Tranquility ® Modular Water-to-Water (TMW) Series Commercial EarthPure ® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance 97B0059N03 Revised: 23 June, 2014 Table of Contents Model Nomenclature 3 General Information 4 Unit Physical Data 6 TMW036 - 120 - Unit Dimensional Data 7 TMW170 & 340 - Unit Dimensional Data 8 Unit Installation 9 Piping Installation 10 Water-Loop Heat Pump Applications 11 Ground-Water Heat Pump Applications 12 Ground-Loop Heat Pump Applications 14 Electrical - Line Voltage 16 Electrical - Accessories 17 Electrical - Line Voltage 18 Electrical - Low Voltage 19 TMW Series Wiring Diagram Matrix 20 Typical Wiring Diagrams 22 CXM Controls 33 DXM Controls 34 Safety Features - CXM/DXM Controls 36 Piping System Cleaning & Flushing 38 Unit & System Checkout 39 Unit Start Up Procedure 40 Operating Pressures 41 Preventative Maintenance 43 Warranty (International) 44 Warranty (US & Canada) 45 Start-Up Log Sheet 46 Refrigeration Troubleshooting Form 47 Revision History 48

Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

Embed Size (px)

Citation preview

Page 1: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

Tranquility® Modular

Water-to-Water

(TMW) Series

Commercial EarthPure®

Water-Source Heat Pumps 50Hz & 60Hz

Installation, Operation

& Maintenance

97B0059N03Revised: 23 June, 2014

Table of Contents

Model Nomenclature 3

General Information 4

Unit Physical Data 6

TMW036 - 120 - Unit Dimensional Data 7

TMW170 & 340 - Unit Dimensional Data 8

Unit Installation 9

Piping Installation 10

Water-Loop Heat Pump Applications 11

Ground-Water Heat Pump Applications 12

Ground-Loop Heat Pump Applications 14

Electrical - Line Voltage 16

Electrical - Accessories 17

Electrical - Line Voltage 18

Electrical - Low Voltage 19

TMW Series Wiring Diagram Matrix 20

Typical Wiring Diagrams 22

CXM Controls 33

DXM Controls 34

Safety Features - CXM/DXM Controls 36

Piping System Cleaning & Flushing 38

Unit & System Checkout 39

Unit Start Up Procedure 40

Operating Pressures 41

Preventative Maintenance 43

Warranty (International) 44

Warranty (US & Canada) 45

Start-Up Log Sheet 46

Refrigeration Troubleshooting Form 47

Revision History 48

Page 2: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

2 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

This Page Intentionally Left Blank

Page 3: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

3c l i m a t e m a s t e r . c o m

Model Nomenclature

T M W A0 3 6 CG 1 0 C 0 C S1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

TM = TRANQUILITY MEDIUM TEMPERATUREMODEL TYPE

W = WATER TO WATER HEAT PUMPCONFIGURATION

UNIT SIZE036 - E,F,G,H,U,V

REVISION LEVELA = CURRENT

VOLTAGE

CONTROLS

CABINET INSULATION1 = COMMERCIAL EXTENDED RANGE

HOT WATER GENERATOR OPTIONS (TMW036-120 ONLY)

C = CopperSOURCE WATER COIL OPTIONS

N = Cupro-Nickel

C = COPPERLOAD WATER COIL OPTIONS

N = CUPRO-NICKEL

S = STANDARD

0 = NONE

RESERVED-FOR FUTURE OPTIONS0 = NONE

060 - F,G,H,N,U120 - F,G,H,N,U170 - F,H,N,U340 - F,H,N,U

2 = COMMERCIAL EXTENDED RANGE w/ULTRA QUIET

2 = HWG (COIL ONLY) COMMERCIAL

NOTES:1. FRONT ACCESS PANELS ARE STAINLESS STEEL, REST OF THE UNIT IS PAINTED BLACK (PEWTER)2. LOAD/SOURCE WATER CONNECTIONS ARE TOP FOR 170 AND 340. WATER CONNECTIONS ARE FRONT FOR 036, 060 & 120.

C = CXMD = DXML = CXM w/LONM = DXM w/LONN = CXM w/MPCP = DXM w/MPC

G = 208-230/60/1 - R410AE = 265/60/1 - R410A

H = 208-230/60/3 - R410AF = 460/60/3 - R410AU = 380-420/50/3 - R410AN = 575/60/3 - R410A

F = CXMG = DXMH = CXM w/LONJ = DXM w/LONT = CXM w/MPCU = DXM w/MPC

CEAPPROVED

FOR EUROPE

V = 220-240/50/1 - R410A

ETLAPPROVED

FOR USA & CANADA

Page 4: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

4 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

General Information

WARNING! To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal profi ciency requirements.

CAUTION! To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and fi lters will quickly become clogged with construction dirt and debris, which may cause system damage.

WARNING!

WARNING!

CAUTION!

SafetyWarnings, cautions, and notices appear throughout this manual. Read these items carefully before attempting any installation, service, or troubleshooting of the equipment.

DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury. DANGER labels on unit access panels must be observed.

WARNING: Indicates a potentially hazardous situation, which if not avoided could result in death or serious injury.

CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.

NOTICE: Notifi cation of installation, operation, or maintenance information, which is important, but which is not hazard-related.

WARNING! All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.

WARNING! WARNING! The installation of water-source heat pumps and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

Page 5: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

5c l i m a t e m a s t e r . c o m

Inspection - Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. Assure the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not fi led within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to fi le all necessary claims with the carrier. Notify the ClimateMaster Traffi c Department of all damage within fi fteen (15) days of shipment.

Storage - Equipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times. Do not stack TMW170 or 340. The stack limit for TMW036, 060 and 120 is three.

Unit Protection - Cover units on the job site with either shipping packaging, vinyl fi lm, or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.

Examine all pipes, fi ttings, and valves before installing any of the system components. Remove any dirt or trash found in or on these components.

Pre-Installation - Installation, Operation, and Maintenance instructions are provided with each unit.. The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation.Prepare units for installation as follows:1. Compare the electrical data on the unit nameplate

Twith ordering and shipping information to verify that the correct unit has been shipped.

2. Keep the cabinet covered with the shipping packaging until installation is complete and all plastering, painting, etc. is fi nished.

3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.

4. Inspect all electrical connections. Connections must be clean and tight at the terminals.

CAUTION! All three phase scroll compressors must have direction of rotation verifi ed at start-up. Verifi cation is achieved by checking compressor Amp draw. Amp draw will be substantially lower compared to nameplate values. Additionally, reverse rotation results in an elevated sound level compared to correct rotation. Reverse rotation will result in compressor internal overload trip within several minutes. Verify compressor type before proceeding.

CAUTION! DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can signifi cantly reduce performance, reliability, and service life. Always move and store units in an upright position. Tilting units on their sides may cause equipment damage.

NOTICE! Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise, and could cause component failure due to added vibration.

CAUTION!

CAUTION!

CAUTION! CAUTION! CUT HAZARD - Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.

Page 6: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

6 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Unit Physical Data

Model 036 060 120 170 340

Compressor (qty) Scroll (1) Scroll (2) Scroll (1) Scroll (2)

Factory Charge HFC-410A (lbs) [kg] per circuit 4.5 [2.04] 5.5 [2.49] 14.9 [6.8]

Water Connection Size

Source/Load (in) 3/4 1 1-1/2 2

Hot Water Generator FPT (in) ½ N/A

Weight - Operating (lbs) [kg] 348 [158] 360 [163] 726 [329] 725 [329] 1330 [604]

Weight - Packaged (lbs) [kg] 373 [169] 385 [175] 770 [349] 765 [347] 1340 [608]

Water Volume (Source)

Gallons (Liters) 0.96 (3.64) 1.33 (5.04) 2.65 (10.02) 3.50 (13.27) 6.72 (25.44)

Dual isolated compressor mountingBalanced port expansion valve (TXV)Insulated Source and Load Water Coils standardInsulated Refrigerant Circuit standardCompressor on (green) and fault (red) light

Unit Maximum Water Working PressureOptions Max Working Pressure PSIG [kPa]

Base Unit 300 [2,068]

Page 7: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

7c l i m a t e m a s t e r . c o m

TMW036 - 120 - Unit Dimensional Data

Water to Water

Overall CabinetWater Connections

Electric Access Plugs1 2 3 4 5 6

ADepth

BWidth

CHeight

DSource

(Outdoor) Water In

E Source

(Outdoor) Water Out

FLoad

(Indoor) Water In

G Load

(Indoor) Water Out

H HWG

Water In

J HWG Water Out

K Low

Voltage

L External

Pump

M Power Supply

036-060in. 30.6 25.4 33 2.7 9.4 19.4 24.5 27.9 30.4 20.9 22.9 30.9

cm. 77.8 64.5 83.8 6.9 23.9 49.3 62.2 70.9 77.2 53.1 58.2 78.5

120in. 30.6 52.9 37 25.2 25.2 30.1 30.1 34.9 34.9 29.9 31.9 34.4

cm. 77.8 134.4 94 64.0 64.0 76.5 76.5 88.6 88.6 75.9 81.0 87.4

Notes:

1. Front & side access is preferred for service access. However, all

components may be serviced from the front access panel if side

access is not available.

2. While clear access to all removable panels is not required,

installer should take care to comply with all building codes and

allow adequate clearance for future field services.

Page 8: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

8 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

TMW170 & 340 - Unit Dimensional Data

12.3[313]

15.0[381]

4.5[114]

4.3[108]

Power Supply Wiring 1.375 x 2.0[ 34.9 x 50.8] Double KO

4.3[108]

Control Wiring 1.125 x 1.375[ 28.6 x 34.9] Double KO

4.5[114]

2” IPT Water Connections

15.0[381]

5.4[138]

21.0[533]

Fault/Run Lights

64.5[1638]

LeftSideView

FrontView

TopView

Load Source

Side

Refrig.CircuitAccessPanel

Front

CompressorAccessPanel

ElectricalAccessPanel

HeaderAccessPanel

Top

Notes: 1. Dimensions shown in inches and [millimeters].2. For multiple units placed side by side, allow sufficient space front or back to remove unit.

Minimum3ft. [91cm]

Required ServiceAccessNOTE 2

45.1[1146]

26.3[669]

Optional (Single Unit)3ft. (91cm) Additional

Service Access

Page 9: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

9c l i m a t e m a s t e r . c o m

Unit Installation

Installation of Supply and Return PipingFollow these piping guidelines.1. Install a drain valve at the base of each supply and

return riser to facilitate system fl ushing.2. Install shut-off / balancing valves and unions at each

unit to permit unit removal for servicing.3. Place strainers at the inlet of each system

circulating pump.4. Select the proper hose length to allow slack between

connection points. Hoses may vary in length by +2% to -4% under pressure.

5. Exceeding the minimum bend radius may cause the hose to collapse which reduces water fl ow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum and causes a slight kink.

PIPING INSTALLATION

Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient temperature. Insulation is required if loop water temperature drops below the dew point.

Pipe joint compound is not necessary when Tefl on threaded tape is pre-applied to hose assemblies or when fl ared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the pipe threads of the fi tting adapters. Prevent sealant from reaching the fl ared surfaces of the joint.

TMW Unit Location - These units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs.

The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the Installing Contractor to determine and comply with ALL applicable codes and regulations.

Locate the unit in an indoor area that allows easy removal of access panels, and has enough space for service personnel to perform maintenance or repair. Provide suffi cient room to make water and electrical connections.. Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. These units are not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate in areas where ambient conditions are not maintained within 40-100°F [4-38°C].

WARNING! WARNING! Piping must comply with all applicable codes.

WARNING! WARNING! Do not bend or kink supply lines or hoses.

Note: When anti-freeze is used in the loop, assure that it is compatible with Tefl on tape or pipe joint compound employed.

Maximum allowable torque for brass fi ttings is 30 ft-lbs [41 N-m]. If a torque wrench is not available, tighten fi nger-tight plus one quarter turn. Tighten steel fi ttings as necessary.

Page 10: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

10 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Piping Installation

TMW Unit Load Plumbing - The applications are too varied to describe in this document. However, some basic guidelines will be presented. Much of the discussions on water loop applications would be valid for the load plumbing discussion as well. All plumbing should conform to local codes with the following considerations:

Wide temperature variation applications such as heating/cooling coils: - Employ piping materials that are rated for the

maximum temperature and pressure combination. This excludes PVC for most heating applications.

- Insure that load water fl ow in high temperature heating applications is at least 3 gpm per ton [3.9 l/m per kW] to improve performance and reduce nuisance high pressure faults.

