    UNIPOWER

    Power Quality Analyzer UP-2210-R

    Silverline

    www.unipower.seUNIPOWER offers a wide range of products for power quality measurementsand demand analysis. Our product line covers a full range from traditional portable PQ analysers to fully integrated, automated Power

    Quality Management systems.

    All UNIPOWER products are developed and manufactured in Sweden.

    www.unipower.seUNIPOWER offers a wide range of products for power quality measurements

    and demand analysis. Our product line covers a full range from traditional portable

    PQ analysers to fully integrated, automated Power Quality Management systems.

    All UNIPOWER products are developed and manufactured in Sweden.

  • 7/27/2019 UP-2210-R[1].pdf

    2/18

    UNIPOWER

    Voltage Changes RVC and more. See

    UP-2210 product brochure for

    additional details.

    UP-2210-R

    Comes in a convenient 19" case that fits

    easily in the sub-station control cabinets.

    The hardware is based on the class A

    platform of the UP-2210 and measures

    voltage, current, frequency, power

    (active, reactive, apparent), energy

    (active, reactive, apparent), U-sum, I-

    sum, power factor, cos , harmonics,

    inter-harmonics, power harmonics,

    voltage unbalance, fl icker, signalling

    voltage, sags & swells (waveform and

    RMS), transients (down to 1 s), Rapid

    .

    Power Quality Analyzer - 19" Rack Mounted

    The UP-2210-R is a IEC 61000-4-30 Class A Power Quality

    Analyzer and Fault Recorder targeted on MV and HV

    applications.

    UP-2210-R - Technical Specification

    integrated, automated

    Rev.

    1.2

    AE.

    Specificationsaresubjecttochangewithoutnotice.

    Voltage inputs

    Voltage channels 4 differential inputs

    Channel input level 0 - 275 VAC RMSResolution 14 bit (84 dB)

    Basic sampling rate 256 samples/cycle

    Input impedance 2 Mohm

    Bandwidth 3.2 kHz analogue anti-aliasing filters

    Accuracy IEC 61000-4-30 class A (0.1%)

    For maximum accuracy, automatic synchronisation to the power frequency is

    performed by a phase-locked loop (PLL).

    Voltage transient inputs

    Voltage transient channels 4 differential inputs

    Channel input level +/- 1500 V peak level

    Resolution 14 bit (84 dB)

    Transient detect ion Fast t ransients (>1us / 1 MHz), sag/swells,

    interruptions

    Input impedance 2 Mohm

    Bandwidth 3 MHz

    Current inputs

    Current channels 4 differential isolated inputs

    Channel input level 0 - 6 A RMS (voltage inpu t op tional)

    Resolution 14 bit

    Basic sampling rate 256 samples/cycle

    Input impedance

  • 7/27/2019 UP-2210-R[1].pdf

    3/18

    UNIPOWER

    Advanced Power Quality Monitor

    UP-2210

    www.unipower.seUNIPOWER offers a wide range of products for power quality measurementsand demand analysis. Our product line covers a full range from traditional portablePQ analysers to fully integrated, automated Power Quality Management systems.All UNIPOWER products are developed and manufactured in Sweden.

  • 7/27/2019 UP-2210-R[1].pdf

    4/18

    UNIPOWER

    Measure unit UP-2210

    The standard unit is fitted with one RS-485, two RS-232

    communication ports and one USB port. Other options

    available include internal modem, external GSM

    modem, ISDN modem and Ethernet.

    The UP-2210 can also be fitted with digital inputs and

    digital outputs. These may be assigned for other

    monitoring purposes such as circuit breaker tripping,

    security alarms in substations etc, or providing local

    alarm or control outputs.

    The UP-2210 can also be equipped with a fault

    recorder module, which activates the unit's digital inputs

    for supervision of the status of circuit breakers, relays

    and other external equipment. Whenever there is a

    disturbance in the electrical grid the unit records voltage

    and current deviations, together with information aboutthe connected external equipment.

    UP-2210Advanced 3-phase

    Power Quality and

    Transient Monitor

    Norm-compliant, IEC 61000-4-30 Class A

    Power Quality Monitoring

    Transient Monitoring

    Demand Monitoring

    Fault Recorder

    GPS Synchronisation

    Fully Simultaneous Operation PQ Secure Information System

    The UP-2210 Power Quality Monitor is designed for

    permanent installation in any 50 / 60 Hz system. All

    voltage and current channels are differential, allowing

    the UP-2210 to be installed regardless of system

    configuration.

    The unit has 12 voltage and 4 current channels which

    may either be connected directly or using PTs and CTs

    as required. The heart of the UP-2210 is a 32-bit digital

    signal processor (DSP) enabling all 8 channels to be

    simultaneously monitored, thereby providing the most

    advanced features available anywhere.

