Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American experience]

Presented at the CIGRE Committee C4 Colloquium on

“Lightning and Power Systems”

In Kuala Lumpur, MalaysiaMay 17, 2010

Page 2: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Location of New Brunswick

Page 3: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

NB Power Transmission System

· Includes 6800 km of transmission lines

·Voltage classes include 69, 138, 230 and 345 kV

Page 4: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Lightning Flash Density Map

Page 5: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Protection“Traditional” Approach

· In the traditional approach shield wires are used to capture the lightning strike

· Lightning performance using shield wires is a calculated prediction based on probabilistic methodologies

· Good lightning performance with shield wires is achieved with good grounding

Page 6: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

“Traditional” versus “Arrester” Approach

· The “Traditional” approach using shield wires is to conduct the lightning strike into the ground before a flashover occurs

· The “Arrester” approach is to conduct the lightning strike around the insulator string without a flashover in the air

Page 7: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

“Traditional” versus “Arrester” Approach

· In the “Traditional” approach, a lightning strike directly to a phase or a high energy lightning strike can still cause a flashover

· In the “Arrester” approach, a high energy lightning strike or a defective arrester can cause an arrester failure and a system line to ground fault

Page 8: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

“Traditional” versus “Arrester” Approach

· In the case of shield wires:· Low resistance grounding is necessary for good

performance

· In the case of arresters applied to all insulator strings:· Good performance is not dependent on the ground

resistance

Page 9: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

“Traditional” versus “Arrester” Approach

Shield Wire Grounding· It is not always possible to achieve low resistance grounding at every structure

Arrester Energy Sharing· The ability of transmission line surge arresters to share in the discharge of lightning current can be an important consideration

Page 10: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· In 2007, NB Power constructed a 95 km 345 kV transmission line

Page 11: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· In 2008, this new 345 kV transmission line experienced 4 lightning outages

· The design target for lightning outages is typically 1 outage per year

· 4 outages is a significant deviation from typical lightning performance on existing 345 kV lines on the NB Power system

Page 12: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· Existing NB Power 345 kV lines use a guyed portal design

· The new line uses a tubular H-Frame design· The shielding angle on the new line is identical to existing portal structure design

· Clearances are slightly reduced on the middle phase for the new H-Frame design

Page 13: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Mitigation Strategy

· Determination of location of the four lightning strikes· Fault Locating Relays· Vaisala Lightning Detection System· Field inspections

· Determination of the cause of the lightning outages· Grounding System analysis· Field testing· Helicopter aerial inspection

Page 14: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

No jumpers around bolted connections

Steel foundation is insulated by protective coating

Rust from weathering steel dripping onto

top insulators

Considerations Included:

Page 15: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· The Vaisala Lightning Detection system provided a Strikenet report for each of the 4 lightning strikes

· Within the Strikenet report a lightning strike was identified with the exact time as the recorded fault time on the transmission line

· From this report the strike time, location and intensity were determined

Page 16: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

The Vaisala data along with the structure locations were displayed on Google Earth

Page 17: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· Distance from strike to tower determined

Page 18: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Conclusions· July 24 fault Flashover

· -68 kA strike, 175 m to structure 184, measured 120 ohm impedance at structure, long span both sides

· July 29 fault Flashover or shielding failure· -45 kA strike, 320 m to mid span

· Aug 3 fault Flashover· -29 kA strike, 66 m to structure 109, flash mark on

tower peak

· Oct 2 fault Shielding failure· -11 kA strike, good grounding, long span

Page 19: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Grounding system analysis was carried out :

· Soil resistivity measurements near structures (Wenner 4 point out to 8 meters)

Megger Earth Tester Model - DET4TD· Computer modeling grounding design software

CDEGS RESAP and MALTZ modules· Field measurements to verify structure grounding

impedance AEMC 6472\6474 Ground Tester

Page 20: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Structure Ground Impedance Measurement

· Testing of a single structure while it is interconnected to a multi-grounded system is difficult to do accurately

· A new test set became available in 2008 which addresses this problem using Rogowski coils to measure electrode currents

