DELTA POWER SYSTEM
User manual
7/23/2019 T ngun Delta -48V
2/75
ESAA150ABC07/09/11 IOM P/N: 50112866022010. 04. 12. R02
ESAA150-ABC07/09/11
Power System
User Manual
7/23/2019 T ngun Delta -48V
3/75
ESAA150ABC07/09/11IOM
Page: 2 of 73
TABLE OF CONTENTS
1 General.....................................................................................................................................4
1.1 USING THIS MANUAL ..................................................................................................................................... 41.2 SAFETYNOTICE .............................................................................................................................................. 41.3 ENVIRONMENTAL ...........................................................................................................................................5
2 Product Description..................................................................................................................6
2.1 PRODUCT DESCRIPTION .................................................................................................................................. 62.2 PRODUCT MAIN FEATURES .............................................................................................................................62.3 CONFIGURATION.............................................................................................................................................72.4 SYSTEM SPECIFICATION.................................................................................................................................. 7
2.5 SYSTEM CONFIGURATION & DIMENSIONS ...................................................................................................... 82.6 SYSTEM SCHEMATICS ................................................................................................................................... 11
3 Installation ..............................................................................................................................14
3.1 TOOL REQUIRED ...........................................................................................................................................143.2 UNPACKING .................................................................................................................................................. 143.3 PRELIMINARY INSPECTION............................................................................................................................143.4 BASE MOUNT................................................................................................................................................ 153.5 SYSTEM MOUNTING...................................................................................................................................... 153.6 MODULE INSTALLATION ...............................................................................................................................153.7 SYSTEM WIRING ...........................................................................................................................................163.8 DC GROUNDING ...........................................................................................................................................163.9 AC INPUT CONNECTIONS..............................................................................................................................163.10
DC DISTRIBUTION CONNECTIONS ................................................................................................................17
3.11 BATTERY CONNECTIONS...............................................................................................................................173.12 RECOMMENDED WIRING...............................................................................................................................173.13 BATTERY AND AMBIENT TEMPERATURE SENSORS....................................................................................... 18
4 START - up Procedure...........................................................................................................19
4.1 INITIAL STARTUP PREPARATION ...................................................................................................................194.2 NO LOAD START-UP...................................................................................................................................... 194.3 BASIC FUNCTIONAL VERIFICATION...............................................................................................................194.4 PARAMETER SETTINGS.................................................................................................................................. 194.5 DC LOAD CONNECTIONS..............................................................................................................................204.6 FUNCTIONALITY CHECK ...............................................................................................................................20
5 CSU & Parameter Adjustment ...............................................................................................21
5.1 DESCRIPTION..............................................................................................................................................215.2 DISPLAY......................................................................................................................................................225.3 FUNCTION ................................................................................................................................................... 225.4 SYSTEM PARAMETER SETTING...................................................................................................................... 235.5 REAL TIME OPERATION STATUS ...................................................................................................................24
6 Switch Mode Rectifier (ESR48/56A series rectifier, 2700W) ................................................37
6.1 DESCRIPTION ................................................................................................................................................ 376.2 SPECIFICATIONS............................................................................................................................................376.3 ENVIRONMENTAL .........................................................................................................................................386.4 PHYSICAL......................................................................................................................................................396.5 OUTLINE & DIMENSIONS ..............................................................................................................................39
6.6 SMR OPERATING PRINCIPLE ........................................................................................................................ 39
7/23/2019 T ngun Delta -48V
4/75
ESAA150ABC07/09/11IOM
Page: 3 of 73
7 Switch Mode Rectifiers (ESR48/40A series rectifier, 2000W) ..............................................41
7.1 DESCRIPTION ................................................................................................................................................ 417.2 SPECIFICATIONS............................................................................................................................................417.3 OUTLINE & DIMENSIONS ..............................................................................................................................43
8 Alarms And Trouble Shooting................................................................................................44
8.1 AC FAIL/AC HIGH VOLTAGE / AC LOW VOLTAGE ALARM DESCRIPTION...................................................448.2 DC OUTPUT VOLTAGE HIGH/LOW (HV/LV)................................................................................................ 458.3 DC CIRCUIT BREAKER TRIPPED ALARM....................................................................................................... 458.4 OVER-TEMPERATURE ALARM....................................................................................................................... 458.5 RECTIFIER FAIL ALARM................................................................................................................................ 46
9 Maintenance...........................................................................................................................47
9.1 CLEANING AND MAINTENANCE ....................................................................................................................479.2 REMOVING AND REPLACING A RECTIFIER MODULE...................................................................................... 47
10 system communication software............................................................................................49
10.1 INTRODUCTION........................................................................................................................................ 4910.2 INSTALL AND UNINSTALL RMS SOFTWARE ....................................................................................4910.3 GET START NRMS SOFTWARE..............................................................................................................5010.4 HOW TO SETUP CONNECTION PROFILE INFORMATION................................................................5110.5 SOFTWARE FUNCTION................................................................................................................................... 5310.6 SYSTEM INFORMATION MONITORING.............................................................................................................5510.7 SYSTEM PARAMETER CONFIGURATION......................................................................................................... 5910.8 OTHER FUNCTION .........................................................................................................................................66
11Acronyms and Abbreviations .................................................................................................71
7/23/2019 T ngun Delta -48V
5/75
ESAA150ABC07/09/11IOM
Page: 4 of 73
1 GENERAL
1.1 Using This Manual
This manual contains specifications and instructions to properly install andmaintain the indoor power system. Component specifications and drawings arecontained in this manual.
Included in this manual is the operation and maintenance of the New Smart CSU(NCSU), ESR48/56A (or ESR48/40A) series Switch Mode Rectifier (SMR), PowerDistribution Unit (PDU) and Low Voltage Disconnect (LVDS), system status andalarms, troubleshooting and system maintenance.
Step by step procedures required for installation and turn-up are detailed. All
equipment parameter settings, adjustments and confirmation as well as systemmonitoring, operations and maintenance procedures are included.
Warnings are printed in bold lettering and alert the installation or maintenancecraftsperson of a potential hazard to either or the craftsperson if the warningadvisement is not followed.
1.2 Safety Notice
Products are not liable for any hazards incurred by not following proper safetyprocedures. Installation, Operation and maintenance personnel should alwaysfollow these safety rules:
1. The equipment is designed for installation and use in areas designated as"Restricted Access Location"only. Where the rack will be secured to aconcrete or other non-combustible floor.
2. Per UL and the NEC an insulated grounding conductor, identical in size andinsulation characteristics to the supply conductors, is to be installed as part ofthe branch circuit that supplies the unit or system. The grounding conductorshould be green, with or without yellow stripes.
3. The grounded conductor described up above is to be grounded to the earth atthe service equipment or if supplied by a separate derived system, at thesupply transformer or motor-generator set.
4. The AC receptacles in the vicinity of the power system are all to be of a
grounding type and the grounding conductors serving all receptacles are to beconnected to earth ground at the service equipment.
5. Before the system is operational, the AC input frequency and voltage must beverified making sure the AC breaker rating and type are adequate and otherenvironmental conditions as noted in the specifications are met.
6. A readily accessible disconnect device shall be incorporated in the buildinginstallation wiring.
7. Protective systems or devices in PRIMARY CIRCUITS shall be in such anumber and located so as to detect and to interrupt the over-current flowing inany possible fault current path (for example, line-to-line, line-to-neutral, line toprotective earth conductor or line to PROTECTIVE BONDING CONDUCTOR).
7/23/2019 T ngun Delta -48V
6/75
ESAA150ABC07/09/11IOM
Page: 5 of 73
8. In a supply using more than one line conductor to a load, if a protective deviceinterrupts the neutral conductor, it shall also interrupt all other supply
conductors. Single pole protective devices, therefore, shall not be used in suchcases.
9. The system has passed stringent system testing prior to shipment. To avoidelectrical shock, the system requires a single ground point permanentlyconnected to earth ground.
10. Recommended room ambient is maximum +45.
11. To avoid electrical hazards, the covers must not be removed on the system orany component.
12. DC output & battery breakers must be replaced with approved replacementcircuit breakers meeting the original design specification.
13. All AC connections must be made per the latest issue of the National ElectricalCode and must conform to all local codes.
