Transient Recovery Voltage (TRV) Studies

Presented by:

Lalin Kothalawala

Dharshana Muthumuni

Page 2: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Modeling and Simulation Studies to Facilitate Offshore Wind and HVDC Systems

The study approach to TRV investigation, using the PSCAD/EMTDC simulation tool, is discussed in this webinar. The following topics are addressed:

• Power system modeling• Station modeling• IEC/IEEE TRV envelopes• TRV simulation• Results interpretation• TRV mitigation methods

Page 3: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Circuit Breaker TRV

TRV - Definition

TRV is the voltage difference observed between the breaker terminals immediately after the current interruption of the breaker.

It is simply the difference in the power system response voltages on the source side and on the load side of the circuit breaker.

Page 4: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Circuit Breaker TRV

TRV - Definition

TRV is the voltage difference observed between the breaker terminals immediately after the current interruption of the breaker.

Page 5: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Electromagnetic Transients in Power Systems

Example: Closing/opening breakers, faults initiate electromagnetic transients.

• The energy exchange between L-C causes the oscillatory transient.

• Resistance in the circuit acts to damp the transient.

RLRRLRL RRL

RL RRLH

V

A

V

A

1e6

120

H

Station A Station B

E1

E2

TL_115KVTL_01_60KM TL_04_40KM

TL_02_110KM

TL_03_180KM

TL_05_210KM

Double circuit

60 km

Double circuit

110 km

Single circuit

290 km

1e6

• Traveling waves on transmission lines/cables

Electromagnetic Transients in Power Systems - Review

Page 6: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Resulted from lumped LC oscillations Vsystem

Circuit Breaker TRV - Illustration

Page 7: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

OpenLm

L1

Lm

𝑓 =1

2𝜋 𝐿𝐶LC circuit oscillation frequency

Opening a shunt reactor Clearing a fault on transformer secondary side

De-energizing a transformer

Bushing capacitance

Page 8: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

The voltage across breaker the terminals upon current interruption has two successive stages; transient recovery voltage stage where high frequency oscillations observed followed by the recovery voltage stage where power frequency oscillations are observed (transient has decayed).

Circuit Breaker TRV - Definitions

Page 9: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Key parameters:

• Rate of Rise of Recovery Voltage (RRRV)

• TRV peak

Both the above quantities must be evaluated in a TRV study

TRV Waveforms and Definitions

Page 10: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

• Trip signal initiate the breaker pole movement (approximately 12 ms for contacts to fully open)

• The current is interrupted at a point of a natural current zero

• An electric arc (of very high temperature) sustains the current during the interval.

o Weakened dielectric immediately following current interruption

o If an 'excessive’ voltage is applied across the breaker immediately after the current interruption, there is a risk of re-strike.

Circuit Breaker Current Interruption

Breaker OPENING initiated

Page 11: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV withstand capability of circuit breakers

TRV capability is defined by a set of curves • by breaker manufacturer• Minimum requirements as listed in IEC/IEEE

Depends on Breaker Rating (voltage and fault current rating)• Example: 245 kV, 40 kA breaker

Depends on the actual current being interrupted• Example: 100%, 60%, 30%, 10% of rated fault current

Page 12: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV is a ‘fast event’ (10s of KHz)

• The impact of the transient is limited to a local area of the station

• The transient (TRV) itself is mainly influenced by the circuit elements (R-L-C) in close vicinity to the breaker

o Circuit components of the station has a significant impact of TRV (bushing capacitances of equipment)

o The ‘remote system’ (1-2 buses away) generally has no impact on overall TRV response.

• It is important to represent station equipment layout/capacitances for TRV studies

TRV: Modeling Considerations

Page 13: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV: Modeling Considerations

The external network is represented in detail up to 1-2 buses away from the substation

• Accurate representation of the fault current level at the station is important

• Accurate representation of the external system using Thevanin’s voltage sources

Detailed representation of substation equipment• Bushing capacitances of equipment

T31

170 km

50 km

120

120

RRL

RL

RRL

T1

BUS 1

69 kV

Page 14: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV: Modeling Considerations

Detailed representation of substation equipment• Bushing capacitances of equipment

Single line Diagram PSCAD Model

a

DS 60 [p

F]

150 [pF]

CT150 [pF]

DS

PT

60 [pF]

150 [pF]

250 [pF]

CT

80 [pF]

SA

CT150 [pF]

SA

80 [p

F]

PT

150 [p

F]

ABC->G

TimedFaultLogic

If

If Fault Current

E2

E1

TRV

I_BR

250 [pF]

BRK 72.5 kV, 40 kA

Breaker

60 [pF]

DS

DS

DS

DS

BR

250 [pF]

DS

60 [pF]

DS

CT

150 [pF]

TLine_3

2000 [p

F]

5000 [p

F]

#1 #2

3000 [pF]

T31

170 km

50 km

120

120

RRL

RL

RRL

T1

BUS 1

69 kV

Page 15: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Typical busing capacitance values

The specific bushing capacitance values may not be available from data sheets.

• Typical values as per IEC/IEEE (IEEE C37.011)

Page 16: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Importance of Bushing/Stray Capacitance: Example: de-energizing a unloaded transformer

Illustration of a simple yet important points

TRV in this case is due to an oscillatory transient. The frequency and magnitude of the transient is thus determined by the L and C of the circuit involved.

