperature (6) (°C) 46Minimum leaving water temperature (7) (°C) -8Maximum leaving water temperature (°C) 15

(1) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature (2) Unit kW input (3) Including fans(4) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996 (5) -18°C minimum operating outdoor air temperature with low ambient option (6) Depending on high ambient option, maximum operating outdoor air temperature is 46-52°C(7) With ethylene glycol solution

Water S

ystem

sR

TAC

137

Page 140: Train Instrument's

138PROD-PRC014-E4

Dimensions, weights and clearances

X

Y

Z

Accesscontrol panel

Unit size 140 155 170 185 200 250 275 300 350 375 400

Power supply (V/Ph/Hz) 400/3/50

Standard starter type Star-delta

Start-up amps (1) (A) 475 512 552 620 669 696 759 836 876 953 1059

Maximum amps (2) (A) 398 437 475 525 574 687 768 867 955 1054 1153

Maximum cable size (mm²) 2x240 2x240 2x240 2x240 2x240 4x185 4x185 4x195 4x195 6x240 6x240

Disconnect switch size (A) 625 925 925 925 925 1000 1000 1250 1250 1600 1600

Fan motor power (3) (kW) 2.05

(1) Equals the sum of the largest compressor starting Amps, plus the other(s) compressor(s) RLA, plus all the fans FLA, plus the control Amps(2) Maximum compressors FLA + all fans FLA + control amps (3) Per fanFor standard units only. For this information on high efficiency units, contact your local sales office.

Dimensions(mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size

Electrical data

Weights (1) (2)

X(2) Y Z A B C

140 5088 2240 2445 4525 4623 1900 1200 1000

155 5088 2240 2445 4691 4799 1900 1200 1000

170 5088 2240 2445 4834 4936 1900 1200 1000

185 6007 2240 2445 5399 5508 1500 1200 1000

200 6007 2240 2445 5508 5629 1500 1200 1000

250 9138 2250 2530 7760 7958 1000 1200 1200

275 9138 2250 2530 8522 8745 1000 1200 1200

300 10056 2250 2530 9235 9474 1000 1200 1200

350 10406 2250 2530 11516 10780 1200 1200 1200

375 11325 2250 2530 11157 11437 1200 1200 1200

400 12244 2250 2530 11758 12052 1200 1200 1200

(1) With aluminium fins(2) For standard units only. For this information on high efficiency units, contact your local sales office.

Page 141: Train Instrument's

Evaporator water pressure drop

PROD-PRC014-E4

1

10

100

1000

10

2

3 5

6

78

9

10

11

12

13

14

15

16

20

5

2

20

50

500

1

4

50 100 200

200

1 = RTAC 120HE - 140 STD2 = RTAC 130HE - 155 STD3 = RTAC 170 STD - 140 HE4 = RTAC 185 STD - 155 HE5 = RTAC 200 STD - 170 HE6 = RTAC 185 HE7 = RTAC 200 HE8 = RTAC 250 STD

9 = RTAC 275 STD 10 = RTAC 300 STD - 250 HE11 = RTAC 275 HE - 300 HE12 = RTAC 350 STD13 = RTAC 375 STD 14 = RTAC 400 STD - 350 HE15 = RTAC 375 HE16 = RTAC 400 HE

Water S

ystem

sR

TAC

139

Water Flow l/s

kP

a

Page 142: Train Instrument's

140PROD-PRC014-E4

Performance data - standard unit

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)Unit Size

Leaving Water

Temperature

(°C)

Condenser Entering Air Temperature (°C)30 35 40 46

140 STD 493.3 141.9 461.7 153.7 429.3 166.7 389.57 183.9

155 STD 539.0 156.7 504.6 169.2 469.4 183.0 426.49 201.5

170 STD 587.2 172.1 550.6 185.4 513.0 200.2 466.57 220

185 STD 648.7 187.6 609.0 202.0 568.5 218.0 518.26 239.5

200 STD 714.1 203.9 671.6 219.4 627.6 236.6 573.11 259.7

5 250 STD 851.6 244.9 799.2 264.4 745.4 286.0 678.94 314.7

275 STD 948.3 276.3 889.9 297.2 830.1 320.4 756.29 351.6

300 STD 1076.3 309.5 1011.9 332.5 945.5 358.2 863.53 392.5

350 STD 1194.7 350.6 1120.6 377.0 1044.3 406.5 950.37 446

375 STD 1323.8 384.0 1243.6 412.6 1161.0 444.5 1058.67 487.3

400 STD 1450.7 417.0 1364.6 447.8 1275.3 482.1 1165.2 528.1

140 STD 526.7 147.3 493.3 159.3 459.2 172.4 417.35 189.9

155 STD 574.9 162.9 538.7 175.5 501.7 189.6 456.03 208.2

170 STD 625.5 179.0 586.8 192.5 547.1 207.4 497.87 227.4

185 STD 690.9 195.2 649.1 209.8 606.2 226.1 553.07 247.8

200 STD 760.5 212.2 715.5 228.0 668.7 245.6 611.08 269.1

7 250 STD 907.5 254.5 852.3 274.3 795.3 296.2 725.35 325.3

275 STD 1010.2 287.6 948.3 308.7 885.0 332.3 806.92 363.8

300 STD 1145.9 322.3 1078.0 345.7 1007.7 371.8 920.84 406.8

350 STD 1271.7 364.8 1193.0 391.5 1125.5 421.2 1013.31 461

375 STD 1408.5 399.7 1323.8 428.7 1236.2 461.1 1228.64 504.4

400 STD 1543.5 434.2 1451.1 465.5 1357.9 500.5 1241.5 547.2

140 STD 560.8 153.0 525.6 165.1 489.8 178.4 445.83 196

155 STD 611.8 169.4 573.8 182.1 534.8 196.3 486.61 251.1

170 STD 664.5 186.2 623.7 199.8 581.9 214.9 530.21 235

185 STD 734.1 203.2 689.8 217.9 644.5 234.4 588.58 256.4

200 STD 808.0 220.9 760.5 237.0 711.3 254.9 650.46 278.8

9 250 STD 965.1 264.5 906.8 284.6 846.7 306.8 772.82 336.3

275 STD 1073.4 299.4 1008.0 320.7 941.2 344.5 858.96 376.4

300 STD 1217.6 335.7 1145.5 359.5 1071.7 386.1 979.91 421.6

350 STD 1350.1 379.5 1267.2 406.5 1182.1 436.4 1077.65 476.5

375 STD 1495.7 416.1 1405.7 445.5 1313.6 478.2 1200.01 522.1

400 STD 1638.8 452.3 1542.5 484.1 1443.0 519.6 1319.91 567.2

Notes:(1) Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 m²°K/kW(2) Consult Trane representative for performance at temperatures outside of the ranges shown(3) kW input = compressor power input only.(4) COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.(5) Ratings are based on an evaporator temperature drop of 5°C.(6) Interpolation between points is permissible. Extrapolation is not permitted.(7) Operation above 40°C = with High Ambient Option.

Page 143: Train Instrument's

Performance data - high efficiency unit

PROD-PRC014-E4

Evaporator

Leaving

Water

Temperature

(°C) Unit size

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Power

input

(kW)

Power

input

(kW)

Power

input

(kW)

Power

input

(kW)

Power

input

(kW)

Condenser Entering Air Temperature (°C)

Water S

ystem

sR

TAC

141

30 35 40 45 46 52

120 HE 421.6 112.8 395.2 122.0 367.4 132.4 339.3 143.9 368.8 160.5 298.5 162.0

130 HE 465.2 123.9 436.0 134.0 406.1 145.3 375.2 157.8 408.9 175.4 330.9 177.4

140 HE 512.3 135.5 481.0 146.6 448.6 158.9 415.6 172.5 444.4 192.4 368.1 193.7

155 HE 556.6 149.7 522.5 161.5 487.7 174.7 451.8 189.3 482.0 209.9 400.5 212.2

170 HE 603.4 164.5 566.4 177.0 528.8 191.0 489.8 206.6 537.6 229.5 434.2 231.1

185 HE 668.0 180.3 628.3 193.8 587.9 209.0 546.0 225.9 595.6 249.6 485.9 252.5

5 200 HE 736.6 196.6 694.1 211.2 650.1 227.6 604.8 245.8 699.3 306.4 539.4 274.3

250 HE 875.1 239.3 821.7 257.9 766.8 278.7 710.9 301.6 783.0 336.8 593.2 317.2

275 HE 976.0 265.5 917.3 285.1 857.2 307.1 795.3 331.6 894.5 377.1 706.4 370.1

300 HE 1105.8 298.4 1042.1 320.0 976.4 344.3 908.2 371.3 981.3 425.6 810.1 413.8

350 HE 1226.7 335.1 1152.2 360.0 1075.5 387.9 997.1 419.0 981.3 425.6 884.6 467.9

375 HE 1359.6 368.5 1279.8 395.4 1197.2 425.6 1112.5 459.2 1095.2 466.4 990.5 512.1

400 HE 1494.3 402.2 1408.2 431.0 1319.2 463.5 1227.8 499.5 1209.2 507.2 1095.2 556.2

120 HE 451.8 117.0 423.7 126.3 394.5 136.8 364.3 148.5 358.3 151.0 321.4 166.9

130 HE 498.2 128.5 467.3 138.7 435.6 150.2 403.3 162.9 396.6 165.6 356.5 182.7

140 HE 548.1 140.5 515.1 151.7 481.0 164.1 446.2 177.9 439.2 180.8 396.3 199.3

155 HE 594.9 155.4 559.0 167.3 522.1 180.7 484.2 195.4 476.8 198.5 430.0 218.5

170 HE 644.5 171.0 605.5 183.6 565.4 197.8 524.2 213.5 516.2 216.8 465.5 238.2

185 HE 713.0 187.4 671.2 201.1 628.0 216.5 584.0 233.6 574.9 237.2 520.4 260.4

7 200 HE 786.2 204.5 741.2 219.3 694.4 235.9 646.6 254.4 637.1 258.3 577.3 283.4

250 HE 934.9 248.7 878.7 267.5 820.6 288.5 761.2 311.8 749.3 316.7 601.6 307.5

275 HE 1042.1 276.2 980.3 296.0 916.6 318.3 851.2 343.0 838.2 348.3 757.4 381.9

300 HE 1180.7 310.6 1112.8 332.5 1043.2 357.2 971.1 384.6 956.7 390.4 867.4 427.7

350 HE 1308.7 348.4 1229.9 373.5 1149.0 401.6 1066.4 432.9 1049.5 439.6 947.6 482.1

375 HE 1450.0 383.3 1365.6 410.4 1278.4 441.0 1188.8 475.0 1170.8 482.2 1049.2 522.5

400 HE 1593.8 418.6 1502.7 447.8 1408.9 480.7 1311.8 517.3 1292.1 525.1 1153.3 564.7

120 HE 482.8 121.3 452.5 130.8 421.9 141.5 390.3 153.3 383.6 155.8 344.9 171.9

130 HE 532.3 133.3 499.6 143.7 466.2 155.2 432.1 168.1 425.1 170.8 382.9 188.1

140 HE 585.1 145.7 550.3 157.0 514.4 169.6 477.5 183.4 470.1 186.3 425.1 205.0

155 HE 634.3 161.4 596.3 173.4 557.6 186.8 517.6 201.7 509.8 204.8 458.1 223.6

170 HE 686.7 177.7 645.5 190.4 603.0 204.7 559.8 220.5 551.3 223.9 497.9 245.4

185 HE 759.1 194.8 715.2 208.7 669.8 224.2 623.0 241.5 613.5 245.2 547.4 264.0

9 200 HE 837.2 212.8 789.7 227.7 740.5 244.6 689.8 263.3 679.6 267.3 594.6 280.5

250 HE 996.4 258.4 937.0 277.5 875.8 298.8 813.3 322.3 800.6 327.3 609.0 297.2

275 HE 1110.4 287.3 1045.0 307.3 977.8 329.8 908.9 354.8 894.8 360.1 781.3 378.3

300 HE 1257.7 323.3 1186.0 345.5 1112.1 370.5 1036.2 398.4 1020.7 404.3 878.3 415.4

350 HE 1392.7 362.2 1309.7 387.4 1224.6 415.8 1137.4 447.2 1119.5 453.9 982.7 480.1

375 HE 1543.5 398.6 1454.2 426.1 1362.1 457.0 1267.5 491.4 1248.5 498.7 1063.2 507.2

400 HE 1696.8 435.7 1600.5 465.3 1501.0 498.7 1398.7 535.8 1377.9 543.7 1166.3 547.1

Notes :(1) Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 m²°K/kW(2) Consult Trane representative for performance at temperatures outside of the ranges shown(3) kW input = compressor power input only.(4) COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.(5) Ratings are based on an evaporator temperature drop of 5°C.(6) Interpolation between points is permissible. Extrapolation is not permitted.(7) Operation above 40°C = with High Ambient Option.

Page 144: Train Instrument's

142PROD-PRC014-E4

INDOOR CHILLERS

Page 145: Train Instrument's

50kW 200 400 1000 4000 6000600 2000 3000 5000

143

180 350 CGWN/CCUN

PROD-PRC014-E4

WA

TE

R S

YS

TE

MS

Light Commercial, Commercial andIndustrial Applications

INDOOR CHILLERS49 - 6000 kW

500 1500 RTHD

200 700 RTWB/RTUB

51 153 CGWH/CCUH

1400 3800CVGF

215 600 RTCA

2000 4800 ABSD

1300 6000ABTF

400 1630 ABSC

350 3900 ABDL

49 150 CGCL

132 168 RTRA

Page 146: Train Instrument's

144PROD-PRC014-E4

Customer benefits • Very low sound level installation: superior acoustic

comfort • Indoor installation: easy maintenance• Minimum maintenance requirements: saving of time and

money

Main Features • Scroll Compressors

- Hermetic, high efficiency, low vibration, low soundlevel

- Full internal overheating protections• External sheet metal parts are galvanized and finished

with powder paint RAL 9002• Access panels are quickly removable using a square key• Designed for indoor installation• Full factory refrigerant and oil charge • Maximum condenser leaving water temperature: 50°C

Options• 380, 400 and 415V power voltage• Control of the condenser leaving water temperature• 400 / 220V transformer for the control• Compressor sound attenuating jackets• High and low pressure gauges• Evaporator water pump command - single or double• Water filter

• Hydraulic module - for information, contact your localsales office

• Auxiliary card to display entering water temperature onthe evaporator or condenser, and/or to validate auxiliarytemperature set point with a remote contact (ships with2 water sensors with 5 meters cable).

• TCI-S card to communicate with BMS

ControlMicroprocessor control module SMM (Scroll ManagerModule) with liquid crystal display operator interfacecontrolling and indicating:• Evaporator leaving water temperature• Equalization of the number of starts and operating hours

of each compressor• Operating parameters• HP limitation• Low pressure protection• Short cycle protection • Remote ON / OFF per circuit (dry contact)• Failure indication per circuit (dry contact)• History of the last 20 defaultsAccess to current settings through a window on theelectrical panel

Scroll compressorPackaged chiller - condenserlesschiller 51-153 kW*

Indoor chillers

CGWH - CCUH

*Also available with R134a. For information, please contact your local Trane Sales Office.

CGWH/CCUH

SMM

Page 147: Train Instrument's

General data

PROD-PRC014-E4

Water S

ystem

s

CG

WH

- C

CU

H

145

Unit size 115 120 125 225 230 235 240 250

Cooling capacity CGWH (1) (kW) 51.1 64.1 77.0 90.7 102.8 115.9 127.2 154.5

Power input CGWH (1) (kW) 14.9 18.8 22.7 25.1 29.9 33.4 37.6 45.1Coefficient of Performance CGWH 3.43 3.41 3.39 3.61 3.46 3.47 3.38 3.44Cooling capacity CCUH (2) (kW) 51.0 63.9 76.8 90.4 102.4 114.5 127.2 153.2

Power input CCUH (2) (kW) 15.0 18.8 22.7 26.1 30.1 33.7 37.6 45.5Coefficient of Performance CCUH 3.41 3.39 3.38 3.46 3.40 3.37 3.38 3.37Refrigerant R407C Number of refrigerant circuits 1 1 1 2 2 2 2 2Refrigerant chargeCGWH circuit 1/circuit 2 (kg) 5/- 7/- 9/- 5/5 7/5 9/5 7/7 9/9Refrigerant charge CCUN (kg) Holding charge - 2Compressor type Scroll Number of compressors 2 2 2 3 3 3 4 4Number of capacity steps 2 2 2 3 3 3 4 4Oil charge circuit 1/circuit 2 (l) 7.6/- 10.0/- 12.4/- 7.6/8.2 10.0/6.2 12.4/6.2 10.0/10.0 12.4/12.4 Evaporator type Brazed plateEvaporator water content (l) 4.7 5.9 7 8.9 10.3 12.3 12.3 16.1Evaporator water connection type ISO R7 maleEvaporator water connection diameter (inches) 1 ½ 1 ½ 1 ½ 2 2 2 2 ½ 2 ½ Condenser type CGWH Brazed plate Condenser water content CGWH (l) 4.7 5.9 7 8.9 10.3 12.3 12.3 16.1Condenser water connection type CGWH ISO R7 male Condenser water connectiondiameter CGWH (inches) 1 ½ 1 ½ 1 ½ 2 2 2 2 ½ 2 ½ Discharge and liquid connection type CCUH BrazedDischarge connection CCUHcircuit 1/circuit 2 (inches (ODF)) 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1""3/8Liquid connection CCUHcircuit 1/circuit 2 (inches (ODF)) 7/8Sound power level (3) (dB (A)) 75 79 81 81 82 83 82 84Min/Max leaving water temperaturecondenser CGWH (°C) +20/+50Min/Max sat discharge temperaturecondenser CCUH (4) (°C) +30/+55Min/Max evaporator leavingwater temperature CGWH/CCUH (°C) -12/+15

(1) Temperature of water entering/leaving evaporator: 12/7°C condenser: 30/35°C, with R407C (2) Temperature of water entering/leaving: 12/7°C, Condenser 45°C - subcooling 5K with R407C (3) At full load, in accordance with ISO 3746 -1996 (4) Dew point

Page 148: Train Instrument's

146146PROD-PRC014-E4

Dimensions, weights and clearances

A

A

A

A

Z

YX

Access tocontrol panel

Electrical data

Z

YX

Sizes 115-125 Sizes 225-250

Weights

Dimensions Shipping Weight Operating Weight Minimum clearance

(mm) CGWN/CCUN (kg) CGWN/CCUN (kg) (mm)

Unit size X Y Z A

115 1001 800 1545 428/405 412/389 800

120 1001 800 1545 460/432 444/416 800

125 1001 800 1545 492/459 476/443 800

225 2002 800 1545 499/657 668/626 800

230 2002 800 1545 733/686 702/655 800

235 2002 800 1545 770/710 739/679 800

240 2002 800 1545 834/788 803/757 800

250 2002 800 1545 904/846 873/815 800

Unit size 115 120 125 225 230 235 240 250

Power supply (V/Ph/Hz) 400/3/50

Standard starter type Direct

Start-up amps (A) 137 192 201 209 218 227 236 254

Maximum amps (A) 35.4 44.3 53.2 62.0 70.9 79.8 88.6 106.4

Maximum cable size (mm²) 16 35 35 35 50 50 95 95

Page 149: Train Instrument's

Evaporator water pressure drop

PROD-PRC014-E4

Water S

ystem

s

CG

WH

- C

CU

H

147

10

50

100

1

3 4 76521

2 3 4 5 6 107 98

20

Water Flow l/s

kP

a

1 = CGWH/CCUH 1152 = CGWH/CCUH 1203 = CGWH/CCUH 1254 = CGWH/CCUH 2255 = CGWH/CCUH 2306 = CGWH/CCUH 235 2407 = CGWH/CCUH 250

Page 150: Train Instrument's

148148PROD-PRC014-E4

Condenser water pressure drop - CGWH

1 2 10

10

100

3 987654

50

3 4 76521

20

Water Flow l/s

kP

a

1 = CGWH 1152 = CGWH 1203 = CGWH 1254 = CGWH 2255 = CGWH 2306 = CGWH 235 2407 = CGWH 250

Page 151: Train Instrument's

Evaporatorleaving watertemperature

(°C) Unit size

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Performance data - CCUH

Performance data - CGWH

PROD-PRC014-E4

Evaporatorleaving watertemperature

(°C)

Unitsize

Coolingcapacity

(kW)*

Power input (kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Cooling capacity

(kW)*

Powerinput (kW)

Coolingcapacity

(kW)*

Powerinput (kW)

Water S

ystem

sC

GW

H -

CC

UH

149

Condenser leaving water temperature (°C) (Delta T° 5K)

25 30 40 50

5 53.1 11.1 51.0 12.3 46.2 15.5 40.7 19.8115 7 56.4 11.2 54.2 12.4 49.2 15.6 43.4 20.0

9 59.7 11.2 57.4 12.4 52.2 15.7 46.1 20.25 66.5 14.0 63.9 15.6 58.0 19.6 51.2 24.9

120 7 70.6 14.2 67.9 15.7 61.7 19.8 54.5 25.19 74.8 14.3 71.9 15.8 65.4 19.9 57.9 25.35 80.0 17.0 76.8 18.9 69.8 23.7 61.8 29.9

125 7 84.8 17.1 81.5 19.0 74.1 23.9 65.7 30.29 89.8 17.3 86.3 19.2 78.5 24.1 69.6 30.45 94.4 19.5 90.7 21.6 82.3 27.1 72.6 34.5

225 7 100.3 19.6 96.3 21.7 87.5 27.4 77.3 34.99 106.2 19.8 102.1 21.9 92.8 27.6 82.1 35.25 107.3 22.4 103.0 24.8 93.6 31.1 82.7 39.4

230 7 113.8 22.5 109.4 25.0 99.4 31.4 87.9 39.79 120.4 22.7 115.7 25.2 105.3 31.6 93.2 40.15 120.5 25.1 115.8 27.8 105.2 34.8 93.2 43.9

235 7 127.7 25.3 122.8 28.0 111.6 35.1 99.0 44.39 135.0 25.5 129.7 28.3 118.1 35.5 104.8 44.85 133.4 28.0 128.1 31.1 116.2 39.0 102.6 49.6

240 7 141.3 28.2 135.7 31.3 123.2 39.4 108.9 50.09 149.2 28.4 143.4 31.5 130.3 39.7 115.2 50.45 161.9 33.6 155.5 37.2 141.2 46.6 125.0 58.8

250 7 171.1 33.8 164.3 37.5 149.4 47.0 132.3 59.39 180.1 34.1 173.1 37.8 157.4 47.4 139.6 59.8

*At evaporator outlet

Powerinput(kW)

Saturated discharge temperature (°C)

35 40 45 55

115 52.5 11.4 50.4 12.6 48.1 14.2 42.8 18.2120 65.9 14.4 63.2 16.0 60.3 17.9 53.8 22.8125 79.2 17.5 76.0 19.4 72.5 21.7 64.8 27.4

5 225 93.3 20.1 89.4 22.3 85.3 25.0 76.0 31.9230 105.8 23.2 101.5 25.7 96.8 28.8 86.3 36.5235 118.6 26.2 113.7 29.1 108.4 32.6 96.8 41.1240 131.9 28.8 126.5 32.0 120.7 35.9 107.6 45.6250 159.4 34.9 152.8 38.8 145.7 43.4 130.0 54.8

115 56.0 11.4 53.7 12.6 51.3 14.2 45.8 18.1120 70.1 14.4 67.4 16.0 64.3 17.9 57.6 22.8125 84.2 17.5 80.9 19.4 77.3 21.7 69.2 27.5

7 225 99.3 20.1 95.3 22.3 91.0 25.0 81.3 31.9230 112.6 23.2 108.1 25.7 103.2 28.8 92.2 36.5235 126.0 26.2 120.9 29.1 115.4 32.6 103.2 41.2240 140.2 28.8 134.5 32.0 128.4 35.9 114.7 45.6250 168.9 35.0 162.1 38.9 154.7 43.5 138.3 54.9

115 59.4 11.4 57.1 12.6 54.6 14.1 48.9 18.1120 74.5 14.4 71.6 16.0 68.4 17.9 61.3 22.8125 89.4 17.5 85.9 19.4 82.1 21.8 73.7 27.5

9 225 105.5 20.1 101.3 22.3 96.8 25.0 86.6 31.9230 119.4 23.2 114.7 25.7 109.6 28.8 98.2 36.5235 133.5 26.2 128.2 29.2 122.5 32.6 109.7 41.2240 148.4 28.8 142.5 32.0 136.1 35.9 121.9 45.6250 178.3 35.0 171.2 38.9 163.5 43.5 146.4 54.9

* At evaporator outlet

Page 152: Train Instrument's

CGWN

150PROD-PRC014-E4

Customer benefits • Compact design + packaged hydraulic module (available

as an option) for easier installation: saving of time• Wide application flexibility for comfort and process

applications: fits the customer's exact requirements• State of the art control to guarantee superior

dependability: low cost of ownership

Main Features• Scroll Compressors

- Hermetic, high efficiency, low vibration, low soundlevel

- Full internal overheating protections• External sheet metal parts are galvanized and finished

with powder paint RAL 9002• Access panels are quickly removable using a square key

and mounted handles• Designed for indoor and outdoor installation• Full factory refrigerant and oil charge• Evaporator flow control• Maximum condenser leaving water temperature: 60°C• 380, 400 and 415V power voltage• 400 / 230V transformer for the control• Condenser water filter

Options• High Efficiency version

• Soft Starter• Phase & unbalanced detection• Control of the condenser leaving water temperature• Evaporator + water pump command - single or double• Condenser + water pump command - single or double

including return and supply water temperature sensor +outdoor air sensor + condenser flow control for winterfreeze

• External linear reset, auxiliary & external water set point• Ice making & compressor kW limiting• Compressor sound attenuating jackets• High and low pressure gauges• Four programmable relays for remote unit status• Hydraulic module including :

- single or dual evaporator pump including water filterand pressure tabs

- 2 stage condenser pump including flow control, con-denser return and leaving water temperature, outdoorair sensor and including water filter & pressure tabs forwinter freeze protection

- Speed inverter condenser pumps including flow con-trol, condenser return and leaving water temperature,outdoor air sensor and including water filter & pres-sure tabs for winter freeze protection

ControlAdaptive Control™ microprocessor-based controlfeaturing:• Easy to use DynaView operator interface• Alarm indicator programmable relays (options)• Ice making controls (optional)• Tracer Summit™ & LonTalk Communication interface

(optional)• Leaving condenser water temperature control (optional)

Scroll compressorPackaged chiller - condenserlesschiller 180-350 kW*

Indoor chillers

CGWN - CCUN

* Also available with R22 for applications outside of the European Union. Contact your local Trane Sales Office.

