Upload
others
View
25
Download
0
Embed Size (px)
Citation preview
– 2 – IEC TR 62368-2:20xx © IEC 20xx
CONTENTS 1
FOREWORD ........................................................................................................................... 6 2
INTRODUCTION ..................................................................................................................... 9 3
0 Principles of this product safety standard ....................................................................... 10 4
1 Scope ............................................................................................................................ 13 5
2 Normative references ..................................................................................................... 13 6
3 Terms, definitions and abbreviations .............................................................................. 13 7
4 General requirements .................................................................................................... 16 8
5 Electrically-caused injury ............................................................................................... 23 9
6 Electrically-caused fire ................................................................................................... 70 10
7 Injury caused by hazardous substances ....................................................................... 105 11
8 Mechanically-caused injury .......................................................................................... 109 12
9 Thermal burn injury ...................................................................................................... 117 13
10 Radiation ..................................................................................................................... 127 14
Annex A Examples of equipment within the scope of this standard ................................. 134 15
Annex B Normal operating condition tests, abnormal operating condition tests and 16
single fault condition tests ................................................................................ 134 17
Annex C UV Radiation .................................................................................................... 137 18
Annex D Test generators ................................................................................................ 137 19
Annex E Test conditions for equipment containing audio amplifiers ................................ 138 20
Annex F Equipment markings, instructions, and instructional safeguards ........................ 138 21
Annex G Components ..................................................................................................... 139 22
Annex H Criteria for telephone ringing signals ................................................................ 147 23
Annex J Insulated winding wires for use without interleaved insulation ........................... 149 24
Annex K Safety interlocks ............................................................................................... 149 25
Annex L Disconnect devices ........................................................................................... 149 26
Annex M Equipment containing batteries and their protection circuits .............................. 150 27
Annex O Measurement of creepage distances and clearances ........................................ 159 28
Annex P Safeguards against conductive objects ............................................................. 160 29
Annex Q Circuits intended for interconnection with building wiring .................................. 161 30
Annex R Limited short-circuit test ................................................................................... 162 31
Annex S Tests for resistance to heat and fire .................................................................. 162 32
Annex T Mechanical strength tests ................................................................................. 163 33
Annex U Mechanical strength of CRTs and protection against the effects of 34
implosion .......................................................................................................... 165 35
Annex V Determination of accessible parts ..................................................................... 165 36
Annex X Alternative method for determing clearances for insulation in circuits 37
connected to an AC mains not exceeding 420 V peak (300 V RMS) .................. 165 38
Annex Y Construction requirements for outdoor enclosures ............................................ 166 39
Annex A (informative) Background information related to the use of SPDs ......................... 169 40
Annex B (informative) Background information related to measurement of discharges 41
– Determining the R-C discharge time constant for X- and Y-capacitors .............................. 182 42
Annex C (informative) Background information related to resistance to candle flame 43
ignition ................................................................................................................................ 194 44
IEC TR 62368-2:20xx © IEC 20xx – 3 –
Bibliography ........................................................................................................................ 195 45
46
Figure 1 – Risk reduction as given in ISO/IEC Guide 51........................................................ 11 47
Figure 2 – HBSE Process Chart ............................................................................................ 12 48
Figure 3 – Protective bonding conductor as part of a safeguard ............................................ 15 49
Figure 4 – Safeguards for protecting an ordinary person ....................................................... 19 50
Figure 5 – Safeguards for protecting an instructed person .................................................... 20 51
Figure 6 – Safeguards for protecting a skilled person ............................................................ 20 52
Figure 7 – Flow chart showing the intent of the glass requirements ....................................... 22 53
Figure 8 – Conventional time/current zones of effects of AC currents (15 Hz to 100 Hz) 54
on persons for a current path corresponding to left hand to feet (see IEC/TS 60479 -55
1:2005, Figure 20) ................................................................................................................ 26 56
Figure 9 – Conventional time/current zones of effects of DC currents on persons for a 57
longitudinal upward current path (see IEC/TS 60479-1:2005, Figure 22) ............................... 27 58
Figure 10 – Illustration that limits depend on both voltage and current .................................. 28 59
Figure 11 – Illustration of working voltage ............................................................................. 39 60
Figure 12 – Illustration of transient voltages on paired conductor external circuits ................ 41 61
Figure 13 – Illustration of transient voltages on coaxial-cable external circuits ...................... 42 62
Figure 14 – Basic and reinforced insulation in Table 14 of IEC 62368-1:2018; ratio 63
reinforced to basic ................................................................................................................ 43 64
Figure 15 – Reinforced clearances according to Rule 1, Rule 2, and Table 14 ...................... 45 65
Figure 16 – Example illustrating accessible internal wiring .................................................... 53 66
Figure 17 – Waveform on insulation without surge suppressors and no breakdown ............... 56 67
Figure 18 – Waveforms on insulation during breakdown without surge suppressors .............. 57 68
Figure 19 – Waveforms on insulation with surge suppressors in operation ............................ 57 69
Figure 20 – Waveform on short-circuited surge suppressor and insulation ............................ 57 70
Figure 21 – Example for an ES2 source ................................................................................ 59 71
Figure 22 – Example for an ES3 source ................................................................................ 59 72
Figure 23 – Overview of protective conductors ...................................................................... 62 73
Figure 24 – Example of a typical touch current measuring network ....................................... 64 74
Figure 25 – Touch current from a floating circuit ................................................................... 66 75
Figure 26 – Touch current from an earthed circuit ................................................................. 67 76
Figure 27 – Summation of touch currents in a PABX ............................................................. 67 77
Figure 28 – Possible safeguards against electrically-caused fire ........................................... 75 78
Figure 29 – Fire clause flow chart ......................................................................................... 78 79
Figure 30 – Prevent ignition flow chart .................................................................................. 83 80
Figure 31 – Control fire spread summary .............................................................................. 85 81
Figure 32 – Control fire spread PS2 ...................................................................................... 86 82
Figure 33 – Control fire spread PS3 ...................................................................................... 87 83
Figure 34 – Fire cone application to a large component ........................................................ 96 84
Figure 35 – Flowchart demonstrating the hierarchy of hazard management ........................ 108 85
Figure 36 – Model for chemical injury .................................................................................. 109 86
Figure 37 – Direction of forces to be applied ....................................................................... 114 87
Figure 38 – Model for a burn injury ..................................................................................... 117 88
– 4 – IEC TR 62368-2:20xx © IEC 20xx
Figure 39 – Model for safeguards against thermal burn injury ............................................. 119 89
Figure 40 – Model for absence of a thermal hazard ............................................................. 119 90
Figure 41 – Model for presence of a thermal hazard with a physical safeguard in place ...... 120 91
Figure 42 – Model for presence of a thermal hazard with behavioural safeguard 92
in place ............................................................................................................................... 120 93
Figure 43 – Flowchart for evaluation of Image projectors (beamers) ................................... 129 94
Figure 44 – Graphical representation of LAeq,T .................................................................. 131 95
Figure 45 – Overview of operating modes ........................................................................... 136 96
Figure 46 – Voltage-current characteristics (Typical data) ................................................... 141 97
Figure 47 – Example of IC current limiter circuit .................................................................. 145 98
Figure 48 – Current limit curves .......................................................................................... 148 99
Figure 49 – Example of a dummy battery circuit .................................................................. 158 100
Figure 50 – Example of a circuit with two power sources..................................................... 162 101
Figure A.1 – Installation has poor earthing and bonding; equipment damaged 102
(from ITU-T K.66) ................................................................................................................ 170 103
Figure A.2 – Installation has poor earthing and bonding; using main earth bar for 104
protection against lightning strike (from ITU-T K.66) ........................................................... 170 105
Figure A.3 – Installation with poor earthing and bonding, using a varistor and a GDT 106
for protection against a lightning strike ................................................................................ 171 107
Figure A.4 – Installation with poor earthing and bonding; equipment damaged (TV set) ...... 171 108
Figure A.5 – Safeguards ..................................................................................................... 172 109
Figure A.6 – Discharge stages ............................................................................................ 175 110
Figure A.7 – Holdover ......................................................................................................... 176 111
Figure A.8 – Discharge ....................................................................................................... 177 112
Figure A.9 – Characteristics ................................................................................................ 179 113
Figure A.10 – Follow on current pictures ............................................................................. 180 114
Figure B.1 – Typical EMC filter schematic ........................................................................... 182 115
Figure B.2 – 100 M oscilloscope probes ........................................................................... 184 116
Figure B.3 – Combinations of EUT resistance and capacitance for 1-s time constant .......... 186 117
Figure B.4 – 240 V mains followed by capacitor discharge .................................................. 188 118
Figure B.5 – Time constant measurement schematic .......................................................... 189 119
Figure B.6 – Worst-case measured time constant values for 100 M and 10 M probes .... 193 120
121
Table 1 – General summary of required safeguards .............................................................. 20 122
Table 2 – Time/current zones for AC 15 Hz to 100 Hz for hand to feet pathway (see 123
IEC/TS 60479-1:2005, Table 11) ........................................................................................... 26 124
Table 3 – Time/current zones for DC for hand to feet pathway (see IEC/TS 60479-125
1:2005, Table 13).................................................................................................................. 27 126
Table 4 – Limit values of accessible capacitance (threshold of pain) ..................................... 30 127
Table 5 – Total body resistances RT for a current path hand to hand, DC, for large 128
surface areas of contact in dry condition ............................................................................... 32 129
Table 6 – Insulation requirements for external circuits .......................................................... 42 130
Table 7 – Voltage drop across clearance and solid insulation in series ................................. 47 131
Table 8 – Examples of application of various safeguards ...................................................... 77 132
IEC TR 62368-2:20xx © IEC 20xx – 5 –
Table 9 – Basic safeguards against fire under normal operating conditions and 133
abnormal operating conditions .............................................................................................. 79 134
Table 10 – Supplementary safeguards against fire under single fault conditions ................... 80 135
Table 11 – Method 1: Reduce the likelihood of ignition ......................................................... 82 136
Table 12 – Method 2: Control fire spread .............................................................................. 91 137
Table 13 – Fire barrier and fire enclosure flammability requirements ..................................... 98 138
Table 14 – Summary – Fire enclosure and fire barrier material requirements ...................... 102 139
Table 15 – Control of chemical hazards .............................................................................. 107 140
Table 16 – Overview of requirements for dose-based systems ............................................ 133 141
Table 17 – Safety of batteries and their cells – requirements (expanded information on 142
documents and scope) ........................................................................................................ 152 143
Table B.1 – 100- M oscilloscope probes ........................................................................... 184 144
Table B.2 – Capacitor discharge ......................................................................................... 185 145
Table B.3 – Maximum Tmeasured values for combinations of REUT and CEUT for 146
TEUT of 1 s ........................................................................................................................ 192 147
148
149
– 6 – IEC TR 62368-2:20xx © IEC 20xx
INTERNATIONAL ELECTROTECHNICAL COMMISSION 150
____________ 151
152
AUDIO/VIDEO, INFORMATION AND 153
COMMUNICATION TECHNOLOGY EQUIPMENT – 154
155
Part 2: Explanatory information related to IEC 62368-1:2018 156
157
FOREWORD 158
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising 159 all national electrotechnical committees (IEC National Committees). The object of IEC is to p romote international 160 co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and 161 in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports, 162 Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their 163 preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with 164 may participate in this preparatory work. International, governmental and non-governmental organizations liaising 165 with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for 166 Standardization (ISO) in accordance with conditions determined by agreement between the two organizations. 167
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international 168 consensus of opinion on the relevant subjects since each technical committee has representation from all 169 interested IEC National Committees. 170
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National 171 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC 172 Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any 173 misinterpretation by any end user. 174
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications 175 transparently to the maximum extent possible in their national and regional publications. Any divergence between 176 any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter. 177
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity 178 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any 179 services carried out by independent certification bodies. 180
6) All users should ensure that they have the latest edition of this publication. 181
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and 182 members of its technical committees and IEC National Committees for any personal injury, property damage or 183 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and 184 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC Publications. 185
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is 186 indispensable for the correct application of this publication. 187
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent 188 rights. IEC shall not be held responsible for identifying any or all such patent rights. 189
The main task of IEC technical committees is to prepare International Standards. However, a 190
technical committee may propose the publication of a technical report when it has collected 191
data of a different kind from that which is normally published as an International Standard, for 192
example, "state of the art". 193
IEC 62368-2, which is a Technical Report, has been prepared by IEC technical committee 194
TC 108: Safety of electronic equipment within the field of audio/video, information technology 195
and communication technology. 196
This third edition updates the second edition of IEC 62368-2 published in 2014 to take into 197
account changes made to IEC 62368-1:2014 as identified in the Foreword of IEC 62368-1:2018. 198
This Technical Report is informative only. In case of a conflict between IEC 62368-1 and IEC 199
TR 62368-2, the requirements in IEC 62368-1 prevail over this Technical Report. 200
The text of this technical report is based on the following documents: 201
IEC TR 62368-2:20xx © IEC 20xx – 7 –
Enquiry draft Report on voting
108/708/DTR 108/711/RVDTR
202
Full information on the voting for the approval of this technical report can be found in the report 203
on voting indicated in the above table. 204
In this document, the following print types are used: 205
– notes/explanatory matter: in smaller roman type; 206
– tables and figures that are included in the rationale have linked fields (shaded in grey if 207
“field shading” is active); 208
– terms that are defined in IEC 62368-1: in bold type. 209
In this document, where the term (HBSDT) is used, it stands for Hazard Based Standard 210
Development Team, which is the Working Group of IEC TC 108 responsible for the development 211
and maintenance of IEC 62368-1. 212
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2. 213
A list of all parts of the IEC 62368 series can be found, under the general title Audio/video, 214
information and communication technology equipment, on the IEC website. 215
In this document, only those subclauses from IEC 62368-1 considered to need further 216
background reference information or explanation to benefit the reader in applying the relevant 217
requirements are included. Therefore, not all numbered subclauses are cited. Unless otherwise 218
noted, all references are to clauses, subclauses, annexes, figures or tables located in 219
IEC 62368-1:2018. 220
The entries in the document may have one or two of the following subheadings in addition to 221
the Rationale statement: 222
Source – where the source is known and is a document that is accessible to the general public, 223
a reference is provided. 224
Purpose – where there is a need and when it may prove helpful to the understanding of the 225
Rationale, we have added a Purpose statement. 226
227
– 8 – IEC TR 62368-2:20xx © IEC 20xx
The committee has decided that the contents of this publication will remain unchanged until the 228
stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data related to 229
the specific publication. At this date, the publication will be 230
• reconfirmed, 231
• withdrawn, 232
• replaced by a revised edition, or 233
• amended. 234
235
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates that it contains colours which are considered to be useful for the correct understanding of its contents. Users should therefore print this document using a colour printer.
236
237
IEC TR 62368-2:20xx © IEC 20xx – 9 –
INTRODUCTION 238
IEC 62368-1 is based on the principles of hazard-based safety engineering, which is a different 239
way of developing and specifying safety considerations than that of the current practice. While 240
this document is different from traditional IEC safety documents in i ts approach and while it is 241
believed that IEC 62368-1 provides a number of advantages, its introduction and evolution are 242
not intended to result in significant changes to the existing safety philosophy that led to the 243
development of the safety requirements contained in IEC 60065 and IEC 60950-1. The 244
predominant reason behind the creation of IEC 62368-1 is to simplify the problems created by 245
the merging of the technologies of ITE and CE. The techniques used are novel, so a learning 246
process is required and experience is needed in its application. Consequently, the committee 247
recommends that this edition of the document be considered as an alternative to IEC 60065 or 248
IEC 60950-1 at least over the recommended transition period. 249
250
251
– 10 – IEC TR 62368-2:20xx © IEC 20xx
AUDIO/VIDEO, INFORMATION AND 252
COMMUNICATION TECHNOLOGY EQUIPMENT – 253
254
Part 2: Explanatory information related to IEC 62368-1:2018 255
256
257
258
0 Principles of this product safety standard 259
Clause 0 is informational and provides a rationale for the normative clauses 260
of the document. 261
0.5.1 General 262
ISO/IEC Guide 51:2014, 6.3.5 states: 263
“When reducing risks, the order of priority shall be as follows: 264
a) inherently safe design; 265
b) guards and protective devices; 266
c) information for end users. 267
Inherently safe design measures are the first and most important step in the 268
risk reduction process. This is because protective measures inherent to the 269
characteristics of the product or system are likely to remain effective, 270
whereas experience has shown that even well-designed guards and 271
protective devices can fail or be violated and information for use might not 272
be followed. 273
Guards and protective devices shall be used whenever an inherently safe 274
design measure does not reasonably make it possible either to remove 275
hazards or to sufficiently reduce risks. Complementary protective measures 276
involving additional equipment (for example, emergency stop equipment ) 277
might have to be implemented. 278
The end user has a role to play in the risk reduction procedure by complying 279
with the information provided by the designer/supplier. However, information 280
for use shall not be a substitute for the correct application of inherently safe 281
design measures, guards or complementary protective measures.” 282
In general, this principle is used in IEC 62368-1. The table below shows a 283
comparison between the hierarchy required in ISO/IEC Guide 51 and the 284
hierarchy used in IEC 62368-1:2018: 285
ISO/IEC Guide 51 IEC 62368-1
a) inherently safe design 1. inherently safe design by limiting all energy hazards to class 1
b) guards and protective devices 2. equipment safeguards
3. installation safeguards
4. personal safeguards
c) information for end users 5. behavioral safeguards
6. instructional safeguards
286
Risk assessment has been considered as part of the development of 287
IEC 62368-1 as indicated in the following from ISO/IEC Guide 51 (Figure 1) 288
in this document. See also the Hazard Based Safety Engineer ing (HBSE) 289
Process Flow (Figure 2) in this document that also provides additional details 290
for the above comparison. 291
IEC TR 62368-2:20xx © IEC 20xx – 11 –
292
Figure 1 – Risk reduction as given in ISO/IEC Guide 51 293
– 12 – IEC TR 62368-2:20xx © IEC 20xx
294
295
Figure 2 – HBSE Process Chart 296
0.5.7 Equipment safeguards during skilled person service conditions 297
Purpose: To explain the intent of requirements for providing safeguards against 298
involuntary reaction. 299
Rationale: By definition, a skilled person has the education and experience to identify 300
all class 3 energy sources to which he may be exposed. However, while 301
servicing one class 3 energy source in one location, a skilled person may 302
be exposed to another class 3 energy source in a different location. 303
In such a situation, either of two events is possible. First, something may 304
cause an involuntary reaction of the skilled person with the consequences 305
of contact with the class 3 energy source in the different location. Second, 306
the space in which the skilled person is located may be small and cramped, 307
and inadvertent contact with a class 3 energy source in the different location 308
may be likely. 309
In such situations, this document may require an equipment safeguard 310
solely for the protection of a skilled person while performing servicing 311
activity. 312
0.10 Thermally-caused injury (skin burn) 313
Purpose: The requirements basically address safeguards against thermal energy 314
transfer by conduction. They do not specifically address safeguards against 315
thermal energy transfer by convection or radiation. However, as the 316
temperatures from hot surfaces due to conduction are always higher than the 317
radiated or convected temperatures, these are considered to be covered by 318
the requirements against conducted energy transfer. 319
___________ 320
IEC TR 62368-2:20xx © IEC 20xx – 13 –
Scope 321
Purpose: To identify the purpose and applicability of this document and the exclusions 322
from the scope. 323
Rationale: The scope excludes requirements for functional safety. Functional safety is 324
addressed in IEC 61508-1. Because the scope includes computers that may 325
control safety systems, functional safety requirements would necessarily 326
include requirements for computer processes and software. 327
The requirements provided in IEC 60950-23 could be modified and added to 328
IEC 62368 as another –X document. However, because of the hazard-based 329
nature of IEC 62368-1, the requirements from IEC 60950-23 have been 330
incorporated into the body of IEC 62368-1 and made more generic. 331
The intent of the addition of the IEC 60950-23 requirements is to maintain 332
the overall intent of the technical requirements from IEC 60950-23, 333
incorporate them into IEC 62368-1 following the overall format of IEC 62368-334
1 and simplify and facilitate the application of these requirements. 335
Robots traditionally are covered under the scopes of ISO documents, 336
typically maintained by ISO TC 299. ISO TC 299 has working groups for 337
personal care robots and service robots, and produces for example, 338
ISO 13482, Robots and robotic devices – Safety requirements for personal 339
care robots. 340
___________ 341
Normative references 342
The list of normative references is a list of all documents that have a 343
normative reference to it in the body of the document. As such, referenced 344
documents are indispensable for the application of this document. For dated 345
references, only the edition cited applies. For undated references, the latest 346
edition of the referenced document (including any amendments) applies . 347
Recently, there were some issues with test houses that wanted to use the 348
latest edition as soon as it was published. As this creates serious problems 349
for manufacturers, since they have no chance to prepare, it was felt that a 350
reasonable transition period should be taken into account. This is in line with 351
earlier decisions taken by the SMB that allow transition periods to be 352
mentioned in the foreword of the documents. Therefore IEC TC 108 decided 353
to indicate this in the introduction of the normative references clause, to 354
instruct test houses to take into account any transition period, effective date 355
or date of withdrawal established for the document. 356
These documents are referenced, in whole, in part , or as alternative 357
requirements to the requirements contained in this document. Their use is 358
specified, where necessary, for the application of the requirements of this 359
document. The fact that a standard is mentioned in the list does not mean 360
that compliance with the document or parts of it are required. 361
___________ 362
Terms, definitions and abbreviations 363
Rationale is provided for definitions that deviate from IEV definitions or from 364
Basic or Group Safety publication definitions. 365
3.3.2.1 electrical enclosure 366
Source: IEC 60050-195:1998, 195-06-13 367
Purpose: To support the concept of safeguards as used in this document. 368
– 14 – IEC TR 62368-2:20xx © IEC 20xx
Rationale: The IEV definition is modified to use the term “safeguard” in place of the 369
word “protection”. The word “safeguard” identifies a physical “thing” whereas 370
the word “protection” identifies the act of protecting. This document sets forth 371
requirements for use of physical safeguards and requirements for those 372
safeguards. The safeguards provide “protection” against injury from the 373
equipment. 374
3.3.5.1 basic insulation 375
Source: IEC 60050-195:1998, 195-06-06 376
Purpose: To support the concept of safeguards as used in this document. 377
Rationale: The IEV definition is modified to use the term “safeguard” in place of the 378
word “protection”. The word “safeguard” identifies a physical “thing” whereas 379
the word “protection” identifies the act of protecting. This document sets forth 380
requirements for use of physical safeguards and requirements for those 381
safeguards. The safeguards provide “protection” aga inst injury from the 382
equipment. 383
3.3.5.2 double insulation 384
Source: IEC 60050-195:1998, 195-06-08 385
Purpose: To support the concept of safeguards as used in this document. 386
Rationale: See 3.3.5.1, basic insulation. 387
3.3.5.6 solid insulation 388
Source: IEC 60050-212:2015, 212-11-02 389
3.3.5.7 supplementary insulation 390
Source: IEC 60050-195:1998, 195-06-07 391
Purpose: To support the concept of safeguards as used in this document. 392
Rationale: See 3.3.5.1, basic insulation. 393
3.3.6.9 restricted access area 394
Source: IEC 60050-195:1998, 195-04-04 395
Purpose: To use the concept of “ instructed persons” and “skilled persons” as used 396
in this document. 397
Rationale: The IEV definition is modified to use the terms “ instructed persons” and 398
“skilled persons” rather than “electrically instructed persons” and 399
“electrically skilled persons.” 400
3.3.7.7 reasonably foreseeable misuse 401
Source: ISO/IEC Guide 51:2014, 3.7 402
Rationale: Misuse depends on personal objectives, personal perception of the 403
equipment, and the possible use of the equipment (in a manner not intended 404
by the manufacturer) to accomplish those personal objectives. Equipment 405
within the scope of this document ranges from small handheld equipment to 406
large, permanently installed equipment. There is no commonality among the 407
equipment for readily predicting human behaviour leading to misuse of the 408
equipment and resultant injury. Where a possible reasonably foreseeable 409
misuse that may lead to an injury is not covered by the requirements of the 410
document, manufacturers are encouraged to consider reasonably 411
foreseeable misuse of equipment and provide safeguards, as applicable, 412
to prevent injury in the event of such misuse. (Not all reasonably 413
foreseeable misuse of equipment results in injury or potential for injury.) 414
IEC TR 62368-2:20xx © IEC 20xx – 15 –
3.3.8.1 instructed person 415
Source: IEC 60050-826:2004, 826-18-02 416
Rationale: The IEV definition is modified to use the terms “energy sources”, “skilled 417
persons”, and “precautionary safeguard”. The definition is made stronger 418
by using the term “instructed” rather than “advised”. 419
3.3.8.3 skilled person 420
Source: IEC 60050-826:2004, 826-18-01 421
Rationale: The IEV definition is modified to use the phrase “to reduce the li kelihood of”. 422
IEC 62368-1, in general, tends not use the word “hazard”. 423
3.3.11.9 protective bonding conductor 424
Rationale: The protective bonding conductor, is not a complete safeguard, but a 425
component part of the earthing system safeguard. The protective bonding 426
conductor provides a fault current pathway from a part (insulated from ES3 427
by basic insulation only) to the equipment protective earthing terminal, 428
see Figure 3 in this document. 429
430
Figure 3 – Protective bonding conductor as part of a safeguard 431
The parts required to be earthed via a protective bonding conductor are 432
those that have only basic insulation between the parts and ES3, and are 433
connected to accessible parts. 434
Only the fault current pathway is required to be a protective bonding 435
conductor. Other earthing connections of accessible conductive parts can 436
be by means of a functional earth conductor to the equipment PE terminal or 437
to a protective bonding conductor. 438
3.3.14.3 prospective touch voltage 439
Source: IEC 60050-195:1998, 195-05-09 440
Purpose: To properly identify electric shock energy source voltages. 441
Rationale: The IEV definition is modified to delete “animal”. The word “person” is also 442
deleted as all of the requirements in the document are with respect to 443
persons. 444
3.3.14.8 working voltage 445
Source: IEC 60664-1:2020, 3.1.7 446
Purpose: To distinguish between RMS. working voltage and the peak of the working 447
voltage. 448
– 16 – IEC TR 62368-2:20xx © IEC 20xx
Rationale: The IEC 60664-1 definition is modified to delete “RMS”. IEC 62368-1 uses 449
both RMS. working voltage and peak of the working voltage; each term is 450
defined. 451
3.3.15.2 class II construction 452
Source: IEC 60335-1:2010, 3.3.11 453
Purpose: Although the term is not used in the document, for completeness, it was 454
decided to retain this definition. 455
Rationale: The word “appliance” is changed to “equipment”. 456
____________ 457
General requirements 458
Purpose: To explain how to investigate and determine whether or not safety is 459
involved. 460
Rationale: In order to establish whether or not safety is involved, the ci rcuits and 461
construction are investigated to determine whether the consequences of 462
possible fault conditions would lead to an injury. Safety is involved if, as a 463
result of a single fault condition, the consequences of the fault lead to a 464
risk of injury. 465
If a fault condition should lead to a risk of injury , the part, material, or device 466
whose fault was simulated may comprise a safeguard. 467
Rationale is provided for questions regarding the omission of some 468
traditional requirements appearing in other safety documents. Rationale is 469
also provided for further explanation of new concepts and requirements in 470
this document. 471
Reasonable foreseeable misuse 472
Rationale: Apart from Annex M, this document does not specifically mention foreseeable 473
misuse or abnormal operating conditions. Nevertheless, the requirements 474
of the document cover many kinds of foreseeable misuse, such as covering 475
of ventilation openings, paper jams, stalled motors, etc. 476
functional insulation 477
Rationale: This document does not include requirements for functional insulation. By 478
its nature, functional insulation does not provide a safeguard function 479
against electric shock or electrically-caused fire and therefore may be 480
faulted. Obviously, not all functional insulations are faulted as this would 481
be prohibitively time-consuming. Sites for functional insulation faults 482
should be based upon physical examination of the equipment, and upon the 483
electrical schematic. 484
Note that basic insulation and reinforced insulation may also serve as 485
functional insulation, in which case the insulation is not faulted. 486
IEC TR 62368-2:20xx © IEC 20xx – 17 –
functional components 487
Rationale: This document does not include requirements for functional components. By 488
their nature, individual functional components do not provide a safeguard 489
function against electric shock, electrically-caused fire, thermal injury, etc., 490
and therefore may be candidates for fault testing. Obviously, not all 491
functional components are faulted as this would be prohibitively time-492
consuming. Candidate components for fault testing should be based upon 493
physical examination of the equipment, upon the electrical schematic 494
diagrams, and whether a fault of that component might result in conditions 495
for electric shock, conditions for ignition and propagation of fire, conditions 496
for thermal injury, etc. 497
As with all single fault condition testing (Clause B.4), upon faulting of a 498
functional component, there shall not be any safety consequence (for 499
example, a benign consequence), or a basic safeguard, supplementary 500
safeguard , or reinforced safeguard shall remain effective. 501
In some cases, a pair of components may comprise a safeguard. If the fault 502
of one of the components in the pair is mitigated by the second component, 503
then the pair is designated as a double safeguard. For example, if two 504
diodes are employed in series to protect a battery from reverse charge, then 505
the pair comprises a double safeguard and the components should be 506
limited to the manufacturer and part number actually tested. A second 507
example is that of an X-capacitor and discharge resistor. If the discharge 508
resistor should fail open, then the X-capacitor will not be discharged. 509
Therefore, the X-capacitor value is not to exceed the ES2 limits specified for 510
a charged capacitor. Again, the two components comprise a double 511
safeguard and the values of each component are limited to values for ES1 512
under normal operating conditions and the values for ES2 under single 513
fault conditions. 514
4.1.1 Application of requirements and acceptance of materials, components and 515
subassemblies 516
Purpose: To accept components as safeguards. 517
Rationale: This document includes requirements for safeguard components. A 518
safeguard component is a component specifically designed and 519
manufactured for both functional and safeguard parameters. Examples of 520
safeguard components are capacitors complying with IEC 60384-14 and 521
other components that comply with their related IEC component document. 522
Acceptance of components and component requirements from 523
IEC 60065 and 60950-1 524
Purpose: To accept both components and sub-assemblies investigated to the legacy 525
documents, IEC 60065 and IEC 60950-1, and components complying with 526
individual component requirements within these documents during the 527
transition period. 528
Rationale: To facilitate a smooth transition from the legacy documents IEC 60065 and 529
IEC 60950-1 to IEC 62368-1, including by the component supply chain, this 530
document allows for acceptance of both components and sub-assemblies 531
investigated to the legacy documents. Individual component requirements 532
within these documents may be used for compliance with IEC 62368-1 533
without further investigation, other than to give consideration to the 534
appropriate use of the component or sub-assembly in the end-product. 535
This means, for example, if a switch mode power supply is certified to 536
IEC 60065 or IEC 60950-1, this component can be used in equipment 537
evaluated to IEC 62368-1 without further investigation, other than to give 538
consideration to the appropriate use of the component, such as use within 539
its electrical ratings. 540
– 18 – IEC TR 62368-2:20xx © IEC 20xx
This also means, for example, since IEC 60950-1 allows for wiring and 541
cables insulated with PVC, TFE, PTFE, FEP, polychloroprene or polyimide 542
to comply with material requirements for parts within a fire enclosure without 543
need for the application of a flammability test, the same wire can be used to 544
comply with the requirements in 6.5.2 for insulation on wiring used in PS2 or 545
PS3 circuits and without the need for application of a flammability test per 546
IEC 60332 series or IEC TS 60695-11-21 as normally is required by 6.5.1. 547
4.1.5 Constructions and components not specifically covered 548
For constructions not covered, consideration should be given for the 549
hierarchy of safeguards in accordance with ISO/IEC Guide 51. 550
4.1.6 Orientation during transport and use 551
See also 4.1.4 552
In general, equipment is assumed to be installed and used in accordance 553
with the manufacturer’s instructions. However, in some cases where 554
equipment may be installed by an ordinary person, it is recognized that it is 555
common practice to mount equipment as desired if screw holes are provided, 556
especially if they allow mounting to readily available brackets. Hence, the 557
exception that is added to 4.1.6. 558
Examples of the above: a piece of equipment, such as a television set or a 559
video projector, that has embedded screw mounting holes that allow it to be 560
attached to a wall or other surface through the use of commercially available 561
vertically or tilt-mountable brackets, shall also take into account that the 562
mounting surface itself may not be vertical. 563
It is also recognized that transportable equipment, by its nature, may be 564
transported in any and all orientations. 565
4.1.8 Liquids and liquid filled components (LFC) 566
The one-litre (1 l) restriction was placed in 4.1.8 since the origin of some of 567
the requirements in Clause G.15 came from requirements in documents often 568
applied to smaller systems. Nevertheless, such a limitation does not always 569
negate the allowed application of 4.1.8 and Clause G.15 to systems with 570
larger volumes of liquid, but it could impact direct (automatic) applicability to 571
the larger systems. 572
4.2 Energy source classifications 573
Classification of energy sources may be done whether the source is 574
accessible or not. The requirements for parts may differ on whether the part 575
is accessible or not. 576
4.2.1 Class 1 energy source 577
A class 1 energy source is a source that is expected not to create any pain 578
or injury. Therefore, a class 1 energy source may be accessible by any 579
person. 580
Under some specific conditions of abnormal operation or single fault 581
conditions, a class 1 energy source may reach class 2 limits. However, this 582
source still remains a class 1 energy source. In this case, an instructional 583
safeguard may be required. 584
Under normal operating conditions and abnormal operating conditions, 585
the energy in a class 1 source, in contact with a body part, may be detectable, 586
but is not painful nor is it likely to cause an injury. For fire, the energy in a 587
class 1 source is not likely to cause ignition. 588
Under single fault conditions, a class 1 energy source, under contact with 589
a body part, may be painful, but is not likely to cause injury. 590
IEC TR 62368-2:20xx © IEC 20xx – 19 –
4.2.2 Class 2 energy source 591
A class 2 energy source is a source that may create pain, but which is 592
unlikely to create any serious injury. Therefore, a class 2 energy source may 593
not be accessible by an ordinary person. However, a class 2 energy source 594
may be accessible by: 595
– an instructed person; and 596
– a skilled person. 597
The energy in a class 2 source, under contact with a body part, may be 598
painful, but is not likely to cause an injury. For fire, the energy in a class 2 599
source can cause ignition under some conditions. 600
4.2.3 Class 3 energy source 601
A class 3 energy source is a source that is likely to create an injury. 602
Therefore, a class 3 energy source may not be accessible to an ordinary 603
person or an instructed person. A class 3 energy source may, in general, 604
be accessible to a skilled person. 605
Any source may be declared a class 3 energy source without measurement, 606
in which case all the safeguards applicable to class 3 are required. 607
The energy in a class 3 source, under contact with a body part, is capable of 608
causing injury. For fire, the energy in a class 3 source may cause ignition 609
and the spread of flame where fuel is available. 610
4.3.2 Safeguards for protection of an ordinary person 611
The required safeguards for the protection of an ordinary person are given in Figure 4. 612
613
Figure 4 – Safeguards for protecting an ordinary person 614
4.3.3 Safeguards for protection of an instructed person 615
The required safeguards for the protection of an instructed person are given in Figure 5. 616
– 20 – IEC TR 62368-2:20xx © IEC 20xx
617
Figure 5 – Safeguards for protecting an instructed person 618
4.3.4 Safeguards for protection of a skilled person 619
The required safeguards for the protection of a skilled person are given in Figure 6. 620
621
Figure 6 – Safeguards for protecting a skilled person 622
Table 1 in this document gives a general overview of the required number of 623
safeguards depending on the energy source and the person to whom the 624
energy source is accessible. The different clauses have requirements that 625
sometimes deviate from the general principle as given above. These cases 626
are clearly defined in the requirements sections of the document. 627
Table 1 – General summary of required safeguards 628
Person
Number of safeguards required to be interposed between an energy source and a person
Class 1 Class 2 Class3
Ordinary person 0 1 2
Instructed person 0 0 2
Skilled person 0 0 0 or 1
629
For a skilled person, there is normally no safeguard required for a class 3 630
energy source. However, if there are multiple class 3 energy sources 631
accessible or if the energy source is not obvious, a safeguard may be 632
required. 633
IEC TR 62368-2:20xx © IEC 20xx – 21 –
4.4.2 Composition of a safeguard 634
Purpose: To specify design and construction criteria for a single safeguard (basic, 635
supplementary, or reinforced) comprised of more than one element, for 636
example, a component or a device. 637
Rationale: Safeguards need not be a single, homogeneous component. Indeed, some 638
parts of this document require a single safeguard be comprised of two or 639
more elements. For example, for thin insulation, two or more layers are 640
required to qualify as supplementary insulation. Another example is 641
protective bonding and protective earthing, both of which are comprised of 642
wires, terminals, screws, etc. 643
If a safeguard is comprised of two or more elements, then the function of 644
the safeguard should not be compromised by a failure of any one element. 645
For example, if a screw attaching a protective earthing wire should loosen, 646
then the current-carrying capacity of the protective earthing circuit may be 647
compromised, making its reliability uncertain. 648
4.4.3 Safeguard robustness 649
Rationale: Safeguards should be sufficiently robust to withstand the rigors of expected 650
use throughout the equipment lifetime. Robustness requirements are 651
specified in the various clauses. 652
4.4.3.4 Impact test 653
Rationale: Stationary equipment can, in some cases, be developed for a speci fic 654
installation in which it is not possible for certain surfaces to be subjected to 655
an impact when installed as intended. In those cases, the impact test is not 656
necessary when the installation makes clear that the side cannot be 657
impacted. 658
4.4.3.6 Glass impact tests 659
Source: IEC 60065 660
Purpose: Verify that any glass that breaks does not cause skin-lacerating injury, or 661
expose class 3 hazards behind the glass. 662
Rationale: When it comes to glass, two hazards can be present in case the glass breaks: 663
− access to sharp edges from the broken glass itself 664
− exposure of class 3 energy hazards in case the glass is used as (part of) 665
the enclosure. 666
Should the glass break during the impact test, T.9 is applied to ensure the 667
expelled fragments will be at MS2 level or less. 668
Platen glass has a long history of being exempted, because it is quite obvious 669
for people that, if broken, the broken glass is hazardous and contact should 670
be avoided. There is no known history of serious injuries with this application. 671
Platen glass is the glass that is typically used in scanners, copiers, etc. 672
Accidents are rare, probably also because they are protected by an 673
additional cover most of the time, which limits the probability that an impact 674
will occur on the glass. 675
CRTs are exempted because they have separate requirements. 676
The test value for floor standing equipment is higher because it is more likely 677
to be impacted by persons or carts and dollies at a higher force while in 678
normal use. 679
The exemption for glass below certain sizes is taken over from IEC 60065. 680
There is no good rationale to keep the exemption, other than that there are 681
no serious accidents known from the field. The HBSDT decided that they 682
want to keep the exemption in. 683
– 22 – IEC TR 62368-2:20xx © IEC 20xx
The flow chart in Figure 7 in this document shows the intent for the 684
requirements. 685
686
Figure 7 – Flow chart showing the intent of the glass requirements 687
4.4.3.10 Compliance criteria 688
The value of 30 g for the weight limit is chosen based on the maximum 689
dimension of a side of 50 mm. A typical piece of glass with a size of 50 mm 690
× 50 mm × 4 mm (roughly 2,80 g/cm3) would have a weight of around 30 g. 691
4.6 Fixing of conductors 692
Source: IEC 60950-1 693
Purpose: To reduce the likelihood that conductors could be displaced such that t hey 694
reduce the creepage distances and clearances. 695
Rationale: These requirements have been successfully used for products in the scope 696
of this document for many years. 697
4.7 Equipment for direct insertion into mains socket-outlets 698
Source: IEC 60065:2014, 15.5 699
IEC 60950-1:2013, 4.3.6 700
IEC 60335-1:2010, 22.3 701
IEC TR 62368-2:20xx © IEC 20xx – 23 –
IEC 60884-1:2013, 14.23.2 702
Purpose: Determine that equipment incorporating integral pins for insertion into mains 703
socket-outlets does not impose undue torque on the socket-outlet due to the 704
mass and configuration of the equipment. This type of equipment often is 705
known as direct plug-in equipment or direct plug-in transformers. 706
Rationale: Socket outlets are required to comply with the safety requirements in 707
IEC 60884-1:2013, Plugs and socket-outlets for household and similar 708
purposes – Part 1: General requirements, including subclause 14.23.2. The 709
requirements result in socket designs with certain design limitations. 710
Equipment incorporating integral pins for insertion into mains socket-outlets 711
is not allowed to exceed these design limitations. 712
For direct plug-in equipment, including equipment for direct insertion into 713
a mains socket-outlet, normal use can be considered by representative 714
testing. The intent is not to require testing in all orientations. Subclause 4.1.6 715
is not applicable unless the manufacturer specifically supplies instructions 716
representing multiple mounting positions or configurations. 717
4.9 Likelihood of fire or shock due to entry of conductive objects 718
Purpose: The purpose of this subclause is to establish opening requirements that 719
would minimize the risk of foreign conductive objects falling into the 720
equipment that could bridge parts within class 2 or class 3 circuits, or 721
between PS circuits that could result in ignition or electric shock. 722
It is considered unlikely that a person would accidentally drop something that 723
could consequently fall into the equipment at a height greater than 1,8 m. 724
4.10.3 Power supply cords 725
Rationale: Power supply cords are neither internal nor external wir ing. They are 726
separately covered in G.7. 727
_____________ 728
Electrically-caused injury 729
Purpose: Clause 5 classifies electrical energy sources and provides criteria for 730
determining the energy source class of each conductive part. The criteria for 731
energy source class include the source current-voltage characteristics, 732
duration, and capacitance. Each conductive part, whether current-carrying 733
or not, or whether earthed or not, shall be classed ES1, ES2, or ES3 with 734
respect to earth and with respect to any other simultaneously accessible 735
conductive part. 736
The breakthrough for the Hazard Based Standard IEC 62368 was in determining 737
reasonable limits for each energy source in a way that did not present a hazard to 738
the user. The Clause 5, electrically-caused injury requirements were developed by 739
the electric shock team as the appointed TC108 technical experts in this subject. 740
For this standard each electrically conductive part is energy source classified 741
according to the source voltage-current characteristics. An accessible part of an 742
equipment is a part that can be touched by a body part as determined by the 743
specified test probes. Accessible parts define those contact points which must 744
provide a specified, limited electric current or electric shock to the user. Based 745
upon IEC 60479-1 Figs 20 & 22 the acceptable touch current for IEC 62368 ES1 746
circuits is ‘a’ line value of 0.5mArms/0.707pk AC/bipolar or 2mAdc monopolar 747
startle-reaction currents and under IEC 62368 ES2 circuits is the ‘b’ line value of 748
5 mArms/7.07mApk AC/bipolar or 25mAdc monopolar letgo-immobilization 749
currents. Accessible touch currents at or below the startle-reaction level are 750
appropriate for normal operation of equipment; accessible touch current at or 751
below the letgo-immobilizaiton level are appropriate under fault conditions. Since 752
earthing/grounding is not considered reliable in cord connected equipment the 753
assessment of touch current usually begins by making this abnormal condition 754
– 24 – IEC TR 62368-2:20xx © IEC 20xx
measurement in the earth/ground lead to determine that the current is below the 755
specified limit and touching the chassis anywhere under these conditions is not 756
hazardous. Measurement of the touch current from all accessible parts is also 757
done. Using the IEC 60990 touch current measurement circuit & methods invoked 758
in IEC 62368 ensure that the high frequency components of non-sinusoidal touch 759
current found in modern switching electronics and motor drivers are properly taken 760
into account. They are reduced to the low frequency equivalent invoking the 761
published frequency factors in IEC 60479-2 for each of the measurement circuits 762
prescribed; this is accomplished by the use of appropriate filter circuits in the 763
measuring circuit. IEC 62368 clearly prescribes the use of peak current 764
measurements for non-sinusoidal waveforms (which is also appropriate for 765
sinusoidal waveforms). 766
The 5 mArms value is higher than has been used previously in IEC 60950, 767
as legacy standards, for example IEC 60950 and IEC 61010 have both used 768
3,5m Arms as the maximum current allowed under fault conditions. But the 769
5 mArms limit represents an acceptable value of current at the letgo-770
immobilization limit for all persons, both children and adults. Although this 771
value of current is strongly felt by most adults, the person is able to pull off 772
of it and disengage. Above this level they may not be able to disengage which 773
defines the hazard properly. 774
240 VA limit 775
IEC 62368-1 does not have requirements for a 240 VA energy hazard that 776
was previously located in 2.1.1.5 of IEC 60950-1:2013. 777
The origin/justification of the 240 VA energy hazard requirement in the legacy 778
documents was never precisely determined, and it appears the VA limits may 779
have come from a manufacturer’s specifications originally applied to exposed 780
bus bars in mainframe computers back in the 1960 ’s and concerns at the 781
time service personnel inadvertently bridging them with a metal part. 782
However, when IEC TC 108 started the IEC 62368-1 project the intent was 783
to take a fresh look at product safety using HBSE and only carry over a 784
legacy requirement if the safety science and HBSE justified it. After 785
considerable study by IEC TC 108, there was no support for carrying over 786
the 240 VA requirement since: 787
− the requirements were not based on any proven sc ience or sound 788
technical basis; 789
− the 240 VA value was relatively arbitrary; and 790
− in practice the requirement was difficult to apply consistently (for 791
example, on a populated printed board or inside a switch mode power 792
supply). 793
In the meantime, there are energy limits for capacitors in Clause 5, which 794
remains a more realistic concern and which were the second set of the 795
energy hazard requirements in IEC 60950-1, the first being steady state 240 796
VA. 797
In addition, there are other requirements in IEC 62368-1 that will limit 798
exposure to high levels of power (VA), including a VA limit for LPS outputs 799
when those are required by Annex Q (for outputs connected to building wiring 800
as required by 6.5.2). 801
Electric burn (eBurn) 802
Analysis of the body current generated by increasing frequency sinuso idal 803
waveforms shows that the current continues to increase with frequency. The 804
same analysis shows that the touch current, which is discounted with 805
frequency, stabilizes. 806
IEC TR 62368-2:20xx © IEC 20xx – 25 –
The following paper describes the analysis fully: ‘Touch Current Comparison, 807
Looking at IEC 60990 Measurement Circuit Performance – Part 1: Electric 808
Burn'; Peter E Perkins; IEEE PSES Product Safety Engineering Newsletter, 809
Vol 4, No 2, Nov 2008. 810
The crossover frequency is different for the startle-reaction circuit than for 811
the let go-immobilization circuit because of the separate Frequency Factor 812
body response curves related to current levels; analysis identifies the 813
crossover frequency where the eBurn current surpasses the touch current. 814
Under these conditions, a person touching the circuit will become 815
immobilized and will not be able to let go of the circuit. This crossover 816
frequency is determined in the analysis. The person contacting the circuit 817
should always be able to let go. 818
The general conditions that apply to eBurn circuits are: 819
− the eBurn limit only applies to HF sinusoidal signals; 820
− the area of contact should be limited to a small, fingertip contact 821
(~ 1cm2); 822
− the contact time should be less than 1 s; at this short contact time, it is 823
not reasonable to define different levels for various persons; 824
This requirement applies to accessible circuits that can be contacted at both 825
poles, including all grounded circuits isolated from the mains and any 826
isolated circuits where both contacts are easily available to touch. 827
A simplified application of these requirements in the documents limits the 828
accessibility of HF sinusoidal currents above a specified frequency. The 829
22 kHz and 36 kHz frequency limits are where the eBurn current crosses the 830
5mA limit for the ES1 and ES2 measurement circuits. This will ensure that 831
the person contacting the circuit will be able to remove themselves from the 832
circuit under these conditions. 833
1 MHz limit 834
The effects of electric current on the human body are described in the 835
IEC 60479 series and the requirements in IEC 62368-1 are drawn from there. 836
The effects versus frequency are well laid out and properly accounted for in 837
these requirements. The body effects move from conducted effects to 838
surface radiofrequency burns at higher frequencies approaching 100 kHz. By 839
long-term agreement, IEC safety documents are responsible for outlining the 840
effects of current to 1 MHz, which are properly measured by the techniques 841
given herein. Above the 1 MHz level, it becomes an EMC issue. Unless the 842
current is provided as a principal action of the equipment operation, electric 843
shock evaluation should not be needed above the 1 MHz level. Where it is 844
fundamental to the equipment's operation, the high-frequency current levels 845
shall be specially measured using proper high-frequency techniques, 846
including classifying the circuits and, if necessary, appropriately protected to 847
avoid any bodily injury. 848
5.2.1 Electrical energy source classifications 849
Source: IEC TS 60479-1:2005 and IEC 61201 850
Purpose: To define the line between hazardous and non-hazardous electrical energy 851
sources for normal operating conditions and abnormal operating 852
conditions. 853
Rationale: The effect on persons from an electric source depends on the current through 854
the human body. The effects are described in IEC TS 60479-1. 855
IEC TS 60479-1 (see Figures 20 and 22, Tables 11 and 13); zone AC-1 and 856
zone DC-1; usually no reaction (Figure 8 and Figure 9, Table 2 and Table 3 857
in this document) is taken as values for ES1. 858
– 26 – IEC TR 62368-2:20xx © IEC 20xx
IEC TS 60479-1 (see Figures 20 and 22; Tables 11 and 13); zone AC-2 and 859
zone DC-2; usually no harmful physiological effects (see Figure 8 and 860
Figure 9, Table 2 in this document) is taken as values for ES2. 861
IEC TS 60479-1; zone AC-3 and zone DC-3; harmful physiological effects 862
may occur (see Figure 8 and Figure 9, Table 2 and Table 3 in this document) 863
is the ES3 zone. 864
865
866
Figure 8 – Conventional time/current zones of effects 867
of AC currents (15 Hz to 100 Hz) on persons for a current path corresponding 868
to left hand to feet (see IEC TS 60479-1:2005, Figure 20) 869
Table 2 – Time/current zones for AC 15 Hz to 100 Hz 870
for hand to feet pathway (see IEC TS 60479-1:2005, Table 11) 871
Zones Boundaries Physiological effects
AC-1 up to 0,5 mA curve a Perception possible but usually no startle reaction
AC-2 0,5 mA up to curve b Perception and involuntary muscular contractions likely but usually no harmful electrical physiological effects
AC-3 Curve b and above Strong involuntary muscular contractions. Difficulty in breathing.
Reversible disturbances of heart function. Immobilisation may occur.
Effects increasing with current magnitude. Usually no organic damage to be expected.
AC-4a Above curve c1 Pathophysiological effects may occur such as cardiac arrest,
breathing arrest, and burns or other cellular damage. Probability of ventricular fibrillation increasing with current magnitude and time.
c1 – c
2 AC-4.1 Probability of ventricular fibrillation increasing up to about
5 %.
c2 – c
3 AC-4.2 Probability of ventricular fibrillation up to about 50 %.
Beyond curve c3 AC-4.3 Probability of ventricular fibrillation above 50 %.
a For durations of current flow below 200 ms, ventricular fibrillation is only initiated within the vulnerable period if the relevant thresholds are surpassed. As regards ventricular fibrillation , this figure relates to the effects of current that flows in the path left hand to feet. For other current paths, the heart current factor has to be considered.
