49 Complementary technical information Type 2 coordination (IEC 60947-4-1) 220/240 V DB505 Circuit breakers, contactors and thermal relays Performance: U = 220/240 V Circuit breakers B F N H S L NSX00/60/50-MA 40 kA 85 kA 90 kA 00 kA 0 kA 50 kA NSX400/60 Micrologic .M 40 kA 85 kA 90 kA 00 kA 0 kA 50 kA NS800L/NS000L Micrologic 5.0 - - - - - 50 kA Starting (2) : normal LRD class 0 A, LR9 class 0 Motors Circuit breakers Contactors (1) Thermal relays P (kW) I (A) 220 V I (A) 240 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (A) (2) 0.8 . . .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.6 0.5 .5 .4 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5 0.7 .8 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5 0.55 .8 .6 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4 0.75 .5 . 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4 . 5 4.5 6 NSX00-MA 6. 8 LC-D LRD-0 4/6 .5 6.5 6 8 NSX00-MA .5 LC-D40 LRD- 5.5/8 . 9 8 0 NSX00-MA .5 8 LC-D40 LRD- 4 7/0 .5 NSX00-MA .5 6 LC-D40 LRD- 6 9/ 4 5 4 8 NSX00MA 5 50 LC-D40 LRD- /8 5.5 9 5 NSX00-MA 5 5 LC-D40 LRD- 7/5 6. 4 5 NSX00-MA 5 5 LC-D40 LRD- 7/5 7.5 8 5 NSX00-MA 50 450 LC-D80 LRD- 5 / 0 6 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 9 6 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 5 5 48 6 NSX00-MA 00 700 LC-D80 LRD- 59 48/65 8.5 6 59 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/65 75 70 80 NSX00-MA 00 00 LC-D80 LRD- 6 6/80 0 00 95 00 NSX00-MA 00 00 LC-D5 LRD-5 67 60/00 LC-F5 LR9-F5 67 7 5 5 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50 LC-F50 LR9-F5 69 45 50 40 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50 LC-F50 LR9-F5 69 55 80 70 85 NSX50-MA 0 40 LC-F85 LR9-F5 7 /0 0 NSX400-MA 0 880 LC-F65 75 50 5 65 NSX400-MA 0 500 LC-F65 LR9-F7 75 00/0 90 00 70 0 NSX400-MA 0 460 LC-F0 LR9-F7 75 00/0 0 60 0 400 NSX60-MA 500 5700 LC-F400 LR9-F7 79 00/500 40 400 500 NSX60-MA 500 6500 LC-F500 LR9-F7 79 00/500 50 460 450 500 NSX60-MA 500 6500 LC-F500 LR9-F7 79 00/500 60 50 480 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60 Micrologic 5.0- LR off 00 60 580 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60 Micrologic 5.0-LR off 0 700 640 700 NS800L 800 9600 LC-F780 TC800/5 + LRD-0 60/000 Micrologic 5.0-LR off 50 800 70 800 NS000L 000 0000 LC-F780 TC800/5 + LRD-0 60/000 Micrologic 5.0-LR off (1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3. (2) For long starting (class 20), see the correspondence table for thermal relay. Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

Type2 -(IEC 60947-4-1)

  • Upload
    011253

  • View
    208

  • Download
    35

Embed Size (px)

DESCRIPTION

Type 2 coordination (IEC 60947-4-1)

Citation preview

  • 49

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 220/240 V

    DB

    5

    05 Circuit breakers, contactors and thermal relaysPerformance: U = 220/240 VCircuit breakers B F N H S L

    NSX00/60/50-MA 40 kA 85 kA 90 kA 00 kA 0 kA 50 kANSX400/60 Micrologic .M 40 kA 85 kA 90 kA 00 kA 0 kA 50 kANS800L/NS000L Micrologic 5.0 - - - - - 50 kAStarting (2): normal LRD class 0 A, LR9 class 0

    Motors Circuit breakers Contactors (1)

    Thermal relays

    P (kW) I (A) 220 V I (A) 240 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (A) (2)0.8 . . .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.60.5 .5 .4 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.50.7 .8 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.50.55 .8 .6 4 NSX00-MA 6. 57 LC-D LRD-08 .5/40.75 .5 . 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4. 5 4.5 6 NSX00-MA 6. 8 LC-D LRD-0 4/6.5 6.5 6 8 NSX00-MA .5 LC-D40 LRD- 5.5/8. 9 8 0 NSX00-MA .5 8 LC-D40 LRD- 4 7/0 .5 NSX00-MA .5 6 LC-D40 LRD- 6 9/4 5 4 8 NSX00MA 5 50 LC-D40 LRD- /85.5 9 5 NSX00-MA 5 5 LC-D40 LRD- 7/56. 4 5 NSX00-MA 5 5 LC-D40 LRD- 7/57.5 8 5 NSX00-MA 50 450 LC-D80 LRD- 5 /0 6 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 9 6 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/405 5 48 6 NSX00-MA 00 700 LC-D80 LRD- 59 48/658.5 6 59 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/65 75 70 80 NSX00-MA 00 00 LC-D80 LRD- 6 6/800 00 95 00 NSX00-MA 00 00 LC-D5 LRD-5 67 60/00

    LC-F5 LR9-F5 677 5 5 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6945 50 40 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6955 80 70 85 NSX50-MA 0 40 LC-F85 LR9-F5 7 /0

    0 NSX400-MA 0 880 LC-F6575 50 5 65 NSX400-MA 0 500 LC-F65 LR9-F7 75 00/090 00 70 0 NSX400-MA 0 460 LC-F0 LR9-F7 75 00/00 60 0 400 NSX60-MA 500 5700 LC-F400 LR9-F7 79 00/500 40 400 500 NSX60-MA 500 6500 LC-F500 LR9-F7 79 00/50050 460 450 500 NSX60-MA 500 6500 LC-F500 LR9-F7 79 00/50060 50 480 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60

    Micrologic 5.0- LR off00 60 580 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60

    Micrologic 5.0-LR off0 700 640 700 NS800L 800 9600 LC-F780 TC800/5 + LRD-0 60/000

    Micrologic 5.0-LR off50 800 70 800 NS000L 000 0000 LC-F780 TC800/5 + LRD-0 60/000

    Micrologic 5.0-LR off(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(2) For long starting (class 20), see the correspondence table for thermal relay.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 149 04/11/2009 16:00:04

  • 50

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 380/415 V

    DB

    5

    04

    Motors Circuit breakers Contactors (1)P (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Trip unit/t.u. Irth(A) Irm(A) (2) Type

    7.5 6 4 0 NSX00 Micrologic . or 6. /5 Irth LC-D800 9 5 NSX00 Micrologic . or 6. /5 Irth LC-D80 5 NSX00 Micrologic . or 6. /5 Irth LC-D805 0 8 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D808.5 7 5 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D80 44 40 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D800 60 55 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D807 7 66 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D8045 85 80 00 NSX00 Micrologic . or 6. 50/00 Irth LC-D5 or LC-F555 05 00 5 NSX60 Micrologic . or 6. 70/50 Irth LC-D5 or LC-F575 8 5 50 NSX60 Micrologic . or 6. 70/50 Irth LC-D50 or LC-F5090 70 65 85 NSX50 Micrologic . or 6. 00/0 Irth LC-F85

    5 NSX400 Micrologic . or 6. 60/0 Irth LC-F50 05 00 0 NSX50 Micrologic . or 6. 00/0 Irth LC-F5

    NSX400 Micrologic . or 6. 60/0 Irth LC-F5 50 40 65 NSX400 Micrologic . or 6. 60/0 Irth LC-F6560 00 80 0 NSX400 Micrologic . or 6. 60/0 Irth LC-F000 70 40 400 NSX60 Micrologic . or 6. 50/500 Irth LC-F4000 408 85 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F50050 460 45 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F500

    60 NS800L Micrologic 5.0 0/800 8000 LC-F6000 565 500 60 NS800L Micrologic 5.0 0/800 8000 LC-F605 60 560 60 NS800L Micrologic 5.0 0/800 8000 LC-F6075 670 60 70 NS800L Micrologic 5.0 0/800 9600 LC-F780400 70 660 70 NS800L Micrologic 5.0 0/800 9600 LC-F780450 800 750 800 NS000L Micrologic 5.0 400/000 0000 LC-F780(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(2) Ii for Micrologic 5.0 control unit.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Circuit breakers, contactorsPerformance: U = 380/415 VCircuit breakers B F N H S L