14. The wiring method to accommodate different power systems should complywith National Electrical Code and Local Code.
1.3 Environmental
1. Input Voltage: 220 - 240VAC, 2W + PE2. Input Frequency: 50 - 60 Hz
3. Operating Temperature: 0to +45
4. Humidity: 10 to 95% RH (non-Condensing)
5. Floor Load Density:
The Building floor structure having a total floor load capacity of 780kg/
6. Altitude: < 3000m above mean sea level0 - 2000 m:
Full of the nominal output power rating at maximum temperature.2000 m - 3000 m:
1% power de-rating per 100m. At 3000m altitude, the output power can be90% of the nominal power rating at maximum temperature.
7/23/2019 T ngun Delta -48V
7/75
ESAA150ABC07/09/11IOM
Page: 6 of 73
2 PRODUCT DESCRIPTION
2.1 Product Description
The ESAA150-ABCxx Power System consists of modular ESR48/56A (orESR48/40A) series Rectifiers, a New Smart CSU (NCSU) and a Power DistributionUnit (PDU).
Up to 3 rectifiers can be equipped in 1 shelf, which can mount a NCSU. Thesystem requires a nominal input of 220V and provide an output of 54 VDC topower the load and also maintain fully charged batteries.
The system is control by the New Smart CSU (NCSU). System monitor and controloutput voltage, status and alarms of rectifiers by NCSU. All system parameters are
set by NCSU too. The parameters include the system float voltage, equalizevoltage, current limit, and alarm thresholds setting. The RS232 interface of NCSUis the Remote Monitoring System (RMS) software to remote and control system byPC.
The environmental control will be done by the separate climate control card, whichwill support the door open alarm, humidity control, fan control and heater control.
2.2 Product Main Features
-54Vdc/~150A (rectifiers 1-3).
User Friendly LCD Interface (128*64 dots display)
Hot Swappable 2700 Watts (or 2000Watts) rectifiers, wide range PFC input(90~275Vac good for unstable utility environment)
Light Weight Plug-in Modules for Simple Installation and Maintenance
High Power Density Saves Valuable Floor space
All rectifier modules are front accessible
Active Power Factor Correction (>.99 PF)
High Efficiency
Temperature Compensation Float Voltage Control for VRLA Batteries
Front Access for Simplified Operation and Maintenance
Intelligent remote shelf monitoring and control (Optional RMS software functionand Modem function, Via RS-232)
Network Maintenance
Battery temperature compensation voltage control
Battery and Load breakers
Equalize charge timer
7/23/2019 T ngun Delta -48V
8/75
ESAA150ABC07/09/11IOM
Page: 7 of 73
2.3 Configuration
AC Input: 220 - 240VAC, 2W + PESystem Capacity: -54VDC/~150A Max.
Rectifier: -54V/2700W (or 2000W) * 3 Max.
CSU: Delta New Smart CSU
2.4 System Specification
Item Specification/Function
AC Input
220 - 240VAC, 2W + PE
Max. 54A for ESR48/56A series (2700W) systemMax. 36A for ESR48/40A series (2000W) system
System Capacity -54V/ ~ 150A Max. (1 ~ 3 rectifiers)
Rectifier1. ESR48/56A series (2700W)
2. ESR48/40A series (2000W)
Control & Supervisor UnitLCD Display: 128*64 charactersLED Indicator: 3
Battery Breaker 2 positions
Output Breaker High priority * 6 positions + Low priority * 6 positions
LVDSLVBD (Low Voltage Battery Disconnect) * 1 + LVLD (Low VoltageLoad Disconnect) * 1
Remote Monitoring andControl
By RMS software (Use RS232 Interface)
Operating Temperature 32~+113(0~+45)
Storage Temperature -40~+158(-40~+75)
Humidity 0~95% Relative Humidity, Non-Condensing
Altitude
< 3000m above mean sea level0 - 2000 m:Full of the nominal output power rating at maximum temperature.2000 m - 3000 m:1% power derating per 100m. At 3000m altitude, the output powercan be 90% of the nominal power rating at maximum temperature.
Acoustic55 dB(A) at the distance of 1m in front of rectifier with 1.5m height,
25 degree C ambient,
7/23/2019 T ngun Delta -48V
9/75
ESAA150ABC07/09/11IOM
Page: 8 of 73
2.5 System Configuration & Dimensions
2.5.1 ESAA150-ABC07
10 11
5
9
6
7
12
4
8
13
565
615
1200
1
2
3
14
ESAA150-ABC07 Main Part
ESAA150-ABC07
Item Description Qty Remark
1 Power System 1
2 Controller & Monitor Unit 1 NSCU
3 Shelf 1 19 inch for 3 SMR(2700W)
4 DC Breaker(Load)-High Priority 2 15Ax2, Expansion to 6
5 DC Breaker(Load)-Low Priority 6 40Ax4 + 15Ax2
6 Battery Breaker 2 125A x 2
7 AC Input Breaker 1 220V Single Phase
8 AC Detector 1
9 LVDS 2
10 Battery Load Terminal Block 2
11 DC Load Terminal Block 5
12 AC Input Terminal Block --
13 DC 0V Bus 1
14 Battery Tray 2 For Battery 180AH x 8
7/23/2019 T ngun Delta -48V
10/75
ESAA150ABC07/09/11IOM
Page: 9 of 73
2.5.2 ESAA150-ABC09
10 11
5
9
6
7
12
4
8
13
565
615
1200
1
2
3
14
ESAA150-ABC09 Main Part
ESAA150-ABC09
Item Description Qty Remark
1 Power System 1
2 Controller & Monitor Unit 1 NSCU
3 Shelf 1 19 inch for 3 SMR(2700W)
4 DC Breaker(Load)-High Priority 4 40Ax4, Expansion to 6
5 DC Breaker(Load)-Low Priority 6 40Ax4 + 10Ax2
6 Battery Breaker 2 125A x 2
7 AC Input Breaker 1 220V Single Phase
8 AC Detector 1
9 LVDS 2
10 Battery Load Terminal Block 2
11 DC Load Terminal Block 5
12 AC Input Terminal Block --
13 DC 0V Bus 1
14 Battery Tray 2 For Battery 180AH x 8
7/23/2019 T ngun Delta -48V
11/75
ESAA150ABC07/09/11IOM
Page: 10 of 73
2.5.3 ESAA150-ABC11
10 11
5
9
6
7
12
4
8 13
565
615
1200
1
2
3
14
ESAA150-ABC11 Main Part
ESAA150-ABC11
Item Description Qty Remark
1 Power System 1
2 Controller & Monitor Unit 1 NSCU
3 Shelf 1 19 inch for 3 SMR
4 DC Breaker(Load)-High Priority 2 63A x 2, Expansion to 6
5 DC Breaker(Load)-Low Priority 3 25A x 3, Expansion to 6
6 Battery Breaker 2 125A x 2
7 AC Input Breaker 1 220V Single Phase
8 AC Detector 1
9 LVDS 2
10 Battery Load Terminal Block 2
11 DC Load Terminal Block 5
12 AC Input Terminal Block --
13 DC 0V Bus 1
14 Battery Tray 2 For Battery 180AH x 8
2.5.4 System Dimension
Item Specification/Function
Dimensions (WxDxH) 615mm x 565mm x 1200mm
7/23/2019 T ngun Delta -48V
12/75
ESAA150ABC07/09/11IOM
Page: 11 of 73
2.6 System Schematics
2.6.1 ESAA150-ABC07
7/23/2019 T ngun Delta -48V
13/75
ESAA150ABC07/09/11IOM
Page: 12 of 73
2.6.2 ESAA150-ABC09
7/23/2019 T ngun Delta -48V
14/75
ESAA150ABC07/09/11IOM
Page: 13 of 73
2.6.3 ESAA150-ABC11
7/23/2019 T ngun Delta -48V
15/75
ESAA150ABC07/09/11IOM
Page: 14 of 73
3 INSTALLATION
3.1 Tool Required
The following tools are recommended for the system installation:
Phillips No. 3 screw driver
Tweaker - Slotted screw driver blade size .09.02
Thomas & Betts crimping tool TBM8-750-1
Insulated side cutters
Metric Socket Wrenches with Extensions
Hydraulic lifter
3.2 Unpacking
Refer and follow the sequence as the figures below to unpack the equipment.
3.3 Preliminary Inspection
Prior to removing the system from the crate, note any damage to the crate.Remove the system cabinet from the crate and inspect the shelf for any dents ordamage. If any damage is noted, contact the carrier immediately.
7/23/2019 T ngun Delta -48V
16/75
ESAA150ABC07/09/11IOM
Page: 15 of 73
3.4 Base Mount
3.4.1 Holes for Base Mount
Refer to the figure below for detail base mount template.