    The unit is designed to be fitted inside a switchboard or

    other equipment and to communicate to a conveniently

    located computer. Several units may be networked to a

    single computer, thus providing centralised monitoringto locations both local or distributed on a global basis.

    Measure unit UP-2210R

  • 7/27/2019 UP-2210-R[1].pdf

    5/18

    UNIPOWER

    The UP-2210 is based on a powerful digital signal

    processor (DSP) which makes it possible to

    monitor all parameters simultaneously with high

    accuracy.

    The analogue sampling system is synchronised with the

    actual fundamental frequency, which ensures class A

    accuracy and precision as well as accurate event

    capturing.

    Each and every cycle is analysed in accordance with

    IEC 61000-4-30 Class A. The UP-2210 can easily be set

    up to measure in accordance with EN 50160 or any

    other national or international standard, with

    automatic reporting to management or other any other

    interested receiver.

    Analogue inputs

    The UP-2210 has 4 differential voltage and 4 differential

    voltage transient inputs. The bandwidth of each input is

    adapted to the appropriate application. When measuring

    harmonics a lower bandwidth is needed than when

    capturing transients.

    The UP-2210 also has 4 differential current input

    channels. In low voltage networks the fourth current

    channel can be used to measure the neutral current.

    Ground fault application

    The fourth voltage channel can be used for earth point

    monitoring in order to find ground faults in impedance

    grounded networks.

    Earth leakage

    The UP-2210 is automatically detecting any earth

    leakage by summing the phase (and neutral) currents. If

    there is a ground fault some current will flow in a

    different path and the leakage is detected.

    Digital Inputs and Fault RecordingThe UP-2210 can be equipped with digital inputs that

    can interface with a variety of external equipment such

    as kWh-meters, water meters, protective relays, circuit

    breakers etc. By connecting signals from the protective

    relays, the UP-2210 can work like a fault recorder,

    recording all signals upon a trig signal at a digital input.

    Digital Outputs

    The UP-2210 can also be equipped with digital outputs

    that can be programmed to alarm when certain pre-set

    conditions are met. This in turn can alert other, externalsystems. The digital outputs can be used to synchronise

    other meters (or UP-2210) to record at en event.

    Power Quality Monitor (UP-2210)

    The UP-2210 is a full-featured, norm-compliant (IEC

    61000-4-30 Class A) power quality monitor capable ofdetecting any disturbances encountered in a network.

    It interfaces with the PQ Secure software package.

    Measure unit (UP-2210)

    Graphical display

    An optional graphical display is also available. The unit

    is equipped with Unipowers unique and user-friendlyTurn&Clickinterface, and can be connected to a PC(RS-232) on-site via a front panel connector.

    Graphical Display Unit

  • 7/27/2019 UP-2210-R[1].pdf

    6/18

    UNIPOWER

    Measured parameters

    The UP-2210 has been developed as a full-featured

    power quality and transient monitor to simultaneouslymeasure all events on all channels. Individual trigger

    levels can be set to enable an infinitely variable range of

    user-defined trigger conditions, either from the remote

    workstation or via a laptop directly connected to the

    monitor. If a disturbance occurs that exceeds the

    defined trigger levels the monitor will record the

    disturbance.

    The internal memory has been chosen so that there are

    no moving parts. Problems with hard disks are a thing

    of the past. Instead, the analyser stores the events onits solid-state internal memory using a sophisticated data

    compression technique so that 4 MB represents

    typically 20 days storage. Remember that the key is the

    automatic download to the central database.

    Waveforms and power quality parameters can be viewed

    in real-time with PQ Online or as historical data with the

    PQ Secure software (SQL database).

    Basic parameters and demands

    All basic power quality parameters are measured

    continuously and can be viewed in real-time with

    PQ Online, or as historical data with PQ Secure.

    Voltage (phase-phase, phase-neutral)

    Current (phase-phase, phase-neutral)

    Active, Reactive and Apparent Power

    Active, Reactive and Apparent Energy

    Power Factor and cos phi

    Frequency

    Fault Recorder Module

    The UP-2210 can also be equipped with a fault recorder

    module, which activates the unit's digital inputs forsupervision of the status of circuit breakers, relays and

    other external equipment. Whenever there is a distur-

    bance in the electrical grid the unit records voltage and

    current deviations, together with information about the

    connected external equipment.

    Communication

    A central feature of UP-2210 is the flexibility and ease

    of communication between the workstation and the

    permanently installed monitor. Communication can be

    via a wire, phone connection, radio (and GSM), fibre/

    wire, etc. The monitor has built-in RS-232, RS-485,

    USB, Ethernet and also a modem.