    NS00/60/50 Micrologic .M/6.M 5 kA 6 kA 50 kA 70 kA 00 kA 0 kANSX400/60 Micrologic .M/6.M 5 kA 6 kA 50 kA 70 kA 00 kA 0 kANS800L/NS000L Micrologic 5.0 - - - - - 0 kA

    Starting Norme IEC 60947-4-1Micrologic .M/.M 6.M/6.M 5.0Normal (class) 5, 0 5, 0 0Long (class) 0 0, 0 0

    Livre 1.indb 150 04/11/2009 16:00:05

  • 5

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 380/415 V

    DB

    5

    05 Circuit breakers, contactors and thermal relaysPerformance: U = 380/415 VCircuit breakers N H L

    NS80-MA - 70 kA -Starting (2): normal LRD class 0 A

    Motors Circuit breakers Contactors (1) Thermal relaysP (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (2)

    0.8 0.7 0.6 NS80H-MA .5 .5 LC-D09 LRD-05 0.6/0.5 0.9 0.8 NS80H-MA .5 .5 LC-D09 LRD-05 0.6/0.7 . . .6 NS80H-MA .5 .5 LC-D09 LRD-06 /.60.55 .6 .5 .5 NS80H-MA .5 .5 LC-D09 LRD-07 .6/.50.75 .8 .5 NS80H-MA .5 .5 LC-D09 LRD-07 .6/.5. .8 .6 4 NS80H-MA 6. 57 LC-D LRD-08 .5/4.5 .7 .4 4 NS80H-MA 6. 57 LC-D LRD-08 .5/4. 5. 4.8 6 NS80H-MA 6. 8 LC-D LRD-0 4/6 7 6.5 8 NS80H-MA .5 LC-D40 LRD- 5.5/84 9 8. 0 NS80H-MA .5 8 LC-D40 LRD- 4 7/05.5 .5 NS80H-MA .5 6 LC-D40 LRD- 6 9/7.5 6 4 6 NS80H-MA 5 50 LC-D40 LRD- /80 9 5 NS80H-MA 5 5 LC-D40 LRD- 7/5 5 NS80H-MA 5 5 LC-D40 LRD- 7/55 0 8 NS80H-MA 50 450 LC-D40 LRD- 5 /8.5 7 4 40 NS80H-MA 50 550 LC-D50 LRD- 55 0/40 4 40 50 NS80H-MA 50 650 LC-D50 LRD- 57 7/500 59 55 6 NS80H-MA 80 880 LC-D65 LRD- 59 48/657 7 66 80 NS80H-MA 80 040 LC-D80 LRD- 6 6/80(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(2) For long starting (class 20), see the correspondence table for thermal relay.

    Livre 1.indb 151 04/11/2009 16:00:05

  • 5

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 380/415 V

    DB

    5

    06 Circuit breakers, contactors and thermal relaysPerformance: U = 380/415 VCircuit breakers B F N H S L

    NSX00/60/50-MA 5 kA 6 kA 50 kA 70 kA 00 kA 0 kANSX400/60 Micrologic .M 5 kA 6 kA 50 kA 70 kA 00 kA 0 kANS800L/NS000L Micrologic 5.0 - - - - - 0 kAStarting (2): normal LRD class 0 A, other classes 0

    Motors Circuit breakers Contactors (1) Thermal relaysP (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Rating (A) Irm (A) (3) Type Type Irth (2)

    0.7 . . .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.60.55 .6 .5 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.50.75 .8 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5. .8 .6 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4.5 .7 .4 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4. 5. 4.8 6 NSX00-MA 6. 8 LC-D LRD-0 4/6 7 6.5 8 NSX00-MA .5 LC-D40 LRD- 5.5/84 9 8. 0 NSX00-MA .5 8 LC-D40 LRD- 4 7 /05.5 .5 NSX00-MA .5 6 LC-D40 LRD- 6 9/7.5 6 4 8 NSX00-MA 5 50 LC-D40 LRD- /80 9 5 NSX00-MA 5 5 LC-D40 LRD- 7/5 5 NSX00-MA 5 5 LC-D40 LRD- 7/55 0 8 NSX00-MA 50 450 LC-D80 LRD- 5 /8.5 7 4 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 4 40 50 NSX00-MA 50 650 LC-D80 LRD- 57 7/500 59 55 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/657 7 66 80 NSX00-MA 00 00 LC-D80 LRD- 6 6/8045 85 80 00 NSX00-MA 00 00 LC-D5 LR9-D5 67 60/00

    LC-F5 LR9-F5 6755 05 00 5 NSX60-MA 50 500 LC-D5 LR9-D5 69 90/50

    LC-F5 LR9-F5 6975 40 5 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6990 70 60 85 NSX50-MA 0 40 LC-F85 LR9-F5 7 /00 0 00 0 NSX50-MA 0 860 LC-F5 LR9-F5 7 /0

    NSX400 Micrologic .M

    0 880 LC-F65

    50 0 65 NSX400 Micrologic .M

    0 500 LC-F65 LR9-F7 75 00/0

    60 00 70 0 NSX400Micrologic .M

    0 460 LC-F0 LR9-F7 75 00/0

    00 80 6 400 NSX60Micrologic .M

    500 5700 LC-F400 LR9-F7 79 00/500

    0 40 80 500 NSX60Micrologic .M

    500 6500 LC-F500 LR9-F7 79 00/500

    50 460 40 500 NSX60Micrologic .M

    500 6500 LC-F500 LR9-F7 79 00/500

    60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60Micrologic 5.0 - LR off

    00 565 500 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60Micrologic 5.0 - LR off

    5 60 560 60 NS800L 800 8000 LC-F60 LR9-F7 8 80/60Micrologic 5.0 - LR off

    75 670 60 70 NS800L 800 9600 LC-F780 TC800/5 + LRD-0 60/000Micrologic 5.0 - LR off

    400 70 660 70 NS800L 800 9600 LC-F780 TC800/5 + LRD-0 60/000Micrologic 5.0 - LR off

    450 800 750 800 NS000L 000 0000 LC-F780 TC800/5 + LRD-0 60/000Micrologic 5.0 - LR off

    (1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(2) For long starting (class 20), see the correspondence table for thermal relay.(3) Ii for Micrologic 5.0 control unit.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 152 04/11/2009 16:00:08

  • 5

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 380/415 V

    DB

    94

    96 Circuit breakers, contactors and thermal relaysPerformance: U = 380/415 VCircuit breakers N H L

    NS80H-MA - 70 kA -Starting (1): adjustable class 0 A to 0.

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (A) (1)

    0.8 0.7 0.6 NS80H-MA .5 .5 LC-D40 LT6-P0M 0./0.5 0.9 0.8 NS80H-MA .5 .5 LC-D40 LT6-P0M 0./0.7 . . .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /50.55 .6 .5 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /50.75 .8 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /5. .8 .6 5 NS80H-MA 6. 70 LC-D40 LT6-P0M /5.5 .7 .4 5 NS80H-MA 6. 70 LC-D40 LT6-P0M /5. 5. 4.8 6. NS80H-MA 6. 8 LC-D40 LT6-P0M 5/5 7 6.5 .5 NS80H-MA .5 6 LC-D40 LT6-P0M 5/54 9 8. .5 NS80H-MA .5 6 LC-D40 LT6-P0M 5/55.5 .5 NS80H-MA .5 6 LC-D40 LT6-P0M 5/57.5 6 4 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/50 9 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/5 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/55 0 8 50 NS80H-MA 50 650 LC-D80 LT6-P0M on CT8.5 7 4 50 NS80H-MA 50 650 LC-D80 LT6-P0M on CT 4 40 50 NS80H-MA 50 650 LC-D80 LT6-P0M on CT0 59 55 80 NS80H-MA 80 040 LC-D80 LT6-P0M on CT7 7 66 80 NS80H-MA 80 040 LC-D80 LT6-P0M on CT(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.

    Livre 1.indb 153 04/11/2009 16:00:09

  • 54

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 380/415 V

    DB

    94

    97 Circuit breakers, contactors and thermal relaysPerformance: U = 380/415 VCircuit breakers B F N H S L

    NSX00/60/50-MA 5 6 50 70 00 0NSX400/60 Micrologic . M 5 6 50 70 00 0NS800/000L Micrologic 5.0 - - - - - 0Starting (1): normal LRD lass 0 A, LR class 0.

