80
Drive Technology \ Drive Automation \ System Integration \ Services Manual UHX71B Controller (Performance Class power) with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN

UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

  • Upload
    others

  • View
    39

  • Download
    0

Embed Size (px)

Citation preview

Page 1: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Drive Technology \ Drive Automation \ System Integration \ Services

Manual

UHX71B Controller (Performance Class power) with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET)

Edition 04/2013 20101341 / EN

Page 2: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

SEW-EURODRIVE—Driving the world

Page 3: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 3

Contents

Contents1 General information ............................................................................................ 7

1.1 How to use this documentation................................................................... 71.2 Structure of the safety notes ....................................................................... 7

1.2.1 Meaning of signal words .............................................................. 71.2.2 Structure of the section safety notes ........................................... 71.2.3 Structure of the embedded safety notes...................................... 7

1.3 Rights to claim under warranty ................................................................... 81.4 Content of the documentation..................................................................... 81.5 Exclusion of liability..................................................................................... 81.6 Other applicable documentation ................................................................. 81.7 Product names and trademarks.................................................................. 81.8 Copyright..................................................................................................... 9

2 Safety Notes ...................................................................................................... 102.1 General information .................................................................................. 102.2 Target group ............................................................................................. 102.3 Bus systems.............................................................................................. 112.4 Functional safety technology .................................................................... 112.5 Hoist applications...................................................................................... 11

3 Introduction ....................................................................................................... 123.1 Content of this manual .............................................................................. 123.2 Characteristics .......................................................................................... 12

3.2.1 Process data exchange ............................................................. 123.2.2 Parameter access...................................................................... 123.2.3 Monitoring functions................................................................... 12

4 Assembly and Installation Notes for Ethernet ............................................... 134.1 Connecting the UHX71B-OSR71B controller to an Ethernet network ...... 134.2 Pin assignment X21 and X22.................................................................... 13

4.2.1 Connection controller / Ethernet ................................................ 144.3 Shielding and routing bus cables .............................................................. 144.4 The integrated Ethernet switch ................................................................. 15

4.4.1 Auto-crossing............................................................................. 154.4.2 Auto-negotiation......................................................................... 154.4.3 Notes on multicast handling....................................................... 15

4.5 Status LED ............................................................................................... 154.5.1 Status LED in EtherNet/IP operation ......................................... 154.5.2 Status LED in PROFINET operation.......................................... 164.5.3 Link/Activity LED........................................................................ 17

Page 4: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

4 Manual – UHX71B Controller with OSR71B Fieldbus Interface

Contents

4.6 TCP/IP addressing and subnetworks........................................................ 184.6.1 Introduction ................................................................................ 184.6.2 MAC address ............................................................................. 184.6.3 IP address.................................................................................. 184.6.4 Network classes......................................................................... 194.6.5 Subnet mask.............................................................................. 194.6.6 Standard gateway...................................................................... 204.6.7 DHCP (Dynamic Host Configuration Protocol) .......................... 20

4.7 Setting the IP address parameters ........................................................... 204.7.1 Initial startup .............................................................................. 204.7.2 Changing the IP address parameters after successful

initial startup............................................................................... 204.7.3 Deactivating / activating the DHCP............................................ 21

4.8 Replacing the unit ..................................................................................... 21

5 Configuration and Startup (EtherNet/IP)......................................................... 225.1 Validity of the EDS file for UHX71B-OSR71B........................................... 225.2 Configuring the master (EtherNet/IP scanner) .......................................... 22

5.2.1 Process data exchange ............................................................. 235.2.2 Other settings ............................................................................ 25

5.3 Settings in the UHX71B-OSR71B controller ............................................. 255.3.1 Process data configuration Ethernet/IP slave and

modbus/TCP.............................................................................. 255.3.2 Status of the Ethernet/IP fieldbus interface .............................. 265.3.3 Checking the process data communication ............................... 27

5.4 Configuration examples in RSLogix5000.................................................. 275.4.1 UHX71B-OSR71B with 16 PD data exchange .......................... 27

6 Ethernet Industrial Protocol (EtherNet/IP) ...................................................... 296.1 Introduction ............................................................................................... 296.2 Process data exchange ............................................................................ 29

6.2.1 Timeout response...................................................................... 296.3 CIP object directory................................................................................... 30

6.3.1 Identity object............................................................................. 306.3.2 Message router object ............................................................... 316.3.3 Assembly object......................................................................... 326.3.4 TCP/IP interface object.............................................................. 336.3.5 Ethernet link object .................................................................... 33

6.4 General Error Codes................................................................................. 35

7 Configuration and Startup (Modbus/TCP) ...................................................... 367.1 Configuration for the master (Modbus scanner) ....................................... 36

7.1.1 Hardware configuration.............................................................. 367.1.2 Settings for the Ethernet component ......................................... 377.1.3 Addressing the drive using I/O scanning ................................... 38

7.2 Settings in the UHX71B-OSR71B controller ............................................. 397.2.1 Process data configuration ........................................................ 39

Page 5: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 5

Contents

7.3 Project planning example in PL7 PRO...................................................... 397.3.1 UHX71B-OSR71B controller with 16 PD data exchange........... 39

7.4 Examples for data exchange via Modbus/TCP......................................... 417.4.1 Writing and reading process data .............................................. 42

8 Modbus Protocol (Modbus/TCP) ..................................................................... 448.1 Introduction ............................................................................................... 44

8.1.1 Mapping and addressing ........................................................... 448.1.2 Services (function codes) .......................................................... 458.1.3 Access ....................................................................................... 45

8.2 Protocol structure...................................................................................... 458.2.1 Header ....................................................................................... 468.2.2 Service FC3 – Read Holding Registers ..................................... 478.2.3 FC16 – Write Multiple Registers ................................................ 488.2.4 Service FC23 – Read/Write Multiple Registers ......................... 498.2.5 Service FC43 - Read Device Identification ................................ 50

8.3 Connection management.......................................................................... 518.3.1 Sending process output data (requesting controlling

connection) ................................................................................ 518.3.2 Dropping connections ................................................................ 518.3.3 Timeout monitoring .................................................................... 51

9 Error Diagnostics for Operation on EtherNet/IP and Modbus/TCP .............. 529.1 Diagnostic procedure ................................................................................ 52

9.1.1 Step 1: Checking the LED status............................................... 529.1.2 Step 2: Check the Status LED and the Status display of the

master (scanner)........................................................................ 529.1.3 Step 3: Error diagnostics ........................................................... 52

10 PROFINET IO Configuration............................................................................. 5410.1 Installing the GSDML file for UHX71B-OSR71B....................................... 5410.2 Assigning a PROFINET device name....................................................... 5510.3 Configuring the PROFINET interface for the UHX71B-OSR71B

controller ................................................................................................... 5610.3.1 Creating a new project............................................................... 5610.3.2 Configuring a node .................................................................... 58

10.4 PROFINET configuration with topology detection..................................... 5910.4.1 Introduction ................................................................................ 5910.4.2 Creating a PROFINET IO project and starting the topology

editor.......................................................................................... 5910.4.3 Specifying the topology and detecting faulty connections ......... 6010.4.4 Changing port properties ........................................................... 6210.4.5 Topology diagnostics ................................................................. 6410.4.6 Port statistics ............................................................................. 65

11 Operating Behavior on PROFINET IO ............................................................. 6711.1 Process data exchange with the SEW controller ...................................... 67

11.1.1 Control example for SIMATIC S7 .............................................. 67

Page 6: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

6 Manual – UHX71B Controller with OSR71B Fieldbus Interface

Contents

11.2 Settings in the UHX71B-OSR71B controller ............................................. 6911.2.1 Process data configuration of the PROFINET slave.................. 6911.2.2 Status of the PROFINET fieldbus interface .............................. 6911.2.3 Checking the process data communication ............................... 70

12 Error Diagnostics on PROFINET ..................................................................... 7112.1 Diagnostic procedures .............................................................................. 71

12.1.1 Diagnostic problem 1: UHX71B-OSR71B does not work on PROFINET IO............................................................................ 72

12.1.2 Diagnostic problem 2: No process data exchange with the I/O controller .................................................................................... 73

13 Appendix............................................................................................................ 7413.1 Overview of parameters ........................................................................... 74

13.1.1 Bus independent parameters..................................................... 7413.1.2 Bus dependent parameters ....................................................... 75

Index................................................................................................................... 76

Page 7: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 7

1How to use this documentationGeneral information

1 General information1.1 How to use this documentation

The documentation is an integral part of the product and contains important informationon operation and service. The documentation is written for all employees who assemble,install, start up, and service this product.

The documentation must be accessible and legible. Make sure that persons responsiblefor the system and its operation, as well as persons who work independently on the unit,have read through the documentation carefully and understood it. If you are unclearabout any of the information in this documentation, or if you require further information,contact SEW-EURODRIVE.

1.2 Structure of the safety notes1.2.1 Meaning of signal words

The following table shows the grading and meaning of the signal words for safety notes,warnings regarding potential risks of damage to property, and other notes.

1.2.2 Structure of the section safety notesSection safety notes do not apply to a specific action but to several actions pertaining toone subject. The symbols used either indicate a general hazard or a specific hazard.

This is the formal structure of a section safety note:

1.2.3 Structure of the embedded safety notesEmbedded safety notes are directly integrated in the instructions just before the descrip-tion of the dangerous action.

This is the formal structure of an embedded safety note:

• SIGNAL WORD Type and source of danger.

Possible consequence(s) if disregarded.

– Measure(s) to prevent the danger.

Signal word Meaning Consequences if disregardedDANGER Imminent danger Severe or fatal injuries

WARNING Possible dangerous situation Severe or fatal injuries

CAUTION Possible dangerous situation Minor injuries

NOTICE Possible damage to property Damage to the drive system or its envi-ronment

INFORMATION Useful information or tip: Simpli-fies the handling of the drive system.

SIGNAL WORDType and source of danger.

Possible consequence(s) if disregarded.• Measure(s) to prevent the danger.

Page 8: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

8 Manual – UHX71B Controller with OSR71B Fieldbus Interface

1 Rights to claim under warrantyGeneral information

1.3 Rights to claim under warrantyA requirement of fault-free operation and fulfillment of any rights to claim under limitedwarranty is that you adhere to the information in the documentation. Therefore read thedocumentation before you start working with the unit.

1.4 Content of the documentationThis document contains additional safety-related information and conditions for opera-tion in safety-related applications.

1.5 Exclusion of liabilityYou must comply with the information contained in this documentation to ensure safeoperation and to achieve the specified product characteristics and performance fea-tures. SEW-EURODRIVE assumes no liability for injury to persons or damage to equip-ment or property resulting from non-observance of these operating instructions. In suchcases, any liability for defects is excluded.

1.6 Other applicable documentationObserve the following applicable documents:

• "Controller UHX71B (performance class power)" manual

• "MOVI-PLC® Programming in the PLC Editor" manual

The following publications and documents apply to the connected units:

• Operating instructions of the units

(Units are, for example, MOVIDRIVE® B, MOVITRAC® B, MOVIAXIS®)

• For units with functional safety technology, also the respective

"Functional Safety" manuals

Make sure you always use the latest documentation.

Our documentation is available in various languages for download from the SEWhomepage (www.sew-eurodrive.com). If you are unclear about any of the information inthis documentation or if you require further information, consult SEW-EURODRIVE.

If required, you can order printed copies of the documentation from SEW-EURODRIVE.

1.7 Product names and trademarksAll product names in this documentation are trademarks or registered trademarks oftheir respective titleholders.

Page 9: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 9

1CopyrightGeneral information

1.8 Copyright© 2013 – SEW-EURODRIVE. All rights reserved.

Unauthorized duplication, modification, distribution or any other use of the whole or anypart of this documentation is strictly prohibited.

Page 10: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

10 Manual – UHX71B Controller with OSR71B Fieldbus Interface

2 General informationSafety Notes

2 Safety Notes2.1 General information

The following basic safety notes must be read carefully to prevent injury to persons anddamage to property. The operator must ensure that the basic safety notes are read andadhered to.

Ensure that persons responsible for the machinery and its operation as well as personswho work independently have read through the documentation carefully and understoodit. If you are unclear about any of the information in this documentation or if you requirefurther information, please contact SEW-EURODRIVE.

The following safety notes refer to the use of the software. Also adhere to the supple-mentary safety notes in this document and in the documentation of the connecteddevices from SEW-EURODRIVE.

This document does not replace the detailed documentation of the connected devices.This document assumes that the user has access to and is familiar with the documen-tation for all connected devices from SEW-EURODRIVE.

Never install or start up damaged products. Submit a complaint to the shipping companyimmediately in the event of damage.

During operation, the devices may have live, uninsulated, and sometimes moving orrotating parts as well as hot surfaces depending on their degree of protection.

Removing covers without authorization, improper use as well as incorrect installation oroperation may result in severe injuries to persons or damage to property. Refer to thedocumentation for additional information.

2.2 Target groupAny work with the software may only be performed by adequately qualified personnel.Qualified personnel in this context are persons who have the following qualifications:

• Appropriate instruction.

• Knowledge of this documentation and other applicable documentation.

• SEW-EURODRIVE recommends additional product training for products that areoperated using this software.

Any mechanical work on connected units may only be performed by adequately quali-fied personnel. Qualified personnel in the context of this documentation are personsfamiliar with the design, mechanical installation, troubleshooting and servicing of theproduct who possess the following qualifications:

• Training in mechanical engineering, e.g. as a mechanic or mechatronics technician(final examinations must have been passed).

• Knowledge of this documentation and other applicable documentation.