AEMC Pylon Ground Tester Model 6472 and Model 6474

Page 21: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

AEMC® InstrumentsTower Ground Resistance Testing

System

Page 22: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

GroundFlex Coil Sensors(Rogowski Coils)

Page 23: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

6472/74GroundFlex® Adaptor

· Capable of testing ground resistance of towers without disconnecting the Overhead ground wire

· Tests both ground resistance of tower legs (individually and total) and Overhead ground wires

· Test at frequencies up to 5kHz to profile impedance, important to characterize for lightning strikes

GroundFlex® Method

Page 24: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Foundation · Steel culverts

installed first· Foundation steel

had a Corrocote coating

Page 25: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Structure Grounding· Steel poles, culverts and counterpoise connected together

Page 26: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance

Mitigation

· Structure Grounding Electrical Circuit

· The AEMC Pylon Ground Tester permits a more detailed analysis of structure impedances

Page 27: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· Top sensor measures shield wire impedance

· Bottom sensor measures structure impedance

Page 28: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

· Two sensors on each pole

· Two turns in each sensor

Page 29: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Structure 243· Calculated 7.9 ohms· Measured 6.7 ohms

Structure 248· Calculated 13.3 ohms· Measured 12.9 ohms

Structure 184· Calculated 110.8 ohms· Measured 120 ohms

Structure 144· Calculated 155 ohms· Measured 40 ohms

Important NoteResistivity and Resistance tests were done on the same day

Structure Grounding Results

Page 30: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

345 kV Transmission Line Lightning Performance Mitigation

Summary

•CDEGS Grounding Software and the AEMC Pylon Ground Test Set can achieve a very close comparative result for determination of structure ground impedance

•Lightning performance improvement can be best achieved by improving the structure ground impedance

•A simple soil resistivity measurement along with the CDEGS model can easily predict which structures will require grounding improvement

Page 31: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Lightning Improvements69 and 138 kV Transmission Lines

· Improvements were first considered in 1999 on 69 and 138 kV lines supplying the City of Saint John

· These lines use double circuit steel lattice towers with shield wires as part of the design

· Built in 1950’s these lines are installed over very rocky terrain

Page 32: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Typical 138 kV Double Circuit Structure

Page 33: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Saint John Area Lines69 and 138 kV Transmission Lines

·Salt and industrial contamination has resulted in failure of the shield wires over the years without replacement

·With no shield wires and with towers sitting on rock (poor grounding) lightning outages were a problem

Page 34: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Saint John Area 69 and 138 kV Transmission Lines

Problems with re-installing shield wires:

·Line outages were difficult to obtain· Improving the ground resistance in this urban environment was a huge challenge

·With towers sitting on rock flashovers would still be expected

Page 35: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Saint John Area Line Arrester Application

·Towers prone to lightning strikes were identified using historical information from fault locating relays

·Arresters were applied to all insulator strings on the selected double circuit towers

·No improvements were made to existing tower grounding systems

Page 36: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Typical 138 kV Tower with Arresters

Page 37: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Arrester Installation69 and 138 kV Transmission Lines

·1500 Gapless Arresters were installed under de-energized conditions

· Installation included:· drilling one hole in the steel crossarm· hanging the arrester· connecting the hotline clamp to the conductor

Page 38: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Arrester Kit

Page 39: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Saint John Area Lightning Performance Summary

Structures Before Arresters Structures With Arresters

Year 69 kV Faults 138 kV Faults 69 kV Faults 138 kV Faults

1996 0 0

1997 1 7

1998 4 2

1999 2 1

2000 1 4 0 0

2001 4 0 0 0

2002 0 2 0 0

2003 0 0

2004 1 0

2005 0 0

2006 1 2

2007 0 1

2008 0 0

2009 0 0

Page 40: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

69 and 138 kV Transmission LinesConclusions

Line arresters installed on all insulator strings on a steel tower can provide zero lightning outages for lightning within the arrester energy rating.

This was demonstrated in July 2002 when the City of Saint John was struck by a severe lightning storm which lasted 3 days. Numerous outages were experienced but none at structures where arresters were installed.