TracerTM CH530

Page 153: Train Instrument's

General data - standard efficiency

PROD-PRC014-E4

Water S

ystem

s

CG

WN

- C

CU

N

151

Unit size 205 206 207 208 209 210 211

Cooling capacity CGWN (1) (kW) 179 209 235 260 288 320 345

Power input CGWN (1) (kW) 42.3 48.2 55.6 62.2 68.0 75.1 83.9Coefficient of Performance CGWN 4.24 4.33 4.22 4.18 4.24 4.26 4.11Cooling capacity CCUN (2) (kW) 182 196 237 263 292 321 349

Power input CCUN (2) (kW) 40.3 45.7 51.0 57.4 63.0 70.0 78.4Coefficient of Performance CCUN 4.50 4.29 4.65 4.58 4.63 4.59 4.45Refrigerant R407C Number of refrigerant circuits 2 2 2 2 2 2 2Refrigerant charge CGWN circuit 1/circuit 2 (kg) 10 / 10 11 / 11 12 / 12 13 / 13 14 / 14 15 / 15 17 / 17Refrigerant charge CCUN (kg) 2/2Compressor type Scroll Number of compressors 4 4 4 4 4 4 4Number of capacity steps 4 6 6 6 4 6 4Oil charge circuit 1/circuit 2 (kg) 8.2/8.2 8.8/8.8 10.4/10.4 11.0/11.0 12.6/12.6 12.6/12.6 12.6/12.6Evaporator type Brazed plate Evaporator water content (l) 17.2 19.7 22.2 25.6 29.0 32.4 35.7Evaporator water connection type Victaulic Evaporator water connection diameter (inches) 3" 3" 4" 4" 4" 4" 4"Condenser type CGWN Brazed plate Condenser water content CGWN (l) 19.7 22.2 25.6 29.0 32.3 35.7 42.4Condenser water connection type CGWN Victaulic Condenser water connection diameter CGWN (inches) 3" 3" 3" or 4" 4" 4" 4" 4"Discharge and liquid connection type BrazedDischarge connection (A/B) (inches) 1"5/8Liquid connection (A/B) (inches) 1"1/8Sound power level (3) (dB(A)) 85 84 86 85 87 87 87Min/Max leaving watertemperature condenser CGWN (°C) +20 (5) /+58Min/Max evaporator leavingwater temperature CGWN (°C) -12/+17Min/Max sat dischargetemperature condenser CCUN (4) (°C) 25/+67Min/Max leaving water temperature CCUN (°C) -12/+18

(1) Temperature of water entering/leaving evaporator: 12/7°C condenser: 30/35°C, with R407C (2) Temperature of water entering/leaving: 12/7°C, Condenser 45°C - subcooling 5K with R407C (3) At full load, in accordance with ISO 3746 -1996, without sound attenuator(4) Dew point(5) At unit start-up: with 2 condenser pumps = 10°C, with speed inverter pump = -10°C

Page 154: Train Instrument's

152152PROD-PRC014-E4

Dimensions, weights and clearances

Electrical data

Unit size 205 206 207 208 209 210 211

Power Supply (V/Ph/Hz) 400/3/50Standard starter type DirectStart-up amps direct start (A) 308 345 405 426 444 508 530Start-up amps with soft starter (A) 229 255 296 317 335 380 402Maximum amps (1) (A) 139 158 180 201 219 246 268Maximum cable size (mm²) 95 95 150 150 150 150 150

(1) At maximum rated conditions including evaporator and condenser pumps

(1) Including water connections(2) Without any pumps

B

B

A

B

Access tocontrol panel

WeightsMinimum clearance

(mm)

Unit size Dimensions

(mm)

Shipping weight

(kg)

Operating Weight (2)

(kg)A B

X Y Z CGWN CCUN CGWN CCUN (mm) (mm)

205 2545 880 1842 1170 1070 1240 1120 1000 800

206 2545 880 1842 1230 1120 1310 1170 1000 800

207 2545 880 1842 1360 1230 1460 1300 1000 800

208 2545 880 1842 1430 1290 1540 1370 1000 800

209 2545 880 1842 1500 1340 1610 1420 1000 800

210 2545 880 1842 1590 1430 1710 1510 1000 800

211 2545 880 1842 1690 1500 1820 1590 1000 800

Page 155: Train Instrument's

PROD-PRC014-E4

Water S

ystem

s

CG

WN

- C

CU

N

153

12

34

56

720

10

100

50

1 10 100505

kPa

l/s

kP

a

1 = CGWN/CCUN 2052 = CGWN/CCUN 2063 = CGWN/CCUN 2074 = CGWN/CCUN 2085 = CGWN/CCUN 2096 = CGWN/CCUN 2107 = CGWN/CCUN 211

20

10

100

50

1 10 100505

kPa

123

45

6

l/s

kP

a

1 = CGWN 205/2062 = CGWN 2073 = CGWN 2084 = CGWN 2095 = CGWN 2106 = CGWN 211

Evaporator water pressure drop

Condenser water pressure drop

Page 156: Train Instrument's

154154PROD-PRC014-E4

Performance data - CGWN

Evaporatorleaving watertemperature

(°C)Unitsize

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Condenser leaving water temperature (°C) (Delta T° 5K)

25 35 45 55

5 182 34.6 167 42.1 149 51.4 131 62.6205 7 196 34.9 179 42.3 161 51.5 141 63.0

9 210 35.1 192 42.4 173 51.3 152 63.85 210 39.4 194 47.9 174 59.6 151 73.9

206 7 226 39.8 209 48.2 187 59.1 162 73.59 242 40.2 224 48.6 202 59.4 176 73.05 238 45.3 218 55.2 195 68.0 170 83.6

207 7 256 45.8 235 55.5 209 68.2 183 84.09 274 46.1 251 56.0 225 68.3 198 83.75 262 50.8 242 61.6 217 76.8 188 96.2

208 7 281 51.3 260 62.2 234 78.0 203 96.89 301 51.8 279 63.0 252 77.7 219 95.55 291 55.0 269 67.3 240 83.3 209 103.3

209 7 312 55.4 288 68.0 258 83.3 226 103.99 334 55.8 309 68.7 278 84.0 243 104.55 325 61.3 298 74.2 265 91.7 228 113.8

210 7 349 62.1 320 75.1 286 91.7 247 114.69 374 62.9 343 75.8 307 92.5 267 115.55 351 68.2 320 83.0 284 101.5 244 126.3

211 7 376 69.1 344 83.9 307 102.5 264 127.39 403 70.2 370 84.2 330 103.5 286 128.3

*At evaporator outlet

Page 157: Train Instrument's

PROD-PRC014-E4

Water S

ystem

sC

GW

N -

CC

UN

155

Evaporatorleaving watertemperature

(°C)

Unit

size

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Powerinput(kW)

Coolingcapacity

(kW)*

Performance data - CCUN

Powerinput(kW)

Saturated discharge temperature (°C)

40 50 60

5 169 40.4 151.1 49.65 132.7 61.01205 7 181 40.3 162.9 49.59 143.3 61.08

9 195 40.2 175.2 49.47 154.3 61.065 196 45.7 176.3 56.93 154.0 71.53

206 7 211 45.8 190.1 57.01 166.7 71.589 226 45.9 204.5 57.05 179.9 71.595 221 50.9 197.9 63.50 173.1 79.33

207 7 237 51 213.2 63.63 187.1 79.429 255 51.1 229.1 63.75 201.8 79.485 245 57.1 219.9 71.91 191.5 91.42

208 7 263 57.4 236.9 72.17 207.4 91.469 282 57.7 254.6 72.45 223.9 91.545 272 62.7 243.5 78.43 212.4 98.64

209 7 292 63 262.1 78.74 229.7 98.719 312 63.2 281.4 79.07 247.8 98.835 301 69.3 269.0 86.59 232.7 109.00

210 7 324 69.7 290.0 86.90 252.3 109.209 348 70.1 311.9 87.23 272.8 109.305 324 77.9 288.2 97.24 247.7 122.40

211 7 349 78.4 311.2 97.58 269.2 122.709 375 78.9 335.1 97.91 291.6 123.00

* At evaporator outlet

Page 158: Train Instrument's

156PROD-PRC014-E4

Customer benefits • Wide application flexibility for comfort and process

applications: fits the customer's exact requirements• Trane helirotor compressor - designed to perform, built

to last: superior reliability and low cost of ownership• R134a refrigerant for high performance: low energy

consumption

Main Features• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only four moving parts, suction-gas-cooled motor

• Fully modulating load control (15-100%)• Compact physical footprint - fits through standard

single-width doors• Bolt-together construction for easy unit disassembly• Simplified piping - the only piping required is for the

evaporator (and condenser on RTWB) connections• Single power connection - reduced wiring costs• Tube-in-shell evaporator (and condenser on RTWB)• Factory-mounted star-delta starter panel• Tracer Summit™ capabilities

Options• Ice making controls• Disconnect switch• Condenser-water temperature sensors (RTWB)• Compressor sound attenuating enclosure• Hydraulic module - for information, contact your local

sales office• 2-pass condenser (RTWB)

Accessories• Flow switch(es)• Neoprene isolators

ControlAdaptive Control™ microprocessor featuring:• Unit control module with Clear Language Display• External Auto/Stop• Chilled water flow interlock• External interlock• Chilled water pump control• Alarm indication contacts• Ice-making card (optional)• Leaving condenser water temperature control (optional

for RTWB) • Tracer communication card Comm 3 (optional)• Chilled water and current-limit remote setpoint card

(optional)• Remote control operator interface panel

Helical rotary compressorPackaged chiller - Condenserlesschiller 200-700 kW

Indoor chillers

RTWB - RTUB

UCM-CLD

RTWB

Page 159: Train Instrument's

General data

PROD-PRC014-E4

Unit size 207 208 210 211 212 214 216 217 218 220 222 224

Cooling capacity RTWB (1) (kW) 215 251 320 338 362 435 472 508 553 600 693 749

Power input RTWB (1) (kW) 48 58 77 82 87 100 110 121 134 151 174 192Coefficient of Performance RTWB 4.4 4.4 4.2 4.1 4.1 4.4 4.3 4.2 4.1 4.0 4.0 3.9Cooling capacity RTUB (1) (kW) 198 234 295 313 336 410 447 483 524 571 665 723

Power input RTUB (1) (kW) 53 63 82 87 93 104 113 123 137 154 173 188Coefficient of Performance RTUB 3.7 3.7 3.6 3.6 3.6 4.0 4.0 3.9 3.8 3.7 3.9 3.8Refrigerant R134a Number of refrigerant circuits 2Refrigerant chargecircuit 1/circuit 2 RTWB (kg) 39/39 39/39 60/60 60/60 60/60 60/60 60/60 60/60 69/69 69/69 74/74 74/74 Refrigerant chargecircuit 1/circuit 2 RTUB (kg) 13/13 13/13 20/20 20/20 20/20 20/20 20/20 20/20 23/23 23/23 25/25 25/25Compressor type Helical rotary Number of compressors 2Oil charge circuit 1/circuit 2 (l) 6/6 6/6 7/7 7/7 7/7 8/8 8/8 8/8 8/8 8/8 11/8 11/11Evaporator type Tube-in-shell/DXEvaporator water content (l) 105 105 265 220 220 200 200 200 415 415 560 560Evaporator waterconnection type Victaulic Evaporator waterconnection diameter (inches) 5 5 6 6 6 6 6 6 6 6 6 6Condenser type RTWB Tube-in-shell/Flooded Condenser water content RTWB (l) 60 60 55 66 66 75 75 75 78 78 78 78Condenser waterconnection type RTWB Victaulic Condenser water connectiondiameter RTWB (inches) 5Sound power level RTWB (2) (dB(A)) 94 95 97 98 99 96 96 97 98 98 99 100Sound power level RTUB (2) (dB(A)) 95 95 97 98 99 96 97 97 98 99 100 101Sound pressure levelat 1 m RTWB (2) (dB(A)) 77 77 78 79 80 77 78 78 79 80 80 81Sound pressurelevel at 1 m RTUB (2) (dB(A)) 77 77 79 80 81 78 78 79 79 80 81 82Min/max operating ambientair temperature RTWB (°C) 5/60Min/max leaving chilledwater temperature RTWB (°C) -12/15Min/max operating ambientair temperature RTUB (°C) 5/50Min/max leaving chilledwater temperature RTUB (°C) -12/15

(1) Temperature of water entering/leaving evaporator: 12/7°C at 0.0176 m2 k/kW, condenser 30/35°C at 0.044 m2 k/kW(2) Without sound attenuating enclosure at full load, data in accordance with ISO 3764-1996

Water S

ystem

sR

TW

B -

RT

UB

157

Page 160: Train Instrument's

158158PROD-PRC014-E4

Dimensions, weights and clearances

Electrical data

Access tocontrol panel

Dimensions (1)(mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size

Weights (1)

X Y Z A B C D

RTWB/RTUB 207 2880 890 1810 2525/2200 2670/2280 920 1615 800 600

RTWB/RTUB 208 2880 890 1810 2525/2200 2670/2280 920 1615 800 600

RTWB/RTUB 210 4150 890 1900 3200/2750 3415/2935 920 2250 800 600

RTWB/RTUB 211 4150 890 1900 3300/2800 3545/3010 920 2250 800 600

RTWB/RTUB 212 4150 890 1900 3300/2800 3545/3010 920 2250 800 600

RTWB/RTUB 214 4150 890 1900 3400/2925 3665/3100 920 2250 800 600

RTWB/RTUB 216 4150 890 1900 3400/2925 3665/3100 920 2250 800 600

RTWB/RTUB 217 4150 890 1900 3400/2925 3665/3100 920 2250 800 600

RTWB/RTUB 218 4150 890 2008 4100/3600 4580/3975 920 2250 800 600

RTWB/RTUB 220 4150 890 2008 4300/3750 4755/4150 920 2250 800 600

RTWB/RTUB 222 4150 890 2097 4625/4100 5240/4625 920 2250 800 600

RTWB/RTUB 224 4150 890 2097 4650/4125 5275/4660 920 2250 800 600

(1) With compressor sound attenuating enclosure

Unit size 207 208 210 211 212 214 216 217 218 220 222 224

Power supply (V/Ph/Hz) 400/3/50

Standard starter type Star-delta

Start-up amps RTWB (1) (A) 170 196 228 264 279 332 374 398 430 457 520 554

Start-up amps RTUB (1) (A) 190 219 256 292 312 370 412 444 476 511 574 619

Maximum amps RTWB (2) (A) 147 170 215 235 255 297 329 360 396 432 477 521

Maximum amps RTUB (2) (A) 150 176 222 243 264 294 325 356 392 428 473 518

Maximum cable size (mm²) 240 240 240 240 240 240 2x300 2x300 2x300 2x300 2x300 2x300

Disconnect switch size (A) 315 315 315 400 400 400 630 630 630 630 800 800

(1) Equals the sum of the largest compressor starting Amps, plus the other(s) compressor(s) maximum Amps, plus all the fans FLA, plus the control Amps(2) To be used in power cable sizing

Page 161: Train Instrument's

Evaporator water pressure drop -RTWB-RTUB

PROD-PRC014-E4

Water S

ystem

s

RT

WB

- R

TU

B

159

4 5 6 7 8 9 10 20 501

10

100

kPa

200

5

50

1 2

3

4

5 6

Water Flow l/s

1 = RTWB-RTUB 207-2082 = RTWB-RTUB 2103 = RTWB-RTUB 211-2124 = RTWB-RTUB 214-216-2175 = RTWB-RTUB 218-2206 = RTWB-RTUB 222-224

kP

a

Page 162: Train Instrument's

160160PROD-PRC014-E4

Condenser water pressure drop - 1 pass - RTWB

1010

100100

1010 1001002020 4040

2

1

34

1 = RTWB 207-2082 = RTWB 2103 = RTWB 211-2124 = RTWB 214-224

Water Flow l/s

Water Flow l/s

kP

a

Condenser water pressure drop - 2 pass (option) - RTWB

kP

a

Page 163: Train Instrument's

Performance data - RTWB

PROD-PRC014-E4

Unitsize

Cooling capacity

(kW)

Powerinput (kW)

Cooling capacity

(kW)

Powerinput(kW)

Coolingcapacity

(kW)

Powerinput (kW)

Evaporatorleaving watertemperature

(°C)

Water S

ystem

sR

TW

B -

RT

UB

161

Condenser leaving water temperature (°C)

35 40 45

5 201 47 189 51 177 55

207 7 215 48 204 52 191 56

9 231 50 218 53 205 57

5 236 56 223 61 209 66

208 7 251 58 239 62 225 67

9 271 59 256 64 241 69

5 300 75 283 80 265 87

210 7 320 77 304 82 285 89

9 345 79 326 85 306 91

5 317 80 299 86 281 93

211 7 338 82 321 88 302 95

9 364 84 344 90 324 97

5 340 85 321 92 301 100

212 7 362 87 344 94 324 102

9 390 90 369 97 347 104

5 408 97 386 105 362 114

214 7 435 100 414 108 389 117

9 469 103 443 111 416 120

5 443 108 418 116 393 126

216 7 472 111 449 119 421 129

9 507 114 480 123 451 132

5 478 118 452 128 424 138

217 7 508 121 484 131 455 142

9 547 125 517 135 487 145

5 517 130 490 141 461 152

218 7 553 134 524 144 494 156

9 591 138 560 148 528 160

5 563 147 533 158 501 171

220 7 600 151 570 163 536 176

9 641 156 608 167 573 180

5 652 169 617 181 581 195

222 7 693 174 660 187 622 201

9 744 180 705 193 664 207

5 705 186 668 200 629 216

224 7 749 192 714 206 673 222

9 803 199 762 213 719 229

With evaporator delta T: 5°C, condenser delta T: 5°C, fouling factor: 0.0176m²K/kW for the evaporator, fouling factor: 0.044m²K/kW for the

condenser, standard heat exchangers, electrical voltage frequency: 50 Hz, refrigerant: R134a.

Page 164: Train Instrument's

162162PROD-PRC014-E4

Performance data - RTUB

Evaporator

leaving water

temperature

(°C)

Cooling

capacity

(kW)

Power

input

(kW)Unit size

Cooling

capacity

(kW)

Power

input

(kW)

Cooling

capacity

(kW)

Power

input

(kW)

Condenser leaving water temperature (°C)

40 50 60

5 205 48 181 57 152 69

207 7 221 49 195 58 164 70

9 237 50 210 59 177 71

5 242 57 214 67 181 81

208 7 260 58 231 69 195 83

9 278 60 248 70 210 84

5 306 74 270 87 231 104

210 7 329 76 291 89 249 106

9 352 78 312 91 269 107

5 323 79 286 93 246 111

211 7 347 81 308 95 266 113

9 372 83 331 97 287 115

5 347 85 308 100 265 119

212 7 372 87 331 102 287 121

9 399 89 356 103 309 123

5 423 94 376 111 326 133

214 7 455 96 405 113 352 135

9 488 98 436 115 379 137

5 461 102 411 121 356 145

216 7 495 105 442 123 385 147

9 531 107 475 125 415 149

5 499 111 445 132 387 158

217 7 536 113 479 134 418 160

9 574 116 514 136 450 162

5 536 124 480 147 419 175

218 7 575 127 515 149 451 178

9 615 130 553 152 486 181

5 585 139 524 163 458 195

220 7 627 142 563 167 493 198

9 671 146 603 170 530 201

5 684 157 614 183 537 216

222 7 734 161 660 187 579 220

9 786 165 708 191 623 224

5 742 171 668 199 588 236

224 7 796 176 718 204 633 240

9 852 181 770 208 680 244

Evaporator deltaT 5°C, sub-cooling 9.6°C, fouling factor 0.0176 m²K/kW, standard evaporators electrical voltage frequency 50Hz,

refrigerant R134a

Page 165: Train Instrument's

Typical installation

PROD-PRC014-E4

Water S

ystem

sR

TW

B -

RT

UB

163

The model RTUB condenserless chiller has been designed for installation and optimized operation with the model RTCA remoteair-cooled condenser.

Provided that rules regarding maximum distance between units and a maximum height of the liquid line are followed, any ofthe following can be done.

