UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

Embed Size (px)

Citation preview

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    1/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 1 of 40

    APPENDICES

    A1. Glossary of Terms & Abbreviations ................................................................... 2A2.

    List of Clauses in the Regulations which do not apply to Old Installations....... 3

    A3. Reference Standards......................................................................................... 4A4. Guidance Note on Supply Voltage Changes ..................................................... 5A5. Guidance Notes for the Estimation of Diversified Connected Load................... 5A6. Customer Earthed (TT) and Distribution Company Earthed Systems (TN-S) . 5A7. Guidance Note on Principles of Electric Shock Protection and Earthing.......... 5A8. Guidance Note on Earth Conductors and Equipotential Bonding...................... 5A9. Electric Shock Protection Using Residual Current Devices............................... 5A10. Performance Characteristics for MCBs complying with BS EN 60898 ............. 5A11. Sizing of Earth Conductors and Equipotential Bonding Conductors................ 5A12. Number of Earth Electrodes Required for Installations...................................... 5A13. Mandatory Connections to Earth Conductors.................................................... 5A14. Earth Leakage Protection for Equipment........................................................... 5A15. Earth Fault Loop Impedance.............................................................................. 5A16. Cable Ratings, Voltage Drop and Ambient Temperature Correction Factors ... 5A17. Colour Identification of Cables........................................................................... 5A18. Capacity of Conduits and Trunking.................................................................... 5A19. IP Coding for Ingress Protection ........................................................................ 5A20. Standard Wiring Diagram Symbols.................................................................... 5A21. Typical Layout for Supply Intake Room............................................................. 5A22. Typical Layout for Ring Circuits ......................................................................... 5A23. Approved and Prohibited Plugs and Socket Types............................................ 5A24. Minimum Recommended Number of Socket Outlets......................................... 5A25. Method for Measuring Earth Resistance............................................................ 5A26. Method for Earth Loop Impedance Test ............................................................ 5A27. Method for Continuity Tests ............................................................................... 5A28. Method for Insulation Resistance Test............................................................... 5A29. Method for Polarity Tests ................................................................................... 5A30. Installation Certificate......................................................................................... 5A31. Inspection Report............................................................................................... 5A32. Testing Report ................................................................................................... 5A33. Load Distribution Schedule................................................................................ 5

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    2/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 2 of 40

    A1. Glossary of Terms & Abbreviations

    A.C alternating current

    D.C. direct current

    RCD residual current device

    RCCB residual current circuit breaker

    RCBO residual current breaker (with) overcurrent

    ELCB earth leakage circuit breaker

    MCB miniature circuit breaker

    MCCB moulded case circuit breaker

    SDB sub distribution board

    MDB main distribution board

    TT a three phase and locally earthed system

    TN-S a three phase system, with neutral earthing a the distribution transformer, and havingseparate neutral and phase conductors in the supply cable

    ESMA Emirates Standardisation & Metrology Authority

    BS British Standard

    IEC International Electrotechnical Commission

    EN European Normalisation standard document

    BS-EN British Standard which has been accepted under the European Normalisation procedure

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    3/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 3 of 40

    A2. List of Clauses in the Regulations whichdo not apply to Old Installations

    The Electricity Wiring Regulations are effective from 1 March 2007[proposed]. For any Installationswhich were completed before this date the following clauses of the Regulations do not apply or willapply after 1 January 2010 or, if earlier, at the time of the next inspection or re-certification.

    Clause Reason / Comment Application

    1.4.4 General requirement forcompliance of all equipment andmaterials to internationalstandards

    Does not apply retrospectively

    1.6.7, 4.4.1 and4.4.6

    Requirement for overall earthleakage protection

    Must apply by 1 January 2010

    1.6.12, 1.6.13 Requirement for labelling of partsof the Installation

    Must apply by 1 January 2010

    4.2.2 Prohibition of fused cut-outs Must apply by 1 January 2010

    5.2.5 Requirement for maximumCustomer Earth Electrodeimpedance

    Must apply by 1 January 2010

    5.5.1 Requirement for EquipotentialBonding Conductors

    Must apply by 1 January 2010

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    4/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 4 of 40

    A3. Reference Standards

    The table below shows the reference standards that may be used for the main components required forElectrical Installations. Additional standards not listed may be referenced from the UK WiringRegulations (BS7671: 2001) or other international standards, with agreement of the relevant DistributionCompany providing supply.

    Item BS IEC

    Cables

    PVC insulation (thermoplastic) - for power &lighting

    6004, 6346 502

    PVC insulation (thermoplastic) - forswitchgear & control wiring

    6231 227

    Rubber insulation (thermosetting) 5467, 6234, 7211

    Mineral insulation 6207, 6081 702

    Flexible cables & cords 6500, 6141, 6004, 6977 227, 245

    Cable glands 6121Conduits

    Steel

    PVC

    Flexible Steel

    4568, 60423*, 50086*, 31

    4607, 6053, 6099

    731

    432, 614

    423

    Degrees of Protection & Ingress 60529*

    529

    Distribution Assemblies for ConstructionSites 4363 364-7-704

    Earthing 7430, 951 364-5-54

    Electrical Accessories

    General 5733

    Ceiling roses 67

    Cooker Control Units 4177

    Plugs & Socket Outlets 546, 196, 1363, 4343

    Switches 3676, 60947-3*

    Emergency Lighting 5266

    Hazardous Areas 5345, 5501

    Household Appliances 3456, 60335*

    Isolating Transformer (for shaver sockets) 3535

    LV Switchgear & Assemblies

    General 60439*, 60947*, 60947-1* 947, 439-1 & 3

    Circuit Breakers (MCB, MCCB) 60898, 3871 898

    Earth Leakage Circuit Breakers (ELCB,RCD)

    4293 755

    Fuses 88, 1361

    Busbar trunking systems 60439-2 439-2

    Neon Signs 559

    Non Combustibility Test 476

    Trunking, Ducting and Fittings 4678 1084

    Thermal Classification of ElectricalInsulation

    2757 85

    * Also listed as EN (European) Standard under the same number

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    5/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 5 of 40

    A4. Guidance Note on Supply Voltage Changes

    Distribution Companies in the UAE have traditionally based the design of their networks on the UK

    power system. Previously, the voltage of supply was declared to be 240V single-phase or 415V three

    phase, with an allowed variation in the supply of +/- 6%. However, with the harmonization of supply

    voltages in Europe (line with IEC 38) the UK has adopted a supply voltage of 230V / 400V +/- 10%.

