Application
Application
Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal unitsDynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casingSuitable for different control tasks depending on how the input for the setpoint value signal is usedThe output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpointOverride control by means of switches or relaysVolume flow rate actual value is available as linear voltage signal
Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow ispassed through the transducer in order to measure the volume flow rate, please note:
With heavy dust levels in the room, suitable extract air filters must be provided.If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used
Application
Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal unitsDynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casingSuitable for different control tasks depending on how the input for the setpoint value signal is usedThe output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpointOverride control by means of switches or relaysVolume flow rate actual value is available as linear voltage signal
Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow ispassed through the transducer in order to measure the volume flow rate, please note:
With heavy dust levels in the room, suitable extract air filters must be provided.If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used
Description
Construction
LMV-D3AL-F for LVC227V-024T-05-013 for LVCLMV-D3A-F for TVR227V-024T-05-002 für TVR227V-024T-15-002 for TVJ, TVTSMV-D3A for TVTLMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA
Operating modes
ELECTRONIC VOLUMEFLOW CONTROLLERS OFTYPE EASY
TYPE EASY
QUICK AND EASY HANDLING
Control components for VAV terminal units, to be mounted on the terminal unit foreasy operation
Simplified ordering and on-site assignment to rooms as selection is basedon the nominal size of the ductRapid volume flow rate setting without additional deviceIndicator light simplifies functional checkingProven technology of the Compact volume flow controllersSuitable for constant and variable volume flows as well as forV / V switchingmin max
Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy
Variable volume flow
V : minimum volume flow rateV : maximum volume flow rate
Constant value
V : constant volume flow rateV : 100 %
Signal voltage range
0 – 10 V DC
Parts and characteristics
Sensor for dynamic differential pressure measurementsMechanical stops for limiting the damper blade positionsActuators with overload protectionRelease button to allow for manual operation
Construction
LMV-D3AL-F for LVC227V-024T-05-013 for LVCLMV-D3A-F for TVR227V-024T-05-002 für TVR227V-024T-15-002 for TVJ, TVTSMV-D3A for TVTLMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA
Operating modes
Variable volume flow
V : minimum volume flow rateV : maximum volume flow rate
Constant value
V : constant volume flow rateV : 100 %
Signal voltage range
0 – 10 V DC
Parts and characteristics
Sensor for dynamic differential pressure measurementsMechanical stops for limiting the damper blade positionsActuators with overload protectionRelease button to allow for manual operation
TECHNICAL INFORMATION
min
max
min
max
min
max
min
max
Function, Technical data, Order code
Functional description
VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – control.
The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with adifferential pressure sensor.
The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available asa voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switchcontacts. Variable volume flow control results in a value between V and V . It is possible to override the room temperature control, e.g. by a completeshut-off of the duct.
The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.
The volume flow rate parameters V and V can be set on potentiometers.
Volume flow control
The volume flow controller works independent of the duct pressureDifferential pressure fluctuations do not result in permanent volume flow rate changesTo prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move.The factory set volume flow rate parameters can be altered by the customer
Functional description
VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – control.
The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with adifferential pressure sensor.
The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available asa voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switchcontacts. Variable volume flow control results in a value between V and V . It is possible to override the room temperature control, e.g. by a completeshut-off of the duct.
The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.
The volume flow rate parameters V and V can be set on potentiometers.
Volume flow control
The volume flow controller works independent of the duct pressureDifferential pressure fluctuations do not result in permanent volume flow rate changesTo prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move.The factory set volume flow rate parameters can be altered by the customer
Principe de fonctionnement – Régulateurs Easy et Compact
① Differential pressure transducer② Actuator③ Volume flow controller④ Setpoint value signal
nom
min max
min max
nom
min max
min max
Régulateur Easy
① Easy controller② qᵥmaxPotentiometer ③ qᵥminPotentiometer④ Indicator light⑤ Service button⑥ Connections for effective pressure sensor⑦ Protective cover⑧ Shaft clamp
Easy controller LMV-D3AL-F
Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC −10/+20 %
Power rating (AC) 3.5 VA max.
Power rating (DC) 2 W max.
Running time for 90° 120 – 150 s
Setpoint value signal input 0 – 10 V DC, R > 100 kΩ
Actual value signal output 0 – 10 V DC, 0.5 mA max.
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC to 2014/30/EU, low voltage to 2014/35/EU
Easy controller 227V-024T-05-013
a
Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC ± 20 %
Power rating (AC) 5 VA max.
Power rating (DC) 3 W max.
Running time for 90° 100 s
Setpoint value signal input 0 – 10 V DC, R > 100 kΩ
Actual value signal output 0 – 10 V DC, 0.5 mA max.
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC according to 2014/30/EU
Easy controllers LMV-D3A and LMV-D3A-F
Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC −10/+20 %
Power rating (AC) 5 VA max.
Power rating (DC) 2.5 W max.