3.5 System Mounting
The system comes fully assembled with the DC Distribution Shelf. The ACconnections from the AC terminal to the rectifier shelf are made at the factory. AllCSU communication and signal leads are connected via the modular plugs andcommunicate with the rectifiers.The system should be mounted to the superstructure and floor per customerprovided equipment engineering drawings.
3.6 Module Installation
In order to minimize the weight of system, all rectifier modules are deliveredseparated and they should be re-installed in the site.
3.6.1 Rectifier Installation
1) Install rectifier modules into the shelf2) Push both locker to lock position to lock the rectifier.
Unit: mm
7/23/2019 T ngun Delta -48V
17/75
ESAA150ABC07/09/11IOM
Page: 16 of 73
Warning! Do not force the module into the slot. If it does not slide in and connecteasily, remove and re-seat the unit.
3.6.2 Sequence of Rectifier Installation
The recommended rectifier installation sequence:From left to right of the shelf.
3.7 System Wiring
The shelf comes fully assembled and all the connections are made at the factory.There is no internal, shelf or module wiring required.
All wiring to the breaker are use lead with striped ends. Ensure to tight the screwand keep the wires are all into the breaker terminal, no any wires or threads areremain outside of the breaker to avoid short-circuit. Refer to the figure below.
3.8 DC Grounding
The DC ground must be connected to a permanent earth ground connection.
Warning! Do not connect this terminal to AC power system neutral.
3.9 AC Input Connections
All AC cables should connect to AC main breaker.
Rating: Refer to the system.
Recommended wiring, refer to Section 3.12.
Warning! The shelf operates at AC voltages that can produce fatal electricalshock. Installation and maintenance personnel must observe all safetyprecautions.
Warning! Confirm the operating voltage before proceeding.Warning! The input feeder circuit breaker at the AC panel must be in the Off
position before attempting to wire the shelf.
OK NG
Remain wires or threads
7/23/2019 T ngun Delta -48V
18/75
ESAA150ABC07/09/11IOM
Page: 17 of 73
3.10 DC Distribution Connections
Rating: Refer to the system.Recommended wiring, refer to Section 3.12.
Note! Load LISTED output breakers to a maximum 80% of marked current.
3.11 Battery Connections
Rating: Refer to the system.Recommended wiring, refer to Section 3.12.
Note! Load LISTED output breakers to a maximum 80% of marked current.
3.12 Recommended Wiring
The recommended wire size (AWG#) for each breaker, refer to the 60C column
for copper wire and with at least 90C insulation.
Battery +Battery -- + - + - + - +
7/23/2019 T ngun Delta -48V
19/75
ESAA150ABC07/09/11IOM
Page: 18 of 73
The comparison list for wiring size of AWG and mm
3.13 Battery And Ambient Temperature Sensors
One battery sensor cable is provided with each system. The cable is labeled TBterminate on connector TB and on the temperature sensor. Place and fix thetemperature sensor on the center of the battery connection bus bar to detecting thebattery temperature.
The Ambient Temperature Sensor is labeled TA and can be placed anywhere clearof the rectifier fan flow. (The TA Sensor had already fix on the appropriate locationof the cabinet by factory, no required to install by customer of this item) The
Ambient Temperature Sensor TA is terminated to the back of the CSU to theconnector labeled Ambient Temp.
7/23/2019 T ngun Delta -48V
20/75
ESAA150ABC07/09/11IOM
Page: 19 of 73
4 START - UP PROCEDURE
4.1 Initial Startup Preparation
Verify all connections prior to starting this section.
Warning! Ensure the input AC circuit breaker located at the AC service panel isswitched to the Off position.
Warning! Confirm the operating voltage before proceeding.
Warning! Ensure the frame ground is properly connected to a permanent earth
ground connection.
Warning! Ensure all the Load DC Circuit breakers located in the DC DistributionCabinet are switched to the Off position.
4.2 No Load Start-up
The shelf can be turned up without a load. The start-up procedure is as follows:
1. Switch all DC load breakers to the Off position.
2. Make sure battery is not connected to the system Battery Bus.
3. Switch on AC input breaker and check the CSU for alarm status.
4. Switch on each DC load breaker and connected battery to operate the systemafter checking without any problem.
4.3 Basic Functional Verification
After shelf start-up, basic functional verification should proceed.
Check the monitor of CSU display.
4.4 Parameter Settings
Most parameters are pre-set at the factory and are listed on the shelf Test Report
included with each shelf. This section provides a general explanation for someparameter may need changing.
Note! In all battery relatedparameters refer to the battery manufacturerspecifications.
4.4.1 Float/Equalize Voltage
Both Float and Equalize voltages are preset at factory and listed on the shelf TestReport. The CSU controls the settings on each rectifier. If a different value isrequired, setting the value from CSU.
7/23/2019 T ngun Delta -48V
21/75
ESAA150ABC07/09/11IOM
Page: 20 of 73
4.4.2 Current Limit
The CSU controls the system current limit threshold by monitoring the total load,the number of rectifiers in-service and the battery current. A parameter setscurrent limit in the event of a DC overload condition for the system and overridesthe current limit set at each rectifier.
4.4.3 Total Number of SMRs
The CSU uses this parameter to scan for rectifier status and alarms.
4.4.4 SMR Slot Assignment
This parameter is used with the parameter Total Number of SMRs and directs theCSU to scan the assigned slots for rectifier status and alarms.
4.4.5 Maximum Battery Capacity
Battery capacity must reflect the rating of the installed battery. Refer the batterymanufacture specification for the rated capacity.
4.5 DC Load Connections
Warning! Basic Functional Testing should be completed prior to the load beingapplied.
Warning! Switch all DC circuit breakers to the OFF position.
A. Connect the positive load cable to the Ground Bus.
B. Connect the negative load cable to the DC breaker lug.
C. Switch the DC circuit breakers or Load Fuse to the ON position.
Warning! Tighten the DC Circuit Breaker lugs to ensure proper contact is madewith the load cable and the trip sense wire. Failure to properly torquethe DC circuit breaker lugs may cause heat damage.
4.6 Functionality Check
Control and supervisory functional testing can be performed at the CSU after theBasic Functional Testing is completed and the DC Load is connected.
Check the status of the equipment by viewing the Main Page and by pressingbutton. Verify voltages, current and temperature for normal operation. Comparethe rectifier voltages by using a multi-meter and taking the measurements at thefront of each rectifier.
Verify the Alarm display at the CSU to ensure that all alarm conditions are resolved.
7/23/2019 T ngun Delta -48V
22/75
ESAA150ABC07/09/11IOM
Page: 21 of 73
5 CSU & PARAMETER ADJUSTMENT
5.1 Description
5.1.1 Software Interface
Power system controller Delta New Smart CSU
Display LCD 128 x 64 dots display
LED (Major, Minor, EQU)
Push button 4 push buttons on the CSU LCD display. They are
use to control the power system.
Language English / Chinese
5.1.2 System Management
Monitoring: AC input information
DC information
Rectifier information
Battery Information
DC load information
Environment detection
Parameter Setting: System output parameter setting
Alarm threhold setting
Alarm configuration setting
System relay setting
Others: Remote management
Event log
Efficiency management
Battery discharge test function
7/23/2019 T ngun Delta -48V
23/75
ESAA150ABC07/09/11IOM
Page: 22 of 73
5.1.3 Communication Management
5.1.3.1 Local
Method: RS-232 cable (9 pin), for local connection
SW Interface: (Optional) Delta Remote Management Software
Note! Remote management function is optional. Please consult Deltarepresentative for details.
5.1.3.2 Remote
IP Adapter (Optional)
5.2 Display
A 128 * 64 characters LCD Display is on the CSU for display shelf status as thefollowing:Main page: DCV, DCI, shelf status, AlarmButton A BACK; B ; C ; D ENTER
5.3 Function
5.3.1 Relay output
5.3.1.1 Relay Specifications
Settings DescriptionArrangementContact ratingResistanceCondition
1 Form C (SPDT)1A at 24VDC, only allow to connect to safe low voltage circuit
100mNormal Open, Normal Close, Common
5.3.1.2 Relay Position and Definition
5.3.1.2.1 Relay Positions and Definition
Relay Alarm Event Alarm Event Description
1 AC Off AC Fail Alarm
2 RFA2 Two or More rectifiers Fail Alarm
3 CSU Fail CSU Fail Alarm
4 DCL DC Low Voltage Alarm
5 Batt. Switch Battery Breaker or Fuse Fail Alarm
6 MajorDCH, HVDS, LVDS Trip, TAH, TA Sensor Fail, AC Fail, TB Sensor Fail, TBH,One Rectifier, Rect Over Percent of Capacity, Load Priority Hi, Load Priority Lo,
7 MinorDCL, TAL, HTSD, CL, Battery Switch, Battery Discharge, Battery TestFail, More Rectifier Fail
7/23/2019 T ngun Delta -48V
24/75
ESAA150ABC07/09/11IOM
Page: 23 of 73
5.4 System Parameter Setting
The lists below are parameter preset in factory for the system.
