Instruction manual of SF6 recloser with FTU-R200 control unit 1 ISO 9001 certified Jin Kwang E & C Corp. Instruction Manual & User’s Guide 10 ~ 38 kV Pole Mounted SF 6 Automatic Vacuum Reclosers with control unit(FTU-R200) JIN KWANG E&C CORPORATION

User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Embed Size (px)

Citation preview

Page 1: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 1

ISO 9001 certified Jin Kwang E & C Corp.

Instruction Manual & User’s Guide

10 ~ 38 kV Pole Mounted SF6 Automatic

Vacuum Reclosers with control unit(FTU-R200)

JIN KWANG E&C CORPORATION

Page 2: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 2

ISO 9001 certified Jin Kwang E & C Corp.

CONTENTS

1. SAFETY INFORMATION ............................................................................................................................................................................... 8

1.1 Safety for Life ..................................................................................................................................................................................... 8

1.2 Safety Information ........................................................................................................................................................................... 8

1.3 Safety Instruction.............................................................................................................................................................................. 8

2. GENERAL INFORMATION ....................................................................................................................................................................... 10

2.1 Instruction ......................................................................................................................................................................................... 10

2.2 Read this Manual First ................................................................................................................................................................ 10

2.3 Additional Information ............................................................................................................................................................... 10

2.4 Applied Standards......................................................................................................................................................................... 10

2.5 Quality Standards .......................................................................................................................................................................... 10

2.6 Acceptance and Initial Inspection ......................................................................................................................................... 10

2.7 Handling and Storage ................................................................................................................................................................. 10

2.8 Description........................................................................................................................................................................................ 10

3. RATING & SPECIFICATIONS................................................................................................................................................................... 12

4. CONSTRUCTION ......................................................................................................................................................................................... 13

4.1 Tank...................................................................................................................................................................................................... 14

4.2 Switching module ......................................................................................................................................................................... 14

4.2.2 Vacuum interrupters....................................................................................................................................................... 15

4.2.3 Operation of switching modules ............................................................................................................................. 15

4.3 Current transformers ................................................................................................................................................................... 18

4.4 Bushings ............................................................................................................................................................................................. 18

4.5 Universal clamp terminal ........................................................................................................................................................... 18

4.6 Grounding connector .................................................................................................................................................................. 18

4.7 Manual Operating and Lock Handle ................................................................................................................................... 18

4.8 Safety locking device ................................................................................................................................................................... 18

4.9 Pressure release device .............................................................................................................................................................. 18

4.10 Counter ............................................................................................................................................................................................ 19

4.11 Position Indicator(ON / OFF) ................................................................................................................................................ 19

4.12 Gas Filling Valve .......................................................................................................................................................................... 19

5. INSTALLATION PROCEDURE.................................................................................................................................................................. 20

5.1 General ............................................................................................................................................................................................... 20

5.2 Checking items prior to installation ..................................................................................................................................... 20

Page 3: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 3

ISO 9001 certified Jin Kwang E & C Corp.

5.3 Installation procedure ................................................................................................................................................................. 22

5.3.1 Mount the recloser ......................................................................................................................................................... 22

5.3.2 Ground the recloser ....................................................................................................................................................... 23

5.3.3 Install the control ............................................................................................................................................................ 26

5.3.4 Ground the control ......................................................................................................................................................... 26

5.3.5 Make the high-voltage line connections. ............................................................................................................ 26

5.4 After installation, checking items .......................................................................................................................................... 27

5.5 Place the recloser in Service .................................................................................................................................................... 27

5.6 Remove the recloser from Service ........................................................................................................................................ 28

6. RECLOER OPERATION .............................................................................................................................................................................. 29

6.1 Closing Operation ......................................................................................................................................................................... 29

6.2 Opening Operation ...................................................................................................................................................................... 29

6.3 Lock Operation ............................................................................................................................................................................... 30

7. MAINTENANCE ............................................................................................................................................................................................ 31

7.1 General ............................................................................................................................................................................................... 31

7.2 Frequency of maintenance ....................................................................................................................................................... 31

7.3 Check the operation of low pressure indicator ............................................................................................................. 31

7.4 Check the recloser visually ....................................................................................................................................................... 31

FTU-R200 CONTROL UNIT .......................................................................................................................................................................... 32

8. OVERVIEW...................................................................................................................................................................................................... 32

8.1 PROTECTION OF DISTRIBUTION LINE ................................................................................................................................ 32

8.2 FUNCTION OF AUTOMATIC CIRCUIT RECLOSER .......................................................................................................... 32

8.3 MAIN FEATURES OF FTU - R200 ........................................................................................................................................... 33

9. TECHNICAL DATA ....................................................................................................................................................................................... 36

9.1 DIGITAL PROCESSOR ................................................................................................................................................................... 36

9.1.1 Dual Processor Architecture ....................................................................................................................................... 36

9.1.2 Analog/Digital Conversion .......................................................................................................................................... 36

9.1.3 DSP ......................................................................................................................................................................................... 37

9.1.4 CPU ......................................................................................................................................................................................... 37

9.1.4 Functional Block Diagram ........................................................................................................................................... 37

9.2 ENVIRONMENTAL CONDITIONS ........................................................................................................................................... 38

9.3 INPUTS/OUTPUTS ......................................................................................................................................................................... 39

9.4 MEASUREMENT .............................................................................................................................................................................. 41

9.4.1 CURRENT ............................................................................................................................................................................. 41

Page 4: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 4

ISO 9001 certified Jin Kwang E & C Corp.

9.4.2 VOLTAGE .............................................................................................................................................................................. 42

9.4.3 POWER.................................................................................................................................................................................. 42

9.4.4 POWER FACTOR ............................................................................................................................................................... 42

9.4.5 FREQUENCY ....................................................................................................................................................................... 42

9.4.6 ENERGY ................................................................................................................................................................................ 43

9.4.7 HARMONIC......................................................................................................................................................................... 43

9.4.8. DEMAND CURRENT AND POWER ......................................................................................................................... 43

9.5 COMMUNICATION ....................................................................................................................................................................... 43

9.5.1 PHYSICAL LAYER .............................................................................................................................................................. 43

9.5.2 PROTOCOL FOR SCADA ............................................................................................................................................... 44

9.6 RECORDING ..................................................................................................................................................................................... 45

9.6.1 EVENT RECORDER ........................................................................................................................................................... 45

9.6.2 WAVEFORM EVENT RECORDER................................................................................................................................ 45

10. CONSTRUCTION AND EXTERNAL CONNECTION .................................................................................................................... 47

10.1 APPEARANCE & DIMENSION ............................................................................................................................................... 47

10.2 CONNECTOR ................................................................................................................................................................................. 49

11. FRONT PANEL OPERATION ................................................................................................................................................................. 50

11.1 BUTTON & LED DESCRIPTION.................................................................................................................................. 51

11.1.1 LCD DISPLAY ................................................................................................................................................................... 51

11.1.2 FTU STATUS...................................................................................................................................................................... 51

11.1.3 MENU/UP/DOWN/ENTER BUTTONS ................................................................................................................... 51

11.1.4 SERIAL PORT ................................................................................................................................................................... 51

11.1.5 ETHERNET/SCADA/PROTECTION COMMUNICATION LED ....................................................................... 51

11.1.6 BATTERY TEST & LAMP TEST .................................................................................................................................. 52

11.1.7 RESET BUTTON............................................................................................................................................................... 52

11.1.8 FUNCTION LED .............................................................................................................................................................. 52

11.1.9 RECLOSE/PROTECTION/GROUND ENABLE BUTTONS AND LEDS ........................................................ 53

11.1.10 REMOTE/CONTROL LOCK BUTTON AND LEDS ........................................................................................... 53

11.1.11 SELECT/OPEN/CLOSE BUTTONS AND LEDS ................................................................................................. 53

11.2.LCD MANIPULATION ................................................................................................................................................................. 54

11.2.1 LCD MENU ....................................................................................................................................................................... 55

13. PROTECTION FUNCTIONS ................................................................................................................................................................... 60

13.1 FAULT DETECTION ................................................................................................................................................................................ 60

13.1.1 DEFINITE TIME PROTECTION .......................................................................................................................... 62

Page 5: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 5

ISO 9001 certified Jin Kwang E & C Corp.

13.1.2 HIGH CURRENT TRIP (HCT) ............................................................................................................................. 62

13.1.3 SINGLE SHOT OPERATION ................................................................................................................................ 63

13.1.4 TC CURVE ...................................................................................................................................................................... 63

13.1.5 EXAMPLE OF TC CURVE EDITING.............................................................................................................. 65

13.1.6 AUTO RECLOSING SEQUENCE ........................................................................................................................ 66

13.1.7 SEQUENCE COODINATION ............................................................................................................................... 68

13.2 COLD LOAD PICKUP ............................................................................................................................................................ 69

13.3 SENSITIVE EARTH FAULT(SEF) DETECTION .................................................................................................................... 71

13.4 DIRECTIONAL BLOCKING .............................................................................................................................................. 72

13.5 INRUSH RESTRAINTS ................................................................................................................................................................ 73

13.6 OPEN LINE DETECTION(LOSS OF PHASE) ...................................................................................................................... 73

13.7 PHASE SYNC. CHECK ................................................................................................................................................................ 74

13.8 UNDER VOLTAGE PROTECTION .......................................................................................................................................... 74

13.9 OVER VOLTAGE PROTECTION ................................................................................................................................... 75

13.10 UNDER FREQUENCY PROTECTION ................................................................................................................................. 76

13.11 MULTIPLE PROTECTION GROUPS .................................................................................................................................... 76

14. CONFIGURATION SETTINGS ............................................................................................................................................................... 77

14.1 I/O CONFIGURATION ............................................................................................................................................................... 77

14.1.1 AC RATINGS ..................................................................................................................................................................... 77

14.1.2 SWITCH INSTALLATION ....................................................................................................................................... 77

14.1.3 DEMAND SETTING ....................................................................................................................................................... 80

14.1.4 WAVE TRIGGER .............................................................................................................................................................. 80

14.1.5 CLOSE INTERLOCK ........................................................................................................................................................ 80

14.1.6 FI RESET SELECT ............................................................................................................................................................ 80

14.1.7 VOLTAGE DISPLAY ........................................................................................................................................................ 81

14.2 POWER QUALITY MEASUREMENT FUNCTION ....................................................................................................................... 81

14.2.1 VOLTAGE & CURRENT UNBALANCE ................................................................................................................... 81

14.2.2 SHORT-DURATION VOLTAGE VARIATION ......................................................................................................... 81

14.2.2.2 SWELL.............................................................................................................................................................................. 82

14.2.3 VOLTAGE & CURRENT ALARM ............................................................................................................................... 83

14.3 COMMUNICATION ..................................................................................................................................................................... 84

14.3.1 PORT PARAMETERS...................................................................................................................................................... 84

14.3.2 DNP 3.0 PARAMETERS................................................................................................................................................ 85

14.3.3 IEC PARAMETERS .................................................................................................................................................. 86

Page 6: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 6

ISO 9001 certified Jin Kwang E & C Corp.

15. STATUS MONITORING & CONTROL............................................................................................................................................... 87

15.1 SWITHCH CONTROL ................................................................................................................................................................. 87

15.2 SWITCH STATUS MONITORING .......................................................................................................................................... 87

15.3 BATTERY MONITORING ........................................................................................................................................................... 87

16. MEASUREMENT ........................................................................................................................................................................................ 88

16.1 BASIC ELECTRIC QUANTITIES ............................................................................................................................................... 88

16.2 SEQUENCE COMPONENTS .................................................................................................................................................... 88

16.3 HARMONICS ................................................................................................................................................................................. 89

16.4 ENERGY ............................................................................................................................................................................................ 89

16.5 DEMAND CURRENTS AND POWER ................................................................................................................................... 89

17. MAINTENANCE SOFTWARE ................................................................................................................................................................ 90

17.1 OVERVIEW ...................................................................................................................................................................................... 90

17.2 OPERATION OF FTUMan......................................................................................................................................................... 91

17.2.1 MENU ................................................................................................................................................................................. 91

17.2.2 TOOLBAR........................................................................................................................................................................... 93

17.2.3 STATUS BAR .............................................................................................................................................................. 94

17.2.4 MONITORING BAR ....................................................................................................................................................... 94

17.2.5 FUNCTION AND CONFIGURATION SETTING .................................................................................................. 94

17.2.6 EVENT ................................................................................................................................................................................. 96

17.2.7 MEASUREMENT ........................................................................................................................................................... 105

17.2.8 STATUS ........................................................................................................................................................................ 111

17.2.9 WAVEFORM ................................................................................................................................................................... 112

18. I/O CONFIGURATION TOOL ............................................................................................................................................................. 114

18.1 OVERVIEW .................................................................................................................................................................................... 114

18.2 OPERATION OF IOConfig ............................................................................................................................................. 115

18.2.1 MENU ............................................................................................................................................................................... 116

18.2.2 TOOLBAR......................................................................................................................................................................... 116

18.2.3 INPUT ................................................................................................................................................................................ 117

18.2.4 OUTPUT ........................................................................................................................................................................... 118

19. DNP 3.0 INDEX CONFIGURATION TOOL.................................................................................................................................... 119

19.1 OVERVIEW .................................................................................................................................................................................... 119

19.2 OPERATION OF DNPCONFIG. ............................................................................................................................................ 120

19.2.1 MENU ............................................................................................................................................................................... 121

19.2.2 TOOLBAR ................................................................................................................................................................... 121

Page 7: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 7

ISO 9001 certified Jin Kwang E & C Corp.

