18
University College Cork Energy Review 2016/17 Student: Pat Mehigan. Word count: 3ing Executive Summary

University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

University College Cork

Energy Review

2016/17

Student: Pat Mehigan.

Word count: 3ing Executive Summary

Page 2: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 2 of 18

EXECUTIVE SUMMARY 3

1 PAST AND PRESENT ENERGY USE 6

1.1 Electrical 6

1.2 Natural Gas 7

2 SIGNIFICANT ENERGY USERS ELECTRICAL 8

3 SIGNIFICANT ENERGY USERS NATURAL GAS 9

4 ENERGY BASELINE & ACTION PLAN 10

4.1 Electrical 10

4.2 Natural Gas 14

Page 3: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 3 of 18

EXECUTIVE SUMMARY

This document records the results of an energy review, undertaken in Q3 2017, of the

operations at University College Cork (UCC). The scope was to review the electrical and

natural gas users and to determine the significant energy users (SEU’s), identify the variables

and people that impact them, identify areas for maintaining and improving energy

performance. The results were obtained from metering information available on the site

metering package and the available billing data. From the review the site SEU’s were

determined based on:

The amount of energy they use.

And / or

The ability to reduce the energy consumption through the register of energy saving

opportunities.

The approach to energy management for 2016/17 focussed on housekeeping measures and

engaging with the SEU’s through the saver saves scheme, where applicable, to understand

how the buildings are used by the departments.

The objective for 2016/17 was to maintain the existing consumption levels for UCC, despite

the planned increases in occupied space, namely the Western Gateway and Food Science

Building. Through ongoing investment, monitoring and engagement with the SEU’s, UCC

achieved a 0.6% decrease in electrical energy and a 8.5% decrease in natural gas

consumption.

16 electrical energy saving projects were completed in 2016/17 and resulted in savings of

440,000 kWh/year. (See appendix III for details).

8 out of 13 electrical SEU’s reported a drop in annual consumption levels totalling 0.6

GWh/year while the remaining 5 SEU’s saw a total increase of 0.3 GWh/year, with the WGB

alone accounting for an increase of 0.16 GWh/year.

Natural gas reduction is mainly attributable to the reduced operating hours of the CHP’s

(discussed further in appendix II) as well as slight savings in other SEU’s.

10 natural gas energy saving projects were completed in 2016/17 and resulted in savings of

55,000 kWh/year. (See appendix III for details).

Page 4: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 4 of 18

CAUL are excluded from the scope of this review as well as Tyndall National Institute and the

Mardyke Arena as both areas operate their own independent ISO50001 process.

The objective for 2017/18 is to expand the saver saves scheme, using the Boole Library as the

template and to reduce the existing consumption levels for UCC, despite the planned

increases in occupied space, namely the Western Gateway and Food Science Building.

Based on this energy review and the action plan, the predicted Oct 2017 to Sept 2018

consumption levels are:

19,520,000 kWh of electrical energy and 17,650,000 kWh of natural gas.

The 2017/18 SEU’s and the appropriate EnPI’s for electrical and gas consumption are detailed

in the tables below.

Table of Electrical SEU’s and their EnPIs for 2017/18 at UCC

SEU % of Electrical Energy across UCC

EnPI ( in term) weekly kWhr EnPI (out of term) weekly kWhr

WGB 20.2 82,147 82,147

Food Science 10.6 39,842 39,842

Kane 10.5 41,224 36,850

Boole 8.6 34,604 22,817

Bioscience 8.4 31,376 31,376

Brookfield 6.7 27,140 22,690

Pharmacy 5.1 18,792 15,667

ORB 3.9 15,419 12,476

Student Centre 2.5 8,965 5,822

BSU 2.3 8,798 8,798

ERI 2 8,742 6,710

Aula Maxima 1.7 6,895 5,635

Glucksman 1.6 6,450 5,042

The above SEU’s account for 84.1% of the electricity consumed across UCC.

