Type 2 Switchgear Combination

Embed Size (px)

Citation preview

  • 8/23/2019 Type 2 Switchgear Combination

    1/15

    Article on Type 2 as per IS

  • 8/23/2019 Type 2 Switchgear Combination

    2/15

    What is CoWhat is Co--ordination?ordination?

    An optimized combination of

    Switching Device

    Overload Protecting Device (OLPD)

    Short Circuit Protecting Device (SCPD)

    .... To ensure protection of personnel and equipment in the event

    of fault

  • 8/23/2019 Type 2 Switchgear Combination

    3/15

    Problem with non coProblem with non co--ordinated feedersordinated feeders

    Erratic tripping of Protective Devices

    Burning of motors

    Altered tripping characteristics of overload relays

    requen p ng we ng o con ac s

    Damaged Insulation of components

    Danger to life of operating personnel=

  • 8/23/2019 Type 2 Switchgear Combination

    4/15

    Motor should not stop when..- running on rated load- drawing starting current for permissible starting time

    - utilized to permissible short time overload capacity- put in service according to utilization category

    Objective of CoObjective of Co--ordinationordination

    - between overload and short circuit protecting device

    Protection

    - of switching and overload device during short circuit

  • 8/23/2019 Type 2 Switchgear Combination

    5/15

    Two types of co-ordination are permissible, "1" or "2".

    Type "1" co-ordination requires that, under short-circuit conditions, the contactor or startershall cause no danger to persons or installation and may not be suitable for further

    service without repair and replacement of parts.

    T e "2" co-ordination re uires that under short-circuit conditions the contactor or

    Co-ordination as per IEC 60947-4-1

    starter shall cause no danger to persons or installation and shall be suitable for furtheruse. The risk of contact welding is recognized, in which case the manufacturer shallindicate the measures to be taken as regards the maintenance of the equipment.

    Use of an SCPD not in compliance with the manufacturer's recommendations mayinvalidate the coordination.

  • 8/23/2019 Type 2 Switchgear Combination

    6/15

    How it is achieved?How it is achieved?

    The selection of devices is done in such a way so that

    The time-current characteristics of OLPD and SCPD must allows sufficienttime for the motor to run up

    SCPD must protect the OLPD from destruction by overload currentsexceeding approximately 10 times its rated current

    mus n errup curren s w c are oo arge o e sw c e o ycontactor (short circuit currents)

    SCPD must protect the contactor in the event of short circuit

    SCPD Short Circuit Protecting DeviceOLPD Over Load Protecting Device

  • 8/23/2019 Type 2 Switchgear Combination

    7/15

    t

    OLPD Curve

    SCPD Curve

    Annexure 4:Trippingcharacteristics of

    various products

    Ian

    OLPD and SCPD must allows sufficient time for the motor to run up

  • 8/23/2019 Type 2 Switchgear Combination

    8/15

    tst

    OLPD destructionCurve

    Ian

    SCPD must protect the OLPD from destruction

  • 8/23/2019 Type 2 Switchgear Combination

    9/15

    SCPD must protect the contactor in the event of short circuit

    Contactor curve forseparable welding

  • 8/23/2019 Type 2 Switchgear Combination

    10/15

    The short circuit test is done at two operational conditions

    a) with all the switching devices closed prior to the test

    b) closing the contactor or starter on to the short-circuit current

  • 8/23/2019 Type 2 Switchgear Combination

    11/15

    MPCB

    Overload curveShort circuit curve

    MPCB MCB

    MCB

    Overload curveShort circuit curve

    Comparison the curve of MCB / contactor andType 2 co-ordinated MPCB / contactor combination

    MPCBOverload destruction curve

    ContactorContactor curve for

    separable welding

  • 8/23/2019 Type 2 Switchgear Combination

    12/15

    Blower Motor ` MPCB

    KW: 1.1 kW MCB

    Amps: 2.6 A Contactor welding curve

    2000

    1000

    500

    200

    100

    50

    20

    10

    5

    Present

    MCB 6AContactor 16A

    Type 2MPCB : 2.2 3.2AContactor 12A

    2

    0.1

    0.05

    0.05

    0.01

    0.005

    0.002

    1.6 2.1 3 5 8 16 21 26 52 78 104 156 Amps

  • 8/23/2019 Type 2 Switchgear Combination

    13/15

  • 8/23/2019 Type 2 Switchgear Combination

    14/15

  • 8/23/2019 Type 2 Switchgear Combination

    15/15

    Present situationAC coaches

    ContactorMPCB

    Short Circuit

    Type 2 co-ordinatedswitchgear

    MCB

    Birelay Contactor

    Type 2 co-ordination

    Contactor