ABB Transformation - Training
ABB Transformation - Training
DISTURBANCE FAULT RECORDER INDACTIC - 650
SEQUENTIAL EVENT RECORDER INDACTIC - 425
Disturbance Fault Recorder System- Indactic -650
Utility Communication Systems
ABB Transformation - Training
Indactic® Product Family
Indactic 650
Disturbance Fault Recording System
DFR
Utility Communication Systems
ABB Transformation - Training
Indactic 425
Sequence of Events Recording
System
SOE
Utility Communication Systems
Indactic® Product Family
ABB Transformation - Training
Products
DRDisturbance Fault Recorder Type I65/I65CDisturbance Fault Recorder Type I650
SERSequence Of Event Recorder Type SER-600Sequence Of Event Recorder Type I425.
ABB Transformation - Training
DFR Indactic 650
Privatisation ( “bad” suppliers will have to pay fine for not supplied power) Eg. MSEB & DPC
Deregulation (open market with international power suppliers)
Refurbishment of power systems (Retrofit)
DFR Indactic 650
Privatisation ( “bad” suppliers will have to pay fine for not supplied power) Eg. MSEB & DPC
Deregulation (open market with international power suppliers)
Refurbishment of power systems (Retrofit)
Future Developments : Why Disturbance Fault Recorder market increasing?
ABB Transformation - Training
Future Developments : Why Disturbance Fault recorders?
High cost of stand still of generators, substations and lines
Avoiding of system failure is of highest concern
No equipment provides the insights as does a good disturbance recorder
Optimisation of protection performance and concepts
Planing of preventive maintenance
ABB Transformation - Training
Future Developments : Common Features Indactic 650 or Indactic 425
Basic Concept: Within the plant diverse „logical Acquisition Stations“, usually one acquisition station
per bay (i.e. one Indactic 650 Unit) or one acquisition station per diameter (i.e. two or more
Indactic 650 Units)
Indactic as De-central SystemBus Structure : Real time bus 1.5 Mbaud, coaxial or fibre optic cable
ABB Transformation - Training
Features Indactic 650
Maximum Configuration
per substation 79 units
per complete network 250 acquisition stations
Acquisition UNIT Acquisition STATION
(Basic unit (1,2,3,.……10 units)
1/3 of 19“ Rack)
Master,
Slave, Slave
Predecessor
Indactic 65 (ABB Product 1981-1994)
Version 65D compatible with WinCom & WinEve under Windows
ABB Transformation - Training
Features Indactic 650
Modules
• Case UB-10
• Power Supply Module PS-25 (prev. PS-10)
• Communication Module CI-10
• Input Module XI-11 (prev. XI-10)
• Transformer Module TR-10
ABB Transformation - Training
Features Indactic 650
Basic Configuration
• Indactic 650 Units
• PC
• Printer - Laser or InkJet
• Software WinCom, WinEve
Output
• Hardware : 4 output relays (dry contacts) per unit
• SW : One file per recording with all analogue and digital signals
• SW : One fault location report
• SW Optional : Expert report
ABB Transformation - Training
Features Indactic 650
Indactic as De-central System What does de-central system mean?
The physical location of the inputs has no meaning with respect to the
logical configuration!
Practically the acquisition units which work as a system need not be located
in the same place
The operating personal (the user) does not „see“ that the units are not
located at the same place
ABB Transformation - Training
Features Indactic 650
Tele-Communication
Central Evaluation Station (Master Station) WinCom/ WinEve
Local Data Concentrators ReCo65 (or PC Anywhere)
WinCom can collect data from many substations (Indactic 650 stations or
ReCo65 stations) via tele-communication connection
ReCo65
MS-DOS SW (also with Windows `95 & 98) currently under re-design
ABB Transformation - Training
Remote communication
Remote structureSMS/SCSWinNT
ModemTelephoneNetwork / Intranet
Bridge
Bridge
Ethernet(TCP/IP)
RE.316
RE.216
GPS/DCF77
SPA-Bus
Ethernet(TCP/IP)
Color Printer
Indactic 650 WinNT
BridgeEthernet(TCP/IP)
Modem
RE.316*4 RE.216
Interbay-Bus
local
REB500 CU
Modem
REB500 CUIndactic
650CB 10
Channel selectorSwitch Box
Fall Back Switch
I n d a c t ic4 2 5
Serial Port
Indactic650
CB 10
I n d a c t ic4 2 5
Serial PortGPS
GPS
ABB Transformation - Training
Indactic® 6504th Generation of Disturbance Fault Recorder
Indactic 650 acquisition unit each with 9 analogue and 16 digital inputs
De-central intelligence for optimised redundancy
(each unit with 2 microprocessors + 1 DSP + 4 MB)
Unit interconnection by a 1.5 Mbaud real time. Only one „wire“ between units, located
hundreds of meters apart, for all functions
Each channel has its own 16 bits A/D converter
No analogue multiplexing !!! No skew delay !!!