872
IEC TR 62368-2:20xx © IEC 20xx – 27 –
873
Figure 9 – Conventional time/current zones of effects of DC currents on persons for 874
a longitudinal upward current path (see IEC TS 60479-1:2005, Figure 22) 875
Table 3 – Time/current zones for DC for hand to feet pathway 876
(see IEC TS 60479-1:2005, Table 13) 877
Zones Boundaries Physiological effects
DC-1 Up to 2 mA curve a Slight pricking sensation possible when making, break ing or rapidly altering current flow.
DC-2 2 mA up to curve b Involuntary muscular contractions likely, especially when making, breaking or rapidly altering current flow, but usually no harmful electrical physiological effects
DC-3 curve b and above Strong involuntary muscular reactions and reversible disturbances of formation and conduction of impulses in the heart may occur, increasing with current magnitude and time. Usually, no organic damage to be expected.
DC-4a Above curve c1 Pathophysiological effects may occur such as cardiac arrest,
breathing arrest, and burns or other cellular damage. Probability of ventricular fibrillation increasing with current magnitude and time.
c1 – c
2 DC-4.1 Probability of ventricular fibrillation increasing up to about
5 %.
c2 – c
3 DC-4.2 Probability of ventricular fibrillation up to about 50 %.
Beyond curve c3 DC-4.3 Probability of ventricular fibrillation above 50 %.
a For durations of current flow below 200 ms, ventricular fibrillation is only initiated within the vulnerable period if the relevant thresholds are surpassed. As regards ventricular fibrillation , this figure relates to the effects of current which flows in the path left hand to feet and for upward current. For other current paths, the heart current factor has to be considered.
878
The seriousness of an injury increases continuously with the energy 879
transferred to the body. To demonstrate this principle Figure 8 and Figure 9 880
in this document (see IEC TS 60479-1, Figures 20 and 22) are transferred 881
into a graph: effects vs energy (see Figure 10 in this document). 882
– 28 – IEC TR 62368-2:20xx © IEC 20xx
883
Figure 10 – Illustration that limits depend on both voltage and current 884
Within the document, only the limits for Zone 1 (green) and Zone 2 (yellow) 885
will be specified. 886
Curve “a” (limit of Zone 1) will be the limit for parts accessible by an 887
ordinary person during normal use. 888
Curve “b” (limit of Zone 2) will be the limit for parts accessible by an 889
ordinary person during (or after) a single fault. 890
IEC TC 108 regarded it not to be acceptable to go to the limits of either Zone 891
3 or 4. 892
In the document three (3) zones are described as electrical energy sources. 893
This classification is as follows: 894
– electrical energy source 1 (ES1): levels are of such a value that they do 895
not exceed curve “a” (threshold of perception) of Figure 8 and Figure 9 in 896
this document (see IEC TS 60479-1:2005, Figures 20 and 22). 897
– electrical energy source 2 (ES2): levels are of such a value that they 898
exceed curve “a”, but do not exceed curve “b” (threshold of let go) of 899
Figure 8 and Figure 9 in this document (see IEC TS 60479-1:2005, 900
Figures 20 and 22). 901
– electrical energy source 3 (ES3): levels are of such a value that they 902
exceed curve “b” of Figure 8 and Figure 9 in this document (see IEC 903
TS 60479-1:2005, Figures 20 and 22). 904
5.2.2.1 General 905
When classifying a circuit or part that is not accessible, that circuit or part 906
shall be regarded as being accessible when measuring prospective touch 907
voltage and touch current. 908
5.2.2.2 Steady-state voltage and current limits 909
Table 4 Electrical energy source limits for steady-state ES1 and ES2 910
IEC TR 62368-2:20xx © IEC 20xx – 29 –
Source: IEC TS 60479-1:2005, Dalziel, Effect of Wave Form on Let-Go Currents; 911
AIEE Electrical Engineering Transactions, Dec 1943, Vol 62. 912
Rationale: The current limits of Table 4 line 1 and 2 are derived from curve a and b, 913
Figure 8 and Figure 9 in this document (see IEC TS 60479-1:2005, Figures 914
20 and 22). 915
The basis for setting limits for combined AC and DC touch current is from 916
the work of Dalziel which provides clear data for men, women and children. 917
In the current diagram (Figure 22), the AC current is always the peak value 918
(per Dalziel). In the voltage diagram (Figure 23), the 30 V AC and 50 V AC 919
points on the baseline are recognized as AC RMS values as stated in 920
Table 4. Since IEC TC 108 is working with consumer appliances, there is a 921
need to provide protection for children, who are generally considered the 922
most vulnerable category of people. The formulas of IEC 62368-1:2018, 923
Table 4 address the Dalziel investigations. 924
Under single fault conditions of a relevant basic safeguard or 925
supplementary safeguard, touch current is measured according to 5.1.2 926
of IEC 60990:2016. However, this IEC 60990 subclause references both the 927
IEC 60990 perception/reaction network (Figure 4) and the let -go network 928
(Figure 5), selection of which depends on several factors. Figure 5 applies 929
to touch current limits above 2 mA RMS. IEC TC 108 has decided that parts 930
under single fault conditions of relevant basic safeguards or 931
supplementary safeguards should be measured per Figure 5 (let-go 932
immobilization network). Therefore, since 5.1.2 makes reference to both 933
Figure 4 and Figure 5, for clarification Table 4 is mentioned directly in 934
5.2.2.2. 935
Because there is usually no reaction of the human body when touching ES1, 936
access is permitted by any person (IEC TS 60479-1; zone AC-1 and 937
zone DC-1). 938
Because there may be a reaction of the human body when touching ES2, 939
protection is required for an ordinary person. One safeguard is sufficient 940
because there are usually no harmful physiological effects when touch ing 941
ES2 (IEC TS 60479-1:2005; zone AC-2 and zone DC-2). 942
Because harmful physiological effects may occur when touching ES3, (IEC 943
TS 60479-1:2005; zone AC-3 and zone DC-3), protection is required for an 944
ordinary person and an instructed person, including after a fault of one 945
safeguard. 946
During the application of the electrical energy source limits for “combined AC 947
and DC” in Table 4, if the AC component of a superimposed AC and DC 948
energy source does not exceed 10 % of the DC energy, then the AC 949
component can be disregarded for purposes of application of Table 4. This 950
consideration is valid based on the definition of DC voltage in 3.3.14.1, 951
which allows peak-to-peak ripple not exceeding 10 % of the average value 952
to integrated into DC voltage considerations. As a result, in such cases 953
where AC does not exceed 10 % of DC, only the DC energy source limits in 954
Table 4 need be applied. 955
When measuring combined AC and DC voltages and currents, both AC and 956
DC measurements shall be made between the same points of reference. Do 957
not combine common-mode measurements with differential-mode 958
measurements. They shall be assessed separately. 959
In using Table 4, ES1 touch current measurement specifies the startle -960
reaction circuit ‘a’ intended for limits less than 2 mA RMS / 2,8 mA peak and 961
ES2 touch current specifies the let-go-immobilization circuit ‘b’ intended for 962
limits > 2 mA RMS / 2,8 mA peak. These circuits are adopted from 963
IEC 60990:2016, Clause 5. 964
Normal operating conditions of equipment for touch current testing are 965
outlined in 5.7.2 and Clause B.2 of IEC 62368-1:2018 and includes operation 966
– 30 – IEC TR 62368-2:20xx © IEC 20xx
of all operator controls. Abnormal operating conditions are specified in 967
Clause B.3 of IEC 62368-1:2018. Single fault conditions (within the 968
equipment), specified in Clause B.4 of IEC 62368-1:2018, includes faults of 969
a relevant basic safeguard or a supplementary safeguard. 970
5.2.2.3 Capacitance limits 971
Table 5 Electrical energy source limits for a charged capacitor 972
Source: IEC TS 61201:2007 (Annex A) 973
Rationale: Where the energy source is a capacitor, the energy source class is 974
determined from both the charge voltage and the capacitance. The 975
capacitance limits are derived from IEC TS 61201:2007, see Table 4 in this 976
document. 977
The values for ES2 are derived from Table A.2 of IEC TS 61201:2007. 978
The values for ES1 are calculated by dividing the values from Table A .2 of 979
IEC TS 61201:2007 by two (2). 980
Table 4 – Limit values of accessible capacitance (threshold of pain) 981
U
V
C
F
U
kV
C
nF
70 42,4 1 8,0
78 10,0 2 4,0
80 3,8 5 1,6
90 1,2 10 0,8
100 0,58 20 0,4
150 0,17 40 0,2
200 0,091 60 0,133
250 0,061
300 0,041
400 0,028
500 0,018
700 0,012
982
5.2.2.4 Single pulse limits 983
Table 6 Voltage limits for single pulses 984
Rationale: The values are based on the DC current values of Table 4, assuming 25 mA 985
gives a voltage of 120 V DC (body resistance of 4,8 kΩ). The lowest value is 986
taken as 120 V because, under single fault conditions, the voltage of ES1 987
can be as high as 120 V DC without a time limit. 988
The table allows linear interpolation because the difference is considered to 989
be very small. However, the following formula may be used for a more exact 990
interpolation of the log-log based values in this table. The variable t or V is 991
the desired unknown "in between value" and either may be determined when 992
one is known: 993
22 1
1
2
1
–
–
–1
–
log loglog log
log logAntilog
log log
log log
t tV V
t tV
t t
t t
+
=
+
994
IEC TR 62368-2:20xx © IEC 20xx – 31 –
and 995
22 1
1
2
1
–
–
–1
–
log loglog log
log logAntilog
log log
log log
V Vt t
V Vt
V V
V V
+
=
+
996
where: 997
t is the time duration that is required to be determined if Upeak
voltage V is known (or t is 998
known and V needs to be determined) 999
t1 is the time duration adjacent to t corresponding to the U
peak voltage V
1 1000
t2 is the time duration adjacent to t corresponding to the U
peak voltage V
2 1001
V is the Upeak
voltage value that is known if time duration t is to be determined (or V is 1002
required to be determined if time duration t is known) 1003
V1 is the value of the voltage U
peak adjacent to V corresponding to time duration t
1 1004
V2 is the value of the voltage U
peak adjacent to V corresponding to time duration t
2 1005
Table 7 Current limits for single pulses 1006
Source: IEC TS 60479-1:2005 1007
Rationale: For ES1, the limit of single pulse should not exceed the ES1 steady-state 1008
voltage limits for DC voltages. 1009
For ES2, the voltage limits have been calculated by using the DC current 1010
values of curve b Figure 9 in this document and the resistance values of 1011
Table 10 of IEC TS 60479-1:2005, column for 5 % of the population (see 1012
Table 5 in this document). 1013
The current limits of single pulses in Table 7 for ES1 levels are from curve a 1014
and for ES2 are from curve b of Figure 9 in this document. 1015
The table allows linear interpolation because the difference is considered to 1016
be very small. However, the following formula may be used for a more exact 1017
interpolation of the log-log based values in this table. The variable t or I is 1018
the desired unknown "in between value" and either may be determined when 1019
one is known: 1020
1021
22 1
1
2
1
–
–
–1
–
log loglog log
log logAntilog
log log
log log
t tI I
t tI
t t
t t
+
=
+
1022
and 1023
22 1
1
2
1
–
–
–1
–
log loglog log
log logAntilog
log log
log log
I It t
I It
I I
I I
+
=
+
1024
where: 1025
t is the time duration that is required to be determined if the electric current I is known 1026 (or t is known and I needs to be determined) 1027
t1 is the time duration adjacent to t corresponding to the electric current I
1 1028
t2 is the time duration adjacent to t corresponding to the electric current I
2 1029
I is the value of the Ipeak
current that is known if time duration t is to be determined 1030
(or I is required to be determined if time duration t is known) 1031
– 32 – IEC TR 62368-2:20xx © IEC 20xx
I1 is the value of the I
peak adjacent to I corresponding to time duration t
1 1032
I2 is the value of the I
peak adjacent to I corresponding to time duration t
2 1033
Table 5 – Total body resistances RT for a current path hand to hand, DC, 1034
for large surface areas of contact in dry condition 1035
Touch voltage
V
Values for the total body resistance RT ()
that are not exceeded for
5 % of the
population
50 % of the
population
95 % of the
population
25
50
75
100
125
150
175
200
225
400
500
700
1 000
2 100
1 600
1 275
1 100
975
875
825
800
775
700
625
575
575
3 875
2 900
2 275
1 900
1 675
1 475
1 350
1 275
1 225
950
850
775
775
7 275
5 325
4 100
3 350
2 875
2 475
2 225
2 050
1 900
1 275
1 150
1 050
1 050
Asymptotic value 575 775 1 050
NOTE 1 Some measurements indicate that the total body resistance RT for the current path hand to foot
is somewhat lower than for a current path hand to hand (10 % to 30 %).
NOTE 2 For living persons the values of RT correspond to a duration of current flow of about 0,1 s.
For longer durations RT values may decrease (about 10 % to 20 %) and after complete rupture
of the skin RT approaches the initial body resistance Ro.
NOTE 3 Values of RT are rounded to 25 .
1036
1037
5.2.2.6 Ringing signals 1038
Source: EN 41003 1039
Purpose: To establish limits for analogue telephone network ringing signals . 1040
Rationale: For details see rationale for Annex H. Where the energy source is an 1041
analogue telephone network ringing signal as defined in Annex H, the energy 1042
source class is taken as ES2 (as in IEC 60950-1:2005, Annex M). 1043
5.2.2.7 Audio signals 1044
Source: IEC 60065:2014 1045
Purpose: To establish limits for touch voltages for audio signals . 1046
Rationale: The proposed limits for touch voltages at terminals involving audio signals 1047
that may be contacted by persons have been extracted without deviation 1048
from IEC 60065. Reference: IEC 60065:2014, 9.1.1.2 a). Under single fault 1049
conditions, 10.2 of IEC 60065:2014 does not permit an increase in 1050
acceptable touch voltage limits. 1051
IEC TR 62368-2:20xx © IEC 20xx – 33 –
The proposed limits are quantitatively larger than the accepted limits of 1052
Tables 5 and 6, but are not considered dangerous for the following reasons: 1053
– the output is measured with the load disconnected (worst case load); 1054
– defining the contact area of connectors and wiring is very difficult due to 1055
complex shapes. The area of contact is considered small due to the 1056
construction of the connectors; 1057
– normally, it is recommended to the user, in the instruction manual 1058
provided with the equipment, that all connections be made with the 1059
equipment in the “off” condition; 1060
– in addition to being on, the equipment would have to be playing some 1061
program at a high output with the load disconnected to achieve the 1062
proposed limits (although possible, highly unlikely). Historically, no known 1063
cases of injury are known for amplifiers with non-clipped output less than 1064
71 V RMS; 1065
– the National Electrical Code (USA) permits accessible terminals with 1066
maximum output voltage of 120 V RMS. 1067
5.3.2 Accessibility to electrical energy sources and safeguards 1068
1069
What are the requirements between the non-accessible sources? 1070
Answer: None. As the enclosure is double insulated, the sources are not 1071
accessible. 1072
1073
Now there is an accessible connection. What are the requirements between 1074
the sources in this case? 1075
Answer: 1076
– Basic insulation between ES1 and ES2 1077
– 34 – IEC TR 62368-2:20xx © IEC 20xx
– Double insulation or reinforced insulation between ES1 and ES3 1078
– The insulation between ES2 and ES3 depends on the insulation between 1079
the ES1 and ES2 1080
1081
Now there are two accessible connections from independent sources. What 1082
are the requirements between the sources in this case? 1083
Answer: 1084
– According to Clause B.4, the insulation or any components between the 1085
sources need to be shorted 1086
– If one of the two ES1 sources would reach ES2 levels basic safeguard 1087
– If both ES1 sources stay within ES1 limits no safeguard (functional 1088
insulation) 1089
For outdoor equipment, lower voltage limits apply because the body impedance 1090
is reduced to half the value when subjected to wet conditions as described in 1091
IEC TS 60479-1 and IEC TS 61201. 1092
Where Class III equipment is acceptable in an indoor application, this outdoor 1093
application does not introduce additional safeguard requirements. 1094
5.3.2.2 Contact requirements 1095
Source: IEC 61140:2001, 8.1.1 1096
Purpose: Determination of accessible parts for adults and children. Tests are in 1097
IEC 62368-1:2018, Annex V. 1098
Rationale: According to Paschen’s Law, air breakdown does not occur below 1099
323 V peak or DC (at sea level). IEC 62368-1:2018 uses 420 V peak (300 V 1100
RMS) to add an additional safety margin. 1101
5.3.2.3 Compliance criteria 1102
The reason for accepting different requirements for components is because 1103
you cannot expect your supplier to make different components for each end 1104
application. 1105
5.3.2.4 Terminals for connecting stripped wire 1106
Source: IEC 60065 1107
Purpose: To prevent contact of ES2 or ES3 parts. 1108
Rationale: Accepted constructions used in the audio/video industry for many years. 1109
IEC TR 62368-2:20xx © IEC 20xx – 35 –
5.4 Insulation materials and requirements 1110
Rationale: The requirements, test methods and compliance criteria are taken from the 1111
actual outputs from IEC TC 108 MT2 (formerly WG6) as well as from IEC TC 1112
108 MT1. 1113
– The choice and application of components shall take into account the 1114
needs for electrical, thermal and mechanical strength, frequency of the 1115
working voltage and working environment (temperature, pressure, 1116
humidity and pollution). 1117
– Components shall have the electric strength, thermal strength, 1118
mechanical strength, dimensions, and other properties as specified in the 1119
document. 1120
– Depending on the grade of safeguard (basic safeguard, supplementary 1121
safeguard, reinforced safeguard) the requirements differ. 1122
– Components complying with their component documents (for example, 1123
IEC 60384-14 for capacitances) have to be verified for their application. 1124
– The components listed in this subclause of the new document have a 1125
separation function. 1126
5.4.1.1 Insulation 1127
Source: IEC 60664-1 1128
Purpose: Provide a reliable safeguard 1129
Rationale: Solid basic insulation, supplementary insulation, and reinforced 1130
insulation shall be capable of durably withstanding electrical, mechanical, 1131
thermal, and environmental stress that may occur during the anticipated 1132
lifetime of the equipment. 1133
Clearances and creepage distances may be divided by intervening 1134
unconnected (floating) conductive parts, such as unused contacts of a 1135
connector, provided that the sum of the individual distances meets the 1136
specified minimum requirements (see Figure O.4). 1137
5.4.1.4 Maximum operating temperatures for materials, components and systems 1138
Source: IEC 60085, IEC 60364-4-43, ISO 306, IEC 60695-10-2 1139
Rationale: Temperature limits given in Table 9: 1140
– limits for insulation materials including electrical insulation systems, 1141
including winding insulation (Classes A, E, B, F, H, N, R and 250) are 1142
taken from IEC 60085; 1143
– limits for insulation of internal and external wiring, including power supply 1144
cords with temperature marking are those indicated by the marking or the 1145
rating assigned by the (component) manufacturer; 1146
– limits for insulation of internal and external wiring, including power supply 1147
cords without temperature marking of 70 °C, are referenced in 1148
IEC 60364-4-43 for an ambient temperature of 25 °C; 1149
– limits for thermoplastic insulation are based on: 1150
• data from Vicat test B50 of ISO 306; 1151
• ball pressure test according to IEC 60695-10-2; 1152
• when it is clear from the examination of the physical characteristics of 1153
the material that it will meet the requirements of the ball pressure test ; 1154
• experience with 125 °C value for parts in a circuit supplied from the 1155
mains. 1156
– 36 – IEC TR 62368-2:20xx © IEC 20xx
5.4.1.4.3 Compliance criteria 1157
Table 9 Temperature limits for materials, components and systems 1158
Rationale Regarding condition “a”, it has been assumed by the technical committee for 1159
many years that the thermal gradient between outer surface and inner 1160
windings will be limited to 10 °C differential as an average. As a result, the 1161
temperature limits for outer surface insulation measured via thermocouple is 1162
10 °C lower than similar measurement with a thermocouple embedded in the 1163
winding(s), with both limits at least 5 °C less than the hot-spot temperature 1164
allowed per IEC 60085 as an additional safety factor. However, some modern 1165
transformer constructions with larger power densities may have larger 1166
thermal gradients, as may some outer surface transformer insulation thermal 1167
measurements in the equipment/system be influenced by forced cooling or 1168
similar effects. Therefore, if thermal imaging, computer modeling, or actual 1169
measurement shows a thermal gradient greater than 10 °C average between 1170
transformer surface temperature and transformer winding(s), the rise of 1171
resistance temperature measurement method and limits for an embedded 1172
thermocouple should be used (for example, 100 °C maximum temperature 1173
for Class 105 (A)) for determining compliance of a transformer with Table 9 1174
since the original assumptions do not hold true. 1175
As an example, a material rated for 124 °C using the rise of resistance 1176
method is considered suitable for classes whose temperature is lower (c lass 1177
with letter codes E and A) and not for classes whose temperature is higher 1178
(class with letter codes B, F, H, N, R and 250). 1179
5.4.1.5 Pollution degrees 1180
Source: IEC 60664-1 1181
Rationale: No values for PD 4 (pollution generates persistent conductivity) are included, 1182
as it is unlikely that such conditions are present when using products in the 1183
scope of the document. 1184
5.4.1.5.2 Test for pollution degree 1 environment and for an insulating compound 1185
The compliance check made by visual inspection applies both to single layer 1186
and multi-layer boards without the need for sectioning to check for voids, 1187
gaps, etc. 1188
5.4.1.6 Insulation in transformers with varying dimensions 1189
Source: IEC 60950-1 1190
Purpose: To consider actual working voltage along the winding of a transformer. 1191
Rationale: Description of a method to determine adequacy of solid insulation along 1192
the length of a transformer winding. 1193
5.4.1.7 Insulation in circuits generating starting pulses 1194
Source: IEC 60950-1, IEC 60664-1 1195
Purpose: To avoid insulation breakdown due to starting pulses. 1196
Rationale: This method has been successfully used for products in the scope of this 1197
document for many years. 1198
5.4.1.8 Determination of working voltage 1199
Source: IEC 60664-1:2020, 3.1.7; IEC 60950-1 1200
Rationale: The working voltage does not include short duration signals, such as 1201
transients. Recurring peak voltages are not included. Transient overvoltages 1202
are covered in the required withstand voltage. Ringing signals do not carry 1203
external transients. 1204
IEC TR 62368-2:20xx © IEC 20xx – 37 –
5.4.1.8.1 General 1205
Rationale: Functional insulation is not addressed in Clause 5, as it does not provide 1206
protection against electric shock. Requirements for functional insulation 1207
are covered in Clause 6, which addresses protection against electrically 1208
caused fire. 1209
Source: IEC 60664-1:2020, 3.1.14 1210
Rationale: In IEC 62368-1, “Circuit supplied from the mains” is used for a “primary 1211
circuit”. “Circuit isolated from the mains” is used for a “secondary circuit”. 1212
“External circuit” is defined as external to the equipment. ES1 can be 1213
external to the equipment. 1214
For an external circuit operating at ES2 level and not exiting the building, 1215
the transient is 0 V. Therefore, in this case, ringing peak voltage needs to be 1216
taken into account. 1217
5.4.1.8.2 RMS working voltage 1218
Source: IEC 60664-1:2020, 3.1.7 1219
Rationale: RMS working voltage is used when determining minimum creepage 1220
distance. Unless otherwise specified, working voltage is the RMS value. 1221
5.4.1.10 Thermoplastic parts on which conductive metallic parts are directly mounted 1222
Source: ISO 306 and IEC 60695-2 series 1223
Rationale: The temperature of the thermoplastic parts under normal operating 1224
conditions shall be 15 K less than the softening temperature of a non-1225
metallic part. Supporting parts in a circuit supplied from the mains shall not 1226
be less than 125 °C. 1227
5.4.2 Clearances 1228
5.4.2.1 General requirements 1229
Source: IEC 60664-1:2020 1230
Rationale: The dimension for a clearance is determined from the required impulse 1231
withstand voltage for that clearance. This concept is taken from 1232
IEC 60664-1:2020, 5.2. In addition, clearances are affected by the largest 1233
of the determined transients. The likelihood of simultaneous occurrence of 1234
transients is very low and is not taken into account. 1235
Overvoltages and transients that may enter the equipment, and peak 1236
voltages that may be generated within the equipment, do not break down the 1237
clearance (see IEC 60664-1:2020, 5.2.4 and 5.2.5). 1238
Minimum clearances of safety components shall comply with the 1239
requirements of their applicable component safety document. 1240
Clearances between the outer insulating surface of a connector and 1241
conductive parts at ES3 voltage level shall comply with the requirements of 1242
basic insulation only, if the connectors are fixed to the equipment, located 1243
internal to the outer electrical enclosure of the equipment, and are 1244
accessible only after removal of a sub-assembly that is required to be in 1245
place during normal operation. 1246
It is assumed that the occurrence of both factors, the sub-assembly being 1247
removed and the occurrence of a transient overvoltage, have a reduced 1248
likelihood and hazard potential. 1249
Source: IEC 60664-2 series, Application guide 1250
Rationale: The method is derived from the IEC 60664-2 series, Application guide. 1251
– 38 – IEC TR 62368-2:20xx © IEC 20xx
Example:
Assuming: – an SMPS power supply, – connection to the AC mains, – a peak of the working voltage (PWV) of 800 V, – frequencies above and below 30 kHz, – reinforced clearances required, – temporary overvoltages: 2 000 V Procedure 1: Table 10 requires 2,54 mm Table 11 requires 0,44 mm Result is 2,54 mm
NOTE All PWV below 1 200 V have clearance requirements less than 3 mm for both Table 10 and Table 11
Procedure 2: Transients (OVC 2): 2 500 V RWV = 2 500 V Table 14 requires 3,0 mm The required ES test voltage according to Table 15 is 4,67 KV Result is 3,0 mm or ES test at 4,67 KV
Final result: – 3,0 mm or – ES test at 4,67 KV and 2,54 mm ATTENTION:
For a product with connection to coax cable, different values are to be used since a different transient and required withstand voltage is required.
1252
IEC TR 62368-2:20xx © IEC 20xx – 39 –
5.4.2.2 Procedure 1 for determining clearance 1253
Rationale: Related to the first dash of 5.4.2.2, it is noted that an example of a cause of 1254
determination of the peak value of steady state voltages that are below the 1255
peak voltage of the mains includes, for example, a determination in 1256
accordance with the 2nd and 3rd dash of 5.4.2.3.3 where filtering is in place 1257
to lower expected peak voltages. 1258
Similarly, related to the second dash of 5.4.2.2, an example of this case 1259
where the recurring peak voltage is limited to 1,1 times the mains voltage 1260
may be use of certain forms of surge protection devices that reduce 1261
overvoltage category. 1262
Peak of the working voltage versus recurring peak voltage. 1263
There has been some discussion between the two terms. The peak of the 1264
working voltage is the peak value of the waveform that occurs each cycle, 1265
and therefore is considered to be a part of the working voltage. 1266
A recurring peak voltage is a peak that does not occur at each cycle of the 1267
waveform, but that reoccurs at a certain interval, usually at a lower frequency 1268
than the waveform frequency. 1269
Figure 11 in this document gives an example of a waveform where the 1270
recurring peak voltage occurs every two cycles of the main waveform. 1271
1272
Figure 11 – Illustration of working voltage 1273
Table 10 Minimum clearances for voltages with frequencies up to 30 kHz 1274
Rationale: IEC TC 108 noted that, if the rules of IEC 60664-1 are followed, for reinforced 1275
clearance, some values were more than double the requirements for basic 1276
insulation. IEC TC 108 felt that this should not be the case and decided to 1277
limit the requirement for reinforced insulation to twice the value of basic 1278
insulation, thereby deviating from IEC 60664-1. 1279
In addition, normal rounding rules were applied to the values in the table. 1280
5.4.2.3.2.2 Determining AC mains transient voltages 1281
Source: IEC 60664-1:2020, 4.3.2 1282
Rationale: Table 12 is derived from Table F.1 of IEC 60664-1:2020. 1283
The term used in IEC 60664-1 is ‘rated impulse voltage’. Products covered 1284
by IEC 62368-1 are also exposed to transients from external circuits, and 1285
therefore another term is needed, to show the different source. 1286
– 40 – IEC TR 62368-2:20xx © IEC 20xx
Outdoor equipment that is part of the building installation, or that may be 1287
subject to transient overvoltages exceeding those for Overvoltage 1288
Category II, shall be designed for Overvoltage Category III or IV, unless 1289
additional protection is to be provided internally or externally to the 1290
equipment. In this case, the installation instructions shall s tate the need for 1291
such additional protection. 1292
5.4.2.3.2.3 Determining DC mains transient voltages 1293
Rationale: Transient overvoltages are attenuated by the capacitive filtering. 1294
5.4.2.3.2.4 Determining external circuit transient voltages 1295
Source: ITU-T K.21 1296
Rationale: Transients have an influence on circuits and insulation, therefore transients 1297
on external circuits need to be taken into account. Transients are needed 1298
only for the dimensioning safeguards. Transients should not be used for the 1299
classification of energy sources (ES1, ES2, etc.). 1300
It is expected that external circuits receive a transient voltage of 1,5 kV 1301
peak with a waveform of 10/700s from sources outside the building. 1302
The expected transient is independent from the application (telecom; LAN or 1303
other). Therefore, it is assumed that for all kinds of applications the same 1304
transient appears. The value 1,5 kV 10/700s is taken from ITU-T K.21. 1305
It is expected that external circuits using earthed coaxial cable receive no 1306
transients that have to be taken into account from sources outside the 1307
building. 1308
Because of the earthed shield of the coaxial cable, a possible transient on 1309
the outside cable will be reduced at the earthed shield at the building 1310
entrance of the cable. 1311
It is expected that for external circuits within the same building no transients 1312
have to be taken into account. 1313
The transients for an interface are defined with respect to the terminals 1314
where the voltage is defined. For the majority of cases, the relevant voltages 1315
are common (Uc) and differential mode (Ud) voltages at the interface. For 1316
hand-held parts or other parts in extended contact with the human body, 1317
such as a telephone hand set, the voltage with respect to local earth (Uce) 1318
may be relevant. Figure 12 in this document shows the definition of the 1319
various voltages for paired-conductor interface. 1320
The transients for coaxial cable interfaces are between the centre conductor 1321
and shield (Ud) of the cable if the shield is earthed at the equipment. If the 1322
shield is isolated from earth at the equipment, then the shield -to-earth 1323
voltage (Us) is important. Earthing of the shield can consist of connection of 1324
the shield to the protective earthing, functional earth inside or immediately 1325
outside the equipment. It is assumed that all earths are bonded together. 1326
Figure 13 in this document shows the definition of the various voltages for 1327
coaxial-cable interfaces. 1328
An overview of insulation requirements is given in Table 6 in this document. 1329
IEC TR 62368-2:20xx © IEC 20xx – 41 –
1330
1331
1332
Figure 12 – Illustration of transient voltages on paired conductor external circui ts 1333
– 42 – IEC TR 62368-2:20xx © IEC 20xx
1334
1335
Figure 13 – Illustration of transient voltages on coaxial-cable external circuits 1336
Table 6 – Insulation requirements for external circuits 1337
External Circuit under consideration
Insulation Requirement
ES1 earthed None None
ES1 unearthed Separation (to floating metal parts and other floating ES1 circuits)
Electric strength test (using Table 15) between unearthed ES1 and other unearthed ES1 and floating parts
ES2 Basic insulation (to ES1 and metal parts)
Clearances; creepage distance; and solid insulation and by electric strength test (using Table 15) between ES2 and ES1 and metal parts
ES3 Double insulation or reinforced insulation (to ES1, ES2 and metal parts)
Clearances; creepage distance; and solid insulation requirements including electric strength test (using Table 15)
1338
Table 13 External circuit transient voltages 1339
Rationale: When the DC power distribution system is located outside the building, 1340
transient over-voltages can be expected. Transients are not present if the 1341
DC power system is connected to protective earthing and is located entirely 1342
within a single building. 1343
5.4.2.3.2.5 Determining transient voltage levels by measurement 1344
Source: Test method is taken from IEC 60950-1:2013, Annex G. 1345
5.4.2.3.4 Determining clearances using required withstand voltage 1346
Source: IEC 60664-1:2020, Table F.2 Case A (inhomogeneous field) and Case B 1347
(homogeneous field) 1348
IEC TR 62368-2:20xx © IEC 20xx – 43 –
Rationale: Values in Table 14 are taken from IEC 60664-1:2020 Table F.2 Case A 1349
(inhomogeneous field) and Case B (homogeneous field) and include explicit 1350
values for reinforced insulation. Clearances for reinforced insulation 1351
have been calculated in accordance with 5.2.5 of IEC 60664-1:2020. For 1352
reinforced insulation 5.2.5 states clearance shall be to the corresponding 1353
rated impulse voltage that is one step higher for voltages in the preferred 1354
series. For voltages that are not in the preferred series, the clearance should 1355
be based on 160 % of the required withstand voltage for basic insulation. 1356
When determining the required withstand voltage, interpolation should be 1357
allowed when the internal repetitive peak voltages are higher than the mains 1358
peak voltages, or if the required withstand voltage is above the mains 1359
transient voltage values. 1360
No values for PD 4 (pollution generates persistent conductivity) are included, 1361
as it is unlikely that such conditions are present when using products in the 1362
scope of the document. 1363
Table 14 Minimum clearances using required withstand voltage 1364
Rationale: IEC 62368-1 follows the rules and requirements of IEC basic safety 1365
publications, one of which is the IEC 60664 series. IEC 60664-1 specifies 1366
clearances for basic insulation and supplementary insulation. 1367
Clearances for reinforced insulation are not specified. Instead, 5.1.6 1368
specifies the rules for determining the reinforced clearances. 1369
The reinforced clearances in Table 14 have a varying slope, and include a 1370
“discontinuity”. The values of Table 14 are shown in Figure 14 in this 1371
document. 1372
1373
Figure 14 – Basic and reinforced insulation in Table 14 of IEC 62368-1:2018; 1374
ratio reinforced to basic 1375
– 44 – IEC TR 62368-2:20xx © IEC 20xx
The brown line, reinforced clearance, is not a constant slope as is the yellow 1376
line, basic clearance. The ratio of reinforced to basic (blue line) varies from 1377
a maximum of 2:1 to a minimum of 1,49:1. Physically, this is not reasonable; 1378
the ratio should be nearly constant. 1379
In IEC 60664-1:2020, the values for basic insulation are given in Table F.2. 1380
No values are given for reinforced insulation. Table F.2 refers to 5.2.5 for 1381
reinforced insulation. 1382
Rule 1, preferred series impulse withstand voltages 1383
Subclause 5.2.5 of IEC 60664-1:2020 states: 1384
“With respect to impulse withstand voltages, clearances of reinforced 1385
insulation shall be dimensioned as specified in Table F.2 corresponding to 1386
the rated impulse withstand voltage but one step higher in the preferred 1387
series of values in 4.2.2.1 than that specified for basic insulation.” 1388
NOTE 1 IEC 62368-1 uses the term “required withstand voltage” instead of the IEC 60664-1389 1 term “required impulse withstand voltage.” 1390
NOTE 2 IEC 62368-1 uses the term “mains transient voltage” instead of the IEC 60664-1 1391 term “rated impulse voltage.” 1392
The preferred series of values of rated impulse voltage according to 4.2.3 of 1393
IEC 60664-1:2007 is: 330 V, 500 V, 800 V, 1 500 V, 2 500 V, 4 000 V, 6 000 1394
V, 8 000 V, 12 000 V 1395
Applying Rule 1, the reinforced clearance (inhomogeneous field, pollution 1396
degree 2, Table F.2) for: 1397
– 330 V would be the basic insulation clearance for 500 V: 0,2 mm 1398
– 500 V would be the basic insulation clearance for 800 V: 0,2 mm 1399
– 800 V would be the basic insulation clearance for 1 500 V: 0,5 mm 1400
– 1 500 V would be the basic insulation clearance for 2 500 V: 1,5 mm 1401
– 2 500 V would be the basic insulation clearance for 4 000 V: 3,0 mm 1402
– 4 000 V would be the basic insulation clearance for 6 000 V: 5,5 mm 1403
– 6 000 V would be the basic insulation clearance for 8 000 V: 8,0 mm 1404
– 8 000 V would be the basic insulation clearance for 12 000 V: 14 mm 1405
– 12 000 V is indeterminate because there is no preferred voltage above 1406
12 000 volts. 1407
Rule 2, 160 % of impulse withstand voltages other than the preferred 1408
series 1409
With regard to non-mains circuits, subclause 5.2.5 of IEC 60664-1:2020 1410
states: 1411
“If the impulse withstand voltage required for basic insulation according to 1412
4.2.2.1 is other than a value taken from the preferred series, reinforced 1413
insulation shall be dimensioned to withstand 160 % of the impulse 1414
withstand voltage required for basic insulation.” 1415
The impulse withstand voltages other than the preferred series (in 1416
IEC 60664-1:2020, Table F.2) are: 400 V, 600 V, 1 200 V, 2 000 V, 3 000 V, 1417
10 000 V, and all voltages above 12 000 V. 1418
Applying Rule 2, the reinforced clearance (inhomogeneous field, pollution 1419
degree 2, Table F.2) for: 1420
400 V x 1,6 = 640 V interpolated to 0,20 mm. 1421
Since 640 V is not in the list, the reinforced insulation is determined by 1422
interpolation. Interpolation yields the reinforced clearance as 0,2 mm. 1423
IEC TR 62368-2:20xx © IEC 20xx – 45 –
Applying Rule 2 to the impulse withstand voltages in Table F.2 that are not 1424
in the preferred series: 1425
– 400 V × 1,6 = 640 V interpolated to 0,20 mm 1426
– 600 V × 1,6 = 960 V interpolated to 0,24 mm 1427
– 1 200 V × 1,6 = 1 920 V interpolated to 0,92 mm 1428
– 2 000 V × 1,6 = 1 320 V interpolated to 2,2 mm 1429
– 3 000 V × 1,6 = 4 800 V interpolated to 3,8 mm 1430
– 10 000 V × 1,6 = 13 000 V interpolated to 19,4 mm 1431
– 15 000 V to 100 000 V × 1,6 and interpolated according to the rule. 1432
Clearance differences for Rules 1 and 2 1433
The two rules, Rule 1 for impulse withstand voltages of the preferred series, 1434
and Rule 2 for impulse withstand voltages other than the preferred series, 1435
yield different clearances for the same voltages. These differences occur 1436
because the slope, mm/kV, of the two methods is slightly different. The slope 1437
for Rule 1 is not constant. The slope for Rule 2 is nearly constant. Figure 15 1438
in this document illustrates the differences between Rule 1, Rule 2 and Table 1439
14 of IEC 62368-1:2018. 1440
1441
Figure 15 – Reinforced clearances according to Rule 1, Rule 2, and Table 14 1442
If the two values for Rules 1 and 2 are combined into one set of values, the 1443
values are the same as in existing Table 14 (the brown line in Figure 14 and 1444
Figure 15 in this document). According to IEC 60664-1:2020, 5.2.5, only the 1445
impulse withstand voltages “other than a value taken from the preferred 1446
series…” are subject to the 160 % rule. Therefore, the clearances jump from 1447
Rule 1 criteria to Rule 2 criteria and back again. This yields the radical slope 1448
changes of the Table 14 reinforced clearances (brown) line. 1449
Rule 1
Rule 2
Basic insulation
Table 15
– 46 – IEC TR 62368-2:20xx © IEC 20xx
Physically, the expected reinforced insulation clearances should be a 1450
constant proportion of the basic insulation clearances. However, the 1451
proportion between steps of Rule 1 (preferred series of impulse withstand 1452
voltages) are: 1453
– 330 V to 500 V: 1,52 1454
– 500 V to 800 V: 1,60 1455
– 800 V to 1 500 V: 1,88 1456
– 1 500 V to 2 500 V: 1,67 1457
– 2 500 V to 4 000 V: 1,60 1458
– 4 000 V to 6 000 V: 1,50 1459
– 6 000 V to 8 000 V: 1,33 1460
– 8 000 V to 12 000 V: 1,50 1461
Average proportion, 330 to 12 000: 1,57 1462
For Rule 2, all of the clearances for reinforced insulation are based on 1463
exactly 1,6 times the non-preferred series impulse withstand voltage for 1464
basic insulation. 1465
The two rules applied in accordance with 5.2.5 of IEC 60664-1:2020 result in 1466
the variable slope of the clearance requirements for reinforced insulation 1467
of IEC 62368-1. 1468
IEC TC 108 noted that, if the rules of IEC 60664-1 are followed, for 1469
clearances for reinforced insulation, some values were more than double 1470
the requirements for basic insulation. IEC TC 108 felt that this should not 1471
be the case and decided to limit the requirement for reinforced insulation 1472
to twice the value of basic insulation, thereby deviating from IEC 60664-1. 1473
In addition, normal rounding rules were applied to the values in the table. 1474
5.4.2.4 Determining the adequacy of a clearance using an electric strength test 1475
Source: IEC 60664-1:2020, Table F.6 1476
Purpose: Tests are carried out by either impulse voltage or AC voltage with the values 1477
of Table 15. 1478
Rationale: The impulse test voltages in Table 15 are taken from IEC 60664-1:2020, 1479
Table F.6. The calculation for the AC RMS. values as well as the DC values 1480
are based on the values given in Table A.1 of IEC 60664-1:2020 (see Table 7 1481
in this document for further explanation). 1482
This test is not suited for homogenous fields. This is for an actual design that 1483
is within the limits of the homogenous and inhomogeneous field. 1484
Calculations for the voltage drop across an air gap during the electric 1485
strength test may be rounded up to the next higher 0,1 mm increment. In 1486
case the calculated value is higher than the value in the next row, the next 1487
row may be used. 1488
Enamel Material: Most commonly used material is polyester resin or 1489
polyester 1490
Dielectric constant for Polyester: 5 (can vary) 1491
Dielectric constant for air: 1 1492
Formula used for calculation (voltage divides inversely proportional to the 1493
dielectric constant) 1494
Transient = 2 500 V = 2 500 (thickness of enamel / 5 + air gap / 1) = 2 500 1495
(0,04 / 5 + 2 / 1 for 2 mm air gap) = 2 500 (0,008 + 2) = (10 V across enamel 1496
+ 2 490 V across air gap) 1497
IEC TR 62368-2:20xx © IEC 20xx – 47 –
Related to condition a of Table 15, although U is any required withstand 1498
voltage higher than 12,0 kV, there is an exception when using Table F.6 of 1499
IEC 60664-1:2020. 1500
Table 7 – Voltage drop across clearance and solid insulation in series 1501
Enamel thickness
mm
Air gap
mm
Transient on 240 V system
Transient voltage
across air gap
Transient voltage across enamel
Peak impulse
test voltage for
2 500 V peak
transient from
Table 16
Test voltage
across air gap
Test voltage across enamel
Material: Polyester, dielectric constant = 5
0,04 2 2 500 2 490 10 2 950 12 2 938
0,04 1 2 500 2 480 20 2 950 24 2 926
0,04 0,6 2 500 2 467 33 2 950 39 2 911
For 2 500 V peak impulse (transient for 230 V system), the homogenous field distance is 0,6 mm (from Table A.1 of IEC 60664-1:2020). Our test voltage for 2 500 V peak is 2 950 V peak from Table 15. This means that a minimum distance of 0,79 mm through homogenous field needs to be maintained to pass the 2 950 V impulse
test. This gives us a margin of (0,19/0,6) 100 = 3,2 %. In actual practice, the distance will be higher as it is not a true homogenous field. Therefore, we do not need to verify compliance with Table 14. We are always on the conservative side.
Material: Polyamide, dielectric constant = 2,5
0,04 2 2 500 2 480 20 2 950 23 2 927
0,04 1 2 500 2 460 40 2 950 46 2 904
0,04 0,6 2 500 2 435 65 2 950 76 2 874
For 2 500 V peak impulse (transient for 230 V system), the homogenous field distance i s 0,6 mm (from Table A.1 of IEC 60664-1:2020). Our test voltage for 2 500 V peak is 2 950 V peak from Table 15. This means that a minimum distance of 0,78 mm through homogenous field needs to be maintained to pass the 2 950 V impulse
test. This gives us a margin of (0,18/0,6) 100 = 3,0 %. In actual practice, the distance will be higher, as it is not a true homogenous field. Therefore, we do not need to verify compliance with Table 14. We are always on the conservative side.
