Article on Type 2 as per IS
8/23/2019 Type 2 Switchgear Combination
2/15
What is CoWhat is Co--ordination?ordination?
An optimized combination of
Switching Device
Overload Protecting Device (OLPD)
Short Circuit Protecting Device (SCPD)
.... To ensure protection of personnel and equipment in the event
of fault
8/23/2019 Type 2 Switchgear Combination
3/15
Problem with non coProblem with non co--ordinated feedersordinated feeders
Erratic tripping of Protective Devices
Burning of motors
Altered tripping characteristics of overload relays
requen p ng we ng o con ac s
Damaged Insulation of components
Danger to life of operating personnel=
8/23/2019 Type 2 Switchgear Combination
4/15
Motor should not stop when..- running on rated load- drawing starting current for permissible starting time
- utilized to permissible short time overload capacity- put in service according to utilization category
Objective of CoObjective of Co--ordinationordination
- between overload and short circuit protecting device
Protection
- of switching and overload device during short circuit
8/23/2019 Type 2 Switchgear Combination
5/15
Two types of co-ordination are permissible, "1" or "2".
Type "1" co-ordination requires that, under short-circuit conditions, the contactor or startershall cause no danger to persons or installation and may not be suitable for further
service without repair and replacement of parts.
T e "2" co-ordination re uires that under short-circuit conditions the contactor or
Co-ordination as per IEC 60947-4-1
starter shall cause no danger to persons or installation and shall be suitable for furtheruse. The risk of contact welding is recognized, in which case the manufacturer shallindicate the measures to be taken as regards the maintenance of the equipment.
Use of an SCPD not in compliance with the manufacturer's recommendations mayinvalidate the coordination.
8/23/2019 Type 2 Switchgear Combination
6/15
How it is achieved?How it is achieved?
The selection of devices is done in such a way so that
The time-current characteristics of OLPD and SCPD must allows sufficienttime for the motor to run up
SCPD must protect the OLPD from destruction by overload currentsexceeding approximately 10 times its rated current
mus n errup curren s w c are oo arge o e sw c e o ycontactor (short circuit currents)
SCPD must protect the contactor in the event of short circuit
SCPD Short Circuit Protecting DeviceOLPD Over Load Protecting Device
8/23/2019 Type 2 Switchgear Combination
7/15
t
OLPD Curve
SCPD Curve
Annexure 4:Trippingcharacteristics of
various products
Ian
OLPD and SCPD must allows sufficient time for the motor to run up
8/23/2019 Type 2 Switchgear Combination
8/15
tst
OLPD destructionCurve
Ian
SCPD must protect the OLPD from destruction
8/23/2019 Type 2 Switchgear Combination
9/15
SCPD must protect the contactor in the event of short circuit
Contactor curve forseparable welding
8/23/2019 Type 2 Switchgear Combination
10/15
The short circuit test is done at two operational conditions
a) with all the switching devices closed prior to the test
b) closing the contactor or starter on to the short-circuit current
8/23/2019 Type 2 Switchgear Combination
11/15
MPCB
Overload curveShort circuit curve
MPCB MCB
MCB
Overload curveShort circuit curve
Comparison the curve of MCB / contactor andType 2 co-ordinated MPCB / contactor combination
MPCBOverload destruction curve
ContactorContactor curve for
separable welding
8/23/2019 Type 2 Switchgear Combination
12/15
Blower Motor ` MPCB
KW: 1.1 kW MCB
Amps: 2.6 A Contactor welding curve
2000
1000
500
200
100
50
20
10
5
Present
MCB 6AContactor 16A
Type 2MPCB : 2.2 3.2AContactor 12A
2
0.1
0.05
0.05
0.01
0.005
0.002
1.6 2.1 3 5 8 16 21 26 52 78 104 156 Amps
8/23/2019 Type 2 Switchgear Combination
13/15
8/23/2019 Type 2 Switchgear Combination
14/15
8/23/2019 Type 2 Switchgear Combination
15/15
Present situationAC coaches
ContactorMPCB
Short Circuit
Type 2 co-ordinatedswitchgear
MCB
Birelay Contactor
Type 2 co-ordination
Contactor