Upload
muzammiliqbal
View
1.022
Download
72
Embed Size (px)
DESCRIPTION
ETAPtransformer Sizing
Citation preview
TRANSFORMER MVA SIZING USING ETAP
By Waqar HussainElectrical Dept.
INTRODUCTIONINTRODUCTION
In power systems, transformer is one of many p y , ydevices whose proper size is critical to the design of a power delivery system.
ETAP has complied the information contained pon standards ANSI IEEE C57, IEC 60076-2 and IEC 60726 into a program that can easily determine the proper size of a power transformer
FACTORS FOR TRAFO MVA SIZING IN ETAPFACTORS FOR TRAFO MVA SIZING IN ETAP
ETAP takes into consideration the following factors ETAP takes into consideration the following factors for trafo MVA sizingAmbient temperatureAmbient temperatureAltitudeCooling StageCooling StageType (dry or liquid fill)Expected future growthShort circuit requirement (trafo impedence and BIL)
2 WINDING TRAFO MVA SIZING2 WINDING TRAFO MVA SIZING
The two winding transformer MVA sizing calculation sizes the following parameters of a transfomer
Rated MVAMaximum MVAPercentage impedance
Maximum MVA is 1.25 times therated MVA for ONAN ONAF trafo.
2 WINDING TRAFO MVA SIZING (CONTD )2 WINDING TRAFO MVA SIZING (CONTD.)
Transformer Loading
This section allows you to find the operating load ( l l t d f l d fl l i ) t d (calculated from load flow analysis) or connected load to this transformer and then use either load for sizing purposesg p p
Also you can manually enter the loading for the transformer
While sizing transformer based on connected load, spares can also be included
2 WINDING TRAFO MVA SIZING (CONTD )2 WINDING TRAFO MVA SIZING (CONTD.)
Load Variation
Growth Factor For allowance for future growth. Growth factor is used for calculating the rated MVA of a factor is used for calculating the rated MVA of a transformer. If Use growth factor for max MVA is checked, then it is used for calculating the max MVA
Load Factor is 100 % if the transformer carries required load continuously all the time
2 WINDING TRAFO MVA SIZING (CONTD )2 WINDING TRAFO MVA SIZING (CONTD.)
Installation
ETAP adjusts the calculated required Rated MVA based on trafos altitude value. For example for Liquid p qImmersed Forced Air Cooled trafo, the MVA rating is derated by factor 0.5 % for every 330 ft above 3300 ftft.
Ambient Temp. ETAP adjusts the required Rated MVA based on ambient temperature valuebased on ambient temperature value
2 WINDING TRAFO MVA SIZING (CONTD )2 WINDING TRAFO MVA SIZING (CONTD.)
Impedancep
Basic Impulse Level (BIL) Limit - ETAP utilizes this p ( )value for determining the trafo minimum impedance according to ANSI IEC standards
Limit Short Circuit kA If this option is checked, then ETAP calculates % impedance based on short circuit kA, trafo type and BIL LimitkA, trafo type and BIL Limit
2 WINDING TRAFO MVA SIZING (CONTD )2 WINDING TRAFO MVA SIZING (CONTD.)
ResultsResults
Any one of the three results can be selected: Any one of the three results can be selected: Larger size, Required size or smaller size
OTHER REQUIRED DATA FOR TRAFO SIZING ON ETAPOTHER REQUIRED DATA FOR TRAFO SIZING ON ETAP
Standard (IEC or ANSI) Standard (IEC or ANSI) Type (Liquid fill or Dry) Sub type (mineral oil synthetic liquid etc ) Sub type (mineral oil, synthetic liquid etc ) Class (ONAN, ONAN-ONAF, OFAF etc ) Temperature rize Temperature rize Primary Winding kV rating
REGULATION OF TRAFO ON MOTOR STARTREGULATION OF TRAFO ON MOTOR START
One of the factors to be considered while sizing a trafo is the voltage drop onthe terminals of the largest motor (connected to trafo secondary) during motorthe terminals of the largest motor (connected to trafo secondary) during motorstart.
