10
UPS THE IDEAL SOLUTION FOR BACK UP POWER www.renergypower.com

ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

UPSTHE IDEAL SOLUTION FOR BACK UP POWER

www.renergypower.com

Page 2: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

VRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply (UPS).

Renergy Power offers several types of UPS batteries :

www.renergypower.com

RPAS

Special grid and plate manufacture technology, automatic manufacture line raise the life and uniformity of battery -3D structure: Optimized design of active material adhesion, fine mesh grid provides more surface area for high power output -Special paste formula, advanced welding technology to ensure excellent high power discharge capacity(W/15Mr, up 20%).

Features:

Application:

Long design life Oxygen recombination efficiency: ≥98%

Wide temperature range: -20°C~50°C

ABS material: UL94-V0

Valve Regulated Lead Acid (VRLA)

Battery, Maintenance Free

Unique vent valve design: control water losing,

prevent air and spark entering

PbCaSn alloy for plate grids: less gassing, less

self-discharging

Bank and Finance Market

Control Facility ata Centre (IDC)

Industrial Process Control Facility

Emergency Power System

0

4

8

12

16

20

20 30 40 50

Battery temperature (ºC)

Floa

t Li

fe (y

ears

)

Temperature Effects on Long Term Float Life

0

20

40

60

80

100

120

-10-20 0 10 20

2.0 C1.0 C

30 40 50

Battery temperature (ºC)

Cap

acit

y (%

)

Temperature Effects in Relation to Battery Capacity

0.22 C0.10 C

Page 3: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

www.renergypower.com

Float Charging Characteristics

2.0

2.1

2.2

2.3

2.4

0.02C

0C

0.04C

0.06C

0.06C

0.10C

40 8 12 16 20 24 28 32 36

Charging Time (hours)

0.1CA-2.25V/cell

ChargingVoltage

ChargingCurrent

(V/cell)(A) Temperature 250C

40

20

60

80

100

120

ChargeVolume

(%)

Charging Current

Charged Volume

Charge Voltage

After 50% Discharge 50%DOD

After 100% Discharge 100%DOD

(Constant 2.25V/cell)

1.33

1.17

1.50

1.67

1.83

2.00

2.17

1 2 4 6810 20 40 60 2 4 6 810 20 4060 2 4 6 810 20

Dischrage Time

min H

Term

inal

Vol

tage

(V)

Discharge Characteristics

S

8.0

7.0

9.0

10.0

11.0

12.0

13.0

12VBattery

(V)