Page 5: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 5 of 18

Table of Thermal SEU’s and their EnPIs for 2017/18 at UCC

SEU Why EnPI 2017/18

kWh/week

CHP Significant natural gas user, producing electricity and using the waste heat for building heating as well as steam for heating and process requirements – accounts for 53% of NG use

Note1

Main Campus Boilers

Significant natural gas user, producing steam for heating and process requirements – accounts for 13.5% of NG use

Base load of

20,388 kWh with 2965 kW per HDD (13)

Brookfield Significant natural gas user for heating– accounts for 4% of NG use

Base load of

3,082 kWh with 1010 kW per HDD (13)

WGB Significant natural gas user for heating– accounts for 4% of NG use

Base load of

1092 kWh with 467 kW per HDD (17)

Food Science Significant natural gas user for heating– accounts for 3.2 % of NG use

Base load of

4,4407 kWh with 647 kW per HDD (12)

Pharmacy Significant natural gas user for heating– accounts for 2.9 % of NG use

Base load of

4,148kWh with 616 kW per HD (13)

BSU Significant natural gas user for heating– accounts for 2.9 % of NG use

Base load of

5,123 kWh with 360 kW per HDD (15)

ORB Significant natural gas user for heating– accounts for 2.2% of NG use

Base load of

682 kWh with 617 kW per HDD (13)

Bioscience Significant natural gas user for heating– accounts for 2.1 % of NG use

Base load of

4,709 kWh with 361 kW per HDD (13)

The above SEU’s account for 88.8 % of the natural gas consumed across UCC.

Note 1: No valid EnPI available.

Page 6: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 6 of 18

1 PAST AND PRESENT ENERGY USE

1.1 Electrical

The table below shows the annual electrical energy use (GWh/a) since 2008/9

Area 08/9 09/10 10/11 11/12 12/13 13/14 14/15 15/16 16/17

UCC- all 21.3 20.8 20.7 20.63 20.10 19.79 19.91 19.78 19.65

WGB 1.2 1.41 2.13 2.97 2.74 3.02 3.20 3.81 3.97

FSB 2.11 2.19 2.06 2.09 2.15 2.26 2.27 2.36 2.1

Kane 2.48 2.54 2.40 2.32 2.15 2.03 2.09 2.01 2.0

Boole 2.60 2.63 2.40 2.13 1.99 1.99 1.91 1.82 1.69

Bio 1.81 1.90 1.76 1.74 1.72 1.63 1.63 1.60 1.64

BHSC 1.3 1.27 1.25 1.17 1.19 1.21 1.29 1.28 1.32

Pharm NA NA 1.11 1.18 1.15 1.17 1.01 0.98 1.01

ORB 0.99 0.96 0.72 0.85 0.85 0.85 0.88 0.82 0.77

Student 0.64 0.63 0.56 0.59 0.56 0.62 0.56 0.54 0.48

ERI 0.50 0.48 0.46 0.44 0.43 0.42 0.42 0.41 0.40

BSU 0.40 0.43 0.43 0.43 0.44 0.53 0.44 0.40 0.44

Aula 0.35 0.36 0.31 0.36 0.36 0.34 0.34 0.35 0.33

Glucksman 0.45 0.25 0.42 0.13 0.42 0.42 0.44 0.40 0.30

The electrical energy consumption for 2016/17 was compared with degree day data (cooling

and heating) and no meaningful correlation was found between the two.

Page 7: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 7 of 18

1.2 Natural Gas

The table below shows the annual natural gas use (GWh/a), where available, since 2008/9.

Year 08/9 09/10 10/11 11/12 12/13 13/14 14/15 15/16 16/17

UCC- all 23.00 23.2 23.44 19.20 21.90 19.32 28.59

note 1

37.26

note 1

34.1

CHP NA NA NA NA NA NA 11.2

note 1

21.59

note 1

17.79

Campus

Boilers

5.3 5.93 6.96 4.48 4.76 4.07 4.58 3.85 4.45

BHSC 1.65 1.53 1.48 1.53 1.48 1.31 1.40 1.43 1.35

East skid 2.35 2.20 1.95 1.68 2.06 1.88 1.94 1.59 1.66

Pharm NA NA NA NA NA 1.16 1.02 0.92 0.98

FSB NA NA NA NA NA 0.90 0.96 0.91 1.01

Bio NA NA NA NA NA 0.94 0.87 0.80 0.69

WGB 0.74 0.60 0.68 0.52 0.87 0.68 0.89 1.08 1.35

BSU 0.83 1.04 0.96 0.87 1.09 0.84 0.99 0.91 0.96

Note 1: Increase in the CHP gas consumption associated with the change of ownership from third party vendor to UCC in April 2015.