According to IEEE Brown Book, the voltage at terminals of starting motorshould not fall below 80% of rated voltage for typical NEMA design B motors
This voltage drop is proportional to the regulation of trafo during motor start
The voltage drop at trafo secondary (regulation) during motor start is inverselyproportional to trafo short circuit kVA and directly proportional to motorstarting kVA
The Transformer MVA Sizing Module of ETAP does not take into account thisfactor. The regulation of trafo can be checked by Motor Starting Study on ETAP
REGULATION OF TRAFO ON MOTOR STARTREGULATION OF TRAFO ON MOTOR START
Approximatevoltagedroponthetransformersecondarypp g p ycanbecalculatedbythefollowingformula
Where
D = % Voltage drop on secondary sideD %Voltagedroponsecondaryside
P=PeakLoadontrafo inkVA otherthanlargestMotor
M = Starting kVA of largest MotorM=StartingkVA oflargestMotor
S=Shortcircuitcapacityoftrafo inkVA
EXAMPLEEXAMPLE
UCH2 Unit Auxiliary Transformer sizing using ETAP
INPUT DATA TRAFO PARAMETERSINPUT DATA TRAFO PARAMETERS
Standard: IECType: Liquid Fill
Sub type: mineral oil
Cl ONAN ONAF T i 65Class: ONAN - ONAF Temp. rise: 65
Primary V = 14.5 kVSec. V = 6.6 kV
INPUT DATA UCH2 ETAP MODELINPUT DATA UCH2 ETAP MODEL
Plant ETAP model is required to is required to evaluate connected and operating load on a transformer
Unit Auxiliary transformer to be sized
Lump1 of 13869 kVAu p o 3869represents the UCH2
operating BOP load other than 1 No. circulation
water pump motor. The lump load contains all the plant cable losses the plant cable losses and loading factors of
different loads
SIZING MODULESIZING MODULE
Based on Operating t f l d 120 % transformer load, 120 % growth factor (for max MVA or ONAF) and 28 degree C ambient temp. , the p ,recommended size by ETAP is 20-25 MVA at ONAN-ONAF
Here worst case load is considered for GT, HRSG and ST MCC as provided and ST MCC, as provided by HET. (This load is included as lump 1 in ETAP model)
UCH2 LOAD FLOW AT 3 DIFFERENT UNIT AUX. TRAFORATINGS WORST CASE LOADING
1620MVAtrafo 2025MVAtrafo 2531.5MVAtrafo%Z=10,X\R=22.2 %Z=10,X\R=22.2 %Z=10,X\R=22.2
TrafoInputkVA 16198 16046 15932
TrafoOutputkVA 15217 15286 15339
Increase in trafooutput kVA as trafo rating is
Decrease in trafoinput kVA as trafo
rating is increased. For ONAN ONAF gincreased. ?
20 % of the lump load in UCH2 ETAP
g?
Trafo % Z is taken
For ONAN ONAF rated trafo, ETAP
performs Load flow at ONAN rating
load in UCH2 ETAP model is static
For good voltage
as contant at 10 %
For good voltage regulation at trafosec. the static load
consumes more kVA
ETAP MOTOR START STUDY AT 3 DIFFERENT TRAFORATINGS NORMAL CASE LOADING
MotorStartingAnalysisTrafoInputMVA
Load Flow afterForCirculationWaterPumpMotor
LoadFlowbeforeMotorstart
LoadFlowatMotorstart
LoadFlowafterMotorstart(steady
state)
1620MVAtrafo13 607 20 865 15 277
%Z=8,X\R=22.213.607 20.865 15.277
2025MVAtrafo%Z=8,X\R=22.2
13.655 21.345 15.333
2025MVAtrafo%Z=10,X\R=22.2
13.632 20.865 15.277
If Normal loading is considered (i e lump 1 = 13600 kVA ) then (i.e lump 1 = 13600 kVA ), then the sizing module recommends
16 20 MVA trafo
ETAP MOTOR START STUDY AT 3 DIFFERENT TRAFORATINGS NORMAL CASE LOADING .. CONTD
MotorStartingAnalysisFor Circulation Water
Trafosec.VoltageatMotorTerminalVoltage at Motor
MotorTerminalVoltage at SteadyForCirculationWater
PumpMotorMotorStart
VoltageatMotorStart
VoltageatSteadyState
1620MVAtrafo%Z=8,X\R=22.2
88.35% 92.09% 98.38%
2025MVAtrafo%Z=8,X\R=22.2
90.34% 94.18% 99.49%
20 25 MVA trafo2025MVAtrafo%Z=10,X\R=22.2
88.35% 92.09% 98.38%
Motor Rated Voltage:
As per IEEE Standard 399-1997, IEEE Recommended Practice for Industrial and Commercial Power System Analysis (Brown Book), the Voltage at terminal of Motorduring starting shall not fall below 80 % of rated voltage.
