49
GEI-100795U Trender Instruction Guide These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein. Public Information – This document contains non-sensitive information approved for public disclosure. GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not provide any license whatsoever to any of these patents. GE provides the following document and the information included therein as is and without warranty of any kind, expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose. For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative. Revised: Nov 2020 Issued: Nov 2011 © 2011 – 2020 General Electric Company. ___________________________________ * Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners. We would appreciate your feedback about our documentation. Please send comments or suggestions to [email protected] Public Information

Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

GEI-100795U

TrenderInstruction Guide

These instructions do not purport to cover all details or variations in equipment, nor to provide for every possiblecontingency to be met during installation, operation, and maintenance. The information is supplied for informationalpurposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications,and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflectedherein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or tothe document itself at any time. This document is intended for trained personnel familiar with the GE products referencedherein.

Public Information – This document contains non-sensitive information approved for public disclosure.

GE may have patents or pending patent applications covering subject matter in this document. The furnishing of thisdocument does not provide any license whatsoever to any of these patents.

GE provides the following document and the information included therein as is and without warranty of any kind,expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness forparticular purpose.

For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE SalesRepresentative.

Revised: Nov 2020Issued: Nov 2011

© 2011 – 2020 General Electric Company.___________________________________* Indicates a trademark of General Electric Company and/or its subsidiaries.All other trademarks are the property of their respective owners.

We would appreciate your feedback about our documentation.Please send comments or suggestions to [email protected]

Public Information

Page 2: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Document UpdatesRevision Location Description

U Capture Buffer/Dynamic Data Recorder Trend Updated to include V07.09.00C statement.

T

Overview

Eliminated the section Display Features and moved the content to thissectionUpdated the figure Trender Features

Retrieve DataMoved the figure Trender Toolbar to the section Overview and updatedthe figure to include the Preset Time Ranges button

Live Auto-range Trace New section to describe Live auto-range Trace

Throughout document

Removed reference to Proficy Machine Edition (PME) as this is nolonger a GE applicationUpdated all figures to include Log tab and Preset Time Ranges toolbarbutton

R Expand Traces List on Mouse Hover New section to describe a new Trace setting

Q Retrieve Data

Updated the Trender Toolbar figure, and other graphics throughout thedocument, to include the Select Chapter button, which allows the userto jump to a specific chapter in the Trender.Added the procedure To display a specific chapter.

P Capture Buffer/Dynamic Data Recorder TrendAdded the section Stored Capture Buffer Data to provide theprocedure to access stored capture buffer data after a loss of power

Acronyms and AbbreviationsCDM Combustion Dynamics MonitoringCSV Comma Separated ValueDDR Dynamic Data RecordersFFT Fast Fourier TransformHMI Human-machine InterfaceOPC DA OPC Data AccessOPC UA OPC Unified Architecture

2 GEI-100795U GEI-100795 TrenderPublic Information

Page 3: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Contents1 Overview ....................................................................................................................................................42 Data Sources................................................................................................................................................72.1 Live Trend.............................................................................................................................................92.2 Historical Trend.................................................................................................................................... 162.3 Capture Buffer/Dynamic Data Recorder Trend ........................................................................................... 172.4 Static File Trend ................................................................................................................................... 262.5 CDM On Demand................................................................................................................................. 272.6 Retrieve Data ....................................................................................................................................... 272.7 Variable Status ..................................................................................................................................... 28

3 Concepts ................................................................................................................................................... 293.1 Chapters.............................................................................................................................................. 293.2 Cursor Values....................................................................................................................................... 293.3 Events ................................................................................................................................................ 313.4 Historical Fill ...................................................................................................................................... 32

4 X-Y Trending ............................................................................................................................................ 335 Graph View ............................................................................................................................................... 355.1 Sample Markers.................................................................................................................................... 395.2 Time Axis ........................................................................................................................................... 40

6 Trace Settings ............................................................................................................................................ 426.1 Auto-range Trace .................................................................................................................................. 426.2 Live Auto-range Trace ........................................................................................................................... 426.3 Manual Range Adjustment...................................................................................................................... 426.4 Colors................................................................................................................................................. 426.5 Hide or Show Traces ............................................................................................................................. 436.6 Statistical Calculations........................................................................................................................... 436.7 Expand Traces List on Mouse Hover ........................................................................................................ 44

7 Command Line Arguments ........................................................................................................................... 458 Print and Export Data .................................................................................................................................. 469 Spectral Analysis ........................................................................................................................................ 47

Instruction Guide GEI-100795U 3Public Information

Page 4: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

1 OverviewTrender captures and displays trend graphs of variables in a configured system and can collect and display values in real timefrom controllers and other data sources. It can also display data collected by high-speed coherent data collection systems,such as Capture Buffers and Dynamic Data Recorders (DDR). Trender can also display previously captured data and tracesfrom a saved data file. Users can create as many Trenders as necessary.