19.2.3 CONFIGURATION TOOL BOX ..................................................................................................................... 122

19.2.4 BINARY INPUT....................................................................................................................................................... 123

19.2.5 BINARY OUTPUT .................................................................................................................................................. 125

19.2.6 ANALOG INPUT ........................................................................................................................................................... 126

19.2.7 COUNTER .................................................................................................................................................................. 127

20. WAVEFORM EVALUATION TOOL .................................................................................................................................................... 129

20.1 OVERVIEW .................................................................................................................................................................................... 129

20.2 OPERATION OF EvalTool....................................................................................................................................................... 130

20.2.1 MENU ............................................................................................................................................................................... 130

20.2.2 TOOLBAR......................................................................................................................................................................... 132

APPENDIX 1.TC (Time-Current) Characteristic Curves ................................................................................................................. 133

APPENDIX 2. DNP3.0 PROTOCOL OBJECT & INDEX TABLE...................................................................................................... 146

APPENDIX 3. IEC 60870-5-101 PROTOCOL OBJECT & INDEX TABLE .................................................................................. 171

Page 8: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 8

ISO 9001 certified Jin Kwang E & C Corp.

1. SAFETY INFORMATION

1.1 Safety for Life

Jinkwang’s products meet or exceed all applicable industry standards relating to product safety. We

actively promote safe practices in the use and maintenance of our products through our technical

information, instructional training programs, and the continuous efforts of all Jinkwang employees

involved in product design, manufacture, marketing and service

1.2 Safety Information

The instructions in this manual are not intended as a substitute for proper training or adequate

experience in the safe operation of the recloser described. Only authorized technicians who are familiar

with this recloser should install, operate and service it.

Following is important safety information. For safe installation and operation of the recloser, be sure to

read carefully and understand fully followings. Additional statements, related to specific matters and

procedures, can be observed throughout this manual.

This manual may contain four types of hazard statements:

Danger : Indicates an imminently hazardous situation which, if not avoided, will result in serious injury.

Warning : Indicates a potentially hazardous situation which, if not avoided, could result in serious injury.

Caution : Indicates a potentially hazardous situation which, if not avoided, may result in minor or

moderate injury or equipment damage.

1.3 Safety Instruction

Following are general cautions and warning statements that apply to this recloser.

Danger :

Follow all locally approved safety procedures when working around high voltage lines and equipment.

Contact with hazardous voltage will cause severe personal injury.

Warning :

This equipment is not intended to protect human life. Follow all locally approved procedures and safety

practices when installing or operating this equipment. Failure to comply can result in severe personal

injury and equipment damage.

The recloser must be selected for the intended application. It must be installed and serviced by proper

personal who have been trained and understand proper safety procedures. This instructions are written

for such personal and are not a substitute for adequate training and experience in safety procedures.

Page 9: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 9

ISO 9001 certified Jin Kwang E & C Corp.

Failure to properly select, install, or maintain this recloser can result in severe personal injury.

Before installing, operating, maintaining or testing this recloser, carefully read and understand the

contents of this manual. Improper operation, handling or maintenance may result in severe personal

injury, and damage to the recloser.

Page 10: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 10

ISO 9001 certified Jin Kwang E & C Corp.

2. GENERAL INFORMATION

2.1 Instruction

This manual provides installation, operation and maintenance instructions for the JK-REC Type

electronically controlled recloser.

Before installing and operating this recloser, carefully read and understand the contents of this

manual.

2.2 Read this Manual First

Read and understand the contents of this manual and follow all locally approved procedures and safety

practices before installing and operating this recloser.

2.3 Additional Information

This manual cannot cover all details or variations in the recloser, procedures or process described, nor

provides directions for meeting every possible contingency during installation, operation or maintenance.

When additional information is desired to satisfy a problem not covered sufficiently for the user’s

purpose, please contact your Jin Kwang sales representative.

2.4 Applied Standards

The recloser is designed, manufactured and tested in accordance with ANSI C37.60, ANSI C37.71, ANSI

C37.73, ANSI C37.85, IEC 60255-5, IEEE C62.41(1991), ANSI/IEEE C37.90.1(1989), IEEE C37.90.2(1995).

2.5 Quality Standards

The recloser shall be manufactured according to ISO9001(1994) quality control system.

2.6 Acceptance and Initial Inspection

The recloser is completely assembled, tested, and inspected at the factory. It is good condition when

accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs for damage.

Unpack the recloser and inspect it thoroughly for damage incurred during shipment. If damage is

discovered, file a claim with carrier immediately.

2.7 Handling and Storage

Be careful during handling and storage of the recloser to minimize the possibility of damage. In

particular, protect the porcelain bushing in handling.

Only use the lifting lug when lifting the recloser. If the recloser is to be stored for any length of time

prior to installation, provide a clean, dry storage area.

2.8 Description

New demands for managing distribution systems call for control devices inherently reliable and

Page 11: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 11

ISO 9001 certified Jin Kwang E & C Corp.

intelligent. Customers require a built-in capability for data gathering and communication, along with an

extremely low maintenance product.

The Jinkwang electronically controlled, three phase automatic recloser (hereinafter referred to as “the

recloser”) provides reliable and economical over-current protection for distribution circuit, ranging from

15 through 38kV.

The recloser senses line current and automatically interrupts the phase of the distribution circuit to

which it is connected when line current exceeds the minimum trip level. Next, it automatically recloses to

restore ser-vice and monitors the line to determine if the fault has been cleared. If the fault is

permanent, the recloser sequences to lockout after one, two, three, or four preset trip operations

Once the recloser sequences to lockout, the recloser must be manually reset to restore service.

Should the fault clear before lockout, the recloser will reset automatically for another sequence of

operations. The recloser can also be set for non-reclosing operation (lock out after the first trip

operation) The recloser can be remotely set for non-reclosing operation via the remote non-reclosing

feature. The trip operations of the recloser can be all fast, all delayed, or any combination of fast

operations and delayed operations up to a maximum total of four. Fast operations clear temporary faults

before branch line fuses are weakened. Delayed operations allow time for fuses or other downline

protective devices to clear to limit permanent faults to the smallest section of line.

The Jinkwang type JK-REC recloser has a characteristic as followings.

1) The recloser meets actively in distribution line protection coordination that change variously by

control technology that use microprocessor, and are being operated locally or remotely.

2) Communication protocols to DAS make the automated protection coordination possible.

3) The control has a total of 48 built-in T-C curves, and a T-C curve, which has a time multiplier and a

minimum response time applied to the fundamental curve and a high current lockout characteristic,

allows programming via keypad or RS232 communication port on the front of control panel.

4) Fault recording for analysis can be backed up using LCD display or handheld controller applying

gradually fault recording that need in the maintenance on the distribution lines.

5) All operating parameters and settings are easily programmable via handheld controller or PC using

RS-232 port on the front panel.

6) The control is equipped with the function of sequence coordination to prevent unnecessary operation

of the upstream reclosers when two or more reclosers are being operated in series.

Page 12: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 12

ISO 9001 certified Jin Kwang E & C Corp.

3. RATING & SPECIFICATIONS

No. Description Unit Specifications

1 Type JK-REC

2 Insulation SF6

3 Ratings

Maximum System Voltage

Rated Current

Rated Frequency

Mechanical Operation(Min.)

Rated Gas Pressure at 20°C

kV

A

Hz

C-O

kg/cm2.G

15

630

50/60

10,000

0.5

27

630

50/60

10,000

0.5

38

630/800

50/60

10,000

0.5

4 Breaking Capacity

Rated symmetrical interrupting current

Short Time Withstand Current(1sec)

Making Current(peak)

Cable Charging

Transformer Magnetizing

A

kA

kA

A

A

12.5

12.5

32.5

5

22

12.5

12.5

32.5

5

22

12.5/16

12.5/16

32.5/40

5

40

5 Impulse Insulation Level(1.2×50ms) kV 110 150 170

6 Power Frequency Insulation Level, dry kV 50 60 70

7 Creepage length of silicon bushings mm Min.830 Min.1090

8 Power Supply

Operation

Control Circuit

V

V

AC 220

DC 24

9 Environmental

Ambient Temperature

Humidity

°C

%

m

-30 ~ + 70

0 ~ 100

10 Net Weight(Switch Body/ Control

Cabinet) kg 195/60 300/60

11 Applied standard ANSI C37.60

Page 13: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 13

ISO 9001 certified Jin Kwang E & C Corp.

4. CONSTRUCTION

The recloser shall consist of a mechanism housing including magnetic actuator and vacuum interrupter,

and controller. The vacuum interrupter provides greatly enhanced long contact life.

The vacuum interrupters are installed into tank that is made of stainless steel. The lightweight and

portable gas insulation effectively reduces installation costs.

1. Grounding terminal

2. Control receptacles(37 pins)

3. Name plate

4. Silicon rubber bushing

5. Manual OPEN handle

6. ON/OFF position indicator

7. Operation counter

12. Universal clamp terminal

10. Gas filling valve

Page 14: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 14

ISO 9001 certified Jin Kwang E & C Corp.

4.1 Tank

The tank of the recloser is fabricated from cold rolled steel and plate. The material used is 304L stainless

steel (SF6 Gas insulated type only)and the design thickness is a minimum 3㎜.

4.2 Switching module

In contrast to the majority of conventional circuit breakers, this patented design incorporates three

independent magnetic actuators: one per pole. This minimizes the number of moving parts, all of

which are symmetrical about the central synchronization of the poles operation.

The vacuum interrupter and the magnetic actuator are located at opposite ends of a hollow support

insulator. The actuator armature is rigidly coupled to the vacuum interrupter moving contact by a linear

drive insulator within the support insulator. This provides direct linear movement in both directions and

avoids the use of rotating shafts, bearings and bell cranks.

The result is a maintenance free switch module with a long trouble free mechanical life.

The actuators are situated inside the frame. A synchronizing shaft connects the three poles and

performs three functions:

▪- synchronization of the poles operation

▪- control of the auxiliary switches

▪- link-motion drive of mechanical interlocks.

8. Lifting lug

9. Gas pressure release device

11. Mechanism box

Page 15: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 15

ISO 9001 certified Jin Kwang E & C Corp.

4.2.1 Magnetic actuator

The actuator is held in its two end positions without the use of mechanical latches. in the OPEN position

the armature is held by the opening spring. in the CLOSED position the armature is held by magnetic

flux produced by a ring permanent magnet.

This actuator has only one coil. To close and trip the actuator it is necessary to inject current into the

coil in different directions.

4.2.2 Vacuum interrupters

As soon as the vacuum interrupter contacts open, the interrupting current initiates a so-called

“vacuum arc” that burns essentially in plasma originating from evaporated contact material.

The current continues to flow through this plasma until a current zero. At this moment the arc is

extinguished and transient recovery voltage appears across the open gap.

If the contact surface is locally overheated it produces a lot of vapor, resulting in the deterioration of

the vacuum followed by electrical breakdown. To avoid this, effective control of the vacuum arc is

necessary.

The most effective way to achieve this goal is to apply an axial magnetic field produced by the

interrupting current itself. This method is implemented in vacuum interrupters developed.