Running time for 90° 110 – 150 s
Setpoint value signal input 0 – 10 V DC, R > 100 kΩ
Actual value signal output 0 – 10 V DC, 0.5 mA max.
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC according to 2014/30/EU
Easy controller 227V-024T-05-002
Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC ± 20 %
Power rating (AC) 5 VA max.
Power rating (DC) 3 W max.
Running time for 90° 100 s
Setpoint value signal input 0 – 10 V DC, R > 100 kΩ
Actual value signal output 0 – 10 V DC, 0.5 mA max.
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC according to 2014/30/EU
a
a
a
Variants, Product details
Easyregler 227V-024T-15-002
Versorgungsspannung (Wechselspannung) 24 V AC ± 20 %, 50/60 Hz
Versorgungsspannung (Gleichspannung) 24 V DC ± 20 %
Anschlussleistung (Wechselspannung) Max. 5 VA
Anschlussleistung (Gleichspannung) Max. 3 W
Laufzeit für 90° 150 – 270 s
Eingang Sollwertsignal 0 – 10 V DC, R > 100 kΩ
Ausgang Istwertsignal 0 – 10 V DC, max. 0,5 mA
Schutzklasse III (Schutzkleinspannung)
Schutzgrad IP 20
EG-Konformität EMV nach 2014/30/EU
Easy controller SMV-D3A
Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC −10/+20 %
Power rating (AC) 6 VA max.
Power rating (DC) 3 W max.
Running time for 90° 110 – 150 s
Setpoint value signal input 0 – 10 V DC, R > 100 kΩ
Actual value signal output 0 – 10 V DC, 0.5 mA max.
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC according to 2014/30/EU
a
a
Part number Type Type of VAV terminal unit
M466EU1 LMV-D3AL-F LVC
M466EU2 227V-024T-05-013 LVC
M466ES1 LMV-D3A-F TVR
M466DC3 227V-024T-05-002 TVR
A00000053055 227V-024T-15-002 TVJ, TVT
M466ES3 SMV-D3A TVT
M466ES2 LMV-D3A TZ-Silenzio, TA-Silenzio, TVZ, TVA
Easy controller LMV-D3AL-F
Easy controller 227V-024T-05-013
Easy controller LMV-D3A
Easy controller 227V-024T-05-002
Easy controller 227V-024T-15-002
Easy controller SMV-D3A
The Easy principle
The Easy principle
Select nominal size
Set flow rates
Green light: Ready!
Electrical connection, Commissioning, Characteristics
Répartition du bornier
1 ⊥, –: Ground 2 ~, +: Supply voltage 24 V 3 w: Setpoint value signal 0 – 10 V DC 4 U: Actual value signal 0 – 10 V DC
Commissioning
Use the potentiometer to set the minimum or maximum volume flow rate on siteTake the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit)Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rateVolume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: 10 – 100%Volume flow rate range of TVJ and TVT: 20 – 100%Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operationRemove the transparent cover of the Easy controller only temporarily for wiring and commissioning
Commissioning
Use the potentiometer to set the minimum or maximum volume flow rate on siteTake the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit)Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rateVolume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: 10 – 100%Volume flow rate range of TVJ and TVT: 20 – 100%Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operationRemove the transparent cover of the Easy controller only temporarily for wiring and commissioning
Échelle de réglage de débit pour TVR-Easy
Chaque unité terminale VAV porte un autocollant avec une échelle de réglage de débit afin de déterminer les paramétrages sur site (voir exemple : TVR-Easy, grandeur nominale 200). Les pourcentages se rapportent à la plage de réglage qui peut être utilisé.
Régulation à débit variable
Les débits requis doivent être réglés sur site. Si V est réglé plus haut que V , V est fourni en tant que débit constant, même en cas d'émission d'unsignal de consigne.
Si V est réglé sur 0 %, le débit en résultant se situera entre la coupure et Vmax. Si le signal de consigne chute en dessous de 0,5 V DC, le clapet deréglage se ferme (coupure).
Régulation à débit constant
Le débit constant est défini avec le potentiomètre V . Dans ce cas, le réglage du potentiomètre V est sans importance.
Variable de pilotage en provenance du système centralisé de gestion du bâtiment (GTB-GTC)
Pour que le système centralisé de gestion du bâtiment pilote le débit, il faut régler le potentiomètre V sur 0 % et le potentiomètre V sur 100 %. Si lesignal de consigne chute en dessous de 0,5 V DC, le clapet de réglage se ferme (coupure). Étant donné que le signal de consigne peut ou ne peut pasêtre inférieure à 0,1 V DC, une régulation prioritaire est recommandée pour la fermeture.
Réglage usine
min max min
min
min max
min max
Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy
À la livraison, les unités possèdent des réglages V = 40 % et V = 80 %.min max
Characteristic of the setpoint value signal
Homepage > Prodotti > Unità di regolazione > VARYCONTROL > Componenti di regolazione > Type Easy