Trender is installed with the ControlST* Software Suite and can be opened from the Windows® Start menu or the ToolboxST*application. When Trender is opened from the Start menu, users can select a location on their computer to which to save thetrend file. When Trender is opened from ToolboxST, the trend file is automatically saved in the Tools folder or in the systemcomponent folder. The following table provides the locations from which Trender may be opened, opening instructions, andhow to add variables from this location.

Trender can also be installed with the WorkstationST* application with limited available data sources.

Trender OpeningLocation Action to Start Trender Trace Data Source

Start MenuFrom the Start menu, select All Programs, GEControlST, ToolboxST, and Trender.

Select variables using Add Trace Wizard.ToolboxST System Editor

From the Tree View, right-click the componentand select Insert New, Tool, and Trender.From the Tree View, double-click Trender.

ToolboxST Component Editor From the View menu, select Trenders.Select variables using Add Trace Wizard(typically the Live data source).

Block Diagram Editor Right-click a block and select Add to Trend. Add variables to the Trend as live traces.

CIMPLICITY* CimViewRight-click a graphic object and selectGo To Trend to launch WorkstationSTHuman-machine Interface (HMI) Trender.

Variables tied to object in focus on CimViewwindow added to trend as live trace, othervariables can be added from localWorkstationST

Watch WindowRight-click a variable and select Add toTrender.

Select variables from ToolboxSTcomponentor using Add Trace Wizard as live traces.

4 GEI-100795U GEI-100795 TrenderPublic Information

Page 5: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Unit Data Highway (UDH)

Third-party OPC DA/UA

Server

Trender

ToolboxST

Recorder

Dynamic Data Recorders (DDRs)Turbine trip logsDCA trend files

OPC DA Server

Live data:- Mark VIe- EX2100e- LS2100e- WorkstationST- Third-party sources

CaptureBuffer

StatusVar 1

Var 2

Var n

Mark VIe Controller

7

5WorkstationST

3

Process Model

2

8

Historical Variable Trace Data

Live Variable Trace Data

Mark VIe Controller

Proficy / PI Historian

1

46

1

Data Source of Trend Data When Variable Browsing

Live ToolboxST component Variables tied to system component the ToolboxST application has open

2

Live System component, such as Mark VIe controller

Variables tied to system component selected

3

Live OPC DA/UA ServerVariables from third-party OPC DA or UA Servers4

Historical RecorderSelect DDR, turbine trip log, or other archived trend file

5

Historical Historian Variables logged by Historian

6

Historical Capture Buffer in Mark VIe controller

Variables configured in Capture Buffer

7

Variables configured in local WorkstationST application

8

Live Local Process ModelVariables configured in local process model

Live Local WorkstationST application

Legend

Trender Data Flow Diagram

Note When live trending is occurring, changes made to a controller configuration are not reflected until Trender is restarted.

Instruction Guide GEI-100795U 5Public Information

Page 6: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

The following figure illustrates and identifies the Trender features.

Trender Features

The Graph View displays trend values represented by each configured trace.

The Property Editor allows users to change settings that affect the capture and data display.

The Trender toolbar provides buttons used to perform Trend commends and retrieve captured data.

Trender Toolbar

Note If Trender is opened from ToolboxST, the Trender toolbar may have fewer buttons than shown in this figure.

The Auxiliary View provides the following tabs that display information about the current data:

• Traces tab displays all trending variables• User Note tab allows the user to save comments, instructions, or notes about the current chapter• Sources tab displays the sources from which data is collected• Events tab lists all events that have occurred during the current chapter• Log tab displays any errors, warnings, and messages that occurred during Trending. A .log file that reflects these items is

also available in the ToolboxST Component folder.

6 GEI-100795U GEI-100795 TrenderPublic Information

Page 7: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2 Data SourcesVariables can be added to Trender from several different data sources that can provide live or historical data. A historical datasource (such as Historian and WorkstationST Recorder) can have thousands of variables with data values that were sampledevery second and span the previous year. Other historical data sources (capture buffers, trip logs, and such) may have fewvariables with values that were sampled every ms over a short period of time. While any number of variables can be added toTrender, all must come from the same type of data source. (For example, you cannot display both live and static file variablessimultaneously.)

Trender represents each variable with a trace. A trace is similar to a digital storage oscilloscope, which displays data bytracing a line across the screen as values are acquired. Traces added to a trend display in the Traces tab. Variables are addedusing the Add Trace Wizard.

Note When a system component providing data source signals to a Trender is replicated, the Trender is replicated, as well.However, previously traced data is not available in the replicated Trender.

➢➢ To add traces and select a data source

1. From the Edit menu, select Add Traces to open the Add Trace Wizard.

2. When the Welcome window displays, click Next.

3. Select the trend type and click Next.

Add Trace Wizard

Note HMI Trender supports Live data trending from local WorkstationST applications and third-party OPC DA/UA servers,Historical data from Recorder or Historian configured WorkstationST applications, and static data file types.