Note! In all battery related parameters refer to the battery manufacturerspecifications.
Parameter Descriptions Setting Setting Range
HVSD Shutdown 59.5 V 58.0~60.0 V
HV Alarm 57.5 V 56.0~58 V
LV Alarm 45.0 V 44.0~50.0 V
LVDS1DISC Voltage 42.0 V 40.0~48.0 V
LVDS2 DISC Voltage 45.2V 40.0~48.0V
LVDS3 DISC Voltage 47.2V 40.0~48.0V
Rectifier Relation Over PercentageOf Capacity
80% 50% ~ 90%
Set FL Voltage 54.0 V 50.0~56 V
Set EQU Voltage 56.0 V 50~57 V
TAH 45 35~ 75
TAL -14 -40~ 10
HTSD Shutdown (Option) 60 45~75
LTSD Shutdown (Option) -15 -40~10
Cooling Fan Start Temp 0Single Phase 220 ACV High Alarm 264V 230~276V
Single Phase 220 ACV Low Alarm 176 V 90~184 V
Battery Capacity 360 AH 0~6000 AH
TBH 40 30~50
Middle test voltage 1V 0.5V ~ 4V
SMR CL (2700W) 50A 5A~50A
Battery charge management Enable
Stage1 max charge current 0.20C 0.05C~0.5C
Stage2 max charge current015C 0.05C~0.5C
Stage3 max charge current 0.1C 0.05C~0.5C
Battery Test Disable
Test Time 1 hr 1~24 hr
Battery Test Voltage 45.0 V 42.0~52.0 V
Battery test current 0.1C 0.05~0.5 C
Battery test periodic Disable
Battery test periodic 1 month 1 ~ 12 month
Battery test date 1 day 1 ~ 31 day
Battery test Hour 0 Oclock 0 ~ 23 Oclock
7/23/2019 T ngun Delta -48V
25/75
ESAA150ABC07/09/11IOM
Page: 24 of 73
Temp compensation Enable
Compensation Mode 0 0 ~ 1Temp Comp Coefficient 4 mV/ 0.1~4mV/
Temp Comp Range 1.3V -1.3 ~ 1.3V
Temp Comp Center 25 15~35
Temp curve T0 0 -20~ +60
Temp curve V0 56.9V 50V ~ 58.0V
Temp curve T1 15 -20~ +60
Temp curve V1 54.5V 50V ~ 58.0V
Temp curve T2 35 -20~ +60
Temp curve V2 54.5V 50V ~ 58.0V
Temp curve T3 60 -20~ +60
Temp curve V3 51.7V 50V ~ 58.0V
EQU Enable
EQU max time 10hour 1 ~ 24 hour
Additional EQU Time 1 hr 0~12 hr
EQU Terminal current 0.01C 0.01C ~ 0.05C
EQU periodic Enable
EQU Charge period 1 Month 1~12 Month
Periodic date 3 1 ~ 31
Periodic Hour 0 0 ~ 23
Deep discharge remain capacity Enable
Deep voltage Enable
AC Fail time Enable
Deep discharge-remain capacity 80 30~90
Deep discharge-voltage 46V 42V~48V
Deep discharge-AC off Time 4Hr 0~24Hr
Charge current 0.08C 0.03C ~ 0.15C
5.5 Real Time Operation Status
The shelf status is displayed on the front of the CSU. The Main page is alwaysdisplayed during normal operation. All values in the list are for reference only.
Main page:
DCV 54.0VDCI 0ASys Sta. FL
Alarm Existing
DCV: System output DC VoltageDCI: Total system output currentSys Sta: System status
Alarm Existing: Alarm Existing will display if alarm had occurred
7/23/2019 T ngun Delta -48V
26/75
ESAA150ABC07/09/11IOM
Page: 25 of 73
5.5.1 System Information
SysInfoSys settingCurr. Alarm
Press ENTER;
RectifierBatteryEvent LogCurr. Setting
AC & TempDate & Version
Press ENTER;
5.5.1.1 Rectifier Information
Rectifier Info01 0.0A OK02 0.0A OK03 0.0A OK
---
24 0.0A OK
Total 24 rectifiers can be display
5.5.1.2 Battery InformationRectifierBatteryEvent LogCurr. Setting
AC & TempDate & Version
Press ENTER
Batt. 1ChargingCurrent 0.0A
Temp. 32
Batt. 2ChargingCurrent 0.0ATemp. 30
5.5.1.3 Event Information
RectifierBatteryEvent LogCurr. Setting
7/23/2019 T ngun Delta -48V
27/75
ESAA150ABC07/09/11IOM
Page: 26 of 73
AC & TempDate & Version
Press ENTER
00 XXXX AlarmYYYY-MM-DD HH: MM: SS
01 XXXX AlarmYYYY-MM-DD HH: MM: SS
--
99 XXXX AlarmYYYY-MM-DD HH: MM: SS
Total 100 events can be display
5.5.1.4 Current Setting Information
RectifierBatteryEvent LogCurr. Setting
AC & TempDate & Version
Press ENTER
5.5.1.4.1 DC Setting
DC SettingAlarm settingBatt. settingOther setting
Press ENTER
DC SettingEQU VLT 56VFL VLT 54V
5.5.1.4.2 Alarm Setting
DC Setting
Alarm settingBatt. settingOther setting
Press ENTER
Alarm SettingHV 57.5VLV 45VHVSD 59V
7/23/2019 T ngun Delta -48V
28/75
ESAA150ABC07/09/11IOM
Page: 27 of 73
ACH 264VACL 176V
HT 45LT -14
HTSD 50
LTSD -15
EQU ALM ONTST ALM ON
BATT OTP 40
LVDS1 42VLVDS2 41VBATT Unb ON
5.5.1.4.3 Batt. SettingDC Setting
Alarm settingBatt. settingOther setting
Press ENTER
B- ParameterT- COMPBDT SettingB-EQU Setting
a. B- Parameter
B- ParameterT- COMPBDT SettingB-EQU Setting
Press ENTER
Batt. Capacity200AH
Stop EQUMax. Time 1Hr
Min. Curr. 0.1CExtra Time 1Hr
b. T- COMP
B- ParameterT- COMPBDT SettingB-EQU Setting
Press ENTER
LinearNon Linear
7/23/2019 T ngun Delta -48V
29/75
ESAA150ABC07/09/11IOM
Page: 28 of 73
b-1. Linear
LinearNon Linear
Press ENTER
ENABLE in EQUCoef 4.0mV/
RANGE 1.3V
T- START 25
b-2. Non Linear
LinearNon Linear
Press ENTERT0, V0 : 0, 56.8T1, V1: 15, 54.5T2, V2: 35, 54.4T3, V3 : 60, 51.6
c. BDT Setting
B- ParameterT- COMPBDT SettingB-EQU Setting
Press ENTER
Periodic BDTStatus ONNext Batt Test05/06/02 00:00
BDT I 0.1CEnd VLT 45VBDT Time 1Hr
Periodic TestPeriod 1MDate 1DTime 0Hr
d. B- EQU Setting
B- ParameterT- COMPBDT SettingB-EQU Setting
Press ENTER
Periodic B-EQUStatus ONNext EQU05/07/02 00:00
7/23/2019 T ngun Delta -48V
30/75
ESAA150ABC07/09/11IOM
Page: 29 of 73
Periodic B-EQUPeriod 1M
Date 1DTime 0Hr
5.5.1.4.4 Other Setting
DC SettingAlarm settingBatt. settingOther setting
Press ENTER
Eficnt Func. ON
5.5.1.5 AC & Temperature Information
RectifierBatteryEvent LogCurr. Setting
AC & TempDate & Version
Press ENTER
ACVACV1 217VAmbient Temp 25
5.5.1.6 Date & Version
RectifierBatteryEvent LogCurr. Setting
AC & TempDate & Version
Press ENTER
Current DateYYYY/MM/DDCurrent TimeHH: MM: SS
HW VersionCU-15W BSW Version0.0 - 28
5.5.2 System Setting
SysInfoSys settingCurr. Alarm
Press ENTER;
7/23/2019 T ngun Delta -48V
31/75
ESAA150ABC07/09/11IOM
Page: 30 of 73
DC SettingAlarm Setting
Batt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
5.5.2.1 DC Setting
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
DC SettingEQU VLT 56VFL VLT 54.0V
5.5.2.2 Alarm Setting
DC SettingAlarm Setting
Batt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
Alarm SettingHV ONLV ONHVSD ON
ACH ONACL ONHT ONLT ON
HTSD ONBatt. OTP ONLVDS1 ONLVDS2 ON
EQU ONBatt. Tst ONBatt. Unb ON
5.5.2.2.1 HV Alarm
7/23/2019 T ngun Delta -48V
32/75
ESAA150ABC07/09/11IOM
Page: 31 of 73
HV Alarm*Enable
DisableSETPOINT 57.5V
5.5.2.2.2 LV Alarm
LV Alarm*EnableDisable
SETPOINT 45V
5.5.2.2.3 HVSD Alarm
HVSD Alarm
SETPOINT 59V
5.5.2.2.4 ACH Alarm
ACH Alarm*EnableDisable
SETPOINT 264V
5.5.2.2.5 ACL Alarm
ACL Alarm*EnableDisable
SETPOINT 176V
5.5.2.2.6 HT Alarm
HT Alarm*EnableDisable
SETPOINT 45
5.5.2.2.7 LT Alarm
LT Alarm*EnableDisable
SETPOINT -14
5.5.2.2.8 HTSD Alarm
HTSD Alarm
SETPOINT 50
5.5.2.2.9 Batt OTP Alarm
Batt OTP Alarm*EnableDisable
SETPOINT 40
7/23/2019 T ngun Delta -48V
33/75
ESAA150ABC07/09/11IOM
Page: 32 of 73
5.5.2.2.10 LVDS1 (LVBD) Alarm
LVDS1 Alarm
SETPOINT 42V
5.5.2.2.11 LVDS2 (LVLD) Alarm
LVDS2 Alarm
SETPOINT 43V
Note! NEVER set the default voltage of LVBD over the default voltage ofLVLD, otherwise, the function of LVLD will UNAVILABLE.