Several major benefits result from this design:

▪ High interrupting capacity

▪ Very compact dimensions

▪ Low chopping current (45 amps) This limits inductive switching overvoltage to safe values.

▪ Axial magnetic field minimizes contact erosion and ensures a very long and reliable life.

4.2.3 Operation of switching modules

Closing

In the OPEN position the vacuum interrupter contacts are held open by the force of the

opening spring in the actuator acting through the drive insulator.

To close the vacuum interrupter contacts a current pulse, derived from the closing capacitor in

the control module, is injected into the actuator coil.

▪ The current in the coil produces a magnetic flux in the gap between the upper yoke and the

actuator armature.

▪ Rising coil current increases the magnetic flux and the electromagnetic attraction between yoke

and armature increases to overcome the restraining force of the opening spring. (Line1)

Page 16: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 16

ISO 9001 certified Jin Kwang E & C Corp.

▪ The armature, drive insulator and moving contact start to move.

▪ As the armature moves towards the upper yoke the magnetic air gap decreases and consequently

the magnetic attraction force increases. This increasing force accelerates the armature, drive

insulator and moving contact to a closing speed of 1 m/s. This optimum speed ensures a complete

absence of contact bounce and reduces the probability of pre-strikes of the vacuum gap before the

contacts close. (Line 2)

▪The accelerating armature also generates a back emf in the coil and reduces the coil current (Line 1-

2)

At contact close (Line 2) the moving contact stops but the armature travel continues for 2mm

under rapid deceleration caused by compressing the contact pressure spring.

▪ At the limit of its travel the armature latches magnetically to the upper yoke. (Line 2a) The moving

armature induced back emf collapses and the coil current again increases (Line 2a-3)

saturating the ring magnet.

This saturation increases the power of the ring permanent magnet to a level that generates flux

to hold the armature in the CLOSED position after the coil current has been cut off by an

auxiliary switch. ( Line 3) Testing has proved that this flux is sufficient to hold the actuator

CLOSED even under vibration and impact conditions.

▪The travel of the armature also compresses the opening spring in preparation for the next opening

operation.

▪The synchronizing shaft is also driven through 44°of rotation during the closing operation and

provides position indication, auxiliary switch operation and mechanical interlocking actions.

Opening

▪To open the interrupter a current of opposite polarity, derived from the opening capacitor in the

control module, is passed through the coil for 1520 milliseconds. (Line 4-5)

▪This current partially demagnetizes the ring magnet and reduces the magnetic holding force on

the armature.

Opposing forces from the charged opening spring and the contact pressure spring cause the

armature to release and accelerate rapidly. After 2 mm of free travel it engages with the drive

insulator and thus the moving contact.

Page 17: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 17

ISO 9001 certified Jin Kwang E & C Corp.

▪The peak force produced by the armature at this point exceeds 2000 N which ensures easy

breaking of any micro-welds at the contact surfaces which can appear due to short circuit

current action.

▪The moving contact accelerates rapidly ensuring a high interrupting capacity. (Line 5)

▪At full travel (Line 6) the armature, drive insulator, moving contact assembly is again held open by

the opening spring force.

▪The synchronizing shaft is also driven through 44° of rotation during the opening operation and

provides position indication, auxiliary switch operation and mechanical interlocking actions.

Manual closing

Closing can only be carried out through the control module.

Manual opening

The module may be manually opened.

By rotating the synchronizing shaft a force exceeding the magnetic attraction forces of the ring magnet

is applied to the armature, which then starts to move.

As the air-gap increases the opening spring and contact pressure spring over come any magnetic

holding force and the interrupter opens.

Auxiliary switches

All switching modules are equipped with thirteen auxiliary switches, six normally open (NO) and seven

normally closed (NC). Auxiliary switches are operated by cam that is fitted on the synchronizing shaft.

One NC auxiliary switch is used for interconnection with the control module. All others are available

for external use.

Auxiliary switches ratings are shown in the table below.

Parameters Value

Type VANCT8AC1

Rated Current

at 250 V AC

Active load

Inductive load

at 30 V DC

Active load

Inductive load

at 125 V DC

Active load

Inductive load

5 A

2 A

5 A

3 A

0.5 A

0.03 A

Page 18: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 18

ISO 9001 certified Jin Kwang E & C Corp.

4.3 Current transformers

The reclosers have a 1000:1 ratio current-sensing transformer. Current transformers shall be mounted

inside the recloser with secondary pre-wired to the controller prior to shipment. The recloser shall

include 3 CT’s, 1 per phase, with sufficient accuracy to operate the controls and designed functions

within tolerances ±1% at rated current. A solid-state CT protector circuit, inside the recloser tank,

ahead of the cable disconnect, is connected to the current transformer

4.4 Bushings

The bushings are constructed of high quality silicon rubber and resistant to moisture, external shock,

and thermo-cycling. The bushings also provide leakage resistance and the high dielectric strength

required for operation of the recloser in pollution contaminated environments.

4.5 Universal clamp terminal

The universal clamp to accommodate 12 ~ 20 mm diameter of conductor is provided for high voltage

connection.

4.6 Grounding connector

The ground connector is provided complete with stainless steel bolt, nut and spring washer for

connecting a 5 ~ 15 mm diameter of conductors.

4.7 Manual Operating and Lock Handle

The manual operating and lock handle is mounted on the side of main body and is operated by hot

stick to enable to be manually opened and lockout.

If you operate the recloser with electric control, the lock handle should be manually returned by hot

stick and placed at normal position.

4.8 Safety locking device

The recloser utilizes gas as the insulation medium. Normal gas pressure at the time of manufacture is

0.5㎏.f/㎠.G. The safety locking device prevents operation of the recloser, electrically from the local

control panel and remote position during low gas pressure condition(i.e. when internal gas pressure

drops to 0.1∼0.2㎏.f/㎠.G), by locking the recloser in its current state.

4.9 Pressure release device

The recloser has a pressure release device (or safety membrane) to release the pressure inside of the

recloser when internal pressure rise to 2.0∼4.0㎏f/㎠.G due to an abnormal condition.

The pressure release device is located on the opposite side to the manual operating and lock handle.

Discharge is vented away from the direction of the operator.

Page 19: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 19

ISO 9001 certified Jin Kwang E & C Corp.

4.10 Counter

The five-digit mechanical operations counter, which records all trip operations, is located at the

bottom of the mechanism box.

4.11 Position Indicator(ON / OFF)

Position indicator flag is coupled to the recloser mechanism to show the position of the main contacts.

When the flag displays Green color , the main contacts are open; When the flag displays Red color, the

main contacts are closed.

4.12 Gas Filling Valve

This Valve is mounted on the side of the recloser tank and “CARE” must be paid not to be opened

with protection cap for preventing the gas leakage on the filling valve.

Page 20: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 20

ISO 9001 certified Jin Kwang E & C Corp.

5. INSTALLATION PROCEDURE

Warning

1. Always use a hot-stick when working with this recloser . Failure to do so could result in contact

with high voltage, which will cause severe personal injury.

2. Solidly ground all equipment. Failure to comply could result in severe personal injury or

equipment damage.

Caution

1. Follow all locally approved safety practices when lifting and mounting the recloser. Use the

lifting lugs provided. Lift the recloser unit smoothly and do not allow it to shift. Improper

lifting can result in it’s damage.

2. Do not connect this control to an energized recloser until all control settings have been

properly programmed and verified. Refer to the programming information for this control.

Failure to comply can result in control and recloser misoperation, equipment damage, and

personal injury.

3. Bushings have sharp edges. Wear protective gloves when handling the unit. Failure to do so

can results in cuts and abrasions.

4. Do not adjust or rotate bushing terminals. The bushing terminals are factory-calibrated to meet

the continuous current requirement of the recloser. Adjusting or rotating the bushing terminals

can damage the encapsulated interrupter resulting in equipment damage or personal injury.

5.1 General

All reclosers are carefully tested and adjusted at the factory to operate according to published data.

Well-equipped test facilities, detailed testing procedures, and thoroughly trained personnel assure

accurately calibrated equipment. Each recloser leaves the factory ready for installation.

5.2 Checking items prior to installation

1) Check bushing’s crack and high voltage line connection(bushing terminal).,

2) Check ratings on the nameplate.

Making sure the ratings and settings on the recloser nameplate are correct for the planned

installation.

Page 21: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 21

ISO 9001 certified Jin Kwang E & C Corp.

3) Check operation of the switch.

Connect control and recloser using the control cable. Connect the control battery Perform several

closing/opening pushing close/open buttons and confirm recloser operation via position indicator. The

five-digit operations counter should count one operation.

4) Check it thoroughly for damage incurred during storage.

Perform high-potential withstand tests. Prior to installing the recloser, perform high potential

withstand tests. This test will help discover any shipping damage affecting the dielectric condition of

the recloser or the vacuum integrity of the interrupter.

5) Low Gas Pressure(SF6 Gas insulated type only)

This recloser is filled with 0.5㎏.f/㎠.G. A low pressure LED on the control panel is illuminates when

internal gas pressure drops to 0.1∼0.2㎏.f/㎠.G. Make sure a low pressure LED to the connection

condition of the main body and control cabinet

6) Make sure a flash of all lamp status indicators to perform a front-panel lamp test in the control

cabinet.

7) Make sure a mounting condition of the control cabinet’s components such as a batteries, power

transformer for power supply, etc.

8) Program the control.

FTU-R200 controls are carefully tested at the factory, shipped and ready for operation. Inspect the

control and make sure that all TCC program settings are correct for the planned installation.

Connect control battery to the battery plug.

Note: The unit should not be stored or shipped with the batteries connected. Even if the recloser is not

in service, connected batteries will still expend energy. Disconnect the batteries when the recloser

is not in service. Make sure that the control cable is connected between the recloser and control.

Page 22: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 22

ISO 9001 certified Jin Kwang E & C Corp.

5.3 Installation procedure

5.3.1 Mount the recloser(Single pole mounting)

Assembly the mounting frames and then assembly the mounting frames and the recloser.

Lift the recloser to the pole with suitable lifting ropes and fix the recloser to the pole with hanger bands.

When lifting the recloser, use the lifting lugs located on the top of the tank and follow approved

procedure. At this point, the contacts are opens. Never use its porcelain bushing, bushing terminals nor

manual trip handle. These handling will cause the damage to the recloser.

The following figure shows Jinkwang’s mounting frames.

The assembly method of mounting frames as follows

Mounting frames 4 Hex bolt, nut, Spring

washer, Plate washer

1

1 Hanger band “B” 11

1 Hanger band “A” 10

2 Vertical bracket 9

2 Bracket support 8

2 Vertical bracket 7

1 Lower band 6

1 Upper band 5

20 Hex bolt, nut, Spring

washer, Plate washer

4

4 Hex bolt, nut, Spring

washer, Plate washer

3

4 Stud washer 2

Q’ty Description No

Page 23: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 23

ISO 9001 certified Jin Kwang E & C Corp.

5.3.2 Ground the recloser

Refer to our typical mounting arrangement as shown in figure.

Make ground connections to the recloser ground connector located on the side of the recloser. It will

accommodate 5 ~ 15 mm diameter ground conductor. Make ground connections in accordance with

approved utility standards.

The following figure shows typical pole type mounting arrangement of the recloser.

(Typical pole type mounting arrangement )

Page 24: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 24

ISO 9001 certified Jin Kwang E & C Corp.

l H Pole mounting

Page 25: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 25

ISO 9001 certified Jin Kwang E & C Corp.

Page 26: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 26

ISO 9001 certified Jin Kwang E & C Corp.

5.3.3 Install the control

Refer to FTU-R200 microprocessor-based recloser control instruction manual and user’s guide for

complete recommended grounding instruction. Connect the control cable between the control and main

body of the recloser.

5.3.4 Ground the control

Ground the control using the ground connector provided at the upper of the control cabinet for

connecting 22 mm2 to 60 mm2 stranded grounding cable to a suitable ground. Make ground

connections in accordance with approved utility standards. Make sure the control is grounded and

properly programmed for the planned installing.

5.3.5 Make the high-voltage line connections.

Provide surge protection to both sides of each recloser.

Connect high-voltage lines to the recloser bushing terminals.

Connect the high-voltage lines to the bushing terminals with source leads connected to bushings 1, 3

and 5. of the recloser. The high-voltage bare conductors should be placed in the hole of the clamp type

terminals fastened with nut up to tensile torque of 400 ㎏.f/㎠.