    Fault Recorder window, displaying voltages, currents and

    digital input channels during a fault.

    GPS Module

    The UP-2210 can also be equipped with a GPS module,

    for time-synchronisation of the UP-2210 unit.

  • 7/27/2019 UP-2210-R[1].pdf

    7/18

    UNIPOWER

    Harmonics

    Harmonic distortion is caused by non-linear generators

    or loads and can cause severe problems. For example,capacitor banks can easily be damaged and neutral

    connectors can overheat. To identify harmonic-related

    problems it is necessary to measure continuously. The

    UP-2210 unit measures harmonics, both amplitude and

    phase, up to the 50th harmonic. Both THD-F, THD-R

    together with K-factor and harmonic power are

    calculated. All harmonics calculations are in accordance

    with IEC 61000-4-30 Class A (IEC 61000-4-7 Class I).

    The UP-2210 also has a module for studying

    interharmonics and signalling.

    Transients, Sags and Swells

    Disturbances in a power system are defined as voltage

    transients, sags or swells. Transients are fast

    disturbances originating from lightning, load switching

    etc. Voltage sags are short-duration low RMS-values

    generally caused by faults such as short circuits in the

    utility system. The reliability of a power system is

    critical to most businesses and is greatly affected by sagsand swells.

    The UP-2210 detects and categorises the type of

    disturbance, and helps to identify the source by

    determining the direction. It measures and calculates the

    RMS value for each half cycle and uses precision peak

    detectors to detect transients down to 1 microsecond

    duration. When a transient or a sag/swell occurs the

    UP-2210 records it and stores all necessary data in the

    built-in memory. It is then automatically transferred to

    the workstation with a seamless timebase for evaluation.Transients and sags & swell measurements are based on

    IEC 61000-4-30 Class A.

    PQ Online: real-time evaluation of harmonics.

    PQ Secure, Sag&Swell RMS evaluation window

    PQ Secure, Sag&Swell duration

    PQ Secure, Transient evaluation window

  • 7/27/2019 UP-2210-R[1].pdf

    8/18

    UNIPOWER

    MountingThe UP-2210 is a compact and rugged unit and is

    intended to be mounted permanently on site. The size is

    only 205 x 300 x 65 mm (width x height x depth) and

    ideal for mounting in any switchboard. An optional

    graphical display is also available for front panel

    monitoring on site and measures only 184 x 91 x 96

    mm. The display unit can be mounted remotely from

    the UP-2210 and is equipped with an extra front panel

    RS-232 communication port to which a portable

    computer easily can be connected to view real-time

    parameters on site.

    UP-2210 installed in a substation cabinet

    Flicker

    Fluctuating loads cause voltage variations that are often

    referred to as f licker. Lamps connected to such a voltageproduce a flickering light, very annoying to the human

    eye. The UP-2210 measures voltage flicker in

    accordance with IEC 61000-4-30 Class A (IEC 61000-4-

    15) and calculates flicker parameters such as IFL, PST

    and PLT.

    Unbalance

    Unbalance is a condition where the three phases differ

    in amplitude. This unbalance is frequently expressed as

    the ratio of the negative phase sequence divided by the

    positive phase sequence, as a percentage. Even small

    amounts of voltage unbalance decrease the efficiency of

    a three-phase motor. Monitoring the unbalance can help

    to improve efficiency and increase the longevity of a

    motor.

    The UP-2210 measures and stores the positive-, nega-

    tive- and zero-phase sequence and the unbalance for

    both voltage and current in accordance with IEC

    61000-4-30 Class A.

    PQ Secure, historical evaluation of PST,

    short-term flicker severity.

    Real-time and troubleshooting

    Without interrupting the logging of all parameters, the

    UP-2210 can show values in different real-time graphs.This makes a great tool that can be used when

    troubleshooting different problems on site as well as

    remote.

    Voltage, current, instantaneous flicker level and

    frequency in real-time.

  • 7/27/2019 UP-2210-R[1].pdf

    9/18

    UNIPOWER

    Example of wiring diagram, 3-phase, 3-wire delta

    with 3 PTs and 3 CTs

    Example of wiring diagram, 3-phase, 3-wire delta

    with 2 PTs and 2 CTs

    Connections

    The UP-2210 supports all power configurations as listed

    below.

    3-wire system

    4-wire system

    Phase-to-phase, wye and delta configurations

    All calculations are based on the correct electrical

    configuration which is set from a drop-down menu.

    Typical Substation Application

    Installation

    Fourth voltage input available for measurements in

    open delta configurations etc.

    Fourth current input available for neutral or ground

    current measurements

    8 (32) digital inputs available for indicationpurposes such as circuit breaker tripping etc.

    2 (4) digital outputs available for alarm purposes

    etc.