Advantages of having a remote condenser as opposed to a condenser built into the chiller:• Allows installation in existing buildings, with limited roof or external surface available• Easy maintenance• No sound radiation outside of the technical room• Possibility of heat reclaim

RTUB

RTCA

RTUBRTCA

RTUB

RTCA

Condenser above chiller

Condenser and chiller at the same level

Condenser below chiller

Discharge line connections

Liquid line connections

Page 166: Train Instrument's

164PROD-PRC014-E4

Customer benefits • Specifically designed to be matched with TRANE indoor

chiller : - guarantee of sustainable performance - single source responsibility- reduced commissioning time

• Low Sound version for sensitive environment: a highlevel of acoustic comfort

Main features • Integral subcooling circuits for energy savings and sys-

tem efficiency• V-shaped coil arrangement • Axial fans, several choices of fan speeds • Designed for optimized operation with an RTUB chiller• Unit-mounted control panel

Options• 2-speed fans• Copper fins• Black epoxy-coated aluminium fins• Factory-mounted starter panel• Night noise setback for noise sensitive applications• Low ambient operation

Condenser, axial fans215-600 kW

Indoor chillers

RTCA

RTCA

Page 167: Train Instrument's

General data

PROD-PRC014-E4

Unit size 108 109 111 113 115 116 208 209 211 213 215 216

Gross heat rejection (1) (kW) 215 245 294 431 492 588 215 245 294 431 492 588

Power input (2) (kW) 4.0 4.0 6.1 8.1 8.1 12.1 2x2.0 2x2.0 2x3.05 2x4.05 2x4.05 2x6.05

Refrigerant R134a

Number of refrigerant circuits 1 1 1 1 1 1 2 2 2 2 2 2

Refrigerant charge (kg) 22 26 36 44 52 72 2 x 11 2 x 13 2 x 18 2 x 22 2 x 26 2 x 36

Condenser type Aluminium fins copper tubesHot gas connection diameter (inches) 1 5/8Liquid connection diameter (inches) 1 1/8

Total airflow (m3/h) 42500 50400 69300 77200 84700 98500 42500 50400 69300 77200 84700 98500

Number of fans 4 4 6 8 8 12 2 x 2 2 x 2 2 x 3 2 x 4 2 x 4 2 x 6

Fan speed (rpm) 690

Sound power level (dB(A)) 85 85 87 88 88 90 85 85 97 88 88 90

Length (mm) 2870 2870 2870 4610 5450 5450 2870 2870 2870 4610 5450 5450

Width (mm) 2285

Height (mm) 1630

Shipping weight (3) (kg) 1020 1100 1300 1870 2170 2450 1020 1100 1300 1870 2170 2450

Operating weight (3) (kg) 810 890 1090 1535 1770 2050 810 890 1090 1535 1770 2050Sound pressure level at 1 m (dB(A)) 67 67 69 69 69 70 67 67 69 69 69 70Minimum operating outdoor air temperature (°C) 0Maximum operating outdoor air temperature (°C) 40

Power supply (V/Ph/Hz) 400/3/50

Full-load amps (4) (A) 2.8

(1) Ambient air temperature: 35°C, saturated condensing temperature: 60°C, subcooling: 9.6°C(2) Fans only(3) With aluminium fins(4) Per fan

Water S

ystem

sR

TC

A

165

Page 168: Train Instrument's

166PROD-PRC014-E4

Customer benefits • Trane helirotor compressor - designed to perform, built

to last: superior reliability and low cost of ownership• State of the art control to guarantee superior

dependability: low cost of ownership• R134a refrigerant for high performance: low energy

consumption

Main Features• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only four moving parts, suction-gas-cooled motor

• Fully modulating load control (25-100%)• Compact physical footprint - fits through standard

double-width doors• Bolt-together construction for easy unit disassembly• Factory mounted star-delta starter panel• Simplified piping - the only piping required is for the

evaporator and condenser Victaulic connections• Single power connection - reduced wiring costs• Tube-in-shell condenser• Falling film evaporator - high COP and reduced

refrigerant charge• Tracer Summit™ capabilites• LonTalkTM compatible

Options• Insulation on evaporator, water boxes, suction line,

motor housing• Fused or non-fused power disconnect switch • Under/over voltage protection

Accessories• Neoprene isolators• Flow switch• Outside air temperature sensor• Condenser valves

ControlAdaptive Control™ microprocessor-based controlfeaturing:• Easy to use DynaView operator interface • Chilled water pump control• Alarm indicator progammable relays• Chilled water and current limit remote setpoint card

(optional)• Ice making controls (optional)• Tracer Summit™ Communication interface (optional)• LonTalk communication card (optional)• Condenser valve regulation card (optional)

Helical rotary compressor500-1500 kW

Indoor chillers

RTHDRTHD

TracerTM CH530

Page 169: Train Instrument's

General data

PROD-PRC014-E4

Unit size (1) Comp B1 B1 B2 B2 C1 C1 C1 C2 C2 C2 D1

EVP B1 C1 B1 C1 D6 D5 D3 D6 D5 E1 D4

CDS B1 D1 B1 D1 E5 E4 E3 E5 E4 F1 E4

Cooling capacity (2) (kW) 540.1 560.5 589.3 611.4 760.5 771.4 792.5 874.4 886.4 932.1 1034.1

Power input (2) (kW) 95.5 94.4 104.8 103.1 141.2 138.9 136.4 165.3 161.7 153.9 195.9Coefficient of Performance 5.7 5.9 5.6 5.9 5.4 5.6 5.8 5.3 5.5 6.1 5.3Refrigerant R134aNumber ofrefrigerant circuits 1Refrigerant charge (kg) 186 222 186 222 222 222 222 222 222 238 222Compressor type Helical rotaryNumber of compressors 1Oil charge (l) 17 17 17 17 23 23 23 23 23 38 23Evaporator type Tube-in-shell/Falling filmEvaporator water content (l) 155 208 155 208 170 197 295 170 197 310 197Evaporatorwater connection type VictaulicEvaporator water connection diameter (mm) 150 150 150 150 200 200 200 200 200 200 200Condenser type Tube-in-shell/FloodedCondenser water content (l) 106 117 106 117 110 121 178 110 121 226 121Condenser water connection type VictaulicCondenserwater connection diameter (mm) 150 150 150 150 200 200 200 200 200 200 200Sound power level (3) (dB(A)) 98 98 98 98 98 98 98 98 98 98 97Soundpressure level at 1 m (3) (dB(A)) 80 80 80 80 80 80 80 80 80 80 78Minimum operatingambient air temperature (°C) 10Maximum operatingambient air temperature (°C) 50Minimum leaving watertemperature condenser (°C) 20Maximum leaving watertemperature condenser (°C) 50Minimum leaving water temperature evaporator (6) (°C) -12Maximum leaving watertemperature evaporator (°C) 18Power supply (V/Ph/Hz) 400/3/50Standard starter type Star-deltaStart-up amps (4) (A) 412 412 412 412 480 480 480 480 480 480 748Maximum amps (5) (A) 233 233 233 233 349 349 349 349 349 349 455Maximum cable size (mm²) 240 240 240 240 240 240 240 240 240 240 2x300Disconnect switch size (A) 250 250 250 250 400 400 400 400 400 400 630

(1) Unit size presented as compressor code-evaporator code-condenser code(2) Standard Eurovent conditions: - Evaporator entering/leaving water temperature 12°C and 7°C. Condenser entering/leaving water temperature 30°C/35°C. -

Evaporator and condenser fouling factor = 0.044 m²K/kW.(3) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996(4) Inrush current in star connection(5) To be used for power cable sizing(6) With ethylene glycol

All units: evaporator 3 pass, condenser 2 pass, except models D1 G1 G1, D2 G2 G1, D3 G2 G2 and E3 G3 G3: evaporator 4 pass, condenser 2 pass

Water S

ystem

s

RT

HD

167

Page 170: Train Instrument's

168168PROD-PRC014-E4

General data

Unit size (1) Comp D1 D1 D2 D2 D2 D3 D3 D3 E3 E3 E3

EVP D3 G1 D1 F1 G2 D1 F1 G2 D2 F2 G3

CDS E3 G1 E1 F2 G1 E1 F2 G2 E2 F3 G3

Cooling capacity (2) (kW) 1063 1136 1138 1202 1240 1213 1284 1333 1323 1401 1457

Power input (2) (kW) 190 183 209 201 198 226 216 211 263 252 246Coefficient of Performance 5.6 6.2 5.5 6.0 6.3 5.4 5.9 6.3 5.0 5.6 5.9Refrigerant R134aNumber of refrigerantcircuits 1Refrigerant charge (kg) 222 318 215 284 318 215 284 318 215 284 318Compressor type Helical rotaryNumber of compressors 1Oil charge (l) 23 42 23 38 42 23 38 42 23 38 42Evaporator type Tube-in-shell/Falling filmEvaporatorwater content (l) 295 515 261 386 545 261 386 545 280 405 602Evaporator waterconnection type VictaulicEvaporator waterconnection diameter (mm) 200Condenser type Tube-in-shell/FloodedCondenser water content (l) 178 299 166 216 299 166 216 344 178 231 367Condenser waterconnection type VictaulicCondenser waterconnection diameter (mm) 200 Sound power level (3) (dB(A)) 97 97 97 97 97 97 97 97 101 101 101Sound pressurelevel at 1 m (3) (dB(A)) 78 78 78 78 78 78 78 78 82 82 82Minimum operatingambient air temperature (°C) 10Maximum operatingambient air temperature (°C) 50Minimum leaving watertemperature condenser (°C) 20Maximum leaving watertemperature condenser (°C) 50Minimum leaving water temperature evaporator (6) (°C) -12Maximum leaving water temperature evaporator (°C) 18Power supply (V/Ph/Hz) 400/3/50Standard starter type Star-deltaStart-up amps (4) (A) 748 748 748 748 748 748 748 748 748 748 748Maximum amps (5) (A) 455 455 455 455 455 455 455 455 488 488 488Maximum cable size (mm²) 2x300Disconnect switch size (A) 630

(1) Unit size presented as compressor code-evaporator code-condenser code(2) Standard Eurovent conditions: - Evaporator entering/leaving water temperature 12°C and 7°C. Condenser entering/leaving water temperature 30°C/35°C. -

Evaporator and condenser fouling factor = 0.044 m²K/kW.(3) Under free field conditions only, on a reflecting surface, data in accordance with ISO 3746-1996(4) Inrush current in star connection(5) To be used for power cable sizing(6) With ethylene glycol

All units: evaporator 3 pass, condenser 2 pass, except models D1 G1 G1, D2 G2 G1, D3 G2 G2 and E3 G3 G3: evaporator 4 pass, condenser 2 pass

Page 171: Train Instrument's

Dimensions, weights and clearances

PROD-PRC014-E4

Access to control panel

Dimensions(mm)

Shipping weight

(kg)

Minimum clearances (mm)

Operating weight

(kg)

Unit size (1)

Weights

Z

XY

X Y Z A B/C/D

B1-B1-B1 3170 1600 1850 3940 4215 2530 1000

B1-C1-D1 3635 1600 1850 4260 4605 2530 1000

B2-B1-B1 3170 1600 1850 3940 4215 2990 1000

B2-C1-D1 3635 1600 1850 4260 4605 2990 1000

C1-D6-E5 3292 1600 1940 5700 6160 2510 1000

C1-D5-E4 3292 1600 1940 5470 5840 2510 1000

C1-D3-E3 3292 1600 1940 5380 5705 2510 1000

C2-D6-E5 3292 1600 1940 5470 5840 2510 1000

C2-D5-E4 3292 1600 1940 5380 5705 2510 1000

C2-E1-F1 3670 1600 1940 6105 6640 2510 1000

D1-D4-E4 3292 1600 1940 5955 6420 2510 1000

D1-D3-E3 3292 1600 1940 5775 6145 2510 1000

D1-G1-G1 3809 1800 2035 7440 8320 2510 1000

D2-D1-E1 3292 1600 1940 5885 6300 2510 1000

D2-F1-F2 3686 1600 1940 6665 7280 2980 1000

D2-G2-G1 3809 1800 2035 7660 8575 2970 1000

D3-D1-E1 3292 1600 1940 5885 6300 2970 1000

D3-F1-F2 3686 1600 1940 6695 7310 2970 1000

D3-G2-G2 3809 1800 2035 7795 8760 3130 1000

E3-D2-E2 3292 1600 1940 6050 6460 3130 1000

E3-F2-F3 3686 1600 1940 6830 7490 3130 1000

E3-G3-G3 3809 1800 2035 8060 9115 3130 1000

(1) With standard pass water box

Water S

ystem

s

RT

HD

169

Page 172: Train Instrument's

170PROD-PRC014-E4

Customer benefits • Hermetic, Multistage Trane Centrifugal compressor

offering both wide operating range + extended part loadcapability - minimum maintenance requirements- no extra ventilation required to cool compressor motor

• State of the art control to guarantee superiordependability: low cost of ownership

• R134a refrigerant for high performance: low energyconsumption

Main Features• Hermetic two-staged centrifugal compressor-motor

assembly with integral lubrication system andeconomizer cycle

• Liquid cooled hermetic induction motor• Advanced motor protection• Hundreds of evaporator-condenser-compressor

combinations available, permitting precise tailoring tosystem requirements

• Single power connection - reduce wiring costs• Factory mounted star-delta starter panel• Prewired instrument and control panel• Lon Talk® compatible

Options• Solid-state starters• Marine waterboxes (10.5 or 21 bar) condenser only• Cold parts thermal insulation

Accessories• Flanged adaptors• Flow switch(es)

ControlsAdaptive Control™microprocessor controls featuring:• Easy to use DynaView operator interface panel• External Auto/Stop• External interlock• Water pump control• Lon Talk® Communication card COMM5 (option)

Centrifugal compressor1400-3800 kW

Indoor chillers

CVGF

CVGF

TracerTM CH530

Page 173: Train Instrument's

General data

PROD-PRC014-E4

Unit size 400 500 650 800 1000

Minimum cooling capacity (1) (kW) 1400 1500 1850 2200 2400

Maximum cooling capacity (1) (kW) 1950 2500 2800 3500 3800

Minimum power input (1) (kW) 220 230 280 330 420

Maximum power input (1) (kW) 340 430 480 600 650Minimum Coefficient of Performance 5.8 5.8 5.8 5.8 5.8Maximum Coefficient of Performance 6.6 6.6 6.6 6.6 6.6

Refrigerant R134a

Number of refrigerant circuits 1 1 1 1 1

Refrigerant charge (kg) 290 290 390 540 540

Compressor type Centrifugal

Number of compressors 1 1 1 1 1

Oil charge (l) 57 57 57 57 57

Evaporator type Falling film

Evaporator water content (l) 380 440 660 820 980Evaporator water connection type Victaulic/Flanged adaptorEvaporator water connection diameter (inches) 8 8 10 10 12

Condenser type Tube-in-shellCondenser water content (l) 430 480 760 900 1100Condenser water connection type Victaulic/Flanged adaptorCondenser water connection diameter (inches) 10 10 12 12 14Sound pressure level at 1 m (2) (dB(A)) 82 82 84 81 81Minimum operating ambient air temperature (°C) 5Maximum operating ambient air temperature (°C) 50Minimum leaving water temperature (°C) +1.4Maximum leaving water temperature (°C) 15

Power supply (V/Ph/Hz) 400/3/50

Standard starter type Star-delta

Start-up amps (3) (A) 699 699 883 975 1200

Maximum amps (4) (A) 375 375 485 546 689

Maximum cable size (mm²) 120 120 150 150 185

Disconnect switch size (A) 400 400 600 600 800

Length (mm) 4600 4600 4800 4950 4950

Width (mm) 1980 1980 2080 2300 2300

Height (mm) 2090 2090 2270 2520 2520

Shipping weight (5) (kg) 8800 8800 11000 14400 15800

Operating weight (5) (kg) 10090 10090 12800 17100 18500

(1) Considering the number of evaporator-condenser-compressor combinations available, only minimum and maximum values are given for each unit size.12/7°C entering/leaving chilled water temperature and 27/32°C entering/leaving condenser water temperature

(2) At full load, in accordance with ISO 3746 -1996(3) Inrush current in star connection(5) Weights are indicative and depend on heat exchanger combinations

Water S

ystem

s

CV

GF

171

Page 174: Train Instrument's

172PROD-PRC014-E4

Customer benefits• Use of available hot water or steam energy sources to

produce chilled water: energy savings• State of the art control to guarantee superior

dependability: low cost of ownership• Single shell design to guarantee superior life time:

maximum return on investment

Main features• Proven refrigeration cycle based on the use of:

- Distilled water as refrigerant- Lithium bromide as absorbant

• Chilled water is produced by recovering waste energyfrom a cogeneration plant, incinerator or any processwhere hot water from 90°C to 130°C, or steam up to1 bar, is available

• COP of 0.63 under nominal duty conditions• One single moving part: hermetic pump-motor

assembly, cooled by a distilled refrigerant water• Single shell design• Cupronickel tubing in concentrator and absorber• Patented fixed and floating tubes support to allow tube

expansion in concentrator• Tubes are individually replaceable• Variable speed solution pumps • Single pump motor

Options• Wide choice of tube materials

Accessories• Flanges

ControlAdvanced microprocessor-based UCP2™ control modulewith extended control, safety and diagnostic capability.• Liquid crystal display• Adaptive ControlTM

• Enhanced operation safety features (automatic crystallization protection)

Single-stage absorption400-1630 kW

Indoor chillers

ABSCABSC

UCP2TM

Page 175: Train Instrument's

General data

PROD-PRC014-E4

Unit size 112 129 148 174 200 228 256 294 354 385 420 465

Cooling capacity (1) (kW) 394 453 520 611 704 801 900 1034 1245 1354 1477 1635

Power input (2) (kW) 3.8 4.2 4.2 5.1 5.4 5.8 7.0 7.2 7.5 8.3 8.3 8.5

Coefficient of Performance 0.63Minimum operating ambient air temperature (°C) 5Maximum operating ambient air temperature (°C) 50Minimum leaving water temperature (°C) 4.5Maximum leaving water temperature (°C) 15

Lithium bromide charge (kg) 680 735 815 950 1050 1140 1240 1430 1640 1600 1920 1920

Distilled water charge (l) 210 231 265 322 360 402 485 572 670 648 795 795

Length (mm) 3370 3800 5000 3800 4300 4900 4400 5000 5850 5050 5950 5950

Width (mm) 1530 1530 1530 1630 1630 1630 1750 1750 1750 1960 1960 1960

Height (mm) 2200 2200 2200 2330 2330 2330 2500 2500 2500 2700 2700 2700

Operating weight (kg) 5100 5600 6100 6800 7400 8200 8700 10400 11200 12600 13700 14600

Shipping weight (kg) 4000 4100 4500 5000 5400 6000 6800 7300 7700 8900 10000 10200

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 10.0 10.0 10.0 12.5 12.5 12.5 12.5 12.5 16.5 16.5 16.5 16.5

(1) With steam at 0.83 bar, chilled water 12.2/6.7°C and cooling water entering at 26.7°C(2) Solution pump motor only

Water S

ystem

s

AB

SC

173

Page 176: Train Instrument's

174PROD-PRC014-E4

Customer benefits • Use of available hot water or steam energy sources to

produce chilled water: energy savings• State of the art control to guarantee superior

dependability: low cost of ownership

Main features• Proven refrigeration cycle based on the use of:

- Distilled water as refrigerant- Lithium bromide as absorbant

• Chilled water is produced by recovering waste energyfrom a cogeneration plant, incinerator, or any processwhere hot water from 90°C to 130°C, or steam up to1 bar, is available

• COP of 0.7 under nominal duty conditions• Double shell design to facilitate installation in an

equipment room• Cupronickel tubing in concentrator and absorber• Patented fixed and floating tubes support to allow tube

expansion in concentrator• Tubes are individually replaceable• Variable speed solution pumps to optimize part load effi-

ciency• Purge unit automatically controlled by UCP2TM

Options• Wide choice of tube materials• Cross-over pipe between absorber and condenser• Marine water boxes for absorber and condenser• Factory-mounted energy valve

Accessories• Lithium bromide filter• Flanges

ControlAdvanced microprocessor-based UCP2™ control modulewith extended control, safety and diagnostic capability.• Liquid crystal display• Adaptive ControlTM

• Enhanced operation safety features (automatic crystallization protection)

Horizon™Single-stage absorption2000-4800 kW

Indoor chillers

ABSD

ABSD

UCP2TM

Page 177: Train Instrument's

General data

PROD-PRC014-E4

Unit size 500 600 700 800 975 1100 1225 1350

Cooling capacity (1) (kW) 2008 2356 2595 3021 3510 3886 4354 4821

Power input (2) (kW) 9.7 9.7 11.6 11.6 13.0 14.9 14.9 14.9

Coefficient of Performance (1) 0.71 0.72 0.71 0.72 0.71 0.70 0.70 0.71Minimum operating ambient air temperature (°C) 5Maximum operating ambient air temperature (°C) 50Minimum leaving water temperature (°C) 4.0Maximum leaving water temperature (°C) 15

Lithium bromide charge (kg) 1650 1840 2100 2340 2310 2500 2670 2820

Distilled water charge (l) 570 720 870 1030 620 680 750 810

Length (mm) 5500 6300 7100 7100 6600 7300 7900 8500

Width (mm) 2500

Height (mm) 2910 2910 2910 2910 3550 3550 3550 3550

Operating weight (kg) 14400 16200 18200 20100 22700 24300 26000 27600

Shipping weight (kg) 10400 11500 12700 13900 16500 17600 18800 20000

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 29 29 32 32 37 41 41 41

(1) With steam at 0.83 bar, chilled water 12.2/6.7°C and cooling water entering at 29.4°C(2) Solution pump motor only

Water S

ystem

s

AB

SD

175

Page 178: Train Instrument's

176PROD-PRC014-E4

Customer benefits• Use of available steam energy sources to produce

chilled water: energy savings• Automatic Crystallization Protection: guarantee of

maximum dependability• Easy installation, start-up and service: saving of time

Main features• High energy efficiency double effect distilled

water/lithium bromide refrigeration cycle with optimizedheat exchangers- COP of 1.2 under nominal duty conditions- Uses superheated water (up to 180°C) or steam (up to

8 bars) as primary energy source- Reduced heat rejection

• Ease of installation: modular design to facilitate reliabledisassembly and reassembly on jobsite

• Lithium bromide solution variable speed pump• Floating tube supports allowing tube expansion• Purge unit automatically controlled by UCP2TM

• Marine water boxes for absorber and condenser

Options• Wide choice of tube materials• Cross-over pipe between absorber and condenser• Factory-mounted energy valve

Accessories• Lithium bromide filter• Flanges

ControlAdvanced microprocessor-based UCP2™ control modulewith extended control, safety and diagnostic capability.• Liquid crystal display• Adaptive ControlTM

• Enhanced operation safety features (automatic crystallization protection)

Horizon™ Two-stage absorption1300-6000 kW

Indoor chillers

ABTF

ABTF

UCP2TM

Page 179: Train Instrument's

General data

PROD-PRC014-E4

Unit size 380 440 500 575 660 750 850 950 1050 1150 1200 1350 1500 1650

Cooling capacity (1) (kW) 1266 1498 1734 1963 2318 2691 3218 3623 4027 4428 4446 4991 5533 6053

Power input (2) (kW) 10.6 10.6 12.0 20.5 20.5 23.0 30.0 30.0 30.0 30.0 32.5 32.5 32.5 32.5Coefficient of Performance (1) 1.20 1.21 1.21 1.21 1.21 1.21 1.23 1.23 1.24 1.24 1.19 1.19 1.19 1.20Minimum operating ambient air temperature (°C) 5Maximum operating ambient air temperature (°C) 50Minimum leaving water temperature (°C) 4.0Maximum leaving water temperature (°C) 15Lithium bromide charge (kg) 2540 2660 2660 3530 3090 3750 4600 4940 5300 5620 6500 7240 7760 8360

Distilled water charge (l) 610 610 610 950 950 950 1030 1140 1330 1400 610 650 690 720

Length (mm) 6600 6600 6600 9400 9400 9400 7300 7900 8500 9100 8300 8900 7600 10200

Width (mm) 2500 2500 2500 2500 2500 2500 3300 3300 3300 3300 4000 4000 4000 4000

Height (mm) 2900 2900 2900 2900 2900 2900 3700 3700 3700 3700 4000 4000 4000 4000

Operating weight (kg) 18400 19200 19800 24500 25400 26300 33100 35500 37700 40000 47100 50400 53700 50900

Shipping weight (kg) 13800 14300 14800 18000 18500 19100 24000 25700 27200 28700 34200 36400 38600 40800

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 27 27 32 42 42 45 56 56 56 56 60 60 60 60

(1 With steam at 8.3 bar, chilled water 12.2/6.7°C, and cooling water entering at 29.4°C(2) Solution pump motor only

Water S

ystem

sA

BT

F

177

Page 180: Train Instrument's

178PROD-PRC014-E4

Customer benefits• Use of available gas energy sources to produce chilled

water: energy saving• All sizes can act as a chiller/heater: specifically designed

for applications requiring chilled water for space coolingduring the summer and hot water for space heatingduring the winter (water temperatures up to 82°C areavailable)

• Available with an auxiliary heat exchanger whichprovides simultaneous cooling and heating of water:flexibility to meet the customer's exact requirements

Main features• Proven refrigeration cycle based on the use of :

- Distilled water as refrigerant- Lithium bromide as absorbant

• Chilled water is produced using the heat provided by anintegrated gas burner to concentrate the solution ofLithium Bromide.