    Distribution Companies in the UAE have now followed the same change but as with companies in theUK they are expected to continue to operate their networks in the old operating range for a transition

    period (1 or 2 years).

    This can be achieved by declaring a supply voltage of 230V/400V +/- 10% but in practice operating the

    LV networks in a range of 230V/400V +10% to -6%. This means that existing equipment and

    appliances will not experience any significant change in the maximum supply voltage and only a small

    change in the minimum supply voltage (see illustration below). However, new equipment and

    appliances must be designed to operate in the wider range of 230V/400V +/- 10%. At the end of the

    transition period Distribution Companies are expected to switch to the wider range which allows for a

    single phase voltage level down to 207V (i.e. 230V - 10%), which allowing for a 4% volt drop within a

    customers premises means that an appliance could receive a voltage as low as 198.7V and must

    continue to operate satisfactorily.

    Figure A4 Comparison of old and new supply voltage ranges

    240 254.4225.6

    210 220 230 240 250 260 200

    230 253.0216.2

    - 6% +10%

    230 253.0207.0

    - 6% +6%

    - 10% +10%

    Volts

    IEC.38 supply voltage range as adopted in

    the Supply Regulations for Abu Dhabi

    Old UK supply voltage range

    previously used in Abu Dhabi

    IEC.38 voltage operated under a restricted

    range by Distribution Companies (transition period)

    240 254.4225.6

    210 220 230 240 250 260 200

    230 253.0216.2

    - 6% +10%

    230 253.0207.0

    - 6% +6%

    - 10% +10%

    Volts

    IEC.38 supply voltage range as adopted in

    the Supply Regulations for Abu Dhabi

    Old UK supply voltage range

    previously used in Abu Dhabi

    IEC.38 voltage operated under a restricted

    range by Distribution Companies (transition period)

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    6/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 6 of 40

    A5. Guidance Notes for the Estimation of Diversified Connected Load

    The total estimated load at a Premise must be calculated and submitted to the Distribution Company inorder to make an application for a new supply of electricity or alteration of an existing supply.

    It is normal practice to calculate the Diversified Connected Load rather than simply take the sum of allequipment and appliances in the Installation. This method avoids over sizing of the Installation as wellas the Distribution Company supply.

    Firstly, the design and layout of an installation should be detailed in the format of load distributionschedules as shown in appendix A33. These schedules should list all connection points and fixedAppliances in each circuit.

    To arrive at the total Diversified Connected Load, assume the following:

    (a) Lighting: sum of wattage of all luminariesOR assume 100W for each lighting pointand / or 1.8 x lamp wattage for fluorescent lighting

    (b) 13A power points: assume 200 watts per point for general ring circuits (except kitchen)

    assume 3000 watts for fixed kitchen appliances (washing machine etc)kitchen worktop points - assume 1000W

    (c) other power points: kitchen cooker take rating of circuit or applianceair conditioning supply points taking rating of each a/c unitwater heater points take rating of each unitlifts and other motors take rating of each unit

    Diversity factors may be applied to sub-totals of the above categories as follows, before taking thegrand total as the Diversified Connected Load:

    (a) total lighting: 80%(b) total 13 general power points: 70%(c) total other power points: no diversity

    For non domestic premises the above rules and diversity factors will need to be adapted to take intoaccount the particular nature of the installation. This should be done by a qualified designer orengineer. For example, the connected load of industrial machinery in continuous operation would betaken as 100% unless it was mainly in night time operation, or had very short (few minutes) load cycles.Another example could be a warehouse with automatic motion operated lighting for energy saving,which may result in a diversity factor as low as 20%. Alternatively, the average load per m

    2of floor

    area can be used if such data is available from other similar premises.

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    7/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 7 of 40

    A6. Customer Earthed (TT) and Distribution CompanyEarthed Systems (TN-S)

    Figure A6 (a) Customer Earthed System (TT)

    Figure A6 (b) Distribution Company Earthed System (TN-S)

    L1

    L2

    L3

    N

    Customers

    Main

    Distribution

    BoardCustomers

    Main Earth

    Terminal

    E

    N

    L

    E

    Appliance Earth

    Distribution Company Transformer

    Transformer

    Neutral Point Earth

    Earth

    fault

    Earth fault

    current

    Customers

    Earth

    Electrode

    L1

    L2

    L3

    N

    Customers

    Main

    Distribution

    Board

    Customers

    Main Earth

    Terminal

    E

    N

    L

    E

    Appliance Earth

    Distribution Company Transformer

    Earth sheath or armour ofDistribution Company CableTransformer

    Neutral Point Earth

    Earth

    fault

    Earth fault current

    L1

    L2

    L3

    N

    Customers

    Main

    Distribution

    Board

    Customers

    Main Earth

    Terminal

    E

    N

    L

    E

    Appliance Earth

    Distribution Company Transformer

    Earth sheath or armour ofDistribution Company CableTransformer

    Neutral Point Earth

    Earth

    fault

    Earth fault current

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    8/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 8 of 40

    A7. Guidance Note on Principles of Electric ShockProtection and Earthing

    The Regulations include requirements which are designed to protect persons against electric shock insituations of both Direct and Indirect Contact with electrical voltages. Direct Contact is defined as theinadvertent or accidental contact with a live phase conductor (or neutral conductor that is connectedthrough a load to a live conductor).

    The term Indirect Contact refers to situations where a person is touching an Earthed Metallic Part of anAppliance, Installation, or other Extraneous Metallic Part which then becomes live (for a short time) dueto the passage of earth fault current. Such metallic parts could include the casing or cover of anAppliance such as a fridge or washing machine, the earthed parts of an Installation such as earthedmetal conduits, metallic switches or socket outlets, or other Extraneous Metallic Parts in a buildingwhich have been earthed, such as metal pipes.