    L1 L2 L3

    LINE

    LOAD

    CT

    CT

    PTs

    UL1

    UL2

    UL3

    CT

    LOAD

    CT

    CT

    PTs

    UL3-L2

    UL1-L2

    L1 L2 L3

    LINE

    Power supply

    (85-264 V AC /

    110-375 V DC)

    4 current inputs

    (0-6 A TRMS)

    4 voltage inputs

    (0-275 V TRMS)

    Communication

    (RS-485 in this case)

    Connection box

    (connected to PTs

    and CTs)

    PT primary: 11 kV

    PT secondary: 110 V

    CT primary: 3000 A

    CT secondary: 5 A

    Digital In-/Outputs

    Power supply

    (85-264 V AC /

    110-375 V DC)

    4 current inputs

    (0-6 A TRMS)

    4 voltage inputs

    (0-275 V TRMS)

    Communication

    (RS-485 in this case)

    Connection box

    (connected to PTs

    and CTs)

    PT primary: 11 kV

    PT secondary: 110 V

    CT primary: 3000 A

    CT secondary: 5 A

    Digital In-/Outputs

  • 7/27/2019 UP-2210-R[1].pdf

    10/18

    UNIPOWER

    Voltage inputs

    Voltage channels 4 differential inputs

    Channel input level 0 - 275 V RMS

    Resolution 14 bit (84 dB)

    Basic sampling rate 256 samples/cycle

    Input impedance 2 Mohm

    Bandwidth 3.2 kHz analogue anti-aliasing filters

    Accuracy IEC 61000-4-30 class A (0.1%)

    For maximum accuracy, automatic synchronisation to the power frequency is performed

    by a phase-locked loop (PLL).

    Voltage transient inputs

    Voltage transient channels 8 differential inputs

    Channel input level +/- 1500 V peak level

    Resolution 14 bit (84 dB)

    Transient detect ion Fast transients (>1us / 1 MHz), sag/swells, interruptions

    Input impedance 2 Mohm

    Bandwidth 3 MHz

    Current inputs

    Current channels 4 di fferential inputs (ful ly isolated inputs optional)

    Channel input level 0 - 6 A RMS (vol tage input optiona l)

    Resolution 14 bitBasic sampling rate 256 samples/cycle

    Input impedance max 10 mohm

    Bandwidth 3.2 kHz analogue anti-aliasing filters

    Accuracy 0.1%

    Digital inputs

    8 opto-isolated digital inputs (0-250 VDC). 32 channels optional.

    Digital outputs

    2 solid state relays (0-110 VDC, 0-110 mA). 4 channels optional.

    Time synchronisation

    Optional GPS unit for time synchronisation.

    Selected calculated parameters

    Power Quanti ties Al l 3-phase configurations. Active power [kW] , React ive

    power [kVAr], Apparent power [kVA], Power Factor and

    cos (displacement factor), Active Energy [kWh], Reactive

    energy [kVArh], Apparent energy [kVAh]

    Energy accuracy class 0.2S (IEC 62053-22)

    Frequency 45 - 65 Hz according to IEC 61000-4-30 Class A.Harmonics 0 - 50th individual harmonics of voltage and current in

    accordance with standard IEC 61000-4-30 Class A. THD

    factors (THD-R, THD-F, TDD, THD-I etc), K-factor

    Power Harmonics (PFFT) Harmonic power with direction

    Interharmonics In accordance with IEC 61000-4-30 Class A.

    Flicker: IFL, Pst, Plt calculated in accordance with standard

    IEC 61000-4-30 Class A (IEC 61000-4-15)

    Voltage / Current Unbalance Positive-, negative- and zero phase sequence plus

    unbalance value (%) according to standard IEC 61000-4-

    30 Class A

    Signal ling Voltage In accordance with EN 50160 and IEC 61000-4-30

    Class A

    RVC Rapid voltage changes in accordance with IEC 61000-3-7

    and 61000-4-30 Class A

    Current l eakage and Isum and Usum parameters

    Voltage sum

    Memory capacity

    4 MB (8 MB is optional) built-in flash memory for measure data. A unit with standard

    memory will be able to measure for at least 20 days with normal configuration.

    Communication

    Built-in RS-232, RS-485 and USB. Optional Ethernet and internal modem. Support for

    external modems, radio devices, ISDN- and GSM/GPRS-modems.