The bare conductor size ranging from 38 mm2 to 240 mm2 is adequate for the connection with the

clamp type terminal.

Note: Disconnect switches and bypass switches are recommended to facilitate switching and

isolation.

Bypass

Switch

Disconnect

Switch

Disconnect

Switch

recloser

1

3

5 6

4

2

Surge

Arresters Surge

Arresters

[Connection diagram with switches to facilitate maintenance and complete protection]

Page 27: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 27

ISO 9001 certified Jin Kwang E & C Corp.

▪ Block ground sensing via the control.

▪ Close source and load disconnect switches.

▪ Close reclosers via control signal.

▪ Open bypass switches.

▪ Enable ground sensing, if applicable.

5.4 After installation, checking items

1) High voltage wire insulation distance that is connected to bushing terminal should be checked by

each phase.(Phase to phase spacing of high voltage wire must keep more than smallest 250mm).

2) Check installation condition of insulation cover that is mounted to the top end of bushing.

3) Check the Work tool remaining and cleanliness condition on the top of main body and mounting

hardware.

4) Check cleanliness condition of bushing.

5) Make sure a position of manual operating and Lock handle (If the lock handle is placed at locking

position, it should be manually returned by hot stick and placed at normal position).

6) Make sure a mounting condition of the control cabinet’s components such as a batteries, power

transformer for power supply, etc.

7) Check a charging condition and capacity of batteries using the battery test button in the control.

8) Check a grounding connection of main body and control cabinet.

9) Check a connection condition of the control cable and power cable.

5.5 Place the recloser in Service

Always follow locally approved procedures and safety practices when placing the recloser in service.

Be sure that 24-volt control back-up battery is properly connected. When the control is connected, the

recloser can be placed in service.

1) Move the manual operating and Lock handle (yellow color) to the OPEN (down) position.

2) Close the source and load disconnect switches.

3) Move the manual operating and Lock handle (yellow color) to up position and then close using a

close button on the control panel necessarily. This resets the control and synchronizes the control to

the recloser. The recloser should immediately close.

Page 28: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 28

ISO 9001 certified Jin Kwang E & C Corp.

4) Open the bypass switch. The recloser is now in service.

5.6 Remove the recloser from Service

1) Follow standard utility procedures for removal of recloser from service.

2) Close the bypass switch.

3) Pull down the manual operating and Lock handle (yellow color) with a hotstick.

4) The manual operating and Lock handle (yellow color) is located on the side of the recloser.

5) Open the source and load disconnect switches.

6) Disconnect the batteries in the control box.

Note: The unit should not be stored or shipped with the batteries connected. Even if the recloser is not

in service, connected batteries will still expend energy. Disconnect the batteries when the recloser is not

in service.

Page 29: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 29

ISO 9001 certified Jin Kwang E & C Corp.

6. RECLOER OPERATION

Warning

Do not reply on the open position of the open/lock handle(yellow color) or the contact position

indicator; it does not ensure that the line has been de-energized. Always establish a visible disconnect.

Failure to follow proper safety practices can result in contact with high voltage, which will cause severe

personal injury.

Caution

Pushing the yellow manual operating and Lock handle to the closed position will not close the recloser.

All close operations are initiated by the FTU-R200 microprocessor-based recloser control.

6.1 Closing Operation

Closing operation should be performed with a close button on the control panel necessarily. But, before

operating the recloser on the control panel, make sure a position of manual open& lock handle. Check

whether the manual open&lock handle indicate lock position or not.

Note: When the recloser is closed, the manual operating and Lock handle should be positioned in free

condition(upward).

6.2 Opening Operation

The manual operating and Lock handle(yellow color) in the recloser is used to open and lock out the

recloser. If the recloser is opened with a manual operating & lock handle, it automatically operates to

lockout. So, it disable in the electrical and supervisory closing.

The manual operating and Lock handle is designed to be operated with a hot stick. Pulling down the

manual operating and Lock handle open the main contacts of the recloser. Contact position is indicated

by the open flag of the contact open indicator. The handle will remain down in the open position and

not return upward in the close position.

Therefore, when the recloser is closed, the manual operating and Lock handle should be positioned in

free condition.

Note: When the recloser electrically operates to lockout, the open/ lock operating handle will not drop

by the open position. The handle remains in the open position only after manual operations are

performed.

Page 30: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 30

ISO 9001 certified Jin Kwang E & C Corp.

6.3 Lock Operation

When the manual operating and Lock handle has been manually pulled down into the lock position, any

current over the minimum trip rating will cause the control to automatically lock the recloser. The

manual operating and Lock handle does not interfere with manual recloser operation or operation via a

SCADA trip or close signal. The recloser can be opened or closed manually regardless of the position of

the lock handle.

Page 31: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 31

ISO 9001 certified Jin Kwang E & C Corp.

7. MAINTENANCE

Warning

Always use a hotstick when working with the recloser. Failure to do so could result in contact with high

voltage, which will cause severe personal injury.

Caution

The equipment requires routine inspection and maintenance to ensure proper operation. If it is not

maintained it may fail to operate properly. Improper operation may cause equipment damage and

possible personal injury.

7.1 GeneralJin Kwang’s reclosers require inspection and maintenance to ensure proper operation.

If the recloser is not adequately maintained, it may fail to operate properly. Even though the recloser has

been designed as a low maintenance unit, maintenance interval depends on the local climatic condition.

Jin Kwang recommends that the recloser be inspected and maintained for long life.

7.2 Frequency of maintenanceTo assure proper and trouble-free operation, reclosers must be

maintained when they have operated the equivalent of a rated duty cycle.

Note: ANSI C 37.61, “Guide fot the application, Operation and Maintenance of Automatic Circuit

reclosers”, gives a procedure for converting the rated standard duty cycle into an equivalent duty

cycle based on the actual operating duty of the recloser

7.3 Check the operation of low pressure indicatorThe recloser is filled with 0.5kgf/cm2 of SF6 gas in

normal service, however, if gas pressure drops to 0.1 ~ 0.2kgf/cm2 or less by means of any cause, a

low pressure locking device works to prevent the operation of the switch manually and electrically (from

local control panel and from remote location).

At the same time, a low gas pressure indicator located at the side of switch will be shown and a low

pressure indicator lamp on the control panel will illuminate to indicate that switch operation has been

blocked.

7.4 Check the recloser visuallyInspect each of the bushing for breaks, cracks, burn or heavy pollution

and other part of the recloser.

1) If polluted, clean the bushing.

2) If damaged, replace whole of the recloser with new one.

Page 32: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 32

ISO 9001 certified Jin Kwang E & C Corp.

FTU-R200 CONTROL UNIT

8. OVERVIEW

8.1 PROTECTION OF DISTRIBUTION LINE

Distribution lines have their own equipment outdoors, the types of loads are various, and the

configurations of the networks are flexible and complicated. There are many kinds of fault causes such

as direct contact of trees or birds, natural phenomenon of lightning or heavy snow, and fault spread-out

due to customer’s facilities. Among these faults, most of faults are temporary and the dominant fault

type is ground-fault.

For rapid fault detection and fault section isolation, blackout area minimization, many protection devices

such as Recloser, Sectionalizer, and Line Fuse are adopted. Among these devices, Automatic Circuit

Recloser is the most important protection device, whose main functions are fault current trip and auto-

reclosing.

One distribution line has over 2 Reclosers of serial connections or Recloser – Sectionalizer - Line Fuse of

serial connections. This configuration is the concept of Primary Protection and Back-up Protection. In

other words, protection coordination is required in the way that a protection device nearer to fault point

operates first to eliminate the fault and other devices farther from fault point are configured to operate

later with time delays.

8.2 FUNCTION OF AUTOMATIC CIRCUIT RECLOSER

When a fault occurs on the load side of Recloser installed location, Recloser detects fault current, trips

fault current at high speed, and does reclosing actions after the set time to re-activate the faulted

section. In case of temporary fault, the fault can be removed by itself according to high-speed trip and

dead time before reclosing actions. But, in case of

permanent fault, because fault current is still detected after trip and reclosing actions of pre-set counts,

Recloser is locked out finally as opened.

Recloser has the time delay element in protection function of its controller and can be freely configured

for protection coordination with other protection devices.

Page 33: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 33

ISO 9001 certified Jin Kwang E & C Corp.

8.3 MAIN FEATURES OF FTU - R200

Recloser body is connected serially to distribution line to operate open / close of the line, and Recloser

Controller is in charge of measurements of currents, voltages, and other electric values, protection,

control, status monitoring, recording, and communication.

FTU-R200 is a kind of IED’s (Intelligent Electronic Device) for power system automation, which is a fully

digitalized and microprocessor-based control device, and through connecting with this control device,

Recloser can play a role of automated protection device.

Main features of FTU-R200 are as follows,

MEASUREMENT

Magnitude and phase angle of voltages & currents(Fundamental frequency)

Sequence components of 3-Phase voltages & currents

True RMS, Harmonics and THD of voltages & currents

Active, reactive and apparent power for each phase and 3-phase

Energy(4-quadrant metering)

Displacement Power Factor

Frequency

PQM, Fault, THD Counter

Phase difference between source-side and load-side voltage

Page 34: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 34

ISO 9001 certified Jin Kwang E & C Corp.

CONTROL

Manual Recloser Open/Close at local or remote(Select Before Operation)

Interlocking(Gas low, Handle lock, Operator place, Sync Fail, Live Load)

Batter Test

External Trip and Close By contact input(Optional)

Enable or disable reclosing, protection and Ground function

PROTECTION

3-stage over current protection

Fast and Delayed TC trip elements for phase and earth fault

54 types of built-in TC Curves and 4 Customized TC Curves

Definite time over-current element

Definite time HCT(High Current Trip)

SEF(Sensitive Earth Fault) Detection

Auto-Reclosing(up to 4 shots)

Cold Load protection(Pickup Adjustment)

Magnetizing Inrush Restraints

Sequence Coordination

Open Line Detection

Phase Sync. Fail Detection

Over Voltage, Under Voltage

Under Frequency

Page 35: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 35

ISO 9001 certified Jin Kwang E & C Corp.

STATUS MONITORING

10 Contact Inputs

Open Line Detection

Fault Indication

Recloser, Protection, Ground Protection, Switch Open/Closed

Over Voltage, Under Voltage, Under Frequency

Handle Locked

Gas Pressure Low

External AC Power Loss

Battery Discharged

Enclosure Door Open

Spare (3 Points : Optionally external trip and close command)

EVENT RECORDING

Event recording with time-stamp

I/O, Functional, System, Fault Current, Demand Current & Power,

Daily Max Current & Power

Waveform Recording

8 Fault Waveforms

8 PQM Waveforms

1 Manual Trigger Waveform

128 samples/cycle, 20 cycles

Saving COMTRADE File Format

COUNTER

FTU Restart count

Switch Trip Count

Fault Detection Count

PQM Count

THD Count

Page 36: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 36

ISO 9001 certified Jin Kwang E & C Corp.

COMMUNICATION PROTOCOLS

SCADA Port

DNP3.0

DNP3.0 over TCP/IP

IEC60870-5-101

IEC60870-5-104

Maintenance Port Modbus-RTU

9. TECHNICAL DATA

9.1 DIGITAL PROCESSOR

9.1.1 Dual Processor Architecture

32-bit RISC type micro-controller with on-chip flash program memory

32-bit floating-point Digital Signal Processor

Dual-Port Memory for communication between two processors

Data Memoty(SRAM)

Non-volatile Memory(1Mbytes) for storing events and parameters

Flash Mamory for stroring fault and PQM Waveforms

Real Time Clock

9.1.2 Analog/Digital Conversion

16-bit A/D Converter

Sampling rate : 128 samples/cycle

Anti-aliasing analog filter

One gain channel for each current input : effective 16-bit resolution for current

measurements

Page 37: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 37

ISO 9001 certified Jin Kwang E & C Corp.

9.1.3 DSP

Correction of analog input error

Fast Fourier Transform : phasor calculation

Electric quantities calculation & Fault Decision

9.1.4 CPU

Status monitoring & Control Command

Local Human-Machine Interface

Event Recording

Remote Communication(DNP3.0, IEC60870-5-101 and IEC60870-5-104)

Self Diagnosis

9.1.4 Functional Block Diagram

[ Functional Block Diagram ]

Page 38: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 38

ISO 9001 certified Jin Kwang E & C Corp.

