  • High voltage products

    TIPStation service voltage transformer

  • 2Station service voltage transformer

    Advantages

    The TIP offers several advanteges: reduced dimensions more than one secondary winding suitable for both metering and power maintenance free higher availability of the power source as the TIP is directly connected with the high voltage side

    higher reliability due to reduced number of components for energy conversion

    no needs of medium voltage connections

    lower costs and connection times for the client

    less space required for installation high seismic withstand capability wide range of power available suitable for applications in mobile stations (Figure 1)

    available with a gas insulated disconnector to increase the flexibility in operation (Figure 2)

    higher performance in very heavy polluted environment thanks to composite insulator

    higher safety thanks to the use of composite insulator and of pressure relief device.

    Technical features

    The TIP is mounted onto a metallic support.

    The gas insulated voltage transformer is suitable for outdoor installations.

    The magnetic cores are made of laminated steel with oriented grain and a high level of permeability.

    The windings are made of electrolytic copper.

    The primary winding is connected directly to the high voltage while the secondary winding supplies the low voltage panels.

    The high voltage terminals are made of high conductivity aluminium and can be either cylindrical or NEMA flat type.

    The external bushing is made of composite material in accordance with IEC 61642 Standards, suitable to be installed in highly polluted areas (level 4).

    Fig. 1 Fig. 2

    The TIP Station service voltage transformer is a voltage transformer insulated in SF6 gas that combines the characteristics of a voltage transformer with power capability.

    The TIP has been designed for voltage up to 420 kV and with power capability up to 125 kVA.

    The main feature of the TIP is that the power- low voltage side- arises directly from the overhead lines.

    In this way the TIP is suitable to supply auxiliary services, lighting loads, motor loads, instrumentation, etc.

    Typical secondary ratings available: 115, 230, 120/240, 277, 240/480, 600 VAC. Other ratings are available.

  • 87

    5 6

    3

    2

    1

    9B

    A

    4

    10

    3

    4 3 2 1 PE

    1a 1n 2a 2n

    A N

    Electrical diagram plate

    Key

    1. High voltage terminal

    2. Composite insulator

    3. Aluminium tank

    4. Pressure relief device

    5. Nameplate

    6. Secondary terminal box

    7. Cable glande for low voltage cables

    8. Earth connection

    9. Density monitor

    10. Hoisting hooks

    Overall dimensions

    Nominal voltage

    kV

    Nominal power

    kVA

    A

    mm

    B

    mm

    Max weight

    kg

    72.5

    25 2050 600 700

    50 2250 600 1000

    100 2570 600 1850

    125 2595 600 2000

    145

    25 2485 600 720

    50 2690 600 1050

    100 3030 600 1900

    125 3060 600 2050

    170

    25 2890 600 890

    50 3230 600 1420

    100 3230 600 2300

    125 3230 600 2650

    245

    25 3810 600 1250

    50 3810 600 1650

    100 4120 800 2550

    125 4120 800 2750

    420

    25 5670 800 1550

    50 5860 900 2350

    100 6050 1000 3750

    125 6050 1000 3900

    The base of the transformer is fitted with: a densimeter for gas monitoring a filling valve DILO type DN8 (DN20 for 420 kV)

    a pressure relief device hoisting hooks a secondary box with a protection degree not less than IP44 according to the IEC 60529 Standards

    a M12 bolt for grounding connection.

    The rating plate of each voltage transformer includes all the data required by the IEC 60044-2 Standards.

    Tightness of the insulation system

    The tightness of the insulation system has been designed to guarantee a life cycle time of 30 years. Maximum admitted gas leakage: less than 0.1% per year.

    Technical details

    TIP Power frequency

    kV

    BIL

    kV

    72.5 kV 140 325

    145 kV 275 650

    170 kV 325 750

    245 kV 460 1050

    420 kV 630 1425

    LOCK OuT ALARM

    SchematicS

    DenSity monitor contactS

  • The data and illustrations are not binding. We reserve theright to modify the contents of this document without priornotice following technical and product developments.

    Copyright 2010 ABB.All rights reserved.

    Contact us

    2GJA

    7084

    54 Rev. B, en

    Broch

    ure TIP 201

    0.12

    (gs)ABB S.p.A.

    Power Products DivisionUnit Operativa Adda-HVVia dei Ceramisti, sncI-26900 LodiTel: +39 0371 452.1Fax: +39 0371 452.222