Source changeover systemsCompact NSX100-630, Compact NS630b-1600,

Compact INS/INV, Masterpact

Low Voltage

Catalogue 2013

Page 2: Tranferencia Datasheet SCHNEIDER
Page 3: Tranferencia Datasheet SCHNEIDER

I

Efficient energy

management and

continuity of service with

source-changeover system

To ensure continuity of service for critical applications, LV electrical installations need to be connected to at least two independent power sources:

* The replacement source (R) can be: a second power source (with possibly different

characteristics from the normal source) or an electrical generator

1A normal

source (N)

2And a replacement

source (R)*used to supply energy to the installation when the normal source unavailable, or, for instance, when its quality and/or availability is no longer guaranteed.

The source-changeover

system switches the

load (partly or fully) between these

two sources.

A few basics on source-changeover systems> A source-changeover system can be

automated to manage

transfers according

to external

conditions.

> Switching from a main power source to a replacement source can be performed

either manually or

automatically.

> A source-changeover system comprises

circuit breakers,

switch-disconnectors

or contactors.

313E.indb 1 09/04/2013 13:04:06

Page 4: Tranferencia Datasheet SCHNEIDER

II

to switch the load to meet your needs

Automatic source-changeover system(or ATSE: Automatic Transfer Switching Equipment)

An automatic controller may be added to a remote-operated source-changeover system. It is possible to automatically control source transfer according to programmed (dedicated controllers) or programmable (PLC) operating modes. These solutions ensure optimum energy management.

3

ApplicationsCommercial and service sector (operating rooms in hospitals, safety systems for buildings, computer rooms for banks and insurance companies, lighting and emergency lighting systems in malls, etc.), industry and

infrastructure.

System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. A mechanical interlocking system protects against electrical malfunctions or incorrect manual operations, with an automatic control system (dedicated controllers or PLC).

1Manual source-changeover system (or MTSE: Manual Transfer Switching Equipment)

The simplest way to switch the load. It is controlled manually by an operator.

The time required to switch from the ‘N’ source to ‘R’ source can vary.

ApplicationsBuildings and infrastructure where the need for continuity of service is significant but not a priority: offices, small and medium-sized businesses.

System2 or 3 mechanically interlocked manually-operated circuit breakers or 2 switch-disconnectors.

3ways

Remote-operated source-changeover system(or RTSE: Remote Transfer Switching Equipment)

The most commonly used system for devices with high ratings. No direct human

intervention is required. Source-changeover is controlled electrically.

2

System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. In addition, a mechanical interlocking system protects against electrical malfunctions or incorrect manual operations.

ApplicationsIndustry (assembly lines, engine rooms on ships, critical auxiliaries in thermal powerstations, etc.); Infrastructure (port and railway installations, runway lighting systems, control systems on military sites, etc.).

313E.indb 2 09/04/2013 13:04:06

Page 5: Tranferencia Datasheet SCHNEIDER

III

> MTSE range

Compact INSFrom 40 A to 630 A

> RTSE range

Compact NSX From 100 A to 630 A

Masterpact NT / NW From 630 A to 6300 A

Whatever the system,

you benefit from our expertise!

Our expertise and support come together

with the source-changeover system you

choose for your LV electrical installation.

With Compact INS, Compact NSX

and Masterpact NT and NW, we offer

a complete range of solutions, designed

around key values:

Maximum continuity

of service> Energy availability is ensured whatever

the external requirements (e.g. high power demand).

> Maintenance and replacement of the sources (N or R) can be done with no interruption of service.

You can maintain a continuous level of service and customer satisfaction.

Optimized energy

management> Transfer the load to a replacement source

according to external requirements.> Manage power sources according to power

quality and power costs.> Perform system regulation.> Switch to an emergency replacement source.You are no longer dependent on your power supply (and supplier)!

Simplicity and reliability> Simple installation on LV switchboard.> Optimized size of the switchboard.> System based on pre-tested components.

> Compliance with IEC 60947-6-1.

Maximum safetyFor LV electrical installations where safety and continuity of service are critical for people and/or equipment such as hospitals, airports, banks, malls, etc.

> ATSE range

UA Controller Compact NSX From 100 A to 630 A

313E.indb 3 09/04/2013 13:04:07

Page 6: Tranferencia Datasheet SCHNEIDER

IV

A source-changeover system is indispensable for applications that need a continuous supply of electric power (hospitals, airports, banks, government facilities, etc.). But a source-changeover system is also suitable for all LV electrical installations exposed to:> Nominal voltage loss or dip (when there

is high demand for electric power)

> Unpredictable power quality

> Frequent power cuts.

For critical applications in particular

For all others

in general

These factors, and many others, can damage the continuity of service of your electrical installation.For infrastructure managers, a source-changeover system gives direct economic benefi ts: it is possible to select your source based on power cost. In this case, the replacement source (R) is used as an alternative, more economical source.

Managing energy

effi ciently

Power Cost

Safety

313E.indb 4 09/04/2013 13:04:11

Page 7: Tranferencia Datasheet SCHNEIDER

1

Source-changeover systems

Compact NSX100-630,

Compact NS630b-1600,

Compact INS/INV, Masterpact

General content

Presentation 2

Functions and characteristics A-1

Dimensions B-1

Electrical diagrams C-1

Catalogue numbers

and order forms D-1

313E.indb 1 09/04/2013 13:04:11

Page 8: Tranferencia Datasheet SCHNEIDER

Presentation For maximum continuity of service...

Incoming feeders and main LV switchboards

CurrentsFrom 630 to 6300 A.

Power distribution

PD

390385_

SE

_R

_35.e

ps

CurrentsFrom 250 to 3200 A.

Loads

PB

111556.e

ps

CurrentsFrom 40 to 400 A.

Db101543.e

ps

PB

105109.e

ps

2

313E.indb 2 09/04/2013 13:04:13

Page 9: Tranferencia Datasheet SCHNEIDER

1 normal source 1 replacement source

2 sources with coupler on busbars

2 normal sources1 replacement source

Db101538.e

ps

Db101539.e

ps

Db101540.e

ps

QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 0

1 0 1 0 1 1 1 0

0 1 1 1 0 0 0 1

0 1 1 1 0 0

1 0 0 (1) 0 1 0

0 0 1 (1)

(1) possible by forcing operation.

Generator or permanent source

Db101541.e

ps QN QR Typical applications:

b continuous production processes

b operating rooms

b computer rooms...

0 0

1 0

0 1

Generator or permanent source

Generator or permanent source

Db101541.e

ps

Db101544.e

ps QN QR Typical applications:

b large electrical installations (e.g. airports)

b refrigeration units

b special electricity tariffs

b pumping stations...

0 0

1 0

0 1

... in a wide range of applications

3

313E.indb 3 09/04/2013 13:04:14

Page 10: Tranferencia Datasheet SCHNEIDER

Ecodial software is dedicated to LV electrical installation

calculation in accordance with the IEC60364

international standard or national standards.

This 4th generation, "Ecodial Advance Calculation 4",

offers a new ergonomic and new features:

p operating mode that allows easy calculation in case of installation with different type of sources

(parallel transformers, back-up generators…)

p discrimination analysis associating curves checking and discrimination tables

p direct access to protection settings including residual current protections

p easy selection of alternate solutions or manual selection of a product.

Ecodial

TOOLS

181E6000.indd 4 09/04/2013 14:05:54

Page 11: Tranferencia Datasheet SCHNEIDER

A-1

Source-changeover systems

Compact NSX100-630,

Compact NS630b-1600,

Compact INS/INV, Masterpact

Functions and characteristics

Presentation 2

Overview of solutionsManual source-changeover systems Compact INS/INV 40 to 630 A, Compact NSX100/630 A-2

Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-3

Remote-operated source-changeover systems Compact NSX100/630, Compact NS630b/1600 A A-4

Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A A-5

Manual source-changeover systemsPossible combinations A-6

Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW A-10

Mechanical interlocking Compact NS or Masterpact NT/NW A-11

General characteristics Compact NSX A-12

General characteristics Compact NS, Masterpact NT/NW A-13

Mech. and elect. durability A-14

Connection and insulation accessories for Compact NSX and INS y 630 A A-15

Electrical interlocking A-16

Associated controllersController selection A-18

Controller installation A-19

BA controller A-20

BA controller, Operating sequences A-21

UA controller A-22

UA controller, Operating sequences, Forced operation mode A-23

UA controller, Operating sequences, Special-tariff mode A-24

UA controller, Operating sequences , Test mode and automatic operation A-25

Operating sequences IVE unit A-26

COM communications option A-28

Dimensions B-1Electrical diagrams C-1Catalogue numbers and order forms D-1

313E.indb 1 09/04/2013 13:04:14

Page 12: Tranferencia Datasheet SCHNEIDER

Functions

and characteristics

Range Compact CompactModels INS40 to INS80

INS100 to INS160INS250 to INS630INV250 to INV630

NSX100 to NSX250NSX400 to NSX630

Rating (A) 40 to 160 100 to 630 100 to 630

Type of device Switch-disconnectors with extended handles

Switch-disconnectors N/H/L circuit breakersNA switch-disconnectors

Manual source-changeover systemsInterlocking via toggles

DB

126589.e

ps

Db101545.e

ps

2 devices side-by-side. 3 devices side-by-side.

Interlocking via rotary handles

DB

126590.e

ps

N2 .4

Db101546.e

ps

ONI

OOFF

ONI

OOFF

Db101548.e

ps

2 devices side-by-side.

Interlocking via keylocks with captive keys

DB

126588.e

ps

Db101549.e

ps

Db101550.e

ps

A number of different devices.

Interlocking on a base plate

Db101551.e

ps

2 devices side-by-side.

Complete source-changeover assemblies

DB

126586.e

ps

2 devices side-by-side.

Overview of solutionsManual source-changeover systems

Compact INS/INV 40 to 630 A, Compact

NSX100/630

A-2

313E.indb 2 09/04/2013 13:04:16

Page 13: Tranferencia Datasheet SCHNEIDER

Range Compact MasterpactModels NS630b to NS1600 NT06 to NT16 NW08 to NW63

Rating (A) 630 to 1600 630 to 1600 800 to 6300

Type of device N/H/L circuit breakersNA switch-disconnectors

H1/L1 circuit breakersHA switch-disconnectors

N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

Manual source-changeover systemsInterlocking via extended rotary handles

DB

126590.e

ps

Db101553.e

ps

2 devices side-by-side.

Interlocking via keylocks with captive keys

DB

126588.e

ps

Db101554.e

ps

Opush OFF

Ipush ON

O OFF

discharged

Opush OFF

Ipush ON

O OFF

discharged

Db101555.e

ps

Db101556.e

ps

A number of different devices.

Mechanical interlocking using connecting rods

DB

126585.e

ps

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

(1)

Db101558.e

ps

Db101559.e

ps

2 devices one above the other.

Mechanical interlocking using cables

DB

126584.e

ps

Db101560.e

ps

(1)

(2)

Db101561.e

ps

Db101562.e

ps

2 or 3 devices one above the other.

DB

126583.e

ps

2 or 3 devices side-by-side.

For this case and other cases, please consult us

DB

126580.e

ps

(1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) page A-13.

Manual source-changeover systems

Compact NS and Masterpact NT/NW

630 A to 6300 A

A-3

313E.indb 3 09/04/2013 13:04:19

Page 14: Tranferencia Datasheet SCHNEIDER

Functions

and characteristics

Range CompactModels NSX100 to NSX630 NS630b to NS1600

Rating (A) 100 to 630 630 to 1600

Type of device N/H/L circuit breakersNA switch-disconnectors

N/H/L circuit breakersNA switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking on base plate + electrical interlocking

Db101563.e

ps

2 electrically-operated devices side-by-side combined with an electrical interlocking system.

Mechanical interlocking using connecting rods + electrical interlocking

DB

126585.e

ps

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

2 electrically-operated devices one above the other combined with an electrical interlocking system.

Mechanical interlocking using cables + electrical interlocking

DB

126581.e

ps

Db101560.e

ps

(1)

2 electrically-operated devices one above the other combined with an electrical interlocking system.

DB

126582.e

ps

2 electrically-operated devices side-by-side combined with an electrical interlocking system.

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

126581.e

ps The automatic controller

operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

404439.e

ps

BA controller

DB

126582.e

ps

DB

404440.e

ps

UA and UA150 controller

(1) page A-13.

Overview of solutionsRemote-operated source-changeover

systems Compact NSX100/630,

Compact NS630b/1600 A

A-4

313E.indb 4 09/04/2013 13:04:20

Page 15: Tranferencia Datasheet SCHNEIDER

Range MasterpactModels NT06 to NT16 NW08 to NW63

Rating (A) 630 to 1600 800 to 6300

Type of device H1/L1 circuit breakersHA switch-disconnectors

N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking using connecting rods + electrical interlocking

DB

126585.e

ps

Db101558.e

ps

Db101559.e

ps

2 electrically-operated devices side-by-side combined with an electrical interlocking system.

Mechanical interlocking using cables + electrical interlocking

DB

126584.e

ps

Db101561.e

ps

Db101562.e

ps

2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1).

DB

126583.e

ps

2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1).

(2)

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

126581.e

ps The automatic controller

operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

404439.e

ps

BA controller

DB

126582.e

ps

DB

404440.e

ps

UA and UA150 controller

(1) Three devices with Masterpact NW only.(2) page A-13.For other cases, please consult us.

Remote-operated source-changeover

systems Masterpact NT/NW

630 A to 6300 A

A-5

313E.indb 5 09/04/2013 13:04:21

Page 16: Tranferencia Datasheet SCHNEIDER

Functions

and characteristics

A manual source-changeover system can be installed

on two or three manually-operated and mechanically

interlocked circuit breakers or switch-disconnectors.

Interlocks prevent connection to both sources at the

same time, even momentarily.

All possibilities for manual source-changeover systems

Type of device Type of interlocking for two devices

Completeassembly

Keylock Direct rotary handle

Extendedrotary handle

Compact switch-disconnectors

INS40 to INS160 b

INS250-100 to INS630 b b b r b r

INV100 to 630 b b r b r r

INS/INV630b to 2500 b

Legend:r Possible but visible break function disabled.r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Type of device Type of interlocking for two devices

Toggle Keylock Direct rotary handle

Extended rotary handle

On base plate (toggle or direct extended rotary control)

On base plate(motor mechanism)

NSX100 to 250 b b b b p b b b b b b b b b b

NSX400 to NS630 b b b b p b b b b b b b b b b

NSX100 to 630 b b p b b p b b p b b b p b b b p

NS630b to 1600 with rotary handle

b b p b b b b

Legend:b Fixed devices only.b Fixed or withdrawable devices.bp With NSX400/630 rotary handle interlocking system.p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.p Devices equipped with rotary handles.

Type of device

Keylock Cable-type,2 devices side-by-side

Cable-type,3 devices side-by-side

Cable-type,2 devices one above the other

Cable-type,3 devices one above another

Rod-type,3 devices one above another

NS630b to 1600 b b b b

NT06 to 16 b b b b

NW08 to 63 b b b b b b

NT06 to NW63 b b b

Manual source-changeover systemsPossible combinations

A-6

313E.indb 6 09/04/2013 13:04:21

Page 17: Tranferencia Datasheet SCHNEIDER

Complete source-changeover assembly for two switch-disconnectors

All possibilities for manual source-changeover systems

These assemblies provide an easy way to implement source changeover functions

with:

b a single 3-position rotary handle that controls the two switch-disconnectors

(Normal source ON, OFF, Replacement source ON)

b a smaller size, taking up less room in the switchboard.A complete source changeover assembly can be ordered with a single catalogue number.

“Normal N” “Replacement” R

INS250-100 INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630

INS250-100

Ratings 100 A b

INS250-160

Ratings 160 A b

INS200-200

Ratings 200 A b

INS250-250

Ratings 250 A b

INS320

Ratings 320 A b

INS400

Ratings 400 A b

INS500

Ratings 500 A b

INS630

Ratings 630 A b

Interlocking of two or three toggle-controlled devices

Possible combinations of “Normal” and “Replacement” source circuit breakers

Db101566.e

ps Two devices can be interlocked using this system. Two identical interlocking systems

can be used to interlock three devices installed side by side, in which case one

device is in the ON position and the two others are in the OFF position. Devices must

The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).