9.2 ENVIRONMENTAL CONDITIONS

Altitude < 2,000m

Wind Speed < 40m/s

Ambıent Temporature - 25 ~ +70°C, KSC 0220/1

Storage Temporature - 40 ~ +85°C

Humidity < 95%RH

Dielectric withstand IEC 60255-5, 2kV

Impulse voltage IEC 60255-5, 6kV for current input circuit

IEC 60255-5, 4kV for voltage, power input & Contacts I/O

Insulation resistance IEC 60255-5, >500MW (DC500V)

High frequency disturbance IEC 61000-4-12 class 3 (2.5kV)

Fast transient noise IEC61000-4-4 class 4 (4kV)

Radio frequency noise IEC 61000-4-3 10V/m

Vibrations IEC 60255-21-1 class 2

Mechanical Shock IEC 60255-21-2 class 2

Enclosure protection IP54

Page 39: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 39

ISO 9001 certified Jin Kwang E & C Corp.

9.3 INPUTS/OUTPUTS

BINARY CONTACTS INPUT : 10 POINTS

DC 24V Baised in the control box

Opto-isolation(Viso) : 2,000 Vrms

Delay time setting(10~500ms) for each contact input to suppress bouncing

Signal

Recloser Open

Recloser Closed

Recloser Locked

Gas Pressure Low

External AC Power Fail

Battery Discharged

Control Box Door Open

External Trip Command(Optional)

External Closer Command(Optional)

Spare

BINARY CONTACTS OUTPUT : 6 POINTS

Pulse width of output is variable

Signal & Contact rating

DC24V Aux. Relay Contact

Contact Relay : Switch Open, Close, Battery Test, Spare

PhotoMOS Relay : Switch Open, Close for

Page 40: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 40

ISO 9001 certified Jin Kwang E & C Corp.

CONTACT RELAY RATINGS

Rated Current

Rated Voltage/Max. Breaking Voltage AC

Max. Breaking Capacity AC

Make Current (Max. 4s at duty cycle 10%)

Dielctring Strength

Coil-Contacts

Open Contact Circuit

Mechnical Life

Operate Time

16A

250Vac/440Vac

4,000VA

30A

5,000Vrms

1,000Vrms

> 30 x 106 operations

typical 7ms

PHOTO MOS RELAY RATING

Rated Load Current

Rated Load Voltage

I/O isolation Voltage

120mA

350Vac

1,500Vac

CURRENT INPUT : 4 CHANNEL

12.5A Maximum(external CT Ratio is 1,000:1 normally)

Burden : below than 1VA

3-Phase Current and Neutral Currents

Isolation by auxiliary CT of RTU(Viso) : 2,000 Vrms

Surge Withstand Voltage : 6kV

Signal : Ia, Ib, Ic, In

Page 41: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 41

ISO 9001 certified Jin Kwang E & C Corp.

VOLTAGE INPUT : 6 CHANNEL

4Vrms at rated Phase Voltages

Burden : below than 0.01VA

Maximum input range : ~200%

Isolation by auxiliary PT of RTU(Viso) : 2,000 Vrms

Surge Withstand Voltage : 4kV

Signal : Va, Vb, Vc, Vr, Vs, Vt

POWER SUPPLY INPUT

DC 24V(DC20~DC29V)

Power Consumption: Max. 15W

9.4 MEASUREMENT

9.4.1 CURRENT

RMS(A) & Phase angle(°) Ia, Ib, Ic, In

Sequence Component I1, I2, I0

True RMS Ia, Ib, Ic

Reading Range 2~12, 500A(External CT Ratio 1,000 : 1)

Accuracy 2~600A ±0.5% or ±1A

600~12,000A ±3%

Page 42: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 42

ISO 9001 certified Jin Kwang E & C Corp.

9.4.2 VOLTAGE

RMS(kV) & Phase angle(°) Va, Vb, Vc, Vr, Vs, Vt

Sequence Component V1s, V2s, V0S, V1L, V2L, V0LS,

True RMS Va, Vb, Vc, Vr, Vs, Vt

Phase Angle Difference(°) ∠Va - ∠Vr

Reading Range 0.1~26kV

Accuracy ±0.5% or ±0.1kV

9.4.3 POWER

Active Power(kW) A-Phase, B-Phase, C-Phase, 3-Phase Total

Reactive Power(kVAR) A-Phase, B-Phase, C-Phase, 3-Phase Total,

Apparent Power(kVA) A-Phase, B-Phase, C-Phase, 3-Phase Total

Reading Range -32767~32767

Accuracy ±1%

9.4.4 POWER FACTOR

A-Phase, B-Phase, C-Phase, 3-Phase Total

Lead/Lag Display

Reading Range 0~1.0

Accuracy ±2%

9.4.5 FREQUENCY

Reading Range 45 ~ 55Hz (System Frequency : 50Hz)

55 ~ 65Hz (System Frequency : 60Hz)

Accuracy ±0.02%

Page 43: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 43

ISO 9001 certified Jin Kwang E & C Corp.

9.4.6 ENERGY

Positive kWh A-Phase, B-Phase, C-Phase, 3-Phase Total

Negative kWh A-Phase, B-Phase, C-Phase, 3-Phase Total

Capacitive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total,

Capacitive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total,

Inductive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total,

Inductive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total,

Reading Range 0~65535(Rollover)

Accuracy ±2%

9.4.7 HARMONIC

Total Harmonic Distortion (%)

3-Phase Current THD (Ia, Ib, Ic, I3ph)

Source side 3-Phase Voltage THD (Va, Vb, Vc,

V3ph)

2nd~31st Harmonic RMS(A, kV) Ia, Ib, Ic, Va, Vb, Vc

9.4.8. DEMAND CURRENT AND POWER

Configurable Demand Interval 5, 10, 15min (Default 15min)

2nd~31st Harmonic RMS(A, kV) Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph

Daily Max Current and Power are Stored

9.5 COMMUNICATION

9.5.1 PHYSICAL LAYER

9.5.1.1 RS232C

9-Pin Male Connector DCD(1), Rx(2), Tx(3), DTR(4), GND(5)

DSR(6), RTS(7), CTS(8), NC(9)

Speed(Baud Rate) 1200, 2400, 4800, 9600, 19200 BPS

Suppots Modam Control CTS, DCD Signal Timeout Configurable

RTS Off-delay Configurable

Optical Isolation

ESD, Transient Noise Protection

Page 44: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 44

ISO 9001 certified Jin Kwang E & C Corp.

9.5.1.2 Rs232C/RS485C

RS232C Mode Rx(2), Tx(3), GND(4), GND(5)CTS(8),

RS485C Mode DATA-(3) DATA+(7)

Speed(Baud Rate) 1200, 2400, 4800, 9600, 19200 BPS

Optical Isolation

ESD, Transient Noise Protection

9.5.1.3 TCP/IP

Ethernet Port 10/100 Base-T

9.5.2 PROTOCOL FOR SCADA

9.5.2.1 DNP3.0

Support DNP3.0 Subset Level 3

Class of each point is settable(Using DNP3.0 Index Configuration Tool)

Supports multi-frame transmission(multi-frame interval is configurable)

Enable/Disable unsolicited message class

Supports file transfer function for uploading fault waveform and local event history

Non-transmitted events are stored on non-volatile memory during communication fail

Event buffer size : Binary Input(254), Analog Input(127), Counter(19)

Supports direct operate or select befor operate(SBO) for control output

Supports report by exception for analog values

Protocol frame monitor was built in FTU(Using data terminal on maintenance connector)

9.5.2.2 IEC60870-5-101

IEC 60870-5-101 is primarily used with relatively slow transmission media on the asynchronous V.24

interface. The standard promises baud rates of up to 9600 bit/s, with much higher baud rates (<115200

bit/s) actually being used. X.24/X.27 interfaces with baud rates up to 64000 bit/s, also part of the

standard's description, could not establish themselves and are rarely used.

Page 45: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 45

ISO 9001 certified Jin Kwang E & C Corp.

9.5.2.3 IEC60870-5-104

IEC 60870-5-104 (also known as IEC 870-5-104) is an international standard, released in 2000 by the IEC

(International Electrotechnical Commission). As can be seen from the standard's full designation

'Network access for IEC 60870-5-101 using standard transport profiles', its application layer is based on

IEC 60870-5-101. IEC 60870-5-104 enables communication between control station and substation via a

standard TCP/IP network. The TCP protocol is used for connection-oriented secure data transmission.

9.6 RECORDING

9.6.1 EVENT RECORDER

This function is used to verify shortly the operated history or log of FTU in normal operation and fault

situation. Event recording is triggered by power reset, set value change, operation of protection

f u n c t i o n s , s y s t e m e r r o r o r s e l f - d i a g n o s i s , e t c . , a n d e v e n t s c a n b e s t o r e d

including event occurred time, measured values of current/voltage and operation description.

And, this recording fuction follows the FIFO (First In First Out) rule. Stored events can be uploaded to

and listed on FTU PC S/W (FTUMan) through RS232C port on front panel.

Event List Sub Items Max.

I/O Events Status change of binary Input/Output 1023

Function Events Operated status of Protection Function 1023

System Events Setting change, Reset, Self Dignosis 255

Fault I Events Latest fault current, phase and time 255

PQM Events Operated status of PQM Function 255

Demand I,P,Q

Events

Each phase daily average load current, active

power and reactive powe with time 1023

Max. I,P,Q Events Each phase daily Peak load current, active

power and reactive powe with time 1023

9.6.2 WAVEFORM EVENT RECORDER

Fault & PQM waveforms recording function are used to store the measured instantaneous

current/voltage values of pre-fault and post-fault at 128 samples per cycle. Record length, trigger source

and trigger position of pre/post-fault in recorded data are adjustable. The record types are 128 samples

* 20 cycles, 64 samples * 40 cycles, 32 samples * 80 cycles, 16 samples * 160 cycles.

Page 46: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 46

ISO 9001 certified Jin Kwang E & C Corp.

According to the purpose, operators can set the fault recording trigger source and trigger position of

pre-fault/post-fault. Trigger position means the percentage position in recorded fault data, and the pre-

fault data are recorded before this point and rest of the data are recorded as the post-fault after this

point. The recorded fault waveforms are also uploaded to FTU PC S/W, and current/voltage waveforms

at fault and protection elements operation can be analyzed with fault evaluation.

This waveform recording fuction follows the COMTRADE file format rule.

Page 47: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 47

ISO 9001 certified Jin Kwang E & C Corp.

10. CONSTRUCTION AND EXTERNAL CONNECTION

10.1 APPEARANCE & DIMENSION

Front panel of FTU-R200 has an operational LCD display, a RS232C port for setting and maintenance,

indicating LED’s, and push buttons.

[ Front Panel Drawing of FTU ]

Page 48: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 48

ISO 9001 certified Jin Kwang E & C Corp.

The following is the Top-view of FTU-R200 panel.

[ Top View of FTU Panel ]

The next drawing is Side-view of FTU-R200 panel, and there are measurement module connector,

control module connector, monitoring module connector, power connectors, and RS232 port for SCADA

communication on the right side of FTU panel.

[ Side View of FTU Panel ]

Page 49: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 49

ISO 9001 certified Jin Kwang E & C Corp.

10.2 CONNECTOR

On the right side of FTU-R200 panel, there are RS232 communication port to SCADA, control source

power connector, DI (Status Monitoring) connector, DO (Control) connector, AI (Measurement)

connectors for Voltage, Current from top to bottom, TCP/IP connector, CAN connector, and TD

connector. RS232C port is DB9 male-type connector.

[ Pin Connectors on the Right Side of FTU-R200 ]

Page 50: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 50

ISO 9001 certified Jin Kwang E & C Corp.

11. FRONT PANEL OPERATION

On the front panel, there are LED’s indicating Recloser’s status, function buttons and LED’s, control

buttons and LED’s, LCD & Menu buttons and a RS232C port for maintenance.

[ Front Panel Sheet of FTU-R200 ]

Page 51: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 51

ISO 9001 certified Jin Kwang E & C Corp.

11.1 BUTTON & LED DESCRIPTION

11.1.1 LCD DISPLAY

4 lines * 20 characters LCD is used and through MENU/UP/DOWN/ENTER buttons, operators can survey

all data and corrent set values.

