Typical Protection Schemes

Embed Size (px)

DESCRIPTION

Protection scheme

Citation preview

  • Page 87 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Typical Protection Schemes

  • Page 88 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Typical protection for a radial system

    Most distant relay gets the shortest delay time

    Definite-Time (51, 51N)System impedance (Infeed) high, no current selectivity

    Inverse-Time (51, 51N)System impedance (Infeed) medium, current selectivity

    Very Extremely Inverse-Time (51, 51N)

    System impedance (Infeed) small, high current selectivity

    1) Auto reclosing cycle only for overhead lines (79)

    2) Negative-phase sequence system as back up protection (46, unbalance protection)

  • Page 89 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Typical protection of ring feeders

    Switch off time of the relays has to be coordinated with down-stream fuses

    Inverse-time characteristic curves (51, 51N)

    Thermical overload (49) for cables

    Negative-phase system protection (46) as sensitive back up protection

    (52: Circuit-breaker)

  • Page 90 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Typical protection for a distribution feeder with reclosing

    The relay settings and the auto reclosing cycle (79) must be coordinated with the down-streamed protection devices.

  • Page 91 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Feeder protection Distribution System

  • Page 92 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Feeder protection Transmission System

  • Page 93 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Feeder protection Transmission System

  • Page 94 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Undelayed I>>, IE>> (50, 50N)

    Main protection OS

    Time-delayed overcurrent-time (51)

    Back-up protection OS

    Buchholz (63)

    Overload (49) Negative-phase

    sequence system (46)

    Limited earth-fault (87N)Main protection US

    Time-delayed overcurrent I > (51G) (Earth path)

    Back-up protection US

    (OS: Overvoltage side)

    (US: Undervoltage side)

    >

    Small transformers < 5 MVA

  • Page 95 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Dual infeed with single transformer

  • Page 96 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Important transformer infeeds

    Differential (87T)Main protection

    Overcurrent-time (50, 51, 51N)Back-up protection

    Limited earth-fault (87N)

    Neg.-phase sequence system (46)

    Thermal (49)Overload protection

    Buchholz (63)

    Earth-fault current protection(51G)

  • Page 97 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Three-winding transformer

  • Page 98 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Autotransformer

  • Page 99 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Large autotransformer bank

  • Page 100 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Small and medium motors with nominal outputs < 1MW

    1) Cable-type current transformer is necessary for sensitive earth-fault protection

    b) In systems with high-resistance neutral earthing (IE IN Motor)

    a) In systems with solid grounding or low-resistance neutral earthing (IE> IN Motor)

    2) Directional protection, Earth-fault monitoring

    (37) Undercurrent relay

  • Page 101 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Big high voltage motors > approx. 1 MW

    1) Cable-type current transformers for the sensitive earth-fault detection

    2) Sensitive directional earth-fault detection in operation with a Petersen-coil

    3) Startup supervision

    4) Temperature sensor

    (27) Undervoltage-relay

    Optional

  • Page 102 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Micro generators < 500 kW

    b) Earthed via resistance

    a) Solid grounding

  • Page 103 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Busbar protection Reverse interlocking principle

    Applicable to distribution buses without considerable (< 0.25 In) back feeding from the outgoing feeders

  • Page 104 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Low impedance - Busbar protection

    Especially used in multiple busbars for which an isolator replica is necessary

    Current transformers can be different

    Feeder protection can be connected to the same current transformer core

    (87): Differential protection

    (86): Tripping relay

    (BF): Breaker failure protection

  • Page 105 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    High impedance busbar protection

  • Page 106 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    1-1/2-breaker arrangement

  • Page 107 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Typical protection for parallel service without back-feed

    Directional overcurrent - time protection relays (67, 67N) switch off fault on the protected line without delay

    Non-directional relays (51, 51N) must be delayed about 1 grading zone

  • Page 108 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Overcurrent-time Phase/Earth directional (67, 67N) non-directional (50, 51, 51N)

    Main protection

    Overcurrent-time Phase/Earth (51, 51N)

    Back-up protection

    Thermal (49)

    Overload protection

    Buchholz (63)

    Limited earth-fault (51G)

    Negative-phase sequence system (46)

    Dual transformer infeed

  • Page 109 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Cable / short overhead line < 20km with infeed of both sides

    Differential (87)Main protection

    Overcurrent-time (51, 51N)Back-up protection

    ThermalOverload protection

    1) Automatic reclosing only in overhead lines (79)

    2) Overload protection (49)mainly in cables

  • Page 110 2007-08Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor: G. Ziegler

    Overhead lines or long cables with infeed of from sides

    Distance (21, 21N)Main protection

    2) Directional Overcurrent-time (67N)

    Back-up protection

    3) Auto reclosing (79)(single or multiple) only in overhead lines

    1) Signal comparison (85)