Upload
lamnguyet
View
216
Download
0
Embed Size (px)
Citation preview
Document 12.05_90320051 ● R1.4 ● Errors and modifications accepted
© 2012 Gehrlicher Solar ● [email protected] ● www.gehrlicher.com
User ManualUser ManualUser ManualUser Manual
GehrTec® TopGehrTec® TopGehrTec® TopGehrTec® Top
GehrTec® TopGehrTec® TopGehrTec® TopGehrTec® Top––––TSTSTSTS
2
GehrTec® Top GehrTec® Top GehrTec® Top GehrTec® Top mountingmountingmountingmounting systemsystemsystemsystem
Dear customer,
Congratulations on your decision to select the GehrTec® Top mounting system for roof-
parallel attachment of photovoltaic elements (solar modules) on sloped roofs.
The GehrTec® Top mounting system is a modular and scalable system suitable for rooftop
mounting on many kinds of roof-top types. There are options for attaching both framed as
well as frameless solar modules - planning of the installation can be optimally adapted to
the installations parameters.
On receiving the shipment, please check the accompanying bill of delivery included to ensure
that your order has been delivered in full. Gehrlicher Solar AG does not bear any costs or
provide guarantees for any subsequent deliveries, if it is not notified until during the time of
installation that any material is missing. Please inspect the shipment for any visible damage
and contact your dealer should damage be detected.
Prior to installation, please familiarize yourself with the components of the mounting system
and their usage. Should you have any further questions, please contact us at the address
found on the last page of this user manual.
We continually strive to improve our products and welcome your feedback.
Dr. Anton Näbauer
Head of Product Development
Gehrlicher Solar AG
Email: [email protected]
Andreas Freyer
Senior Designer
Gehrlicher Solar AG
Email: [email protected]
3
Table of cTable of cTable of cTable of contentsontentsontentsontents ppppageageageage
1 1 1 1 –––– Safety instructions and general informationSafety instructions and general informationSafety instructions and general informationSafety instructions and general information .................................................................................................................................................................................................................................................................................................................................................................................................................... 4444
Duty of care on the part of the operator................................................................................................................... 4
Basic safety instructions ........................................................................................................................................................... 4
Operating personnel requirements ..................................................................................................................................... 5
Special hazard types ................................................................................................................................................................... 5
Safety and information symbols .......................................................................................................................................... 5
Safety information .......................................................................................................................................................................... 5
Rules and regulations ................................................................................................................................................................. 6
Notes about this user manual .............................................................................................................................................. 7
Further information ........................................................................................................................................................................ 7
Specific information ...................................................................................................................................................................... 8
Maintenance ....................................................................................................................................................................................... 8
Lightning and overvoltage protection .............................................................................................................................. 9
2 2 2 2 –––– InstallationInstallationInstallationInstallation ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ 10101010
GehrTec® Top system overview ........................................................................................................................................ 10
Tools required ................................................................................................................................................................................ 11
Positioning on the roof ............................................................................................................................................................ 12
Maximum combined rail length........................................................................................................................................... 15
Installing roof hooks .................................................................................................................................................................. 16
Installing hanger bolts............................................................................................................................................................... 19
Installing solar fasteners ......................................................................................................................................................... 21
Installing on trapezoidal profiles ....................................................................................................................................... 23
Installing the Top-TS system ................................................................................................................................................ 25
Installing clamp holders ........................................................................................................................................................... 32
The mounting rail system ...................................................................................................................................................... 34
Mounting solar modules .......................................................................................................................................................... 36
3 3 3 3 –––– The components of GehrTec® TopThe components of GehrTec® TopThe components of GehrTec® TopThe components of GehrTec® Top .................................................................................................................................................................................................................................................................................................................................................................................................................................................................................... 38383838
Mounting rails and accessories ......................................................................................................................................... 38
Module clamps for framed modules .............................................................................................................................. 40
Module clamps for frameless solar modules ........................................................................................................... 41
Roof hooks ........................................................................................................................................................................................ 42
Hanger bolts .................................................................................................................................................................................... 43
Solar fasteners ............................................................................................................................................................................... 44
Clamp holders................................................................................................................................................................................. 45
Top-TS .................................................................................................................................................................................................. 46
Bolts and accessories ............................................................................................................................................................... 47
4 4 4 4 –––– System staticsSystem staticsSystem staticsSystem statics ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ 49494949
DisclaimerDisclaimerDisclaimerDisclaimer ........................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ 55555555
ContactContactContactContact ............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................ 56565656
4
1 – Safety instructions and general information
1 1 1 1 –––– Safety instructions and general informationSafety instructions and general informationSafety instructions and general informationSafety instructions and general information
The following guidelines are for your protection and the protection of installers, third parties
and the components. Other specific safety guidelines are in the supplementary sheets
provided. Adherence to these guidelines is also an absolute requirement. Installation, initial
use and maintenance may only be carried out by those who are able to guarantee that the
work is carried out properly on the basis of their professional qualifications (training and
previous activities) and experience. All instructions pertain to intended use as it is laid down
in the Product Liability Law.
Duty of care on the part of the operatorDuty of care on the part of the operatorDuty of care on the part of the operatorDuty of care on the part of the operator
The GehrTec® Top mounting system was designed and developed in respect of a risk
analysis, and following careful selection of harmonized specifications to be observed, as well
as other technical specifications. The system is state-of-the-art and guarantees the highest
levels of safety.
However, these levels of safety can only be guaranteed in the field when all necessary
procedures have been taken. Part of the duty of care on the part of the installation firm
and system operator is to plan with respect to these measures and to check they are in
place.
It is particularly important for the installers and the operator to ensure that:
o The GehrTec® Top mounting system is only installed and operated for its intended
purpose
o The GehrTec® Top mounting system is only operated while in perfect working condition
o Specific installation instructions from the module and auxiliary component manufacturers
are observed
o Installation and maintenance work is carried out by adequately qualified and trained
personnel who have carefully read, and follow, this user manual
o This user manual is kept in a legible condition at all times and is available in full where
the GehrTec® Top system is installed
o All applicable laws, directives and regulations are observed
Basic safety instructionsBasic safety instructionsBasic safety instructionsBasic safety instructions
o Barriers must be used to cordon off the area prior to installation
o All those present during installation and operation must have undergone training
o Any necessary anti-fall guards must be in place
o Any personal protective gear required must be made available (see Tab. 2)
o Adherence to the Labour Protection Law in regards to load lifting must be observed
o Modifications to the GehrTec® Top mounting system may only be carried out by
qualified personnel and only after consultation with the manufacturer.
o Caution: high voltage Protective measurements against high voltages, and resultant
electric arcs, must also be in place on the DC side because of potentially high open
circuit voltages.
5
1 – Safety instructions and general information
OOOOperating personnelperating personnelperating personnelperating personnel requirementsrequirementsrequirementsrequirements
o Deploy an adequate number of authorised and qualified personnel
o Provision of general and site-specific safety instruction prior to beginning tasks
Special Special Special Special hhhhazardazardazardazard typestypestypestypes
o Third-party adaptations may only be used with prior approval from the manufacturer
o Inspection is mandatory given that hazards can arise in the event of inadequate
fastening
o Sharp-edged profile ends must also include edge protection to prevent injuries
Safety and information symbolsSafety and information symbolsSafety and information symbolsSafety and information symbols
Tab. 1: Safety and information symbols
SymbolSymbolSymbolSymbol MeaningMeaningMeaningMeaning ExplanationExplanationExplanationExplanation
DANGER “DANGER” denotes a safety guideline for which failure to
comply may result in immediate death or serious injury.
CAUTION “CAUTION” denotes a safety guideline for which failure to
comply may result in material damage.
NOTE “NOTE” denotes information that is important for optimal
operation of the product.
TIP “TIP” is information that is particularly useful and simplifies
installation.
Safety informationSafety informationSafety informationSafety information
Read this user manual carefully before starting with the installation, and observe all
applicable safety regulations and all other applicable national regulations in the country of
use.
During the installation, the installer is obliged to confirm the compliance of the user manuals
safety measures with all current rules and regulations, and to observe any new regulations
that may be applicable. Outside the European Union, adherence to applicable work safety
laws and regional national regulations for specific countries is required.
Caution!Caution!Caution!Caution! Always observe the applicable standards and regulations at the site of installation.
6
1 – Safety instructions and general information
All general safety and relevant accident prevention regulations, especially these relating to
roof work, as well as all applicable environmental protection regulations, are to be observed
and followed, in addition to the work safety measures detailed in this user manual.
Follow all of the instructions given in this user manual fully, unconditionally and without
exception.
Rules and regulationsRules and regulationsRules and regulationsRules and regulations
The industrial safety act and subsequent directives, as well as the rules and regulations set
out by the professional trade association, fund for accidents at work and Central Association
of the German Roofing Trade e. V. (ZVDH), must be observed during installation and
operation.
Particular reference is made to the following hazards and measures for the elimination of
risk:
Tab. 2: Risks and measures
SymbolSymbolSymbolSymbol HazardHazardHazardHazard MeasuresMeasuresMeasuresMeasures
General riskGeneral riskGeneral riskGeneral riskssss
Risk assessmentRisk assessmentRisk assessmentRisk assessment
Measures to avert Measures to avert Measures to avert Measures to avert recognizedrecognizedrecognizedrecognized rrrrisksisksisksisks
Instruction/trainingInstruction/trainingInstruction/trainingInstruction/training
Labour Protection Law
BGV A1 "Basics of Prevention"
Danger of falling from roof edgeDanger of falling from roof edgeDanger of falling from roof edgeDanger of falling from roof edge
Roof safety scaffolding, roof protection wallRoof safety scaffolding, roof protection wallRoof safety scaffolding, roof protection wallRoof safety scaffolding, roof protection wall
BGV C22 "Construction work"
BGV 807 "Securing of side protection, edge
protection and roof protection walls as anti-fall
protection during construction work"
BGR 198 "Deployment of personal anti-fall protection
equipment"
Operating safety legislation
BGR 203 "Roof work"
DIN 4420-1
DIN 4426
DIN EN 13374 and DIN EN 517
Side protectionSide protectionSide protectionSide protection
BGV C22 "Construction work"
BGV 807 "Securing of side protection, edge
protection and roof protection walls as anti-fall
protection during construction work"
DIN EN 13374
Operating safety legislation
7
1 – Safety instructions and general information
Tab. 2: Risks and measures - continued
Danger of falling Danger of falling Danger of falling Danger of falling
through roofthrough roofthrough roofthrough roof
Safety netsSafety netsSafety netsSafety nets
BGV C22 "Construction work"
BGR 179 "Deployment of safety nets"
DIN 1263 Parts 1 and 2
Danger of falling Danger of falling Danger of falling Danger of falling
through parts of the roofthrough parts of the roofthrough parts of the roofthrough parts of the roof
((((DomeDomeDomeDome lights, etc.)lights, etc.)lights, etc.)lights, etc.)
Built-in dome lights, window strips and smoke vents
with no fall protection must be secured with side
protection or covered with protective nets.