1502
5.4.2.5 Multiplication factors for altitudes higher than 2 000 m above sea level 1503
Source: IEC 60664-1:2020, curve number 2 for case A using impulse test. 1504
Purpose: Test is carried out by either impulse voltage or AC voltage with the values of 1505
Table 16 and the multiplication factors for altitudes higher than 2 000 m. 1506
Rationale: Table 16 is developed using Figure A.1 of IEC 60664-1:2020, curve number 1507
2 for case A using impulse test. 1508
5.4.2.6 Compliance criteria 1509
Source: IEC 60664-1:2020, 5.2 1510
Rationale: IEC 62368-1:2018, Annex O figures are similar/identical to figures in 1511
IEC 60664-1:2020. 1512
Tests of IEC 62368-1:2018, Annex T simulate the occurrence of mechanical 1513
forces: 1514
– 10 N applied to components and parts that may be touched during 1515
operation or servicing. Simulates the accidental contact with a finger or 1516
part of the hand; 1517
– 30 N applied to internal enclosures and barriers that are accessible to 1518
ordinary persons. Simulates accidental contact of part of the hand; 1519
– 48 – IEC TR 62368-2:20xx © IEC 20xx
– 100 N applied to external enclosures of transportable equipment and 1520
handheld equipment. Simulates expected force applied during use or 1521
movement; 1522
– 250 N applied to external enclosures (except those covered in T.4). 1523
Simulates expected force applied by a body part to the surface of the 1524
equipment. It is not expected that such forces will be applied to the bottom 1525
surface of heavy equipment ( 18 kg). 1526
During the force tests metal surfaces shall not come into contact with parts 1527
at ES2 or ES3 voltage. 1528
5.4.3 Creepage distances 1529
Source: IEC 60664-1:2020, 3.1.5 1530
Purpose: To prevent flashover along a surface or breakdown of the insulation. 1531
Rationale: Preserve safeguard integrity. 1532
In IEC 60664-1:2020, Table F.5 columns 2 and 3 for printed wiring boards 1533
are deleted, as there is no rationale for the very small creepage distances 1534
for printed wiring in columns 2 and 3 (the only rationale is that it is in the 1535
basic safety publication IEC 60664-1). 1536
However, there is no rationale why the creepage distances are different for 1537
printed wiring boards and other isolation material under the same condition 1538
(same PD and same CTI). 1539
Moreover the creepage distances for printed boards in columns 2 and 3 are 1540
in conflict with the requirements in G.13.3 (Coated printed boards). 1541
Consequently the values for voltages up to 455 V in Table G.16 were 1542
replaced. 1543
Creepage distances between the outer insulating surface of a connector 1544
and conductive parts at ES3 voltage level shall comply with the requirements 1545
of basic insulation only, if the connectors are fixed to the equipment, 1546
located internal to the outer electrical enclosure of the equipment, and are 1547
accessible only after removal of a sub-assembly which is required to be in 1548
place during normal operation. 1549
It is assumed that the occurrence of both factors, the sub-assembly being 1550
removed, and the occurrence of a transient overvoltage have a reduced 1551
likelihood and hazard potential. 1552
5.4.3.2 Test method 1553
Source: IEC 60664-1:2020, 3.1.4 1554
Purpose: Measurement of creepage distance. 1555
Rationale: To preserve safeguard integrity after mechanical tests. 1556
Annex O figures are similar/identical to figures in IEC 60950-1 and 1557
IEC 60664-1. 1558
Tests of Annex T simulate the occurrence of mechanical forces: 1559
– 10 N applied to components and parts that are likely to be touched by a 1560
skilled person during servicing, where displacement of the part reduces 1561
the creepage distance. Simulates the accidental contact with a finger or 1562
part of the hand. 1563
– 30 N applied to internal enclosures and barriers that are accessible to 1564
ordinary persons. Simulates accidental contact of part of the hand. 1565
– 100 N applied to external enclosures of transportable equipment and 1566
hand-held equipment. Simulates expected force applied during use or 1567
movement. 1568
IEC TR 62368-2:20xx © IEC 20xx – 49 –
– 250 N applied to external enclosures (except those covered in T.4). 1569
Simulates expected force when leaning against the equipment surface. It 1570
is not expected that such forces will be applied to the bottom surface of 1571
heavy equipment ( 18 kg). 1572
Creepage distances are measured after performing the force tests of Annex 1573
T. 1574
5.4.3.3 Material group and CTI 1575
Source: IEC 60112 1576
Rationale: Classification as given in IEC 60112. 1577
5.4.3.4 Compliance criteria 1578
Source: IEC 60664-1:2020, Table F.5; IEC 60664-4 for frequencies above 30 kHz 1579
Rationale: Values in Table 17 are the same as in Table F.5 of IEC 60664-1:2020. 1580
Values in Table 18 are the same as in Table 2 of IEC 60664-4:2005 and are 1581
used for frequencies up to 400 kHz. 1582
5.4.4 Solid insulation 1583
Source: IEC 60950-1, IEC 60664-1 1584
Purpose: To prevent breakdown of the solid insulation. 1585
Rationale: To preserve safeguards integrity. 1586
Exclusion of solvent based enamel coatings for safety insulations are based 1587
on field experience. However, with the advent of newer insulation materials 1588
those materials may be acceptable in the future when passing the adequate 1589
tests. 1590
Except for printed boards (see G.13), the solid insulation shall meet the 1591
requirements of 5.4.4.4 to 5.4.4.7 as applicable. 1592
5.4.4.2 Minimum distance through insulation 1593
Source: IEC 60950-1:2005 1594
Purpose: Minimum distance through insulation of 0,4 mm for supplementary 1595
insulation and reinforced insulation. 1596
Rationale: Some (very) old documents required for single insulations 2 mm dti (distance 1597
through insulation) for reinforced insulation and 1 mm for supplementary 1598
insulation. If this insulation served also as outer enclosure for Class II 1599
equipment, it had to be mechanically robust, which was tested with a 1600
hammer blow of 0,5 Nm. 1601
The wire documents did not distinguish between grades of insulation, and 1602
required 0,4 mm for PVC insulation material. This value was considered 1603
adequate to protect against electric shock when touching the insulation if it 1604
was broken. This concept was also introduced in VDE 0860 (which evolved 1605
into IEC 60065), where the 0,4 mm value was discussed first. For IT products 1606
this value was first only accepted for in accessible insulations. 1607
The VDE document for telecom equipment (VDE 0804) did not include any 1608
thickness requirements, but the insulation had to be adequate for the 1609
application. 1610
The document VDE 0730 for household equipment with electric motors 1611
introduced in 1976 the requirement of an insulation thickness of 0,5 mm 1612
between input and output windings of a transformer. Th is was introduced by 1613
former colleagues from IBM and Siemens (against the position of the people 1614
from the transformer committee). 1615
– 50 – IEC TR 62368-2:20xx © IEC 20xx
Also VDE 0110 (Insulation Coordination, which evolved into the IEC 60664 1616
series) contained a minimum insulation thickness of 0,5 mm for 250 V supply 1617
voltage, to cover the effect of insulation breakage. 1618
These 0,5 mm then evolved into 0,4 mm (in IEC 60950-1), with the reference 1619
to VDE 0860 (IEC 60065), where this value was already in use. 1620
It is interesting to note that the 0,31 mm which is derived from Table 2A of 1621
IEC 60950-1, has also a relation to the 0,4 mm. 0,31 mm is the minimum 1622
value of the average insulation thickness of 0,4 mm, according to experts 1623
from the wire manufacturers. 1624
5.4.4.3 Insulating compound forming solid insulation 1625
Source: IEC 60950-1 1626
Purpose: Minimum distance through insulation of 0,4 mm for supplementary 1627
insulation and reinforced insulation. 1628
Rationale: The same distance through insulation requirements as for solid insulation 1629
apply (see 5.4.4.2). Insulation is subjected to thermal cycling (see 5.4.1.5.3), 1630
humidity test (see 5.4.8) and electric strength test (see 5.4.9). Insulation is 1631
inspected for cracks and voids. 1632
5.4.4.4 Solid insulation in semiconductor devices 1633
Source: IEC 60950-1, UL 1577 1634
Purpose: No minimum thickness requirements for the solid insulation. 1635
Rationale: – type testing of 5.4.9.1 (electric strength testing at 160 % of the normal 1636
value after thermal cycling and humidity conditioning), and routine 1637
electric strength test of 5.4.9.2 has been used for many years, especially 1638
in North America. 1639
– refers to G.12, which references IEC 60747-5-5. 1640
5.4.4.5 Insulating compound forming cemented joints 1641
Source: IEC 60950-1 1642
Rationale: a) The distances along the path comply with PD 2 requirements irrespective 1643
of the joint; 1644
b) applies if protected to generate PD 1 environment ; 1645
c) applies if treated like solid insulation environment, no clearances and 1646
creepage distances apply; 1647
d) is not applied to printed boards, when the board temperature is below 1648
90 °C, as the risk for board delaminating at lower temperatures is 1649
considered low. 1650
Optocouplers are excluded from the requirements of this subclause, because 1651
the document requires optocouplers to comply with IEC 60747-5-5, which 1652
sufficiently covers cemented joints. 1653
IEC TR 62368-2:20xx © IEC 20xx – 51 –
5.4.4.6.1 General requirements 1654
Source: IEC 60950-1, IEC 61558-1:2005 1655
Rationale: No dimensional or constructional requirements for insulation in thin sheet 1656
material used as basic insulation, is aligned to the requirements of 1657
IEC 61558-1. 1658
Two or more layers with no minimum thickness are required for 1659
supplementary insulation or reinforced insulation, provided they are 1660
protected against external mechanical influences. 1661
Each layer is qualified for the full voltage for supplementary insulation or 1662
reinforced insulation. 1663
The requirements are based on extensive tests performed on thin sheet 1664
material by manufacturers and test houses involved in IEC TC 74 (now IEC 1665
TC 108) work. 1666
5.4.4.6.2 Separable thin sheet material 1667
Source: IEC 60950-1 1668
Rationale: For two layers, test each layer with the electric strength test of 5.4.9 for the 1669
applicable insulation grade. For three layers, test all combinations of two 1670
layers together with the electric strength test of 5.4.9 for the applicable 1671
insulation grade. 1672
Each layer is qualified for the full voltage for supplementary insulation or 1673
reinforced insulation. 1674
The requirements are based on extensive tests performed on thin sheet 1675
material by manufacturers and test houses involved in IEC TC 74 (now IEC 1676
TC 108) work. 1677
5.4.4.6.3 Non-separable thin sheet material 1678
Source: IEC 60950-1 1679
Rationale: For testing non-separable layers, all the layers are to have the same material 1680
and thickness. If not, samples of different materials are tested as given in 1681
5.4.4.6.2 for separable layers. When testing non-separable layers, the 1682
principle used is the same as for separable layers. 1683
When testing two separable layers, each layer is tested for the requ ired test 1684
voltage. Two layers get tested for two times the required test voltage as each 1685
layer is tested for the required test voltage. When testing two non-separable 1686
layers, the total test voltage remains the same, for example, two times the 1687
required test voltage. Therefore, two non-separable layers are tested at 1688
200 % of the required test voltage. 1689
When testing three separable layers, every combination of two layers is 1690
tested for the required test voltage. Therefore, a single layer gets tested for 1691
half the required test voltage and three layers are tested for 150 % of the 1692
required test voltage. 1693
5.4.4.6.4 Standard test procedure for non-separable thin sheet material 1694
Source: IEC 60950-1 1695
Rationale: Test voltage 200 % of Utest if two layers are used. 1696
Test voltage 150 % of Utest if three or more layers are used. 1697
See the rationale in 5.4.4.6.3. The procedure can be applied to both 1698
separable and non-separable layers as long as the material and material 1699
thickness is same for all the layers. 1700
– 52 – IEC TR 62368-2:20xx © IEC 20xx
5.4.4.6.5 Mandrel test 1701
Source: IEC 61558-1:2005, 26.3.3; IEC 60950-1:2013; IEC 60065:2011 1702
Purpose: This test should detect a break of the inner layer of non-separated foils. 1703
Rationale: This test procedure is taken from IEC 61558-1, 26.3.3, and the test voltage 1704
is 150 % Utest, or 5 kV RMS., whatever is greater. 1705
5.4.4.7 Solid insulation in wound components 1706
Source: IEC 60950-1, IEC 61558-1 1707
Purpose: To identify constructional requirements of insulation of winding wires and 1708
insulation between windings. 1709
Rationale: Requirements have been used in IEC 60950-1 for many years and are 1710
aligned to IEC 61558-1. 1711
Planar transformers are not considered wound components and have to 1712
comply with G.13. 1713
5.4.4.9 Solid insulation requirements at frequencies higher than 30 kHz 1714
Source: IEC 60664-4:2005 1715
Purpose: To identify requirements for solid insulation that is exposed to voltages at 1716
frequencies above 30 kHz. 1717
Rationale: The requirements are taken from the data presented in Annex C of 1718
IEC 60664-4:2005. Testing of solid insulation can be performed at line 1719
frequency as detailed in 6.2 of IEC 60664-4:2005. 1720
In general, the breakdown electric field strength of insulation can be 1721
determined according to IEC 60243-1 (Electrical strength of insulating 1722
materials−Test methods−Part 1) as referred from 5.3.2.2.1 of 1723
IEC 60664-1:2007 (see below). Note that this text is not repeated in IEC 1724
60664-1:2020. 1725
5.3.2.2.1 Frequency of the voltage 1726
The electric strength is greatly influenced by the frequency of the applied 1727
voltage. Dielectric heating and the probability of thermal instability increase 1728
approximately in proportion to the frequency. The breakdown field strength 1729
of insulation having a thickness of 3 mm when measured at power frequency 1730
according to IEC 60243-1 is between 10 kV/mm and 40 kV/mm. Increasing 1731
the frequency will reduce the electric strength of most insulating materials. 1732
NOTE The influence of frequencies greater than 30 kHz on the electric strength is described 1733 in IEC 60664-4. 1734
Table 20 shows the electric field strength for some commonly used materials. 1735
These values are related to a frequency of 50/60 Hz. 1736
Table 21, which is based on Figure 6 of IEC 60664-4:2005, shows the 1737
reduction factor for the value of breakdown electric field strength at higher 1738
frequencies. The electric field strength of materials drops differently at higher 1739
frequencies. The reduction of the insulation property is to be considered 1740
when replacing the calculation method by the alternative ES test at mains 1741
frequency, as shown after the sixth paragraph of 5.4.4.9. Table 21 is for 1742
materials of 0,75 mm in thickness or more. Table 22 is for materials of less 1743
than 0,75 mm in thickness. 1744
The 1,2 times multiplier comes from IEC 60664-4:2005, subclause 7.5.1, 1745
where the partial discharge (PD) extinction voltage must include a safety 1746
margin of 1,2 times the highest peak periodic voltage. 1747
IEC TR 62368-2:20xx © IEC 20xx – 53 –
5.4.5 Antenna terminal insulation 1748
Source: IEC 60065 1749
Purpose: To prevent breakdown of the insulation safeguard. 1750
Rationale: The insulation shall be able to withstand surges due to overvoltages present 1751
at the antenna terminals. These overvoltages are caused by electrostatic 1752
charge build up, but not from lightning effects. A maximum voltage of 10 kV 1753
is assumed. The associated test of G.10.4 simulates this situation by using 1754
a 10 kV test voltage discharged over a 1 nF capacitor. 1755
5.4.6 Insulation of internal wire as a part of a supplementary safeguard 1756
Source: IEC 60950-1 1757
Purpose: To specify constructional requirements of accessible internal wiring 1758
Rationale: Accessible internal wiring isolated from ES3 by basic insulation only needs 1759
a supplementary insulation. If the wiring is reliably routed away so that it 1760
will not be subject to handling by the ordinary person, then smaller than 0,4 1761
mm thick supplementary insulation has been accepted in IEC 60950-1. But 1762
the insulation still has to have a certain minimum thickness together with 1763
electric strength withstand capability. The given values have been 1764
successfully used in products covered by this document for many years (see 1765
Figure 16 in this document). 1766
1767
Figure 16 – Example illustrating accessible internal wiring 1768
– 54 – IEC TR 62368-2:20xx © IEC 20xx
5.4.7 Tests for semiconductor components and for cemented joints 1769
Source: IEC 60950-1 1770
Purpose: To simulate lifetime stresses on adjoining materials. 1771
To detect defects by applying elevated test voltages after sample 1772
conditioning. 1773
To avoid voids, gaps or cracks in the insulating material and delaminating in 1774
the case of multilayer printed boards. 1775
Rationale: This method has been successfully used for products in the scope of this 1776
document for many years. 1777
5.4.8 Humidity conditioning 1778
Source: IEC 60950-1 and IEC 60065. Alternative according to IEC 60664-1:2020, 1779
6.4.3 1780
Purpose: Material preparations for dielectric strength test . Prerequisite for further 1781
testing. 1782
A tropical climate is a location where it is expected to have high temperatures 1783
and high humidity during most of the year. The document does not indicate 1784
what levels of temperature or humidity constitute a tropical climate. National 1785
authorities define whether their country requires products to comply with 1786
tropical requirements. Only a few countries, such as Singapore and China, 1787
have indicated in the CB scheme that they require such testing. 1788
5.4.9 Electric strength test 1789
Source: IEC 60664-1: 2020 1790
Purpose: To test the insulation to avoid breakdown. 1791
Rationale: Values of test voltages are derived from Table F.6 of IEC 60664-1:2020, 1792
however the test duration is 60 s. 1793
This method has been successfully used for products in the scope of 1794
IEC 60065 and IEC 60950-1 for many years. 1795
The DC voltage test with a test voltage equal to the peak value of the AC 1796
voltage is not fully equivalent to the AC voltage test due to the different 1797
withstand characteristics of solid insulation for these types of voltages. 1798
However in case of a pure DC voltage stress, the DC voltage test is 1799
appropriate. To address this situation the DC test is made with both 1800
polarities. 1801
Table 25 Test voltages for electric strength tests based on transient voltages 1802
Source: IEC 60664-1:2020 1803
Rationale: To deal with withstand voltages and cover transients. 1804
The basic insulation and supplementary insulations are to withstand a 1805
test voltage that is equal to the transient peak voltage. The test voltage for 1806
the reinforced insulation shall be equal to the transient in the next in the 1807
preferred series. According to 5.2.5 of IEC 60664-1:2020, the use of 160 % 1808
test value for basic insulation as the test value for reinforced insulation is 1809
only applicable if other values than the preferred series are used. 1810
Functional insulation is not addressed, as is it presumed not to provide any 1811
protection against electric shock. 1812
IEC TR 62368-2:20xx © IEC 20xx – 55 –
Table 26 Test voltages for electric strength tests based on the peak of the working 1813
voltages and recurring peak voltages 1814
Source: IEC 60664-1:2020 1815
Rationale: Column B covers repetitive working voltages and requires higher test 1816
voltages due to the greater stress to the insulation. 1817
Recurring peak voltages (IEC 60664-1:2020, 5.4.3.2) need to be considered, 1818
when they are above the temporary overvoltage values, or in circuits 1819
separated from the mains. 1820
If the recurring peak voltages are above the temporary overvoltage values, 1821
these voltages have to be used, multiplied by the factor given in 1822
IEC 60664-1:2020, 5.4.3.2. 1823
Table 27 Test voltages for electric strength tests based on temporary overvoltages 1824
Source: IEC 60664-1:2020 1825
Rationale: Temporary overvoltages (IEC 60664-1:2020, 5.4.3.2) need to be 1826
considered as they may be present up to 5 s. The test voltage for reinforced 1827
insulation is twice the value of basic insulation. 1828
5.4.10 Safeguards against transient voltages from external circuits 1829
Source: IEC 62151:2000, Clause 6 1830
Purpose: To protect persons against contact with external circuits subjected to 1831
transients (for example, telecommunication networks). 1832
Rationale: External circuits are intended to connect the equipment to other equipment. 1833
Connections to remote equipment are made via communication networks, 1834
which could leave the building. Examples for such communication networks 1835
are telecommunication networks and Ethernet networks. The operating 1836
voltages of communication networks are usually within the limits of ES1 (for 1837
example, Ethernet) or within the limits of ES2 (for example, 1838
telecommunication networks). 1839
When leaving the buildings, communication networks may be subjected to 1840
transient overvoltages due to atmospher ic discharges and faults in power 1841
distribution systems. These transients are depending on the infrastructure of 1842
the cables and are independent on the operating voltage of the 1843
communication network. The expected transients on telecommunication 1844
networks are specified in ITU-T recommendations. The transient value in 1845
Table 13 ID 1 is taken from ITU-T K.21 as 1,5 kV 10/700 µs (terminal 1846
equipment). This transient of 1,5 kV 10/700 µs does not cause a hazardous 1847
electric shock, but it is very uncomfortable to persons effecting by such a 1848
transient. To avoid secondary hazards a separation between an external 1849
circuit connected to communication networks subjected transients is 1850
required. 1851
Because the transient does not cause a hazardous electric shock the 1852
separation element needs not to be a reinforced safeguard nor a basic 1853
safeguard in the meaning of IEC 62368-1. It is sufficient to provide a 1854
separation complying with an electric strength test, only. Therefore for this 1855
separation no clearance, no creepage distances and no thickness 1856
requirements for solid insulation are required. 1857
The separation is required between the external circuit subjected to 1858
transients and all parts, which may accessible to ordinary persons or 1859
instructed persons. 1860
– 56 – IEC TR 62368-2:20xx © IEC 20xx
The likelihood a transient occurs and a body contact with an accessible part 1861
occurs at the same time increases with the contact time. Therefore non-1862
conductive parts and unearthed parts of the equipment maintained in 1863
continuous contact with the body during normal use ( for example, a 1864
telephone handset, head set, palm rest surfaces) the separation should 1865
withstand a higher test voltage. 1866
Two test procedures for the electric strength test are specified in 5.4.10.2. 1867
5.4.10.2.2 Impulse test 1868
The impulse test is performing an impulse test by using the impulse generator 1869
for the 10/700 µs impulse (see test generator D.1 of Annex D). With the 1870
recorded waveforms it could be judged whether a breakdown of insulation 1871
has occurred, or if the surge suppression device has worked properly. 1872
The examples in Figure 17, Figure 18, 1873
1 – gas discharge type
2 – semiconductor type
3 – metal oxide type
Consecutive impulses are identical in their waveforms.
1874
Figure 19 and Figure 20 in this document could be used to assist in judging whether or not 1875
a surge suppressor has operated or insulation has broken down. 1876
1877
Consecutive impulses are identical in their waveforms.
1878
Figure 17 – Waveform on insulation without surge suppressors and no breakdown 1879
IEC TR 62368-2:20xx © IEC 20xx – 57 –
Consecutive impulses are not identical in their waveforms. The pulse shape changes from pulse to pulse until a stable resistance path through the insulation is established. Breakdown can be seen clearly on the shape of the pulse voltage oscillogram.
1880
Figure 18 – Waveforms on insulation during breakdown without surge suppressors 1881
1 – gas discharge type
2 – semiconductor type
3 – metal oxide type
Consecutive impulses are identical in their waveforms.
1882
Figure 19 – Waveforms on insulation with surge suppressors in operation 1883
1884
Figure 20 – Waveform on short-circuited surge suppressor and insulation 1885
– 58 – IEC TR 62368-2:20xx © IEC 20xx
5.4.10.2.3 Steady-state test 1886
The steady-state test is performing an electric strength test according to 1887
5.4.9.1. This test is simple test with an RMS voltage. But if for example, surge 1888
suppressors are used to reduce the transients from the external circuits 1889
within the equipment this RMS test may by not adequate. In this case an 1890
impulse test is more applicable. 1891
5.4.11 Separation between external circuits and earth 1892
Source: IEC 62151:2000, 5.3 1893
Purpose: To protect persons working on communication networks, and users of other 1894
equipment connected to the network from hazards in the equipment. 1895
Rationale: Class I equipment provides basic insulation between mains and earthed 1896
conductive parts and requires the conductive parts to be connected to a PE 1897
conductor that has to be connected to the earthing terminal in the buildings 1898
installation to be safe to use. In an isolated environment such an earth 1899
terminal is not present in the building installation. Nevertheless the use of 1900
class I equipment in such an isolated environment is still safe to use, 1901
because in case of a breakdown of the insulation in the equipment (fault of 1902
basic insulation) the second barrier is provided by the isolated environment 1903
(similar to a supplementary insulation). 1904
With the connection of the equipment via an external circuit to a 1905
communication network from outside the building installation to a remote 1906
environment the situation will change. It is unknown whether the remote 1907
environment is an isolated or non-isolated environment. During and after a 1908
fault of the basic insulation in a class I equipment (from mains to 1909
conductive parts) installed in an isolated installation (non-earthed installation) 1910
the conductive parts will become live (mains potential). If now the conductive 1911
parts are not separated from the external circuit, the mains voltage will be 1912
transferred to the remote installation via the communication network. This is 1913
a hazardous situation in the remote environment and can be dangerous for 1914
persons in that remote environment. 1915
Also in old building installations socket outlets exist with no earth contact. 1916
This situation will not be changed in the near future. 1917
To provide protection for those situations, a separation between an external 1918
circuit intended to be connected to communication networks outside the 1919
building (for example, telecommunication networks) and a separation 1920
between the external circuit and earthed parts is required. 1921
For this separation, it is sufficient to comply with the requirements of 5.4.11.2 1922
tested in accordance with 5.4.11.3. For this separation, no clearance, no 1923
creepage distances and no thickness requirements for solid insulation is 1924
required. 1925
5.5 Components as safeguards 1926
Rationale: For failure of a safeguard and a component or device that is not a 1927
safeguard: 1928
Safeguard failure: A failure is considered to be a safeguard failure if the 1929
part itself or its function, during normal operating conditions, contributes 1930
to change an ES class to a lower ES class. In this case, the part is assessed 1931
for its reliability by applying the applicable safeguard component 1932
requirements in 5.5 and the associated requirements in Annex G. When 1933
establishing ES1, ES2 limits apply during single fault condition of these 1934
parts. In case no requirements for the component are provided in 5.5 or 1935
Annex G, the failure is regarded as a non-safeguard failure. 1936
IEC TR 62368-2:20xx © IEC 20xx – 59 –
Non-safeguard failure: A failure is considered to be a non-safeguard failure 1937
if the part itself or its function, under normal operating conditions, does 1938
not contribute to change an ES class to a lower ES Class. In this case, there 1939
is no need to assess the reliability of the part. When establishing ES1, ES1 1940
limits apply for the single fault condition of these parts. Where applicable, 1941
5.3.1 applies. Figure 21 and Figure 22 in this document give practical 1942
examples of the requirements when ordinary components bridge insulation. 1943
Example 1 1944
1945
Figure 21 – Example for an ES2 source 1946
A single fault of any component or part may not result in the accessible part 1947
exceeding ES1 levels, unless the part complies with the requirements for a 1948
basic safeguard. 1949
The basic safeguard in parallel with the part(s) is to comply with: 1950
– the creepage distance requirements; and 1951
– the clearance requirements 1952
for basic insulation. 1953
There are no other requirements for the components or parts if the 1954
accessible part remains at ES1. 1955
Example 2 1956
1957
Figure 22 – Example for an ES3 source 1958
A single fault of any component or part may not result in the accessible part 1959
exceeding ES1 levels, unless the parts comply with the requirements for a 1960
double or reinforced safeguard. 1961
– 60 – IEC TR 62368-2:20xx © IEC 20xx
The double safeguard or reinforced safeguard in parallel with the part(s) 1962
is to comply with: 1963
– the creepage distance requirements; and 1964
– the clearance requirements, 1965
for double insulation or reinforced insulation. 1966
There are no other requirements for the components or parts if the 1967
accessible part remains at ES1. 1968
5.5.2.1 General requirements 1969
Source: Relevant IEC component documents 1970
Purpose: The insulation of components has to be in compliance with the relevant 1971
insulation requirements of 5.4.1, or with the safety requirements of the 1972
relevant IEC document. 1973
Rationale: Safety requirements of a relevant document are accepted if they are 1974
adequate for their application, for example, Y2 capacitors of IEC 60384-14. 1975
5.5.2.2 Capacitor discharge after disconnection of a connector 1976
Source: IEC TS 61201:2007, Annex A 1977
Rationale: The 2 s delay time represents the typical access time after disconnecting a 1978
connector. When determining the accessible voltage 2 s after disconnecting 1979
a connector, the tolerance of the X capacitor is not considered. 1980
If a capacitor is discharged by a resistor (for example, a bleeder resistor), 1981
the correct value of the resistor can be calculated using the following formula: 1982
R = (2 / C) x [1 / ln(E / Emax)] M 1983
where: 1984
C is in microfarads 1985
E is 60 for an ordinary person or 120 for an instructed person 1986
Emax is the maximum charge voltage or mains peak voltage 1987
ln is the natural logarithm function 1988
NOTE 1 When the mains is disconnected, the capacitance is comprised of both the X 1989 capacitors and the Y capacitors, and other possible capacitances. The circuit is analyzed to 1990 determine the total capacitance between the poles of the connector or plug. 1991
NOTE 2 If the equipment rated mains voltage is 125 V, the maximum value of the discharge 1992 resistor is given by: 1993
R = 1,85 / C M 1994
NOTE 3 If the equipment rated mains voltage is 250 V, the maximum value of the discharge 1995 resistor is given by: 1996
R = 1,13 / C M 1997
NOTE 4 The absolute value of the above calculations is used for the discharge resistor value. 1998
The test method includes a maximum time error of about 9% less than the 1999
calculated time for a capacitive discharge. This error was deemed 2000
acceptable for the sake of consistency with past practice. 2001
For measuring the worst case, care should be taken that the discharge is 2002
measured while at the peak of the input voltage. To ensure this, an automatic 2003
control system that switches off at the peak voltage can be used. 2004
IEC TR 62368-2:20xx © IEC 20xx – 61 –
A method used by several other documents, such as IEC 60065 and 2005
IEC 60335-1 is to repeat the measurement 10 times and record the maximum 2006
value. This assumes that one of the 10 measurements will be sufficiently 2007
close to the peak value. 2008
Another possibility might be to use an oscilloscope during the measurement, 2009
so one can see if the measurement was done near the maximum. 2010
Single fault conditions need not be considered if the component complies 2011
with the relevant component requirements of the document. For example, a 2012
resistor connected in parallel with a capacitor where a capacitor voltage 2013
becomes accessible upon disconnection of a connector, need not be faulted 2014
if the resistor complies with 5.5.6. 2015
When determining the accessible voltage 2 s after disconnection of the 2016
connector, the tolerance of the X-capacitor is not considered. 2017
5.5.6 Resistors 2018
Source: IEC 60950-1 and IEC 60065 2019
Rationale: When a group of resistors is used, the resistors are in series. The whole path 2020
consists of the metal lead and helical end (metal) and resis tor body. The 2021
clearance and creepage distance is across the resistor body only. The total 2022
path then consists of conductive metal paths and resistor bodies (all in 2023
series). In this case, Figure O.4 becomes relevant when you want to 2024
determine the total clearance and creepage distance. 2025
5.5.7 SPDs 2026
Rationale: See Attachment A for background information on the use o f SPD’s. 2027
It should be noted that the issue is still under discussion in IEC TC 108. The 2028
rationale will be adapted as soon as the discussion is finalized. 2029
A GDT is a gap, or a combination of gaps, in an enclosed discharge medium 2030
other than air at atmospheric pressure, and designed to protect apparatus or 2031
personnel, or both, from high transient voltages (from ITU-T K.12- 2032
Characteristics of gas discharge tubes for the protection of 2033
telecommunications installations). It shall be used to protect equipment from 2034
transient voltages. 2035
Even if a GDT operates during the occurrence of transient voltages, it is not 2036
hazardous according to 5.2.2.4, Electrical energy source ES1 and ES2 limits 2037
of Single pulses. 2038
NOTE These single pulses do not include transients 2039
Because a transient does not cause a hazardous electric shock, the 2040
separation element does not need to be a reinforced safeguard nor a basic 2041
safeguard in the meaning of IEC 62368-1. 2042
If suitable components are connected in-series to the SPD (such as a VDR, 2043
etc.), a follow current will not occur, and there will be no harmful effect. 2044
5.5.8 Insulation between the mains and an external circuit consisting of a coaxial 2045
cable 2046
Source: IEC 60065:2014, 10.2 and IEC 60950-1:2005, 1.5.6. 2047
Rationale: The additional conditioning of G.10.2 comes from IEC 60950-1:2005, 1.5.6 2048
Capacitors bridging insulation. 2049
The 21-days of damp-heat conditioning of resistors serving as a safeguard 2050
between the mains and an external circuit consisting of a coaxial cable is 2051
necessary to ensure the reliability of such resistors. 2052
– 62 – IEC TR 62368-2:20xx © IEC 20xx
Except for components such as the resistors in parallel of the insulation 2053
between the mains and the connection to a coaxial cable, the 21-days of 2054
damp-heat conditioning is not necessary for this insulation in IEC 60065, 2055
IEC 60950-1 and IEC 62368-1. 2056
5.6 Protective conductor 2057
See Figure 23 in this document for an overview of protective earthing and 2058
protective bonding conductors. 2059
2060
Figure 23 – Overview of protective conductors 2061
5.6.1 General 2062
Source: IEC 60364-5-54, IEC 61140, IEC 60950-1 2063
Purpose: The protective earthing should have no excessive resistance, sufficient 2064
current-carrying capacity and not be interrupted in all circumstances. 2065
5.6.2.2 Colour of insulation 2066
Source: IEC 604461 2067
Purpose: For clear identification of the earth connection. 2068
An earthing braid is a conductive material, usually copper, made up of three 2069
or more interlaced strands, typically in a diagonally overlapping pattern. 2070
It should be noted that IEC 60227-1:2007 has specific requirements for the 2071
use of the colour combination as follows: 2072
2073
2074
___________
1 This publication was withdrawn.
IEC TR 62368-2:20xx © IEC 20xx – 63 –
5.6.3 Requirements for protective earthing conductors 2075
Source: IEC 60950-1 2076
Purpose: The reinforced protective conductor has to be robust enough so that the 2077
interruption of the protective conductor is prevented in any case 2078
(interruption is not to be assumed). 2079
Rationale: These requirements have been successfully used for products in the scope 2080
of this document for many years. 2081
Where a conduit is used, if a cord or conductor exits the conduit and is not 2082
protected, then the values of Table 30 cannot be used for the conductor that 2083
exits the conduit. 2084
For pluggable equipment type B and permanently connected equipment, 2085
an earthing connection is always expected to be present. The earthing 2086
conductor can therefore be considered as a reinforced safeguard. 2087
5.6.4 Requirements for protective bonding conductors 2088
Source: IEC 60950-1 2089
Purpose: To demonstrate the fault current capability and the capability of the 2090
termination. 2091
Rationale: These requirements and tests have been successfully used for products in 2092
the scope of this document for many years (see Figure 3 in this document). 2093
5.6.5 Terminals for protective conductors 2094
5.6.5.1 Requirements 2095
Source: IEC 60998-1, IEC 60999-1, IEC 60999-2, IEC 60950-1 2096
Purpose: To demonstrate the fault current capability and the capability of the 2097
termination. 2098
Rationale: Conductor terminations according to Table 32 have served as reliable 2099
connection means for products complying with IEC 60950-1 for many years. 2100
The value of 25 A is chosen to cover the minimum protective current rating 2101
in all countries of the world. 2102
5.6.6.2 Test method 2103
Source: IEC 60950-1 2104
Rationale: This method has been successfully used for products in the scope of this 2105
document for many years. 2106
5.6.7 Reliable connection of a protective earthing conductor 2107
Source: IEC 60309 (plugs and socket outlets for industrial purpose) 2108
Purpose: To describe reliable earthing as provided by permanently connected 2109
equipment, pluggable equipment type B, and pluggable equipment type 2110
A. 2111
Rationale: Permanently connected equipment is considered to provide a reliable 2112
earth connection because it is wired by an electrician. 2113
Pluggable equipment type B is considered to provide a reliable earth 2114
connection because IEC 60309 type plugs are more reliable and earth is 2115
always present as it is wired by an electrician. 2116
For stationary pluggable equipment type A where a skilled person 2117
verifies the proper connection of the earth conductor . 2118
5.7 Prospective touch voltage, touch current and protective conductor current 2119
Source: IEC 60990 2120
– 64 – IEC TR 62368-2:20xx © IEC 20xx
5.7.3 Equipment set-up, supply connections and earth connections 2121
Rationale: Equipment that is designed for multiple connections to the mains, where 2122
more than one connection is required, shall be subjected to either of the tests 2123
below: 2124
– have each connection tested individually while the other connections are 2125
disconnected, 2126
– have each connection tested while the other connections are connected, 2127
with the protective earthing conductors connected together. 2128
For simultaneous multiple connections, the requirement in the document is 2129
that each connection shall be tested while the other connections are 2130
connected, with the protective earthing conductors connected together. If 2131
the touch current exceeds the limit in 5.2.2.2, the touch current shall be 2132
measured individually. 2133
This means that if the total touch current with all connections tested 2134
together does not exceed the limit, the equipment complies with the 2135
requirement, if not, and each of the individual conductor touch currents don’t 2136
exceed the limit, the equipment also compl ies with the requirement. 2137
5.7.5 Earthed accessible conductive parts 2138
Rationale: Figure 24 in this document is an example of a typical test configuration for 2139
touch current from single phase equipment on star TN or TT systems. Other 2140
distribution systems can be found in IEC 60990. 2141
2142
Figure 24 – Example of a typical touch current measuring network 2143
5.7.6 Requirements when touch current exceeds ES2 limits 2144
Source: IEC 61140:2001, IEC 60950-1 2145
Rationale: The 5 % value has been used in IEC 60950-1 for a long time and is 2146
considered acceptable. The 5 % value is also the maximum allowed 2147
protective conductor current (7.5.2.2 of IEC 61140:2001). 2148
In the case that the protective conductor current exceeds 10 mA, 2149
IEC 61140 requires a reinforced protective earthing conductor with a 2150
conductor size of 10 mm2 copper or 16 mm2 aluminium or a second terminal 2151
for a second protective earthing conductor. This paragraph of IEC 62368-2152
1 takes that into account by requiring a reinforced or double protective 2153
earthing conductor as per 5.6.3. 2154
IEC TR 62368-2:20xx © IEC 20xx – 65 –
IEC 61140:2001, 7.5.2.2 requires information about the value of the 2155
protective conductor current to be in the documentation and in the 2156
instruction manual, to facilitate the determination that the equipment with the 2157
high protective conductor current is compatible with the residual current 2158
device which may be in the building installation. 2159
The manufacturer shall indicate the value of the protective conductor 2160
current in the installation instructions if the current exceeds 10 mA, this to 2161
be in line with the requirements of IEC 61140:2001, 7.6.3.5. 2162
5.7.7 Prospective touch voltage and touch current associated with external circuits 2163
5.7.7.1 Touch current from coaxial cables 2164
Source: IEC 60728-11 2165
Purpose: To avoid having an unearthed screen of a coaxial network within a building. 2166
Rationale: An earthed screen of a coaxial network is reducing the risk to get an electric 2167
shock. 2168
Coaxial external interfaces very often are connected to antennas to receive 2169
TV and sound signals. Antennas installed outside the buildings are exposed 2170
to external atmospheric discharges (for example, indirect lightning). To 2171
protect the antenna system and the equipment connected to such antennas , 2172
a path to earth needs to be provided via the screen of the coaxial network. 2173
Each piece of mains-powered equipment delivers touch current to a coaxial 2174
external circuit via the stray capacitance and the capacitor (if provided) 2175
between mains and coaxial interface. This touch current is limited by the 2176
requirement for each individual equipment to comply with the touch current 2177
requirements (safe value) to be measured according IEC 60990. Within a 2178
building, much individual equipment (for example, TV’s receivers) may be 2179
connected to a coaxial network (for example, cable distribution system). In 2180
this case, the touch current from each individual equipment sums up in the 2181
shield of the coaxial cable. With an earthed shield of a coaxial cable , the 2182
touch current has a path back to the source and the shield of the coaxial 2183
cable remains safe to touch. 2184
5.7.7.2 Prospective touch voltage and touch current associated with paired 2185
conductor cables 2186
Source: IEC 62151 2187
Purpose: To avoid excessive prospective touch voltage and excessive currents from 2188
equipment into communication networks ( for example, telecommunication 2189
networks). 2190
Rationale: All touch current measurements according to IEC 60990 measure the 2191
current from the mains to accessible parts. ES1 circuits are permitted to 2192
be accessible by an ordinary person and therefore it is included in the 2193
measurement according to IEC 60990. Circuits of class ES2 are not 2194
accessible and therefore these classes of circuits are not covered in the 2195
measurements according to IEC 60990. 2196
Because ES2 circuits may be accessible to instructed persons and may 2197
become accessible during a single fault to an ordinary person, the touch 2198
current to external circuit has to be limited, to protect people working on 2199
networks or on other equipment, which are connected to the external circuit 2200
via a network. 2201
An example for an external interface ID 1 of Table 13 is the connection to a 2202
telecommunication network. It is common for service personal of 2203
telecommunication networks and telecommunication equipment to make 2204
servicing under live conditions. Therefore, the telecommunication networks 2205
are operating with a voltage not exceeding energy class ES2. 2206
– 66 – IEC TR 62368-2:20xx © IEC 20xx
The rationale to limit the touch current value to 0,25 mA (lower than ES2) 2207
has a practical background. Telecommunication equipment very often have 2208
more than one external circuit ID 1 of Table 13 (for example, connection to 2209
a telecommunication network). In such configurations a summation of the 2210
touch current may occur (see 5.7.7). With the limitation to 0,25 mA per each 2211
individual external circuit up to 20 external circuits could be connected 2212
together without any additional requirement. In 5.7.7 this value of 0,25 mA is 2213
assumed to be the touch current from a network to the equipment. 2214
5.7.8 Summation of touch currents from external circuits 2215
Source: IEC 60950-1 2216
Purpose: To avoid excessive touch currents when several external circuits are 2217
connected. 2218
Rationale: When limiting the touch current value to each individual external circuit 2219
(as required in 5.7.6.2), more circuits can be connected together before 2220
reaching the touch current limit. This allows better utilization of resources. 2221
Detailed information about touch currents from external circuits is given 2222
in Annex W of IEC 60950-1:2005. 2223
a) Touch current from external circuits 2224
There are two quite different mechanisms that determine the current through 2225
a human body that touches an external circuit, depending on whether or not 2226
the circuit is earthed. This distinction between earthed and unearthed 2227
(floating) circuits is not the same as between class I equipment and class II 2228
equipment. Floating circuits can exist in class I equipment and earthed 2229
circuits in class II equipment. Floating circuits are commonly, but not 2230
exclusively, used in telecommunication equipment and earthed circuits in 2231
data processing equipment, also not exclusively. 2232
In order to consider the worst case, it will be assumed in this annex that 2233
telecommunication networks are floating and that the AC mains supply and 2234
human bodies (skilled persons, instructed persons or ordinary persons) 2235
are earthed. It should be noted that a skilled person and an instructed 2236
person can touch some parts that are not accessible by an ordinary 2237
person. An "earthed" circuit means that the circuit is either directly earthed 2238
or in some way referenced to earth so that its potential with respect to ea rth 2239
is fixed. 2240
a.1) Floating circuits 2241
If the circuit is not earthed, the current ( Ic) through the human body is 2242
"leakage" through stray or added capacitance (C) across the insulation in the 2243
mains transformer (see Figure 25 in this document). 2244
2245
Figure 25 – Touch current from a floating circuit 2246
IEC TR 62368-2:20xx © IEC 20xx – 67 –
This current comes from a relatively high voltage, high impedance source, 2247
and its value is largely unaffected by the operating voltage on the external 2248
circuit. In this document, the body current (Ic) is limited by applying a test 2249
using the measuring instrument in Annex D of IEC 60950-1:2005, which 2250
roughly simulates a human body. 2251
a.2) Earthed circuits 2252
If the external circuit is earthed, the current through the human body ( Iv) is 2253
due to the operating voltage (V) of the circuit, which is a source of low 2254
impedance compared with the body (see Figure 26 in this document). Any 2255
leakage current from the mains transformer (see a.1), will be conducted to 2256
earth and will not pass through the body. 2257
2258
Figure 26 – Touch current from an earthed circuit 2259
In this document, the body current (Iv) is limited by specifying maximum 2260
voltage values for the accessible circuit, which shall be an ES1 circuit or 2261
(with restricted accessibility) an ES2 circuit. 2262
b) Interconnection of several pieces of equipment 2263
It is a characteristic of information technology equipment, in particular in 2264
telecommunication applications, that many pieces of equipment may be 2265
connected to a single central equipment in a "star" topology. An example is 2266
telephone extensions or data terminals connected to a PABX, which may 2267
have tens or hundreds of ports. This example is used in the following 2268
description (see Figure 27 in this document). 2269
2270
Figure 27 – Summation of touch currents in a PABX 2271
– 68 – IEC TR 62368-2:20xx © IEC 20xx
Each terminal equipment can deliver current to a human body touching the 2272
interconnecting circuit (I1, I2, etc.), added to any current coming from the 2273
PABX port circuitry. If several circuits are connected to a common point, their 2274
individual touch currents will add together, and this represents a possible 2275
risk to an earthed human body that touches the interconnection circuit. 2276
Various ways of avoiding this risk are considered in the following subclauses. 2277
b.1) Isolation 2278
Isolate all interconnection circuits from each other and from earth, and limit 2279
I1, I2, etc., as described in a.1. This implies either the use in the PABX of a 2280
separate power supply for each port, or the provision of an individual line 2281
(signal) transformer for each port. Such solutions may not be cost effective. 2282
b.2) Common return, isolated from earth 2283
Connect all interconnection circuits to a common return point that is isolated 2284
from earth. (Such connections to a common point may in any case be 2285
necessary for functional reasons.) In this case the total current from all 2286
interconnection circuits will pass through an earthed human body that 2287
touches either wire of any interconnection circuit. This current can only be 2288
limited by controlling the values I1, I2, .. In. In relation to the number of ports 2289
on the PABX. However, the value of the total current will probably be less 2290
than I1 + I2 +... + In due to harmonic and other effects. 2291
b.3) Common return, connected to protective earth 2292
Connect all interconnection circuits to a common return point and connect 2293
that point to protective earthing. The situation described in a.2) applies 2294
regardless of the number of ports. Since safety depends on the presence of 2295
the earth connection, it may be necessary to use high-integrity earthing 2296
arrangements, depending on the maximum value of the total current that 2297
could flow. 2298
5.8 Backfeed safeguard in battery backed up supplies 2299
Source: IEC 62040-1:2017, IEC 62368-1, UL 1778 5th edition 2300
Purpose: To establish requirements for certain battery backed up power supply 2301
systems that are an integral part of the equipment and that have the 2302
capability to backfeed to the mains of the equipment during stored energy 2303
mode. Examples include CATV network distribution supplies and any other 2304
integral supply commonly evaluated under this document with a battery 2305
backed option. 2306
Rationale: Principles of backfeed safeguard 2307
Battery backed up supplies store and generate hazardous energy . These 2308
energies may be present at the input terminals of the unit. 2309
A backfeed safeguard is intended to prevent ordinary persons, instructed 2310
persons or skilled persons from unforeseeable or unnecessary exposure 2311
to such hazards. 2312
A mechanical backfeed safeguard should meet a minimum air gap 2313
requirement. If not, the mechanical device (contacts) may be forced closed, 2314
and this will not be counted as a fault. The backfeed safeguard operates 2315
with any and all semiconductor devices in any single phase of the mains 2316
power path failed. 2317
A backfeed safeguard works under any normal operating condition. This 2318
should include any output load or input source condition deemed normal by 2319
the manufacturer; however, it is common practice to only test at full - and no-2320
load conditions, unless analysis of the circuitry proves other conditions would 2321
be less favourable. The circuitry that controls the backfeed safeguard is 2322
intended to be single-fault tolerant. 2323
IEC TR 62368-2:20xx © IEC 20xx – 69 –
A backfeed safeguard can accomplish this by disconnecting the mains 2324
supply wiring from the internal energy source, by disabling the inverter and 2325
removing the hazardous source(s) of energy, reducing the source to a safe 2326
level, or by placing a suitable safeguard between the ordinary person, 2327
instructed person or skilled person and the hazardous energy. ES1 is 2328
defined in the body of this document. The method of measurement is as 2329
follows: 2330
– For pluggable equipment, it is determined by opening all phases, neutral 2331
and ground. 2332
– For permanently connected equipment, the neutral and ground are not 2333
removed during the backfeed safeguard tests. 2334
Measurements are taken at the unit input connections across the phases, 2335
from phase to neutral and phase and neutral to ground, using the body 2336
impedance model as the measurement device. 2337
Air gap requirements for mechanical disconnect: 2338
An air gap is only required when the backfeed safeguard is mechanical in 2339
nature. The air gap is defined as the clearance distance. There are several 2340
elements to consider when determining the clearance requirement: 2341
– Under normal operation, the space between poles of phases must meet 2342
the requirements for basic insulation (see 5.4.2). 2343
– If the unit is operating on inverter, the source is considered to be a 2344
secondary supply, which is transient free (see 5.4.2). 2345
For a unit with floating outputs, opening all phases and the neutral using the 2346
required clearance for basic insulation is considered acceptable. If the 2347
output is grounded to the chassis , reinforced insulation or equivalent is 2348
required. 2349
Fault testing 2350
All backfeed safeguard control circuits are subjected to failure analysis and 2351
testing. 2352
Relays 2353
Relays in the mains path that are required to open for mechanical protection 2354
should be normally open when not energized. 2355
If the relay does not meet the required clearances, the shorting of either 2356
pole/contact may be considered as a single fault to simulate the welding of 2357
the contacts. The failure of a single relay contact may be sensed and the 2358
inverter disabled to prevent feedback. 2359
A relay used for mechanical protection shall be horsepower-rated or pass a 2360
50-cycle endurance test at 600 % of the normal switching current. 2361
Electronic protection 2362
Electronic protection for a backfeed safeguard is acceptable if the operation 2363
of the electronic protection device is sensed and the inverter is disabled if a 2364
fault is found. This is the same requirement as for a relay having less than 2365
the required air gap or clearance or is not relied upon entirely for mechanical 2366
protection. 2367
Mechanical protection 2368
Mechanical protection for a backfeed safeguard is acceptable if it prevents 2369
the user from accessing greater than ES1 and cannot be readily defeated 2370
without the use of tool. The voltage rating of the mechanical protection 2371
should be no less than the maximum out-of-phase voltage. 2372
Control circuitry 2373
– 70 – IEC TR 62368-2:20xx © IEC 20xx
The failure, open- or short-circuit, of any component of the backfeed 2374
safeguard circuitry may be analyzed to evaluate the effects on the proper 2375
operation of the backfeed safeguard. Testing may be done on all 2376
components where analysis of the results is arguable. 2377
Components, such as resistors and inductors, are considered to fail open-2378
circuit only. In general, capacitors may fail open or shorted. Solid-state 2379
devices typically fail short and then open. 2380
Microprocessor controls are considered to be acceptable if the circuit 2381
operates safely with any single control line open or shorted to control logic 2382
ground, or shorted to Vcc where such fault is likely to occur . Failure of the 2383
microprocessor can also be simulated by opening the Vcc pin or shorting the 2384
Vcc pin to ground. 2385
If the control circuitry is fully redundant, (for example, N + 1), failure analysis 2386
of individual components is not required if the failure of one circuit results in 2387
a fail-safe mode of operation. 2388
_____________ 2389
Electrically-caused fire 2390
Rationale: Electrically-caused fire is due to conversion of electrical energy to thermal 2391
energy, where the thermal energy heats a fuel material to pyrolyze the solid 2392
into a flammable gas in the presence of oxygen. The resulting mixture is 2393
heated further to its ignition temperature which is followed by c ombustion of 2394
that fuel material. The result ing combustion, if exothermic or with additional 2395
thermal energy converted from the electrical source, can be sustained and 2396
subsequently ignite adjacent fuel materials that result in the spread of fire. 2397
The three-block model (see 0.7.2, Figure 6) for electrically (internally) 2398
caused fire addresses the separation of a potential ignition sources from 2399
combustible materials. In addition, it can also represent an ignited fuel and 2400
the safeguards interposed between ignited fuels and adjacent fuels or to 2401
fuels located outside the equipment. 2402
6.2 Classification of power sources (PS) and potential ignition sources (PIS) 2403
Rationale: The first step in the application of this clause is to determine which energy 2404
sources contain potential ignition sources requiring a safeguard. The 2405
power available to each circuit can first be evaluated to determine the energy 2406
available to a circuit. Then each point or component within a circuit can be 2407
tested to determine the power that would be available to a fault at that 2408
component. With this information each part of the component energy sources 2409
within the product can be classified as either a specific ignition source or a 2410
component within a power source. 2411
Throughout the clause, the term “reduce the likelihood of ignition” is used in 2412
place of the terms “prevent” or “eliminate”. 2413
6.2.2 Power source circuit classifications 2414
Source: IEC 60950-1, IEC 60065 2415
Rationale: These power source classifications begin with the lowest available energy 2416
necessary to initiate an electronic fire (PS1) and include an intermediate 2417
level (PS2) where ignition is possible but the spread of fire can be localized 2418
with effective material control or isolation safeguards. The highest energy 2419
level (PS3), assumes both ignition and a potential spread of fire beyond the 2420
ignition source. Criteria for safeguards will vary based on the type of power 2421
source that is providing power to the circuit. 2422
IEC TR 62368-2:20xx © IEC 20xx – 71 –
This power measurement and source classification are similar to LPS test 2423
requirements from IEC 60950-1 but are applied independently and the 2424
criteria limited to available power as opposed to in combination of criteria 2425
required in IEC 60950-1. 2426
All circuits and devices connected or intended to be connected as a load to 2427
each measured power source are classified as being part of that power 2428
source. This test method determines the maximum power available from a 2429
power source to any circuit connected to that power source. 2430
The identification of test points for determination of power source is at the 2431
discretion of the manufacturer. The most obvious are outputs of internal 2432
power supply circuits, connectors, ports and board to board connections. 2433
However, these measurements can be made anywhere within a circuit. 2434
When evaluating equipment (peripherals) connected v ia cables to an 2435
equipment port or via cable, the impedance of any connecting cable may be 2436
taken into account in the determination of the PS classification of a 2437
connected peripheral. Therefore, it is acceptable to make the measurement 2438
at the supply connector or after the cable on the accessory side. 2439
The location of the wattmeter is critical, as the total power available from the 2440
power source (not the power available to the fault) is measured during each 2441
fault condition. As some fault currents may be limited by a protective device, 2442
the time and current breaking characteristics of the protective device used 2443
is considered where it has an effect on the value measured. 2444
This test method assumes a single fault in either the power source or the 2445
load circuits of the circuit being classified. It assumes both: 2446
a) a fault within the circuit being classified, and 2447
b) any fault within the power source supplying power to the circuit being 2448
classified, 2449
each condition a) or b) being applied independently. 2450
The higher of the power measured is considered the PS circuit classification 2451
value. 2452
6.2.2.2 Power measurement for worst-case fault 2453
Rationale: This test method determines the maximum power available from a power 2454
source that is operating under normal operating conditions to any c ircuit 2455
connected to that power source, assuming any single fault condition within 2456
the circuit being classified. This power measurement assumes normal 2457
operating conditions are established before applying the single fault to any 2458
device or insulation in the load circuit to determine the maximum power 2459
available to a circuit during a fault. 2460
This is different for potential ignition source power measurements where 2461
the measured power available is that at the fault location. 2462
A value of 125 % was chosen to have some degree of certainty that the fuse 2463
will open after a certain amount of time. As such, the measured situation will 2464
not be a continuous situation. It was impossible to use the interruption 2465
characteristics of a fuse, since different types of interrupting devices have 2466
completely different interrupting characteristics. The value of 125 % is a 2467
compromise that should cover the majority of the situations. 2468
6.2.2.3 Power measurement for worst-case power source fault 2469
Rationale: This test method determines the maximum power available to a normal load 2470
from a power source assuming any single fault within the power source. A 2471
power source fault could result in an increase in power drawn by a normal 2472
operating load circuit. 2473
– 72 – IEC TR 62368-2:20xx © IEC 20xx
6.2.2.4 PS1 2474
Source: IEC 60065, IEC 60695, IEC 60950-1 2475
Rationale: A PS1 source is considered to have too little energy to cause ignition in 2476
electronic circuits and components. 2477
The requirement is that the continuous available power be less than 15 W to 2478
achieve a very low possibility of ignition. The value of 15 W has been used 2479
as the lower threshold for ignition in electronic components in many 2480
documents, including IEC 60950-1 and IEC 60065. It has also routinely been 2481
demonstrated through limited power fault testing in electronic circuits. 2482
– In order to address the ease of measurement, it was decided to make the 2483
15 W measurement after 3 s. The value of 3 s was chosen to permit ease 2484
of measurement. Values as short as 100 ms and as high as 5 s were also 2485
considered. Quickly establishing a 15 W limit (less than 1 s) is not 2486
practical for test purposes and not considered important for typical fuel 2487
ignition. It is recognized that it normally takes as long as 10 s for 2488
thermoplastics to ignite when impinged directly by a small flame 2489
(IEC 60695 small scale material testing methods). 2490
– In principle the measurements are to be made periodically (for example, 2491
each second) throughout the 3 s period with the expectation that after 3 2492
s, the power would “never” exceed 15 W. 2493
– Historically telecommunication circuits (Table 13, ID 1) are power limited 2494
by the building network to values less than 15 W and the circuits 2495
connected to them are considered PS1 (from IEC 60950-1). 2496
It should be noted that the statement for external circuits is not intended to 2497
cover technologies such as USB and PoE. It is meant to relate to analogue 2498
ringing signals only. 2499
6.2.2.5 PS2 2500
Source: IEC 60695-11-10, IEC 60950-1 2501
Rationale: Power Source 2 assumes a level of energy that has the possibility of ignition 2502
and subsequently requires a safeguard. Propagation of the ignition beyond 2503
the initially ignited component is limited by the low energy contribution to the 2504
fault and subsequently by safeguards to control the ignition resistance of 2505
nearby fuels. 2506
The primary requirement is to limit power available to these circuits to no 2507
more than 100 W. This value includes both power available for normal 2508
operation and the power available for any single fault condition. 2509
– This value has been used in IEC 60950-1 for a similar purpose, where 2510
ignition of internal components is possible but fire enclosures are not 2511
required. 2512
– The value of 100 W is commonly used in some building or fire codes to 2513
identify where low power wiring can be used outside of a fire containing 2514
enclosure. 2515
– The value is also 2 × 50 W, which can be related to the energy of standard 2516
flaming ignition sources (IEC 60695-11-10 test flame) on which our small-2517
scale V-rating material flammability classes are based. It is recognized 2518
that the conversion of electrical energy to thermal energy is far less than 2519
100 %, so this value is compatible with the safeguards prescribed for 2520
PS2 circuits, which are generally isolation and V-rated fuels. 2521
IEC TR 62368-2:20xx © IEC 20xx – 73 –
The 5 s measurement for PS2 ensures the available power limits are both 2522
limited and practical for the purposes of measurement. The value is also 2523
used in IEC 60950 series as referenced above. No short-term limits are 2524
considered necessary, as possibility of ignition is presumed for components 2525
in these power limited circuits, recognizing that it generally takes 10 s or 2526
more for thermoplastics to pyrolyze and then ignite when impinged directly 2527
by a small 50 W flame. 2528
Reliability of overcurrent devices (such as those found in IEC 60950 series) 2529
is not necessary as these circuits are used within or directly adjacent to the 2530
product (not widely distributed like IEC 60950-1 LPS circuits used for 2531
connection to building power). The reliability assessment for PS2 circuits 2532
that are intended to be distributed within the building wiring is addressed for 2533
external circuits later in this document. 2534
6.2.2.6 PS3 2535
Rationale: PS3 circuits are circuits that are not otherwise classified as PS1 or PS2 2536
circuits. No classification testing is required as these circuits can have 2537
unlimited power levels. If a circuit is not measured, it can be assumed to be 2538
PS3. 2539
6.2.3 Classification of potential ignition sources 2540
Rationale: With each power source, points and components within a circuit can be 2541
evaluated to determine if potential ignition sources are further identified. 2542
These ignition sources are classified as either an arcing PIS for arcing 2543
sources or a resistive PIS for resistance heating sources. Criteria for 2544
safeguards will vary based on the type of PIS being addressed. 2545
Ignition sources are classified on their ability to either arc or dissipate 2546
excessive heat (resistive). It is important to distinguish the type of ignition 2547
source as distances through air from arcing parts versus other resistive 2548
ignition sources vary due to a higher thermal loss in radiated energy as 2549
compared to conducted flame or resistive heat impinging directly on a 2550
combustible fuel material. 2551
6.2.3.1 Arcing PIS 2552
Source: IEC 60065 2553
Rationale: Arcing PIS are considered to represent a thermal energy source that results 2554
from the conversion of electrical energy to an arc, which may impinge directly 2555
or indirectly on a fuel material. 2556
Power levels below 15 W (PS1) are considered to be too low to initiate an 2557
electrical fire in electronic circuits. This value is used in IEC 60065 (see also 2558
6.2.1). 2559
The minimum voltage (50 V) required to initiate arcing is also from IEC 60065 2560
and through experimentation. 2561
For low-voltages, the fault that causes arc-heating is generally a result of a 2562
loose connection such as a broken solder connection, a cold -solder 2563
connection, a weakened connector contact, an improperly c rimped wire, an 2564
insufficiently tightened screw connection, etc. As air does not break down 2565
below 300 V RMS. (Paschen’s Law), most low voltage arc-heating occurs in 2566
direct contact with a fuel. For voltages greater than 300 V, arcing can occur 2567
through air. 2568
The measurement of voltage and current necessary to establish an arcing 2569
PIS is related the energy that is available to the fault (as opposed to energy 2570
available from a power source). The value (Vp × Irms) specified is neither a 2571
W or VA but rather a calculated number reflect ing a peak voltage and RMS 2572
current. It is not directly measurable. 2573
– 74 – IEC TR 62368-2:20xx © IEC 20xx
Arcing below 300 V is generally the result of a disconnection of current-2574
carrying connections rather than the mating or connection of potentially 2575
current-carrying connections. 2576
Once the basic parameters of voltage and power are met, there are three 2577
conditions for which safeguards are required: 2578
– those that can arc under normal operating conditions; 2579
– all terminations where electrical failure resulting in heating is more likely ; 2580
and 2581
– any electrical separation that can be created during a single fault 2582
condition (such as the opening of a trace). 2583
A reliable connection is a connection which is expected not to become 2584
disconnected within the lifetime of the equipment. The examples in the note 2585
give an idea as to what kinds of connections can be considered reliable. 2586
The manufacturer may declare any location to be an arcing PIS. 2587
6.2.3.2 Resistive PIS 2588
Source: IEC 60065 2589
Rationale: Resistive potential ignition sources can result from a fault that causes 2590
over-heating of any impedance in a low-resistance that does not otherwise 2591
cause an overcurrent protection to operate. This can happen in any circuit 2592
where the power to the resistive heating source is greater than 15 W (see 2593
above). A resistive PIS may ignite a part due to excessive power dissipation 2594
or ignite adjacent materials and components. 2595
Under single fault conditions, this clause requires that two conditions exist 2596
before determining that a part can be a resistive PIS. The first is that there 2597
is sufficient available fault energy to the component. The second is that 2598
ignition of the part or adjacent materials can occur. 2599
The requirement for a resistive PIS under normal operating conditions is 2600
not the available power but rather the power dissipation of the part under 2601
normal operating conditions. 2602
The value of 30 s was used in IEC 60065 and has historically proven to be 2603
sufficient. The value of 100 W was used in IEC 60065 and has historically 2604
proven to be adequate. 2605
The manufacturer may declare any location to be a resistive PIS. 2606
6.3 Safeguards against fire under normal operating conditions and abnormal 2607
operating conditions 2608
Rationale: The basic safeguard under normal operating conditions and abnormal 2609
operating conditions is to reduce the likelihood of ignit ion by limiting 2610
temperature of fuels. This can be done by assuring that any available 2611
electrical energy conversion to thermal energy does not raise the 2612
temperature of any part beyond its ignition temperature. 2613
IEC TR 62368-2:20xx © IEC 20xx – 75 –
2614
Figure 28 – Possible safeguards against electrically-caused fire 2615
There are several basic safeguards and supplementary safeguards against 2616
electrically-caused fire under abnormal operating conditions and single fault 2617
conditions (see Figure 28, Table 8 and Table 9 in this document). These 2618
safeguards include, but are not limited to: 2619
S1) having insufficient power to raise a fuel material to ignition temperature; 2620
S2) limiting the maximum continuous fault current; limiting the maximum duration for 2621
fault currents exceeding the maximum continuous fault current (for example, a 2622
fuse or similar automatic-disconnecting overcurrent device); 2623
S3) selecting component rating based on single fault conditions rather than 2624
normal operating conditions (prevents the component from overheating); 2625
S4) ensuring high thermal resistance of the thermal energy transfer path from the 2626
thermal energy source to the fuel material (reduces the temperature and the rate 2627
of energy transfer to the fuel material so that the fuel material cannot attain 2628
ignition temperature); or a barrier made of non-combustible material; 2629
S5) using an initial fuel material located closest to an arcing PIS or resistive PIS 2630
having a temperature rating exceeding the temperature of the source (prevents 2631
fuel ignition); or a flame-retardant fuel material (prevents sustained fuel burning 2632
and spread of fire within the equipment); or a non-combustible material (for 2633
example, metal or ceramic); 2634
S6) ensuring high thermal resistance of the thermal energy transfer path from the 2635
initial fuel to more fuel material; or flame isolation of the burning initial fuel from 2636
more fuel material (prevents spread of fire within the equipment); 2637
S7) ensuring that subsequent material is either non-combustible material (for 2638
example, metal or ceramic); or is a flame-retardant material (prevents sustained 2639
fuel burning and spread of fire within the equipment); 2640
S8) use of a fire-containing enclosure (contains the fire within the equipment) or 2641
an oxygen-regulating enclosure (quenches a fire by suffocating it); 2642
S9) use of reliable electrical connections; 2643
– 76 – IEC TR 62368-2:20xx © IEC 20xx
S10) use of non-reversible components and battery connections; 2644
S11) use of mechanical protection (for example, barriers, mesh or the like) with limited 2645
openings; 2646
S12) use of clear operating instructions, instructional safeguards, cautions. 2647
Methods of protection 2648
A) Protection under normal operating conditions and abnormal 2649
operating conditions 2650
Materials and components shall not exceed their auto-ignition temperatures. 2651
B) Protection under single fault conditions 2652
There are two methods of providing protection. Either method may be applied to 2653
different circuits in the same equipment: 2654
– Prevent ignition: equipment is so designed that under abnormal operating 2655
conditions and single fault conditions no part will ignite; 2656
– Control fire spread: selection and application of components, wiring, materials 2657
and constructional measures that reduce the spread of flame and, where 2658
necessary, by the use of a fire enclosure. 2659
Thermoplastic softening values or relative thermal indices (RTI) were not 2660
considered appropriate as they do not relate specifically to ignition properties of 2661
fuel materials. 2662
Any device that operates as a safeguard during normal operation (when left in 2663
the circuit) shall be assessed for reliability. If a device is taken out of the circuit 2664
during the normal operation testing then it is not considered as being a 2665
safeguard. 2666
Abnormal operating conditions that do not result in a single fault are 2667
considered in much the same way as normal operating conditions as the 2668
condition is corrected and normal operation is presumed to be restored. 2669
However, abnormal operating conditions that result in a single fault 2670
condition are to be treated in accordance with 6.4 rather than 6.3. See Figure 29 2671
in this document for a fire clause flow chart. 2672
IEC TR 62368-2:20xx © IEC 20xx – 77 –
Table 8 – Examples of application of various safeguards 2673
Cause Prevention/protection methods Safeguard
Start of fire under normal operating conditions
Limit temperature of combustible material Basic
Start of fire under abnormal operating conditions and single fault conditions
Select prevent ignition or control fire spread method
Supplementary
PS1 circuit Low available power reduces the likelihood of ignition
S1
PS2 or PS3 circuit Reduce the likelihood of ignition
Use of protection devices
S1, S2, S3, S5
S2
Sufficient distance or solid barrier interposed between any combustible material and each potential ignition source
S4 (S6)
PS2 circuit Limit the available power
Sufficient distance or solid barrier interposed between any combustible material and each potential ignition source
Use flame-retardant or non-combustible material
S1, S2
S4, S6
S5
PS3 circuit Use all PS2 options and:
− use fire containing enclosures
− use flame-retardant or similar materials
S8
S7
Internal and external wiring Reliable construction
Limit of wire temperature and use of fire resistant insulation
S9
Fire caused by entry of foreign objects and subsequent bridging of electrical terminals in PS2 circuits and PS3 circuits
Prevent entry of foreign objects S11
Mains supply cords Reliable construction
Limit of wire temperature and use of fire resistant insulation
S9
Fire or explosion due to abnormal operating conditions of batteries
Limit charge/discharge currents
Limit short-circuit currents
Prevent use of wrong polarity
S1
S2
S10
2674
– 78 – IEC TR 62368-2:20xx © IEC 20xx
2675
Figure 29 – Fire clause flow chart 2676
6.3.1 Requirements 2677
Source: IEC 60950-1, ISO 871 2678
Rationale: Spontaneous-ignition temperature as measured by ISO 871 for materials 2679
was chosen as the ignition point of fuels. The materials specific tables were 2680
deleted in favour of a simple requirement or completely referring to the ASTM 2681
standard for material auto-ignition temperatures. 2682
IEC TR 62368-2:20xx © IEC 20xx – 79 –
The 300 °C value for thermoplastics is approximately 10 % less than the 2683
lowest ignition temperature of materials commonly used in ICT and CE 2684
equipment. This value has also been used in IEC 60950-1. The designer is 2685
permitted to use material data sheets for materials that exceed this value but 2686
the auto-ignition specification has to be reduced by 10 % to accommodate 2687
measurement variations and uncertainty. 2688
In the context of fire, abnormal operating conditions (blocked vents, 2689
connector overload, etc.) are to be considered just as a normal operating 2690
condition unless the abnormal operating condition results in a single 2691
fault condition. 2692
As part of the compliance check, first the datasheets of the materials used 2693
have to be checked to be able to evaluate the results of the temperature rise 2694
measurements. 2695
The glow-wire test is a fire test method of applying a heat source to the 2696
sample. The test provides a way to compare a material’s tendency to resist 2697
ignition, self-extinguish flames (if ignition occurs), and to not propagate fire. 2698
Manufacturers have been using this test method to determine a plastic’s 2699
flame resistance characteristics to IEC 60950-1 for many years without field 2700
issues identified with the suitability of the test. Hence, the glow-wire test 2701
should continue to be an option to the HB rating for plastics outside of the 2702
fire enclosure or mechanical enclosures and for electrical enclosures 2703
housing PS1 circuits. This precedence has been set in IEC 60950-1 and 2704
should be included in IEC 62368-1. 2705
Table 9 – Basic safeguards against fire under normal operating conditions 2706
and abnormal operating conditions 2707
Normal operating conditions and abnormal operating conditions
The objective of this subclause is to define requirements to reduce the likelihood of ignition under normal operating conditions and abnormal operating conditions.