- DO NOT employ plastic to metal threaded joints- Utilize a pressure tank and air separator vent system

to equalize pressure and remove air..

Swimming Pool Hot Tub Applications:- Load coax should be isolated with secondary heat

exchanger constructed of anti-corrosion material in all chlorine/bromine fl uid applications.

Potable Water Applications:- Load coax material should always be vented double

walled for use in potable water systems.- Insure load water fl ow in high temperature heating

applications is at least 3 gpm per ton to improve performance and reduce nuissance to high pressure faults.

LOAD PLUMBING INSTALLATION

Optional pressure-rated hose assemblies designed specifi cally for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.

Refer to Figure 1 for an illustration of a Supply/Return Hose Kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life. CAUTION!

CAUTION! Corrosive system water requires corrosion resistant fi ttings and hoses and possibly water treatment.

Figure 2: Typical Water Loop Application

Load Connections(Hot Water/Chilled Water)

Source Connections(Boiler/Tower, Geothermal Loop)

Power Disconnect

Figure 1: Supply/Return Hose Kit

Rib Crimped

Length(0.6m Length Standard)

SwivelBrassFitting

BrassFitting

MPTMPT

Note: The manufacturer strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any fi nishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system. The manufacturer will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.

WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.

WARNING!

Page 11: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

11c l i m a t e m a s t e r . c o m

Water-Loop Heat Pump Applications

Commercial systems typically include a number of units plumbed to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system, therefore air elimination equipment is a major portion of the mechanical room plumbing. In piping systems expected to utilize water temperatures below 50°F [10°C], 1/2" [13mm] closed cell insulation is required on all piping surfaces to eliminate condensation. Metal to plastic threaded joints should never be employed due to their tendency to leak over time. Tefl on tape thread sealant is recommended for FPT water connections (commercial class) to minimize internal fouling of the heat exchanger. Do not overtighten connections and route piping so as not to interfere with service or maintenance access. Hose kits are available from ClimateMaster in different confi gurations as shown in Figure 2 for connection between the TMW Series and the piping system. The hose kits include shut off valves, P/T plugs for performance measurement, high pressure stainless steel braid hose, "Y" type strainer 20 mesh (841 micron) [0.84mm]) with blowdown valve, and "J" type swivel connection. Balancing valves to facilitate the balancing of the system, and an external low pressure drop solenoid valve for use in variable speed pumping systems, may also be included in the hose kit. The piping system should be fl ushed to remove dirt, piping chips, and other foreign material prior to operation. See Piping System Cleaning and Flushing Procedures later in this document. The fl ow rate is usually set between 2.25 gpm and 3 gpm per ton [2.9 l/m and 4.5 l/m per kW] of cooling capacity. ClimateMaster recommends 2.5 gpm

Air Pad or Extruded polystyrene insulation board

Unit Power

Disconnect

Pressure Tank

FlowRegulatorWater

Control Valve

P/T Plugs

Water Out

Shut-OffValve

Boiler Drains

Water In

Optional Filter

Thermostat Wiring

WARNING!

CAUTION! CAUTION! Many units are installed with a factory or fi eld supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any fi eld provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The fi eld installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal fl are connection as part number 39B0005N02.

per ton [3.2 l/m per kW] for most applications of water loop heat pumps. To insure proper maintenance and servicing, P/T ports are imperative for temperature and fl ow verifi cation, as well as performance checks.

Cooling Tower/Boiler Systems typically utilize a common loop maintained 60-90°F [16-32°C]. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and fi ltering will be necessary.

Low Water Temperature Cutout Setting - CXM or DXM Control: When an antifreeze is selected, the LT1 jumper (JW3) should be clipped to select the low temperature (Antifreeze 15°F [-9.4°C]) setpoint to avoid nuisance faults. See Figure 4: Low Water Temperature Cutout - LT1.

WARNING! Never jumper terminal “A” from CXM or DXM board #1 to CXM or DXM board #2 on multi-compressor/control bound units. See Figure 5 in electrical section of this document for motorized valve wiring.

Figure 3: Typical Open Loop/Well Application

Page 12: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

12 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Ground-Water Heat Pump Applications

Typical open loop piping is shown in Figure 3. Shut off valves should be included in case of servicing. Boiler drains or other valves should be ‘tee’d’ into the line to allow acid fl ushing of just the heat exchanger. Pressure temperature plugs should be used so that fl ow and temperature can be measured. Supply and return water piping materials should be limited to copper, PE, or similar material. PVC or CPVC should never be used as they are incompatible with the POE oils used in HFC-410A products and piping system failure and property damage may result.

Table 1: Water Quality Standards

Water QualityParameter

HXMaterial

ClosedRecirculating Open Loop and Recirculating Well

Scaling Potential - Primary Measurement

pH/Calcium HardnessAll

-pH < 7.5 and Ca Hardness <100ppm

Method

Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)

RyznarAll

- 6.0 - 7.5Stability Index If >7.5 minimize steel pipe use.

Langelier All- -0.5 to +0.5

Saturation Index If <-0.5 minimize steel pipe use. Based upon 66°C HWG andDirect well, 29°C Indirect Well HX

Iron FoulingIron Fe 2+ (Ferrous) All

- <0.2 ppm (Ferrous)(Bacterial Iron potential) If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.

Iron Fouling All- <0.5 ppm of Oxygen

Above this level deposition will occur .

Corrosion Prevention

pH All6 - 8.5 6 - 8.5

Monitor/treat asneeded Minimize steel pipe below 7 and no open tanks with pH <8

Hydrogen Sulfide (H2S) All- <0.5 ppm

At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.Rotten egg smell appears at 0.5 ppm level.

Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.Ammonia ion as hydroxide, chloride, nitrate and sulfate compounds All - <0.5 ppm

Maximum

Maximum Allowable at maximum water temperature.

Chloride Levels

10 C 24 C 38 CCopper

Cupronickel- <20ppm NR NR- <150 ppm NR NR

304 SS - <400 ppm <250 ppm <150 ppm316 SS - <1000 ppm <550 ppm < 375 ppm

Titanium - >1000 ppm >550 ppm >375 ppm

Erosion and Clogging

Particulate Size andErosion

All

<10 ppm of particlesand a maximumvelocity of 1.8 m/sFiltered for maximum841 micron [0.84 mm,20 mesh] size.

<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,20 mesh] size. Any particulate that is not removed can potentiallyclog components.

Notes:

Rev.: 5/6/2014 S

• NR - Application not recommended.• "-" No design Maximum.

• Closed Recirculating system is identified by a closed pressurized piping system.• Recirculating open wells should observe the open recirculating design considerations.

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below

Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use. A monitoring plan should be implemented.

The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger and any other components damaged by a leak.

WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.

WARNING!

Page 13: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

13c l i m a t e m a s t e r . c o m

Water quantity should be plentiful and of good quality. Consult Table 1 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Copper is recommended for closed loop systems and open loop ground water sys-tems that are not high in mineral content or corrosive-ness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended.

In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. It is recommended to install an intermediate heat exchanger to isolate an open loop from the heat pump loop on open well systems. Heat exchangers may over time lose heat exchange capabilities due to a build up of mineral deposits inside. These can be cleaned only by a qualifi ed service mechanic as acid and special pumping equipment are required.

In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid fl ushing.

Expansion Tank and Pump - Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. The expansion tank should be sized to handle at least one minute run time of the pump to prevent premature pump failure using its drawdown capacity rating. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways depending on local building codes; i.e. recharge well, storm sewer, drain fi eld, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.

Low Water Temperature Cut-Out Setting - For all open loop systems the 35°F [1.7°C] LT1 setting (factory setting-water) should be used to avoid freeze damage to the unit. See Figure 4: “Low Water Temperature Cutout - LT1”.

CAUTION! CAUTION! Low temperature limit system will not allow leaving load water temperature (cooling mode) or leaving source water temperature (heating mode) to be below 42°F [5.6°C].

WARNING!

CAUTION! CAUTION! Many units are installed with a factory or fi eld supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any fi eld provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The fi eld installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal fl are connection as part number 39B0005N02.

Water Control Valve - Note the placement of the water control valve. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Pilot operated or Taco slow closing valve’s solenoid valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance the Taco slow closing valve can draw up to 35VA. This can overload smaller 40 or 50 VA transformers depending on the other controls employed. A typical pilot operated solenoid valve draws approximately 15VA.

Flow Regulation - Flow regulation can be accomplished by two methods. First, most water control valves have a built in fl ow adjustment. By measuring the pressure drop through the unit heat exchanger, fl ow rate can be determined and compared to Tables 7 and 8. Since the pressure is constantly varying, two pressure gauges might be needed. Simply adjust the water control valve until the desired fl ow of 1.5 to 2 gpm per ton is achieved. Secondly, a fl ow control device may be installed. The devices are typically an orifi ce of plastic material that is designed to allow a specifi ed fl ow rate. These are mounted on the outlet of the water control valve. On occasion, these valves can produce a velocity noise that can be reduced by applying some back pressure. This is accomplished by slightly closing the leaving isolation valve of the well water setup.

WARNING! Never jumper terminal “A” from CXM or DXM board #1 to CXM or DXM board #2 on multi-compressor/control bound units. See Figure 5 in electrical section of this document for motorized valve wiring.

Page 14: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

14 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Ground-Loop Heat Pump Applications

Pre-Installation - Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.

Piping Installation - All earth loop piping materials should be limited to only polyethylene fusion for inground sections of the loop. Galvanized or steel fi tting should not be used at any time due to their tendency to corrode. All plastic

to metal threaded fi ttings should be avoided due to their potential to leak in earth coupled applications and a fl anged fi tting substituted. P/T plugs should be used so that fl ow can be measured using the pressure drop of the unit heat exchanger in lieu of other fl ow measurement means. Earth loop temperatures can range between 25 to 110°F [-4 to 43°C], and 2.25 to 3 gpm of fl ow per ton [2.9 l/m to 3.9 l/m per kW] of cooling capacity is recommended in these applications. Upon completion of the ground loop piping, pressure test the loop to assure a leak free system. Horizontal Systems: Test individual loops as installed. Test entire system when all loops are assembled. Vertical U-Bends and Pond Loop Systems: Test Vertical U-bends and pond loop assemblies prior to installation with a test pressure of at least 100 psi [689 kPa].

Flushing the Earth Loop - Upon completion of system installation and testing, fl ush the system to remove all foreign objects and purge to remove all air. Flush the loop fi rst with the unit isolated to avoid fl ushing debris from the loop into the unit heat exchanger.

Table 2: Antifreeze Percentages by Volume

Antifreeze - In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, anti-freeze is needed. Alcohols and glycols are commonly used as antifreezes, however your local sales manager should be consulted for the antifreeze best suited to your area. Low temperature protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and low temperature protection should be at 15°F [-10°C] e.g. 30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. All alcohols should be premixed and pumped from a res er voir outside of the

building when possible or introduced under water level to prevent fuming. Initially calculate the total volume of fl uid in the piping system. Then use the percentage by volume shown in Table 2 for the amount of an ti freeze. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specifi c gravity.

Low Water Temperature Cut-Out Setting - CXM or DXM Control: When an an ti freeze is se lect ed, the LT1 jumper [JW3] should be clipped to select the low tem per a ture (An ti freeze 15°F [-9.4°C]) setpoint to avoid nuisance faults. See Figure 4.

CAUTION! CAUTION! The following instructions represent industry accepted installation practices for Closed Loop Earth Coupled Heat Pump Systems. They are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State and Local Codes MUST be followed and installation MUST conform to ALL applicable Codes. It is the responsibility of the Installing contractor to determine and comply with ALL applicable Codes and Regulations.

TypeMinimum Temperature for Low Temperature Protection

10°F [-12.2°C] 15°F [-9.4°C] 20°F [-6.7°C] 25°F [-3.9°C]

Methanol100% USP food grade Propylene GlycolEthanol*

25%38%29%

21%25%25%

16%22%20%

10%15%14%

* Must not be denatured with any petroleum based product

Page 15: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

15c l i m a t e m a s t e r . c o m

WARNING!

CAUTION! CAUTION! Many units are installed with a factory or fi eld supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any fi eld provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The fi eld installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal fl are connection as part number 39B0005N02.

WARNING! Never jumper terminal “A” from CXM or DXM board #1 to CXM or DXM board #2 on multi-compressor/control bound units. See Figure 5 in electrical section of this document for motorized valve wiring.