Page 8: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 8 of 18

2 SIGNIFICANT ENERGY USERS ELECTRICAL

From the 2016/17 energy review, the SEU’s were selected based on the amount of energy

they use or the ability to reduce their energy consumption.

SEU Description % of Site

energy use

WGB WGB building, located on the Western Road houses

lecture rooms, offices, conferencing facilities, Labs.

20.2

Food Science

Building

A research intensive building, FSB houses labs, dairy

processing, brewery, meat processing areas as well as

office spaces.

10.6

Kane Building The Kane building is home to research labs, IT data

centre, Lecture theatres and offices.

10.5

Boole Library Main Campus library. 8.6

Bioscience The building accommodates scientific labs, seminar

rooms and office rooms.

8.4

Brookfield Teaching rooms, medical simulation labs, offices and lecture halls.

6.7

Pharmacy Houses Labs, lecture halls, cleanroom and café. 5.1

ORB Home to offices, classrooms and café. 3.9

Student Centre UCC student centre, i.e. shops, computer rooms, halls, bar and café.

2.5

BSU Home to research labs 2.3

ERI Environmental Research Building, offices, heat pump, research labs.

2.0

Aula Located in the Quad, home to offices , conference rooms.

1.7

Glucksman UCC art gallery. 1.6

Others Other sites (91) account for the remaining 15.9% of energy use.

15.9

Appendix I gives a summary of the electrical SEU’s, detailing their 2016/17 performance,

2017/18 targets, operational controls etc.

Page 9: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 9 of 18

3 SIGNIFICANT ENERGY USERS NATURAL GAS

From the 2016/17 energy review, the SEU’s were selected based on the amount of natural

gas they consume and/or the ability to reduce their consumption.

Area Description % of Site gas

use

CHP 2 off CHP units used to generate steam and LPHW. 53

Main Campus Steam boilers

2 off Natural Gas fired shell & tube boilers that generate steam at 7 bar gauge.

13.5

Brookfield Gas feed for boilers / café. 4

WGB Gas feed for boilers / café. 4

Food Science Gas feed for boilers 3.2

Cavanagh building

Gas feed for boilers / café. 2.9

BSU Gas feed for boilers BSU research building 2.9

ORB Gas feed for boilers / café. 2.2

Bioscience Gas feed for boilers / café. 2.1

Others Other sites (34) account for the remaining 12.2 % of energy use.

12.2

Appendix II gives a summary of the natural gas SEU’s, detailing the 2016/17 performance, 2017/18 targets, operational controls etc.

Page 10: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 10 of 18

4 ENERGY BASELINE & ACTION PLAN

4.1 Electrical

The baseline for electrical usage is from October 2016 to September 2017. Based on this energy review the estimated reduction associated with

the SEU’s for 2017/18 will be 102,500 kWh

SEU 2017/18

Annual Target

(GW/h/year)

Predicted

annual savings

(kW/h/year)

Action plan 2017/18

WGB 4.177 +200,000 Assess suitability for sustainability campaign, assess suitability for LED replacement, building

management approach to be documented as template for Capital Projects. Extend the no of

meters on the resourcekraft metering package. Continue to closely manage the BSU area.

FSB 2.02 -70,000 The savings from the ESO completed in the summer of 2017 will carry forward to 2017/18,

reducing the expected annual consumption by 20,000 kWh. With the upcoming planned

collaboration with the school for the saver saves scheme we have set a target of saving a

further 50,000 kWh over the year. The following actions are planned for the 2017/18:

Communicate weekly to user on energy usage. Undertake trial of the saver saves scheme.

Connect up PV array to metering load. Undertake energy audit of Block A and C.

Page 11: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 11 of 18

SEU 2017/18

Annual Target

(GW/h/year)

Predicted

annual savings

(GW/h/year)

Action plan 2017/18

Kane 2.1 0 The following actions are planned for the 2017/18: Continue to monitor weekly energy

consumption. Audit the building services (24% of total energy consumption) to ensure correct

operation.

Boole 1.6 -90,000 The savings from the ESO completed in the summer of 2017 will carry forward to 2017/18,

reducing the expected annual consumption by 90,000 kWh The following actions are planned

for the 2017/18: Communicate weekly to College on energy usage. Investigate suitability for

chilled water system replacement. Lighting management protocols to reduce PGL lighting for

summer term. Review occupancy patterns verses opening times.