PS1
PS2
PS3
6.3.1
Ignition is not allowed
Tmax
90 % auto ignition temperature according to ISO 871; or
Tmax
300 ºC
Combustible materials for components and other parts outside fire enclosures (including electrical enclosures, mechanical enclosures and decorative parts), shall have a material flammability class of at least: – HB75 if the thinnest significant thickness of this material is < 3 mm, or
– HB40 if the thinnest significant thickness of this mater ial is 3 mm, or – HBF.
NOTE Where an enclosure also serves as a fire enclosure, the requirements for fire enclosures apply.
These requirements do not apply to:
– parts with a size of less than 1 750 mm3; – supplies, consumable materials, media and recording materials; – parts that are required to have particular properties in order to perform
intended functions, such as synthetic rubber rollers and ink tubes; – gears, cams, belts, bearings and other parts that would contribute
negligible fuel to a fire, including labels, mounting feet, key caps, knobs and the like.
2708
– 80 – IEC TR 62368-2:20xx © IEC 20xx
6.3.2 Compliance criteria 2709
Rationale: Steady state for temperature measurements in excess of 300 °C requires 2710
more tolerance on the rise value due to the difficulty in achieving a stable 2711
reading. However, the value in B.1.6 was considered adequate, as these 2712
values typically do not continue to rise but rather cycle. The value of 3 °C 2713
over a 15 min period was also considered for measurement of these very 2714
high temperatures but was not used in favour of harmonization with other 2715
clauses. 2716
The use of temperature-limiting safeguards under normal operating 2717
conditions and abnormal operating conditions is considered acceptable 2718
only where the safeguard or device has been deemed a reliable 2719
temperature control device. 2720
6.4 Safeguards against fire under single fault conditions 2721
6.4.1 General 2722
Source: IEC 60065, IEC 60950-1 2723
Rationale: The consideration in the prior clause is to limit the likelihood of 2724
ignition of fuels under normal operating conditions and abnormal 2725
operating conditions with a basic safeguard. All fuels should be used 2726
below their ignition temperatures and separated from arcing parts. 2727
The requirements in this clause are to limit the ignition or the spread of fire 2728
under single fault conditions by employing supplementary safeguards, 2729
see Table 10 in this document. There are two approaches that can be used 2730
either jointly or independently: 2731
– method 1 minimizes the possibility of ignition through the use of 2732
safeguards applied at each potential point of ignition; 2733
– method 2 assumes the ignition of limited fuels within the product and 2734
therefore requires safeguards that limit the spread of fire beyond the 2735
initial ignition point or for higher energy, beyond the equipment 2736
enclosure. 2737
Table 10 – Supplementary safeguards against fire under single fault conditions 2738
Single fault conditions
There are two methods of providing protection. Either method may be applied to different circuits of the same equipment (6.4.1)
Method 1
Reduce the likelihood of
ignition
Equipment is so designed that under single fault conditions no part shall ignite.
This method can be used for any circuit in which the available steady state power to the circuit does not exceed 4 000 W.
The appropriate requirements and tests are detailed in 6.4.2 and 6.4.3.
Method 2
Control fire spread
Selection and application of supplementary safeguards for components, wiring, materials and constructional measures that reduce the spread of fire and, where necessary, by the use of a second supplementary safeguard such as a fire enclosure.
This method can be used for any type of equipment.
The appropriate requirements are detailed in 6.4.4, 6.4.5 and 6.4.6.
2739
The document’s user or product designer will select a method to apply to each 2740
circuit, (either prevent ignition method or control the spread of fire method). The 2741
selection of a method can be done for a complete product, a part of a product or 2742
a circuit. 2743
IEC TR 62368-2:20xx © IEC 20xx – 81 –
The power level of 4 000 W was chosen to ensure that products which are 2744
connected to low power mains (less than 240 V × 16 A), common in the office 2745
place or the home, could use the ignition protection methods , and to provide a 2746
reasonable and practical separation of product types. It is recognized that this is 2747
not representative of fault currents available but is a convenient and 2748
representative separation based on equipment connected to normal office and 2749
home mains circuits where experience with potential ignition sources 2750
safeguards is more common. 2751
Limit values below 4 000 W create a problem for the AC mains of almost all 2752
equipment used in the home or office, which is not the intent. It would be much 2753
more practical to use an energy source power of 4 000 W based on mains 2754
voltage and overcurrent device rating which would effectively permit all 2755
pluggable type A equipment to use either method, and restrict very high-power 2756
energy sources to use only the method to control fire spread. 2757
The 4 000 W value can be tested for individual circuits; however, a note has 2758
been added to clarify which types of products are considered below without test. 2759
Calculation of the product of the mains nominal voltage and mains overcurrent 2760
device rating is not a normal engineering convention but rather the product of 2761
two numbers should not exceed 4 000 (see text below). 2762
NOTE All pluggable equipment type A are considered to be below the steady state value of 2763 4 000 W. Pluggable equipment type B and permanently connected equipment are considered 2764 to be below this steady state value if the product of nominal mains voltage and the current rating 2765 of the installation overcurrent protective device is less than 4 000. 2766
Prevent ignition method: Prescribes safeguard requirements that would prevent 2767
ignition and is predominantly based on fault testing and component selection and 2768
designs that reduce the likelihood of sustained flaming. Where a PIS is identified, 2769
additional safeguards are required to use barriers and the fire cone ‘keep out’ 2770
areas for non-flame rated materials (see Table 11 and Figure 30 in this 2771
document). 2772
The prevent ignition method has been used in IEC 60065 where the predominant 2773
product connection is to low power (< 16 A) mains circuits. The use of this 2774
method was not considered adequate enough for larger mains circuits because 2775
the size of the fire cone does not adequately address large igni tion sources 2776
common in higher power circuits. 2777
This approach limits the use of prevent ignition methods to those products where 2778
the ignition sources is characterized by the fire cones and single fault 2779
conditions described in 6.4.7. 2780
– 82 – IEC TR 62368-2:20xx © IEC 20xx
Table 11 – Method 1: Reduce the likelihood of ignition 2781
Method 1: Reduce the likelihood of ignition under single fault conditions
PS1
(≤ 15 W after 3) 6.4.2
No supplementary safeguards are needed for protection against PS1.
A PS1 is not considered to contain enough energy to result in materials reaching ignition temperatures.
PS2
( PS1 and
≤ 100 W after 5 s)
and
PS3
( PS2 and
≤ 4 000 W)
6.4.3
The objective of this subclause is to define the supplementary safeguards needed to reduce the likelihood of ignition under single fault conditions in PS2 circuits and PS3 circuits where the available power does not exceed 4 000 W. All identified supplementary safeguards need to be considered based on the equipment configuration.
Sustained flaming 10 s is not allowed and no surrounding parts shall have ignited.
Separation from arcing PIS and resistive PIS according to 6.4.7
– Distances have to comply with Figures 37, 38, 39a and 39b; or
– In case the distance between a PIS and combustible material is less than specified in Figures 37, 38, 39a and 39b;
• Mass of combustible material < 4 g, or
• Shielded from the PIS by a fire barrier, or
• Flammability requirements:
o V-1 class material; VTM-1 class material or HF-1 class material, or needle flame in Clause S.2, or
o Relevant component IEC document
Using protective devices that comply with G.3.1, G.3.2, G.3.3 and G.3.4 or the relevant IEC component documents for such devices;
Using components that comply with G.5.3, G.5.4 or the relevant IEC component document;
Components associated with the mains shall comply with:
the relevant IEC component documents; and
the requirements of other clauses of IEC 62368-1
2782
2783
IEC TR 62368-2:2019 © IEC 2019 – 83 –
Figure 30 – Prevent ignition flow chart
– 84 – IEC TR 62368-2:2019 © IEC 2019
Control fire spread method: Prescribes safeguards that are related to the spread of fire from acknowledged ignition sources. This assumes very little performance testing (no single fault conditions) and the safeguards are designed to minimize the spread of flame both within the product and beyond the fire enclosure. The safeguards described are based on power level, with higher power sources requiring more substantial safeguards (see Figure 31, Figure 32 and Table 12 in this document).
This power (4 000 W) separation is also used in the control of fire spread method to delineate safeguard criteria for fire enclosure materials (V-1 versus 5 V). IEC 60950-1 has historically used weight to define fire enclosure criteria and it was felt that the use of available power was more appropriate and genera lly reflective of current practice.
IEC TR 62368-2:20xx © IEC 20xx – 85 –
Figure 31 – Control fire spread summary
– 86 – IEC TR 62368-2:20xx © IEC 20xx
Figure 32 – Control fire spread PS2
IEC TR 62368-2:20xx © IEC 20xx – 87 –
Figure 33 – Control fire spread PS3
– 88 – IEC TR 62368-2:20xx © IEC 20xx
6.4.2 Reduction of the likelihood of ignition under single fault conditions in PS1 1
circuits 2
Rationale: Low available power prevents ignition – 15 W is recognized as the lower limit 3
of ignition for electronic products. The limiting of power is not considered the 4
basic safeguard but rather the characteristic of the circuit being considered. 5
This determination is made as part of the classification of power sources. 6
6.4.3 Reduction of the likelihood of ignition under single fault conditions in PS2 7
circuits and PS3 circuits 8
Rationale: To identify all potential ignition sources, all circuits and components within 9
the PS2 and PS3 circuits should be evaluated for their propensity to ignite. 10
The ignition source derived from either PS2 or a PS3 circuit is considered 11
equivalent. The resulting flame size and burn time is identical in all PS2 and 12
PS3 circuits unless the power available is very large (for example, greater 13
than 4 000 W). 14
For very large sources (greater than 4 000 W) the safeguards described for 15
addressing potential ignition sources are not recognized as being 16
adequate and the control fire spread method is used (see 6.4.1 for 4 000 W 17
rationale). 18
6.4.3.1 Requirements 19
Source: IEC 60065, IEC 60695-2-13, IEC 60950-1 20
Rationale: Flaming of a fuel under single fault conditions is only permitted if very 21
small and quickly extinguished (for example, a fuse resistor). A length of time 22
is necessary during single fault conditions to permit the characteristic 23
“spark” or short term “combustion flash” common when performing single 24
fault conditions in electronic circuits. The value of 10 s is used, which has 25
been used by IEC 60065 for many years. The energy of this short-term event 26
is considered too low to ignite other parts. This value corresponds with 27
IEC 60695-2-13 and has been used in practice by IEC TC 89 for glow wire 28
ignition times. The time period is necessary to accommodate the expected 29
flash/short duration flames that often result as a consequence of faults. The 30
value of 10 s is considered to be the minimum time needed for ignition of 31
commonly used thermoplastics by direct flame impingement. It is recognized 32
that times as short as 2 s are used by other documents. 33
Protection is achieved by identifying each PIS and then limiting the 34
temperature of parts below auto-ignition temperatures during single fault 35
conditions, minimizing the amount of flammable material near a PIS, 36
separating combustible materials from PIS by barriers, and by using 37
reliable protection devices to limit temperature of combustible parts. 38
Single fault testing, while not statistically significant, has been common 39
practice in both IEC 60065 and IEC 60950-1. 40
Temperatures limiting ignition are considered to be the material self-ignition 41
points or flash temperatures for flammable liquids and vapours (this value 42
should include a 10 % margin to take into account ambient, laboratory and 43
equipment operating conditions). The spread to surrounding parts during and 44
after the fault is also checked. 45
Providing sufficient distance or solid barrier between any combustible 46
material and a potential ignition source should minimize the potential for 47
the spread of fire beyond the fuels directly in contact with the potential 48
ignition source. The fire cone distances developed for IEC 60065 are used 49
and considered adequate. Single fault testing is not completely 50
representative; therefore, some material and construction requirements are 51
necessary (fuel control area or keep out area). 52
IEC TR 62368-2:20xx © IEC 20xx – 89 –
Use of reliable protection devices – This includes reliability requirements for 53
the devices that are used to prevent ignition. This permits only the use of 54
devices that have reliability requirements included in Annex G. 55
Components that comply with their relevant IEC component standards are 56
also considered to comply given these standards also have ignition 57
protection requirements. The components included are those that are almost 58
always part of a potential ignition source as they are mains connected. 59
Opening of a conductor: In general, opening of a conductor is not permitted 60
during single fault conditions as it is not considered reliable protection 61
device for limiting ignition. However for resistive PIS, it may be suitable 62
provided the printed wiring board is adequately flame retardant and the 63
opening does not create an arcing PIS. The V-1 printed circuit board is 64
considered adequate to quench low voltage events and will not propagate 65
the flame. It is not sufficient when the opening creates an arcing PIS 66
(< 50 V). 67
As a consequence of the test, any peeling of conductor during these tests 68
shall not result in or create other hazards associated with the movement of 69
conductive traces during or after the test provided they do so predictably. 70
During a single fault the peeling could bridge a basic safeguard but should 71
not result in the failure of a supplementary safeguard or reinforced 72
safeguard. 73
6.4.3.2 Test method 74
Source: IEC 60065, IEC 60127 75
Rationale: The available power and the classification criteria for resistive and arcing 76
potential ignition sources should be used to determine which components 77
to fault. 78
If the applied single fault condition causes another device or subsequent 79
fault, then the consequential failure is proven reliable by repeating the single 80
fault condition two more times (total of three times). This is a method used 81
historically in IEC 60065. 82
Steady state determination for single fault conditions is related to 83
temperature rise and the requirement is the same as the steady state 84
requirements of Annex B, even though material ignition temperatures 85
( 300 °C) are much higher than required temperatures of other clauses (~25 86
°C – 100 °C). Shorter time periods (such as 15 min) were considered but 87
dropped in favour of harmonization of other parts. The term steady state 88
should take into account temperatures experienced by a material throughout 89
the test. 90
Maximum attained temperature for surrounding material of heat source 91
should be considered if further temperature increase is observed after 92
interruption of the current. 93
Limit by fusing: The reliability of protection devices is ensured where they 94
act to limit temperatures and component failures. The criteria used by the 95
component document applying to each are considered adequate provided 96
the parts are used as intended. The requirements included assume an 97
IEC 60127 type fuse as the most common device. 98
The test methodology is established to ensure that available energy through 99
the fuse link based on its current hold and interrupt conditions the breaking 100
time characteristics of specified in IEC 60127. IEC 60127 permits 2,1 times 101
the breaking current rating for 1 min. 102
In order to determine the impact of a fuse on the results of a single fault 103
condition, if a fuse operates, it is replaced with a short circuit and the test 104
repeated. There are three possible conditions when comparing the actual 105
fault current through the fuse to the pre-arcing current and time data sheets 106
provided by the fuse manufacturer. 107
– 90 – IEC TR 62368-2:20xx © IEC 20xx
– Where the measured current is always below the fuse manufac turer's 108
pre-arcing characteristics (measured current is less than 2,1 times the 109
fuse rating), the fuse cannot be relied upon as a safeguard and the test 110
is continued with the fuse short circuited until steady state where the 111
maximum temperature is measured. 112
– Where the measured current quickly exceeds the fuse pre-arcing 113
characteristics (measured current is well above 2,1 times the rating 114
current of the fuse) then the test is repeated with the open circuit in place 115
of the fuse (assumes fuse will open quickly and be an open circuit) and 116
then the maximum temperature recorded. 117
– Where the measured current does not initially exceed the fuse pre-arcing 118
characteristics, but does at some time after introduction of the fault. The 119
test is repeated with the short circuit in place and the temperature 120
measured at the time where measured current exceeds the fuse pre-121
arcing characteristics. It is assumed the measured current through the 122
short circuit can be graphed and compared with the fuse manufacturer’s 123
pre-arcing curves provided on the fuse datasheet to determine the test 124
time. 125
6.4.4 Control of fire spread in PS1 circuits 126
Rationale: Low available power reduces the likelihood for ignition – 15 W is recognized 127
as the lower limit of ignition for electronic circuits. This lower power limit is 128
considered as a circuit characteristic of the circuit, not a basic safeguard. 129
IEC TR 62368-2:20xx © IEC 20xx – 91 –
Table 12 – Method 2: Control fire spread 130
Method 2: Control fire spread
PS1
(≤ 15 W) 6.4.4
No supplementary safeguards are needed for protection against PS1.
A PS1 is not considered to contain enough energy to result in materials reaching ignition temperatures.
PS2
(≤ 100 W after 5 s) 6.4.5
The objective of this subclause is to describe the supplementary safeguards needed to reduce the likelihood of fire spread from a PIS in PS2 circuits to nearby combustible materials.
The limiting of power available to PS2 circuits is the basic safeguard used to minimize the available energy of an ignition source.
A supplementary safeguard is required to control the spread of fire from any possible PIS to other parts of the equipment
For conductors and devices with a PIS the following apply:
– Printed boards shall be at least V-1 class material
– Wire insulation shall comply with IEC 60332 series or IEC 60695-11-21
Battery cells and battery packs shall comply with Annex M.
All other components:
– Mounted on V-1 class material, or
– Materials V-2 class material, VTM-2 class material, or HF-2 class material, or
– Mass of combustible material < 4 g, provided that when the part is ignited the fire does not spread to another part, or
– Separated from PIS according to 6.4.7,
Distances have to comply with Figures 37; 38; 39 and 40, or
In case distances do not comply with Figures 37; 38; 39 and 40
– Mass of combustible material < 4 g, or
– Shielded from the PIS by a fire barrier, or
– Flammability requirements: V-1 class material; VTM-1 class material or HF-1 class material, or comply with the needle flame test of IEC 60695-11-5 as described in Clause S.2; or
– Comply with IEC component document flammability requirements, or comply with G.5.3 and G.5.4
– Insulation materials used in transformers, bobbins, V-1 class material
– In a sealed enclosure ≤ 0,06 m3 made of non-combustible material and having no ventilation openings
The following shall be separated from a PIS according to 6.4.7 or shall not ignite due to fault conditional testing
– Supplies, consumables, media and recording materials
– Parts which are required to have particular properties in order to perform intended functions, such as synthetic rubber rollers and ink tubes
131
– 92 – IEC TR 62368-2:20xx © IEC 20xx
Method 2: Control fire spread
PS3
( PS2)
The objective of this subclause is to describe the supplementary safeguards needed to reduce the likelihood of fire spread from a PIS in PS3 circuits to nearby combustible materials.
6.4.6
Fire spread in PS3 circuit shall be controlled by;
– the use of a fire enclosure as specified in 6.4.8. and
– applying all requirements for PS2 circuits as specified in 6.4.5
Devices subject to arcing or changing contact resistance (for example, pluggable connectors) shall comply with one of the following:
– Materials V-1 class material; or
– Comply with IEC component document flammability requirements; or
– Mounted on V-1 class material and volume ≤ 1 750 mm3
Exemptions:
– Wire and tubing insulation complying with IEC 60332 series or IEC 60695-11-21
– Components, including connectors complying with 6.4.8.2.2 and that fill an opening in a fire enclosure
– Plugs and connectors forming a part of a power supply cord or complying with 6.5, G.4.1 and G.7
– Transformers complying with G.5.3
– Motors complying with G.5.4
6.4.6
For PS2 or a PS3 circuit
within a fire en-closure
See all requirements for PS2 (6.4.5)
6.4.6
For a PS1 circuit
within a fire
enclosure
Combustible materials:
Needle flame test in Clause S.1 or V-2 class material or VTM-2 class material or HF-2 class material
Exemptions:
– Parts with a size less than 1 750 mm3
– Supplies, consumable materials, media and recording materials
– Parts that are required to have particular properties in order to perform intended functions such as synthetic rubber rollers and ink tubes
– Gears, cams, belts, bearings and other small parts that would contribute negligible fuel to a fire, including, labels, mounting fee t, key caps, knobs and the like
– Tubing for air or any fluid systems, containers for powders or liquids and foamed plastic parts, provided that they are of HB75 class material if the thinnest significant thickness of the material is < 3 mm, or HB40 class material if the thinnest significant thickness of the material is ≥ 3 mm, or HBF class foamed material
132
6.4.5 Control of fire spread in PS2 circuits 133
Source: IEC 60950-1 134
Rationale: In principle, limiting the available power to the circuit (100 W) in PS2 circuits 135
and control of adjacent fuel materials will reduce the spread of fire, assuming 136
that ignition of components can occur. This power level limit minimizes the 137
size of the ignition source and its impingement on adjacent fuels that are in 138
the PS2 circuits. 139
IEC TR 62368-2:20xx © IEC 20xx – 93 –
The purpose of this clause is to establish control of fuels in or near circuits 140
that have the possibility of ignition. As no fault testing is done for PS2 141
circuits, it is assumed that a fire ignition can occur anywhere within the 142
circuits. These safeguards are to be based on component material 143
flammability characteristics that keep the initial ignition source from 144
spreading to surrounding internal materials. 145
This clause assumes only construction safeguards in a manner consistent 146
with the historically effective requirements of IEC 60950-1. 147
Only fuels that would contribute significant fuel to a fire are considered. 148
Acceptance of limited power sources in Annex Q.1 to be classified as PS2 149
has been added to allow continued use of the long existing practice in 150
IEC 60950-1. 151
6.4.5.2 Requirements 152
Source: IEC 60065, IEC 60950-1 153
Rationale: Requirements around conductors and devices subject to arcing parts and 154
resistive heating have the most onerous requirements for sustained ignition 155
and protection of wiring and wiring boards. 156
– Mounting on a flame-retardant material to limit fire growth. V-1 mounting 157
materials are considered important as they limit fuel to reduce sustained 158
flaming and also would not contribute to large fires or pool fire. The 159
spread of fire from ignited small parts can be managed by the larger 160
printed wiring board. This provision is made to allow the use of a 161
longstanding IEC 60950-1 provision for small devices mounted directly 162
on boards. The value 1 750 mm3 has been used in practice in IEC 60065. 163
– Use of flame retardant wiring is identical to the internal and external 164
wiring requirements of Clause 6. 165
– Accepting existing component requirements for devices that have their 166
own requirements (IEC or annexes of this document) are considered 167
adequate. 168
– Sufficient distance or solid flame-resistant barrier between any 169
combustible material and potential ignition sources. (KEEP OUT 170
ZONES or RESTRICTED AREA). 171
All other components (those that are not directly associated with arcing or 172
resistive heating components) have a reduced set of safeguards when 173
compared to those parts more likely to ignite. Those safeguards include any 174
of the following: 175
– For parts not directly subject to arcing or resistive heating, V-2 ratings 176
are considered adequate. This is also a historical requirement of 177
IEC 60950-1 for parts used in limited power circuits. Sustained ignition 178
of V-2 class materials is similar to that of V-1 class materials in the 179
small-scale testing. The use of VTM-2 or HF-2 class materials were also 180
considered adequate. 181
– Limiting the combustible fuel mass within the area around PS2 circuit 182
devices. The limit of 4 g is brought from the small parts definition used 183
with PIS requirements of this clause and which were originally used in 184
IEC 60065. 185
– As an alternative, components and circuits can be separated from fuels 186
per the requirements of the fire cone described for isolation of fuels from 187
potential ignition sources. 188
– Enclosing parts in small oxygen limiting, flame proof, housing. The 189
0,06 m2 value has been in practice in IEC 60950-1 and small enough to 190
mitigate fire growth from a low power source. 191
– 94 – IEC TR 62368-2:20xx © IEC 20xx
The exceptions included are based on common constructions of material that 192
do not routinely have flame retardants or that cannot contain flame 193
retardants due to functional reasons. They are either isolated from any PIS 194
or through single fault condition testing demonstrate that they will simply 195
not ignite in their application. 196
Supplies are quantities of materials such as paper, ink, toner, staples etc., 197
and that are consumed by the equipment and replaced by the user when 198
necessary. 199
6.4.5.3 Compliance criteria 200
Rationale: Material flammability requirements are checked by the testing of Annex S, 201
by compliance with the component document or through review of material 202
data sheets. 203
6.4.6 Control of fire spread in a PS3 circuit 204
Source: IEC 60950-1 205
Rationale: There are two basic requirements to control the spread of fire from PS3 206
circuits: 207
a) use of materials within the fire enclosure that limit fire spread. This 208
includes the same requirements as for components in PS2 circuits and 209
includes a requirement from IEC 60950-1 to address all combustible 210
materials that are found within the fire enclosure; 211
b) use fire-containing enclosures – Product enclosures will have a design 212
capable of preventing the spread of fire from PS3 circuits. The criteria for 213
fire enclosures is based on the available power. 214
Rationale: PS3 sourced circuits may contain a significant amount of energy. During 215
single fault conditions, the available power may overwhelm the safeguard 216
of material control of fuels adjacent to the fault or any consequential ignition 217
source making a fire enclosure necessary as part of the supplementary 218
safeguard. A fire enclosure and the material controls constitute the 219
necessary supplementary safeguard required for a PS3 circuit. 220
Use adequate materials, typically permitting material pre-selection of non-221
combustible or flame-resistant materials for printed wiring and components 222
in or near PS3. Only fuels that would contribute significant fuel to a fire are 223
considered. This implies compliance with all the requirements for PS2 224
circuits and in addition, application of a fire containing enclosure. 225
Material flammability requirements for all materials inside a fire enclosure 226
are included in this clause. This model has been used historically in 227
IEC 60950-1 to control the amount and type of fuel that may become 228
engaged in a significant fire. Because there is no single fault tes ting when 229
applying this method, a significant ignition source may engage other fuels 230
located inside the fire enclosure. PS3 circuits, particularly higher power 231
PS3 circuits can create significant internal fires if adjacent combustible 232
materials, not directly associated with a circuit, become involved in an 233
internal fire. These fires, if unmitigated, can overwhelm the fire enclosures 234
permitted in this document. Control of material flammability of fuels located 235
within the enclosure should be sufficient based on historical experience with 236
IEC 60950-1. 237
The exceptions provided in this clause for small parts, consumable 238
material, etc. that are inside of a fire enclosure, mechanical components 239
that cannot have flame retardant properties are exempt from the materia l 240
flammability requirements. This is the current practice in IEC 60950-1. 241
Components filling openings in a fire enclosure that are also V-1 are 242
considered adequate, as it is impractical to further enclose these devices. 243
These constructions are commonly used today in IT and CE products. 244
Wiring already has requirements in a separate part of this clause. 245
IEC TR 62368-2:20xx © IEC 20xx – 95 –
Motors and transformers have their own flammability spread requirements 246
and as such do not need a separate enclosure (see G.5.3 and G.5.4). 247
6.4.7 Separation of combustible materials from a PIS 248
Rationale: Where potential ignition sources are identified through classification and 249
single fault conditions, separation from the ignition source by distance 250
(material controls) or separation by barriers are used to limit the spread of 251
fire from the ignition source and are necessary to ensure the ignition is not 252
sustained. 253
6.4.7.2 Separation by distance 254
Source: IEC 60065 255
Rationale: The safeguard for materials within the fire cone includes material size 256
control (and including prohibition on co-location of flammable parts). 257
Otherwise the parts close to the PIS shall be material flammability class 258
V-1, which limits sustained ignition and spread. 259
Small parts (less than 4 g) are considered too small to significantly 260
propagate a fire. This value is also used for components used in PS2 and 261
PS3 circuits. It has been used in IEC 60065 with good experience. 262
Where these distances are not maintained, a needle flame test option is 263
included with 60 s needle flame application based on previous requirements 264
in IEC 60065. This alternative to these distance requirements (the needle 265
flame test) can be performed on the barrier to ensure that any additional 266
holes resulting from the test flame are still compliant (openings that will limit 267
the spread of fire through the barrier). 268
Redundant connections: An arcing PIS cannot exist where there are 269
redundant or reliable connections as these connections are considered not 270
to break or separate (thereby resulting in an arc). 271
Redundant connections are any kind of two or more connections in parallel, 272
where in the event of the failure of one connection, the remaining 273
connections are still capable of handling the full power. Arcing is not 274
considered to exist where the connections are redundant or otherwise 275
deemed not likely to change contact resistance over time or through use. 276
Some examples are given, but proof of reliable connections is left to the 277
manufacturer and there is no specific criteria that can be given: 278
– Tubular rivets or eyelets that are addit ionally soldered – this assumes 279
that the riveting maintains adequate contact resistance and the soldering 280
is done to create a separate conductive path. 281
– Flexible terminals, such as flexible wiring or crimped device leads that 282
remove mechanical stress (due to heating or use) from the solder joint 283
between the lead and the printed wiring trace. 284
– Machine or tool made crimp or wire wrap connections – well-formed 285
mechanical crimps or wraps are not considered to loosen. 286
– Printed boards soldered by auto-soldering machines and the auto-287
soldering machines have two solder baths, but they are not considered 288
reliable without further evaluation. This means most printed boards have 289
been subjected to a resoldering process. But there was no good 290
connection of the lead of the component(s) and the trace of the printed 291
board in some cases. In such cases, resoldering done by a worker by 292
hand may be accepted. 293
– 96 – IEC TR 62368-2:20xx © IEC 20xx
Combustible materials, other than V-1 printed wiring boards are to be 294
separated from each PIS by a distance based on the size of resulting ignition 295
of the PIS. The flame cone dimensions 50 mm and 13 mm dimensions were 296
derived from IEC 60065, where they have been used for several years with 297
good experience. The area inside the cone is considered the area in which 298
an open flame can exist and where material controls should be applied. 299
Resistive potential ignition sources are never a point object as presented 300
in Figure 37 of IEC 62368-1. They are more generally three-dimensional 301
components, however only one dimension and two-dimension drawings are 302
provided. The three-dimensional drawing is difficult to understand and 303
difficult to make accurate. 304
Figure 34 in this document shows how to cope with potential ignition 305
sources that are 3D volumes. This drawing does not include the bottom part 306
of the fire cone. The same approach should be used for the bottom side of 307
the part. 308
Figure 34 – Fire cone application to a large component
The fire cone is placed at each corner. The locus of the outside lines 309
connecting each fire cone at both the top and the base defines the restricted 310
volume. 311
Figure 37 Minimum separation requirements from a PIS 312
This drawing of a flame cone and its dimensions represents the one-313
dimension point ignition source drawn in two dimensions. The three-314
dimension envelope (inverted ice cream cone) of a flame from a potential 315
ignition source. This PIS is represented as a point source in the drawing 316
for clarity, however these PISs are more often three-dimensional 317
components that include conductors and the device packaging. 318
Figure 38 Extended separation requirements from a PIS 319
A two-dimensional representation of an ignition source intended to provide 320
more clarity. 321
IEC TR 62368-2:20xx © IEC 20xx – 97 –
6.4.7.3 Separation by a fire barrier 322
Source: IEC 60065 323
Rationale: The use of flame retardant printed wiring is considered necessary as the fuel 324
and the electrical energy source are always in direct contact. V-1 has 325
historically been adequate for this purpose. 326
Printed wiring boards generally directly support arcing PIS and as such, 327
cannot be used as a barrier. There is a potential that small openings or holes 328
may develop, thus permitting the arc to cross through the board. 329
A printed board can act as a barrier for an arcing PIS, provided the PIS is 330
not directly mounted on the board acting as a barrier. 331
For resistive PIS, printed wiring boards can be used provided they are of V-332
1 or meet the test of Clause S.1. Any V-1 and less-flammable fuels are 333
required to minimize the possibility flammable material fall ing onto the 334
supporting surface or contact with combustible fuels (resulting in pool fires). 335
If a PIS is located on a board and supplied by a PS2 or PS3 source, there 336
should be no other PS2 or PS3 circuits near the PIS, as this could create 337
faults due to PIS heating that was not otherwise considered. 338
Figure 39 Deflected separation requirements from a PIS when a fire barrier is used 339
This figure demonstrates the change on the fire cone when there is a fire 340
barrier used to separate combustible material from a potential ignition 341
source. This drawing was retained as an example application for only two 342
angles. Recognizing that many examples are possible, only two are kept for 343
practical reasons. History with multiple drawings of barriers in varying angles 344
could be difficult to resolve. The fire team decided to keep only two drawings 345
with an angle barrier as representative. 346
6.4.8 Fire enclosures and fire barriers 347
Rationale: The safeguard function of the fire enclosure and the fire barrier is to 348
impede the spread of fire through the enclosure or barrier (see Table 13 in 349
this document). 350
– 98 – IEC TR 62368-2:20xx © IEC 20xx
Table 13 – Fire barrier and fire enclosure flammability requirements 351
Flammability requirements
Fire barrier
6.4.8.2.1
Fire barrier requirements
Non-combustible material or
Needle flame test Clause S.1 or V-1 class material or VTM-1 class material
6.4.8.4
Separation of a PIS to a fire barrier
– Distance 13 mm to an arcing PIS and
– Distance 5 mm to a resistive PIS
Smaller distances are allowed provided that the part of the fire barrier complies with one of the following:
– Needle flame Clause S.2; After the test no holes bigger than in 6.4.8.3.3 and 6.4.8.3.4 allowed or
– V-0 class material
Fire enclosure
6.4.8.2.2
Fire enclosure materials:
– Non-combustible, or
– For PS3 ≤ 4 000 W, needle flame test Clause S.1 or V-1 class material
– For PS3 > 4 000 W, needle flame test Clause S.5 or 5VB class material
Component materials which fill an opening in a fire enclosure or intended to be mounted in such opening
– Comply with flammability requirements of relevant IEC component document; or
– V-1 class material; or
– needle flame test Clause S.1
6.4.8.4
Separation of a PIS to a fire enclosure
– Distance 13 mm to an arcing PIS and
– Distance 5 mm to a resistive PIS
Smaller distances are allowed, provided that the part of the fire enclosure complies with one of the following:
– Needle flame Clause S.2; After the test no holes bigger than in 6.4.8.3.3 and 6.4.8.3.4 allowed; or
– V-0 class material
352
6.4.8.2.1 Requirements for a fire barrier 353
Source: IEC 60065, IEC 60950-1 354
Rationale: Barriers used to separate PIS from flammable fuels reduce the ability of a 355
resulting PIS flame from impinging on flammable materials. This can be 356
achieved by using flame retardant materials that pass the performance test 357
in Clause S.1 or the pre-selection criteria of a minimum V-1 flame class. 358
The test in Clause S.1 is based on the needle flame test which is currently 359
an option for enclosure testing in both IEC 60950-1 and IEC 60065. 360
6.4.8.2.2 Requirements for a fire enclosure 361
Source: IEC 60065, IEC 60950-1 362
Rationale: The material flammability class V-1 was chosen as the minimum value 363
based on its historical adequacy, and recent testing done during the 364
development of the requirements for externally caused fire. 365
IEC 60950-1 – Prior requirements for 5 V class materials based on product 366
weight lacked sufficient rationale. This has been improved and related to 367
power available to a fault in this document. 368
IEC TR 62368-2:20xx © IEC 20xx – 99 –
IEC 60065 – V-2 class material performance during large scale test 369
reviewed by the fire team indicated inconsistencies in performance over a 370
range of different V-2 materials. The propensity for V-2 class materials to 371
create ‘pool’ fires is also detrimental to fire enclosure performance and 372
therefore not accepted unless it passes the end-product testing. 373
In addition to pre-selection requirements, an end-product test (material test) 374
is also included by reference to Clauses S.1 (for < 4 000 W) and S.5 (for 375
4 000 W). This test is based on the needle flame test which is currently an 376
option for enclosure testing in both IEC 60950-1 and IEC 60065. 377
This power (4 000 W) separation is also used in the control of fire spread 378
method to delineate safeguard criteria for fire enclosure materials (V-1 379
versus 5 V). IEC 60950-1 has historically used weight to define fire 380
enclosure criteria and it was felt the use of available power was more 381
appropriate and generally reflective of current practice. 382
Both 5 VA and 5 VB class materials are considered acceptable for 383
equipment with power above 4 000 W. This is consistent with current 384
practice in IEC 60950-1. 385
6.4.8.2.3 Compliance criteria 386
Rationale: In each case there is a performance test, and construction (pre-selection) 387
criteria given. For material flammability, compliance of the material is 388
checked at the minimum thickness used as a fire enclosure or fire barrier. 389
6.4.8.3 Constructional requirements for a fire enclosure and a fire barrier 390
Rationale: Opening requirements for barriers and fire enclosure should limit the spread 391
of flame through any existing opening. A fire enclosure limits the spread of 392
fire beyond the equipment and is permitted to have holes (within established 393
limits). 394
6.4.8.3.1 Fire enclosure and fire barrier openings 395
Rationale: These requirements are intended to reduce the spread of an internal fuel 396
ignition through a fire enclosure or barrier. 397
Openings are restricted based on the location of each potential ignition 398
source using the flame cones or in the case of control fire spread, above all 399
PS3 circuits. 400
Figure 40 Determination of top, bottom and side openings 401
In the left figure, when the vertical surface has an inclination (angle) of less 402
than 5° from vertical, then only the side opening requirements of 6.4.8.3.5 403
apply. 404
In the right figure, when the vertical surface has an inclination (angle) of 405
more than 5° from the vertical, then the openings are subject to the 406
requirements for top openings of 6.4.8.3.3 or bottom openings of 6.4.8.3.4. 407
6.4.8.3.2 Fire barrier dimensions 408
Rationale: Edges can be more easily ignited than a solid surface. Barrier dimensions 409
shall also be sufficient to prevent ignition of the barrier edges. 410
Barriers made of combustible materials shall have edges that extend 411
beyond the limits of the fire cone associated with each potential ignition 412
source. If the barrier edge does not extend beyond the cone, then it is 413
assumed the edges may ignite. 414
– 100 – IEC TR 62368-2:20xx © IEC 20xx
6.4.8.3.3 Top openings and top opening properties 415
Source: IEC 60065 416
Rationale: Top opening drawings are restricted in the areas of likely flame propagation 417
to the side and above an ignition source. 418
Top openings are also considered to cover what has historically been called 419
side opening where the opening is above the horizontal plane containing the 420
ignition source. 421
The top/side openings that are subject to controls are only those within the 422
fire cone drawing (Figure 37) plus a tolerance of 2 mm, as shown in Figure 423
41. The application of the fire cone dimensions has been used in IEC 60065 424
and proven historically adequate. 425
Control of openings above the flame cone is also not necessary given that 426
the heat transfer (convection) will follow the gases moving through those 427
openings and is not sufficient to ignite adjacent materials. If the openings 428
are directly blocked, the convection path will be blocked which would restrict 429
any heat transfer to an object blocking the opening. 430
Openings to the side of the fire cone dimensions were reviewed and 431
ultimately not considered necessary as the radiant heat propagation through 432
openings to the side of the ignition is very small. This radiant heat is not 433
considered sufficient to ignite adjacent materials given the anticipated flame 434
size and duration in AV and ICT products. 435
In this aspect, the virtual flame cone deflection as per Figure 39 need not be 436
considered since the actual needle flame application will cover that. 437
The test method option proposed provides a test option for direct application 438
of a needle flame. The test (S.2) referred to in this clause is intended to 439
provide a test option where holes do not comply with the prescriptive 440
measures. S.2 is originally intended to test the material flammability, but in 441
this subclause the purpose of the test is to see the potential ignition of outer 442
material covering the openings, so application of the needle flame is 443
considered for that aspect rather than the burning property of the enclosure 444
itself. 445
Cheesecloth is used as a target material for the evaluation of flame spread 446
due to its flexible nature (ease of use) and its quick propensity to ignite. 447
The flame cone envelope is provided as a single point source. The applicable 448
shape and any affecting airflow are taken into account for determining the 449
whole shape of the PIS, not just a single point. The point is appl ied from the 450
top edge of the component being considered and, in practice, it is rarely a 451
single point. 452
The opening dimensions for the 5 mm and 1 mm dimensions have been 453
determined through test as being restrictive enough to cool combustible 454
gases as they pass through the openings and those mitigate any flame from 455
passing through the opening. Top openings properties are based on tests 456
conducted by the fire team with open flames (alcohol in a Petri dish) that 457
demonstrated these opening dimensions are adequate. 458
6.4.8.3.4 Bottom openings and bottom opening properties 459
Source: IEC 60065, IEC 60950-1 460
Rationale: The location of openings is restricted for barriers inside the flame cone of 461
Figure 37 and for enclosures, inside the cone and directly below to protect 462
against flammable drips from burning thermoplastic as shown in Figure 42. 463
The application of the fire cone dimensions has been used in IEC 60065 and 464
proven historically adequate. 465
IEC TR 62368-2:20xx © IEC 20xx – 101 –
There are several options for opening compliance (see Table 14 in this 466
document). Flaming oils and varnishes are not common in ICT equipment 467
today. The performance test based on the hot flaming oil test, in use for 468
IEC 60950-1, have other opening options and are developed based on lower 469
viscosity materials (when burning). They are more commonly found in ICT 470
(that provide additional options). 471
Clause S.3 (hot flaming oil test) is the base performance option and provides 472
a test option (hot flaming oil test) that historically has been adequate for 473
tests of bottom openings. 474
The values in items band c) come directly from IEC 60950-1 where they have 475
been historically adequate and have demonstrated compliance with the S.3 476
performance testing. These requirements, previously from IEC 60950-1, 477
4.6.2 Bottoms of fire enclosures, have been updated in the third edition of 478
IEC 62368-1. The IEC 60950-1 requirements are more stringent than the 479
new IEC 62368-1 requirements and may still be used as an option without 480
additional tests, which is likely since designs based on the IEC 60950-1 481
requirements have been in use for some time. 482
The work done to validate top openings was also considered adequate for 483
bottom openings under materials of any properties (3 mm and 1 mm slots). 484
This requirement is less onerous than those found in IEC 60950-1 which 485
permitted NO openings unless they complied with the other options. 486
Openings under V-1 class materials (or those that comply with Clause S.1) 487
are controlled in the same manner as done in IEC 60950-1 which was 488
considered adequate however an additional option to use 2 mm slots of 489
unlimited length is also considered adequate. 490
The 6 mm maximum dimension relates to a maximum square opening 491
dimension of 36 mm2 and a round opening of 29 mm2. In IEC 60950-1 the 492
requirement was 40 mm2, which relates to a maximum 7 mm diameter if 493
round or 6,3 mm maximum if not round. 494
The only option where flammable liquids are used is to meet the 495
requirements of the hot flaming oil test (Clause S.3). 496
An option for equipment that is installed in special environments where a 497
non-combustible flooring is used (environmental safeguard) may obviate the 498
need for an equipment bottom safeguard. This is current practice in 499
IEC 60950-1 where equipment is used in “restricted access locations”. 500
Baffle plate constructions were added, as they have been used in 501
IEC 60950-1 and have proven to be an acceptable solution. 502
The intent of IEC 62368-1 is to apply hazard-based safety engineering 503
principles. When the calculated enclosure side opening size (when the 5 -504
degree trajectory is applied) meets the maximum opening size permitted in 505
both subclause 6.4.8.3.4 and Annex P.2, it technically meets the 506
requirements. Additionally, the flaming oil and entry of foreign object 507
experimental testing done by the TC108 HBSDT fire enclosure team 508
demonstrated such safeguards provide suitable protection. Refer to 509
Appendix A below for more details on testing. 510
For side openings, refer to Figures 44 and 45 for illustration examples of 511
using enclosure wall thickness in relationship to the vertical height of an 512
opening to help determine if opening sizes meet requirements of 1) 513
subclause 6.4.8.3.4 (bottom fire enclosure openings); and 2) Annex P.2 514
(side opening requirement limitations to prevent vertical falling objects). 515
– 102 – IEC TR 62368-2:20xx © IEC 20xx
Table 14 – Summary – Fire enclosure and fire barrier material requirements 516
Parameters Fire barrier Fire enclosure
Input < 4 000 W Input 4 000 W
Co
mb
us
tib
le m
ate
ria
l:
Separation from PIS
13 mm or more from arcing PIS
5 mm or more from resistive PIS
Note: exceptions may apply
Dimensions Sufficient to prevent ignition of the edges
Not applicable
Flammability
a) Test S.1; or
b) V-1; or
c) VTM-1
a) Test S.1; or
b) V-1
a) Test S.5; or
b) 5 VA; or
c) 5 VB
No
n-
Co
mb
us
tib
le
ma
teri
al:
Acceptable
Top openings See 6.4.8.3.3
Bottom openings See 6.4.8.3.4
517
6.4.8.3.5 Side opening and side opening properties 518
Source: IEC 60950-1 519
Rationale: For Edition 3, IEC TC 108/WG HBSDT agreed to adopt from 520
IEC 60950-1:2005 (4.6.1, 4.6.2 and Figure 4E) the principles and criteria for 521
determination of suitable side openings using a five (5) degree projection. 522
The primary rationale for adopting these principles was the demonstration of 523
many years of a solid safety record of use for ITE with IEC 60950-1. 524
However, one issue that had to be resolved was that in IEC 60950-1 the 5-525
degree projection of Figure 4E was always made from the outer surface of a 526
combustible internal component or assembly rather than a defined potential 527
ignition source (PIS), typically a metallic circuit inside the component. The 528
PIS principle was not inherent to IEC 60950-1. 529
For example, in a component or assembly, electrical or not, made of 530
combustible material that might ignite within a f ire enclosure, the 5-degree 531
projection was made from the surface of the component or assembly closest 532
to the side enclosure and not from a metallic circuit inside the component or 533
subassembly that could be a potential source of ignition. Therefore, for 534
example, if a printed board was considered the component/subassembly 535
likely to ignite, the 5-degree projection was made from the edge of the 536
printed board and not the current carrying trace, which in IEC 62368-1 is the 537
PIS. In some cases throughout the history of IEC 60950-1, this distance from 538
the metallic trace to component edge could have been up to several 539
centimetres. 540
IEC TR 62368-2:20xx © IEC 20xx – 103 –
However, when IEC TC 108/WG HBSDT considered the common 541
construction of internal components and subassemblies likely to be 542
associated with a PIS, including printed boards, it was determined that it was 543
reasonable to assume that in modern AV/ICT equipment the distance 544
between the PIS and the outer edge of a component or sub-assembly was 545
likely to have negligible impact on the overall fire safety of the product , in 546
particular in the application of the 5 degree principle. Due to general 547
miniaturization of products, material cost optimization, and modern design 548
techniques (including CAD/CAM), printed boards and other electronic 549
components and assemblies associated with a PIS typically do not use 550
unnecessary amounts of combustible materials – modern printed boards 551
more typically now have metallic traces very close to the board edge rather 552
than many millimetres away. 553
As a result IEC TC 108/WG HBSDT considered that the IEC 60950-1 five (5) 554
degree projection principle for side openings remained sound even if 555
projected from the actual PIS rather than the edge of combustible material 556
associated with the PIS. This view also is consistent with the Note to Figure 557
38, Extended separation requirements from a PIS, which states, for a 558
resistive PIS “…measurements are made from the nearest power dissipating 559
element of the component involved. If in pract ice it is not readily possible to 560
define the power dissipating part, then the outer surface of the component 561
is used.” 562
6.4.8.3.6 Integrity of a fire enclosure 563
Source: IEC 60950-1 564
Rationale: The clause ensures that a fire enclosure where required, is assured to 565
remain in place and with the product through either an equipment or 566
behavioural safeguard. This requirement is a service condition safeguard 567
for ordinary persons to ensure that a fire enclosure (if required) is replaced 568
prior to placing the equipment back into use. This safeguard is also required 569
in IEC 60950-1. 570
6.4.8.3.7 Compliance criteria 571
Rationale: In each case, there is a performance test, and construction (pre-selection) 572
criteria given. 573
6.4.8.4 Separation of a PIS from a fire enclosure and a fire barrier 574
Source: IEC 60065, IEC 60950-1 575
Rationale: Non-metallic fire enclosures and fire barriers may not be sufficient to limit 576
the spread of fire where an enclosure is close or in direct contact with a 577
potential ignition source. 578
The 13 mm and 5 mm distances were used in IEC 60065 to prevent an 579
ignition source from transferring sufficient energy to adjacent flame-580
retardant V-1 barriers. These distances are intended to reduce the likelihood 581
