Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 1 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Three Phase Numerical Distance Protection Relay Protection Elements for Comprehensive Numerical Transmission Line Protection Relay; (A) Impedance Function:
Three Phase Distance Protection
Four Independent Groups
Five Independent Zones of Protection
Permissive Over reach Trip Transfer (Z1ext.)
Independent Polygonal/Mho characteristics for Phase to Phase and Phase to Ground Faults
Power swing Detection
Load Encroachment Detection
Settable Switch On to faults and Auto Recloser
VT Fuse Fail
Circuit Breaker failure(50BF)
Disturbance Recorder
16 Red, Green LED for Indications
Relay healthy indication (Green)
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 2 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
(B) Backup Over current Function: Directional / Non-directional Phase Over current element (Three stages)
Ground Over current element (Three stages)
(C) Under voltage/Over voltage Function: Three phase Under voltage element (Two stages)
Three phase Over voltage element (Two stages)
(D) Auto Recloser: (E) Trip Circuit supervision: Relay Design Features:
Minimum operating time of 1.5 Cycles (30msec).
Large 20x4 LCD display for Parameter and setting display.
In built Real Time Clock with non-volatile memory for time stamping.
Display of various counters
Disturbance Recorder - Up to 1sec of actual waveform of current & voltage along with logical and
physical status are captured & saved in built-in memory with date time stamping, for analyzing fault
condition & fault location.
Fully communicable with IEC standard open protocol. 60870-5-103.
Separate Communication Port for SCADA (RS485) as well as Local testing (RS232C).
Online display of CB status and other digital and logical status.
Continuous monitoring of module’s internal hardware and alarm generation in case of failure of any
critical components.
10 Programmable Digital Output contacts.
8 Optically isolated digital status input for monitoring of status and avoid use of external relay logic.
2 dedicated status input for Trip Circuit Monitoring.
100 nos. of event memory, event such CB close, Trip, digital status change, relay pkp etc. All events
are with date and time stamped with up to 1ms accuracy.
10 nos. of Fault data stored with keypad interface and time stamping.
Display of Voltage, current, frequency, Reactance, Resistance in terms of secondary value.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 3 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Power System Data: (General settings)
General Settings Setting Range This use for communication Unit ID : 001 – 250
Baud Rate : Range 1200 – 57600 Com Port : RS232/RS485 Set Parity : None/Even/Odd
Rated frequency Freq Select : 50Hz – 60Hz Setting Group setting Grp Select : Range G1 – G4 Breaker Fail Function BF Enable : YES/NO
< BF I : 10 – 100 % BF Delay : 100 – 1000mSec
CT/PT settings CT Sec : 1Amp/5Amp CT Primary : 1 – 30000 Amp PT Primary : 110 – 1000 KV
Local tripping blocking Local Control : Yes/No Trip circuit supervision Function Enable / disable
Trip Ckt Test : Yes/No
calibration const R Angle Offset : 000 – 359 Y Angle Offset : 000 – 359 B Angle Offset : 000 – 359 Reset Delay : (50-500)msec
Fault Detection Ph / F Det.Ip>= : 0.05 – 4.00 x In E/F Det : (3Io|3Vo) / (3Io&3Vo) 3Io > : 0.05-4 x In 3Vo > : 0.1 – 100V x Vn
Compensation setting for EF Kconst : 0.1 – 10 KAngle : 0 – 90
Fault Distance Constant X/km 1A : 0.005 to 10 Ohms / km X/Km 5A : 0.001 to 2 Ohms / km
DPR (distance protection settings)
Beta : 0 – 135 Deg Alpha : 0 – 45 Deg Reactive Ang Dir : +/- Reactive Angle : (0-20)Deg RCA Ang : 30 – 90 Deg in steps of 10 Deg.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 4 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
(A) Impedance Function (21): Fault Detection logic:
Phase to Phase Fault detection: Ph-to-ph distance element can pick up, when the relay detect the vector difference between two phase
current greater than the Minimum Iph: 0.05 to 4 X In or The phase-phase loops are evaluated when the
phase current in both of the affected phases exceeds the minimum value Iph> to detection settings.