11.1.2 FTU STATUS

These LED’s indicate status of FTU-R200.

CPU Run Normal operation of FTU(CPU OK)

System Error Self-diagnosis Error & Switch Status Trouble

Ext.Power External AC Power is supplied

Battery Fail Battery voltage is low (discharged)

11.1.3 MENU/UP/DOWN/ENTER BUTTONS

These buttons are used to operate FTU in local position. Refer to LCD Manipulation section for detailed

methods.

11.1.4 SERIAL PORT

Engineering tool on PC is connected to this port for maintenance and upgrade. RS232C port for

maintenance is DB9 femail-type connector.

RS232C Rx(2), Tx(3), GND(5), MODE(9)

11.1.5 ETHERNET/SCADA/PROTECTION COMMUNICATION LED

These LED’s indicate status of FTU-R200.

Ethernet Link Ethernet Linking

Ethernet Act Ethernet Active

SCADA Rx Communication data are received

SCADA Tx Transmitting communication data

SCADA RTS Data transmission request

Protection Rx Communication data are received from another FTU by CAN

communication.

Page 52: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 52

ISO 9001 certified Jin Kwang E & C Corp.

Protection Tx Transmitting communication data to another FTU by CAN

communication.

11.1.6 BATTERY TEST & LAMP TEST

To test the battery and charger circuit, push ‘BATTERY TEST’ button. When the test result is fail, we will

see turn on Battery Fail LED.

To test the LED, push ‘LAMP TEST’ button. When test is OK, all of the LEDs are turn on for a while.

11.1.7 RESET BUTTON

This button is used for Annunciator LED Reset (LED turn off). Annunciator LED represents all the LED’s

related to Protection, Reclosing and Self-diagnosis Error.

11.1.8 FUNCTION LED

- LIVE LINE LED’s indicate if the lines to source side and load side are activated or deactivated.

LED’s are on, when the line voltage goes up the set ‘Voltage ON Level’ and LED’s are off, when

the voltage goes down the set ‘Voltage OFF Level’.

- Under Voltage LED’s indicate if the voltage reaches under the setting value.

- Sync.Fail LED is on, when the phase angle difference between source-side voltage (Va) and

load-side voltage (Vr) is over the setting value. In this case, Close control command should be

inhibited.

- Fault Indicator LED’s on, when a fault related to each faulted phase occurs. For earth fault of

non-gronded networks, SEF LED is on.

- Reclose Ready LED is on, when the reclosing action is normally operated. This represents the

normal stand-by status for reclosing action.

- Reclose Progress LED is indicates the status that reclosing action is normally processed

according to the preset tripping and reclosing operation sequences.

- Reclose Lockout LED is on, when the reclosing action is locked out to open according to the

operation sequences or the Recloser is opened by the manual control command.

Page 53: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 53

ISO 9001 certified Jin Kwang E & C Corp.

11.1.9 RECLOSE/PROTECTION/GROUND ENABLE BUTTONS AND LEDS

Push the enable buttons and makes the respective LED’s on to fulfill the Reclosing and Protection

functions. These buttons are toggled between Enable and Disable.

- RECLOSE ENABLE button enables or disables the Reclosing Function. In disable mode, the

Recloser is locked out right the 1st trip.

- PROTECTION ENABLE button enables or disables Phase Fault Detection and Earth Fault

Detection Functions, simultaneously.

- GROUND ENABLE button enables or disables Earth Fault Detection Function only.

11.1.10 REMOTE/CONTROL LOCK BUTTON AND LEDS

To decide the control position to Remote, push REMOTE button and make the LED on. This button and

LED are also toggled between Remote and Local position. But, the manipulation of this button is

possible only in the local for operator’s safety.

CONTROL LOCK button enables or disables the Recloser switching operation. If Control Lock LED is on,

Recloser switch is not operated.

11.1.11 SELECT/OPEN/CLOSE BUTTONS AND LEDS

These buttons are used to locally control (OPEN/CLOSE) the Recloser. Before local control command,

check first if the control position is LOCAL. SELECT button is a two-phase safety & confirmation check

machanism, and this concept is similar to SBO (Select Before Operate) in communication protocol. To

manually and locally control the Recloser, SELECT button shuld be pushed down to make the

corresponding LED on, and this SELECT function can be expanded to the scheme of Multiple Recloser

Control in the future.

SELECT → CLOSE

Push this button to control the Recloser manually to be closed. After closing, normal fault detection

functions are re-performed. In case that Cold Load Pickup function is off or the load current is below

the Cold Load Pickup Level, normal Phase & Ground Fault Detection is functined.

SELECT→OPEN

Manual open control opens the Recloser and makes the switch locked out to open.

Page 54: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 54

ISO 9001 certified Jin Kwang E & C Corp.

11.2.LCD MANIPULATION

MENU/UP/DOWN/ENTER buttons are used to manipulate the LCD. The following table explains the

common roles of 4 buttons.

Button Description

MENU

ü To toggle between Main Menu Display from Initial Display

ü To come back to Parent Menu from Child Menu

ü Be careful, because all the set value changes are canceled

when this button is pushed down during the change of set values

ENTER

ü To select and enter into each menu item

ü To enter the changed set value and configuration

ü After entering the changed set value, this button again goes out from

each item to menu tree. (Toggle between menu tree and each menu item)

ü After changing the set values, be sure to save the changed values

in the Set Value Change Save Menu.

UP

ü To move up the cursor in the menu tree

ü To increment the set values

ü The set values are rolled up and UP button at the highest value goes

to the lowest value

DOWN

ü To move down the cursor in the menu tree

ü To decrement the set values

ü The set values are rolled down and DOWN button at the lowest value goes

to the highest value

Page 55: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 55

ISO 9001 certified Jin Kwang E & C Corp.

11.2.1 LCD MENU

[ LCD Menu Tree Diagram of FTU-R200 ]

11.2.1.1 Initial Display

[Initial Display] shows up the reclosing status.

< R / C f o r D A S >

S e q u e n c e : 0 [ H O ]

R / C S t a t u s : C L O S E

[ H O M E ]

[ Initial Display ]

MENU button at [Initial Display] goes to [Main Menu Display]. MENU button toggles between [Initial

Display] and [Main Menu Display].

Page 56: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 56

ISO 9001 certified Jin Kwang E & C Corp.

UP or DOWN button at [Initial Display] goes to [Current / Voltage Measurement Display]. UP / DOWN

button toggles between [Initial Display] and [Current / Voltage Measurement Display].

I a : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0

I b : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0

I c : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0

I n : 0 0 0 0 0 A < A B C . R S T >

[ Current / Voltage Measurement Display ]

Reclosing Sequence 0, 1, 2, 3 and 4

Total Reclosing Shot

3 Times

0[HO], 1~3[SR], 4[LO]

HO Home

SR Sequence Running

LO Lockout

R/C Status CLOSE/OPEN/TROUBLE (No Status Input)

Current (Ia,Ib,Ic,In) Each Phase Instantaneous Current Value (unit : A)

Voltage (ABC.RST) Source Side Voltage (Va,Vb,Vc) /

Load Side Voltage (Vr,Vs,Vt), (unit : kV)

Diagnosis Fail

If diagnosis failure happens, [FAIL] message will appear

in the right side of [HOME] or <ABC.RST> will change

into <FAIL>.

12.2.1.2.Main Menu Display

[ M A I N M E N U ]

1 . F u n c t i o n S e t t i n g

2 . C o n f i g u r a t i o n

3 . D i s p l a y

4 . E v e n t L i s t

[ Main Menu Display ]

Page 57: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 57

ISO 9001 certified Jin Kwang E & C Corp.

[Main Menu Display] shows up 4 main menu items. And UP & DOWN buttons move up and down the

main menu trees. ‘>’ symbol indicates the cursor position and ENTER button enters into the selected

main menu’s sub items.

12.2.1.3 FUNCTION SETTING

[ S e t t i n g M e n u ]

1 . G r o u p 1

2 . G r o u p 2

3 . G r o u p 3

4 . G r o u p 4

5 . G r o u p S e t t i n g

[ Function Setting ]

In Function Setting, there are 4 different setting groups and the different setting values can be stored

individually in 4 different setting groups.

After finishing the set value change, when MENU button is pushed to return to [Main Menu Display],

[Set Value Change Save Display] shows up to determine Yes or No. If selecting yes and pushing ENTER

button, the changed set values are all saved. However, if selecting No and ENTER button or MENU

button again, the changed set values are not saved and the existing set values are still applied.

ø CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set

values are neither saved nor applied.

Main Menus Sub Items

Function Setting Group1, Group2, Group3, Group4, Group Setting

Configuration I/O, Communication, Event, Time

Display Measurements, Status, Counter

Event List

I/O events, Function events, System events, Fault I events,

Demand I events, Demand P events, Demand Q events,

Max. I events, Max. P events, Max. Q events

Page 58: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 58

ISO 9001 certified Jin Kwang E & C Corp.

S a v e C h a n g e d S e t ?

Y e s / N o

[ Set Value Change Save Display ]

S e t t i n g S a v i n g !

[ ENTER to Yes ]

[ M A I N M E N U ]

> 1 . F u n c t i o n S e t t i n g

2 . C o n f i g u r a t i o n

3 . D i s p l a y

[ ENTER to No ]

12.2.1.4 Configuration

[ C O N F I G M E N U ]

1 . I / O

2 . C o m m u n i c a t i o n

3 . E v e n t

4 . T i m e

[ Configuration ]

Configuration menu has the setting items for communication, I/O, and system configuration. Setting

items are I/O, Communication, Event and Time.

After finishing the set value change, when MENU button is pushed to return to [Main Menu Display],

[Set Value Change Save Display] shows up to determine Yes or No. If selecting yes and pushing ENTER

Page 59: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 59

ISO 9001 certified Jin Kwang E & C Corp.

button, the changed set values are all saved. However, if selecting No and ENTER button or MENU

button again, the changed set values are not saved and the existing set values are still applied.

ø CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set

values are neither saved nor applied.

12.2.1.5 Display

[ D I S P L A Y M E N U ]

1 . M e a s u r e m e n t s

2 . S t a t u s

3 . C o u n t e r

[ Display ]

In Display menu, measurement values, monitored status, and counter values are displayed.

12.2.1.6 Event List

[ E V E N T L I S T ]

1 . I / O E v e n t s

2 . F u n c t i o n e v e n t s

3 . S y s t e m e v e n t s

4 . F a u l t s e v e n t s

5 . D e m a n d I e v e n t s

6 . D e m a n d P e v e n t s

7 . D e m a n d Q e v e n t s

8 . M a x . I e v e n t s

9 . M a x . P e v e n t s

10 . M a x . Q e v e n t s

[ Event List ]

Page 60: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 60

ISO 9001 certified Jin Kwang E & C Corp.

In Event List menu, all types of events are displayed with occurred time and event description. Using UP

& DOWN buttons, event list can be scrolled up and down in the LCD display.

13. PROTECTION FUNCTIONS

13.1 FAULT DETECTION

FTU detects the Phase & Earth Fault and trip the breaker.

The fastest operation time is within 45msec including auto-recloser operating time. There are 58 trip

curves, which can be selected for fast and delayed operation respectively. The Curve can be edited by

using several parameters, i.e. time multiplier, time adder and minimum response time.

And high current trip element can be used for instantaneous trip. It is definite time characteristics.

During cold-load condition, pickup multiplied by cold-load multiplier. During the cold-load condition,

time-delayed curve is applied instead of fast curve. This function can be enabled or disabled by cold-

load multiplier.

Earth fault detection function can be enabled or disabled by ‘Ground Protection Enable’.

Item Phase Fault Earth Fault

Step Unit Range Def. Range Def.

Pickup

Current 10~1260 400 5~900 60 1 A

Inrush Block NO/YES YES NO/YES YES

Event List Sub Items Max.

I/O Events Status change of binary Input/Output 1023

Function Events Operated status of Protection Function 1023

System Events Setting change, Reset, Self Dignosis 255

Fault I Events Latest fault current, phase and time 255

Demand I,P,Q Events Each phase daily average load current, active

power and reactive powe with time 1023

Max. I,P,Q Events Each phase daily Peak load current, active

power and reactive powe with time 1023

Page 61: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 61

ISO 9001 certified Jin Kwang E & C Corp.