• COP of 1 under nominal duty conditions• Possibility to produce hot water up to 60°C in reversible

mode (up to 80°C optional)• Gas burner fully integrated and contolled by unit micro-

processor-based control module• Fully modulating burner (100 - 30%)

Options• Auxiliary heat recovery condenser to produce hot water

up to 82°C in simultaneous mode (control not Trane-sup-plied)

• Full enclosure for outdoor installation up to size 550• Possibility to ship unit disassembled from size 600

Control• Microprocessor based control module to operate the

chiller and the burner safely• Automatic crystallization protection

Direct-fired absorption350-3900 kW

Indoor chillers

ABDL

ABDL

Page 181: Train Instrument's

General data

PROD-PRC014-E4

Unit size 450 500 550 600 700 800 900 1000 1100

Cooling capacity (1) (kW) 1582 1758 1933 2109 2461 2812 3164 3516 3867

Coefficient of Performance (2) 0.99

Heating capacity (3) (kW) 1331 1479 1627 1775 2071 2367 2662 2958 3254

Minimum operating ambient air temperature (°C) 5

Minimum leaving chilled water temperature (°C) 6

Maximum leaving chilled water temperature (°C) 11

Minimum entering coolingwater temperature (°C) 22

Maximum leaving cooling water temperature (°C) 38

Lithium bromide charge (kg) 2885 3180 3485 4015 4305 5125 5655 5995 6875

Distilled water charge (l) 360 401 439 431 492 583 640 712 780

Length (mm) 5950 6630 7190 6050 6600 7230 7870 6750 7130

Width (mm) 2180 2180 2180 3060 3060 3220 3220 3800 3800

Height (mm) 2740 2740 2740 3330 3330 3330 3330 3680 3680

Operating weight (kg) 16600 18500 20800 27100 28900 32800 36400 41900 44900

Shipping weight (4) (kg) 14800 16500 18600 23700 25300 28500 31900 31000 33100

Power supply (V/Ph/Hz) 400/3/50

Total electrical input (5) (kW ) 7.8 9.3 9.3 13 16.3 16.3 16.3 21.5 21.5

(1) Chilled water=12/7°C, cooling water = 27/35°C, Fouling factor=0.088 m2K/kW(2) Based on PCS=11 kWh/m3

(3) Hot water= 50/60°C, Fouling factor = 0.088 m2K/kW(4) Includes Lithium Bromide and distilled water charges(5) Includes solution pumps, burner, purge and control

Unit size 100 120 150 180 200 240 300 350 400

Cooling capacity (1) (kW) 351 421 527 632 703 843 1054 1230 1406

Coefficient of Performance (2) 0.99

Heating capacity (3) (kW) 295 354 444 533 591 710 887 1035 1183

Minimum operating ambient air temperature (°C) 5

Minimum leaving chilled water temperature (°C) 6

Maximum leaving chilled water temperature (°C) 11

Minimum entering coolingwater temperature (°C) 22

Maximum leaving cooling water temperature (°C) 38

Lithium bromide charge (kg) 615 720 870 1095 1205 1420 1895 2165 2430

Distilled water charge (l) 87 102 125 140 151 189 265 310 352

Length (mm) 3020 3020 3650 4160 4520 5330 4250 4790 5390

Width (mm) 1490 1490 1490 1610 1610 1610 2030 2030 2030

Height (mm) 2190 2190 2190 2250 2250 2250 2740 2740 2740

Operating weight (kg) 4800 5300 6100 7100 7600 8600 12700 14300 15400

Shipping weight (4) (kg) 4400 4900 5600 6500 7000 7900 11300 12700 13700

Power supply (V/Ph/Hz) 400/3/50

Total electrical input (5) (kW ) 3.8 4.15 4.15 5.2 5.95 5.95 6.7 6.7 7.4

Water S

ystem

s

AB

DL

179

Page 182: Train Instrument's

180PROD-PRC014-E4

Customer benefits • Indoor installation:

- allows installation in existing buildings, with limited roof or external surface available

- easy maintenance, - no sound radiation outside of technical room - possibility of heat reclaim

• Trane Scroll compressor: minimum maintenancerequirement

Main features• Scroll Compressors

- Hermetic, high efficiency, low vibration, low soundlevel

- Full internal protections, internal temperature andbypass valve

• External sheet metal parts are galvanized and finishedwith powder paint RAL 9002

• Access panels are quickly removable using a square key• Vertical or horizontal condenser fan discharge• Compact - fits through standard-width doors (866 mm

except size 500 and 600)• Up to 500 Pa total static pressure at the fan

Options• 380, 400 and 415V power voltage• 400 / 220V transformer for the control• Disconnect switch • Black epoxy-coated aluminium fins• Copper fins• 300, 400 and 500 Pa total static pressure at the fan• Compressor sound attenuating jacket• High and low pressure gauges

• Evaporator water pump command• Water filter• Filter box fitted with A150/AR300/M8 filters• Hydraulic module - for information, contact your local

sales office• Auxiliary card to display entering water temperature on

the evaporator and or to validate auxiliary temperatureset point with a remote contact (ships with water sensorwith 5m cable)

• TCI-S card to communicate with BMS

ControlMicroprocessor control module SMM (Scroll ManagerModule) with liquid crystal display operator interfacecontrolling and indicating :• Leaving water temperature• Equalization of the number of starts and operating hours

of each compressor• Fan speed• HP limitation• Low pressure protection• Short cycle protection • Remote on/off per circuit (dry contact)• Failure indication per circuit (dry contact)• History of the last 20 defaultsAccess to current settings through a window in theelectrical panel

Centrifugal fans, scroll compressor49-150 kW*

Indoor chillers

CGCL

* Also available with R134a. For information, please contact your local Trane Sales Office.

CGCL

SMM

Page 183: Train Instrument's

General data

PROD-PRC014-E4

Unit size 200 250 300 350 400 450 500 600

Cooling capacity (1) (kW) 49.2 61.1 74.0 86.9 100.7 110.6 126.1 151.6

Power input (1) (kW) 21.9 26.9 34.6 38.2 46.8 55.6 59.6 73.0Coefficient of Performance cooling mode 2.3 2.3 2.1 2.3 2.2 2.0 2.1 2.1

Refrigerant R407C

Number of refrigerant circuits 1 1 1 1 1 1 2 2

Refrigerant charge per circuit (kg) 12 15 15 23 23 23 15 15

Compressor type Scroll

Number of compressors 2 2 2 3 3 3 4 4

Number of capacity steps 2 2 2 2 2 2 4 4Oil charge circuit 1/circuit 2 (l) 7.6/- 10.4/- 13.2/- 14.2/- 17/- 19.8/- 10.4/ 10.4 13.2/ 13.2

Evaporator type Brazed plateEvaporator water content (l) 4.7 5.9 7.0 8.2 10.5 10.5 12.3 16.1Unit water connection type ISO R7 maleUnit water connection diameter (inches) 1 ½ 1 ½ 1 ½ 2 2 2 2 ½ 2 ½

Condenser type Copper tubes with aluminium fins

Total airflow (m3/h) 15300 17800 23800 26800 30600 34500 39100 47600

Number of fans 1 2 2 2 2 2 3 3

Fan speed (rpm) 1450

Sound power level 300 Pa (dB(A)) 88 84 87 89 91 95 90 94

Sound power level 400 Pa (dB(A)) 90 86 89 90 93 96 92 95

Sound power level 500 Pa (dB(A)) 91 88 90 92 94 97 93 96Minimum operating outdoor air temperature (°C) -5Maximum operating outdoor air temperature (°C) 40Minimum leaving water temperature (2) (°C) -12Maximum leaving water temperature (°C) 12

Number of fan discharge openings 1 2 2 2 2 2 3 3Fan discharge opening dimensions (mm) 560 560 560 570 570 570 570 570

x 481 x 481 x 481 x 485 x 485 x 485 x 493 x 493Air inlet opening dimensions (mm) 1829 1829 1829 2743 2743 2743 2743 2743

x 914 x 1219 x 1219 x 1219 x 1219 x 1219 x 1626 x 1626

(1) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature(2) With 37% glycol solution

Note: Configurations 1.0 and 2.0 are available on all sizes of CGCL. Configuration 2.1 is only available on sizes 500 and 600. Configuration 3.0 is not available onsizes 500 and 600.

Fan configuration options

xxxxxxxxxxxxxxxxxx

181

CG

CL

181

Water S

ystem

s

Page 184: Train Instrument's

182PROD-PRC014-E4

Dimensions, weights and clearances

B

D

A

C

Z

X

Y

Unit size 200 250 300 350 400 450 500 600

Power supply (V/Ph/Hz) 400/3/50

Standard starter type Direct

Start-up amps (A) Depends on total fan static pressure

Maximum amps (A) Depends on total fan static pressure

Maximum cable size (mm²) 35 35 50 50 95 95 95 95

Electrical data

Accesscontrol panel

X Y Z A B C D

200 2268 866 1997 750 710 800 800 800 800

250 2268 866 1997 870 830 800 800 800 800

300 2268 866 1997 930 890 800 800 800 800

350 3230 866 1997 1130 1080 800 800 800 800

400 3230 866 1997 1190 1140 800 800 800 800

450 3230 866 1997 1250 1200 800 800 800 800

500 3230 1216 1997 1450 1380 1200 800 800 800

600 3230 1216 1997 1570 1500 1200 800 800 800

(1) With aluminium fins

Dimensions(mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size

Weights (1)

Page 185: Train Instrument's

Evaporator water pressure drop

PROD-PRC014-E4

1010

100100

1 2 3 4 5 6 7 8 9 1010

2020

5050

Performance data

Water Flow l/s

kP

a

EvaporatorLeavingWater

Temperature(°C) Unit size

Coolingcapacity

(kW)

Powerinput (1)

(kW)

Coolingcapacity

(kW)

Powerinput (1)

(kW)

Coolingcapacity

(kW)

Powerinput (1)

(kW)

Coolingcapacity

(kW)

Powerinput (1)

(kW)

xxxxxxxxxxxxxxxxxx

183

CG

CL

183

Condenser Entering Air Temperature (°C)

25 30 35 40

200 51.7 13.8 49.2 15.6 46.4 17.6 43.5 19.9250 64.3 17.9 61.1 20.1 57.7 22.6 54.1 25.5300 77.5 21.5 73.8 24.0 69.8 26.9 65.6 30.2

5 350 91.1 24.2 86.8 27.1 82.1 30.5 77.0 34.4400 105.7 28.4 100.6 31.8 95.1 35.6 89.2 40.0450 116.2 32.3 110.6 36.1 104.6 40.4 98.3 45.2500 132.1 35.3 125.9 39.6 119.1 44.5 111.9 50.0600 159.1 43.5 151.5 48.6 143.4 54.4 134.7 60.9

200 54.8 14.1 52.1 15.9 49.2 17.9 46.1 20.2250 68.0 18.3 64.7 20.5 61.1 23.1 57.3 26.0300 82.1 21.9 78.2 24.5 74.0 27.4 69.4 30.7

7 350 96.5 24.6 91.9 27.6 86.9 31.0 81.6 35.0400 111.9 28.9 106.5 32.4 100.7 36.3 94.5 40.7450 122.9 32.9 116.9 36.7 110.6 41.1 103.9 46.0500 139.8 35.9 133.2 40.3 126.1 45.3 118.5 50.9600 167.9 44.3 159.9 49.5 151.3 55.4 142.2 62.0

200 57.9 14.4 55.1 16.1 52.1 18.2 48.8 20.6250 71.8 18.6 68.3 20.9 64.5 23.5 - -300 86.7 22.3 82.5 24.9 78.1 27.9 - -

9 350 101.9 25.0 97.0 28.1 91.8 31.6 86.2 35.6400 118.1 29.5 112.4 33.0 106.3 37.0 99.7 41.5450 129.5 33.5 123.2 37.4 116.6 41.9 - -500 147.4 36.6 140.5 41.0 133.0 46.1 125.0 51.8600 176.6 45.1 168.1 50.4 159.1 56.3 - -

- Limit

Notes:(1) Compressor only.(2) Ratings are based on evaporator temperature drop of 5°C.(3) Interpolation between points is permissible. Extrapolation is not permitted.

Water S

ystem

s

Page 186: Train Instrument's

184PROD-PRC014-E4

Customer benefits • Indoor installation :

- allows installation in existing buildings, with limitedroof or external surface available

- easy maintenance, - no sound radiation outside of technical room - possibility of heat reclaim

• Trane helirotor compressor - designed to perform, builtto last: superior reliability and low cost of ownership

Main features• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only three or four moving parts,suction-gas-cooled motor

• Centrifugal fans with forward-curved blades - for indoorinstallation

• Ductable condenser air intake• Part-winding starter• Tracer Summit™ capabilities

Options• Star-delta starter• Disconnect switch• Low ambient operation• Copper fins

Accessories• Remote Clear Language Display operator interface• Counterflanges• Filter box

ControlAdaptive Control™ microprocessor featuring:• Unit control module with Clear Language Display• External Auto/Stop• External interlock• Chilled water pump control• Alarm indication contacts• Ice-making card (optional)• Tracer communication card Comm 3 (optional)• Chilled water and current limit remote setpoint card

(optional)

Centrifugal fans, helical rotary compressor132-168 kW*

Indoor chillers

RTRA

*Also available with R22 for applications outside of the European Union. Contact your local Trane Sales Office.

RTRA

UCM-CLD

Page 187: Train Instrument's

General data

PROD-PRC014-E4

Unit size 108 109 110

Cooling capacity (1) (kW) 131.8 138.6 167.9

Power input (2) (kW) 56.8 58.7 78Min/max coefficient ofPerformance (2) 2.3 2.4 2.2

Refrigerant R134aNumber of refrigerant circuits 1Refrigerant charge per circuit (kg) 34 34 34Compressor type Helical rotaryNumber of compressors 1Oil charge per circuit (l) 16 16 16Evaporator type Tube-in-shellEvaporator watercontent (l) 95 134 118Evaporator waterconnection type FlangedEvaporator waterconnection diameter (inches) 3 5 5Condenser type Internally finned copper tubes with aluminium finsTotal airflow (m3/s) 14.17 16.55 18.89Number of fans 3/4 4 4Fan speed (rpm) Depends on external static pressure requiredAvailable static pressure (Pa) 100-400Sound power level (dB(A)) Depends on external static pressure requiredSound pressure level (dB(A)) Depends on external static pressure requiredMinimum operating outdoorair temperature (4) (°C) 15Maximum operating outdoorair temperature (°C) 40Minimum leavingwater temperature (5) (°C) -8Maximum leavingwater temperature (°C) 15Power supply (V/Ph/Hz) 400/3/50Standard starter type Part-windingStart-up amps (6) (8) (A) 339 407 515Maximum amps (7) (8) (A) 149 162 200Maximum cable size (mm²) 95 95 240Disconnect switch size (A) 300 300 300Fan motor power (8) (kW) 22.5 22 30Length (mm) 3650 4650 4650Width (mm) 1300Height (mm) 2000Shipping weight (9) (kg) 2280 2640 2690Operating weight (9) (kg) 2320 2720 2760Number of fan dischargeopenings 3 4 4Fan discharge opening dimensions (mm) 557 x 478

(1) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature(2) Inluding fans 100 Pa static pressure(3) Including fans(4) -18°C minimum operating outdoor air temperature with low ambient option(5) With glycol solution(6) To be used for power cable sizing(7) Maximum compressors FLA + all fans FLA + control Amps(8) At 400 Pa(9) With aluminium fins

xxxxxxxxxxxxxxxxxx

185

RT

RA

185

Water S

ystem

s

Page 188: Train Instrument's

186PROD-PRC014-E4

ROOFTOPS

Page 189: Train Instrument's

10kW 20 30 50 100 15040 60 80 120

187PROD-PRC014-E4

New

• Textile duct soft starter available on the Voyager range (option)

• Supply fan energy saving system

RO

OF

TO

P S

YS

TE

MS

Light commercial, commercial, offi-ce, lodging and industrial applications

ROOFTOPS17 - 143 kW

36 60 WKD/WKH Voyager II

42 62 YKD/YKH Voyager II

17 33

42 62

81 143TKD/TKH Voyager III

81 143YKD/YKH Voyager III

TKD/TKH Voyager II

YSD/YSH Voyager I

WSD/WSH Voyager I

TSD/TSH Voyager I3317

17 26

Page 190: Train Instrument's

WSD/WSHWKD/WKH

188PROD-PRC014-E4

Customer benefits • High performance: lowest energy consumption• High reliability: low maintenance costs

Main features• High COP (Coefficient Of Performance)• Adjustable pulley • Dedicated horizontal or vertical airflow configuration

(also convertible on field on sizes 060 to 090)• Fire-resistant and washable aluminum foil-faced

insulated panels on air section• Single-side access for easy service

Options• Supply fan soft starter• Fan energy saving system with 80-100% 2 speeds

invertor• Black Epoxy coating on condensing and/or evaporating

coils (sizes 125-200)• Electric heater• Hot water coil with 3-way-valve (except WKH)• Communication interfaces to Trane or non-Trane supervi-

sors and thermostats- TCI-R for Tracer, Tracker or Varitrac- LonTalk® card

• Fresh air intake for air quality and/or energy savings(free cooling) through:

- Motorized hoods (0-50%)- Advanced comparative enthalpy economizers

• CO2 sensors• High efficiency washable EU4 filters

• Fire thermostat• Smoke detector• Remote fault relay• Clogged filter sensor• Fan failure switch (sizes 060 to 120)• Fused disconnect switch

Accessories• Adjustable or non-adjustable roofcurbs• Electronic (THS) and programmable (THP) thermostats

Control • 24 V easy-to-start and service microprocessor controls

ReliaTel™

• Built-in test mode • Anti-short cycle timers• Compressor minimum on/off time• Alternative compressor lead/lag• Low ambient cooling (down to -18°C) and anti-freeze

protection • Emergency Stop Input• Intelligent fallback (built-in setpoints)• On-board diagnostics• Built-in conventional thermostat interface• Remote on/off input

* Also available with R22 refrigerant for applications outside the European Union. For information, contact your local Trane Sales Office.

Reversible17-62 kW*

Rooftops

Voyager™ I range

WSD: Downflow discharge and intakeWSH: Horizontal discharge and intakeVoyager™ II range

WKD: Downflow discharge and intakeWKH: Horizontal discharge and intake

WKH

THP 03

Page 191: Train Instrument's

General data WSD/WSH Voyager I

PROD-PRC014-E4

Ro

ofto

p S

ystem

sW

SD

/WS

H-W

KD

/WK

H

189

Unit size 060 072 090

Cooling capacity (1) (kW) 16.7 21.3 26.2

Cooling mode power input (2) (kW) 6.1 6.0 8.0Coefficient of Performance - cooling mode (2) 2.73 3.55 3.28Number of cooling steps 1 1 1Capacity per cooling step (%) 100 100 100Heating capacity (3) (kW) 16.0 20.0 24.2

Heating mode power input (2) (kW) 5.2 5.8 6.5Coefficient of Performance - heating mode (2) 3.10 3.47 3.74Number of heating steps 1 1 1Capacity of heating step (%) 100 100 100Electric heater capacity (option) (kW) 12 18 18

Number of electric heater steps 2 2 2Capacity per heating step (kW) 6/6 6/12 6/12Refrigerant R407CCompressor type ScrollNumber of compressors 1 1 1Number of circuits 1 1 1Indoor fan type Belt FC CentrifugalOutdoor fan type Direct drive axialNumber of outdoor fans 1 1 1Nominal airflow (m3/h) 3400 4080 5100

Static pressure available (WSD/WSH) (3) (Pa) 325/225 250/200 225/175Maximum static pressure available (WSD/WSH) (4) (Pa) 375/325 375/375 375/375Sound power level (2) (dB(A)) 79 81 81Sound pressure level (6) (dB(A)) 48 49 49Sound power level in the duct (2) (dB(A)) 71 68 70Minimum operating outdoor air temperature - cooling mode (°C) -18Minimum operating outdoor air temperature - heating mode (7) (°C) -14Maximum operating outdoor air temperature - cooling mode (°C) 46Maximum operating outdoor air temperature - heating mode (°C) 18Minimum intake air temperature on the indoor coil - cooling mode (°C) 18Minimum intake air temperature on the indoor coil - heating mode (°C) 10

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) At Eurovent conditions: indoor air temperature at 19°C and outdoor air temperature at 7°C DB/6°C WB (4) At the nominal airflow (5) At the nominal airflow with oversized drive when available(6) At 10m from the unit in a free field(7) Depends on installation conditions and local climatic conditions (wind, snow, rain...).

Page 192: Train Instrument's

190190PROD-PRC014-E4

Performance data WSD/WSH - cooling mode

Unit size Airflow

(m3/h)

Air Temperature

(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 18.1 17.5 16.7 15.5 14.13060 27/19 18.3 17.7 16.8 15.5 14.1

30/19 18.5 17.8 16.8 15.6 14.533/19 18.7 18.2 17.6 16.8 15.824/19 18.3 17.8 17.0 15.8 14.4

060 3400 27/19 18.5 17.9 17.1 15.9 14.530/19 18.8 18.3 17.2 16.2 15.233/19 19.1 18.7 18.1 17.3 16.524/19 18.6 18.1 17.4 16.4 15.0

4080 27/19 18.8 18.3 17.5 16.4 15.130/19 19.1 18.5 17.9 17.1 16.233/19 19.6 19.3 18.7 18.1 17.3

24/19 23.2 22.7 21.9 20.5 18.93670 27/19 23.4 23.0 22.1 20.8 19.2

30/19 23.8 23.3 22.5 21.4 19.933/19 24.2 23.9 23.4 22.7 21.824/19 23.5 23.0 22.3 21.0 19.4

072 4080 27/19 23.8 23.3 22.6 21.4 19.830/19 24.2 23.7 23.1 22.0 21.033/19 24.7 24.4 24.0 23.3 22.524/19 23.7 23.5 22.8 21.8 20.2

4900 27/19 24.1 23.8 23.2 22.3 20.930/19 24.5 24.3 23.8 23.2 22.333/19 25.0 25.0 24.7 24.2 23.5

24/19 28.8 28.2 27.2 25.2 16.24590 27/19 29.2 28.5 27.3 25.4 16.6

30/19 29.6 28.9 27.8 26.0 17.033/19 30.2 29.6 28.9 27.9 17.324/19 29.1 28.6 27.6 25.7 23.3

090 5100 27/19 29.5 28.9 27.8 26.1 23.830/19 30.0 29.4 28.3 27.1 25.433/19 30.5 30.1 29.6 28.7 27.524/19 29.4 29.2 28.2 26.7 24.2

6120 27/19 29.8 29.6 28.6 27.2 24.830/19 30.3 30.2 29.4 28.4 27.133/19 30.9 31.1 30.4 29.7 28.7

Page 193: Train Instrument's

Performance data WSD/WSH - heating mode

PROD-PRC014-E4

Unit size Indoor

airflow

(m3/h)

Indoor air

dry bulb

(°C)

Outdoor air temp dry bulb @ 70%RH (°C)

-12 -6 0 6 12

15 7.6 9.6 11.7 13.9 18.0060 3400 21 7.4 9.3 11.4 13.5 17.4

24 7.3 9.1 11.2 13.3 17.127 7.2 9.0 11.0 13.1 16.9

15 10.4 12.6 15.0 17.6 22.6072 4080 21 10.2 12.3 14.7 17.2 22.0

24 10.1 12.2 14.5 16.9 21.827 9.9 12.1 14.3 16.7 21.5

15 11.5 14.6 17.8 21.0 27.021 12.2 14.9 17.7 20.7 26.5

090 5100 24 12.5 14.9 17.6 20.5 26.227 12.6 14.9 17.5 20.3 25.9

Ro

ofto

p S

ystem

sW

SD

/WS

H-W

KD

/WK

H

191

Page 194: Train Instrument's

192192PROD-PRC014-E4

General data WKD/WKH Voyager II

Unit size 125 155 200

Cooling capacity (1) (kW) 36.3 44.8 60.2

Cooling mode power input (2) (kW) 12.5 15.5 22.2Coefficient of performance - cooling mode (2) 2.90 2.89 2.71

Number of cooling steps 2 2 2

Capacity per cooling step (%) 50/50 50/50 50/50

Heating capacity (3) (kW) 34.4 40.8 59.8

Heating mode power input (2) (kW) 10.1 12.0 17.9Coefficient of performance - heating mode (2) 3.41 3.40 3.34

Number of heating steps 1 1 1

Capacity per heating step (%) 100 100 100

Electric heater capacity (option) (kW) 25.0 25.0 37.5

Number of electric heater steps 2 2 2

Capacity per heating step (kW) 12.5/12.5 12.5/12.5 25.0/12.5

Refrigerant R407C

Compressor type Scroll Scroll Scroll

Number of compressors 2 2 2

Number of circuits 2 2 2

Indoor fan type Belt FC centrifugal

Outdoor fan type Direct drive axial

Number of outdoor fans 2 2 2

Nominal airflow (m3/h) 7140 8500 11210

Static pressure available (4) (Pa) 200 175 200

Maximum static pressure available (5) (Pa) 425 325 350

Sound power level (2) (dB(A)) 85 86 90

Sound pressure level (6) (dB(A)) 54 54 58

Sound power level in the duct (2) (dB(A)) 79 74 81Minimum operating outdoor air temperature - cooling mode (°C) -18Minimum operating outdoor air temperature - heating mode (7) (°C) -14Maximum operating outdoor air temperature - cooling mode (°C) 46Maximum operating outdoor air temperature - heating mode (°C) 18Minimum intake air temperature on the indoor coil - cooling mode (°C) 18Minimum intake air temperature on the indoor coil - heating mode (°C) 10

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions (3) At Eurovent conditions: indoor air temperature at 19°C and outdoor air temperature at 7°C DB/6°C WB (4) At the nominal airflow (5) At the nominal airflow with oversized drive when available(6) At 10m from the unit in a free field(7) Depends on installation conditions and local climatic conditions (wind, snow, rain...).