Figure: Short-circuit of a phase-phase loop Phase to Ground Fault detection: Earth fault is detected when a zero sequence current or a zero sequence voltage threshold is exceeded
or when both criteria are met. 3I0> OR 3U0> (default setting) applies E/F recognition if only one of the
two criteria is valid. Select 3I0> AND 3U0> to activate both criteria for earth-fault detection. If you want to
detect only the earth current, set 3I0> OR 3U0> and also 3U0> Threshold (1-100V in step of 1V).
Fault Detection Z<
Phase fault Detection
Ground fault Detection
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 5 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
When an earth fault detection is recognized ie. 3Io or 3Uo greater than the Minimum 3I0:0.05 to 4 X In,
3U0: 1-100V and the phase current exceeds a settable minimum value Minimum Iph>.0.05 to 4 X In for
E/F detection settings, respectively.
Figure: Short-circuit of a phase-earth loop
Timer Logic: If the measured value of the impedance falls in zone-2, zone-3, zone-4 or zone-5, the relay starts a timer.
When the timer count value exceeds the preset value for the corresponding zone, the flag for the fault
detection of that particular zone is set. Timers are incorporated in the software by counting the number of
samples during processing. If the fault in zone-1, the trip signal is issued by the relay only after ensuring
the impedance consistency for the subsequent three samples.
For Three Phase Fault In case of a three phase fault, positive sequence current should be greater than the set value.
Zabc = Z1 = V1/I1 = positive sequence impedance
Zone1 settings (same for z2, z3, z4, z5) Status : Enable / Disable
Operating Mode : Forward / Reverse / Non-Directional Characteristic Mode : Quadrilateral/ mho
Quadrilateral Mode
R1Ph (R) in Ohms : 0.05 to 200 Ohms in step 0.01ohm R1Ph (L) in Ohms : 0.05 to 200 Ohms X1Fw in Ohms : 0.05 to 200 Ohms X1Rv in Ohms : 0.05 to 200 Ohms R1E (R) in Ohms : 0.05 to 200 Ohms R1E (L) in Ohms : 0.05 to 200 Ohms Time delay Z2-Z5 :0.00-30 Sec in step of 0.01 Sec
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 6 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Z1 Extension Z1 ext : Enable Kz1e PP : 1 – 50
Kz1e PG : 1 – 50 Tz1e : 0.1 – 10 Sec in step 0.01sec
Mho Mode Zone 1-5
Z1 : 0.05 – 200 Ohms Zoffset :+Ve/-Ve Zoffset :0.05 – 10 Direction Ang. :0 – 90 Deg in steps of 1 Deg.
Figure: Polygonal characteristic Power Swing Detection: Power swings occur when the output voltages of generators at different points in the power system slip
relative to each other, as a result of system instabilities which may be caused by sudden changes in load
magnitude or direction
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 7 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
During power swing condition, the relay operation should be blocked. Power swing is sensed when the
computed value of the impedance is found to lie within the power swing band for more than the preset
value of the timer to detect power swing blocking condition. If the measured impedance lies in the power
swing band for more than the fixed time of 35ms, the relay operation is blocked for a period of selectable
time otherwise the distance relay operates in the normal ways.
Power Swing Detection: Power Swing Detection: Status: Enable / Disable Quadrilateral Mode
Rin Fwd in Ohms 0.05 to 200 Ohms Xin Fwd in Ohms 0.05 to 200 Ohms Rin Rwd in Ohms 0.05 to 200 Ohms Xin Rwd in Ohms 0.05 to 200 Ohms Rout Fwd in Ohms: 0.05 to 200 Ohms Xout Fwd in Ohms 0.05 to 200 Ohms Rout Rwd in Ohms: 0.05 to 200 Ohms Xout Rwd in Ohms 0.05 to 200 Ohms Inclination Angle 30 to 90 Degrees in steps of 1 Degree I start: 0.5 to 2 X In Time delay P/S 0.04 to 5s P/S Block Zones All Zones/ Selectable Zones (Z1, Z2, Z3, Z4, Z5)
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 8 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Load Encroachment Detection: If the transmission line is long and the resistive setting chosen conflicts with load, a load encroachment
element is required. The purpose of this element is to avoid trip in high load conditions. They blocked the
operation of distance elements if the calculated positive sequence impedance stays within the range set
for the timers.