Fast Operation

Time Curve

Type 1~58 1-A 1~58 2-B 1

Time

Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec

Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec

Min.

Response

Time

0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec

Reset Type RDMT/

RIDMT RDMT

RDMT/

RIDMT RDMT

RDMT(Definite Time)

RIDMT(Inverse Time)

Reset

Definite Time 0.00~100.00 0.00 0.00~100.00 0.00 0.01 sec

Item

Phase Fault Earth Fault

Step Unit Range Def. Range Def.

Delayed Operation

Time Curve

Type 1~58 20-1 1~58 21-2 1

Time Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec

Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec

Min. Response

Time 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec

Reset Type RDMT/

RIDMT RDMT

RDMT/

RIDMT RDMT

RDMT(Definite Time)

RIDMT(Inverse Time)

Reset Definite

Time

0.00~100.0

0 0.00 0.00~100.00 0.00 0.01 sec

Page 62: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 62

ISO 9001 certified Jin Kwang E & C Corp.

13.1.1 DEFINITE TIME PROTECTION

Definite Time is an alternative to Inverse Time Protection. It works by tripping the recloser at a fixed

time after pick-up.

Item Range Def. Step Unit Comment

Phase Detection

Active OFF/ON OFF

Pickup Current 50~10000 1000 1 A

Detection Time 0.00~1.00 0.00 0.01 sec

Earth Detection

Active OFF/ON OFF

Pickup Current 50~10000 1000 1 A

Detection Time 0.00~1.00 0.00 0.01 sec

13.1.2 HIGH CURRENT TRIP (HCT)

Very high valued current can cause serious damage to the Recloser and the resultant fault spread-out,

therefore HCT element should operate faster than Instantaneous or Time-Delayed TC curve’s operation

time and its priority must be higher than the normal auto-reclosing sequence.

HCT can be configured up to 4 times for phase fault and earth fault, respectively. HCT Count setting

value ‘0’ means HCT element disabled.

Range Def. Step Unit Comment

Phase Detection

Operation Count 0~4 0 1 ‘0' means

disable.

Pickup Current 50~10000 2000 1 A

Detection Time 0.00~1.00 0.00 0.01 sec

Earth Detection

Operation Count 0~4 0 1 ‘0' means

Page 63: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 63

ISO 9001 certified Jin Kwang E & C Corp.

disable.

Pickup Current 50~10000 2000 1 A

Detection Time 0.00~1.00 0.00 0.01 sec

13.1.3 SINGLE SHOT OPERATION

In Single Shot Operation is used to provide an appropriate protection curve when non-reclosing

operation is required, for example, when closing onto a fault.

In Single Shot Operation the controller goes directly to lockout after one trip and will not auto-reclosing.

Item Range Def. Step Unit Comment

Single Shot Time 0~180 10 1 sec

13.1.4 TC CURVE

FTU-R200 has 54 types of built-in TC curves including ANSI, IEC Standard curves. And customer can

define additional 4 curves as his own curves by using PC Software. Basically, built-in curves have inverse

time characteristrics, but can be easily adjusted by three parameters such as multiplier, time adder and

minimum response time. In engineering step, the selection and adjustments of TC curves shall be done

for the protection coordination with other protection devices in the feeder.

The follwing parameters are related to change and editing of TC curve’s characteristics.

ü Time Multiplier

ü Time Adder

ü Minimum Response Time

Time Multiplier is multiplied to the operating time of basic curve (TDM=1.0), then Time Adder is added

to the resulting operating time of the curve adjusted by multiplier. Minimum Response Time defines the

fastest operating time of the curve.

The following tables describe the built-in TC Curve Type and the corresponding numbers in the setting.

TC Curve graphs are shown in the appendix.

Setting No. 1 2 3 4 5 6 7 8 9 10

Curve A B C D E EI KP L M N

Setting No. 11 12 13 14 15 16 17 18 19 20

Curve NI P R T V VI W Y Z 1

Setting No. 21 22 23 24 25 26 27 28 29 30

Page 64: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 64

ISO 9001 certified Jin Kwang E & C Corp.

Curve 2 3 4 5 6 7 8 8* 9 11

Setting No. 31 32 33 34 35 36 37 38 39 40

Curve 13 14 15 16 18 N1 N2 N3 N4 F

Setting No. 41 42 43 44 45 46 47 48 49 50

Curve G H J LI 8+ 17 KG A* SI IM

Setting No. 51 52 53 54 55 56 57 58

Curve IV IE U8 U2 C1 C2 C3 C4

Curve Type Curve Name

Recloser Curves A,A*,B,C,D,E,F,G,H,J,KP,KG,L,M,N,P,R,T,V,W,Y,Z,

1,2,3,4,5,6,7,8,8*,8+,9,11,13,14,15,16,17,18

IEC Standard Curve

Standard Inverse(NI),Very Inverse(VI),Extremely

Inverse(EI)

Long-time Inverse(LI),Short-time Inverse(SI)

ANSI/IEEE Standard

Curve

Moderately Inverse(IM),Very Inverse(IV),Extremely

Inverse(IE),

Long-time Inverse(U8),Short-time Inverse(U2)

KEPCO Standard

Curve N1,N2,N3,N4

User Customized

Curve C1,C2,C3,C4

IEC, ANSI/IEEE, US STANDARD TC CURVE EQUATION

T = TDM · {a / (Mb - 1) +g}

TRESET = TDM · {t / (Mb - 1)}

T : Operate Time, TDM : Multiplier Setting, TRESET : Reset Time

Curve Type Standard α β γ τ

Standard Inverse(NI)

IEC

0.14 0.02 - -

Very Inverse(VI) 13.5 1 - -

Extremely Inverse(EI) 80.0 2 - -

Short-time Inverse(SI) 0.05 0.04 - -

Long-time Inverse(LI) 120 1 - -

Very Inverse(IV) IEEE

19.61 2 0.491 21.6

Extremely Inverse(IE) 28.2 2 0.1215 29.1

Page 65: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 65

ISO 9001 certified Jin Kwang E & C Corp.

Moderately Inverse(IM) 0.0515 0.02 0.114 4.85

Short-time Inverse(U2) CO2 0.2394 0.02 0.0169

4 2.261

Long-time Inverse(U8) CO8 5.95 2 0.18 5.95

13.1.5 EXAMPLE OF TC CURVE EDITING

3-parameters are applied in the follwing order. The values in the parenthesis are examples.

ü Time Multiplier : 1.5

ü Time Adder : 0.03

ü Minimum Response Time : 0.1

In the next figure, for example, the curve A is the basic curve. Assume the operating time of the

basic curve (A) at 16 times pickup current is 0.04 sec. When applying Time Multiplier, curve ‘A’

changes its shape, that is, the curve becomes less steep in t ime axis and operat ion

time becomes longer by a multiplier at the same current value like ‘B’ in the figure. The operating

time at 16 times pickup becomes 0.06 sec. Then Time Adder shall be applied. The operating time

of the resulting curve ‘C’ is 0.09sec. Finally Minimum Response Time cuts the curve part, which is

shorter than this time. Then the actual operating time of the example at 16 times becomes 0.1sec.

[ TC Curve Editing Example 1 ]

There are two additional definite time over-current elements in the controller. The next figure shows 3-

stage over-current protection characteristics. The third stage is prepared for instantaneous protection.

Therefore the harmonic restraint is not applied to third stage elements, but the second stage definite

time over-current element.

Page 66: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 66

ISO 9001 certified Jin Kwang E & C Corp.

[ TC Curve Editing Example 2 ]

13.1.6 AUTO RECLOSING SEQUENCE

The FTU-R200 supports 3-shot reclosing with sequence coordination.

For Permanent fault, under the condition of reclosing enabled, no other restraints such as cold-load,

inrush and no High Current Trip, recloser will be locked out to open the Reclosing Count repeating trip

and reclose according to the preset settings.

Item Range Def. Step Unit Comment

Phase

Operation Count 1~4 4 1

Instantaneous Count 0~4 2 1

Earth

Operation Count 1~4 4 1

Instantaneous Count 0~4 2 1

Phase/ Earth Reclosing

Reclose Interval 1st 0.5~180 0.6 0.1 sec

Reclose Interval 2nd 1~180 2 1 sec

Reclose Interval 3rd 1~180 15 1 sec

Reset Time 3~180 30 1 sec

Page 67: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 67

ISO 9001 certified Jin Kwang E & C Corp.

SEF Reclosing

Operation Count 1~4 4 1

Reclose Interval 1st 0.5~180.0 0.6 0.1 sec

Reclose Interval 2nd 1~180 2 1 sec

Reclose Interval 3rd 1~180 15 1 sec

Reset Time 3~180 30 1 sec

For example in the below figure, the reclosing sequence is organized in 2F2D, which means

the Recloser protection function operates as Instantaneous(Fast) element during first 2 reclosing shots

and operates as Time-Delayed element during last 2 reclosing shots. This composition also can be

configured.

[ Permanent Fault: 3 shot Reclosing & 2F2D ]

For temporary fault, if the fault is removed before the preset Reclosing Count and no fault is detected

during the preset Reset Time, then the reclosing sequence is initialized to normal operation standby

mode. When a fault is detected again during the Reset Time, the Recloser will be locked out after the

remaining reclosing counts excluding the previously operated reclosing counts.

Page 68: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 68

ISO 9001 certified Jin Kwang E & C Corp.

[ Temporary Faults: Fault Removal during 1st Reclosing Interval ]

13.1.7 SEQUENCE COODINATION

In case that there are over 2 Reclosers which operate in serial connections, Sequence Coordination

function prevents unnecessary trip of source-side Recloser by instantaneous element due to load-side

fault. When this function is set to on and the fault is restored to normal state by load-side Recloser

during source-side Recloser’s time-delayed operation, source-side Recloser only increments the

reclosing counts without tripping. However, source-side Recloser performs tripping at the last reclosing

count. If the Reclosing function is disabled, Sequence Coordination function is no longer carried out.

Item Range Def. Step Unit Comment

Seq. Coordination Active OFF/ON OFF

For Sequence Coordination, the following setting items should be issued and checked precisely between

serially connected Reclosers.

ü Identical Protection Characteristics such as TC Curves, Total Operation Count,

Instantaneous Operation Count

ü Identical Reclosing Interval(Dead Time)

ü Source-side TC Curve Time Delay Over 100msec than Load-side

ü Source-side Reset Time longer than Load-side longest Reclosing Interval

(to Prevent Source-side Recloser reset during Load-side Reclosing action)

Page 69: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 69

ISO 9001 certified Jin Kwang E & C Corp.

[ Operation of Sequence Coordination ]

13.2 COLD LOAD PICKUP

Cold Load Pickup is the phenomenon that takes place when a distribution circuit is re-energized

following an extended outage of that circuit. Cold load pickup is a composite of two conditions: inrush

and loss of load diversity. The magnitude of cold load pickup current is a combination of non-diverse

cyclic load current, continuously operating load current, transformer magnetizing current, capacitor

inrush current, etc. The combination can result in current levels that are significantly higher than normal

peak load levels. Cold load pickup current can be high enough to cause instantaneous overcurrent

and/or time overcurrent relays to operate.

Cold load pickup is primarily an overcurrent condition. If degraded voltage is also a concern, then the

application of voltage sensitive relays should also be considered.

Page 70: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 70

ISO 9001 certified Jin Kwang E & C Corp.

[ Cold Load Pickup Current Shape ]

In Cold Load Pickup mode, without changing operational characteristics, pickup level is changed by the

times of Cold Load Multiplier (0~10) and the characteristics of time-delayed element operate even if the

setting is in the Instantaneous element. If the transient current goes down and retrains below the pickup

level within Cold Load Duration, then the normal sequence mode is restored after Cold Load Restore

Time. The Cold Load Restore Time is fixed value of 30msec. These setting exist for both phase fault and

earth fault separately, and the value ‘0’ of Cold Load Multiplier means Cold Load Pickup Function

disabled. Normaly Reclosing Sequence mode is applied.

Item Range Def. Step Unit Comment

Phase Detection

Pickup Multiplier 0~10 2 1 ‘0' means disable.

Duration Time 0.00~60.00 3.00 0.01 sec

Earth Detection

Pickup Multiplier 0~10 2 1 ‘0' means disable.

Duration Time 0.00~60.00 3.00 0.01 sec

Page 71: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 71

ISO 9001 certified Jin Kwang E & C Corp.