5.5.2.2.12 EQU Alarm
EQU Alarm*EnableDisable
5.5.2.2.13 Batt. Tst Alarm
Batt. Tst Alarm*EnableDisable
5.5.2.2.14 Batt. Unb Alarm
Batt. Unb Alarm*EnableDisable
SETPOINT --V
5.5.2.3 Batt. Setting
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
B-ParameterT-COMPBDT SettingB-EQU Setting
5.5.2.3.1 B-Parameter Setting
7/23/2019 T ngun Delta -48V
34/75
ESAA150ABC07/09/11IOM
Page: 33 of 73
B-ParameterCapacity 200AH
EQU StopEQU Enable
a. EQU Stop Setting
Stop EQUMax. Time 1HrMin. Curr 0.01CExtra Time 1Hr
EQU CLStage1 0.25CStage2 0.15CStage3 0.10C
b. EQU Enable Setting
EQU EnableBatt. Cap ONBO Time ONBatt. VLT ON
b-1. Batt. Cap Setting
Battery Remain Cap
ONOFF
SETPOINT 80%
b-2. Batt. Time Setting
AC Break TimeONOFF
SETPOINT 1Hr
b-1. Batt. VLT Setting
Batt. VoltONOFF
SETPOINT 45V
5.5.2.3.2 T-COMP Setting
T-COMP*EnableDisable
7/23/2019 T ngun Delta -48V
35/75
ESAA150ABC07/09/11IOM
Page: 34 of 73
T-COMP EnableChoose T-COMP
LinearNon Linear
a. Linear
Coef 4mV/
RANGE 1.3V
T- START 25
b. Non Linear
T0, V0 0, 56.8T1, V1 15, 54.5T2, V2 35, 54.4T3, V3 60, 51.6
5.5.2.3.3 BDT Setting
Manual BDTPeriodic BDTNext BDT 00: 00YYYY/MM/DD
Manual BDT Setting
Manual BDTStatus: OFFSettingStart MBDT
BDTI 0.10CEnd VLT 45VBDT Time 1Hr
5.5.2.3.4 B-EQU Setting
Manual B-EQUPeriodic B-EQUNext B-EQU 00: 00YYYY/MM/DD
5.5.2.4 Date Setting
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
7/23/2019 T ngun Delta -48V
36/75
ESAA150ABC07/09/11IOM
Page: 35 of 73
Date SettingYYYY/MM/DD
HH: MM
5.5.2.5 Efficiency Mgt.
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
Efficiency Mgt.Status ON* Enable
Disable
5.5.2.6 Alarm Reset
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.
Alarm ResetTemp. Unit
Press ENTER;
Alarm ResetReset HVSDReset Com-Fail
a. Reset HVSD
- High voltage shutdown reset-
b. Reset Com-Fail
-Communication fail reset-
5.5.2.7 Temp. Unit
DC SettingAlarm SettingBatt. SettingDate Setting
Efficiency Mgt.Alarm ResetTemp. Unit
Press ENTER;
7/23/2019 T ngun Delta -48V
37/75
ESAA150ABC07/09/11IOM
Page: 36 of 73
Temp. UnitFahrenheit
* Celsius
5.5.3 Curr. Alarm
Sys InfoSys settingCurr. Alarm
Press ENTER;
L Bkr0-06A
BDT C AlarmTASF Alarm
7/23/2019 T ngun Delta -48V
38/75
ESAA150ABC07/09/11IOM
Page: 37 of 73
6 SWITCH MODE RECTIFIER (ESR48/56A SERIES RECTIFIER, 2700W)
6.1 Description
Deltas DPR2700 series is a compact and very reliable family of front-end rectifieroffering 2700W constant power output (From 48Vdc to 59.5Vdc, under 48Vdc isconstant current output). The modular design provides the flexibility to configureand expand the system as the load demand increases. Each rectifier is hotswappable with front access for ease of maintenance without system shutdownproviding uninterrupted service.
DPR2700 series is active power factor corrected to great than 0.99 PF (THD 0.99 at full load, nominal line
Efficiency: >91% at nominal line input
Protection: Fuse
6.2.2 Output
DC Output Voltage -40V~-59.5V
Output Power 2700W/ fixed
Regulation:
7/23/2019 T ngun Delta -48V
39/75
ESAA150ABC07/09/11IOM
Page: 38 of 73
Load: 250mV (load 0~100%)
Line: 50mV
Acoustic:
7/23/2019 T ngun Delta -48V
40/75
ESAA150ABC07/09/11IOM
Page: 39 of 73
6.4 Physical
Physical Dimensions (W x H x D) 4.94 x 1.61 x 10.63 inch125.5 x 41 x 269.9 mm
Weight 4.4lbs / 2.0Kg
6.5 Outline & Dimensions
6.6 SMR Operating Principle
After applying single phase 220 VAC to the SMR, current is applied to the EMI filterand circulates through protection components such as the AC circuit breaker andthe fuse. The major functions of the protection devices are to prevent the SMRfrom being damaged by surge current and to efficiently reduce the interruptionsignal of differential mode and common mode, to eliminate the high frequencyinterruption signal from input current and to prevent the feedback of interruptionsignal reverse current to the circuit.
After the single phase AC current been converted to DC current through bridge
rectifier, PFC boost converter, and reaches the requirement of True Power Factor(PF>0.99) (THD
7/23/2019 T ngun Delta -48V
41/75
ESAA150ABC07/09/11IOM
Page: 40 of 73
Before the stable voltage and DC current is delivered by the output of the rectifier,it has been converted by a DC/DC converter, the common mode EMI noise is
eliminated by a filter circuit, through an output circuit fuse, to the system in parallel.
7/23/2019 T ngun Delta -48V
42/75
ESAA150ABC07/09/11IOM
Page: 41 of 73
7 SWITCH MODE RECTIFIERS (ESR48/40A SERIES RECTIFIER, 2000W)
7.1 Description
Deltas DPR2000 series is a compact and very reliable family of front-end rectifieroffering 2000W constant power output (From 48Vdc to 59.5Vdc, under 48Vdc isconstant current output). The modular design provides the flexibility to configureand expand the system as the load demand increases. Each rectifier is hotswappable with front access for ease of maintenance without system shutdownproviding uninterrupted service.
