Application Application Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal units Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing Suitable for different control tasks depending on how the input for the setpoint value signal is used The output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpoint Override control by means of switches or relays Volume flow rate actual value is available as linear voltage signal Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow is passed through the transducer in order to measure the volume flow rate, please note: With heavy dust levels in the room, suitable extract air filters must be provided. If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used Application Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal units Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing Suitable for different control tasks depending on how the input for the setpoint value signal is used The output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpoint Override control by means of switches or relays Volume flow rate actual value is available as linear voltage signal Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow is passed through the transducer in order to measure the volume flow rate, please note: With heavy dust levels in the room, suitable extract air filters must be provided. If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used Description Construction LMV-D3AL-F for LVC 227V-024T-05-013 for LVC LMV-D3A-F for TVR 227V-024T-05-002 für TVR 227V-024T-15-002 for TVJ, TVT SMV-D3A for TVT LMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA Operating modes ELECTRONIC VOLUME FLOW CONTROLLERS OF TYPE EASY TYPE EASY QUICK AND EASY HANDLING Control components for VAV terminal units, to be mounted on the terminal unit for easy operation Simplified ordering and on-site assignment to rooms as selection is based on the nominal size of the duct Rapid volume flow rate setting without additional device Indicator light simplifies functional checking Proven technology of the Compact volume flow controllers Suitable for constant and variable volume flows as well as for V / V switching min max Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy

TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Application

Application

Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal unitsDynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casingSuitable for different control tasks depending on how the input for the setpoint value signal is usedThe output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpointOverride control by means of switches or relaysVolume flow rate actual value is available as linear voltage signal

Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow ispassed through the transducer in order to measure the volume flow rate, please note:

With heavy dust levels in the room, suitable extract air filters must be provided.If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used

Application

Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal unitsDynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casingSuitable for different control tasks depending on how the input for the setpoint value signal is usedThe output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpointOverride control by means of switches or relaysVolume flow rate actual value is available as linear voltage signal

Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow ispassed through the transducer in order to measure the volume flow rate, please note:

With heavy dust levels in the room, suitable extract air filters must be provided.If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used

Description

Construction

LMV-D3AL-F for LVC227V-024T-05-013 for LVCLMV-D3A-F for TVR227V-024T-05-002 für TVR227V-024T-15-002 for TVJ, TVTSMV-D3A for TVTLMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA

Operating modes

ELECTRONIC VOLUMEFLOW CONTROLLERS OFTYPE EASY

TYPE EASY

QUICK AND EASY HANDLING

Control components for VAV terminal units, to be mounted on the terminal unit foreasy operation

Simplified ordering and on-site assignment to rooms as selection is basedon the nominal size of the ductRapid volume flow rate setting without additional deviceIndicator light simplifies functional checkingProven technology of the Compact volume flow controllersSuitable for constant and variable volume flows as well as forV / V switchingmin max

Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy

Page 2: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Variable volume flow

V : minimum volume flow rateV : maximum volume flow rate

Constant value

V : constant volume flow rateV : 100 %

Signal voltage range

0 – 10 V DC

Parts and characteristics

Sensor for dynamic differential pressure measurementsMechanical stops for limiting the damper blade positionsActuators with overload protectionRelease button to allow for manual operation

Construction

LMV-D3AL-F for LVC227V-024T-05-013 for LVCLMV-D3A-F for TVR227V-024T-05-002 für TVR227V-024T-15-002 for TVJ, TVTSMV-D3A for TVTLMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA

Operating modes

Variable volume flow

V : minimum volume flow rateV : maximum volume flow rate

Constant value

V : constant volume flow rateV : 100 %

Signal voltage range

0 – 10 V DC

Parts and characteristics

Sensor for dynamic differential pressure measurementsMechanical stops for limiting the damper blade positionsActuators with overload protectionRelease button to allow for manual operation

TECHNICAL INFORMATION

min

max

min

max

min

max

min

max

Function, Technical data, Order code

Functional description

VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – control.