    Standards

    Voltage Qua lity EN 50160, IEC 61000-2-2 , IEC 61000-2-12 and other

    norms

    Harmonics Measurements IEC 61000-4-30 Class A (IEC 61000-4-7)

    Flicker Measurements IEC 61000-4-30 Class A (IEC 61000-4-15)

    Power Quality IEC 61000-4-30 Class A (Testing and measurement

    techniques)

    Mechanical data

    Size W x H x D 205 x 300 x 65 mm

    Operat ional temperature -10 C to +55 C

    Humidity 10% - 98% non-condensing

    Weight 1.3 kg

    Safety IEC 61 010-1

    EMC IEC 61000-6-4 and IEC 61000-6-2 (EN 50 081-1,2;

    EN 50 082-1,2)

    Calibration and self-testThe calibration of UP-2210 is software-based and is therefore easy to make directly on

    site without having to dismount the units. To assure maximum reliability the UP-2210

    always performs an automatic self-test (AST) before measuring.

    Power supply

    Standard: 110/230 V AC or 100-375 V DC

    Optional: 18-36 V DC or 36-72 V DC

    Technical SpecificationUP-2210 main features:

    Sampling frequency

    High-speed sampling frequency (256 samples/cycle)gives a high accuracy of all measured parameters.

    Transient high speed capture

    High-speed transients down to 1 us are captured and

    the waveforms for all 8 channels are recorded and can

    easily be evaluated with pre- and post trig.

    Sag & Swell long time recording

    8-channel recording of sags/swells up to 10 seconds

    (every single cycle is recorded). Selectable pre- and post-

    trig.

    Realtime graphs

    Realtime values can be studied together with waveform,

    harmonics graph, vector diagram and unique realtime

    time graph of instantaneous flicker level and other

    parameters.

    Historical Trend graph

    Unique automatic historical trend graph that shows all

    important values 24 hours back in time in real-time

    mode. This can also be shown in the optional display

    unit that can be mounted in substations etc.

    PLL Sampling Synchronisation

    High accuracy of all measured parameters achieved by a

    synchronisation between the sampling of the input

    signals and the power frequency. The synchronisation is

    made possible by a built-in PLL (phase-locked loop).

    Flash memory

    Easy to upgrade with new software thanks to the

    built-in flash memory. No moving parts ensures total

    reliability.

    For more information, contact your local representative:

    Unipower ABBox 411SE-441 28 ALINGSS

    Sweden

    [email protected]

    Rev.

    5.0

    AE.

    Specificatio

    nsaresubjecttochangewithoutnotice.

    UNIPOWER

  • 7/27/2019 UP-2210-R[1].pdf

    11/18

    When combined with the UP-2210, PQ Secure

    provides the ultimate solution for comprehensive

    user-friendly continuous monitoring of and remote

    access to all power quality parameters.

    PQ Secure is the key tool used by utilities in several

    countries for the management of Power Quality in

    their networks, as this is critical to many of their

    customers.

    PQ Secure is equally powerful to the end user not

    only to monitor the power quality they receive but

    also to diagnose potential problems within their own

    installations.

    Based on the internationally renowned SQL database,

    PQ Secure is configured to provide a powerful yet

    intuitive man-machine interface. Being a Microsoft

    product it is not only a universal standard but

    immediately compatible with all standard Microsoft

    tools such as Office etc.This unique system can be set to automatically

    evaluate to standards such as EN 50160 or any

    national standard, and produce an automatic report

    to a designated computer anywhere world wide.

    Power Quality

    ManagementSystem for

    Utilities and

    Industries

    A central feature of PQ Secure is the flexibility and

    ease of communication between the host computer

    and the permanently installed monitors (UP-2210).

    Communication can be via a wire, phone connection,

    radio (and GSM), fibre/wire, etc. The monitor has

    built-in RS-232, RS-485, Ethernet and a modem.

    Thus, using either a laptop plugged into the UP-2210

    or via the remote computer, an immediate analysis

    can be made of any or all parameters from a histori-

    cal trend to an in-depth analysis of an event down to

    1 microsecond. This information is not polled but

    created simultaneously on all channels within the

    UP-2210 and accurately time-stamped.

    The Advanced Digital Signal Processing within the

    UP-2210 combined with the Adaptive Phase Locked

    Loop (PLL) enables an accuracy of measurement that

    is unrivalled.

    By using solid-state memory and state-of-the-artcompression techniques the UP-2210 contains no

    moving parts, yet has the performance of an

    equipment with a large hard disk.

    !!!!! Power Quality Monitoring

    !!!!! Substation Monitoring and

    Control!!!!! Demand Analysis

    !!!!! Global Event Viewer

    !!!!! Automatic Analysis and

    Reporting

  • 7/27/2019 UP-2210-R[1].pdf

    12/18

    The Growing Importance of Power Quality

    Industry and commerce is now dependent on modern

    computer systems. These systems are seriously affectedby power quality problems ranging from extended powerinterruptions to very short-term events of a fewmicroseconds.Power quality problems can be created at any point inthe network and indeed the most consistent polluter isthe very computer system at the heart of the customers

    business activity.In some countries Power Quality laws have been passedto guarantee a defined level of Power Quality tocustomers. If they are not met, customers get theirmoney back. In other countries there is a trend towardsthe customer being able to choose level of power qualitythey wish to purchase. Common to both is the need to

    be able to demonstrate and provide accurate evidencethat the standard is either met or not. This requiresaccurate reliable cost-effective permanent monitoring.