More information:
BGV C22 "Construction work"
Notes Notes Notes Notes about this about this about this about this user manualuser manualuser manualuser manual
This user manual is a part of your product - please keep it in a safe place near the
product.
Note!Note!Note!Note! For installation outside the Federal Republic of Germany, the legal and insurance stipulations as well as the technical regulations of that specific country must be observed and applied.
Further informationFurther informationFurther informationFurther information
Further information is available from the download section of our website under
www.gehrlicher.com.
8
1 – Safety instructions and general information
Specific informationSpecific informationSpecific informationSpecific information
The roof must be capable of supporting the additional load of a photovoltaic system, i.e.
there must be guarantees in place at all times that the roof and its supporting structure can
carry the additional static loads. If in doubt, consulting a structural engineer is strongly
recommended. Load propagation within the building is not factored in here (on-site statics).
Particular guarantees must be in place tParticular guarantees must be in place tParticular guarantees must be in place tParticular guarantees must be in place to ensure that:o ensure that:o ensure that:o ensure that: The roof in question is in perfect condition The mounting system is the correct one for the solar modules used and the roof type All legal construction site regulations are observed At no time is there any risk emanating from the solar modules Measures are always in place to distribute loading when working on the roof
MaintenanceMaintenanceMaintenanceMaintenance
The materials used mean the GehrTec® TOP mounting system is broadly maintenance free.
In addition to the prescribed electro-technical system inspections of the entire photovoltaic
system, we recommend an annual maintenance inspection respective of the following
inspection of:
o the solar modules for damage and dirt
o all mechanical connections for secure fit
o the mounting system and the module frame for mechanical damage
o the roof covering for leaks
o all electrical lines for damage (caused by animals for example)
o all electrical plug-in and screw connections for reliable contact and electric shock
protection
If an increase in the number of relevant faults is observed during the electro-technical
system inspection or on other reasons, the maintenance intervals must be shortened to a
sensible period (also for maintenance inspections). Additional special inspections must be
carried out after unusually bad weather, earthquakes or other unusual events that can
negatively impact the mounting system.
If the modules need cleaning, only clear water may be used with no chemical cleaning
products (follow the instructions provided by the module manufacturer). Remove the module
cabling and undo the module clamps to replace modules. Follow the relevant safety
instructions during this process (Page 4).
If the maintenance intervals and inspections described above are adhered to and carried out
is use as intended as laid down in the Product Liability Law. Only then do the
manufacturer's product liability take effect.
The inspections can, and should, be used to ensure that minor damage can be rectified
cost-effectively and that no further damage arises over time.
9
1 – Safety instructions and general information
Danger!Danger!Danger!Danger! Equipment to isolate the DC and AC voltages must be installed when carrying out maintenance work.
Lightning and overvoltage protectionLightning and overvoltage protectionLightning and overvoltage protectionLightning and overvoltage protection
You are informed that lightning and overvoltage protection of the photovoltaic system must
conform to the most recent versions of the following standards and directives.
Tab. 3: Technical rules and regulations for lightning and overvoltage protection
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN EN 62305-1
(IEC 62305-1:2006)
2006-10 Lightning protection (VDE 0185-305-1)
Part 1: General principles
DIN EN 62305-2
(IEC 62305-2:2006)
2006-10 Lightning protection (VDE 0185-305-2)
Part 2: Risk management
DIN EN 62305-3
(IEC 62305-3:2006)
2006-10 Lightning protection (VDE 0185-305-3)
Part 3: Protection of structural installations and people
DIN EN 62305-4
(IEC 62305-4:2006)
2006-10 Lightning protection (VDE 0185-305-4)
Part 4: Electrical and electronic systems in structural
installations
DIN VDE 0100-712
(IEC 60364-7-712:2002)
2006-06 Installation of low voltage systems
Part 7-712: Requirements for power supply systems (PV)
VdS 2010
2005-07 Risk-oriented lightning and overvoltage protection
Guidelines on damage prevention
Please refer to the directives and standards listed for more detailed information.
We generally recommend connecting the mounting system to the on-site potential
equalization system and using the overvoltage protection devices. Potential equalization is
always necessary when the solar modules used are not in Protection Class II and/or
transformer-less inverters are used.
10
2 – Installation
2 2 2 2 –––– InstallationInstallationInstallationInstallation
The GehrTec® Top mounting system can be used under the following conditions:
o Place of use: mono pitched roof, duo pitched roof
o Slope: 5° to 50°
o Installation: Rooftop mounting
o Building height: max. 25 m
o Solar modules: Frameless (laminate) or framed (aluminium)
o Module dimensions: max. Length 2,000 mm, max. Width 1,300 mm
o Module alignment: vertically, horizontally
GehrTec® Top system overviewGehrTec® Top system overviewGehrTec® Top system overviewGehrTec® Top system overview
Fig. 1: System overview using the example of a cross-rail system for frameless solar modules
1 - Roof hooks
2 - Cross members (e.g. horizontal mounting rail)
3 - Butt connectors
4 - Main members (e.g. vertical mounting rail)
5 - Cross connectors
6 - Module end clamps (e.g. GehrTec© laminate clamp)
7 - Module centre clamps (e.g. GehrTec© laminate clamp)
11
2 – Installation
Tools requiredTools requiredTools requiredTools required
The following tools and materials are needed for simply and secure installation (dependent
on application):
Tab. 4: Tools
NameNameNameName Use, type, size, accessoriesUse, type, size, accessoriesUse, type, size, accessoriesUse, type, size, accessories
Measuring tape For levelling PV generators for example
Marking string For making long straight lines (e.g. markings on roof)
Pencil / chalk For marking
Safety angle grinder Diamond cutting wheel for roofs (clay tiles, concrete tiles)
Drill, electric For pre-drilling the substructure or roof sheeting
Battery-powered drill driver With assorted bits, e.g. hex. drive
Battery-powered blind riveter With bit for Ø 4.8mm stainless steel
Combination spanner Sizes 13, 15, 17 mm AF
Screwdriver internal hexagon Sizes 5, 6 mm AF
Spiral drill bit for wood Ø 6 mm, Ø 7 mm, Ø 9 mm
Multi-purpose drill bit Ø 13 mm, Ø 14 mm
Spiral drill bit for metal Ø 5 mm, Ø 6.5 mm, Ø 6.8 mm, Ø 7.0 mm, Ø 7.2 mm, Ø 7.4 mm
Fig. 2: Tools required
Danger!Danger!Danger!Danger! Tools and materials must be in perfect condition. The use of impact wrenches is not generally permitted.
12
2 – Installation
Positioning on the roofPositioning on the roofPositioning on the roofPositioning on the roof
Two variations for the alignment and installation of solar modules are described below.
Provided it is allowed in the manufacturer's user manual, solar modules can always be
installed vertically (Fig. 3) or horizontally (Fig. 4). The standards and guidelines that must
apply and be followed when mounting the solar modules can be found in the installation
instructions from the relevant module supplier. With our mounting system, both variations are
possible either with a single-layer rail system or with a cross-rail system, depending on the
condition of the roof substructure.
Caution!Caution!Caution!Caution! Frameless solar modules must be mounted horizontally (see Fig. 4)
Fig. 3: Vertical alignment of solar modules on single-rail system
1 - Width of module area (generator area)
2 - Length of module area (generator area)
3 - Length of mounting rail
4 - Distance between mounting rails (note manufacturer specifications)
13
2 – Installation
Fig. 4: Horizontal alignment of solar modules on cross-rail system
1 - Width of module area (generator area)
2 - Length of module area (generator area)
3 - Distance between solar module clamps
4 - Distance between mounting rails
5 - Distance between mounting rails
All of the information and specifications in this user manual assume a four-point mounting
along the long side of the solar modules (at a gap of about ½ of the module lengths
according to the static calculation). One module is therefore carried by 2 mounting rails.
This ensures uniform load distribution onto the solar module.
Caution!Caution!Caution!Caution! Always observe the module manufacturer specifications (position of clamping points, gaps, etc.).
Example:
Module length as per data sheet: 1,200 mm
Clamping point position as per manufacturer: 275 +/- 25 mm from the edge
Distance (3) = 1,200 – 2 x 275 mm = 650 mm (corresponds to about ½ of the module
length)
Distance (5) = 1,200 – 650 mm = 550 mm + 10 mm (distance between the modules) = 560
mm
14
2 – Installation
Given the different module technologies and manufacturers on the market, there is a broad
array of solar module dimensions, giving rise to many possibilities for partitioning of the roof
area. The following information and recommendations are aimed at helping you in this
important step to find the best roof arrangement for your particular circumstances. The size
of a module area is calculated from the number of individual solar module dimensions plus
appropriate additions, such as for the module clamps (Table 5).
Tab. 5: Additions for the individual clamp types
Clamp typeClamp typeClamp typeClamp type Exact spacingExact spacingExact spacingExact spacing PlanningPlanningPlanningPlanning
Module centre clamp type 1 13 mm 20 mm
Module centre clamp type 2 19 mm 20 mm
Module end clamps (35 - 50mm) 24 mm 50 mm
Laminate centre clamp Top 24 mm 30 mm
Laminate end clamp Top 24 mm 50 mm
A corresponding distance from the roof edge must also be planned in to ensure the roof is
not hindered in its function (e.g. rainwater runoff into gutter).
Tab. 6: Minimum distances from roof edge
Roof edgeRoof edgeRoof edgeRoof edge Minimum distance recommendedMinimum distance recommendedMinimum distance recommendedMinimum distance recommended
Ridge > 50 cm
Verge board > 50 cm
Roof structures (chimney, skylight, etc.) > 50 cm (bear in mind shadowing)
Eaves (roof gutter) > 50 cm
We recommend drawing up a layout plan (prior to installation) with the positioning of the
module areas on the roof. Ensure that module areas are positioned far enough away from
roof structures so that they stay out of the shade.
15
2 – Installation
Maximum combined rail lengthMaximum combined rail lengthMaximum combined rail lengthMaximum combined rail length
For the forces caused by temperature fluctuations not to negatively impact the solar
modules or roof substructure, we recommend restricting the sizes of module areas and
splitting them up into several parts. This enables expansion in the lengthwise direction to be
reduced and simplifies accessibility to the solar modules for future maintenance work by
creating maintenance areas.
Note!Note!Note!Note! If the roof area available does not allow for the planning in of maintenance areas, the mounting rails must be interrupted by an expansion gap of at least 20 mm.
For this we recommend the maximum total lengths depending on roofing type (Table 7); i.e.
the maximum length of a combined mounting rail securely attached with butt connectors to
prevent damage to the solar module and roof. The maximum lengths apply for all mounting
rails in both directions, i.e. for both the lower position for the cross-rail system and also for
the mounting rails on which the solar modules lie and are attached.
Tab. 7: Maximum overall length of mounting rails connected together
Roofing typeRoofing typeRoofing typeRoofing type Recommended overall lengthRecommended overall lengthRecommended overall lengthRecommended overall length
Clay tile roof 12.0 m
Corrugated panels (e.g. Eternit) 12.0 m
Standing seam roofs 6.0 m
Trapezoidal sheet roofs 6.0 m
16
2 – Installation
InstallingInstallingInstallingInstalling roof hooksroof hooksroof hooksroof hooks
The area of roof above a rafter must first be cleared for the attachment point planned. To
do this, remove the roof tiles until the rafter is fully exposed (Fig. 5). Then whether the
whole area of the roof hook baseplate can lay flat on the rafter must be checked.