Page 11: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 11

2Bus systemsSafety Notes

Any electrical work on connected units may only be performed by adequately qualifiedelectricians. Qualified electricians in the context of this documentation are personsfamiliar with electrical installation, startup, troubleshooting and servicing of the productwho possess the following qualifications:

• Training in electrical engineering, e.g. as an electrician or mechatronics technician(final examinations must have been passed).

• Knowledge of this documentation and other applicable documentation.

• Knowledge of the relevant safety regulations and laws.

• Knowledge of the other standards, guidelines, and laws mentioned in this documen-tation.

The above mentioned persons must have the authorization expressly issued by thecompany to operate, program, configure, label and ground units, systems and circuits inaccordance with the standards of safety technology.

All work in further areas of transportation, storage, operation and waste disposal mustonly be carried out by persons who are trained appropriately.

2.3 Bus systemsA bus system makes it is possible to adapt frequency inverters and/or motor starters tothe specific conditions of the machinery within wide limits. This results in the risk that achange of parameters that cannot be detected externally can result in unexpected,though not uncontrolled, system behavior.

2.4 Functional safety technologyThe inverters and servo drives controlled by the SEW controller may not execute anysafety functions without higher-level safety systems unless they are described in the rel-evant documentation and expressly approved.

Use higher-level safety systems to ensure protection of equipment and personnel.

2.5 Hoist applicationsMOVIDRIVE® B, MOVITRAC® B, MOVIAXIS®, MOVIPRO® and MOVIFIT® must not beused as a safety device in hoist applications.

Use monitoring systems or mechanical protection devices as safety equipment to avoidpossible damage to property or injury to people.

Page 12: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

12 Manual – UHX71B Controller with OSR71B Fieldbus Interface

3 Content of this manualIntroduction

3 Introduction3.1 Content of this manual

This user manual illustrates:

• Startup of the UHX71B-OSR71B controller on the fieldbus systems EtherNet/IP,Modbus/TCP and PROFINET IO.

• The configuration of the EtherNet/IP master with EDS files.

• The configuration of the Modbus/TCP master.

• The configuration of the PROFINET master using GSDML files.

The creation of IEC programs or the connection of SEW drives to the system bus inter-faces of the controller is not described.

3.2 CharacteristicsDue to its powerful universal fieldbus interfaces, the UHX71B-OSR71B controller allowsfor the connection to higher-level automation systems via EtherNet/IP, Modbus/TCPand PROFINET IO.

3.2.1 Process data exchangeVia the PROFIBUS interface, the UHX71B-OSR71B controller provides digital accessto a special data section the IEC 61131-3 evaluates as process input and output data toa higher-level controller. The meaning of the transferred data depends on the IEC pro-gram.

3.2.2 Parameter accessThe UHX71B-OSR71B controller does not support the MOVILINK® parameter channel.The "MultiMotion" program provides a bus-dependent, cyclical parameter channel. Forfurther information refer to the publication "MultiMotion for MOVI-PLC®".

3.2.3 Monitoring functionsUsing a fieldbus system requires additional monitoring functions, for example, time mon-itoring of the fieldbus (fieldbus timeout) or rapid stop concepts. For example, you canadapt the monitoring functions specifically to your application in the IEC program. Youcan determine, for instance, which error responses should be triggered in the event of abus error. For many applications, a rapid stop function is useful. However, you can alsofreeze the last setpoints so that the drive continues to operate with the most recentlyvalid setpoints. As the range of functions for the control terminals is also guaranteed infieldbus mode, you can continue to implement rapid stop concepts using the terminalsof the UHX71B-OSR71B controller, irrespective of the fieldbus used.

Pi

fkVA

Hz

n

Page 13: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 13

4Connecting the UHX71B-OSR71B controller to an Ethernet networkAssembly and Installation Notes for Ethernet

4 Assembly and Installation Notes for Ethernet4.1 Connecting the UHX71B-OSR71B controller to an Ethernet network

This chapter only describes the connection to Ethernet networks via X21 and X22. Con-nection and functionality via X37 (engineering) are described in the "UHX71B (Perfor-mance Class power)" manual.

4.2 Pin assignment X21 and X22Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801, edition2.0, category 5.

Front viewUHX71B with OSR71B (Ethernet) Designation LED

Terminal Function

7995857803

LED LED 23.1LED 23.2LED 23.3LED 23.4

ReservedReservedEthernet Communication statusSystem status

X21: Ethernet connectionLED Link (green)LED Activity (yellow)X22: Ethernet connectionLED Link (green)LED Activity (yellow)

LAN

3LA

N4

USB1 USB2 USB3

X1 OnM-24+

L23.1

L23.4

X21

X22

L23.1

L23.4

X21

X22

6139704459

A View from front B View from back[1] Pin 1 TX+ Transmit Plus [2] Pin 2 TX– Transmit Minus[3] Pin 3 RX+ Receive Plus [6] Pin 6 RX– Receive Minus

[3] [2] [1]23

61

[6]

A B

Page 14: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

14 Manual – UHX71B Controller with OSR71B Fieldbus Interface

4 Shielding and routing bus cablesAssembly and Installation Notes for Ethernet

4.2.1 Connection controller / Ethernet

To connect the UHX71B-OSR71B controller to the Ethernet network, connect the Ether-net interface X21 or X22 (RJ45 plug connector) to the other network stations using a cat-egory 5, class D twisted-pair cable in accordance with IEC 11801 edition 2.0. The inte-grated switch assists you in implementing a line topology and provides auto-crossingfunctions.

4.3 Shielding and routing bus cablesOnly use shielded cables and connection elements that meet the requirements of cate-gory 5, class D according to IEC 11801 edition 2.0.

Correct shielding of the bus cable attenuates electrical interference that can occur in in-dustrial environments. The following measures ensure the best possible shielding:

• Manually tighten the mounting screws on the connectors, modules, and equipotentialbonding conductors.

• Use only connectors with a metal housing or a metalized housing.

• Connect the shielding in the connector over a wide surface area.

• Apply the shielding of the bus cable on both ends.

• Route signal and bus cables in separate cable ducts. Do not route them parallel topower cables (motor leads).

• Use metallic, grounded cable racks in industrial environments.

• Route the signal cable and the corresponding equipotential bonding close to eachother using the shortest possible route.

• Avoid using plug connectors to extend bus cables.

• Route the bus cables closely along existing grounding surfaces.

INFORMATION• According to IEC 802.3, the maximum cable length for 10/100 MBaud Ethernet

(10BaseT / 100BaseT), e.g. between 2 network stations, is 100 m.• We recommend that you do not directly connect non-SEW end devices to the

UHX71B-OSR71B controller in order to minimize the load on the end devices inEtherNet/IP networks caused by undesired multicast data traffic. Connect non-SEW devices via a network component that supports the IGMP snooping function-ality (e.g. managed switch).

INFORMATIONIn case of fluctuations in the ground potential, a compensating current may flow via thebilaterally connected shield that is also connected to the protective earth (PE). Makesure you supply adequate equipotential bonding in accordance with relevant VDE reg-ulations in such a case.

Page 15: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 15

4The integrated Ethernet switchAssembly and Installation Notes for Ethernet

4.4 The integrated Ethernet switchYou can use the integrated Ethernet switch to achieve line topologies known from thefieldbus technology. Other bus topologies, such as star or tree, are also possible. Ringtopologies are not supported.

4.4.1 Auto-crossingThe two ports leading out of the Ethernet switch have auto-crossing functionality. Thismeans that they can use both patch and cross-over cables to connect to the next Ether-net node.

4.4.2 Auto-negotiationThe baud rate and duplex mode are negotiated by both Ethernet nodes when establish-ing the connection. For this purpose, both Ethernet ports of the EtherNet/IP connectionsupport an auto-negotiation functionality and work with a baud rate of either 100 Mbit or10 Mbit in full duplex or half-duplex mode.

4.4.3 Notes on multicast handling• The integrated Ethernet switch does not provide a filter function for Ethernet multi-

cast telegrams. Multicast telegrams that are usually sent in Ethernet/IP networksfrom the adapters (UHX71B-OSR71B controller) to the scanners (PLC) are passedon to all switch ports.

• IGMP Snooping (e.g. Managed Switches) is not supported.

• SEW-EURODRIVE therefore recommends to connect the UHX71B-OSR71B con-troller in EtherNet/IP networks only with network components that support IGMPsnooping (e.g. managed switch) or that have safety mechanisms integrated againstexcess multicast load (e.g. units from SEW-EURODRIVE). Units that do not havethis integrated function can fail due to high network loads.

4.5 Status LED The LEDs of the UHX71B-OSR71B controller indicate the current status of the UFR41Boption and the fieldbus system. Depending on the set protocol, the LEDs have the fol-lowing meaning.

4.5.1 Status LED in EtherNet/IP operationLED L23.2 The LED L23.2 (NETWORK STATUS) indicates the state of the fieldbus system.

INFORMATIONThe number of industrial Ethernet switches connected in line impacts the telegramruntime. If a telegram passes through the units, the telegram runtime is delayed by thestore & forward function of the Ethernet switch:• For a telegram length of 64 bytes by approximately 10 µs (at 100 Mbit/s)• For a telegram length of 1500 bytes by approximately 130 µs (at 100 Mbit/s)This means the more units a telegram has to pass through, the higher the telegramruntime is.

State of LED 23.2 Meaning

Off The UHX-OSR71B controller does not yet have any IP parameters.

Page 16: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

16 Manual – UHX71B Controller with OSR71B Fieldbus Interface

4 Status LEDAssembly and Installation Notes for Ethernet

LED L23.3 LED L23.3 (MODULE STATUS) indicates that the bus electronics are operating cor-rectly.

LED L23.4 LED 23.4 (SYS) indicates the proper functioning of the fieldbus electronics (hardware).

4.5.2 Status LED in PROFINET operationLED L23.2 The LED L23.2 (BUS FAULT) shows the status of the PROFINET.

LED L23.3 LED L23.3 (SYS FAULT) indicates that the bus electronics are operating correctly.

Flashing green/red The UHX-OSR71B performs a self test.

Flashing green There is no controlling IO connection.

Green There is a controlling EtherNet/IP connection.

Red Conflict detected in the assigned IP addresses. Another station in the network uses the same IP address.

Flashing red The previously established controlling IO connection is in timeout state. The state is reset by restarting communication.

State of LED 23.2 Meaning

State of LED 23.3 Meaning

Off The UHX71B-OSR71B controller is either not supplied with voltage or it is faulty.

Flashing green Device has not been configured yet and is in "Standby" state.

Flashing green/red The UHX71B-OSR71B controller performs a self test.

Green The UHX71B-OSR71B controller is in normal operating state.

Red The UHX71B-OSR71B controller is in error state.

Flashing red Conflict detected in the assigned IP addresses. Another station in the network uses the same IP address.

State of LED 23.4 Diagnostics Troubleshooting

Green The fieldbus hardware is OK. -

Orange Hardware is being initialized. -

State of LED L23.2 Cause of error Troubleshooting

Off PROFINET IO device is currently exchanging data with the PROFINET IO controller (Data Exchange).

-

Flashing red at 2 Hz No data exchange. -

Red • Connection to the PROFINET IO controller has failed.

• PROFINET IO device does not detect a link.

• Bus interruption• PROFINET IO controller is not in

operation

• Check the PROFINET connection of the UHX71B-OSR71B controller

• Check the PROFINET IO control-ler.

• Check the cabling of your PROFI-NET network

State of LED L23.3 Cause of error Troubleshooting

Off No error

Switch the unit on again. Consult SEW Service if the error occurs again.

Red Error in the UHX71B-OSR71B con-troller hardware.

Flashing red 2 Hz, for 3 s

DCP Signal Service is triggered via fieldbus. The flashing function in the PROFINET IO controller configura-tion is activated to visually localize the stations.

Page 17: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 17

4Status LEDAssembly and Installation Notes for Ethernet

LED L23.4 LED 23.4 (SYS) indicates the proper functioning of the fieldbus electronics (hardware).

4.5.3 Link/Activity LEDThe two LEDs Link (green) and Activity (yellow) integrated in the RJ45 plug connec-tors (X21, X22) display the state of the Ethernet connection.

State of LED 23.4 Diagnostics Troubleshooting

Green The fieldbus hardware is OK. -

Orange Hardware is being initialized. -

7869987467

LED/state Meaning

Link/green There is an Ethernet connection.

Link/off There is no Ethernet connection.

Link/flashes Locating function of SEW Address Editor (see chapter 4.8)

Activity/yel-low

Data is currently being exchanged via Ethernet.

X22

X21

LED "Link"

LED "Activity"

Page 18: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

18 Manual – UHX71B Controller with OSR71B Fieldbus Interface

4 TCP/IP addressing and subnetworksAssembly and Installation Notes for Ethernet

4.6 TCP/IP addressing and subnetworks4.6.1 Introduction

The settings for the address of the IP protocol are made using the following parameters:

• MAC address

• IP address

• Subnet mask

• Standard gateway

The addressing mechanisms and subdivision of the IP networks into subnetworks areexplained in this chapter to help you set the parameters correctly.

4.6.2 MAC addressThe MAC address (Media Access Controller) is the basis for all address settings. TheMAC address of an Ethernet device is a worldwide unique 6-byte value (48 bits). TheMAC address of SEW Ethernet devices is 00-0F-69-xx-xx-xx. The MAC address is dif-ficult to handle for larger networks. This is why freely assignable IP addresses are used.

4.6.3 IP addressThe IP address is a 32-bit value that uniquely identifies a node in the network. An IP ad-dress is represented by 4 decimal numbers separated by decimal points.

Example: 192.168.10.4

Each decimal number stands for one byte (= 8 bits) of the address and can also be rep-resented using binary code (see following table).

The IP address comprises a network address and a node address (→ following table).

The part of the IP address that denotes the network and the part that identifies the nodeis determined by the network class and the subnet mask.