ELECTRICAL LINE VOLTAGE

All fi eld installed wiring, including electrical ground, must comply with the National Electrical Code as well as all applicable local codes.

Refer to the unit wiring diagrams for fuse sizes and a schematic of the fi eld connections which must be made by the installing (or electrical) contractor.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. All fi nal electrical connections must be made with a length of fl exible conduit to minimize vibration and sound transmission to the building.

General Line Voltage Wiring - Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.

TMW Power Connection - Line voltage connection is made by connecting the incoming line voltage wires to L1, L2, and L3 on power distribution block. Consult electrical data table for correct fuse size.

208 Volt Operation - All 208-230 Volt units are factory wired for 208 Volt. The transformers may be switched to 230V operation as illustrated on the wiring diagram by switching the Red (208V) and the Orange (230V) at the contactor terminal L2.

WARNING! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION! CAUTION! Use only copper conductors for fi eld installed electrical wiring. Unit terminals are not designed to accept other types of conductors.

WARNING! WARNING! Disconnect electrical power source to prevent injury or death from electrical shock.

Water Control Valve - Note the placement of the water control valve. Always maintain water pressure in the heat exchanger by installing water control valves at the source out of the unit to prevent mineral precipitation. Position water high pressure switch between unit and valve. Pilot operated or slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, some slow closing valves can draw up to 35VA. This can overload smaller transformers depending on the other controls employed. A typical pilot operated solenoid valve draws approximately 15VA.

Flow Regulation - Install on source in of unit. Flow regulation can be accomplished by two methods. First, most water control valves have a built in fl ow adjustment. By measuring the pressure drop through the unit heat exchanger, fl ow rate can be determined and compared to Table 6. Since the pressure is constantly varying, two pressure gauges might be needed. Simply adjust the water control valve until the desired fl ow of 2.5 to 3 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. Secondly, a fl ow control device may be installed. The devices are typically an orifi ce of plastic material that is designed to allow a specifi ed fl ow

rate. These are mounted on the outlet of the water control valve. On occasion, these valves can produce a velocity noise that can be reduced by applying some back pressure. This is accomplished by slightly closing the leaving isolation valve of the well water setup.

Page 16: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

16 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Electrical - Line Voltage

TMW Electrical Data

ELECTRICAL - LOW VOLTAGE

Thermostat Connections - The aquastat/thermostat should be wired directly to the CXM/DXM board #1. Note: The TMW second stage is wired directly to the CXM #2.

Low Water Temperature Cutout - LT1 - The CXM/DXM control allows the fi eld selection of source fl uid low temperature cutout points. The factory setting of LT1 is set for water (35°F [1.7°C]). In cold temperature applications jumper JW3 (LT1- antifreeze 15°F [-9.4°C]) should be clipped as shown in Figure 4 to change the setting to 10°F [-12.2°C], a more suitable temperature when using antifreezes. Never clip JW3 prior to antifreeze being added to the loop.

LT1LT2

Figure 4: Changing LT1-Low Water Temperature Cutout Setpoint

CXM PCB

JW3-LT1 jumper should be clipped when antifreeze is used.

Model Voltage Code Voltage Voltage Min/

MaxCompressor Total Unit

FLAMin Circuit

Amps

Max Fuse/HACRQty RLA LRA

TMW036

G 208-230/60/1 187/254 1 16.7 79 16.7 20.8 35E 265/60/1 239/292 1 13.5 72 13.5 16.8 30H 208-230/60/3 187/254 1 10.4 73 10.4 13.1 20F 460/60/3 414/506 1 5.8 38 5.8 7.2 15N 575/60/3 518/633 1 3.8 36.5 3.8 4.7 15V 220-240/50/1 198/264 1 13.5 67 13.5 16.9 30U 380-420/50/3 342/462 1 5.4 38 5.4 6.8 15

TMW060 B

G 208-230/60/1 187/254 1 26.3 134 26.3 32.9 50H 208-230/60/3 187/254 1 15.6 110 15.6 19.5 35F 460/60/3 414/506 1 7.8 52 7.8 9.8 15N 575/60/3 518/633 1 5.8 38.9 5.8 7.3 15U 380-420/50/3 342/462 1 7.8 51.5 7.8 9.8 15

TMW120 B

G 208-230/60/1 187/254 2 26.3 134 52.6 59.2 80H 208-230/60/3 187/254 2 15.6 110 31.2 35.1 50F 460/60/3 414/506 2 7.8 52 15.6 17.6 25N 575/60/3 518/633 2 5.8 38.9 11.6 13.1 15U 380-420/50/3 342/462 2 7.8 51.5 15.6 17.6 25

TMW170

H 208-230/60/3 187/254 1 53.6 245 53.6 67.0 110F 460/60/3 414/506 1 20.7 125 20.7 25.9 45N 575/60/3 518/633 1 16.4 100 16.4 20.5 35U 380-420/50/3 342/462 1 20.7 118 20.7 25.9 45

TMW340

H 208-230/60/3 187/254 2 53.6 245 107.2 120.6 150F 460/60/3 414/506 2 20.7 125 41.4 46.6 60N 575/60/3 518/633 2 16.4 100 32.8 36.9 50U 380-420/50/3 342/462 2 20.7 118 41.4 46.6 60

Page 17: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

17c l i m a t e m a s t e r . c o m

WARNING!

CXM/DXM, LONWORKS, OR MPC CONTROL OPERATION

Note: See CXM AOM (part #97B0003N12), DXM AOM (part #97B0003N13), Lon Controller AOM (part #97B0013N01) or MPC Controller AOM (part #97B0031N01) on the web at climatemaster.com

ALL wiring diagrams are available at climatemaster.com

Figure 5: Field Wiring of 24 Volt Motorized Valve for Units Size 120-340

Electrical - Accessories

Coil

VR 1

6 8

RefrigerantHP SwitchCircuit #1

VR3NO

RED RED

Coil

Valve Relay 3

WaterHigh PressureSwitch NC

Notes - Disconnect red wire at refrigerant HP switch connect to N.O. contact, connect new red wire from N.O. contact to refrigerant HP switch.Valve Relay 1, 2 - 13B0001N01 (SPDT) VR1, VR2Valve Relay 3 - 13B0004N01 (DPDT) VR3

Coil

6 8

RefrigerantHP SwitchCircuit #1

VR3NO

RED RED

Coil

Valve Relay 3

WaterHigh PressureSwitch NC

Coil

VR2

2 4

RefrigerantHP SwitchCircuit #2

VR3NO

RED RED

,

2 4

RefrigerantHP SwitchCircuit #2

VR3NO

RED RED

WARNING! Never jumper terminal “A” from CXM or DXM board #1 to CXM or DXM board #2 on multi-compressor/control bound units. See Figure 5 in electrical section of this document for motorized valve wiring.

Accessory Connections - A terminal paralleling the compressor contactor coil has been provided on the CXM/DXM control of the TMW line. "A" has been provided to control accessory devices, such as water valves, electronic air cleaners, humidifi ers, etc. Note: This terminal must be used only with 24 Volt signals and not line voltage signals. This signal operates with the compressor contactor. See Figure 8 or the wiring schematic for details.

24 Volt Accessory Wiring

These terminals may be used to power 24 volt water valves on units size 036, 060

CXM/DXM Terminal Strip

Page 18: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

18 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

All fi eld installed wiring, including electrical ground, must comply with the National Electrical Code as well as all applicable local codes.

Refer to the unit wiring diagrams for fuse sizes and a schematic of the fi eld connections which must be made by the installing (or electrical) contractor.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup.

All fi nal electrical connections must be made with a length of fl exible conduit to minimize vibration and sound transmission to the building.

208 Volt Operation - All 208-230 Volt units are factory wired for 208 Volt. The transformers may be switched to 230V operation as illustrated on the wiring diagram. By switching the Red (230V) and the Orange (208V) at the contactor terminal L2.

Electrical - Line Voltage

L2

L3

L1

Contactor -C

Grnd

ALL wiring diagrams available at climatemaster.com

TMW120 Series Line Voltage Field Wiring Commercial Class

TMW036-060 Series Line Voltage Field Wiring Commercial Class (3 phase shown)

Page 19: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

19c l i m a t e m a s t e r . c o m

Electrical - Low Voltage

Thermostat Connections - The aquastat/thermostat should be wired directly to the CXM/DXM board as shown in Figure 6a for TMW036-060 and Figure 6b for the TMW120. Note the TMW second stage is wired directly to the CXM #2.

Low Water Temperature Cutout - LT1 - The CXM/DXM control allows the fi eld selection of source fl uid low temperature cutout points. The factory setting of LT1 is set for water (30°F). In cold temperature applications jumper JW3 (LT1- antifreeze 10°F) should be clipped as shown in Figure 7 to change the setting to 10°F, a more suitable temperature when using antifreezes. It should be noted that the extended range option should be specifi ed to operate the TMW Series at entering water temperatures below 60°F.

Figure 6a. TMW036-060 Low Voltage Field Wiring (CXM shown)

Figure 6b: TMW120 Low Voltage Field Wiring (CXM shown)

Figure 7: Changing LT1-Low Water Temperature Cut-out Setpoint

LT1LT2

JW3-LT1 jumper should be clipped when antifreeze is used.

CXM Board

Capacitor

Transformer

CXM Control

Contactor -CC

Low VoltageConnector

CB

L2

L1

Low Voltage Wiring

Contactor -CC1

Transformer

Grnd

L2 L3L1

Contactor -CC2

CXM Control #2

Power Distribution Block

CXM Control #1

Low Voltage Wiring

Second Stage Call (Not needed on DXM Models all low voltage wires to DXM #1)

Low VoltageConnector

Low VoltageConnector

Page 20: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

20 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

TMW Series Wiring Diagram Matrix

Representative diagrams in bold are presented in this Installation Manual. All diagrams can be located online at climatemaster.com using the part numbers below.

Model RefrigerantWiring

Diagram Part Number

Electrical Control DDC Agency Electrical Agency Type

TMW036-060 EarthPure HFC-410A

96B0116N01 208-230/60/1

CXM

- ETL

ResidentialLON ETL

MPC ETL

96B0116N02 208-230/60/1, 265/60/1 (TMW036 ONLY)

- ETL

220-240/50/1

NO

CommercialLON ETL NO

MPC ETL NO

96B0116N03 208-230/60/3, 460/60/3, 575/60/3

- ETL

380-420/50/3

NO

CommercialLON ETL NO

MPC ETL NO

96B0116N04 220-240/50/1 (TMW036 ONLY)

- CE -

ResidentialLON CE -

MPC CE -

96B0116N05 380-420/50/3

- CE -

CommercialLON CE -

MPC CE -

96B0116N11 208-230/60/1 (TMW060 ONLY)

- ETL

220-240/50/1

NO

CommercialLON ETL NO

MPC ETL NO

96B0116N06 208-230/60/1

DXM

- ETL

ResidentialLON ETL

MPC ETL

96B0116N07 208-230/60/1, 265/60/1 (TMW036 ONLY)

- ETL

220-240/50/1

NO

CommercialLON ETL NO

MPC ETL NO

96B0116N08 208-230/60/3, 460/60/3, 575/60/3

- ETL

380-420/50/3

NO

CommercialLON ETL NO

MPC ETL NO

96B0116N09 220-240/50/1 (TMW036 ONLY)

- CE -

ResidentialLON CE -

MPC CE -

96B0116N10 380-420/50/3

- CE -

CommercialLON CE -

MPC CE -

96B0116N12 208-230/60/1 (TMW060 ONLY)

- ETL

CommercialLON ETL

MPC ETL

Table Continued on Next Page

Page 21: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

21c l i m a t e m a s t e r . c o m

Model RefrigerantWiring

Diagram Part Number

Electrical Control DDC Agency Electrical Agency Type

TMW120 EarthPure HFC-410A

96B0117N01 208-230/60/1

CXM

- ETL

Commercial

LON ETL

MPC ETL

96B0117N02 208-230/60/3, 460/60/3, 575/60/3

- ETL

380-420/50/3

NO

LON ETL NO

MPC ETL NO

96B0117N03 380-420/50/3

- CE -

LON CE -

MPC CE -

96B0117N04 208-230/60/1

DXM

- ETL

LON ETL

MPC ETL

96B0117N05 208-230/60/3, 460/60/3, 575/60/3

- ETL

380-420/50/3

NO

LON ETL NO

MPC ETL NO

96B0117N06 380-420/50/3

- CE -

LON CE -

MPC CE -

TMW170

EarthPure HFC-410A

96B0112N01

208-230/60/3, 460/60/3, 575/60/3

CXM

- ETL

380-420/50/3

NO

96B0112N03 LON ETL NO

96B0112N05 MPC ETL NO

96B0112N02

DXM

- ETL NO

96B0112N04 LON ETL NO

96B0112N06 MPC ETL NO

96B0112N07

380-420/50/3

CXM

- CE -

96B0112N08 LON CE -

96B0112N09 MPC CE -

96B0112N10

DXM

- CE -

96B0112N11 LON CE -

96B0112N12 MPC CE -

TMW340

96B0107N01

208-230/60/3, 460/60/3, 575/60/3

CXM

- ETL

380-420/50/3

NO

96B0107N03 LON ETL NO

96B0107N05 MPC ETL NO

96B0107N02

DXM

- ETL NO

96B0107N04 LON ETL NO

96B0107N06 MPC ETL NO

96B0107N07

380-420/50/3

CXM

- CE -

96B0107N08 LON CE -

96B0107N09 MPC CE -

96B0107N10

DXM

- CE -

96B0107N11 LON CE -

96B0107N12 MPC CE -

Representative diagrams in bold are presented in this Installation Manual. All diagrams can be located online at climatemaster.com using the part numbers below.