of melting or burn-through of the barrier of fire enclosure. 582
Where these distances are not maintained, a needle flame test option is 583
included with 60 s needle flame application based on work in IEC 60065. 584
Openings following the needle flame test were discussed with criteria being: 585
a) no additional opening, 586
b) no enlargement of existing holes, 587
c) compliance with the fire enclosure opening requirements. 588
Due to test repeatability, the criteria of a) are considered most readily 589
reproduced. 590
– 104 – IEC TR 62368-2:20xx © IEC 20xx
The option to use V-0 or 5 V class materials without distance or thickness 591
requirements is based on historical practices in IEC 60065 and IEC 60950-1 592
where no distance requirements were applied. 593
The material thickness requirements where ignition sources are in close 594
proximity to a barrier were not included based on discussions in IEC TC 108 595
and current practice for IEC 60950-1 enclosures. There is fire test data 596
(barrier testing from IEC 60065) indicating that 2 mm thick (or greater) V-0 597
barriers and 5 VA barriers have sufficient flame resistance to minimize a risk 598
of creating openings when used in direct contact with PIS’s. Good HWI or 599
HAI tests are not available internationally to address the distance from 600
ignition sources to fire enclosure and barriers. The fire team has chosen to 601
use the needle flame test as a surrogate test (simi lar to that done for 602
barriers). 603
6.5.1 General requirements 604
Source: IEC 60332-1-2, IEC 60332-2-2 605
Rationale: Wiring flammability proposals have now been included for all wiring (external 606
and internal). 607
Compliance with IEC 60332-1-2 for large wires and IEC 60332-2-2 for small 608
wires has historically proven adequate for mains wiring. These documents 609
include their own material flammability requirements. 610
The requirements of IEC TS 60695-11-21 are also considered adequate 611
given that the flame spread requirements for vertical testing are more 612
onerous than the IEC 60332 series of documents. 613
The compliance criteria are based on application of the above test methods. 614
These are consistent with international wiring standards. National standards 615
may have more onerous requirements. 616
6.5.2 Requirements for interconnection to building wiring 617
Source: IEC 60950-1:2005 618
Rationale: Externally interconnected circuits that are intended for connection to 619
unprotected building wiring equipment can receive sufficient power from the 620
product to cause ignition and spread of fire with the building wall, ceiling, or 621
remotely interconnected equipment. These requirements limit the power 622
available to connectors/circuits intended for interconnection to specific types 623
of wiring where the product is responsible for protection of that wiring. 624
Where a circuit is intended for connection to equipment that is directly 625
adjacent to the equipment, 6.6 prescribes the appropriate safeguards and 626
limits associated for PS2 and PS3 sources. 627
Telecommunication wiring is designed based on the expected power from 628
the network. The requirements of IEC 60950-1 were considered adequate 629
and were included. Wiring in this application should be equivalent to 0,4 mm 630
diameter wiring (26 AWG) and have a default 1,3 A current limit established. 631
This value has been used in IEC 60950-1 for the smaller telecommunication 632
wiring. 633
For some building wiring, the PS2 and PS3 safeguards are not considered 634
adequate in some countries for connection to building wiring where that 635
wiring is run outside of the conduit or other fire protective enclosures. The 636
requirements for this clause come directly from requirements in IEC 60950-637
1, 2.5 for circuits identified as limited power circuits. These requirements 638
have proven to be historically adequate for connection of IT equipment to 639
building wiring in these jurisdictions. 640
The values used and protection requirements included in IEC 60950-1 and 641
included in Annex Q.1 came from the building and fire codes requiring this 642
protection. 643
IEC TR 62368-2:20xx © IEC 20xx – 105 –
These requirements do not apply to connectors/circuits intended for 644
interconnection of peripheral equipment used adjacent to the equipment. 645
This requirement is also important for the use of ICT equipment in 646
environments subject to electrical codes such as National Fire Protection 647
Association NFPA 70, which permit the routing of low power wiring outside 648
of a fire containment device. 649
Annex Q.1 was based on requirements from IEC 60950-1 that are designed 650
to comply with the external circuit power source requirements necessary 651
for compliance with the electrical codes noted above. 652
6.6 Safeguards against fire due to the connection of additional equipment 653
Source: IEC 60950-1 654
Rationale: This subclause addresses potential fire hazards due to the connection of 655
accessories or other additional equipment to unknown power source 656
classifications. Most common low-voltage peripherals are not evaluated for 657
connection to PS3 and therefore power sources should be identified. This is 658
a current requirement of IEC 60950-1. 659
Where the interconnected devices are known (device requirements are 660
matched to the appropriate power source), this requirement for safeguard 661
is not necessary. 662
___________ 663
Injury caused by hazardous substances 664
Rationale: The majority of chemical injuries arise from inhalation or ingestion of 665
chemical agents in the form of vapours, gases, dusts, fumes and mists, or 666
by skin contact with these agents (see Table 15 in this document). The 667
degree of risk of handling a given substance depends on the magnitude and 668
duration of exposure. These injuries may be either acute or chronic. 669
Many resins and polymers are relatively inert and non-toxic under normal 670
conditions of use, but when heated or machined, they may decompose to 671
produce toxic by-products. 672
Toxicity is the capacity of a material to produce injury or harm when the 673
chemical has reached a sufficient concentration at a cer tain site in the body. 674
Potentially hazardous chemicals in the equipment are either: 675
– as received in consumable material or items, such as printer cartridges, 676
toners, paper, cleaning fluids, batteries; 677
– produced under normal operating conditions as a by-product of the 678
normal function of the device (for example, dust from paper handling 679
systems, ozone from printing and photocopying operations, and 680
condensate from air conditioning/de-humidifier systems); or 681
– produced under abnormal operating conditions or as a result of a fault. 682
It is essential to: 683
– determine what substances are present in relative amounts in the 684
equipment or could be generated under normal operating conditions; 685
and 686
– minimize the likelihood of injury to a person due to interaction with these 687
substances. 688
NOTE In addition to their potential toxicity, loss of containment of chemical materials may 689 cause or contribute to failure of safeguards against fire, electric shock, or personal injury due 690 to spillages. 691
– 106 – IEC TR 62368-2:20xx © IEC 20xx
The number of different chemical materials that may be used in the wide 692
variety of equipment covered by this document makes it impossible to 693
identify specific hazards within the body of this document. Information needs 694
to be sought by equipment manufacturers from the material suppliers on the 695
hazards associated with their products and their compliance with any 696
national and/or governmental regulations on the use and disposal of such 697
materials. 698
Energy source: 699
The energy source for most chemically-caused injuries is ultimately the 700
ability of a material to chemically react with human tissue, either directly or 701
indirectly. The exception would be inert materials that can damage tissues 702
by preventing them from functioning by limiting certain chemical reactions 703
necessary for life. An example of this would be types of dust, which do not 704
react with lung tissue, but prevent air from reaching the bloodstream. The 705
reactions may be very energetic and damaging, such as acids on the skin, 706
or can be very slow, such as the gradual build-up of substances in human 707
tissues. 708
Transfer mechanism: 709
Transfer can only occur when chemical energy makes contact with human 710
tissue. The routes for contact with human tissue are through the skin [or any 711
outer membrane such as the eyes or nasal lining] (absorption), through the 712
digestive tract (digestion), or through the lungs (inhalation). The route taken 713
will depend largely on the physical form of the chemical: solid, liquid, or gas. 714
Injury: 715
An injury can be either acute or chronic. Acute injuries are injuries with 716
immediate and serious consequences (for example, a strong acid in the 717
lungs) or the injury can be mild and result in irritation or headac he. Chronic 718
injuries are injuries with long term consequences and can be as serious as 719
acute injuries (for example, consequences of long-term exposure to cleaning 720
solvents). 721
In most cases, the difference is the quantity and lethality of the toxic 722
substance. A large amount of acetone can lead to death; a small amount 723
may simply result in a headache. Many chemical compounds essential to life 724
in small quantities (for example, zinc, potassium and nickel) can be lethal in 725
larger amounts. The human body has different degrees of tolerance for 726
different hazardous chemical substances. Exposure limits may be 727
controlled by government bodies for many chemical substances. Where the 728
use of hazardous chemical substances in equipment cannot be avoided, 729
safeguards shall be provided to reduce the likelihood of exceeding the 730
exposure limits. 731
The different types of chemical hazards are identified in Table 15 and Figure 732
35 in this document demonstrating the hierarchy of hazard management. 733
IEC TR 62368-2:20xx © IEC 20xx – 107 –
Table 15 – Control of chemical hazards 734
Transfer mechanism Prevention / safeguards
Ingestion, inhalation, skin contact, or other exposure to potentially hazardous chemicals
Hierarchy of hazard management:
1. Eliminate the chemical hazard by avoiding the use of the chemical.
2. Reduce the chemical hazard by substitution of a less hazardous chemical.
3. Minimize the exposure potential of the chemical by containment, ventilation and/or reduced quantities of the chemicals.
4. Use of personal protective equipment (PPE).
5. Provide use information and instructional safeguards.
Exposure to excessive concentrations of ozone during equipment operation
Hierarchy of hazard management:
1. Where possible, minimize the use of functions that produce ozone.
2. Provide adequate room ventilation.
3. Provide filtration to remove ozone.
Explosion caused by chemical reaction during use
Hierarchy of hazard management:
1. Eliminate the explosive charge.
2. Reduce the amount of explosive charge to the least amount possible.
3. Minimize hazard by the means of vents.
4. Provide use information and instructional safeguards.
735
736
– 108 – IEC TR 62368-2:20xx © IEC 20xx
737
Figure 35 – Flowchart demonstrating the hierarchy of hazard management 738
739
IEC TR 62368-2:20xx © IEC 20xx – 109 –
Chemical hazards may also degrade or destroy the safeguards provided for 740
other hazards such as fire and electric shock (for example, ozone attack on 741
electrical insulation or corrosion of metallic parts). Chemical spillages or loss 742
of containment can also lead to other hazards such as electric shock or fire 743
depending on the location of any spillage and proximity to electric circuits. 744
The same methods used for chemical health exposure control should also 745
protect against such liquid spillages. 746
Using a hazard-based engineering approach, Figure 36 in this document 747
shows the main types of chemical health hazards and their transfer 748
mechanisms. 749
750
Figure 36 – Model for chemical injury 751
_____________ 752
Mechanically-caused injury 753
8.1 General 754
Rationale: Mechanically caused injury such as cuts, bruises, broken bones, etc., may 755
be due to relative motion between the body and accessible parts of the 756
equipment, or due to parts ejected from the equipment colliding with a body 757
part. 758
8.2 Mechanical energy source classifications 759
Purpose: To differentiate between mechanical energy source levels for normal 760
operating conditions, abnormal operating conditions and single fault 761
conditions applicable to each type of person. 762
8.2.1 General classification 763
Table 35 Classification for various categories of mechanical energy sources 764
Line 3 – Moving fan blades 765
Rationale: The acceptance criteria is based upon any number of factors such as 766
location, but the key factor for judging acceptance is based upon the K factor, 767
the relationship between mass (m) in kg, radius (r) in mm and speed (N) in 768
rpm. This relationship can be used to find the K factor for the fan. Fans with 769
a low K factor and low speeds are considered safer. See Figure 47 and 770
Figure 48 for MS1 values. An MS2 fan requires an instructional safeguard 771
in addition to the limitation on the K factor value and the speed of the fan. 772
The need for the relevant safeguard is based on the classification of fans. 773
The K factor formula is taken from the UL standard for fans, UL 507 (which 774
is based on a University of Waterloo study of fan motors). 775
Single fault condition on a fan includes, but is not limited to, inappropriate 776
input voltage due to the fault of a voltage regulator located upstream . 777
– 110 – IEC TR 62368-2:20xx © IEC 20xx
As plastic fan blades are regarded less hazardous than metal fan blades, 778
different values are used to determine separation between energy class 2 779
and class 3. 780
Typical parameters for fans used in products covered by this document are 781
as follows: 782
fan mass (m) = about 25 g or 0,025 kg; 783
fan diameter (r) = 33 mm; 784
fan speed (N) = 6 000 rpm (maximum speed when the system is hottest, 785
slower if the system is cool). 786
Line 4 – Loosening, exploding or imploding parts 787
Rationale: IEC TC 108 has tried to come up with specific requirements for solid rotating 788
media. However, the result became too complex to be useful at this time. 789
Line 5 – Equipment mass 790
Rationale: The values chosen align with some commonly used values today. However, 791
it is noticed that these are not completely reflecting reality and not a very 792
good hazard-based approach. IEC TC 108 plans to work on these values in 793
the future. 794
Line 6 – Wall/ceiling or other structure mount 795
Rationale: The values chosen align with some commonly used values today. However, 796
it is noticed that these are not completely reflecting reality and not a very 797
good hazard-based approach. IEC TC 108 plans to work on these values in 798
the future. 799
Notes b and c 800
Rationale: The current values are based on experience and basic safety publications. 801
8.2.2 MS1 802
Rationale: Safe to touch. No safeguard necessary. 803
8.2.3 MS2 804
Rationale: Contact with this energy source may be painful, but no injury necessitating 805
professional medical assistance occurs, for example, a small cut, abrasion 806
or bruise that does not normally require professional medical attention. A 807
safeguard is required to protect an ordinary person. 808
8.2.4 MS3 809
Rationale: An injury may occur that is harmful, requiring professional medical 810
assistance. For example, a cut requiring stitches, a broken bone or 811
permanent eye damage. A double or reinforced safeguard is required to 812
protect an ordinary person and an instructed person. 813
8.3 Safeguards against mechanical energy sources 814
Purpose: To determine the number of safeguards needed between the type of person 815
and the relevant energy source classification. 816
Rationale: An instructional safeguard describing hazard avoidance may be employed 817
to circumvent the equipment safeguard permitting access to MS2 part 818
locations to perform an ordinary person service function. The instructional 819
safeguard indicates that the equipment safeguard be restored after the 820
service activity and before power is reconnected. When an instructional 821
safeguard is allowed, a warning is also required to identify insidious 822
hazards. 823
IEC TR 62368-2:20xx © IEC 20xx – 111 –
For an instructed person and a skilled person, an instructional 824
safeguard, in the form of a warning marking, is necessary to supplement the 825
instruction they have received to remind them of the location o f hazards that 826
are not obvious. 827
However, for a skilled person, an equipment safeguard is required in the 828
service area of large equipment with more than one level 3 energy sources, 829
where the skilled person can insert their entire head, arm, leg or complete 830
body. This safeguard is intended to protect the skilled person against 831
unintentional contact with any other level 3 energy source due to an 832
involuntary startle reaction to an event in the equipment while servicing 833
intended parts. 834
The involuntary reaction may occur for a number of reasons, such as an 835
unexpected loud noise, an arc flash or receipt of a shock, causing the person 836
to recoil away from the energy source or part being serviced. Where more 837
than one of the level 3 energy sources may require servicing at some time, 838
removable equipment safeguards shall be designed such that any level 3 839
sources not being serviced can remain guarded. The equipment 840
safeguards for this purpose only need to protect against larger body contact, 841
since the potential involuntary recoil reaction will likely be full limb or body 842
and not small body parts. 843
8.4 Safeguards against parts with sharp edges and corners 844
Rationale: Engineering judgment shall be used to class a mechanical energy source as 845
MS1, MS2 or MS3 and an appropriate safeguard shall be provided. Where 846
a MS2 or MS3 cannot be fully guarded without interfering with the intended 847
function of the equipment, it shall be guarded as much as practical. Such an 848
energy source shall not be accessible to children and be obvious to an adult. 849
Instructional safeguards shall be provided to warn the person about 850
potential contact with the energy source and what steps to take to avoid 851
unintentional contact. 852
We rely on engineering judgment as there are too many variables involved 853
to define the type of edge or corner combined with the applied force and 854
direction of contact or to provide specific values. 855
8.5 Safeguards against moving parts 856
Rationale: Enclosures and barriers protect against access to hazardous moving parts. 857
See 8.5.1 for the exception of requirements related to parts not fully guarded 858
because of their function in the equipment. 859
8.5.1 Requirements 860
Rationale: The MS2 or MS3 energy sources need to be guarded against accidental 861
access by a person's extremities, jewellery that may be worn, hair and 862
clothing, etc. Access is determined by applying the appropriate tool from 863
Annex V, and no further testing is necessary. We note that while it may be 864
technically possible for some jewellery and hair to enter an opening smaller 865
than the test finger, in such cases, the jewellery strands would have to be 866
very thin and flexible enough to enter (as would a few strands of hair). As 867
such while some pain may result if they happen to be caught in the 868
mechanical device, it is deemed unlikely an injury would occur as described 869
by this document. The residual risk can be considered a MS2 energy source 870
at most. 871
– 112 – IEC TR 62368-2:20xx © IEC 20xx
8.5.4.3 Equipment having an electromechanical device for destruction of media 872
Source: UL/CSA 60950-1 second edition [national difference] 873
Rationale: Recent large scale introduction of media shredders into the home 874
environment resulted in an increase of children being injured when inserting 875
their fingers through the shredder openings. These incidents were studied 876
and a new probe was developed to assess potential access by children. The 877
new probe/wedge has been designed for both application with force when 878
inserted into the shredder openings and assessment of access to MS3 879
moving parts by a population consisting of both adults and children. Th is 880
design differs from the existing UL and IEC accessibility probes since the UL 881
Articulated Accessibility Probe is not intended to be used with a force applied 882
to it, and the current IEC probes, while having an unjointed version for 883
application under force, do not adequately represent the population for both 884
adults and children. 885
Because cross-cut shredders typically apply more force to the media than 886
straight-cut shredders, the requirements include differentiated application 887
forces for the two designs. The force values consider typical forces 888
associated with straight-cut and cross-cut designs, taking into account data 889
generated by the USA Consumer Product Safety Commission on typical pull 890
forces associated with both strip type and crosscut type shredders. 891
The dimensions of the new probe/wedge are based on the data generated 892
during the development of the UL Articulated Accessibility Probe. However, 893
the dimensions of the UL Articulated Accessibility Probe were defined in 894
consideration of causal handling of products. Because of this, the 95th 895
percentile points from the data were used to define the UL Articula ted 896
Accessibility Probe. The thickness and length dimensions of the new 897
proposed probe/wedge have been developed in consideration of all data 898
points. Articulation points are identical to those for the UL Articulated 899
Accessibility Probe. 900
8.6 Stability of equipment 901
Source: IEC 60950-1 and IEC 60065 902
Purpose: To align existing practice with the MS1, MS2 and MS3 energy. 903
Rationale: Equipment weighing more than 25 kg is considered MS3. Regardless of 904
weight, equipment mounted to the wall or ceiling is considered MS3 when it 905
is to be mounted above 2 m height. 906
Equipment weighing between 7 kg and not exceeding 25 kg is considered 907
MS2. Equipment with a weight of 1 kg or more and that is mounted to the 908
wall or ceiling to a maximum height of 2 m is also considered MS2. 909
Equipment with weight not exceeding 7 kg is considered MS1 if floor 910
standing, but can be either MS2 or MS3 if mounted to the wall or ceiling. 911
Also see carts and stands, and wall or ceiling mounted equipment. 912
Children are naturally attracted to moving images and may attempt to touch 913
or hold the image by pulling or climbing up on to the equipment. The tests 914
assess both the static stability and mounting grip when placed on a slippe ry 915
surface such as glass. Children might also misuse controls that are readily 916
available to them. 917
8.6.2.2 Static stability test 918
Rationale: Equipment is assessed for stability during expected use by applying force 919
horizontally and downward on surfaces that could be used as a step or have 920
other objects placed upon it. 921
The value of 1,5 m was chosen as the maximum height where an average 922
person could lean on or against the product. 923
IEC TR 62368-2:20xx © IEC 20xx – 113 –
The 1,5 m is also used for table top equipment, since we do not know 924
whether the product is going to be placed on a table or, if so, what the height 925
of the table will be. 926
8.6.2.3 Downwards force test 927
Rationale: The height of 1 m represents the maximum height one could expect that 928
people could try to use as a step to reach something. 929
8.6.3 Relocation stability 930
Source: IEC 60950-1 and IEC 60065 931
Rationale: The 10° tilt test simulates potential horizontal forces applied to the 932
equipment either accidentally or when attempting to move the equipment. In 933
addition it simulates moving the equipment up a ramp during transport. 934
The test on the horizontal support may be necessary (for example, for 935
equipment provided with small feet, casters or the like). 936
8.6.4 Glass slide test 937
Source: IEC 60065:2011 938
Purpose: To address the hazard of equipment with moving images sliding off a smooth 939
surface when a child attempts to climb onto the equipment. 940
Rationale: To ensure the display does not slide too easily along a smooth surface that 941
could result in the display falling from an elevated height on to a child. 942
8.6.5 Horizontal force test and compliance criteria 943
Purpose: To simulate the force of a child climbing up on to equipment with front 944
mounted user controls or with moving images. 945
Rationale: Field data and studies in the US have shown that chi ldren 2-5 years of age 946
were attracted to the images on the display that may result in the ch ild 947
climbing onto the display to touch/get close to the image. The equipment 948
could then tip over and crush the child. Also, products with accessible 949
controls or that are shorter than 1 m in height are considered likely to be 950
handled by children. 951
– Data was gathered in the 1986 to 1998 for CRT TV sets ranging from 952
48,26 cm to 68,58 cm (19 to 27 inches). The average horizontal force 953
was 13 % of the equipment weight. 954
– The 15° tilt test (an additional 5° over static stability test) provides an 955
additional safety factor. 956
8.7 Equipment mounted to a wall, ceiling or other structure 957
Source: IEC 60065 and 60950 series 958
Purpose: The objective of this subclause is to minimize the likelihood of injury caused 959
by equipment falling due to failure of the mounting means. 960
Rationale: Equipment intended to be mounted to a wall or ceiling should be tested to 961
ensure adequacy for all possible mounting options and all possible failure 962
modes. For typical equipment, such as flat panel televisions, mounting 963
bosses are usually integrated into the equipment and used with an 964
appropriate wall or ceiling mounting bracket to attach to a wall or ceiling. 965
Typical mounting bosses are comprised of threaded inserts into the rear 966
panel of the equipment. 967
The appropriate load is divided by the number of mounting means (for 968
example, mounting bosses) to determine the force applied to each individual 969
mounting means. 970
The horizontal force values of 50 N and 60 s have been successfully used 971
for products in the scope of these documents for many years. 972
– 114 – IEC TR 62368-2:20xx © IEC 20xx
8.7.2 Test methods 973
Figure 37 in this document gives a graphical view of the different tests 974
required by Test 2 and show the directions that the forces are applied. 975
976
Figure 37 – Direction of forces to be applied 977
Table 37 Torque to be applied to screws 978
Source: IEC 60065 979
Rationale: These torque values have been successfully used for products in the scope 980
of this document for many years. 981
8.8 Handle strength 982
Source: IEC 60065 and IEC 60950-1 983
Rationale: A handle is a part of the equipment that is specifically designed to carry the 984
equipment or subassembly around. A grip which is made for easy removal 985
or placement of a subassembly in an equipment is not considered to be a 986
handle. 987
The 75 mm width simulates the hand width. The safety factors take into 988
account the acceleration forces and additional stresses that could be applied 989
due to extra weight on top of the equipment when being lifted. The safety 990
factor is less at the higher weight (MS3) because the equipment would be 991
lifted more slowly, reducing the acceleration force, and there is less 992
probability that extra weight would be added before lifting, as this would 993
exceed the normal weight to be lifted by one person without assistance of a 994
tool. Equipment classed as MS1 with more than one handle could be used 995
to support additional objects when being carried and should be tested. 996
8.8.2 Test method 997
Rationale: There is no test for MS1 with only one handle. Having 2 handles facilitates 998
transporting the equipment while carrying additional objects adding stress to 999
the handles. 1000
8.9 Wheels or casters attachment requirements 1001
Purpose: To verify that wheels or casters are securely fixed to the equipment . 1002
Source: UL 1667 1003
IEC TR 62368-2:20xx © IEC 20xx – 115 –
Purpose: For wheel size, reduce the likelihood of the equipment on the cart or stand 1004
tipping while being moved from room to room where the wheels may 1005
encounter a variety of obstacles, such as: friction of different surfaces ( for 1006
example, transition from a hard surface over carpet edging), cables, and 1007
doorway sills. 1008
Rationale: The 100 mm min wheel size was found to be adequate to enable rolling over 1009
these obstacles without abruptly stopping that could cause the cart or stand 1010
to tip, or the equipment located on the cart or stand to slide off. 1011
8.10 Carts, stands, and similar carriers 1012
Source: UL 60065 1013
Rationale: To avoid tipping, the 20 N test simulates cart wheels being unintentionally 1014
blocked during movement. 1015
8.10.1 General 1016
Source: IEC 60065 1017
Rationale: A wheel of at least 100 mm diameter can be expected to climb over usual 1018
obstacles such as electrical cords, door jambs, etc., and not be halted 1019
suddenly. 1020
8.10.2 Marking and instructions 1021
Rationale: Various means of marking may apply depending on the method o f 1022
associating the equipment with a particular cart, stand of similar carrier. 1023
8.10.3 Cart, stand or carrier loading test and compliance criteria 1024
Source: IEC 60065 1025
Purpose: To verify that a cart or stand can withstand foreseeable overloading without 1026
creating a hazardous situation. 1027
Rationale: The 220 N force simulates the weight of a small child approximately 5 years 1028
of age, who may attempt to climb onto the cart or stand. The 30 mm circular 1029
cylinder simulates a child’s foot. The 750 mm height is the approximate 1030
access height of the 5-year-old child. The additional 440 N force test 1031
simulates potential additional materials or equipment being placed on the 1032
cart or stand. The additional 100 N simulates overloading by the user. 1033
Testing has been limited to 1 min as experience has shown that the 1034
likelihood of a test failure will occur within that time. 1035
8.10.4 Cart, stand or carrier impact test 1036
Purpose: To verify that a cart or stand can withstand a foreseeable impact without 1037
creating a hazardous situation. 1038
Source: IEC 60065 and IEC 60950 series 1039
Rationale: The 7 joules simulate intentional and accidental contact with the equipment 1040
and come from the T.6 enclosure test. 1041
8.10.5 Mechanical stability 1042
Purpose: To verify that a cart or stand remains stable under specified loading. The 1043
equipment installed on the cart may come loose, but not fall off the cart. 1044
Rationale: The weight of the force test is reduced to 13 % should the equipment on the 1045
cart or stand move, as the equipment would then be considered separately 1046
from the cart or stand. When the equipment does not move during the force 1047
test, together they are considered a single unit. 1048
8.10.6 Thermoplastic temperature stability 1049
Source: IEC 60065 and IEC 60950-1 1050
– 116 – IEC TR 62368-2:20xx © IEC 20xx
Rationale: Intended to prevent shrinkage, relaxation or warping of materials that could 1051
expose a hazard. 1052
8.11 Mounting means for slide-rail mounted equipment (SRME) 1053
8.11.1 General 1054
Source: UL/CSA 60950-1 second edition 1055
Rationale: The potential hazardous energy source is a product that contains significant 1056
mass, and which is mounted on slide-rails in a rack. A joint US/Canadian 1057
Adhoc researched and developed these requirements based on hazard-1058
based assessment and tests. 1059
The center of gravity was chosen to apply the downward force because in 1060
general, when installing equipment in a rack, it is foreseeable that previously 1061
installed equipment of similar size/mass may be pulled out into the service 1062
position (fully extended) and used to set the new equipment on while 1063
positioning and installing the new slide/rails. In this scenario, it is not likely 1064
that the new equipment would be significantly off-centre from the installed 1065
equipment that it is being set on. 1066
Vertically mounted SRMEs are not addressed in this document. 1067
8.11.3 Mechanical strength test 1068
Purpose: To simulate temporary placement of another server on top of an existing one 1069
during installation of the new one. So the test is the downward force. 1070
Rationale: 50 % of the equipment mass is derived from the mass of the equipment, and 1071
a 50 % tolerance allowed for manufacturing differences in the rails which 1072
effectively adds a safety buffer. 1073
The 330 N to 530 N additional force accounts for equipment that is about to 1074
be installed in a rack being placed or set on a previously installed piece of 1075
equipment where the previously installed equipment is being used as a 1076
temporary shelf or work space. It is estimated that 530 N is the maximum 1077
mass of equipment allowed to be safely lifted by two persons without the use 1078
of mechanical lifting devices. Equipment having a mass greater than 530 N 1079
will have mechanical lifting devices and it is therefore unlikely that the 1080
equipment being installed will be set on any equipment previously installed 1081
in the rack. 1082
Taking the actual installation environment into consideration, an additional 1083
force is limited to maximum 800 N (average weight of an adult man) that is 1084
same value as the downward test force in 8.6.2.3. The 800 N value comes 1085
from IEC 60950-1:2005, 4.1 Stability. 1086
8.11.3.2 Lateral push foce test 1087
8.11.3.3 Integrity of slide rail end stops 1088
Source: UL/CSA 60950-1 second edition 1089
Purpose: To simulate maintenance on the server itself, by smaller applying forces 1090
equivalent to what is expected during subassembly and card replacement, 1091
etc. So this also tests the laterally stability of the slide rails. It is not 1092
necessary to retest the downward vertical force if it is already tested for 1093
8.11.3, but that should be common sense when preparing a test plan. 1094
The cycling of the slide rail after the tests ensures they have not been bent 1095
in a way that could easily fly apart after the service operation. 1096
IEC TR 62368-2:20xx © IEC 20xx – 117 –
Rationale: The 250 N force is considered a force likely to be encountered during 1097
servicing of the equipment, and normal operations around equipment. The 1098
force is partially derived from the existing IEC 60950-1:2005, 4.1, and 1099
partially from research into normally encountered module plug forces seen 1100
on various manufacturers’ equipment. The application of force at the most 1101
unfavourable position takes into account the servicing of a fully extended 1102
piece of equipment, leaning on or bumping into an extended piece of 1103
equipment and other reasonably foreseen circumstances which may be 1104
encountered. 1105
___________ 1106
Thermal burn injury 1107
9.1 General 1108
Source: ISO 13732-1:2006 and IEC Guide 117 1109
Rationale: A General 1110
A burn injury can occur when thermal energy is conducted to a body part to 1111
cause damage to the epidermis. Depending on the thermal mass of the 1112
object, duration of contact and exposure temperature, the body response 1113
can range from perception of warmth to a burn. 1114
The energy transfer mechanism for equipment typically covered by the 1115
document is via conduction of thermal energy through physical contact with 1116
a body part. 1117
The likelihood of thermal injury is a function of several thermal energy 1118
parameters including: 1119
– temperature difference between the part and the body; 1120
– the thermal conductivity (or thermal resistance) between the hot part and 1121
the body; 1122
– the mass of the hot part; 1123
– the specific heat of the part material; 1124
– the area of contact; 1125
– the duration of contact. 1126
B Model for a burn injury 1127
A skin burn injury occurs when thermal energy impinges on the skin and 1128
raises its temperature to a level that causes cell damage. The occurrence of 1129
a burn will depend on several parameters. The hazard based three block 1130
model applied to the occurrence of a burn (see Figure 38 in this document) 1131
takes account of not just the temperature of the source, but its total thermal 1132
energy, which will depend on its temperature (relative to the skin), as well 1133
as its overall heat capacity. The model also takes account of the energy 1134
transfer mechanism, which will depend on the thermal conductivity between 1135
the body and the thermal source as well as the area and duration o f contact. 1136
The occurrence and severity of a burn will depend on the amount of thermal 1137
energy transferred. 1138
1139
Figure 38 – Model for a burn injury 1140
– 118 – IEC TR 62368-2:20xx © IEC 20xx
Normally, the energy transfer mechanism from the energy source to a body 1141
part is through direct contact with the body part and sufficient contact 1142
duration to allow transfer of thermal energy causing a burn. The higher the 1143
temperature of the thermal source and the more efficient the transfer 1144
mechanism, the shorter the contact time becomes before the occurrence of 1145
a burn. This is not a linear function and it is dependent on the material, the 1146
temperature and the efficiency of the thermal transfer. The following 1147
examples demonstrate the impact of this non-linear relationship to short-1148
term/high temperature and longer term/lower temperature contact burns. 1149
Example 1: An accessible metal heat sink at a temperature of 60 °C may 1150
have sufficient energy to cause a burn after contact duration of about 5 s. At 1151
a temperature of 65 °C, a burn may occur after contact duration of just 1,5 s 1152
(see IEC Guide 117:2017, Figure A.1). As the temperature of the metal 1153
surface increases, the contact time necessary to cause a burn decreases 1154
rapidly. 1155
Example 2: Consider a thermal source with low to moderate conductivity 1156
such as a plastic enclosure. At a temperature of 48 °C, it may take up to 10 1157
min for the transfer of sufficient thermal energy to cause a burn. At 60 °C, a 1158
burn may occur after contact duration of just 1 min (see IEC Guide 117:2010, 1159
Table A.1). Although the temperature of the source has increased by just 1160
25 %, the contact time necessary to cause a burn threshold has decrease d 1161
by 90 %. 1162
In practice, the actual thermal energy and duration of exposure required to 1163
cause a burn will also depend on the area of contact and condition of the 1164
skin. For simplification of the model and based upon practice in the past, it 1165
is assumed that the contact area will be 10 % of the body and applied to 1166
healthy, adult skin. 1167
As a general rule, low temperature devices are likely to cause a heating or 1168
pain sensation before causing a significant burn to which ordinary persons 1169
will normally respond (see ISO 13732-1:2009, Note of 5.7.3). Requirements 1170
for persons with impaired neurological systems are not considered in this 1171
document but may be considered in the future. 1172
NOTE 1 The impact of surface area contact is not being addressed in this paper at this time 1173 and is an opportunity for future work. Use and coverage of large contact areas as might occur 1174 in medical applications of heating pads covering more than 10 % of the body surface are 1175 outside the scope of this document, as this type of application is more appropriate to medical 1176 device publications. 1177
NOTE 2 The pressure of the contact between the thermal source and the body part can have 1178 an impact on the transfer of thermal energy. Studies have shown this effect to have 1179 appreciable impact at higher pressures. For typical pressures associated with casual cont act 1180 up to a pressure of 20 N the effect has been shown to be negligible, and thus contact pressure 1181 is not considered in this document (Ref: ATSM C 1055, X1.2.3.4, ASTM C 1057,7, Note 10). 1182
NOTE 3 Considerations for burns generated by infrared (IR), visible, ultra violet light 1183 radiation and RF radiation sources are outside the scope of Clause 9 dealing with thermal 1184 burn injury. 1185
C Types of burn injuries 1186
Burn injuries are commonly classed as first degree, second degree or third 1187
degree in order of increasing severity: 1188
First degree burn: the reaction to an exposure where the intensity or 1189
duration is insufficient to cause complete necrosis of the epidermis. The 1190
normal response to this level of exposure is dilation of the superficial blood 1191
vessels (reddening of the skin). No blistering occurs. (Reference: ASTM 1192
C1057) 1193
Second degree burn: the reaction to an exposure where the intensity and 1194
duration is sufficient to cause complete necrosis of the epidermis but no 1195
significant damage to the dermis. The normal response to this exposure is 1196
blistering of the epidermis. (Reference: ASTM C1057) 1197
IEC TR 62368-2:20xx © IEC 20xx – 119 –
Third degree burn: the reaction to an exposure where significant dermal 1198
necrosis occurs. Significant dermal necrosis with 75 % destruction of the 1199
dermis is a result of the burn. The normal response to this exposure is open 1200
sores that leave permanent scar tissue upon healing. 1201
(Reference: ASTM C1057) 1202
ISO 13732-1, 3.5 classifies burns as follows: 1203
Superficial partial thickness burn – In all but the most superficial burns, 1204
the epidermis is completely destroyed but the hair follicles and sebaceous 1205
glands as well as the sweat glands are spared. 1206
Deep partial thickness burn: a substantial part of the dermis and all 1207
sebaceous glands are destroyed and only the deeper parts of the hair 1208
follicles or the sweat glands survive. 1209
Whole thickness burn: when the full thickness of the skin has been 1210
destroyed and there are no surviving epithelial elements. 1211
Although there is some overlap between the classifications in ASTM C1057 1212
and those in IEC Guide 117, the individual classifications do not correspond 1213
exactly with each other. Further, it should be noted that the classifications of 1214
burns described here is not intended to correspond with the individual 1215
thermal source classifications (TS1, TS2, and TS3) described later in this 1216
document. 1217
D Model for safeguards against thermal burn injury 1218
To prevent thermally-caused injury, a safeguard is interposed between the 1219
body part and the energy source. More than one safeguard may be used to 1220
meet the requirements for thermal burn hazard protection. 1221
Figure 39 – Model for safeguards against thermal burn injury
To prevent thermally-caused injury, a safeguard is interposed between the 1222
body part and the energy source (see Figure 39 in this document). More than 1223
one safeguard may be used to meet the requirements for thermal burn 1224
hazard protection. 1225
Safeguards overview 1226
This section shows examples of the different types of safeguards that may 1227
be applied: 1228
a) Thermal hazard not present 1229
The first model, see Figure 40 in this document, presumes contact to a 1230
surface by an ordinary person where a thermal hazard is not present. In 1231
this case, no safeguard is required. 1232
1233
Figure 40 – Model for absence of a thermal hazard 1234
– 120 – IEC TR 62368-2:20xx © IEC 20xx
b) Thermal hazard is present with a physical safeguard in place 1235
The second model, see Figure 41 in this document, presumes some contact 1236
with a surface by an ordinary person. The thermal energy source is above 1237
the threshold limit value for burns (Table 38 of IEC 62368-1:2018), but there 1238
are safeguards interposed to reduce the rate of thermal energy transferred 1239
such that the surface temperature will not exceed the threshold limit values 1240
for the expected contact durations. Thermal insulation is an example of a 1241
physical safeguard. 1242
1243
Figure 41 – Model for presence of a thermal hazard 1244
with a physical safeguard in place 1245
c) Thermal hazard is present with a behavioural safeguard in place 1246
The third model, see Figure 42 in this document, presumes the possibility of 1247
some contact to the thermal source or part by an ordinary person. The 1248
temperature is above the threshold limit value but the exposure time is 1249
limited by the expected usage conditions or through instructions to the user 1250
to avoid or limit contact to a safe exposure time. The contact time and 1251
exposure will not exceed the threshold limit value. An additional safeguard 1252
may not be required. 1253
1254
Figure 42 – Model for presence of a thermal hazard 1255
with behavioural safeguard in place 1256
9.2 Thermal energy source classifications 1257
Rationale: Surfaces that may be touched are classified as thermal energy sources TS1, 1258
TS2 or TS3 with TS1 representing the lowest energy level and TS3 the 1259
highest. The classification of each surface will determine the type of 1260
safeguards required. 1261
The assessment of thermal burn hazards is complex and, as discussed in 1262
the model for a burn injury above, involves several factors. Important aspects 1263
include the overall heat capacity of the source, its temperature relative to the 1264
body, thermal conductivity of the contact and others. To present a simple 1265
model for assessment of a given surface, it is assumed that the overall heat 1266
capacity and the thermal conductivity will remain constant. 1267
Thus, thermal energy sources are classified in terms of the material of the 1268
surface, its relative temperature and duration of contact only. Usually, for a 1269
given material the temperature and duration of contact are likely to be the 1270
only significant variables when assessing the risk of a burn injury. 1271
IEC TR 62368-2:20xx © IEC 20xx – 121 –
9.2.1 TS1 1272
Rationale: The lowest thermal energy source is TS1. TS1 represents a level of thermal 1273
energy that generally will not cause a burn injury. 1274
9.2.2 TS2 1275
Rationale: A TS2 thermal energy source has sufficient energy to cause a burn injury in 1276
some circumstances. The occurrence of a burn from a TS2 source will largely 1277
depend on the duration of contact. Depending on the contact time, and 1278
contact area, contact material, and other factors, a TS2 source is not likely 1279
to cause an injury requiring professional medical attention. Table 38 defines 1280
the upper limits for TS2 surfaces. 1281
A TS2 circuit is an example of a class 2 energy source where the basic 1282
safeguard may, in some cases, be replaced by an instructional safeguard. 1283
Details are given in Table 38, footnote e. 1284
9.2.3 TS3 1285
Rationale: A TS3 thermal energy source has sufficient energy to cause a burn injury 1286
immediately on contact with the surface. There is no table defining the limits 1287
for a TS3 surface because any surface that is in excess of TS2 limits is 1288
considered to be TS3. Within the specified contact time, as well as contact 1289
area, contact material and other factors, a TS3 source may cause an injury 1290
requiring professional medical attention. As TS3 surfaces require that 1291
maximum level of safeguard defined in the document. All surfaces may be 1292
treated as TS3 if not otherwise classified. 1293
Source: IEC Guide 117. 1294
Rationale: When doing the temperature measurements, an ambient temperature is used 1295
as described in 9.2.5 to measure the temperatures without taking into 1296
account the maximum ambient specified by the manufacturer. 1297
9.3 Touch temperature limits 1298
Table 38 Touch temperature limits for accessible parts 1299
Source: The limits in Table 38 are primarily derived from data in IEC Guide 117. 1300
Rationale: The temperature of the skin and the duration of raised temperature are the 1301
primary parameters in the occurrence of a skin burn injury. In pract ice, it is 1302
difficult to measure the temperature of the skin accurately while it is in 1303
contact with a hot surface. Thus the limits in Table 38 do not represent skin 1304
temperatures. These limits do represent the surface temperatures that are 1305
known to cause a skin burn injury when contacted for greater than the 1306
specified time limit. 1307
The thermal energy source criterion takes account of the temperature of the 1308
source, its thermal capacity and conductivity as well as the likely duration 1309
and area of contact. As the thermal capacity and conductivity will normally 1310
remain constant for a given surface, the limits here are expressed in degrees 1311
C for typical material types and contact durations. 1312
Contact time duration > 8 h 1313
For devices worn on the body (in direct contact with the skin) in normal use 1314
(> 8 h), examples include portable, lightweight devices such watches, 1315
headsets, music players and sports monitoring equipment. Since the values 1316
in the table do not represent skin temperature as indicated above, 1317
measurements should not be done while wearing the devices. 1318
– 122 – IEC TR 62368-2:20xx © IEC 20xx
The value of 43 °C for all materials for a contact period of 8 h and longer 1319
assumes that only a minor part of the body (less than 10 % of the entire skin 1320
surface of the body) or a minor part of the head (less than 10 % of the skin 1321
surface of the head) touches the hot surface. If the touching area is not local 1322
or if the hot surface is touched by vital areas of the face ( for example, the 1323
airways), severe injuries may occur even if the surface temperature does not 1324
exceed 43 °C (see IEC Guide 117). 1325
NOTE Prolonged exposure to 43 °C may result in erythema (temporary redness of the skin 1326 causing dilation of the blood capillaries) which will typically go away within a few hours after 1327 removal of the heat source. For some users, this may be misperceived as a burn. 1328
Contact time durations > 1 min 1329
For very long-term contact ( 10 min), the temperature below which a burn 1330
will not occur converges towards 43 °C for most materials (see 1331
IEC Guide 117:2010, Figure A.1). Studies carried out on portable IT 1332
Equipment have shown that for long term contact, a surface temperature will 1333
drop by between 5 °C and 12 °C when in contact with the body due to the 1334
cooling effect of the blood circulation. On this basis, and taking accou nt of 1335
the probability that long-term contact will normally be insulated by clothing 1336
or some other form of insulation, the TS1 temperature limit for contact 1337
periods greater than 1 min in Table 39 are conservatively chosen as 48 °C 1338
for all materials. 1339
Examples of products with surfaces where expected continuous contact 1340
durations greater than 1 min include joysticks, mice, mobile telephones, and 1341
PDAs. Any handles, knobs or grips on the equipment that are likely, under 1342
normal usage, to be touched or held for greater than 1 min are also included. 1343
Contact time durations between 10 s and 1 min 1344
For surfaces that are touched for shorter contact durations (up to 1 min), the 1345
temperature below which a burn will not occur is influenced by the material 1346
type as well as other factors. Because the contact time is shorter, there is 1347
insufficient time for heat transfer to cause the cooling effect described above, 1348
so it is not considered in the limits. The TS1 temperature limits in Table 38 1349
for contact durations up to 1 min are taken directly from IEC Guide 117:2010, 1350
Table A.1. 1351
Examples of surfaces with contact durations up to 1 min include handles or 1352
grips used primarily for moving or adjusting the equipment. Also tuning dials 1353
or other controls where contact for up to 1 min may be expected. 1354
Contact time durations up to 10 s 1355
Even shorter-term contact may occur for surfaces such as push 1356
button/switch, volume control; computer or telephone keys. In this case, the 1357
surfaces will not normally be touched for a duration greater than 10 s. The 1358
TS1 temperature limits in Table 38 for these surfaces are based on the burn 1359
threshold limits in IEC Guide 117 for contact durations of up to 10 s. 1360
For surfaces that are accessible but need not be touched to operate the 1361
equipment, contact duration of up to 1 s is assumed. For healthy adults, a 1362
minimum reaction time of 0,5 s can be assumed. For more general 1363
applications, the reaction time increases to 1 s IEC Guide 117, Table 2. The 1364
TS1 temperature limits in Table 38 for these surfaces are based on the burn 1365
threshold limits in Guide 117 for contact durations of 1 s 1366
(see IEC Guide 117:2010, Figures A.1 – A.6). More conservative values than 1367
those in IEC Guide 117 are chosen for metal and glass to provide some 1368
margin against a reduced reaction time while in contact w ith a high thermal 1369
energy surface of high thermal conductivity. 1370
Examples of such parts include general enclosure surfaces, accessible 1371
print heads of dot matrix printers or any internal surfaces that may be 1372
accessible during routine maintenance. Accidental contact, with no intention 1373
to hold or contact the surface is also included. 1374
IEC TR 62368-2:20xx © IEC 20xx – 123 –
For contact durations between 1 s and 10 s, IEC Guide 117 provides 1375
temperature ranges over which a burn may occur rather than precise limits. 1376
This takes account of the uncertainty that applies to the occurrence of burn 1377
injury over shorter periods. The texture of the surface can also be a factor in 1378
the occurrence of a burn and this is not taken into account in the limits in 1379
IEC Guide 117. As most surfaces in IT equipment will have some texturing, 1380
values at the higher end of the spreads have been chosen. 1381
Contact time durations up to 1 s 1382
For accessible surfaces that are not normally intended or expected to be 1383
touched while operating or disconnecting the equipment, a contact time 1384
duration of up to 1 second is appropriate. This would apply to any surface of 1385
the equipment that does not have functionality when touched or is unlikely 1386
to be inadvertently contacted when accessing functional surfaces such as 1387
keyboards or handles. Typical and readily expected usage should be 1388
considered when assessing likely contact duration with such a surface. 1389
For example, it is not necessary to touch a direct plug-in external power 1390
supply adapter (Figure 43) during normal use of the equipment, but it will 1391
likely be touched or briefly held for disconnection from the mains. Thus, this 1392
type of equipment is expected to be contacted for more than one second. 1393
1394
Figure 43 – Direct plug in Figure 44 – External power supply
1395
Other external power supplies, such as those often supplied with notebook 1396
computers and other equipment (Figure 44), with a connected power cord 1397
will not normally be touched either during usage or for disconnection. For 1398
external power supplies with power cord, to disconnect from mains, the user 1399
will grip the power cord plug. The contact time with the plug would be more 1400
than 1 second and the contact time of the power supply would be less than 1401