    Power Quality Management System

    To meet the requirements set by the global trends withinthe energy sector, Unipower has developed an advanced

    power quality management system called PQ Secure. Bycontinuously measuring all power quality parameters incritical locations within the network, the system provides acentral window on the network and can even identify thedirection of an event. By identifying the direction the locationand hence the cause can be identified.This technique is presently being used by electricaltransmission and distribution authorities, but is also now beingadopted by other industries, particularly those with datacentres. These often contain multiple feeds, several UPSsystems and emergency generators and it is critical toidentify the potential for harm before damage is done toexpensive computer systems.

    By deploying several UP-2210s at key locations, eachcommunicating with the host computer, simultaneous eventcomparisons can be made tracking the location and effectof a given event on the system. The host computerevaluates, displays and generates reports. The figure belowshows the outline for such an installation. Most customers

    Building

    PQ Secure

    Management

    Centre

    Electrical Network

    Trans-

    former

    station

    Substation

    PQ Secure provides new evaluation possibilities.

    Overview of the PQ Secure system.

    Automatic reports can be set up together with event logs.Alarm outputs can be configured to connect to a BMS if a

    potentially damaging event has occurred.National or international standards can also beprogrammed, to confirm that the power system has metthe specification. The key issue here is the ability to tailorthe reporting to avoid swamping the user whilst retainingthe built-in powerful features needed for close analysis.

    PQ Secure software

    The PQ Secure system provides two software packages:PQ Secure and PQ Online. PQ Online manages allcommunication with the measuring units. It is also used forconfiguration of the UP-2210 units and real-time evalua-tion of values and waveforms etc. The software will callall UP-2210 units in an installation, and download data intothe SQL database according to a preset time schedule.All measured data is stored within the SQL database andPQ Secure is the key for accessing it through advancedevaluation tools which allow the user to select betweenglobal and local event lists, historical evaluation windows,automatic report functions and much more.

    do not want to routinely analyse each andevery mains cycle on each channel. Theydo require however to be able to get to thedata if circumstances dictate, but mostlywant to be able to filter the standard reports

    issued by the system. Unipower hasextensively researched customersrequirements and has developed aflexible and yet easy-to-use system.

    At the office:

    Analysis and presentation

    RS-232

    Communication

    Telephone line, radio,optical fiber, etc.

    RS-232 RS-485Converter

    RS-232ConverterConverter Ethernet etc.

    UP-2210

    UP-2210UP-2210

    UP-2210

    UP-2210 UP-2210

    On location:

    RS-485/ RS-232

    ModemModem

  • 7/27/2019 UP-2210-R[1].pdf

    13/18

    PQ Online Software

    Communication and configuration software

    The PQ Secure system is easy to use as the software is

    configured with standard Windows drop-down menus.PQ Online is the software package controllingcommunication, configuration and real-time analysis. PQOnline manages the necessary link between the hostcomputer and the various UP-2210 monitors. PQ Onlinealso enables historical statistical data and waveformsrecorded since the last download to be retrieved. Thesoftware is option-based and supports different hardwareinterfaces as well as different software protocols. Theseinclude RS-232, RS-485, modem, Ethernet etc.Thus the host computer can become an oscilloscope, trenddisplay, transient analyser, power analyser, harmonic analyserand flicker analyser all in one!

    PQ Online, Configuration window

    The picture above shows how easy it is to configure a PQmonitor. First you select the type of installation (for exam-

    ple 4-Wire WYE). The software then presents a graphicalview and helps you step by step through the configuration.

    All unit configurations are easily changed from the man-agement centre and every PQ monitor can have its ownindividual settings. It is also possible to use different com-munication equipment for the PQ monitors in the system.

    PQ Online - Real-time Values

    Rather than wait for a standard reporting window to have

    occurred and to then review data historically, PQ Onlinedials up and displays all measured parameters in real-time.PQ Online receives packets of data enabling the waveformof the voltage and current together with all standard powerquality parameters to be displayed.By using for example a GSM connection the engineer canthus remotely view an installation and be able to identify a

    problem in advance of attending the site. This enables theengineer to bring the correct spares, and maximises thechance of fixing a problem in one hit.

    PQ Online - Trend monitorPQ monitors can be remotely accessed via PQ Online.They store values for a period of time allowing the user tosee a historical trend graph when PQ Online is connectedto a UP-2210 monitor. This offers a quick and easy over-view of the most recent period and reveals any irregularvalues. The trends can also be viewed on site using theoptional display unit.