• Here, the TRV is mainly due to oscillations on transformer side of the breaker (E2)

• Oscillation frequency : 1/(2𝜋 ∙ √(𝐿𝐶))

• The rate of rise of TRV can be limited by adding capacitance

Page 17: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

First Pole to Clear

The three poles (of breaker) do not break the current at the same instant due to 120 degree phase shift on the 3 phases

• First pole to clear typically has the worst TRV

• Grounding conditions have an impact

Illustration of a simple yet important points

A

B

C

RL

I1

500 [p

F]

B1

B2

B3

500 [p

F]

500 [p

F]

0.1 [H]

0.1 [H]

0.1 [H]E1

Neutral Grounding

With neutral grounded

With neutral not grounded

Page 18: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

The more severe contribution to TRV is imposed from line side.Note that the voltage magnitude is very low.

Triangular TRV (Short Line Fault)- Travelling waves in lines impact TRV

Illustration of a simple yet important points

Page 19: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Generator Breaker TRV Studies - IEEE Std. C37.013

Illustration of a simple yet important points

System-Source Faults

• Fault Current through the breaker from system side

• Single envelop based on MVA rating and kV rating of the machine (No fault duty)

• Relaxed envelope compared to Generator-Source faults

G

Generator-Source Faults

• Fault Current through the breaker from generator side

• Single envelop based on MVA rating and kV rating of the machine (No fault duty)

• Tight envelope compared to System-Source faults

Out-of-Phase TRV

• Single envelop based on MVA rating and kV rating of the machine

G

G

Page 20: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV study scenarios

Study scenarios should be carefully selected after reviewing the breaker arrangements.

Page 21: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Typical study Scenarios

• Station faults (breaker terminal faults)

• Short line faults (2-3 km from the station)

• Remote faults (Ex. mid line faults)

• Faults on Series compensated lines

• Reactor and transformer de-energization

TRV study scenarios

Fault Types

• 3 phase unground fault

o Typically gives the worst TRV

o Not always a credible case

• Three phase faults

• Phase -G faults

Page 22: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

JNS2 NAM2KMT

NAM1IWPP

TR1

SAZ2

Bus 1

Bus 2

G9

G10G6 G8

G7 WDJ G11

SAPRE

TRV should be studied under credible conditions: Study scenarios should be carefully selected.

• Studying the opening of the breaker under condition (a) is meaningless• Study scenario (b) instead.

JNS2 NAM2KMT

NAM1IWPP

TR1

SAZ2

Bus 1

Bus 2

G9

G10G6 G8

G7 WDJ G11

SAPRE

(a) (b)

TRV study scenarios

Page 23: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Example: 380 kV substation TRV study - 22 scenarios were studied for TRV compliance (3 selected scenarios illustrated below)

TRV study scenarios

Page 24: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV withstand capability of circuit breakers

TRV capability is defined by a set of curves • TRV capability is provided by the vendor in the form of family of curves.• If specific capability curves are not available, information in IEC Std. 62271-100 is used for the

study

Pick relevant curve (to compare system TRV waveform)based on actual % current being interrupted.• Example: if the fault current is 24 kA and the breaker is rated for 40 kA, use the 60% curve.

Page 25: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Breaker TRV Capability Curves

• 2 and 4 parameter curves• Adjustments for Short Line Faults (SLF) (Breakers have higher TRV withstand capability

than for station faults)

Two Parameter Four Parameter

TRV withstand capability of circuit breakers

Page 26: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

PSCAD TRV Envelop Module

TRV_C

TRV_B

TRV_A

TRV_C

TRV_B

23

1

TRV_A

Env_C

Env_B

Env_A

BRKB_St

BRKC_St

BRKA_St

TRVEnv

VioBrk

TRV

TRV withstand capability of circuit breakers

Appropriate set of capability curves can be selected based on application:• Breaker connected to cables • Breaker connected to overhead lines• Effectively grounded system• Non-effectively grounded system• Generator fed faults

Page 27: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Station fault

TRV – Typical responses

Page 28: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

Reactor switching (opening)

TRV – Typical responses

Page 29: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

pscad.comPowered by Manitoba Hydro International Ltd.

TRV – PSCAD example cases

75 km

200 km

120 km

100 km

110 km

210 km

T31

170 km

50 km

P = 321Q = 280.1V = 1.006

V

A

120

120

150

120

RL

RRL

RL RRL

RL

RRL

RRL

RL

RRL

BUS 2

BUS 3

BUS 4

BUS 5

BUS 6

BUS 7

P = 161.2Q = -7.936V = 1.039

V

A

P = 177.4Q = -6.726V = 1.039

V

A

T5

T2

T1

T4

T6

T17

T18

BUS 1

69 kV

Breaker TRV Example

- 69 kV transforemr breaker has severe

TRV violation

- 50 nF surge capacitor installed

between transformer and breaker will

solve the problem

Feb -2016

Lalin Kothalawala

Page 30: Transient Recovery Voltage (TRV) Studies•Traveling waves on transmission lines/cables Electromagnetic Transients in Power Systems - Review. ... transient recovery voltage stage where

Thank you