1 second. 1402
Other considerations 1403
In the event of a fault condition arising, the user is less likely to touch the 1404
equipment and any contact with accessible surfaces is likely to be very brief. 1405
Thus higher limits than those allowed under IEC Guide 117 are permitted. 1406
For metal, glass and plastic surfaces, the limit is 100 °C (IEC 60065:2010, 1407
Table 3). For wood, a temperature of 150 °C was chosen because 100 °C 1408
would be lower than the normal temperature of 140 °C. 1409
When contact with a TS1 surface is unlikely due to its limited size or 1410
accessibility, a temperature up to 100 °C is acceptable if an instructional 1411
safeguard is provided on the equipment (see IEC 60950-1:2005, Table 4C, 1412
IEC 60065:2001, Table 3). 1413
In the case where a surface is hot in order to carry out its function, the 1414
occurrence of contact with the surface or a subsequent burn injury is unlikely 1415
if the user is made aware that the surface is hot. Thus, a temperature up to 1416
100 °C or higher is acceptable if there is an effective instructional 1417
safeguard on the body of the equipment indicating that the surface is hot 1418
(see IEC 60950-1:2005, Table 4C and IEC 60065:2001, Table 3). 1419
– 124 – IEC TR 62368-2:20xx © IEC 20xx
Factors for consideration in determining test conditions 1420
For consistency with other parts of the document and to reflect typical user 1421
conditions, the ambient conditions described in B.1.6 apply. 1422
Assessment of safeguards should be carried out under normal operating 1423
conditions of the product that will result in elevated surface temperatures. 1424
The chosen normal operating conditions should be typical of the 1425
manufacturer’s intended use of the product while precluding deliberate 1426
misuse or unauthorized modifications to the product or its operating 1427
parameters by the user. For some simple equipment, this will be 1428
straightforward. For more complex equipment, there may be several 1429
variables to be considered including the typical usage model. The 1430
manufacturer of the equipment should perform an assessment to determine 1431
the appropriate configuration. 1432
Example: Factors that may be considered in determining the test conditions 1433
for a notebook computer: 1434
– Mode of operation 1435
• Variable CPU speed 1436
• LCD brightness 1437
– Accessories installed: 1438
• Number of disk drives 1439
• USB devices 1440
• External HDD 1441
– Software installed: 1442
• Gaming applications 1443
• Duration of continuous use 1444
• Long term contact likely? 1445
• Other specialist applications 1446
– Battery status: 1447
• Fully charged/ Discharged 1448
• AC connected 1449
9.3.1 Touch temperature limit requirements 1450
Rationale: Table 38 provides touch temperature limits for accessible parts, assuming 1451
steady state. IEC Guide 117 provides the methodology to assess products 1452
with changing temperatures or small parts which are likely to drop in 1453
temperature upon touch. Using a thermesthesiometer for a specified time 1454
interval, the thermesthesiometer simulates the skin temperature of human 1455
finger and heating effects caused by contact with the product surface under 1456
test. Once contact is made, the thermesthesiometer and product under test 1457
will eventually reach thermal equilibrium at which point finger skin 1458
temperature can be determined. 1459
Background: The touch limits from Table 38 for > 1 s and < 10 s may be used for small 1460
hand-held equipment with localized hotspots, given a small thermal energy 1461
source and touching can be easily avoided by changing holding position of 1462
the device. 1463
IEC TR 62368-2:20xx © IEC 20xx – 125 –
This same rationale would also apply to small multi -media peripherals which 1464
are removed from a host device (for example, USB memory stick, PCMCIA 1465
cards, SD card, Compact Flash card, ejectable media, etc.). In many cases , 1466
these peripherals may be removed from their host ( for example, power 1467
source) exposing higher thermally conductive materials ( for example, 1468
metals), but are in thermal decay (i.e. no longer powered). 1469
In cases of doubt, the method in IEC Guide 117 may be used for steady-1470
state conditions. An example of a simplified method for thermally decaying 1471
parts is provided as a reference: 1472
Touch temperature limits in IEC Guide 117 are based on time-weighted 1473
exposure for burn (for example, thermal energy). As long as integrated 1474
thermal energy calculations (for example, area of temp vs. time) of the part 1475
at specified time intervals is less than the associated integrated thermal 1476
energy calculated limits over that duration, the measured temperatures 1477
should be acceptable. 1478
The most significant time internals to consider for decaying thermal energy 1479
is between 1 s to 10 min (using 10 s, 1 min, 10 min intervals). 1480
– For exposure times < 1 s, the 1 s temperature limits of the IEC Guide 117 1481
should be used for 2 reasons: 1) Reaction times – under general 1482
applications reaction times of < 1 s are not probable and greatest risk of 1483
burn. 2) Repeatability – temperature measurement capability < 1 s 1484
intervals is less common and more difficult to accurately calculate the 1485
part energy. 1486
– For exposure times > 10 min, the temperature limits of IEC Guide 117 1487
should be used: after 10 min parts should either have cooled or reach 1488
sufficient equilibrium to utilize the temperature limits without the need for 1489
assessing thermal energy. 1490
This simplified method requires the part under test to be mounted using 1491
thermally insulating clamp. Clamp to the part’s least thermally conductive 1492
material and smallest contact needed to hold the part. Measured in still-air 1493
room ambient. 1494
NOTE Parts that are hand-held will decay faster than open-air measurements (for example, 1495 radiation and convection) owing to direct conduction of heat to skin. 1496
9.3.2 Test method and compliance criteria 1497
Rationale: The general intent of the requirements are to use an ambient temperature 1498
as follows without taking into account the maximum ambient specified by the 1499
manufacturer: 1500
– The test may be performed between 20 °C and 30 °C. 1501
– If the test is performed below 25 °C, the results are normalized to 1502
25 °C. 1503
– If the test is performed above 25 °C, the results are not normalized to 1504
25 °C and the limits (Table 38) are not adjusted. In case the product fails 1505
the requirements, the test may be repeated at 25 °C. 1506
9.4 Safeguards against thermal energy sources 1507
Rationale: TS1 represents non-hazardous energy and thus, no safeguard is required. 1508
Because the energy is non-hazardous, and there is no possibility of an injury, 1509
it may be accessible by ordinary persons and there is no restriction on 1510
duration of contact under normal operating conditions. 1511
– 126 – IEC TR 62368-2:20xx © IEC 20xx
TS2 represents hazardous energy that could cause a burn injury if the 1512
contact duration is sufficient. Therefore, a safeguard is required to protect 1513
an ordinary person. A TS2 surface will not cause a burn immediately on 1514
contact. Because the burn injury from a TS2 surface is likely to be minor and 1515
pain or discomfort is likely to precede the occurrence of a burn injury, a 1516
physical safeguard may not be required if there is an effective means to 1517
inform the ordinary person about the risks of touching the hot surface. 1518
Thus, a TS2 safeguard may be one of the following: 1519
– a physical barrier to prevent access; or 1520
– an instructional safeguard to limit contact time below the threshold limit 1521
value versus time. 1522
TS3 represents hazardous energy that is likely to cause a burn injury 1523
immediately on contact. Because a TS3 surface is always likely to cause a 1524
burn immediately or before the expected reaction time due to pain or 1525
discomfort, an equipment safeguard is required. 1526
Unless otherwise specified in the document, ordinary persons need to be 1527
protected against all TS2 and TS3 energy sources. 1528
Instructed persons are protected by the supervision of a skilled person 1529
and can effectively employ instructional safeguards. Thus, equipment 1530
safeguards are not required for TS2 energy sources. An instructional 1531
safeguard may be required. 1532
TS3 energy sources can cause severe burns after very short contact 1533
duration. Thus, an instructional safeguard alone is not sufficient to protect 1534
an instructed person and an equipment safeguard is required. 1535
Skilled persons are protected by their education and experience and are 1536
capable of avoiding injury from TS3 sources. Thus, an equipment 1537
safeguard is not required to protect against TS3 energy sources. As a pain 1538
response may cause an unintentional reflex action even in skilled persons, 1539
an equipment or instructional safeguard may be required to protect against 1540
other class 3 energy sources adjacent to the TS3 energy source. 1541
9.5.1 Equipment safeguard 1542
Rationale: The function of the equipment safeguard is to limit the transfer of 1543
hazardous thermal energy. An equipment safeguard may be thermal 1544
insulation or other physical barrier. 1545
9.5.2 Instructional safeguard 1546
Rationale: An instructional safeguard will inform any person of the presence of 1547
hazardous thermal energy. Instructional safeguards may be in a text or 1548
graphical format and may be placed on the product or in the user 1549
documentation. In determining the format and location of the safeguard, 1550
consideration will be given to the expected user group, the likelihood of 1551
contact and the likely nature of the injury arising. 1552
9.6 Requirements for wireless power transmitters 1553
Rationale: Transmitters for near-field wireless power transfer can warm up foreign 1554
metallic objects that may be placed close to or on such a transmitter. To 1555
avoid burn due to high temperatures of the foreign metallic objects, the 1556
transmitter is tested as specified in 9.6.3. 1557
Far-field transmitters are generally called "power-beaming" and are not 1558
covered by these requirements. 1559
IEC TR 62368-2:20xx © IEC 20xx – 127 –
9.6.3 Test method and compliance criteria 1560
Rationale: While 9.6.3 specifies a maximum temperature of 70 °C, aluminum foil that 1561
reaches 80 °C is considered to comply with the requirement. The foil 1562
described in Figure 51 complies with the method allowed in in 9.3.1 based 1563
on the foil dimensions and low mass. 1564
This requirement is expected to align with the current Qi standard. 1565
Rationale: While many devices (servers, laptops, etc.) may be evaluated accurately for 1566
thermal burn injury using Table 38, foreign objects (FO’s) and other similar 1567
devices with low thermal mass and finite heat flux cannot be evaluated for 1568
thermal burn injury accurately. 1569
Both the experimental (thermesthesiometer method) and the computat ional 1570
(bio-heat equation model) in conjunction with the thermal burn thresholds 1571
from ASTM C 1055 provide for a greater level of accuracy than IEC Guide 1572
117 in assessing the potential risk for thermal burn injury from foreign objects 1573
by, 1574
- representing temperatures of the skin; 1575
- being material and geometry agnostic and; 1576
- considering quality of contact. 1577
Both methods take into account conservative assumptions that build in a 1578
margin of safety: 1579
- single finger (typically, finger and thumb would be used to pick up object); 1580
- no perfusion; 1581
- children/elderly reaction times; and 1582
- full thickness burn thresholds (vs +10˚C to obtain TS2). 1583
However, the findings from the experimental thermesthesiometer testing are 1584
being recommended due to the simplicity of the test method and to further 1585
promote future hazard-based testing using the thermesthesiometer. 1586
____________ 1587
Radiation 1588
10.2 Radiation energy source classifications 1589
Rationale: The first step in application is determining which energy sources represent 1590
potential radiation energy sources. Each energy source within the product 1591
can be classified as a radiation source based on the available energy within 1592
a circuit that can be used to determine the type of and number of safeguards 1593
required. The radiation energy source classifications include 1594
electromagnetic radiation energy sources. 1595
10.2.1 General classification 1596
Rationale: Radiation energy source classifications for X-rays and acoustics are given in 1597
Table 39. For optical radiation (“Lasers” and “Lamps and lamp systems”), the 1598
classification is defined by the IEC 60825 series or the IEC 62471 series as 1599
applicable. 1600
The general classification scheme specified in IEC 60825-1 is for laser products 1601
and is not a classification scheme for energy sources. It is not practical to classify 1602
laser radiation as RS. The classification according to IEC 60825-1 is used 1603
without modification. 1604
– 128 – IEC TR 62368-2:20xx © IEC 20xx
The classification schemes given in IEC 62471 and IEC 62471-5 specify a 1605
measurement distance (200 mm other than lamps intended for general lighting 1606
service and 1m for Image projectors) for the determination of the Risk Group. 1607
The Risk Group classification is not the actual source of the light. It is not 1608
practical to classify the radiation from lamps and lamp systems as RS. The 1609
classification according to IEC 62471 is used without modification. 1610
Abnormal operating conditions (see Clause B.3) and single fault conditions 1611
(see Clause B.4) need to be taken into account. If it becomes higher risk group 1612
when abnormal operating condition or single fault condition is applied, the 1613
higher risk group is applied for classification. 1614
Laser equipment classified as Class 1C is generally not within the scope of this 1615
document as it mainly applies to medical related applications. 1616
1617
IEC TR 62368-2:20xx © IEC 20xx – 129 –
Source: IEC 60825-1:2014 and IEC 62471-5 1618
Rationale: Image Projectors are evaluated using the process in Figure 45 in this 1619
document (see IEC 60825-1:2014 and IEC 62471-5). 1620
1621
Figure 45 – Flowchart for evaluation of Image projectors (beamers) 1622
10.2.2 & 10.2.3 RS1 and RS2 1623
Rationale: The output circuits of personal music players are not subject to single fault 1624
conditions, since the outputs will not increase to a level exceeding RS2 by 1625
nature of their highly integrated hardware designs. Typically, when 1626
component faults are introduced during testing (by bypassing or shorting of 1627
the audio related ICs), the outputs are either shut down, reduced in level or 1628
muted. 1629
10.2.4 RS3 1630
Rationale: RS3 energy sources are those that are not otherwise classified as RS1 or 1631
RS2. No classification testing is required as these energy sources can have 1632
unlimited levels. If an energy source is not measured, it assumed to be RS3 1633
for application of the document. A skilled person uses personal protective 1634
equipment or measures to reduce the exposure to safe limits when working 1635
where RS3 may be present. 1636
– 130 – IEC TR 62368-2:20xx © IEC 20xx
10.3 Safeguards against laser radiation 1637
Source: IEC 60825-1:2014, Annex A 1638
Rationale: IEC 60825-1:2014, Annex A provides an explanation of the different classes 1639
of products. Accessible emission limits (AELs) are generally derived from 1640
the maximum permissible exposures (MPEs). MPEs have been included in 1641
this informative annex to provide manufacturers with additional information 1642
that can assist in evaluating the safety aspects related to the intended use 1643
of their product, such as the determination of the nominal ocular hazard 1644
distance (NOHD). 1645
10.4 Safeguards against optical radiation from lamps and lamp systems (including 1646
LED types) 1647
Source: IEC 62471 and IEC TR 62471-2 1648
Rationale: Excessive optical radiation may damage the retina and cause vision 1649
impairment or blindness. The limits in the referenced documents are 1650
designed to reduce the likelihood of vision impairment due to optical 1651
radiation sources. 1652
For the Instructional safeguard for lamps and lamp systems, see IEC 1653
TR 62471-2. 1654
10.4.1 General Requirements 1655
Source: IEC 60065 1656
Rationale: The term ‘Electronic light effect equipment ’ has been used in IEC 60065 (see 1657
1.1) and is a commonly understood term for entertainment/stage effect 1658
lighting. 1659
10.5 Safeguards against X-radiation 1660
Source: IEC 60950-1; IEC 60065 1661
Rationale: Exposure to X-radiation will cause injury with excessive exposure over time. 1662
The limits in this document have been selected from IEC 60950-1 and 1663
IEC 60065 in order to limit exposure to that which is below harmful levels. 1664
10.6 Safeguards against acoustic energy sources 1665
Source: EN 60065:2002/A11:2008 1666
Rationale: The requirements of this subclause are made to protect against hearing loss 1667
due to long term exposure to high sound pressure levels. Therefore, the 1668
requirements are currently restricted to those kinds of products that are 1669
designed to be body-worn (of a size suitable to be carried in a clothing 1670
pocket) such that a user can take it with them all day long to listen to music 1671
(for example, on a street, in a subway, at an airport, etc.) . 1672
At this moment, the clause does not contain requirements against the hazard 1673
of short term exposure to very high sound pressure levels. 1674
Rationale: Significance of LAeq,T in EN 50332-1 and additional information 1675
LAeq,T is derived from the general formula for equivalent sound pressure: 1676
1677
IEC TR 62368-2:20xx © IEC 20xx – 131 –
This can be represented graphically as given in Figure 46 in this document. 1678
1679
Figure 46 – Graphical representation of LAeq,T 1680
In EN 50332-1 the measurement time interval (t2 – t1) is 30 s. 1681
In practice, and for the purposes of listening to personal music player 1682
content, LAeq,T has a time interval T (t2 – t1) in the order of minutes / hours 1683
and not seconds. 1684
Subclause 6.5 (Limitation value) of EN 50332-1:2000 acknowledges this fact 1685
and states that the 100-dB limit equates to a long time average of 90 dB 1686
LAeq,T. By using the IEC 60268-1 “programme simulation noise” test signal, 1687
this also takes the spectral content into account. 1688
The SCENHIR report states that 80 dB(A) is considered safe for an exposure 1689
time of 40 h/week. Most persons do not listen to 40 h/week to their personal 1690
music player. In addition, not all music tracks are at the same level of the 1691
simulated noise signal. Whilst modern music tends to be at around the same 1692
level, most of the available music is at a lower average level. Therefore, CLC 1693
TC 108/WG03 considered a value of 85 dB(A) to be safe for an overwhelming 1694
majority of the users of personal music players. 1695
10.6.3 Requirements for dose-based systems 1696
Rationale: The requirements on dose measurement have been developed to replace 1697
the requirements on maximum exposure as this better protects against 1698
hearing damage, which results from the combination of exposure and time 1699
(dose). For now, both systems can be used. See Table 16 in this document 1700
for a comparison. 1701
– 132 – IEC TR 62368-2:20xx © IEC 20xx
The dose-based system mainly uses the expression CSD, meaning 1702
"calculated sound dose". The value is based on the values mentioned in the 1703
EU Commission Decision 2009/490/EC, which stipulated that sound is safe 1704
when below 80 dB(A) for a maximum of 40 h per week. Therefore, the value 1705
of 100 % CSD corresponds to 80 dB(A) for 40 h. This also means that the 1706
safe limit in the dose measurement system is chosen to be lower than the 1707
safe limit in the maximum exposure system, as this specifies the safe limit 1708
at 85 dB(A). Consequently, a user will normally receive warnings earlier with 1709
the dose measurement system compared to the maximum exposure limit. In 1710
the maximum exposure system, the warning only had to be given once every 1711
20 h of listening when exceeding 85 dB(A). In the dose measurement system, 1712
the warning and acknowledgement has to be repeated at least at every 100 1713
% increase of the dose. In practice, this means that the warning is repeated 1714
at a comparable level of 83 dB(A), meaning a dose that corresponds to 1715
listening to 83 dB(A) for 40 h. At each next 100 % increase of dose level, the 1716
increase in corresponding dB’s is halved. Manufacturers have the freedom 1717
to give warnings earlier or ask for acknowledgement more frequently, but it 1718
has to be no later than at the next 100 % CSD increase since the last 1719
acknowledgement. For example, a device has provided the warning and 1720
acknowledgement at 100 % CSD. The manufacturer may choose to provide 1721
the next warning before 200 % CSD, for example, at 175 % CSD. If that is 1722
done, the next warning and acknowledgement may not be later than at 1723
275 % CSD. While there are no requirements for manufacturers to warn 1724
users before the 100 % CSD is reached, it is allowed to do so. Even more, it 1725
was felt by the document writers that it would be responsible behaviour if 1726
manufacturers warn consumers about the risks before the 100 % CSD level 1727
is reached. With the maximum exposure measurement, the maximum 1728
allowable sound output is 100 dB(A). With the dosage system, only a 1729
momentary exposure limit (MEL) is required when exceeding 100 dB(A) if a 1730
visual or audible warning is provided. Where a visual or audible MEL is not 1731
provided the maximum exposure measurement of 100 dB(A) is required. 1732
An essential element to educating the user and promoting safe listening 1733
habits is appropriate and useful guidance. This can be accomplished with 1734
informative CSD and MEL warnings that allow the user to understand the 1735
hazard, risks, and recommended action. Appropriate warnings about using 1736
the device and user instructions shall be provided. It should be noted that 1737
the CSD warning can be provided in various forms not limited to visual or 1738
audio. However, the MEL can only be provided visually or audibly. 1739
Consideration should be given to not over-message and annoy the user to 1740
the point where the message is neglected or evasive attempts (software 1741
hacks) to defeat the safe guards are taken. Extreme care should be gi ven 1742
when implementing the MEL warning and shall be at the discretion of the 1743
manufacturer. 1744
Manufacturers should be aware that digital sensitivity between PMP and 1745
unknown listening devices may result in excessive false positives. It is 1746
recommended industry to promote sharing of sensitivity data through a 1747
standardized means. 1748
IEC TR 62368-2:20xx © IEC 20xx – 133 –
Table 16 – Overview of requirements for dose-based systems 1749
Devices with Visual or Audible MEL EN 50332-3
SPL
before transition3
SPL
after
transition3
Dose
requirements
Dose
test method
Analog
known 1
> 85 dB(A) if ack,
< 100 dB(A) max
<80 dB(A) max
CSD warn at every 100 %
MEL warn at >100 dB(A)
cl 5.2
Analog
unknown 2
> 27 mV r.m.s. if ack,
< 150 mV r.m.s. max
< 15 mV rms max
CSD warn at every 100 % (= integrate. rms level 15 mV)
MEL warn at > 150 mV r.m.s.
cl 5.3
Digital
known 1
> 85 dB(A) if ack,
< 100 dB(A) max
< 80 dB(A) max
CSD warn at every 100 %
MEL warn at > 100 dB(A)
cl 5.2
Digital
unknown 2
> -25 dBFS if ack,
< 100 dB(A)4 max
< -30 dBFS max
CSD warn at every 100 % (= integrate level -30 dBFS)
< 100 dB(A) max or MEL warn at >
100 dB(A)4
TBD 5
Devices without MEL EN 50332-3
SPL
before transition3
SPL
after
transition3
Dose
requirements
Dose
test method
Analog
known 1
> 85 dB(A) if ack,
< 100 dB(A) max
< 80 dB(A) max
CSD warn at every 100 %
< 100 dB(A) max
cl 5.2
Analog
unknown 2
> 27 mV r.m.s. if ack,
< 150 mV r.m.s. max
< 15 mV r.m.s. max
CSD warn at every 100 % (= integrate rms level 15 mV)
< 150 mV r.m.s. max
cl 5.3
Digital
known 1
> 85 dB(A) if ack,
< 100 dB(A) max
< 80 dB(A) max
CSD warn at every 100 %
< 100 dB(A) max
cl. 5.2
Digital
unknown 2
> -25 dBFS if ack,
< 100 dB(A)4 max
< -30 dBFS max
CSD warn at every 100 % (= integrate level -30 dBFS)
< 100 dB(A)4 max
TBD 5
1 PMP includes or can detect listening device
2 PMP cannot detect listening device
3 Transition period allows migration to CSD before becoming mandatory
4 Defaults to 100 dB(A) gain cap from digital listening device. Need to develop industry wide protocol for digital (wired/wireless) listening device for PMPs to learn sensitivity lookup table.
5 Need to create test requirements with EN 50332-3. Otherwise, SPL requirements (30 dBFS gain cap) will be only feasible option.
1750
– 134 – IEC TR 62368-2:20xx © IEC 20xx
10.6.6.1 Corded listening devices with analogue input 1751
Rationale: The value of 94 dB(A) was chosen to align with current practice in EN 50332. 1752
In addition, some equipment may already start clipping at 100 dB(A). The 1753
value used does not influence the result of the measurement. 1754
_____________ 1755
Annex A Examples of equipment within the scope of this standard 1756
Rationale: A variety of personal electronic entertainment products/systems can be 1757
covered by this document, including self-propelling types sometimes known 1758
as entertainment robots, which typically contain electronic components and 1759
circuits that power the device's motion, a battery system and charger, the 1760
electric motor(s) and control systems, together with wireless 1761
communications and audio. When no other IEC or ISO document explicitly 1762
covers these products, they can be accommodated by IEC 62368-1. 1763
Examples of Entertainment-type Robots: 1764
1765
____________ 1766
Annex B Normal operating condition tests, abnormal operating condition 1767
tests and single fault condition tests 1768
General Equipment safeguards during various operating conditions 1769
Purpose: To identify the various operating and use conditions of equipment that are taken 1770
into account in the document. This clause was proposed to be added to the 1771
document as a Clause 0.12, but was agreed to be added to the Rationale instead. 1772
Rationale: Operating conditions 1773
Normal operating condition – A normal operating condition is a state with 1774
intended functionality of the equipment. All equipment basic safeguards, 1775
supplementary safeguards, and reinforced safeguards remain effective and 1776
comply with all required safeguard parameters. 1777
Abnormal operating condition – An abnormal operating condition is a 1778
temporary state. The equipment may have full, limited, or no functionality. The 1779
equipment generally requires operator intervention for restoration to normal 1780
operating condition. All equipment basic safeguards remain effective but may 1781
not need to comply with the required safeguard parameters. All equipment 1782
supplementary safeguards and reinforced safeguards remain effective and 1783
comply with the required safeguard parameters. 1784
IEC TR 62368-2:20xx © IEC 20xx – 135 –
Upon restoration of normal operating conditions, all basic safeguards comply 1785
with the required parameters unless the abnormal operating condition leads 1786
to a single fault condition, in which case the requirements for single fault 1787
condition apply. 1788
Reasonably foreseeable misuse condition – Reasonably foreseeable misuse 1789
is a form of an abnormal operating condition but may be either a temporary or 1790
a permanent state. The equipment may have full, limited, or no functionality. The 1791
equipment may not be capable of restoration to a normal operating condition. 1792
Reasonably foreseeable misuse may lead to a single fault condition, in which 1793
case equipment basic safeguards are not required to remain effective. All 1794
equipment supplementary safeguards and reinforced safeguards remain 1795
effective and comply with the required safeguard parameters. 1796
Other misuse condition – Other misuse (unreasonable or unforeseeable) may 1797
lead to a single or multiple fault condition, in which basic safeguards, 1798
supplementary safeguards and reinforced safeguards may not remain 1799
effective. The equipment may not be repairable to a normal operating 1800
condition. Safeguards against unreasonable or unforeseeable misuse are not 1801
covered by this document. 1802
Single fault condition – A single fault condition is a component or safeguard 1803
fault. The equipment may have full, limited or no functionality. The equipment 1804
requires repair to return to a normal operating condition. Equipment basic 1805
safeguards are not required to be functional, in this case the supplementary 1806
safeguards are functional and comply with the required safeguard parameters; 1807
or equipment supplementary safeguards are not required to be functional, in 1808
this case the basic safeguards are functional and comply with the required 1809
safeguard parameters. 1810
NOTE As a basic safeguard and a supplementary safeguard may be interchangeable, the 1811 concept of which safeguard is not required to remain effective can be reversed. 1812
B.1.5 Temperature measurement conditions 1813
Source: IEC 60950-1 1814
Purpose: To determine whether the steady state temperature of a part or material does or 1815
does not exceed the temperature limit for that part or material. 1816
Rationale: Steady state is considered to exist if the temperature rise does not exceed 3 K in 1817
30 min. If the measured temperature is less than the required temperature limit 1818
minus 10 %, steady state is considered to exist if the temperature rise does not 1819
exceed 1 K in 5 min. 1820
Temperature rise follows an exponential curve and asymptotically approaches 1821
thermal equilibrium. The rate of temperature rise can be plotted as a function of 1822
time and used to guess the value at steady state. The actual steady state value 1823
needs to be accurate only to the extent to prove whether the value will exceed 1824
the limit or not. 1825
Steady-state conditions of typical electronic devices have many different 1826
temperatures, so thermal equilibrium does not exist. 1827
The resistance method may be used to measure temperature rises of windings 1828
unless the windings are non-uniform or if it is difficult to make the necessary 1829
connections, in which case the temperature rise is determined by other means. 1830
When the resistance method is used, the temperature rise of a winding is 1831
calculated from the formula: 1832
Δt = 1
12
R
RR − (k + t1) – (t2 – t1) 1833
where: 1834
Δt is the temperature rise of the winding; 1835
– 136 – IEC TR 62368-2:20xx © IEC 20xx
R1 is the resistance at the beginning of the test; 1836
R2 is the resistance at the end of the test; 1837
k is equal to: 1838
• 225 for aluminium windings and copper/aluminium windings with an 1839
aluminium content ≥ 85 %, 1840
• 229,75 for copper/aluminium windings with a copper content 15 % 1841
to 85 %, 1842
• 234,5 for copper windings and copper/aluminium windings with an 1843
copper content ≥ 85 %; 1844
t1 is the room temperature at the beginning of the test; 1845
t2 is the room temperature at the end of the test. 1846
NOTE It is recommended that the resistance of windings at the end of the test be determined by 1847 taking resistance measurements as soon as possible after switching off and then at short intervals 1848 so that a curve of resistance against time can be plotted for ascertaining the resistance at the 1849 instant of switching off. 1850
B.1.6 Specific output conditions 1851
Examples For example, connecting the intended representative worst-case load or external 1852
powered devices, and repeating with the appropriate resistive load and/or fault 1853
conditions. This is critical for determining characteristics such as output voltage 1854
and current for ES and PS classifications, use on building and other wiring, 1855
Annex Q, as well as proper loading for heating tests. These examples are not 1856
necessarily all inclusive. 1857
B.2.3 Supply Voltage 1858
Rationale: Where a test subclause does not require the most unfavourable supply voltage, 1859
the supply voltage is the value of the rated voltage or any value in the rated 1860
voltage range. This is applicable to the tests in abnormal operation condition 1861
and single fault condition as well. 1862
B.2 – B.3 – B.4 Operating modes 1863
See Figure 47 in this document for an overview of operating modes. 1864
1865
Figure 47 – Overview of operating modes 1866
IEC TR 62368-2:20xx © IEC 20xx – 137 –
B.4.4 Functional insulation 1867
Rationale: The use of a functional insulation is only acceptable when the circuit does not 1868
exceed its limits of its class under normal operating conditions and abnormal 1869
operation conditions and single fault conditions of a component not serving 1870
as a safeguard (see 5.2.1.1 and 5.2.1.2). Otherwise a basic 1871
insulation/safeguard would be required. 1872
If the functional insulation possesses a certain quality (clearance, creepage 1873
distances, electric strength) comparable to a basic safeguard, it is acceptable 1874
to omit short-circuit. 1875
This cannot be compared to the short-circuiting of a basic safeguard as required 1876
in B.4.1, because this basic safeguard is a required one, while the added quality 1877
of the functional insulation is not required. 1878
If the short-circuiting of this functional insulation with added quality would lead 1879
to a changing of the class, the functional insulation was wrongly chosen, and 1880
a basic safeguard would have been required. 1881
B.4.8 Compliance criteria during and after single fault conditions 1882
Source: IEC 60065 1883
Rationale: During single fault conditions, short term power is delivered in components 1884
which might be outside the specifications for that component. As a result, the 1885
component might interrupt. During the interruption, sometimes a small flame 1886
escapes for a short period of time. The current practice in IEC 60065 allows 1887
these short term flames for a maximum period of 10 s. This method has been 1888
successfully used for products in the scope of this document for many years. 1889
____________ 1890
Annex C UV Radiation 1891
C.1.1 General 1892
Rationale: UV radiation can affect the physical properties of thermoplastic materials and so 1893
it can have a consequential effect on components protecting body parts from a 1894
range of injurious energy sources. 1895
____________ 1896
Annex D Test generators 1897
Source: ITU-T Recommendation K.44 1898
Rationale: The circuit 1 surge in Table D.1 is typical of voltages induced into telephone 1899
wires and coaxial cables in long outdoor cable runs due to lightning strikes to 1900
their earthing shield. 1901
The circuit 2 surge is typical of earth potential rises due to either lightning strikes 1902
to power lines or power line faults. 1903
The circuit 3 surge is typical of voltages induced into antenna system wiring due 1904
to nearby lightning strikes to earth. 1905
Figure D.3 provides a circuit diagram for high energy impulse to test the high-1906
pressure lamps. 1907
____________ 1908
– 138 – IEC TR 62368-2:20xx © IEC 20xx
Annex E Test conditions for equipment containing audio amplifiers 1909
Source: IEC 60065:2011 1910
Rationale The proposed limits for touch voltages at terminals involving audio signals that 1911
may be contacted by persons have been extracted without deviation from 1912
IEC 60065:2011, 9.1.1.2 a). Under single fault conditions, 11.1 of 1913
IEC 60065:2011 does not permit an increase in acceptable touch voltage limits. 1914
The proposed limits are quantitatively larger than the accepted limits of Table 4, 1915
but are not considered dangerous for the following reasons: 1916
– the output is measured with the load disconnected (worst-case load); 1917
– defining the contact area of connectors and wiring is very difficult due to 1918
complex shapes. The area of contact is considered small due to the 1919
construction of the connectors; 1920
– normally, it is recommended to the user, in the instruction manual provided 1921
with the equipment, that all connections be made with the equipment in the 1922
“off” condition. 1923
– in addition to being on, the equipment would have to be playing some program 1924
at a high output with the load disconnected to achieve the proposed limits. 1925
Although possible, it is highly unlikely. Historically, no known cases of injury 1926
have been recorded for amplifiers with a non-clipped output less than 71 V 1927
RMS. 1928
– the National Electrical Code (USA) permits accessible terminals with a 1929
maximum output voltage of 120 V RMS. 1930
It seems that the current normal condition specified in IEC 60065 is appropriate 1931
and a load of 1/8 of the non-clipped output power should be applied to the 1932
multichannel by adjusting the individual channels. 1933
___________ 1934
Annex F Equipment markings, instructions, and instructional safeguards 1935
F.3 Equipment markings 1936
Source: EC Directives such as 98/37/EC Machinery Directive, Annex I, clause 1.7.3 1937
marking; NFPA 79:2002, clause 17.4 nameplate data; CSA C22.1 Canadian 1938
Electric Code, clause 2-100 marking of equipment give organized requirements. 1939
The requirements here are principally taken from IEC 60065 and IEC 60950 1940
series. 1941
F.3.3.2 Equipment without direct connection to mains 1942
Source: IEC 60950-1 1943
Purpose: To clarify that equipment powered by mains circuits, but not directly connected 1944
to the mains using standard plugs and connectors, need not have an electrical 1945
rating. 1946
Rationale: Only equipment that is directly connected to the mains supplied from the building 1947
installation needs to have an electrical rating that takes into account the full load 1948
that may be connected to the building supply outlet. For equipment that is daisy-1949
chained or involves a master-slave configuration, only the master unit or the first 1950
unit in the daisy chain needs to be marked. 1951
IEC TR 62368-2:20xx © IEC 20xx – 139 –
F.3.6.2 Equipment class marking 1952
Rationale: For compliance with EMC standards and regulations, more and more class II 1953
products are equipped with a functional earth connection. The latest version of 1954
the basic safety publication IEC 61140 allows this construction. On request of 1955
IEC TC 108, IEC SC3C has developed a new symbol, which is now used in 1956
IEC 62368-1. 1957
Rationale: Equipment having a class II construction, but that is provided with a class I input 1958
connector with the internal earthing pin not connected is also considered to be 1959
a class II equipment with functional earth. The class I connector is used to 1960
provide a more robust connection means, which is considered to be a functional 1961
reason for the earth connection. 1962
F.4 Instructions 1963
Rationale: The dash requiring graphical symbols placed on the equipment and used as an 1964
instructional safeguard to be explained does not apply to symbols used for 1965
equipment classification (see F.3.6). 1966
Markings on the equipment are reproduced in the instruction manual. Any 1967
translation of the wording on the marking is suggested to be provided in the 1968
manual. 1969
F.5 Instructional safeguards 1970
Rationale: When a symbol is used, the triangle represents the words “Warning” or “Caution”. 1971
Therefore, when the symbol is used, there is no need to also use the words 1972
“Warning” or “Caution”. However, when only element 2 is used, the text needs 1973
to be preceded with the words. 1974
___________ 1975
Annex G Components 1976
G.1 Switches 1977
Source: IEC 61058-1 1978
Rationale: A contact should not draw an arc that will cause pitting and damage to the 1979
contacts when switching off and should not weld when switching on if located in 1980
PS2 or PS3 energy sources. A PS1 energy source is not considered to have 1981
enough energy to cause pitting and damage to the contacts. Both these actions 1982
(pitting and damage) may result in a lot of heating that may result in fire. There 1983
should be sufficient gap between the two contact points in the off position which 1984
should be equal to the reinforced clearance if the circuit is ES3 and basic 1985
clearance if the circuit is ES2 or ES1 (we may have an arcing PIS or resistive 1986
PIS in an ES1 circuit) in order to avoid shock and fire hazards. The contacts 1987
should not show wear and tear and pitting after tests simulating lifetime 1988
endurance; and overload tests and operate normally after such tests. 1989
– 140 – IEC TR 62368-2:20xx © IEC 20xx
G.2.1 Requirements 1990
Source: IEC 61810-1, for electromechanical relays controlling currents exceeding 0,2 A 1991
AC or DC, if the voltage across the open relay contacts exceeds 35 V peak AC 1992
or 24 V DC 1993
Rationale: A contact should not draw an arc that will cause pitting and damage to the 1994
contacts when switching off and should not weld when switching on if located in 1995
PS2 or PS3 energy sources. A PS1 energy source is not considered to have 1996
enough energy to cause pitting and damage to the contacts. Both these actions 1997
(pitting and damage) may result in lot of heating that may result in fire. There 1998
should be sufficient gap between the two contact points in the off position which 1999
should be equal to the reinforced clearance if the circuit is ES3 and basic 2000
clearance if the circuit is ES2 or ES1 (we may have an arcing PIS or resistive 2001
PIS in an ES1 circuit) in order to avoid shock and fire hazards. The contacts 2002
should not show wear and tear and pitting after tests simulating lifetime 2003
endurance, and overload tests and operate normally after such tests. 2004
G.3.3 PTC thermistors 2005
Source: IEC 60730-1:2006 2006
Rationale: PTC thermistor for current limitation is always connected in series with the load 2007
to be protected. 2008
In a non-tripping stage, the source voltage is shared by the load impedance and 2009
the resistance of PTC thermistor (which is close to the zero-power resistance at 2010
25 °C). In order to define the power dissipation of the PTC thermistor in this 2011
stage, the source voltage and the load impedance are also important 2012
parameters. 2013
In a tripping stage, the PTC thermistor heats up by itself and increases the 2014
resistance value to protect the circuit. The zero-power resistance at 25 °C is no 2015
longer related to the power dissipation of PTC thermistors in this stage. The 2016
power dissipation of PTC thermistor in this stage depends on factors such as 2017
mounting condition and ambient temperature. 2018
In either stage, some parameters other than the rated zero-power resistance at 2019
an ambient temperature of 25 C are required to calculate the power dissipation 2020
of PTC thermistor. 2021
The tripping stage is more hazardous than the non-tripping stage because the 2022
temperature of the PTC thermistor in the tripping stage becomes much higher 2023
than in the non-tripping stage. 2024
Figure 48 in this document shows “Voltage-Current Characteristics”. The blue 2025
dotted lines show the constant power dissipation line. It shows that the power at 2026
the operation point, during the tripping stage, is the highest power dissipation. 2027
This point is calculable with “Ires x Umax” of IEC 60738-1:2006, 3.38. 2028
(Umax = maximum voltage, Ires = residual current, measured by the PTC 2029
manufacturers.) 2030
2031
IEC TR 62368-2:20xx © IEC 20xx – 141 –
2032
Figure 48 – Voltage-current characteristics (Typical data) 2033
If the PTC is installed in a PS1 circuit, the power dissipation of the PTC will be 2034
15W or less. In this state, the PTC is not considered to be a resistive PIS, 2035
regardless of its Ires x Umax. 2036
A PTC with a size of less than 1 750 mm3 is not considered to be a resistive 2037
PIS, described in 6.3.1, 6.4.5.2 and 6.4.6. 2038
G.3.4 Overcurrent protective devices 2039
Rationale: Just like any other safety critical component, protective devices are not allowed 2040
to be used outside their specifications, to guarantee safe and controlled 2041
interruption (no fire and explosion phenomena’s) during single fault 2042
conditions (short circuits and overload conditions) in the end products. This 2043
should include having a breaking capacity capable of interrupting the maximum 2044
fault current (including short-circuit current and earth fault current) that can 2045
occur. 2046
G.3.5 Safeguard components not mentioned in G.3.1 to G.3.4 2047
Rationale: Protective devices shall have adequate ratings, including breaking capacity. 2048
G.5.1 Wire insulation in wound components 2049
Source: IEC 60317 series, IEC 60950-1 2050
Purpose: Enamel winding wire is acceptable as basic insulation between external circuit 2051
at ES2 voltage level and an ES1. 2052
– 142 – IEC TR 62368-2:20xx © IEC 20xx
Rationale: ES1 becomes ES2 under single fault conditions. The enamel winding wires 2053
have been used in telecom transformers for the past 25 years to provide basic 2054
insulation between TNV and SELV. The winding wire is type tested for electric 2055
strength for basic insulation in addition to compliance with IEC 60317 series of 2056
standards. Enamel is present on both input and output winding wires and 2057
therefore, the possibility of having pinholes aligned is minimized . The finished 2058
component is tested for routine test for the applicable electric strength test 2059
voltage. 2060
G.5.2 Endurance test 2061
Source: IEC 60065:2011, 8.18 2062
Rationale: This test is meant to determine if insulated winding wires without additional 2063
interleaved insulation will isolate for their expected lifetime. The endurance test 2064
comprises a heat run test, a vibration test and a humidity test. After those tests, 2065
the component still has to be able to pass the electric strength test. 2066
G.5.2.2 Heat run test 2067
Rationale: In Table G.2, the tolerance is ± 5 °C. It is proposed that the above tolerance be 2068
the same. 2069
G.5.3 Transformers 2070
Source: IEC 61558-1, IEC 60950-1 2071
Rationale: Alternative requirements have been successfully used with products in the scope 2072
of this document for many years. 2073
G.5.3.3 Transformer overload tests 2074
G.5.3.3.2 Compliance criteria 2075
Source: IEC 61558-1, IEC 60950-1 2076
Rationale: The transformer overload test is conducted mainly to check the deterioration by 2077
thermal stress due to overload conditions, and the compliance criteria is to check 2078
whether the temperature of the windings are within the allowable limits specified 2079
in Table G.3. For that purpose, the maximum temperature of windings is 2080
measured. 2081
However, in the actual testing condition, the windings or other current carrying 2082
parts of the transformer under testing may pose temperature higher than the 2083
measured value due to uneven temperature, such as a windings isolated from 2084
the mains (see third paragraph of G.5.3.3.2), so that such spot exposed to higher 2085
temperature may have thermal damage. 2086
In order to evaluate such potential damage, electric strength test after the 2087
overload condition is considered necessary. 2088
Both of the source documents require the electric strength test after the overload 2089
test. 2090
Table G.3 Temperature limits for transformer windings and for motor windings 2091
(except for the motor running overload test) 2092
Although the document does not clearly state it, the first row should also be used 2093
in cases where no protective device is used or the component is inherently 2094
protected by impedance. 2095
IEC TR 62368-2:20xx © IEC 20xx – 143 –
For example, in the test practice of a switch mode power supply, a transformer 2096
is to be intentionally loaded to the maximum current without a protection 2097
operating. In this case, the method of protection is NOT ‘inherently’ or 2098
‘impedance’, but other sets of limits are specified with the time of protection to 2099
operate. In reality, a switch mode transformer tested with a maximum load 2100
attempting the protection not to operate, but the limits in first row have been 2101
considered appropriate, because the thermal stress in that load ing condition 2102
continues for a long time (no ending). Thus, the lowest limit should be applied. 2103
In this context, the application of the first row limit shall be chosen according to 2104
the situation of long lasting overloading rather than the type of protection. 2105
G.5.3.4 Transformers using fully insulated winding wire (FIW) 2106
Source: IEC 60317-56, IEC 60317-0-7 2107
Rationale: In 2012, IEC TC 55 published IEC 60317-56 and IEC 60317-0-7, Specification 2108
for Particular Types of Winding Wires – Part 0-7: General requirements – Fully 2109
insulated (FIW) zero-defect enamelled round copper wire with nominal conductor 2110
diameter of 0,040 mm to 1,600 mm. 2111
This wire is more robust enameled-coated wire used with minimal amounts of 2112
interleaved insulation. It is another step in the advancement of technology to 2113
allow manufacturers to design smaller products safely. 2114
IEC TC 96 was the first TC to incorporate the use of FIW in their safety 2115
documents for switch mode power supply units, IEC 61558-2-16. Since 2116
IEC 62368-1:2018 references in G.5.3.1 IEC 61558-1-16 as one of the 2117
acceptable documents for transformers used in switch mode power supplies, 2118
FIW already is acceptable in equipment investigated to IEC 62368-1 that use an 2119
IEC 61558-1-16 compliant transformer. 2120
FIW may not be accessible, whether it has basic insulation, double insulation 2121
or reinforced insulation. Note that this differs from other parts of the document 2122
that permit supplementary insulation and reinforced insulation to be 2123
accessible to an ordinary person. The reason is that this kind of wire is fragile 2124
and the insulation could easily be damaged when it is accessible to an ordinary 2125
person. 2126
G.5.4 Motors 2127
Source: IEC 60950-1 2128
Rationale: Requirements have been successfully used with products in the scope of this 2129
document for many years. 2130
G.7 Mains supply cords 2131
Source: IEC 60245 (rubber insulation), IEC 60227 (PVC insulation), IEC 60364-5-54 2132
Rationale: Mains connections generally have large normal and fault energy available from 2133
the mains circuits. It is also necessary to ensure compatibility with installation 2134
requirements. 2135
Stress on mains terminal that can result in an ignition source owing to lose or 2136
broken connections shall be minimized. 2137
Terminal size and construction requirements are necessary to ensure adequate 2138
current-carrying capacity and reliable connection such that the possibility of 2139
ignition is reduced. 2140
Wiring flammability is necessary to reduce flame propagation potential should 2141
ignition take place. 2142
Conductor size requirements are necessary to ensure adequate current-carrying 2143
capacity and reliable connection such that the possibility of ignition is reduced. 2144
– 144 – IEC TR 62368-2:20xx © IEC 20xx
Alternative cords to rubber and PVC are accepted to allow for PVC free 2145
alternatives to be used. At the time of development of the document, IEC TC20 2146
had no published documents available for these alternatives. However, several 2147
countries do have established requirements. Therefore, it was felt that these 2148
alternatives should be allowed. 2149
G.7.3 – G.7.5 Mains supply cord anchorage, cord entry, bend protection 2150
Source: IEC 60065:2011 and IEC 60950-1:2013 2151
Purpose: Robustness requirements for cord anchorages 2152
Rationale: The requirements for cord anchorages, cord entry, bend protection and cord 2153
replacement are primarily based on 16.5 and 16.6 of IEC 60065:2011 and 3.2.6 2154
and 3.2.7 of IEC 60950-1:2013. 2155
Experience shows that 2 mm displacement is the requirement and if an 2156
appropriate strain relief is used there is no damage to the cord and therefore, no 2157
need to conduct an electric strength test in most cases. This method has been 2158
successfully used for products in the scope of these documents for many years. 2159
G.8 Varistors 2160
Source: IEC 61051-1 and IEC 61051-2 2161
Rationale: The magnitude of external transient overvoltage (mainly at tributed to lightning), 2162
to which the equipment is exposed, depends on the location of the equipment. 2163
This idea is described in Table 14 of IEC 62368-1:2018 and also specified in 2164
IEC 60664-1. 2165
In response to this idea, IEC 61051-2 has been revised taking into account the 2166
location of the equipment, which also influences the requirement for the varistors 2167
used in the equipment. 2168
The combination pulse test performed according to G.8.2 of IEC 62368-1:2018 2169
can now refer to the new IEC 61051-2 with Amendment 1. 2170
G.9 Integrated circuit (IC) current limiters 2171
Source: IEC 60730-1, IEC 60950-1 2172
Rationale: Integrated circuits (containing numerous integral components) are frequently 2173
used for class 1 and class 2 energy source isolation and, more frequently ( for 2174
example, USB or PoE), for functions such as current limiting. 2175
IEC 60335 series already has requirements for “electronic protection devices,” 2176
where conditioning tests such as EMF impulses are applied to such ICs, and the 2177
energy source isolation or current limiting funct ion is evaluated after conditioning 2178
tests. When such energy isolation or current limitation has been proven reliable 2179
via performance, pins on the IC associated with this energy isolation or limitation 2180
are not shorted. 2181
For ICs used for current limitation, two test programs were used in 2182
IEC 60950-1:2009. An additional program was developed in IEC 62368-1:2010. 2183
It was felt that all three programs were considered adequate. Therefore , the 2184
three methods were kept. 2185
An Ad Hoc formed at the March 2015, Northbrook HBSDT meeting revised this 2186
test program with the following guiding principles: 2187
a) Streamline the number of tests in overall test program to concentrate on 2188
those tests and conditions that most likely will identify deficiencies in IC 2189
Current Limiter design from a safety perspective, such as allowing more 2190
current to flow than designed for. Some of the existing conditions are 2191
redundant or have questionable value identifying such deficiencies. 2192
b) Focus on test conditions that are applicable for semiconductor devices 2193
rather than test conditions more suited for tradit ional electro-mechanical 2194
IEC TR 62368-2:20xx © IEC 20xx – 145 –
devices. For example, 10 000-cycle testing has more applicability to 2195
electro-mechanical devices (in relation to parts wearing out) versus 2196
semiconductor devices (such as IC current limiters). 2197
c) Combine test conditions when justified to increase efficiency when 2198
conducting individual tests, also trying to make the testing more compatible 2199
with automated testing processes (for example, combine individual 2200
temperature tests as individual sub-conditions of other required tests). 2201
Table G.10 provides the specific performance test program for IC current 2202
limiters. 2203
– Input loading to the device should be representative of the manufacturer’s 2204
IC specification (as typically communicated in the IC application notes for 2205
the particular device). 2206
– Output loading is intended to represent a short circuit condition (0 Ω shunt), 2207
with parallel capacitive loading (470 µF +/- 20 %) to better accommodate 2208