Trip logic : Two independent positive-sequence impedance ie. Complex positive sequence impedance
characteristics monitor load conditions and test it against the boundaries of these regions. If the
impedance is inside either region, or the load-encroachment logic is enabled (ELE = Y), then the relay
concludes the impedance represents load, and three-phase distance elements are blocked.
If the impedance is outside both load regions, the Quadrilateral elements are permitted to operate.
Load detected in the load-in or load-out regions. If │I1│ must exceed 0.1·Inom A. Z1 = Calculated Positive Sequence Impedance
I1 = Positive Sequence current
Inom = Nominal rated current
Load Encroachment Detection: Load Encroachment Detection:
Status: : Enable / Disable
Rloadmax Fwd in Ohms : 0.05 to 200 Ohms Rloadmin Fwd in Ohms : 0.05 to 200 Ohms Rloadmax Rwd in Ohms : 0.05 to 200 Ohms Rloadmin Rwd in Ohms : 0.05 to 200 Ohms Ang1Fwd : 0 to +90 Degree Ang2Fwd : 270 to 360 Degree Ang1Rwd : 90 to 180 Degree Ang2Rwd : 180 to 270 Degree
Automatic Switch On to Fault Detection (SOTF): Switch on to fault protection (SOTF) is provided for high speed clearance of any detected fault
immediately following manual closure of the circuit breaker. SOTF protection remains enabled for 500ms
following circuit breaker closure, detected via the CB Man Close input or CB close with CB control or for
the duration of the close pulse on internal detection.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 9 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Automatic Switch On to Fault Detection (SOTF): SOTF Status : Enable / Disable
Characteristic Mode : mho / Quadrilateral
IPh> in % : 5 to 100% of In, steps of 1% VPh< in % : 5 to 100% of Un, steps of 1% t> : 0 to 10s, steps of 10ms
Voltage Transformer Supervision/Fuse Fail Detection: Loss of one or several secondary voltages, without equivalent loss of respective primary voltage signal(s),
is called VT signal failure. This feature will enable if phase voltage is greater than Vp set or default value
0.7*Vnom/1.732 and phase current is greater than set Iph> , default sett.0.05*In.
This function can block the operation of the distance elements.
Condition shall be detected when;
3Vo > 20% of VN (L-N)& 3Io < 20% of IN
Fuse failure will cause voltage unbalance and hence vo(v2)but no current unbalance io(i2)
Unbalanced faults cause both voltage/current unbalance, preventing vts operation
Fuse fail supervision is blocked for 150 to 300ms following line energization in order not to operate for
unequal pole closing & also during auto-reclosing
Fuse Fail Detection FFD Status: : Enable / Disable Zero Seq. Mode:
3V0> in % : 5 - 100 in steps of 1% 3I0< in % : 5 - 100 in steps of 1% Alarm Time : 0 to 300s in steps of 10ms
VPh<
IPh>
Close Command from CB
SOTF Trip
t>
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 10 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
(B) Backup Over current Function: If there is a fault in the voltage-measuring circuit, distance protection is blocked, since accurate
impedance measurement is not possible. Backup over current-time protection (BUOC) is automatically
activated. if set accordingly.
The relay has three independent stages of over current (IP>, IP>>, & IP>>>) element. Stage 1 (>) stage 2
(>>) can be programmed as IDMT or Definite Time. Directional or non directional.. It has C1 to C5
selectable IDMT curves as per IEC standard, C7- C11 as per IEEE/ANSI and C12-C13 RI /RXIDG curve.
The C6 is definite time.
Followings are different IDMT curves. Though it are mention under Over current element these formulas
are applicable to all elements which support IDMT characteristics
t = T*{[K/ ((I/Is)α -1)] + L} where
t = operation time
K = constant
I = Measured current
Is = Current threshold setting
α = Constant
L = ANSI/IEEE constant (zero for IEC curve)
T = Time multiplier setting or Time dial Setting
Curve Type Description Standard K α L C1 Standard Inverse_1 IEC 0.14 0.02 0 C2 Standard Inverse_2 IEC 0.06 0.02 0 C3 Very Inverse IEC 13.5 1 0 C4 Extremely inverse IEC 80 2 0 C5 Long Time Inverse IEC 120 1 0 C6 Define Time - - - 0 C7 Moderate Inverse IEEE 0.0515 0.02 0.114
I>
Internal Logic Signal
IP>
IP>>>
IA IB IC
DT/IDMT
DT
IP>>
DT/IDMT
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 11 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
C8 Very Inverse IEEE 19.61 2 0.491 C9 Extremely Inverse IEEE 28.2 2 0.1217 C10 Inverse IEEE 5.95 2 0.18 C11 Short Time Inverse IEEE 0.0239 0.02 0.0169 C12 RI - - - - C13 RXIDG - - - -
For RI /RXIDG Curve the time delay is calculated as :
Although the curves tend towards infinite when the current approaches Is (general threshold), the
minimum guaranteed value of the operating current for all the curves with the inverse time characteristic
is 1.1Is (with a tolerance of ± 0.05Is).