Caution!Caution!Caution!Caution! There must be no contact with the roof tile underneath (risk of breakage). If the tile height and/or roof batten do not have the standard dimensions, a shim must be placed between the rafter and baseplate of the roof hook, such as a wooden slat (Figs. 7 and 8), to maintain the gap between roof hook and tile.
Fig. 5: Removing the roof tiles Fig. 6: Fixing roof hook to rafter
Fig. 7: Roof hook must lie flat Fig. 8: Insert wooden shim for height compensation
Caution!Caution!Caution!Caution! Clay tile roofs generally have a rafter gap of 65 to 80 cm. Rafters are normally dimensioned for the effects of dead weight, snow and wind without any considerable reserves. The substructure for the solar modules must therefore be planned such that every rafter is loaded underneath the module surface area.
WRONGWRONGWRONGWRONG RIGHTRIGHTRIGHTRIGHT
17
2 – Installation
Fig. 9: Grinding off the ridges of roof tiles
Fig. 10: Replacing the roof tiles Fig. 11: Do not use roof hooks as a climbing aid
Caution!Caution!Caution!Caution! Roof hooks in place may not be used as a climbing aid for the installation.
Attachment Attachment Attachment Attachment screwsscrewsscrewsscrews
Roof hooks may only be attached directly to supporting parts of the roof (rafters, beams) to
which the screws can be attached to secure the baseplates of roof hooks (while observing
the edge distances of screws permitted - see DIN 1052). The baseplate is long enough to
allow pulling out of the hook in the tile trough by shifting the hook sideways. Two wood
screws (d = 8mm) in the centre line of the baseplate of the rook hooks must be used. The
wood screw diameter required is governed by the minimum screw-in depth necessary into
the supporting structural member of l ≥ 60 mm.
Tab. 8: Overview of wood screws with wheel head
Part no.Part no.Part no.Part no. SizeSizeSizeSize VariantVariantVariantVariant
Z34011880 8 x 80 mm e.g. without sheathing and counter batten
Z340118100 8 x 100 mm e.g. sarking membrane, counter batten 24 mm
Z340118120 8 x 120 mm e.g. sheathing 20 mm, counter batten 30 mm
Z340118140 8 x 140 mm e.g. sheathing 30 mm, counter batten 40 mm
NoteNoteNoteNote!!!! Use on roofs with on-roof insulation must be checked on a case-by-case basis by the customer.
To attach the roof hooks, tile ridges must
be ground off with an angle grinder at the
places where passage of roof hooks
between tiles is necessary (Fig. 9). This
applies to the ridge on the top of the tile
below and for the ridge on the bottom of
the tile covering the roof hook. The tiles
are then put back into position.
18
2 – Installation
Mounting railsMounting railsMounting railsMounting rails
Tip!Tip!Tip!Tip! If only the outermost roof hooks of a rail row are attached, and the mounting rail initially only hand-tightened, the roof hooks in-between can be positioned such that alignment of the rail using the long holes of the roof hooks is simplified.
Fig. 12: Securing of mounting rail on roof hooks Fig. 13: Alignment of mounting rail
Fig. 14: Securing of mounting rail on roof hooks Fig. 15: Alignment of mounting rail
The mounting rails are attached to the roof hook with a hammerhead bolt (part no.
Z34131020 or Z34131025) and a hexagonal nut with flange M 10 (part no. Z341510).
Caution!Caution!Caution!Caution! Adherence to the safety regulations for roofing work is required (DIN 18338). DIN 1052 regulations apply.
Adjustable roof hooks with extra bracketAdjustable roof hooks with extra bracketAdjustable roof hooks with extra bracketAdjustable roof hooks with extra bracket
Adjustable roof hooks are supplied with an extra bracket that allow for certain compensation
in the roof level. The following tightening torque is stipulated for the screw connection
between roof hook and extra bracket.
NoteNoteNoteNote!!!! Guide value for the tightening torque to DIN EN ISO 3506: 30 Nm (M10 screw)
19
2 – Installation
InstallInstallInstallInstalling haning haning haning hanger boltsger boltsger boltsger bolts
Hanger bolts with adaptor plates are used for attachment to roofs with fibre cement
corrugated panels (e.g. Eternit). We strongly advise against installation on roofs containing
asbestos. Professional renovation of the roof is strong recommended before installation.
DangerDangerDangerDanger!!!! It is illegal to drill or machine asbestos cement plates! Corrugated panels made of fibre cement or synthetic materials are often not fall-through resistant. Always use planks for load distribution when carry out installation work. The relevant laws and health & safety regulations must be observed.
Tab. 9: Overview of hanger bolts
Part no.Part no.Part no.Part no. SizeSizeSizeSize
Hanger boltHanger boltHanger boltHanger bolt
Adapter plateAdapter plateAdapter plateAdapter plate
Part no.Part no.Part no.Part no.
Hexagonal nutHexagonal nutHexagonal nutHexagonal nut
with flangewith flangewith flangewith flange
Part no.Part no.Part no.Part no.
PrePrePrePre----drilling diameterdrilling diameterdrilling diameterdrilling diameter
Roof tileRoof tileRoof tileRoof tile
Wooden Wooden Wooden Wooden
building building building building
structurestructurestructurestructure
340010200 M 10 x 200 Z3310003 Z341510 Ø 13 mm Ø 7 mm
340012300 M 12 x 300 Z3310004 Z3415112 Ø 14 mm Ø 9 mm
An attachment kit with an M12x300 hanger bolt is generally recommended. A M10 x 200
version is also available for special kinds of attachment for reduced horizontal spacing.
Other dimensions are available on request.
Fig. 16: Drilling through a roof tile / pre-drilling of the wooden structure
NoteNoteNoteNote!!!! Hanger bolts may not be positioned in the troughs of roof tiles (through which water passes).
20
2 – Installation
The roof tile (1) is drilled at the relevant places and then the wooden structure (2) is pre-
drilled (see Table 9 for the pre-drilling diameter). Holes may not be located in troughs
(through which water passes), only on the ridges of the panel profile. Hanger bolts must be
screwed into the supporting wooden structure over the length of the wood thread.
Hanger bolts must be screwed in at right angles to the surface to ensure perfect attachment
and protection from rain. The required screw depth into the supporting wood substructure l
must be ≥ 100 mm (Fig. 17).
TipTipTipTip!!!! An integrated power unit enables a battery-powered screwdriver or drill to be used.
Fig. 17: Screw in hanger bolt Fig. 18: Press in seal and tighten nut
For sealing, the slide-on rubber washer (part no. Z3200001) is pressed into the tile by
screwing in the hanger bolt into the hole drilled, and pressed onto the tile by hand-
tightening the hexagonal nut with flange (part no. Z341510 ) - see Fig. 18.
Caution!Caution!Caution!Caution! This is only for the purposes of sealing and is not intended to transfer any forces. Only press the rubber seal gently as there is a risk of breakage.
The mounting rails are attached to the adapter plate with a hammerhead bolt (part no.
Z34131020 or Z34131025) and a hexagonal nut with flange (part no. Z341510).
Caution!Caution!Caution!Caution! Adherence to the safety regulations for roofing work is required (DIN 18338). DIN 1052 regulations apply.
21
2 – Installation
InstallInstallInstallInstalling solar fastenersing solar fastenersing solar fastenersing solar fasteners
Our solar fasteners with adaptor plates can be used for secure and simply mounting on
roofs with a steel or wooden substructure. Easy to fit, they guarantee leak tightness, high
load bearing capacity and precise adjustment. The solar fasteners are anchored in the
substructure and transfer all resulting tensile and compressive forces into the substructure
so that, for example, the thin covers of sandwich elements are not damaged.
Solar fasteners are suitable for roofs with profile panels made of steel, aluminum, sandwich
elements or fibre cement corrugated panels.
Fig. 19: Drilling through a roof tile / pre-drilling of the substructure
The profiled tiles (1) are drilled at the relevant places, then the substructure (2) must be
pre-drilled (Fig. 19). Holes may not be located in troughs (through which water passes), only
on the ridges of profiled tiles. Select the bit length and drill hole depth in line with the
screw length. The profiled tiles and substructure must be pre-drilled in line with Table 10.
Tab. 10: Pre-drilling diameter in mm for profiled tiles and substructure
SolarSolarSolarSolar fastenerfastenerfastenerfastener
Thickness of substructure [mm], made ofThickness of substructure [mm], made ofThickness of substructure [mm], made ofThickness of substructure [mm], made of
steelsteelsteelsteel timbertimbertimbertimber
1.5 … < 5.01.5 … < 5.01.5 … < 5.01.5 … < 5.0 5.0 … < 7.55.0 … < 7.55.0 … < 7.55.0 … < 7.5 7.5 … < 107.5 … < 107.5 … < 107.5 … < 10 ≥ 10101010 ≥ 40404040
Type Z 6.8 7.0 7.2 7.4 -
Type A - - - - 6.0
TipTipTipTip!!!! For existing roofs attached to a steel substructure with Ø 5.5 mm or Ø 6.3 mm screws, the old screws can be removed and be replaced with Ø 8.0 mm solar fasteners. The pre-drill diameter must always be observed.
22
2 – Installation
NoteNoteNoteNote!!!! Fibre cement corrugated panels must be pre-drilled with an 11 mm diameter.
Fig. 20: Screwing in solar fastener
Tab. 11: Overview of type Z solar fasteners for steel substructures
Part no.Part no.Part no.Part no. DiameterDiameterDiameterDiameter LengthLengthLengthLength Screw lengthScrew lengthScrew lengthScrew length SetSetSetSetscrewscrewscrewscrew
Z34271880 Ø 8 mm 80 mm
Sandwich element
thickness / profile
height
+ 20 mm
M10 x 50 mm
Z342718100 Ø 8 mm 100 mm
Z342718125 Ø 8 mm 125 mm
Z342718150 Ø 8 mm 150 mm
Z342718200 Ø 8 mm 200 mm
Tab. 12: Overview of type A solar fasteners for timber substructures
Part no.Part no.Part no.Part no. DiameterDiameterDiameterDiameter LengthLengthLengthLength ScrewScrewScrewScrew----in depthin depthin depthin depth SetscrewSetscrewSetscrewSetscrew
Z342728100 Ø 8 mm 100 mm
In wood:
min. 34 mm
max. 96 mm
M10 x 50 mm
Z342728130 Ø 8 mm 130 mm
Z342728150 Ø 8 mm 150 mm
Z342728180 Ø 8 mm 180 mm
Z342728200 Ø 8 mm 200 mm
The M10 adapter plate (part no. Z3310003) is locked against the welded-on setscrew
between the hexagonal nuts and washers, allowing a connection to the mounting rails. This
connection to the adapter plate is established with a hammerhead bolt (part no. Z34131020
or Z34131025) and a hexagonal nut with flange (part no. Z341510).