Node addresses cannot consist of only zeros or ones (binary) because they representthe network itself or a broadcast address.

Byte 1 Byte 2 Byte 3 Byte 4

11000000 . 10101000 . 00001010 . 00000100

Network address Node address

192.168.10 4

Page 19: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 19

4TCP/IP addressing and subnetworksAssembly and Installation Notes for Ethernet

4.6.4 Network classes

The first byte of the IP address determines the network class and as such representsthe division into network addresses and node addresses.

This rough division is not sufficient for a number of networks. They also use an explicit,adjustable subnet mask.

4.6.5 Subnet maskA subnet mask is used to divide the network classes into even finer sections. Like theIP address, the subnet mask is represented by 4 decimal numbers separated by decimalpoints.

Example: 255,255,255,128

Each decimal number stands for one byte (= 8 bits) of the subnet mask and can also berepresented using binary code (→ following table).

If you compare the IP addresses with the subnet masks, you see that in the binary rep-resentation of the subnet mask all ones determine the network address and all the zerosdetermine the station address (see following table).

The class C network with the address 192.168.10. is further subdivided by the subnetmask 255.255.255.128. 2 networks are created with the address 192.168.10.0 and192.168.10.128.

The following node addresses are permitted in the two networks:

• 192.168.10.1 ... 192.168.10,126

• 192.168.10,129 ... 192.168.10,254

The network nodes use a logical AND operation for the IP address and the subnet maskto determine whether there is a communication partner in the same network or in a dif-ferent network. If the communication partner is in a different network, the standard gate-way is addressed for passing on the data.

Value rangeNetwork class Complete network address

(Example) MeaningByte 1

0 ... 127 A 101.22.3 10 = Network address1.22.3 = Node address

128 ... 191 B 17216.52.4 172.16 = Network address52.4 = Node address

192 ... 223 C 192.168.10.4 192.168.10 = Network address4 = Node address

Byte 1 Byte 2 Byte 3 Byte 4

11111111 . 11111111 . 11111111 . 10000000

Byte 1 Byte 2 Byte 3 Byte 4

IP addressdecimal 192 . 168. . 10 . 129

binary 11000000 . 10101000 . 00001010 . 10000001

Subnet maskdecimal 255 . 255 . 255 . 128

binary 11111111 . 11111111 . 11111111 . 10000000

Page 20: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

20 Manual – UHX71B Controller with OSR71B Fieldbus Interface

4 Setting the IP address parametersAssembly and Installation Notes for Ethernet

4.6.6 Standard gateway

The standard gateway is also addressed via a 32-bit address. The 32-bit address is rep-resented by 4 decimal numbers separated by decimal points.

Example: 192.168.10.1

The standard gateway establishes a connection to other networks. In this way, a net-work station that wants to address another station can use a logical AND operation withthe IP address and the subnet mask to determine whether the desired station is locatedin the same network. If this is not the case, the node addresses the standard gateway(router), which must be part of the actual network. The standard gateway then takes onthe job of transmitting the data packages.

If for the standard gateway, the same address is set as for the IP address, the standardgateway is deactivated. The address of the standard gateway and the IP address mustbe in the same subnetwork.

4.6.7 DHCP (Dynamic Host Configuration Protocol)Instead of setting the 3 parameters IP address, subnet mask and standard gatewaymanually, they can be assigned automatically by a DHCP server in the Ethernet net-work.

This means the IP address is assigned from a table, which contains the allocation ofMAC address to IP address.

Parameter P785 indicates whether the UHX71B-OSR71B controller expects the IP pa-rameters to be assigned manually or via DHCP.

4.7 Setting the IP address parameters4.7.1 Initial startup

The "DHCP" protocol (Dynamic Host Configuration Protocol) is activated as the defaultsetting for the UHX71B-OSR71B controller. This means that the option card expects itsIP address parameters from a DHCP server.

Once the DHCP server has been configured and the settings have been made for thesubnetwork screen and the standard gateway, the UHX71B-OSR71B controller must beinserted in the assignment list of the DHCP server. The MAC ID of the UHX71B-OSR71B controller is allocated a valid IP address.

4.7.2 Changing the IP address parameters after successful initial startupIf the UHX71B-OSR71B controller was started using a valid IP address, you can alsoaccess the IP address parameters via the Ethernet interface.

INFORMATIONThere is a free DHCP server available on the Rockwell Automation homepage. Thetool is known as "BOOTP Utility" and can be downloaded from the following website:http://www.ab.com/networks/bootp.html.

INFORMATIONThe configured IP address parameters are permanently adopted into the parameterset if DHCP is deactivated after the IP address has been assigned.

Page 21: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 21

4Replacing the unitAssembly and Installation Notes for Ethernet

You can change the IP address parameters via Ethernet by one of the following meth-ods:

• with the MOVITOOLS® MotionStudio software via [Diagnose] / [File System Monitor]

• using the EtherNet/IP TCP/IP interface object (see chapter "EtherNet/IP CIP objectdirectory")

If the IP address parameters are assigned to the UHX71B-OSR71B controller via DHCPserver, then you can only change the parameters by adjusting the settings of the DHCPserver.

The options listed above for changing the IP address parameters only come into effectonce the supply voltages (DC 24 V) have been switched off and back on again.

4.7.3 Deactivating / activating the DHCPThe type of IP address assignment is determined by the setting of the attribute Config-uration Control of the EtherNet/IP TCP/IP interface object. The value is displayed orchanged in the parameter P785 DHCP / Startup Configuration.

• "Stored IP parameters" setting

The stored IP address parameters are used.

• "DHCP" setting

The IP address parameters are requested by a DHCP server.

If you use the DHCP server from Rockwell Automation, you can activate or deacti-vate the DHCP by clicking a button. In this case, an EtherNet/IP telegram is sent tothe TCP/IP interface object of the station that is being addressed.

4.8 Replacing the unit• If DHCP is active, the assignment list of the DHCP server must be updated when the

UHX71B-OSR71B is replaced. The MAC address of the UHX71B-OSR71B control-ler is printed on its front panel for this purpose.

• If DHCP is not active, the IP parameters saved on the memory card of the UHX71B-OSR71B controller will be used.

If, after the UHX71B-OSR71B controller has been replaced, you do not plug the oldmemory card into the replacement unit, you will have to perform a complete startupwith the new controller (if DHCP is not active incl. the IP parameters). Alternatively,you can transfer a data backup to the new unit created with the MOVITOOLS® Mo-tionStudio software.

Page 22: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

22 Manual – UHX71B Controller with OSR71B Fieldbus Interface

5 Validity of the EDS file for UHX71B-OSR71BConfiguration and Startup (EtherNet/IP)

5 Configuration and Startup (EtherNet/IP)This chapter provides information on the configuration of the EtherNet/IP master andstartup of the UHX71B-OSR71B controller for fieldbus operation. Prerequisite is the cor-rect connection and setting of the IP address parameters of the UHX71B-OSR71B con-troller in accordance with the chapter "Assembly and Installation Instructions".

5.1 Validity of the EDS file for UHX71B-OSR71B

SEW-EURODRIVE provides the following EDS file for configuring the scanner (Ether-Net/IP master):

• SEW_CONTROLLER_POWER.eds

5.2 Configuring the master (EtherNet/IP scanner)The following example refers to configuration for the Allen-Bradley CompactLogix 1769-L32E controller with RSLogix 5000 programming software. The EtherNet/IP interface isalready integrated into the CPU component of this controller.

INFORMATIONDo not edit or amend the entries in the EDS file. SEW assumes no liability for invertermalfunctions caused by a modified EDS file.

INFORMATIONCurrent versions of the EDS files for the UHX71B-OSR71B option are available on theSEW homepage (http://www.sew-eurodrive.com) under the heading "Software".

INFORMATIONIf a CPU without an EtherNet/IP interface is used, an Ethernet communication inter-face must first be added to the I/O configuration.

Page 23: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 23

5Configuring the master (EtherNet/IP scanner)Configuration and Startup (EtherNet/IP)

5.2.1 Process data exchangeIn the following project planning example, the UHX71B-OSR71B controller is added toa project. To do so, go to the “Controller Organizer” screen in the RSLogix 5000 programas shown in the screenshot below (use the tree structure on the left side of the screen).

• In the "IO Configuration" folder, select the entry "1769-L32E Ethernet Port Lo-calENB" as the Ethernet communication interface. Right-click and choose "NewModule" from the context menu. The selection window "Select Module" appears.

• To add option UHX71B-OSR71B to the project, mark the entry “ETHERNET MOD-ULE” in the “Communications” category. Confirm your selection by clicking [OK].

• The "New Module" window opens.

7874677003

Page 24: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

24 Manual – UHX71B Controller with OSR71B Fieldbus Interface

5 Configuring the master (EtherNet/IP scanner)Configuration and Startup (EtherNet/IP)

First enter the name under which the data is stored in the controller tags for the newlycreated module, and then enter the IP address.

• In the “Comm Format” dropdown menu, choose “Data - INT” as the data for-mat. Process data for UHX71B-OSR71B always contains 16 bits (INT).

• In the "Connection Parameters" group box, enter the value "171" in the "Input As-sembly Instance" input field. The input data of the PLC must be linked to the outputinstance of UHX71B-OSR71B.

• To establish a controlling connection, in the "Connection Parameters" group boxenter the value "161" in the "Output Assembly Instance" input field. The input data ofthe PLC must be linked to the output instance of UHX71B-OSR71B.

• In the selection fields "Input Size" and "Output Size", set a maximum value of "64"(16 bit) as the data length.

• In the "Configuration Size" selection field, enter the value "0". The "Configuration As-sembly Instance" input field is not used in this case.

• Click [OK] to complete the process.

• To ensure compatibility with existing DeviceNet configurations, you can also choosethe data type "SINT" in the "Comm Format" selection field. In this case, you must en-sure that an even number of bytes (2 – 128) is configured and that data consistencyis maintained during operation when the IO data is accessed.

7874681483

Page 25: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 25

5Settings in the UHX71B-OSR71B controllerConfiguration and Startup (EtherNet/IP)

5.2.2 Other settingsOn the "Connection" tab page you can set the data rate and, if necessary, the error re-sponse of the controller.

• The UHX71B-OSR71B controller supports a minimum data rate (input field "Re-quested Packet Interval (RPI)") of 4 ms. Longer cycle times can be implementedwithout any problems.

• Click [OK]. You have now configured process data exchange with a UHX71B-OSR71B.

5.3 Settings in the UHX71B-OSR71B controllerThe creation of IEC programs is described in detail in the "MultiMotion for MOVI-PLC®"manual. This is why only the fieldbus-specific characteristics are described in this chap-ter.

5.3.1 Process data configuration Ethernet/IP slave and modbus/TCPTo activate the fieldbus interface, set the Fieldbus selection parameter in the parametertree of MOVITOOLS® MotionStudio to the required bus type (Ethernet/IP or Mod-bus/TCP).

8229832203

8229837195

Page 26: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

26 Manual – UHX71B Controller with OSR71B Fieldbus Interface

5 Settings in the UHX71B-OSR71B controllerConfiguration and Startup (EtherNet/IP)

In the "IP parameters" group box, enter the following addresses:

• IP address

• Subnet mask

• Standard gateway

5.3.2 Status of the Ethernet/IP fieldbus interface The FbusGetInfoV2 function block makes the status and some display parameters ofthe fieldbus interface available for the IEC program and for diagnostics.

If there is no communication with the fieldbus master, the output Error is set to TRUE.During an active fieldbus connection, the output Done is set to TRUE, and the outputsAddress, Baud rate, timeout and Bus type show the respective parameters as they wereset via the parameter tree in MOVITOOLS® MotionStudio or via PLC.

8229853963

INFORMATIONFor Modbus/TCP, the timeout monitoring must take place in the application (e.g. via atoggle bit).

7628791563

FBusGetInfoV2

Enable Done

Type

ErrorID

Baudrate

Timeout

BusType

Address

BusState

PdConfig

BOOL BOOL BOOL

BOOL

UDINT

UDINT

UDINT

T_PLC_BUS_TYPE

T_PLC_BUS_STATE

T_PLC_BUS_PD_CONFIG

Page 27: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 27

5Configuration examples in RSLogix5000Configuration and Startup (EtherNet/IP)

5.3.3 Checking the process data communicationNow actual values can be read from the UHX71B-OSR71B controller and setpoint val-ues can be written. The process data should correspond with the values displayed in thePLC Editor or in the diagnostics plug-in of the active IEC program in MOVITOOLS® Mo-tionStudio.

5.4 Configuration examples in RSLogix50005.4.1 UHX71B-OSR71B with 16 PD data exchange

1. Set the IP address of the UHX71B-OSR71B controller (see chapter Setting the IP ad-dress parameters).

2. Add the UHX71B-OSR71B to the Ehernet/IP configuration according to chapter"Configuration of the master (Ethernet/IP scanner)".

3. You can now start integration into the RSLogix project.

To do so, create a controller tag with a user-defined data type to create a simple, dataconsistent interface to the process data of the UHX71B-OSR71B controller (see fol-lowing figure).

The description for the process input and output data of the controller tag can matchthe definition of the process data (PD) in the UHX71B-OSR71B.

INFORMATIONFor more detailed information on process data communication in the IEC program,refer to the publication "MultiMotion for MOVI-PLC®".

7882429323

Page 28: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

28 Manual – UHX71B Controller with OSR71B Fieldbus Interface

5 Configuration examples in RSLogix5000Configuration and Startup (EtherNet/IP)

4. To copy the data of the UHX71B-OSR71B to the new data structure, a CPS com-mand is added at the start of the MainRoutine which reads the data from the control-ler tag (see following figure).

To copy the data from the new data structure to the UHX71B-OSR71B, insert a CPScommand at the end of the "MainRoutine" (see following figure).