Bioscience 1.630 -12,000 The following actions are planned for the 2017/18: Sign up College to the saver saves scheme.

Investigate suitability for lighting replacement and / or upgrade and start roll out. Investigate

suitability for replacement and rationalisation of LPHW systems. Cost up metering plan for the

building and agree implementation plan.

BHSC 1.32 0 The following actions are planned for 2017/18: Assess suitability for sustainability campaign.

Assess suitability for LED replacement and commence. Extend the no of meters on the

resourcekraft metering package.

Page 12: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 12 of 18

SEU 2017/18

Annual Target

(GW/h/year)

Predicted

annual savings

(GW/h/year)

Action plan 2017/18

Pharmacy 0.97 -38,000 Installation of new air compressor. Upgrade lighting controls in the atrium. Fumehood sash

speed control project. Roll out of building awareness campaign. Upgrade the BMS platform.

ORB 0.74 -29,000 Continue to monitor weekly energy consumption. Investigate causes of nightload, which

achieve an annual reduction of 2%. Extend the metering plan in the building.

Student

Centre

0.4 -81,000 Continue to monitor weekly energy consumption. Investigate the investment required to

upgrade the existing Siemens and Trend BMS. Verify lighting savings. Cost proposal for

extending the metering plan in the building. Investigate suitability of divorcing the radio room

from the Hall AHU. Detailed audit on building services equipment to identify SEU’s within the

building and the night load consumers,

BSU 0.4 -22,000 Conduct detailed energy audit and building awareness campaign to achieve a 5% reduction in

annual energy consumption.

ERI 0.39 -20,500 Continue to monitor weekly energy consumption. Roll out building awareness campaign.

Extend the metering plan in the building. Review feasibility of dry cooling loop for cooling

circuit. Assess suitability of ESCO model for PV array/ battery storage. Conduct energy review

and achieve a 5% reduction in annual savings.

Page 13: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 13 of 18

SEU 2017/18

Annual Target

(GW/h/year)

Predicted

annual savings

(GW/h/year)

Action plan 2017/18

Aula

Maxima

0.33 0 Continue to monitor weekly energy consumption. Replace the failed BMS system.

Investigate extending the no of meters on the resourcekraft metering package.

Glucksman 0.35 +60,000 Continue to monitor weekly energy consumption. Verify lighting savings. Extend the metering

plan in the building.

Total 16.427 -102,500

Page 14: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 14 of 18

4.2 Natural Gas

The baseline for gas usage is from October 2016 to September 2017. Based on this energy review and action plan the total estimated reduction

associated with the SEUs for 2017/18 will be 16.43 GWh for the year.

SEU 2017/18

Target

(GW/h/year)

Predicted annual

savings

(GW/h/year)

Action plan 2017/18

CHP 0 -17.79 Shutdown of the CHP units

Campus

Boilers

5.36 +1.5 Development of plan for FSB steam supply Progress tendering of the ESCO for the district

heating project. Review operating sequence in the absence of CHP, i.e. which boiler will

lead.

BHSC 1.35 0 Assess ESO for installation of dedicated DHW boiler.

WGB 1.35 0 Assess ESO for installation of dedicated DHW boiler.

FSB 1 -0.055 Replace failed BMS controller. Rationalisation of LPHW systems

Pharmacy 0.98 -0.02 Roll out of fumehood sash speed control. Assess need for dedicated DHW boiler.

BSU 0.96 0 Continue to monitor

ORB 0.70 -0.02 Repair BMs controller

Bioscience 0.69 -0.07 10% saving from rationalisation of LPHW systems

Page 15: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 15 of 18

Total -16.455

Page 16: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 16 of 18

APPENDIX I

SUMMARY OF ELECTRICAL SEU’S, TARGETS, CONTROL & ACTION PLANS

Page 17: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 17 of 18

APPENDIX II

SUMMARY OF NATURAL GAS SEU’S, TARGETS, CONTROL & ACTION PLANS

Page 18: University College Cork Energy Review 2016/17greencampus.ucc.ie/.../uploads/2017/11/UCC-Energy-review-2016_17 … · UCC Energy Review 2016/17 Page 5 of 18 Table of Thermal SEU’s

UCC Energy Review 2016/17

Page 18 of 18

APPENDIX III

SUMMARY OF ENERGY SAVING OPPORTUNITIES COMPLETED 2016/17