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 380 V I (A) 415 V Ie max (A) Type Rating (A) Irm (A) (3) Type Type Irth (A) (1)

    0.7 . . .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.60.55 .6 .5 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.50.75 .8 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5. .8 .6 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4.5 .7 .4 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4. 5. 4.8 6 NSX00-MA 6. 8 LC-D LRD-0 4/6 7 6.5 8 NSX00-MA .5 LC-D40 LRD- 5.5/84 9 8. 0 NSX00-MA .5 8 LC-D40 LRD- 4 7 /05.5 .5 NSX00-MA .5 6 LC-D40 LRD- 6 9/7.5 6 4 8 NSX00-MA 5 50 LC-D40 LRD- /80 9 5 NSX00-MA 5 5 LC-D40 LRD- 7/5 5 NSX00-MA 5 5 LC-D40 LRD- 7/55 0 8 NSX00-MA 50 450 LC-D80 LRD- 5 /8.5 7 4 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 4 40 50 NSX00-MA 50 650 LC-D80 LRD- 57 7/500 59 55 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/657 7 66 80 NSX00-MA 00 00 LC-D80 LRD- 6 6/8045 85 80 00 NSX00-MA 00 00 LC-D5 LR9-D5 67 60/00

    LC-F5 LR9-F5 6755 05 00 5 NSX60-MA 50 500 LC-D5 LR9-D5 69 90/50

    LC-F5 LR9-F5 6975 40 5 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6990 70 60 85 NSX50-MA 0 40 LC-F85 LR9-F5 7 /00 0 00 0 NSX50-MA 0 860 LC-F5 LR9-F5 7 /0

    NSX400-Micrologic . M 0 880 LC-F65 50 0 65 NSX400-Micrologic . M 0 500 LC-F65 LR9-F7 75 00/060 00 70 0 NSX400-Micrologic . M 0 460 LC-F0 LR9-F7 75 00/000 80 6 400 NSX60-Micrologic . M 500 5700 LC-F400 LR9-F7 79 00/5000 40 80 500 NSX60-Micrologic . M 500 6500 LC-F500 LR9-F7 79 00/50050 460 40 500 NSX60-Micrologic . M 500 6500 LC-F500 LR9-F7 79 00/500

    60 NS800LMicrologic 5.0 - LR off

    800 8000 LC-F60 LR9-F7 8 80/60

    00 565 500 60 NS800LMicrologic 5.0 - LR off

    800 8000 LC-F60 LR9-F7 8 80/60

    5 60 560 60 NS800LMicrologic 5.0 - LR off

    800 8000 LC-F60 LR9-F7 8 80/60

    75 670 60 70 NS800LMicrologic 5.0 - LR off

    800 9600 LC-F780 TC800/5 + LRD-0 60/000

    400 70 660 70 NS800LMicrologic 5.0 - LR off

    800 9600 LC-F780 TC800/5 + LRD-0 60/000

    450 800 750 800 NS000LMicrologic 5.0 - LR off

    000 0000 LC-F780 TC800/5 + LRD-0 60/000

    75 670 60 70 NS800L 800 9600 LC-F800/780 LT6-P0M on CTMicrologic 5.0 - LR off

    400 70 660 70 NS800L 800 9600 LC-F800/780 LT6-P0M on CTMicrologic 5.0 - LR off

    450 800 750 800 NS000L 000 0000 LC-F800/780 LT6-P0M on CTMicrologic 5.0 - LR off

    (1) For installation with a class 30 relay. a derating of 20 % must be apply on circuit breakers.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(3) Ii for Micrologic 5.0 control unit.Note: where more than one association is possible for a rated power. if the motor starting current is high or unknown. the highest association shoud be applied.

    Livre 1.indb 154 04/11/2009 16:00:17

  • 55

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 440 V

    DB

    5

    Motors Circuit breakers Contactors (2)P (kW) I (A) 440 V Ie max (A) Type Trip unit/t.u. Irth (A) Irm (A) (3) Type

    7.5 .7 5 NSX00 Micrologic . or 6. /5 Irth LC-D800 9 5 NSX00 Micrologic . or 6. 5/5 Irth LC-D80 0 5 NSX00 Micrologic . or 6. 5/5 Irth LC-D805 6.5 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D808.5 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D80 9 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D800 5 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D807 64 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D8045 76 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D8055 90 00 NSX00 Micrologic . or 6. 50/00 Irth LC-D5 or LC-F575 5 50 NSX60 Micrologic . or 6. 70/50 Irth LC-D50 or LC-F5090 46 50 NSX60 Micrologic . or 6. 70/50 Irth LC-D50 or LC-F500 78 85 NSX50 Micrologic . or 6. 00/0 Irth LC-F85

    NSX400 Micrologic . or 6. 60/0 Irth LC-F85 5 0 NSX50 Micrologic . or 6. /0 Irth LC-F5

    NSX400 Micrologic . or 6. 60/0 Irth LC-F560 56 65 NSX400 Micrologic . or 6. 60/0 Irth LC-F6500 0 0 NSX400 Micrologic . or 6. 60/0 Irth LC-F00 5 400 NSX60 Micrologic . or 6. 50/500 Irth LC-F40050 400 400 NSX60 Micrologic . or 6. 50/500 Irth LC-F40000 460 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F500

    60 NS60bL Micrologic 5.0 0/800 8000 LC-F605 540 60 NS800L Micrologic 5.0 0/800 8000 LC-F6075 575 60 NS800L Micrologic 5.0 0/800 8000 LC-F60400 6 70 NS800L Micrologic 5.0 0/800 9600 LC-F780450 70 70 NS800L Micrologic 5.0 0/800 9600 LC-F780500 800 800 NS000L Micrologic 5.0 400/000 0000 LC-F780(1) Valid for 480 V NEMA.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(3) Ii for Micrologic 5.0 control unit.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Circuit breakers, contactorsPerformance: U = 440 VCircuit breakers B F N H S L

    NSX00/60/50 Micrologic . M/6. M 0 kA 5 kA 50 kA 65 kA 90 kA 0 kANSX400/60 Micrologic . M/6. M - 0 kA 4 kA 65 kA 90 kA 0 kANS60b/800/000L Micrologic 5.0

    - - - - - 0 kA

    Starting Norme IEC 60947-4-1Micrologic . M/. M 6. M/6. M 5.0Normal (class) 5, 0 5, 0 0Long (class) 0 0, 0 0

    Livre 1.indb 155 04/11/2009 16:00:18

  • 56

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 440 V

    DB

    5

    9 Circuit breakers, contactors and thermal relaysPerformance (1): U = 440 VCircuit breakers N H L

    NS80H-MA - 65 kA -Starting (3): normal LRD class 0 A

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 440 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (A) (3)

    0.5 0.7 NS80H-MA .5 .5 LC-D09 LRD-05 0.6/0.7 .6 NS80H-MA .5 .5 LC-D09 LRD-06 /.60.55 .4 .6 NS80H-MA .5 .5 LC-D09 LRD-06 /.60.75 .7 .5 NS80H-MA .5 .5 LC-D09 LRD-07 .6/.5. .4 .5 NS80H-MA .5 .5 LC-D09 LRD-07 .6/.5.5 . 4 NS80H-MA 6. 57 LC-D LRD-08 .5/4. 4.5 6 NS80H-MA 6. 8 LC-D LRD-0 4/6 5.8 6 NS80H-MA 6. 8 LC-D LRD-0 4/64 8 8 NS80H-MA .5 LC-D40 LRD- 5.5/85.5 0.5 .5 NS80H-MA .5 6 LC-D40 LRD- 6 9/7.5 .7 6 NS80H-MA 5 50 LC-D40 LRD- /80 9 5 NS80H-MA 5 5 LC-D40 LRD- 7/5 0 5 NS80H-MA 5 5 LC-D40 LRD- 7/55 6.5 NS80H-MA 50 450 LC-D40 LRD- 5 /8.5 40 NS80H-MA 50 550 LC-D50 LRD- 55 0/40 9 40 NS80H-MA 50 550 LC-D50 LRD- 55 0/400 5 6 NS80H-MA 80 880 LC-D65 LRD- 59 48/657 6 6 NS80H-MA 80 880 LC-D65 LRD- 59 48/6545 76 80 NS80H-MA 80 040 LC-D80 LRD- 6 6/80(1) Valid for 480 V NEMA.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(3) For long starting (class 20), see the correspondence table for thermal relay.

    Livre 1.indb 156 04/11/2009 16:00:19

  • 57

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 440 V

    DB

    5

    0 Circuit breakers, contactors and thermal relaysPerformance (1): U = 440 VCircuit breakers F N H S L

    NSX00/60/50-MA 5 kA 50 kA 65 kA 90 kA 0 kANSX400/60 Micrologic . M 0 kA 4 kA 65 kA 90 kA 0 kANS60b/800/000L Micrologic 5.0 - - - - 0 kAStarting (4): normal LRD class 0 A, LR9 class 0.