2VBattery

(V)Temperature 250C

10C

3C

2.1C

1.2C

0.7C 0.4C0.22C 0.10C 0.05C

Model10Hr20HrW15

1.8 V/cell1.8 V/cell1.67 V/cell

Width Height TH Weight

T*V

Length

mm in. mm in. mm in. mm in. kg lbs

24 5.7 5.3 90 3.54 70 2.76 101 3.98 107 4.21 1.88 4.15 T1

26 6.5 6.5 151 5.94 65 2.56 93.5 3.68 99.5 3.92 2.08 4.59 T1

35 8 7.8 151 5.94 65 2.56 93.5 3.68 99.5 3.92 2.5 5.51 T2

55 14 13 151 5.94 98 3.86 95 3.74 101 3.98 4 8.82 T2

85 20 19 181.5 7.15 77 3.03 167.5 6.59 167.5 6.59 6 13.23 T12

125 40 38 197 7.76 165 6.5 170 6.69 170 6.69 11.6 25.58 T6

160 48 45 197 7.76 165 6.5 170 6.69 170 6.69 14.2 31.31 T6

185 58 55 229 9.02 138 5.43 205 8.07 211 8.31 16.2 35.72 T6

215 69 65 348 13.7 167 6.57 178 7.01 178 7.01 19.2 42.34 T6

255 75 70 348 13.7 167 6.57 178 7.01 178 7.01 21.6 47.63 T6

300 80 75 256.4 10.09 173 6.81 213 8.39 216 8.5 23.4 51.6 T11

350 90 85 293.2 11.54 173 6.81 213 8.39 216 8.5 26.8 59.09 T11

360 102 100 330 12.99 173 6.81 213 8.39 216 8.5 29.4 64.83 T11

400 103 100 330 12.99 173 6.81 213 8.39 216 8.5 30.2 66.59 T11

430 106 100 330 12.99 173 6.81 213 8.39 216 8.5 30.8 67.91 T11

460 127 120 408 16.06 177 6.97 225 8.86 225 8.86 37.3 82.25 T11

510 159 150 483 19.02 170 6.69 238.5 9.39 238.5 9.39 43.2 95.26 T11

600 191 180 532 20.94 207 8.15 214 8.43 220 8.66 53.6 118.19 T11

690 212 200 522 20.55 240 9.45 218 8.58 224 8.82 62.2 137.15 T11

765 240 225 522 20.55 240 9.45 218 8.58 224 8.82 64.8 142.85 T11

820 265 250 522 20.55 268 10.55 220 8.66 226 8.9 73.3 161.6 T11

593 212 200 170 6.69 110 4.33 328 12.91 343 13.5 13.1 28.89 T18

857 318 300 170 6.69 150 5.91 330 12.99 345 13.58 18.1 39.91 T18

1186 424 400 210 8.27 175 6.89 330 12.99 345 13.58 26.4 58.21 T18

1450 530 500 240 9.45 175 6.89 328 12.91 343 13.5 31.1 68.58 T18

1714 636 600 300 11.81 175 6.89 330 12.99 345 13.58 37.2 82.03 T18

2372 848 800 410 16.14 175 6.89 330 12.99 345 13.58 52.9 116.64 T18

2900 1060 1000 475 18.7 175 6.89 328 12.91 343 13.5 62 136.71 T18

RPAS 1

RPAS 2

RPAS 3 RPAS 4

RPAS 5

RPAS 6

RPAS 7

RPAS 8

RPAS 9

RPAS 10

RPAS 11

RPAS 12

RPAS 13

RPAS 14

RPAS 15

RPAS 16

RPAS 17

RPAS 18

RPAS 19

RPAS 20

RPAS 21

RPAS 22

RPAS 23

RPAS 24

RPAS 25

RPAS 26

RPAS 27

RPAS 28

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

2

2

2

2

2

2

2

Page 4: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

RPBS

www.renergypower.com

RPBS Series batteries incorporate advanced VRLA&TTP technology designed for ultra high rate performance in UPS & power supply applications with 12 years design life at 25 °C ambient temperature. By using strong grid and specific paste plate to insure extra durable stable performance under high rate discharge.

Features:

Application:

Hospital& Testing Laboratories

Banks & Financial CentreTelecommunicationData Centre (High Rate UPS)

High Power Backup Supply

Emergency Power SupplyEmergency LightingPower Generation Plants

Absorbent Glass Mat (AGM) Separators

technology for high efficiency gas absorption

of up to 98%

Maintenance Free (no topping up)

No restrictions for rail, road, sea & air transport

-Complies with IATA/ICAO Special Provisions A67

Special designed grids for optimized high power

density

Valve Regulated Lead Acid (VRLA)

Battery

Oversized partition intercell welds, providing

low resistance connections & minimal

power loss

Performance excels at high rates of discharge &

recharge

High integrity post seal for long life

Vent Valve - allows the release of excess gases &

prevents case rupture

Advanced lead tin calcium alloy, reduces grid corrosion &

promotes long battery life

Page 5: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

www.renergypower.com

0

2

4

6

8

10

12

20 30 40 50

Battery temperature (ºC)

Floa

t Li

fe (y

ears

)

Temperature Effects on Long Term Float Life

0

20

40

60

80

100

120

-10-20 0 10 20

2.0 C1.0 C

30 40 50

Battery temperature (ºC)

Cap

acit

y (%

)

Temperature Effects in Relation to Battery Capacity

0.24 C0.10 C

Float Charging Characteristics

2.0

2.1

2.2

2.3

2.4

0.02C

0C

0.04C

0.06C

0.06C

0.10C

40 8 12 16 20 24 28 32 36

Charging Time (hours)

0.1CA-2.25V/cell

ChargingVoltage

ChargingCurrent

(V/cell)(A) Temperature 250C

40

20

60

80

100

120

ChargeVolume

(%)

Charging Current

Charged Volume

Charge Voltage

After 50% Discharge 50%DOD

After 100% Discharge 100%DOD

(Constant 2.25V/cell)

1 2 4 6810 20 40 60 2 4 6 810 20 4060 2 4 6 810 20

Dischrage Time

min H

Term

inal

Vol

tage

(V)