Page 41: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Line Arrester Problems – Early Years

·NB Power’s experience spans 10 years with line arresters

·Numerous manufacturing defects as well as installation problems have been experienced

·Some components are showing prematured signs of wear

Page 42: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Manufacturing Defect

Line Arrester Problems – Early Years

Page 43: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

· Improper Installation

Line Arrester Problems – Early Years

Page 44: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Manufacturing Defect

Defective End Cap Moisture Seal

Line Arrester Problems – Early Years

Page 45: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Manufacturing Defect

Defective End Cap Causing Internal Tracking from Moisture Ingress

Line Arrester Problems – Early Years

Page 46: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Manufacturing Defect

Inferior Lugs Broke in Service

Line Arrester Problems – Early Years

Page 47: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Lead & Chain Worn Out After 6 Years of Service

Line Arrester Problems – Early Years

Page 48: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

· Close-up of Chain (6 years service)

Line Arrester Problems – Early Years

Page 49: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Lead Broken Away From Lug

Line Arrester Problems – Early Years

Page 50: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Summary of Defective Arrester Quantities

Supplier 69 kVInstalled/Defective

138 kVInstalled/Defective

A 627/120 794/220

B 516/3

C 30/30

Line Arrester Problems – Early Years

Page 51: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance

Mitigation•Lightning performance of transmission lines with shield wires can be improved by lowering the structure ground impedance

•Transmission line lightning performance can also be improved by installing transmission line surge arresters (TLSA)

J Williamson Engineering Inc

Page 52: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Shield Wire Performance

J Williamson Engineering Inc

Page 53: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

J Williamson Engineering Inc

Transmission Line Lightning Performance

Page 54: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

New Transmission LinesLightning Performance Determination

· Identify the Lightning Ground Flash Density for the location

· Select structure type and voltage· Model the structure and line in Sigma SLP Lightning Performance software

· Calculate the Lightning Flashover Rates for:· Different values of ground impedance· With and without shield wires· Partial and full application of arresters

· Select the appropriate design to match the desired lightning performance

J Williamson Engineering Inc

Page 55: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance

Example # 1· 138 kV Transmission Line· Wood Pole H-Frame Construction· Two Shield Wires with 30 degree Shield Angle· 7 Suspension Porcelain Insulators· 695 kV Critical Impulse (+)· Structure Ground Resistances 25 to 125 ohms

J Williamson Engineering Inc

Page 56: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Lightning Performance AnalysisSigma SLP Software

J Williamson Engineering Inc

Page 57: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance Example # 1 with GFD = 0.2

J Williamson Engineering Inc

Page 58: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance Example # 1 with GFD = 1.0

J Williamson Engineering Inc

Page 59: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance Example # 1 with GFD = 8

J Williamson Engineering Inc

Page 60: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Transmission Line Lightning Performance

Example # 2

· 138 kV Transmission Line· Single Pole Wood Construction· No Shield Wire· Two Side and One Vertical Post Polymer Insulator· 675 kV Critical Impulse (+)· Structure Ground Resistances - 25 to 125 ohms

J Williamson Engineering Inc

Page 61: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Arrester on Top Phase

UnderbuiltShield Wires 5 ohms

25 ohms

50 ohms

75 ohms

100 ohms

125 ohms

No No 86.06 83.77 85.89 85.27 85.76 85.06No Yes 84.55 87.67 83.91 84.74 86.95 85.89Yes No 0 0 0 6.76 18.3 21.51Yes Yes 0 0 0 0.85 3.46 7.82

Transmission Line Lightning Performance Example # 2 with GFD = 8

Flashover Rates

•Top phase arresters will significantly improve lightning performance•For lines with top phase arresters and where ground impedance is high, lowering ground impedance and/or installing under built shield wire will improve lightning performance

J Williamson Engineering Inc

Page 62: Transmission Line Surge Arrester Application and Overhead … · 2018-08-23 · Transmission Line Surge Arrester Application and Overhead Shield Wire Grounding Issues [North American

Presentation Summary

· NB Power Transmission System· Traditional Shield Wire versus Arrester Approach· Shielded 345 kV Transmission Line Lightning

Performance Mitigation· 69 and 138 kV Arrester Application on Steel Towers

· Performance Results over 10 Years· Defects in Early Years

· Lightning Performance Determination on New Lines