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 440 V Ie max (A) Type Rating (A) Irm (A) (3) Type Type Irth (A) (4)

    0.7 .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.60.55 .4 .6 NSX00-MA .5 .5 LC-D09 LRD-06 /.60.75 .7 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5. .4 .5 NSX00-MA .5 .5 LC-D09 LRD-07 .6/.5.5 . 4 NSX00-MA 6. 57 LC-D LRD-08 .5/4. 4.5 6 NSX00-MA 6. 8 LC-D LRD-0 4/6 5.8 6 NSX00-MA 6. 8 LC-D LRD-0 4/64 8 8 NSX00-MA .5 LC-D40 LRD- 5.5/85.5 0.5 .5 NSX00-MA .5 6 LC-D40 LRD- 6 9/7.5 .7 8 NSX00-MA 5 50 LC-D40 LRD- /80 9 5 NSX00-MA 5 5 LC-D40 LRD- 7/5 0 5 NSX00-MA 5 5 LC-D40 LRD- 7/55 6.5 NSX00-MA 50 450 LC-D80 LRD- 5 /8.5 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/40 9 40 NSX00-MA 50 550 LC-D80 LRD- 55 0/400 5 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/657 6 6 NSX00-MA 00 900 LC-D80 LRD- 59 48/6545 76 80 NSX00-MA 00 00 LC-D80 LRD- 6 6/8055 90 00 NSX00-MA 00 00 LC-D5 LR9-D5 67 60/00

    LC-F5 LR9-F5 6775 5 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6990 40 50 NSX60-MA 50 950 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 690 78 85 NSX50-MA 0 40 LC-F85 LR9-F5 7 /0 0 0 NSX50-MA 0 860 LC-F5 LR9-F5 7 /0

    65 NSX400 Micrologic .M 0 500 LC-F6560 56 65 NSX400 Micrologic .M 0 500 LC-F65 LR9-F7 75 00/000 0 0 NSX400 Micrologic .M 0 460 LC-F0 LR9-F7 75 00/00 5 400 NSX60 Micrologic .M 500 5500 LC-F400 LR9-F7 79 00/50050 400 500 NSX60 Micrologic .M 500 6500 LC-F500 LR9-F7 79 00/50000 460 500 NSX60 Micrologic .M 500 6500 LC-F500 LR9-F7 79 00/500

    60 NS60bL Micrologic 5.0 - LR off 800 8000 LC-F60 LR9-F7 8 80/605 540 60 NS800L Micrologic 5.0 - LR off 800 8000 LC-F60 LR9-F7 8 80/6075 575 60 NS800L Micrologic 5.0 - LR off 800 8000 LC-F60 LR9-F7 8 80/60400 6 70 NS800L Micrologic 5.0 - LR off 800 9600 LC-F780 TC800/5 + LRD-0 60/000450 70 70 NS800L Micrologic 5.0 - LR off 800 9600 LC-F780 TC800/5 + LRD-0 60/000500 800 800 NS000L Micrologic 5.0 - LR off 000 0000 LC-F780 TC800/5 + LRD-0 60/000(1) Valid for 480 V NEMA.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(3) Ii for Micrologic 5.0 control unit.(4) For long starting (class 20), see the correspondence table for thermal relay.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 157 04/11/2009 16:00:20

  • 58

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 440 V

    DB

    94

    96 Circuit breakers, contactors and thermal relaysPerformance (1): U = 440 VCircuit breakers N H L

    NS80H-MA - 65 kA -Starting (3): adjustable class 0 A to 0.

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 440 V Ie max (A) Type Rating (A) Irm (A) Type Type Irth (A) (3)

    0.5 0.7 NS80H-MA .5 .5 LC-D40 LT6-P0M 0./0.7 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /50.55 .4 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /50.75 .7 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /5. .4 .5 NS80H-MA .5 .5 LC-D40 LT6-P0M /5.5 . 4 NS80H-MA 6. 8 LC-D40 LT6-P0M /5. 4.5 5 NS80H-MA 6. 8 LC-D40 LT6-P0M /5 5.8 6. NS80H-MA 6. 8 LC-D40 LT6-P0M 5/54 8 .5 NS80H-MA .5 6 LC-D40 LT6-P0M 5/55.5 0.5 .5 NS80H-MA .5 6 LC-D40 LT6-P0M 5/57.5 .7 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/50 9 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/5 0 5 NS80H-MA 5 5 LC-D40 LT6-P0M 5/55 6.5 50 NS80H-MA 50 550 LC-D80 LT6-P0M on CT8.5 50 NS80H-MA 50 550 LC-D80 LT6-P0M on CT 9 50 NS80H-MA 50 550 LC-D80 LT6-P0M on CT0 5 80 NS80H-MA 80 040 LC-D80 LT6-P0M on CT7 6 80 NS80H-MA 80 040 LC-D80 LT6-P0M on CT45 76 80 NS80H-MA 80 040 LC-D80 LT6-P0M on CT(1) Valid for 480 V NEMA.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3. (3) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.

    Livre 1.indb 158 04/11/2009 16:00:22

  • 59

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 440 V

    DB

    5

    Circuit breakers, contactors and thermal relaysPerformance (2): U = 440 VCircuit breakers B F N H S L

    NSX00/60/50-MA 0 kA 5 kA 50 kA 65 kA 90 kA 0 kANSX400/60-MA - 0 kA 4 kA 65 kA 90 kA 0 kANS60b/800/000L Micrologic 5.0 - - - - - 0 kAStarting (1): normal LRD class 0 A, LR9 class 0.

    Motors Circuit breakers Contactors (3) Thermal relaysP (kW) I (A) 440 V Ie max (A) Type Rating (A) Irm (A) (4) Type Type Irth (A) (1)

    0.7 .5 NSX00-MA .5 .5 LC-D40 LTM R08 0.4/80.55 .4 .5 NSX00-MA .5 .5 LC-D40 LTM R08 0.4/80.75 .7 .5 NSX00-MA .5 .5 LC-D40 LTM R08 0.4/8. .4 .5 NSX00-MA .5 .5 LC-D40 LTM R08 0.4/8.5 . 6. NSX00-MA 6. 8 LC-D40 LTM R08 0.4/8. 4.5 6. NSX00-MA 6. 8 LC-D40 LTM R08 0.4/8 5.8 6. NSX00-MA 6. 8 LC-D40 LTM R08 0.4/84 8 .5 NSX00-MA .5 6 LC-D80 LTM R7 .5/75.5 0.5 .5 NSX00-MA .5 6 LC-D80 LTM R7 .5/77.5 .7 5 NSX00-MA 5 5 LC-D80 LTM R7 .5/70 9 5 NSX00-MA 5 5 LC-D80 LTM R7 .5/7 0 5 NSX00-MA 5 5 LC-D80 LTM R7 .5/75 6.5 50 NSX00-MA 50 550 LC-D80 LTM R00 5/008.5 50 NSX00-MA 50 550 LC-D80 LTM R00 5/00 9 50 NSX00-MA 50 550 LC-D80 LTM R00 5/000 5 80 NSX00-MA 00 00 LC-D80 LTM R00 5/007 6 80 NSX00-MA 00 00 LC-D80 LTM R00 5/0045 76 80 NSX00-MA 00 00 LC-D80 LTM R00 5/0055 90 00 NSX00-MA 00 00 LC-D5 LTM R00 5/00

    LC-F575 5 50 NSX60-MA 50 950 LC-D50 LTM R08 on CT

    LC-F50 on CT90 40 50 NSX60-MA 50 950 LC-D50 LTM R08 on CT

    LC-F50 on CT0 78 85 NSX50-MA 0 40 LC-F85 LTM R08 on CT 0 0 NSX50-MA 0 860 LC-F5 LTM R08 on CT

    65 NSX400-MA 0 500 LC-F65 on CT60 56 65 NSX400-MA 0 500 LC-F65 LTM R08 on CT00 0 0 NSX400-MA 0 4000 LC-F0 LTM R08 on CT0 5 400 NSX60-MA 500 5500 LC-F400 LTM R08 on CT50 400 500 NSX60-MA 500 6500 LC-F500 LTM R08 on CT00 460 500 NSX60-MA 500 6500 LC-F500 LTM R08 on CT