Instruction Guide GEI-100795U 7Public Information

Page 8: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

a. If Live is selected, the next window in the Wizard allows you to select the live data source of the variables. Refer tothe section Live Trend.The available Live data sources are as follows:

i. System Component provides specific data from a ToolboxST system component. Not applicable to HMITrender.

ii. Local WorkstationST provides data from the WorkstationST application running on the same computer asTrender.

iii. OPC DA Server provides data from any OPC DA server, including third-party servers, even if the server is notpart of the ControlST system. Select this to obtain data from the WorkstationST OPC DA server if it runs on adifferent computer, or to test OPC DA capabilities of the local WorkstationST application.

iv. OPC UA Server provides data from any OPC UA server, even if the server is not part of the ControlST system.Refer to the section OPC UA as Data Source.

v. Model provides data from a simulation running either an Easy5 or a Dynsim model.

b. If Historical is selected, the next window allows you to select the historical data source. Refer to the sectionHistorical Trend.

c. If Capture Buffer / Dynamic Data Recorder is selected, the next window allows you to select the system filecontaining the capture buffer or DDR. Refer to the section Capture Buffer/Dynamic Data Recorder Trend.

d. When Static is selected, the next window allows you to select the type of file containing the static data source.Refer to the section Static File Trend.File types include:

i. COMTRADE files

ii. CSV files

iii. D04 files

iv. DCA/DcaST files

v. TRN files

e. If CDM On Demand is selected, the next window allows you to browse to the .tcw file that contains a controllerwith a configured WorkstationST component and an AM Gateway. Refer to the section CDM On Demand.

8 GEI-100795U GEI-100795 TrenderPublic Information

Page 9: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.1 Live TrendLive trends are useful for monitoring systems in continuous operation. Trender displays live trends as incoming data in realtime.

➢➢ To add traces from a Live data source

1. From the Edit menu, select Add Traces.

2. When the Welcome Wizard displays, click Next.

3. Select Live and click Next.

4. Select the data source of the variables and click Next.

Note The following steps assume System Component was selected as the Live data source. The other Live data sourceswill open dialogs to connect to the correct source.

5. Select the component with the variables to trend and click Next. When running Trender from the Start menu, the nextwindow requires you to first select the system, then the component.

6. Select the time period to trend the data and click Next. For controller data, this must be a multiple of the controller framerate.

7. Click Add to display the Select a Variable dialog box.

8. Select the variables to trend, then click OK.

Note If there are already traces in Trender, you can add additional traces from the same data source or component.

Variables Selected for Trending

9. Click Finish to start the trend.

Instruction Guide GEI-100795U 9Public Information

Page 10: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

ToolboxST System Component Frame Period

The default frame period for a trend in ToolboxST is the frame rate set in the system component. The frame period can bechanged in the Property Editor from the Sources tab or from the Add Trace Wizard. For more information about frame rateconfiguration in a ToolboxST system component, refer to the ToolboxST User Guide for Mark Controls Platforms (GEH-6700or GEH-6703), the section General Tab.

➢➢ To select a frame rate: from the Sources tab, select the controller, then select the frame rate from the Property EditorPeriod property drop-down menu.

Default Trender Frame Period

10 GEI-100795U GEI-100795 TrenderPublic Information

Page 11: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.1.1 OPC UA as Data Source

➢➢ To obtain data from an OPC UA server used with ToolboxST

1. From the Edit menu, select Add Traces.

2. When the Welcome Wizard displays, click Next.

3. Leave the default trend type as Live and click Next.

4. Select OPC-UA Server as the data source for the variables and click Next.

OPC UA Sever Selected as Data Source

Attention

To connect to an OPC UA server, you must have that server’s Security Certificate inyour certificate store. For further details, refer to ToolboxST User Guide for MarkControls Platform (GEH-6700 or GEH-6703), the section Security Certificate/UserAssociation.

Instruction Guide GEI-100795U 11Public Information

Page 12: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

5. Configure the OPC UA server from which to trend variables.

OPC UA Client Server Connection Configuration

Provide the OPC UA server configuration settings as follows:

Discovery URL: allows the user interface to browse registered OPC UA servers at the selected URL. The default URL opc.tcp://localhost:4840 allows the Endpoint URL drop-down menu to display registered OPC UA servers on the local computer.

Endpoint URL: defines the OPC UA server’s endpoint and optional security settings. Select one of the servers available fromthe Discovery server listed in the drop-down menu, or enter a known URL. Example URLs (provided hyperlinks) aredisplayed for known GE OPC UA servers.

Security Settings: the client can be configured to use a specific security profile using the Security Policy andMessageSecurity Mode drop-down menus, or the client can be made to use the most secure endpoint exposed by the server byselecting the Use Best Security check box. To use no security and avoid exchanging application certificates, select a SecurityPolicy of None and a Message Security Mode of None (the server must support the None security profile).

Authentication settings: the client can be configured to use an anonymous user or a user name and password.

12 GEI-100795U GEI-100795 TrenderPublic Information

Page 13: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.1.2 Add Additional Traces

➢➢ To add additional traces

1. From the Edit menu, select Add Traces. The Select a Variable dialog box displays available variables for thatcomponent.Or click the Add Traces button on the Trender toolbar at the bottom of the Trender window.

2. Click the Add drop-down arrow and select Add using Add Trace Wizard to add variables from a differentcomponent.

The selected variable displays in the Traces tab in the Auxiliary View.