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 12 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
The characteristic show at for C1 curve. Similar can be plotted for other curves as per formula.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 13 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 14 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 15 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Stage 3 (>>>) can be programmed as high fault Define Time. Range, 50% to 3000% for phase the output
of stage 1 (IP>) is separate and not connected to trip contact. And for IP>,IP>> Setting is 10% to 250%.
The output of IP>, IP>>and IP>>> can be assigned to any of 10 programmable relay through key board
and are also connected to TRIP by default. Each stage can be independently set as +directional –
directional, non directional or off. In directional mode relay use other healthy phase to phase voltage for
polarization for example for phase A current relay use Phase BC voltage as polarization. The Directional
characteristic can be rotated by using angle MTA. Settable from 0 90 lead in steps of 5 deg. The
operating region is +/- 90 deg at both side of MTA line
Phase Section (Ip)
Phase (OC) Low set
: IP> Enable +DIR /-DIR/ NONDIR/OFF : IP> Settings 10% – 250% in steps of 1%. : IP> Time Multiplier (TMS) x 0.02 – x1.00 in steps of 0.01 : IP> Curve (Operating Time)
C1 – C13 ( IDMT curve C1 –C13 for Define Time C6 )
: IP> C6 Delay 0 – 1800.0 Sec in steps of 0.1Sec. : IP>> Enable +DIR /-DIR/ NONDIR/OFF : IP>> Settings 10% – 250% insteps of 1% : IP>> Time Multiplier (TMS) x 0.02 – x1.00 in step of 0.01 : IP>> Curve
C1 – C13 (IDMT curve C1–C13 for Define Time C6 )
Phase (OC) High set : IP>> C6 Delay 0 – 1800.0 Sec in steps of 0.1Sec. : IP>>> Enable +DIR /-DIR/ NONDIR/OFF : IP>>> Settings 50% – 3000% insteps of 10% : IP>>> C6 Delay 0.0 – 100.00 Sec in steps of 0.01Sec.
Torque Angle MTA 0 – 90 lead
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 16 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Earth Fault Element: The relay having 3 stages of 3Io (>, >>, & >>>). All major international IDMT curves are available. Stage
1 (>) stage 2 (>>) can be programmed as IDMT or Definite Time. It has C1 to C5 selectable IDMT curves
as per IEC standard, C7- C11 as per IEEE/ANSI and C12 RI & C13 RXIDG and C6 curve are used for DT
Time for >,>>stage and relay will trip as per curve selection. Stage 3 (>>>) can be programmed Define
Time and used for high fault only. Range for stage 1 and stage 2 3Io is 10% to 100% and for stage 3, 3Io
is 10% - 1200%. The Range for EF is from 10% to 100% for stage 1, stage 2 and 50% to 1200% for stage
3. The output of stage 1 (3Io >) is separate and not connected to trip contact. The output of >, >>and
P>>> can be assigned to any of 10 programmable relay through key board and are also connected to
TRIP by default. Each stage is can be made as +directional –directional, non directional or off
independently. During directional mode relay take 3Vo as polarization voltage. The directional
characteristic can be rotated by MTA setting stable fro 0 – 90 Lag. The directional characteristic is as
shown in fig.