Two interlocking system models are available for:

b Compact NSX100 to 250

b Compact NSX400 to 630.

“Normal N” “Replacement” R

NSX100 NSX160 NSX250 NSX400 NSX630

NSX100

Ratings 16... 100 A b b b b b

NSX160

Ratings 80...160 A b b b b b

NSX250

Ratings 125...250 A b b b b b

NSX400

Ratings 150... 400 A b b b b b

NSX630

Ratings 630 A b b b b b

Possible combinations

313E.indb 7 09/04/2013 13:04:21

Page 18: Tranferencia Datasheet SCHNEIDER

Functions

and characteristics

Interlocking of a number of devices using keylocks (captive keys)

Combination of “Normal” and “Replacement” devices

Db101569.e

ps All Compact and Masterpact circuit breakers and Compact switch-disconnectors

from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.

Interlocking is based on two identical keylocks with a single key and a keylock

adapter (different for each device). This solution enables interlocking between two

devices that are physically distant or that have very different characteristics, for

example between a low and a medium-voltage device, or between Compact NSX

circuit breakers and switch-disconnectors.

A system of wall-mounted captive key boxes makes possible a large number of

combinations between many devices.

Interlocking of two devices with rotary handles

Possible combinations of “Normal” and “Replacement” source circuit breakers

ON

I

OOFF

ON

I

OOFF

Db101568.e

ps The direct or extended rotary handles are padlocked with the devices in the OFF

position. The mechanism prevents simultaneous closing of the devices, but allows

them to be opened.

“Normal N” “Replacement” R

Compact NSX100/630 (1) NSX100 NSX160 NSX250 NSX400 NSX630

NSX100

Ratings 16... 100 A b b b v v

NSX160

Ratings 80...160 A b b b v v

NSX250

Ratings 125...250 A b b b v v

NSX400

Ratings 160... 400 A v v v b b

NSX630

Ratings 630 A v v v b b

v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking system.

“Normal N” “Replacement” R

Compact NS630b/1600 (1) NS630b NS800 NS1000 NS1200 NS1600

NS630b

Ratings 250... 630 A b b b b b

NS800

Ratings 320... 800 A b b b b b

NS1000

Ratings 400... 1000 A b b b b b

NS1200

Ratings 480... 1200 A b b b b b

NS1600

Ratings 640... 1600 A b b b b b

(1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630 interlocking system.

Manual source-changeover

systemsPossible combinations

A-8

313E.indb 8 09/04/2013 13:04:22

Page 19: Tranferencia Datasheet SCHNEIDER

Interlocking of two devices with rotary handlesPossible combinations of “Normal” and “Replacement” source switch-disconnectors

The direct or extended rotary handles are padlocked with the devices in the OFF

position. The mechanism prevents simultaneous closing of the devices, but allows

them to be opened.

“Normal N” “Replacement” R

Compact INS (1) INS40 INS63 INS80 INS100 INS125 INS160

INS40

Ratings 40 A b b b b b b

INS63

Ratings 63 A b b b b b b

INS80

Ratings 80 A b b b b b b

INS100

Ratings 100 A b b b b b b

INS125

Ratings 125 A b b b b b b

INS160

Ratings 160 A b b b b b b

(1) With extended rotary handles only.(2)

“Normal N” “Replacement” R

Compact INS /INV (2) INS250-100/INV100

INS250-160/INV160

INS250-200/INV200

INS250-250/INV250

INS320/INV320

INS400/INV400

INS500/INV500

INS630/INV630

INS250-100/INV100

Ratings 100 A b b b b v v v

INS250-160/INV160

Ratings 160 A b b b b

INS250-200/INV200

Ratings 200 A b b b b

INS250-250/INV250

Ratings 250 A b b b b v v

INS320/INV320

Ratings 320 A v v b b b b

INS400/INV400

Ratings 400 A b b b b

INS500/INV500

Ratings 500 A b b b b

INS630/INV630

Ratings 630 A v v b b b b

v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Interlocking of two devices on a base platePossible combinations of Compact NSX “Normal” and “Replacement” source circuit breakers

DB

414891.e

ps A base plate is available for mechanical interlocking of two manually-operated

Compact NSX100 to 630 circuit breakers or switch-disconnectors.

“Normal N” “Replacement” RNSX100 NSX160 NSX250 NSX400 NSX630

NSX100

Ratings 16... 100 A b b b b b

NSX160

Ratings 80... 160 A b b b b b

NSX250

Ratings 125... 250 A b b b b b

NSX400

Ratings 150... 400 A b b b b b

NSX630

Ratings 630 A b b b b b

Interlocking of a number of devices using keylocks (captive keys)Combination of Masterpact devices

Db101903.e

ps Interlocking uses two identical keylocks with a single key. This solution enables

different characteristics.

Possible combinations

A-9

313E.indb 9 09/04/2013 13:04:23

Page 20: Tranferencia Datasheet SCHNEIDER

A-10

Functions

and characteristics

Mechanical interlocking of two or three devices is used

to create a remote-operated source-changeover

system. A basic mechanical interlocking system

enhances the reliability of system operation.

Interlocking of two Compact NSX100 to 630 devices using a

base plateA base plate designed for two Compact circuit breakers can be installed horizontally

or vertically on a mounting rail. Interlocking is carried out on the base plate by a

mechanism located behind the breakers. Access to the circuit breaker controls and

without earth-leakage protection or measurement modules. The base plate and the

circuit breakers are supplied separately.

b Base plate for Compact NSX100 to 250 devicesThis base plate is intended for two Compact NSX100 to 250 devices.

b Base plate for Compact NSX400 to 630 devicesThis base plate is intended for two Compact NSX400 to 630 devices. It may also be

Compact NSX400 or 630 device.

An adapter kit is required for plug-in versions of the Compact NSX100 to 250

devices.

equipped with spreaders.

PB

105106_

50.e

ps

Possible combinations of “Normal” and “Replacement” Compact NSX source circuit breakers

Interlocking of two electrically-operated Compact NSX circuit breakers using a base plate. “Normal N” “Replacement” R

NSX100 NSX160 NSX250 NSX400 NSX630

NSX100

Ratings 12,5... 100 A b b b b b

NSX160

Ratings 12,5...160 A b b b b b

NSX250

Ratings 12,5...250 A b b b b b

NSX400

Ratings 160... 400 A b b b b b

NSX630

Ratings 250... 630 A b b b b b

DB

126268.e

ps

Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rods

2 withdrawable/drawout devices).

Combinations are possible between Compact NS630b to NS1600 devices and

between Masterpact NT and Masterpact NW devices.

InstallationThis function requires:

bdisconnector

b a set of connecting rods with no-slip adjustments.

disconnectors are supplied separately, ready for assembly by the customer.

Possible combinations of “Normal” and “Replacement” source circuit breakers

“Normal N” “Replacement” R

NS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600

Ratings 250... 1600 A b

Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

NT06 to NT16

Ratings 250... 1600 A b b b

NW08 to NW40

Ratings 320... 4000 A b b b

NW40b to NW63

Ratings 4000... 6300 A b b b

Remote-operated source-changeover systems Mechanical interlocking Compact NSX,

Compact NS or Masterpact NT/NW

313E.indb 10 09/04/2013 13:04:24

Page 21: Tranferencia Datasheet SCHNEIDER

A-11

PB

100842_

68_

SE

.eps

Interlocking of two Compact NS630b to 1600 or two Masterpact

NT/NW or up to three Masterpact NW devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or

side-by-side.

different ratings and sizes.

Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW)

This function requires:

b b a set of cables with no-slip adjustments.

Interlocking between three devices (Masterpact NW only)

This function requires:

bof each device

b two or three sets of cables with no-slip adjustments.

Installation

are supplied separately, ready for assembly by the customer.

Installation conditions for cable interlocking systems:

b cable length: 2.5 m

b radius of curvature: 100 mm

b maximum number of curves: 3.

Interlocking of two Masterpact circuit breakers using cables.

Possible combinations of “Normal” and “Replacement” source circuit breakers

“Normal N” “Replacement” R

NS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600

Ratings 250... 1600 A b

NT06 to NT16

Ratings 250... 1600 A b b b

NW08 to NW40

Ratings 320... 4000 A b b b

NW40b to NW63

Ratings 4000... 6300 A b b b

It is not possible to combine Compact NS630b to 1600 and Masterpact NT

(or Masterpact NW) devices.

All combinations of two Masterpact NT and Masterpact NW devices are possible,

whatever the rating or size of the devices.

Possible combinations of three device

“Normal N” “Replacement” R

NS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600

Ratings 250... 1600 A

NT06 to NT16

Ratings 250... 1600 A

NW08 to NW40

Ratings 320... 4000 A b b

NW40b to NW63

Ratings 4000... 6300 A b b

Only Masterpact NW may be used for three-device combinations.

Types of mechanical interlocking and combinations

See page A-4 to page A-9.

Mechanical interlocking

Compact NS or Masterpact NT/NW

313E.indb 11 09/04/2013 13:04:25

Page 22: Tranferencia Datasheet SCHNEIDER

A-12

Functions

and characteristics

Range Compact NSXTypes of devices NSX100 to NSX250 NSX400 to NSX630

Types of circuit breakers N / H / L N / H / L

Switch-disconnector version NA NA

Mixing possibilities all devices all devices

NS100 to NS250 NS100 to NS630

N/H/L/NA N/H/L/NA

Electrical characteristicsRating 15 to 250 A 15 to 630 A

Insulating voltage Ui (V AC)

Positive break indication b b

Number of poles(N and R devices must have the same number of poles)

3, 4

Electrical durability See page A-14

Operating temperature

Control characteristicsControl voltage AC 48 V - 50 Hz 48 V - 50 Hz

110/130, 220/240, 380/440 V - 50/60 Hz 110/130, 220/240, 380/440 V - 50/60 Hz

DC 24-250 V 24-250 V

Maximum consumption AC 500 VA 500 VA

DC 500 W 500 W

Minimum switching time 800 ms 800 ms

InterlockingMechanical (see page A-10)

Electrical by diagram (without IVE) b b

with IVE unit b b

auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE

Protection and measurementOverload protection long time b b

Short-circuit protection short time b b

instantaneous b b

Earth-fault protection b

Zone selective interlocking (ZSI) b

Earth-leakage protection by Vigi module b b

by control unit

by add-on Vigirex relay b b

Current measurements

Voltage, frequency, power measurements, etc.

Indication and control auxiliariesAvailable auxiliary indication contacts OF + SD (+ SDV) 3 OF + SD (+ SDV)

Voltage releases MX shunt b b

MN undervoltage b b

Voltage presence indicator b b

Voltage transformer b b

Ammeter module b b

Insulation monitoring module b b

Source-changeover controllerWith permanent replacement source b BA controller

With standby generator set b UA controller

Remote communication via busDevice status indications

Device remote control

Transmission of settings b b

b b

Transmission of measurements b b

Installation and connectionFixed front connected

Fixed rear connected b (long rear connections) b (long rear connections)

Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)

Installation and connection accessoriesDownstream coupling accessory b b

Bare-cable connectors b b

Terminal extensions b b

Terminal shields and inter-phase barriers b

Locking by padlock b b

by keylock b b

Front panel escutcheons b b

Remote-operated source-changeover systems0 General characteristics

Compact NSX

313E.indb 12 09/04/2013 13:04:25

Page 23: Tranferencia Datasheet SCHNEIDER

A-13

Compact NS MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63

N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1

NA NA / HA / HF NA / HA / HF

all devices all mixing possibilities all mixing possibilities

NS630b to 1600

N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HF

250 to 1600 A 600 to 1600 A 800 to 6300 A

1000 1000

b b

3, 4

See page A-14

48 to 415 V - 50/60 Hz

440 V - 60 Hz

24-250 V 24-250 V 24-250 V

180 VA 180 VA 180 VA

180 W 180 W 180 W

800 ms 800 ms 800 ms

b b b

b only with UA or BA only with UA or BA

1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF

b b b

b b b

b b b

b b b

b b b

b b b

b b b

b b b

b b

2 OF + SD 2 OF + SD 2 OF + SD

b b b

b b b

b b

b b

b b

b b

b BA controller

b UA controller

b b b

b b b

b b b

b b b

b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal)

b (drawout) b (drawout) b (drawout)

b

b

b b b

b b b

b b b

General characteristics

Compact NS, Masterpact NT/NW

313E.indb 13 09/04/2013 13:04:26

Page 24: Tranferencia Datasheet SCHNEIDER

A-14

Functions

and characteristics

Compact INS switch-disconnectors

INS250-100 INS250-160 INS250-200 INS250Number of poles 3, 4 3, 4 3, 4 3, 4

Conventional thermal current (A) lth at 60 °C 100 160 200 250

Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

440-480 V 100 100 160 160 200 200 250 250

660-690 V 100 100 160 160 200 200 250 250

Durability (category A) (O

N-C

R-O

R-C

N cycles)

Mechanical 15000 15000 15000 15000

Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

440-480 V 1500 1500 1500 1500 1500 1500 1500 1500

660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

INS320 INS400 INS500 INS630Number of poles 3, 4 3, 4 3, 4 3, 4

Conventional thermal current (A) lth at 60 °C 320 400 500 630

Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

440-480 V 320 320 400 400 500 500 630 630

660-690 V 320 320 400 400 500 500 630 630

Durability (category A) (O

N-C

R-O

R-C

N cycles)

Mechanical 10000 10000 10000 10000

Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

440-480 V 1500 1500 1500 1500 1500 1500 1500 1500

660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

Compact NSX100-630, Compact NS630b-1600

NSX100-250 NSX400-630 NS630b-

NS1600Number of poles 3, 4 3, 4 3, 4

Rated current In (A) 100 to 250 400 to 630 630 to 1600

Mechanical durability(O

N-C

R-O

R-C

N cycles)

20000 - 40000 - 50000

15000 8000

Electrical durability at In (O

N-C

R-O

R-C

N cycles)

for y 440 V and 480 V NEMA (2)

10000 - 20000 - 30000

4000 - 6000 2000

Electrical durability at In (O

N-C

R-O

R-C

N cycles)

for U = 500 V to 690 V (2)

2000 - 3000 1500

Masterpact NT06-NT16/NW08-NW63 (1)

NT06-NT10

NT12-NT16

NW08-NW16

NW20 NW25-NW40

NW50-NW63

Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4

Rated current In (A) 630 to 1600

1250 to 1600

800 to 1600

2000 2500 to 4000

5000 to 6300

Mechanical durability(O

N-C

R-O

R-C

N cycles)

8000 8000 10000 10000 10000 5000

Electrical durability at In (O

N-C

R-O

R-C

N cycles)

for y 440 V and 480 V NEMA (2)

6000 6000 NT16:3000

10000 8000 5000 1500

Electrical durability at In (O

N-C

R-O

R-C

N cycles)

for U = 500 V to 690 V (2)

3000 2000NT16:1000

10000 6000 2500 1500

(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.

Note:ON: opening of Normal sourceCR: closing of Replacement sourceOR: opening of Replacement sourceCN: closing of Normal source

Remote-operated source-changeover systems Mech. and elect. durability Compact INS,

Compact NSX, NS, Masterpact NT/NW

313E.indb 14 09/04/2013 13:04:26

Page 25: Tranferencia Datasheet SCHNEIDER

A-15

1

2

3

4

DB

413568.e

ps

Downstream coupling accessory

It may be used to couple two circuit breakers (Compact NSX100 to 630) or switch-

disconnectors (Compact INS/INV100 to 630) of the same size.

Pitch between outgoing terminals:

b Compact INS250 and INV100 to 250: 35 mm

b Compact INS/INV320 to 630: 45 mm

b Compact NSX100 to 250: 35 mm

b Compact NSX400 to 630: 45 mm.

For Compact NSX circuit breakers, the downstream coupling accessory can be used

only with .

Connection and insulation accessories

accessories as the circuit breakers and switch-disconnectors.