    60 NS60bLMicrologic 5.0 - LR off

    800 8000 LC-F60 LTM R08 on CT

    5 540 60 NS800LMicrologic 5.0 - LR off

    800 8000 LC-F60 LTM R08 on CT

    75 575 60 NS800LMicrologic 5.0 - LR off

    800 8000 LC-F60 LTM R08 on CT

    400 6 70 NS800LMicrologic 5.0 - LR off

    800 9600 LC-F780 LTM R08 on CT

    450 70 70 NS800LMicrologic 5.0 - LR off

    800 9600 LC-F780 LTM R08 on CT

    500 800 800 NS000LMicrologic 5.0 - LR off

    000 0000 LC-F780 LTM R08 on CT

    (1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.(2) Valid for 480 V NEMA.(3) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 159 04/11/2009 16:00:23

  • 60

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 500/525 V

    DB

    5

    Motors Circuit breakers Contactors (1)P (kW) I (A) 500 V I (A) 525 V Ie max (A) Type Dcl./t.u. Irth (A) Irm (A) Type

    0 5 5 5 NSX00 Micrologic . or 6. /5 Irth LC-D80 8.4 8.4 5 NSX00 Micrologic . or 6. /5 Irth LC-D805 5 NSX00 Micrologic . or 6. /5 Irth LC-D808.5 8.5 8.5 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D80 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D800 45 45 50 NSX00 Micrologic . or 6. 5/50 Irth LC-D807 55 55 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D8045 65 65 80 NSX00 Micrologic . or 6. 50/00 Irth LC-D8055 75 75 00 NSX00 Micrologic . or 6. 50/00 Irth LC-D5 or LC-F575 05 05 5 NSX60 Micrologic . or 6. 70/50 Irth LC-D5 or LC-F590 0 0 50 NSX60 Micrologic . or 6. 70/50 Irth LC-D50 or LC-F500 55 55 85 NSX50 Micrologic . or 6. 00/0 Irth LC-F85

    NSX400 Micrologic . or 6. 60/0 Irth LC-F85 85 85 0 NSX50 Micrologic . or 6. 00/0 Irth LC-F65

    NSX400 Micrologic . or 6. 60/0 Irth LC-F6560 0 0 65 NSX400 Micrologic . or 6. 60/0 Irth LC-F6500 80 80 0 NSX400 Micrologic . or 6. 60/0 Irth LC-F4000 0 0 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F50050 60 60 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F5005 445 445 500 NSX60 Micrologic . or 6. 50/500 Irth LC-F500

    60 NS800L Micrologic 5.0 0/800 700 LC-F605 460 460 60 NS800L Micrologic 5.0 0/800 8800 LC-F6055 500 500 60 NS800L Micrologic 5.0 0/800 8800 LC-F6075 50 50 60 NS800L Micrologic 5.0 0/800 8800 LC-F60400 570 570 70 NS800L Micrologic 5.0 0/800 9600 LC-F780450 60 60 70 NS800L Micrologic 5.0 0/800 9600 LC-F780(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Circuit breakers, contactorsPerformance: U = 500/525 VCircuit breakers B F N H S L

    NSX00/60/50 Micrologic .M/6.M

    5/ kA 5/ kA 6/5 kA 50/5 kA 65/40 kA 70/50 kA

    NSX60/50 Micrologic .M/6.M

    5/ kA 0/ kA 6/5 kA 50/5 kA 65/40 kA 70/50 kA

    NSX400/60 Micrologic .M/6.M

    - 5/ kA 0/ kA 50/5 kA 65/40 kA 70/50 kA

    NS800L Micrologic 5.0 - - - - - 00 kA

    Starting Norme IEC 60947-4-1Micrologic .M/.M 6.M/6.M 5.0Normal (class) 5, 0 5, 0 0Long (class) 0 0, 0 0

    Livre 1.indb 160 04/11/2009 16:00:25

  • 6

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 690 V

    DB

    5

    8

    Motors Circuit breakers Contactors (1)P (kW) I (A) 690 V Ie max (A) Type Trip unit/t.u. Irth (A) Irm (A) (2) Type

    0 .5 0 NS00L STRME /0 Irth LC-D805 7 0 NS00L STRME /0 Irth LC-D808.5 0. 5 NS00L STRME /0 Irth LC-D80 4. 40 NS00L STRME 4/40 Irth LC-D800 50 NS00L STRME 0/50 Irth LC-D807 40 50 NS00L STRME 0/50 Irth LC-D8045 47 50 NS00L STRME 0/50 Irth LC-D8055 58 6 NS00L STRME 48/80 Irth LCF-575 76 80 NS00L STRME 60/00 Irth LCF-5

    65 NS400L STR4ME 60/0 Irth LCF-6590 94 65 NS400L STR4ME 60/0 Irth LCF-650 65 NS400L STR4ME 00/00 Irth LCF-65 5 65 NS400L STR4ME 00/00 Irth LCF-6560 65 65 NS400L STR4ME 00/00 Irth LCF-6500 0 0 NS400L STR4ME 60/0 Irth LCF-00 4 0 NS400L STR4ME 60/0 Irth LCF-050 5 55 NS400L STR4ME 60/0 Irth LCF-4005 5 500 NS60LB Micrologic 5.0 60 6900 LC-F6055 55 500 NS60LB Micrologic 5.0 60 6900 LC-F60400 400 500 NS60LB Micrologic 5.0 60 6900 LC-F60500 500 500 NS60LB Micrologic 5.0 60 6900 LC-F60560 560 60 NS800LB Micrologic 5.0 800 8800 LC-F6060 60 60 NS800LB Micrologic 5.0 800 8800 LC-F60(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(2) Ii for Micrologic 5.0 control unit.

    Circuit breakers, contactorsPerformance: U = 690 VCircuit breakers L

    NS00L-STRME 75 kANS400L-STR4ME 75 kANS60LB/NS800LB - Micrologic 5.0 75 kA

    Starting Norme IEC 947-4-1STR22ME STR43ME

    Normal (class) 0 0Long (class) - 0

    Livre 1.indb 161 04/11/2009 16:00:26

  • 6

    Complementary technical information

    Type 2 coordination (IEC 60947-4-1) 690 V

    DB

    5

    9

    Motors Circuit breakers Contactors (2) Thermal relaysP (kW) I (A) 690 V Ie max (A) Type Rating (A) Irm (A) (3) Type Type Irth (A)

    0.75 . .6 NS00L MA ,5 ,5 LC-D09 LRD-06 /,6 .5 NS00L MA ,5 7,5 LC-D09 LRD-06 ,5/.5 .5 NS00L MA ,5 ,5 LC-D09 LRD-07 ,6/,5. .8 4 NS00L MA 6, 57 LC-D40 LRD- 08 ,5/4 .8 4 NS00L MA 6, 57 LC-D40 LRD- 08 ,5/44 4.9 6 NS00L MA 6, 8 LC-D40 LRD- 0 4/65.5 6.6 8 NS00L MA ,5 LC-D80 LRD- 5,5/87.5 8.9 0 NS00L MA ,5 8 LC-D80 LRD- 4 7 /00 .5 NS00L MA 5 75 LC-D80 LRD- 6 9/5 7 8 NS00L MA 5 50 LC-D80 LRD- /88.5 0. 5 NS00L MA 5 5 LC-D80 LRD- 7/5 4. 5 NS00L MA 5 5 LC-D80 LRD- 7/55 7.5 NS00L MA 50 50 LC-D80 LRD- 5 /0 40 NS00L MA 50 650 LC-D80 LRD- 55 0/407 40 50 NS00L MA 50 650 LC-D80 LRD- 57 7/5045 47 50 NS00L MA 50 650 LC-D80 LRD- 57 7/5055 58 80 NS00L MA 00 00 LCF-5 LR9-F5 6 48/8075 76 80 NS00L MA 00 00 LCF-5 LR9-F5 6 48/8090 94 00 NS400L MA 0 880 LCF-65 LR9-F5 67 60/000 50 NS400L MA 0 880 LCF-65 LR9-F5 69 90/50 5 50 NS400L MA 0 880 LCF-65 LR9-F5 69 90/5060 65 65 NS400L MA 0 880 LCF-65 LR9-F5 7 /000 0 0 NS400L MA 0 880 LCF-0 LR9-F7 75 00/00 4 0 NS400L MA 0 880 LCF-0 LR9-F7 75 00/050 5 55 NS400L MA 0 50 LCF-400 LR9-F7 75 00/05 5 500 NS60LB Micrologic 5.0 - LR off 6900 LC-F60 LR9-F7 79 00/50055 55 500 NS60LB Micrologic 5.0 - LR off 6900 LC-F60 LR9-F7 79 00/500400 400 500 NS60LB Micrologic 5.0 - LR off 6900 LC-F60 LR9-F7 79 00/500500 500 500 NS60LB Micrologic 5.0 - LR off 6900 LC-F60 LR9-F7 8 80/60560 560 60 NS800LB Micrologic 5.0 - LR off 8800 LC-F60 LR9-F7 8 80/6060 60 60 NS800LB Micrologic 5.0 - LR off 8800 LC-F60 LR9-F7 8 80/60(1) For long starting (class 20), see the correspondence table for thermal relay.(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.(3) Ii for Micrologic 5.0 control unit.