Earth Fault Section (3Io) 3Io : 3Io> Enable +DIR /-DIR/ NONDIR/OFF
: 3Io> Settings 10% – 100% insteps of 1% : 3Io> Time Multiplier (TMS) x 0.02 – x1.00 in step of 0.01. : 3Io> Curve (Operating Time)
C1 – C13 ( IDMT curve C1–C13 for Define Time C6 )
: 3Io> C6 Delay 0 – 1800.0 Sec in steps of 0.1Sec.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 17 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
: 3Io>> Enable +DIR /-DIR/ NONDIR/OFF
: 3Io>> Settings 10% – 100% insteps of 1% : 3Io>> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01. : 3Io>> Curve (Operating Time)
C1 – C13 ( IDMT curve C1–C13 for Define Time C6 )
: 3Io>> C6 Delay 0 – 1800.0 Sec in steps of 0.1Sec. : 3Io>>> Enable +DIR /-DIR/ NONDIR/OFF : 3Io>>> Settings 50% – 1200% in steps of 10% : 3Io>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.
(C) Under Voltage Element:
The under voltage protection included within the ADR239A relays consists of two stages of
definite time under voltage.
Trip Logic Circuit of under voltage Element Any of the output elements from RL1 to RL10 can be assign to this function. The output can be
use for alarm or tripping of CB.
Under Voltage (V<, V<<) Under voltage (UV<, UV<<) : V< YES / NO
: Setting 10V – 60 V in steps of 0.1V : Operating Time 0 – 100 sec in step of 0.01
3Io
Internal Logic Signal
3Io >
3Io >>>
DT/IDMT
DT
3Io >>
DT/IDMT
V<
Internal Logic Signal V<
V<<
VA VB VC
DT
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 18 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Over voltage element (59): The over voltage protection included within the ADR239A relays consists of two stages of definite
time over voltage.
Trip Logic Circuit of Over voltage Element
Any of the output elements from RL1 to RL10 can be assign to this function. The output can be
use for alarm or tripping of CB.
Over voltage Section V>,V>> Over voltage V> : V> YES / NO
: Setting 50V – 120 V in steps of 0.1 : Operating Time 0 – 100 sec
(D) Auto Reclose Logic:
The ADR239A is provided with 4 shot auto recloser function. After the fault relay initiate the
auto recloser sequence. The auto recloser sequence can be block by using blocking logic.
Followings are condition during which Auto recloser sequence can block.
Relay is already in lock out condition
REC block input is active. This is an status input which can be used to block ARR by
external event.
Auto Recloser Section Setting Range : N SHOT 00 - 04
: Dead Time 1 DT1 0.1 – 180.0 sec in steps of 0.1sec
: Dead Time 2 DT2 0.1 – 180.0 sec in steps of 0.1sec
: Dead Time 3 DT3 0.1 – 180.0 sec in steps of 0.1sec
: Dead Time 4 DT4 0.1 – 180.0 sec in steps of 0.1sec
: Operating Time 10 – 300 sec in steps of 1sec
V>
Internal Logic Signal V>
V>>
VA VB VC
DT
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 19 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
(E) Trip circuit Supervision:-
The ADR239A is having 2 separate digital opto-coupler status input which can be used to
continuously monitor continuity of trip-circuit. The general scheme is shown in below fig.
Relay monitor Trip coil continuity through CB NO during close condition and through CBNC
during Trip condition. If any discontinuity observed it generate Alarm signal.
The output marked as PROTH (Protection healthy) is normally is ON and become OFF at
following condition
When DC supply is not sufficient (DC fail)
When T1 and T2 both active and both inactive.
i.e CB NO as will as CB NC are both close or open. Relay detects any internal hard- ware
Error.
Breaker Failure Detection:- The breaker failure function is used to quickly detect that a circuit-breaker has not opened (phase fault
currents still present) after a trip signal. This function is based on a "I<BF" current threshold setting 10% to
100% and on a "tBF" time-delay; these two settings can be configured by the user in General Settings
Menu. Normally after tripping, current should become Zero within 100 – 200ms time depending upon type
of fault and breaker mechanism. After Fault ADR239A trigger internal timer (settable from 100 ms to 1000
ms) if fault is not cleared during this time then relay declare as Breaker fail (LBB function) and change
another contacts. This contact is marked as Breaker Fail can be used to trip back up breaker or can be
used to generate ALARM signal.