DPR2000 series is active power factor corrected to great than 0.99 PF (THD 0.99 at full load, nominal line
Efficiency: 91% at nominal line input
Protection: Fuse
7.2.2 Output
DC Output Voltage -40V~-59.5V
7/23/2019 T ngun Delta -48V
43/75
ESAA150ABC07/09/11IOM
Page: 42 of 73
Output Power 2000W/ fixed
Regulation:
Load: 250mV (load 0~100%)
Line: 50mV
Acoustic: 300Khours at 25, rated load
7.2.5 Physical
Physical Dimensions (W x H x D)
4.94 x 1.61 x 10.63 inch
125.5 x 41 x 269.9 mm
Weight 4.4lbs / 2.0Kg
7/23/2019 T ngun Delta -48V
44/75
ESAA150ABC07/09/11IOM
Page: 43 of 73
7.3 Outline & Dimensions
7/23/2019 T ngun Delta -48V
45/75
ESAA150ABC07/09/11IOM
Page: 44 of 73
8 ALARMS AND TROUBLE SHOOTING
8.1 AC Fail/AC High Voltage / AC Low Voltage Alarm Description
There are three (3) AC alarm conditions that are monitored by the system: AC Fail,AC High Voltage and AC Low Voltage. AC fail occurs when AC current is notpresent. AC high Voltage (ACH) is a factory set parameter and can be adjusted.High Voltage Alarm (ACH) to the desired voltage. AC Fail alarms result in thesystem shutting down rectifiers until AC is restored (AC is restored, or the ACvoltage returns to levels within the parameter threshold settings.
8.1.1 AC Fail, AC Input High(ACH) and AC Input Low (ACL) Alarm Conditions
AC Fail: Major AlarmWhen the CSU senses the absence of AC voltage at the AC terminal, the CSU willactivate a major alarm. ACL and AC Fail Alarm are indicated on the CSU. Batteryis in discharge status. The alarm will be re-set to normal condition when AC isrestored.
AC Input High (ACH):
When the CSU senses the input AC Voltage exceeding parameter alarm, the CSUwill activate an AC High Alarm, displayed on the CSU. The CSU will continue tomonitor the AC input voltage. The ACH alarm will re-set to the normal operationwhen AC input voltage decreases within the threshold parameter setting.
AC Voltage Low (ACL):
The AC Voltage Low Alarm occurs when the AC input voltage falls below thethreshold set in parameter alarm. When the ACL condition is sensed, an ACLalarm is displayed on the CSU. The CSU will continue to monitor the AC inputvoltage. The ACL alarm will re-set to the normal operation when AC input voltageincreases within the threshold parameter setting.
8.1.2 AC Fail Trouble Shooting
Verify the AC input voltage at the AC service panel by a multi-meter. To checkwhether commercial power problem or AC circuit breaker tripped causes the ACFail. The AC circuit breaker should be tripped until the AC utility is repaired and the
AC input is within input specifications.
8.1.3 AC High Voltage (ACH) Trouble shooting
Verify the AC input voltage at the AC service panel by a multi-meter. If the AC inputvoltage is higher than the threshold setting, the system will continue to operate. Butif the AC voltage is not higher than the setting value, although the system stillcontinues to operate, the CSU may be faulty. The CSU should be swapped with aspare. Follow established repair/return policy to have the faulty CSU repaired byDelta Products.
7/23/2019 T ngun Delta -48V
46/75
ESAA150ABC07/09/11IOM
Page: 45 of 73
8.2 DC Output Voltage High/Low (HV/LV)
8.2.1 DC Output Voltage High Alarm-HV Minor Alarm.
This alarm condition exists when the DC output voltage is higher than theparameter alarm setting. The alarm will re-set to the normal condition when thevoltage is decreased below the threshold parameter setting. The output voltagecan be adjusted via the CSU.
8.2.2 DC Output Low Alarm-LV Minor Alarm
This alarm condition exists when the DC output voltage is lower than the parameteralarm setting. The alarm will clear when the DC output voltage increases. Theoutput voltage can be adjusted via the CSU.
8.2.3 DC Voltage High/Low Trouble Shooting
Verify the output of each rectifier. If the rectifier output is not within tolerance, swapthe rectifier with a spare module, and return the faulty unit to Delta Products forrepair. If the output of each rectifier is within tolerance, check the parameters toensure the correct settings.
8.3 DC Circuit Breaker Tripped Alarm
8.3.1 DC Circuit Breaker Tripped Alarm
When a DC load circuit breaker is tripped, the CSU will go into alarm.Press the alarm button and the CSU will display Breaker Fail.
Re-set the tripped circuit breaker.The CSU alarm should clear.
8.3.2 Circuit Breaker Fail Condition Trouble Shooting
If the circuit breaker continues to fail:Check the DC Branch load (fed by the DC circuit breaker) to ensure the circuitbreaker is the correct size.If the branch load exceeds the circuit breaker rating, the circuit breaker must bechanged to a higher rating.Swap with a spare circuit breaker with a higher rating.
8.4 Over-Temperature Alarm
8.4.1 Temperature-Ambient
This alarm is generated when the threshold temperature set in parameter alarmsetting TA is exceeded and also controls the Temperature Compensation VoltageControl. The CSU senses the temperature via sensor TA and generates an
Ambient Over Temperature Alarm setting TA.
8.4.2 Over Temperature - Ambient Troubleshooting
Verify that the ambient temperature has exceeded the parameter setting bychecking the thermal sensor reading in the hut or equipment room and comparingthe reading to the CSU Reading.
7/23/2019 T ngun Delta -48V
47/75
ESAA150ABC07/09/11IOM
Page: 46 of 73
The CSU will decrease the float voltage for every degree over 25or 77
threshold.
The CSU will decrease the equalize voltage for every degree below 25or 77 threshold.If the TA parameter setting has been exceeded, increase the air conditioning.If the TA threshold is exceeded, it is recommended to turn off the AC Main feedingthe Rectifiers until the ambient temperature has decreased below the thresholdtemperature.If the sensor is defective, turn the Temperature Compensation Feature off. ContactDelta for a replacement sensor
Warning! Operating the system at excessive temperatures can damage therectifier.
8.4.3 Over Temperature - Battery Alarm
This alarm is generated when the TB temperature is exceeded the thresholdtemperature set. The CSU senses the temperature via sensor TB and generates aBattery Over Temperature Alarm-TB.
8.4.4 Over Temperature-Battery Troubleshooting
Check the battery temperature and verify it is within the TB parameter threshold.If the TB thresholds are not exceeded, check the thermostat reading in the hut orequipment room and comparing the reading to the CSU reading. If the TB sensoris defective, contact Delta for a replacement sensor.
It is recommended that if the system is in the equalize mode, switch the status tofloat to reduce the battery temperature.
8.5 Rectifier Fail Alarm
When a rectifier fails, the alarm information is sent to the CSU and the rectifier isshut down. The rectifier should be swapped out with a spare unit and the faulty unitreturned to Delta for repair.
Warning! Do not open the rectifier module. There are no serviceable parts. CallDelta Customer Service for a RMA number for repair and return.
7/23/2019 T ngun Delta -48V
48/75
ESAA150ABC07/09/11IOM
Page: 47 of 73
9 MAINTENANCE
9.1 Cleaning and Maintenance
9.1.1 General
Special maintenance is not necessary for this shelf, unless the shelf is beingoperated in a severely harsh environment (dusty environment). The front panelsand the cover of the shelf were treated with a special coating, do not use organiccleanser or volatile solvent or corrosion damage may occur. For daily cleaning,brush the dust from the cover and panel. If necessary, use a gentle cleanser or alightly dampened lint free cloth to remove any dirt or smudges.
9.1.2 Periodic Maintenance
Periodic maintenance is not required for normal operation. If necessary, wipe toremove the dust from the front of the shelf with a lint free, soft cloth and gently wipethe front of the shelf, the CSU and rectifiers. Use a gentle detergent to clean isacceptable.
Warning! Do not use spray cleanser to clean the equipment. Using a spraycleanser directly on the equipment can result in serious equipmentdamage.
Check the DC Bus for heat discoloration. If the bus has any heat discoloration,
notify Delta Customer Service.
9.2 Removing and Replacing a Rectifier Module
9.2.1 Removing a Rectifier
LOCKER
TO LOCK
TO UNLOCK
7/23/2019 T ngun Delta -48V
49/75
ESAA150ABC07/09/11IOM
Page: 48 of 73
Warning! Do not touch the DC output Bus when pulling out the SMR module.
Warning! The rectifiers are equipped with a pair of safety locker.