Caution!Caution!Caution!Caution! Adherence to the safety regulations for roofing work is required (DIN 18338). The regulations lay down in DIN 1052 and DIN 18807 applies.
Solar fasteners must be secured at right
angles to the surface to guarantee perfect
supporting attachment and protection from
rain as required.
Drilling chips must be removed from the
surface.
The solar fasteners are pre-assembled and
have an integrated hexagonal recess (5
mm) so a power screwdriver can be used.
The use of impact wrenches is not
permitted.
23
2 – Installation
InstallInstallInstallInstalling oing oing oing onnnn trapezoidal profilestrapezoidal profilestrapezoidal profilestrapezoidal profiles
The T1 mounting rail enables direct installation on trapezoidal sheet roofs. It can be used
as both a simple horizontal rail system and as a cross-rail system. Applied all over the
underside is an EPDM seal that functions as a separator from the trapezoidal profile and
seals the joint.
NoteNoteNoteNote!!!! Vertical orientation of the T1 mounting rail parallel to the sheet ridges is not permitted. The T1 mounting rail must be connected with two connecting elements per ridge.
PrinciplePrinciplePrinciplePrinciple
The T1 mounting rail is placed directly on the trapezoidal profile with the underside at right
angles (!) to the sheet ridges aligned (Fig. 21) and joined. This attains as uniform a load
distribution as possible onto the trapezoidal profile.
Attachment methodAttachment methodAttachment methodAttachment method
Only fastening elements with general building authority approval are used. Different drill hole
diameters are used depending on fastening element (see Table 13). The T1 mounting rail
has a small indentation on both sides for orientation and for keeping to the edge distances
required for the drilling process. Fastening elements must be positioned at right angles to
the surface to establish a perfect supporting and rain-protected joint.
Tab. 13: Overview of fastening elements
Part no.Part no.Part no.Part no. NameNameNameName SizeSizeSizeSize PrePrePrePre----drilling diameterdrilling diameterdrilling diameterdrilling diameter Panel thickness tPanel thickness tPanel thickness tPanel thickness tIIIIIIII mmmmmmmm
Z34056325 Drilling screw 6.3 x 25 Ø 6.5 mm 0.50 ≤ tII ≤ 1.25
Z3430001 Blind rivet 4.8 x 15 Ø 5.0 mm 0.50 ≤ tII ≤ 1.25
Drilling screwsDrilling screwsDrilling screwsDrilling screws
The screws are drilling screws made of non-rusting steel with a drill bit made of case-
hardened steel. The screws are used with an EPDM sealing washer. For installing of the
screws, the T1 mounting rail (but not the trapezoidal profile) is pre-drilled with a hole with
diameter 6.5 mm. The sealing washer shows whether the screw joint has been tightened
correctly. The joint is correct when the metal back of the sealing washer is almost flat and
the remolded EPDM sealing bends up slightly out of the side. The screw is governed by
Annex 3.126 of general building regulation approval Z-14.1-4.
NoteNoteNoteNote!!!! The use of impact wrenches is not permitted. Drilling screws must be screwed in up to the end stop, guideline value: 5 Nm Screws that are not tightened adequately enough, and sealing washers compressed too much, can negatively impact the sealing function.
24
2 – Installation
Blind rivetsBlind rivetsBlind rivetsBlind rivets
A rivet is a blind rivet with an aluminum sleeve and a rustproof steel mandrel. Blind rivets
are used with "under-head seals". To fit blind rivets, the T1 mounting rail and the
trapezoidal profile are pre-drilled with a hole of diameter 5.0 mm. Blind rivets are governed
by Annex 2.15 of general building regulation approval Z-14.1-4.
NoteNoteNoteNote!!!! To prevent corrosion and leaks, we recommend removal ALL drill shavings from the roofing and adjacent areas, such as the guttering. We recommend using a suitable vacuum cleaner or compressed air to remove the drill shavings so that the roofing is not damaged in any way.
Using conventional cleaning equipment (such as a broom) presents a risk of damaging the
protective paint of the roof.
Fig. 21: Placing and positioning of mounting rail Fig. 22: Pre-drilling of the T1 mounting rail
Fig. 23: Screwing in of hanger bolt Fig. 24: Inserting a blind rivet
TipTipTipTip!!!! When using the drilling screw, we recommend pre-drilling the T1 mounting rail near the bottom bead to prevent pre-drilling the trapezoidal profile.
25
2 – Installation
InstallInstallInstallInstalling the Toping the Toping the Toping the Top----TS systemTS systemTS systemTS system
The GehrTec® Top-TS system allows the mounting of framed solar modules directly on
trapezoidal profile plates and is based on the attachment of the T1 mounting rail. The solar
modules can be attached to very slightly sloped roof areas using the additional setting
angle, and on roof areas pointing in an unfavorable direction with perfect alignment towards
the sun. The setting angle attained in relation to the roof surface is 15°. The slope of the
roof can be between 5° and 20°. The GehrTec® Top-TS system can be used under the
following conditions:
o Place of use: mono pitched roof, duo pitched roof (trapezoidal sheet)
o Roof slope: 5° to 20°
o Building height: max. 25 m
o Solar modules: Framed (aluminium), frame height 35 to 50 mm
o Module dimensions: Max. 1700 mm x 1100 mm
o Module alignment: horizontal
Alignment of the solar modulesAlignment of the solar modulesAlignment of the solar modulesAlignment of the solar modules
The solar modules themselves must be positioned horizontally (as seen in the direction of
sun rays) on the attachment system, and must form a row of solar modules next to each
other. These solar module rows can be aligned to two different roof boundaries. There is
alignment of the solar module rows parallel to the two gable boards of a roof surface (see
Fig. 25) - recommended for roof surfaces pointing mainly in the east/west direction. This
variant is referred to as installation variant A below.
Fig. 25: Example of Top-TS installation, alignment of the solar module rows parallel to the gable board
26
2 – Installation
There is also an option of positioning the solar module rows parallel to the roof ridge or
eaves on roof surfaces that point in exactly the right direction as regards the sun but only
have a gentle slope (see Fig. 26). This variant is referred to as installation variant B below.
Fig. 26: Example of Top-TS installation, alignment of the solar module rows parallel to the roof ridge/eaves
Orientation of the T1 mounting rail stays the same in both cases, i.e. parallel to the roof
ridge/eaves and running at right angles to the top bead of the trapezoidal profile (see Fig.
27).
Fig. 27: Alignment of the T1 mounting rail
NoteNoteNoteNote!!!! The specifications and guidelines for attaching the T1 mounting rail are described in Section "Installing of trapezoidal profiles" and must be observed.
27
2 – Installation
PositioningPositioningPositioningPositioning on the roofon the roofon the roofon the roof
The arrangement and positioning of T1 mounting rails essentially depend on the dimensions
of the solar modules used and the orientation of the solar module rows. For installation
variant A, the gaps are given by the position of the clamping points on the solar modules
(see Fig. 28). For installation variant B, the gaps between mounting rails are determined by
the distance between base supports (see Figs. 29 and 30). Distance x between the solar
module rows must be taken into consideration to prevent shadowing.
Caution!Caution!Caution!Caution! Always observe the module manufacturer specifications (position of clamping points, gaps, etc.).
Example of clamping point positioning
Module length as per data sheet: 1,650 mm
Clamping point position as per manufacturer: 330 +/- 25 mm measured from the edge (A3)
Distance (A1) = 1,650 mm – 2 x 330 mm = 990 mm
Distance (A2) = 2 x A3 + 20 mm (distance between modules) = 2 x 330 mm + 20 mm =
680 mm
Fig. 28: Distance between clamping points
28
2 – Installation
The base supportsThe base supportsThe base supportsThe base supports
The actual Top-TS system comprises the base supports and the module clamps. There is
short base support 1 for holding the solar module directly above the T1 mounting rail, and
two-part base support 2 that lifts the solar module to the required angle of 15°. The length
of base support 2 can be adjusted so that solar modules having different dimensions can be
installed (see Figs. 29 and 30).
Fig. 29: Example module width 800mm Fig. 30: Example module width 1,100mm
Fig. 31: Mounting together base support 2
An M10x25 hammerhead bolt (part no. Z34131025) and a hexagonal nut with flange (part no.
Z341510) are used for securing onto the T1 mounting rail.
Fig. 32: Mounting base support 1 Fig. 33: Mounting base support 2
NoteNoteNoteNote!!!! Guide value for the tightening torque to DIN EN ISO 3506: 30 Nm (M10 screw)
The following parts are required for
mounting base support 2.
1 x base support 2-1
(part no. Z3340014)
1 x base support 2-2
(part no. Z3340015)
2 x hexagonal bolt with M10x30 flange
(part no. Z34291030)
2 x hexagonal nut with M10 flange
(part no. Z341510)
29
2 – Installation
Tab. 14: Overview of distances in relation to module width
Module widthModule widthModule widthModule width Length aLength aLength aLength a Centre to centre Centre to centre Centre to centre Centre to centre
distance ddistance ddistance ddistance d Height hHeight hHeight hHeight h
800 mm 241 mm 803 mm 207 mm
810 mm 244 mm 814 mm 210 mm
820 mm 247 mm 824 mm 212 mm
830 mm 249 mm 835 mm 215 mm
840 mm 252 mm 845 mm 217 mm
850 mm 255 mm 855 mm 220 mm
860 mm 257 mm 866 mm 223 mm
870 mm 260 mm 876 mm 225 mm
880 mm 263 mm 886 mm 228 mm
890 mm 265 mm 897 mm 230 mm
900 mm 268 mm 907 mm 233 mm
910 mm 271 mm 917 mm 236 mm
920 mm 273 mm 928 mm 238 mm
930 mm 276 mm 938 mm 241 mm
940 mm 279 mm 948 mm 243 mm
950 mm 281 mm 959 mm 246 mm
960 mm 284 mm 969 mm 248 mm
970 mm 287 mm 980 mm 251 mm
980 mm 289 mm 990 mm 254 mm
990 mm 292 mm 1,000 mm 256 mm
1,000 mm 295 mm 1,011 mm 259 mm
1,010 mm 297 mm 1,021 mm 261 mm
1,020 mm 300 mm 1,031 mm 264 mm
1,030 mm 303 mm 1,042 mm 267 mm
1,040 mm 305 mm 1,052 mm 269 mm
1,050 mm 308 mm 1,062 mm 272 mm
1,060 mm 311 mm 1,073 mm 274 mm
1,070 mm 314 mm 1,083 mm 277 mm
1,080 mm 316 mm 1,093 mm 280 mm
1,090 mm 319 mm 1,104 mm 282 mm
1,100 mm 322 mm 1,114 mm 285 mm
NoteNoteNoteNote!!!! Centre to centre distance d is for the bolts (see Figs 34 and 35)
30
2 – Installation
Distance between solar module rowsDistance between solar module rowsDistance between solar module rowsDistance between solar module rows
Because of the additional angle of 15°, roof planning must take into consideration an
appropriate distance between solar module rows for shadowing. This distance is dependent
on the module width used and the orientation and slope of the roof surface. For a roof
pointing southwards, there should be no shadowing at midday on midwinters day (21
December), i.e. when the sun is at its lowest point. In Germany, the elevation angle of the
sun is about 15°, from which the necessary clearances can be calculated.