PT’s & CT’s are integrated into the unit (no external components)
Accuracy better than 2% of actual (± 0.5%on full scale) without any recalibration on site
ABB Transformation - Training
Technical Data per Unit
Digital Inputs
Number: 16
Input Type 48V to 250V or potential free
Analogue Inputs
Resolution: 16 bits
Number: 9, current or voltage
Importance of high resolution (16 bits)
The resolution will determine the accuracy of all measures. Look at the LSB.
50 A x 2 x 2-15 = 2.12 mA, 50 A x 2 x 2-11 = 34.53 mA 16 times less !!!
That is an error of 3.45 %. This error cannot be compensated by any measures!
ABB Transformation - Training
Technical Data per Unit (suite 1)
Voltage Inputs: 100V/3, 100V, 200V/3 , 200V
Measurement range 2 x Un x 2
Accuracy ± 0.5% of Un (0.2 to 1.6 x Un)
Current Inputs: 1A or 5A Measurement range 50 x In x 2 = full range Thermal (IEC 255-3/-4) 100 x In 1 sec
30 x In 10 sec 4 x In
continuous Accuracy ± 0.5 % on full range (i.e 50 x 2 A)
± 2% of actual value (i.e.1A)
DC Inputs (optional): ± 20 mA, ± 10 V
i.e. excitation of generators or pressure of transformer oil,temperature, etc
ABB Transformation - Training
Trigger Settings
Digital-Inputs: high or low levels
Analog-Inputs: high limit low limit
rate of change (du/dt, di/dt)
Special Trigger: Frequency (high & low limit & r.o.c. df/dt)
Zero-, pos.- & negative sequence trigger
Technical Data per Unit (suite 2)
ABB Transformation - Training
Recording Duration
Prefault: 0.1 s to 0.5 s, prog. in steps of 0.1 s
Postfault: 0.1 s to 0.5 s, prog. in steps of 0.1 s
Fault: 0.1 s to 30 s, prog. in steps of 0.1 s
optional to 600 s at the lowest sampling rates
On Board Memory
Total 4 Mbyte per unit - 200'000 samples per channel
Data back-up for 6 hours
Technical Data per Unit (suite 3)
ABB Transformation - Training
Sampling rate & bandwith
The frequency response of a primary transformer is the limit of the disturbance recorder
bandwith
Advanced technologies allows to analyse frequency up to 0.5 time of the sampling rate
frequency
A very high sampling rate might not be the best as it needs lots of memory and a lot of time
to transfer a file which limits the performance of the disturbance recorder
How to specify disturbance recorder ?
ABB Transformation - Training
BETTER THAN OTHER FAULT RECORDERS BECAUSE .....
DEVELOPED BY A COMPANY WITH WORLDWIDE POWER
SYSTEM EXPERIENCE
RUNNING SUCCESSFUL BY CUSTOMERS SINCE 1994 (WELL
PROVEN TRACK RECORD)
MINIMISED ENGINEERING & COMMISSIONING COSTS
ONLY ONE EVALUATION SOFTWARE FOR INDACTIC 650,
REB500, RE.216, RE.316 and REVAL FORMATS
ABB Transformation - Training
BETTER THAN OTHER FAULT RECORDERS BECAUSE .....
ONLY ONE REMOTE SOFTWARE FOR INDACTIC 650, REB500,
RE.216, RE.316 (SOFTWARE RELEASE END 2000)
DE-CENTRAL INTELLIGENCE MEANS BETTER RELIABILITY
DE-CENTRAL ACQUISITION MEANS BETTER OVERALL
SYSTEM COSTS
ABB Transformation - Training
BETTER THAN OTHER FAULT RECORDERS BECAUSE .....