Page 195: Train Instrument's

Performance data WKD/WKH - cooling mode

PROD-PRC014-E4

Unit size Airflow

(m3/h)

Air Temperature(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 39.3 38.1 36.9 34.0 30.8

6430 27/19 39.9 38.4 36.9 34.0 31.1

30/19 40.4 38.7 36.9 34.3 31.1

33/19 40.4 39.0 37.5 34.6 32.2

24/19 39.9 38.7 37.5 34.9 31.7

125 7140 27/19 40.2 39.0 37.8 34.9 31.9

30/19 40.2 39.0 37.8 35.2 32.2

33/19 41.0 39.6 38.1 36.3 33.7

24/19 39.9 39.3 38.7 36.3 32.8

8560 27/19 40.4 39.6 38.7 36.3 33.1

30/19 40.7 39.9 39.0 36.9 33.4

33/19 40.7 40.4 40.2 38.7 36.6

24/19 49.8 47.8 45.7 41.9 38.1

7650 27/19 49.8 47.8 45.7 42.2 38.1

30/19 50.4 48.1 45.7 42.2 38.4

33/19 50.7 48.4 46.0 42.8 39.0

24/19 50.1 48.4 46.6 43.1 39.0

155 8500 27/19 50.4 48.7 46.9 43.4 39.3

30/19 51.0 48.9 46.9 43.4 39.3

33/19 51.3 49.2 47.2 44.3 40.7

24/19 50.4 49.2 48.1 44.8 40.7

10200 27/19 51.6 49.8 48.1 45.1 40.7

30/19 51.9 50.1 48.4 45.4 41.3

33/19 52.5 50.7 48.9 46.9 43.7

24/19 68.9 65.4 61.8 57.1 52.2

10090 27/19 69.5 65.6 61.8 57.1 52.2

30/19 69.2 65.6 62.1 57.7 52.8

33/19 70.0 66.5 63.0 58.3 54.8

200 24/19 69.8 66.5 63.3 58.3 53.3

11210 27/19 70.3 66.8 63.3 58.6 53.6

30/19 70.6 67.1 63.6 59.2 54.5

33/19 71.5 68.0 64.5 61.3 57.1

24/19 71.2 68.3 65.4 60.7 55.4

13450 27/19 71.8 68.6 65.4 61.0 55.7

30/19 72.1 69.2 66.2 62.1 56.9

33/19 72.4 70.3 68.3 65.4 61.5

Ro

ofto

p S

ystem

sW

SD

/WS

H-W

KD

/WK

H

193

Page 196: Train Instrument's

194194PROD-PRC014-E4

Performance data WKD/WKH - heating mode

Unit size

Indoor

airflow

(m3/h)

Indoor air

dry bulb

(°C)

Outdoor air temp dry bulb @ 70%RH (°C)

-12 -6 0 6 12

15 16.6 19.7 23.7 30.7 37.4125 7140 21 16.4 19.4 23.3 30.1 36.5

24 16.3 19.2 23.1 29.7 36.127 16.2 19.1 22.9 29.4 35.7

15 21.3 24.5 29.0 37.3 45.2155 8500 21 20.4 24.0 28.7 37.0 44.7

24 20.1 23.9 28.6 36.8 44.527 19.9 23.8 28.6 36.7 44.2

15 29.7 35.9 43.0 55.2 66.3200 11210 21 31.2 36.4 42.8 54.3 64.9

24 31.7 36.5 42.7 54.0 64.327 32.0 36.6 42.5 53.6 63.8

Page 197: Train Instrument's

Dimensions, weights and clearances

PROD-PRC014-E4

C

E

B

D

A

X

Z

Y

Unit size

Dimensions(mm)

Weights (1)

Shipping weight

(kg)

Operating weight

(kg) Minimum clearances

(mm)

X Y Z A B C D E

WSD/WSH 060 1775 1124 921 266 241 1829 1219 914 914 914

WSD/WSH 072 2251 1353 1038 408 368 1829 1219 914 914 914

WSD/WSH 090 2251 1353 1038 418 378 1829 1219 914 914 914

WKD/WKH 125 2726 1811 1273 658/673 625 1900 1800 1220 1000 1300

WKD/WKH 155 2726 1811 1273 680/695 642 1900 1800 1220 1000 1300

WKD/WKH 200 3107 2154 1372 922/942 871 1900 1800 1220 1000 1300

(1) For standard unit, without accessories or options.

Accesscontrol panel

Unit size WSD/WSH WSD/WSH WSD/WSH WKD/WKH WKD/WKH WKD/WKH

060 072 090 125 155 200

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 20 23 26 30 34 46

Start-up amps (A) 79 109 110 94 101 127Maximum recommended fuse size (AM) (1) (A) 25 32 32 40 50 63

(1) For standard unit, without accessories or options

Electrical data

xxxxxxxxxxxxxxxxxx

195

WS

D/W

SH

-WK

D/W

KH

195

Ro

ofto

p S

ystem

s

Page 198: Train Instrument's

TSD/TSHTKD/TKH

196PROD-PRC014-E4

Customer benefits• High performance: lowest energy consumption• High reliability: low maintenance costs

Main features• High COP (Coefficient Of Performance)• Adjustable pulley (sizes 060 to 250) or drive kit

(sizes 275 to 500)• Dedicated horizontal or vertical airflow configuration

(also convertible on field on sizes 060 to 120)• Fire-resistant and washable aluminum foil-faced

insulated panels on air section• Single-side access for easy service

Options• Supply fan soft starter• Fan energy saving system with 80-100% 2 speeds

invertor (sizes 275-500)• Black epoxy coating on condensing and/or evaporating

coils (consult for sizes)• Electric heater• Hot water coil with 3-way-valve (except TKH)• Communication interfaces to Trane or non-Trane

supervisors and thermostats- TCI-R for Tracer, Tracker or Varitrac- All thermostats can be directly connected to the

ReliaTel™ board- LonTalk® card

• Fresh air intake for air quality and/or energy savings(free cooling) through:

- Manual (0-25% on sizes 275 to 500) or motorized hoods(0-50% on sizes 060 to 250)

- Advanced comparative enthalpy economizers- Exhaust fan (sizes 275 to 500)

• CO2 (or Volatile Organic Components: sizes 275 to 500)sensors

• High efficiency washable EU4 filters• Fire thermostat• Smoke detector• Remote fault relay• Clogged filter sensor• Fan failure switch (sizes 060 to 120)• Fused disconnect switch

Accessories• Adjustable or non-adjustable roofcurbs• Electronic (THS) and programmable (THP) thermostats• Barometric relief

Control • 24 V easy-to-start and service microprocessor controls

ReliaTel™ (sizes 060-250), UCP2™ (sizes 275-500)

• Built-in test mode • Anti-short cycle timers• Compressor minimum on/off time• Alternative compressor lead/lag• Low ambient cooling (down to -18°C) and anti-freeze

protection • Emergency Stop Input• Intelligent fallback (built-in setpoints)• On-board diagnostics• Built-in conventional thermostat interface (sizes 060-250)• Remote on/off input (sizes 060-250)

* Also available with R22 refrigerant for applications outside the European Union. For information, contact your local Trane Sales Office.

Cooling-only18-143 kW*

Rooftops

Voyager ITM range

TSD: Downflow discharge and intakeTSH: Horizontal discharge and intakeVoyagerTM II range

TKD: Downflow discharge and intakeTKH: Horizontal discharge and intakeVoyagerTM III range

TKD: Downflow discharge and intakeTKH: Horizontal discharge and intake

TKH

THP 03

Page 199: Train Instrument's

General data TSD/TSH Voyager I

PROD-PRC014-E4

Unit size060 072 090 102 120

Cooling capacity (1) (kW) 17.3 21.8 24.9 29.6 32.6

Cooling mode power input (2) (kW) 5.8 6.3 7.7 10.7 12.3

Coefficient of Performance (2) 2.98 3.44 3.22 2.76 2.65

Number of cooling steps 1 1 1 2 2

Capacity per cooling step (%) 100 100 100 60/40 65/35

Electric heater capacity (option) (kW) 12 18 18 25 25

Number of electric heater steps 2 2 2 2 2

Capacity per heating step (kW) 6/6 6/12 6/12 12.5/12.5 12.5/12.5

Refrigerant R407C

Compressor type Scroll

Number of compressors 1 1 1 2 2

Number of circuits 1 1 1 2 2

Indoor fan type Belt drive FC Centrifugal

Outdoor fan type Direct drive axial

Number of outdoor fans 1 1 1 1 1

Nominal airflow (m3/h) 3400 4080 5100 5780 6800

Static pressure available TSD/TSH (3) (Pa) 325/225 275/225 250/175 275/200 325/225

Maximum static pressure available TSD/TSH (4) (Pa) 375/325 375/375 375/375 500/500 500/450

Sound power level (2) (dB(A)) 79 81 81 83 79

Sound pressure level (5) (dB(A)) 48 49 49 51 47

Sound power level in the duct (2) (dB(A)) 71 68 70 78 80

Minimum operating outdoor air temperature (°C) -18

Maximum operating outdoor air temperature (°C) 46

Minimum intake air temperature on the indoor coil (°C) 18

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) At the nominal airflow(4) At the nominal airflow with oversized drive when available(5) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sT

SD

/TS

H-T

KD

/TK

H

197

Page 200: Train Instrument's

198198PROD-PRC014-E4

Performance data TSD/TSH

Unit size Airflow

(m3/h)

Air Temperature

(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 19.0 18.5 17.8 16.5 15.13060 27/19 19.2 18.7 17.8 16.6 15.2

30/19 19.4 18.9 18.2 17.1 15.633/19 19.8 19.4 18.8 18.0 17.124/19 19.2 18.8 18.1 16.9 15.4

060 3400 27/19 19.4 19.0 18.2 17.0 15.630/19 19.7 19.3 18.6 17.5 16.433/19 20.0 19.8 19.3 18.7 17.824/19 19.4 19.2 18.5 17.5 16.1

4080 27/19 19.7 19.4 18.7 17.8 16.530/19 20.1 19.8 19.1 18.5 17.633/19 20.5 20.4 19.9 19.5 18.7

24/19 24.5 23.7 22.7 21.3 19.53670 27/19 24.7 23.9 22.7 21.3 19.6

30/19 24.9 24.1 23.0 21.7 20.233/19 25.4 24.6 23.8 22.8 21.724/19 24.8 24.1 23.0 21.7 20.0

072 4080 27/19 25.0 24.2 23.2 21.8 20.130/19 25.3 24.5 23.5 22.3 20.933/19 25.8 25.2 24.4 23.5 22.424/19 25.2 24.5 23.6 22.4 20.8

4900 27/19 25.5 24.8 23.8 22.5 21.030/19 25.9 25.2 24.3 23.3 22.233/19 26.5 26.0 25.3 24.4 23.4

24/19 27.5 27.0 26.1 24.6 22.34590 27/19 27.9 27.3 26.3 24.6 22.4

30/19 28.3 27.6 26.7 25.2 23.233/19 28.8 28.1 27.5 26.5 25.124/19 27.7 27.4 26.4 25.0 22.9

090 5100 27/19 28.1 27.7 26.7 25.2 23.130/19 28.5 28.2 27.2 25.8 24.333/19 29.0 28.5 28.0 27.2 25.924/19 27.9 27.7 26.9 25.7 23.8

6120 27/19 28.3 28.1 27.2 26.0 24.230/19 28.7 28.6 27.8 26.9 25.633/19 29.2 29.3 28.7 27.9 26.9

24/19 33.0 31.8 30.0 27.7 25.05200 27/19 33.3 32.1 30.4 28.1 25.5

30/19 33.8 32.6 30.8 29.0 26.833/19 34.3 33.5 32.2 30.8 29.024/19 33.3 32.3 30.7 28.4 25.7

102 5780 27/19 33.8 32.7 31.1 28.9 26.330/19 34.3 33.3 31.8 30.1 28.033/19 34.9 34.2 33.2 31.8 30.224/19 33.9 32.9 31.5 29.4 26.8

6940 27/19 34.5 33.5 32.1 30.0 27.730/19 35.1 34.1 33.0 31.5 29.833/19 36.0 35.2 34.3 33.1 31.6

24/19 36.3 35.3 33.8 31.6 28.96120 27/19 36.8 35.8 34.2 32.1 29.4

30/19 37.4 36.3 34.8 32.9 31.033/19 37.7 37.2 36.4 35.1 33.624/19 36.7 35.9 34.4 32.5 29.7

120 6800 27/19 37.3 36.4 34.9 33.0 30.430/19 37.9 37.1 35.5 34.1 32.433/19 38.4 38.3 37.1 36.0 34.724/19 37.2 36.5 35.2 33.5 31.1

8160 27/19 37.9 37.1 35.9 34.2 31.730/19 38.6 37.9 36.8 35.7 34.333/19 39.5 38.9 38.3 37.4 36.1

Page 201: Train Instrument's

General data TKD/TKH Voyager II

PROD-PRC014-E4

Unit size 155 175 200 250

Cooling capacity (1) (kW) 42.4 48.1 57.8 62.0

Cooling mode power input (2) (kW) 14.5 17.6 21.1 20.7

Coefficient of performance (2) 2.92 2.73 2.74 3.00

Number of cooling steps 2 2 2 2

Capacity per cooling step (%) 60/40 70/30 50/50 50/50

Electric heater capacity (option) (kW) 25.0 25.0 37.5 37.5

Number of electric heater steps 2 2 2 2

Capacity per heating step (kW) 12.5/12.5 12.5/12.5 25.0/12.5 25.0/12.5

Refrigerant R407C

Compressor type Scroll Scroll Scroll Scroll

Number of compressors 2 2 2 2

Number of circuits 2 2 2 2

Indoor fan type Belt FC centrifugal

Outdoor fan type Direct drive axial

Number of outdoor fans 2 2 2 2

Nominal airflow (m3/h) 8500 9850 11210 14100

Static pressure available (3) (Pa) 175 250 200 125Maximum static pressure available (4) (Pa) 325 400 375 350

Sound power level (2) (dB(A)) 86 86 89 90

Sound pressure level (5) (dB(A)) 54 54 57 58

Sound power level in the duct (2) (dB(A)) 74 77 77 82Minimum operating outdoor air temperature (°C) -18Maximum operating outdoor air temperature (°C) 46Minimum intake air temperature on the indoor coil (°C) 18

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) At the nominal airflow(4) At the nominal airflow with oversized drive when available(5) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sT

SD

/TS

H-T

KD

/TK

H

199

Page 202: Train Instrument's

200200PROD-PRC014-E4

Performance data TKD/TKH

Unit size Airflow

(m3/h)

Air Temperature(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 47.3 45.2 43.1 40.7 38.1

7650 27/19 47.5 45.3 43.1 40.8 38.1

30/19 47.5 45.4 43.3 39.3 38.5

33/19 48.0 46.1 44.2 42.2 40.2

24/19 47.9 45.9 43.9 41.5 38.9

155 8500 27/19 48.2 46.1 44.0 41.6 39.0

30/19 49.7 46.3 42.9 42.0 39.7

33/19 49.1 47.3 45.5 43.6 41.6

24/19 49.2 47.1 45.0 42.7 40.1

10200 27/19 49.6 47.4 45.2 42.9 40.3

30/19 48.0 46.9 45.8 43.7 41.4

33/19 50.7 49.1 47.5 45.7 43.7

24/19 55.1 52.2 49.3 46.0 42.5

8860 27/19 55.3 52.3 49.3 46.0 42.5

30/19 55.4 52.4 49.4 46.2 42.8

33/19 55.6 53.0 50.4 48.0 45.4

24/19 57.3 53.9 50.5 47.2 43.6

175 9850 27/19 56.3 53.4 50.5 47.3 43.6

30/19 56.5 53.6 50.7 47.6 44.2

33/19 56.6 54.5 52.4 50.0 47.4

24/19 57.4 54.8 52.2 49.0 45.3

11830 27/19 57.6 55.0 52.4 49.0 45.4

30/19 58.0 55.4 52.8 49.5 46.8

33/19 59.0 57.1 55.2 53.0 50.5

24/19 64.6 61.4 58.2 54.6 50.6

10090 27/19 64.7 61.5 58.3 54.7 50.7

30/19 64.7 61.6 58.5 54.9 51.2

33/19 64.1 61.7 59.3 56.6 53.7

24/19 65.5 62.5 59.5 55.9 51.9

200 11210 27/19 65.6 62.6 59.6 55.9 52.0

30/19 65.9 62.9 59.9 56.4 51.7

33/19 65.9 63.7 61.5 58.8 56.0

24/19 66.7 64.0 61.3 57.9 53.8

13450 27/19 67.1 64.3 61.5 58.0 54.0

30/19 67.7 64.9 62.1 58.4 55.3

33/19 68.7 66.6 64.5 62.1 59.3

24/19 70.7 67.2 63.7 59.7 55.4

12690 27/19 71.0 67.4 63.8 59.8 55.6

30/19 71.2 67.8 64.4 60.3 57.1

33/19 72.7 70.2 67.7 64.9 61.9

24/19 71.7 68.3 64.9 60.9 56.6

250 14100 27/19 72.0 68.5 65.0 61.1 56.8

30/19 72.7 69.2 65.7 62.6 59.4

33/19 74.5 72.1 69.7 67.0 64.1

24/19 73.2 69.9 66.6 62.8 58.4

16920 27/19 73.5 70.2 66.9 63.1 59.0

30/19 74.1 71.5 68.9 66.1 62.9

33/19 77.3 75.0 72.7 70.1 67.2

Page 203: Train Instrument's

General data TKD/TKH Voyager III

PROD-PRC014-E4

Unit size 275 300 350 400 500

Cooling capacity (1) (kW) 81.5 88.6 99.1 126.2 143.1

Cooling mode power input (2) (kW) 24.5 28.1 32.0 42.0 49.8

Coefficient of performance (2) 3.32 3.15 3.10 3.01 2.87

Number of cooling steps 2 2 2 3 3

Capacity per cooling step (%) 40/60 50/50 50/50 33/33/33 33/33/33

Electric heater capacity (option) (kW) 25.0 37.5 50.0 62.5 75.0

Number of electric heater steps 2 2 2 2 2

Capacity per heating step (kW) 12.5/12.5 25.0/12.5 25.0/25.0 25.0/37.5 25.0/50.0

Refrigerant R407C

Compressor type Scroll

Number of compressors 2 2 2 3 3

Number of circuits 1 1 1 2 2

Indoor fan type Belt FC centrifugal

Outdoor fan type Direct drive axial

Number of outdoor fans 3 3 3 4 4

Nominal airflow (m3/h) 13600 15300 17000 20400 24600

Maximum static pressure available (3) (Pa) 550 550 500 600 600

Sound power level (2) (dB(A)) 89 89 94 96 96

Sound pressure level (4) (dB(A)) 57 57 62 64 64Sound power level in the duct (2) (dB(A)) 84 84 85 87 87Minimum operating outdoor air temperature (°C) -18Maximum operating outdoor air temperature (°C) 46Minimum intake air temperature on the indoor coil (°C) 18

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) At the nominal airflow(4) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sT

SD

/TS

H-T

KD

/TK

H

201

Page 204: Train Instrument's

202202PROD-PRC014-E4

Performance data TKD/TKH

Unit size Airflow

(m3/h)

Air Temperature(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 84.4 81.3 78.0 74.5 70.727/19 84.6 81.5 78.2 74.7 71.0

10880 30/19 85.3 82.2 79.0 75.6 71.933/19 85.5 82.5 79.3 75.9 72.324/19 88.0 84.7 81.1 77.4 73.427/19 88.3 85.0 81.5 77.7 73.8

275 13600 30/19 89.5 86.3 82.8 79.1 75.533/19 90.0 86.9 83.5 80.0 76.024/19 90.9 87.4 83.6 79.5 75.327/19 91.4 87.9 84.1 80.1 75.9

17680 30/19 93.9 90.6 87.1 83.4 79.533/19 95.1 92.2 89.0 85.6 82.0

24/19 91.9 88.6 84.9 81.1 77.027/19 92.2 88.8 85.2 81.4 77.4

12240 30/19 92.9 89.6 86.1 82.3 78.433/19 93.2 89.9 86.4 82.7 78.924/19 95.6 92.0 88.1 84.0 79.627/19 96.0 92.4 88.5 84.4 80.1

300 15300 30/19 97.3 93.8 89.7 86.0 82.033/19 97.9 94.4 90.8 87.0 82.724/19 98.4 94.5 90.3 85.9 81.327/19 98.9 95.0 90.9 86.6 82.0

19890 30/19 101.6 98.0 94.2 90.1 85.833/19 103.0 99.8 96.3 92.6 88.6

24/19 104.4 100.4 96.2 91.7 87.027/19 104.7 100.7 96.4 92.0 87.3

13600 30/19 105.8 101.8 97.6 93.3 88.733/19 106.2 102.3 98.2 93.9 89.524/19 108.0 103.7 99.1 94.3 89.327/19 108.3 104.1 99.6 94.8 89.8

350 17000 30/19 109.9 106.0 101.8 97.5 92.933/19 111.3 107.3 102.7 98.8 -24/19 110.2 105.6 100.7 95.7 90.427/19 110.9 106.4 101.6 96.6 91.4

22100 30/19 115.0 110.7 106.2 101.4 96.533/19 117.8 113.9 109.7 105.3 -

24/19 132.6 127.3 121.6 115.6 109.427/19 133.0 127.7 122.1 116.0 109.8

16320 30/19 134.4 129.1 123.6 117.7 111.533/19 135.0 129.8 124.3 118.6 112.624/19 137.6 131.9 125.8 119.5 112.827/19 138.1 132.4 126.4 120.1 113.6

400 20400 30/19 140.3 134.8 128.8 123.0 116.833/19 141.8 136.4 130.6 124.0 118.624/19 140.9 134.8 128.4 121.7 114.627/19 141.9 135.9 129.6 122.9 116.0

26520 30/19 146.6 140.9 134.9 128.6 122.133/19 149.6 144.4 138.8 133.0 126.9

24/19 153.2 146.9 140.2 133.2 125.927/19 153.6 147.3 140.7 133.8 126.5

19680 30/19 155.6 149.4 142.8 136.0 -33/19 156.5 150.4 144.0 137.3 -24/19 157.6 150.8 143.7 136.3 -27/19 158.3 151.7 144.6 137.3 129.6

500 24600 30/19 161.4 155.3 148.7 141.9 -33/19 163.6 156.7 150.8 144.6 -24/19 159.1 151.9 144.4 136.6 -27/19 160.6 153.5 146.1 138.4 -

31980 30/19 167.5 160.8 153.7 146.3 -

33/19 172.6 166.3 159.7 152.8 -

Page 205: Train Instrument's

Dimensions, weights and clearances

PROD-PRC014-E4

X

Z

Y

Accesscontrol panel

C

E

B

D

A

Unit size

Shipping weight

(kg)

Operating weight

(kg)

Weights

Minimum clearances (mm)

X Y Z A B C D E

TSD/TSH 060 1775 1124 921 259 235 1829 1219 914 914 914

TSD/TSH 072 2251 1353 1038 365 326 1829 1219 914 914 914

TSD/TSH 090 2251 1353 1038 428 389 1829 1219 914 914 914

TSD/TSH 102 2251 1353 1190 445 405 1829 1219 914 914 914

TSD/TSH 120 2251 1353 1190 485 445 1829 1219 914 914 914

TKD/TKH 155 2726 1811 1273 662/677 623 1900 1800 1220 1000 1300

TKD/TKH 175 2726 1811 1273 680/695 660 1900 1800 1220 1000 1300

TKD/TKH 200 3107 2154 1372 872/892 841 1900 1800 1220 1000 1300

TKD/TKH 250 3107 2154 1372 921/941 866 1900 1800 1220 1000 1300

TKD/TKH 275 4580 2302 1821 1697/1717 1597/1617 1900 2440 1220 1220 1830

TKD/TKH 300 4580 2302 1821 1733 1633 1900 2440 1220 1220 1830

TKD/TKH 350 4580 2302 1821 1772 1672 1900 2440 1220 1220 1830

TKD/TKH 400 5917 2302 1988 2199 2059 1900 2440 1220 1220 1830

TKD/TKH 500 5917 2302 1988 2277 2137 1900 2440 1220 1220 1830(1) For standard unit, without options or accessories

Dimensions (1)(mm)

Unit size TSD/TSH TSD/TSH TSD/TSH TSD/TSH TSD/TSH TKD/TKH TKD/TKH TKD/TKH TKD/TKH

060 072 090 102 120 155 175 200 250

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 18 24 26 28 33 33 39 41 43

Start-up amps (A) 79 103 110 91 93 136 141 144 145Maximum recommended fuse size (AM) (1) (A) 25 32 32 32 40 50 50 50 63

(1) For standard unit, without accessories or options

Unit size TKD/TKH TKD/TKH TKD/TKH TKD/TKH TKD/TKH

275 300 350 400 500

Power supply (V/Ph/Hz) 400/3/50Maximum amps (A) 74 83 89 111 129Start-up amps (A) 222 231 237 259 276

Electrical dataxxxxxxxxxxxxxxxxxx

203

TS

D/T

SH

-TK

D/T

KH

203

Ro

ofto

p S

ystem

s

Page 206: Train Instrument's

YSD/YSHYKD/YKH

204PROD-PRC014-E4

Customer benefits • High performance: lowest energy consumption• High reliability: low maintenance costs

Main features• High COP (Coefficient Of Performance)• Adjustable pulley (sizes 060 to 250) or drive kit

(sizes 275 to 500)• Dedicated horizontal or vertical airflow configaration

(also convertible on field on sizes 060-120)• Fire-resistant and washable aluminum foil-faced

insulated panels on air section• Single-side access for easy service• Gas burners, compatible with G20, G25 and G31 gas

(corrosion resistant aluminized steel tubes)

Options• Supply fan soft starter• Fan energy saving system with 80-100% 2 speeds

invertor• Black epoxy coating on condensing and/or evaporating

coils (consult for sizes)• Oversized drive kits to increase available static pressure• Communication interfaces to Trane or non-Trane

supervisors and thermostats-TCI-R for Tracer, Tracker or Varitrac- All thermostats can be directly connected to the

ReliaTel™ board- LonTalk® card

• Fresh air intake for air quality and/or energy savings(free cooling) through:

- Manual (0-25% on sizes 275 to 500) or motorized hoods(0-50% on sizes 060 to 250)

- Advanced comparative enthalpy economizers- Exhaust fan (sizes 275 to 500)

• CO2 sensors• High efficiency washable EU4 filters• Fire thermostat• Smoke detector• Remote fault relay• Clogged filter sensor• Fan failure switch (sizes 060 to 120)• Fused disconnect switch

Accessories• Adjustable or non-adjustable roof curbs• Electronic (THS 03) and programmable (THP 03)

thermostats• Barometric relief

Control • 24 V easy-to-start and service microprocessor controls

ReliaTel™

• Built-in test mode • Anti-short cycle timers• Compressor minimum on/off time• Alternative compressor lead/lag• Low ambient cooling (down to -18°C) and anti-freeze

protection • Emergency Stop Input• Intelligent fallback (built-in setpoints)• On-board diagnostics• Built-in conventional thermostat interface (sizes 060-250)• Remote on/off input

* Also available with R22 refrigerant for applications outside the European Union. For information, contact your local Trane Sales Office.