Please note that the motor rated voltage is 6.3 kA where as the MV bus and trafo sec. rated voltage is 6.6 kV
g g g
Hence this condition is satistfied for all the three different trafo ratings
For ONAN ONAF rated trafo, ETAP performs Motor Start at ONAN
rating
CALCULATION OF TRAFO SEC. VOLTAGE AT MOTOR START USING FORMULA COMPARISON
MotorStartingAnalysisFor Circulation Water
Trafo sec.VoltageatMotorStart
calculated usingForCirculationWaterPumpMotor calculatedusingETAP
calculatedusingFormula
1620MVAtrafo%Z=8,X\R=22.2
88.35% 87.36%
Almost same results using formula and ETAP, confirms the validity of the formula
2025MVAtrafo%Z=8,X\R=22.2
90.34% 89.89%
2025MVAtrafo% Z = 10 X\R = 22 2
88.35% 87.35%
used in UCH2 trafo sizing calculations
%Z=10,X\R=22.2
Starting kVA of motor = Full Load kVA x 6 = 11412 kVAPeak load on trafo excluding motor load = 13869 kVA
SUMMARY UCH2 UAT SIZINGSUMMARY . UCH2 UAT SIZING
Growth 16 20
ETAP
Normal load for GT, ST,
HRSG
Factor at ONAF
Growth Factor at
16 20 MVA
20 25 ETAP
Transformer Sizing Module
Worst load
Factor at ONAN MVA
20 25 Worst load for GT, ST,
HRSG
20 25 MVA
AT Normal Load for GT, ST, HRSG Total BOP Load including UAT losses = 15.9 MVA approx
AT Worst Load for GT, ST, HRSG Total BOP Load including UAT losses = 15.3 15.6 MVA approx
The Motor starting Condition is satisfied for both transformer ratings as indicated in previous slides
SUMMARY . UPSIZING OF UCH2 UAT FROM 16 -20 MVA TO 20 25 MVAMVA TO 20 25 MVA
Before addition of 1 MW colony feeder and two
For 16 20 MVA trafo, at motor start the voltage at
825 kW HSD Electric Heaters
MV bus was greater than 90 %
After addition of 1 MW colony feeder and two 825 kW HSD Electric
Heaters
For 16 20 MVA trafo, at motor start the voltage at
MV bus became lesser than 90 %
Mushtaq Sb. (from PMT) required the voltage to be greater than 90 %
To incorporate this comment, UAT rating was
increased to 20 25 increased to 20 25 MVA trafo at 8 % Z
STANDARDIZATION ON ETAP FOR TRAFO SIZINGSTANDARDIZATION ON ETAP FOR TRAFO SIZING
Having witnessed the harmony between ETAP g ytransformer sizing module and manual sizing through formulae, the sizing calculations can be standardized on ETAP
Following documents can be issued if sizing is done using ETAP
ETAP Load Flow Snapshot of ETAP ETAP Motor Start ETAP Load Flow analysis Report
Snapshot of ETAP sizing Module
ETAP Motor Start Study Report
THANK YOUTHANK YOUOU
Q & A
OU
Q & AQ & AQ & A