on/off cycling. 2209
See Figure 49 in this document for additional detail. 2210
2211
Figure 49 – Example of IC current limiter circuit 2212
Regarding the 250 VA provision, this provision is intended to mean that the usual 2213
test power source has 250 VA capability as long as the IC is designed for 2214
installation in a system with a source of 250 VA or larger. If the power source 2215
capability is intended to be less than 250 VA, then the manufacturer must specify 2216
so, or test in the end product. Testing at 250 VA is intended to include 250 VA 2217
or larger sources because the test program is covering relatively small and low-2218
voltage silicon devices – if these devices pass at 250 VA they likely would pass 2219
at higher VA too since they are not electro-mechanical. Also, this allows for more 2220
practical associated certification test programs. 2221
Also, to avoid recertification of existing components, IC current limiters that met 2222
a previous legacy test program (G.9.2, G.9.3 or G.9.4) are an equivalent level of 2223
safety as the proposed rewritten Clause G.9, primarily because Clause G.9 is 2224
derivation of the legacy requirements. Therefore, IC current limiters that comply 2225
with the legacy test program should not need to be reinvestigated to the latest 2226
document that includes this revised Clause G.9. However, this is a certification 2227
consideration outside the scope of this technical committee. 2228
– 146 – IEC TR 62368-2:20xx © IEC 20xx
G.11 Capacitors and RC units 2229
Source: IEC 60384-14:2005 2230
Rationale: Table G.11: Test voltage values aligned with those used in IEC 60384-14 (Tables 2231
1, 2 and 10 of IEC 60384-14:2005). 2232
Table G.12: Minimum number of Y capacitors based on required withstand 2233
voltage of Table 25 of IEC 62368-1:2018. 2234
Table G.13: Maximum voltage that can appear across a Y capacitor based on 2235
the peak value of the working voltage of Table 26 of IEC 62368-1:2018. 2236
Table G.14: Minimum number of Y capacitors based on the test voltages (due to 2237
temporary overvoltages) of Table 27 of IEC 62368-1:2018. 2238
Table G.15: Minimum number of X capacitors (line to line or line to neutral) based 2239
on the mains transient withstand voltage of Table 13 of IEC 62368-1:2018. 2240
All of the above are aligned with the requirements of IEC 60384-14. 2241
G.13 Printed boards 2242
Source: IEC 60950-1 or IEC 60664-3:2003. 2243
Purpose: To provide details for reliable construction of PCBs. 2244
Rationale: This proposal is based on IEC 60664-3 and the work of IBM and UL in testing 2245
coatings on printed boards when using coatings to achieve insulation 2246
coordination of printed board assemblies. Breakdown voltages of more than 2247
8 000 V for 0,025 mm were routinely achieved in this program. 2248
These parts have multiple stresses on the materials with limited separation 2249
between conductors. This section is taken from IEC 60950-1, where these 2250
requirements have been used for many years. 2251
G.13.6 Tests on coated printed boards 2252
Purpose: Prevent breakdown of the insulation safeguard. 2253
Rationale: Avoid pinholes or bubbles in the coating or breakthrough of conductive tracks at 2254
corners. 2255
G.14 Coatings on component terminals 2256
Source: IEC 60950-1 and IEC 60664-3 2257
Purpose: The mechanical arrangement and rigidity of the terminations are adequate to 2258
ensure that, during normal handling, assembly into equipment and subsequent 2259
use, the terminations will not be subject to deformation which would crack the 2260
coating or reduce the separation distances between conductive parts. 2261
Rationale: The terminations are treated like coated printed boards (see G.13.3) and the 2262
same separation distances apply. 2263
This section is taken from IEC 60950-1 where these requirements have been 2264
used for many years. 2265
G.15 Pressurized liquid filled components 2266
Source: IEC 60950-1, IEC 61010-1, UL 2178, UL 1995 2267
Purpose: Avoid spillage of liquids resulting in electric shock hazard 2268
Rationale: The requirements apply to devices that contain less than 1 l of liquid. A leak in 2269
the system may result in a shock hazard and therefore, needs to be properly 2270
addressed. A leak is not desirable and therefore, a strict performance criterion 2271
is proposed. Requirements were developed based on the following description 2272
of a typical system using liquid filled heat sinks. If a different type of sys tem is 2273
used, then the requirements need to be re-evaluated. 2274
IEC TR 62368-2:20xx © IEC 20xx – 147 –
Liquid filled heat-sink system (LFHS): a typical system consists of a heat 2275
exchanger, fan, pump, tubing, fittings and cold plate or radiator type heat 2276
exchanger. The liquid filled heat sink comes from the vendor already charged, 2277
sealed; and is installed and used inside the equipment (small type, typically 2278
found in cell stations and computing devices or other types of systems). The 2279
proposed requirements are based on a LFHS being internal to a unit, 2280
used/installed adjacent/over ES1 circuits, in proximity to an enclosed power 2281
supply (not open frame). 2282
The liquid-filled heat components are used in desktop units or stationary 2283
equipment and in printers. These are not used in any portable equipment where 2284
orientation may change (unless the product is tested in all such orientations. If 2285
the liquid heat sink system is of a sealed type construction, then the system is 2286
orientation proof (this should not be a concern but a good engineering practice 2287
is that the pump does not become the high point in the system). 2288
Following assumptions are used: 2289
– The tubing is a single-layered metal (copper or aluminium) or non-metallic 2290
construction. If it is non-metallic, flammability requirements will apply. 2291
– The fittings are metal. If it is non-metallic, flammability requirements will 2292
apply. 2293
– Working pressure is determined under normal operating conditions and 2294
abnormal operating conditions and construction (tubing, fitting, heat 2295
exchanger, any joints, etc.) is suitable for this working pressure; 2296
– The volume of the liquid is reasonable (less than 1 000 ml). 2297
– The fluid does not cause corrosion and is not flammable (for example, 2298
corrosion resistant and non-flammable liquid). 2299
– The liquid is non-toxic as specified for the fluid material. 2300
___________ 2301
Annex H Criteria for telephone ringing signals 2302
H.2 Method A 2303
Source: IEC 62949:2016. 2304
Rationale: Certain voltages within telecommunication networks often exceed the steady 2305
state, safe-to-touch limits set within general safety documents. Years of practical 2306
experience by world-wide network operators have found ringing and other 2307
operating voltages to be electrically safe. Records of accident statistics indicate 2308
that electrical injuries are not caused by operating voltages. 2309
Access to connectors carrying such signals with the standard test finger is 2310
permitted, provided that inadvertent access is unlikely. The likelihood of 2311
inadvertent access is limited by forbidding access with the test probe Figure 2C 2312
of IEC 60950-1:2013 that has a 6 mm radius tip. 2313
This requirement ensures that: 2314
– contact by a large part of the human body, such as the back of the hand, is 2315
impossible; 2316
– contact is possible only by deliberately inserting a small part of the body, 2317
less than 12 mm across, such as a fingertip, which presents a high 2318
impedance; 2319
– the possibility of being unable to let-go the part in contact does not arise. 2320
– 148 – IEC TR 62368-2:20xx © IEC 20xx
This applies both to contact with signals arriving from the network and to signals 2321
generated internally in the equipment, for example, ringing signals for extension 2322
telephones. By normal standards, these internally generated signals would 2323
exceed the voltage limits for accessible parts, but the first exemption in 2324
IEC 60950-1 states that limited access should be permitted under the above 2325
conditions. 2326
Ventricular fibrillation of the heart is considered to be the main cause of death 2327
by electric shock. The threshold of ventricular fibrillation (Curve A) is shown in 2328
Figure 50 in this document and is equivalent to curve c1 of IEC TS 60479-1:2005, 2329
Figure 14. The point 500 mA/100 ms has been found to correspond to a 2330
fibrillation probability of the order of 0,14 %. The let go limit (Curve B) is 2331
equivalent to curve 2 of IEC TS 60479-1:2005, Figure 14. Some experts consider 2332
curve A to be the appropriate limit for safe design, but use of this curve is 2333
considered as an absolute limit. 2334
2335
Figure 50 – Current limit curves 2336
Contact with telecommunication operating voltages (EN 41003) 2337
Total body impedance consists of two parts, the internal body resistance of blood 2338
and tissue and the skin impedance. Telecommunication voltages hardly reach 2339
the level where skin impedance begins to rapidly decrease due to breakdown. 2340
The skin impedance is high at low voltages, its value varying widely. The effects 2341
of skin capacitance are negligible at ringing frequencies. 2342
IEC TS 60479-1 body impedance figures are based upon a relatively large 2343
contact area of 50 cm2 to 100 cm2, which is a realistic value for mains operated 2344
domestic appliances. Practical telecommunication contact is likely to be much 2345
less than this, typically 10 cm2 to 15 cm2 for uninsulated wiring pliers or similar 2346
tools and less than 1 cm2 for finger contact with pins of a telephone wall socket. 2347
For contact with thin wires, wiring tags or contact with tools where fingers move 2348
beyond insulated handles, the area of contact will again be of the order of 1 cm2 2349
or less. These much smaller areas of contact with the body produce significantly 2350
higher values of body impedance than the IEC TS 60479 figures. 2351
In IEC 60950-1, a body model value of 5 k is used to provide a margin of safety 2352
compared with the higher practical values of body impedance for typical 2353
telecommunication contact areas. 2354
IEC TR 62368-2:20xx © IEC 20xx – 149 –
The curve B' [curve C1 of IEC TS 60479-1:2005, Figure 22 (curve A in this 2355
document)] used within the hazardous voltage definition is a version of curve B 2356
modified to cover practical situations, where the current limit is maintained 2357
constant at 16 mA above 1 667 ms. This 16 mA limit is still well within the 2358
minimum current value of curve A. 2359
The difficulties of defining conditions that will avoid circumstances that prevent 2360
let-go have led to a very restricted contact area being allowed. 2361
Contact with areas up to 10 cm2 can be justified and means of specifying this 2362
and still ensuring let-go are for further study. 2363
H.3 Method B 2364
Source: This method is based on USA CFR 47 ("FCC Rules") Part 68, Sub part D, with 2365
additional requirements that apply under fault conditions. 2366
___________ 2367
Annex J Insulated winding wires for use without interleaved insulation 2368
Source: IEC 60851-3:2009, IEC 60851-5:2008, IEC 60851-6:1996 2369
Purpose: Winding wires shall withstand mechanical, thermal and electrical stress during 2370
use and manufacturing. 2371
Rationale: Test data indicates that there is not a major difference between rectangular wires 2372
and round wires for electric strength after the bend tests. Therefore, there is no 2373
reason to not include them. 2374
Subclause 4.4.1 of IEC 60851-5:2008 covers only solid circular or stranded 2375
winding wires as a twisted pair can easily be formed from round wires. It is 2376
difficult to form a twisted pair from square or rectangular winding wires. 2377
IEC 60851-5:2008, 4.7 addresses a test method that can be used for square and 2378
rectangular wires. A separate test method for square and rectangular wires has 2379
been added. The test voltage is chosen to be half of the twisted pair as a single 2380
conductor is used for the testing. 2381
In addition, the edgewise bend test is not required by IEC 60851-5 and 2382
IEC 60851-6 for the rectangular and square winding wires. 2383
The reference to trichloroethane is being deleted as trich loroethane is an 2384
environmentally hazardous substance. 2385
For J.2.3 (Flexibility and adherence) and J.2.4 (Heat shock), 5.1.2 in Test 8 of 2386
IEC 60851-3:2009 and 3.2.1 of IEC 60851-6:1996 are not used for solid square 2387
and solid rectangular winding wires. 2388
___________ 2389
Annex K Safety interlocks 2390
Source: IEC 60950-1 2391
Purpose: To provide reliable means of safety interlock devices. 2392
Rationale: Safety interlock constructions have been used for many years in products within 2393
the scope of this document. Safety interlocks should not be associated with 2394
electro-mechanical components only. 2395
K.7.1 Safety interlocks 2396
Source: IEC 60950-1 2397
Purpose: To provide reliable means of safety interlock devices. 2398
– 150 – IEC TR 62368-2:20xx © IEC 20xx
Rationale: Clearance values specified in 5.4.2 are based on IEC 60664-1 and are specified 2399
for protection against electric shock. The values are the shortest distance 2400
through air between two different conductive parts. In that context, one conductor 2401
is at hazardous voltage (energy source) and another conductor is accessible to 2402
a person (body part). The required clearance is the minimum distance required 2403
to protect the person from being exposed to current causing electric shock. The 2404
distance acts as a safeguard against the hazardous energy source (ES2/ES3). 2405
Contact gaps of interlock relays or switches are most likely not directly serving 2406
as the safeguard as explained above. Instead, the gap is meant to interrupt the 2407
electrical power to the energy sources, for example, motors generating MS2/3 2408
energy or laser units generating Class IIIb or larger energy. In this situation, the 2409
distance of the gap is required to interrupt the power supply to the device so 2410
that the device is shut down. Again, it is not for the purpose of blocking current 2411
to a body part. 2412
Although the purpose of the clearance is different, the required values based on 2413
IEC 60664-1 are used because there is no other data available addressing the 2414
minimum values required to establish circuit interruption to shut off the power to 2415
a load device. It is believed that the distance required to protect a person from 2416
shock hazard is sufficient to have a circuit interruption as part of proper circuit 2417
operation. The specified voltage in clause 5.4 is from 330 Vpeak or Vdc, and the 2418
contacts for interlock relays/switches most likely operate in DC low voltage such 2419
as 5 or 24 V, so much lower than 330 V. Mains operated contacts are required 2420
to have a gap for disconnect device that is much larger than the distance for 2421
insulation. 2422
Due to the above considerations, slight adjustment by altitude multiplicat ion 2423
factor is not considered necessary for contact gaps of interlock relays/switches. 2424
___________ 2425
Annex L Disconnect devices 2426
Source: IEC 60950-1 2427
Purpose: To provide adequate protective earth connection. 2428
Rationale: 3 mm separation distances of contacts. Can be part of building installation. 2429
For class I equipment, the supply plug or appliance coupler, if used as the 2430
disconnect device, shall make the protective earthing connection earlier than 2431
the supply connections and shall break it later than the supply connections. 2432
Clearance of 3 mm can withstand peak impulse voltages of 4 000 V, which 2433
corresponds to a transient overvoltage present in overvoltage category III 2434
environment (equipment as part of the building installation). 2435
One instructional safeguard could be used for more than one disconnect 2436
device, as long as it can be visible from each disconnect point. 2437
___________ 2438
Annex M Equipment containing batteries and their protection circuits 2439
M.1 General requirements 2440
Rationale: Stand-alone battery chargers for general purpose batteries shall be evaluated 2441
using their relevant safety document, and not IEC 62368-1. If the battery and 2442
the charger are designed specifically for AV or ICT equipment and not to be used 2443
for other purposes, the provisions of IEC 62368-1:2018 including Annex M may 2444
be applied. 2445
IEC TR 62368-2:20xx © IEC 20xx – 151 –
M.2 Safety of batteries and their cells 2446
Rationale: Equipment containing batteries shall be designed to reduce the risk of fire, 2447
explosion and chemical leaks under normal operating conditions and after a 2448
single fault condition in the equipment, including a fault in circuitry within the 2449
equipment battery pack. For batteries replaceable by an ordinary person or 2450
an instructed person, the design shall provide safeguards against reverse 2451
polarity installation or replacement of a battery pack from different component 2452
manufacturers if this would otherwise defeat a safeguard. 2453
Other clauses in this document address in generic terms safeguards associated 2454
with the use of batteries. This annex does not specifically address those 2455
safeguards, but it is expected that batteries and associated circuits conform to 2456
the relevant requirements in this document. 2457
This annex addresses safeguards that are unique to batteries and that are not 2458
addressed in other parts of the document. Energy sources that arise from the 2459
use of batteries are addressed in this annex and include the following: 2460
– situations where the battery is in a state that exceeds its specifications or 2461
ratings (for example, by overcharging, rapid-charge, rapid-discharge, 2462
overcurrent or overvoltage conditions); 2463
– thermal runaway due to overcharge or short circuits within battery cells; 2464
– reverse-charging of the battery; 2465
– leakage or spillage of electrolyte; 2466
– emission of explosive gases; and 2467
– location of safeguards where battery packs may be replaceable by an 2468
ordinary person or an instructed person. 2469
Thermal runaway in the cell can result in explosion or fire, when the 2470
temperature rise in the cell caused by the heat emission raises the internal cell 2471
pressure faster than can be released by the cell pressure release device. 2472
Thermal runaway can be initiated by several causes: 2473
– defects introduced into the cell during cell construction. These defects are 2474
often not detected during the manufacturing process and may bridge an 2475
internal insulation layer or block a vent; 2476
– over-charge and rapid-charge or rapid-discharge; 2477
– high operational temperature or high battery environment temperature; 2478
– other cells in a pack feeding energy to a fault in a single cell; and 2479
– crushing of the enclosure. 2480
NOTE Batteries may contain multiple cells. 2481
During charging operation, gases are emitted from secondary cells and 2482
batteries excluding gastight sealed (secondary) cells, as the result of the 2483
electrolysis of water by electric current. Gases produced are hydrogen and 2484
oxygen. 2485
Table 17 in this document gives an overview of the referenced battery 2486
documents. 2487
2488
Table 17 – Safety of batteries and their cells – requirements (expanded information on documents and scope) 2489
Document
Chemistry Category Movability
Scope (details)
Alk
ali
ne
; n
on
-ac
id
Le
ad
Ac
id
NiC
d/N
iMH
Lit
hiu
m
Nic
ke
l; a
lka
lin
e
ele
ctr
oly
te
Va
rio
us
Va
rio
us
, w
ith
aq
ue
ou
s e
lec
tro
lyte
Pri
ma
ry
Se
co
nd
ary
Po
rta
ble
Sta
tio
na
ry
All
IEC 60086-4 (2014); Primary Batteries – Part 4 – Safety of Lithium Batteries
X X X Specifies tests and requirements for primary lithium batteries to ensure their safe operation under intended use and reasonably foreseeable misuse (including coin / button cell batteries).
IEC 60086-5 (2016): Primary Batteries – Part 5 – Safety of batteries with aqueous electrolyte
X X X Specifies tests and requirements for primary batteries with aqueous electrolyte to ensure their safe operation under intended use and reasonably foreseeable misuse (includes coin/button cell batteries).
IEC 60896-11 (2002): Stationary Lead Acid Batteries – Part 11 – Vented type
X X X X Applicable to lead-acid cells and batteries that are designed for service in fixed locations (for example, not habitually to be moved from place to place) and which are permanently connected to the load and to the DC power supply. Batteries operating in such applications are called "stationary batteries". Any type or construction of lead-acid battery may be used for stationary battery applications. Part 11 is applicable to vented types only.
IEC 60896-21 (2004): Stationary Lead Acid Batteries – Part 21 – Valve regulated type – method of test
X X X X Applies to all stationary lead-acid cells and monobloc batteries of the valve regulated type for float charge applications, (for example, permanently connected to a load and to a DC power supply), in a static location (for example, not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications. The objective is to specify the methods of test for all types and construction of valve regulated stationary lead acid cells and monobloc batteries used in standby power applications.
Document
Chemistry Category Movability
Scope (details)
Alk
ali
ne
; n
on
-ac
id
Le
ad
Ac
id
NiC
d/N
iMH
Lit
hiu
m
Nic
ke
l; a
lka
lin
e
ele
ctr
oly
te
Va
rio
us
Va
rio
us
, w
ith
aq
ue
ou
s e
lec
tro
lyte
Pri
ma
ry
Se
co
nd
ary
Po
rta
ble
Sta
tio
na
ry
All
IEC 60896-22 (2004): Stationary Lead Acid Batteries – Part 22 – Valve regulated type – requirements
X X X X Applies to all stationary lead-acid cells and monobloc batteries of the valve regulated type for float charge applications, (for example, permanently connected to a load and to a DC power supply), in a static location (for example, not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications. The objective is to assist the specifier in the understanding of the purpose of each test contained within IEC 60896-21 and provide guidance on a suitable requirement that will result in the battery meeting the needs of a particular industry application and operational condition. This document is used in conjunction with the common test methods described in IEC 60896-21 and is associated with all types and construction of valve regulated stationary lead-acid cells and monobloc batteries used in standby power applications.
IEC 61056-1 (2012): General purpose lead-acid batteries (valve-regulated types) – Part 1: General requirements, functional characteristics – Methods of test
X X X X Specifies the general requirements, functional characteristics and methods of test for all general-purpose lead-acid cells and batteries of the valve-regulated type:
– for either cyclic or float charge application;
– in portable equipment, for instance, incorporated in tools, toys, or in static emergency, or uninterruptible power supply and general power supplies.
(For stationary applications, the battery will need to meet IEC 60896-21/-22 or subject to additional evaluation).
Document
Chemistry Category Movability
Scope (details)
Alk
ali
ne
; n
on
-ac
id
Le
ad
Ac
id
NiC
d/N
iMH
Lit
hiu
m
Nic
ke
l; a
lka
lin
e
ele
ctr
oly
te
Va
rio
us
Va
rio
us
, w
ith
aq
ue
ou
s e
lec
tro
lyte
Pri
ma
ry
Se
co
nd
ary
Po
rta
ble
Sta
tio
na
ry
All
IEC 61056-2 (2012): General purpose lead-acid batteries (valve-regulated types) – Part 2: Dimensions, terminals and marking
X X X X Specifies the dimensions, terminals and marking for all general-purpose lead-acid cells and batteries of the valve regulated type:
– for either cyclic or float charge application;
– in portable equipment, for instance, incorporated in tools, toys, or in static emergency, or uninterruptible power supply and general power supplies.
(For stationary applications, the battery will need to meet IEC 60896-21/-22 or subject to additional evaluation).
IEC 61427 (all parts) (2013): Secondary cells and batteries for renewable energy storage – General requirements and methods of test – Part 1: Photovoltaic off-grid application
X X X Part of a series that gives general information relating to the requirements for the secondary batteries used in photovoltaic energy systems (PVES) and to the typical methods of test used for the verification of battery performances. This part deals with cells and batteries used in photovoltaic off-grid applications. This document is applicable to all types of secondary batteries.
IEC TS 61430 (1997): Secondary Cells and Batteries – Test Methods for Checking the Performance of Devices Designed for Reducing Explosion Hazards – Lead-Acid Starter Batteries
X X X Specification gives guidance on procedures for testing the effectiveness of devices which are used to reduce the hazards of an explosion, together with the protective measures to be taken.
IEC 61434 (1996): Secondary cells and batteries containing alkaline or other non-acid electrolytes Guide to the designation of current in alkaline secondary cell and battery standards
X X X Applies to secondary cells and batteries containing alkaline or other non-acid electrolytes. It proposes a mathematically correct method of current designation which shall be used in future secondary cell and battery documents.
Document
Chemistry Category Movability
Scope (details)
Alk
ali
ne
; n
on
-ac
id
Le
ad
Ac
id
NiC
d/N
iMH
Lit
hiu
m
Nic
ke
l; a
lka
lin
e
ele
ctr
oly
te
Va
rio
us
Va
rio
us
, w
ith
aq
ue
ou
s e
lec
tro
lyte
Pri
ma
ry
Se
co
nd
ary
Po
rta
ble
Sta
tio
na
ry
All
IEC 61959 (2004): Secondary cells and batteries containing alkaline or other non-acid electrolytes Mechanical tests for sealed portable secondary cells and batteries
X X X Specifies tests and requirements for verifying the mechanical behavior of sealed portable secondary cells and batteries during handling and normal use.
IEC 62133 (all parts) (2012 – superseded by IEC 62133-1 and IEC 62133-2); Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary cells, and for batteries made from them, for use in portable applications
X X X X* Specifies requirements and tests for the safe operation of portable sealed secondary cells and batteries (other than coin / button cell batteries) containing alkaline or other non-acid electrolyte, under intended use and reasonably foreseeable misuse.
IEC 62133-1 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary cells, and for batteries made from them, for use in portable applications – Part 1: Nickel systems
X X X Specifies requirements and tests for the safe operation of portable sealed secondary nickel cells and batteries containing alkaline electrolyte, under intended use and reasonably foreseeable misuse.
IEC 62133-2 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary lithium cells, and for batteries made from them, for use in portable applications – Part 2: Lithium systems
X X X X* Specifies requirements and tests for the safe operation of portable sealed secondary lithium cells and batteries containing non-acid electrolyte, under intended use and reasonably foreseeable misuse.
Document
Chemistry Category Movability
Scope (details)
Alk
ali
ne
; n
on
-ac
id
Le
ad
Ac
id
NiC
d/N
iMH
Lit
hiu
m
Nic
ke
l; a
lka
lin
e
ele
ctr
oly
te
Va
rio
us
Va
rio
us
, w
ith
aq
ue
ou
s e
lec
tro
lyte
Pri
ma
ry
Se
co
nd
ary
Po
rta
ble
Sta
tio
na
ry
All
IEC 62281 (2016): Safety of primary and secondary lithium cells and batteries during transport
X X X X Specifies test methods and requirements for primary and secondary (rechargeable) lithium cells and batteries to ensure their safety during transport other than for recycling or disposal (similar to UN 38.3).
IEC 62485-2
(2010): Safety requirements for secondary batteries and battery installations – Part 2: Stationary batteries
X X X X Applies to stationary secondary batteries and battery installations with a maximum voltage of 1 500 V DC (nominal) and describes the principal measures for protections against hazards generated from:
– electricity,
– gas emission,
– electrolyte.
Provides requirements on safety aspects associated with the erection, use, inspection, maintenance and disposal. It covers lead-acid and NiCd/NiMH batteries (IEC 62485-2 requires the valve regulated batteries to meet safety requirements from IEC 60896).
IEC 62619 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for secondary lithium cells and batteries, for use in industrial applications
X X X Specifies requirements and tests for the safe operation of secondary lithium cells and batteries used in industrial applications including stationary applications.
* IEC 62133-2 (2017) may be used with stationary equipment for sub-system powering. Such batteries/packs typically are a similar format as batteries and battery packs used in portable equipment and only provide sub-system powering of part(s) of the equipment for orderly shutdown and similar functional purposes in the event of power loss (compared to storage batteries for full system powering).
2490
IEC TR 62368-2:20xx © IEC 20xx – 157 –
M.3 Protection circuits for batteries provided within the equipment 2491
Rationale: Equipment containing batteries is categorized into two types; 2492
1. Equipment containing batteries which are embedded in the equipment and 2493
cannot be separated from the equipment. 2494
2. Equipment containing batteries which can be separated from the equipment. 2495
The requirements in IEC 62368-1 cover only the battery circuits that are not an 2496
integral part of the battery itself, and as such form a part of the equipment. 2497
M.4 Additional safeguards for equipment containing a portable secondary 2498
lithium battery 2499
Rationale: M.4 applies to all equipment with lithium batteries. M.4.4 applies only to 2500
equipment as specified in M.4.4 (typically portable equipment). 2501
Secondary lithium batteries (often called lithium-ion or li-ion batteries) are 2502
expected to have high performance, such as light-weight and high energy 2503
capability. The use of li-ion batteries has been continuously expanding in the 2504
area of high-tech electronic equipment. However, it is said that this technology 2505
involves risks because the safety margin (distance between safe-operation zone 2506
and unsafe-operation zone) is relatively small compared to other battery 2507
technologies. 2508
IEC TC 108 noted that for designing equipment containing or us ing li-ion battery, 2509
it is imperative to give careful consideration to selecting highly reliable battery 2510
cells, providing high performance battery management systems for operating 2511
batteries within their specified operating environment and parameter range (for 2512
example, battery surrounding temperature or battery charging/discharging 2513
voltage and current). It is also imperative to introduce safeguards against 2514
abnormal operating conditions, such as vibration during the use of devices, 2515
mechanical shock due to equipment drop, surge signals caused internally or 2516
externally, and a mechanism to reduce the likelihood of catastrophic failure such 2517
as battery explosion or fire. 2518
It is suggested that suppliers of equipment and batteries should take into 2519
account possible abnormal operating conditions that may occur during use, 2520
transport, stock, and disposal, so that the equipment is well prepared for such 2521
conditions. 2522
It is important that the key parameters (highest/lowest charging temperatures, 2523
maximum charging current, and upper limit charging voltage) during charging 2524
and discharging of the battery are not exceeded. 2525
IEC TC 108 noted that, when designing battery compartments, the battery 2526
compartment dimensions should allow sufficient space for cells to expand 2527
normally under full operating temperature range or be flexible to prevent 2528
unnecessary compression of the cells. Given the wide range of battery 2529
constructions, corresponding battery compartment dimensional requirements 2530
will differ. When necessary, coordinate with the battery manufacturer to 2531
determine change in battery dimensions over full operating range during 2532
charging and discharging. 2533
M.4.1 General 2534
Rationale: Sub-clause M.2.1 contains a list of IEC standard for batteries that are normative 2535
for batteries and cells that are relevant based on their intended use. Included in 2536
the list is IEC 62619, which mentions in its scope, “… specifies requirements and 2537
tests for the safe operation of secondary lithium cells and batteries used in 2538
industrial applications including stationary applications.” “Telecommunication” 2539
equipment is one of the stationary equipment applications given as an example 2540
under its scope. 2541
2542
– 158 – IEC TR 62368-2:20xx © IEC 20xx
Included in IEC 62619 in Clause 8 are requirements for battery system safety 2543
(considering functional safety, Clause 8.1), which also includes specific 2544
requirements for the battery management system, BMS (8.2.1). While the BMS 2545
requirements in 8.2.1 are relatively similar in nature to IEC 62133-2 and Annex 2546
M of IEC 62368-1, the provision for additional investigation of electric, electronic 2547
and software controls and systems used for critical safety is not something 2548
covered by IEC 62133-2 and Annex M to the degree as it is covered in 2549
IEC 62619. 2550
Therefore, if batteries (including battery packs) intended for transportable 2551
equipment are used in stationary equipment it is appropriate to consider the 2552
requirements of 8.1 of IEC 62619 if electric, electronic and software controls and 2553
systems are relied upon as the primary safeguard for safety of the battery, 2554
provided the battery is not provided with a supplementary safeguard. 2555
M.4.2.2 Compliance criteria 2556
The highest temperature point in the battery may not always exist at the center 2557
of the battery. The battery supplier should specify the point where the highest 2558
temperature in the battery occurs. 2559
To test the charging circuit, instead of using a real battery (which is a chemical 2560
system), an electrical circuit emulating the battery behavior (dummy battery 2561
circuit) may make the test easier by eliminating a possible battery defect. 2562
An example of a dummy battery circuit is given in Figure 51 in this document. 2563
Figure 51 – Example of a dummy battery circuit
M.4.3 Fire enclosure 2564
Lithium-ion batteries with an energy more than PS1 (15 W) must be provided 2565
with a fire enclosure (either at the battery or at the equipment containing the 2566
battery) because even though measurements of output voltage and current may 2567
not necessarily show them to be a PIS, however they contain flammable 2568
electrolyte that can be easily ignited by the enormous amount of heat developed 2569
by internal shorts as a result of possible contaminants in the electrolyte. 2570
M.4.4 Drop test of equipment containing a secondary lithium battery 2571
Annex M.4.4 applies only to batteries used in portable applications. 2572
This includes batteries in the scope of IEC 62133 and IEC 62133-2 which are 2573
typically used in hand-held equipment or transportable equipment. 2574
Batteries or sub-assemblies containing batteries used in other types of 2575
equipment, that are not routinely held or carr ied but may be occasionally 2576
removed for service or replacement, are not considered to be portable batteries 2577
and are not in scope of Annex M.4.4. 2578
IEC TR 62368-2:20xx © IEC 20xx – 159 –
Monitoring of lithium-ion battery output voltage and surface temperature during 2579
or after the drop test may not help. The concern is that if a minor dent occurs, 2580
nothing may happen to the battery. Temperature may go up slightly and then 2581
drop down without any significant failure. If the battery is damaged, the damage 2582
may only show up if the battery is then subjected to few charging and 2583
discharging cycles. Therefore, the surface temperature measurement was 2584
deleted and replaced with charging and discharging cycles after the drop test. 2585
The charging and discharging of the battery shall not result in any fire or 2586
explosion. 2587
It is important that the equipment containing a secondary lithium battery 2588
needs to have a drop impact resistance. Equipment containing a secondary 2589
lithium battery should avoid further damage to the control circuit and the 2590
batteries. 2591
As M.4.4 requires the equipment to be tested, the relevant equipment heights 2592
need to be used instead of the height for testing parts that act as a fire 2593
enclosure. 2594
After the drop test: 2595
– Initially, the control functions should be checked to determine if they continue 2596
to operate and all safeguards are effective. A dummy battery or appropriate 2597
measurement tool can be used for checking the function of the equipment . 2598
– Then, the batteries are checked whether or not a slight internal short circuit 2599
occurs. 2600
Discharge and charge cycles under normal operating conditions test hinder 2601
detection of the slight internal short circuit because the current to discharge and 2602
charge is higher than the current caused by a slight internal short circuit. 2603
Thus, it is very important to conduct a voltage observation of the battery 2604
immediately after the drop test without any discharge and charge. 2605
To detect a slight internal short circuit of the battery, IEC TC 108 adopts a no-2606
load test, which can detect a battery open voltage drop caused by an internal 2607
short circuit leak current in a 24 h period. 2608
Equipment containing an embedded type of battery has internal power 2609
dissipation (internal consumption current). Therefore, two samples of the 2610
equipment are prepared, one for the drop test and the other for reference in a 2611
standby mode. In this way, the effect of internal power dissipation can be 2612
detected by measuring a difference between voltage drops in the 24 h period. 2613
M.6.1 Requirements 2614
Examples: Examples of battery documents containing an internal short test are IEC 62133, 2615
IEC 62133-2 and IEC 62619. 2616
Another example of compliance to internal fault requirements is a battery using 2617
cells that have passed the impact test as specified in IEC 62281. 2618
M.7.1 Ventilation preventing an explosive gas concentration 2619
Rationale: During charging, float charging, and overcharg ing operation, gases are emitted 2620
from secondary cells and batteries excluding gastight sealed (secondary) cells, 2621
as the result of the electrolysis of water by electric current. Gases produced are 2622
hydrogen and oxygen. 2623
M.7.2 Test method and compliance criteria 2624
Source: The formula comes from IEC 62485-2:2010, 7.2. 2625
M.8.2.1 General 2626
Source: The formula comes from IEC 60079-10-1:2015, Clause B.4. 2627
___________ 2628
– 160 – IEC TR 62368-2:20xx © IEC 20xx
Annex O Measurement of creepage distances and clearances 2629
Source: IEC 60664-1, IEC 60950-1 2630
Purpose: Clearances are measured from the X-points in the figure 2631
Rationale: Figure O.4. At an IEC/TC 109 meeting in Paris, a draft CTL interpretation was 2632
discussed regarding example 11 of IEC 60664-1:2007. The question was if 2633
distances smaller than X should be counted as zero. There was a quite lengthy 2634
debate, but the conclusion was that, based on the other examples in the standard 2635
(and especially example 1), there is no reason why in this example the distance 2636
should be counted as zero. If this should be done, many other examples should 2637
be changed where it is shown that the distance is measured across X rather than 2638
to disregard X. TC 109 has decided to modify the example 11 to remove the X 2639
from the figure to avoid this confusion in future. This is now represented in Figure 2640
14 of IEC 60664-1:2020. As a result, the statement that distances smaller than 2641
X are disregarded is deleted from Figure O.4. 2642
Figure O.13. The clearance determination is made from the X-points in the 2643
figure, as those are the first contact points when the test finger enters the 2644
enclosure opening. It is assumed that the enclosure is covered by conductive 2645
foil, which simulates conductive pollution. 2646
___________ 2647
Annex P Safeguards against conductive objects 2648
P.1 General 2649
Rationale: The basic safeguard against entry of a foreign object is that persons are not 2650
expected to insert a foreign object into the equipment. Where the equipment is 2651
used in locations where children may be present, it is expected that there will be 2652
adult supervision to address the issue of reasonable foreseeable misuse by 2653
children, such as inserting foreign objects . Therefore, the safeguards specified 2654
in this annex are supplementary safeguards. 2655
P.2 Safeguards against entry or consequences of entry of a foreign object 2656
Source: IEC 60950-1 2657
Purpose: Protect against the entry of foreign objects 2658
Rationale: There are two alternative methods that may be used. 2659
P.2.2 specifies maximum size limits and construction of openings. The relatively 2660
small foreign conductive objects or amounts of liquids that may pass through 2661
these openings are not likely to defeat any equipment safeguards. This option 2662
prevents entry of objects that may defeat a safeguard. 2663
Alternatively, if the openings are larger than those specified in P.2.2, P.2.3 2664
assumes that a foreign conductive object or liquid passing through these 2665
openings is likely to defeat an equipment basic safeguard, and requires that the 2666
foreign conductive object or liquid shall not defeat an equipment supplementary 2667
safeguard or an equipment reinforced safeguard. 2668
P.2.3.1 Safeguard requirements 2669
Rationale: Conformal coating material is applied to electronic circuitry to act as protection 2670
against moisture, dust, chemicals, and temperature extremes that, if uncoated 2671
(non-protected), could result in damage or failure of the electronics to function. 2672
When electronics are subject to harsh environments and added protection is 2673
necessary, most circuit board assembly houses coat assemblies with a layer of 2674
transparent conformal coating rather than potting. 2675
IEC TR 62368-2:20xx © IEC 20xx – 161 –
The coating material can be applied by various methods, from brushing, spraying 2676
and dipping, or, due to the increasing complexities of the electronic boards being 2677
designed and with the 'process window' becoming smaller and smaller, by 2678
selectively coating via robot. 2679
P.3 Safeguards against spillage of internal liquids 2680
Source: IEC 60950-1 2681
Rationale:If the liquid is conductive, flammable, toxic, or corrosive, then the l iquid shall not 2682
be accessible if it spills out. The container of the liquid provides a basic 2683
safeguard. After the liquid spills out, then barrier, guard or enclosure that 2684
prevents access to the liquid acts as a supplementary safeguard. Another 2685
choice is to provide a container that does not leak or permit spillage for example, 2686
provide a reinforced safeguard. 2687
P.4 Metalized coatings and adhesives securing parts 2688
Source: IEC 60950-1 2689
Rationale:Equipment having internal barriers secured by adhesive are subject to 2690
mechanical tests after an aging test. If the barrier does not dislodge as a whole 2691
or partially or fall off, securement by adhesive is considered acceptable. 2692
The temperature for conditioning should be based on the actual temperature of 2693
the adhesive secured part. 2694
The test program for metalized coatings is the same as for aging of adhesives. 2695
In addition, the abrasion resistance test is done to see if particles fall off from 2696
the metalized coating. Alternatively, clearance and creepage distances for PD3 2697
shall be provided. 2698
___________ 2699
Annex Q Circuits intended for interconnection with building wiring 2700
Source: IEC 60950-1:2013 2701
Rationale: For the countries that have electrical and fire codes based on NFPA 70, this 2702
annex is applied to ports or circuits for external circuits that are interconnected 2703
to building wiring for limited power circuits. Annex Q was based on requirements 2704
from IEC 60950-1 that are designed to comply with the external circuit power 2705
source requirements necessary for compliance with the electrical codes noted 2706
above. 2707
Q.1.2 Test method and compliance criteria 2708
In determining if a circuit is a limited power source, all conditions of use should 2709
be considered. For example, for circuits that may be connected to a battery 2710
source as well as a mains source, determination whether the available output 2711
from the circuit is a limited power source is made with each of the sources 2712
connected independently or simultaneously (see Figure 52 in this document). 2713
Q.2 Test for external circuits – paired conductor cable 2714
Time/current characteristics of type gD and type gN fuses specified in 2715
IEC 60269-2-1 comply with the limit. Type gD or type gN fuses rated 1 A, would 2716
meet the 1,3 A current limit. 2717
– 162 – IEC TR 62368-2:20xx © IEC 20xx
2718
Figure 52 – Example of a circuit with two power sources 2719
___________ 2720
Annex R Limited short-circuit test 2721
Source: IEC SC22E 2722
Rationale: The value of 1 500 A is aligned with the normal breaking capacity of a high 2723
breaking fuse. In Japan the prospective short circuit current is considered less 2724
than 1 000 A. 2725
___________ 2726
Annex S Tests for resistance to heat and fire 2727
S.1 Flammability test for fire enclosure and fire barrier materials of equipment 2728
where the steady-state power does not exceed 4 000 W 2729
Rationale: This test is intended to test the ability of an end-product enclosure to adequately 2730
limit the spread of flame from a potential ignition source to the outside of the 2731
product. 2732
– Included the text from IEC 60065 using the needle flame as the ignition source 2733
for all material testing. The reapplication of the flame after the first flaming 2734
was added to clarify that the test flame is immediately re-applied based on 2735
current practices. 2736
– This conditioning requirement of 125 °C for printed wiring boards is derived 2737
from laminate and PCB documents. 2738
S.2 Flammability test for fire enclosure and fire barrier integrity 2739
Rationale: This test method is used to test the integrity of a fire barrier or fire enclosure 2740
where a potential ignition source is in very close proximity to an enclosure or 2741
a barrier. 2742
The criteria of “no additional holes” is considered important as flammable 2743
materials may be located immediately on the other side of the barrier or fire 2744
enclosure. 2745
Rationale: Application of needle flame 2746
IEC TR 62368-2:20xx © IEC 20xx – 163 –
The flame cone and the 50 mm distance is a new requirement that was not 2747
applied in IEC 60950 to top openings. This new requirement does impact already 2748
certified IEC 60950 ITE products, and it was found that some manufacturers’ 2749
current designs were not able to comply with the 50-mm distance prescribed 2750
ventilation opening requirements and will not be able to pass the needle flame 2751
test as per IEC 60695-11. An HBSDT’s fire enclosure adhoc team performed 2752
some experimental flame testing with the needle flame located at various 2753
distances from various size ventilation openings. This test approach was found 2754
to align more with hazard-based safety engineering principles and deemed to be 2755
a more realistic representation of when a thermal event may occur. 2756
A PIS can be in the form of any size/shape, so it was determined not reasonable 2757
to directly apply the needle flame to top surface openings when realistically a 2758
thermal event from smaller components is unlikely to touch the top surface 2759
openings. Additionally, typically it is common for such components to be 2760
mounted on V-0 rated boards that further help reduce the spread of fire. 2761
The test data from the fire experimental testing demonstrated clearly that , when 2762
the flame is at distances well within 50 mm, significantly larger openings can be 2763
used beyond the pre-specified sizes by 6.4.8.3.3 (for example less than 5 mm in 2764
any dimension and/or less than 1 mm regardless of length). 2765
Therefore, for the purpose of this standard and to align more with hazard-based 2766
safety engineering principles, the needle flame is to be applied at a distance 2767
measured from the closest assessed point of a PIS to the closest surface point 2768
of the test specimen. The application of the flame is measured from the top of 2769
the needle flame burner to the closest surface point. See Figure S.1 in Clause 2770
S.2 of IEC 62368-1:2018. 2771
S.3 Flammability tests for the bottom of a fire enclosure 2772
Source: IEC 60950-1:2013 2773
Rationale: This text was not changed from the original ECMA document which was originally 2774
in IEC 60950-1. This test is intended to determine the acceptability of holes or 2775
hole patterns in bottom enclosures to prevent flaming material from falling onto 2776
the supporting surface. It has been used principally for testing metal bottom 2777
enclosures. 2778
This test is being proposed to test all bottom enclosures. Research is ongoing 2779
to develop a similar test based on the use of flammable (molten) therm oplastic 2780
rather than oil. 2781
S.4 Flammability classification of materials 2782
Rationale: The tables were considered helpful to explain the hierarchy of material 2783
flammability class requirements used in this document. 2784
Whenever a certain flammability class is required, a better classification is 2785
allowed to be used. 2786
S.5 Flammability test for fire enclosure materials of equipment with a steady 2787
state power exceeding 4 000 W 2788
Source: IEC 60950-1:2013 2789
Rationale: The annex for flammability test for high voltage cables was withdrawn and 2790
replaced by flammability test for fire enclosure materials of equipment having 2791
greater than 4 000 W faults. 2792
___________ 2793
– 164 – IEC TR 62368-2:20xx © IEC 20xx
Annex T Mechanical strength tests 2794
T.2 Steady force test, 10 N 2795
Source: IEC 60950-1 2796
Rationale: 10 N applied to components and parts that may be touched during operation or 2797
servicing. This test simulates the accidental contact with a finger or part of a 2798
hand. 2799
T.3 Steady force test, 30 N 2800
Source: IEC 60065 and IEC 60950-1 2801
Rationale: This test simulates accidental contact with a part of the hand. 2802
T.4 Steady force test, 100 N 2803
Source: IEC 60065 and IEC 60950-1 2804
Rationale: This test simulates an expected force applied during use or movement. 2805
T.5 Steady force test, 250 N 2806
Source: IEC 60065 and IEC 60950-1 2807
Rationale: 250 N applied to external enclosures (except those covered in Clause T.4). This 2808
test simulates an expected force when leaning against the equipment surface to 2809
ensure clearances are not bridged to introduce a hazard such as shock. The 2810
30 mm diameter surface simulates a small part of hand or foot. It is not expected 2811
that such forces will be applied to the bottom surface of heavy equipment ( 2812
18 kg). 2813
T.6 Enclosure impact test 2814
Source: IEC 60065 and IEC 60950-1 2815
Rationale: To check integrity of the enclosure, to ensure that no hazard is created by an 2816
impact. 2817
The values in T.6 are taken over from existing requirements in IEC 60065 and 2818
IEC 60950-1. 2819
The impact is applied once for each test point on the enclosure. 2820
T.7 Drop test 2821
Source: IEC 60065 and IEC 60950-1 2822
Rationale: This test addresses potential exposure to a hazard after the impact and not 2823
impact directly on a body part. The test is applied to desk top equipment under 2824
7 kg as it is more likely these products could be accidentally knocked off the 2825
desk. The drop height was chosen based on intended use of the product. 2826
The term “table-top” has been used in IEC 60065, while the term “desk-top” has 2827
been used in IEC 60950-1. Both terms had been taken over in IEC 62368-1 2828
without the intention to make the different requirements for these types of 2829
equipment. Therefore, the requirements are applicable to both type of equipment 2830
even if only either one is referred to. From edition 3 onwards, the term “table-2831
top” has been replaced by “desk-top”. 2832
T.8 Stress relief test 2833
Source: IEC 60065 and IEC 60950-1 2834
Rationale: To ensure that the mechanical integrity of moulded plastic parts is not affected 2835
by their relaxation or warping following thermal stress. 2836
IEC TR 62368-2:20xx © IEC 20xx – 165 –
T.9 Glass impact test 2837
Source: IEC 60065 2838
Rationale: Test applied to test the strength of the glass. 2839
The value of 7 J is a value that has been used for CRT in the past. Except for 2840
that, the value has also been used in commercial applications, but not in 2841
households, where the forces expected on the glass are much lower. CRT’s have 2842
separate requirements in Annex W. Therefore, a value of 3,5 J is considered 2843
sufficient. 2844
The centre of a piece of glass can be determined via the intersection of two 2845
diagonals for a rectangular piece or any other appropriate means for pieces of 2846
other geometries. 2847
T.10 Glass fragmentation test 2848
Source: IEC 60065 2849
Rationale: Test applied to ensure the fragments are small enough to be considered at MS2 2850
level or less. 2851
___________ 2852
Annex U Mechanical strength of CRTs and protection against the effects of 2853
implosion 2854
U.2 Test method and compliance criteria for non-intrinsically protected CRTs 2855
Source: IEC 61965, IEC 60065 2856
Rationale: The 750 mm simulates the height of a typical supporting surface such as a table 2857
or counter top. Test applied to ensure any expelled fragments are small enough 2858
to be considered at MS2 level or less. The fragment size represents a grain of 2859
sand. The test distances selected ensure fragments do not travel far enough to 2860
strike a person and cause injury. 2861
___________ 2862
Annex V Determination of accessible parts 2863
Figure V.3 Blunt probe 2864
Source: This test probe is taken from Figure 2c, IEC 60950-1:2013 2865
___________ 2866
Annex X Alternative method for determining clearances for insulation in 2867
circuits connected to an AC mains not exceeding 420 V peak (300 V 2868
RMS) 2869
Rationale: IEC TC 108 made a responsible decision to harmonize the requirements for 2870
clearances and creepage distances with the horizontal IEC 60664-x series 2871
documents produced by IEC TC 109. This decision is aligned with IEC 2872
harmonization directives and allows manufacturers the design benefits afforded 2873
by the IEC 60664-x series documents when minimization of spacings is a primary 2874
consideration of the product design. 2875
– 166 – IEC TR 62368-2:20xx © IEC 20xx
However, because of the complexity of determining clearances as per 5.4.2, 2876
sometimes the more state-of-art theory is not practical to implement for designs 2877
not requiring minimized spacings. For example, there are a very large number of 2878
existing designs and constructions qualified to IEC 60950-1 that are associated 2879
with products, mainly switch mode power supplies, connected to AC mains 2880
(overvoltage category II) not exceeding 300 V RMS. These constructions have 2881
successfully used the clearance requirements in IEC 60950-1 without any 2882
evidence of field issues, and even at switching frequencies well above 30 kHz. 2883