➢➢ To remove traces: from the Edit menu, select Remove Selected Traces.

Instruction Guide GEI-100795U 13Public Information

Page 14: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.1.3 Triggered TrendTrends from a Live data source can optionally be configured to collect incoming data when a specific triggered event occursin the control system. A triggered event can capture data for a predetermined period before and after the event occurs.

Note These options apply to the current trend only.

➢➢ To configure a triggered trend

1. Add a Live trend.

2. From the File menu, select Properties or click the Trender Properties button.

3. Enter the Triggered Recording values for each option.

From the Non Triggered drop-down list, select Edge or Level.

Options for triggered trends display.

Triggered Trend Recording Properties

14 GEI-100795U GEI-100795 TrenderPublic Information

Page 15: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Options for the Triggered Recording include:

• Max Captures is the maximum number of chapters to collect due to a recurring trigger.• Post-trigger Time is the time to capture values after the trigger occurs.• Pre-trigger Time is the time to capture values before the trigger occurs.• Trigger Compare is how the trigger trace value is compared to the trigger value to determine when the value is

captured (for example, greater than).• Trigger Mode can be either edge or level.

− Edge collects pre-trigger and post-trigger samples.− Level collects pre-trigger and post-trigger samples, and also continues to

collect samples until the signal goes False.• Trigger Trace is the trace whose value is compared against the trigger value.• Trigger Value is the value to which the trigger trace value is compared.

While Trender is waiting for the trigger to occur, Pre-Trigger displays in the status bar.

While Trender is collecting data after the trigger occurs, Post-Trigger displays.

Instruction Guide GEI-100795U 15Public Information

Page 16: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.2 Historical Trend➢➢ To add traces from a Historical data source

1. From the Edit menu, select Add Traces.

2. When the Welcome Wizard displays, click Next.

3. Select Historical as the trend type and click Next.

4. Select the Computer name of the workstation configured with the Recorder or Historian feature.

• Data Source automatically populates to identify the type of historical data (Recorder or Historian).• Server and Collection is the source of the data.

− Server (Historian) specifies the OPC HDA server to use.− Collection (Recorder) specifies the live data collection to use.

5. Click Next to continue.

6. Click Add to display the Select a Variable dialog box and select variables to trend.

7. Click OK, then click Finish.

Historical Trend Window

Note The Zoom to Data command in the View menu does not apply to either Historical trends or to the Historical Fillfeature.

16 GEI-100795U GEI-100795 TrenderPublic Information

Page 17: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.3 Capture Buffer/Dynamic Data Recorder TrendMany components use different methods of high-speed synchronous data capture. While each method addresses differentneeds, all methods are accessed as capture buffers in Trender because they have similar underlying data collectionmechanisms.

Note When running Trender from the Start menu, an extra wizard window displays for the system selection before thecomponent window displays.

➢➢ To add traces from a capture buffer data source

1. From the Edit menu, select Add Traces.

2. When the Welcome Wizard displays, click Next.

3. Select Capture Buffer / Dynamic Data Recorder and click Next.

4. Select the component and click Next to display a list of all available capture buffers.

5. Select one capture buffer and click Finish.

Capture Buffer Trend List

Instruction Guide GEI-100795U 17Public Information

Page 18: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Stored Capture Buffer Data

Capture Buffer data that was saved immediately before the loss of control power is accessible from ToolboxST. A newCapture Buffer must be created using the Trender Wizard, but instead of creating an empty Capture Buffer, access thetime-and-date stamped Capture Buffer containing the stored data.

➢➢ To access stored Capture Buffer data

1. From the ToolboxST Component Editor toolbar, select View, then select Trenders.

2. Click Add, enter a name for the Trender, and click OK.

18 GEI-100795U GEI-100795 TrenderPublic Information

Page 19: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

3. From the blank Trend Edit menu, select Add Traces.

Instruction Guide GEI-100795U 19Public Information

Page 20: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

4. When the Add Trace Wizard Welcome window displays, click Next.

20 GEI-100795U GEI-100795 TrenderPublic Information

Page 21: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

5. Select Capture Buffer / Dynamic Data Recorder and click Next.

Instruction Guide GEI-100795U 21Public Information

Page 22: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

6. Select the appropriate component (device) from the drop-down menu for which the Capture Buffer was created (defaultsto last device you worked in), and click Next.

22 GEI-100795U GEI-100795 TrenderPublic Information

Page 23: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

7. Select the Capture Buffer with the last date and time in the system (not saved to flash). The most current one should bethe last one created before power loss. Starting with V07.09.00C, if the associated Capture Buffer Upload Type isTripFlash, then in addition to uploading the Capture Buffer Data, Trender will also upload extra data for the variablesthat it reads from the Compressed Data Log.