Fig. 34: Clearances for installation variant A
The height of the structure at right angles to the roof surface is an important part of the
calculation and dependent on the module width.
Fig. 35: Distance x between module rows for installation variant B
NoteNoteNoteNote!!!! Calculation of the distances (x) should only be performed by experienced system planners
hhhh
dddd
dddd xxxx
dddd
dddd
31
2 – Installation
InstallInstallInstallInstalling of solar modulesing of solar modulesing of solar modulesing of solar modules
After the base supports have been mounted, the solar modules can be inserted (Fig. 36) and
then secured into place with Top-TS module clamps (part no. Z3340016) and appropriate
hexagonal bolts with cheese head (see Table 15) - Fig. 37.
Fig. 36: Inserting a solar module Fig. 37: Mounting TOP TS module clamps
Tab. 15: Overview of the bolts for the Top-TS module clamp (part no. Z3340016)
Cylinder head M 8xCylinder head M 8xCylinder head M 8xCylinder head M 8x [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm]
Frame height 35 40 42 45 46 50
Part no. Z34118xx 35 40 45 45 50 50
(Example: part no. Z3411850 for Allen screw M8x50)
Component part listComponent part listComponent part listComponent part list
Tab. 16: Components required to attach a solar module
Part no.Part no.Part no.Part no. NameNameNameName SizeSizeSizeSize QtyQtyQtyQty.... / solar module/ solar module/ solar module/ solar module
Z3340013 Base support 1 60 mm 2
Z3340014 Base support 2-1 60 mm 2
Z3340015 Base support 2-2 60 mm 2
Z3340016 Top-TS module clamp 60 mm 4
Z34291030 Hexagon bolt with flange M10x30 4
Z34131025 Hammerhead bolt M10X25 4
Z341510 Hexagon nut with flange M10 8
Z34118xx Allen screw M8xL 4
32
2 – Installation
InstallInstallInstallInstalling clamp holdersing clamp holdersing clamp holdersing clamp holders
We use special clamp holders for mounting solar power systems on metal roofs. For
standing seam roofs in particular, and pre-manufactured profile sheets such as Kalzip, Bemo
and RibRoof, the roofing is not damaged by using the clamp system because clamp holders
are attached to the sheet seam.
NoteNoteNoteNote!!!! Adherence to the relevant building regulation approvals of the manufacturer is an absolute requirement for installing profile sheet systems (Kalzip, BEMO, etc.).
The specification of the number of clamp holders is dependent on the design, weight and
size of the solar modules.
Tab. 17: Overview of the different clamp holders
Part no.Part no.Part no.Part no. Sheet profileSheet profileSheet profileSheet profile LengthLengthLengthLength MaterialMaterialMaterialMaterial Profile typesProfile typesProfile typesProfile types
Z3330001 Standing seam 110 mm Aluminium Standing seam and similar
Z3330002 Round head profiles 110 mm Aluminium Bemo, Kalzip and similar
Z3330003 Round head profiles 110 mm Aluminium RibRoof 465/480, Domico
Z3330004 Round head profiles 110 mm Aluminium RibRoof 500
Z3330005 Round head profiles 55 mm Aluminium Bemo, Kalzip and similar
Z3330006 Round head profiles 55 mm Aluminium RibRoof 465/480, Domico
Caution!Caution!Caution!Caution! The individual wind-drag loads and snow loads possible must be established to determine the load transfer to the wooden substructure. A check must be carried out by the customer on whether attachment with clamp holders is sufficient or whether the system needs to be secured with additional measures.
The number of attachment points must be determined by a structural engineer based on the
conditions on site. An extraction force of about 400 N (40 kg) must be applied for nails
used for securing on metal roofs. This can result in the sheet metal clips coming off the
wooden substructure before the clamp holder comes off the sheet seams.
Specific informationSpecific informationSpecific informationSpecific information
The following special guidelines must be followed for mounting on sheet profile systems
(Kalzip, BEMO, etc.). Most sheet profile systems are attached with clips (spacers) to the roof
substructure (e.g. steel girders). The loads caused by tensile and compressive forces that can
be taken up by the sheet profile system flange depend on the centre spacing of these clips
and the sheet thickness.
For the securing of the sheet profiles in the event of thermal agitation and for the transfer
of shear and normal forces arising in the roof due to the solar power system, fixed points
are provided where, in compliance with the building authority approval from the
manufacturer, the mounting system for the solar power system must be mounted and
connected.
33
2 – Installation
A clamp holder that attaches the profiles of the substructure to the roof can generally
transfer greater loads than the flange of the sheet profile system.
Elevations must generally be rated critically for sheet profile systems. Elevations are not
permitted at all for standing seam roofs.
NoteNoteNoteNote!!!! Adherence to the regulations of the metal roofer trade is required (DIN 18339).
Fig. 38: Mounting a clamp holder Fig. 39: Securing a mounting rail
Fig. 40: Aligning the mounting rail Fig. 41: Cross-rail system
34
2 – Installation
The The The The mountingmountingmountingmounting rail systemrail systemrail systemrail system
The GehrTec® Top mounting system from Gehrlicher Solar AG boasts an innovative mounting
rail system - every groove allows quick and simple insertion of nuts and bolts at any
position, simplifying considerably installation.
NoteNoteNoteNote!!!! All connections on mounting rails must be tightened by hand. Guide values for tightening torques to DIN EN ISO 3506: 15 Nm (M8) / 30 Nm (M10)
Fig. 42: Inserting a bolt Fig. 43: Turning in the bolt
Fig. 44: Turning a hammerhead bolt Fig. 45: Side view of hammerhead bolt
Fig. 46: Turning a hammerhead nut Fig. 47: Side view of hammerhead nut
Tab. 18: Overview of hammerhead nuts and bolts
Part no.Part no.Part no.Part no. NameNameNameName SizeSizeSizeSize MaterialMaterialMaterialMaterial
Z34131020 Hammerhead bolt M 10x20 Stainless steel A2
Z34131025 Hammerhead bolt M 10x25 Stainless steel A2
Z34149 Hammerhead nut M 8 Stainless steel A2
35
2 – Installation
The GehrTec® Top mounting system from Gehrlicher Solar AG is a general purpose system
that always works to the same principle. Mounting rails are attached to the roof, on which
solar modules are secured at four clamping points. The mounting rails run either horizontally
(see Fig. 2) or vertically (see Fig. 3) depending on orientation and positioning of the solar
modules. The mounting rails are secured to the roof substructure with attachment points
(dependent on roofing) - e.g. roof hooks.
If the roof substructure does not offer any suitable attachment points for the mounting rails,
a cross-rail system is recommended. Using a second rail level, offset by 90°, means the
system can be used flexibly in both directions.
NoteNoteNoteNote!!!! We generally recommend a cross-rail system for frameless solar modules. A cross-rail system does not reduce the number of attachment points required.
Rail cross connectorsRail cross connectorsRail cross connectorsRail cross connectors
Crossing points are established with our rail cross connector (Fig. 48). The following parts
are required:
1 x rail cross connector (part no. Z3110002)
2 x Allen key bolt M8x16 (part no. Z34111816)
2 x M8 hammerhead nut (part no. Z34149)
Fig. 48: Rail cross connector Fig. 49: Butt connector
Butt connectorButt connectorButt connectorButt connector
Two butt connectors are used to connect the mounting rails. The cross-section is designed
such that they can be inserted into the profile channel (Fig. 49). The following parts are
required for every butt connection:
2 x butt connectors (part no. Z3110001)
4 x Allen key bolt M8x16 (part no. Z34111816)
4 x M8 thrust washer (part no. Z34188)
NoteNoteNoteNote!!!! All butt connections must be made with two butt connectors and must be positioned within two support points. No cantilever arm may be extended. Use in the top profile channel may lead to overlaps with module clamps or solar modules >> note the position of butt connectors!
36
2 – Installation
MountMountMountMounting solar modulesing solar modulesing solar modulesing solar modules
Framed solar modulesFramed solar modulesFramed solar modulesFramed solar modules
Framed solar modules are clamped to the mounting rails with our module centre clamps and
an appropriately long Allen key bolt plus hammerhead nut M8 (part no. Z34149). Used on
both ends of a module row are our module clamps for the relevant module frame height
and M8x16 Allen key bolts (part no. Z34111816) plus hammerhead nuts M8 (part no.
Z34149).
Tab. 19: Overview of the bolts for module centre clamp 1 (part no. Z3120001)
Countersunk head M 8xCountersunk head M 8xCountersunk head M 8xCountersunk head M 8x [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm]
Frame height 35 40 42 45 46 50
Part no. Z34128xx 50 55 55 60 60 65
(Example: part no. Z3412860 for Allen countersunk screw M8x60)
Tab. 20: Overview of the bolts for module centre clamp 2 (part no. Z3120010)
Cylinder head M 8xCylinder head M 8xCylinder head M 8xCylinder head M 8x [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm] [mm][mm][mm][mm]
Frame height 35 40 42 45 46 50
Part no. Z341118xx 16 20 20 25 25 30
(Example: part no. Z34111820 for Allen key bolt M8x50)
Fig. 50: Mounting a module centre clamp Fig. 51: Mounting a module end clamp
37
2 – Installation
Frameless solar modulesFrameless solar modulesFrameless solar modulesFrameless solar modules
Frameless solar modules (laminates) are attached with our Gehrtec® Laminate Clamp. These
laminate clamps are two-part, i.e. comprise a top and a bottom part. The bottom clamp part
can be pressed into the groove of the mounting rail and positioned (Fig. 53) using the
special Top clip (part no. Z3120018) already with an M8 hammerhead nut (part no. Z34149)
and that is clicked into the bottom clamp part (Fig. 52). This enables precise alignment of
the clamping points and insertion of the frameless solar modules into the bottom clamp
parts positioned (Fig. 54). The last step is inserting and screwing in the top clamp parts with
Allen countersunk screws (part no. Z3412835) - Fig. 55.
The module clamps have special EPDM rubber profiles, meaning the frameless solar module
is only clamped and not subjected to mechanical loading. Please refer to the user manual
from the relevant manufacturer for the positions of the clamping points on the solar module.
Our laminate clamps are suitable for frameless solar modules having a thickness of 6.8 – 7.0
mm.
Fig. 52: Click the TOP clip into the bottom part Fig. 53: Press in and align the bottom part
Fig. 54: Insert a solar module Fig. 55: Insert the top clamp part and the screws
NoteNoteNoteNote!!!! Follow the installation instructions for the GehrTec® laminate clamps (see package insert). Follow the installation instructions from the module manufacturer (minimum distances, clamping points, etc.). Frameless solar modules must be mounted horizontally.