Discharge Characteristics

S

8.0

7.0

9.0

10.0

11.0

12.0

13.0

12VBattery

(V)Temperature 250C

10C

3C

2.1C

1.2C

0.7C 0.4C0.22C 0.10C 0.05C

Model20HrW15

1.80 V/cell1.67 V/cell

Width Height TH Weight

TerminalRated

Voltage

V

Length

mm in. mm in. mm in. in. kg lbs

12

12

12

12

12

12

12

12

12

12

RPBS 1 92.8 27 164 6.46 125 4.92 172 6.77 6.89 7.9 17.42 T12

RPBS 2 150 35 195 7.68 130 5.12 164 6.46 6.57 10.2 22.49 T6

RPBS 3 225.1 55 229 9.02 138 5.43 200 7.87 7.99 17.3 38.15 T6

RPBS 4 324.6 82 260 10.24 168 6.61 208 8.19 8.31 24 52.92 T6

RPBS 5 370.3 95 306 12.05 168 6.61 208 8.19 8.31 28 61.74 T6

RPBS 6 405.7 100 325.5 12.81 170 6.69 213 8.39 8.5 31.4 69.24 T8

RPBS 7 490.9 142 335 13.19 172 6.77 275 10.83 10.94 42 92.61 T8

RPBS 8 539 155 335 13.19 172 6.77 275 10.83 10.94 42.4 93.49 T8

RPBS 9 740 220 522 20.55 240 9.45 218 8.58 8.82 63.5 140.02 T11

RPBS 10 810 250 522 20.55 268 10.55 220 8.66 8.9 72.5 159.86 T11

Page 6: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

RPCS

www.renergypower.com

Features:

Application:

2

4

6

8

10

12

14

20 25 30 35 40 45 50

Battery temperature (ºC)

Floa

t Li

fe (y

ears

)

Temperature Effects on Long Term Float Life

0

20

40

60

80

100

120

-10-20 0 10 20 30 40 50 60

Battery temperature (ºC)

Cap

acit

y (%

)

Temperature Effects in Relation to Battery Capacity

0.25CA

0.17CA

0.1CA

Using oxygen recombination

technology: maintenance-free

ABS material: increase the strength of battery

container.

High quality AGM separator: extend cycle life and prevent micro

short circuit

PbCaSn alloy for plate grids: less gassing, less

self-discharging

Silver-coated copper terminals (T1, T2 terminal), brass insert terminals and lead terminals

improve the electric conductivity

High purity raw material: ensure low self discharge rate

Uninterruptable Power Supply (UPS)

Electric Power System (EPS)

Emergency light Emergency backup power supply

All purpose

Tele-communication central station

Power system communication

Network communication including: data

transmission, television signal transmission, etc.

Uninterruptable Power System (UPS- for

Telecom)

Auto control system

Page 7: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

www.renergypower.com

Float Charging Characteristics

11.0

12.0

13.0

14.0

15.0

0.05

0

0.10

0.15

0.20

0.25

40 8 12 16 20 24 28 32 36

Charging Time (hours)

0.1CA-2.25V/cell

ChargingVoltage

ChargingCurrent

(V)(XCA) Temperature 250C

0102030405060708090

100110120

ChargeVolume

(%)

Charged Volume

Charging Current

Charge Voltage

After 50% Discharge 50%DOD

After 100% Discharge 100%DOD

(Constant 2.25V/cell)

2C

1C

1 2 4 6 810 20 40 260 4 6 8 2010

Dischrage Time

Min H

Term

inal

Vol

tage

(V)