Page 22: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

22 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Three Phase - TMW 170 Units with CXM Controller

Page 23: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

23c l i m a t e m a s t e r . c o m

Typical Wiring Diagram Three Phase - TMW 340 Units with CXM & MPC Controller

Page 24: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

24 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Three Phase - TMW 340 Units with CXM Controller

Page 25: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

25c l i m a t e m a s t e r . c o m

Typical Wiring Diagram Three Phase - TMW 340 Units with DXM

Page 26: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

26 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Three Phase - TMW 170 Units with DXM Controller

Page 27: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

27c l i m a t e m a s t e r . c o m

Typical Wiring Diagram Three Phase - TMW 170 Units with CXM CE

Page 28: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

28 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Three Phase - TMW 170 Units with DXM CE

Page 29: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

29c l i m a t e m a s t e r . c o m

Typical Wiring Diagram Three Phase - TMW 340 Units with CXM Controller CE

Page 30: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

30 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Three Phase - TMW 340 Units with DXM Controller CE

Page 31: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

31c l i m a t e m a s t e r . c o m

Typical Wiring Diagram Three Phase - TMW 120 Units with CXM Controller

Page 32: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

32 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Typical Wiring Diagram Single Phase - TMW 036 Units

Page 33: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

33c l i m a t e m a s t e r . c o m

DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage 2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.On = Stage 1. Off = Stage 2DIP switch 3: Not Used.DIP switch 4: DDC Output at EH2 - provides selection for DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.On = EH2 Normal. Off = DDC Output at EH2.NOTE: Some CXM controls only have a 2 position DIP switch package. If this is the case, this option can be selected by clipping the jumper which is in position 4 of SW1.Jumper not clipped = EH2 Normal. Jumper clipped = DDC Output at EH2.DIP switch 5: Factory Setting - Normal position is “On.” Do not change selection unless instructed to do so by the factory.

CXM Controls

CXM Control - For detailed control information, see the CXM Application, Operation and Maintenance (AOM) manual (part #97B0003N12).

Field Selectable Inputs - Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the CXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will fl ash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.

Retry Mode: If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash = one fl ash every 2 seconds) to indicate the control is in the process of retrying.

Field Confi guration Options - Note: In the following fi eld confi guration options, jumper wires should be clipped ONLY when power is removed from the CXM control.

Water coil low temperature limit setting: Jumper 3 (JW3-LT1 Low Temp) provides fi eld selection of temperature limit setting for LT1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Air coil low temperature limit setting: Jumper 2 (JW2-LT2 Low Temp) provides fi eld selection of temperature limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by the factory.Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection).Not Clipped = AL2 connected to R. Clipped = AL2 dry contact (no connection).

DIP Switches - Note: In the following fi eld confi guration options, DIP switches should only be changed when power is removed from the CXM control.DIP switch 1: Unit Performance Sentinel Disable - provides fi eld selection to disable the UPS feature.On = Enabled. Off = Disabled.

Table 3a: LED And Alarm Relay Operations

-Slow Flash = 1 fl ash every 2 seconds-Fast Flash = 2 fl ashes every 1 second-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick fl ashes, 10 second pause, etc.-On pulse 1/3 second; off pulse 1/3 second

Description of Operation LED Alarm

Normal Mode ON Open

Normal Mode w/UPS Warning ON Cycle (Closed 5 seconds, Open 25 seconds)

CXM is non-functional OFF OpenFault Retry Slow Flash Open

Lockout Fast Flash Closed

Over/Under Voltage Shutdown Slow Flash Open (Closed after 15 Minutes)

Test Mode - No Fault in Memory Flashing Code 1 Cycling Code 1Test Mode - HP Fault in Memory Flashing Code 2 Cycling Code 2Test Mode - LP Fault in Memory Flashing Code 3 Cycling Code 3Test Mode - LT1 Fault in Memory Flashing Code 4 Cycling Code 4Test Mode - LT2 Fault in Memory Flashing Code 5 Cycling Code 5Test Mode - CO Fault in Memory Flashing Code 6 Cycling Code 6

Test Mode - Over/Under Shutdown in Memory Flashing Code 7 Cycling Code 7

Test Mode - UPS in Memory Flashing Code 8 Cycling Code 8Test Mode - Swapped Thermistor Flashing Code 9 Cycling Code 9

Page 34: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

34 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

DXM Control - For detailed control information, see the DXM AOM (part #97B0003N13), Lon controller AOM (part #97B0013N01) or MPC AOM (part # 97B0031N01).

-Slow Flash = 1 fl ash every 2 seconds-Fast Flash = 2 fl ashes every 1 second-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick fl ashes, 10 second pause, etc.-On pulse 1/3 second; off pulse 1/3 second

Field Selectable Inputs - Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the DXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will fl ash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.Retry mode: If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash = one fl ash every 2 seconds) to indicate the control is in the process of retrying.

Field Confi guration Options - Note: In the following fi eld confi guration options, jumper wires should be clipped ONLY when power is removed from the DXM control.

Water coil low temperature limit setting: Jumper 3 (JW3-LT1 Low Temp) provides fi eld selection of temperature limit setting for LT1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].

Description ofOperation

Status LED(green)

Test LED(yellow)

Fault LED (red)

Alarm Relay

Normal mode On - Off Open

Normal mode with UPS On - Flashing Code 8 Cycle (closed 5 sec,open 25 sec)

DXM is non-functional Off Off Off OpenFault Retry Slow Flash - Flashing fault code OpenLockout Fast Flash - Flashing fault code ClosedTest Mode - On - -Night Setback Flashing Code 2 - - -ESD Flashing Code 3 - - -

HP Fault Slow Flash - Flashing Code 2 OpenLP Fault Slow Flash - Flashing Code 3 OpenLT1 Fault Slow Flash - Flashing Code 4 OpenLT2 Fault Slow Flash - Flashing Code 5 OpenCO Fault Slow Flash - Flashing Code 6 Open

Over/Under Voltages Slow Flash - Flashing Code 7 Open (closed after 15minutes)

Invalid T-stat Inputs Flashing Code 4 - - -

DXM Controls

Air coil low temperature limit setting: Jumper 2 (JW2-LT2 Low Temp) provides fi eld selection of temperature limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only

be clipped under extenuating circumstances, as recommended by ClimateMaster technical services.Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Alarm relay setting: Jumper 4 (JW4-AL2 Dry) provides fi eld selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection).Not Clipped = AL2 connected to R.Clipped = AL2 dry contact (no connection).Low pressure normally open: Jumper 1 (JW1-LP norm open) provides fi eld selection for low pressure input to be normally closed or normally open.

Not Clipped = LP normally closed. Clipped = LP normally open.

DIP Switches - Note: In the following fi eld confi guration options, DIP switches should only be changed when power is removed from the DXM control.

DIP Package #1 (S1) - DIP Package #1 has 8 switches and provides the following setup selections:1.1 - Unit Performance Sentinel (UPS) disable: DIP Switch 1.1 provides fi eld selection to disable the UPS feature. On = Enabled. Off = Disabled.1.2 - Compressor relay staging operation: DIP 1.2 provides selection of compressor relay staging operation. The compressor relay can be selected to turn on with a stage 1 or stage 2 call from the thermostat. This is used with dual stage units (2 compressors where 2 DXM controls are being used) or with master/slave applications. In master/slave applications, each compressor and fan will stage according to its appropriate DIP 1.2 setting. If set to stage 2, the compressor will have a 3 second on-delay before energizing during a Stage 2 demand. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.On = Stage 1. Off = Stage 2.

Table 3b: DXM LED And Alarm Relay Operations

Page 35: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

35c l i m a t e m a s t e r . c o m

1.3 - Thermostat type (heat pump or heat/cool): DIP 1.3 provides selection of thermostat type. Heat pump or heat/cool thermostats can be selected. When in heat/cool mode, Y1 is the input call for cooling stage 1; Y2 is the input call for cooling stage 2; W1 is the input call for heating stage 1; and O/W2 is the input call for heating stage 2. In heat pump mode, Y1 is the input call for compressor stage 1; Y2 is the input call for compressor stage 2; W1 is the input call for heating stage 3 or emergency heat; and O/W2 is the input call for reversing valve (heating or cooling, depending upon DIP 1.4).On = Heat Pump. Off = Heat/Cool.1.4 - Thermostat type (O/B): DIP 1.4 provides selection of thermostat type for reversing valve activation. Heat pump thermostats with “O” output (reversing valve energized for cooling) or “B” output (reversing valve energized for heating) can be selected with DIP 1.4. On = HP stat with “O” output for cooling. Off = HP stat with “B” output for heating.1.5 - Dehumidifi cation mode: DIP 1.5 provides selection of normal or dehumidifi cation fan mode. In dehumidifi cation mode, the fan speed relay will remain off during cooling stage 2. In normal mode, the fan speed relay will turn on during cooling stage 2.On = Normal fan mode. Off = Dehumidifi cation mode.1.6 - DDC output at EH2: DIP 1.6 provides selection for DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.On = EH2 Normal. Off = DDC Output at EH2.1.7 - Boilerless operation: DIP 1.7 provides selection of boilerless operation. In boilerless mode, the compressor is only used for heating when LT1 is above the temperature specifi ed by the setting of DIP 1.8. Below DIP 1.8 setting, the compressor is not used and the control goes into emergency heat mode, staging on EH1 and EH2 to provide heating. On = normal. Off = Boilerless operation.1.8 - Boilerless changeover temperature: DIP 1.8 provides selection of boilerless changeover temperature set point. Note that the LT1 thermistor is sensing refrigerant temperature between the coaxial heat exchanger and the expansion device (TXV or cap tube). Therefore, the 50°F [10°C] setting is not 50°F [10°C] water, but approximately 60°F [16°C] EWT.On = 50°F [10°C]. Off = 40°F [16°C].

DIP Package #2 (S2) - DIP Package #2 has 8 switches and provides the following setup selections:2.1 - Accessory1 relay personality: DIP 2.1 provides selection of ACC1 relay personality (relay operation/characteristics). See table 6c for description of functionality. 2.2 - Accessory1 relay personality: DIP 2.2 provides selection of ACC 1 relay personality (relay operation/characteristics). See table 6c for description of functionality.2.3 - Accessory1 relay personality: DIP 2.3 provides selection of ACC 1 relay options. See table 6c for description of functionality.2.4 - Accessory2 relay personality: DIP 2.4 provides selection of ACC 2 relay personality (relay operation/characteristics). See table 6c for description of functionality. 2.5 - Accessory2 relay personality: DIP 2.5 provides selection of ACC 2 relay personality (relay operation/characteristics). See table 6c for description of functionality.2.6 - Accessory2 relay personality: DIP 2.6 provides selection of ACC 2 relay options. See table 6c for description of functionality.2.7 - Auto dehumidifi cation fan mode or high fan mode: DIP 2.7 provides selection of auto dehumidifi cation fan mode or high fan mode. In auto dehumidifi cation mode, the fan speed relay will remain off during cooling stage 2 IF the H input is active. In high fan mode, the fan enable and fan speed relays will turn on when the H input is active.On = Auto dehumidifi cation mode. Off = High fan mode.2.8 - Special factory selection: DIP 2.8 provides special factory selection. Normal position is “On.” Do not change selection unless instructed to do so by the factory.