    Circuit breakers, contactorsPerformance: U = 690 VCircuit breakers L

    NS00L-MA 75 kANS400L-MA 75 kANS60LB/NS800LB - Micrologic 5.0 75 kAStarting (1): normal LRD class 0 A other class 0

    Livre 1.indb 162 04/11/2009 16:00:26

  • 6

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    5

    9 NS80H-MA circuit breakers, contactors and thermal relaysDirect-on-line startingReverser"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.Starting (1): normal LR class 0 A, LR9 class 0.

    Motors Circuit breakers Contactors (3) Thermal relays220/230 V 380 V 415 V 440 V (2) 500/525 V 660/690 VP I P I P I P I P I P I Type Rating Type Type Irth (1)(kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)

    0.37 . 0.37 . 0.37 0.55 . 0.75 . NS80H-MA .5 LC-D09 LRD-06 /.60.55 .6 0.55 .5 0.55 .4 0.75 .5 1 .5 NS80H-MA .5 LC-D09 LRD-06 /.6

    0.37 .8 0.75 0.75 .8 0.75 .7 NS80H-MA .5 LC-D09 LRD-07 .6/.51.1 .4 1.1 1.5 NS80H-MA .5 LC-D09 LRD-07 .6/.5

    0.55 .8 1.1 .8 1.1 .5 1.5 .6 2.2 .8 NS80H-MA 6. LC-D09 LRD-08 .5/41.5 .7 1.5 .5 1.5 . 3 .8 NS80H-MA 6. LC-D09 LRD-08 .5/4

    1.1 4.4 2.2 5 2.2 4.8 2.2 4.5 3 5 4 4.9 NS80H-MA 6. LC-D09 LRD-0 4/61.5 6. 3 6.6 3 6.5 3 5.8 4 6.5 5.5 6.6 NS80H-MA .5 LC-D09 LRD- 5.5/82.2 8.7 4 8.5 4 8. 4 7.9 5.5 9 NS80H-MA .5 LC-D09 LRD-4 7/0

    7.5 8.9 NS80H-MA .5 LC-D LRD-4 7/03 .5 5.5 .5 5.5 5.5 0.4 7.5 NS80H-MA .5 LC-D LRD-6 9/4 4.5 7.5 5.5 7.5 4 7.5 .7 9 4 NS80H-MA 5 LC-D8 LRD- /8

    9 7 9 6.9 10 5 NS80H-MA 5 LC-D8 LRD- /810 .5 NS80H-MA 5 LC-D8 LRD-6 9/

    5.5 0 11 11 11 0. 11 8.4 NS80H-MA 5 LC-D5 LRD- 6/415 7 NS80H-MA 5 LC-D5 LRD- /818.5 . NS80H-MA 50 LC-D LRD- 6/4

    7.5 8 15 0 15 8 15 6.5 18.5 8.5 NS80H-MA 50 LC-D LRD- /22 30 4.6 NS80H-MA 50 LC-D40 LRD- 55 0/40

    11 9 18.5 7 22 40 22 9 NS80H-MA 50 LC-D40 LRD- 57 7/5022 44 25 47 30 45 33 9 NS80H-MA 50 LC-D50 LRD- 57 7/50

    15 5 30 5.5 NS80H-MA 50 LC-D50 LRD- 59 48/6537 4 NS80H-MA 50 LC-D65 LRD- 57 7/50

    18.5 64 30 59 30 55 37 64 37 55 NS80H-MA 80 LC-D65 LRD- 59 48/6537 66 NS80H-MA 80 LC-D65 LRD- 6 55/70

    45 49 NS80H-MA 80 LC-D80 LRD- 57 7/5022 75 37 7 45 80 45 76 55 80 NS80H-MA 80 LC-D80 LRD- 6 6/80

    55 60 NS80H-MA 80 LC-D5 LR9-D5 67 60/0075 80 LC-F5 LR9-F5 6 48/80

    (1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.(2) Valid for 480 V NEMA.(3) Reversers: replace LC1 by LC2.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 163 04/11/2009 16:00:27

  • 64

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    5

    9 NSX100 circuit breakers, contactors and thermal relaysDirect-on-line startingReverser"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.Starting (1): normal LRD class 0, others class 0.

    Motors Circuit breakers Contact. (3) Thermal relays220/230 V 380 V 415 V 440 V (2) 500/525 V 660/690 VP I P I P I P I P I P I Type Rating Type Type Irth (1)(kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)

    0.37 . 0.37 . 0.37 0.55 . 0.75 . NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-06 /.60.55 .6 0.55 .5 0.55 .4 0.75 .5 1 .5 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-06 /.6

    0.37 .8 0.75 0.75 .8 0.75 .7 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-07 .6/.51.1 .4 1.1 1.5 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-07 .6/.5

    0.55 .8 1.1 .8 1.1 .5 1.5 .6 2.2 .8 NSX00B/F/N/H/S/L-MA 6. LC-D09 LRD-08 .5/41.5 .7 1.5 .5 1.5 . 3 .8 NSX00B/F/N/H/S/L-MA 6. LC-D09 LRD-08 .5/4

    1.1 4.4 2.2 5 2.2 4.8 2.2 4.5 3 5 4 4.9 NSX00B/F/N/H/S/L-MA 6. LC-D09 LRD-0 4/61.5 6. 3 6.6 3 6.5 3 5.8 4 6.5 5.5 6.6 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD- 5.5/82.2 8.7 4 8.5 4 8. 4 7.9 5.5 9 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD- 4 7/0

    7.5 8.9 NSX00B/F/N/H/S/L-MA .5 LC-D LRD- 4 7/03 .5 5.5 .5 5.5 5.5 0.4 7.5 NSX00B/F/N/H/S/L-MA .5 LC-D LRD- 6 9/4 4.5 7.5 5.5 7.5 4 7.5 .7 9 4 NSX00B/F/N/H/S/L-MA 5 LC-D8 LRD- /8

    9 7 9 6.9 10 5 NSX00B/F/N/H/S/L-MA 5 LC-D8 LRD- /810 .5 NSX00B/F/N/H/S/L-MA 5 LC-D8 LRD- 6 9/

    5.5 0 11 11 11 0. 11 8.4 NSX00B/F/N/H/S/L-MA 5 LC-D5 LRD- 6/415 7 NSX00B/F/N/H/S/L-MA 5 LC-D5 LRD- /818.5 . NSX00B/F/N/H/S/L-MA 50 LC-D LRD- 6/4

    7.5 8 15 0 15 8 15 6.5 18.5 8.5 NSX00B/F/N/H/S/L-MA 50 LC-D LRD- /22 30 4.6 NSX00B/F/N/H/S/L-MA 50 LC-D40 LRD- 55 0/40

    11 9 18.5 7 22 40 22 9 NSX00B/F/N/H/S/L-MA 50 LC-D40 LRD- 57 7/5022 44 25 47 30 45 33 9 NSX00B/F/N/H/S/L-MA 50 LC-D50 LRD- 57 7/50

    37 4 NSX00B/F/N/H/S/L-MA 50 LC-D65 LRD- 57 7/5015 5 30 59 30 55 30 5.5 NSX00B/F/N/H/S/L-MA 00 LC-D65 LRD- 59 48/6518.5 64 37 64 37 55 NSX00B/F/N/H/S/L-MA

    45 49 NSX00B/F/N/H/S/L-MA 00 LC-D80 LRD- 57 7/5022 75 37 7 37 7 45 76 55 80 NSX00B/F/N/H/S/L-MA 00 LC-D80 LRD- 6 6/80

    45 80 NSX00B/F/N/H/S/L-MA25 85 45 85 NSX00B/F/N/H/S/L-MA 00 LC-D95 LRD- 65 80/04

    55 60 NSX00B/F/N/H/S/L-MA 00 LC-D5 LR9-D5 6 48/8030 00 55 00 55 96 75 80 NSX00B/F/N/H/S/L-MA 00 LC-D5 LR9-D5 67 60/00(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.(2) Valid for 480 V NEMA.(3) Reversers: replace LC1 by LC2.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 164 04/11/2009 16:00:29

  • 65

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    5

    0 NSX160 to NS1250 circuit breakers, contactors and thermal relaysDirect-on-line startingReverser"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.Starting (1): normal class 0.