I/O and Programmable AND Logic Eque. AND LOGIC EQUAT allows the operator to program four AND logic equations. Each equation can be the
logic AND link of signals from internal functions or from external binary input signals. In this submenu, the
operator sets the parameter cells of each of the 4 AND logic equations by assigning individual signals to
the individual AND logic equations. An operating timer stage and a reset timer stage are assigned to each
1
62
B+
B-
TC
CB NO
CB NC
1
62
To Relay CPU
To Relay CPU
TCCOM
T1
T2
1
62
B+
B-
TCCB NC
1
62
To Relay CPU
To Relay CPU1
62
B+
B-
TCCB NC
Trip Circuit Logic
1
62
To Relay CPU
To Relay CPU
TCCOM
1
62
B+
B-
TC
CB NO
CB NC
1
62
To Relay CPU
To Relay CPU
TCCOM
T1
T2
1
62
B+
B-
TCCB NC
1
62
To Relay CPU
To Relay CPU1
62
B+
B-
TCCB NC
Trip Circuit Logic
1
62
To Relay CPU
To Relay CPU
TCCOM
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 20 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
AND logic equation. These eight independent timer stages can be set in the submenu AND LOGIC
EQUAT T DELAY.
The operating timer stage Toperate is initiated only if all the associated data in the logic equation are in
logic state 1 (AND gate). It allows the logic equation validation to be delayed for a time period set in
Toperate. The reset timer stage Treset is initiated as soon as any of the data associated with the equation
disappears i.e. goes to logic state 0. It allows the logic equation to remain valid for a time period set in
Treset.
Programmable DI/DO and LED:- The ADR239A has 10 digital outputs, 2 status dedicated for CBNO (T2) & CBNC (T1) and 8 status
programmable opto-isolated input and 8 nos.of dual LEDs out of which 6 are programmable. These can
be programmed by local key board or through communication protocol. Any logical or physical status can
be assigned to any relay contact or any programmable LEDs. Many additional functions such as Ext
Reset, Thermal Reset, The disturbance record trigger, Trip, Blocking different protection etc. can be
configured to any of 8 Physical Status Inputs.
Monitoring Functions (Event, Disturbance Record):- Apart from basic protection functions relay is continuously monitors all numerical three phase distance
operation through status, its internal functions, internal hardware etc. If any change is observed, it is
marked as event. Such types of events are stored in internal non-volatile memory along with time stamp.
Following are some of the events. Relay PKP, Relay Reset, CB Trip, CB close, changed of any digital
status input, Change in Relay settings etc.
Up to 100 such events can be stored and can be downloaded for detail analysis. Apart from Event record,
relay also records actual waveform of current and voltage along with all digital and logical status during
fault condition. Up to 10 such waveforms can be recorded; the duration of disturbance record is 1 sec.
The disturbance record can be trigger from physical status input as well as from pick-up, trip operation of
relay. This waveform can be downloaded through communication port for further analysis.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 21 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
While Order ing Speci fy the fo l lowing Informat ion for ADR239A Relay
Ordering information:
A D R 2 3 9 A - A M - X X X - X X - X - X - X X - X
Example
ADR239A – AM – 201 – 01 – 03 – 01 – 06 – 00
Type: ADR239A St . Back termina l layout
Aux i l ia ry Supply: 18 – 250V AC/DC
CT sec: 1 Amp. / 5 Amp selectable
PT sec : 63.5V P-N
Three Phase Distance Protection Relay AM
201 For Adity-V2 series start from 201
01 Relay with standard Back Connection
D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s
A M X X X – X X – X – X – X X – X
Auxiliary Supply 01 = 18 – 52 V dc 04 = 30 V dc 02 = 77 – 250 V dc 05 = 48 V dc 03 = 24 V dc 06 = 18 – 250 V dc
Reserved for Future Use
PT Secondary 0 = NO PT 1 = 63.5 PT sec 2= 110 V
CT Secondary 1 = 1 Amp 2 = 5 Amp 3= 1Amp / 5Amp selectable
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 22 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5Amp or 1Amp site selectable
II. Aux. Supply : 77 - 250VDC or 18 – 250VDC to be specified
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. VA burden on PT : Less than 0.2 VA
VI. Operating Temp. range : -10 deg. To + 65 deg.
VII. Continuous carrying capacity
: 2 x of rated for CT and 1.5 x of rated for PT
VIII. Pick up : Within 1.1 times of set value.
IX. Reset Value : 95% to 90% of pick up.
X. Output Contact : 2 NO for Trip : 1 NO + 1 NC for Protection Healthy : 8 NO General Programmable
XI. Contact Rating : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make & carry for 3 sec : 15A
XII. Opto Isolated input status : 1 for CB NO & 1 for CB NC : 8 are general programmable
XIII. Thermal With stand for CT
: 20 x of rated for 3.0 sec.