    (a) Direct Contact:

    The risk of persons coming into contact directly with live phase conductors is mitigated against in thefollowing ways:

    (i) insulation of conductors (basic insulation)(ii) double insulation of conductors (Class II Appliances)(iii) secure enclosures, barriers or covers on all un-insulated parts (e.g. connection

    terminals, busbar sections etc)

    (iv) reduced voltage systems (SELV)(v) isolated (unearthed) systems (e.g. BS3535 shaver socket isolating transformer)(vi) limitation of contact time and current by use of a Residual Current Device

    The requirement for all occupied Premises to have overall earth leakage protection is new to theseRegulations. Previously, there was no provision for Protective Devices which could give protectionagainst Direct Contact with a live conductor.

    Note: overcurrent devices such as MCBs do not give protection against electric shock.In addition, RCDs do not give protection against electric shock between phase conductors or betweenphase conductors and earth, although this would be a rare occurrence.

    (b) Indirect Contact:

    Indirect Contact, through Earthed metallic parts, is mitigated against by:

    (i) ensuring that the voltage rise on earthed metal parts during the passage of faultcurrent is kept below a safe level (deemed to be 50V)

    (ii) ensuring that persons cannot be in contact with any two metallic parts which are at adifferent potential during the passage of earth fault current

    (iii) ensuring that a high resistance earth fault does not persist and is cleared by operation

    of earth leakage protection

    The diagram over leaf illustrates cases of Direct and Indirect Contact

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    9/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 9 of 40

    Figure A7 Cases of Direct and Indirect Contact which may lead to Electric Shock

    1 Direct Contact with live conductor2 Contact with external metallic part of Appliance during earth fault3 Contact with earthed metallic part of Electrical Installation during earth fault4 Contact between extraneous metallic part and earthed metallic part

    Note: Installations must be designed to keep the voltage rise on earthed metallic partsbelow 50V during the time of fault

    Customers

    Main

    DistributionBoard

    Customers

    Main Earth

    Terminal

    Appliance

    Earth fault

    Earth fault

    current

    Customers

    Earth Electrode

    (for TT system)

    Connection to earth

    sheath of Distribution

    Companys cable

    (TN-S system)

    L1L2L3N

    RCD

    N LE

    11

    2

    33

    44

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    10/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 10 of 40

    A8. Guidance Note on Earth Conductorsand Equipotential Bonding

    Earth Conductors

    Earth Conductors within Installations are a vital link for safety. They provide a path for current from a

    faulty line touching Extraneous Metallic Parts in a premises, or touching Exposed Metallic Parts of anAppliance to flow to Earth and back to the earthed neutral of the distribution transformer.

    Such earth currents can include short circuits, high resistance faults, as well as current flow due toDirect Contact with persons.

    The term Earth Conductor covers all of the following:

    main Earth Conductors:- conductors from Earth Electrodes to the Main Earth Terminal

    - conductors from the Main Earth Terminal to Distribution Boards

    circuit Earth Conductors:

    - conductors from Distribution Boards to Final Circuits and Applianceconnection points (also known as circuit Earth Conductors)

    appliance Earth Conductors:

    - conductors from Appliance connection points (e.g. 3 pin socket outlets)to an Appliance, normally within a sheathed cable or flex

    - conductors connecting Exposed Metallic Parts within an Appliance

    Other terminology which is confusingly used outside these Regulations includes: circuit protectiveconductor (CPC), earth continuity conductor (ECC), or earth wire.

    The main Earth Conductors in an installation are very important, since they provide the only route to theMain Earth Terminal or Earth Electrodes, and therefore must be safeguarded against damage,corrosion, accidental disconnection etc. They should be subject to regular inspection and testing.Connections to the Main Earth Terminal and Earth Electrodes should have a standard warning label asshown below:

    Figure A8(a) Standard Safety Label for main Earth connections

    Equipotential Bonding Conductors

    The purpose of Equipotential Bonding Conductors is to prevent the rise of dangerous voltage onextraneous metallic parts in a premises which may be touched by persons during the instant of a faultoccurring. In addition, Equipotential Bonding is a safeguard in the unlikely event of loss of the mainearth connection (either Customer Earth or Distribution Company Earth) whereby all metallic parts in apremises are kept at the same voltage, even if there is a rise of voltage above zero (assuming that anypersons inside a building cannot touch the physical Earth outside the premises).

    Main Equipotential Bonding Conductors are used to connect major metallic parts such as water pipesand other underground services that enter a building, see figure A8 (e) over leaf.

    Supplementary Equipotential Bonding Conductors are used to connect metal items in a premises thatare in high risk areas such as bathrooms, kitchens, semi-outdoor locations (e.g. garage). Theselocations are similar in that persons may be in contact with water or moisture when touching an earthedextraneous metallic part such as a water tap or pipe. Supplementary Equipotential Bonding

    conductors are connected to the nearest circuit Earth Conductor or main Earth Conductor rather thanback to the Main Earth Terminal, see figure A8 (d) over leaf. Supplementary Bonding conductors arenot required for standalone items which are not near to any electrical wiring, such as metal doors(unless part of the Electrical Installation), windows, small parts such as handles, brackets etc. As a

    SSAAFFEETTYY EEAARRTTHH CCOONNNNEECCTTIIOONN

    -- DDOO NNOOTT RREEMMOOVVEE

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    11/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 11 of 40

    main Earth Conductor

    customers Earth Electrode

    label at connection clamp

    letters at least

    5mm height SAFETY EARTH CONNECTION

    - DO NOT REMOVE

    inspection pit

    general rule, metal parts which are not near to electrical wiring and which have a resistance to earth of50 k ohms or greater, need not be connected to Equipotential Bonding.

    The standard sizing of Earth Conductors and Equipotential Bonding Conductors is given in appendixA11.