Discharge Characteristics

8.0

7.0

9.0

10.0

11.0

12.0

13.0

12VBattery

(V)Temperature 250C

0.4C0.205C

0.1C0.05C

0.6C

Model10Hr20Hr

1.80 V/cell1.80 V/cell

Width Height TH Weight

TerminalRated

Voltage

V

Length

mm in. mm in. mm in. in. kg lbs

RPCS 1 4 3.5 3.3 90 3.5 34 1.3 59 2.3 2.6 0.5 1 T1

RPCS 2 4 4.5 4.2 53 2.1 48 1.9 94 3.7 3.9 0.6 1.3 T1

RPCS 3 4 5 4.7 91 3.6 50 2 74 2.9 2.9 0.7 1.5 T1

RPCS 4 4 8 7.4 91 3.6 50 2 101 4 4 1 2.1 T2

RPCS 5 4 10 9.3 102 4 50 2 94 3.7 3.9 1.1 2.5 T2

RPCS 6 6 1 0.9 51 2 42 1.7 51 2 2.2 0.3 0.6 T1

RPCS 7 6 1.2 1.1 97 3.8 24 0.9 52 2 2.3 0.3 0.6 T1

RPCS 8 6 2 1.9 43 1.7 37 1.5 76 3 3 0.3 0.7 /

RPCS 9 6 2.8 2.6 66 2.6 33 1.3 97 3.8 4.1 0.6 1.3 T1

RPCS 10 6 3.2 3 134 5.3 34 1.3 60 2.4 2.6 0.7 1.5 T1

RPCS 11 6 4 3.7 70 2.8 47 1.9 100 3.9 4.2 0.7 1.6 T1

RPCS 32 12 0.8 0.75 96 3.8 25 1 62 2.4 2.4 0.4 0.8 /

RPCS 33 12 1.2 1.1 97 3.8 43 1.7 52 2 2.3 0.6 1.3 T1

RPCS 34 12 1.9 1.8 178 7 35 1.4 60 2.4 2.6 0.9 1.9 T1

RPCS 35 12 2.2 2.05 70 2.8 47.5 1.9 98 3.9 4.1 0.8 1.8 T1

RPCS 36 12 2.3 2.1 178 7 35 1.4 60 2.4 2.6 1 2.1 T1

RPCS 37 12 2.8 2.6 133 5.2 34 1.3 98 3.9 4.1 1.2 2.6 T1

RPCS 38 12 2.9 2.7 79 3.1 56 2.2 99 3.9 4.1 1.1 2.4 T1

RPCS 39 12 3.2 3 134 5.3 67 2.6 61 2.4 2.6 1.4 3 T1

RPCS 69 6 62.4 60 185 7.3 112 4.4 205 8.1 8.1 9.1 20.1 T2

RPCS 70 6 124.8 120 280 11 128 5 203 8 8 16.8 37 T6

RPCS 71 6 156 150 260 10.2 180 7.1 247 9.7 10 21 46.3 T7

RPCS 72 6 210 190 306 12 168 6.6 222 8.7 9 28 61.7 T8

RPCS 73 12 40 38 197 7.8 165 6.5 170 6.7 6.7 12.2 26.9 T6

RPCS 74 12 40 38.5 255 10 97 3.8 203 8 8 12.5 27.6 T7

RPCS 75 12 46.8 45 197 7.8 165 6.5 170 6.7 6.7 14.2 31.3 T6

RPCS 76 12 52 50 257 10.1 132 5.2 200 7.9 7.9 15.7 34.6 T6

RPCS 77 12 57.2 55 229 9 138 5.4 205 8.1 8.3 16.2 35.7 T6

RPCS 78 12 62.4 60 260 10.2 168 6.6 208 8.2 8.4 18.4 40.6 T6

RPCS 79 12 65 60 348 13.7 167 6.6 178 7 7 19.2 42.3 T6

Page 8: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

RPDS

www.renergypower.com

Thin plate technology, special grid design, unique paste formula and plate curing process optimize high rate performance.

Features:

Application:

0

2

3

5

81012

20 30 40 50

Battery temperature (ºC)

Floa

t Li

fe (y

ears

)

Temperature Effects on Long Term Float Life

Charging voltage :2.25V/cell

0

20

40

60

80

100

120

-10-20 0 10 20

2.0 C1.0 C

30 40 50

Battery temperature (ºC)

Cap

acit

y (%

)

Temperature Effects in Relation to Battery Capacity

0.28 C0.125 C

Silver-coated copper terminals (T1,

T2 terminal), brass insert terminals and

lead terminals improvethe electric

conductivity

ABS material: increase the strength of battery

container (Flame-retardant ABS is

optional)

High quality AGM separators with less electrical resistance improve high current

discharging properties

Thin plate technology, special grid design, unique

paste formula and plate curing process optimize high rate performance

UPS (High rate) Starting systemEmergency power supplyHigh power backup supply

Power tools Electric startingEmergency lighting

Page 9: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

www.renergypower.com

Float Charging Characteristics

2.0

2.1

2.2

2.3

2.4

0.02C

0C

0.04C

0.06C

0.06C

0.10C

40 8 12 16 20 24 28 32 36

Charging Time (hours)