DIP 2.1 DIP 2.2 DIP 2.3 ACC1 Relay OptionOn On On Cycle with fan

Off On On Digital NSB

On Off On Water Valve - slow opening

On On Off OAD

Off Off Off Reheat Option - Humidistat

Off On Off Reheat Option - Dehumidistat

DIP 2.4 DIP 2.5 DIP 2.6 ACC2 Relay OptionOn On On Cycle with compressor

Off On On Digital NSB

On Off On Water Valve - slow opening

On On Off OAD

All other DIP combinations are invalid

Table 3c: Accessory DIP Switch Settings

Page 36: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

36 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Safety Features – CXM/DXM Control - The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor.Note: The 5 minute anti-short cycle also occurs at power up.Random start: The control features a random start upon power up of 5-80 seconds.Fault Retry: In Fault Retry mode, the Status LED begins slowly fl ashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfi ed, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed at the “fault” LED (DXM board) or by going into test mode (CXM board). Note: LT1/LT2 faults are factory set at only one try.Lockout: In lockout mode, the status LED will begin fast fl ashing. The compressor relay is turned off immediately. Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset (disconnecting power to the control) resets the control and erases fault memory.Lockout with emergency heat: While in lockout mode, if W becomes active (CXM), emergency heat mode will occur. If DXM is confi gured for heat pump thermostat type (DIP 1.3), emergency heat will become active if O/W2 is energized.High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor).High pressure lockout code = 2Example: 2 quick fl ashes, 10 sec pause, 2 quick fl ashes, 10 sec. pause, etc.Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The low pressure switch input is bypassed for the initial 120 seconds of a compressor run cycle.

Safety Features - CXM/DXM Controls

Low pressure lockout code = 3Water coil low temperature (LT1): The LT1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT1 fault. The LT1 input is bypassed for the initial 120 seconds of a compressor run cycle. LT1 is set at the factory for one try. Therefore, the control will go into lockout mode once the LT1 fault has occurred.LT1 lockout code = 4Air coil low temperature (LT2): The LT2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT2 fault. The LT2 input is bypassed for the initial 60 seconds of a compressor run cycle. LT2 is set at the factory for one try. Therefore, the control will go into lockout mode once the LT2 fault has occurred.LT2 lockout code = 5Condensate overfl ow: The condensate overfl ow sensor must sense overfl ow level for 30 continuous seconds to be recognized as a CO fault. Condensate overfl ow will be monitored at all times.CO lockout code = 6Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 19VAC to 30VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the CXM/DXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close.Over/under voltage shut down code = 7Unit Performance Sentinel-UPS (patent pending): The UPS feature indicates when the heat pump is operating ineffi ciently. A UPS condition exists when:

a. In heating mode with compressor energized, LT2 is greater than 125°F [52°C] for 30 continuous seconds, or:

b. In cooling mode with compressor energized, LT1 is greater than 125°F [52°C] for 30 continuous seconds, or:

c. In cooling mode with compressor energized, LT2 is less than 40°F [4.5°C] for 30 continuous seconds.

Page 37: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

37c l i m a t e m a s t e r . c o m

If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc.UPS warning code = 8

Swapped LT1/LT2 thermistors: During test mode, the control monitors to see if the LT1 and LT2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout with code 9 after 30 seconds if:

a. The compressor is on in the cooling mode and the LT1 sensor is colder than the LT2 sensor, or:

b. The compressor is on in the heating mode and the LT2 sensor is colder than the LT1 sensor.

Swapped LT1/LT2 thermistor code = 9.

ESD (DXM only): The ESD (Emergency Shut Down) mode can be enabled from an external common signal to terminal ESD to shut down the unit. The green status light will fl ash code 3 when the unit is in ESD mode. ESD mode = code 3 (green “status” LED)

CXM/DXM CONTROLS

Diagnostic Features - The LED on the CXM board advises the technician of the current status of the CXM control. The LED can display either the current CXM mode or the last fault in memory if in test mode. If there is no fault in memory, the LED will fl ash Code 1 (when in test mode).

The green status LED and red fault LED on the DXM board advise the technician of the current status of the DXM control. The status LED will indicate the current mode that the DXM control is in. The fault LED will ALWAYS fl ash a code representing the LAST fault in memory. If there is no fault in memory, the fault LED will fl ash Code 1. The yellow test LED will turn on when in test mode.

CXM/DXM Control Start-up Operation - The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The fi rst time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized. On all subsequent compressor calls, the random start delay is omitted.

Environment -This unit is designed for indoor installation only. Do not install in an area subject to freezing or where humidity levels can cause cabinet condensation.

Power Supply - A voltage variation of +/- 10% of nameplate utilization voltage is acceptable.

Operation and performance is primarily dependent upon water temperatures, water fl ow rates and ambient air temperature. This water to water heat pump is capable of operating over a wide temperature range and with fl ow rates of between 1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however usually no more than one of these factors may be at a minimum or maximum level at a time.

The commissioning table indicates water temperatures which are suitable for initial unit commissioning in an environment where the fl ow rate and water temperature is not yet stable and to avoid nuisance shut down of the units freeze and refrigerant pressure safeties.

The operating table indicates the maximum and minimum ranges of the unit.

For more specifi c unit performance reference the product catalog, the submittal data sheets or contact your supplier for assistance.

BUILDING COMMISSIONINGCooling Heating

Unit Size 036 060/120 170/340 036 060/120 170/340

Source Min/Max 50/110 50/120 50/90 30/80 30/80 50/70

Load Min/Max 60/80 60/90 60/90 60/120 60/120 80/120

Ambient Min/Max 45/110 39/85

BUILDING OPERATINGCooling Heating

Unit Size 036 060/120 170/340 036 060/120 170/340

Source Min/Max 50/120 50/120 50/110 20/80 20/80 20/70

Load Min/Max 50/90 50/90 50/90 60/130 60/130 60/120

Ambient Min/Max 45/110 39/85

Page 38: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

38 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Cleaning and fl ushing of the WLHP piping system is the single most important step to ensure proper start-up and continued effi cient operation of the system.Follow the instructions below to properly clean and fl ush the system:1. Verify electrical power to the unit is disconnected.2. Install the system with the supply hose connected

directly to the return riser valve. Use a single length of fl exible hose.

3. Open all air vents. Fill the system with the water. DO NOT allow system to overfl ow. Bleed all air from the system. Pressurize and check the system for leaks and repair appropriately.

4. Verify all strainers are in place. Start the pumps, and systematically check each vent to ensure all air is bled from the system.

5. Verify make-up water is available. Adjust make-up water appropriately to replace the air which was bled from the system. Check and adjust the water/air level in the expansion tank.

6. Set the boiler to raise the loop temperature to approximately 85°F [29°C]. Open the a drain at the lowest point in the system. Adjust the make-up water replacement rate to equal the rate of bleed.

7. Refi ll the system and add trisodium phosphate in a proportion of approximately one pound per 150 gallons [1/2 kg per 750 L] of water (or other equivalent approved cleaning agent). Reset the boiler to raise the loop temperature to about 100°F [38°C]. Circulate the solution for a minimum of 8 to 24 hours. At the end of this period, shut off the circulating pump and drain the solution. Repeat system cleaning if desired.

8. When the cleaning process is complete, remove the short-circuited hoses. Reconnect the hoses to the proper supply, and return connections to each of the units. Refi ll the system and bleed off all air.

9. Test the system pH with litmus paper. The system water should be slightly alkaline (pH 7.5-8.5). Add chemicals, as appropriate, to maintain acidity levels.

10. When the system is successfully cleaned, fl ushed, refi lled and bled, check the main system panels, safety cutouts and alarms. Set the controls to properly maintain loop temperatures.

CAUTION! CAUTION! To avoid possible damage to a plastic (PVC) piping system, do not allow temperatures to exceed 110°F [43°C].

CAUTION! CAUTION! DO NOT use 'stop leak' or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and inhibit unit operation.

Piping System Cleaning & Flushing

Page 39: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

39c l i m a t e m a s t e r . c o m

LT1LT2

Short test pins together to enter Test Mode and speed-up timing and delays for 20 minutes.

Figure 5: Test Mode Pins

CXM BOARD

UNIT CHECKOUT Balancing/Shutoff Valves: Ensure all isolation valves are open, water control valves wired and open or coax may freeze and burst.

Line Voltage and Wiring: Ensure Voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Low voltage wiring is complete.

Unit Control Transformer: Ensure transformer has properly selected control voltage tap. 208-230V units are factory wired for 208V operation unless specifi ed otherwise.

Entering Water: Ensure entering water temperatures are within operating limits of Table 6.

Low Water Temperature Cutout: Verify low water temperature cut-out on CXM/DXM is properly set.

Water Flow Balancing: Verify inlet and outlet water temperatures on both Load and source are recorded for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water fl ows that can erode heat exchangers.

Unit Controls: Verify CXM or DXM fi eld selection options are proper and complete.

BEFORE POWERING SYSTEM, please check the following:

SYSTEM CHECKOUT System Water Temperature: Check load and source water temperature for proper range and also verify heating and cooling setpoints for proper operation.

System pH: System water pH is 6 - 8.5. Proper pH promotes longevity of hoses and fi ttings. System Flushing: Verify all hoses are connected end to end when fl ushing to ensure debris bypasses unit heat exchanger and water valves etc. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Verify all air is purged from the system. Air in the system can cause poor operation or system corrosion.

Cooling Tower/Boiler: Check equipment for proper setpoints and operation.

Standby Pumps: Verify the standby pump is properly installed and in operating condition.

System Controls: Verify system controls function and operate in the proper sequence.

Low Water Temperature Cutout: Verify low water temperature cut-out controls are provided for the outdoor portion of the loop or operating problems will occur.

System Control Center: Verify control center and alarm panel for proper setpoints and operation.

Strainers: Verify 20 mesh (841 micron) [0.84mm] strainers are installed in load and source water piping. Confi rm maintenance schedule for strainers.

Miscellaneous: Note any questionable aspects of the installation.

WARNING! WARNING! Verify ALL water controls are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.

WARNING! WARNING! To avoid equipment damage, DO NOT leave system fi lled in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.

Unit & System Checkout

Note: The manufacturer strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any fi nishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system. The manufacturer will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.

WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.

WARNING!

Page 40: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

40 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Table 6: Water Temperature Change Through Source Heat Exchanger

Table 7: Coax Water Pressure Drop TMW170/340

Note: Units have a fi ve minute time delay in the control circuit that can be eliminated on the CXM PCB as shown in Figure 5. See controls description for detailed features of the control.

1. Adjust all valves to their full open position. Turn on the line power to all heat pump units.

2. Operate each unit in the cooling cycle. Loop water temperature entering the heat pumps should be between 70°F [21°C] and 110° F [43°C].

3. Operate each heat pump in the heating cycle immediately after checking cooling cycle operation. A time delay will prevent the compressor from re-starting for approximately fi ve (5) minutes.

4. Establish a permanent operating record by logging the unit operating conditions at initial start-up for each unit.

5. If a unit fails to operate, conduct the following checks:a. Check the voltage and current. They should

comply with the electrical specifi cations described on the unit nameplate.

b. Look for wiring errors. Check for loose terminal screws where wire connections have been made on both the line and low-voltage terminal boards.

c. Check the supply and return piping. They must be properly connected to the inlet and outlet connections on the unit.

d. If the checks described above fail to reveal the problem and the unit still will not operate, contact a trained service technician to ensure proper diagnosis and repair of the equipment.

WARNING! WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.

WARNING! WARNING! Verify ALL water controls are open and allow water fl ow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.