    Figure A8 (b) Types of Earth Conductors

    Figure A8 (c) Connection of Main Earth Conductor to Earth Electrode

    circuit Earth Conductor

    in Appliance flexible cord

    circuit Earth Conductor

    in Ring Circuit

    circuit Earth Conductors to

    accessories (even if plastic)

    circuit Earth Conductors

    alongside phase and neutral

    conductors

    Fixed appliances

    main Earth Conductor

    Main Earth

    Terminal

    Earth

    Bar

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    12/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 12 of 40

    Figure A8 (d) Connection of supplementary Equipotential Bonding Conductors

    Figure A8 (e) Connection of main Equipotential Bonding Conductors

    supplementary Equipotential

    Bonding Conductor

    SAFETY EARTH CONNECTION

    - DO NOT REMOVE

    label

    circuit Earth Conductors

    customers Main

    Earth Terminal

    incoming electricity supply

    (TN-S Earth System)

    main Earth

    Conductors

    SAFETY EARTH CONNECTION

    - DO NOT REMOVE

    label

    if lower section of pipe is insulated connect

    main Bonding Conductor at B rather than A

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    13/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 13 of 40

    A9. Electric Shock Protection Using Residual Current Devices

    The Regulations include a compulsory requirement for the provision of overall earth leakage protection,normally using an RCD, for any occupied Premises. Such devices must conform to the performancecharacteristics specified in BS4293, which requires that a device must operate within 40 milliseconds at5 times the nominal operating current, and should not operate at less than 50% of its nominal operatingcurrent.

    The performance characteristic of RCD devices is designed so as to reduce the risk of harmful electricshock to persons, either due to Direct Contact with a live conductor or due to Indirect Contact throughthe earthing of an Installation, Appliance, or Extraneous metallic part in a Premises. The risk to thehuman body depends on the time and magnitude of current that may pass at the time of an electricshock incident. The low risk and high risk range of current against time is illustrated below, along withthe operating times of typical RCD devices (from IEC60479).

    Figure A9(a) Time/current response of human body to Electric Shock, vs. RCD characteristics

    Response of human body:

    Zone 1: usually no reactionZone 2: shock sensation, but usually no harmful effectsZone 3: likelihood of muscular contraction, and temporary cardiac arrest without ventricular

    fibrillationZone 4: in addition to the effects of zone 3, the probability of ventricular fibrillation is increased by

    5% for curve C2 and 50% for curve C3; harmful effects such as cardiac arrest, breathingarrest and burns are likely to occur

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    14/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 14 of 40

    Figure A9(b) Illustration of operation of RCD devices (3 phase and 1 phase)

    Figure A9(c) DC sensing RCDsDue to the use of semiconductors devices in an Installation there may be situations when an earthfault current is not purely sinusoidal but contains a dc or chopped waveform. This may de-sensitiseor disable standard AC operated RCDs. Special devices are available which are designed tocontinue to function even for non-sinusoidal supply waveforms (complying with IEC1008, IEC1009).The following symbols are shown on RCDs along with the nominal trip current rating.

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    15/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 15 of 40

    A10. Performance Characteristics for MCBscomplying with BS EN 60898

    Figure A10(a) Current limiting performance data

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    16/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 16 of 40

    Figure A10(b) Time/current characteristic (type B, C and D circuit breakers)

    Figure A10(c) Internal Construction of MCB

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    17/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 17 of 40

    A11. Sizing of Earth Conductors and EquipotentialBonding Conductors

    Cross Sectional Area ofPhase and Neutral

    conductors (S)

    Minimum CrossSectional Area ofEarth Conductors

    Minimum Cross SectionalArea of EquipotentialBonding Conductors

    S

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    18/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 18 of 40

    A12. Number of Earth Electrodes Required for Installations

    The number of Earth Electrodes required at a Premises will be determined primarily by the value ofEarth Resistance that can be achieved from each. However, the minimum number in any case shall beas shown below:

    Main Incoming CircuitBreaker Rating (Amps)

    Minimum Number ofEarth Electrodes

    Minimum size ofEarth Conductors

    60/100 1 16

    200 1 50

    300 1 50

    400 1 70

    500 2 70

    600 2 70800 2 70

    1000 2 70

    1600 2 70

    2000 2 150

    2500 2 150

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    19/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 19 of 40

    A13. Mandatory Connections to Earth Conductors

    The following items must be connected to the circuit Earth Conductor, which should be providedseparately for each Final Circuit, insulated with green/yellow PVC sheath, be of the appropriate size(appendix A11) and be installed in the same conduits or routes as the phase and neutral conductors.

    Items where connections must be made to thecircuit Earth Conductor

    Distribution Boards - frame and external metallic parts,including door

    Metal conduits, trunking etc - at start and end of runs, atpulling points and inspection boxes

    Switchgear - frame and external metallic parts, doors etc

    Luminaires - external metallic parts2

    Switches - metallic parts, mounting boxes, cover plates1

    Socket outlets - metallic parts, mounting boxes, cover

    plates

    1

    Fixed appliances and machinery - external metallic parts(e.g. metal casing)

    Note 1: the earthing of cover plates should not rely solely on the connection offixing screws to an earthed mounting box (due to the possibili ty of poorconnections, corrosion etc); a short flexible earth conductor should be connectedbetween the mounting box and the plate

    Note 2: the circuit Earth Conductor should be terminated in the connection box fora Luminare even if it is plastic (in order to provide for future use)

    Figure A13 Circuit Earth Conductor connection to socket outlet and back box

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    20/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 20 of 40

    A14. Earth Leakage Protection for Equipment

    The table below shows the required nominal operating current values for RCDs and similar devices.These are intended to provide for electric shock protection, particularly in high risk areas, as well asprotection against high resistance earth faults which may not operate overcurrent devices and pose arisk of overheating or fire.

    The values may be varied in special circumstances with prior approval from the Distribution Company.However, an overall earth leakage protection device of nominal operating current 100mA is required inall occupied Premises (see Regulation 4.4.10 for exceptions).