8. Click Finish to load the trend variables.

Instruction Guide GEI-100795U 23Public Information

Page 24: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

9. Click the Upload icon to upload the saved Capture Buffer data for the variables.

24 GEI-100795U GEI-100795 TrenderPublic Information

Page 25: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Stored Capture Buffer Data Retrieved

Instruction Guide GEI-100795U 25Public Information

Page 26: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.4 Static File TrendIn addition to acquiring data from a component, Trender can also display data from a static file stored on a hard disk. Thereare five static file formats:

• COMTRADE• Comma Separated Value (.csv)• Static (D04)• Data Collection and Analysis (.dca/.dcaST)• GE Control System Toolbox Trend (.trn)

Note The procedure to add a trace is identical for all static files.

➢➢ To add trace(s) from a Static File data source

1. From the Edit menu, select Add Traces.

2. Select Static as the trend type and click Next.

3. Select the type of data source to import from and click Next.

Static File Data Source List

4. From your computer, select the appropriate file and click Open.

5. From the Select Variables wizard, click Add.

6. From the Select Variables dialog box, select one or more variables.

7. Click OK, then click Finish.

26 GEI-100795U GEI-100795 TrenderPublic Information

Page 27: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

2.5 CDM On DemandIf you select the Skip opening system configuration file check box, the next window allows you to manually enter the name ofthe WorkstationST component running the AM Gateway and the controller that contains the PAMC I/O module forCombustion Dynamics Monitoring (CDM). You can also select them from the provided drop-down lists.

Note For more information, refer to the ToolboxST User Guide for Mark Controls Platform (GEH-6700 or 6703), thechapter Special I/O Functions, and the section Configure PAMC I/O Module.

2.6 Retrieve DataLive and Capture Buffer traces do not initially contain any data because they depend on the presence of a controller. Onceconnected to the controller, the procedure for obtaining data depends on the type of traces present. Data from Live traces iscaptured in a way similar to the way a video recorder operates (using Record and Pause buttons). Data from a Capture Bufferis uploaded from the controller in a single operation. When data from a Static file source is imported, it automatically displaysin the trace.

Capture buffer data is uploaded either On Demand or at Capture Completed. On Demand uploads the data currently in thecapture buffer. Capture Completed uploads the data only when the capture buffer is in a complete state. The default is OnDemand.

➢➢ To change the upload mode: from the File menu, select Properties and enter the Upload Mode value.

Note If any of the source controllers are redundant, Trender prompts you to select a redundant channel before opening theconnection.

➢➢ To capture, pause, or retrieve data

1. Click the Online icon.

2. From the Trender toolbar, click the Record Data icon to change Trender to Live mode. The Graph View continuouslyscrolls the time axis to display the latest incoming data while recording.

Note The Trender toolbar buttons may vary according to the data source of the current trace. For example, if CaptureBuffer data is being retrieved, the Record button changes to Upload. If historical data is being retrieved, the Recordbutton changes to Refresh.

For more information on the Trender toolbar, refer to the section Overview.

3. Click Pause to pause recording. The data continues to be collected but Trender switches to Replay mode until Pause isselected again.

4. Click Record Data again and Trender returns to Replay mode.

➢➢ To navigate between chapters: click Previous Chapter or Next Chapter. For more information, refer to thesection Chapters.

Note If these options are grayed, there are no other chapters available.

Instruction Guide GEI-100795U 27Public Information

Page 28: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

➢➢ To display a specific chapter

1. From the Trender toolbar, click the Select Chapter drop-down arrow to display a list of available chapters. (Refer tothe figure Trender Toolbar.)

2. Select a chapter from the list to display that specific chapter in the Trender. The Chapter page number displays in thelower right corner of the Trender.

Note The Select Chapter feature can be used as an alternative to using the Next Chapter and Previous Chapter buttons,which move through chapters one at a time.

2.7 Variable StatusThe Auxiliary View displays the trending variables. Healthy variables display in green. If the variable is unhealthy, the valuedisplays in red and it is followed by the letter U.

Variable Status LettersLetter DescriptionU UnhealthyF ForcedA AlarmedK Alarm acknowledgedS Simulated

28 GEI-100795U GEI-100795 TrenderPublic Information

Page 29: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

3 Concepts

3.1 ChaptersTrender can record more than one set of data. The basic unit of data capture in Trender is a chapter. A chapter represents onesession, which is either a single upload for a Capture Buffer trend or a single period between clicks of the Record Data buttonfor a Live trend. Chapters are organized chronologically, so the first session is always the first chapter and the most recentsession is always the last chapter.

Trender only displays one chapter of information at a time. The user can navigate between chapters. Each chapter maintainsits own traces and events. The Events tab only displays events applicable to the currently displayed data. Similarly, the UserNote tab is unique to each chapter so comments about a data set are stored alongside each chapter.

3.2 Cursor ValuesIn the Graph View replay mode, two cursors individually select values of time and together select ranges of time. The cursorsare used by a number of functions in Trender, such as trace statistics, user events, and data export. The time represented byeach cursor is displayed in the status bar in the bottom of the Trender window.

Cursor Active cursor Click cursor to activate

Graph View Cursor Values

Instruction Guide GEI-100795U 29Public Information

Page 30: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

➢➢ To select a range of time: click and drag each cursor to the desired left and right boundaries.