Gas-fired17-143 kW*

Rooftops

Voyager™I range

YSD: Downflow discharge and intakeYSH: Horizontal discharge and intakeVoyager™II range

YKD: Downflow discharge and intakeYKH: Horizontal discharge and intakeVoyager™ III range

YKD: Downflow discharge and intakeYKH: Horizontal discharge and intake

YKD/YKH

THP 03

Page 207: Train Instrument's

General data YSD/YSH Voyager I

PROD-PRC014-E4

Unit size 060 072 090 102 120

Cooling capacity (1) (kW) 17.3 21.8 24.9 29.6 32.6

Cooling mode power input (2) (kW) 5.8 6.3 7.7 10.7 12.3Coefficient of Performance - cooling mode (2) 2.98 3.44 3.22 2.76 2.65Number of cooling steps 1 1 1 2 2Capacity per cooling step (%) 100 100 100 40/60 45/55Heating capacity (3) (kW) 24.6 41.3 41.3 51.9 51.9

Efficiency (%) 93 93 93 93 93Refrigerant R407CCompressor type ScrollNumber of compressors 1 1 1 2 2Number of circuits 1 1 1 2 2Indoor fan type Belt FC CentrifugalOutdoor fan type Direct drive axialNumber of outdoor fans 1 1 1 1 1Nominal airflow (m3/h) 3400 4080 5100 5780 6800

Static pressure available YSD/YSH (4) (Pa) 350/250 300/250 250/200 275/175 375/200Maximum static pressure available YSD/YSH (5) (Pa) 350/250 375/375 375/375 500/500 450/325Sound power level (2) (dB(A)) 79 81 81 83 79Sound pressure level (6) (dB(A)) 48 49 49 51 47Sound power level in the duct (2) (dB(A)) 71 68 70 78 80Minimum operating outdoor air temperature (°C) -18Maximum operating outdoor air temperature (°C) 46Minimum intake air temperature on the indoor coil - cooling mode (°C) 18Minimum intake air temperature on the indoor coil - heating mode (°C) 4

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) Heating output with G20 gas(4) At the nominal airflow(5) At the nominal airflow with oversized drive when available(6) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sY

SD

/YS

H-Y

KD

/YK

H

205

Page 208: Train Instrument's

206206PROD-PRC014-E4

Performance data YSD/YSH - cooling mode

Unit size Airflow

(m3/h)

Air Temperature

(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 19.0 18.5 17.8 16.5 15.13060 27/19 19.2 18.7 17.8 16.6 15.2

30/19 19.4 18.9 18.2 17.1 15.633/19 19.8 19.4 18.8 18.0 17.124/19 19.2 18.8 18.1 16.9 15.4

060 3400 27/19 19.4 19.0 18.2 17.0 15.630/19 19.7 19.3 18.6 17.5 16.433/19 20.0 19.8 19.3 18.7 17.824/19 19.4 19.2 18.5 17.5 16.1

4080 27/19 19.7 19.4 18.7 17.8 16.530/19 20.1 19.8 19.1 18.5 17.633/19 20.5 20.4 19.9 19.5 18.7

24/19 24.5 23.7 22.7 21.3 19.53670 27/19 24.7 23.9 22.7 21.3 19.6

30/19 24.9 24.1 23.0 21.7 20.233/19 25.4 24.6 23.8 22.8 21.724/19 24.8 24.1 23.0 21.7 20.0

072 4080 27/19 25.0 24.2 23.2 21.8 20.130/19 25.3 24.5 23.5 22.3 20.933/19 25.8 25.2 24.4 23.5 22.424/19 25.2 24.5 23.6 22.4 20.8

4900 27/19 25.5 24.8 23.8 22.5 21.030/19 25.9 25.2 24.3 23.3 22.233/19 26.5 26.0 25.3 24.4 23.4

24/19 27.5 27.0 26.1 24.6 22.34590 27/19 27.9 27.3 26.3 24.6 22.4

30/19 28.3 27.6 26.7 25.2 23.233/19 28.8 28.1 27.5 26.5 25.124/19 27.7 27.4 26.4 25.0 22.9

090 5100 27/19 28.1 27.7 26.7 25.2 23.130/19 28.5 28.2 27.2 25.8 24.333/19 29.0 28.5 28.0 27.2 25.924/19 27.9 27.7 26.9 25.7 23.8

6120 27/19 28.3 28.1 27.2 26.0 24.230/19 28.7 28.6 27.8 26.9 25.633/19 29.2 29.3 28.7 27.9 26.9

24/19 33.0 31.8 30.0 27.7 25.05200 27/19 33.3 32.1 30.4 28.1 25.5

30/19 33.8 32.6 30.8 29.0 26.833/19 34.3 33.5 32.2 30.8 29.024/19 33.3 32.3 30.7 28.4 25.7

102 5780 27/19 33.8 32.7 31.1 28.9 26.330/19 34.3 33.3 31.8 30.1 28.033/19 34.9 34.2 33.2 31.8 30.224/19 33.9 32.9 31.5 29.4 26.8

6940 27/19 34.5 33.5 32.1 30.0 27.730/19 35.1 34.1 33.0 31.5 29.833/19 36.0 35.2 34.3 33.1 31.6

24/19 36.3 35.3 33.8 31.6 28.96120 27/19 36.8 35.8 34.2 32.1 29.4

30/19 37.4 36.3 34.8 32.9 31.033/19 37.7 37.2 36.4 35.1 33.624/19 36.7 35.9 34.4 32.5 29.7

120 6800 27/19 37.3 36.4 34.9 33.0 30.430/19 37.9 37.1 35.5 34.1 32.433/19 38.4 38.3 37.1 36.0 34.724/19 37.2 36.5 35.2 33.5 31.1

8160 27/19 37.9 37.1 35.9 34.2 31.730/19 38.6 37.9 36.8 35.7 34.333/19 39.5 38.9 38.3 37.4 36.1

Page 209: Train Instrument's

General data YKD/YKH Voyager II

PROD-PRC014-E4

Unit size 155 175 200 250

Cooling capacity (1) (kW) 42.4 48.1 57.8 62.0

Cooling mode power input (2) (kW) 14.5 17.6 21.4 20.7Coefficient of performance -cooling mode (2) 2.92 2.73 2.74 3.00Number of cooling steps 2 2 2 2Capacity per cooling step (%) 60/40 70/30 50/50 50/50Heating capacity (3) (kW) 69.3 69.3 69.3 69.3

Efficiency (%) 90 90 90 90Refrigerant R407CCompressor type Scroll Scroll Scroll ScrollNumber of compressors 2 2 2 2Number of circuits 2 2 2 2Indoor fan type Belt FC centrifugalOutdoor fan type Direct drive axialNumber of outdoor fans 2 2 2 2Nominal airflow (m3/h) 8500 9850 11210 14100

Static pressure available YKD (4) (Pa) 150 75 175 75Maximum static pressure available YKD (5) (Pa) 350 375 450 375

Sound power level (2) (dB(A)) 86 86 89 90Sound pressure level (6) (dB(A)) 54 54 57 58Sound power level in the duct (2) (dB(A)) 74 77 77 82Minimum operating outdoor air temperature - cooling mode (°C) -18Maximum operating outdoor air temperature - cooling mode (°C) 46Minimum intake air temperature on the indoor coil - cooling mode (°C) 18Minimum intake air temperature on the burner- heating mode (°C) 5

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) Heating output with G20 gas(4) At the nominal airflow(5) At the nominal airflow with oversized drive when available(6) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sY

SD

/YS

H-Y

KD

/YK

H

207

Page 210: Train Instrument's

208208PROD-PRC014-E4

Performance data YKD/YKH - cooling mode

Air Temperature(°C)

Airflow (m3/h)

Unit size Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 47.3 45.2 43.1 40.7 38.17650 27/19 47.5 45.3 43.1 40.8 38.1

30/19 47.5 45.4 43.3 39.3 38.533/19 48.0 46.1 44.2 42.2 40.224/19 47.9 45.9 43.9 41.5 38.9

155 8500 27/19 48.2 46.1 44.0 41.6 39.030/19 49.7 46.3 42.9 42.0 39.733/19 49.1 47.3 45.5 43.6 41.624/19 49.2 47.1 45.0 42.7 40.1

10200 27/19 49.6 47.4 45.2 42.9 40.330/19 48.0 46.9 45.8 43.7 41.433/19 50.7 49.1 47.5 45.7 43.7

24/19 55.1 52.2 49.3 46.0 42.58860 27/19 55.3 52.3 49.3 46.0 42.5

30/19 55.4 52.4 49.4 46.2 42.833/19 55.6 53.0 50.4 48.0 45.424/19 57.3 53.9 50.5 47.2 43.6

175 9850 27/19 56.3 53.4 50.5 47.3 43.630/19 56.5 53.6 50.7 47.6 44.233/19 56.6 54.5 52.4 50.0 47.424/19 57.4 54.8 52.2 49.0 45.3

11830 27/19 57.6 55.0 52.4 49.0 45.430/19 58.0 55.4 52.8 49.5 46.833/19 59.0 57.1 55.2 53.0 50.5

24/19 64.6 61.4 58.2 54.6 50.610090 27/19 64.7 61.5 58.3 54.7 50.7

30/19 64.7 61.6 58.5 54.9 51.233/19 64.1 61.7 59.3 56.6 53.724/19 65.5 62.5 59.5 55.9 51.9

200 11210 27/19 65.6 62.6 59.6 55.9 52.030/19 65.9 62.9 59.9 56.4 51.733/19 65.9 63.7 61.5 58.8 56.024/19 66.7 64.0 61.3 57.9 53.8

13450 27/19 67.1 64.3 61.5 58.0 54.030/19 67.7 64.9 62.1 58.4 55.333/19 68.7 66.6 64.5 62.1 59.3

24/19 70.7 67.2 63.7 59.7 55.412690 27/19 71.0 67.4 63.8 59.8 55.6

30/19 71.2 67.8 64.4 60.3 57.1250 33/19 72.7 70.2 67.7 64.9 61.9

24/19 71.7 68.3 64.9 60.9 56.614100 27/19 72.0 68.5 65.0 61.1 56.8

30/19 72.7 69.2 65.7 62.6 59.433/19 74.5 72.1 69.7 67.0 64.1

24/19 73.2 69.9 66.6 62.8 58.4

16920 27/19 73.5 70.2 66.9 63.1 59.0

30/19 74.1 71.5 68.9 66.1 62.9

33/19 77.3 75.0 72.7 70.1 67.2

Page 211: Train Instrument's

General data YKD/YKH Voyager III

PROD-PRC014-E4

Unit size 275 300 350 400 500

Cooling capacity (1) (kW) 81.5 88.6 99.1 126.2 143.1

Cooling mode power input (2) (kW) 24.5 28.1 32.0 42.0 49.8Coefficient of performance - cooling mode 3.33 3.15 3.10 3.00 2.87

Number of cooling steps 2 2 2 3 3

Capacity per cooling step (%) 40/60 50/50 50/50 33/33/33 33/33/33

Heating capacity - low heat (3) (kW) 69.3 69.3 69.3 77.4 77.4

Heating capacity - high heat (3) (kW) 117.5 117.5 117.5 154.8 154.8

Efficiency (%) 90 90 90 91 91

Refrigerant R407C

Compressor type Scroll

Number of compressors 2 2 2 3 3

Number of circuits 1 1 1 2 2

Indoor fan type Belt FC centrifugal

Outdoor fan type Direct drive axial

Number of outdoor fans 3 3 3 4 4

Nominal airflow (m3/h) 13600 15300 17000 20400 24600

Maximum static pressure available (4) (Pa) 525 520 465 590 590

Sound power level (2) (dB(A)) 89 89 94 96 96

Sound pressure level (5) (dB(A)) 57 57 62 64 64

Sound power level in the duct (2) (dB(A)) 83 84 85 87 87Minimum operating outdoor air temperature - cooling mode (°C) -18Maximum operating outdoor air temperature - cooling mode (°C) 46Minimum intake air temperature on the indoor coil - cooling mode (°C) 18Minimum intake air temperature on the burner - heating mode (°C) 5

(1) At Eurovent conditions: indoor air temperature at 27°C DB/19°C WB and outdoor air temperature at 35°C(2) At Eurovent conditions(3) Heating output with G20 gas(4) At the nominal airflow(5) At 10m from the unit in a free field

Ro

ofto

p S

ystem

sY

SD

/YS

H-Y

KD

/YK

H

209

Page 212: Train Instrument's

210210PROD-PRC014-E4

Performance data YKD/YKH -cooling mode

Unit size Airflow

(m3/h)

Air Temperature(°C)

Outdoor Air Temperature (°C)

DB/WB 25 30 35 40 45

24/19 84.4 81.3 78.0 74.5 70.727/19 84.6 81.5 78.2 74.7 71.0

10880 30/19 85.3 82.2 79.0 75.6 71.933/19 85.5 82.5 79.3 75.9 72.324/19 88.0 84.7 81.1 77.4 73.427/19 88.3 85.0 81.5 77.7 73.8

275 13600 30/19 89.5 86.3 82.8 79.1 75.533/19 90.0 86.9 83.5 80.0 76.024/19 90.9 87.4 83.6 79.5 75.327/19 91.4 87.9 84.1 80.1 75.9

17680 30/19 93.9 90.6 87.1 83.4 79.533/19 95.1 92.2 89.0 85.6 82.0

24/19 91.9 88.6 84.9 81.1 77.027/19 92.2 88.8 85.2 81.4 77.4

12240 30/19 92.9 89.6 86.1 82.3 78.433/19 93.2 89.9 86.4 82.7 78.924/19 95.6 92.0 88.1 84.0 79.627/19 96.0 92.4 88.5 84.4 80.1

300 15300 30/19 97.3 93.8 89.7 86.0 82.033/19 97.9 94.4 90.8 87.0 82.724/19 98.4 94.5 90.3 85.9 81.327/19 98.9 95.0 90.9 86.6 82.0

19890 30/19 101.6 98.0 94.2 90.1 85.833/19 103.0 99.8 96.3 92.6 88.6

24/19 104.4 100.4 96.2 91.7 87.027/19 104.7 100.7 96.4 92.0 87.3

13600 30/19 105.8 101.8 97.6 93.3 88.733/19 106.2 102.3 98.2 93.9 89.524/19 108.0 103.7 99.1 94.3 89.327/19 108.3 104.1 99.6 94.8 89.8

350 17000 30/19 109.9 106.0 101.8 97.5 92.933/19 111.3 107.3 102.7 98.8 -24/19 110.2 105.6 100.7 95.7 90.427/19 110.9 106.4 101.6 96.6 91.4

22100 30/19 115.0 110.7 106.2 101.4 96.533/19 117.8 113.9 109.7 105.3 -

24/19 132.6 127.3 121.6 115.6 109.427/19 133.0 127.7 122.1 116.0 109.8

16320 30/19 134.4 129.1 123.6 117.7 111.533/19 135.0 129.8 124.3 118.6 112.624/19 137.6 131.9 125.8 119.5 112.827/19 138.1 132.4 126.4 120.1 113.6

400 20400 30/19 140.3 134.8 128.8 123.0 116.833/19 141.8 136.4 130.6 124.0 118.624/19 140.9 134.8 128.4 121.7 114.627/19 141.9 135.9 129.6 122.9 116.0

26520 30/19 146.6 140.9 134.9 128.6 122.133/19 149.6 144.4 138.8 133.0 126.9

24/19 153.2 146.9 140.2 133.2 125.927/19 153.6 147.3 140.7 133.8 126.5

19680 30/19 155.6 149.4 142.8 136.0 -33/19 156.5 150.4 144.0 137.3 -24/19 157.6 150.8 143.7 136.3 -27/19 158.3 151.7 144.6 137.3 129.6

500 24600 30/19 161.4 155.3 148.7 141.9 -33/19 163.6 156.7 150.8 144.6 -24/19 159.1 151.9 144.4 136.6 -27/19 160.6 153.5 146.1 138.4 -

31980 30/19 167.5 160.8 153.7 146.3 -

33/19 172.6 166.3 159.7 152.8 -

Page 213: Train Instrument's

Dimensions, weights and clearances

PROD-PRC014-E4

E

D

C

B

A

Z

X

Y

Dimensions(mm)

Shipping weight

(kg)Minimum clearances

(mm)

Operating weight

(kg)

Unit size X Y Z A B C D E

YSD/YSH 060 1775 1124 921 285 260 1829 1219 914 914 914

YSD/YSH 072 2251 1353 1038 390 350 1829 1219 914 914 914

YSD/YSH 090 2251 1353 1038 458 419 1829 1219 914 914 914

YSD/YSH 102 2251 1353 1190 474 434 1829 1219 914 914 914

YSD/YSH 120 2251 1353 1190 520 481 1829 1219 914 914 914

YKD/YKH 155 2726 1811 1273 685/700 698 1900 1800 1220 1000 1300

YKD/YKH 175 2726 1811 1273 740/755 735 1900 1800 1220 1000 1300

YKD/YKH 200 3107 2167 1372 955/975 920 1900 1800 1220 1000 1300

YKD/YKH 250 3107 2167 1372 1005/1025 946 1900 1800 1220 1000 1300

YKD/YKH 275 L 4580 2302 1821 1756 1656 1900 2440 1220 1220 1830

YKD/YKH 275 H 5285 2302 1821 1940/1969 1820/1849 1900 2440 1220 1220 1830

YKD/YKH 300 L 4580 2302 1821 1792 1692 1900 2440 1220 1220 1830

YKD/YKH 300 H 5285 2302 1821 1976/1999 11856/1879 1900 2440 1220 1220 1830

YKD/YKH 350 L 4580 2302 1821 1931 1731 1900 2440 1220 1220 1830

YKD/YKH 350 H 5285 2302 1821 2015/2037 1895/1917 1900 2440 1220 1220 1830

YKD/YKH 400 L 5917 2302 1988 2301/2313 2161/2173 1900 2440 1220 1220 1830

YKD/YKH 400 H 5917 2302 1988 2356/2369 2216/2229 1900 2440 1220 1220 1830

YKD/YKH 500 L 5917 2302 1988 2379/2390 2239/2250 1900 2440 1220 1220 1830

YKD/YKH 500 H 5917 2302 1988 2433/2447 2293/2307 1900 2440 1220 1220 1830

(1) For standard unit, without accessories or options

Weights (1)

Unit size YSD/YSH YSD/YSH YSD/YSH YSD/YSH YSD/YSH YKD/YKH YKD/YKH YKD/YKH YKD/YKH

060 072 090 102 120 155 175 200 250

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 18 24 26 28 31 33 39 41 43

Start-up amps (A) 79 103 110 91 93 136 141 144 145Maximum recommended fuse size (AM) (1) (A) 32 32 40 40 40 50 50 50 63

(1) For standard unit, without accessories or options

Unit size YKD/YKH YKD/YKH YKD/YKH YKD/YKH YKD/YKH

275 300 350 400 500

Power supply (V/Ph/Hz) 400/3/50

Maximum amps (A) 74.0 83.0 89.0 111.0 129.0

Start-up amps (A) 222 231 237 259 276

Electrical data

Access control panel

xxxxxxxxxxxxxxxxxx

211

YS

D/Y

SH

-YK

D/Y

KH

211

Ro

ofto

p S

ystem

s

Page 214: Train Instrument's

Tracker™

212PROD-PRC014-E4

Customer benefits • Advanced scheduler: easy building operation• Easy diagnosis: Tracker collects and displays status of all

connected units• Remote building management: Tracker supports modem

connection

Main features• Electronic liquid crystal display• 16-key keypad operator interface measuring 30.4 cm x

24.9 cm x 5.6 cm• Power supply : 20 to 30V/50 or 60Hz/1Ph• Control and monitoring, on a serial link, of two relay

cards (12 independent contacts) plus 16 air handling sys-tems with a maximum of:- 12 Trane Voyager™ rooftops- 12 non-Trane ICS-compatible air handlers via Trane TCM- 8 VariTrac™ variable air volume systems via CCP2 with

16 zones and one blower unit each• Main information available:- Calendar (programming for seven days)- Adjustment of day/night temperature setpoints for each

zone- Definition of 24 days of holiday- Alarm diagnostic: when a temperature or system failure

is received at the Tracker™, the red LED next to the dis-play will light. The alarms can be reviewed at the dis-play. The system can even call you or a maintenanceservice.

- History of last 32 defaults, including description, date,and time

- Load shedding to limit energy consumption in an entirebuilding

- Restricted access protected by password

• Remote monitoring through a modem• Control of external equipment (lighting, building alarms,

fans)• Optimization of start-ups based on history• Easy connection to a PC using Windows® Hyperterminal

software and RJ-12 telephone cable, allowing access toall programming parameters and log reports

• Timed override: the user can place an area or unit backinto occupied setpoints for up to four hours, using thedisplay

• TZS 004 zone sensor can be used to adjust timed over-ride and local setpoints

Accessories• TCI 3 communication card for communication with a

Voyager rooftop• TCM interface card for communication with a blower or

an air handling unit• TZS zone sensors

Supervises up to 16 units

Light commercial buildingsupervisor

Tracker™

Page 215: Train Instrument's

213213PROD-PRC014-E4

VariTrac™ IIControls up to 16 zones

Variable Air Volume Systems

TZS

VariTrac™ IICCP2

Customer benefits • Individual zone temperature control: optimal building

occupant comfort• Easy installation: saving of time• Low first and maintenance costs: saving of time and

money

Main features• Brings individual temperature control to each comfort

zone in a building, while using the same constant airflowair conditioning unit.

• Varies the flow of supply air to each zone, providing theheating and cooling capacity required to match the loadin each zone.

The Varitrac™ II system is composed of the followingcomponents :- Varitrac™ II Central Control Panel (CCP2)- Main duct velocity/static pressure sensor (DVS)- Main duct supply air temperature sensor (DTS)- Main duct supply air bypass damper (BYPS)- VariTrac™ zone dampers (VADA)- Zone temperature sensor (TZS)

• CCP2 coordinates, monitors, and diagnoses for theVariTrac™ zone control system. It communicates withthe Zone Dampers to determine heating and coolingrequirements, and selects the mode and number ofstages needed.

• DVS measures the air pressure in the main supply ductand provides the information to CCP2 which controls theair bypass damper system.

• DTS monitors the temperature of the air stream in themain supply duct and provides the information to CCP2the air conditioning unit.

• BYPS is modulated by CCP2 and bypasses air from thesupply duct to prevent over-pressurization of the system.

• VADA with a UCM III control module and a ZoneTemperature Sensor (not included) measures space tem-perature and provides the proper heating or cooling bymodulating the damper. It also provides CCP2 with infor-mation about current comfort conditions in the specifiedzone (up to 16 zones with the possibility to have slavezones).

Page 216: Train Instrument's

214214PROD-PRC014-E4

Typical application

1

2

3

4

5

6

7

Control of multiple individual zones using constant volume fan air-conditioning unit

1 - Room temperature sensor (TZS)2 - Zone damper (VADA)3 - Air bypass damper (BYPS)4 - Duct temperature sensor (DTS)5 - Duct velocity sensor (DVS)6 - CCP27 - Tracker

Page 217: Train Instrument's

VADA 06 VADA 08 VADA 10 VADA 12 VADA 14 VADA 16152.4 203.2 254 304.8 355.6 406.4

At 3m/s 200 56 360 59 560 59 800 59 1090 59 1420 61

At 4m/s 270 58 470 61 740 61 1070 61 1450 61 1890 63

At 5m/s 340 60 600 64 920 64 1330 63 1820 64 2370 66

At 6m/s 400 62 710 66 1110 66 1600 66 2170 67 2850 69

At 7m/s 460 63 830 69 1300 68 1870 68 2550 69 3320 71

(1) Sound power level when damper opening creates 130 Pa pressure drop

BYPS 06 BYPS 08 BYPS 10 BYPS 12 BYPS 14 x 12 BYPS 16 X 16 BYPS 20 x 20 BYPS 30 x 20

152.4 203.2 254 304.8 355.6 x 304.8 406.4 x 406.4 508 x 508 762 x 508

At 8m/s 535 950 1490 2135 3155 4810 7515 11275

At 9m/s 595 1070 1665 2405 3550 5410 8455 12685

At 10m/s 665 1190 1855 2700 3945 6015 9395 14095

At 11m/s 730 1310 2040 2940 4340 6615 10335 15500

At 12m/s 800 1430 2230 3205 4735 7215 11275 16910

Example:

Airflow needed: Zone 1 = 1800 m3/hZone 2 = 2520 m3/hZone 3 = 1080 m3/hZone 4 = 1800 m3/h

Total airflow needed: 7200 m3/h

Minimum airflow: Zone 1 = 360 m3/hZone 2 = noneZone 3 = 430 m3/hZone 4 = 290 m3/h

Total minimum airflow: 1080 m3/h

Quick Selection

PROD-PRC014-E4

Ro

ofto

p S

ystem

sV

ariT

rac™

II

215

VADA VariTrac™ zone dampers - 1 per zoneDetermine airflow velocity (m/s) in the duct where theVariTracTM damper will be installed.Refer to the table below for air volume (m3/h) at the propervelocity and VariTacTM damper size for the zone. If the airflowexceeds the damper range, increase the damper size.Considerations: Minimum airflow should be 10% in heatingor cooling when a zone duct temperature sensor for stand-alone control is used.