38
3 – Components of GehrTec® Top
3 3 3 3 –––– The components of GehrTec® TopThe components of GehrTec® TopThe components of GehrTec® TopThe components of GehrTec® Top
Mounting rails and accessoriesMounting rails and accessoriesMounting rails and accessoriesMounting rails and accessories
Mounting rail 1Mounting rail 1Mounting rail 1Mounting rail 1 Part no.:Part no.:Part no.:Part no.: Z3100001Z3100001Z3100001Z3100001
Usable as cross beam (cross-rail system) or as main beam.
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 30 x 50 mm
Mounting rail 2Mounting rail 2Mounting rail 2Mounting rail 2 Part no.:Part no.:Part no.:Part no.: Z3100002Z3100002Z3100002Z3100002
Usable as cross beam (cross-rail system).
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 30 x 30 mm
Mounting rail 3Mounting rail 3Mounting rail 3Mounting rail 3 Part no.:Part no.:Part no.:Part no.: Z3100003Z3100003Z3100003Z3100003
Usable as cross beam (cross-rail system) or as main beam.
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 40 x 50 mm
Mounting rail 4Mounting rail 4Mounting rail 4Mounting rail 4 Part no.:Part no.:Part no.:Part no.: Z3100004Z3100004Z3100004Z3100004
Usable as cross beam (cross-rail system) or as main beam.
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 40 x 60 mm
39
3 – Components of GehrTec® Top
Mounting rail 5Mounting rail 5Mounting rail 5Mounting rail 5 Part no.:Part no.:Part no.:Part no.: Z3100005Z3100005Z3100005Z3100005
Usable as cross beam (cross-rail system) or as main beam.
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 40 x 70 mm
Mounting rail T1Mounting rail T1Mounting rail T1Mounting rail T1 Part no.:Part no.:Part no.:Part no.: Z3100006Z3100006Z3100006Z3100006
For mounting on trapezoidal sheet roofs with special EPDM
sealing on the underside.
EN AW6063 T66
Standard length: 6,000 mm
Cross-section: 30 x 30 (80) mm
Butt connectorButt connectorButt connectorButt connector Part no.:Part no.:Part no.:Part no.: Z3110001Z3110001Z3110001Z3110001
Fastening element for mounting rails.
EN AW6063 T66
Length: 100 mm
Accessories required:
2 x Allen key bolt M8x16 (part no. Z34111816)
2 x M8 thrust washer (part no. Z34188)
Rail crossRail crossRail crossRail cross----connectorconnectorconnectorconnector Part no.:Part no.:Part no.:Part no.: Z3110002Z3110002Z3110002Z3110002
Fastening element for the cross-rail system.
EN AW6063 T66
Two mounting holes for M8
Accessories required:
2 x Allen key bolt M8x16 (part no. Z34111816)
2 x M8 hammerhead nut (part no. Z34149)
40
3 – Components of GehrTec® Top
Module clamps for framed modulesModule clamps for framed modulesModule clamps for framed modulesModule clamps for framed modules
Module centre clamp type 1Module centre clamp type 1Module centre clamp type 1Module centre clamp type 1 Part no.:Part no.:Part no.:Part no.: Z3120001Z3120001Z3120001Z3120001
For attaching solar modules with aluminium frame.
EN AW6063 T66, length 80mm
General purpose
Accessories required:
1 x M8 countersunk screw (part no. Z34128xx)
1 x M8 hammerhead nut (part no. Z34149)
Module centre clamp type 2Module centre clamp type 2Module centre clamp type 2Module centre clamp type 2 Part no.:Part no.:Part no.:Part no.: Z3120010Z3120010Z3120010Z3120010
For attaching solar modules with aluminium frame.
EN AW6063 T66, length 80mm
General purpose
Accessories required:
1 x M8 Allen key bolt (part no. Z3411xx)
1 x M8 hammerhead nut (part no. Z34149)
Module end clamp 35Module end clamp 35Module end clamp 35Module end clamp 35 Part no.:Part no.:Part no.:Part no.: Z3120007Z3120007Z3120007Z3120007
Module end clamp 40Module end clamp 40Module end clamp 40Module end clamp 40 Part no.:Part no.:Part no.:Part no.: ZZZZ3120008312000831200083120008
Module end clamp 42Module end clamp 42Module end clamp 42Module end clamp 42 Part no.:Part no.:Part no.:Part no.: Z3120002Z3120002Z3120002Z3120002
Module end clamp 45Module end clamp 45Module end clamp 45Module end clamp 45 Part no.:Part no.:Part no.:Part no.: Z3120035Z3120035Z3120035Z3120035
Module end clamp 46Module end clamp 46Module end clamp 46Module end clamp 46 Part no.:Part no.:Part no.:Part no.: Z3120003Z3120003Z3120003Z3120003
Module end clamp 50Module end clamp 50Module end clamp 50Module end clamp 50 Part no.:Part no.:Part no.:Part no.: Z3120004Z3120004Z3120004Z3120004
For attaching solar modules with aluminium frame.
EN AW6063 T66, length 80mm
Accessories required:
1 x Allen key bolt M8x16 (part no. Z34111816)
1 x M8 hammerhead nut (part no. Z34149)
41
3 – Components of GehrTec® Top
Module clamps for frameless solar modulesModule clamps for frameless solar modulesModule clamps for frameless solar modulesModule clamps for frameless solar modules
GehrTec© laminate centre clampGehrTec© laminate centre clampGehrTec© laminate centre clampGehrTec© laminate centre clamp Part no.:Part no.:Part no.:Part no.: Z3120016Z3120016Z3120016Z3120016
For attaching frameless solar modules.
EN AW6063 T66
Special EPDM rubber profiles
Approved by First Solar PD-5-321-34 EU
Accessories required:
1 x countersunk screw M8x35 (part no. Z3412835)
1 x TOP clip (part no. Z3120018)
IMPORTANT: Follow the installation instructions (see package
insert)
GehrTGehrTGehrTGehrTec© laminate end clampec© laminate end clampec© laminate end clampec© laminate end clamp Part no.:Part no.:Part no.:Part no.: Z3120017Z3120017Z3120017Z3120017
For attaching frameless solar modules.
EN AW6063 T66
Special EPDM rubber profiles
Approved by First Solar PD-5-321-34 EU
Accessories required:
1 x countersunk screw M8x35 (part no. Z3412835)
1 x TOP clip (part no. Z3120018)
IMPORTANT: Follow the installation instructions (see package
insert)
Top clipTop clipTop clipTop clip Part no.:Part no.:Part no.:Part no.: Z3120018Z3120018Z3120018Z3120018
For quick and easy mounting of GehrTec© laminate clamps.
Synthetic ASA
Colour: light grey
Already with M8 hammerhead nut (part no. Z34149)
42
3 – Components of GehrTec® Top
Roof hooksRoof hooksRoof hooksRoof hooks
Slate rooSlate rooSlate rooSlate rooffff hookhookhookhook Part no.:Part no.:Part no.:Part no.: Z3301017Z3301017Z3301017Z3301017
For attachment on slate roofs.
Stainless steel 1.4301
Bracket cross-section: 35x6 mm
Mounting holes d=9mm
Beaver tail roof hookBeaver tail roof hookBeaver tail roof hookBeaver tail roof hook Part no.:Part no.:Part no.:Part no.: Z3301018Z3301018Z3301018Z3301018
For attachment on plain tile roofs.
Stainless steel 1.4301
Bracket cross-section: 35x6 mm
Mounting holes d=9 mm
Frankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hook Part no.:Part no.:Part no.:Part no.: Z3301002Z3301002Z3301002Z3301002
For attachment on pan roofs for normal static requirements.
Stainless steel 1.4301
Bracket cross-section: 35x6 mm
Baseplate mounting holes d=9 mm
Frankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hook Part no.:Part no.:Part no.:Part no.: Z3301005Z3301005Z3301005Z3301005
For attachment on pan roofs for increased static requirements.
Stainless steel 1.4301
Bracket cross-section: 35x8 mm
Baseplate mounting holes d=9 mm
43
3 – Components of GehrTec® Top
Frankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hook Part no.:Part no.:Part no.:Part no.: Z3301015Z3301015Z3301015Z3301015
For attachment on pan roofs for normal static requirements.
Stainless steel 1.4301
Bracket cross-section: 35x6 mm
Baseplate mounting holes d=9 mm
Adjustable version with extra bracket
Frankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hookFrankfurter Pan roof hook Part no.:Part no.:Part no.:Part no.: Z3301016Z3301016Z3301016Z3301016
For attachment on pan roofs for increased static requirements.
Stainless steel 1.4301
Bracket cross-section: 35x8 mm
Baseplate mounting holes d=9 mm
Adjustable version with extra bracket
Hanger boltsHanger boltsHanger boltsHanger bolts
Hanger bolt M10x200Hanger bolt M10x200Hanger bolt M10x200Hanger bolt M10x200 Part no.:Part no.:Part no.:Part no.: Z340010200Z340010200Z340010200Z340010200
For attachment on the supporting wooden substructure.
Stainless steel 1.4301, size M10x200
Accessories required:
3 x hexagonal nut with M10 flange (part no. Z341510)
1 x M10 adapter plate (part no. Z3310003)
1 x rubber seal (part no. Z3200001)
Also available OPTIONALLY as a pre-assembled set:
1 x hanger bolt set M10x200 (part no. Z340010200S)
Hanger bolt M12x300Hanger bolt M12x300Hanger bolt M12x300Hanger bolt M12x300 Part no.:Part no.:Part no.:Part no.: Z340012300Z340012300Z340012300Z340012300
For attachment on the supporting wooden substructure.
Stainless steel 1.4301, size M12x300
Accessories required:
3 x hexagonal nut with M12 flange (part no. Z3415112)
1 x M12 adapter plate (part no. Z3310004)
1 x rubber seal (part no. Z3200001)
Also available OPTIONALLY as a pre-assembled set:
1 x hanger bolt set M12x300 (part no. Z340012300S)
44
3 – Components of GehrTec® Top
Solar fastenersSolar fastenersSolar fastenersSolar fasteners
Solar faSolar faSolar faSolar fastener / steelstener / steelstener / steelstener / steel Part no.:Part no.:Part no.:Part no.: On requestOn requestOn requestOn request
For attachment to the supporting steel substructure.
Stainless steel 1.4301, Ø 8.0 x L mm
Setscrew: M10 x 50 mm
Already with nuts and EPDM seal
With general building regulation approval
Accessories required:
1 x M10 adapter plate (part no. Z3310003)
Solar fastener / woodSolar fastener / woodSolar fastener / woodSolar fastener / wood Part no.:Part no.:Part no.:Part no.: On requestOn requestOn requestOn request
For attachment on the supporting wooden substructure.
Stainless steel 1.4301, Ø 8.0 x L mm
Setscrew: M10 x 50 mm
Already with nuts and EPDM seal
With general building regulation approval
Accessories required:
1 x M10 adapter plate (part no. Z3310003)
M10 adapter plateM10 adapter plateM10 adapter plateM10 adapter plate Part no.:Part no.:Part no.:Part no.: Z3310003Z3310003Z3310003Z3310003
For attachment of mounting rails on hanger bolt / solar fastener.