Cursor values are defined as follows

• Min Value is the minimum sample value between the left and right cursors.• Max Value is the maximum sample value between the left and right cursors.• Left Value is the value at the left cursor.• Right Value is the value at the right cursor.

Time Range Values

Tip � When selecting a range of values, there is no left or right cursor – you may arrange the cursors in whichever way ismost convenient. Trender automatically identifies the left-most and right-most cursors.

While there are always two cursors on the Graph View, it can appear that there is only one cursor if both are set to the sametime value.

Additional tips once the cursor is activated:

• The left or right arrow keys can be used to fine position the cursor.

• [Ctrl]+right arrow and [Ctrl]+left arrow can be used to jump to exact data samples on the top trace.

If you rest the pointer over an axis or a trace in the Graph View, Trender displays the exact value in a screen tip.

30 GEI-100795U GEI-100795 TrenderPublic Information

Page 31: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

3.3 EventsThe Events tab displays the time and description of all events in the current chapter. The Number column displays the alarmID. This number is assigned by the system to each event. Alarm IDs are unique within the system, but can change within acomponent during a Build. They identify a particular alarm instance from a list of alarms with the same text or variable name.

➢➢ To retrieve events: from the Properties dialog box, set the Enable Events property to True.

Note Alarms and events will not be logged to Trender if it is connected to a non-designated controller.

During real-time monitoring of the controller, alarms and diagnostics display in the Trender Graph View as a small triangle on the time axis.

➢➢ To jump to an event: from the Event tab, double-click the description.

Note In addition to events added by the controller, you can add your own user events. If added during Live mode, the userevent is placed at the time of the most recently received sample at the instant the Add User Event command is selected.During replay mode, new user events are added at the time indicated by the active cursor. (For more information, refer to thesection Cursors Values.)

➢➢ To add a user event

1. Select an active cursor.

2. From the Edit menu, select Add User Event.

3. Enter a name and click OK.

Instruction Guide GEI-100795U 31Public Information

Page 32: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

3.4 Historical FillThe Historical Fill option allows you to capture historical data while recording live trends.

➢➢ From the File menu, select Properties.

The Enable Historical Fillproperty is set to True by default.

Historical data is retrieved when Trender starts recording the live data. Trender retrieves three times the trend duration worthof historical data. For example, if the trend duration is one minute, three minutes of historical data is retrieved.

Note Historical data for a variable can only be retrieved if the variable is being collected by the Recorder in theContinuousLive collection or by the Historian.

When in Replay mode, scrolling backward past the last collected data in the Graph View starts a historical fill.

32 GEI-100795U GEI-100795 TrenderPublic Information

Page 33: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

4 X-Y TrendingThe X-Y Trending feature allows you to plot one variable against another.

➢➢ To plot two variables

1. Set the X variable.

From the Traces tab, right-click the variable and select Set as X Variab le.

2. Set the X-Y plot.

From the View menu, select X-Y Plot .

Instruction Guide GEI-100795U 33Public Information

Page 34: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Sine and Cosine Wave Example

34 GEI-100795U GEI-100795 TrenderPublic Information

Page 35: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

5 Graph ViewThe Graph View can display data on either a single graph or a set of stacked graphs. Single Trace mode displays all traces onthe same graph, while Stacked Trace mode displays each trace on an individual graph. In both modes, all traces share thesame time axis, but each trace maintains its own vertical axis.

Note When a trend is first opened in Single Graph mode, the vertical axis corresponds to the first trace listed on the Tracestab. Each trace is drawn according to its own scale. Traces other than the first trace may not correspond to the displayedvertical axes.

If there are too many traces to display stacked graphs effectively in the available space, Trender may revert to Single Tracemode even if you have selected Stacked Trace mode.

➢➢ To display additional vertical axes

1. From the File menu, select Properties.

2. From the [name] Properties dialog box, set the Left Axes to the desired value.

Instruction Guide GEI-100795U 35Public Information

Page 36: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

3. From the Select Axis for Trace dialog box, select the vertical axis to attach the selected trace to and click OK.

36 GEI-100795U GEI-100795 TrenderPublic Information

Page 37: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

In this example, the selected trace (cyan) displays over the selected vertical axis (green)

Stacked Trace Mode, Single Trace Mode

Instruction Guide GEI-100795U 37Public Information

Page 38: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

➢➢ To turn Stacked Trace mode on or off: from the View menu, select Stacked Traces.

Trender can display grid lines that correspond to major axis divisions on the Graph View. These lines, which only displaywhen Trender is in Replay mode, can be useful when the exact trace values are important.

Grid Lines On, Grid Lines Off

➢➢ To enable or disable grid lines

1. From the Options menu, select Settings.

2. From the Grid Lines category, set the values for Horizontal and Vertical to either True or False.

3. Click OK.

38 GEI-100795U GEI-100795 TrenderPublic Information

Page 39: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

5.1 Sample MarkersWhen exact values at each sample reading are important, Trender can display Sample Markers at each collection point. Bydefault, Sample Markers display when the current Graph View contains ten or fewer samples. If desired, you can set theSample Marker threshold.