Page 3: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with adifferential pressure sensor.

The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available asa voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ).

The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switchcontacts. Variable volume flow control results in a value between V and V . It is possible to override the room temperature control, e.g. by a completeshut-off of the duct.

The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.

The volume flow rate parameters V and V can be set on potentiometers.

Volume flow control

The volume flow controller works independent of the duct pressureDifferential pressure fluctuations do not result in permanent volume flow rate changesTo prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move.The factory set volume flow rate parameters can be altered by the customer

Functional description

VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – control.

The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with adifferential pressure sensor.

The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available asa voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ).

The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switchcontacts. Variable volume flow control results in a value between V and V . It is possible to override the room temperature control, e.g. by a completeshut-off of the duct.

The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.

The volume flow rate parameters V and V can be set on potentiometers.

Volume flow control

The volume flow controller works independent of the duct pressureDifferential pressure fluctuations do not result in permanent volume flow rate changesTo prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move.The factory set volume flow rate parameters can be altered by the customer

Principe de fonctionnement – Régulateurs Easy et Compact

① Differential pressure transducer② Actuator③ Volume flow controller④ Setpoint value signal

nom

min max

min max

nom

min max

min max

Page 4: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Régulateur Easy

① Easy controller② qᵥmaxPotentiometer ③ qᵥminPotentiometer④ Indicator light⑤ Service button⑥ Connections for effective pressure sensor⑦ Protective cover⑧ Shaft clamp

Easy controller LMV-D3AL-F

Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC) 24 V DC −10/+20 %

Power rating (AC) 3.5 VA max.

Power rating (DC) 2 W max.

Running time for 90° 120 – 150 s

Setpoint value signal input 0 – 10 V DC, R > 100 kΩ

Actual value signal output 0 – 10 V DC, 0.5 mA max.

IEC protection class III (protective extra-low voltage)

Protection level IP 20

EC conformity EMC to 2014/30/EU, low voltage to 2014/35/EU

Easy controller 227V-024T-05-013

a

Page 5: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC) 24 V DC ± 20 %

Power rating (AC) 5 VA max.

Power rating (DC) 3 W max.

Running time for 90° 100 s

Setpoint value signal input 0 – 10 V DC, R > 100 kΩ

Actual value signal output 0 – 10 V DC, 0.5 mA max.

IEC protection class III (protective extra-low voltage)

Protection level IP 20

EC conformity EMC according to 2014/30/EU

Easy controllers LMV-D3A and LMV-D3A-F

Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC) 24 V DC −10/+20 %

Power rating (AC) 5 VA max.

Power rating (DC) 2.5 W max.

Running time for 90° 110 – 150 s

Setpoint value signal input 0 – 10 V DC, R > 100 kΩ

Actual value signal output 0 – 10 V DC, 0.5 mA max.

IEC protection class III (protective extra-low voltage)

Protection level IP 20

EC conformity EMC according to 2014/30/EU

Easy controller 227V-024T-05-002

Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC) 24 V DC ± 20 %

Power rating (AC) 5 VA max.

Power rating (DC) 3 W max.

Running time for 90° 100 s

Setpoint value signal input 0 – 10 V DC, R > 100 kΩ

Actual value signal output 0 – 10 V DC, 0.5 mA max.

IEC protection class III (protective extra-low voltage)

Protection level IP 20

EC conformity EMC according to 2014/30/EU

a

a

a

Page 6: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Variants, Product details

Easyregler 227V-024T-15-002

Versorgungsspannung (Wechselspannung) 24 V AC ± 20 %, 50/60 Hz

Versorgungsspannung (Gleichspannung) 24 V DC ± 20 %

Anschlussleistung (Wechselspannung) Max. 5 VA

Anschlussleistung (Gleichspannung) Max. 3 W

Laufzeit für 90° 150 – 270 s

Eingang Sollwertsignal 0 – 10 V DC, R > 100 kΩ

Ausgang Istwertsignal 0 – 10 V DC, max. 0,5 mA

Schutzklasse III (Schutzkleinspannung)

Schutzgrad IP 20

EG-Konformität EMV nach 2014/30/EU

Easy controller SMV-D3A

Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC) 24 V DC −10/+20 %

Power rating (AC) 6 VA max.