5. Now the project is saved and uploaded to the PLC. The PLC is set to RUN mode.

Now actual values can be read from the UHX71B-OSR71B controller and setpointvalues can be written.

The process data should correspond to the values displayed in the PLC Editor or inthe diagnostics plug-in of the active IEC program in MOVITOOLS® MotionStudio. Formore detailed information on process data connection in the IEC program, refer tothe publication "MultiMotion for MOVI-PLC®".

7882586123

7882591115

Page 29: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 29

6IntroductionEthernet Industrial Protocol (EtherNet/IP)

6 Ethernet Industrial Protocol (EtherNet/IP)6.1 Introduction

The EtherNet Industrial Protocol (EtherNet/IP) is an open communication standardbased on the classic EtherNet protocols TCP/IP and UDP/IP.

EtherNet/IP was defined by the Open DeviceNet Vendor Association (ODVA) and Con-trolNet International (CI).

With EtherNet/IP, Ethernet technology is expanded to include the CIP (Common Indus-trial Protocol) application protocol. CIP is known in the field of automation engineeringbecause it is also used for DeviceNet and ControlNet as an application protocol.

6.2 Process data exchangeUp to 120 process data words can be exchanged with an EtherNet/IP master (scanner)depending on the use of the UHX71B-OSR71B unit. The EtherNet/IP master (scanner)sets the process data length when opening the connection.

In addition to a controlling "Exclusive Owner Connection", up to two additional "ListenOnly Connections" are available. This means the actual values of the drive can also beread out by stand-by controllers or visualization devices.

If there is already a controlling connection via Modbus/TCP, you cannot activate an "Ex-clusive Owner Connection" via EtherNet/IP before a power-on reset.

6.2.1 Timeout responseThe timeout status is triggered by the UHX71B-OSR71B option. The timeout intervalmust be set by the EtherNet/IP master (scanner) when the connection is established.The EtherNet/IP specification refers to a "Requested Packet Interval (RPI)" rather thana timeout time in this case.

The timeout interval displayed in the MOVITOOLS® MotionStudio parameter tree re-sults from the Requested Packet Interval (RPI) multiplied with the "Timeout Multiplier".

This timeout interval is retained in the device when an "Exclusive Owner Connection" isremoved, and the device switches to timeout status after the timeout interval haselapsed. The timeout status is displayed on the front of the UHX71B-OSR71B by theflashing red L13 LED.

A you can only activate the timeout delay via the bus, you must not change the value viaMOVITOOLS® MotionStudio.

The timeout state causes the response programmed in the IEC program.

The timeout status can be reset via EtherNet/IP as follows:

• Via the reset service of the identity object (class 0x01, instance 0x01, undeterminedattribute)

• By re-establishing the connection

• Via the reset bit in the control word

00

I

Page 30: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

30 Manual – UHX71B Controller with OSR71B Fieldbus Interface

6 CIP object directoryEthernet Industrial Protocol (EtherNet/IP)

6.3 CIP object directoryIn the Common Industrial Protocol, all unit data can be accessed via objects. The ob-jects listed in the following table are integrated in the UHX71B-OSR71B.

The meaning of the objects and a description of how to access them is given in the fol-lowing section.

6.3.1 Identity object• The identity object contains general information on the EtherNet/IP device.

• Class code: 01hex

Class

Instance 1

• Coding of attribute 5 "Status"

Class [hex] Name

01 Identity object

02 Message Router Object

04 Assembly Object

06 Connection Manager Object

07 Register Object

0F Parameter Object

64 Vardata Object

F5 TCP/IP Interface Object

F6 EtherNet Link Object

Attribute Access Name Data type Default value [hex] Description

1 Get Revision UINT 0001 Revision 1

2 Get Max Instance UINT 0001 Maximum instance

Attribute Access Name Data type Default value [hex] Description

1 Get Vendor ID

UINT 013B SEW-EURODRIVE GmbH & Co KG

2 Get Device Type

UINT 0065 Manufacturer-specific type

3 Get Product Code

UINT 000A Product no.10: UHX71B

4 Get

Revision STRUCT of

Revision of the identity object, depends on firmware version

Major Revision

USINT

Minor Revision

USINT

5 Get Status WORD → Table in "Coding of attribute 5 Status"

6 Get Serial number

UDINT Unique serial number of fieldbus connection

7 Get Product Name

SHORT_ STRING

SEW CONTROLLER POWER

Product name

Bit Name Description

0 Owned Controlling connection is active

1 - Reserved

00

I

Page 31: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 31

6CIP object directoryEthernet Industrial Protocol (EtherNet/IP)

• Coding of the “Extended device status” (bits 4 – 7):

Supported ser-vices

6.3.2 Message router object• The message router object provides information on the implemented objects.

• Class code: 02hex

Class

Instance 1

2 Configured Configuration complete

3 - Reserved

4 – 7 Extended Device Status See table "Coding of the Extended Device Status"

8 Minor Recoverable Fault Minor error that can be remedied

9 Minor Unrecoverable Fault Minor error that cannot be remedied

10 Major Recoverable Fault Major error that can be remedied

11 Major Unrecoverable Fault Major error that cannot be remedied

12 – 15 - Reserved

Value [binary] Description

0000 Unknown

0010 At least one faulty I/O connection

0011 No I/O connection established

0110 At least one I/O connection active

Bit Name Description

Service code [hex] Service Name Class Instance

01 Get_Attributes_All X X

05 Reset - X

0E Get_Attribute_Single X X

Attribute Access Name Data type Default value [hex] Description

1 Get Revision UINT 0001 Revision 1

Attribute Access Name Data type Default value [hex] Description

1 Get Object_List STRUCT of Object list comprising:• Number of objects• List of objects

Number UINT 0009

Classes ARRAY ofUINT

01 00 02 0004 00 06 0007 00 0F 0064 00 F5 00F6 00

2 Get Number Available

UINT 0009 Maximum number of connec-tions

00

I

Page 32: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

32 Manual – UHX71B Controller with OSR71B Fieldbus Interface

6 CIP object directoryEthernet Industrial Protocol (EtherNet/IP)

Supported ser-vices

6.3.3 Assembly object• The assembly object is used to access the UHX71B-OSR71B process data. IO con-

nections can be created for the instances of the assembly object to exchange cyclicprocess data.

• Class code: 04hex

Class

Instance 161 – SEW PO data range

This instance is used to access the UHX71B-OSR71B process output data.MOVIDRIVE® can be controlled by only one scanner. Therefore, only one connectioncan be established with this instance.

Instance 121 – "Heartbeat"

This instance is accessed when the scanner wants to establish an input only connection.No process output data is sent with this type of connection. It is used only to read pro-cess input data.

Instance 171 –SEW PI data sec-tion

This instance is used to access the UHX71B-OSR71B process input data. Several mul-ticast connections or a point-to-point connection can be established to this instance.

Supported ser-vices

Service code [hex] Service Name Class Instance

01 Get_Attributes_All X -

0E Get_Attribute_Single X X

Attribute Access Name Data type Default value [hex] Description

1 Get Revision UINT 0002 Revision 2

2 Get Max Instance UINT 0082 Maximum instance

Attribute Access Name Data type Default value [hex] Description

3 Get Data Array of BYTE

- OUTPUT assembly

Attribute Access Name Data type Default value [hex] Description

3 Get Data Array of BYTE

- OUTPUT assemblyData size = 0

Attribute Access Name Data type Default value [hex] Description

3 Get Data Array of BYTE

- INPUT assembly

INFORMATIONThe designations "INPUT assembly" and "OUTPUT assembly" refer to the processesas seen from the network's point of view. An "INPUT assembly"” produces data on thenetwork, "OUTPUT assembly" consumes data from the network.

Service code [hex] Service Name Class Instance 161 Instance 121 Instance 171

0E Get_Attribute_Single X X - X

00

I

Page 33: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 33

6CIP object directoryEthernet Industrial Protocol (EtherNet/IP)

6.3.4 TCP/IP interface object• The TCP/IP interface object enables the IP parameters to be configured via Ether-

Net/IP.

• Class code: F5hex

Class

Instance 1

Supported ser-vices

6.3.5 Ethernet link object• Information on the Ethernet communication interface is stored in the Ethernet link ob-

ject.

• Class code: F6hex

Attribute Access Name Data type Default value [hex] Description

1 Get Revision UINT 0001 Revision 1

2 Get Max Instance UINT 0001 Maximum instance

3 Get Number of Instances

UINT 0001 DHR41B has one TCP/IP interface

Attribute Access Name Data type Default value [hex] Description

1 Get Status DWORD 00000001 Valid configuration

2 Get Configuration capability

DWORD 00000014 The interface configura-tion attribute (5) is writable. The DHCP can be used for configuration.

3 Set Configuration control

DWORD 00000002 0 = The unit uses the stored IP parameters at startup.2 = The unit waits for its IP configuration via DHCP at startup.

4 Get Physical Link Object

STRUCT of Reference to the EtherNet link object (class code 0xF6) as sublayer.Path Size UINT 0002

Path Padded EPATH

20 F6 24 01

5 Set Interface con-figuration

STRUCT of

IP Address UDINT Current IP address

Network Mask UDINT Current subnetwork mask

Gateway Address

UDINT Currently set standard gateway

Name Server UDINT 00000000 DNS is not supported

Name Server 2 UDINT 00000000 DNS is not supported

Domain Name STRING sew.de

6 Get Host Name STRING Not used

Service code [hex] Service Name Class Instance

01 Get_Attributes_All X _

0E Get_Attribute_Single X X

10 Set_Attribute_Single - X

00

I

Page 34: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

34 Manual – UHX71B Controller with OSR71B Fieldbus Interface

6 CIP object directoryEthernet Industrial Protocol (EtherNet/IP)

Class

Instance 1 – Ether-net connection X21

Instance 2 – Ether-net connection X22

Supported ser-vices

Attri-bute

Access

Name Data type Default value [hex]

Description

1 Get Revision UINT 0002 Revision 2

2 Get Max Instance UINT 0002 Maximum instance

3 Get Number of Instances

UINT 0002 DHR41B has 2 Ethernet interfaces

Attri-bute

Access

Name Data type Default value [hex]

Description

1 Get Interface Speed

UDINT 00000064 Default value = 100 → transmission speed in MBit/s

2 Get Interface Flags

DWORD • Bit 0 displays the active link• Bit 1 displays full duplex mode• Bit 2 – bit 4 indicate the negotia-

tion status• Bit 5 shows whether the manual

setting has to be reset• Bit 6 indicates a local hardware

error

3 Get Physical Address

ARRAY of 6 USINTs

00 0F 69 xx xx xx MAC IDSEW MAC OUI: 00 0F 69

Attri-bute

Access

Name Data type Default value [hex] Description

1 Get Interface Speed

UDINT 00000064 Default value = 100 → transmission speed in MBit/s

2 Get Interface Flags

DWORD • Bit 0 displays the active link• Bit 1 displays full duplex mode• Bit 2 – bit 4 indicate the negotia-

tion status• Bit 5 shows whether the manual

setting has to be reset• Bit 6 indicates a local hardware

error

3 Get Physical Address

ARRAY of 6 USINTs

00 0F 69 xx xx xx xx MAC IDSEW MAC OUI: 00 0F 69

Service code [hex] Service Name Class Instance

01 Get_Attributes_All X _

0E Get_Attribute_Single X X

00

I

Page 35: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 35

6General Error CodesEthernet Industrial Protocol (EtherNet/IP)

6.4 General Error Codes

General error code (hex)

Error name Description

00 Success Successful

01 Connection failure A connection-specific service has failed.

02 Resource unavailable The source required for performing the service is unavailable.

03 Reserved

04 Path segment error The processing node was unable to interpret the "Path Seg-ment Identifier" or the segment syntax.

05 Path destination unknown The "Path" refers to an object class, object instance or a structural element that is not supported by the processing node.

06 – 07 Reserved

08 Service not supported The service is not supported for the selected class/instance

09 Invalid attribute value Invalid attribute data have been sent.

0A – 0B

0C Object state conflict The selected object cannot perform the service in its current status.

0D Reserved

0E Attribute not settable It is not possible to access the selected object for writing.

10 Device state conflict The current status of the device makes it impossible to per-form the required service.

11 – 12 Reserved

13 Not enough data The length of the transferred data is too short for the service to be performed.

14 Attribute not supported The selected attribute is not supported.

15 Too much data The length of the transferred data is too long for the service to be performed.

16 Object does not exist The selected object is not implemented in the device.

17 – 1D Reserved

1E Embedded Service Error Internal processing error

1F Vendor specific error Manufacturer-specific error (see "Fieldbus Unit Profile" man-ual)

20 Invalid parameter Invalid parameter. This error message is used when a param-eter does not satisfy the requirements of the specification and/or the requirements of the application.

21 – FF Reserved

00

I

Page 36: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

36 Manual – UHX71B Controller with OSR71B Fieldbus Interface

7 Configuration for the master (Modbus scanner)Configuration and Startup (Modbus/TCP)

7 Configuration and Startup (Modbus/TCP)This section provides information about the configuration of the Modbus/TCP masterand startup of the inverter for fieldbus operation. Prerequisite is the correct connectionand setting of the IP address parameters of the UHX71B-OSR71 in accordance with thesection "Assembly and Installation Instructions".

7.1 Configuration for the master (Modbus scanner)The first example refers to the configuration and programming of a Schneider Electriccontrol system TSX Premium P57203 using the programming software PL7 PRO. AnETY4103 is used as the Ethernet component. The information and illustrations arebased on the English version of the PL7 PRO software.

7.1.1 Hardware configuration• Start PL7 PRO and enter the control type.

• Enter the hardware configuration for the control system in the application browserunder STATION / Configuration / Hardware configuration.

INFORMATION• There are no specific unit description files for Modbus/TCP.• For Modbus/TCP, the timeout monitoring must take place in the application (e.g.

via a toggle bit).

INFORMATION• Enter values in PL7 PRO using the keypad.• As Ethernet bus master, use components from Schneider Electric that support I/O

scanning. The Modbus/TCP interface module for SEW drives cannot be addressedvia "Peer Cop". However, Ethernet-Busmasters that only support "Peer Cop" canaccess the drives from the PLC program using read and write commands.

7898326155

00

I

Page 37: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 37

7Configuration for the master (Modbus scanner)Configuration and Startup (Modbus/TCP)

7.1.2 Settings for the Ethernet component• To open the configuration window, double-click on the Ethernet component.

• If you have a non-extendable rack, enter a "1" in the "Network" input field in the"XWAY address" section.

• Enter the number of the slot that the Ethernet component is plugged into (here: 2) inthe input field "Station" in the "XWAY address" section. 2). In this case, the XWAYaddress is 1.2.

• In the section "IP address configuration", select the checkbox "Configured". Enter theIP address and the network parameters in the input fields "IP address", "Subnetworkmask" and "Gateway address". If the control system is to receive the address param-eters via a DHCP server, select the radio button "Client/Server configuration" in thesection "IP address configuration".

• In the "Ethernet configuration" section, select the checkbox "Ethernet II".

• In the "Module utilities" group, select the "IO Scanning" radio button.

7898818699

Page 38: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

38 Manual – UHX71B Controller with OSR71B Fieldbus Interface

7 Configuration for the master (Modbus scanner)Configuration and Startup (Modbus/TCP)

7.1.3 Addressing the drive using I/O scanning

• Select the "IO Scanning" tab. In this tab page you specify which of the stations con-nected to the Modbus are to exchange cyclical data.

• In the section "Master %MW zones" enter the control memory areas that are to beused to exchange cyclical data with the Modbus stations. You will use the memoryaddresses later in your PLC program.

• Enter the following in the "Scanned peripherals" group:

– In the "IP address" input field, enter the IP address of the SEW drive.

– In the "Unit ID" field, enter "0".

– In the "Repetitive rate" dropdown menu, enter the cycle time that is used to ad-dress the stations.

– Enter the value "4 "in the input fields "RD ref.slave" and "WR ref. slave" as thecyclical data are available from offset 4.

– In the input fields "RD count" and "WR count" enter the number of words to beexchanged. The values must be the same in both fields. You can set 1 – 64 wordsfor the UHX71B-OSR71B.

• Click on the button "Confirm" to confirm the rack configuration and the global config-uration.

• Once you have transferred your settings and started the program, the color of LEDL13 (NETWORK/STATUS) of DHR41B changes to green (see chapter "StatusLED").

7900597387

Page 39: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 39

7Settings in the UHX71B-OSR71B controllerConfiguration and Startup (Modbus/TCP)

7.2 Settings in the UHX71B-OSR71B controllerThe creation of IEC programs is described in detail in the "MOVI-PLC®" manual. Thissection only describes the fieldbus-specific characteristics.

7.2.1 Process data configurationThe process data interface is normally configured by the master (scanner). The mastersets the number of process data words.

In the parameter tree of MOVITOOLS® MotionStudio (index 8451), the currently setvalue is displayed in the field "PD configuration" (see following figure).

7.3 Project planning example in PL7 PRO7.3.1 UHX71B-OSR71B controller with 16 PD data exchange

1. Set the IP address of the UHX71B-OSR7141B controller (see chapter Setting the IPaddress parameters).

2. Integrate the UHX71B-OSR71B into the configuration for the IO scanning accordingto section "Configuration of the master (Modbus scanner)".

3. Now, the integration into the PLC project can be performed.

4. Create a new section in PL7 PRO in the application browser under [Station] /[Program] / [Mast Task] / [Sections] .

7946698251

INFORMATIONFor Modbus/TCP, the timeout monitoring must take place in the application (e.g. via atoggle bit).

Page 40: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

40 Manual – UHX71B Controller with OSR71B Fieldbus Interface

7 Project planning example in PL7 PROConfiguration and Startup (Modbus/TCP)

5. In this example, the setpoints for the drive start from MW150 (see following figure).

6. Now the project is saved and uploaded to the PLC. The PLC is set to RUN mode.

Now actual values can be read from the UHX71B-OSR71B controller and setpointvalues can be written.

The process data should correspond to the values displayed in the PLC Editor or inthe diagnostics plug-in of the active IEC program in MOVITOOLS® MotionStudio. Formore detailed information on the process connection in the IEC program, refer to thepublication "MultiMotion for MOVI-PLC®".

7956122507

Page 41: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 41

7Examples for data exchange via Modbus/TCPConfiguration and Startup (Modbus/TCP)

7.4 Examples for data exchange via Modbus/TCPAs there are many different master systems and software solutions available for Mod-bus/TCP for standard PCs, there is no "reference controller" the examples are based on.This is why this section gives detailed examples regarding the telegram structure.

You can use the telegram structure from these examples and compare it to the structureused in your application for troubleshooting purposes. There are simple tools for record-ing telegrams via the Ethernet network, e.g. Wireshark (see following figure), Packetizeretc. These freeware tools are available on the Internet.

Observe that tracing all Ethernet telegrams in a network is only possible with a tab, hubor a switch with a port mirror function. The telegrams sent from and to the PC which isalso used for recording can always be recorded, of course.

The figure above provides an example of how setpoints are written (FC16) to the Mod-bus/TCP slave with IP address 10.3.71.119. The 3 process data words are located fromoffset 4 (reference number) and are addressed via unit ID 255.

All the other examples merely describe the Modbus/TCP part of the telegram. TheTCP/IP part of the telegram, as well as establishing and dropping a TCP/IP connectionare not explained in detail.

7956560139

Page 42: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

42 Manual – UHX71B Controller with OSR71B Fieldbus Interface

7 Examples for data exchange via Modbus/TCPConfiguration and Startup (Modbus/TCP)

7.4.1 Writing and reading process data

The process data exchange can be performed either via FC3 (read) and FC16 (write),or FC23 (read and write):

For writing 3 process data words (setpoints) to a Modbus/TCP slave via FC16, theTCP/IP telegram to port 502 is structured as illustrated above.

Only bytes 0-11 are returned in the response telegram of port 502 of the Modbus/TCPslave, where all values remain unchanged with the exception of byte 5. Byte 5 (low bytelength field) is corrected to value 6.

Byte Value Meaning Interpretation Help

00x00 Transaction identifier

For a detailed description refer to the Modbus/TCP specification and section "Modbus protocol (Mod-bus/TCP)"

1

20x00 Protocol identifier

3

4 0x00Length field

Number of bytes after byte 5:3 (number PD) × 2 + 7 = 135 0x0d

6 0xFF Unit identifier Must be 0 or 255

7 ox10 Function code Service = FC16 (Write Register)

8 0x00Write Reference-number

Offset where PD start:Must always be 49 0x04

10 0x00Write word count

Number of PD (here 3):Must for PD 1...6411 0x03

12 0x06 Write byte count Number of PD × 2 = 6

13 0x00

Data

Process output data word 1

Data mapping and definition, see IEC program

14 0x11

15 0x22Process output data word 2

16 0x33

17 0x44Process output data word 3

18 0x55

Page 43: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 43

7Examples for data exchange via Modbus/TCPConfiguration and Startup (Modbus/TCP)

During process data exchange via FC23, the telegram that is used to write and read 3process data words (PD) each is structured as follows.

The following data bytes are returned in the response telegram of the Modbus/TCPslave.

Byte Value

Meaning Interpretation Help

00x00 Transaction identifier

For a detailed description refer to the Modbus/TCP specification and section "Modbus protocol (Mod-bus/TCP)"

1

20x00 Protocol identifier

3

4 0x00Length field

Number of bytes after byte 5:3 (number PD) × 2 + 11 = 175 0x11

6 0xFF Unit identifier Must be 0 or 255

7 0x10 Function code Service = FC23 (read + write reg-ister)

8 0x00Read reference number

Offset where PD start:Must always be 49 0x04

10 0x00Read word count

Number of PD (here 3):Must for PD 1 – 6411 0x03

12 0x00Write reference number

Offset where PD start:Must always be 413 0x04

14 0x00Write word count

Number of PD (here 3):see read word count15 0x03

16 0x06 Write byte count Number of PD × 2 = 6

17 0x00

Data

Process output data word 1

Data mapping and definition, see IEC program

18 0x11

19 0x22Process output data word 2

20 0x33

21 0x44Process output data word 3

22 0x55

Byte Value

Meaning Interpretation Help

00x00 Transaction identifier

For a detailed description refer to the Modbus/TCP specification and section "Modbus protocol (Mod-bus/TCP)"

1

20x00 Protocol identifier

3

4 0x00Length field

Number of bytes after byte 5:3 (number PD) × 2 + +3 = 95 0x09

6 0xFF Unit identifier Must be 0 or 255

7 0x17 Function code Service = FC23 (read + write reg-ister)

8 0x06 Write byte count Number of PD × 2 = 6

9 0x00

Data

Process input data word 1

Data mapping and defini-tion, see IEC program

10 0xAA

11 0xBBProcess input data word 2

12 0xCC

13 0xDDProcess input data word 3

14 0xEE

Page 44: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

44 Manual – UHX71B Controller with OSR71B Fieldbus Interface

8 IntroductionModbus Protocol (Modbus/TCP)

8 Modbus Protocol (Modbus/TCP)8.1 Introduction

Modbus/TCP is an open protocol based on TCP/IP. It was one of the first protocol typesto become standard in industrial Ethernet interfaces for process data transfer.

Modbus frames are exchanged via the TCP/IP port 502. Every master IP address is ac-cepted. Modbus exclusively uses the coding "BIG ENDIAN" (Motorola data format orhigh byte first).

Access via "Peer Cop" is not possible. Make sure that the bus master supports "IO scan-ning".

Modbus/TCP is integrated into the UHX71B-OSR71B as of firmware version .11.

8.1.1 Mapping and addressingThe logic Modbus address range is 64 k words and is addressed via the reference num-ber (offset). Four different tables can be in the address range:

• Binary inputs (RO)

• Binary outputs (RW)

• Input register (RO)

• Output register (RW)

The tables can be separated or overlapping.

The UHX71B-OSR71B option provides the following data areas:

• For process data transfer, there is a table that allows for write access (for setpointvalues) as well as read access (for actual values).

This table starts at offset 4 and ends at offset 0FFhex. It contains the 1 – 64 cyclicallytransferred process data words.

• The process data output words from the controller are also saved in another table. Itallows for one or several additional clients (e.g. visualization) to read the current set-point values.

This table starts at offset 104hex and ends at offset 1FFhex.

• The remaining address scope from offset 400hex to FFFFhex is reserved and mustnot be addressed.

The data word at offset 219hex (8606dec) is a special case, it allows for writing (andreading) the timeout monitoring time.

INFORMATIONNote the following for control systems from Schneider Electric:

The address range often starts with 40001hex, which corresponds to an offset with thevalue "0".

Page 45: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 45

8Protocol structureModbus Protocol (Modbus/TCP)

8.1.2 Services (function codes)

For process data exchange, parameter data exchange and unit identification, theUHX71B-OSR71B provides 4 FC.. services (Function Codes).

• FC 3 Read Holding Registers

• FC16 Write Multiple Registers

• FC23 Read/Write Multiple Registers

• FC43 Read Device Identification

The FC3 and FC16 services allow reading or writing of one or more registers. FC23 al-lows a register block to be read and written simultaneously. FC43 can be used for a unitidentification by reading out the identity parameters.

8.1.3 AccessThe implemented registers and possible services (function codes) for data exchangeare summarized in the following table.

8.2 Protocol structureThe Modbus protocol consists of a header and function code data. The header is thesame for all request/response telegrams and error messages (exceptions). Dependingon the function code, a different number of data is attached to the header (see followingpicture).

Meaning of

Offset (hex) Read Write Access Comment

0 – 3 - - - Reserved

4 – FF Process input data (actual val-ues)

Process output data (setpoint values)

FC3, FC16, FC23

0 – 64 words

100 – 103 - - - Reserved

104 – 1FF Process output data (setpoint val-ues)

- FC3 For reading the setpoint values by a client other than the controlling one

200 – 2FF Result acyclical parameter chan-nel

Request acyclical parameter channel

FC3, FC16, FC23

4 words

300 – FFFF - - - Reserved

Special case: 219E (8606dec)

Fieldbus timeout interval, read value

Fieldbus timeout interval, write value

FC3, FC16 Parameter P819: 16-bit value, tim-eout interval in ms

7971408907

MBAP Header

Transaction-ID Protocol-ID Length (1+1+N) UI-D

Function Code-Data

FC N Data

00

I

Page 46: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

46 Manual – UHX71B Controller with OSR71B Fieldbus Interface

8 Protocol structureModbus Protocol (Modbus/TCP)

8.2.1 HeaderThe protocol bytes of the header are described in the following table:

• The slave simply copies the transaction identifier (byte 0 and 1). It can help the mas-ter to identify related actions.

• The Protocol identifier (byte 2 and 3) must always be "0".

• The length bytes (byte 4 and 5) specify the number of bytes occurring in the lengthfield. As the maximum telegram length is 255 bytes, the "upper byte" must be "0".

• The unit identifier (byte 6) can be used for distinguishing between several connectedstations (e.g. bridges or gateways). It has the function of a subaddress that is onlyused for parameter access in SEW units. The process data are always mapped tothe unit that is addressed via the unit identifier 0 or FFhex.

• The 7 bytes of the header are followed by the function code and the data.

Byte Designation Meaning

0Transaction identifier Often "0", is simply copied by the server (slave)

1

2Protocol identifier 0

3

4 Length field (upper byte) 0

5 Length field (lower byte) Number of function codes data bytes +1 (Unit identifier)

6 Unit identifier (slave address) This is the slave address. In order to access the UHX71B-OSR71B process data, it must be set to "0" (0x00) or 255 (0xFF).The following address assignments apply to the parameter chan-nel access (Offset 200 - 203hex):• 0 or 254 for parameters of the UHX71B-OSR71B• 1 - 253 for parameters of a lower-level unit connected to

UHX71B-OSR71B. The assignment of unit identifier to the units on the system buses is determined via the routing table on the UHX71B-OSR71B memory card (see chapter Appen-dix).

7 Function code Requested service

8 ... Data Data depending on requested service

00

I

Page 47: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 47

8Protocol structureModbus Protocol (Modbus/TCP)

8.2.2 Service FC3 – Read Holding Registers

With the service FC3 Read holding registers, you can read a variable number of regis-ters (see following figure).

Example Request:

Response:

Exception:

7971446283

MBAP Header Function Code-Data(FC03)

FC(0x03) Read Address Read WordCountT- ID (0x00) Prot-ID (0x00) Length (1+5) UI-D

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Requested service: 3 (Read Holding Register)

8 Reference number (high) Offset

9 Reference number (low) Offset

10 Word count (high) Number of words (register)

11 Word count (low) Number of words (register)

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Service: 3 (Read Holding Register)

8 Byte count Number of following bytes

9.... Data 2 – ... Data bytes depending on length

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code 83hex

8 Exception Code Error code

00

I

Page 48: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

48 Manual – UHX71B Controller with OSR71B Fieldbus Interface

8 Protocol structureModbus Protocol (Modbus/TCP)

8.2.3 FC16 – Write Multiple Registers

With the service FC16 Write Multiple Registers you can write a variable number of reg-isters (see following figure).

Example Request:

Response:

Exception:

7971450763

MBAP Header Function Code-Data(FC16)

FC(0x10)

T- ID (0x00) Prot-ID (0x00) UI-D(0x00)

Length(1+6+N) Write Address Write WordCount

Bytes(N)

Write Data(1 ... N)

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Requested service: 16 (Write Multiple Registers)

8 Reference number (high) Offset

9 Reference number (low) Offset

10 Word count (high) Number of words (register)

11 Word count (low) Number of words (register)

12 Byte count 2* Word Count

13 ... Register values 2 – ... Data bytes depending on length

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Service: 16 (Write Multiple Registers)

8 Reference number (high) Offset

9 Reference number (low) Offset

10 Word count (high) Number of words (register)

11 Word count (low) Number of words (register)

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code 90hex

8 Exception Code Error code

00

I

Page 49: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 49

8Protocol structureModbus Protocol (Modbus/TCP)

8.2.4 Service FC23 – Read/Write Multiple Registers

With the service FC23 Read/write multiple registers, you can simultaneously write andread a variable number of registers. The write access is carried out first. Preferably, thisservice is used for the process data (see following picture).

Example Request:

Response:

Exception:

7971469067

MBAP Header Function Code-Data (FC23)

Bytes(N) (1...N)

FC(0x17)

T- ID (0x00) Prot-ID (0x00) UI-DLength(1+10+N)

Read Address Write Address Write DataReadWordCount

Write WordCount

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Requested service: 23 (Read/Write Multiple Registers)

8 Read reference number (high)

Offset

9 Read reference number (low)

Offset

10 Read word count (high) Number of words (register) always 0

11 Read word count (low) Number of words (register)

12 Write reference number (high)

Offset

13 Write reference number (low) Offset

14 Write word count (high) Number of words (register) always 0

15 Write word count (low) Number of words (register)

16 Write byte count 2* Word Count

17 ... Write register values 2 – ... Data bytes depending on length

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Service: 23 (Read/Write Multiple Registers)

8 Byte count Number of following bytes

9 Data 2 – ... Data bytes depending on length

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code 97hex

8 Exception Code Error code

00

I

Page 50: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

50 Manual – UHX71B Controller with OSR71B Fieldbus Interface

8 Protocol structureModbus Protocol (Modbus/TCP)

8.2.5 Service FC43 - Read Device Identification

The service FC43 Read Device Identifications is also referred to as MEI ("Modbus En-capsulated Interface Transport"). It can tunnel services and method calls. The serviceRead Device Identification is tunneled with the MEI-Type 0x0E. According to the Mod-bus specifications, there are 3 blocks Basic, Regular and Extended that can be read.The UHX71B-OSR71B supports the Basic and Regular blocks (conformity level 02).The entire block is always read (streaming). This means that values 01 and 02 are per-mitted in the Read Device ID Code. The Object ID must be zero. The response is notfragmented.

Example Request:

Response:

Exception:

Objects UHX71B-OSR71B

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Requested service: 43 (Read Device Identification)

8 MEI type 0x0E

9 Read device ID code 01 or 02

10 Object ID 0

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code Service: 43 (Read Device Identification)

8 MEI type 0x0E

9 Read device ID code 01 or 02

10 Conformity level 02

11 More follows 0

12 Next object ID 0

13 Number of objects e.g. 3

14 Object ID

15 Object length

16 Object value

17 ....

Byte Designation Meaning/permitted values

0 – 6 MBAP header See section "Header"

7 Function code 43hex

8 Exception Code Error code

Object ID Name Type M/O Category Value (example)

0x00 VendorName

ASCII string

Mandatory Basic

"SEW-EURODRIVE"

0x01 ProductCode "SEW CONTROLLER POWER"

0x02 MajorMinorRevisons "823 568 0.10" (e.g.)

0x03 VendorUrl

Optional Regular

"www.sew.de"

0x04 ProductName "SEW CONTROLLER POWER"

0x05 ModelName "UHX71B-OSR71B"

00

I

Page 51: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 51

8Connection managementModbus Protocol (Modbus/TCP)

8.3 Connection managementUp to 8 simultaneous Modbus connections are possible, max. one of which has writeaccess to the process data area (controlling connection).

Connections that are no longer used must be disconnected by the master. If a ninth con-nection is required and the slave detects an inactive connection, the slave disconnectsthe inactive connection as it presumes that the corresponding master is no longer active.If there are 8 active connections, the attempt to establish a ninth connection is cancelled(socket is closed on the server). Connections 1 - 8 operate independently of each other.There is no prioritization. Only one controlling connection that can change process datais permitted.

If a controlling connection has already been established via EtherNet/IP, you cannot es-tablish another controlling connection via Modbus/TCP. The slave can at least bufferone frame with maximum Modbus length on receipt or transmission.

8.3.1 Sending process output data (requesting controlling connection)Sending process output data is only permitted if the connection already is a controllingconnection or if there is no controlling connection. If the unit accepts the connection, ittransfers the process output data to the process data image or transmits the processdata to a lower-level station (gateway operation). As long as this connection is activated,no other master can change the process output data (PO data).

8.3.2 Dropping connectionsA connection is deleted from the internal connection list in the following cases:

• if the "keep alive" time has elapsed and the server no longer receives a response, or

• if the socket reports an error

• if the connection to the client has been dropped

If it was a controlling connection, another controlling connection can be established.If no valid PO data has been sent within the timeout interval, a fieldbus timeout is trig-gered.

The default keep-alive time is 10 seconds. If there is a controlling connection with thetimeout interval > 5 s, the keep-alive time is increased to 2 × timeout interval.

In a controlling connection, the fieldbus timeout is displayed in the unit after the set tim-eout interval elapses during a break in the cable or an error in the socket. Then a newcontrolling connection can be established.

8.3.3 Timeout monitoring

INFORMATIONFor Modbus/TCP, the timeout monitoring must take place in the application (e.g. via atoggle bit).

00

I

Page 52: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

52 Manual – UHX71B Controller with OSR71B Fieldbus Interface

9 Diagnostic procedureError Diagnostics for Operation on EtherNet/IP and Modbus/TCP

9 Error Diagnostics for Operation on EtherNet/IP and Modbus/TCP9.1 Diagnostic procedure

The diagnostic procedures described below demonstrate the integration of theUHX71B-OSR71B into an Ethernet network and the error analysis method for the fol-lowing problems:

• The UHX71B-OSR71B controller is not integrated properly in the EtherNet/IP orModbus/TCP network

• The master (scanner) cannot specify any process data.

For further information regarding the programming of the UHX71B-OSR71B, refer to themanual "MultiMotion for MOVI-PLC®".

For more diagnostic information, refer to the online status display in the EtherNet/IPmaster (scanner), in the Modbus/TCP master and the corresponding online help.

9.1.1 Step 1: Checking the LED statusCheck the status of the LED on the UHX71B-OSR71B acc. to chapter "Status LED".

In order to check and set the IP parameters, you can proceed according to section "Set-ting IP address parameters" or use MOVITOOLS® MotionStudio.

The PING and IPCONFIG commands that you can enter via the DOS console on yourPC are further tools for checking the communication via Ethernet.

9.1.2 Step 2: Check the Status LED and the Status display of the master (scanner)To do so, use the documentation of the controller or master module.

Should there be no working EtherNet/IP or Modbus/TCP master yet, you can use anSEW master simulator for testing or starting up the UHX71B-OSR71B. The latest ver-sion of the master simulator is available on the SEW website.

You can use the SEW master simulator to exchange process or parameter data withEtherNet/IP or Modbus/TCP profile with an SEW fieldbus interface.

9.1.3 Step 3: Error diagnosticsIf the UHX71B-OSR71B is in the "Connected" status, data exchange between master(scanner) and slave is active. If the data is not transferred to the IEC application of theUHX71B-OSR71B via EtherNet/IP or Modbus/TCP correctly, the following steps will as-sist you in finding the cause for the problem.

A Are the correct values for the process data words displayed in the PLC Editor?

If yes, continue with F.

B Is the process data exchange activated in the scanner (master)?

C Is the process data written to the correct location in the scanner? Check the tags andscanner mapping.

D Is the PLC in RUN mode or does active forcing overwrite the transfer of the normalprocess data words?

E If the PLC does not transmit data to the UHX71B-OSR71B, refer to the documenta-tion of the PLC manufacturer for support.

F Are the process data words being used correctly in the IEC program?

00

I

Page 53: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 53

9Diagnostic procedureError Diagnostics for Operation on EtherNet/IP and Modbus/TCP

G Which status is displayed in the IEC application for the communication interface viathe FBusGetInfo module (see chapter Settings in the UHX71B-OSR71B)?

Page 54: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

54 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 Installing the GSDML file for UHX71B-OSR71BPROFINET IO Configuration

10 PROFINET IO Configuration10.1 Installing the GSDML file for UHX71B-OSR71B

Proceed as follows to install the GSD file:

1. Start STEP 7 HW Config and select the [Install new GSD file] menu item from the[Extras] menu.

A window is displayed.

2. Click [Browse] and select the GSDML file matching the UHX71B-OSR71B SEW con-troller:

"yyyymmdd" represents the date.

3. Click [OK] for confirmation.

4. You find the PROFINET IO interface for the respective controller in the hardware cat-alog under [PROFINET IO] / [Other field units] / [Drives] / [SEW] / [SEW controllers].

For more information regarding the PROFINET interface of the UHX71B-OSR71B,refer to chapter "Configuring a PROFINET interface for the UHX71B-OSR71B".

INFORMATIONThe latest versions of the GSD(ML) files are available for download from the SEWwebsite (www.sew-eurodrive.com). You find them in the "Software" section of the re-spective units.

GSDML file SEW controllerGSDML-V2.1-SEW-Controller-Power-yyyymmdd.xml UHX71B

Page 55: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 55

10Assigning a PROFINET device namePROFINET IO Configuration

10.2 Assigning a PROFINET device nameProceed as follows to assign the PROFINET device name:

1. Select [Ethernet]/[Edit Ethernet node ...] from the [Target system] menu in STEP 7HW Config.

The following window opens:

2. Click the [Browse...] [1] button in the "Ethernet node " group. You receive an overviewof all PROFINET IO nodes that you can reach online with your configuration tool.

In addition, you can use the flash test to visually locate the nodes. For more informa-tion, refer to section "Status LED in PROFINET operation".

3. Choose the required node.

9007200469135755

[1] [Browse...] button[2] "IP address" edit box[3] "Subnet mask" edit box[4] "Router address" edit box[5] "Assign IP configuration" button[6] "Device name" edit box[7] "Assign name" button[8] [Close] button

[1]

[4]

[7][6]

[5]

[2]

[3]

[8]

Page 56: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

56 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 Configuring the PROFINET interface for the UHX71B-OSR71B controllerPROFINET IO Configuration

The SEW node appears under device type. Assign an appropriate device name. Sev-eral SEW controllers can be differentiated by the displayed MAC addresses. TheMAC address is affixed to the SEW controller.

4. Enter the device name in the "Device name" edit box [6] and click the [Assign name]button [7].

The device name can have up to 255 characters. The characters "." (dot) and "_" (un-derscore) are not permitted. The device name is transmitted to and saved by thenode.

You can reset the device name of the SEW controller online using the [Reset] button.You will then have to restart the SEW controller.

5. Specify an IP address [2] and a subnet mask [3] as well as a router address [4], ifrequired.

Click the [Assign IP configuration] button [5].

6. Check whether the settings have been applied by clicking the [Browse] button [1]again.

7. Click the [Close] button [8].

10.3 Configuring the PROFINET interface for the UHX71B-OSR71B controller10.3.1 Creating a new project

Proceed as follows to create a new project:

1. Start the SIMATIC Manager and create a new project.

Select your control type and add the required modules. The following modules makesense:

• OB82 module: This module makes sure that the controller does not trigger"STOP" in the event of so-called diagnostic alarms.