Sample Markers Graph View

➢➢ To set the Sample Marker threshold

1. From the Options menu, select Settings.

2. From the General category, enter a value for Sample Markers.

3. Click OK.When a cursor is positioned on the exact sample value on a trace, the value displayed in the Traces tab is marked with anasterisk (*) (even if sample markers are not displayed on the trend).

Instruction Guide GEI-100795U 39Public Information

Page 40: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

5.2 Time AxisThe time axis controls the range of samples that display in the Graph View. All traces share a single time axis, even whenStacked Trace mode is enabled. Time axis adjustments are made from the Trender toolbar.

➢➢ To change the range displayed on the Time Axis: click Reverse or Forward.

➢➢ To display a shorter or longer period of time: click Zoom In (to reduce the duration) or Zoom Out.

Note You can also click the time axis and, from the Property Editor, edit the Duration property.

The Zoom In and Zoom Out commands perform differently depending on the mode. In Live mode, Zoom In sets the durationto one third of the current value, and Zoom Out sets the duration to three times the current value. In replay mode, Zoom Outstill sets the duration to three times the current value, but Zoom In sets the duration to the exact region selected by the twocursors. For more information on selecting a range, refer to the section Cursor Values.

Tip � To quickly change the axis range, click any point on the axis and drag it to a new location. This works for both thevalue and time axes, and is frequently the most effective way to change the displayed set of data.

Horizontal Axes

Each trace can have a horizontal axis or a single axis can be used for multiple traces.

Horizontal axes are locked by default

40 GEI-100795U GEI-100795 TrenderPublic Information

Page 41: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Example of locked horizontal axis (one axis for three traces)

Example of unlocked horizontal axis (one axis for each trace)

Unlocked axes are individually scrollable

Instruction Guide GEI-100795U 41Public Information

Page 42: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

6 Trace SettingsTrender maintains separate settings for each trace. These settings, which include trace color, precision, and pen width, areaccessed through the Property Editor when a trace is selected on the Trace tab. Additionally, range properties allow anappropriate scale to be set for the value (vertical) axis for each trace.

6.1 Auto-range TraceTo display a set of collected samples in the Graph View, an appropriate value axis range must be selected. For most data sets,an optimal range displays all collected samples in the selected time range with minimal wasted space. The Auto-range featuresets the range of the value axis for the currently selected trace(s) to the optimal values. Even if you decide to further refine therange of the trace, the Auto-range feature provides a convenient starting point.

➢➢ To auto-range a trace: from the Traces tab, select one or more traces and from the Trender toolboar, clickAuto-Range Selected Traces. (Refer to the figure Trender Toolbar.)

6.2 Live Auto-range TraceTraces may be configured to perform live auto-ranging, which means that during live trending the Trender will automaticallyre-adjust the range of the value axis any time the value of the trace goes above or below the displayed range for the trace.

➢➢ To enable live auto-ranging for a trace: from the Traces tab, select one or more traces and, from the PropertyEditor, set the Live Auto Range property to True.

6.3 Manual Range AdjustmentWhen Auto-Range Selected Traces selects an inappropriate range, or if you want precise control over the range, you canprovide a minimum and maximum value for the value (vertical) axis.

➢➢ To manually adjust the range for a trace: from the Traces tab, select one or more traces and, from the PropertyEditor, set the Bottom Value and Top Value.

6.4 ColorsThe Trender assigns each new trace a color from a set of eight stored in the Settings dialog box. After eight traces are created,these colors are reused.

➢➢ To change an assigned color

1. From the Traces tab, select a trace.

2. From the Property Editor, select the Color property.

3. From the drop-down list, select a color and click OK.

➢➢ To modify default trace colors

1. From the Options menu, select Settings.

2. From the Property Editor, select the trace to be changed.

3. From the drop-down list, select the desired trace color and click OK.

42 GEI-100795U GEI-100795 TrenderPublic Information

Page 43: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

6.5 Hide or Show TracesTrender can contain more traces than can be monitored at once such as with capture buffers. Traces that are hidden still collectdata, but they do not display in the Graph View or the Trace tab.

➢➢ To hide or show traces

1. From the Traces tab, select one or more traces.

2. From the Edit menu, select Hide Selected Traces or Show Traces.

6.6 Statistical CalculationsIn Replay mode, Trender can calculate a set of basic one-variable statistics for the collected data. These statistics, which arecalculated only on the data in the time range selected by the two cursors, include Difference, Average, Maximum, Minimum,and Standard Deviation (calculated as final – initial). The calculated values display as columns on the Traces tab.

➢➢ To display statistical calculations

1. From the Options menu, select Settings.

2. From the Tree View, select Replay Columns.

3. From the Available list, select one or more columns and click either Add or Add All to move the statistics to theSelected list.

4. Click OK.

Instruction Guide GEI-100795U 43Public Information

Page 44: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

6.7 Expand Traces List on Mouse HoverIf the Trender Trace items detail splitter bar is collapsed all the way to the bottom, when the Expand the traces list on mousehover option is set to True (enabled), the traces list will automatically unhide when the mouse hovers over the toolbar.

The following figure displays the toolbar and slider fully collapsed.