Possible uses Downstream couplingPossiblemounting

Outgoing pitch (mm)

Manual source-changeover systems

INS250 (100 to 250 A) with rotary handle b 35

NSX100/250 with rotary handle b 35

NSX100/250 on base plate with toggle control b 35

INS400/630 (320 to 630 A) with rotary handle b 45

NSX400/630 with rotary handle b 45

1 Short terminal shields2 Terminals3 Interphase barriers4 Long terminal shields

NSX400/630 on base plate with toggle control b 45

Complete source-changeover assembly

INS250 (100 to 250 A) b 35

INS400/630 (320 to 630 A) b 45

Remote-operated source-changeover systems

NSX100/250 b 35

NSX400/630 b 45

Connection and insulation accessories

for Compact NSX and INS y 630 A

313E.indb 15 09/04/2013 13:04:27

Page 26: Tranferencia Datasheet SCHNEIDER

A-16

Functions

and characteristics

Electrical interlocking is used with a mechanical

interlocking system.

An automatic controller may be added to take into

account information from the distribution system.

Morover, the relays controlling the closing order to the “Normal” and “Replacement” circuit-breakers must be mechanically and/or electrically interlocked to prevent them from giving simultaneous closing commands.

Electrical interlocking is carried out by an electrical control device.

For Compact NSX up to 630 A, electrical interlocking is implemented by the IVE unit

integrating control circuits and an external terminal block in accordance with the

pages C-5 to C-4 of the chapter “Electric diagrams” of this catalogue.

The integrated control circuits implement the time delays required for correct source

transfer.

For Compact NS630b to 1600 and Masterpact, this function can be implemented

in one of two ways:

b using the IVE unit

b by an electrician based on the diagrams in accordance with the pages C-9 to C-14

of the chapter “Electric diagrams” of this catalogue.

Characteristics of the IVE unit b External connection terminal block:

v inputs: circuit breaker control signals

v outputs: status of the SDE contacts on the “Normal” and “Replacement” source

circuit breakers.

b 2 connectors for the two “Normal” and “Replacement” source circuit breakers:

v inputs:

- status of the OF contacts on each circuit breaker (ON or OFF)

- status of the SDE contacts on the “Normal” and “Replacement” source circuit breakers

v outputs: power supply for operating mechanisms.

b Control voltage:

v 24 to 250 V DC

v 48 to 415 V 50/60 Hz - 440 V 60 Hz.

The IVE unit control voltage must be same as that of the circuit breaker operating

mechanisms.

IVE unit.

Necessary equipment

For Compact NSX100 to 630, each circuit breaker must be equipped with: b a motor mechanism

b an OF contact

b an SDE contact.

The components are supplied ready for assembly and the circuit breakers prewired.

For Compact NS630b to 1600, each circuit breaker must be equipped with:

b a motor mechanism

b an available OF contact

b a CE connected-position contact (carriage switch) on withdrawable circuit breakers

b an SDE contact.

For Masterpact NT and NW, each circuit breaker must be equipped with:

b a remote-operation system made up of:

v MCH gear motor

v MX or MN opening release

v XF closing release

v PF “ready to close” contact

b an available OF contact

b one to three CE connected-position contacts (carriage switches) on drawout

circuit breakers (depending on the installation).

Remote-operated source-changeover systemsElectrical interlocking

313E.indb 16 09/04/2013 13:04:27

Page 27: Tranferencia Datasheet SCHNEIDER

Compact NS, Masterpact NT and NW Types of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.

2 devices

QN QR Compact NSX100 to 630:

0 0 b electrical interlocking without emergency power off (EPO) auxiliaries: 512011771 0

v with EPO by MN 512011780 1

v with EPO by MX 51201179

Compact NS630b to 1600:

b electrical interlocking with lockout after fault:

v permanent replacement source (with IVE) 51201183

v with EPO by MX (with IVE) 51201184

v with EPO by MN (with IVE) 51201185

Masterpact NT and NW:

b electrical interlocking with lockout after fault:

v permanent replacement source (with IVE) 51201142

v with EPO by MX (with IVE) 51201143

v with EPO by MN (with IVE) 51201144

b automatic control with lockout after fault:

v permanent replacement source (with IVE) 51156904

v engine generator set (with IVE) 51156905

b BA/UA controller (with IVE) 51156903

Masterpact NW onlyTypes of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.

3 devices: 2 “Normal” sources and 1 “Replacement” source

QN1 QN2 QR b electrical interlocking:

0 0 0 v without lockout after fault 51156906

1 1 0 v with lockout after fault 51156907

0 0 1

3 devices: 2 “Normal” sources and 1 “Replacement” source with source selection

QN1 QN2 QR b automatic control with engine generator set:

0 0 0 v without lockout after fault (with MN) 51156908

1 0 0 v with lockout after fault (with MN) 51156909

0 0 1

1 1 0

0 1 0

3 devices: 3 sources, only one device

QS1 QS2 QS3 b electrical interlocking:

0 0 0 v without lockout after fault 51156910

1 0 0 v with lockout after fault 51156911

0 1 0

0 0 1

3 devices: 2 sources + 1 coupling

QS1 QC QS2 b electrical interlocking:

0 0 0 v without lockout after fault 51156912

1 0 1 v with lockout after fault 51156913

1 1 0 b automatic control with lockout after fault 51156914

0 1 1

1 0 0 (1)

0 0 1 (1)

(1) possible by forcing operation

“Lockout after fault” option. This option makes it necessary to manually reset the device following fault tripping.

Standard configurations

313E.indb 17 09/04/2013 13:04:28

Page 28: Tranferencia Datasheet SCHNEIDER

A-18

Functions

and characteristics

By combining a remote-operated source-changeover

system with an integrated BA or UA automatic

controller, it is possible to automatically control source

transfer according to user-selected sequences.

These controllers can be used on source-changeover

systems comprising 2 circuit breakers.

For source-changeover systems comprising 3 circuit

breakers, the automatic control diagram must be

prepared by the installer as a complement to to

diagrams provided in the “electrical diagrams” section

of this catalogue.

Controller BA UACompatible circuit breakers All Compact NS,

Compact NSX and Masterpact circuit breakers

4-position switch

Automatic operation b b

Forced operation on “Normal” source b b

Forced operation on “Replacement” source b b

Stop (both “Normal” and “Replacement” sources off) b b

Automatic operation

Monitoring of the “Normal” source and automatic transfer b b

Generator set startup control b

Delayed shutdown (adjustable) of generator set b

Load shedding and reconnection of non-priority circuits b

Transfer to the “Replacement” source if one of the phases of the “Normal” phase is absent

b

Test

By opening the P25M circuit breaker supplying the controller b

DB

403809.e

ps

By pressing the test button on the front of the controller b

Indications

Circuit breaker status indication on the front of the controller: on, off, fault trip

b b

Automatic mode indicating contact b b

Other functions

Selection of type of “Normal” source (single-phase or three-phase) (1)

b

Voluntary transfer to “Replacement” source (e.g. energy management commands)

b b

During peak-tariff periods (energy management commands) forced operation on “Normal” sourceif “Replacement” source not operational

b

Additional contact (not part of controller). Transfer to “Replacement” source only if contact is closed(e.g. used to test the frequency of UR).

b b

BA controller. Setting of maximum startup time for the replacement source b

Options

DB

403810.e

ps

Communication option

Power supply

Control voltages (2) 110 V b b

220 to 240 V 50/60 Hz b b

380 to 415 V 50/60 Hz and 440 V 60 Hz

b b

Operating thresholds

Undervoltage 0.35 Un y voltage y b b

Phase failure 0.5 Un y voltage y b

Voltage presence voltage u 0.85 Un b b

IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)

Front IP40 b b

Side IP30 b b

Connectors IP20 b b

UA controller. Front b b

Characteristics of output contacts (dry, volt-free contacts)

Rated thermal current (A) 8

Minimum load 10 mA at 12 V

Output contacts:

Position of the Auto/Stop switch b b

Load shedding and reconnection order b

Generator set start order. b

AC DC

AC12 AC13 AC14 AC15 DC12 DC13

Operational current (A) 24 V 8 5 5 8 2

48 V 8 5 5 2 -

110 V 8 6 4 4 0.6 -

220/240 V 8 6 4 3 - -

250 V - - - - 0.4 -

380/415 V 5 - - - - -

440 V 4 - - - - -

660/690 V - - - - - -

(1) For example, 220 V single-phase or 220 V three-phase.(2) The controller is powered by the ACP control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can be used directly for the power supply. If not, an isolation transformer must be used.

Associated controllersController selection

313E.indb 18 09/04/2013 13:04:28

Page 29: Tranferencia Datasheet SCHNEIDER

A-19

ACP control plateThe control plate provides in a single unit:

b protection for the BA or UA controller with two highly limiting P25M circuit breakers

b control of circuit-breaker ON and OFF functions via two relay contactors

b connection of the circuit breakers to the BA or UA controller via a built-in terminal

block.

Control voltages

b 110 V 50/60 Hz.

b 220 to 240 V 50/60 Hz.

b 380 to 415 V 50/60 Hz and 440 V 60 Hz.

The same voltage must be used for the ACP control plate, the controller and the

circuit breaker operating mechanisms.

InstallationConnection between the ACP control plate and the IVE unit may use:

b wiring done by the installer

b prefabricated wiring (optional).

Installation of the BA and UA controllersThe BA and UA controllers may be installed in one of two manners:

b directly mounted on the ACP control plate

b mounted on the front panel of the switchboard

b if the length of the connection between the controller and the control plate (ACP) is

less than or equal to 1 m, the connecting cable ref. 29368 can be ordered as an

optional extra. Cables longer than 1 m, but not longer than 2 m will be the

responsibility of the installer.

ACP control plate.

DB

126269.e

ps

Mounting on the ACP control plate.

Mounting on the front panel of the switchboard.

Controller installation

313E.indb 19 09/04/2013 13:04:29

Page 30: Tranferencia Datasheet SCHNEIDER

A-20

Functions

and characteristics

The BA controller is used to create simple source-

changeover systems that switch from one source to

another depending on the presence of voltage UN on

the “Normal” source.

It is generally used to manage two permanent sources

and can control Compact NS, Compact NSX and

Masterpact NT/NW circuit breakers and switch-

disconnectors.

Operating modesA four-position switch may be used to select:

b automatic operation

b forced operation on the “Normal” source

b forced operation on the “Replacement” source

b stop (both “Normal” and “Replacement” sources off).

Setting the time delaysTime delays are set on the front of the controller.

t1. delay between detection that the “Normal” source has failed and the transmission

of the order to open the “Normal” source circuit breaker (adjustable from 0.1 to

30 seconds).

t2. delay between detection that the “Normal” source has returned and the

transmission of the order to open the “Replacement” source circuit breaker

(adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indicationsThe status of the circuit breakers is indicated on the front of the controller.

b ON, OFF, fault.

A built-in terminal block may be used to connect the following input/output signals:

b inputs:

v voluntary order to transfer to source R (e.g. for special tariffs, etc.)

v additional control contact (not part of the controller). Transfer to the “Replacement”

source takes place only if the contact is closed (e.g. used to test the frequency of UR,

etc.)

b outputs:

v indication of operation in automatic or stop mode via changeover contacts.

TestIt is possible to test the operation of the BA controller by turning OFF (opening)

the P25M circuit breaker for the “Normal” source and thus simulating a failure of

voltage UN.

DB

403841.e

ps

BA Controller

DB

403838.e

ps

Front of the BA controller.

Associated controllersBA controller

313E.indb 20 09/04/2013 13:04:29

Page 31: Tranferencia Datasheet SCHNEIDER

A-21

Switch set to Auto (automatic operation and special-tariff mode) Switch set to the “N” position (forced operation on the “Normal” source)

DB

126548.e

ps

Switch set to the “R” position (forced operation on the “Replacement” source)

Switch set to the “Stop” position

DB

126549.e

ps

DB

126550.e

ps

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker

WAITING

when an external event occurs (e.g. failure or return of UN).

The number sends to the indicated step when the condition is true.

BA controller

Operating sequences

11

313E.indb 21 09/04/2013 13:04:30

Page 32: Tranferencia Datasheet SCHNEIDER

A-22

Functions

and characteristics

The UA controller is used to create a source-

changeover system integrating the following automatic

functions:

b transfer from one source to another depending on

the presence of voltage UN on the “Normal” source

b startup of an engine generator set

b shedding and reconnection of non-priority circuits

b transfer to the “Replacement” source if one of the

phases on the “Normal” source fails.

The UA controller can control Compact NS,

Compact NSX and Masterpact NT/NW devices.

Operating modesA four-position switch may be used to select:

b automatic operation

b forced operation on the “Normal” source

b forced operation on the “Replacement” source

b stop (both “Normal” and “Replacement” sources off, then manual operation).

Setting the time delaysTime delays are set on the front of the controller.

t1. delay between detection that the “Normal” source has failed and the transmission

of the order to open the “Normal” source circuit breaker (adjustable from 0.1

to 30 seconds).

t2. delay between detection that the “Normal” source has returned and the

transmission of the order to open the “Replacement” source circuit breaker

(adjustable from 0.1 to 240 seconds).

t3. delay following opening of QN with load shedding and before closing of QR

(adjustable from 0.5 to 30 seconds).

t4. delay following opening of QR with load reconnection and before closing of QN

(adjustable from 0.5 to 30 seconds).

t5.generator set (adjustable from 60 to 600 seconds).

t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indicationsCircuit breaker status indications on the front of the controller:

b ON, OFF, fault.

A built-in terminal block may be used to connect the following input/output signals:

b inputs:

v voluntary order to transfer to source R (e.g. for special tariffs, etc.)

v additional control contact (not part of the controller). Transfer to the “Replacement”

source takes place only if the contact is closed (e.g. used to test the frequency of UR,

etc.)

b outputs:

v control of an engine generator set (ON / OFF)

v shedding of non-priority circuits

v indication of operation in automatic mode via changeover contacts.

Distribution-system settingsThree switches are used to:

b select the type of “Normal” source, whether single-phase or three-phase

(e.g. 240 V single-phase or 240 V three-phase)

b select whether to remain (or not) on the “Normal” source if the “Replacement”

source is not operational during operation on special tariffs

b select the maximum permissible startup time for the engine generator set during

operation on special tariffs (120 or 180 seconds).

TestA pushbutton on the front of the controller may be used to test transfer from the

“Normal” source to the “Replacement” source, then the return to the “Normal” source.

The test lasts approximately three minutes.

COM communications optionUsing the internal bus protocol, this option may be used to remote the following

information:

b circuit breaker status (ON, OFF, fault trip)

b presence of the “Normal” and “Replacement” voltages

b presence of an order for forced operation (e.g. special tariffs)

b b status of non-priority circuits (loads shed or not)

b position of the switch (stop, auto, forced operation on the “Normal” source, forced

operation on the “Replacement” source).

DB

403842.e

ps

UA Controller

Front of the UA controller.

Associated controllersUA controller

313E.indb 22 09/04/2013 13:04:31

Page 33: Tranferencia Datasheet SCHNEIDER

A-23

Switch set to the “R” position (forced operation on the “Replacement” source) Switch set to the “N” position (forced operation on the “Normal” source)

DB

126551.e

ps

DB

126552.e

ps

Switch set to the “Stop” position

DB

126553.e

ps

WAITING The system exits this mode when the

external event occurs (e.g. failure or return

of UN).

When the UA controller is not energised, the output for

generator set startup is activated).

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker

UA controller

Operating sequences

Forced operation mode

313E.indb 23 09/04/2013 13:04:32

Page 34: Tranferencia Datasheet SCHNEIDER

A-24

Functions

and characteristics

Switch set to the “Auto” position (special-tariff mode)

WAITING The system exits this mode when the

external event occurs (e.g. failure or return

of UN).

When the UA controller is not energised, the output for

generator set startup is activated).

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breakerB : Penalties accepted (N ON), i.e. B = 1

1 The number sends to the indicated step when the condition is true.

Associated controllersUA controller

Operating sequences

Special-tariff mode

DB

126554.e

ps

313E.indb 24 09/04/2013 13:04:32

Page 35: Tranferencia Datasheet SCHNEIDER

A-25

Switch set to the “Auto” position (automatic operation and test mode).

DB

126555.e

ps

WAITING The system exits this mode when the

external event occurs (e.g. failure or return

of UN).

When the UA controller is not energised, the output for

generator set startup is activated).

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker B : Penalties accepted (N ON), i.e. B = 1(*) The test lasts 180 seconds.