• OB86 module: This module indicates the failure of decentralized peripherals.

• OB122 module: This module is called if the controller cannot access data of anode of the decentralized periphery. This can occur, for example, when theUHX71B-OSR71B controller is ready for operation later than the controller.

2. Start STEP 7 HW Config and select the PROFINET IO slot in the control rack.

3. Add a PROFINET IO system by right-clicking the context menu with your mouse.

4. Specify an IP address for the PROFINET IO controller when doing this.

5. Add a new PROFINET subsystem by clicking the [ETHERNET] button.

6. Open [PROFINET IO] / [Additional Field Devices] / [Drives] / [SEW] / [Controller] inthe hardware catalog.

7. Move the entry "UHX71B V1.0" to the PROFINET IO system with the mouse and as-sign a PROFINET station name. This name must correspond to the PROFINET de-vice name specified in the UHX71B-OSR71B controller.

8. Enter the IO and periphery addresses in slot 2 and save the configuration.

INFORMATIONThe IO controller must not yet be in a cyclic data exchange with the IO devices.

Page 57: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 57

10Configuring the PROFINET interface for the UHX71B-OSR71B controllerPROFINET IO Configuration

The slot model is used for configuration with PROFINET. Each slot is assigned to acontroller fieldbus interface. The following structure is used:

Do not modify the default configuration "Slot not used". Slot 1 is reserved for futurePROFIsafe applications.

Slots 2 – 17 can be assigned process data channels. The maximum process datawidth is 64 words.

9. Expand your user program by data exchange with the new units. Process data trans-fer is consistent. SFC14 and SFC15 can be used to transfer process data.

8230522251

Page 58: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

58 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 Configuring the PROFINET interface for the UHX71B-OSR71B controllerPROFINET IO Configuration

10.3.2 Configuring a node

Once the individual slots are configured, further settings have to be made for the newnode.

Proceed as follows to configure a node:

1. Double-click on the device symbol of the new node.

The following window opens:

2. Enter the device name mentioned above in the "Device name" edit box [2] on the"General" tab.

Note that the name is case-sensitive.

3. Click on the [ETHERNET] button [3] in the "Station/PN IO system" group in order toenter the previously assigned IP address.

8230526731

[1] "General" tab[2] "Device name" edit box[3] [ETHERNET] button

[1]

[2]

[3]

Page 59: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 59

10PROFINET configuration with topology detectionPROFINET IO Configuration

10.4 PROFINET configuration with topology detection10.4.1 Introduction

PROFINET topology detection allows for configuring and monitoring the structure of thenetwork with the PROFINET IO controller in addition to the PROFINET IO devices.

The so-called "Physical device (PHDEV)" is the starting point for configuration. PDEV isa model for the Ethernet interface and can be found in slot 0 in the configuration with an"Ethernet interface" subslot and one subslot for each Ethernet port.

The Ethernet ports made visible in this way can be connected to the configuration tool.The result is an image of the desired Ethernet routing for the plant. This image is storedin the PROFINET IO controller.

To determine the real plant topology, the PROFINET IO devices must support the so-called LLDP (Link Layer Discovery Protocol). The PROFINET IO devices exchangeinformation with the neighboring PROFINET IO devices via LLDP. Via LLDP, eachPROFINET IO device cyclically sends information using its own PROFINET devicename and port number. The neighboring unit receives and stores this information. APROFINET IO controller can now read the stored information from the PROFINET IOdevices and determine the real plant topology.

By comparing the configured topology with the real topology, you can detect any missingor incorrectly wired PROFINET IO devices and localize them in the plant.

Apart from cabling you can still determine the transmission characteristics for the ports.For example, you can set an "Auto-negotiation" port to "100 Mbit full duplex". Thesettings will be monitored.

SNMP as a protocol for network diagnostics extends the topology detection by standarddiagnostics mechanisms from the IT area.

10.4.2 Creating a PROFINET IO project and starting the topology editorThe following section describes the configuration procedure for a PROFINET topologywith the SIMATIC STEP 7 topology editor. Configuration can be performed in differentways in SIMATIC STEP 7. This example will focus on one approach.

1. In STEP 7 HW Config, import the PROFINET IO devices from the hardware cataloginto the PROFINET IO network as usual.

Make sure that the PROFINET IO controller supports topology detection. The con-troller manufacturer will provide according information.

Page 60: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

60 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 PROFINET configuration with topology detectionPROFINET IO Configuration

The hardware catalog contains several entries for each SEW interface marked as dif-ferent versions. An entry marked with "OLD" does not support the PROFINET IO to-pology detection.

2. Right-click on "PROFINET IO system" and select "PROFINET IO topology" from thecontext menu to open the topology editor.

The "Topology editor" window is displayed.

3. Proceed according to chapter "Specifying the topology".

10.4.3 Specifying the topology and detecting faulty connectionsTopology detec-tion with topology editor

The purpose of topology detection is to compare the current topology (online topology)with the configured topology (offline topology). Any deviation suggests faulty connec-tions in the PROFINET network.

The following section provides an introduction as to how to use the topology editor tospecify PROFINET nodes and detect faulty connections to ports.

Refer to the online help for a detailed description and important additional information(e.g. the color code of the comparison results).

Click [Help] to open the online help in the open topology editor.

Specifying the topology

Proceed as follows to specify the topology of nodes in a PROFINET network:

1. Start the topology editor according to section "Creating a PROFINET project andstarting the topology editor".

2. Select the "Offline/online comparison" tab [6].

7975727371

Page 61: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 61

10PROFINET configuration with topology detectionPROFINET IO Configuration

3. Click [Start] [1] to determine the online topology and compare it with the configuredtopology (offline topology).

The left part of the window displays the "Configured topology (offline)" list [5] and theright part displays the "Detected topology (online)" list [3].

The color code (the online help) and the order of the entries provide information re-garding the comparison result.

4. Make sure that the assignment corresponds to your requirements and is applied tothe configuration.

• If required, change the assignment of the devices. To do so, select the respectivedevice in both lists and click [Assign] [4].

5. Make sure that the connection of the partner ports corresponds to your requirementsand is applied to the configuration.

• Click the plus sign [2] in front of the respective device in the right part of the win-dow (online topology) [3] to display the partner ports.

• Change the connection of the partner ports if required. To do so, select the re-spective port and choose [Apply port connection] from the context menu (right-click).

To disconnect port connections, mark the respective port in the left part of the win-dow and select [Interrupt port connection].

• Repeat the procedure until all ports in the list are marked "green".

Detecting faulty connections

Faulty connections can be detected in the graphic view of the topology editor.

Proceed as follows to switch to the graphic view:

1. Start the topology editor according to section "Creating a PROFINET project andstarting the topology editor".

2. Select the "graphic view" tab [1].

9007200652515339

[1] [Start] button[2] Plus symbol/minus symbol[3] "Online topology" list[4] [Assign] button[5] "Offline topology" list[6] "Offline/online comparison" tab

[6]

[1]

[4]

[3][5]

[2]

Page 62: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

62 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 PROFINET configuration with topology detectionPROFINET IO Configuration

The graphic view provides a clear display of your PROFINET network (offline or on-line) with all devices and connected ports.

Faulty connections between ports are indicated by red lines.

3. Move the cursor over the port with the faulty connection [2] to display a status mes-sage for the error.

The example illustrates a faulty connection between the controller and "port 1" of thefirst device. The faulty connection is indicated by a red connection line and the statusmessage to the port.

10.4.4 Changing port propertiesThe two Ethernet ports of the PROFINET interface are set to "Automatic setup" by de-fault. Observe the following for this default setup:

• Auto-negotiation and auto-crossover are activated in this setup.

• Baud rate and duplex mode are configured automatically.

• The neighboring port must also be set to "Automatic setup".

• You can use patch or crossover cables.

You can set a port to "100 Mbit/s full duplex". Observe the following for this setup:

• This setting must also be made for the port of the neighboring unit, otherwise it wouldwork with 100 Mbit/s half duplex.

• If auto-crossover is deactivated, you have to use cross cables.

Proceed as follows to set a port to "100 Mbit/s full duplex":

1. Select a unit in STEP 7 HW Config.

2. Select the desired port on slot 0.

3. Right-click on the port and select "Object properties" from the context menu.

A window is displayed.

2379075979

[1] "Graphic view" tab[2] Port with faulty connection

[1]

[2]

Page 63: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 63

10PROFINET configuration with topology detectionPROFINET IO Configuration

4. Select the "Options" tab [1].

5. From the "Transmission medium/duplex" [2] drop-down menu select "TP/ITP with100 Mbit/s full duplex".

6. Deactivate "Auto-negotiation/auto-crossover" checkbox [3].

7975898507

[1] "Options" tab[2] "Transmission medium/duplex" drop-down

menu[3] "Auto-negotiation/auto-crossover" checkbox

[2]

[1]

[3]

Page 64: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

64 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 PROFINET configuration with topology detectionPROFINET IO Configuration

10.4.5 Topology diagnosticsTopology errors are reported to the PROFINET IO controller as diagnostics alarms. Inthe event of an error, the EXTF-LED of the PROFINET IO controller is lit. The error isalso indicated by a red cross [1] in STEP 7 HW Config.

Possible causes:

• Ethernet ports swapped

• Incorrectly set port properties

• Units cannot be addressed

Proceed as follows to display information about an error:

1. Select the unit or the respective slot.

2. Right-click and select "Module status" from the context menu.

A window is displayed.

3. Select the "Communication diagnostics" tab.

7975757451

[1] "Red cross" – symbol for errors

[1]

[1]

[1]

Page 65: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 65

10PROFINET configuration with topology detectionPROFINET IO Configuration

10.4.6 Port statistics

Proceed as follows to display the port statistics for an Ethernet port in STEP 7 HW Con-fig:

1. Click the "ONLINE ↔ OFFLINE" symbol, to switch to "online" communication mode.

2. Select a unit.

3. Select the desired port on slot 0.

4. Right-click and select "Module status" from the context menu.

A window is displayed.

Select the "Statistics" tab [1].

The following view is displayed:

The following statistic values can be displayed:

• Dropped received packets – no resources Shows the number of valid Ethernetpackets discarded upon reception. A large number of discarded valid packets sug-gests a high load on the bus system. In this case, try to reduce the utilization by re-ducing in particular the number of broadcast and multicast telegrams and reducingthe IO cycle or the number of PROFINET units in a line if required.

• Bad received packets Shows the number of faulty Ethernet packets. A high numbersuggests a bus error. In this case, check the cabling and shielding of the network.

• Received octets Shows the number of received packets.

• Dropped sent packets – no resource Shows the number of valid Ethernet packetsdiscarded during transmission. A large number of discarded valid packets suggestsa high load on the bus system. In this case, try to reduce the utilization by reducingin particular the number of broadcast and multicast telegrams and reducing the IOcycle or the number of PROFINET units in a line if required.

7975762187

[1] "Statistics" tab

[1]

Page 66: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

66 Manual – UHX71B Controller with OSR71B Fieldbus Interface

10 PROFINET configuration with topology detectionPROFINET IO Configuration

• Bad sent packets – transmit collisions Shows the number of discarded Ethernetpackets due to collisions. There should be no collisions in a switched network.

• Sent Octets shows the number of transmitted packets.

Page 67: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 67

11Process data exchange with the SEW controllerOperating Behavior on PROFINET IO

11 Operating Behavior on PROFINET IOThis chapter describes the basic characteristics of the UHX71B-OSR71B controller con-nected to the PROFIBUS system.

11.1 Process data exchange with the SEW controllerThis chapter illustrates the basic behavior of the SEW controllers on the PROFINETfieldbus system.

The drive SEW controllers are controlled via the process data channel which is up to 120I/O process input and output words in length.

These process data words are mapped in the I/O or peripheral area when a higher-levelprogrammable logic controller is used as PROFINET IO controller, and can thus be ad-dressed in the usual way.

11.1.1 Control example for SIMATIC S7Depending on the selected process data configuration, the process data exchange withSEW controller via SIMATIC S7 is carried out via special system functions

• SFC14 DPRD_DAT and

• SFC15 DPWR_DAT

STEP 7 program example

In this example, the SEW controller is configured with the process data configuration 10PD to the input addresses PIW512... and output addresses POW512... .

A data block DB3 is created with about 50 data words.

7988296203

LAN

3

X2

LAN

4USB1 USB2 USB3

X1 OnM-24+

X21

X22

L23.1

L23.4

PW160

PW160

PA 3

PE 3

PA 2

PE 2

PA 1

PE 1

PW158

PW158

PW156

PW156

PA 1

PE 1 PE 2

PA 2

PE 3

PA 3

PE 120

PA 120[1]

UHX71B - OSR71B

[1] Address range of the higher-level PLCPI1 – PI120 Process input dataPO1 – PO120 Process output data

Page 68: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

68 Manual – UHX71B Controller with OSR71B Fieldbus Interface

11 Process data exchange with the SEW controllerOperating Behavior on PROFINET IO

When SFC14 is called, the process input data is copied to data block DB3, data words0 to 18. When SFC15 is called after the control program has been processed, the pro-cess output data is copied from data words 20 – 38 to the output address POW 512....

Note the length specification in bytes for the RECORD parameter. The length informa-tion must correspond to the configured length.

Refer to the online help for STEP 7 for detailed information about the system functions.