Model GPMPressure Drop PSI (FT)

30°F 50°F 70°F 90°F

Source/Outdoor Coax

340355370

1.6 (3.7)4.0 (9.3)

7.2 (16.6)

1.2 (2.7)3.6 (8.3)

6.5 (15.0)

1.0 (2.3)3.3 (7.6)

5.9 (13.6)

0.9 (2.0)3.0 (7.0)5.5 (12.6)

170182735

0.8 (1.9)2.7 (6.3)

4.8 (11.2)

0.4 (1.0)1.7 (3.9)3.3 (7.6)

0.2 (0.4)1.5 (3.4)3.0 (6.9)

0.1 (0.3)1.4 (3.1)2.8 (6.4)

Model l/sPressure Drop kPa

0°C 10°C 20°C 30°CSource/Outdoor Coax

3402.213.344.42

11.0326.8848.95

8.2724.8244.82

7.2223.1041.36

6.2921.2938.47

1701.1

1.672.21

4.8217.9232.40

2.7611.7222.75

1.7211.3821.37

.889.4719.30

Water Flow, gpm [l/m]Rise, Cooling

°F, [°C]Drop, Heating

°F, [°C]

For Closed Loop: Ground Source or Closed Loop Systems at 3 gpm per

ton [3.9 l/m per kW]

9 - 12[5 - 6.7]

4 - 8[2.2 - 4.4]

For Open Loop: Ground Water Systems at 1.5 gpm per ton

[2.0 l/m per kW]

20 - 26[11.1 - 14.4]

10 - 17[5.6 - 9.4]

Unit Start Up Procedure

Table 8: Coax Water Pressure Drop TMW036-120

Model GPMPressure Drop PSI

30°F 50°F 70°F 90°F

Source/Outdoor Coax

0364.56.89.0

1.74.17.1

1.33.46.0

1.02.85.1

0.82.44.5

0607.5

11.315.0

1.54.06.9

1.33.46.2

1.13.05.5

0.92.75.0

12015.022.530.0

1.74.47.6

1.43.86.8

1.23.36.1

0.92.75.0

Load/Outdoor Coax

0364.56.89.0

0.61.42.6

0.51.32.4

0.31.12.2

0607.5

11.315.0

1.43.56.2

1.33.25.8

1.23.05.5

12015.022.530.0

1.63.86.8

1.43.56.4

1.33.36.0

Must use antifreeze if operation falls in grey area Operation not recommdedMultiply PSI x 2.31 to determine ft of hd

Page 41: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

41c l i m a t e m a s t e r . c o m

Operating Pressures

TMW036-340 (TMW120, 340 Per Circuit)

Source Entering

Water Temp ºF

Source Water Flow

GPM/ton

Cooling

Load EWT F @ 1.5-3.0 GPM/Ton

Suction Pressure

PSIG

Discharge Pressure

PSIGSuper-heat Sub-cooling

Water Temp Rise ºF Source

Water Temp Drop ºF

Load

50

1.5

50 99-106 230-234 11-18 18-25

20-28

7-1560 111-122 241-243 11-18 18-25 8-1770 122-137 251-253 17-25 18-25 8-1980 126-145 254-258 26-35 18-25 9-20

2.3

50 98-105 212-214 18-23 14-20

13-18

7-1560 106-117 218-220 18-23 14-20 8-1770 114-129 225-227 24-32 14-20 9-1980 117-135 228-230 32-41 14-20 9-20

3.0

50 87-101 199-203 12-18 12-18

9-12

8-1660 91-113 203-207 12-18 12-18 8-1770 95-124 204-216 16-34 12-18 9-1980 107-128 212-217 33-35 12-18 9-20

80

1.5

50 104-111 343-348 9-14 18-25

19-28

7-1460 121-132 355-360 9-14 18-25 7-1670 138-152 367-373 9-14 18-25 8-1880 148-161 377-381 12-23 18-25 9-20

2.3

50 103-111 320-325 8-14 14-21

13-18

7-1460 118.-129 328-334 8-14 14-21 8-1670 132-147 336-344 12-20 14-21 8-1880 140-172 343-353 19-29 14-21 9-20

3.0

50 94-110 305-314 9-13 12-18

8-12

7-1560 112-121 313-319 9-13 12-18 8-1670 121-146 317-329 12-20 12-18 9-1880 131-151 324-333 18-27 12-18 9-20

110

1.550 109-116 483-497 9-13 17-23

18-265-11

60 128-135 494-511 9-13 17-23 6-1370 147-154 505-525 9-13 17-23 7-15

2.350 109-116 459-473 9-13 15-20

14-175-11

60 127-135 466-484 9-13 15-20 6-1370 153-159 473-495 9-13 15-20 7-15

3.0

50 100-112 444-431 9-14 12-17

8-13

5-1260 120-130 449-467 9-14 12-17 6-1470 131-152 454-474 9-14 12-17 7-1580 153-164 463-479 13-21 12-17 8-17

Page 42: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

42 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

TMW036-340 (TMW120, 340 Per Circuit)

Source Entering

Water Temp ºF

Source Water Flow

GPM/ton

Heating

Load EWT F @ 1.5-3.0 GPM/Ton

Suction Pressure

PSIG

Discharge Pressure

PSIGSuper-heat Sub-cooling

Water Temp Drop ºF Source

Water Temp Rise ºF Load

20 3.0

60 56-63 199-228 4-14 6-14

2-6

5-1480 58-65 286-297 4-14 6-14 5-1490 59-66 310-344 4-14 6-14 4-14

100 61-65 360-385 4-14 6-14 4-14120 64-69 459-510 4-14 6-14 4-13

50

1.5

60 85-95 212-224 6-11 7-11

9-16

6-1780 91-99 290-310 6-11 7-11 6-1790 92-101 326-338 6-11 7-11 6-17

100 96-103 381-399 6-11 7-11 5-17120 100-108 474-488 6-11 7-11 4-16

2.3

60 95-102 215-228 6-13 7-11

6-12

7-1880 98-106 299-313 6-13 7-11 6-1890 99-108 329-341 6-13 7-11 6-18

100 102-110 384-401 6-13 7-11 6-17120 106-114 475-491 6-13 7-11 5-17

3.0

60 95-107 215-256 6-14 7-15

5-9

7-1980 101-110 310-326 6-14 7-15 7-1990 103-112 329-376 6-14 7-15 6-19

100 105-114 399-414 6-14 7-15 6-18120 108-118 476-524 6-14 7-15 5-17

80

1.5

60 109-129 225-237 14-26 5-14

15-21

8-1880 123-138 314-327 14-26 5-14 8-1990 130-142 343-357 10-15 5-14 7-19

100 137-147 402-415 10-15 5-14 7-19120 150-157 493-504 10-15 5-14 6-20

2.3

60 111-132 227-239 14-38 6-15

10-15

8-2080 135-147 315-330 14-38 6-15 8-2090 143-152 344-360 10-16 6-15 8-20

100 145-154 405-418 10-16 6-15 7-20120 156-163 494-507 10-16 6-15 6-20

3.0

60 110-149 227-279 19-44 6-18

7-12

9-2180 135-150 286-332 19-44 6-18 8-2190 145-166 345-408 13-23 6-18 8-21

100 148-158 405-420 13-23 6-18 8-21

Page 43: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

43c l i m a t e m a s t e r . c o m

Heat Exchanger Maintenance - (Direct Ground Water Applications Only)If the installation is performed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the heat exchanger material or copper water lines. Generally, the more water fl owing through the unit the less chance for scaling therefore 2.5 gpm per ton [2.0 l/m per kW] is recommended as a minimum fl ow.

Heat Exchanger Maintenance - (All Other Water Loop Applications) Generally water coil maintenance is not needed however, if the installation is located in a system with a known high dirt or debris content, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. These dirty installations are a result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with both the heat exchanger material and copper water lines. Generally, the more water fl owing through the unit, the less chance for scaling, however fl ow rates over 3 gpm per ton [3.9 l/m per kW] can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.Clean or replace 20 mesh (841 micron) [0.84mm] strainer/fi lters on a timely schedule.

Compressors - Conduct annual amperage checks to ensure amp draw is no more than 10% greater than that indicated by serial plate data.

Cabinet - Do not allow water to stay in contact with the cabinet for long periods of time to prevent corrosion of the cabinet sheet metal. Generally vertical cabinets are set up from the fl oor a few inches for prevention. The cabinet can be cleaned using a mild detergent.

Refrigerant System - To maintain sealed circuit integ-rity, do not install service gauges unless unit operation appears abnormal. Reference the operating chart for pressure and temperatures. Verify that air and water fl ow rates are at proper levels before servicing the re-frigerant circuit.

If the refrigerant circuit is opened for any reason, a new liquid line fi lter-drier must be installed.

Preventative Maintenance

Page 44: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

44 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Warranty (International)

CL

IMA

TE

MA

STE

R, I

NC

.

LIM

ITE

D E

XP

RE

SS W

AR

RA

NT

Y /L

IMIT

AT

ION

OF

RE

ME

DIE

S A

ND

LIA

BIL

ITY

(F

OR

IN

TE

RN

AT

ION

AL

CL

ASS

PR

OD

UC

TS)

Dis

clai

mer

: It

is e

xpre

ssly

und

erst

ood

that

unl

ess

a st

atem

ent i

s sp

eci

cally

iden

ti e

d as

a w

arra

nty,

sta

tem

ents

mad

e by

Clim

ate

Mas

ter,

Inc.

, a D

elaw

are

corp

orat

ion,

U. S

. A. (

“CM

”) o

r its

rep

rese

ntat

ives

, rel

atin

g to

CM

’s p

rodu

cts,

whe

ther

ora

l, w

rit-

ten

or c

onta

ined

in a

ny s

ales

lite

ratu

re, c

atal

og, t

his

or a

ny o

ther

agr

eem

ent o

r ot

her

mat

eria

ls, a

re n

ot e

xpre

ss w

arra

ntie

s an

d do

not

for

m a

par

t of

the

basi

s of

the

barg

ain,

but

are

mer

ely

CM

’s o

pini

on o

r co

mm

enda

tion

of C

M’s

pro

duct

s. E

XC

EP

T A

S SP

EC

IFIC

AL

LY S

ET

FO

RT

H H

ER

EIN

AN

D T

O T

HE

FU

LL

EST

EX

TE

NT

PE

RM

ITT

ED

BY

AP

PL

ICA

BL

E L

AW

, CM

MA

KE

S N

O W

AR

RA

NT

Y A

S T

O A

NY

OF

CM

’S P

RO

DU

CT

S, A

ND

CM

MA

KE

S N

O W

AR

RA

NT

Y A

GA

INST

L

AT

EN

T D

EF

EC

TS

OR

AN

Y W

AR

RA

NT

Y O

F M

ER

CH

AN

TA

BIL

ITY

OF

TH

E G

OO

DS

OR

OF

TH

E F

ITN

ESS

OF

TH

E G

OO

DS

FO

R A

NY

PA

RT

ICU

LA

R P

UR

PO

SE.

GR

AN

T O

F L

IMIT

ED

EX

PR

ESS

WA

RR

AN

TY

CM

war

rant

s C

M p

rodu

cts

purc

hase

d an

d in

stal

led

outs

ide

the

Uni

ted

Stat

es o

f Am

eric

a (“

U.S

.A.”

) an

d C

anad

a to

be

free

fro

m m

ater

ial d

efec

ts in

mat

eria

ls a

nd w

orkm

ansh

ip u

nder

nor

mal

use

and

mai

nten

ance

as

follo

ws:

(1)

All

com

plet

e ai

r co

nditi

onin

g, h

eatin

g or

hea

t pum

p un

its b

uilt

or s

old

by C

M f

or tw

elve

(12

) m

onth

s fr

om d

ate

of u

nit s

tart

-up

or e

ight

een

(18)

mon

ths

from

dat

e of

shi

pmen

t (fr

om C

M’s

fac

tory

), w

hich

ever

com

es

rst;

and,

(2)

Rep

air

and

repl

acem

ent p

arts

, whi

ch a

re

not s

uppl

ied

unde

r w

arra

nty,

for

nin

ety

(90)

day

s fr

om d

ate

of s

hipm

ent (

from

fac

tory

).

War

rant

y pa

rts

shal

l be

furn

ishe

d by

CM

if o

rder

ed th

roug

h an

aut

hori

zed

sale

s re

pres

enta

tive

of C

M (

“Rep

rese

ntat

ive”

) w

ithin

six

ty (

60)

days

aft

er th

e fa

ilure

of

the

part

. If

CM

det

erm

ines

that

a p

arts

ord

er q

uali

es

for

repl

acem

ent u

nder

CM

’s

war

rant

y, s

uch

part

s sh

all b

e sh

ippe

d fr

eigh

t pre

paid

to th

e R

epre

sent

ativ

e or

the

ultim

ate

user

, as

requ

este

d by

Rep

rese

ntat

ive.

All

dutie

s, ta

xes

and

othe

r fe

es s

hall

be p

aid

by th

e ul

timat

e us

er th

roug

h th

e R

epre

sent

ativ

e.

