20 10 S c h o o l o f E l e c t r i c a l E n g i n e e r i n g & T e l e c o m m u n i c a t i o n s UNSW ENGINEERING @ UNSW 10 Author – Alan Pak Lon Ao (z3235241) Supervisor – Dr. Toan Phung Assessor: Dr. Jayashri Ravishankar UHF detection of partial discharge in oil–insulated power transformers All power equipments need good insulating systems to prevent dielectric breakdown and unwanted current flow between conductors. Partial Discharge (PD) is a one of the usual disasters which partially bridges the insulating material between conductors. Online monitoring of PD is significant for preventing power transformer failure that may lead to huge economic loses. One way of PD detection is via capturing the emitted electromagnetic (EM) waves during discharge by ultra high frequency (UHF) antennas. The problem statement is defined as: Detecting and localizing PD inside oil-insulated transformers using UHF method. The high-level structure of UHF detection system is presented by a four-step approach as following: 1.Electromagnetic waves generated by PD 2.Signals detected by UHF Antennas 3.Waveforms stored by oscilloscope 4.Data analysed by computer program Hence, the two main objectives are classified as designing a type of UHF antenna and developing a series of MATLAB ® functions which helps to localize PD. 10cm-diameter log spiral Antenna Micro strip type antenna is preferable since it provides good uniformity. The size of antenna should be limited as one or more of them will be installed inside transformer tanks. The physical looking of log spiral is shown in the following figure. Simulations of varies design parameters have been completed to obtain the best possible response with the size constraint. More simulations for other micro strip type antenna have also been carried out. Log spiral (middle in figure above) is concluded as the best among log periodic and spiral. A balun (left in figure above) is needed for connecting antenna with an Four log spirals are placed coplanar on an antenna array (left in figure below) which is expected to overcome the issues of reflection and obstruction inside transformer tanks. An artificial corona partial discharge (middle in figure below) has been set up and immersed in oil during experiment. The antenna array is installed in air gap half way between the oil level and the lid. The model of UHF detection system is shown in the circuit diagram below. Wavelet de-noising The signal and noise manifest differently in the post- decomposition results. The noise components are hence possible to be distinguished as they have lower energy level. PD arrival time estimation Correlative first-peak energy method estimates the time shift of first arrived PD energy between antennas. Two level space-grid-search Light of sight propagation is assumed and different propagation speeds in respective media have been counted in. The best possible PD location is estimated by minimizing the differences between actual and measured time delay. The experiment results have shown that this UHF detection system is able to identify the existence of partial discharge. The arrival order of PD signals can be successfully determined by correlative first-peak energy method. However, the noticeable errors in arrival time could not made estimating PD location completely reliable (S=57.1%). De-noised waveforms are proven to be more effective for localization (S=71.4%). Future works such as employing more sensors in antenna array and a higher Genera te Detect Store Analys e Background and problem statement Approaches and objectives Antenna construction Experiment setup Data analysis Results discussion and future works

UHF detection of partial discharge in oil–insulated power transformers

  • Upload
    bella

  • View
    42

  • Download
    6

Embed Size (px)

DESCRIPTION

UHF detection of partial discharge in oil–insulated power transformers. 10. Author – Alan Pak Lon Ao (z3235241) Supervisor – Dr. Toan Phung Assessor: Dr. Jayashri Ravishankar. - PowerPoint PPT Presentation

Citation preview

Page 1: UHF detection of partial discharge  in oil–insulated power transformers

2010

School of Electrical Engineering &

Telecomm

unications

UNSW ENGINEERING @

UNSW

10Author – Alan Pak Lon Ao (z3235241)Supervisor – Dr. Toan Phung Assessor: Dr. Jayashri Ravishankar

UHF detection of partial discharge in oil–insulated power transformers

All power equipments need good insulating systems to prevent dielectric breakdown and unwanted current flow between conductors. Partial Discharge (PD) is a one of the usual disasters which partially bridges the insulating material between conductors. Online monitoring of PD is significant for preventing power transformer failure that may lead to huge economic loses. One way of PD detection is via capturing the emitted electromagnetic (EM) waves during discharge by ultra high frequency (UHF) antennas.

The problem statement is defined as:Detecting and localizing PD inside oil-insulated transformers using UHF method.

The high-level structure of UHF detection system is presented by a four-step approach as following:

1. Electromagnetic waves generated by PD2. Signals detected by UHF Antennas3. Waveforms stored by oscilloscope4. Data analysed by computer program

Hence, the two main objectives are classified as designing a type of UHF antenna and developing a series of MATLAB® functions which helps to localize PD.

10cm-diameter log spiral AntennaMicro strip type antenna is preferable since it provides

good uniformity. The size of antenna should be limited as one or more of them will be installed inside transformer tanks. The physical looking of log spiral is shown in the following figure.

Simulations of varies design parameters have been completed to obtain the best possible response with the size constraint. More simulations for other micro strip type antenna have also been carried out. Log spiral (middle in figure above) is concluded as the best among log periodic and spiral.

A balun (left in figure above) is needed for connecting antenna with an unbalanced transmission line and also transforming the impedance of antenna to match up with the impedance of transmission line. Its design is based on a Chebyshev multi-section impedance transformer circuit. The overall performance of built antenna has been tested for verifying the consistence with simulated result.

Four log spirals are placed coplanar on an antenna array (left in figure below) which is expected to overcome the issues of reflection and obstruction inside transformer tanks. An artificial corona partial discharge (middle in figure below) has been set up and immersed in oil during experiment. The antenna array is installed in air gap half way between the oil level and the lid.

The model of UHF detection system is shown in the circuit diagram below.

• Wavelet de-noisingThe signal and noise manifest differently in the post-decomposition results. The noise components are hence possible to be distinguished as they have lower energy level.

• PD arrival time estimationCorrelative first-peak energy method estimates the time shift of first arrived PD energy between antennas.

• Two level space-grid-searchLight of sight propagation is assumed and different propagation speeds in respective media have been counted in. The best possible PD location is estimated by minimizing the differences between actual and measured time delay.

The experiment results have shown that this UHF detection system is able to identify the existence of partial discharge. The arrival order of PD signals can be successfully determined by correlative first-peak energy method. However, the noticeable errors in arrival time could not made estimating PD location completely reliable (S=57.1%). De-noised waveforms are proven to be more effective for localization (S=71.4%).

Future works such as employing more sensors in antenna array and a higher sampling rate oscilloscope are expected to improve accuracy in localization. The application can be further expanded to identify Pd types.

Generate Detect Store Analyse

Background and problem statement

Approaches and objectives

Antenna construction

Experiment setup

Data analysis

Results discussion and future works