BYPS bypass dampersThe bypass damper must be dimensioned so that it canabsorb 80% of the total airflow envisaged for the system,minus the sum of the minimum airflow required in eachzone. This calculation must be carried out to ensure the sys-tem operates correctly when the unit is reversible. In theevent the bypass airflow is too great to be absorbed by a single damper, a second damper can be used in parallel. Theairflow will divide up between them. The number of dampersshould not exceed three round bypass or two rectangulardampers for each CCP2.

VADA damper calculation:Zone 1 = Size 12 at 7m/sZone 2 = Size 14 at 7m/sZone 3 = Size 10 at 6m/sZone 4 = Size 12 at 7m/s

BYPS damper calculation:a) 80% of the system’s maximum airflow = 5760m3/hb) Sum of the minimum airflow in the zones = 1080m3/hc) Bypass volume = 5760-1080=4680m3/hd) According to the table, one size 14 should be selected.

Air

flo

w(m

3/h

)

Air

flo

w(m

3/h

)

Air

flo

w(m

3/h

)

Air

flo

w(m

3/h

)

Air

flo

w(m

3/h

)

Air

flo

w(m

3/h

)

So

un

dp

ow

er

(1)

dB

(A)

So

un

dp

ow

er

(1)

dB

(A)

So

un

dp

ow

er

(1)

dB

(A)

So

un

dp

ow

er

(1)

dB

(A)

So

un

dp

ow

er

(1)

dB

(A)

So

un

dp

ow

er

(1)

dB

(A)

Nominal ø

(mm)

Nominal ø

(mm)

Page 218: Train Instrument's

216PROD-PRC014-E4

SPLIT SYSTEMS AND CONDENSING UNITS

Page 219: Train Instrument's

10kW 20 30 50 100 30040 60 80 200

217PROD-PRC014-E4

SP

LIT

SY

ST

EM

S

TTK/TWK, TTA/TWA: Comfort, lightcommercial, office and restaurantapplications

SPLIT SYSTEMSAND CONDENSING UNITS

3 - 218 kW

55 218 RAUL

3 15 TTK/TWK

RAUL: Process and comfort applica-tions, food and beverage storage

19 31 TTA/TWA

Page 220: Train Instrument's

218PROD-PRC014-E4

Customer benefits• Flexibility: customized system to fit the application exact

requirements for residential and light commercialsegments

Main features - TTK/TWK outdoor unit• Designed for optimized operation with MCD/MWD

indoor units• Scroll compressor on size 530 to 060 (rotary on sizes 512

to 524)• Protection of compressor motor winding• Built-in drain pan• Aluminum fin coil with copper tubes• External sheet metal parts are galvanized and finished

with electro-static powder paint RAL 9002

Main features - MCD/MWD indoor unit• Non-painted galvanized steel casing• Aluminium fin heat exchanger with copper tubes• Self-contained condensate tray• Air inlet behind or underneath the unit• Adjustable airflow and available static pressure

Control• Wireless remote control for indoor unit

* Also available with R22 for applications outside the European Union. For information, contact your local Trane Sales Office.

TTK/TWK + MCD/MWD

Split Systems

TTK/TWK

MCD/MWD

Scroll compressor, axial fans3-15 kW*

Page 221: Train Instrument's

General data

PROD-PRC014-E4

Sp

lit S

ystem

sT

TK

/TW

K +

MC

D/M

WD

219

Unit size 512* 518* 524* 530* 530** 536* 536** 048** 060**

Cooling capacity - TTK in cooling mode (1) (kW) 3.16 4.56 6.76 8.60 8.60 9.42 9.42 13.14 14.90

Power input - TTK in cooling mode (1) (kW) 1.27 1.88 2.87 3.41 3.41 4.35 4.35 5.25 6.37

Coefficient of Performance 2.5 2.4 2.4 2.5 2.5 2.2 2.2 2.5 2.3

Heating capacity - TWK in heating mode (2) (kW) 3.38 5.11 6.87 9.57 8.94 11.20 10.52 13.55 15.38

Power input - TWK in heating mode (2) (kW) 1.15 1.84 2.35 3.54 3.09 4.25 3.87 4.64 5.44

Coefficient of Performance (2) 2.94 2.78 2.93 2.70 2.89 2.64 2.72 2.92 2.83

Refrigerant R407C

Electric Heater (3) (kW) 2 2 3 4 4 4 4 6 6

Number of compressors 1 1 1 1 1 1 1 1 1

Suction connection (brazed) (inches) 1/2 1/2 5/8 3/4 3/4 3/4 3/4 1 1/8 1 1/8

Liquid connection (inches) 1/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Fan type outdoor / indoor unit Axial / Centrifugal

Nominal Airflow (m3/h) 550 820 1100 1370 1370 1650 1650 2190 2300

Available static pressure

indoor unit (4) (Pa) 60 50 115 90 90 60 60 140 150

Number of fans outdoor unit 1 1 1 1 1 1 1 2 2

Fan speed outdoor unit (rpm) 750 780 780 900 900 900 900 850 850

Sound power level indoor unit (dB(A)) 49 52 59 63 63 63 63 70 70

Sound power level outdoor unit (dB(A)) 69 68 68 73 73 74 74 74 74

Minimum operating outdoor air temperature cooling/heating mode (°C) 10 / -5 10 / -5 10 / -5 10 / -5 10 / -5 10 / -5 10 / -5 10 / -5 10 / -5

Maximum operating outdoor air temperature cooling/heating mode (°C) 45 / 20 45 / 20 45 / 20 45 / 20 45 / 20 45 / 20 45 / 20 45 / 20 45 / 20

Nominal amps outdoor unit (A) 6.4 9.6 12.8 19.8 7.7 24.6 11.1 11.3 12.7

Start-up amps outdoor unit (A) 28.7 44.0 72.0 97.0 45.5 116.0 52.0 64.0 72.5

Nominal amps indoor unitwithout electric heater (A) 0.45 0.56 1.29 1.73 1.73 1.87 1.87 3.22 4.15

Nominal amps indoor unit with electric heater (A) 8.2 8.2 12.4 16.5 16.5 16.5 16.5 24.5 24.5

Maximum cable size (mm²) 3 x 1.52 3 x 2.52 3 x 2.52 3 x 4 4 x 2.52 3 x 6 4 x 2.52 4 x 2.52 4 x 2.52

Length outdoor unit (mm) 700 1018 1018 1018 1018 1018 1018 1018 1018

Width outdoor unit (mm) 253 360 360 360 360 360 360 360 360

Height outdoor unit (mm) 530 595 595 798 798 798 798 1254 1254

Operating weight outdoor unit (kg) 36 54 58 87 87 89 89 105 108

Length Indoor unit (mm) 578 578 578 578 578 578 578 703 703

Width Indoor unit (mm) 980 980 1090 1228 1228 1228 1228 1091 1245

Height Indoor unit (mm) 305 305 305 305 305 305 305 395 395

Operating weight Indoor unit (kg) 29.5 29.5 37 42.5 42.5 42.5 42.5 50 54.5

* Power supply 230V/1Ph/50Hz** Power supply 400V/3Ph/50Hz(1) At 27°C db /19°C wb indoor and 35°C outdoor(2) At 20°C indoor and 7°C db/6°C wb(3) For cooling only MCD only(4) At high speed, at nominal airflow, in cooling mode

Page 222: Train Instrument's

TTA/TWA

220

TTA/TWA + MWD

PROD-PRC014-E4

Customer benefits • Flexibility: customized system to fit the application exact

requirements especially for new or existing light com-mercial buildings

Main features - TTA/TWA outdoor unit• Highly reliable Scroll compressor• Robust and compact structure• Disconnect switch• Black epoxy-coated aluminium fins for aggressive

atmosphere• Electrostatic paint finish

Main features - MWD indoor unit• High external static pressure• Adjustable airflow• Cleanable filters• Removable external electrical panel

Options• Low ambient operation

Accessories - TTA/TWA outdoor unit• High and low pressure gauges

Accessories - MWD indoor unit• Electric heater (additional casing)• Hot water coil (additional casing)• Circular duct adapter plenum• EU2 filter box• EU4 filter box• Diffusers (see page 92)

Control• Digital programmable thermostats with 24 hour timer or

non-programmable thermostats• Compatible with Trane TrackerTM light commercial build-

ing supervisor and Trane VariTracTM variable air volumesystem

* Also available with R22 for applications outside the European Union. For information, contact your local Trane Sales Office.

Scroll compressors, axial fans19-31 kW*

Split systems

MWD

Page 223: Train Instrument's

xxxxxxxxxxxxxxxxxx

221

TTA

/TW

A +

MW

D

221

General data

PROD-PRC014-E4

System PerformancesUnit Size 075/075 100/100 120/125

Cooling Capacity TTA + MWD (1)(3) (kW) 19.3 26.8 31.4

Power Input TTA + MWD (kW) 7.9 10.2 13.7

Cooling Capacity TWA + MWD (1)(3) (kW) 18.8 26.3 30.7

Cooling mode power input TWA + MWD (kW) 7.8 10.1 13.6

Heating Capacity TWA + MWD (2)(3) (kW) 21.4 28.0 36.5

Heating mode power input TWA + MWD (kW) 8.2 9.4 15.0

Main Power supply (V/Ph/Hz) 400/3/50 400/3/50 400/3/50

TTA/TWAUnit Size 075 100 120

Sound Power Level (dB(A)) 76 78 82

Starting Amps (A) 101 133 142

Compressor Type Scroll Scroll Scroll

Airflow (3) (4) (m3/h) 9300 12000 17000

Length (uncrated) (mm) 1060 1060 1260

Width (uncrated) (mm) 950 950 1050

Height (uncrated) (mm) 1230 1230 1230

Weight (uncrated) (kg) 185 205 221

Refrigerant Connections Brazed Brazed Brazed

Suction line (inches) 1"1/8 1"3/8 1"3/8

Liquid line (inches) 1/2" 1/2" 1/2"

MWDUnit Size 075 100 125

Nominal airflow (m3/h) 3000 4500 4500

External static pressure MWD (3)(4) (Pa) 214 240 240

Sound power level (5) (dB(A)) 62 62 62

Length (uncrated) (mm) 970 1095 1095

Width (uncrated) (mm) 1290 1290 1290

Height (uncrated) (mm) 450 655 655

Weight (uncrated) (kg) 76 118 118

(1) At 27°C db /19°C wb indoor and 35°C outdoor(2) At 20°C indoor and 7°C db/6°C wb(3) At nominal airflow(4) High fan speed(5) At maximum airflow and 0 static pressure

Sp

lit S

ystem

s

Page 224: Train Instrument's

* Also available with R22 refrigerant. For information, contact your local Trane Sales Office.222PROD-PRC014-E4

Customer benefits • Flexibility: customized system to fit the application exact

requirements

Main Features • Scroll compressors

Hermetic, high efficiency, low vibration, low soundFull internal overheating protections

• Access panels are quickly removable using a square key• Disconnect switch • Discharge and liquid line service valves• Evaporator temperature sensor with 5 meter cable

Options• Low ambient operation (down to -18°C)• 380, 400 and 415V power voltage• Black epoxy-coated aluminium fins • Copper fins• 400 / 220V transformer for the control• Compressor sound attenuating jackets• High and low pressure gauges• Auxiliary card to validate auxiliary temperature setpoint

with a remote contact• TCI-S card to communicate with BMS • Unit without control module (special)

Control Microprocessor control module SMM (Scroll ManagerModule) with liquid crystal display operator interface con-trolling and indicating:• Evaporator temperature• Equalization of the number of starts and operating hours

of each compressor• Fan speed• Operating parameters• High pressure limitation• Low pressure protection• Short cycle protection • Remote on/off per circuit (dry contact)• Failure indication per circuit (dry contact)• History of the last 20 defaultsAccess to current settings through a window in the electrical panel

RAULScroll compressors, axial fans55-218 kW*

Condensing unit

RAUL

SMM

Page 225: Train Instrument's

General data

PROD-PRC014-E4

Unit size 190 260 300 350 400 450 500 600 700 800

Cooling capacity (1) (kW) 54.8 66.6 81.1 95.3 108.3 118.8 133.0 162.0 194.7 218.8

Power input (kW) 18.2 25.1 29.8 33.4 38.4 45.6 51.7 61.0 71.3 83.9

Coefficient of Performance 3.01 2.65 2.72 2.85 2.82 2.61 2.19 2.66 2.73 2.61

Refrigerant R407C

Number of circuits 1 1 1 2 2 2 2 2 2 2

Refrigerant holding charge per circuit (kg) 2 2 2 2 2 2 2 2 3 3

Number of compressors 2 2 2 3 3 3 4 4 6 6

Suction connection (brazed) (inches) 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8

Liquid connection (inches) 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8

Fan type Direct drive axial - vertical discharge

Airflow (m3/h) 27000 27000 25300 35900 37900 37900 54000 50700 89100 89100

Number of fans/fan motors 2 2 2 3 3 3 4 4 6 6

Fan speed (rpm) 680 680 680 680 680 680 680 680 915 915

Fan motor power (2) (kW) 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 1.88 1.88

Sound power level (dB(A)) 86 87 89 89 90 90 90 92 98 98

Minimum operating outdoor air temperature (°C) 0 (-18 with all-season operation option)

Power supply (V/Ph/Hz) 400/3/50

Nominal amps (A) 35.4 44.3 53.2 62.0 70.9 79.8 88.6 106.4 124.0 141.8

Start-up amps (A) 138 193 202 210 219 228 237 255 272 290

Maximum cable size (mm²) 35 35 35 50 50 95 95 95 150 150

(1) At Eurovent conditions: 35°C outdoor, 7°C saturated suction temperature, with R407C(2) Per fan

Sp

lit S

ystem

sR

AU

L

223

Page 226: Train Instrument's

Dimensions, weights and clearances

224224PROD-PRC014-E4

Z

X

Y

Dimensions(mm)

Shippingweight

Minimumclearances

(mm)Operating

weight Unit size

Accessfor maintenance

Unit sizeRAUL

(R407C)

Unit sizeCLCE

DX coilcoolingcapacity

Air handlingnominalairflow

Unit sizeCLCE

DX coilcoolingcapacity

Air handlingnominalairflow

X Y Z (kg) (kg) A B C D

190 2061 1021 1582 555 514 800 800 800 900

260 2061 1021 1582 625 584 800 800 800 900

300 2061 1021 1582 691 650 800 800 800 900

350 2921 1021 1582 869 810 800 800 800 900

400 2921 1021 1582 959 900 800 800 800 900

450 2921 1021 1582 985 926 800 800 800 900

500 2250 1890 1584 1123 1040 800 900 800 800

600 2250 1890 1584 1251 1168 800 900 800 800

700 3130 1973 1598 1695 1575 1000 1000 1000 1300

800 3130 1973 1598 1754 1634 1000 1000 1000 1300

Split performance data examples

Condenser entering air temperature (°C) and CLCE entering air conditions (40% humidity)

30 35

(kW) (m3/s) (kW) (m3/s)190 08-06 56.0 2.73 06-05 52.8 1.50260 09-07 68.1 3.32 06-06 64.0 1.82300 09-08 83.1 4.05 07-06 78.1 2.22350 10-08 97.4 4.75 08-06 92.0 2.62400 10-09 111.2 5.42 09-06 104.2 2.96450 11-09 122.2 5.96 09-07 114.4 3.25500 12-09 136.4 6.65 10-07 128.4 3.65600 12-11 166.1 8.10 10-08 156.6 4.45700 14-11 199.0 9.70 10-09 187.2 5.32800 16-11 224.4 10.94 11-09 211.1 6.00

• CLCE running with 100% fresh air, 30ºC, 35ºC• Leaving air temperature: 16ºC, outdoor air temperature: 30ºC, 35ºC• RAUL saturated suction temperature: 6ºC

Page 227: Train Instrument's

Power input (kW)

Performance data

PROD-PRC014-E4

Unit size

Cooling capacity

(kW)

Power input (kW)

Cooling capacity

(kW)

Power input (kW)

Cooling capacity

(kW)

Power input (kW)

Cooling capacity

(kW)

Saturated suction

temperature(°C)

Condenser entering air temperature (°C)

25 35 40 46

190 25.3 11.3 22.7 14.3 38 °C260 31.8 15.0 28.4 18.9 35 °C300 38.6 17.9 34.5 22.6 37 °C350 44.5 20.6 39.9 25.8 38 °C400 51.0 23.4 45.6 29.4 36 °C

-14 450 57.1 27.5 50.8 34.6 36 °C500 63.6 30.9 56.7 39.1 35 °C600 77.2 36.8 68.9 46.3 37 °C700 89.6 41.5 80.2 52.2 37 °C800 102.5 48.8 91.6 61.4 36 °C

190 36.7 12.0 32.8 15.0 30.6 17.0 27.7 19.7260 45.7 16.2 40.6 20.5 37.8 23.1 42 °C300 55.5 19.4 49.5 24.4 46.3 27.4 44 °C350 64.3 21.9 57.4 27.5 53.6 31.0 45 °C400 73.5 25.2 65.6 31.6 61.3 35.5 43 °C

-6 450 81.7 29.8 72.8 37.4 67.9 42.0 43 °C500 91.3 33.5 81.2 42.3 75.6 47.7 42 °C600 110.9 39.9 99.0 50.1 92.6 56.3 43 °C700 130.0 44.1 116.2 55.3 108.6 62.4 44 °C800 147.9 52.3 132.0 65.7 123.4 73.9 43 °C

190 47.2 12.5 42.1 15.8 39.3 17.8 35.7 20.6260 58.3 17.3 51.8 21.8 48.2 24.5 43.6 28.2300 70.8 20.8 63.1 26.0 59.0 29.2 53.6 33.4350 82.4 23.1 73.6 29.0 68.7 32.6 62.5 37.6400 93.9 26.7 83.9 33.5 78.4 37.6 71.3 43.2

0 450 104.1 31.8 92.6 39.9 86.3 44.7 78.3 51.2500 116.5 35.8 103.4 45.1 96.2 50.7 45 °C600 141.5 42.6 126.2 53.5 117.8 59.9 107.1 68.6700 167.0 46.3 149.5 58.2 139.9 65.4 127.4 75.4800 189.4 55.4 169.1 69.5 158.0 78.0 143.8 89.5

190 59.1 13.2 52.9 16.6 49.5 18.6 45.1 21.5260 72.4 18.6 64.4 23.3 59.9 26.1 54.2 29.8300 88.0 22.4 78.4 27.9 73.2 31.2 66.5 35.5350 102.9 24.5 92.0 30.7 86.0 34.4 78.2 39.5400 117.1 28.5 104.6 35.7 97.8 40.0 89.0 45.7

6 450 129.2 34.2 114.9 42.7 107.0 47.7 97.0 54.4500 144.8 38.4 128.5 48.2 119.6 54.0 108.2 61.7600 175.9 45.9 156.6 57.3 146.1 64.0 132.7 72.9700 209.5 48.9 187.8 61.3 175.9 68.9 160.5 79.1800 236.6 59.1 211.3 73.8 197.4 82.6 179.7 94.3

= Maximum ambient limit (°C)

Sp

lit S

ystem

sR

AU

L

225

Page 228: Train Instrument's

226PROD-PRC014-E4

CLOSE CONTROL UNITS

Page 229: Train Instrument's

5kW 10 15 30 60 8020 40 50 70

227

CL

OS

E C

ON

TR

OL

UN

ITS

Light commercial, office, restaurant,and industrial applications

CLOSE CONTROL UNITS5 - 63 kW

5 Jupiter

22Mercury

PROD-PRC014-E4

20

81

Page 230: Train Instrument's

228

Jupiter

PROD-PRC014-E4

Customer benefits • Compact design: space savings in plant rooms• Accuracy: accurate temperature and humidity control for

any size of applications

Main features• Designed for environments in which high-tech

equipment is the predominant heat source and comfortapplications (offices…)

• Front access for total unit maintenance• Downflow discharge and upflow discharge

configurations• Scroll compressors• Double inlet galvanised steel centrifugal fans with

forward curved blades• Inner and outer door panels providing security, continual

operation, and reduced sound levels duringmaintenance

Options• Electric reheat• Enhanced electric reheat• Hot water reheat• High pressure centrifugal fans• Electrode boiler humidifier• High efficiency filters• Fresh air module with filter• Air suction from the front, rear or base (upflow

configuration only)

Accessories• Fire and/or smoke detector• Water leak detector with one sensor• Dirty filter alarm (differential pressure switch)• Temperature and humidity sensor• External sensors for high ambient temperature and

humidity alarm signals• Base frames and plenums (intake or discharge) for easier

integration

ControlMicroprocessor control module• mP20 with 4x20 alphanumeric display showing status

information and allowing alarm message and historymanagement

• mP3 with LCD symbol display showing statusinformation and alarm history to regulate airtemperature and humidity

Communication protocols for interfacing with most BMSLAN card for run/standby operation (mP20 only)

Technology and comfort applications5-20 kW*

Close control units

Chilled water units

JDCC DownflowJUCC Upflow

Air-cooled direct expansion units

JDAC DownflowJUAC Upflow

Water-cooled direct expansion units

JDWC DownflowJUWC Upflow

* Available in certain countries. For information, contact your local Trane Sales Office.