    Equipment Nominal OperatingCurrent (mA)

    13A switched socket outlets 30

    Water heaters 30

    Kitchen fixed appliances (e.g. washing machine) 30

    Domestic water pumps 30

    Swimming pool pumps, or Jacuzzi 10

    Under water lighting 10

    General fixed lighting 100

    Flood lighting 100 - 300

    Window / split type air conditioning 100

    Air handling, a/c fan coils etc 100

    Central / package a/c units 100 - 300

    Chiller unit 100 - 500

    Irrigation pump 100

    Electric Cooker (not supplied by 13A socket outlet) 100

    Industrial machines etc 100 - 300

    Elevators, escalators, lifts 300 - 500

    Neon signs 300

    Note: where 2 values are indicated the higher value is allowed only where theequipment is not normally accessible to persons.

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    21/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 21 of 40

    A15. Earth Fault Loop Impedance

    Table A15(a) Maximum Earth Fault Loop Impedance for circuits connected by MCBs to give adisconnection time within 0.4 seconds

    - Maximum earth-fault loop impedance (Ohms)

    Devicerating

    (A)

    MCBtype 1

    MCBtype 2

    MCBtype 3

    and type C

    MCBtype B

    MCBtype D

    5 12.00 6.86 4.80 - 2.40

    6 10.00 5.71 4.00 8.00 2.00

    10 6.00 3.43 2.40 4.80 1.20

    15 4.00 2.29 1.60 - 0.80

    16 3.75 2.14 1.50 3.00 0.75

    20 3.00 1.71 1.20 2.40 0.60

    25 2.40 1.37 0.96 1.92 0.48

    30 2.00 1.14 0.80 - 0.40

    32 1.88 1.07 0.75 1.50 0.38

    40 1.5 0.86 0.60 1.20 0.30

    Table A15(b) Resistance per metre of copper conductors for calculation of R1 + R2

    Conductor cross-sectional area(mm)

    Resistance per metre run(m ohms / m)

    1.0 18.1

    1.5 12.10

    2.5 7.41

    4.0 4.61

    6.0 3.08

    10.0 1.83

    16.0 1.15

    25.0 0.727

    Note: to allow for the increase in resistance with increased temperature under faultconditions these values must be multiplied by 1.2 for p.v.c. insulated cables

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    22/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 22 of 40

    Figure A15(a) Formula for Earth Fault loop Impedance

    Zs = Ze + ZR1 + R2

    Where:

    Zs = total Earth Fault Loop Impedance

    Ze = Distribution Company supply impedance

    ZR1 + R2 = impedance of the longest circuit in the Installation, taken by measuring a circuit phaseconductor impedance R1, and the same circuits Earthing Conductor impedance R2.

    Figure A15(b) Illustration of Component Parts of Earth Fault loop Impedance

    l. - the phase conductor from the transformer to the installation

    2 -the protective device(s) in the installation3 -the installation phase conductors from the intake position to the fault4. - the fault itself (usually assumed to have zero impedance)5. - the circuit earth conductors6. - the main earthing terminal7. - the main earthing conductor8. - the installation earth electrode9. - the general mass of earth10. - the Distribution Company's transformer earth electrode11. - the Distribution Company's main earthing conductor12. -the secondary winding of the Distribution Company's transformer

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    23/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 23 of 40

    A16. Cable Ratings, Voltage Drop and Ambient TemperatureCorrection Factors

    Table A16(a) Standard cable ratings and Voltage drop for single core, PVC (thermoplastic), non-armoured, stranded copper conductor (BS6004 and BS6346), with or without sheath,installed in concealed or surface conduit.

    Crosssectional

    area

    In conduit inthermal

    insulation

    In conduitin thermalinsulation

    Inconduiton wall

    Inconduiton wall

    Voltdrop

    Voltdrop

    (mm) (A) (A) (A) (A) (mV/A/m) (mV/A/m)

    - 2 cables 3 or 4cables

    2cables

    3 or 4cables

    2 cables 3 or 4cables

    1.0 11.0 10.5 13.5 12.0 44.0 38.0

    1.5 14.5 13.5 17.5 15.5 29.0 25.0

    2.5 19.5 18.0 24.0 21.0 18..0 15.04.0 26.0 24.0 32.0 28.0 11.0 9.5

    6.0 34.0 31.0 41.0 36.0 7.3 6.4

    10.0 46.0 42.0 57.0 50.0 4.4 3.8

    16.0 61.0 56.0 76.0 68.0 2.8 2.4

    At 30oC ambient

    Table A16(b) Standard cable ratings and Voltage drop for multi-core core, PVC (thermoplastic)cables (BS6346)

    Crosssectional

    area

    In conduitin thermalinsulation

    In conduitin thermalinsulation

    Inconduiton wall

    Inconduiton wall

    Clippeddirect

    Clippeddirect

    Volt drop Volt drop

    (mm) (A) (A) (A) (A) (A) (A) (mV/A/m) (mV/A/m)

    - 2 core 3 or 4 core 2 core 3 or 4core

    2 core 3 or 4core

    2 core 3 or 4core

    1.0 11.0 10.0 13.0 11.5 15.0 13.5 44.0 38.0

    1.5 14.0 13.0 16.5 15.0 19.5 17.5 29.0 25.0

    2.5 18.5 17.5 23.0 20.0 27.0 24.0 18.0 15.0

    4.0 25.0 23.0 30.0 27.0 36.0 32.0 11.0 9.5

    6.0 32.0 29.0 38.0 34.0 46.0 41.0 7.3 6.4

    10.0 43.0 39.0 52.0 46.0 63.0 57.0 4.4 3.8

    16.0 57.0 52.0 69.0 62.0 85.0 76.0 2.8 2.4

    At 30oC ambient

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    24/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 24 of 40

    Table A16(c) Standard cable ratings and Voltage drop for mineral insulated cables

    Cross-sectional

    area

    p.v.c.sheath

    2 x singleor twin

    p.v.c.Sheath

    3 core

    p.v.c.Sheath 3 x

    single ortwin

    Baresheath 2

    x single

    Baresheath

    3 xsingle

    (mm) (A) (A) (A) (A) (A)