Stainless steel 1.4301, size 30 x 80 mm
Round hole: Ø 11 mm
Long hole: 11 x 40 mm
M12 adapter plateM12 adapter plateM12 adapter plateM12 adapter plate Part no.:Part no.:Part no.:Part no.: Z3310004Z3310004Z3310004Z3310004
For attachment of mounting rails on hanger bolt / solar fastener.
Stainless steel 1.4301, size 30 x 80 mm
Round hole: Ø 13 mm
Long hole: 11 x 40 mm
45
3 – Components of GehrTec® Top
Clamp holdersClamp holdersClamp holdersClamp holders
Standing seam clampStanding seam clampStanding seam clampStanding seam clamp ParParParPart no.:t no.:t no.:t no.: Z3330001Z3330001Z3330001Z3330001
For attachment on standing seam roofs.
Aluminium, length 110 mm
Fixed with 2 round-head screws M 8x35 mm
Two long holes: 9x25 mm and 11x25 mm
Rounded seam clampRounded seam clampRounded seam clampRounded seam clamp Part no.:Part no.:Part no.:Part no.: Z3330002Z3330002Z3330002Z3330002
For attachment on round-head profile roofs (Kalzip, BEMO, etc.).
Aluminium, length 110 mm
Fixed with 2 round-head screws M 8x35 mm
Two long holes: 9x25 mm and 11x25 mm
Seam clamp 465/480Seam clamp 465/480Seam clamp 465/480Seam clamp 465/480 Part no.:Part no.:Part no.:Part no.: Z3330003Z3330003Z3330003Z3330003
For attachment on clamped seam profile roofs (RibRoof 465/480,
Domico).
Aluminium, length 110 mm
Fixed with 2 round-head screws M 8x35 mm
Two long holes: 9x25 mm and 11x25 mm
Seam clamp 500Seam clamp 500Seam clamp 500Seam clamp 500 Part no.:Part no.:Part no.:Part no.: Z3330004Z3330004Z3330004Z3330004
For attachment on clamped seam profile roofs (RibRoof 500).
Aluminium, length 110 mm
Fixed with 2 round-head screws M 8x40 mm
Two long holes: 9x25 mm and 11x25 mm
Girder claw Kalzip©Girder claw Kalzip©Girder claw Kalzip©Girder claw Kalzip© Part no.:Part no.:Part no.:Part no.: Z3330008Z3330008Z3330008Z3330008
For attachment on Kalzip profile roofs.
Aluminium, length 60 mm
Attachment screw M 6
One round hole: d = 11 mm
46
3 – Components of GehrTec® Top
TopTopTopTop----TSTSTSTS
Base support 1Base support 1Base support 1Base support 1 Part no.:Part no.:Part no.:Part no.: Z3340013Z3340013Z3340013Z3340013
For elevated mounting of framed solar modules.
Aluminium EN AW6063
Fixed with hammer-headed bolt and flanged hexagonal nut
Also available as pre-assembled set:
1 x pre-assembled base support 1 (type no. Z3340020)
Base support 2Base support 2Base support 2Base support 2----1111 Part no.:Part no.:Part no.:Part no.: Z3340014Z3340014Z3340014Z3340014
For elevated mounting of framed solar modules.
Aluminium EN AW6063
Fixed with hammer-headed bolt and flanged hexagonal nut
Also available as pre-assembled set:
1 x pre-assembled base support 2 (type no. Z3340021)
Base support 2Base support 2Base support 2Base support 2----2222 Part no.:Part no.:Part no.:Part no.: Z3340015Z3340015Z3340015Z3340015
For elevated mounting of framed solar modules.
Aluminium EN AW6063
Screwed joint with base support 2-1 (see part no. Z3340014)
Also available as pre-assembled set:
1 x pre-assembled base support 2 (type no. Z3340021)
TopTopTopTop----TS module clampTS module clampTS module clampTS module clamp Part no.:Part no.:Part no.:Part no.: Z3340016Z3340016Z3340016Z3340016
For attaching framed solar modules.
Aluminium EN AW6063
Frame height from 35 - 50 mm
Accessories required:
1 x M8 Allen key bolt (part no. Z34118xx)
47
3 – Components of GehrTec® Top
Bolts and accessoriesBolts and accessoriesBolts and accessoriesBolts and accessories
Hammerhead bolt M10x20Hammerhead bolt M10x20Hammerhead bolt M10x20Hammerhead bolt M10x20 Part no.:Part no.:Part no.:Part no.: Z34131020Z34131020Z34131020Z34131020
Hammerhead bolt M10x25Hammerhead bolt M10x25Hammerhead bolt M10x25Hammerhead bolt M10x25 ParParParPart no.:t no.:t no.:t no.: Z34131025Z34131025Z34131025Z34131025
Stainless steel 1.4301
Accessories required:
1 x hexagonal nut with M10 flange (part no. Z341510)
Hammerhead nut M8Hammerhead nut M8Hammerhead nut M8Hammerhead nut M8 Part no.:Part no.:Part no.:Part no.: Z34149Z34149Z34149Z34149
Stainless steel 1.4301, size M8
With Clemm-Loc thread lock
Hexagon nut with M10 flangeHexagon nut with M10 flangeHexagon nut with M10 flangeHexagon nut with M10 flange Part no.:Part no.:Part no.:Part no.: Z341510Z341510Z341510Z341510
Stainless steel 1.4301, size M10
To DIN EN 1661 (DIN 6923)
Hexagon nut with M12 flangeHexagon nut with M12 flangeHexagon nut with M12 flangeHexagon nut with M12 flange Part no.:Part no.:Part no.:Part no.: Z3415112Z3415112Z3415112Z3415112
Stainless steel 1.4301, size M12
To DIN EN 1661 (DIN 6923)
Thrust washerThrust washerThrust washerThrust washer Part no.:Part no.:Part no.:Part no.: Z34188Z34188Z34188Z34188
Stainless steel A4, size Ø 8.2 mm
For high-strength joints with normal contact surface
48
3 – Components of GehrTec® Top
Wheel head wood screwWheel head wood screwWheel head wood screwWheel head wood screw Part no.:Part no.:Part no.:Part no.: See Page 16See Page 16See Page 16See Page 16
Stainless steel 1.4301, size Ø 8 mm
With wheel head d=19mm
Drive AW40 / TX40
With building regulation approval
Drilling screw 6.3Drilling screw 6.3Drilling screw 6.3Drilling screw 6.3x25x25x25x25 Part no.:Part no.:Part no.:Part no.: Z34056325Z34056325Z34056325Z34056325
Stainless steel 1.4301, with sealing washer Ø 16 mm
With building regulation approval
Blind rivet 4.8x15Blind rivet 4.8x15Blind rivet 4.8x15Blind rivet 4.8x15 Part no.:Part no.:Part no.:Part no.: Z3430001Z3430001Z3430001Z3430001
Sleeve: Aluminium, pin tap: Stainless steel
With under-head seal
With building regulation approval
Allen screwAllen screwAllen screwAllen screw Part no.:Part no.:Part no.:Part no.: See Page 36See Page 36See Page 36See Page 36
Stainless steel 1.4301, size M8, 5 AF
With cylinder head to DIN 7984
Allen screwAllen screwAllen screwAllen screw Part no.:Part no.:Part no.:Part no.: See Page 36See Page 36See Page 36See Page 36
Stainless steel 1.4301, size M8, 5 AF
With countersunk head to DIN EN ISO 10642 (DIN 7991)
Hexagon bolt with flangeHexagon bolt with flangeHexagon bolt with flangeHexagon bolt with flange Part no.:Part no.:Part no.:Part no.: Z34291030Z34291030Z34291030Z34291030
Stainless steel 1.4301, size M10x30
With flange to DIN EN ISO 1665 (DIN 6921)
49
4 – System statics
4 4 4 4 –––– System staticsSystem staticsSystem staticsSystem statics
The basis for planning and sizing the mounting system is a static type calculation with
tabular summaries of the sizing parameters, from which the constructive installation for the
specific case is carried out.
For the complex task of planning and static sizing of the mounting system, a high degree of
expert knowledge is necessary, for which a structural engineer must be brought in on a
case-by-case basis. Since an individual static calculation would, for small systems, put the
cost-effectiveness of the project into question, we have designed a type calculation in
cooperation with expert planners from the building industry and had it tested by the LGA®
Public Law Corporation Bavaria (Bavarian State Trade Agency). This allows sizing of the
supporting profiles (mounting rails) and connections on the substructure and meets the
demands of the specific structural conditions on site.
For many building projects, especially in the public sector, static calculations for mounting
solar modules are required in individual cases. With the static type calculation from LGA®
Public Law Corporation Bavaria, the building authority is released from its obligation to
examine the calculation once again. This way there is no complex, project-related static
calculation, thereby saving valuable time and financial resources. It does not, however,
release one from the structural-related examination of structural analyses and drawings for
adjacent structural members.
NoteNoteNoteNote!!!! The static type test does not release the constructor from the obligation to obtain a construction permit for each project, as long as the respective building regulations or other legal directives do not basically free him of this obligation.
Static calculations for special applications outside of the type calculation can be performed
on request.
Technical regulations and standardsTechnical regulations and standardsTechnical regulations and standardsTechnical regulations and standards
Our products and the type calculation are based upon valid standards and technical
regulations and therefore comply with recognized rules of technology. This applies to the
selection of materials and for the static type calculation and construction design.
Tab. 21: Technical regulations for materials
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN EN 485-2 2007-07 Aluminium and aluminium alloys – strips, sheets and plates
Part 2: Mechanical properties
DIN EN 573-3 2007-11 Aluminium and aluminium alloys – chemical composition and
form of semi-finished products
Part 3: Chemical composition and product forms
DIN EN 15088 2006-03 Aluminium and aluminium alloys – products for structural
applications
Technical shipping conditions
DIN EN 10088-1 2005-09 Non-rusting steels
Part 1: Register of non-rusting steels
50
4 – System statics
Tab. 21: Technical regulations for materials - continued
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN EN 10088-2 2005-09 Non-rusting steels
Part 2: Technical shipping conditions
DIN EN 10088-3 2005-09 Non-rusting steels
Part 3: Technical shipping conditions
Tab. 22: Technical rules and regulations for nuts and bolts
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN EN ISO 4762 2004-06 Allen head screws with cylindrical head
DIN EN ISO 10642 2004-06 Allen head countersunk screws
DIN EN 1661 1998-02 Hexagon nut with flange
DIN EN 1665 1998-02 Hexagon bolts with flange
DIN 571 1986-12 Hexagon wood screws
Tab. 23: Technical rules and regulations for sizing and constructive implementation
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN 1055-1 2002-06 Effects on building structures
Part 1: Weighting and surface loads of building structures
DIN 1055-3 2006-03 Effects on building structures
Part 3: Dead-weight and payload for building construction
DIN 1055-4 2005-03 Effects on building structures
Part 4: Wind loads + report version 2006-03
DIN 1055-5 2005-07 Effects on building structures
Part 5: Snow and ice loads
DIN 1055-100 2001-03 Effects on building structures
Part 100: Fundamentals of building structure planning – safety
concept and dimensioning rules
DIN 4113-1 1980-05 Aluminium structures primarily under static load
Part 1: Calculation and construction design
DIN 4113-1/A1 2002-09 Aluminium structures primarily under static load
Part 1: Calculation and construction design; modification A1
DIN 18800-1 1990-11 Steel structures
Part 1: Dimensioning and construction
DIN 18800-2 1990-11 Steel structures
Part 2: Bending bars and bar construction
51
4 – System statics
Solar modulesSolar modulesSolar modulesSolar modules
In standards IEC 61215 and IEC 61646 are specifications for an allowed surface load of
2400 Pa (corresponds to 2.40 kN/m² or approx. 240 kg/m²). During a test of the solar
modules, an optional greater test load of 5400 Pa is permitted if it is determined that the
solar module can withstand higher snow and wind loads. This increased test load is not
mandatory however.