OPTIMISED RESOLUTION (16 bits) ALLOWS BETTER ANALYSIS
HIGH ACCURACY MEANS BETTER FAULT LOCATION &
EFFICIANT FAULT CLEARING
ONE A/D CONVERTER PER CHANNEL = HIGH SECURITY IN
CASE OF ONE A/D CONVERTER FAILURE
ABB Transformation - Training
Indactic® 650 Example
G enerator-Fault R ecorder C oncept
Fault Recorder w ith the follow ing inputs3 C T S ta r P o in t 1A nom .1 V T 100% E arth F au lt V o ltage (s ta to r) 100 V nom .1 V T 100% E arth F au lt V o ltage (ro to r) 30 V nom .4 D C Inpu ts 4 -20 m A (A V R s igna ls )4 V T 22 kV s ide inc l. open -de lta 57 .7 V nom .3 C T 22 kV s ide 1 A nom .3 V T 400 kV s ide 57 .7 V nom .3 C T 400 kV s ide 1 A nom .(3 V T 11 kV U n it A 57 .7 V nom .) - O p tiona l(3 V T 11 kV U n it B 57 .7 V nom .) - O p tiona l
F ie ld C urrentF ie ld Vo ltage
M ain R otor F ie ld C urrentM ain R otor F ie ld Vo ltage
DC
4..
20m
A22 kV
G 380 kV
11 kV
B reake r
B reake r
B reake r
P ow er T rans fo rm er700 M V A
G enera to r600 M V A
11 kV un it ATrans fo rm er
11 kV U n it BTrans fo rm er
Input S tar Po in t(1 A )
G enera torC urrents, Vo ltages
(1 A / 57 .7 V )
C urrents, Vo ltages400 kV side
( 1 A / 57 .7 V )
100% Earth Fau ltVo ltage (100 V )
Rot
or
100% Earth Fau ltVo ltage (30 V )
Excita tion
ABB Transformation - Training
Indactic® System
Fibre optic
50/125
Generator unit 1
Generator unit 2
Coaxial cable 75Ω Coaxial cable 75Ω
GPS
Users
Ethernet
Data
Internal Office LAN
M
M
Master Evaluation Station
Fibre optic
50/125
RS-232
RS-232 / FO Converter
RS-232 / FO Converter
RS-232
Local evaluation stationData gateway
WinCom
WinEve
ABB Transformation - Training
List of Products and Peripherals
Indactic 650 Rubrik wxyz (rubrik identifies the configuration)
GPS Clock & Receiver
19“ Mounting Rack
WinCom/WinEve/ReCo65
Industrial PC
Desktop PC
InkJet/ Laser Printers
RS232/ F-O Converters
Telephone Modems
TC-630 - Coax to F-O converters
•Ethernet
•Data
•Internal Office LAN
•M
•M
ABB Transformation - Training
Indactic® Application Software
Communication Package - WinCom
Communication with different acquisition stations
ABB Transformation - Training
Indactic® Application Software
WinCom- Signal parameters
ABB Transformation - Training
Indactic® Application Software
WinCom-Trigger setting
ABB Transformation - Training
Fault analysis software under MS-WINDOWS ‘95 and NT
One program covers all aspects of fault analysis
Comprehensive formula editor for all relevant calculations, i.e. true RMS,
impedance, power, harmonics, etc.
Fault location
Fault Analysis Package - WinEve
ABB Transformation - Training
Merging of events
Multi-event display
User-definable layouts
Reads and writes COMTRADE file formats
Compatible to Indactic 65/650, RE. 216/316 & REB500 formats
WinEve - Fault analysis software
ABB Transformation - Training
WinEve - Fault analysis software
Event display
ABB Transformation - Training
Based on a well proven distance relay algorithm, accuracy is better than 2 %
mutual and zero sequence impedance
capacitance (for long lines)
parallel lines
WinEve - Fault analysis software
Fault locator
ABB Transformation - Training
symmetric or asymmetric lines
reduces fault resistance influence
re-calculate the distance to fault i.e. with seasonal or "better" parameters.
distance to fault as a number or as a table
Development of a fault impedance - "R/X" diagram
Next release (end 2000) with 2 Terminals Fault Location
WinEve - Fault analysis software
Fault locator
ABB Transformation - Training
Alstom.
CSD(Hathaway.- Make)
Siemens.