If r

eque

sted

by

CM

, all

defe

ctiv

e pa

rts

shal

l be

retu

rned

to C

M’s

fac

tory

in O

klah

oma

City

, Okl

ahom

a, U

.S.A

, fre

ight

and

dut

y pr

epai

d, n

ot la

ter

than

six

ty (

60)

days

aft

er th

e da

te o

f th

e re

ques

t. If

the

defe

ctiv

e pa

rt is

not

tim

ely

retu

rned

or

if C

M

dete

rmin

es th

e pa

rt to

not

be

defe

ctiv

e or

oth

erw

ise

not t

o qu

alif

y un

der

CM

’s L

imite

d E

xpre

ss W

arra

nty,

CM

sha

ll in

voic

e C

usto

mer

the

cost

s fo

r th

e pa

rts

furn

ishe

d, in

clud

ing

frei

ght.

The

war

rant

y on

any

par

t rep

aire

d or

rep

lace

d un

der

war

rant

y ex

pire

s at

the

end

of th

e or

igin

al w

arra

nty

peri

od.

Thi

s w

arra

nty

does

not

cov

er a

nd d

oes

not a

pply

to: (

1) A

ir

lters

, fus

es, r

efri

gera

nt,

uid

s, o

il; (

2) P

rodu

cts

relo

cate

d af

ter

initi

al in

stal

latio

n; (

3) A

ny p

ortio

n or

com

pone

nt o

f an

y sy

stem

that

is n

ot s

uppl

ied

by C

M, r

egar

dles

s of

the

caus

e of

the

failu

re

of s

uch

port

ion

or c

ompo

nent

; (4)

Pro

duct

s on

whi

ch th

e un

it id

enti

cat

ion

tags

or

labe

ls h

ave

been

rem

oved

or

defa

ced;

(5)

Pro

duct

s on

whi

ch p

aym

ent b

y C

usto

mer

to C

M o

r its

dis

trib

utor

s or

Rep

rese

ntat

ives

, or

the

Cus

tom

er’s

sel

ler

is in

def

ault;

(6

) Pr

oduc

ts w

hich

hav

e de

fect

s or

dam

age

whi

ch r

esul

t fro

m im

prop

er in

stal

latio

n, w

irin

g, e

lect

rica

l im

bala

nce

char

acte

rist

ics

or m

aint

enan

ce; o

r fr

om p

arts

or

com

pone

nts

man

ufac

ture

d by

oth

ers;

or

are

caus

ed b

y ac

cide

nt, m

isus

e, n

eglig

ence

, abu

se,

re,

oo

d, li

ghtn

ing,

alte

ratio

n or

mis

appl

icat

ion

of th

e pr

oduc

t; (7

) Pr

oduc

ts w

hich

hav

e de

fect

s or

dam

age

whi

ch r

esul

t fro

m a

con

tam

inat

ed o

r co

rros

ive

air

or li

quid

sup

ply,

ope

ratio

n at

abn

orm

al te

mpe

ratu

res

or

ow r

ates

, or

unau

thor

ized

ope

ning

of

the

refr

iger

ant c

ircu

it; (

8) M

old,

fun

gus

or b

acte

ria

dam

ages

; (9)

Pro

duct

s su

bjec

ted

to c

orro

sion

or

abra

sion

; (10

) Pr

oduc

ts, p

arts

or

com

pone

nts

man

ufac

ture

d or

sup

plie

d by

oth

ers;

(11

) Pr

oduc

ts w

hich

hav

e be

en s

ubje

cted

to m

isus

e, n

eglig

ence

or

acc

iden

ts; (

12)

Prod

ucts

whi

ch h

ave

been

ope

rate

d in

a m

anne

r co

ntra

ry to

CM

’s p

rint

ed in

stru

ctio

ns; (

13)

Prod

ucts

whi

ch h

ave

defe

cts,

dam

age

or in

suf

cie

nt p

erfo

rman

ce a

s a

resu

lt of

insu

f c

ient

or

inco

rrec

t sys

tem

des

ign

or th

e im

prop

er

appl

icat

ion,

inst

alla

tion,

or

use

of C

M’s

pro

duct

s; o

r (1

4) E

lect

rici

ty o

r fu

el c

osts

, or

any

incr

ease

s or

unr

ealiz

ed s

avin

gs in

sam

e, f

or a

ny r

easo

n.

CM

is n

ot r

espo

nsib

le f

or: (

1) T

he c

ost o

f an

y u

ids,

ref

rige

rant

or

othe

r sy

stem

com

pone

nts,

or

the

asso

ciat

ed la

bor

to r

epai

r or

rep

lace

the

sam

e, w

hich

is in

curr

ed a

s a

resu

lt of

a d

efec

tive

part

cov

ered

by

CM

’s L

imite

d E

xpre

ss W

arra

nty;

(2)

The

cos

t of

labo

r, re

frig

eran

t, m

ater

ials

or

serv

ice

incu

rred

in d

iagn

osis

and

rem

oval

of

the

defe

ctiv

e pa

rt, o

r in

obt

aini

ng a

nd r

epla

cing

the

new

or

repa

ired

par

t; (3

) T

rans

port

atio

n co

sts

of th

e de

fect

ive

part

fro

m th

e in

stal

latio

n si

te to

CM

or

of th

e re

turn

of

any

part

not

cov

ered

by

CM

’s L

imite

d E

xpre

ss W

arra

nty;

or

(4)

The

cos

ts o

f no

rmal

mai

nten

ance

.

Lim

itatio

n: T

his

Lim

ited

Exp

ress

War

rant

y is

giv

en in

lieu

of

all o

ther

war

rant

ies.

If,

not

with

stan

ding

the

disc

laim

ers

cont

aine

d he

rein

, it i

s de

term

ined

by

a co

urt o

r ot

her

qual

i ed

judi

cial

bod

y th

at o

ther

war

rant

ies

exis

t, an

y su

ch w

arra

nty,

incl

udin

g w

ithou

t lim

itatio

n an

y ex

pres

s w

arra

nty

or a

ny im

plie

d w

arra

nty

of

tnes

s fo

r pa

rtic

ular

pur

pose

and

mer

chan

tabi

lity,

sha

ll be

lim

ited

to th

e du

ratio

n of

the

Lim

ited

Exp

ress

War

rant

y. T

his

Lim

ited

Exp

ress

War

rant

y do

es n

ot e

xclu

de a

ny w

arra

nty

that

is

man

dato

ry a

nd th

at m

ay n

ot b

e ex

clud

ed u

nder

app

licab

le im

pera

tive

law

.

LIM

ITA

TIO

N O

F R

EM

ED

IES

In th

e ev

ent o

f a

brea

ch o

f th

is L

imite

d E

xpre

ss W

arra

nty

or a

ny w

arra

nty

that

is m

anda

tory

und

er a

pplic

able

impe

rativ

e la

w, C

M w

ill o

nly

be o

blig

ated

at C

M’s

opt

ion

to e

ither

rep

air

the

faile

d pa

rt o

r un

it or

to f

urni

sh a

new

or

rebu

ilt p

art o

r un

it in

ex-

chan

ge f

or th

e pa

rt o

r un

it w

hich

has

fai

led.

If

afte

r w

ritte

n no

tice

to C

M’s

fac

tory

in O

klah

oma

City

, Okl

ahom

a, U

.S.A

. of

each

def

ect,

mal

func

tion

or o

ther

fai

lure

and

a r

easo

nabl

e nu

mbe

r of

atte

mpt

s by

CM

to c

orre

ct th

e de

fect

, mal

func

tion

or o

ther

fa

ilure

and

the

rem

edy

fails

of

its e

ssen

tial p

urpo

se, C

M s

hall

refu

nd th

e pu

rcha

se p

rice

pai

d to

CM

in e

xcha

nge

for

the

retu

rn o

f th

e so

ld g

ood(

s). S

aid

refu

nd s

hall

be th

e m

axim

um li

abili

ty o

f C

M. T

O T

HE

FU

LL

EST

EX

TE

NT

PE

RM

ITT

ED

BY

A

PP

LIC

AB

LE

LA

W, T

HIS

RE

ME

DY

IS

TH

E S

OL

E A

ND

EX

CL

USI

VE

RE

ME

DY

OF

TH

E C

UST

OM

ER

AG

AIN

ST C

M F

OR

BR

EA

CH

OF

CO

NT

RA

CT

, FO

R T

HE

BR

EA

CH

OF

AN

Y W

AR

RA

NT

Y O

R F

OR

CM

’S N

EG

LIG

EN

CE

O

R I

N S

TR

ICT

LIA

BIL

ITY

.

LIM

ITA

TIO

N O

F L

IAB

ILIT

YC

M s

hall

have

no

liabi

lity

for

any

dam

ages

if C

M’s

per

form

ance

is d

elay

ed f

or a

ny r

easo

n or

is p

reve

nted

to a

ny e

xten

t by

any

even

t suc

h as

, but

not

lim

ited

to: a

ny w

ar, c

ivil

unre

st, g

over

nmen

t res

tric

tions

or

rest

rain

ts, s

trik

es, o

r w

ork

stop

page

s,

re,

oo

d, a

ccid

ent,

allo

catio

n, s

hort

ages

of

tran

spor

tatio

n, f

uel,

mat

eria

ls, o

r la

bor,

acts

of

God

or

any

othe

r re

ason

bey

ond

the

sole

con

trol

of

CM

. TO

TH

E F

UL

LE

ST E

XT

EN

T P

ER

MIT

TE

D B

Y A

PP

LIC

AB

LE

LA

W A

ND

SU

BJE

CT

TO

T

HE

NE

XT

SE

NT

EN

CE

, CM

EX

PR

ESS

LY D

ISC

LA

IMS

AN

D E

XC

LU

DE

S A

NY

LIA

BIL

ITY

FO

R L

OSS

OF

PR

OF

ITS,

LO

SS O

F B

USI

NE

SS O

R G

OO

DW

ILL

, CO

NSE

QU

EN

TIA

L, I

NC

IDE

NT

AL

, SP

EC

IAL

, LIQ

UID

AT

ED

, OR

P

UN

ITIV

E D

AM

AG

E I

N C

ON

TR

AC

T, F

OR

BR

EA

CH

OF

AN

Y E

XP

RE

SS O

R I

MP

LIE

D W

AR

RA

NT

Y, O

R I

N T

OR

T, W

HE

TH

ER

FO

R C

M’s

NE

GL

IGE

NC

E O

R A

S ST

RIC

T L

IAB

ILIT

Y. N

othi

ng in

this

Agr

eem

ent i

s in

tend

ed to

ex

clud

e C

M’s

liab

ility

for

dea

th, p

erso

nal i

njur

y or

fra

ud.

OB

TA

ININ

G W

AR

RA

NT

Y P

ER

FO

RM

AN

CE

Nor

mal

ly, t

he c

ontr

acto

r or

ser

vice

org

aniz

atio

n w

ho in

stal

led

the

prod

ucts

will

pro

vide

war

rant

y pe

rfor

man

ce f

or th

e ow

ner.

Shou

ld th

e in

stal

ler

be u

nava

ilabl

e, c

onta

ct a

ny C

M r

ecog

nize

d R

epre

sent

ativ

e. I

f as

sist

ance

is r

equi

red

in o

btai

ning

war

rant

y pe

rfor

man

ce, w

rite

or

call:

Clim

ate

Mas

ter,

Inc.

• C

usto

mer

Ser

vice

• 7

300

S.W

. 44t

h St

reet

• O

klah

oma

City

, Okl

ahom

a, U

.S.A

. 731

79 •

(40

5) 7

45-6

000

• F

AX

(40

5) 7

45-6

068

NO

TE

: Som

e co

untr

ies

do n

ot a

llow

lim

itatio

ns o

n ho

w lo

ng a

n im

plie

d w

arra

nty

last

s, o

r th

e lim

itatio

n or

exc

lusi

ons

of c

onse

quen

tial o

r in

cide

ntal

dam

ages

, so

the

fore

goin

g ex

clus

ions

and

lim

itatio

ns m

ay n

ot a

pply

to y

ou. T

his

war

rant

y gi

ves

you

spec

i c

lega

l rig

hts,

and

you

may

als

o ha

ve o

ther

rig

hts

whi

ch v

ary

from

sta

te to

sta

te a

nd c

ount

ry to

cou

ntry

.

Plea

se r

efer

to th

e C

M I

nsta

llatio

n, O

pera

tion

and

Mai

nten

ance

Man

ual f

or o

pera

ting

and

mai

nten

ance

inst

ruct

ions

.