    Motors Circuit breaker Contactors (2)

    Thermal relays (1)

    220/230 V 380 V 415 V 440 V (2) 500/525 V 660/690 VP I P I P I P I P I P I Type Rating Type Type Irth (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)

    37 5 55 05 75 5 75 4 75 0 90 00 NSX60B/F/N/H/S/L MA 50 LC-D50 LR9-D5 69 90/5045 50 75 40 90 0 110 0 LC-F50 LR9-F5 69 00/6055 80 90 70 90 60 90 56 110 56 NSX50B/F/N/H/S/L MA 0 LC-F85 LR9-F5 7 /0 110 80

    110 0 110 00 132 5 NSX50B/F/N/H/S/L MA 0 LC-F5 LR9-F5 7 /0132 90 132 40 NSX50B/F/N/H/S/L MA 0 LC-F65 LR9-F5 7 /0

    160 75 75 50 132 50 132 0 160 56 160 8 NSX400F/N/H/S/L

    Micrologic .M0 LC-F65 LR9-F7 75 00/0

    90 160 00 160 70 200 8 200 0 NSX400F/N/H/S/L 0 LC-F0 LR9-F7 75 00/0 220 40 Micrologic .M 110 60 200 80 220 80 220 60 220 0 NSX60F/N/H/S/L

    Micrologic .M500 LC-F400 LR9-F7 79 00/500

    250 70 NSX60F/N/H/S/L Micrologic .M

    500 LC-F400 LR9-F7 75 00/0

    220 40 250 40 335 5 NSX60F/N/H/S/L Micrologic .M

    500 LC-F500 LR9-F7 79 00/500

    150 480 250 480 250 40 315 445 NSX60F/N/H/S/L 500 LC-F500 LR9-F7 79 00/500 335 460 Micrologic .M

    300 480 375 400 NSX60F/N/H/S/L 500 LC-F60 LR9-F7 8 80/60 450 480 Micrologic .M 160 50 300 570 300 50 335 540 355 500 NS800N/H-NS000L 800 LC-F60 LR9-F7 8 80/60

    375 50 Micrologic 5.0 - LR off 000 400 570 200 60 335 60 335 580 375 590 450 60 NS800N/H-NS000L 800 LC-F60 LR9-F7 8 80/60 Micrologic 5.0 - LR off 00 0 220 700 375 700 375 650 400 650 NS800N/H-NS000L 800 LC-F800 LR-F8 8 500/800 Micrologic 5.0 - LR off 000

    400 750 400 690 450 70 NS800N/H-NS000L 800 LC-F800 LR-F8 8 500/800 Micrologic 5.0 - LR off 000 LC-BL

    500 50 NS800N/H-NS000L 800 LC-BL LR-F8 8 500/800 560 580 Micrologic 5.0 - LR off 000 250 800 450 800 450 750 500 700 NS000N/H 000 LC-BM LR-F8 8 500/800 560 760 Micrologic 5.0 - LR off

    500 900 500 80 500 800 600 80 NS000N/H 000 LC-BM LR-F8 85 60/000 560 900 Micrologic 5.0 - LR off 300 970 560 000 560 90 600 960 670 90 NS50N/H 50 LC-BP LR-F8 85 60/000 600 00 600 000 670 080 750 00 Micrologic 5.0 - LR off (1) For long starting (class 20), see the correspondence table for thermal relay.(2) Reversers: replace LC1 by LC2.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 165 04/11/2009 16:00:30

  • 66

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    5

    NS160 to NS1250 circuit breakers, contactors Direct-on-line startingReverser"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.

    Starting Norme IEC 60947-4-1Micrologic .M/.M 6.M/6.M 5.0Normal (class) 5, 0 5, 0 0Long (class) 0 0, 0 0

    Motors Circuit breakers Contactors (2)220/230 V 380 V 415 V 440 V (1) 500/525 V 660/690 VP I P I P I P I P I P I Type Trip unit Irth Type(kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (kW) (A) (A)

    7,5 8 15 0 15 8 15 6,5 19 8,5 NSX00B/F/N/H/S/L Micrologic . or 6. 5/50 LC-D11 9 19 7 22 40 22 9 22 30 4,6 NSX00B/F/N/H/S/L Micrologic . or 6. 5/50 LC-D40 22 44 25 47 30 45 33 9 NSX00B/F/N/H/S/L Micrologic . or 6. 5/50 LC-D5015 5 30 59 30 55 30 5,5 37 4 NSX00B/F/N/H/S/L Micrologic . or 6. 48/80 LC-D6519 64 37 64 37 55 NSX00B/F/N/H/S/L Micrologic . or 6. 50/00 LC-D6522 75 37 7 37 7 45 76 55 80 45 49 NSX00B/F/N/H/S/L Micrologic . or 6. 48/80 LC-D8025 85 45 85 NSX00B/F/N/H/S/L Micrologic . or 6. 50/00 LC-D95 55 60 NSX00B/F/N/H/S/L Micrologic . or 6. 50/00 LC-D5 or LC-F530 00 55 00 55 96 75 80 NSX00B/F/N/H/S/L Micrologic . or 6. 50/00 LC-D5 or LC-F537 5 55 05 75 5 75 4 75 0 90 00 NSX60B/F/N/H/S/L Micrologic . or 6. 70/50 LC-D50 or LC-F5045 50 75 40 90 0 110 0 55 80 90 70 90 60 90 56 110 56 NSX50B/F/N/H/S/L Micrologic . or 6. 00/0 LC-F85 110 80 110 0 110 00 132 5 NSX50B/F/N/H/S/L Micrologic . or 6. 00/0 LC-F5

    132 90 132 40 NSX50B/F/N/H/S/L Micrologic . or 6. 00/0 LC-F65 160 75 75 50 132 50 132 0 160 56 160 8 NSX400F/N/H/S/L Micrologic . or 6. 60/0 LC-F6590 160 00 160 70 200 8 200 0 NSX400F/N/H/S/L Micrologic . or 6. 60/0 LC-F0 220 40 110 60 200 80 220 80 220 60 220 0 250 70 NSX60F/N/H/S/L Micrologic . or 6. 50/500 LC-F400 220 40 250 40 315 445 335 5 NSX60F/N/H/S/L Micrologic . or 6. 50/500 LC-F500150 480 250 480 250 40 335 460 NSX60F/N/H/S/L Micrologic . or 6. 50/500 LC-F500

    300 480 355 500 375 400 NSX60F/N/H/S/L Micrologic . or 6. 50/500 LC-F60 375 50 450 480 160 50 300 570 300 50 335 540 400 570 NS800N/H Micrologic 5.0 0/800 LC-F60 NS000L 400/000 200 60 335 60 335 580 375 590 450 60 NS800N/H Micrologic 5.0 0/800 LC-F60 NS000L 400/000 220 700 375 700 375 650 400 650 NS800N/H Micrologic 5.0 0/800 LC-F800 NS000L 400/000

    400 750 400 690 450 70 NS800N/H Micrologic 5.0 0/800 LC-F800 NS000L 400/000 LC-BL

    500 50 NS800N/H Micrologic 5.0 0/800 LC-BL 560 580 NS000L 400/000 250 800 450 800 450 750 500 700 NS000N/H Micrologic 5.0 400/000 LC-BM 560 760

    500 900 500 80 500 800 600 80 NS000N/H Micrologic 5.0 400/000 LC-BM 560 900 300 970 560 000 560 90 600 960 670 90 NS50N/H Micrologic 5.0 60/50 LC-BP

    600 00 600 000 670 080 750 00 NS50N/H Micrologic 5.0 60/50 LC-BP(1) Valid for 480 V NEMA.(2) Reversers: replace LC1 by LC2.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 166 04/11/2009 16:00:32

  • 67

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    09

    NS80H-MA and NSX100 circuit breakers, contactors and thermal relaysStar-delta starting"Iq" breaking performance: equal to the breaking capacity of the circuit breaker.Starting: normal.