Push the both locker (on the center of the fan) to unlock direction to un-lock therectifier.Pull out the SMR module slowly from the shelf, using one hand to support the rearhalf of the SMR and remove the rectifier from the shelf.
9.2.2 Replacing a Rectifier
Install the rectifier module, holding the handle with one hand and using the other tosupport the rear half of the rectifier module. Place the rectifier in the shelf and pushinto the shelf.
Warning! Do not force the module into the slot. If it does not slide in and connecteasily, remove and re-set the unit.
Lock the rectifier by push the locker to the lock direction to lock the rectifier.
9.2.3 Adding a Rectifier
Refer to the procedures in section 9.2.2.
7/23/2019 T ngun Delta -48V
50/75
ESAA150ABC07/09/11IOM
Page: 49 of 73
10 SYSTEM COMMUNICATION SOFTWARE
10.1 INTRODUCTION
This document describes initialization and functionality of system communicationsoftware for New Smart CSU, and how to use it in user applications. The remotecontrol and monitor functions, which is in a Windows based PC via dial-up USBinterface port. It can remote control and monitoring by communicating remotelyover PC loaded with the NRMS software package. In addition, NRMS software iswith the following features.
Applied in Local Access (USB).
Complete monitoring and control to CSU & Rectifier.
Being Suitable for all New Smart CSU.
Reach Up to 100 Event Logs for Power Diagnosis and Analysis.
Being with User-friendly Interface.
Battery Management.
Windows 2000/XP Support
10.2 INSTALL AND UNINSTALL RMS SOFTWARE
This chapter describes how to install and uninstall the NRMS software underWindows Operation System. Please follow the steps below to start.
10.2.1 System Requirements
The following minimum configuration is required to run RMS Software.
PC-compatible Pentium class system
Microsoft Windows 2000 / XP (Strong suggestion Windows XP)
Microsoft Office 2000 or above. (Strong suggestion Microsoft Office 2003)
64 MB memory (128MB recommended)
45 MB of hard disk space
10.2.2 SYSTEM Components
In addition to PC whose operation system is Windows, the following component isrequired:
NRMS Software-installed on the PC to control and monitor Telecom PowerSystem.
USB cable To connect NCSU to COM port on the PC.
7/23/2019 T ngun Delta -48V
51/75
ESAA150ABC07/09/11IOM
Page: 50 of 73
10.2.3 When the PC is without NRMS
If your PC has never installed NRMS, please follow below to install this software. Turn on the host computer.
Please copy NRMS software into Hard Disk. And choose setup.exe to RunSetup to do installation.
10.2.4 When the PC is with NRMS
Remove old versions
Follow the step of 10.2.3
10.2.5 Uninstall
Click on Start>Settings> Control Panel> Add/Remove Programs.
Choose NRMS.
Click on Remove icon to remove NRMS Software.
10.3 GET START NRMS SOFTWARE
This section will describe how to get start the NRMS software, including whatcomponents should be prepared, menu and toolbar functions.
10.3.1 RMS Toolbar
This is a listing of RMS menus and Toolbar. You can achieve your desired functioneither by clicking toolbar.
10.3.1.1 Toolbar
Below, Figure1, is the toolbar RMS provides.
Figure 1. The Toolbar of RMS software
CSU
Click on this icon to access the CSU information.
Rectifier
Click on this icon to access the rectifier information.
Battery
7/23/2019 T ngun Delta -48V
52/75
ESAA150ABC07/09/11IOM
Page: 51 of 73
Click on this icon to access the battery information.
Parameter
Click on this icon to access the parameter setting screen.
Alarm
Click on this icon to access the alarm information.
Event
Click on this icon to access the event information.
Setting
Click on this icon to access the parameter setting.
10.4 HOW TO SETUP CONNECTION PROFILE INFORMATION
This section will describe how to setup every component of Connection profileInformation
10.4.1 Explanation of connection field
Below is the explanation of connection field.
10.4.1.1 Start up
The waiting screen will display after NRMS had switch on. There wont be anyinformation on each item.
7/23/2019 T ngun Delta -48V
53/75
ESAA150ABC07/09/11IOM
Page: 52 of 73
10.4.1.2 Direct Connection with USB
NRMS can be direct connecting to NSCSU with USB cable. Refer to the figurebelow. (Click RS-232 Icon)
7/23/2019 T ngun Delta -48V
54/75
ESAA150ABC07/09/11IOM
Page: 53 of 73
10.5 Software Function
10.5.1 Permission Management
NRMS has four permission levels of system operation, setting and debug to suiteach level of user.Function of each level:1. USER level: Monitoring the parameter of system, Alarm and Even log.2. ADMIN level: User level plus parameter setting and time setting.3. SADMIN level: Admin level plus Secondary language Translation, Installation
Notes, NCSUs EEPROM Download & Upload and Relay & LED Configuration.
Permission level
Function item
USERLEVEL
ADMINLEVEL
SADMINLEVEL
System Monitor
System parameter set
Manual BT & EQU
LVDS manual Trip
System Time set
Data log
Secondary language Translation
Installation Notes
NCSUs EEPROMDownload & Upload
Relay & LED Configuration
10.5.2 Changing Permission
The function will be in USER level after NRMS connect to the CSU, user canchange the level by using the Setting Chang Permission button.
7/23/2019 T ngun Delta -48V
55/75
ESAA150ABC07/09/11IOM
Page: 54 of 73
10.5.3 Change Password
NRMS provide the function of setting and change for password to protect theoperation function of ADMINlevel. User can change the password by using theSetting Chang Password button.
The preset password of ADMIN LEVEL is 0000, SADMIN LEVEL is 8888when ex-factory, change the password after NRMS install completed.
10.5.4 Log Out
User can return to User level by using the Setting Log out button.
7/23/2019 T ngun Delta -48V
56/75
ESAA150ABC07/09/11IOM
Page: 55 of 73
10.6 system information monitoring
This section describes every information display on the monitor and theirrepresentational meaning.
10.6.1 CSU Information
DCV: DC voltage of the systemAmbient Tem: Ambient Temperature of the systemDCI: DC current of the systemTotal Current: Total SMR current + Battery current
ACV1: AC voltage 1ACV2: AC voltage 2ACV3: AC voltage 3EQU Start: Manual equalizing chargingBattery Test Start: Manual battery testClear Buzzer: Buzzer clear
Modal Name: Name of the firmware modalFile Name: Firmware file nameFirmware Ver.: Firmware version
RMS Version
7/23/2019 T ngun Delta -48V
57/75
ESAA150ABC07/09/11IOM
Page: 56 of 73
10.6.2 Rectifier Information
Max. No. ofSMR
Fail SMR On dutySMR
Off dutySMR
Communica
tion errorSMR
To clear the
communicationerror
SMR
7/23/2019 T ngun Delta -48V
58/75
ESAA150ABC07/09/11IOM
Page: 57 of 73
10.6.3 Battery Information
Total Current: Total SMR current + Battery currentEstimate Capacity: Total battery capacityBattery Current 1: Current of battery 1Battery Current 2: Current of battery 2Battery Current 3: Current of battery 3Battery Voltage 1: Middle point voltage of battery 1Battery Voltage 2: Middle point voltage of battery 2Battery Voltage 3: Middle point voltage of battery 3Battery Voltage 4: Middle point voltage of battery 4Battery Temp 1: Battery 1 temperatureBattery Temp 2: Battery 2 temperatureBattery Temp 3: Battery 3 temperature
7/23/2019 T ngun Delta -48V
59/75
ESAA150ABC07/09/11IOM
Page: 58 of 73
10.6.4 Alarm Status
10.6.5 Event Log
Contents of the event
Numbers of the event
Clear the events
Alarmdisplayin red
Ex ort the events
7/23/2019 T ngun Delta -48V
60/75
ESAA150ABC07/09/11IOM
Page: 59 of 73
10.7 System Parameter Configuration
The configuration in this chapter is suit only for ADMIN level and above.