Jupiter

Page 231: Train Instrument's

General data

PROD-PRC014-E4

Clo

se co

ntro

l u

nit

s

Jup

iter

229

Air-cooled direct expansion units (JDAC/JUAC)

0115 0125 0133 0135 0150 0160

Cooling capacity (1) (kW) 5.7 7.7 9.3 12.0 15.4 18.0Sensible cooling capacity (1) (kW) 5.2 6.1 7.5 10.4 14.9 16.0

Refrigerant R407CNumber of circuits/compressors 1/1

Airflow (1) (m3/h) 1584 1584 1944 3024 4968 4968

External static pressure (Pa) 10

Height (mm) 1740

Width (mm) 550 550 700 850 1200 1200

Depth (mm) 450

Weight (kg) 130 130 150 185 260 260

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, chilled water temperature=7/12°C, ethylene glycol 0%

Water-cooled direct expansion units (JDWC/JUWC)

0115 0125 0133 0135 0150 0160

Cooling capacity (1) (kW) 5.4 7.3 8.9 11.4 14.8 17.2Sensible cooling capacity (1) (kW) 5.1 5.9 7.3 10.2 14.8 16.0

Refrigerant R407CNumber of compressors/circuits 1/1

Airflow (1) (m3/h) 1580 1580 1950 3020 4940 4940

External static pressure (Pa) 10

Height (mm) 1740

Width (mm) 550 550 700 850 1200 1200

Depth (mm) 450

Weight (kg) 135 135 155 190 265 265

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, chilled water temperature=7/12°C, ethylene glycol 0%

Chilled water units (JDCC/JUCC)

0020 0025 0030 0040 0060

Cooling capacity (1) (kW) 6.5 8.4 9.3 11.8 19.2Sensible coolingcapacity (1) (kW) 5.9 7.5 8.1 11.0 17.8

Airflow (1) (m3/h) 1584 1944 2052 3024 4968

External static pressure (Pa) 10

Height (mm) 1740

Width (mm) 550 700 850 850 1200

Depth (mm) 450

Weight (kg) 100 115 150 155 210

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, chilled water temperature=7/12°C, ethylene glycol 0%

Page 232: Train Instrument's

* Available in certain countries. For information, contact your local Trane Sales Office.230

Mercury

PROD-PRC014-E4

Customer benefits • Flexibility: customized system to fit the application's

exact requirements• Accuracy: accurate temperature and humidity control for

demanding applications• Noise level: a level of acoustic comfort unmatched in the

market place

Main features• Designed for environments in which high-tech

equipment is the predominant heat source• Front access for total unit maintenance• Downflow discharge and upflow discharge

configurations• Scroll compressors• Double inlet galvanised steel centrifugal fans with

forward curved blades• Inner and outer door panels providing security, continual

operation, and reduced sound levels duringmaintenance

Options• Electric reheat• Enhanced electric reheat• Hot water reheat• High pressure centrifugal fans with backward curved

blades• Electrode boiler humidifier• Air filters• Fresh air module• Air suction from the front, rear or base (upflow

configuration only)• Front discharge floor stand• Different acoustic linings for the panels of the unit

casing

Accessories• Condensate drain pump• Humidifier condensate drain pump• External sensors for high ambient temperature and

humidity alarm signals• Fire and/or smoke detector• Water leak detector• Base frames and plenums (intake or discharge) for easier

integration

ControlmP40 microprocessor control module with easy-to-useLCD display• temperature and humidity control• complete alarm signalling system• recording of all alarms• programming of automatic restart after power is

restored• remote unit switch on/off• setting of the electronic thermostat valve with signalling

of any irregularities• possibility of communicating with a supervision system

using the RS485 serial board (optional)• Override function

High tech applications22-63 kW*

Close control units

Chilled water units

EDCC DownflowEUCC Upflow

Air-cooled direct expansion units

EDAC DownflowEUAC Upflow

Water-cooled direct expansion units

EDWC DownflowEUWC Upflow

Energy saving units

EDEB DownflowEUEB Upflow

Twin cool units

EDTB/EDDB DownflowEUTB/EUDB Upflow

Mercury

Page 233: Train Instrument's

General data

PROD-PRC014-E4

Air-cooled direct expansion units (EDAC/EUAC)

Water-cooled direct expansion units (EDWC/EUWC)

Unit size 1105 1106 1107 2207 1108 2208 1113 2213 1114 2214 2216 4216 2217 4217 2218 4218

Cooling capacity (1) (kW) 22.0 22.9 26.3 27.8 30.0 32.1 34.6 33.5 42.3 37.4 50.5 50.3 57.4 57.1 64.3 63.1

Sensible cooling

capacity (1) (kW) 20.1 20.5 26.3 27.8 30.0 32.1 34.6 33.5 39.4 37.4 50.5 50.3 57.4 57.1 60.7 60.1

Refrigerant R407C

Number of circuits/

compressors 1/1 1/1 1/1 2/2 1/1 2/2 1/1 2/2 1/1 2/2 2/2 2/4 2/2 2/4 2/2 2/4

Airflow (1) (m3/h) 5600 5600 9740 9740 9740 9740 10790 10790 10790 10790 16730 16730 16730 16730 16730 16730

External static pressure (Pa) 20

Height (mm) 1980

Width (mm) 1100 1100 1510 1510 1510 1510 1750 1750 1750 1750 2400 2400 2400 2400 2400 2400

Depth (mm) 750

Weight (kg) 255 260 330 385 335 395 450 460 455 465 615 620 625 620 625 630

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, condensing temperature=48°C

Chilled water units (EDCC/EUCC)

Unit size 0010 0013 0014 0018 0024 0026

Cooling capacity (1) (kW) 28.1 33.3 39.3 53.4 69.5 81.0

Sensible cooling

capacity (1) (kW) 23.8 28.7 33.2 45.2 59.9 68.7

Airflow (1) (m3/h) 7410 10170 10060 14050 22280 21870

External static pressure (Pa) 20

Height (mm) 1980

Width (mm) 1100 1510 1510 1750 2400 2400

Depth (mm) 750

Weight (kg) 245 345 350 365 455 465

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, chilled water temperature=7/12°C, ethylene glycol 0%

Twin cool and energy saving units (EDEB/EUEB/EDTB/EUTB/EDDB/EUDB)

Unit size 1105 1106 1107 2207 1108 2208 1113 2213 1114 2214 2216 4216 2217 4217 2218 4218

Cooling capacity -

Direct expansion mode (1) (kW) 22.6 23.4 26.5 28.0 30.3 32.4 35.5 34.3 42.7 38.4 51.1 50.9 58.1 57.8 64.1 63.1

Sensible cooling capacity -

Direct expansion mode (1) (kW) 22.6 23.4 26.5 28.0 30.3 32.4 35.5 34.3 42.7 38.4 51.1 50.9 58.1 57.8 64.1 63.1Cooling capacity Chilled Water mode (2) (kW) 20.8 20.8 32.5 32.5 32.5 32.5 37.1 37.1 37.1 37.1 50.8 50.8 50.8 50.8 50.8 50.8Sensible cooling capacity Chilled Water mode (2) (kW) 18.5 18.5 27.8 27.8 27.8 27.8 32.5 32.5 32.5 32.5 46.0 46.0 46.0 46.0 46.0 46.0Number of circuits/compressors 1/1 1/1 1/1 2/2 1/1 2/2 1/1 2/2 1/1 2/2 2/2 2/4 2/2 2/4 2/2 2/4

Airflow (1) (m3/h) 7200 7200 10340 10340 10340 10340 12340 12340 12340 12340 17870 17870 17870 17870 17870 17870

External static pressure (Pa) 20

Height (mm) 1980

Width (mm) 1100 1100 1510 1510 1510 1510 1750 1750 1750 1750 2400 2400 2400 2400 2400 2400

Depth (mm) 750

Weight (kg) 255 260 330 385 335 395 450 460 455 465 615 620 625 620 625 630

Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24°C/50%, ESP=20Pa, condensing temperature=48°C(2) Based on chilled water temperature=7/12°C

Clo

se co

ntro

l u

nit

s

Mer

cury

231

Page 234: Train Instrument's

232PROD-PRC014-E4

VARIABLE FREQUENCY DRIVES

Page 235: Train Instrument's

0,5kW 1 10 100 300 40050 200 250 350

233PROD-PRC014-E4

VA

RIA

BL

E F

RE

QU

EN

CY

DR

IVE

S

Office buildings, shopping centers,banks, hospitals, hotels, schools,“industrial” process cooling....

VARIABLE FREQUENCY DRIVES0.37 - 400 kW

18

1.1 400

TR1 2800 Series

TR1 6000 Series

0.37

Page 236: Train Instrument's

234PROD-PRC014-E4

0.37 - 400 kW applications

Variable Frequency Drives

VarioTrane TR1

Customer benefits• Designed to operate with fans and pumps to achieve

lower energy consumption• Reliability: low cost of ownership and risk reduction• High performance: low energy consumption• Comfort: optimal building occupant comfort

Main features of TR1 6000 Series• Offers a total BMS integrated capability, delivering

optimum system cost savings for new and retrofitinstallations on pumps and fans

• Integrated EMC filters to meet EN55011 Class 1A (150M)and 1B (50M)

• Integrated DC coil harmonic filters• HVAC designed alphanumeric keypad and software

functionality• Double feedback or double zone advanced built in PID

controller• Detachable upload/download keypad with H/O/A·

Monitors and displays kW/hr, running hours, A, V, Hz, kW• 8 x DI, 3 x AI, 2 x AO/DO, 2 x relay output• RS485 with embedded Modbus RTU and N2

Options TR1 6000• Cascade controller option for 5 x pump/fan• Lonworks option board - free topology, including

memory option• DeviceNet option board - including memory option• Profibus option board - including memory option• Cascade controller - application open• Relay card option to add 4 more relays• LCP remote mounting kit for control panel mounting

IP00 - IP20 and IP 54 versions

• IP20 terminal cover• IP20 bottom cover• IP21 top cover (sizes 6016-6042-6052-6072)• LC filter module• BacNet gateway (external module)

Main features of TR1 2800 Series• Compact and highly functional• Integrated EMC filter EN55011 Class 1A, option for 1B

external mount filter• Integrated DC coil harmonic filter• Numerical keypad with option for remote mount

alphanumeric keypad• HVAC application software functionality including a built-

in PID controller• Monitors and displays kW/hr, running hours, A, V, Hz, kW• 5 x DI, 2 x AI, 1 x AO/DO, 1 x relay output, thermistor

input• Drive version for Profibus and DeviceNet

Options TR1 2800• Cable for LCP, 3 m• LCP control unit• Remote mount kit IP00/20, including 3m cable• RFI 1B-filter• IT mains filter• IP21 top cover• NEMA 1 terminal cover• RFI 1B + LC filter• Motor choke IP10• BacNet gateway (external module)

6000 Series2800 Series

Page 237: Train Instrument's

Trane can also offer Softstarter and Integrated Drive-Motor Solutions.

Contact your local sales office for more information.

Selection data

PROD-PRC014-E4

Motorshaft

power(kW)

Voltage

3 x 380V

3 x 480V

Varia

ble

Freq

uen

cy D

riv

es

TR

1

235

Motor shaft

power(kW)

TR1 6000 Series

Voltage Enclosure HxWxD Voltage Enclosure HxWxD Voltage Enclosure HxWxD

3 x 200V IP20 (mm) IP54 (mm) 3 x 380V IP20 (mm) IP54 (mm) 3 x 600V IP20 (mm)

1.1 TR1 6002 395x220x160 460x282x195 TR1 6002 395x220x160 460x282x195 TR1 6002 395x220x200

1.5 TR1 6003 395x220x160 460x282x195 TR1 6003 395x220x160 460x282x195 TR1 6003 395x220x200

2.2 TR1 6004 395x220x200 530x282x195 TR1 6004 395x220x160 460x282x195 TR1 6004 395x220x200

3 TR1 6005 395x220x200 530x282x195 TR1 6005 395x220x160 460x282x195 TR1 6005 395x220x200

4 TR1 6006 560x242x260 810x350x280 TR1 6006 395x220x200 530x282x195 TR1 6006 395x220x200

5.5 TR1 6008 560x242x260 810x350x280 TR1 6008 395x220x200 530x282x195 TR1 6008 395x220x200

7.5 TR1 6011 560x242x260 810x350x280 TR1 6011 395x220x200 530x282x195 TR1 6011 395x220x200

11 TR1 6016 700x242x260 940x400x280 TR1 6016 560x242x260 810x350x280 TR1 6016 560x242x260

15 TR1 6022 700x242x260 940x400x280 TR1 6022 560x242x260 810x350x280 TR1 6022 560x242x260

18.5 TR1 6027 800x308x296 940x400x280 TR1 6027 560x242x260 810x350x280 TR1 6027 560x242x260

22 TR1 6032 800x308x296 940x400x280 TR1 6032 700x242x260 810x350x280 TR1 6032 700x242x260

30 TR1 6042 954x370x335 937x495x421 TR1 6042 700x242x260 940x400x280 TR1 6042 700x242x260

37 TR1 6052 954x370x335 937x495x421 TR1 6052 800x308x296 940x400x280 TR1 6052 800x308x296

45 TR1 6062 954x370x335 937x495x421 TR1 6062 800x308x296 940x400x280 TR1 6062 800x308x296

55 TR1 6072 800x308x296 940x400x280

75 TR1 6100 800x370x335 940x400x360

90 TR1 6122 800x370x335 940x400x360

110 TR1 6150 1201x420x373 1201x420x373

132 TR1 6172 1201x420x373 1201x420x373

160 TR1 6222 1584x420x373 1584x420x373

200 TR1 6272 1584x420x373 1584x420x373

250 TR1 6350 1584x420x373 1584x420x373

315 TR1 6400 2010x1200x600 2010x1200x600

355 TR1 6500 2010x1200x600 2010x1200x600

400 TR1 6550 2010x1200x600 2010x1200x600

TR1 2800 Series

Voltage Enclosure HxWxD Voltage Enclosure HxWxD Enclosure HxWxD

1 x 220V IP20 (mm) 3 x 220V IP20 (mm) IP20 (mm)

0.37 TR1 2803 200x75x168 TR1 2803 200x75x168

0.55 TR1 2805 200x75x168 TR1 2805 200x75x168 TR1 2805 200x75x168

0.75 TR1 2807 200x75x168 TR1 2807 200x75x168 TR1 2807 200x75x168

1.1 TR1 2811 200x75x168 TR1 2811 200x75x168 TR1 2811 200x75x168

1.5 TR1 2815 200x75x168 TR1 2815 200x75x168 TR1 2815 200x75x168

2.2 TR1 2822 267.5x90x168 TR1 2822 267.5x90x168

3 TR1 2830 267.5x90x168

3.7 TR1 2840 267.5x140x168

4 TR1 2840 267.5x90x168

5.5 TR1 2865 267.5x140x168

7.5 TR1 2875 267.5x140x168

11 TR1 2880 505x200x244

15 TR1 2881 505x200x244

18.5 TR1 2882 505x200x244

Other enclosures available upon request

Page 238: Train Instrument's

236PROD-PRC014-E4

SERVICE SOLUTIONS

Page 239: Train Instrument's

237PROD-PRC014-E4

SE

RV

ICE

SO

LU

TIO

NS

Comprehensive programsEvoluTraneTrane Select Contracts

Trane delivers comprehensive service solutions.

Process: # 1780© American Standard Inc. 2005

PROPERTY OF THE TRANE COMPANY - TO BE USED ONLY BY AUTHORISED EMPLOYEE IN CONJUNCTION WITK VSF - FOR INTERNAL USE ONLY

1

3

2

14

4

5

6

7

8

9

10

11

12

13

SAFETY TQC WORK VERIFY

MARK AND DISCONNECT THE WIRING

CONFIRM OIL HAS BEEN DRAINED. ALL REFRIGERANT HAS�BEEN RECLAIMED AND THE CHILLER IS AT ATMOSPHERICPRESSURE

REMOVE PAINT FROM SECTION(S) OF PIPE WORK TO BE CUT

CUT ALL PIPES AS REQUIRED

USE PIPE CUTTER

MARK TOP ON THE OIL PUMP COVER PLATE

REMOVE 2 BOLTS AND INSERT GUIDE PINS

UNBOLT AND REMOVE ALL REMAINING COVER PLATE BOLTS

SLIDE COVER PLATE BACK OUT

PREPARE FOR MINOR OIL SPILL

REMOVE 2 LONG BOLTS

REMOVE OIL PUMP

CLEAN OIL SUMP ANS ASSOCIATED PIPE WORK WITH SAFETYSOLVENT AND LINT FREE GAS

USE SAFETY EQUIPMENT

1

3

47

6 8 9 10 11 12

13

14

As your Service Partner,Trane:• Has a reliable network of people who have the expertise

and the experience you need• Allows you to reach the best cost of ownership

• Offers simple, transparent, and consistent services

throughout the Europe, Middle-East, Africa, and Indiaregions

• Brings you energy saving solutions through plannedmaintenance

• Helps your installation be environmentally responsible

Start-up

All Trane engineers and technicians are experts in refriger-ation and air-conditioning control. Trane will take theextra step beyond installation to perfectly adapt theequipment to its environment, by taking control of andseeing to an efficient and high-performance start-up.

Service product rangeChemical analysisEddy current tube analysisVibration analysisRemanufactured compressorsEquipment enhancementParts and supplies

Service is not only about providing you with spare parts. At Trane, we are committed

to providing you with service solutions that are efficient and reliable, just like our

equipment.

Page 240: Train Instrument's

EvoluTrane

238PROD-PRC014-E4

Whatever segment your business is in, whether yourinstallation is for comfort cooling or industrial cooling,your company chose the system that best correspondedto its needs at that time, based on the products and services that existed on the market.Since then, your needs may have evolved. Your coolingsystem may be oversized, undersized or may not be oper-ating at optimum efficiency. Your equipment may be at theend of its lifecycle. Continuously changing legislation maymean that your installation no longer complies with envi-ronmental or energy consumption standards.

Customer benefits• Improved equipment operation• Reduced cost of ownership• Ensures that your system complies to the most recent

regulations

Main featuresWith customer input via an individual interview and a sitevisit, Trane• Detects areas for productivity improvements or how to

take into account the evolution of your cooling systemor business needs

• Detects areas for economy improvements or how replac-ing the equipment can have an advantageous financialimpact

• Evaluates installation conformity to new environmentaland health regulations

Based on the analysis of the gathered information, Tranespecialists help you find solutions that can be best adapt-ed to your current needs and your future needs. Trane willrecommend a solution and also offer flexible financingoptions for your cooling system investment.

Optimization and upgradesolution programs

Page 241: Train Instrument's

239239PROD-PRC014-E4

Trane SelectContracts

Comprehensivemaintenance programs

Customer benefits Best cost of ownership

• Planned maintenance ensures your HVAC system runs attop efficiency, providing up to 12% energy savings.

• Your equipment will receive regular inspection, preven-tive maintenance and proper calibration. Any potentialproblem will be corrected before anyone in your build-ing becomes aware of it.

• In choosing your level of coverage, you know exactlywhat services and parts are covered. There are no sur-prises when it comes to expenses.

Total peace of mind

• Trane looks out for your needs.

Main featuresWith our extended service plans, Trane is your ideal service solutions provider to protect your HVAC installa-tion investment. Trane Select Contracts are tailored to fityour HVAC system needs and business requirements.They offer four different levels of coverage - from preven-tive maintenance plans to comprehensive maintenance.

As your preferred service partner, we look out for yourneeds and your total peace of mind.

24hrs/day, 7 days/week

Maintenance

Parts coverage

Lifecycle management

Servic

e so

lutio

ns

Pro

gra

ms

239

Page 242: Train Instrument's

240

Chemical analysis

PROD-PRC014-E4

The Trane Chemical Laboratory has developed thespecialized expertise to analyze various types of fluidsfound in your HVAC installation. Having regular analyses done by experienced serviceengineers helps reduce maintenance costs and guaranteeequipment efficiency and reliability. Problems can befound and fixed before they become major.• Fast delivery of results• Graphs of the current test data with past test data for

easy comparison• Past and present interpretations and service

recommendations

Compressor oil analysis• All compressor makes and types (scroll, reciprocating,

centrifugal and helical-rotary)• Helps extend the life of the existing charge and maintain

compressor efficiency• Allows compressor repairs to be scheduled to reduce

downtime• Identify problems without tearing down the compressor·• Reduce problems of used oil disposal• Lower refrigerant emissions• Standard testing includes : ferrous index, non-ferrous

index, particle count, spectrometry, wear level evolutionchart, contamination index, total presence of moisture,contamination level evolution chart, chemical index,dielectric test, viscosity at 40°C, viscosity index,chemistry level evolution chart, TAN (total acid number)test

Refrigerant analysis• Detects contamination levels. When contaminant levels

fall outside acceptable ranges, corrective actions arerecommended.

• All types of refrigerants• Helps extend the life of the existing charge

Lithium bromide analysis• Detects substance imbalance• Corrective actions are recommended if necessary.• Helps extend the life of the existing charge

Chemical analysis

Predictive maintenance

Page 243: Train Instrument's

2424

241241PROD-PRC014-E4

Eddy current tubeanalysis

Heat exchanger tube testing

Predictive maintenance

Customer benefits• Improved equipment operation and reliability• Extended equipment life• Reduced operating costs• Reduced risk of costly breakdowns• Reduced downtime

Main featuresThe condition of the tubes in a heat exchanger has adirect impact on the efficiency of your chiller. Dependingon its size, a heat exchanger contains hundreds or thou-sands tubes, all undergoing mechanical stress and chemi-cal corrosion. Tubes are therefore critical to chiller per-formance, and yet standard maintenance techniques cancheck most everything except these tubes.

Equipped with the latest technological tools, Trane candetect, locate and record internal and external corrosion,deposits, wear or cracking before their consequences startto damage your installation.

This analysis results in a detailed report containing all therecordings, photographs of defective zones, and mostimportantly, recommendations as to the technical andpractical actions required to resolve the situation.

Servic

e so

lutio

ns

Pro

du

cts

241

Page 244: Train Instrument's

242

Vibrationanalysis

PROD-PRC014-E4

Every piece of HVAC equipment with rotating componentshas its own, distinct vibration "signature". If a problemdevelops, this vibration signature changes, and the way itchanges can be used as an accurate means of identifyingpotential problems (bearing wear, shaft balancing default,screw gearing default…). The savings in major repairs aresubstantial (up to 50% savings on compressor replace-ment cost).

Customer benefits• Reduced risk of costly breakdowns• Improved energy performance• Fast diagnosis of existing mechanical defects• Increased equipment safety• Extended equipment life• Contained noise pollution• Better scheduling of planned maintenance

Trane vibration experts know baseline vibration data ofeach mobile component and define alarm levels according to the application. Vibration analyses can beintegrated into any Trane maintenance contract or ondemand.

Vibration analysis

Predictive maintenance

Phot

ogra

phic

cre

dits

: Em

erso

n.

Page 245: Train Instrument's

2424

243243PROD-PRC014-E4

Remanufacturedcompressors

Remanufactured compressors

Reciprocating and helical-rotary

A Trane remanufactured compressor can be an economi-cally-effective solution when a compressor replacement isneeded. In addition to replacement situations, Trane also thinksahead and anticipates preventive maintenance on com-pressors which have already clocked hundreds of runninghours. This service starts by dismantling the compressor,cleaning and sandblasting to eliminate any trace of car-bon residues, acid, metal debris or rust.Each sub-assembly undergoes rigorous control and partswhich have been subjected to extensive wear arereplaced.In both cases, the result is a reliable compressor that willcontinue running at its optimum performance.

Customer benefits• Improved equipment operation and reliability• Fast delivery due to large stock• Reduced downtime

Main features• A complete range of remanufactured compressors is

held in stock - reciprocating and helical-rotary compres-sors

• Sold with the same warranty as a new compressor

Servic

e so

lutio

ns

Pro

du

cts

243

Page 246: Train Instrument's

244

Equipmentenhancement

PROD-PRC014-E4

Your chiller controls may have become obsolete, trouble-some and/or inefficient. You are making other payback-related investments in the chiller plant. You want the samecontrols on your existing chillers as on your new chillers.In these cases, Trane's Tracer™ CH531 controls can replacean existing chiller's temperature and safety controls.

Customer benefits• reduced operating costs

- CH531 eliminates the existing controller's 3° setpointerror

- CH531's automatic chilled water reset raises chilledwater temperatures at low-load times

- CH531 soft loads the chiller, reducing building startupdemand

• improved equipment reliability and maintainability

- CH531 is based on Adaptive Control, keeping the chilleronline where other controls would have shut the chillerdown

- CH531 allows automatic restart without operator inter-vention after power failures

- Advanced controls protect your chiller's motor frompower line faults

- Clear language diagnostics and messages allow opera-tors to quickly make decisions to get the chiller backonline.

Main featuresAdaptive Control™ microprocessor-based controlfeaturing:• Easy-to-use DynaView operator interface panel• Evaporator leaving water temperature• Chilled water reset based on return water temperature• Evaporator refrigerant temperature limit• Smart short-cycling protection• Smart auto-restart• Ice-making control (optional)• Free cooling (optional)• Bearing temperature (optional)• Heat recovery (optional)• Pump start/stop (optional)

Tracer™ CH531 retrofit

Control upgrading

Tracer™ CH531

Page 247: Train Instrument's

2424

245245PROD-PRC014-E4

Parts andsupplies

Parts and supplies

Customer benefits• Guarantee of parts that meet the specifications of the

original part• Quick and efficient ordering and delivery service• Reduced equipment downtime

Main features• Large inventories of repair and replacement parts for

many types of HVAC equipment• Original parts conforming to your equipment's original

specifications for guaranteed fit and optimal performance

• Strategically located parts distribution centers meaningshorter delivery times and lower shipping costs

• High-performance infrastructure to find, deliver, andeven install the needed part with a minimum downtime

• Parts availability in real time

Servic

e so

lutio

ns

Pro

du

cts

245

Page 248: Train Instrument's

Notes

Page 249: Train Instrument's

American Standard Europe BVBARegistered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium

Literature Order Number PROD-PRC014-E4

Date 0406

Supersedes PROD-PRC013-E4_0205

Stocking Location France

Trane has a policy of continuous product and product data improvement and reserves the right to changedesign and specifications without notice.

> Select your countrytrane.com

[email protected]

Austria: .............................................(+43) 2236.378.400

Belgium: ..............................................(+32) 2.672.23.73

Czech Republic: ................................(+420) 296.337.233

Egypt:.....................................................(+20) 2.2641328

France: ..............................................(+33) 4.72.52.28.50

Germany: ...........................................(+49) 203.768.04.0

Greece: .............................................(+30) 210.811.22.00

Hungary: ...............................................(+36) 23.422.572

India: ..................................................(+91) 22.56778679

Ireland: ...............................................(+353) 1.460.60.30

Israel: ..................................................(+972) 3.942.0802

Italy: .....................................................(+39) 02.903.35.1

Kuwait:...................................................(+965) 482.6207

Lebanon: ...............................................(+961) 1.510.922

Netherlands:......................................(+31) 35.603.93.00

Poland: ...............................................(+48) 22.434.77.00

Portugal: ......................................(+351) 210.303.500/01

Romania: ............................................(+40) 21.410.87.33

Russia: ................................................(+7) 095.742.0009

Saudi Arabia:......................................(+971) 4.346.0080

Spain: .................................................(+34) 91.428.82.00

Sweden:.............................................(+46) 8.556.134.50

Switzerland: .......................................(+41) 22.301.11.20

Turkey:..............................................(+90) 212.284.25.68

United Arab Emirates: .......................(+971) 4.346.0090

United Kingdom: .............................(+44) 1256.306.000

EUR Regional Headquarters: .............(+32) 2.663.98.00

MAIR Regional Headquarters: ..........(+971) 4.346.0080

With 130 locations in EMAIR (Europe, Middle East, Africa and India Region), Trane has one of the most extended sales and services network staffed by a team of the industry's most experienced sales engineering resources, controls and service engineers and technicians. All are networked to provide uniform local support capabilities such as engineering expertise, application assistance, services, parts and on-site maintenance, repair and operation of your HVAC systems. They have the knowledge and resources to assist system designers, consulting engineers, contractors and building owners in creating and maintaining safe, comfortable and efficient indoor environments for new and existing buildings and industrial processes. Contact Trane today. Don't lose time.

CONTACT US