Trender Toolbar and Slider Collapsed

The following figure displays the toolbar and slider on mouse hover when this option is enabled.

Trender Toolbar and Slider Expanded

44 GEI-100795U GEI-100795 TrenderPublic Information

Page 45: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

7 Command Line ArgumentsCommand line arguments are used for variable configuration and functionality. For example, a command line argument usedto change the trend time duration is Trender.exe /Duration:00:02:01 c:\site\MyTrend.trend.

The following table describes the possible command line arguments used in Trender.

Command Line Argument Description

File Path

Used to provide a path to a .Trend file or .tcw file.A .Trend file is a previously saved trend configuration file created by the Trender (forexample, C:\site\Startup.Trend).A .tcw file is a ToolboxST project configuration file.

/AddLocalVar:VarName,DataType,[DisplayHigh],[DisplayLow], [Units],[Description],[SecondLanguageDescription],[FormatSpecification]

For Live type trends, a comma-separated argument list can be provided. Thevariable name and data type are required; the remaining arguments are optional.Multiple variables can be added by repeating the argument for each variable. Thedata source is expected to be the Local WorkstationSTsource.

/AddVariable:SourceName, VarName,DataType, [DisplayHigh],[DisplayLow],[Units],[Description],[SecondLanguageDescription],[FormatSpecification]

For Live type trends, a comma-separated argument list can be provided. The sourcename must be a valid source in the trend configuration, so the File Path argumentshould be specified as either a .Trend file or a .tcw file.Valid source names are:• A device name from a .tcw file or a saved trend of a component in a .tcw file.• Local WorkstationST

The variable name and data type are required; the remaining arguments areoptional.

/DeleteVariable:SourceName, VarName

The source name must be a valid source in the trend configuration, so the File Pathargument should be specified as either a .Trend file or a .tcw file.Valid source names are:• A device name from a .tcw file or a saved trend of a component in a .tcw file.• Local WorkstationST

The variable name is a required argument.

/Record When specified, data recording will begin after Trender initialization.

/Pause When specified, automatic live scrolling is paused.

/Export:FilePathExports all data from the Trender to a .csv file. The File Path argument should bespecified as a .Trend file.

/DisableBackFill When specified, the Trender will not attempt to backfill from historical data sources.

/Duration:hh:mm:ssChanges the duration of the trend from 1 minute (default) to the specified duration inhh (hours), mm (minutes), and ss (seconds). For example /Duration:00:10:00 wouldyield a time axis of 10 minutes.

Instruction Guide GEI-100795U 45Public Information

Page 46: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

8 Print and Export DataTrender can print the currently displayed graph to any printer attached to the system. Printed graphs reflect the current displayof the Graph View, including displayed traces, colors, and axis boundaries. Use the File menu and select either Print Previewor Print.

All traces in a trend, including ones currently hidden, can be exported to an external file for analysis.

➢➢ To export traces

1. From the File menu, select Export Data.

2. In the Trender Export Data Options dialog box, select options described in the following figure and save to thedesired format. The default options produce a standard .csv file.

3. Click OK and save the file.

Enter the character used to separate values in the exported file (as, or, and such).

Select for the time range set by the cursors.

Select to use the value of the previous sample for missing samples.

Select for a column to contain increasing numbers.

Select to include more information, such as descriptions, units, and data types.

Select for a column containing time stamps.

Select the precision of the exported time stamps.

Select for the first line of the exported file to contain header information for each column. Enter a value

to use for a data field if no data is available.

46 GEI-100795U GEI-100795 TrenderPublic Information

Page 47: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

9 Spectral AnalysisTrender can perform a spectral analysis on a data set. The spectral analysis of this data quickly isolates the most commonvarying frequencies. A spectral analysis of a waveform changes this time domain data into frequency domain data, also calleda frequency spectrum of the data set. This is also referred to as a fast Fourier transform (FFT).

The effect of an FFT on a sample data set is displayed in the following procedure. The first is an input data set displayingactual generator speed (RPM) and PWA accelerometer Y/Z direction data (force in Gs).

➢➢ To perform a spectral analysis

From the View menu, select Spectral Analysis

In the following example, analyzing the input waveform (top) produces the frequency spectrum below it, where one distinctgrouping displays at a frequency centered on 0.

Spectral Analysis Example

Instruction Guide GEI-100795U 47Public Information

Page 48: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

➢➢ To access FFT settings: from the File menu, select Properties or click the Trender Properties icon.

Settings include:

• Between Cursors, if set to True, applies an FFT on the data between the left and right cursors.• Padding Factor provides a way to interpolate between real points with copies of the same data, which enhances the

spectrum resolution.• Remove Mean, if set to True, improves the ability to scale the data for visualization.• Windowing Mode affects the equations used by the FFT as follows:

− None− Hann− Hamming− Bartlett− Welch

Note For information on these mathematical terms, refer to any textbook on numerical methods.

48 GEI-100795U GEI-100795 TrenderPublic Information

Page 49: Trender - General Electric...Trender captures and displays trend graphs of variables in a configured system and can collect and display values in real time from controllers and other

Public Information