1 The number sends to the indicated step when the condition is true.

UA controller

Operating sequences

Test mode and automatic operation

313E.indb 25 09/04/2013 13:04:33

Page 36: Tranferencia Datasheet SCHNEIDER

A-26

Functions

and characteristics

IVE unit

Db126594.e

ps

SymbolsQN : “Normal” Compact circuit breaker equipped

for remote operation (motor mechanism)

QR : “Replacement” Compact circuit breaker

equipped for remote operation (motor

mechanism)

ON : Circuit breaker QN opening order

OR : Circuit breaker QR opening order

IN : Circuit breaker QN closing order

IR : Circuit breaker QR closing order

L1 : Faulty “Normal” indication LED

L2 : Faulty “Replacement” indication LED

KeyO: OFF (circuit open)I: ON (circuit closed

: either ON or OFF.

Note: following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.

Operating sequences IVE unit

313E.indb 26 09/04/2013 13:04:33

Page 37: Tranferencia Datasheet SCHNEIDER

BA controller

Db126595.e

ps

InputsUN : “Normal” source voltage

UR : “Replacement” source voltage

KT : order for forced-operation on R

KR : additional check before transfer

OutputsQN : “Normal” source circuit breaker

QR : “Replacement” source circuit breaker

UA controller

Db126599.e

ps

Inputs

UN : “Normal” source voltage

UR : “Replacement” source voltage

KT : order for forced-operation on R

KR : additional check before transfer

Outputs

KG : order to the genset

SH : load-shedding order

QN : “Normal” source circuit breaker

QR : “Replacement” source circuit breaker

KeyO: OFF (circuit open)I: ON (circuit closed

: either ON or OFF.

ImportantIf UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.

BA/UA controller

313E.indb 27 09/04/2013 13:04:33

Page 38: Tranferencia Datasheet SCHNEIDER

A-28

Functions

and characteristics

RS 232, Ethernet

RS 485

DC150 data

concentrator

Communicationinterface

Communication bus

Devices

MasterpactIVE MasterpactR

N

9600

19200

JBus

N°1

N°2

BBus

5

13

91

3 7

15

5

13

91

3 7

15

error24V

OK

error

com. com.

N°1 N°2

DC150

N

Electrical-installation management Communications option for Compact NS u 630 A

and Masterpact NT/NWThe COM communications option is compatible with all the source-changeover

systems for Compact NS630b-1600 and Masterpact NT/NW circuit breakers and

switch-disconnectors.

It can be used to remote status information. It may not be used to operate the circuit

breakers (only possible locally on the front of the UA150 controller).

Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors

are compatible with the Modbus ECO COM option.

Depending on the trip units or control units used, the COM option may also be used

to analyse distribution-system parameters required for the operating and

maintenance assistance.

Circuit breaker communicationSwitch-disconnector

Circuit breaker

Compact NS630b-1600 status indications

ON / OFF b b

Fault trip b

Connected / disconnected position b b

Masterpact NT/NW status indications

ON / OFF b b

Fault trip b

Connected / disconnected position b b

Operating and maintenance assistanceOperating and maintenance aids Modbus

Measurement

Current A E P H

Voltages, power... E P H

Frequency P H

Power quality: fundamental, harmonics H

Programming of demand metering E P H

Fault readings

Type of fault A E P H

Interrupted current P H

Waveform capture

On faults H

On demand or programmed H

Histories and logs

Trip history E P H

Alarm history P H

Event logs P H

Indicators

Counter operation A E P H

Contact wear P H

Maintenance register P H

Note: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.

COM communications option

313E.indb 28 09/04/2013 13:04:36

Page 39: Tranferencia Datasheet SCHNEIDER

A-29

Controller UA150Status indications

“Normal” source

ON / OFF b

Circuit breaker ON b

Fault trip (SDE) b

Voltage presence b

“Replacement” source

Circuit breaker ON b

Fault trip (SDE) b

Voltage presence b

Status of R voltage contact b

Controller

Automatic mode b

“Normal” mode b

“Replacement” mode b

Stop mode b

Testing b

“Replacement” engine generator set

Genset failure b

Genset OFF b

Genset ON b

Shedding of non-priority circuits b

Reconnection of non-priority circuits b

Settings

Time delay t1 for validation of UN absence b

Time delay t2 for validation of UN return b

Time delay t3 for wait between opening of N and closing of R b

Time delay t4 for wait between opening of R and closing of N b

Time delay t5 for wait between return of UN and order for genset shutdown b

Time delay t6 for wait before declaring genset failure b

Penalties accepted to avoid special tariff transfer b

9600

19200

JBus

N°1

N°2

BBus

5

13

91

3 7

15

5

13

91

3 7

15

error24V

OK

error

com. com.

N°1 N°2

DC150

N

DC150 data concentratorThe DC150 data concentrator is designed to centralise the information provided

by the communicating switchgear of the Digipact range and to make this information

accessible to a supervisor or PLC under the MODBUS/JBUS protocol.

Main characteristics

b Power supply:

110 V AC to 240 V AC

115 V DC to 125 V DC.

b Weight: 1.5 kg.

b Installation: on panel with the DC150 box which must be earthed on metal part of

the installation.

b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.

COM communications option

313E.indb 29 09/04/2013 13:04:37

Page 40: Tranferencia Datasheet SCHNEIDER

This international site allows you

to access all the Schneider Electric

Solution and Product information via :

pcomprehensive descriptions

p range data sheets

pa download area

pproduct selectors

p ...

You can also access the information

dedicated to your business and get

in touch with your Schneider Electric

country support.

schneider-electric.com

TOOLS

181E6100.indd 12 09/04/2013 14:06:21

Page 41: Tranferencia Datasheet SCHNEIDER

B-1

Source-changeover systems

Compact NSX100-630,

Compact NS630b-1600,

Compact INS/INV, Masterpact

Dimensions

Presentation 2Functions and characteristics A-1

Manual source-changeover systems Interlocking of direct rotary handles B-2

Interlocking of extended rotary handles B-3

Interlocking of toggles B-5

Complete source-changeover assembly B-6

Remote-operated source-changeover systemsInterlocking on a base plate B-9

Interlocking using connecting rods B-13

Interlocking using cables B-15

IVE unit, BA and UA automatic controllers B-20

Electrical diagrams C-1Catalogue numbers and order forms D-1

313E.indb 1 09/04/2013 13:04:37

Page 42: Tranferencia Datasheet SCHNEIDER

B-2

Dimensions

Compact NSX100 to 630Dimensions Front-panel cutout

DB

126608.e

ps

DB

404483.e

ps

Dimensions (mm)

Type A B C D F G H J K L M N P

NSX100/160/250 325 90 156 133 9.25 9 295 150 155

NSX400/630 416 115 100 200 210 5 24.6 386 100

Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630Dimensions Front-panel cutout

Db101609.e

ps

Db101610.e

ps

Db101611.e

ps

Dimensions (mm)

Type A B C D F G H K L M N P

INS/INV250 - 100/160/200/250 325 90 156 106 295 150 131

INS/INV320/400/500/630 416 115 100 200 210 130 22.5 386 100 160.4

Note: X and Y are the symmetry planes for a 3-pole device.

Manual source-changeover systems Interlocking of direct rotary handles

313E.indb 2 09/04/2013 13:04:38

Page 43: Tranferencia Datasheet SCHNEIDER

B-3

Compact NSX100 to 630Dimensions Front-panel cutout

DB

126610.e

ps

DB

126608.e

ps

DB

404482.e

ps

Dimensions (mm)

Type A B C D F G min G max H J P Q

NSX100/160/250 325 90 156 600 9.25 9 25.5 25.5

NSX400/630 416 115 100 200 210 195 600 5 24.6 30.8 30.8

Compact INS40/63/80/100/125/160 / Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630

Dimensions Front-panel cutout

Db101614.e

ps

Db101615.e

ps

Dimensions (mm)

Type A B C D F G min G max H P Q

INS40/63/80 325 90 156 155 396 0 25.5 25.5

INS100/125/160 325 90 156 200 441 0 25.5 25.5

INS/INV250 - 100/160/200/250 325 90 156 185 600 25.5 25.5

INS320/400/500/630 416 115 100 200 210 204 600 22.5 30.8 30.8

Interlocking of extended rotary handles

313E.indb 3 09/04/2013 13:04:39

Page 44: Tranferencia Datasheet SCHNEIDER

B-4

Compact NS630b to 1600Dimensions

DB

101618.e

ps

Front-panel cutout

Db101619.e

ps

Dimensions (mm)

Type A B C D F G min G max H J P Q R

NS630b/800/1000/1200/1600 411 63.5 98 280 218 605 25 24 25.5 25.5 64

Manual source-changeover systemsInterlocking of extended rotary handles

Dimensions

313E.indb 4 09/04/2013 13:04:39

Page 45: Tranferencia Datasheet SCHNEIDER

B-5

Compact NSX100 to 630Dimensions 3 poles 4 poles

DB

126612.E

PS

DB

126613.E

PS

DB

126614.E

PS

Front-panel cutout 3 poles on left 4 poles on left

Db101623.e

ps

Db101624.e

ps

Dimensions (mm)

Type C2 C3 L L16 L17 L18 R2 R18 R19 P5 P

NSX100/160/250 54 108 52.5 140 245 280 54 89 140 83 120

NSX400/630 92.5 182 185 325 116.5 185 150

Interlocking of toggles

313E.indb 5 09/04/2013 13:04:40

Page 46: Tranferencia Datasheet SCHNEIDER

B-6

Assembly for INS250 - 100 to 250 / Assembly for INS320/400/500/630Dimensions

Db101625.e

ps

Db101626.e

ps

Front-panel cutout

Dimensions (mm)

Type A B C D E F G H I J K L M N

INS250 - 100/160/200/250 60.4 130.4 296 68 136 131 61.8 42 84 156 186.5 5.5 50

INS320/400/500/630 82.5 395 102.5 205 155 64 128 210 213 8 50

Dimensions of the complete source-changeover assembly with an extended handle

Db101650.e

ps

Db101651.e

ps

Dimensions (mm)

Type A B C E K L M N

INS250 - 100/160/200/250 60.4 130.4 295 136 156 138.5 631 50

INS320/400/500/630 82.5 395 205 210 162.5 658

Dimensions (mm)

Type P Mmax Mmin Q

INS250 - 100/160/200/250 100 195 64

INS320/400/500/630 150 593 220.5 64

Note: lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.

Manual source-changeover systemsComplete source-changeover assembly

Dimensions

313E.indb 6 09/04/2013 13:04:41

Page 47: Tranferencia Datasheet SCHNEIDER

Compact NSX100 to NSX630Dimensions

DB

413282.e

ps

Dimensions Connection

DB

413280.e

ps

= = = =

= =

DB

413569.e

ps

Dimensions (mm)

Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

NSX100/160/250 118 181.5 244.5 96 152.5 35 35 51 156 8

NSX400/630 165.9 143.5 220.5 45 45 210 113.5 15

Dimensions (mm)

Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT

NSX100/160/250 320 99.5 300 89.5 130.5 139.5 19.5 9.5 140 6

NSX400/630 425 130 400 5.15 98.5 26 115 9.85 6

Note:

Downstream coupling accessory

313E.indb 7 09/04/2013 13:04:42

Page 48: Tranferencia Datasheet SCHNEIDER

B-8

Compact INS250 - 100 to 250 / Compact INS320/400/500/630Dimensions

DB

413286.e

ps

DB

413283.e

ps

Dimensions Connection

DB

413284.e

ps

= = = =

= =

Dimensions (mm)

Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

INS250-100/160/200/250 105.5 169 232 83.5 140 165.5 35 35 51 156 25.5

INS320/400/500/630 141 313 119 195.6 240 45 45 210 88.5

Dimensions (mm)

Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT

INS250-100/160/200/250 320 83 300 12.8 130.5 139.5 21.5 8.5 140 6

INS320/400/500/630 425 400 95 98.5 26 92.5 12.65 6

Manual source-changeover systemsDownstream coupling accessory

Dimensions

313E.indb 8 09/04/2013 13:04:43

Page 49: Tranferencia Datasheet SCHNEIDER

B-9

Compact NSX100 to 250Dimensions, 3 or 4 poles Fixed device Withdrawable device

DB

413288.e

ps

DB

126619.E

PS

(*) Short terminal shields are mandatory.

Vertical mounting Horizontal mounting

Db101638.e

ps

Dimensions (mm)

Type G50 G51 H20 H21 H22 H23 H42 H43 H44 H45 H46 K25 K35 K36

NSX100/160/250 285 62.5 45.5 60 120 144.5 300 156 210.5 300

NSX400/630 180 360 100 152 83 123 60 120 189 210 282.5 400

Dimensions (mm)

Type L31 L32 P7 P8 P9 P32 P33 P50 P52 P54 ØT9 ØT10 U

NSX100/160/250 110.5 354 25 45 182 143 25 99.5 21 9 6 y 32

NSX400/630 150.5 466 25 45 100 256 215 25 123 21 9 6 y 32

Note:

Remote-operated source-changeover systemsInterlocking on a base plate

313E.indb 9 09/04/2013 13:04:44

Page 50: Tranferencia Datasheet SCHNEIDER

B-10

Compact NSX400 to 630Dimensions, 3 or 4 poles Fixed device

DB

413289.e

ps

DB

413290.e

ps

Withdrawable device

Note:circuit breakers.

DB

126622.E

PS

(*) Short terminal shields are mandatory.

DimensionsVertical mounting Horizontal mounting

Db101638.e

ps

Note: dimensions see page B-9.

Remote-operated source-changeover systemsInterlocking on a base plate

Dimensions

313E.indb 10 09/04/2013 13:04:45

Page 51: Tranferencia Datasheet SCHNEIDER

B-11

“Normal” and “Replacement” source devices: NSX100 to NSX250Dimensions Front-panel cutout

177145

DB

413291.e

ps

NSX100to

NSX250

NSX100to

NSX250

77

9595

156

47.5 47.5

29.5

DB

404134.e

ps

“Normal” and “Replacement” source devices: NSX400 to NSX630 Dimensions Front-panel cutout

249217

DB

413300.e

ps

NSX400to

NSX630

127

63.5

127

127

42

210

63.5

NSX400to

NSX630

DB

404135.e

ps

Note for Compact NSX:For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

313E.indb 11 09/04/2013 13:04:46

Page 52: Tranferencia Datasheet SCHNEIDER

B-12

NSX400 to NSX630 as the “Normal” device, NSX100 to NSX250 as the “Replacement” deviceDimensions Front-panel cutout

DB

126623.E

PS

NSX400to

NSX630

NSX100to

NSX250

DB

404136.e

ps

Remote-operated source-changeover systemsInterlocking on a base plate

Dimensions

313E.indb 12 09/04/2013 13:04:47

Page 53: Tranferencia Datasheet SCHNEIDER

B-13

Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

Db101655.e

ps

Two Masterpact NT devices one above the other Fixed devices Withdrawable devices

Db101656.e

ps

Db101655.e

ps

Interlocking using connecting rods

313E.indb 13 09/04/2013 13:04:47

Page 54: Tranferencia Datasheet SCHNEIDER

B-14

Two Masterpact NW devices one above the otherFixed devices Withdrawable devices

Remote-operated source-changeover systems Interlocking using connecting rods

Dimensions

313E.indb 14 09/04/2013 13:04:47

Page 55: Tranferencia Datasheet SCHNEIDER

B-15

Two Compact NS630b to NS1600 devices side-by-sideFixed devices Withdrawable devices

Db101661.e

ps

Db101662.e

ps

Two Masterpact NT devices side-by-side Fixed devices Drawout devices

Db101663.e

ps

Db101662.e

ps

Combination of two Masterpact NT and NW devices side-by-side Fixed devices Drawout devices

Db101664.e

ps

Interlocking using cables

313E.indb 15 09/04/2013 13:04:48

Page 56: Tranferencia Datasheet SCHNEIDER

B-16

Two Masterpact NW devices side-by-sideFixed devices Drawout devices

Db101666.e

ps

Three Masterpact NW devices side-by-side Fixed devices

Db101668.e

ps

Drawout devices

Db101669.e

ps

Remote-operated source-changeover systemsInterlocking using cables

Dimensions

313E.indb 16 09/04/2013 13:04:49

Page 57: Tranferencia Datasheet SCHNEIDER

Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

Two Masterpact NT devices one above the other Fixed devices Drawout devices

313E.indb 17 09/04/2013 13:04:49

Page 58: Tranferencia Datasheet SCHNEIDER

B-18

Two Masterpact NW devices one above the otherFixed devices Drawout devices

Two Masterpact NT and NW devices one above the otherFixed devices Drawout devices

DB

404148.e

ps

Remote-operated source-changeover systemsInterlocking using cables

Dimensions

313E.indb 18 09/04/2013 13:04:50

Page 59: Tranferencia Datasheet SCHNEIDER

B-19

Three Masterpact NW devices one above the otherFixed devices Drawout devices

Remote-operated source-changeover systemsInterlocking using cables

Dimensions

313E.indb 19 09/04/2013 13:04:50

Page 60: Tranferencia Datasheet SCHNEIDER

B-20

IVE unit

ACP control plate and BA/UA controllers Door cutout for BA/UA controllers

Db101680.e

ps

Db101681.e

ps

Db101682.e

ps

DB

101683.e

ps

(1) Cutout according DIN 43700 standard.