Operational Indicators (Flags)
XIV. PROT.H /ERR : Green LED indicates Relay OK (Protection Healthy) : Red LED indicates Fault in following conditions. 1. Problem in relay Hardware. 2. Trip Circuit Fault
L2/L3/L4/L5/L6/L7/L8 : Programmable dual LED
Drawing References
XV. Drawing References
: For Block Diagram - ADV03101
: For Back Connections - ADV03201
: For Cabinet Type - MAC01301
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 23 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
The Relay Confirm to following standards. Sr. No. Title Standard no. Electromagnetic Compatibility Type Test:
1. High Frequency test : IEC 60255-22-1, class – III : Frequency : 1MHz Damped Oscillatory : Longitudinal :5 KV (peak) : Duration: sec duration 2 sec. : Between input current Terminal
2. Electrostatic discharge Direct application
: IEC 60255-22-2 Class III and IEC 61000-4-2 class III. : Contact discharge: 6kV, : Air discharge: 8KV : Polarity: both +ve and –Ve polarities.
3. Indirect application : IEC-61000-4-2, Class-III
4. Fast transient disturbance
: IEC 60255-22-4 and IEC 61000-4-4, class A : 1.2KV; 5/50ns; 5KHz burst duration = 15ms. : Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
5. Surge immunity test
: IEC 60255-22-5 / IEC 61000-4-6 class 4 : Differential Mode = 2kV : Common Mode = 4kV : 1.2/50uS , 5 surges of each polarity
6. Power frequency immunity test : IEC-60255-22-7, Class-A
7. Power frequency magnetic field test
: IEC-61000-4-8, Class-V
8. Radiated electromagnetic field disturbance
: IEC- 60255-22-3 : EN-61000-4-3 : Frequency 80MHz – 1GHz
9. Conducted Disturbance induced by Radio Frequency field
: IEC 60255-22-6 / IEC 61000-4-6: 1996. : Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM @ 1 KHz
10. AC Ripple in DC supply Test
: IEC 60255-11
11. Radiated emission : IEC- 60255-25 Insulation Tests:
12. High Voltage Test
: IEC 60255-5. class – III : At 2.5kV 50Hz between all terminal connected together and earth for 1 minutes
13. Impulse Voltage Test
: IEC60255-5. class – III : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and – Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec.
Ref.: ADR239A_V2Issue: 04 15.05.2012
Page 24 / 24
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR239A( ADITY A–V2 Ser ies )
(Pre l iminary) ASHIDA Numerical 3 Phase Distance Relay
‚þ¹ªþ¸þ
Environmental tests:
14. Cold test Storage test : IEC-60068-2-1 15. Dry heat test : IEC-60068-2-2
16. Damp heat test, steadystate : IEC-60068-2-3
17. Damp heat test, cyclic : IEC-60068-2-30 CE compliance
18. Immunity : IEC-60255-26 19. Emissive Test : IEC- 60255-26 20. Low voltage directive : EN-50178
Mechanical tests
21. Vibration
: IEC 60255-21-1 class 1 : Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8
m/s2) : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
22. Bump Test : IEC 60255-21-2 Class-1 : 1000 bumps of 10gn peak acceleration and 16ms pulse
duration in each of the two opposite direction per axis as per IEC60255-21-2 class 1 No. of axes . 3.
23. Shock Withstand : IEC 60255-21-2 Clas-1 : 3 shocks of 15gn peak acceleration and 11ms pulse in each of
two opposite direction . No. of axis : 3 24. Seismic Test : IEC 60255-21-3
: In single axis sine sweep in X-axis - sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn (whichever is less)
: In single axis sine sweep in Y-axis - sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn (whichever is less)
Revision Note:
Revision No. Date Description
01 18.10.2010 Original specifications 02 16.07.2010 ARR function added 03 02.11.2010 Format revised. IDMT graphs added 04 15.05.2012 Load Encroachment Features added.