    Motors Circuit breakers Contactors Thermal relays220/230 V 380 V 415 V 440 V (1)P I P I P I P I Type Rating Type Type Irth(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)

    0.55 .8 1.5 .7 1.5 .5 1.5 . NS80H-MA 6. LC-D09 LRD-07 .6/.51.1 4.4 2.2 5 2.2 4.8 2.2 4.5 NS80H-MA 6. LC-D09 LRD-08 .5/41.5 6. 3 6.6 3 6.5 3 5.8 NS80H-MA .5 LC-D09 LRD-08 .5/42.2 8.7 4 8.5 4 8. 4 7.9 NS80H-MA .5 LC-D09 LRD-0 4/63 .5 5.5 .5 5.5 5.5 0.4 NS80H-MA .5 LC-D09 LRD- 5.5/84 4.5 7.5 5.5 7.5 4 7.5 .7 NS80H-MA 5 LC-D09 LRD-4 7/05.5 0 9 7 9 6.9 NS80H-MA 5 LC-D LRD-6 9/

    11 11 11 0. NS80H-MA 5 LC-D LRD-6 9/7.5 8 15 0 15 8 15 6.5 NS80H-MA 50 LC-D8 LRD- /811 9 18.5 7 22 40 22 9 NS80H-MA 50 LC-D8 LRD- 7/5

    22 44 25 47 NS80H-MA 50 LC-D LRD- /15 5 30 5.5 NS80H-MA 80 LC-D LRD- /

    30 55 NS80H-MA 80 LC-D LRD- /18.5 64 30 59 37 66 37 64 NS80H-MA 80 LC-D40 LR-D 55 0/40

    37 7 NS80H-MA 80 LC-D40 LR-D 57 7/5022 75 45 80 45 76 NS80H-MA 80 LC-D50 LR-D 57 7/500.55 .8 1.5 .7 1.5 .5 1.5 . NSX00B/F/N/H/S/L-MA 6. LC-D09 LRD-07 .6/.51.1 4.4 2.2 5 2.2 4.8 2.2 4.5 NSX00B/F/N/H/S/L-MA 6. LC-D09 LRD-08 .5/41.5 6. 3 6.6 3 6.5 3 5.8 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-08 .5/42.2 8.7 4 8.5 4 8. 4 7.9 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD-0 4/63 .5 5.5 .5 5.5 5.5 0.4 NSX00B/F/N/H/S/L-MA .5 LC-D09 LRD- 5.5/84 4.5 7.5 5.5 7.5 4 7.5 .7 NSX00B/F/N/H/S/L-MA 5 LC-D09 LRD-4 7/05.5 0 9 7 9 6.9 NSX00B/F/N/H/S/L-MA 5 LC-D LRD-6 9/

    11 11 11 0. NSX00B/F/N/H/S/L-MA 5 LC-D LRD-6 9/7.5 8 15 0 15 8 15 6.5 NSX00B/F/N/H/S/L-MA 50 LC-D8 LRD- /811 9 18.5 7 22 40 22 9 NSX00B/F/N/H/S/L-MA 50 LC-D8 LRD- 7/5

    22 44 25 47 NSX00B/F/N/H/S/L-MA 00 LC-D LRD- /15 5 30 5.5 NSX00B/F/N/H/S/L-MA 00 LC-D LRD- /

    30 55 NSX00B/F/N/H/S/L-MA 00 LC-D LRD- /18.5 64 30 59 37 66 37 64 NSX00B/F/N/H/S/L-MA 00 LC-D40 LR-D 55 0/40

    37 7 NSX00B/F/N/H/S/L-MA 00 LC-D40 LR-D 57 7/5022 75 45 80 45 76 NSX00B/F/N/H/S/L-MA 00 LC-D50 LR-D 57 7/5025 85 45 85 NSX00B/F/N/H/S/L-MA 00 LC-D50 LR-D 57 7/5030 00 55 00 55 96 NSX00B/F/N/H/S/L-MA 00 LC-D50 LR-D 59 48/65(1) Valid for 480 V NEMA.

    Livre 1.indb 167 04/11/2009 16:00:34

  • 68

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    09

    NSX160 to NS1000 circuit breakers, contactors and thermal relaysStar-delta starting "Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.Starting: normal.

    Motors Circuit breakers Contactors Thermal relays 220/230 V 380 V 415 V 440 V (1)P I P I P I P I Type Rating Type Type Irth(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)

    55 05 NSX60B/F/N/H/S/L-MA 50 LC-D80 LR-D 59 48/6537 5 75 40 75 5 75 4 NSX60B/F/N/H/S/L-MA 50 LC-D80 LR-D 6 6/8045 50 75 40 NSX60B/F/N/H/S/L-MA 50 LC-D5 LR9-D5 67 60/00

    LC-F5 LR9-F5 6790 70 90 60 90 56 NSX50B/F/N/H/S/L-MA 0 LC-D5 LR9-D5 67 60/00

    LC-F5 LR9-F5 6755 80 110 80 NSX50B/F/N/H/S/L-MA 0 LC-D5 LR9-D5 69 90/50

    LC-F5 LR9-F5 67110 0 110 00 NSX50B/F/N/H/S/L-MA 0 LC-D5 LR9-D5 69 90/50

    LC-F5 LR9-F5 69132 5 NSX50B/F/N/H/S/L-MA 0 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6975 50 132 50 132 0 NSX400F/N/H/S/L Micrologic .M 0 LC-D50 LR9-D5 69 90/50

    LC-F50 LR9-F5 6990 160 00 160 70 160 56 NSX400F/N/H/S/L Micrologic .M 0 LC-F85 LR9-F5 7 /0110 60 200 80 220 80 220 60 NSX60F/N/H/S/L Micrologic .M 500 LC-F65 LR9-F7 75 00/0

    220 40 250 40 NSX60F/N/H/S/L Micrologic .M 500 LC-F65 LR9-F7 75 00/0150 480 250 480 250 40 NSX60F/N/H/S/L Micrologic .M 500 LC-F0 LR9-F7 75 00/0

    300 480 NSX60F/N/H/S/L Micrologic .M 500 LC-F0 LR9-F7 75 00/0160 50 300 570 300 50 335 540 NS800N/H-NS000L 800 LC-F400 LR9-F7 75 00/0

    Micrologic 5.0 - LR off 000335 580 375 590 NS800N/H-NS000L 800 LC-F400 LR9-F7 79 00/500

    Micrologic 5.0 - LR off 000(1) Valid for 480 V NEMA.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 168 04/11/2009 16:00:35

  • 69

    Complementary technical information

    Type 1 coordination (IEC 60947-4-1)

    DB

    49

    68 NSX100 to NS1000 circuit breakers contactorsStar-delta starting "Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.Starting: normal.

    Motors Circuit breakers Contactors220/230 V 380 V 415 V 440 V (1)P I P I P I P I Type Trip unit Irth Type(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A)

    7.5 8 15 0 15 8 15 6.5 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 5/50 LC-D811 9 18.5 7 22 40 22 9 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 5/50 LC-D8

    22 44 25 47 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 5/50 LC-D15 5 30 5.5 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D

    30 55 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D18.5 64 30 59 37 66 37 64 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D40

    37 7 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D4022 75 45 80 45 76 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D5025 85 45 85 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D5030 00 55 00 55 96 NSX00B/F/N/H/S/L Micrologic .M or 6.E-M 50/00 LC-D50

    55 05 NSX60B/F/N/H/S/L Micrologic .M or 6.E-M 70/50 LC-D8037 5 75 40 75 5 75 4 NSX60B/F/N/H/S/L Micrologic .M or 6.E-M 70/50 LC-D8045 50 75 40 NSX60B/F/N/H/S/L Micrologic .M or 6.E-M 70/50 LC-D5 or LC-F5

    90 70 90 60 90 56 NSX50B/F/N/H/S/L Micrologic .M or 6.E-M 00/0 LC-D5 or LC-F555 80 110 0 110 00 110 80 NSX50B/F/N/H/S/L Micrologic .M or 6.E-M 00/0 LC-D5 or LC-F5

    132 5 NSX50B/F/N/H/S/L Micrologic .M or 6.E-M 00/0 LC-D50 or LC-F5075 50 132 50 132 0 NSX400F/N/H/S/L Micrologic .M or 6.E-M 60/0 LC-D50 or LC-F5090 160 00 160 70 160 56 NSX400F/N/H/S/L Micrologic .M or 6.E-M 60/0 LCF-85110 60 200 80 220 80 220 60 NSX60F/N/H/S/L Micrologic .M or 6.E-M 50/500 LC-F65

    220 40 250 40 NSX60F/N/H/S/L Micrologic .M or 6.E-M 50/500 LC-F65150 480 250 480 250 40 NSX60F/N/H/S/L Micrologic .M or 6.E-M 50/500 LC-F0

    300 480 NSX60F/N/H/S/L Micrologic .M or 6.E-M 50/500 LC-F0160 50 300 570 300 50 335 540 NS800N/H Micrologic 5.0 0/800 LC-F400

    NS000L 400/000335 580 375 590 NS800N/H Micrologic 5.0 0/800 LC-F400

    NS000L 400/000(1) Valid for 480 V NEMA.Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

    Livre 1.indb 169 04/11/2009 16:00:37