    PQ Online - Oscilloscope and Phasors

    PQ Online has a built-in oscilloscope feature that can displayall 8 measured channels at the same time. A phasor diagramcan also be displayed to verify connections and phase angles.

    PQ Online - Harmonics

    The UP-2210 monitor measures harmonics (and inter-harmonics) up to the 50th continuously. PQ Online enablesthe voltage and current harmonics on all 8 channels to beviewed at the same time, either in bar graph or in tabularform.

    PQ Online - Power Harmonics

    The UP-2210 monitors even measure and calculate thepower harmonics, and with PQ Online you will have infor-mation about the direction of the individual harmonics, whichis very useful when looking for the harmonics source.

    Oscilloscope,

    trend graph and

    values in real-

    time from a

    remote unit.

    Phasor diagram

    and Harmonics

    graph are other

    features

    available in

    real-time.

  • 7/27/2019 UP-2210-R[1].pdf

    14/18

    PQ Secure - Evaluation software

    All data is stored in an open SQL database and PQ

    Secure lets the user make advanced evaluations andanalyses. PQ Secure is built on three main modules. First,is the Global Event Viewer, which shows all events thatare registered in all the monitors. Second, there isPowerProfile, a graph and analysis tool that lets the userview all the different power quality parameters. Third, isthe automatic report generator that assembles data andtests it against international and other standards like theEN 50160. In the software, the meters are represented

    by symbols that can be arranged on a map or schematicdrawing for a clear overview.

    Global & Local Event Viewer

    The PQ Secure software has built-in global and local eventviewer windows that are developed to fit into an operationcentre. The event viewer windows show all events thathappen in the system divided into system events and powerquality events. The event viewers help the user to get early

    warnings and hence a better picture of the situation in thenetwork.

    Basic and advanced historical evaluations

    The function for historical graphical evaluations is calledPowerProfile and is easy to run. Choose the measuringunit that shall be evaluated by clicking on the measureunit icon and then click on the PowerProfile icon. Thenchoose a time span and view the historical data.

    There are several pre-set evaluation windows that eachhandle one power quality parameter. These windows aredesigned to help the user evaluate the most important sub-

    parameters for each power quality phenomena.All data from the evaluation windows can easily be printedor exported to Microsoft compatible products.

    Custom evaluation window

    If the user wishes to make a detailed evaluation there isa special window called Custom that can be used. Thisenables all pre-selected power quality parameters to bedisplayed in the same window.

    PQ Secure, Main window PQ Secure, Historical evaluation window

    PQ Secure, Custom evaluation windowPQ Secure, Global Event Viewer window

    The global event viewer shows all events from allmeasuring units in one window and the local event viewer

    sorts out data from one unit at a time, which means thatthe user can also evaluate the measured power qualityfor one specific meter.

  • 7/27/2019 UP-2210-R[1].pdf

    15/18

    Multiple sites in the same window

    The PQ Secure program supports several UP-2210 units

    on different sites in the same diagram window. This givesa transmission authority the unique ability to comparemeasured power quality parameters at the different voltagelevels in the same network. The evaluation diagram provideskey information on one diagram and shows the spread fromdifferent voltage levels through the electrical grid.The data centre manager can see the effectiveness of UPSsystems and filters using the same technique.

    Sag/swell evaluation

    Sags and swells can be viewed as events in a time graph,in a duration graph or as a RMS graph. The former showsevents plotted on a time axis with the severity (depth) onthe y-axis. The different phases are colour and symbolcoded. The duration graph shows events plotted on aduration time axis with the severity (depth), on the y-axis. Here the severity distribution of events is displayedand can be compared to standards like the CBEMA orANSI.

    By clicking on the symbol for the actual event aninformation window will appear with data for the

    sag/swell along with the direction information. Does thesag/swell come from upstream or downstream? Thereis also a View button. Hit this button and the RMS trendgraph will appear as shown in the picture below.

    Sag/swell RMS trend graph

    The trend graph shows a 1.3 - 2.5 second RMS-trendgraph for every sag/swell that has been recorded. Thediagram is based on RMS values that are calculated everyhalf-period. If one or more voltage channels captures asag/swell event, all channels are recorded. This givesthe ability to view both voltages and currents when asag/swell occurs.

    Transient evaluation

    Every time a transient is captured on one or morechannels all channels are recorded. The evaluation canthen be done with both voltage and current waveformsto see where the disturbance was created. Waveformsare typically recorded with one cycle pre-trig and 4 cycles

    post-trig.