10.7.1 ParameterSystem Parameter
DCH: DC high voltageDCL: DC low voltageHVSD: High voltage shutdownLVDS 1: Low voltage disconnect 1LVDS 2: Low voltage disconnect 2LVDS 3: Low voltage disconnect 3Float Voltage: Floating charge voltageEQU Voltage: Equalizing charge voltageTAH: High ambient temperatureTAL: Low ambient temperatureHTSD: High temperature shutdownLTSD: Low temperature shutdown
ACH: AC high voltageACL: AC low voltageEnergy Saving: Energy saving functionLVDS 1 Trip: Manual low voltage disconnect trip 1LVDS 2 Trip: Manual low voltage disconnect trip 2LVDS 3 Trip: Manual low voltage disconnect trip 3Set Date and Time: Present date and time settingOver percentage of capacity: Rectifier output capacity alarm setting
7/23/2019 T ngun Delta -48V
61/75
ESAA150ABC07/09/11IOM
Page: 60 of 73
10.7.2 ParameterBattery Parameter
Capacity: Total battery capacityTBH: High battery temperatureMiddle Test Voltage: Battery middle test voltage
SMR Max. Current Limit: Value of SMR Max. current limitCharge Management: Charge management functionStage 1 Current Limit: Charge current limit (Stage 1)Stage 2 Current Limit: Charge current limit (Stage 2)Stage 3 Current Limit: Charge current limit (Stage 3)Battery Test: Battery testTest Time: Battery test timeTest Voltage: Battery test end voltageTest Current: Battery test currentBattery Periodic: The periodic of battery testTest Periodic: The periodic of battery test (month)Test Date: The periodic of battery test (day)
Test Oclock: The periodic of battery test (hour)Last Battery Test Time: Last battery test timeNext Battery Test Time: Next battery test time
7/23/2019 T ngun Delta -48V
62/75
ESAA150ABC07/09/11IOM
Page: 61 of 73
10.7.3 ParameterTemperature Compensation
Temp Compensation: Temperature compensation functionCompensation Mode: Temperature compensation modeLinear: Linear temperature compensation modeCoefficient: Coefficient of temperature compensationRange: Range of temperature compensationTemp Comp Center: Center temperature of temperature compensation
Click here when inCurve mode
Select a battery typewhen in Curve Mode
7/23/2019 T ngun Delta -48V
63/75
ESAA150ABC07/09/11IOM
Page: 62 of 73
Curve: Curve temperature compensation modeT0: Temperature setting 1
T1: Temperature setting 2T2: Temperature setting 3T3: Temperature setting 4V0: Voltage setting 1V1: Voltage setting 2V2: Voltage setting 3V3: Voltage setting 4
10.7.4 ParameterEQU Parameter
7/23/2019 T ngun Delta -48V
64/75
ESAA150ABC07/09/11IOM
Page: 63 of 73
EQU: Equalize charging modeEQU Max. Time: Equalize charging maximum time
Additional EQU Time: Additional equalize charging timeEQU Terminal Current: Equalize charging end currentEQU Periodic: The periodic of equalize chargingEQU Period: The periodic of equalize charging (month)EQU Date: The periodic of equalize charging (day)
Deep Discharge ConditionSetting Icon
Deep DischargeParameter SettingIcon
7/23/2019 T ngun Delta -48V
65/75
ESAA150ABC07/09/11IOM
Page: 64 of 73
EQU Oclock: The periodic of equalize charging (hour)Last EQU Time: Last equalize charging time
Next EQU Time: Next equalize charging time
10.7.5 ParameterAlarm Mask
Current Limit: Current limit alarmOne Rectifier Fail: One rectifier fail alarmMore Rectifiers Fail: More than one rectifiers fail alarmMajor: Major alarmMinor: Minor alarmLoad Breaker: Load breaker trip alarmLoad Priority Hi: High priority load breaker trip alarmLoad Priority Low: Low priority load breaker trip alarmLoad Fuse: Load fuse blown alarmRail: Rail output load alarmGMT Fuse: GMT fuse blown alarmDCH: DC high voltage alarmDCL: DC low voltage alarmLVDS trip: Low voltage disconnect trip alarmTAH: High ambient temperature alarmTAL: Low ambient temperature alarmTA Sensor Fail: Ambient temperature sensor fail alarm
ACH: AC high voltage alarmACL: AC low voltage alarmAC Breaker: AC breaker trip alarmAC Phase Lost: AC phase lost alarmTB Sensor Fail: Battery temperature sensor fail alarmTBH: High battery temperature alarmBattery Switch: Battery fuse blown alarmBattery Discharge: Battery discharge alarm
7/23/2019 T ngun Delta -48V
66/75
ESAA150ABC07/09/11IOM
Page: 65 of 73
Battery Breaker: Battery breaker trip alarmMiddle Test Fail: Battery middle test fail alarm
Battery Test Fail: Battery test fail alarmRect Over Percent of Capacity: Rectifier over percent of capacity alarm
10.7.6 Relay and LED
10.7.7 WEB Connective (Optional)
7/23/2019 T ngun Delta -48V
67/75
ESAA150ABC07/09/11IOM
Page: 66 of 73
10.8 Other function
10.8.1 Data Logging
Notice:
1. When in Data Logging process, do not open the file, which is assigned to save;otherwise, unexpected mistake may occur.
2. If theapplication of Excel version is Office 2000, suggest to open DataLogging file as following steps:
Click to enter the IP address,Subnet Mask and Gateway
1. Click to selectWEB IP Rule
2. Always clickFOLLOW and Enter
7/23/2019 T ngun Delta -48V
68/75
ESAA150ABC07/09/11IOM
Page: 67 of 73
a. Open Excel application first, then, click Open to choose the assignData Logging file to open the file.
b. Close the NRMS software; double click to open the Data Logging file.
Note! The Excel software may appear unnormal or can not be open if youopen the Data Logging file directly without close the NRMS softwarefirst.
Assign the file name
Setting the file recording
size and period
Starting datalog
Datalog executing
7/23/2019 T ngun Delta -48V
69/75
ESAA150ABC07/09/11IOM
Page: 68 of 73
10.8.2 Secondary Language Support
Starting the secondarylanguage translatefunction
Copy theword
Keyingtranslate word
Saving
the word
7/23/2019 T ngun Delta -48V
70/75
ESAA150ABC07/09/11IOM
Page: 69 of 73
10.8.3 NCSUs EEPROM Download & Upload
10.8.3.1 Download
Select the language
English: EnglishLocal: Second language
1.Select download function
2. Assign the file name
3. Startin download
7/23/2019 T ngun Delta -48V
71/75
ESAA150ABC07/09/11IOM
Page: 70 of 73
10.8.3.2 Upload
2. Assign the file name
1.Select u load function
3. Starting upload
7/23/2019 T ngun Delta -48V
72/75
ESAA150ABC07/09/11IOM
Page: 71 of 73
11 ACRONYMS AND ABBREVIATIONS
--- A ---Amp Ampere
--- B ---BTU British Thermal Unit
--- C ---C CentigradeCB Circuit BreakerCCU Climate Control UnitCE European CommunityCISPR International Special Committee on Radio InterferenceCL Current LimitCM Centimeter
CSU Control & Supervising UnitC
UL Canadian Underwriters Laboratory
--- D ------ E ---
EMI Electro-Magnetic InterferenceES Power SystemESD Electrostatic DischargeESR Rectifier
--- F ---F FahrenheitFCC Federal Communications CommissionFt. Foot
--- G ---
GND Ground--- H ---HV High VoltageHVSD High Voltage ShutdownHz Hertz
--- I ---IEC International Electronics CommissionIEEE Institute of Electrical and Electronics EngineersIn. Inch
--- J ------ K ---
Kg. KilogramKgf-cm Kilogram Force-CentimeterKHz Kilohertz
KHz KilohertzKV KilovoltKW Kilowatt
--- L ---Lb. PoundLCD Liquid Crystal DisplayLED Light-Emitting DiodeLV Low VoltageLVD Low Voltage DisconnectLVBD Low Voltage Battery DisconnectLVLD Low Voltage Load DisconnectLVDS Low Voltage Disconnect Switch
--- M ---
7/23/2019 T ngun Delta -48V
73/75
ESAA150ABC07/09/11IOM
Page: 72 of 73
M Meter
Max.Maximum
MHz Megahertz
mm Millimeter
ms Millisecond
MTBF Mean Time Between Failure
mV Millivolt
mVrms Millivolt root mean square
--- N ---
NCSU New Smart CSU
NEMA National Electrical Manufacturers Association
Nm Newton-Meter
No. Number
--- O ------ P ---
PDU Power Distribution Unit
PF Power Factor
PFC Power Factor Correction
--- Q ---
Qty. Quantity
--- R ------ S ---
--- T ---
TB Terminal Block
THD Total Harmonic Distortion
--- U ---
UL Underwriters Laboratory--- V ---
V Volt
VAC Volts AC
VDC Volts DC
--- W ---
W Watt
--- X ------ Y ------ Z ---
RFA Rectifier Failure Alarm
RFI Radio Frequency Interference
RH Relative Humidity
RMA Return Material Authorization