Our static type calculation was performed with a threshold of 5400 Pa and so covers all
currently valid applications for solar modules having a valid certificate.
NoteNoteNoteNote!!!! Only solar modules with the following certificates may be used: IEC 61215 or IEC 61646 Protection Class II / IEC 61730
Tab. 24: Technical regulations for solar modules
StandardStandardStandardStandard VersionVersionVersionVersion DescriptionDescriptionDescriptionDescription
DIN EN 61215
(IEC 61215:2005)
2006-02 Terrestrial crystalline silicon photovoltaic (PV) modules
Construction suitability and construction approval
DIN EN 61646
(IEC 61646:2006)
2007-07 Terrestrial thin-film photovoltaic (PV) modules
Construction suitability and construction approval
NoteNoteNoteNote!!!! The maximum test load of the solar modules used (see manufacturer operating instructions) must always be used as the basis for system planning.
52
4 – System statics
Load combinations to DIN 1055Load combinations to DIN 1055Load combinations to DIN 1055Load combinations to DIN 1055----100100100100
The effects of photovoltaic systems on supporting building structures must be determined in
accordance with the relevant technical regulations of the building industry. Since 1 January
2007, the load effects to DIN 1055 Parts 1-5 must be included in the safety concept to DIN
1055-100. Because valuable and sensitive solar modules are installed outside a protective
building and exposed to the elements, integration of loads from wind and snow are vital in
planning a photovoltaic system.
Our mounting system has been designed for a very broad range of applications. The system
can be used in all wind and snow load zones up to elevations of 1000m above sea level.
Tab. 25: Permitted snow and wind load zone combinations for GehrTec© Top
Snow load zone Snow load zone Snow load zone Snow load zone
SLZSLZSLZSLZ
Wind zone Wind zone Wind zone Wind zone
WZWZWZWZ Max. elevationMax. elevationMax. elevationMax. elevation
1 1 or 2 To 765 m above sea level
1 3 To 400 m above sea level
1a 1 or 2 To 765 m above sea level
2 1 or 2 To 1,000 m above sea level
2 3 or 4 To 285 m above sea level
2a 1 or 2 To 1,000 m above sea level
3 1 or 2 To 1,000 m above sea level
3 3 or 4 To 255 m above sea level
Listed in Table 25 are all permitted load combinations to DIN 1055 investigated in our static
calculation and approved for installation parallel to the roof.
Tab. 26: Permitted snow and wind load zone combinations for GehrTec© Top-TS
Snow load zone Snow load zone Snow load zone Snow load zone
SLZSLZSLZSLZ
Wind zone Wind zone Wind zone Wind zone
WZWZWZWZ Max. elevationMax. elevationMax. elevationMax. elevation
1 1 to 3 To 1,000 m above sea level
1a 1 or 2 To 1,000 m above sea level
2 1 to 3 To 770 m above sea level
2a 1 or 2 To 600 m above sea level
3 1 to 3 To 590 m above sea level
Listed in Table 26 are all permitted load combinations to DIN 1055 investigated in our static
calculation and approved for the Top-TS system.
Dead loads to DIN 1055Dead loads to DIN 1055Dead loads to DIN 1055Dead loads to DIN 1055----1111
Because accurate inclusion of bolts and small parts would normally be associated with
unreasonable overhead, they are usually neglected. Please refer to the manufacturer data
sheets for the dead loads of solar modules. The dead loads to be applied are between
g=0.12–0.20 kN/m² depending on element used. Assumed in our static calculations is a dead
load of solar power system and supporting structure of g=0.20 kN/m².
53
4 – System statics
Snow load zones to DIN 1055Snow load zones to DIN 1055Snow load zones to DIN 1055Snow load zones to DIN 1055----5555
DIN 1055 Part 5 applies for determining the snow loads to be applied. In the general
method, the snow load zone (SLZ) for the location of the photovoltaic system is taken from
the snow load zone map of the Federal Republic of Germany (Fig. 56). The elevation above
sea level is also required in addition to the snow load zone.
Fig. 56: Snow load zone map to DIN 1055 Part 5
54
4 – System statics
Wind zones to DIN 1055Wind zones to DIN 1055Wind zones to DIN 1055Wind zones to DIN 1055----4444
DIN 1055 Part 4 applies for determining the wind loads to be applied. The wind zone (WZ)
for the location of the photovoltaic system must be taken from the wind zone map for the
Federal Republic of Germany (Fig. 57).
Fig. 57: Wind zone map to DIN 1055 Part 4
Wind zones are valid for domestic installation under normal conditions and classification by
wind zone and building height. Stronger winds can be expected near the coast and in
exposed areas (summits and plains).
If in any doubt, calling in a planning expert is recommended.
55
DisclaimerDisclaimerDisclaimerDisclaimer
General Terms and Conditions of Gehrlicher Solar AG apply.
The content of these instructions are subject to continual revision and are amended as
required from time to time. Discrepancies may nevertheless occur. We provide no guarantee
for completeness. The most up-to-date version is available in the Internet from our website
at www.gehrlicher.com and through the usual sales channels.
Because Gehrlicher Solar AG has no control over the conditions and methods used for
installation and mounting, or the use and maintenance of photovoltaic components,
Gehrlicher Solar AG explicitly disclaims liability for losses, damages and costs arising as a
result of unprofessional mounting, installation, initial use, usage and maintenance.
Guarantee and liability claims in the event of damage of any kind are excluded if
attributable to one or more of the following causes:
o Transportation damage
o Improper use of the product or non-intended use of the product
o Use of the product in a non-intended environment
o Use of the product whilst failing to comply with relevant legal safety regulations at the
place of installation
o Failure to comply with warning and safety instructions in all documents relevant to the
product
o Use of the product in deficient safety and protective conditions
o Modifications to, or repair of, the product or the software also supplied
o Malfunction of the product due to the effects of connected or adjacent equipment that
are not within legal thresholds
o Emergencies and force majeure
Warranty conditionsWarranty conditionsWarranty conditionsWarranty conditions
The most up-to-date warranty conditions can be downloaded from our website at
(www.gehrlicher.com) and are available in paper form from the usual sales channels.
Should relevant damages occur within the warranty period, please contact the complaints
department at Gehrlicher Solar: [email protected]
56
CCCContactontactontactontact
Munich Munich Munich Munich OOOOffice (ffice (ffice (ffice (AAAAdministration)dministration)dministration)dministration)
Gehrlicher Solar AG
Max-Planck-Str. 3
D–85609 Dornach / Munich
Tel +49 89 420792 – 0
Fax +49 89 420792 – 8540
CCCCoburg oburg oburg oburg OfficeOfficeOfficeOffice ((((HeadquartersHeadquartersHeadquartersHeadquarters))))
Gehrlicher Solar AG
Austraße 101b
D–96465 Neustadt n. Coburg
Tel +49 9568 / 896609 – 0
Fax +49 9568 / 896609 – 999
Board of Directors: Klaus Gehrlicher (CEO)
Chairman of Supervisory Board: Christoph Nadler
Registered office: Neustadt n. Coburg
HR Coburg Dept. B no. 4377, VAT no. DE 202 435 014
www.gehrlicher.com
57
List of tablesList of tablesList of tablesList of tables
Tab. 1: Safety and information symbols ............................................................................................................................. 5
Tab. 2: Risks and measures ......................................................................................................................................................... 6
Tab. 3: Technical rules and regulations for lightning and overvoltage protection............................... 9
Tab. 4: Tools ......................................................................................................................................................................................... 11
Tab. 5: Additions for the individual clamp types ........................................................................................................ 14
Tab. 6: Minimum distances from roof edge ................................................................................................................... 14
Tab. 7: Maximum overall length of mounting rails connected together .................................................... 15
Tab. 8: Overview of wood screws with wheel head .................................................................................................. 17
Tab. 9: Overview of hanger bolts ........................................................................................................................................... 19
Tab. 10: Pre-drilling diameter in mm for profiled tiles and substructure ................................................. 21
Tab. 11: Overview of type Z solar fasteners for steel substructures .......................................................... 22
Tab. 12: Overview of type A solar fasteners for timber substructures ...................................................... 22
Tab. 13: Overview of fastening elements ......................................................................................................................... 23
Tab. 14: Overview of distances in relation to module width ............................................................................. 29
Tab. 15: Overview of the bolts for the Top-TS module clamp (part no. Z3340016) ....................... 31
Tab. 16: Components required to attach a solar module ................................................................................... 31
Tab. 17: Overview of the different clamp holders ..................................................................................................... 32
Tab. 18: Overview of hammerhead nuts and bolts ................................................................................................... 34
Tab. 19: Overview of the bolts for module centre clamp 1 (part no. Z3120001) ............................. 36
Tab. 20: Overview of the bolts for module centre clamp 2 (part no. Z3120010) ............................. 36
Tab. 21: Technical regulations for materials.................................................................................................................. 49
Tab. 22: Technical rules and regulations for nuts and bolts ............................................................................ 50
Tab. 23: Technical rules and regulations for sizing and constructive implementation ................... 50
Tab. 24: Technical regulations for solar modules ..................................................................................................... 51
Tab. 25: Permitted snow and wind load zone combinations for GehrTec© Top ................................ 52
Tab. 26: Permitted snow and wind load zone combinations for GehrTec© Top-TS ........................ 52
58
Revision listRevision listRevision listRevision list
Document: 90320051
RevisionRevisionRevisionRevision DateDateDateDate ChangeChangeChangeChange PagePagePagePage
R1.0 12.08.2009 Initial release All
R1.1 26.07.2010 Application aligned
Attachment bolts for roof hook mounting
Drill hole diameter changed
45 mm module end clamp added
Table of contents added
10
16
23
32
48
R1.2 06.08.2010 System part images aligned 38
R1.3 14.02.2011 GehrTec© Top-TS 24ff
R1.4 28.09.2011 Specific information, item numbers updated
Trapezoidal sheet mounting, Top-TS installation
Logo change
All
59
NotesNotesNotesNotes
60
PublisherPublisherPublisherPublisher
Gehrlicher Solar AG
Max-Planck-Str. 3
D-85609 Dornach / Munich
Editing, desEditing, desEditing, desEditing, design and coordinationign and coordinationign and coordinationign and coordination
Andreas Freyer
IllustrationsIllustrationsIllustrationsIllustrations
Leonhard Büttner Graphic Design
Munich