*LC079*

LC

079

Rev

.: 10

/09

Page 45: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

45c l i m a t e m a s t e r . c o m

Warranty (US & Canada)C

LIM

AT

E M

AST

ER

, INC

.L

IMIT

ED

EX

PR

ESS W

AR

RA

NT

Y/ L

IMIT

AT

ION

OF R

EM

ED

IES A

ND

LIA

BIL

ITY

It is expressly understood that unless a statement is speci cally identi ed as a w

arranty, statements m

ade by Clim

ate Master, Inc., a D

elaware corporation, (“C

M”) or its representatives, relating to C

M’s products, w

hether oral, w

ritten or contained in any sales literature, catalog or any other agreement, are not express w

arranties and do not form a part of the basis of the bargain, but are m

erely CM

’s opinion or comm

endation of CM

’s products.

EX

CE

PT

AS SP

EC

IFIC

AL

LY SE

T F

OR

TH

HE

RE

IN, T

HE

RE

IS NO

EX

PR

ESS W

AR

RA

NT

Y A

S TO

AN

Y O

F CM

’S PR

OD

UC

TS. C

M M

AK

ES N

O W

AR

RA

NT

Y A

GA

INST

LA

TE

NT

DE

FE

CT

S. CM

MA

KE

S N

O W

AR

RA

NT

Y O

F ME

RC

HA

NT

AB

ILIT

Y O

F TH

E G

OO

DS O

R O

F TH

E F

ITN

ESS O

F TH

E G

OO

DS F

OR

AN

Y PA

RT

ICU

LA

R P

UR

PO

SE.

GR

AN

T O

F LIM

ITE

D E

XP

RE

SS WA

RR

AN

TY

CM

warrants C

M products purchased and retained in the U

nited States of Am

erica and Canada to be free from

defects in material and w

orkmanship under norm

al use and maintenance as follow

s: (1) All com

plete air condition-ing, heating and/or heat pum

p units built or sold by CM

for twelve (12) m

onths from date of unit start up or eighteen (18) m

onths from date of shipm

ent (from factory), w

hichever comes rst; (2) R

epair and replacement parts,

which are not supplied under w

arranty, for nintey (90) days from date of shipm

ent (from factory). A

ll parts must be returned to C

M’s factory in O

klahoma C

ity, Oklahom

a, freight prepaid, no later than sixty (60) days after the date of the failure of the part; if C

M determ

ines the part to be defective and within C

M’s L

imited E

xpress Warranty, C

M shall, w

hen such part has been either replaced or repaired, return such to a factory recognized dealer, contractor or service organization, F.O

.B. C

M’s factory, O

klahoma C

ity, Oklahom

a, freight prepaid. The w

arranty on any parts repaired or replaced under warranty expires at the end of the original w

arranty period.

This w

arranty does not cover and does not apply to: (1) Air lters, fuses, refrigerant, uids, oil; (2) Products relocated after initial installation; (3) A

ny portion or component of any system

that is not supplied by CM

, regardless of the cause of the failure of such portion or com

ponent; (4) Products on which the unit identi cation tags or labels have been rem

oved or defaced; (5) Products on which paym

ent to CM

is or has been in default; (6) Products w

hich have defects or damage w

hich result from im

proper installation, wiring, electrical im

balance characteristics or maintenance; or are caused by accident, m

isuse or abuse, re, ood, alteration or misapplication of the prod-

uct; (7) Products which have defects or dam

age which result from

a contaminated or corrosive air or liquid supply, operation at abnorm

al temperatures, or unauthorized opening of refrigerant circuit; (8) M

old, fungus or bacteria dam

ages; (9) Products subjected to corrosion or abrasion; (10) Products manufactured or supplied by others; (11) Products w

hich have been subjected to misuse, negligence or accidents; (12) Products w

hich have been operated in a m

anner contrary to CM

’s printed instructions; or (13) Products which have defects, dam

age or insuf cient perform

ance as a result of insuf cient or incorrect system

design or the improper application of C

M’s products.

CM

is not responsible for: (1) The costs of any uids, refrigerant or other system

components, or associated labor to repair or replace the sam

e, which is incurred as a result of a defective part covered by C

M’s L

imited E

xpress W

arranty; (2) The costs of labor, refrigerant, m

aterials or service incurred in removal of the defective part, or in obtaining and replacing the new

or repaired part; or, (3) Transportation costs of the defective part from

the installa-tion site to C

M or of the return of any part not covered by C

M’s L

imited E

xpress Warranty.

Lim

itation: This L

imited E

xpress Warranty is given in lieu of all other w

arranties. If, notwithstanding the disclaim

ers contained herein, it is determined that other w

arranties exist, any such warranties, including w

ithout limita-

tion any express warranties or any im

plied warranties of tness for particular purpose and m

erchantability, shall be limited to the duration of the L

imited E

xpress Warranty.

LIM

ITA

TIO

N O

F RE

ME

DIE

SIn the event of a breach of the L

imited E

xpress Warranty, C

M w

ill only be obligated at CM

’s option to repair the failed part or unit or to furnish a new or rebuilt part or unit in exchange for the part or unit w

hich has failed. If after w

ritten notice to CM

’s factory in Oklahom

a City, O

klahoma of each defect, m

alfunction or other failure and a reasonable number of attem

pts by CM

to correct the defect, malfunction or other failure and the rem

edy fails of its essential purpose, C

M shall refund the purchase price paid to C

M in exchange for the return of the sold good(s). Said refund shall be the m

aximum

liability of CM

. TH

IS RE

ME

DY

IS TH

E SO

LE

AN

D E

XC

LU

SIVE

R

EM

ED

Y O

F TH

E B

UY

ER

OR

TH

EIR

PU

RC

HA

SER

AG

AIN

ST C

M F

OR

BR

EA

CH

OF C

ON

TR

AC

T, F

OR

TH

E B

RE

AC

H O

F AN

Y W

AR

RA

NT

Y O

R F

OR

CM

’S NE

GL

IGE

NC

E O

R IN

STR

ICT

LIA

BIL

ITY

.

LIM

ITA

TIO

N O

F LIA

BIL

ITY

CM

shall have no liability for any damages if C

M’s perform

ance is delayed for any reason or is prevented to any extent by any event such as, but not limited to: any w

ar, civil unrest, government restrictions or restraints, strikes

or work stoppages, re, ood, accident, shortages of transportation, fuel, m

aterial, or labor, acts of God or any other reason beyond the sole control of C

M. C

M E

XP

RE

SSLY D

ISCL

AIM

S AN

D E

XC

LU

DE

S AN

Y L

IAB

IL-

ITY

FO

R C

ON

SEQ

UE

NT

IAL

OR

INC

IDE

NT

AL

DA

MA

GE

IN C

ON

TR

AC

T, F

OR

BR

EA

CH

OF A

NY

EX

PR

ESS O

R IM

PL

IED

WA

RR

AN

TY

, OR

IN T

OR

T, W

HE

TH

ER

FO

R C

M’s N

EG

LIG

EN

CE

OR

AS

STR

ICT

LIA

BIL

ITY

.

OB

TA

ININ

G W

AR

RA

NT

Y P

ER

FO

RM

AN

CE

Norm

ally, the contractor or service organization who installed the products w

ill provide warranty perform

ance for the owner. Should the installer be unavailable, contact any C

M recognized dealer, contractor or service organiza-

tion. If assistance is required in obtaining warranty perform

ance, write or call:

Clim

ate Master, Inc. • C

ustomer Service • 7300 S.W

. 44th Street • Oklahom

a City, O

klahoma 73179 (405) 745-6000

NO

TE

: Some states or C

anadian provinces do not allow lim

itations on how long an im

plied warranty lasts, or the lim

itation or exclusions of consequential or incidental damages, so the foregoing exclusions and lim

itations may

not apply to you. This w

arranty gives you speci c legal rights, and you may also have other rights w

hich vary from state to state and from

Canadian province to C

anadian province.

Please refer to the CM

Installation, Operation and M

aintenance Manual for operating and m

aintenance instructions.

*LC083*

Rev.: 11/09

LC

083

Page 46: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

46 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Start-Up Log Sheet

Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record unit information, temperatures and pressures during start-up. Keep this form for future reference.

Job Name: Street Address:

Model Number: Serial Number:

Unit Location in Building:

Date: Sales Order No:

In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.

Temperatures: F or C Antifreeze: _____% Type of Antifreeze: __________________

Cooling Mode Heating Mode

Sour

ce

Entering Fluid TemperatureLeaving Fluid TemperatureTemperature DifferentialPressure InPressure OutPressure Differential

Load

Entering Fluid TemperatureLeaving Fluid TemperatureTemperature DifferentialPressure InPressure OutPressure Differential

Com

pres

sor Amps

Volts

Discharge Line Temperature(6” from Compressor Outlet)

Allow unit to run 15 minutes in each mode before taking data.Do not connect gauge lines

Page 47: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

THE SMART SOLUTION FOR ENERGY EFFICIENCY

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

47c l i m a t e m a s t e r . c o m

Refrigeration Troubleshooting Form

:etaD putratS:epyT pooL:remotsuC

Model #: :% & epyT ezeerfitnA:# laireS

Complaint:

VoltageCompressor Amps

1 Suction Temp2 Suction Press

2a Saturation Temp2b Superheat3 Discharge Temp4 Discharge Press

4a Saturation Temp4b Subcooling5 Liquid Line Temp6 Source Water In Tmp7 Source Water Out Tmp8 Source Water In Pres9 Source Water Out Pres

9a Press Drop9b Flow Rate GPM [l/s]10 Load Water In Temp 11 Load Water Out Temp12 Load Water In Pres13 Load Water Out Pres

13a Press Drop13b Flow Rate GPM [l/s]

Heat of Extraction (Absorption) or Heat of Rejection:

HE or HR =

Flow Rate x Temp. Diff x Fluid Factor

setoNnoitpircseD

Temp Diff. =

Temp Diff. =

Heating Cooling

Refrigeration Troubleshooting FormWater-to-Water Units

COMPRESSOR

DISCHARGE

SUCTION

HWG**

EXPANSIONVALVE FILTER

DRIER

REVERSINGVALVE

HEATING POSITION COOLING POSITION

1

COAX

CO

AX

5

1210

1311

9

7

8

6

4

3

2

LT2:HEATINGLIQUIDLINE

5 LT1:COOLINGLIQUIDLINE

CONDENSER (HTG)EVAPORATOR (CLG)

CONDENSER (COOLING)EVAPORATOR (HEATING)

**Turn off HWG before troubleshooting.

REFRIG FLOW - HEATING REFRIG FLOW - COOLING

REFRIGERANT: HFC-410A

OPERATING MODE: HEATING COOLING

Fluid Factor: (for Btuh)500 (Water); 485 (Antifreeze)

Source

Load

Fluid Factor: (for kW)4.18 (Water); 4.05 (Antifreeze)

Page 48: Tranquility Modular Water-to-Water (TMW) Series® Modular Water-to-Water (TMW) Series Commercial EarthPure® Water-Source Heat Pumps 50Hz & 60Hz Installation, Operation & Maintenance

CLIMATEMASTER WATER-SOURCE HEAT PUMPS

Tranquil ity® Water-to-Water (TMW) SeriesR e v. : 0 6 / 2 3 / 1 4

48 C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

Revision History

Date: Item: Action:

06/23/14 Water Quality Table Updated

11/09/12POE Oil Warning Added

Water Quality Table Updated

11/14/11 TMW170 & 340 Unit Dimensional Data Updated

08/09/11 Unit Maximum Working Water Pressure Updated to Refl ect New Safeties

01/03/11 Format - All Pages Updated

10/06/10 Start-Up Log Sheet Added

07/26/10 Wiring Diagrams Updated

06/11/10 Format - All Pages Updated

04/08/10 Electrical and Operating Pressures Tables Updated

11/05/09 Warranty Updated

09/15/09 Safety Features - CXM/DXM Control Section Updated

06/01/09 Operating Pressures Heating Table Updated

05/07/09 ‘Unit Starting & Operating Conditions’ Section & Table Edited and renamed ‘Unit Commissioning and Operating Conditions’

04/21/09 Physical Data Table Water Volume Data Updated

04/21/09 Water-Loop & Ground-Loop Heat Pump Applications Sections, Electrical Line Voltage Section, Safety Feature Section Verbiage Updated

04/02/09 First Published

97B0059N03

*97B0059N03*

7300 S.W. 44th StreetOklahoma City, OK 73179

Phone: 405-745-6000Fax: 405-745-6058climatemaster.com

ISO 9001:2008Certified

Quality: First & Always

ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.

The management system governing the manufacture of ClimateMaster’s products is ISO 9001:2008 certifi ed.

ClimateMaster is a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org.

© ClimateMaster, Inc. 2006