    1.0 18.5 16.5 16.5 22.0 21.0

    1.5 24.0 21.0 21.0 28.0 27.0

    2.5 31.0 28.0 28.0 38.0 36.0

    4.0 42.0 37.0 37.0 51.0 47.0

    1.0 20.0 17.5 17.5 24.0 24.0

    1.5 25.0 22.0 22.0 31.0 30.0

    2.5 34.0 30.0 30.0 42.0 41.0

    4.0 45.0 40.0 40.0 55.0 53.0

    6.0 57.0 51.0 51.0 70.0 67.0

    10.0 78.0 69.0 69.0 96.0 91.0

    16.0 104.0 92.0 92.0 127.0 119.0

    At 30oC ambient

    Table A16(d) Ambient temperature correction factors (relative to 30

    o

    C) for cable ratings[from tables 4C1 of BS7671:2001]

    Ambienttemperature

    Type of cable insulation

    (C) 70C PVC 85C rubber 70C mineralinsulated

    105C mineralinsulated

    25 1.03 1.02 1.03 1.02

    30 1.00 1.00 1.00 1.00

    35 0.94 0.95 0.93 0.96

    40 0.87 0.90 0.85 0.92

    45 0.79 0.85 0.77 0.8850 0.71 0.80 0.67 0.84

    55 0.61 0.74 0.57 0.80

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    25/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 25 of 40

    A17. Colour Identification of Cables

    Note: the European harmonised cable colours [BS EN 60446effective from Jan 2006] of Brown, Grey and Black for Phase 1,Phase 2, and Phase 3 have not been adopted for the Emirate ofAbu Dhabi

    A18. Capacity of Conduits and Trunking

    Note: for cable trays and trunking the space factor (total crosssectional area of cables vs. the interior cross section of trunking)shall not exceed 50%.

    Conductor Colour

    Non-flexible / fixed wiring and all 3 phase cables:

    Earth Conductors Green / yellow

    Phase 1 Red

    Phase 2 Yellow

    Phase 3 Blue

    Neutral Black

    Flexible cables for single phase Appliances:

    Earth Conductors Green / yellow

    Phase 1 Brown

    Neutral Blue

    Conductor (mm) Size of Conduit (mm)

    20 25 32

    Maximum number of conductors

    1.5 7 12 -

    2.5 5 9 12

    4.0 3 6 9

    6.0 - 5 8

    10.0 - 3 6

    16.0 - - 4

    25.0 - - 3

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    26/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 26 of 40

    A19. IP Coding for Ingress Protection

    The IP (Ingress Protection) system of coding provides a standardised interpretation of the level ofphysical protection that equipment or enclosures maybe designed for. The coding system is specifiedin BS EN 60529: 1992 (adopted from IEC 529: 1989).

    The first digit of the code specifies protection against ingress of foreign objects of varying size, rangingfrom hands / fingers to fine dust particles. The second digit specifies protection against ingress ofmoisture, ranging from free falling water, to immersion in water.

    BS EN 60529 does not specify protection against the risk of explosion, humidity and corrosive gases.

    If enclosures or equipment is drilled or knockouts removed, suitable measures should be taken torestore the equipment to the original IP rating.

    Typical Examples:

    (a) Domestic 13A socket outlet: IP 53(b) Outdoor extension lead & socket: IP 64(c) Outdoor weather-proof light switch: IP 66

    Ingress Protection - IP Codes

    First Digit -Protection against ingress by solid

    objects

    Second Digit -Protection against ingress by

    liquids

    X Not tested or not applicable X Not tested or not applicable

    0 No protection 0 No protection

    1 Human hand or objects > 50mm 1 Vertically dripping water

    2 Human finger or objects > 12mm 2 Sprays of water < 15o

    from

    vertical

    3 Objects > 2.5mm

    (e.g. tools or wires)

    3 Sprays of water < 60o

    from

    vertical

    4 Objects > 1.0mm

    (e.g. small wires)

    4 Splashes of water (from anydirection)

    5 Limited protection against dust(to the extent that does not harmthe equipment)

    5 Low pressure jets of water(from any direction)

    6 Totally protected against dust6 Strong jets of water (from any

    direction)

    7 Temporary immersion

    8 Total immersion

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    27/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 27 of 40

    A20. Standard Wiring Diagram Symbols

    Note: additional wiring symbols may be taken from BS EN 60617

    Symbol Description

    Main Distribution Board (MDB)

    Sub Main Distribution Board (SMDB)

    Distribution Board (DB)

    Air Circuit Breaker (ACB)

    Moulded Case Circuit Breaker (MCCB)

    Miniature Circuit Breaker (MCB)

    Earth Leakage Circuit Beaker (ELCB)

    Fuse

    Link

    kWh meter (direct reading)

    kWh meter (ct operated)

    Switched line (e.g. connecting all outletscontrolled by one switch)

    Circuit line (e.g. connecting all outlets on thesame circuit)

    13A switched socket outlet

    15A switched socket outlet

    20A double pole switch with neon indicator

    30A double pole switch

    Shaver socket to BS 3052

    Cooker control unit

    M

    M

    CCU

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    28/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 28 of 40

    WW

    Appendix A20 continued

    Note: additional wiring symbols may be taken from BS EN 60617

    Symbol Description

    Tungsten light fitting - ceiling mounted

    Tungsten light fitting - wall mounted

    Fluorescent light fitting - ceiling mounted

    Fluorescent light fitting - wall mounted

    Light switch - 1 way

    Light switch - 2 way

    Light switch - intermediate way

    Light switch - pull cord operated

    Light switch - key operated

    Light switch - weather proof type

    Exhaust fan

    Ceiling mounted fan

    Low level cooker outlet connection

    Earth connection

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    29/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 29 of 40