Remote-operated source-changeover systemsIVE unit, BA and UA automatic controllers

Dimensions

313E.indb 20 09/04/2013 13:04:51

Page 61: Tranferencia Datasheet SCHNEIDER

C-1

Source-changeover systems

Compact NSX100-630,

Compact NS630b-1600,

Compact INS/INV, Masterpact

Presentation 2Functions and characteristics A-1Dimensions B-1

Remote-operated source-changeover systems2 Compact NSX100/630 devices C-2

2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-5

Source-changeover systems with automatic controllers2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-6

2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-8

Remote-operated source-changeover systems2 Compact NS630b/1600 devices C-9

2 Masterpact NT or NW devices C-12

Source-changeover systems with automatic controllers2 Masterpact NT or NW devices C-26

Catalogue numbers and order forms D-1

Electrical diagrams

313E.indb 1 09/04/2013 13:04:51

Page 62: Tranferencia Datasheet SCHNEIDER

C-2

Source-changeover system without automatic-control systemWithout auxiliaries for emergency off Local reset

Db401805.e

ps

Db101659.e

ps

Voluntary remote reset

Db101660.e

ps

Automatic reset

(1)

LegendsQN “Normal” source Compact NSX equipped with motor mechanismQR “Replacement” source Compact NSX equipped with motor

mechanismSDE “fault-trip” indication contactIVE electrical interlocking and terminal block unitMT motor mechanismOF2 breaker ON/OFF indication contactRN reset order for breaker QNRR reset order for breaker QR

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Remote-operated source-changeover systems2 Compact NSX100/630 devicesDiagram no. 51201177

Electrical diagrams

313E.indb 2 09/04/2013 13:04:52

Page 63: Tranferencia Datasheet SCHNEIDER

C-3

Electrical diagrams

Source-changeover system without automatic-control systemWith emergency off by MN release and automatic reset

KA5 KA5

KA5KA5

DB

415114.e

ps

Automatic reset

(1) Prefabricated wiring supplied.(2) Independent auxiliary source.

LegendsQN “Normal” source Compact NSX equipped with

motormechanismQR “Replacement” source Compact NSX equipped with motor

mechanismMN undervoltage releaseOF2 breaker ON/OFF indication contactSDE “fault-trip” indication contactMT motor mechanismIVE electrical interlocking and terminal block unitBP emergency off button with latchingKA5 auxiliary relayF1 auxiliary power supply circuit breaker

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: after a fault trip, the breaker must be reset manually by pressing its reset button.Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Remote-operated source-changeover systems 2 Compact NSX100/630 devicesDiagram no. 51201178

313E.indb 3 09/04/2013 13:04:53

Page 64: Tranferencia Datasheet SCHNEIDER

C-4

Source-changeover system without automatic-control systemWith emergency off by MX release and automatic reset

DB

415115.e

ps

Automatic reset

(1) Prefabricated wiring supplied(2) This source can be:

b the source present in the case of voltage monitoringb an independent source.

In this case, the MX release must be protected.(3) The reset orders must be delayed by 0.3 seconds.

LegendsQN “Normal” source Compact NSX equipped with motor

mechanismQR “Replacement” source Compact NSX equipped with motor

mechanismSDE “fault-trip” indication contactOF2 breaker ON/OFF indication contactMX shunt releaseMT motor mechanismIVE electrical interlocking and terminal block unitKA5 time-delayed auxiliary relaysKA6 time-delayed auxiliary relaysF1 auxiliary power supply circuit breakerF2 auxiliary power supply circuit breaker

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: after a fault trip, the breaker must be reset manually by pressing its reset button.Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Remote-operated source-changeover systems 2 Compact NSX100/630 devicesDiagram no. 51201179

Electrical diagrams

313E.indb 4 09/04/2013 13:04:54

Page 65: Tranferencia Datasheet SCHNEIDER

C-5

Electrical diagrams

Electrical interlocking by the IVE unitIndependent order to Normal/Replacement source Simultaneous order to Normal/Replacement source

KA1KA1

KA2

KA3

KA4

KA2

KA4

KA3

CN CR

(1)

(1)

Closure order to

"Replacement" source

Closure order to

"Normal" source

Opening order to

"Replacement" source

Opening order to

"Normal" source

DB

415112.e

ps

KA1

KA1

KA2

KA2

CN CR

Order for transfer to

"Normal" source (1)

Order for transfer to

"Replacement" source (1)

DB

415113.e

ps

Controlling each circuit breaker independently. Control of two circuit breakers by “common” transfer order.

(1) See section “IMPORTANT” here after.(2) Operating diagram: the SDE “fault-trip” signals are transmitted to the IVE unit. The SDE auxiliary contacts are mounted in the circuit breakers.

IMPORTANTThe relays controlling the closing order to the “Normal” and “Replacement” circuit breakers must be mechanically and/or electrically

interlocked to prevent them from giving simultaneous closing commands.

It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically

interlocked.

LegendsON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing orderCR “Replacement” source closing orderKA1 auxiliary relayKA2 auxiliary relayKA3 auxiliary relayKA4 auxiliary relayL1 “Normal” source “fault-trip” signalL2 “Replacement” source “fault-trip” signalN “Normal” source auxiliary wiring connectorR “Replacement” source auxiliary wiring connector

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Remote-operated source-changeover systems 2 Compact NSX100/630, NS630b/1600

or Masterpact NT/NW devices

313E.indb 5 09/04/2013 13:04:54

Page 66: Tranferencia Datasheet SCHNEIDER

C-6

Electrical diagrams

Source-changeover system with UA controllerLoad shedding and genset management

Transfer conditions

Terminals 20 and 21: additional control contact (not part of

controller).

Tests on “Normal” and “Replacement” source voltages

“Normal” source voltage UN test

“Replacement” source voltage UR test

The single-phase check for UR is

implemented across terminals 1 and 5

of circuit breaker Q2.

LegendsQ1 circuit breaker supplying and protecting the automatic-

control circuits for the “Normal” sourceQ2 circuit breaker supplying and protecting the automatic-

control circuits for the “Replacement” sourceACP control plateUA automatic controllerIVE electrical interlocking and terminal block unit

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Source-changeover systems with automatic controllers2 Compact NSX100/630, NS630b/1600

or Masterpact NT/NW devices

313E.indb 6 09/04/2013 13:04:55

Page 67: Tranferencia Datasheet SCHNEIDER

Electrical diagrams

Source changeover system with UA controllerController settings Using communication functions

Tests on “Normal” source voltage

A = 0 single-phase test,

A = 1 three-phase test.

Voluntary transfert (e.g. for energy management) b action in the event of genset failure

B = 0 circuit breaker N opens,

B = 1 circuit breaker N remains closed.

b maximum permissible genset startup time (T6)

C = 0 T = 120 s,

C = 1 T = 180 s.

After this time has elapsed, the genset is considered to

have failed.

The address of the UA 150 controller is set using

the two BBus dials.

Source-changeover systems with automatic controllersController settings

313E.indb 7 09/04/2013 13:04:55

Page 68: Tranferencia Datasheet SCHNEIDER

C-8

Electrical diagrams

Source-changeover system with BA controllerCoupling

Transfer conditions

Terminals 20 and 21:

additional control contact (not part of

controller).

Tests on “Normal” and “Replacement” source voltages

The single-phase check for UN and UR

is implemented across terminals 1 and 5

of circuit breakers Q1 and Q2.

LegendsQ1 circuit breaker supplying and protecting the automatic-

control circuits for the “Normal” sourceQ2 circuit breaker supplying and protecting the automatic-

control circuits for the “Replacement” sourceACP control plateBA automatic controllerIVE electrical interlocking and terminal block unit

Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

Source-changeover systems with automatic controllers2 Compact NSX100/630, NS630b/1600

or Masterpact NT/NW devices

313E.indb 8 09/04/2013 13:04:56

Page 69: Tranferencia Datasheet SCHNEIDER

C-9

Electrical diagrams

Electrical interlocking by IVE unit

IVE *

* IVE connection see pages C5, C6 or C8

DB

415209.e

ps

ATTENTION (1)(2) Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Compact NS630b to 1600QR “Replacement” source Compact NS630b to 1600OF... breaker ON/OFF indication contactSDE “fault-trip” indication contactCE1 “connected-position” indication contact (carriage switch)F1 auxiliary power supply circuit breakerIVE electrical interlocking and terminal block unitON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)MT Motor Mechanism

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: after a fault trip, the breaker must be reset manually by pressing its reset button.Diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MT...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Compact NS630b/1600 devicesDiagram no. 51201183

313E.indb 9 09/04/2013 13:04:56

Page 70: Tranferencia Datasheet SCHNEIDER

C-10

Electrical diagrams

Electrical interlocking by IVE unit with emergency off by shunt release

KA5

KA5

Interlocking by IVE see page C5:

- Independent Order to

Normal/Replacement source

- Simultaneous Order to

Normal/Replacement source

KA5

CN CR

DB

415210.e

ps

ATTENTION (1)(2) Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Compact NS630b to 1600QR “Replacement” source Compact NS630b to 1600OF... breaker ON/OFF indication contactSDE “fault-trip” indication contactCE1 “connected-position” indication contact (carriage switch)F1 auxiliary power supply circuit breakerIVE electrical interlocking and terminal block unitMX shunt releaseBP emergency off button with latchingKA5 auxiliary relayON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)MT Motor Mechanism

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: after a fault trip, the breaker must be reset manually by pressing its reset button.Diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MX, MT...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems 2 Compact NS630b/1600 devicesDiagram no. 51201184

313E.indb 10 09/04/2013 13:04:57

Page 71: Tranferencia Datasheet SCHNEIDER

C-11

Electrical diagrams

Electrical interlocking by IVE unit with emergency off by undervoltage release

CN CR

KA5

KA5

Interlocking by IVE see page C5:

- Independent Order to

Normal/Replacement source

- Simultaneous Order to

Normal/Replacement source

KA5

DB

415211.e

ps

ATTENTION (1)(2) Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Compact NS630b to 1600QR “Replacement” source Compact NS630b to 1600OF... breaker ON/OFF indication contactSDE “fault-trip” indication contactCE1 “connected-position” indication contact (carriage switch)F1 auxiliary power supply circuit breakerIVE electrical interlocking and terminal block unitMN undervoltage releaseBP emergency off button with latchingKA5 auxiliary relayON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)MT Motor Mechanism

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: after a fault trip, the breaker must be reset manually by pressing its reset button.Diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MN, MT...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Compact NS630b/1600 devicesDiagram no. 51201185

313E.indb 11 09/04/2013 13:04:57

Page 72: Tranferencia Datasheet SCHNEIDER

C-12

Electrical diagrams

Electrical interlocking by IVE unit with lockout after a fault

IVE *

* IVE connection see pages C5, C6 or C8

DB

415212.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactIVE electrical interlocking and terminal block unit F1 auxiliary power supply circuit breakerON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems0

2 Masterpact NT or NW devicesDiagram no. 51201142

313E.indb 12 09/04/2013 13:04:58

Page 73: Tranferencia Datasheet SCHNEIDER

C-13

Electrical diagrams

Electrical interlocking by IVE unit with lockout after a fault and emergency off by shunt release

KA5

KA5

Interlocking by IVE see page C5:

- Independent Order to

Normal/Replacement source

- Simultaneous Order to

Normal/Replacement source

KA5

CN CR

DB

415213.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactIVE electrical interlocking and terminal block unitKA5 auxiliary relayF1 auxiliary power supply circuit breakerBP emergency off button with latchingON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Masterpact NT or NW devicesDiagram no. 51201143

313E.indb 13 09/04/2013 13:04:59

Page 74: Tranferencia Datasheet SCHNEIDER

C-14

Electrical diagrams

Electrical interlocking by IVE unit with lockout after a fault and emergency off by undervoltage release

Interlocking by IVE see page C5:

- Independent Order to

Normal/Replacement source

- Simultaneous Order to

Normal/Replacement source

KA5

KA5

KA5

CN CR

DB

415214.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseMN undervoltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactIVE electrical interlocking and terminal block unitKA5 auxiliary relayF1 auxiliary power supply circuit breakerBP emergency off button with latchingON “Normal” source opening orderOR “Replacement” source opening orderCN “Normal” source closing order (0.25 second delay)CR “Replacement” source closing order (0.25 second delay)

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, MN, XF...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Masterpact NT or NW devicesDiagram no. 51201144

313E.indb 14 09/04/2013 13:04:59

Page 75: Tranferencia Datasheet SCHNEIDER

C-15

Electrical diagrams

Automatic-control system for permanent replacement source with lockout after a fault (with MN)

DB

414899.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

IMPORTANTThe relays controlling the closing order to the “Normal” and “Replacement” circuit breakers must be mechanically and/or electrically

interlocked to prevent them from giving simultaneous closing commands.

It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically

interlocked.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorXF standard closing voltage releaseMN undervoltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactIVE electrical interlocking and terminal block unitF1 auxiliary power supply circuit breakerF2 circuit breaker (high breaking capacity)S1 control switchesKA1 auxiliary relaysKA2 auxiliary relaysKA3 auxiliary relays

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MN, XF...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Masterpact NT or NW devicesDiagram no. 51156904

313E.indb 15 09/04/2013 13:05:00

Page 76: Tranferencia Datasheet SCHNEIDER

C-16

Electrical diagrams

Automatic-control system for replacement source generator set with lockout after a fault (with MN)

DB

414900.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

IMPORTANTThe relays controlling the closing order to the “Normal” and “Replacement” circuit breakers must be mechanically and/or electrically

interlocked to prevent them from giving simultaneous closing commands.