In fact, almost every switch mode power supply (SMPS) used today with IT & 2884
ICT equipment intended to be connected to mains less than 300 V RMS, 2885
including external power supplies, direct plug-in type, and internal power 2886
supplies, have clearances based on the base requirements in Subclause 2887
2.10.3.3 and Tables 2K and 2L of IEC 60950-1. Although the requirements do 2888
not incorporate the latest research on clearances used in circuits operating 2889
above 30 kHz, they are considered to be suitable for the application because 2890
they are a conservative implementation of IEC 60664-1 without minimization. 2891
As a result, and in particular based on their proven history of acceptability in the 2892
broad variety of power supplies used today, IEC TC 108 should support 2893
continued limited application of a prescribed set of clearances as an alternative 2894
to the more state-of-art IEC 60664-based requirements in IEC 62368-1 today. 2895
However, because of the valid concern with circuits operating above 30 kHz as 2896
clearances are further minimized, the IEC 60950-1 option in Tables 2K and 2L 2897
for reduced clearances in products with manufacturing subjected to a quality 2898
control programme (values in parenthesis in Tables 2K/2L) are not included in 2899
this proposal since the reduced clearances associated with the quality control 2900
option has not been used frequently under IEC 60950-1, and therefore there is 2901
not the same proven track record of successful implementation in a very large 2902
number of products. Similarly, there is not the same large quantity of qualified 2903
designs/construction associated with equipment connected to mains voltages 2904
exceeding 300 V RMS, or for equipment connected to DC mains, so these 2905
constructions should comply with the existing IEC 60664-based requirements in 2906
IEC 62368-1. 2907
___________ 2908
Annex Y Construction requirements for outdoor enclosures 2909
Rationale: General 2910
In preparing the requirements for outdoor enclosures, it has been assumed 2911
that: 2912
– exterior to the outdoor equipment there should be no hazards, just as is the 2913
case with other information technology equipment; 2914
– protection against vandalism and other purposeful acts will be treated as a 2915
product quality issue (for example, IEC 62368-1 does not contain 2916
requirements for the security of locks, types of acceptable screw head, forced 2917
entry tests, etc.). 2918
Electric shock 2919
It is believed that most aspects relating to protection against the risk of electric 2920
shock are adequately covered by IEC 62368-1 including current proposals, and 2921
in some cases, quoted safety documents (in particular, the IEC 60364 series), 2922
and with the exception of the following, do not require modification. Specific 2923
requirements not already suitably addressed in IEC 60950-1 were considered as 2924
follows: 2925
– clearing of earth faults for remotely located (exposed) information technology 2926
equipment; 2927
– the degree of protection provided by the enclosure to rain, dust, etc.; 2928
IEC TR 62368-2:20xx © IEC 20xx – 167 –
– the effect of moisture and pollution degree on the insulation of the enclosed 2929
parts; 2930
– the possible consequences of ingress by plants and animals (since these 2931
could bridge or damage insulation); 2932
– the maximum permissible touch voltage and body contact impedance for wet 2933
conditions. 2934
It is noted that the voltage limits of user-accessible circuits and parts in outdoor 2935
locations only are applicable to circuits and parts that are actually “user -2936
accessible”. If the circuits and parts are not user accessible (determined via 2937
application of accessibility probes) and are enclosed in electrical enclosures, 2938
connectors and cable suitable for the outdoor application, including being subject 2939
to all relevant outdoor enclosure testing, voltage limits for indoor locations may 2940
be acceptable based on the application. For example, a power-over-ethernet 2941
(PoE) surveillance camera mounted outdoors supplied by 48 V DC from PoE 2942
would be in compliance with Clause 5 if the electrical enclosure met the 2943
applicable requirements for outdoor enclosures. 2944
Fire 2945
It is believed that most aspects relating to protection against fire emanating from 2946
within the equipment are adequately covered by IEC 62368-1. However, certain 2947
measures that may be acceptable for equipment located inside a building would 2948
not be acceptable outdoors because they would permit the entry of rain, etc. 2949
For certain types of outdoor equipment, it could be appropriate to allow the ‘no 2950
bottom fire enclosure required if mounted on a concrete base’ exemption that 2951
presently can be used for equipment for use within a restricted access location. 2952
Mechanical hazards 2953
It is believed that all aspects relating to protection against mechanical hazards 2954
emanating from the equipment are adequately covered by IEC 62368-1. 2955
Heat-related hazards 2956
It is believed that most aspects relating to protection against direct heat hazards 2957
are adequately covered by IEC 62368-1. However, it may be appropriate to 2958
permit higher limits for equipment that is unlikely to be touched by passersby (for 2959
example, equipment that is only intended to be pole mounted out of reach). A 2960
default nominal ambient temperature range for outdoor equipment has been 2961
proposed. The effects of solar heating have not been addressed. 2962
In addition to direct thermal hazards, there is a need to consider consequential 2963
hazards. For instance, some plastics become brittle as they become cold. An 2964
enclosure made from such brittle plastic could expose users to other hazards 2965
(for example, electrical or mechanical) if it were to break. 2966
Radiation 2967
It is believed that most aspects relating to direct protection against radiation 2968
hazards are adequately covered by IEC 62368-1. However, there may be 2969
consequential hazards to consider. Just as polymeric materials can be affected 2970
by low temperatures, they can also become embrittled owing to the effect of UV 2971
radiation. An enclosure made from such brittle plastic could expose users to 2972
other hazards (for example, electrical or mechanical) if it were to break. 2973
Chemical hazards 2974
It is believed that certain types of outdoor equipment need to have measures 2975
relating to chemical hazards originating within, or external to, the equipment. 2976
Exposure to chemicals in the environment (for example, salt used to clear roads 2977
in the winter) can also cause problems. 2978
– 168 – IEC TR 62368-2:20xx © IEC 20xx
Biological hazards 2979
These are not presently addressed in IEC 62368-1. As with radiation hazards 2980
and chemical hazards, it is thought that there is not likely to be any direct 2981
biological hazard. However, plastics and some metals can be attacked by fungi 2982
or bacteria and this could result in weakening of protective enclosures. As 2983
stated under 'electric shock', the ingress of plants and animals could result in 2984
damage to insulation. 2985
Explosion hazards 2986
Outdoor equipment may need to be weather-tight, in such cases there is an 2987
increased probability that an explosive atmosphere can build up as a result of: 2988
– hydrogen being produced as a result of charging lead-acid batteries within 2989
the equipment and; 2990
– methane and other ‘duct gasses’ entering the equipment from the outdoors. 2991
Y.3 Resistance to corrosion 2992
Rationale: Enclosures made of the following materials are considered to comply with XX.1 2993
without test: 2994
(a) Copper, aluminum, or stainless steel; and 2995
(b) Bronze or brass containing at least 80 % copper. 2996
Y.4.6 Securing means 2997
Rationale: Gaskets associated with doors, panels or similar parts subject to periodic 2998
opening is an example of a gasket needing either mechanical securement or 2999
adhesive testing. 3000
3001
___________ 3002
3003
IEC TR 62368-2:20xx © IEC 20xx – 169 –
Annex A 3004
(informative) 3005
3006
Background information related to the use of SPDs 3007
NOTE Since there is ongoing discussion in the committee on the use of SPDs in certain situations, the content of 3008 this Annex is provided for information only. This Annex does not in any way override the requirements in the document, 3009 nor does it provide examples of universally accepted constructions. 3010
A.1 Industry demand for incorporating SPDs in the equipment 3011
The industry has the demand of providing protection of communication equipment from 3012
overvoltage that may be caused by lightning strike surge effect. There are r eports in Japan that 3013
hundreds of products are damaged by lightening surges every year, including the risk of fire 3014
and/or electrical shock according to the damage to the equipment, especially in the regions 3015
where many thunderstorms are observed. We believe it will be the same in many other countries 3016
by the reason described in the next paragraph where the voltage of the surge is much higher 3017
than expected value for overvoltage category II equipment (1 500 V peak or 2 500 V peak). For 3018
the surge protection purpose, the manufacturers have need to introduce the surge protection 3019
devices in the equipment, not only for class I equipment but also for class II equipment or 3020
class III equipment, but facing to the difficulty of designing equipment because of the limited 3021
acceptance in IEC 60950-1, 2nd edition and IEC 62368-1, 1st edition. 3022
If the point of bonding of electrical supply to the equipment is not adjacent to the point of 3023
bonding of telecommunication circuit that is connected to the external circuit of the same 3024
equipment, the surge entered from power line or from communication line causes the high 3025
potential difference on the insulation in the equipment, and cause the insulation/component 3026
breakdown which may cause product out-of-use. In some cases, the damage on the insulation 3027
or safeguard can cause hazardous voltage on the SELV/ES1 and accessible metal, or heat-3028
up of insulation material and fire (see Figure A.1 in this document, with the example of class II 3029
equipment.) 3030
The most effective way to protect equipment from a lightning surge is, as commonly understood 3031
internationally, to have an equipotential bonding system in the building/facility with a very low 3032
in-circuit impedance by the use of main-earth bar concept (see Figure A.2 in this document). 3033
This kind of high-quality earthing provision can be introduced in the building/facility in the 3034
business area, such as computer rooms, or in modern buildings. This kind of high quality 3035
earthing provision may not always be possible in the residential area, in already-existing 3036
buildings and in some countries where the reliably low impedance earth connection may not be 3037
easily obtained from technical (according to the characteris tics of land) or even by practical 3038
reasons (because very expensive construction change to the building is required, or according 3039
to the lack of regulatory co-work it is difficult to get the relevant permission for cabling). We 3040
should not disregard the fact that many ICT equipment (including PCs, fax machines, TVs and 3041
printers) are brought to home, school and small business offices into the existing buildings (see 3042
Figure A.3 and Figure A.4 in this document). 3043
If the use of surge suppressors by the means of “a varistor in series with a GDT” is allowed in 3044
the equipment to bridge safeguards for class I equipment and to bridge a double safeguard 3045
or a reinforced safeguard for class II equipment, means can be provided to bypass the surge 3046
current, and to avoid the possibility that the lightening surge breaks the circuit or the insulation 3047
within the equipment (see Figure A.2 in this document). 3048
Thus, there is industry demand for using surge protecting devices (SPDs) in the equipment 3049
independent of whether the product is class I equipment, class II equipment or class III 3050
equipment. 3051
– 170 – IEC TR 62368-2:20xx © IEC 20xx
3052
Figure A.1 – Installation has poor earthing and bonding; 3053
equipment damaged (from ITU-T K.66) 3054
3055
Figure A.2 – Installation has poor earthing and bonding; using main earth bar 3056
for protection against lightning strike (from ITU-T K.66) 3057
3058
IEC TR 62368-2:20xx © IEC 20xx – 171 –
3059
Figure A.3 – Installation with poor earthing and bonding, using a varistor 3060
and a GDT for protection against a lightning strike 3061
3062
Figure A.4 – Installation with poor earthing and bonding; equipment damaged (TV set) 3063
A.2 Technical environment of relevant component standards 3064
Before the publication of IEC 62368-1:2010, there was no appropriate component document for 3065
a GDT deemed to be providing a sufficient level of endurance to be accepted as a safeguard 3066
for a primary circuit. For this reason, a GDT could not be accepted as a reliable component for 3067
use as a safeguard between a primary and secondary circuit. 3068
However, recently IEC SC 37B has been developed new documents for GDTs. In these 3069
documents the spark over voltage of GDT’s has been extended up to 4 500 V DC, taking the 3070
use of GDTs in the mains circuit in to account. We believe therefore that a GDT may be used 3071
as a safeguard if it complies with the following documents: 3072
– IEC 61643-311:2013: Components for low-voltage surge protective devices – Part 311: 3073
Performance requirements and test circuits for gas discharge tubes (GDT) ; 3074
– IEC 61643-312:2013: Components for low-voltage surge protective devices – Part 312: 3075
Selection and application principles for gas discharge tubes ; 3076
The sentence “does not deal with GDTs connected in series with voltage-dependent resistors 3077
in order to limit follow-on currents in electrical power systems;” in the scope of these documents 3078
– 172 – IEC TR 62368-2:20xx © IEC 20xx
with a purpose for expressing that GDTs connected in series with varistors are a kind of SPD 3079
and this issue should be in IEC 61643-11 for SDP’s standard. But this sentence may be misread 3080
as “a GDT is not allowed to be used for primary circuits”, so SC37B decided to delete the 3081
sentence. This decision was made during the IEC SC 37B meeting at Phoenix, U.S.A, in Oct, 3082
2010. 3083
A.3 Technical discussion 3084
A.3.1 General 3085
For the use as surge protective devices (SPD), there are many types of components and the 3086
combined use of them. Some of them are relatively large in size and useful only in the outd oor 3087
facility or in the building circuits. Some are reliable but others may not. 3088
For use with equipment in the scope of IEC 62368-1, varistors and GDT’s are very commonly 3089
available with appropriate physical size and reliability. 3090
3091
Figure A.5 – Safeguards 3092
A.3.2 Recommended SPD and its level of sparkover voltage 3093
The recommended construction of SPD for the purpose of protecting human and the insulations 3094
in the equipment is the combined use of a GDT and a varistor in series, by the reasons 3095
described in this subclause and A.3.3. 3096
The level of sparkover voltage of the SPD constructed as recommended as above is important 3097
and should be selected as higher than withstand voltage level of insulation which SPD is 3098
intended to protect from damage by surge overvoltage. IEC 61643-311 and IEC 61643-312 3099
provides the selection of GDT’s up to 4 500V DC sparkover voltage series (see “A” in 3100
Figure A.5 in this document). 3101
A.3.3 Consideration of a GDT and its follow current 3102
If you are going to use a GDT in the primary circuit, or in the external circuit, you have to take 3103
the follow current in GDT into account. For more information on the GDT’s follow current, see 3104
Clause A.4 in this document. 3105
D
IEC TR 62368-2:20xx © IEC 20xx – 173 –
The follow current in the GDT after the surge transient voltage/current that flows through it may 3106
keep the GDT in the low impedance mode while the equipment power is on, resulting in a risk 3107
of electric shock if somebody touches the circuit connected to the GDT. The combined use of 3108
a GDT and a varistor in series is the common method to avoid this risk. After the transient 3109
overvoltage condition is over, the varistor will stop the GDT ’s follow current. Complying with 3110
Clause G.8 is required for the varistor’s working voltage. It means that 1,25 x Vac is required 3111
for the varistor’s working voltage. After the transient, the varistor will stop the current from the 3112
AC line immediately. 3113
For the reliability of the GDT, it is required that the GDT meets the requirements for electric 3114
strength and the external clearance and creepage distance requirements for reinforced 3115
insulation (see “B” in Figure A.5). 3116
A.3.4 Consideration of varistors and its leak current 3117
If a varistor is used in the primary circuit or in the external circuit, the leakage current in the 3118
varistor has to be taken into account. The continuous current caused by the leakage current 3119
may burn the varistor or other components in the circuit, and is energy inefficient. The combined 3120
use of a GDT and a varistor in series is the common method to avoid this effect, since the GDT 3121
can kill the leakage current just after the surge transient voltage passed through these 3122
components. 3123
For the reliability of the varistor, it has to comply with Clause G.8 (see “C” in Figure A.5 in this 3124
document). 3125
A.3.5 Surge voltage/current from mains 3126
A.3.5.1 Case of transversal transient on primary circuit 3127
A surge caused by lightning may enter in the mains circuit and get into the equipment as a 3128
transversal transient overvoltage. In this case, incorporating an SPD (that may be a varistor 3129
only) between the line and neutral of the primary circuit is an effective method to prevent 3130
damage in the circuit, as the surge is bypassed from line to neutral or vice versa. In this case, 3131
the reliability requirement may not be mandatory for the SPD, because the failure of th e SPD 3132
can lead to an equipment fault condition (out of use) but may not lead to risk to human (see “D” 3133
in Figure A.5 in this document). 3134
A.3.5.2 Case of longitudinal transient on primary circuit 3135
A surge caused by lightning may enter in the mains circuit and get into the equipment as a 3136
longitudinal (common mode) transient overvoltage, which may cause high-level potential 3137
difference between the primary circuit and the external circuits in the equipment. In this case, 3138
providing a bypass circuit from the primary circuit to the reliable bonding, or a bypass circuit 3139
between the primary circuit and the external circuits, or both, incorporating an SPD (a 3140
combined use of a GDT and a varistor in series is recommended) is an effective method to 3141
prevent insulations and components in the equipment from being damaged (see “E” in 3142
Figure A.5 in this document). 3143
For preventing the risk of electrical shock in this case, a bypass circuit connected to the SPD 3144
shall be either connected to the earth, or provided with a suitable safeguard from ES1. (A 3145
double safeguard or a reinforced safeguard between the primary side of an SPD and ES1, 3146
and a basic safeguard between external circuit side of SPD and ES1, see “J” and “G” in 3147
Figure A.5 in this document). 3148
There may be a discussion about the safety of the telecommunication network connected to the 3149
external circuit, but it is presumed that the telecommunication network is appropriately bonded 3150
to the earth through the grounding system. Also, the maintenance person accessing the 3151
telecommunication for maintenance is considered to be a skilled person, and knows that they 3152
should not access the network lines when lightning strikes are observed in the nearby area (see 3153
“F” in Figure A.5 in this document). 3154
– 174 – IEC TR 62368-2:20xx © IEC 20xx
For the risk that the connection of the external circuit to the telecommunication network is 3155
disconnected, the SPD cannot operate. However, in this case, the external circuit is left open 3156
circuit, therefore the telecom side shall have a safeguard to ES1. Under this condition, the SPD 3157
can be the open circuit (see “G” and “F” in Figure A.5 in this document). 3158
A.3.6 Surge voltage/current from external circuits 3159
A.3.6.1 Case of transversal transient on external circuits 3160
A surge caused by lightning may enter from the external circuit (such as the telecommunication 3161
network) as a transversal transient overvoltage. In this case, incorporating an SPD (may be a 3162
GDT only) between the Tip and Ring of the external circuit is the effective method to prevent 3163
damage in the circuit, as the surge is bypassed from one wire of the external circuit to another 3164
wire. In this case, the reliability requirement is not mandatory for the SPD, because the failure 3165
of the SPD can only lead to an equipment fault condition (out of use) but may not lead to risk 3166
to a person (see “H” in Figure A.5 in this document). 3167
A.3.6.2 Case of longitudinal transient on external circuits 3168
A surge caused by lightning may enter the telecommunication network and get into the external 3169
circuit of the equipment as longitudinal (common mode) transient overvoltage, which may 3170
cause high level potential difference between a mains circuit and external circuits. In this 3171
case, providing a bypass circuit between the primary circuit and external circuits, or between 3172
external circuit and bonding, or both, incorporating an SPD (a combined use of a GDT and a 3173
varistor in series is recommended) is an effective method to protect insulations and components 3174
in the equipment (see “I” in Figure A.5 in this document). 3175
For limiting the risk of electrical shock in this case, a bypass circuit connected to the SPD shall 3176
be either connected to the earth, or provided with suitable safeguard from ES1 (A double 3177
safeguard or a reinforced safeguard between the primary side of the SPD and ES1, and a 3178
basic safeguard between the external circuit side of the SPD and ES1, see “J” in Figure A.5 3179
in this document). 3180
About the consideration of some countries that have no polarity of the AC plug, SPDs installed 3181
between power lines in accordance with IEC 60364 will operate and the surge will go into the 3182
AC line (see “I” in Figure A.5 in this document). 3183
A.3.7 Summary 3184
As a summary of the above technical discussions, the following are proposed requirements if a 3185
varistor is connected in series with a GDT and used as safeguard: 3186
– the GDT’s sparkover voltage level should be selected from IEC 61643-311 and IEC 61643-3187
312 in accordance with the bridged insulation (see A.3.2 in this document); 3188
– the GDT shall pass the electric strength test and meet the external clearance and creepage 3189
distance requirements for reinforced insulation (see A.3.3 in this document); 3190
– the varistor shall comply with Clause G.8 (see A.3.3 and A.3.4 in this document); 3191
– the bypass circuit connected to the SPD shall be either connected to earth, or provided with 3192
a suitable safeguard from ES1 (a double safeguard or a reinforced safeguard between 3193
the primary side of the SPD and ES1, and a basic safeguard between the external circuit 3194
side of the SPD and ES1, see A.3.5.2 and A.3.6.2 in this document). 3195
A.4 Information about follow current (or follow-on current) 3196
A.4.1 General 3197
The information was taken from “MITSUBISHI Materials home page” 3198
IEC TR 62368-2:20xx © IEC 20xx – 175 –
A.4.2 What is follow-on-current? 3199
Follow-on-current is literally something that will continue to flow. In this case it is the 3200
phenomenon where the current in a discharge tube continues to flow. 3201
Normally surge absorbers are in a state of high impedance. When a surge enters the absorber 3202
it will drop to a low impedance stage, allowing the surge to bypass the electronic circuit it is 3203
protecting. After the surge has passed, the absorber should return to a high impedance 3204
condition. 3205
However, when the absorber is in a low impedance state and if there is sufficient voltage on the 3206
line to keep the current flowing even when the surge ends, the absorber remains in a discharge 3207
state and does not return to a high impedance state. The current will then continue to flow. This 3208
is the phenomenon known as follow-on-current. 3209
Surge absorbers that display this follow-on-current phenomenon are of the discharge type or 3210
semiconductor switching absorbers. A characteristic of these absorbers is that during surge 3211
absorption (bypass) the operating voltage (remaining voltage) is lower than the starting volt age. 3212
The advantage of this is that during suppression the voltage is held very low, so as to reduce 3213
stress on the equipment being protected. But there can be a problem when the line current of 3214
the equipment is sufficient so that it continues to drive the absorber when the voltage is at a 3215
low state. 3216
Below are more details about the follow-on-current mechanism. The discharge and power 3217
source characteristics for the discharge tube as well as conditions of follow-on-current will be 3218
explained. 3219
A.4.3 What are the V-I properties of discharge tubes? 3220
The micro-gap type surge absorber is one kind of discharge tube. The discharge characteristics 3221
where the part passes through pre-discharge, glow discharge and then arc discharge are shown 3222
in Figure A.6 in this document. 3223
Figure A.6 in this document shows the V-I characteristics relation between voltage and current 3224
for the discharge tube. When the tube discharges, electric current flows and if moves to a glow 3225
discharge state and then an arc state all while the discharge voltage decreases. Conversely, 3226
as the discharge decreases, the voltage increases as it moves from an arc state to a glow state. 3227
3228
Figure A.6 – Discharge stages 3229
– 176 – IEC TR 62368-2:20xx © IEC 20xx
Pre-glow discharge 3230
The voltage that is maintaining this discharge is approximately equal to the DC breakdown 3231
voltage of the part. A faint light can be seen from the part at this point . 3232
Glow discharge 3233
There is a constant voltage rate versus the changing current. The voltage maintai ning this 3234
discharge will depend on the electrode material and the gas in the tube. The discharge light 3235
now covers one of the electrodes. 3236
Arc discharge 3237
With this discharge, a large current flows through the part and it puts out a bright light. The 3238
maintaining voltage at this point (voltage between the discharge tube terminals) is in the 10’s 3239
of volts range. 3240
A.4.4 What is holdover? 3241
When a discharge tube is used on a circuit that has a DC voltage component, there is a 3242
phenomenon where the discharge state in the tube continues to be driven by the current from 3243
the power supply even after the surge voltage has subsided. This is called holdover (see Figure 3244
A.7 in this document). 3245
When holdover occurs, for example, in the drive circuit of a CRT, the screen darkens and 3246
discharge in the absorber continues, which can lead to the glass tube melting, smoking or 3247
burning. 3248
Figure A.7 – Holdover 3249
Holdover can occur when the current can be supplied to the discharge tube due to varying 3250
conditions of output voltage and output resistance of the DC power supply. What are then the 3251
conditions that allow current to continue to flow to the discharge tube? 3252
The relation between the power supply voltage (V0), serial resistance (R), discharge current (I) 3253
and the terminal voltage (v) are shown in the linear relation below: 3254
v = V0 – I x R 3255
If the voltage V0 is fixed, the slope of the power supply output characteristic line increases or 3256
decreases according to the resistance and may or may not intersect with the V-I characteristics 3257
of the discharge tube. 3258
IEC TR 62368-2:20xx © IEC 20xx – 177 –
The characteristic linear line of a power supply shows the relation between the output voltage 3259
and current of the power supply. Likewise, the V-I curve of a discharge tube shows the relation 3260
between the voltage and current. 3261
When static surge electricity is applied to the discharge tube, the shape of the curve shows that 3262
the surge is being absorbed during arc discharge. 3263
As the surge ends, the discharge goes from arc discharge to glow discharge and then to the 3264
state just prior to glow discharge. At this time the relationship between the discharge tubes V -I 3265
curve and the power supply’s output characteristics are very important. 3266
As shown in the figure, with a high resistance in the power supply, the o utput characteristic line 3267
(pink) and the discharge tubes V-I characteristic curve (red) never intersect. Therefore, current 3268
will not flow from the power supply and follow-on-current will not occur. 3269
However, when the output characteristic line of the power supply (pink) intersects with the V-I 3270
curve of the discharge tube (red), it is possible for current from the power supply to flow into 3271
the discharge tube. When the surge ends, the current should decrease from arc discharge to 3272
the pre-glow state, but instead the power supply will continue to drive the current where it 3273
intersects in the glow or arc discharge region. This is called holdover, and is the condition where 3274
the power supply continues to supply current to the discharge tube at the intersection on its 3275
characteristic line and the discharge tubes V-I curve. 3276
Figure A.8 in this document shows where the power supply can continue supplying current to 3277
the discharge tube when its characteristic line intersects the discharge tubes V-I line in the glow 3278
or arc discharge sections. 3279
Figure A.8 – Discharge 3280
To prevent holdover from occurring, it is important to keep the V-I characteristic line of the 3281
power supply from intersecting with the V-I curve of the discharge tube. 3282
A.4.5 Follow-on-current from AC sources? 3283
When using the discharge tube for AC sources, when follow-on-current occurs as per the case 3284
with DC it is easy to understand. 3285
That is, as can be seen in the figure below, the only difference is that the power supply voltage 3286
(V0) changes with time. 3287
As shown on the previous page, when the power supply voltage is shown as V0(t), the output 3288
power characteristics are displayed as follows: 3289
– 178 – IEC TR 62368-2:20xx © IEC 20xx
v = V0(t) – R x I 3290
where 3291
v is the the voltage at the power out terminal 3292
I is the current of the circuit 3293
V0(t) will vary with time, so when displaying the above equation on a graph, it will appear as in 3294
Figure A.9 in this document on the left. Then when V0 (t) is shown as: 3295
V0(t) = V0 sin wt 3296
When the power supply voltage becomes 0 (zero cross), there is a short time around this 3297
crossing where the voltage range and time range of the power supply output and discharge tube 3298
V-I curve do not intersect. 3299
For an AC power supply, because there is always a zero crossing of the supply’s voltage, more 3300
than holdover it is easier to stop the discharge. In the vicinity of the zero crossing, it is 3301
impossible to maintain the discharge since the current to the discharge is cut off. The discharge 3302
is then halted by the fact that the gas molecules, which were ionized during this time, return to 3303
their normal state. 3304
Because the terminal voltage does not exceed the direct current break down voltage, if the 3305
discharge is halted it will not be able to start again. 3306
However, if the gas molecules remain ionized during this period and voltage is again applied to 3307
both terminals of the discharge tube (enters the cycle of opposite voltage), this newly applied 3308
voltage will not allow the discharge to end and it will continue in the discharge mode. This is 3309
follow-on-current for alternating current. 3310
When follow-on-current occurs, the tube stays in a discharge mode and the glass of the tube 3311
will begin to smoke, melt and possibly ignite. 3312
IEC TR 62368-2:20xx © IEC 20xx – 179 –
3313
3314
Figure A.9 – Characteristics 3315
It is important to insert a resistance in series that is sufficiently large to prevent follow -on-3316
current from occurring according to the conditions of the alternating current. 3317
– 180 – IEC TR 62368-2:20xx © IEC 20xx
Picture 1: with 0 Ω (follow-on current occurs)
Picture 2: with 0,5 Ω (follow-on current is stopped within half a wave)
3318
Figure A.10 – Follow on current pictures 3319
With 1 Ω and 3 Ω resistance, results are the same as those in picture 2, follow-on-current is 3320
interrupted and discharge stops (see Figure A.10 in this document). 3321
For AC power sources, the resistance value that is connected in series with the discharge tube 3322
is small in comparison to DC sources. 3323
If the series resistance is 0,5 Ω or greater it should be sufficient, however for safety a value of 3324
3 Ω (for 100 V) or greater is recommended. 3325
In addition there is also a method to use a varistor in series that acts as a resistor. In this case 3326
the varistor should have an operating voltage greater than the AC voltage and be placed in 3327
series with the discharge tube. Unlike the resistor, discharge will be stopped without follow -on-3328
current occurring during the first half wave. 3329
Recommended varistor values are: 3330
– for 100 VAC lines: a varistor voltage of 220 V minimum; 3331
– for 200 VAC lines: a varistor voltage of 470 V minimum. 3332
IEC TR 62368-2:20xx © IEC 20xx – 181 –
A.4.6 Applications with a high risk of follow-on-current 3333
1) Holdover: CRT circuits and circuits using DC power supplies 3334
2) Follow-on-current: Circuits using AC power source 3335
3336
– 182 – IEC TR 62368-2:20xx © IEC 20xx
Annex B 3337
(informative) 3338
3339
Background information related to measurement of discharges – 3340
Determining the R-C discharge time constant for X- and Y-capacitors 3341
B.1 General 3342
Since the introduction of 2.1.1.7, “Discharge of capacitors in equipment,” in IEC 60950-1:2013, 3343
questions continually arise as to how to measure the R-C discharge time constant. The objective 3344
of this article is to describe how to measure and determine the discharge time constant. 3345
B.2 EMC filters 3346
EMC filters in equipment are circuits comprised of inductors and capacitors arranged so as to 3347
limit the emission of RF energy from the equipment into the mains supply line. In EMC filters, 3348
capacitors connected between the supply conductors ( for example, between L1 and L2) of the 3349
mains are designated as X capacitors. Capacitors connected between a supply conductor and 3350
the PE (protective earthing or grounding) conductor are designated as Y capacitors (Safety 3351
requirements for X and Y capacitors are specified in IEC 60384-14 and similar national 3352
standards). The circuit of a typical EMC filter is shown in Figure B.1. CX is the X capacitor, and 3353
CY are the Y capacitors. 3354
3355
Figure B.1 – Typical EMC filter schematic 3356
B.3 The safety issue and solution 3357
When an EMC filter is disconnected from the mains supply line, both the X (Cx) and the Y (CYa 3358
and CYb) capacitors remain charged to the value of the mains supply voltage at the instant of 3359
disconnection. 3360
Due to the nature of sinusoidal waveforms, more than 66 % of the time (30° to 150° and 210° 3361
to 330° of each cycle) the voltage is more than 50 % of the peak voltage. For 230 V mains (325 3362
Vpeak), the voltage is more than 162 V for more than 66 % of the time of each cycle. So, the 3363
IEC TR 62368-2:20xx © IEC 20xx – 183 –
probability of the voltage exceeding 162 V at the time of disconnection is 0,66. This probability 3364
represents a good chance that the charge on the X and Y capacitors will exceed 162 V. 3365
If a hand or other body part should touch both pins (L1 and L2) of the mains supply plug at the 3366
same time, the capacitors will discharge through that body part. If the total capacitance exceeds 3367
about 0,1 µF, the discharge will be quite painful. 3368
To safeguard against such a painful experience, safety documents require that the capacitors 3369
be discharged to a non-painful voltage in a short period of time. The short period of time is 3370
taken as the time from the disconnection from the mains to the time when contact with both 3371
pins is likely. Usually, this time is in the range of 1 s to 10 s, depending on the documents and 3372
the type of attachment plug cap installed. 3373
B.4 The requirement 3374
The time constant is measured with an oscilloscope. The time constant and its parameters are 3375
defined elsewhere. 3376
The significant parameters specified in the requirement are the capacitance exceeding 0,1 µF 3377
and the time constant of 1 s or less (for pluggable equipment type A) or 10 s or less (for 3378
pluggable equipment type B). These values bound the measurement. This attachment 3379
addresses pluggable equipment type A and the 1 s time constant requirement. The 3380
attachment applies to pluggable equipment type B and the time constant is changed to 10 s. 3381
Pluggable equipment type A is intended for connection to a mains supply via a non-industrial 3382
plug and socket-outlet. Pluggable equipment type B is intended for connection to a mains 3383
supply via an industrial plug and socket-outlet. 3384
The document presumes that measurements made with an instrument having an input 3385
resistance of 95 M to 105 M and up to 25 pF in parallel with the impedance and capacitance 3386
of the equipment under test (EUT) will have negligible effect on the measured time constant. 3387
The effect of probe parameters on the determination of the time constant is discussed 3388
elsewhere in this document. 3389
The requirement specifies a time constant rather than a discharge down to a specified voltage 3390
within a specified time interval. If the document required a discharge to a specific voltage, then 3391
the start of the measurement would need to be at the peak of the voltage. This would mean that 3392
the switch (see Figure B.5) would need to be opened almost exactly at the peak of the voltage 3393
waveform. This would require special switching equipment. The time constant is specified 3394
because it can be measured from any point on the waveform (except zero), see Figure B.4b. 3395
B.5 100 M probes 3396
Table B.1 in this document is a list of readily available oscilloscope probes with 100 M input 3397
resistance and their rated input capacitances (the list is not exhaustive). Also included is a 400 3398
M input resistance probe and a 50 M input resistance probe. 3399
– 184 – IEC TR 62368-2:20xx © IEC 20xx
Table B.1 – 100 M oscilloscope probes 3400
Manufacturer Input resistance
M
Input capacitance
pF
A 100 1
B 100 6,5
C 100 3
D 400 10 – 13
E 100 2,5
F 50 5,5
3401
Note that the input capacitances of the 100 M probe input capacitances are very much less 3402
than the maximum capacitance of 25 pFs. This attachment will discuss the effect of the probe 3403
capacitance and the maximum capacitance elsewhere. 3404
100 M probes are meant for measuring high voltages, typically 15 kV and more. These probes 3405
are quite large and are awkward to connect to the pins of a power plug. 3406
3407
Figure B.2 – 100 M oscilloscope probes
General purpose oscilloscope probes have 10 M input resistance and 10 pF to 15 pF input 3408
capacitance. General-purpose probes are easier to connect to the pins of the power plug. This 3409
attachment shows that a 10 M, 15 pF probe can be used in place of a 100 M probe. 3410
B.6 The R-C time constant and its parameters 3411
Capacitor charge or discharge time can be expressed by the R-C time constant parameter. One 3412
time constant is the time duration for the voltage on the capacitor to change 63 %. In five time 3413
constants, the capacitor is discharged to almost zero. 3414
IEC TR 62368-2:20xx © IEC 20xx – 185 –
Table B.2 – Capacitor discharge 3415
Time constant Percent capacitor voltage (or
charge)
Capacitor voltage
(230 Vrms
, 331 Vpeak
)
0 100 325
1 37 120
2 14 45
3 5 16
4 2 6
5 0,7 2
3416
The values in Table B.2 in this document are given by: 3417
)(
0RC
t
t eVV−
= 3418
where: 3419
tV is the voltage at time t 3420
0V is the voltage at time 0 3421
R is the resistance, in 3422
C is the capacitance, in F (Farads) 3423
t is the time, in s 3424
3425
The time constant is given by the formula: 3426
EUTEUTEUT CRT = 3427
where: 3428
EUTT is the time, in seconds, for the voltage to change by 63 % 3429
EUTR is the EUT resistance, in 3430
EUTC is the EUT capacitance, in F (Farads) 3431
In the equipment under test (EUT), the EUT capacitance, CEUT, in the line filter (Figure B.1) 3432
includes both the X-capacitor and the Y-capacitors. 3433
The two Y-capacitors, CYa and CYb, are in series. The resultant value of two capacitors in series, 3434
CY, is: 3435
YbYa
YbYa
YCC
CCC
+
= 3436
Assuming the two Y-capacitors have the same value, their L1-L2 value is one-half of the value 3437
of one of the capacitors. 3438
– 186 – IEC TR 62368-2:20xx © IEC 20xx
The X-capacitor is in parallel with the two Y-capacitors. The EUT capacitance is: 3439
YXEUT CCC += 3440
The EUT resistance is the resistance, REUT, in the EUT that is used for discharging the 3441
capacitance. 3442
The time constant, TEUT, in s, is the product of the EUT capacitance in farads and the EUT 3443
resistance in . More useful units are capacitance in µF and resistance in M. 3444
Two parameters of the time constant formula are given by the requirement: EUT capacitance is 3445
0,1 µF or larger and the EUT time constant does not exceed 1 s. Solving the time constant 3446
formula for EUT resistance: 3447
EUTEUTEUT CTR = 3448
Substituting the values: 3449
1 / 0,1EUTR s F= 3450
10 = MREUT 3451
This means that the EUT resistance is no greater than 10 M if the EUT capacitance is 0,1 µF 3452
or greater. The combinations of EUT resistance and EUT capacitance for EUT time constant of 3453
1 s are shown in Figure B.3 in this document. 3454
Figure B.3 – Combinations of EUT resistance and capacitance for 1 s time constant
IEC TR 62368-2:20xx © IEC 20xx – 187 –
B.7 Time constant measurement. 3455
The objective is to measure and determine the EUT time constant. 3456
Measurement of the time constant is done with an oscilloscope connected to th e mains input 3457
terminals of the equipment under test (EUT). Mains is applied to the EUT, the EUT is turned 3458
off, and then the mains is disconnected from the EUT. The EUT is turned off because the load 3459
circuits of the EUT may serve to discharge the EUT capacitance. The resulting oscilloscope 3460
waveform, the AC mains voltage followed by the discharge of the total capacitance, is shown 3461
in Figure B.4 in this document. 3462
– 188 – IEC TR 62368-2:20xx © IEC 20xx
a) 240 V mains followed by capacitor discharge V = 50 V/div, H = 1 s/div
3463
b) 240 V mains followed by capacitor discharge V = 50 V/div, H = 0,2 s/div
Figure B.4 – 240 V mains followed by capacitor discharge 3464
The time constant is the time duration measured from the instant of disconnection to a point 3465
that is 37 % of the voltage at the instant of disconnection. 3466
The problem is that the process of measurement affects the measured time constant. This is 3467
because the oscilloscope probe has a finite resistance and capac itance, see Figure B.5 in this 3468
document. 3469
IEC TR 62368-2:20xx © IEC 20xx – 189 –
Figure B.5 – Time constant measurement schematic 3470
The probe resistance, Rprobe, is in parallel to the EUT resistance, REUT. And, the probe 3471
capacitance, Cprobe, is in parallel with the EUT capacitance, CEUT. 3472
The measured time constant, Tmeasured, is a function of the Thevenin equivalent c ircuit 3473
comprised of Rtotal and Ctotal. The measured time constant is given by: 3474
totaltotalmeasured CRT = 3475
where: 3476
measuredT is the measured time for the voltage to change by 63 % 3477
totalR is the total resistance, both the probe and the EUT 3478
totalC is the total capacitance, both the probe and the EUT 3479
Rtotal is: 3480
EUTprobe
EUTprobe
totalRR
RRR
+
= 3481
Ctotal is: 3482
Combining terms, the measured time constant is: 3483
)()( EUTprobe
EUTprobe
EUTprobe
measured CCRR
RRT +
+
= 3484
– 190 – IEC TR 62368-2:20xx © IEC 20xx
In this formula, Tmeasured, Rprobe, and Cprobe are known. Tmeasured is measured with a given 3485
probe. Rprobe and Cprobe are determined from the probe specifications (see examples in 3486
Table B.1 in this document). Elsewhere, we shall see that Cprobe is very small and can be 3487
ignored. 3488
EUTtotal CC = 3489
The measured time constant can now be expressed as: 3490
total
EUTprobe
EUTprobe
measured CRR
RRT
+
= )( 3491
B.8 Effect of probe resistance 3492
As has been shown, the EUT discharge resistance, REUT, is 10 M or less in order to achieve 3493
a 1 s time constant with a 0,1 µF capacitor or larger. 3494
Rtotal is comprised of both the EUT discharge resistance REUT, and the probe resistance, Rprobe. 3495
If REUT is 10 M and CEUT is 0,1 µF, then we know that TEUT is 1 s. If we measure the time 3496
constant with a 100 M probe, the parallel combination of REUT and Rprobe is about 9,1 M and 3497
the measured time constant, Tmeasured, will be: 3498
totaltotalmeasured CRT = 3499
FMTmeasured 1,01,9 = 3500
sTmeasured 91,0= 3501
So, for a CEUT of 0,1 µF capacitance and a REUT of 10 M, a measured time constant (using a 3502
100 M probe), Tmeasured, of 0,91 s would indicate a EUT time constant, TEUT, of 1 s. 3503
If we substitute a 10 M probe for the same measurement, then Rtotal, the parallel combination 3504
of REUT (10 M) and Rprobe (10 M), is 5 M. The measured time constant, Tmeasured, will be: 3505
totaltotalmeasured CRT = 3506
FMTmeasured 1,05 = 3507
sTmeasured 5,0= 3508
So, for a CEUT of 0,1 µF capacitance and a REUT of 10 M, the measured time constant (using 3509
a 10 M probe), Tmeasured, is 0,5 s and would indicate a EUT time constant, TEUT, of 1 s. 3510
IEC TR 62368-2:20xx © IEC 20xx – 191 –
B.9 Effect of probe capacitance 3511
According to the document, CEUT is 0,1 µF or more. Also, according to the document, Cprobe is 3512
25 pF or less. Assuming the worst case for Cprobe, the total capacitance is: 3513
EUTprobetotal CCC += 3514
uFuFCtotal 1,0000025,0 += 3515
uFCtotal 100025,0= 3516
The worst-case probe capacitance is extremely small (0,025 %) compared to the smallest CEUT 3517
capacitance (0,1 µF) and can be ignored. We can say that: 3518
EUTtotal CC = 3519
B.10 Determining the time constant 3520
According to the document, TEUT may not exceed 1 s. 3521
1=EUTT 3522
EUTEUT CR =1 3523
where: 3524
EUTR is 10 M or less 3525
EUTC is 0,1 µF or more 3526
The problem is to determine the values for REUT and CEUT. Once these values are known, the 3527
equipment time constant, TEUT, can be determined by calculation. 3528
As shown in Figure B.1 in this document, REUT can be measured directly with an ohmmeter 3529
applied to the mains input terminals, for example, between L1 and L2. Care is taken that the 3530
capacitances are fully discharged when the resistance measurement is made. Any residual 3531
charge will affect the ohmmeter and its reading. Of course, if the circuit is provided with a 3532
discharge resistor, then the capacitances will be fully discharged. If the circuit does not have a 3533
discharge resistor, then the ohmmeter will provide the discharge path, and the reading will 3534
continuously increase. 3535
CEUT can also be measured directly with a capacitance meter. Depending on the particular 3536
capacitance meter, REUT may prevent accurate measurement of CEUT. For the purposes of this 3537
paper, we assume that the capacitance meter cannot measure the CEUT. In this case, we 3538
measure the time constant and compensate for the probe resistance. 3539
So, the time constant is measured, and the probe resistance is accounted for. 3540
Since probe resistance is more or less standardized, we can calculate curves for 100 M and 3541
10 M probes for all maximum values of REUT and CEUT. The maximum values for combinations 3542
– 192 – IEC TR 62368-2:20xx © IEC 20xx
of REUT, CEUT (Ctotal), Rprobe, Rtotal and Tmeasured are given in Table B.3 in this document. 3543
(Rprobe and Rtotal values are rounded to 2 significant digits.) 3544
Table B.3 – Maximum Tmeasured values for combinations of REUT 3545
and CEUT for TEUT of 1 s 3546
TEUT
s
CEUT
(Ctotal
)
µF
REUT
M
Rprobe
M
Rtotal
M
Tmeasured
s
1 0,1 10 100 9,1 0,91
1 0,2 5 100 4,8 0,95
1 0,3 3,3 100 3,2 0,97
1 0,4 2,5 100 2,4 0,97
1 0,5 2 100 2,0 0,98
1 0,6 1,7 100 1,6 0,98
1 0,7 1,4 100 1,4 0,99
1 0,8 1,25 100 1,2 0,99
1 0,9 1,1 100 1,1 0,99
1 1,0 1 100 1,0 0,99
1 0,1 10 10 5,0 0,50
1 0,2 5 10 3,3 0,67
1 0,3 3,3 10 2,5 0,75
1 0,4 2,5 10 2,0 0,80
1 0,5 2 10 1,7 0,83
1 0,6 1,7 10 1,4 0,86
1 0,7 1,4 10 1,25 0,88
1 0,8 1,25 10 1,1 0,89
1 0,9 1,1 10 1,0 0,90
1 1,0 1 10 0,91 0,91
3547
For each value of REUT and Rprobe we can calculate the worst-case measured time constants, 3548
Tmeasured for a TEUT of 1 s. These are shown in Figure B.6 in this document. 3549
The process is: 3550
– With the unit disconnected from the mains and the power switch “off,” measure the 3551
resistance between the poles of the EUT. Repeat with the power switch “on” as the filter 3552
may be on the load side of the power switch. Select the higher value as REUT. 3553
– Connect the oscilloscope probe between L1 and L2 as shown in Figure B.5 in this document. 3554
For safety during this test, use a 1:1 isolating transformer between the mains and the EUT. 3555
Set the scope sweep speed to 0,2 ms per division (2 s full screen). 3556
– When the display is about 1 or 2 divisions from the start, turn the test switch off, and me asure 3557
the time constant as shown in Figure B.4 in this document. This step may need to be 3558
repeated several times to get a suitable waveform on the oscilloscope. This step should be 3559
performed twice, once with the EUT power switch “off” and once with the EUT power switch 3560
“on.” Select the maximum value. This value is Tmeasured. 3561
– Plot REUT and Tmeasured on the chart, Figure B.6 in this document. 3562
IEC TR 62368-2:20xx © IEC 20xx – 193 –
If the point is below the curve of the probe that is used to measure the time constant, then the 3563
EUT time constant, TEUT, is less than 1 s. 3564
3565
Figure B.6 – Worst-case measured time constant values for 100 M and 10 M probes 3566
B.11 Conclusion 3567
Measurement of the time constant can be made with any probe, not just a 100 M probe. Ideally, 3568
the probe input resistance should be at least equal to the worst -case EUT discharge resistance 3569
(10 M for pluggable equipment type A) or higher. The effect of the probe input resistance is 3570
given by the equation for Rtotal. 100 M probes, while approaching ideal in terms of the effect 3571
on the measured time constant, are bulky and expensive and not necessary. 3572
The document is a bit misleading by ignoring a 9 % error when a 100 M probe is used to 3573
measure the time constant associated with a 10 M discharge resistor (see Figure B.5 in this 3574
document). 3575
3576
– 194 – IEC TR 62368-2:20xx © IEC 20xx
Annex C 3577
(informative) 3578
3579
Background information related to resistance to candle flame ignition 3580
In line with SMB decision 135/20, endorsing the ACOS/ACEA JTF recommendations, the former 3581
Clause 11 was added to the document up to CDV stage. However, the CDV was rejected and 3582
several national committees indicated that they wanted to have the requirements removed from 3583
the document. At the same time, several countries indicated that they wanted the requirements 3584
to stay, while others commented that they should be limited to CRT televisions only. 3585
IEC TC 108 decided to publish the requirements as a separate document so that the different 3586
issues can be given appropriate consideration. 3587
3588
3589
IEC TR 62368-2:20xx © IEC 20xx – 195 –
Bibliography 3590
IEC 60065:2014, Audio, video and similar electronic apparatus – Safety requirements 3591
IEC 60215, Safety requirements for radio transmitting equipment – General requirements and 3592
terminology 3593
IEC 60364-4-43, Low-voltage electrical installations – Part 4-43: Protection for safety – 3594
Protection against overcurrent 3595
IEC 60364-5-52, Low-voltage electrical installations – Part 5-52: Selection and erection of 3596
electrical equipment – Wiring systems 3597
IEC 60364-5-54, Low-voltage electrical installations – Part 5-54: Selection and erection of 3598
electrical equipment – Earthing arrangements and protective conductors 3599
IEC 60446, Identification by colours or numerals2 3600
IEC TS 60479-2, Effects of current on human beings and livestock – Part 2: Special aspects 3601
IEC 60664-2 (all parts), Insulation coordination for equipment within low-voltage systems – Part 3602
2: Application guide 3603
IEC 60664-4:2005, Insulation coordination for equipment within low-voltage systems – Part 4: 3604
Consideration of high-frequency voltage stress 3605
IEC 60695-2 (all parts), Fire hazard testing – Part 2: Glowing/hot-wire based test methods 3606
IEC 60695-2-13, Fire hazard testing – Part 2-13: Glowing/hot-wire based test methods – Glow-3607
wire ignition temperature (GWIT) test method for materials 3608
IEC 60695-11-2, Fire hazard testing – Part 11-2: Test flames – 1 kW nominal pre-mixed flame 3609
– Apparatus, confirmatory test arrangement and guidance 3610
IEC 60950-1:2005, Information technology equipment – Safety – Part 1: General requirements 3611
IEC 60950-1:2005/AMD1:2009 3612
IEC 60950-1:2005/AMD2:2013 3613
IEC 61010-1, Safety requirements for electrical equipment for measurement, control, and 3614
laboratory use – Part 1: General requirements 3615
IEC 61051-1, Varistors for use in electronic equipment – Part 1: Generic specification 3616
ISO/IEC Guide 51:1999, Safety aspects — Guidelines for their inclusion in standards 3617
ITU-T K.21:2008, Resistibility of telecommunication equipment installed in customer premises 3618
to overvoltages and overcurrents 3619
EN 41003:2008, Particular safety requirements for equipment to be connected to 3620
telecommunication networks and/or a cable distribution system 3621
EN 60065:2002, Audio, video and similar electronic apparatus – Safety requirements 3622
___________
2 This publication was withdrawn.
– 196 – IEC TR 62368-2:20xx © IEC 20xx
NFPA 70, National Electrical Code 3623
NFPA 79:2002, Electrical Standard for Industrial Machinery 3624
UL 1667, UL Standard for Safety Tall Institutional Carts for Use with Audio-, Video-, and 3625
Television-Type Equipment 3626
UL 1995, UL Standard for Safety for Heating and Cooling Equipment 3627
UL 2178, Outline for Marking and Coding Equipment 3628
UL 60065, Audio, Video and Similar Electronic Apparatus – Safety Requirements 3629
UL/CSA 60950-1, Information Technology Equipment – Safety – Part 1: General Requirements 3630
CAN/CSA C22.1, Information Technology Equipment – Safety – Part 1: General Requirements 3631
CSA C22.1-09, Canadian Electrical Code – Part I: Safety Standard for Electrical Installations – 3632
Twenty-first Edition 3633
ASTM C1057, Standard Practice for Determination of Skin Contact Temperature from Heated 3634
Surfaces Using A Mathematical Model and Thermesthesiometer 3635
EC 98/37/EC Machinery Directive 3636
3637
_____________ 3638
3639