    Main

    Distribution

    Board

    Main cable

    Earth

    Conductor

    Main cable

    pulling pit

    600 x 600

    Earth cable pit

    300 x 300

    13A socket

    outlet

    Meters

    Capacitor

    bank

    Louvered door (for

    non-air conditioned room

    A21. Typical Layout for Supply Intake Room

    Standard Size of Supply Intake Rooms

    Main Circuit Breaker Rating Intake Room Dimension(metres)

    600A - 1000A 2.5 x 2.5

    350A - 600A 2.5 x 2.0

    100A - 300A 2.0 x 2.0

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    30/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 30 of 40

    Fused spur to

    fixed appliance

    Spur socket outlet

    To Final DB

    Spur socket

    outlets

    Fused spur to

    fixed appliance

    Spur socket outlet

    To Final DB

    Spur socket

    outlets

    A22. Typical Layout for Ring Circuits

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    31/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 31 of 40

    A23. Approved and Prohibited Plugs and Socket Types

    A23(a) Approved BS1363 plug and socket

    A23(b) Approved BS546 plug and socket (for non-domestic only)

    A23(c) Prohibited CEE7/7 shuko plug and socket

    A23(d) Type CEE7/14 europlug permitted only with a correct adapter

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    32/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 32 of 40

    A24. Minimum Recommended Number of Socket Outlets

    Room Minimum number of outlets

    Kitchen:

    13A switched socket outlets

    20A spur connection points(for washing machine, dryer etc)

    45A cooker control unit

    4

    4

    1

    Bedrooms 4

    Lounge / dining 4

    Hall / corridor 1

    Bathrooms Only BS3535 shaversocket

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    33/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 33 of 40

    A25. Method for Measuring Earth Resistance

    (i) a proprietary earth electrode test device should be used

    (ii) auxiliary earth spikes should be applied at least 5m apart and 5m distant from theelectrode under test

    (iii) a earth resistance value of less than 5 ohms is required for a Customer EarthedSystem

    (iv) an additional number of electrodes may be required (or deeper electrodes) toachieve the required earth resistance value

    (v) due consideration should be given to future changes in soil condition (e.g. dryingout)

    (vi) sufficient time should be allowed if special chemicals or salts are added to theground to improve the earth resistance values

    A26. Method for Earth Loop Impedance Test

    (i) Earth Fault Loop Impedance may be measured directly at the Supply Intake by

    specialist instruments(ii) alternatively, if the external loop impedance is known, this may be added to the

    R1 + R2 test, to determine the total Earth Fault Loop Impedance

    (iii) the main circuit breaker should be open and the test link at the Main EarthTerminal should be opened for these tests

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    34/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 34 of 40

    A27. Method for Continuity Tests

    (i) All Earth Conductors, phase conductors and neutral conductors should bechecked

    (ii) A low reading ohmmeter is required capable of reading down to 0.01 ohms, andproducing a test current of 200mA, and having an open circuit voltage of 4 to 24volts

    (iii) Measurement of R1+R2 (phase conductor resistance + earth conductorresistance) can be made for each circuit by bridging phase and earth terminals atthe relevant Distribution Board and measuring the resistance between phase andearth terminals at the most remote connection point or socket outlet

    (iv) separate values of R1 and R2 can be made using a long test lead so thatmeasurement is directly from one end of each conductor to the other (note: theresistance of the test leads should be subtracted from the result)

    (v) testing of Earth Bonding Conductors should be made using the long lead method

    A28. Method for Insulation Resistance Test

    (i) Insulation resistance should be checked between all live conductors, and betweenlive conductors and Earth

    (ii) the test instrument should be capable of producing a d.c. test voltage of 500Vwhen loaded to 1mA and be capable of measurement of up to 200Mohm

    (iii) the minimum acceptable value of insulation resistance for any test is 0.5Mohm

    (iv) the supply should be disconnected and all current using equipment switched off(including neon indicator lamps, and voltmeters mounted on Distribution Boardsetc)

    (v) insulation measurements should be taken from each Distribution Board betweeneach pair of phases in turn, between each phase and neutral, and between eachphase and Earth

    (vi) a final test should be made between the neutral bar and earth; if a reading of lessthan 2Mohm is observed, then each neutral conductor should be tested separatelyto Earth.

    A29. Method for Polarity Tests

    (i) the polarity test is required to confirm that all single pole devices, and lampholders with an outer neutral contact (i.e. ES screw type) are correctly connected

    (ii) single pole devices must only be connected in the live conductor and the neutralconductor of all circuits must be continuous

    (iii) the test method used is the same as for the continuity test (appendix A27).

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    35/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 35 of 40

    A30. Installation Certificate

    Project / Building Name: .............................................................................................. Document No. / Ref. .............

    Address / Location: ...............................................................................................

    Details of Client / Customer:..

    ..

    Account No. etc ..

    Contact Details: ..

    New or modified installation: New: Modification: Existing:

    If modification or extension, quote original Installation Certificate number: .

    Brief description of modification or extension work: ..

    ....

    Details of Designer: ..

    Contact Details: ..

    We hereby declare that the work completed by us in relation to the above named installation, and detailed in thereference drawings and documents listed below, has been carried out with due skill and care, and in accordance with theElectricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water and Electricity Sectorin Abu Dhabi:

    Authorized Signatory & name: Date: ...

    Reference drawings and schedules:

    Company Stamp: ..

    Supply Characteristics:Earthing System: (Local or Company Earth)........ Earth Electrode(s) Resistance: ..

    Incoming Cable Size & Type: ... Earth Electrode(s) Location: .

    Main CB type & rating: ... Main Earth Conductor Size: ...

    Main Earth Protection Device, rating: ... Earth Loop Impedance: ......

    Main Distribution Board type & rating: Max Prospective Fault Current: .

    Sub & final DBs ref, nos: ................... Total Connected Load:

    Load Distribution Schedules attached: ...

    Meter ref. nos and type: ...................................................................................................................................

    Details of Installer: ..

    Contact Details: ..

    We hereby declare that the work completed by us in relation to the above named installation, and detailed in thereference drawings and documents listed below, has been carried out with due skill and care, and in accordance with theElectricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water and Electricity Sectorin Abu Dhabi:

    Authorized Signatory & name: Date: ...