Power rating (DC) 3 W max.

Running time for 90° 110 – 150 s

Setpoint value signal input 0 – 10 V DC, R > 100 kΩ

Actual value signal output 0 – 10 V DC, 0.5 mA max.

IEC protection class III (protective extra-low voltage)

Protection level IP 20

EC conformity EMC according to 2014/30/EU

a

a

Page 7: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Part number Type Type of VAV terminal unit

M466EU1 LMV-D3AL-F LVC

M466EU2 227V-024T-05-013 LVC

M466ES1 LMV-D3A-F TVR

M466DC3 227V-024T-05-002 TVR

A00000053055 227V-024T-15-002 TVJ, TVT

M466ES3 SMV-D3A TVT

M466ES2 LMV-D3A TZ-Silenzio, TA-Silenzio, TVZ, TVA

Easy controller LMV-D3AL-F

Easy controller 227V-024T-05-013

Easy controller LMV-D3A

Page 8: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Easy controller 227V-024T-05-002

Easy controller 227V-024T-15-002

Easy controller SMV-D3A

Page 9: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

The Easy principle

The Easy principle

Select nominal size

Set flow rates

Green light: Ready!

Page 10: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Electrical connection, Commissioning, Characteristics

Répartition du bornier

1 ⊥, –: Ground 2 ~, +: Supply voltage 24 V 3 w: Setpoint value signal 0 – 10 V DC 4 U: Actual value signal 0 – 10 V DC

Commissioning

Use the potentiometer to set the minimum or maximum volume flow rate on siteTake the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit)Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rateVolume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: 10 – 100%Volume flow rate range of TVJ and TVT: 20 – 100%Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operationRemove the transparent cover of the Easy controller only temporarily for wiring and commissioning

Commissioning

Use the potentiometer to set the minimum or maximum volume flow rate on siteTake the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit)Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rateVolume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: 10 – 100%Volume flow rate range of TVJ and TVT: 20 – 100%Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operationRemove the transparent cover of the Easy controller only temporarily for wiring and commissioning

Échelle de réglage de débit pour TVR-Easy

Chaque unité terminale VAV porte un autocollant avec une échelle de réglage de débit afin de déterminer les paramétrages sur site (voir exemple : TVR-Easy, grandeur nominale 200). Les pourcentages se rapportent à la plage de réglage qui peut être utilisé.

Régulation à débit variable

Page 11: TYPE EASY - TROX · Easy controller SMV-D3A Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC −10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W

Les débits requis doivent être réglés sur site. Si V est réglé plus haut que V , V est fourni en tant que débit constant, même en cas d'émission d'unsignal de consigne.

Si V est réglé sur 0 %, le débit en résultant se situera entre la coupure et Vmax. Si le signal de consigne chute en dessous de 0,5 V DC, le clapet deréglage se ferme (coupure).

Régulation à débit constant

Le débit constant est défini avec le potentiomètre V . Dans ce cas, le réglage du potentiomètre V est sans importance.

Variable de pilotage en provenance du système centralisé de gestion du bâtiment (GTB-GTC)

Pour que le système centralisé de gestion du bâtiment pilote le débit, il faut régler le potentiomètre V sur 0 % et le potentiomètre V sur 100 %. Si lesignal de consigne chute en dessous de 0,5 V DC, le clapet de réglage se ferme (coupure). Étant donné que le signal de consigne peut ou ne peut pasêtre inférieure à 0,1 V DC, une régulation prioritaire est recommandée pour la fermeture.

Réglage usine

min max min

min

min max

min max

Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy