Page 1 of 30
User Instructions
SITOP DC UPS Software
“Application”
for SITOP DC UPS Modules
6A with serial interface (6EP1931-2DC31) 6A with USB interface (6EP1931-2DC42) 15A with serial interface (6EP1931-2EC31) 15A with USB interface (6EP1931-2EC42) 40A with USB interface (6EP1931-2FC42) 500S (15A / 2.5kWs capacitor) (6EP1933-2EC41) 500S (15A / 5kWs capacitor) (6EP1933-2EC51)
Release 1.0
Page 2 of 30
Contents 1. Download SITOP DC UPS Software.........................................................................3 2. Installation of Application ..........................................................................................4 2.1. Basic Installation ...................................................................................................4 2.2. Installation USB Drivers ......................................................................................11 2.3. Update USB Drivers ............................................................................................15 3. Program Operation..................................................................................................17 3.1. Program Start ......................................................................................................17 3.2. Configuration .......................................................................................................18 3.3. SITOP DC UPS Monitoring .................................................................................23 3.4. Protocol Window .................................................................................................24 3.5. Logfile..................................................................................................................25 3.6. Further Settings...................................................................................................26 4. OPC Server .............................................................................................................27 4.1. Manual Registration of OPC Server ....................................................................27 4.2. Description of OPC Server Interface ...................................................................28 5. Help and Support ....................................................................................................29
1. Download SITOP DC UPS Software
Software download from our homepage (www.siemens.com/sitop).
Page 3 of 30
2. Installation of Application
2.1. Basic Installation Execute file “Setup_Sitop_3.x.2.x.exe“.
Select your language.
Installation is started.
Page 4 of 30
Accept the license agreement.
Page 5 of 30
Select the program components required. For installation as application the components “Application” and “Driver“ (when using a USB connection) are required.
Page 6 of 30
Choose the destination folder in which to instal the program packages.
Page 7 of 30
Select a start menu folder, if you would like to create an entry there.
Page 8 of 30
Typical settings of the SITOP software can be preset here: • Communication interface • Location of logfile (please note: write permission is required) • Service actions in UPS buffer mode (mains failure) • Automatic installation of OPC server interface (see chapter 4)
Page 9 of 30
Completion of installation.
Page 10 of 30
2.2. Installation USB Drivers The installation of drivers is only required for versions with USB interface. Before starting the installation please make sure that the SITOP DC UPS software (freeware download under www.siemens.de/sitop) is installed completely. Then connect the SITOP DC UPS module with a free USB interface. The SITOP DC UPS module is now identified automatically, the hardware wizard opens:
Page 11 of 30
Select “Install software from a list or specific location”. Click “Next“ to continue. In the next window you choose the location from where the driver will be installed, normally: ”C:\Program Files\Sitop\DRIVER“. If you have installed the SITOP DC UPS software in a different location, please enter it in the browse field. Click “Next” to continue.
Page 12 of 30
Please acknowledge the following warning with a click on “Continue Anyway“.
In the next window you complete the driver installation with a click on “Finish“.
Page 13 of 30
Following the same steps, the driver for a new serial COM port is installed.
In this window you complete the driver installation with a click on “Finish“. The driver for the SITOP DC UPS module is now installed successfully. Yon can control in the device manager whether the SITOP DC UPS module has been identified correctly:
Page 14 of 30
2.3. Update USB Drivers For the correct function of the SITOP DC UPS software it is necessary to install an up-to-date USB driver. From driver version 2.2.4.0 upwards this is guaranteed. If an older driver is installed already, an update of the USB driver has to be made. Before starting the driver update please make sure that the SITOP DC UPS software (freeware download on www.siemens.de/sitop) is installed completely. Search the entry ”SITOP xx“ in the folder “USB controllers” of the device manager. Mark the entry and by clicking the right mouse button open the context menu “Properties“. Here you can check the driver version.
Page 15 of 30
If the driver version is less than 2.2.4.0, an update has to be made. In order to do this please activate the button “Update Driver“. Then continue as described in chapter 2.2, “Installation USB drivers”.
Page 16 of 30
3. Program Operation
3.1. Program Start
Double click on ”SITOP_DC_USV.exe.
On the first program start the language selection opens.
Page 17 of 30
3.2. Configuration
• Selection of communication interface (COM or USB) • Option for display of monitoring window on status change (optionally after a time
that can be set) • Option for an acoustic signal on status change
• Selection of location of logfile (write permission required!)
• Option for sending a signal on manual Windows shutdown (latching shutdown of
SITOP DC UPS module; only available when communicating via USB of the following versions: 6EP1931-2DC42; 6EP1931-2EC42 und 6EP1931-2FC42)
• Option for saving the configuration with write protection
Page 18 of 30
• Option for starting an application after a set time when buffering
(example: *.exe, *.bat, *.vbs or *.js) • Option for PC shutdown after a set time when buffering (note: if the mains
voltage returns during the set time, the PC will NOT shut down)
• Option for signalizing the DC UPS on Windows shutdown (remote off)
Page 19 of 30
• Option for starting an application after a set time at ALARM (buffer not ready), (example: *.exe, *.bat, *.vbs or *.js)
• Option for starting an application after a set time at interrupted data communication (example: *.exe, *.bat, *.vbs or *.js)
Page 20 of 30
• Option for starting an application after a set time at recommended “battery replacement depending on aging“ (example: *.exe, *.bat, *.vbs oder *.js)
Page 21 of 30
• Option for starting an application after a set time at reaching battery charge >85% (battery fully charged), (example: *.exe, *.bat, *.vbs oder *.js)
• Option for starting an application after a set time at falling below battery charge
>85% (battery not fully charged), (example: *.exe, *.bat, *.vbs oder *.js)
Page 22 of 30
3.3. SITOP DC UPS Monitoring
Display of version number Display of SITOP DC UPS module connected Display of operating states in accordance with the LEDs on the SITOP DC UPS module
• DC o.k. • Alarm • Normal mode / buffer mode • Battery charge condition
Buttons:
opens configuration menu
opens protocol window
opens additional window with received data words
minimizes monitor window to system tray, can be displayed again by clicking the right mouse button
Page 23 of 30
3.4. Protocol Window The protocol window opens after clicking the button “Protocol“.
Display protocol file, all events are registered here with timestamp. Button:
opens logfile with Windows editor
Page 24 of 30
3.5. Logfile
In the logfile all events are registered and made available for later evaluation.
Page 25 of 30
3.6. Further Settings
In the “SITOP_DC_USV.INI“ file further individual program settings can be made.
Page 26 of 30
4. OPC Server The SITOP DC UPS software “Application” has an integrated OPC server interface. This software interface allows access to information sent by the SITOP DC UPS module out of own applications.
4.1. Manual Registration of OPC Server Before the OPC server interface can be used, it is necessary to register the SITOP DC UPS software in the operating system. If this was not effected during installation, the OPC server can also be registered manually. On clicking the Windows buttons “Start“ -> “Run...“ the following window opens:
As destination the path has to be selected where the program file “SITOP_DC_UPS.exe“ – unpacked in step “Basic Installation“ - is located. The OPC server can be removed by following the same steps, using the parameter “-unregserver“.
Page 27 of 30
Page 28 of 30
4.2. Description of OPC Server Interface Addressing the OPC server interface implicates an automatic start of the SITOP DC UPS software “Application“. Note: On starting the program a stable data connection to the SITOP DC UPS module is built up. This process may last a few seconds. A resulting possible delay of data availability at the OPC server interface must be taken into account. Sitop DC UPS OPC server - name: SITOP_UPS.OPC Sitop DC UPS OPC server – available items: Table1: Item name Type Description AKKU
Bool – active: battery exchange required
ALARM
Bool – active: buffer not ready
BAT
Bool – active: buffer mode
BAT85
Bool – active: battery fully charged
DC_OK Bool – active: input voltage o.k.
Variables describing the status of the SITOP UPS. “True” corresponds to the active LED on the device.
Connection Longint Status: 0 – no connection 1, 2 – connection available Status changes between 1 and 2 for monitoring connection
Status Longint Binary-coded status word, see table 2
Device String Type of connected device (example.: SITOP DC UPS 40)
last_Message String Last message/ logfile entry Received String Last telegram from UPS
Table 2: Coding status word The status word consists of 2 bytes, always 4 bits belonging to a LED of the SITOP UPS. Bits Correlation Status binary Description 0-3 Battery charge 1000
0010
Battery not fully loaded Battery fully loaded
4-7 Input voltage 1000 0010
No input voltage Input voltage available
8-11 Buffer mode 1000 0100
Normal mode Buffer mode
12-15 Alarm 1000 0001 0100
No alarm Buffer not ready Battery replacement required (LED flashing)
5. Help and Support
Further information is available in “ReadMe.rtf“.
Page 29 of 30
Page 30 of 30
Note: The information provided in these user instructions contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. Technical specifications are subject to change without prior notice, errors excepted. © Siemens AG, 2008 Industry Sector, Industry Automation SE IP Postfach 2355, D-90713 Fürth