It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically

interlocked.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorXF standard closing voltage releaseMN undervoltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactIVE electrical interlocking and terminal block unitF1 auxiliary power supply circuit breakerF2 circuit breaker (high breaking capacity)S1 control switchesKA1 auxiliary relayKA2 time delay for genset startup order to avoid starting

the genset for transient UN disturbancesKA3 auxiliary relay

States permitted by mechanical interlocking systemNormal Replacement

0 0

1 0

0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MN, XF...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated source-changeover systems2 Masterpact NT or NW devicesDiagram no. 51156905

313E.indb 16 09/04/2013 13:05:01

Page 77: Tranferencia Datasheet SCHNEIDER

Electrical diagrams

2 normal sources and 1 replacement source: electrical interlocking without lockout after a fault

LegendsQN... “Normal” source Masterpact NWQR “Replacement” source Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactPF “ready-to-close” contactCE “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakert1 order for transfer from “R” to “N1 + N2”

(QN1 and QN2 closing time delay = 0.25 sec. minimum)t2 order for transfer from “N1 + N2” to “R”

(QR closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system

Normal 1 Normal 2 Replacement

0 0 0

1 1 0

0 0 1

1 0 0

0 1 0

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156906

313E.indb 17 09/04/2013 13:05:01

Page 78: Tranferencia Datasheet SCHNEIDER

C-18

Electrical diagrams

2 normal sources and 1 replacement source: electrical interlocking with lockout after a fault

ATTENTION

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

LegendsQN... “Normal” source Masterpact NWQR “Replacement” source Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakerS1 control switchesS2 source selection switchesKA1 auxiliary relayKA2 auxiliary relays with 10 to 180 sec. time delayt1 order for transfer from “R” to “N1 + N2”

(QN1 and QN2 closing time delay = 0.25 sec. minimum)t2 order for transfer from “N1 + N2” to “R”

(QR closing time delay = 0.25 sec. minimumm)

States permitted by mechanical interlocking system

Normal 1 Normal 2 Replacement

0 0 0

1 1 0

0 0 1

1 0 0

0 1 0

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156907

313E.indb 18 09/04/2013 13:05:01

Page 79: Tranferencia Datasheet SCHNEIDER

C-19

Electrical diagrams

2 normal sources and 1 replacement source: automatic-control system for generator set without lockout

after a fault (with MN)

LegendsQN... “Normal” source Masterpact NWQR “Replacement” source Masterpact NWMCH spring-charging motorXF standard closing voltage releaseMN undervoltage releaseOF... breaker ON/OFF indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakerF2/F3 circuit breaker (high breaking capacity)S1 control switchesS2 source selection switchesKA1 auxiliary relayKA2 auxiliary relays with 10 to 180 sec. time delayKA3 auxiliary relays with 0.1 to 30 sec. time delayKA4 auxiliary relayKA5 auxiliary relays with 0.25 sec. time delayKA6 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system and with associated automatism

Normal 1 Normal 2 Replacement

0 0 0

1 1 0

0 0 1

1 0 0

0 1 0

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MN, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156908

313E.indb 19 09/04/2013 13:05:02

Page 80: Tranferencia Datasheet SCHNEIDER

C-20

Electrical diagrams

2 normal sources and 1 replacement source: automatic-control system for generator set with lockout

after a fault (with MN)

ATTENTION

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

LegendsQN... “Normal” source Masterpact NWQR “Replacement” source Masterpact NWMCH spring-charging motorXF standard closing voltage releaseMN undervoltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakerF2/F3 circuit breaker (high breaking capacity)S1 control switchesS2 source selection switchesKA1 auxiliary relayKA2 auxiliary relays with 10 to 180 sec. time delayKA3 auxiliary relays with 0.1 to 30 sec. time delayKA4 auxiliary relayKA5 auxiliary relays with 0.25 sec. time delayKA6 auxiliary relays with 0.25 sec. time delayKA7 auxiliary relayKA8 auxiliary relay

States permitted by mechanical interlocking system

and with associated automatism

Normal 1 Normal 2 Replacement

0 0 0

1 1 0

0 0 1

1 0 0

0 1 0

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MN, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156909

313E.indb 20 09/04/2013 13:05:02

Page 81: Tranferencia Datasheet SCHNEIDER

C-21

Electrical diagrams

3 sources with only 1 device closed: electrical interlocking without lockout after a fault

LegendsQS... “Source” Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakert1 order for transfer to “Source 1”

(QS1 closing time delay = 0.25 sec. minimum)t2 order for transfer to “Source 2”

(QS2 closing time delay = 0.25 sec. minimum)t3 order for transfer to “Source 3”

(QS3 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system

Source 1 Source 2 Source 3

0 0 0

1 0 0

0 1 0

0 0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156910

313E.indb 21 09/04/2013 13:05:03

Page 82: Tranferencia Datasheet SCHNEIDER

C-22

Electrical diagrams

3 sources with only 1 device closed: electrical interlocking with lockout after a fault

ATTENTION

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

LegendsQS... “Source” Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakert1 order for transfer to “Source 1”

(QS1 closing time delay = 0.25 sec. minimum)t2 order for transfer to “Source 2”

(QS2 closing time delay = 0.25 sec. minimum)t3 order for transfer to “Source 3”

(QS3 closing time delay = 0.25 sec. minimum)KA1 auxiliary relaysKA2 auxiliary relaysKA3 auxiliary relays

States permitted by mechanical interlocking system

Source 1 Source 2 Source 3

0 0 0

1 0 0

0 1 0

0 0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156911

313E.indb 22 09/04/2013 13:05:03

Page 83: Tranferencia Datasheet SCHNEIDER

C-23

Electrical diagrams

2 sources and 1 coupling: electrical interlocking without lockout after a fault

LegendsQS... “Source” Masterpact NWQC “Coupling” Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakert1 coupling order for “Source 1 failure”

(QC closing time delay = 0.25 sec. minimum)t2 coupling order for “Source 2 failure”

(QC closing time delay = 0.25 sec. minimum)t3 coupling order for “Source 1 restored”

(QS1 closing time delay = 0.25 sec. minimum)t4 coupling order for “Source 2 restored “

(QS2 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system

Source 1 Source 2 Coupling

0 0 0

1 1 0

1 0 1

0 1 1

1 0 0

0 1 0

0 0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156912

313E.indb 23 09/04/2013 13:05:03

Page 84: Tranferencia Datasheet SCHNEIDER

C-24

Electrical diagrams

2 sources and 1 coupling: electrical interlocking with lockout after a fault

ATTENTION

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

LegendsQS... “Source” Masterpact NWQC “Coupling” Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakert1 coupling order for “Source 1 failure”

(QC closing time delay = 0.25 sec. minimum)t2 coupling order for “Source 2 failure”

(QC closing time delay = 0.25 sec. minimum)t3 coupling order for “Source 1 restored”

(QS1 closing time delay = 0.25 sec. minimum)t4 coupling order for “Source 2 restored “

(QS2 closing time delay = 0.25 sec. minimum)KA1 auxiliary relaysKA2 auxiliary relaysKA3 auxiliary relays

States permitted by mechanical interlocking system

Source 1 Source 2 Coupling

0 0 0

1 1 0

1 0 1

0 1 1

1 0 0

0 1 0

0 0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156913

313E.indb 24 09/04/2013 13:05:04

Page 85: Tranferencia Datasheet SCHNEIDER

C-25

Electrical diagrams

2 sources and 1 coupling: automatic-control system with lockout after a fault

ATTENTION

The diagram shows the electrical wiring for circuit breakers. When wiring the SDE with switch-disconnectors, connect the SDE to terminals 81 and 84.

LegendsQS... “Source” Masterpact NWQC “Coupling” Masterpact NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault trip” indication contactPF “ready-to-close” contactCE... “connected-position” indication contact (carriage switch)CH “springs charged” indication contactF1 auxiliary power supply circuit breakerF2/F3 circuit breaker (high breaking capacity)S1 control switchesS2 source selection switchesKA1 auxiliary relays with 10 to 180 sec. time delayKA2 auxiliary relays with 0.1 to 30 sec. time delayKA3 auxiliary relays with 10 to 180 sec. time delayKA4 auxiliary relays with 0.1 to 30 sec. time delayKA5 auxiliary relays with 0.25 sec. time delayKA6 auxiliary relays with 0.25 sec. time delayKA7 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system

and with associated automatism

Source 1 Source 2 Coupling

0 0 0

1 1 0

1 0 1

0 1 1

1 0 0

0 1 0

0 0 1

Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.Auxiliary power supply = supply voltage of auxiliary relays (KA...) = supply voltage of electrical auxiliaries (electrical operation, MCH, MX, XF...).

Remote-operated source-changeover systems3 Masterpact NW devicesDiagram no. 51156914

313E.indb 25 09/04/2013 13:05:04

Page 86: Tranferencia Datasheet SCHNEIDER

C-26

Electrical diagrams

Electrical interlocking with lockout after a fault

DB

415120.e

ps

ATTENTION (1) Not to be wired for the “without lockout after a fault” solution.(2)(3) Prefabricated wiring supplied.The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with switch-disconnectors, connect wire BK to terminal 82.

LegendsQN “Normal” source Masterpact NT or NWQR “Replacement” source Masterpact NT or NWMCH spring-charging motorMX standard opening voltage releaseXF standard closing voltage releaseOF... breaker ON/OFF indication contactSDE1 “fault-trip” indication contactPF “ready-to-close” contactCE1 “connected-position” indication contact (carriage switch)CH “springs charged” indication contact

States permitted by mechanical interlocking system

Normal Replacement

0 0

1 0

0 1

Wiring colour codes Note: diagram shown with circuit breakers in connected position, open, charged, and ready to close.RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Source-changeover systems with automatic controllers2 Masterpact NT or NW devicesDiagram no. 51156903

313E.indb 26 09/04/2013 13:05:05

Page 87: Tranferencia Datasheet SCHNEIDER

Source-changeover systems

Compact NSX100-630,

Compact NS630b-1600,

Compact INS/INV, Masterpact

Catalogue numbers and order forms

Presentation 2Functions and characteristics A-1Dimensions B-1Electrical diagrams C-1

Source-changeover systems for 2 devicesCompact INS40 to INS2500 and INV100 to INV2500 D-2

Compact NSX100 to NSX630 D-3

Compact NS630b to NS1600 circuit breakers and switch-disconnectors D-5

Source-changeover systems for 2 or 3 devicesMasterpact NW circuit breakers and switch-disconnectors D-8

Source-changeover systems for 2 devicesCompact INS40 to INS630 switch-disconnectors D-10

Compact NSX100 to NSX630 / circuit breakers and switch-disconnectors D-12

Compact NS630b to NS1600 / circuit breakers and switch-disconnectors D-14

Masterpact NT or NW / circuit breakers and switch-disconnectors D-16

Source-changeover systems for 3 devicesMasterpact NW / circuit breakers and switch-disconnectors D-18

D-1

313E.indb 1 09/04/2013 13:05:05

Page 88: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Manual source-changeover systems Compact INS40 to INS630 and INV100 to INV630Interlocking for rotary handle

3/4P

Mechanical device for INS40 to INS160equipped with an extended rotary handle

28953

ø5...8

Mechanical device for INS250-100 to INS250/INV100 to INV250equipped with a direct or extended rotary handle

31073

Mechanical device for INS/INV320 to INS/INV630equipped with a direct or extended rotary handle

31074

Complete assembly source-changeover systems Compact INS250 to INS6303P 4P

With Compact INS250-100A 31140 31141

With Compact INS250-160A 31144 31145

With Compact INS250-200A 31142 31143

With Compact INS250 31146 31147

With Compact INS320 31148 31149

With Compact INS400 31150 31151

With Compact INS500 31152 31153

With Compact INS630 31154 31155

Locking for INS complete source changeover assembly

Handle locking by 1 to 3 padlocks (in OFF position) Built in

By keylock Keylocking device 31097

+ Ronis 1351B.500 keylock 41940

or + Profalux KS5 B24 D4Z keylock 42888

Rotary handle

Extended front control for complete source changeover assembly 31055

Manual source-changeover systems Compact INS250 to INS2500 and INV250 to INV2500 by keylockInterlocking

3/4P

Db101549.e

ps

Locking device for Ronis/Profalux keylocks on INS250-100 to INS250/INV100 to INV250

2x 31087

Locking device for Ronis/Profalux keylockson INS/INV320 to INS/INV630

2x 31088

DB

404080.e

ps

Locking device for Ronis/Profalux keylockson INS/INV630b to INS/INV2500

2x 31291

+ Ronis 1351B.500 keylock (2 keylocks / 1 key) 41950

or + Profalux KS5 B24 D4Z keylock (2 keylocks / 1 key) 42878

Connection accessoriesDownstream coupling accessories

Short terminal shields (1 pair) + “normal” source/“replacement” source

DB

101062.e

ps

3/4P

INS250/INS250 LV429359

INS320 to INS630/INS320 to INS630 LV432620

DB

413292.e

ps

Long terminal shields (1 piece)

Db403921.e

ps

INS250 long terminal shield LV429518

INS320 to INS630

Long terminal shield, 45 mm (1 piece) LV432594

Long terminal shield for spreaders, 52.5 mm (1 piece) LV432596

Terminal extensions

DB

115652.e

ps

Spreaders 52.5 mm 4P LV432491

Source-changeover systems for 2 devices Compact INS40 to INS2500

and INV100 to INV2500

+

D-2

313E.indb 2 09/04/2013 13:05:08

Page 89: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Manual source changeoverMechanical interlocking

DB

404083.e

ps For toggle controlled circuit breakers NSX100...250 LV429354

NSX400...630 LV432614

DB

404084.e

ps

For rotary handled circuit breakers NSX100...250 LV429369

NSX400...630 LV432621

Key lock interlocking

DB

404085.e

ps For rotary handled or remote controlled circuit breakers

2 locks, 1 key Ronis 1351B.500 41950

Profalux KS5 B24 D4Z 42878

Remote controlled source changeoverPlate + IVE unit

DB

404086.e

ps Source “normal”/source “replacement” (identical voltages) 24 to 250 V DC 48 to 415 V AC 50/60 Hz

440 V 60 Hz

NSX100...250/NSX100...250

Plate + IVE unit (1) 29351 29350

Plate 29349 29349

IVE unit 29356 29352

Auxiliary switches 2 OF + 2 SDE 4 x 29450 4 x 29450

Spare wiring system (device/IVE unit) 29365 29365

Back sockets option add: Only long RC (2) (2)

Plug in base option add: Plug in kit (2) (2)

NSX400...630/NSX100...630

Plate + IVE unit (1) 32611 32610

Plate 32609 32609

IVE unit 29356 29352

Auxiliary switches 2 OF + 2 SDE 4 x 29450 4 x 29450

Spare wiring system (device/IVE unit) 29365 29365

Back sockets option add: Only long RC (2) (2)

Plug in base option add: Plug in kit (2) (2)

Adaptator kit for NSX100...250 1 x 32618 1 x 32618

Control unit option

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

110/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz440 V 60 Hz

ACP + controller BA (1) 29470 29471

Plate ACP 29363 29364

Controller BA 29376 29377

ACP + controller UA (1) 29448 29472 29473

Plate ACP 29447 29363 29364

Controller UA 29446 29378 29380

ACP + controller UA150 (1) (communication option) 29474 29475

Plate ACP 29363 29364

Controller UA150 29379 29381

Wiring cable between BA/UA and ACP/IVEWiring cable (1.5 meter) 29368 29368

Communication module

960019200

JBus

N°1

N°2

BBus

5

1391

3 7

155

1391

3 7

15

error24VOKerror

com. com.

N°1 N°2

DC150N

DB

403922.e

ps DC150 data concentrator

110-240 V AC / 115-125 V DC

50823

(1) The supply voltages BA/UA controller, ACP plate, IVE unit and the remote control must be identical whatever the source changeover type.(2) See products pages.

Source-changeover systems for 2 devicesCompact NSX100 to NSX630

D-3

313E.indb 3 09/04/2013 13:05:10

Page 90: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order formsSource-changeover systems for 2 devicesCompact NSX100 to NSX630 (cont.)

Connection accessoriesDownstream coupling accessories

DB

101062.e

ps Short terminal shields (1 pair) + “normal” source/“replacement” source

3P 4P

NSX100...250/NSX100...250 / 250 A LV429358 LV429359

NSX400...630/NSX400...630 / 630 A LV432619 LV432620

Long terminal shields (1 piece)

Db403921.e

ps 3/4P

NSX100...250 long terminal shield LV429518

NSX400...630

Long terminal shield, 45 mm (1 piece) LV432594

Long terminal shield for spreaders, 52.5 mm (1 piece)

LV432596

Terminal extensions

DB

115652.e

ps

Spreaders 52.5 mm 4P LV432491

Typical composition of remote controlled source changeoverRemote controlled source changeover

+

DB

413426.e

ps 1 normal device N (1)

+ 1 replacement device R (2)

+ 2 remote controls (3)

+ 1 plate with interlocking (4) with IVE (5) and its wiring (8)

+ 2 plug-in kits (if plug-in version)

+ 1 adaptor kit for NSX100...250 plug-in (if NSX400...630 with NSX100...250)

+ auxilary switches (6)

2 x (1 OF + 1 SDE) for Compact NSX100...630

+ long RC (if back connection)

IVE voltages and remote controls are identical.

Associated control unit

0 . OFF

0 . OFF

DB

403059.e

ps 1 source changeover without associated control unit

+ 1 ACP (9) with BA control unit (10)

Or + 1 ACP (9) with UA control unit (11)

Or + 1 ACP (9) with UA150 control unit (11)

+ extension (12) for remote UA/BA connection on front of switchboard

IVE voltages + remote control + ACP + BA or UA are identical.

+

D-4

313E.indb 4 09/04/2013 13:05:12

Page 91: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Interlocking for source-changeover systemsMechanical interlocking

DB

404090.e

ps For 2 devices with extended rotary handles 33890

Interlocking using connecting rods for Compact electrically-operated devices

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

DB

404091.e

ps

33910

2 Compact withdrawable devices 33913

Interlocking using cables for Compact electrically-operated devices

OpushOFF

IpushON

OOFF

discharged

Opush OFF

IpushON

OOFF

discharged

DB

404092.e

ps

33911

2 Compact withdrawable devices 33914

33915

Source-changeover systems for 2 devicesCompact NS630b to NS1600

circuit breakers and switch-disconnectors

D-5

313E.indb 5 09/04/2013 13:05:13

Page 92: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Associated controllerThe automatic-control option includes:

b an IVE electrical-interlocking unit

b an ACP control plate

b a BA or UA controller, depending on the required functions

b a UA/BA adapter kit.

Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit 24 to 250 V DC 48/415 V AC 50/60 Hz440 V 60 Hz

DB

404093.e

ps For 2 devices 29356 29352

54655

Control unit option 110/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz440 V 60 Hz

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

ACP + controller BA (1) 29470 29471

Plate ACP 29363 29364

Controller BA 29376 29377

ACP + controller UA (1) 29448 29472 29473

Plate ACP 29447 29363 29364

Controller UA 29446 29378 29380

ACP + controller UA150 (1) (communication option) 29474 29475

Plate ACP 29363 29364

Controller UA150 29379 29381

Communication module

960019200

JBus

N°1

N°2

BBus

5

1391

3 7

155

1391

3 7

15

error24VOKerror

com. com.

N°1 N°2

DC150N

DB

403922.e

ps

DC150 data concentrator110-240 V AC / 115-125 V DC

50823

(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.

Source-changeover systems for 2 devicesCompact NS630b to NS1600 circuit breakers and switch-disconnectors (cont.)

D-6

313E.indb 6 09/04/2013 13:05:14

Page 93: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Interlocking for source-changeover systemsInterlocking using connecting rods

DB

404094.e

ps

33912

2 Masterpact NT drawout devices 33913

Interlocking using cables (*)

33200

33201

1 set of 2 cables 33209

(*)

Associated controllerThe automatic-control option includes:

b an IVE electrical-interlocking unit

b an ACP control plate

b a BA or UA controller, depending on the required functions

b a UA/BA adapter kit.

Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit 24 to 250 V DC 48/415 V AC 50/60 Hz440 V 60 Hz

DB

404093.e

ps For 2 devices 29356 29352

54655

Control unit option 110/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz440 V 60 Hz

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

ACP + controller BA (1) 29470 29471

Plate ACP 29363 29364

Controller BA 29376 29377

ACP + controller UA (1) 29448 29472 29473

Plate ACP 29447 29363 29364

Controller UA 29446 29378 29380

ACP + controller UA150 (1) (communication option) 29474 29475

Plate ACP 29363 29364

Controller UA150 29379 29381

Communication module

960019200

JBus

N°1

N°2

BBus

5

1391

3 7

155

1391

3 7

15

error24VOKerror

com. com.

N°1 N°2

DC150N

DB

403922.e

ps DC150 data concentrator

110-240 V AC / 115-125 V DC

50823

(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.

Source-changeover systems for 2 devicesMasterpact NT circuit breakers

and switch-disconnectors

313E.indb 7 09/04/2013 13:05:15

Page 94: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order forms

Interlocking for source-changeover systems for 2 devicesInterlocking of 2 devices using connecting rods

DB

404095.e

ps

48612

2 Masterpact NW drawout devices 48612

Interlocking of 2 devices using cables (*)

47926

47926

1 set of 2 cables 33209

(*)

Associated controller for 2 devicesThe automatic-control option includes:

b an IVE electrical-interlocking unit

b an ACP control plate

b a BA or UA controller, depending on the required functions

b a UA/BA adapter kit.

Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit 24 to 250 V DC 48/415 V AC 50/60 Hz

440 V 60 Hz

DB

404093.e

ps For 2 devices 29356 29352

54655

Control unit option 110/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz

440 V 60 Hz

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

Test

MERLIN GERIN

multi 9

P25M

660V

AC3-IEC292-1

0 . OFF

ACP + controller BA (1) 29470 29471

Plate ACP 29363 29364

Controller BA 29376 29377

ACP + controller UA (1) 29448 29472 29473

Plate ACP 29447 29363 29364

Controller UA 29446 29378 29380

ACP + controller UA150 (1) (communication option) 29474 29475

Plate ACP 29363 29364

Controller UA150 29379 29381

(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.

Source-changeover systems for 2 or 3 devicesMasterpact NW circuit breakers

and switch-disconnectors

D-8

313E.indb 8 09/04/2013 13:05:16

Page 95: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order formsSource-changeover systems for 2 or 3 devicesMasterpact NW circuit breakers

and switch-disconnectors

Communication module

960019200

JBus

N°1

N°2

BBus

5

1391

3 7

155

1391

3 7

15

error24VOKerror

com. com.

N°1 N°2

DC150N

DB

403922.e

ps DC150 data concentrator

110-240 V AC / 115-125 V DC50823

Interlocking for source-changeover systems for 3 devicesInterlocking of 3 devices using cables

48610

48609

48608

D-9

313E.indb 9 09/04/2013 13:05:17

Page 96: Tranferencia Datasheet SCHNEIDER

D-10

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the

appropriate information in the rectangles .

Mechanical interlocking of two INS40 to INS630 devices

Devices with front rotary handles, mounted side by side

Two devices with direct rotary handles

INS250 INS320/400/500/630

Two devices with extended rotary handles

INS40/63/80 INS100/125/160

INS250 INS320/400/500/630

Downstream coupling accessory

INS250 INS320/400/500/630

Long terminal shields INS250 INS320/400/500/630

Complete source-changeover assembly

INS250-100 A INS250-160 A

INS250-200 A INS250-250 A

INS320 INS400

INS500 INS630

Source-changeover systems for 2 devicesCompact INS40 to INS630

Switch-disconnectors

313E.indb 10 09/04/2013 13:05:17

Page 97: Tranferencia Datasheet SCHNEIDER

D-11

Catalogue numbers

and order forms

To indicate your choices, check the applicable square

boxes and enter the appropriate information in the

rectangles .

(one sheet per device, make copies if necessary)

Indication and measurements

4P ammeter module For INS250 Rating 100 A

150 A

250 A

Adaptation kit required for direct handles

Q 1 - NORMAL SOURCE For INS320/630 Rating 400 A

Q 2 - REPLACEMENT SOURCE 600 A

Switch-disconnector 4P current-transformermodule

For INS250 Rating 100 A

Compact type INS40/63/80 150 A

INS100/125/160 250 A

INS250 For INS320/630 Rating 400 A

INS320/400/500/630 600 A

Rating A Auxiliary contact For INS40/160 1OF/CAF/CAO Standard

Number of poles 3 or 4 Low level

Connections For INS250/630 1 OF/CAM Standard

Front connection Standard Low level

Rear connection 2 short 2 long Rotary handles

INS40/80

connectors

Distribution 3x16v rigid/10v Extended front handles INS40 to INS160 Black Red on yellow front

INS250 Black Red on yellow front

INS100/160

connectors

Snap-on y 95v INS320 to INS630 Black Red on yellow front

Distribution 4x25v rigid/16v For complete changeover assembly INS250

INS250

connectors

Snap-on 1.5v to 95v (< 160 A) INS320/630

Snap-on 10v to 185v (< 250 A) Locking of rotary handles

Voltage tap connector for 185v

connector

Padlocking 1 to 3 padlocks (in OFF position)

Keylocking Keylock adapter (keylock not included)

Clips for connectors Set of 10 Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z

Distribution 6x1.5v to 35v rigid

with interphase barriers

Installation accessories

Front-panel escutcheon For switch-disconnectors

INS320/630

connectors

1 cable 35v to 300v For ammeter module, IP40

2 cables 35v to 240v

Voltage tap connector for 185v

connector

Distribution

blocks

Linergy DX

4P 125 A 160 A

1P 160 A

Linergy BS(multi stage)

160 A 250 A

Linergy DP 250 A

Rt-angle extension Set of 3 or 4 250 A 630 A

Straight extension INS250

Edgewise ext. INS630

Spreader INS250 (45 mm)

Front alignment base

INS320/630 52.5 mm

One-piece INS250 INS630

Cu cable lugs

supplied with

2 or 3 inter-phase

barriers

INS100/160 For 95v cable

INS250 For 120v cable

For 150v cable

For 185v cable

INS320/630 For 240v cable

For 300v cable

Al cable lugs

supplied with

2 or 3 inter-phase

barriers

INS250 For 150v cable

For 185v cable

INS320/630 For 240v cable

For 300v cable

Terminal shrouds INS40/63/80 INS100/125/160

Terminal shields INS40/63/80 INS100/125/160

INS250 Long

INS320/630 Long

Long for 52.5 mm spreaders

Interphasebarriers

INS100/160 Set of 6

INS250 Set of 6

INS320/630 Set of 6

Source-changeover systems for 2 devicesCompact INS40 to INS630

Switch-disconnectors

313E.indb 11 09/04/2013 13:05:18

Page 98: Tranferencia Datasheet SCHNEIDER

D-12

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the

appropriate information in the rectangles .

Diagram for two Compact NSX devices

Without automatic control, without emergency off auxiliaries

Without automatic control, with emergency off by MN

Without automatic control, with emergency off by MX

Mechanical interlocking of two NSX100 to NSX630 devices

Manually operated devices, mounted side by side:

Two devices with toggles

Two devices with rotary handles

Mechanical and electrical interlocking of two NSX100 to NSX630 devices

Electrically operated devices, mounted side by side:

Select 1 base plate + IVE unit, the 4 auxiliary contacts and the options / accessories

Base plate + IVE unit Identical voltages: 48 to 415 V AC 50/60 Hz

24 to 250 V DC 440/480 V AC 60 Hz

“Normal” NSX100/250 “Replacement” NSX100/250

“Normal” NSX400/630 “Replacement” NSX400/630

“Normal” NSX400/630 “Replacement” NSX100/250

Adapter kit for NSX400/630 with NSX100/250 (plug-in)

Auxiliary contacts 2 OF + 2 SDE (mandatory) Quantity 4

Options Long rear connections Plug-in base

Downstream coupling accessory 3P NSX100/250

4P NSX400/630

Prefabricated wiring Between device and IVE Quantity

Automatic-control option

Power supply 220/240 V - 50/60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Source-changeover systems for 2 devicesCompact NSX100 to NSX630 / Circuit

breakers and switch-disconnectors

313E.indb 12 09/04/2013 13:05:18

Page 99: Tranferencia Datasheet SCHNEIDER

D-13

Catalogue numbers

and order formsSource-changeover systems for 2 devicesCompact NSX100 to NSX630 / Circuit

breakers and switch-disconnectors

(One sheet per device, make copies if necessary) Indication and measurement

Name of customer: Ammeter module Standard 3P 4P

Address for delivery: I max 3P

Current-transformer module 3P 4P

Requested delivery date: Current-transformer module + TCU 3P 4P

Customer order no.: Insulation-monitoring module 3P 4P

Voltage-presence indicator

To indicate your choices, check the applicable square boxes Auxiliary contact OF SD SDE SDV Standard

and enter the appropriate information in the rectangles OF SD SDE SDV Low level

SDE adapter (TM, MA or Micrologic 2 trip units)

Q 1 - NORMAL SOURCE SDX module

Q 2 - REPLACEMENT SOURCE Remote operation

Circuit breaker or switch disconnector Electrical operation Motor mechanism AC DC V

Compact type NSX100/160/250 NSX400/630 Voltage releases Instantaneous MX AC DC V

Rating A Instantaneous MN AC DC V

Circuit breaker B, F, N, H, S, L Fixed time delay MN AC DC V

Switch-discon. NA Adjust. time delay MN AC DC V

No. of poles 2, 3 or 4 Rotary handles

No. of poles protected

2d, 3d or 4d Direct Black Red and yellow front

Fixed device Front connections MCC conversion access. CNOMO conversion access.

Plug-in/withdr. Plug-in Withdrawable Extended Black Red and yellow front

Earth-leakageprotection

ME, MH, MB Telescopic handle for withdrawable device

Vigi module Voltage V Indication auxiliary 1 early-break switch 2 early-make switches

4P option on 3P NSX Locking

Trip unit Toggle (1 to 3 padlocks) Removable Fixed

Thermal-mag. TMD rating (16 … 250 A) Rotary handle Keylock adapter (keylock not included)

TMG rating (16 … 63 A) Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z

MA rating (2.5 … 220 A) Motor mechanism Keylock adapter + keylock Ronis (special) NSX100/250

Electronic Micrologic 2.2 Micrologic 2.3 Keylock adapter (keylock not included) NSX400/630

Micrologic 2.2 G Micrologic 2.3 AB Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z

Micrologic 2.2 AB Micrologic 5.3 A Interlocking

Micrologic 5.2 A Micrologic 5.3 E Mechanical Toggle operated Rotary Handle

Micrologic 5.2 E Micrologic 5.3 A-Z By key (2 keylocks,

1 key) for rotary handle

Locking kit without locks

Micrologic 5.2 A-Z Micrologic 6.3 A Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z

Micrologic 6.2 A Micrologic 6.3 E

Micrologic 6.2 E Micrologic 1.3 M Installation accessories

Micrologic 2.2 M Micrologic 2.3 M IP30 escutcheon for all types (toggle/rotary handle/motor mechanism)

Micrologic 6.2 E-M Micrologic 6.3 E-M IP30 escutcheon (with access to toggle + trip unit)

SDTAM module IP30 escutcheon for Vigi module

External neutral CT IP40 escutcheon for all types (toggle/rotary handle/motor mechanism)

24 V DC power supply connector IP40 escutcheon for Vigi module

ZSI wiring accessory for NS630b NW/NT IP40 escutcheon for Vigi or ammeter module

External power

supply module

24 V DC

24-30 V DC 48-60 V DC Toggle cover

100-125 V AC 110-130 V AC Sealing accessories

200-240 V AC 380-415 V AC DIN rail adapter

Battery module 3P 60 mm busbar adapter

Connection

Rear-connection

kit

Short Long Auxiliary connections

Mixed 1 automatic connector moving part with 9 wires (for circuit breaker)

NSX100/250

connectors

Snap-on 1.5v to 95v (< 160 A) 1 sup. for 3 auto. conn. moving parts 1 sup. for 2 auto. conn.

Snap-on 25v to 95v (< 250 A)

Snap-on 120v to 185v (< 250 A) Plug-in base

accessories

Long insulated terminals Set of 2

Distribution 6 x 1.5v to 35v 2 IP4 shutters for base

Aluminium 2 cables 50v to 120v Chassis accessories Escutcheon collar Toggle Vigi

NSX400/630

connectors

1 cable 35v to 300v Locking kit (keylock not included)

2 cables 35v to 240v 2 carriage switches (conn./disconnected position indication)

Right-angle terminal extensions Parts or plug-in

Withdrawable kits

Plug-in base FC/RC 2P 3P 4P

Straight extensions NSX100/250 Set of two power connections Standard Vigi

Edgewise extensions 45° term. ext. Dbl.-L term. ext. Safety trip for advanced opening

Spreader NSX100/250 (one piece) (45 mm) For 3P/4P chassis Moving part

NSX400/630 (52.5 mm) Fixed part

Cu cable lugs NSX100/250 120v 150v 185v Adaptater for plug-in base (for terminal shield or interphase barriers)

NSX400/630 240v 300v Communication

Al cable lugs NSX100/250 150v 185v NSX Cord L = 0.35 m NSX Cord L = 1.3 m

NSX400/630 240v 300v NSX Cord U > 480 V AC L = 0.35 m NSX Cord L = 3 m

V mesrt Input for

connector

For lugs NSX100/250 y 185v BSCM (NSX400/630)

For lugs NSX400/630 Communicating motor mechanism 220-240 V

Terminal shields NSX100/250 Long Switchboard front display module FDM121

NSX400/630 Long FDM mounting accessory

Long for 52.5 mm spreaders Modbus interface

Interphase barriers Set of 6 Stacking accessory

2 insulating scrn. NSX100/250 NSX400/630 ULP line termination

Test tool RJ45 connectors

female/female

Wire length RJ45 L = 0.3 m Wire length RJ45 L = 0.6 m

Pocket battery for Micrologic Wire length RJ45 L = 1 m Wire length RJ45 L = 2 m

Maintenance case Wire length RJ45 L = 3 m Wire length RJ45 L = 5 m

USB maintenance interface

Power supply 110-240 V AC

Spare Micrologic cord

313E.indb 13 09/04/2013 13:05:18

Page 100: Tranferencia Datasheet SCHNEIDER

D-14

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the

appropriate information in the rectangles .