0.1CA-2.25V/cell

ChargingVoltage

ChargingCurrent

(V/cell)(A) Temperature 250C

40

20

60

80

100

120

ChargeVolume

(%)

Charging Current

Charged Volume

Charge Voltage

After 50% Discharge 50%DOD

After 100% Discharge 100%DOD

(Constant 2.25V/cell)

8.0

9.0

10.0

11.0

12.0

13.0

1 2 4 6810 20 40 60 2 4 6 810 20 4060 2 4 6 810 20

Dischrage Time

min H

Term

inal

Vol

tage

(V)

Discharge Characteristics

S

4.0

4.5

5.0

5.5

6.0

6.5

6VBattery

(V)

12VBattery

(V)Temperature 250C

10C 7C 5C

3.5C

2C

1.0C

0.7C 0.4C0.2C 0.093C 0.05C

Model10Hr20Hr

1.80 V/cell1.80 V/cell

Width Height TH Weight

TerminalRated

Voltage

V

Length

mm in. mm in. mm in. in. kg lbs

RPDS 1 12 97 3.8 48.5 1.91 52.5 2.1 2.3 0.59 1.3 T1

RPDS 2 12 8.2 2.1 178 7 35 1.38 60 2.4 2.6 0.97 2.1 T1

RPDS 3 12 12.5 3.1 134 5.3 67 2.64 60.5 2.4 2.6 1.35 3 T1

RPDS 4 12 20.7 4.8 90 3.5 70 2.76 101 4 4.2 1.83 4 T1

RPDS 5 12 25.6 6 151 5.9 65 2.56 93.5 3.7 3.9 2.26 5 T2

RPDS 6 12 29 7 151 5.9 65 2.56 93.5 3.7 3.9 2.5 5.5 T2

RPDS 7 12 32.2 7.6 151 5.9 65 2.56 93.5 3.7 3.9 2.47 5.4 T2

RPDS 8 12 33.3 8 151 5.9 65 2.6 93.5 3.7 3.9 2.66 5.9 T2

RPDS 9 12 49.8 12 151 5.9 98 3.86 95 3.7 4 4.05 8.9 T2

RPDS 10 12 63.4 17 181.5 7.1 77 3.03 167.5 6.6 6.6 5.78 12.7 T12

RPDS 11 12 67.4 18 181.5 7.1 76.5 3.01 167.5 6.6 6.6 6 13.2 T3

RPDS 12 12 81.4 20 181.5 7.1 77 3.03 166 6.5 6.5 6.9 15.2 T12

RPDS 13 12 99.8 24 166 6.5 175 6.89 125 4.9 4.9 8.6 19 T3

RPDS 14 12 120.1 33.3 195 7.7 130 5.12 164 6.5 7.1 10.5 23.2 T10

RPDS 15 12 126.3 36.6 197 7.8 165 6.5 170 6.7 6.7 13.2 29.1 T6

RPDS 16 12 221.2 65 348 13.7 167 6.57 178 7 7 21.2 46.7 T6

RPDS 17 12 237.7 72 260 10.2 168 6.61 208 8.2 8.4 22.3 49.2 T6

RPDS 18 12 356.1 100 330 13 173 6.81 212 8.3 8.7 30.6 67.5 T11

RPDS 19 12 483.8 120 408 16.1 177 6.97 225 8.9 8.9 37.3 82.2 T11

RPDS 20 12 487.5 150 483 19 170 6.69 238.5 9.4 9.4 43.2 95.3 T11

RPDS 21 12 675.8 200 522 20.6 240 9.45 218 8.6 8.8 62.2 137.2 T11

RPDS 22 12 783.3 250 522 20.6 268 10.55 220 8.7 8.9 72.5 159.9 T11

RPDS 23 6 675.8 200 322 12.7 178 7.01 226 8.9 9.1 30.3 66.8 T11

Page 10: ups - renergypower.com fileVRLA-AGM battery for UPS are Valve -regulated Lead-Acid batteries with Absorbed Glass Matt (AGM) separators, makes it ideal for Uninterruptable Power Supply

[email protected]

(0044) 1908920612

500 Avebury Boulevard, Milton Keynes,Buckinghamshire, MK9 2BE

RPAS

RPCS RPDS

RPBS