    Reference drawings and schedules:

    Company Stamp: ..

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    36/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 36 of 40

    A31. Inspection Report

    Project / Building Name: .............................................................................................. Document No. / Ref. .............

    Address / Location: ..........................................................................................................

    Customer/owner: ..

    Contact Details: ..

    New or modified or existing installation: New: Modification: Existing:

    Original Installation Certificate number: .

    Brief description of modification or extension work: ..

    ....

    Inspected & tested by: ..

    Contact Details: ..

    We hereby declare that the inspection and testing completed by us in relation to the above named installation, anddetailed in the reference documents listed below, has been carried out with due skill and care, and in accordance with theElectricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water and Electricity Sectorin Abu Dhabi:

    Authorized Signatory & name: Date: ...

    Reference drawings and schedules:

    Company Stamp: ..

    Supply Characteristics:

    Earthing System: (Local or Company Earth)........ Earth Electrode(s) Resistance: ..

    Incoming Cable Size & Type: ... Earth Electrode(s) Location: .

    Main CB type & rating: ... Main Earth Conductor Size: ...

    Main Earth Protection Device, rating: ... Earth Loop Impedance: ......

    Main Distribution Board type & rating: Max Prospective Fault Current: .

    Sub & final DBs ref, nos: ................... Total Connected Load:

    Load Distribution Schedules attached: ...

    Meter ref. nos and type: ...................................................................................................................................

    General Details of Inspection & Testing

    Date of last inspection & test: ...................................................................

    Any modifications noted: ...................................................................

    Have modifications been recorded: Yes / No details: ..................................

    Age of installation & estimated age of modifications: ..................................

    Date of next inspection: .............................................................................................

    Any dangerous conditions or urgent work required (give details over leaf): Yes / No

    Any work or improvements recommended (give details over leaf): Yes / No

    Extent of inspection All: Part:

    Areas not tested / inspected: ...................................................................................

    Criteria of Inspections:

    For each of the items listed over leaf the following visual checks have been completed:

    (a) Protection against direct contact (insulation of live parts, adequate barriers and enclosures)

    (b) Protection against indirect contact (presence of earthing conductors, equi-potential bondingconductors, presence of earth leakage devices ELCB or RCD)

    (c) Correct positioning of apparatus for safe access and security (including proximity of other servicessuch as alarm systems, water, telephone, gas etc)

    (d) Correct signs, warnings and identification labels on all equipment and circuits

    (e) Overall condition of apparatus (signs of aging or deterioration to be noted)

    (f) Integrity of all connections, no signs of overheating or overloading

    [quote non compliance with Regulations, para. no. where required]

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    37/40

    CONSULTATION VERSION 0.1

    The Electricity Wiring Regulations 2007 APPENDICES - page 37 of 40

    Inspection Report (continued)

    Equipment Inspected: satisfactory not satisfactory (give details / comments)

    not applicable urgent work required

    Main intake room condition: .....................................................................

    Metering Equipment: .....................................................................

    Main Distribution Board: .....................................................................

    Main Isolation Device (CB): .....................................................................

    Main LV switchboard (if any): .....................................................................

    Incoming supply cable(s): .....................................................................

    Main earth conductor and earth pits: .....................................................................

    Sub Distribution Boards (give ref. nos): .....................................................................

    .....................................................................

    .....................................................................Final Distribution Boards: .....................................................................

    .....................................................................

    .....................................................................

    Distribution Cables (between DBs): .....................................................................

    .....................................................................

    Main Earth Leakage Device: .....................................................................

    Circuit cables (where visible): .....................................................................

    Power factor correction equipment: .....................................................................

    Standby generation equipment: .....................................................................

    .....................................................................

    Power points & socket outlets: .....................................................................

    Plugs & flexible cords: .....................................................................

    Any Appliances inspected: .....................................................................

    Internal Inspection of sample points (10% sample recommended):

    List circuit connections inspected: .....................................................................

    .....................................................................

    List lighting points inspected: .....................................................................

    .....................................................................Power points & socket outlets inspected: .....................................................

    .....................................................

    .....................................................

    Deviation from Wiring Regulations & Special Notes:

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    38/40

    The Electricity Wiring Regulations 2007 APPENDICES - page 38 of 40

    A32. Testing Report

    Project / Building Name: .......................................................................................................... Document No. / Ref. .................... Te

    Address / Location: .......................................................................................................... Tested by .................................. Lo

    Distribution Board No. / Ref. .......................................................................................................... Date: ...................... Co

    Fed from: .......................................................................................................... Date: ...................... Ins

    Continuity Test (ohms) Insulation Resistance(M-ohms)

    CCTIdentity

    No.

    CCTref.No.

    MCBrating

    (A)

    Wiresize(cct.)mm

    2

    Wiresize

    (ecc.)mm

    2

    Circuit name

    R1 + R2 R2 Ring L-L Live-EarthPolarity

    Deviation from Wiring Regulations & Special Notes:

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    39/40

    The Electricity Wiring Regulations 2007 APPENDICES - page 39 of 40

    A33. Load Distribution Schedule

    Project / Building Name: ..........................................................................................................

    Address / Location: ..........................................................................................................

    Distribution Board No. / Ref. ........................................ Incoming Cable size / type and ECC: ..........................................................

    Fed from: ........................................ Main breaker type & rating: ....................................................................................

    CCTIdentity

    No.

    CCTref.No.

    MCBrating

    (Amps)

    Phase &Neutral

    Sizemm

    2

    EarthConductorsize mm

    2

    Circuit name/ Point reference

    No. ofpoints

    Wattsper

    point

    R1

    Y1

    B1

    R2

    Y2

    B2

    R3

    Y3

    B3

    TOTAL CONNECTED LOAD _ _ _ _ _ kW Re

    TOTAL LOAD AFTER DIVERSITY _ _ _ _ _ kW Re

  • 8/3/2019 UAE Earthing Appendices Electricity Wiring Regulations 5-8-200703 51 179552500

    40/40

    CONSULTATION VERSION 0.1