//Start of cyclical program processing in OB1BEGINNETWORKTITLE = Copy PI data from the DHR41B control card to DB3, words 0...18CALL SFC 14 (DPRD_DAT) //Read DP Slave RecordLADDR := W#16#200 //Input address 512RET_VAL:= MW 30 //Result in flag word 30RECORD := P#DB3.DBX 0.0 BYTE 20 //PointerNETWORKTITLE =PLC program with drive application// PLC program uses the process data in DB3 for data exchange// with the DHR41B control cardL DB3.DBW 0 //Load PI1L DB3.DBW 2 //Load PI2L DB3.DBW 4 //Load PI3// etc.L W#16#0006T DB3.DBW 20 //Write 6hex to PO1L 1500T DB3.DBW 22 //Write 1500dec to PO2L W#16#0000T DB3.DBW 24 //Write 0 hex to PO3// etc.NETWORKTITLE = Copy PO data from DB3, words 20...38 to the DHR41B control cardCALL SFC 15 (DPWR_DAT) //Write DP slave recordLADDR := W#16#200 //Output address 512 = 200 hexRECORD := P#DB3.DBX 20.0 BYTE 20 //Pointer to DB/DWRET_VAL:= MW 32 //Result in flag word 32

INFORMATION• This program example is a special and free service that demonstrates only the

basic principles of generating a PLC program as a non-binding sample. SEW is notliable for the contents of the sample program.

• For S7 sample projects, refer to the "Software" section on the SEW website.

00

I

Page 69: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 69

11Settings in the UHX71B-OSR71B controllerOperating Behavior on PROFINET IO

11.2 Settings in the UHX71B-OSR71B controllerThe creation of IEC programs is described in detail in the "MultiMotion for MOVI-PLC®"manual. This is why only the fieldbus-specific characteristics are described in this chap-ter.

11.2.1 Process data configuration of the PROFINET slaveThe configuration of the process data interface is performed by the fieldbus master. Itsets the number of process data words and the timeout interval. For information regard-ing the current settings, refer to the parameter tree in MOVITOOLS® MotionStudio viamenu [Display values] / [Bus diagnostics].

11.2.2 Status of the PROFINET fieldbus interface The FbusGetInfoV2 function block makes the status and some display parameters ofthe fieldbus interface available for the IEC program and for diagnostics.

If there is no communication with the fieldbus master, the output Error is set to TRUE.During an active fieldbus connection, the output Done is set to TRUE, and the outputsAddress, Baud rate, timeout and Bus type show the respective parameters as they wereset via the parameter tree in MOVITOOLS® MotionStudio or via PLC.

8230094987

7628791563

FBusGetInfoV2

Enable Done

Type

ErrorID

Baudrate

Timeout

BusType

Address

BusState

PdConfig

BOOL BOOL BOOL

BOOL

UDINT

UDINT

UDINT

T_PLC_BUS_TYPE

T_PLC_BUS_STATE

T_PLC_BUS_PD_CONFIG

00

I

Page 70: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

70 Manual – UHX71B Controller with OSR71B Fieldbus Interface

11 Settings in the UHX71B-OSR71B controllerOperating Behavior on PROFINET IO

11.2.3 Checking the process data communicationNow actual values can be read from the UHX71B-OSR71B controller and setpoint val-ues can be written. The process data should correspond with the values displayed in thePLC Editor or in the diagnostics plug-in of the active IEC program in MOVITOOLS® Mo-tionStudio.

INFORMATIONFor more detailed information on process data communication in the IEC program,refer to the publication "MultiMotion for MOVI-PLC®".

Page 71: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 71

12Diagnostic proceduresError Diagnostics on PROFINET

12 Error Diagnostics on PROFINET12.1 Diagnostic procedures

The diagnostics procedures described in the following section demonstrate the erroranalysis methods for the most frequent problems:

• The UHX71B-OSR71B controller does not work on PROFINET IO

• The UHX71B-OSR71B controller cannot be controlled using the IO controller

INFORMATIONFor further information on the programming of the UHX71B-OSR71B controller, referto the publication "MultiMotion for MOVI-PLC®".

00

I

Page 72: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

72 Manual – UHX71B Controller with OSR71B Fieldbus Interface

12 Diagnostic proceduresError Diagnostics on PROFINET

12.1.1 Diagnostic problem 1: UHX71B-OSR71B does not work on PROFINET IO

Initial status:• UHX71B-OSR71B is physically connected to PROFINET IO• UHX71B-OSR71B has been configured in the IO controller and bus communication

is active

Ethernet bus connector X21, X22 plugged in? No → [A]Yes↓

Yes↓

Response of the Link LED? OFF → [B] Response of the

BUS FAULT LED? Red → [B]

Green↓

Off↓

UHX71B-OSR71B has no connection to Ethernet.

Compare the set PROFINET name to the configured one.

PROFINET names identical? No → [C]Yes↓

You may have configured an incorrect unit type or defined an incorrect configuration.

Delete configuration for the UHX71B-OSR71B option from the PROFINET IO network.

Configure the UHX71B-OSR71B option again, selecting the unit designation "UHX".Assign the address ranges for your control system.

Load the configuration data into the PROFIBUS IO controller master and restart the bus communication.

[A] Check the bus cabling.

[B] The UHX71B-OSR71B option indicates that the PROFINET IO con-troller has not yet established communication.

The PROFINET IO controller is switched off or has not yet been started up.

[C] Adapt PROFINET names

Page 73: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 73

12Diagnostic proceduresError Diagnostics on PROFINET

12.1.2 Diagnostic problem 2: No process data exchange with the I/O controller

• Check the settings in the higher-level I/O controller again.

Is the user program switched off correctly? (see sample program in chapter "Processdata exchange with the UHX71B-OSR71B controller")

• Check the settings on the UHX71B-OSR71B controller (see chapter "Settings on theUHX71B-OSR71B controller")

Page 74: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

74 Manual – UHX71B Controller with OSR71B Fieldbus Interface

13 Overview of parametersAppendix

13 Appendix13.1 Overview of parameters

The following tables show the assignment of MOVILINK® indexes to the respective field-bus option.

The following abbreviations are used:

13.1.1 Bus independent parameters

Fieldbus AbbreviationPROFIBUS PBPROFINET PNEtherNet/IP EPModbus/TCP MB

MOVILINK® MeaningIndex Subindex8451 0 Process data configuration (Modbus/TCP: always120 process data words)8452 0 Fieldbus type8362 0 Option 110497 1 Fieldbus timeout

For Modbus/TCP, additonal timeout monitoring is necessary according to the applica-tion.

10530 1 Item number10530 2 Serial number10530 3 Fieldbus version 1 (2 ×16 bits: major/minor)10530 4 Fieldbus version 2 (2 ×16 bits: revision/build)10530 5 Firmware load state10530 6 Firmware load error10530 7 Fieldbus selection10530 8 Bootloader version 110530 9 Bootloader version 210530 10 Hardware revision15800.0 – 15863.015864.1 – 15864.56

Process data IN (PO)

15900.0 – 15963.015964.1 – 15964.56

Process data OUT (PI)

Page 75: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 75

13Overview of parametersAppendix

13.1.2 Bus dependent parameters

MOVILINK® Meaning PB PN EP MBIndex Subindex8606 0 Fieldbus timeout x x x8454 0 Profibus address x8453 0 Fieldbus baud rate x10520 1 ACD Enable x10520 2 ACD Last Activity x10520 3 ACD Last MAC Low x10520 4 ACD Last MAC High x10520 5 ACD Last IP x9233 0 DHCP startup control x x8992 0 IP address x x8993 0 Subnet mask x x x8994 0 Default gateway x x x8995 0 MAC Address Low x x x8996 0 MAC Address High x x x8997 0 Ethernet baud rate x x x10093 Blob PROFINET device name x

Page 76: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 76

Index

Index

AAppendix ................................................................74

Overview of parameters.....................................74Assembly and installation notes for Ethernet .........13Assigning a PROFINET device name....................55Auto-crossing .........................................................15

BBus system ............................................................11

CCharacteristics, overview .......................................12

Monitoring functions...........................................12Parameter access ..............................................12process data exchange......................................12

CIP object directory (EtherNet/IP)Assembly object.................................................32Ethernet link object ............................................33Identity object.....................................................30Message router object .......................................31

CIP object directory (Ethernet/IP)TCP/IP interface object ......................................33

ConfigurationPROFINET topology ..........................................59

Configuration and startup on the fieldbusEthernet/IP .........................................................22Configuring the master (Ethernet/IP scanner) ...22EDS file ..............................................................22

Configuration and startup (Modbus/TCP) ..............36Configuring the master (Modbus scanner).........36Data exchange via Modbus/TCP – examples....41Project planning example in PL7 PRO...............39Settings in the UHX71B-OSR71B controller ......39

Configuration of the master (Modbus scanner)Addressing the drive using I/O scanning ...........38Settings for the Ethernet component .................37

Configuring the master (EtherNet/IP scanner)Other settings.....................................................25Process data exchange .....................................23

Configuring the master (Ethernet/IP scanner)Project planning example in RSLogix 5000 .......27

Configuring the master (Modbus scanner)Hardware configuration......................................36

Configuring the PROFINET interface for the UHX71B-OSR71B controllerConfiguring stations ...........................................58Creating a new project.......................................56

Connecting UHX71B-OSR71B to an Ethernet networkEstablishing a connection ..................................14Pin assignment X21 and X22 ............................13Shielding and installing bus cables....................14

Connection management (Modbus/TCP) ..............51Disconnecting connections ................................51Sending process output data .............................51Timeout connections..........................................51

Content of the manual ...........................................12Control example for SIMATIC S7 ..........................67

STEP 7 program example .................................67Copyright .................................................................9

DDiagnostics

PROFINET topology ..........................................64

EEmbedded safety notes ...........................................7Error diagnostics for operation on EtherNet/IP and

Modbus/TCP......................................................52Checking the LED status and the status display on the master (step 2) ...........................52Checking the LED status (step 1) ......................52Error diagnostics (step 3)...................................52

Error diagnostics for operation on PROFINETDiagnostic procedures .......................................71No process data exchange with the I/O controller ............................................................73UHX71B-OSR71B does not work on PROFINET IO....................................................72

Error diagnostics on PROFINET............................71EtherNet Industrial Protocol (EtherNet/IP).............29

Process data exchange .....................................29Ethernet Industrial Protocol (EtherNet/IP)

CIP object directory ...........................................30Introduction ........................................................29

Ethernet switch ......................................................15Auto-crossing.....................................................15Notes on multicast handling...............................15

Ethernet-SwitchAuto-negotiation.................................................15

Page 77: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

77 Manual – UHX71B Controller with OSR71B Fieldbus Interface

Index

Exclusion of liability ..................................................8

FFunctional safety technology

Safety note.........................................................11

GGSDML file.............................................................54

HHoist applications...................................................11

LLink/Activity LED ....................................................17L23.1, LED .............................................................16L23.2, LED .............................................................15L23.3, LED .............................................................16L23.4, LED .......................................................16, 17

MModbus protocol (Modbus/TCP) ............................44

Connection management...................................51Introduction ........................................................44Mapping and addressing....................................44Protocol structure...............................................45Services (function codes)...................................45

Multicast handling, notes .......................................15

NNotes

Designation in the documentation........................7

OOverview of parameters

Bus dependent parameters................................75Bus independent parameters.............................74

PPort statistics

PROFINET topology ..........................................65Process data exchange EtherNet/IP

Timeout response ..............................................29Process data exchange with the SEW controller

Control example for SIMATIC S7.......................67Product names.........................................................8

PROFINETTopology detection ............................................59

PROFINET IO configuration ..................................54Assigning PROFINET device name...................55Installing the GSDML file for UHX71B-OSR71B .............................................54

Protocol structure Modbus/TCPService FC3 - Read Holding Registers..............47

Protocol structure (Modbus/TCP)Header ...............................................................46Service FC16 - Write Multiple Registers............48Service FC23 - Read/Write Multiple Registers ..49Service FC43 - Read Device Identifications ......50

RReturn codes of the parameterization via explicit

messages (Ethernet/IP)General Error Codes..........................................35

Rights to claim under warranty ................................8

SSafety functions .....................................................11Safety notes

Designation in the documentation .......................7General information ...........................................10Structure of the embedded safety notes..............7Structure of the section safety notes ...................7

Section safety notes ................................................7Setting the IP parameters ......................................20

Changes after initial startup ...............................20Disabling/enabling DHCP ..................................21Initial startup ......................................................20

Shielding and routing bus cables...........................14Signal words in safety notes ....................................7Status LED.............................................................15

in EtherNet/IP operation ....................................15In PROFINET operation.....................................16Link/Activity........................................................17

Status LED in EtherNet/IP operationL23.2..................................................................15L23.3..................................................................16L23.4............................................................16, 17

Status LED in PROFINET operationL23.1..................................................................16L23.3..................................................................16

TTarget group ..........................................................10

Page 78: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

Manual – UHX71B Controller with OSR71B Fieldbus Interface 78

Index

TCP/IP addressing and subnetworks.....................18Dynamic Host Configuration Protocol (DHCP) ..20Introduction ........................................................18IP address..........................................................18MAC address .....................................................18Network classes.................................................19Standard gateway ..............................................20Subnet mask ......................................................19

Topology detection.................................................60PROFINET.........................................................59

Topology editor ......................................................60Trademarks..............................................................8

UUHX71B-OSR71B

Configuring the PROFINET interface ................56Connection to an Ethernet network ...................13Procedure after unit replacement ......................21Status LED.........................................................15

XX21, X22

Pin assignment ..................................................13

Page 79: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving
Page 80: UHX71B Controller with OSR71B Fieldbus Interface (EtherNet ... · with OSR71B Fieldbus Interface (EtherNet/IP, Modbus/TCP and PROFINET) Edition 04/2013 20101341 / EN. SEW-EURODRIVE—Driving

SEW-EURODRIVE—Driving the world

SEW-EURODRIVEDriving the world

www.sew-eurodrive.com

SEW-EURODRIVE GmbH & Co KGP.O. Box 3023D-76642 Bruchsal/GermanyPhone +49 7251 75-0Fax +49 7251 [email protected]