Diagram for two Compact NS devices

Electrical interlocking with lockout after fault:

Permanent replacement source (with IVE unit) (no. 51201183)

With emergency off by MX (with IVE unit) (no. 51201184)

With emergency off by MN (with IVE unit) (no. 51201185)

Interlocking using connecting rods between two NS630b to NS1600 devices

Manually operated devices installed side-by-side:

Electrically operated devices installed one above the other:

Complete set for:

2 withdrawable NS devices

Interlocking using cables between two NS630b to NS1600 devices

Electrically operated devices installed one above the other or side-by-side:

Complete set for:

2 withdrawable NS devices

Electrical interlocking between two NS630b to NS1600 devices

1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz

Automatic-control option

Power supply 110 V - 50/60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Power supply 220/240 V - 50/60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Source-changeover systems for 2 devices Compact NS630b to NS1600 / Circuit

breakers and switch-disconnectors

313E.indb 14 09/04/2013 13:05:19

Page 101: Tranferencia Datasheet SCHNEIDER

D-15

Catalogue numbers

and order formsSource-changeover systems for 2 devicesCompact NS630b to NS1600 / Circuit

breakers and switch-disconnectors

(One sheet per device, make copies if necessary) Indication contacts

Name of customer: SD trip indication (maximum 1)

Address for delivery: 6 A-240 V AC Low level

SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices)

Requested delivery date: 6 A-240 V AC Low level

Customer order no.: OF ON/OFF indication contacts (maximum 3)

6 A-240 V AC qty Low level qty

To indicate your choices, check the applicable square boxes Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT)

and enter the appropriate information in the rectangles CE - “connected” position 6 A-240 V AC qty Low level qty

Device i CD - “disconnected” position 6 A-240 V AC qty Low level qty

Q 1 - NORMAL SOURCE CT - “test” position 6 A-240 V AC qty Low level qty

Q 2 - REPLACEMENT SOURCE Auxiliary terminals for chassis alone Jumpers (set of 10)

Circuit breaker or switch disconnector 3-wire terminal (30 parts) 6-wire terminal (10 parts)

Compact type NS630b to NS1600 Remote operation

Rating A Electrical operation Standard Communicating

Circuit breaker N, H, L Power supply AC DC V

Switch-disconnector NA Voltage releases MX AC DC V

Number of poles 3 or 4 MN AC DC V

Device Fixed MN delay unit Adjustable Non-adjustable

Withdr. with chassis

Withdr. without chassis Direct Black Red on yellow front

(moving part only) CNOMO conversion access.

Chassis alone without connections Extended Black Red on yellow front

Micrologic control unit Telescopic handle for withdrawable device

Basic protection 2.0 5.0 6.0 Indication auxiliary 6 A-240 V AC 2 early-make switches

A - ammeter 2.0 5.0 6.0 7.0 2 early-break switches

E - energy meter 2.0 5.0 6.0 Locking

P - power meter 5.0 6.0 7.0 Toggle (1 to 3 padlocks) Removable system Fixed system

AD - external power-supply module V Rotary handle using a keylock

OFF position ON and OFF positions

TCE - external sensor (CT) for neutral protection Ronis 1351B.500 Profalux KS5 B24 D4Z

Rectangular sensor 280 x 115 mm Keylock kit (without keylock)

TCW - external sensor for SGR protection For electrically operated devices

VBP - ON/OFF pushbutton locking

LR - long-time rating plug Standard 0.4 to 1 Ir OFF position locking:

Low setting 0.4 to 0.8 Ir VCPO - by padlocks

High setting 0.8 to 1 Ir VSPO - by keylocks

LT OFF Keylock kit (w/o keylock) Profalux Ronis

Communication 1 keylock Profalux Ronis

Eco COM module Modbus Device Chassis 2 identical keylocks, 1 key Profalux Ronis

Front Display Module (FDM121) Mounting accessory Chassis locking in “disconnected” position:

Breaker ULP cord L = 0.35 m VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis

L = 1.3 m Kirk Castell

L = 3 m 1 keylock Profalux Ronis

Connections 2 identical keylocks, 1 key Profalux Ronis

Horizontal rear connections Top Bottom 2 keylocks, different keys Profalux Ronis

Vertical rear connections Top Bottom Optional connected/disconnected/test position locking

Front connections Top Bottom VPEC - door interlock On right-hand side of chassis

4x240v bare cable connectors On left-hand side of chassis

+ shields VPOC - racking interlock

Long connection shields VDC - mismatch protection

Vertical-connection adapters Accessories

Cable-lug adapters CDM - mechanical operation counter

Arc chute screen CDP - escutcheon

Interphase barriers CP - transparent cover for escutcheon

Spreaders OP - blanking plate for escutcheon

VO - safety shutters on chassis For mounting on horizontal plane

Test kits Mini test kit Portable test kit

313E.indb 15 09/04/2013 13:05:19

Page 102: Tranferencia Datasheet SCHNEIDER

D-16

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the

appropriate information in the rectangles .

Diagram for 2 Masterpact NT/NW devices

Electrical interlocking with lockout after fault:

Permanent replacement source (with IVE unit) (no. 51201142)

With emergency off by MX (with IVE unit) (no. 51201143)

With emergency off by MN (with IVE unit) (no. 51201144)

Automatic control with lockout after fault:

Permanent replacement source (with IVE unit) (no. 51156904)

Engine generator set (with IVE unit) (no. 51156905)

BA/UA controller (with IVE unit) (no. 51156903)

Interlocking using connecting rods (NT/NW devices one above the other)

Complete set for: 2 drawout NT devices

2 drawout NW devices

1 drawout NT device + 1 drawout NW device

Interlocking using cables (NT/NW devices one above the other or side-by-side)

devices may be mixed)

qty

1 drawout NT device qty

qty

1 drawout NW device qty

1 set of 2 cables (for two devices)

Electrical interlocking 2 Masterpact NT/NW devices

1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz

Automatic-control option

Power supply 220/240 V - 50/60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz: ACP + BA controller

ACP + UA controller

ACP + UA150 controller

Source-changeover systems for 2 devicesMasterpact NT or NW / Circuit breakers

and switch-disconnectors

313E.indb 16 09/04/2013 13:05:19

Page 103: Tranferencia Datasheet SCHNEIDER

Catalogue numbers

and order formsSource-changeover systems for 2 devicesMasterpact NT or NW / Circuit breakers

and switch-disconnectors

(One sheet per device, make copies if necessary) Indication contacts

Name of customer: OF - ON/OFF indication contacts

Address for delivery: Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW)

Additional 1 block of 4 OF for NW max. 2 qty

Requested delivery date: EF - combined “connected/closed” contacts

Customer order no.: 1 EF 6 A-240 V AC for NW max. 8 qty

1 EF low-level for NW max. 8 qty

To indicate your choices, check the applicable square boxes SDE - “fault-trip” indication contact

and enter the appropriate information in the rectangles Standard 1 SDE 6 A-240 V AC

Device i Additional 1 SDE 6 A-240 V AC 1 SDE Low level

Q 1 - NORMAL SOURCE Programmable contacts 2 M2C contacts 6 M6C contacts

Q 2 - REPLACEMENT SOURCE Carriage switches 6 A-240 V AC Low level

Circuit breaker or switch disconnector CE - “connected” position max. 3 for NW / NT qty

Masterpact type NT NW CD - “disconnected” position max. 3 for NW, 2 for NT qty

Rating A CT - “test” position max. 3 for NW, 1 for NT qty

Sensor rating A AC - NW actuator for 6 CE - 3 CD - 0 CT additional carriage switches qty

Circuit breaker N1, H1, H2, H3, L1 Remote operation

Switch-disconnector NA, HA, HF, ES, HA10 (NW) Remote ON/OFF MCH - gear motor VNumber of poles 3 or 4 XF - closing voltage release VOption: neutral on right side MX - opening voltage release VDevice Fixed PF - “ready to close” contact Low level

Withdr. with chassis 6 A-240 V AC

Withdr. without chassis BPFE - electrical closing pushbutton

(moving part only) Res - electrical reset option V

Chassis alone without connections RAR - automatic reset option

Micrologic control unit Remote tripping MN - undervoltage release VA - ammeter 2.0 5.0 6.0 7.0 R - delay unit (non-adjustable)

E - energy meter 2.0 5.0 6.0 Rr - adjustable delay unit

P - power meter 5.0 6.0 7.0 2nd MX - shunt release VH - harmonic meter 5.0 6.0 7.0 Locking

AD - external power-supply module V VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)

TCE - external sensor (CT) for neutral protection OFF position locking:

Rectangular sensor for NT (280 x 115 mm) VCPO - by padlocks

earth-leakage protection VSPO - by keylocks Keylock kit (w/o keylock) Profalux Ronis

LR - long-time rating plug Standard 0.4 to 1 Ir Kirk Castell

Low setting 0.4 to 0.8 Ir 1 keylock Profalux Ronis

High setting 0.8 to 1 Ir 2 identical keylocks, 1 key Profalux Ronis

LT OFF 2 keylocks, different keys (NW) Profalux Ronis

PTE - external voltage measurement input (required for reverse

supply)

Chassis locking in “disconnected” position:

VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis

BAT - battery module Kirk Castell

Communication 1 keylock Profalux Ronis

Eco COM module Modbus Device Chassis 2 identical keylocks, 1 key Profalux Ronis

Front Display Module (FDM121) Mounting accessory 2 keylocks, different keys Profalux Ronis

Breaker ULP cord L = 0.35 m Optional connected/disconnected/test position locking

L = 1.3 m VPEC - door interlock On right-hand side of chassis

L = 3 m On left-hand side of chassis

Connections VPOC - racking interlock

Horizontal Top Bottom IPA - cable-type door interlock

Vertical Top Bottom IBPO - racking interlock between crank and OFF pushbutton for NW

Front Top Bottom DAE - automatic spring discharge before breaker removal for NW

Vertical-connection adapters VDC - mismatch protection device - chassis

Cable-lug adapters Accessories

Arc chute screen CDM - mechanical operation counter

Interphase barriers CB - auxiliary terminal shield for chassis

Spreaders CDP - escutcheon

Disconnectable front CP - transparent cover for escutcheon

connection adapter OP - blanking plate for escutcheon

Lugs for 240v or 300v cables On backplates

VO - safety shutters on chassis NT, NW X Test kits Mini test kit Portable test kit

VIVC - shutter position NW

indication and locking

313E.indb 17 09/04/2013 13:05:20

Page 104: Tranferencia Datasheet SCHNEIDER

D-18

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the

appropriate information in the rectangles .

Diagram for 3 Masterpact NW devices

2 “Normal” sources + 1 “Replacement” source:

Electrical interlocking without lockout after fault (no. 51156906)

Electrical interlocking with lockout after fault

2 “Normal” sources + 1 “Replacement” source with source selection:

Automatic control w/ engine generator set w/o lockout after fault (no. 51156908)

Automatic control w/ engine generator set w/ lockout after fault (no. 51156909)

3 sources, only 1 device ON:

Electrical interlocking without lockout after fault (no. 51156910)

Electrical interlocking with lockout after fault (no. 51156911)

2 “Normal” sources + 1 coupling:

Electrical interlocking without lockout after fault (no. 51156912)

Electrical interlocking with lockout after fault (no. 51156913)

Automatic control with lockout after fault: (no. 51156914)

Interlocking using cables (NW devices one above the other or side-by-side)

1 complete set for:

Source-changeover systems for 3 devicesMasterpact NW / Circuit breakers

and switch-disconnectors

313E.indb 18 09/04/2013 13:05:20

Page 105: Tranferencia Datasheet SCHNEIDER

D-19

Catalogue numbers

and order forms

To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles .(one sheet per device, make copies if necessary)

Indication contactsOF - ON/OFF indication contactsStandard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level)Additional 1 block of 4 OF max. 2 qtyEF - combined “connected/closed” contacts

Q 1 - NORMAL SOURCE 1 EF 6 A-240 V AC max. 8 qtyQ 2 - REPLACEMENT SOURCE 1 EF low-level max. 8 qtyCircuit breaker or switch-disconnector SDE - “fault-trip” indication contact

Masterpact type NW Standard 1 SDE 6 A-240 V ACRating A Additional 1 SDE 6 A-240 V AC 1 SDE Low levelSensor rating A Programmable contacts 2 M2C contacts 6 M6C contactsCircuit breaker N1, H1, H2, H3, L1 Carriage switches 6 A-240 V AC Low levelSwitch-disconnector NA, HA, HF CE - “connected” position Max. 3 qtyNumber of poles 3 or 4 CD - “disconnected” position Max. 3 qty

CT - “test” position Max. 3 qtyDevice Fixed AC - NW actuator for 6 CE - 3 CD - 0 CT additional carriage switches qty

Drawout with chassis Remote operationDrawout without chassis(moving part only)

Remote ON/OFF MCH - gear motor VXF - closing voltage release V

Chassis alone without connections MX - opening voltage release VMicrologic control unit PF - “ready to close” contact Low level

A - ammeter 2.0 5.0 6.0 7.0 6 A-240 V ACE - energy meter 2.0 5.0 6.0 BPFE - electrical closing pushbuttonP - power meter 5.0 6.0 7.0 Res - electrical reset option VH - harmonic meter 5.0 6.0 7.0 RAR - automatic reset optionAD - external power-supply module V Remote tripping MN - undervoltage release VTCE - external sensor (CT) for neutral protection R - delay unit (non-adjustable)Rectangular sensor for earth-leakage protection

470 x 160 mm Rr - adjustable delay unit2eme MX - shunt release V

TCW - external sensor for SGR protection LockingLR - long-time rating plug Standard 0.4 to 1 Ir VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)

Low setting 0.4 to 0.8 Ir OFF position locking:High setting 0.8 to 1 Ir VCPO - by padlocks LT OFF VSPO - by keylocks Keylock kit (w/o keylock) Profalux Ronis

PTE - external voltage measurement input (required for reverse supply)

Kirk Castell1 keylock Profalux Ronis

BAT - battery module 2 identical keylocks, 1 key Profalux RonisCommunication 2 keylocks, different keys (NW) Profalux Ronis

Eco COM module Modbus Device Chassis Chassis locking in “disconnected” position:Front Display Module (FDM121) Mounting accessory VSPD - by keylocks Keylock kit (w/o keylock) Profalux RonisBreaker ULP cord L = 0.35 m Kirk Castell

L = 1.3 m 1 keylock Profalux RonisL = 3 m 2 identical keylocks, 1 key Profalux Ronis

Connections 2 keylocks, different keys Profalux RonisHorizontal Top Bottom Optional connected/disconnected/test position lockingVertical Top Bottom VPEC - door interlock On right-hand side of chassisFront Top Bottom On left-hand side of chassisInterphase barriers Fixed, drawout VPOC - racking interlockDisconnectable front connection adapter

Fixed IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW

VO - safety shutters on chassis X DAE - automatic spring discharge before breaker removal for NWVIVC - shutter position indication and locking VDC - mismatch protection

AccessoriesCDM - mechanical operation counterCB - auxiliary terminal shield for chassisCDP - escutcheonCP - transparent cover for escutcheonOP - blanking plate for escutcheonBrackets for mounting On backplatesTest kits Mini test kit Portable test kit

Source-changeover systems for 3 devicesMasterpact NW / Circuit breakers

and switch-disconnectors

313E5100.indd 19 22/04/2013 13:27:59

Page 106: Tranferencia Datasheet SCHNEIDER

D-20

313E5100.indd 20 22/04/2013 13:28:00

Page 107: Tranferencia Datasheet SCHNEIDER

313E0100.indd 3 15/04/2013 10:38:34

Page 108: Tranferencia Datasheet SCHNEIDER

04-2013

Schneider Electric Industries SAS35, rue Joseph MonierCS 3032392506 Rueil Malmaison Cedex FranceRCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com

This document has been printed on ecological paper.

Publication: Schneider Electric Industries SASPhotos: Schneider ElectricPublishing: Altavia St Etienne

ART9

6066

6 © 20

13 - S

chne

ider E

lectric

- All ri

ghts r

eserv

ed.

LVPED211022EN

10-31-1247

313E0100.indd 4 15/04/2013 10:38:34