    PQ Secure, several units evaluated in one diagram

    PQ Secure, Sag&Swell time diagram

    PQ Secure, Sag&Swell RMS evaluation window

    PQ Secure, Transient evaluation window

  • 7/27/2019 UP-2210-R[1].pdf

    16/18

    PQ Secure Network

    With the SQL database software installed it isstraightforward to make use of the local area networkto distribute PQ Secure in an organisation. The PQSecure client software can be installed on additionalclient computers and configured to collect informationfrom the central database server via the existing

    computer network. This means that several engineerscan use PQ Secure in different offices at the same time.

    For more information, contact your local representative:

    UNIPOWER ABBOX 411SE-441 28 ALINGSS

    SWEDEN

    http://[email protected]

    Rev2.1

    AE

    Unipower is represented in many countr ies worldwide.On our web site you will f ind all our representatives.

    http://www.unipower.se

    Unipower - setting new

    standards for Power

    Quality Management

    Systems

    Built-in automatic Report function

    The PQ Secure has an automatic report function. With

    this function, the user can easily format a standard reportusing data from either one or several of the UP-2210units. The reporting parameters can be programmed toconform to international standards such as EN 50160 orother national standards. The report detailing thedeviations can be viewed directly on screen or be printed.All reports are immediately compatible with Word andother Microsoft products for inclusion in other documents.The report can even be e-mailed to someone directly!

    PQ Secure, Automatic report generator

    Measuring unit UP-2210

    mounted in a substation

    Display unit

    Central computer

    PQ Secure

    SQL database

    Local Area Network

    TCP/IP

    PQ Secure client PQ Secure client

    Measure units (UP-2210)

    Hardware Unit

    PQ Secure communicates with the UP-2210 monitors.

    The UP-2210 monitor is designed for permanentmounting and measures all power quality parameterssimultaneously in an electrical network. Parametersinclude voltage, current, harmonics, flicker, sags, swells,transients etc. More information about the UP-2210monitor can be found in the separate hardware brochure.

  • 7/27/2019 UP-2210-R[1].pdf

    17/18

    UNIPOWER

    Power Quality Analyzer UP-2210-R

    Silverline

    www.unipower.seUNIPOWER offers a wide range of products for power quality measurementsand demand analysis. Our product line covers a full range from traditional portable PQ analysers to fully integrated, automated Power

    Quality Management systems.

    All UNIPOWER products are developed and manufactured in Sweden.

    www.unipower.seUNIPOWER offers a wide range of products for power quality measurements

    and demand analysis. Our product line covers a full range from traditional portable

    PQ analysers to fully integrated, automated Power Quality Management systems.

    All UNIPOWER products are developed and manufactured in Sweden.

  • 7/27/2019 UP-2210-R[1].pdf

    18/18

    UNIPOWER

    Voltage Changes RVC and more. See

    UP-2210 product brochure for

    additional details.

    UP-2210-R

    Comes in a convenient 19" case that fits

    easily in the sub-station control cabinets.

    The hardware is based on the class A

    platform of the UP-2210 and measures

    voltage, current, frequency, power

    (active, reactive, apparent), energy

    (active, reactive, apparent), U-sum, I-

    sum, power factor, cos , harmonics,

    inter-harmonics, power harmonics,

    voltage unbalance, fl icker, signalling

    voltage, sags & swells (waveform and

    RMS), transients (down to 1 s), Rapid

    .

    Power Quality Analyzer - 19" Rack Mounted

    The UP-2210-R is a IEC 61000-4-30 Class A Power Quality

    Analyzer and Fault Recorder targeted on MV and HV

    applications.

    UP-2210-R - Technical Specification

    integrated, automated

    Rev.

    1.2

    AE.

    Specificationsaresubjecttochangewithoutnotice.

    Voltage inputs

    Voltage channels 4 differential inputs

    Channel input level 0 - 275 VAC RMSResolution 14 bit (84 dB)

    Basic sampling rate 256 samples/cycle

    Input impedance 2 Mohm

    Bandwidth 3.2 kHz analogue anti-aliasing filters

    Accuracy IEC 61000-4-30 class A (0.1%)

    For maximum accuracy, automatic synchronisation to the power frequency is

    performed by a phase-locked loop (PLL).

    Voltage transient inputs

    Voltage transient channels 4 differential inputs

    Channel input level +/- 1500 V peak level

    Resolution 14 bit (84 dB)

    Transient detect ion Fast t ransients (>1us / 1 MHz), sag/swells,

    interruptions

    Input impedance 2 Mohm

    Bandwidth 3 MHz

    Current inputs

    Current channels 4 differential isolated inputs

    Channel input level 0 - 6 A RMS (voltage inpu t op tional)

    Resolution 14 bit

    Basic sampling rate 256 samples/cycle

    Input impedance