13.3 SENSITIVE EARTH FAULT(SEF) DETECTION

On the non-grounded network, it is hard to detect fault current because ground current of non-

grounded network is much low. Therefore, FTU-R200 is designed to measure zero-sequence values from

either external core Balanced Current Transformer (or ZCT) or Residual Connection of 3 Phase Current

Transformers to detect earth fault in the non-grounded network. This function is generally called SEF

detection.

In case of earth fault in the non-grounded network, since very small fault current due to line

capacitance component flows into the fault point from both sides, SEF detection also considers the fault

direction even in the radial network. Maximum Torque Angle is for setting the phase difference between

zero-sequence voltage and zero-sequence current, and the protection zone is between -90° and +90°

on the basis of Maximum Torque Angle. And it can be used for alarm or Trip.

[ Phase Diagram of SEF ]

Page 72: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 72

ISO 9001 certified Jin Kwang E & C Corp.

13.4 DIRECTIONAL BLOCKING

Directional Blocking is a protection feature that restricts tripping on faults to a designated side of the

recloser. It prevents nuisance tripping if particular network conditions are causing ‘False’ earth faults. In

radial systems Directional Blocking prevents nuisance tripping by blocking faults in the reverse direction

and only responding to faults in the foward direction.

Protect for faults in the forward and reverse direction. A forward fault may use a different time-current

curve and setting to a reverse fault (i.e. these are individually selectable). Both the forward protection

and reverse protection are operating at the same time. This is an additional protection feature.

Item Range Def. Step Unit Comment

Phase Detection

Trip Direction OFF/FWD/

REV/ALL FWD

3V1 Threshold 0~100 20 1 %

3I1 Threshold 0~100 20 1 %

3I1 Max. Torque Angle 0~355 60 5 Degree

Earth Detection

Trip Direction OFF/FWD/REV/

ALL FWD

Item Range Def. Step Unit Comment

Pickup Current(3I0) 2~20 5 1 A

Pickup Voltage(-3V0) 10~80 30 1 % Rated Phase

Voltage

Max. Torque Angle 0~345 90 15 Degree Leading

Detection Time 0.1~30.0 1.0 0.1 sec

Inrush Block NO/YES YES

Function In Use

OFF/

ALARM/

TRIP

OFF

Page 73: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 73

ISO 9001 certified Jin Kwang E & C Corp.

-3V0 Threshold 0~100 20 1 %

3I0 Threshold 0~100 20 1 %

3I0 Max. Torque Angle 0~355 60 5 Degree

13.5 INRUSH RESTRAINTS

Inrush Restraint works by raising the phase and earth currents for a short period of time to allow the

inrush current to subside.

Inrush current is an over-current higher than pickup current level, which is mainly caused by

transformer’s excitation current at closing action. To distinguish inrush current from load current, 2nd

harmonics percentage is adopted as a criterion.

When, in the setting, ‘Fault Detection-Inrush Block’ is set to ‘Yes’ and ‘Fault Detection-Inrush

Detection-Function In Use’ is set to ‘ON’, inrush current over pickup level is considered as normal load

current and reclosing sequence is not processed.

This Function can be used to detect magnetizing inrush condition by comparing 2nd harmonic

component to fundamental frequency component of current.

Item Range Def. Step Unit Comment

2nd Harmonic 5~50 20 1 %

Detection Time 0.02~1.00 0.02 0.01 sec

Function In Use OFF/ON ON

13.6 OPEN LINE DETECTION(LOSS OF PHASE)

Open Line is detected by Under Voltage characteristics at unbalanced condition.

When the voltage on one or two phases drops below the ‘Volt OFF Level’ setting, the ‘Delay Time’ starts

running. If the voltage on those phases stays below ‘Volt OFF Level’ setting until the ‘Delay Time’ timer

expires, the Loss of Phase will be detected.

If the voltage on detected phase rises to the ‘Vol ON Level’ setting, the Loss of Phase is released

immediately.

Page 74: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 74

ISO 9001 certified Jin Kwang E & C Corp.

Item Range Def. Step Unit Comment

Volt ON Level 50~90 80 5 %

Volt OFF Level 35~75 50 5 %

Delay Time 0.1~30.0 0.4 0.1 sec

Function In Use OFF/ON ON

13.7 PHASE SYNC. CHECK

Item Range Def. Step Unit Comment

Phase Difference 5~60 30 1 Degree

Dalay Time 0.1~30.0 0.1 0.1 sec

Function In Use OFF/ON ON

13.8 UNDER VOLTAGE PROTECTION

As the supplied voltage to load lowers down, there occur the weakness of illumination intensity and

shortening of life span for lighting load, and the damage to motors because of the over-current flow. To

cope with this situation of damages to equipment, under-voltage protection (UV) is used. UV of FTU

supports the delay time element. Furthermore, UV can be used to generate only alarm signal to

operator instead of trip signal to Recloser.

[ Functional Diagram for Under Voltage Protection ]

Page 75: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 75

ISO 9001 certified Jin Kwang E & C Corp.

Item Range Def. Step Unit Comment

Pickup Level 0.30~0.95 0.80 0.01 PU

Delay Time 0.0~180.0 1.0 0.1 sec

Function In Use OFF/ARAMP/TRIP OFF

13.9 OVER VOLTAGE PROTECTION

On the other hand, as the supplied voltage goes up behind the regular load voltage, there occur some

problems of equipment deterioration, insulation breakdown, equipment life span shortening, etc. Over

Voltage Protection (OV) manages this situation. OV of FTU supports the delay time element. OV also

can be used to generate only alarm signal to operator instead of trip signal to Recloser.

[ Functional Diagram for Over Voltage Function ]

Range Def. Step Unit Comment

Pickup Level 1.05~1.50 1.20 0.01 PU

Delay Time 0.0~180.0 1.0 0.1 sec

Function In Use OFF/ARAMP/TRIP OFF

Page 76: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 76

ISO 9001 certified Jin Kwang E & C Corp.

13.10 UNDER FREQUENCY PROTECTION

Under Frequency protection (UF) element is used into expenditure that detect under frequency and

separated load or generator. Under Frequency demands for power increase or occurs in control failure

of generator.

Under Frequency protection element acts in case of voltage more than ‘Voltage OFF Level’ is approved

to Voltage A-Phase. UF of FTU supports the delay time element. Furthermore, UV can be used to

generate only alarm signal to operator instead of trip signal to Recloser.

13.11 MULTIPLE PROTECTION GROUPS

The FTU-R200 supports up to 4 Protection Groups, each of which can be confiqured with completely

separate protection characteristics with different inverse time curves and setting currents. The number of

protection group avaliable to the operator can be configured.

And FTU-R200 support Automatic Protection Group Selection. Automatic Protection Group Selection is

used to change the protection group depending on the direction of power flow. This allows the

Recloser to be correctly graded with devices downstream regardless of the power flow direction.

Item Range Def. Step Unit

Default Group 1~4 1 1

ADGS(Automatic Default Group Selection)

Function OFF/ON OFF

Reverse Group 1~4 1 1

Item Range Def. Step Unit Comment

Pickup 47.00~59.98 49.80 0.01 Hz

Dalay Time 0.03~10.00 0.10 0.01 sec

Function In Use OFF/ARAMP/TRIP OFF

Page 77: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 77

ISO 9001 certified Jin Kwang E & C Corp.

14. CONFIGURATION SETTINGS

14.1 I/O CONFIGURATION

14.1.1 AC RATINGS

Item Range Def. Step Unit Comment

Line Configuration Y-G/DELTA Y-G

Systme Frequency 50/60 50 40 Hz

Rated Voltage (L-L) 1000~30000 22900 10 V Phase to Phase

Reference Voltage (L-N) 1000~30000 13200 10 V Phase to Earth

Reference Phase A/B/C A

CB Operating Time 0~35 1 1 ms

CT Ratio 1~5000 1000 1

CT Direction FWD/REV FWD

NCT Ratio 1.0~5000.0 133.3 0.1

NCT Direction FWD/REV FWD

Phase Rotation A-B-C/A-C-B A-B-C

Sample Record

Frequency 16/32/64/128 128

14.1.2 SWITCH INSTALLATION

The FTU-R200 provides a function to set ‘Reference Phase’ and the ‘CT Direction’ according to

the switch installation position and the current flowing direction.

The following figure shows the general and ‘assumed-default’ case of switch installation, in which the

distribution lines with current A, B, C are connected to the phase A, B, C terminals of the switch, and the

current is flowing A/B/C to R/S/T of the switch. In this case, the ‘Referece Phase’ setting value should

‘A’, which means that the phase of current flowing into the phase A terminal of the switch is ‘A’, In

addition, the ‘CT Direction’

Page 78: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 78

ISO 9001 certified Jin Kwang E & C Corp.

setting value should be ‘Foward’, which means that the current is flowing in the direction from the

phase A/B/C terminals to the R/S/T terminals of the switch.

[ Switch installation position and the current flowing direction - Case 1 ]

The following figure shows another case of switch installation, in which the distriburion lines with

current A, B, C are connected to the phase A, B, C terminals of the switch, and the current is flowing

from R/S/T to A/B/C of the switch. In this case, the ‘Referece Phase’ setting value should ‘A’, which

means that the phase of current flowing into the phase A terminal of the switch is ‘A’, In addition, the

‘CT Direction’ setting value should be ‘Reverse’, which means that the current is flowing in the

direction from the phase R/S/T terminals to the A/B/C terminals of the switch.

[ Switch installation position and the current flowing direction - Case 2 ]

Page 79: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 79

ISO 9001 certified Jin Kwang E & C Corp.

The following figure shows another case of switch installation, in which the distriburion lines with

current A, B, C are connected to the phase C, B, A terminals of the switch, and the current is flowing

from R/S/T to A/B/C of the switch. In this case, the ‘Referece Phase’ setting value should ‘C’, which

means that the phase of current flowing into the phase A terminal of the switch is ‘C’, In addition, the

‘CT Direction’ setting value should be ‘Reverse’, which means that the current is flowing in the

direction from the phase R/S/T terminals to the A/B/C terminals of the switch.

[ Switch installation position and the current flowing direction - Case 3 ]

The following figure shows another case of switch installation, in which the distriburion lines with

current A, B, C are connected to the phase C, B, A terminals of the switch, and the current is flowing

from A/B/C to R/S/T of the switch. In this case, the ‘Referece Phase’ setting value should ‘C’, which

means that the phase of current flowing into the phase A terminal of the switch is ‘C’, In addition, the

‘CT Direction’ setting value should be ‘Forward’, which means that the current is flowing in the

direction from the phase A/B/C terminals to the R/S/T terminals of the switch.

[ Switch installation position and the current flowing direction – Case 4 ]

Page 80: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 80

ISO 9001 certified Jin Kwang E & C Corp.

14.1.3 DEMAND SETTING

The FTU calculates and stores average of currents and active, reactive powers during the demand

interval, which is configurable as 5, 10 or 15 minutes. The buffer has 1023 demands. Also FTU stores

daily peak demand up to 1023.

Item Range Def. Step Unit Comment

Block Interval 15/30/60 15

Roll Interval 1/5/15/30/60 15

14.1.4 WAVE TRIGGER

Item Range Def. Step Unit Comment

Sample Record

Frequency 16/32/64/128 128

Pre-1st Cycle 1~5 2 1 Cycle

Post-2nd Cycle 1~5 2 1 Cycle

Pre-2nd Trigger Cycle 1~10 10 1 Cycle

14.1.5 CLOSE INTERLOCK

Item Range Def. Step Unit Comment

Live Load NO/YES YES

Sync. Fail NO/YES YES

14.1.6 FI RESET SELECT

Item Range Def. Step Unit Comment

FI Reset MANUAL/AUTO MANUAL

Page 81: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 81

ISO 9001 certified Jin Kwang E & C Corp.

14.1.7 VOLTAGE DISPLAY

The controller supports two voltage display of LCD.

Item Range Def. Step Unit Comment

Voltage Display L-N/L-L L-N L-N : Phase to Earth

L-L : Phase to Phase

14.2 POWER QUALITY MEASUREMENT FUNCTION

14.2.1 VOLTAGE & CURRENT UNBALANCE

Voltage unbalance (or imbalance) is a condition in which the maximum deviation from the average of

the three-phase voltages or currents, divided by the average of the three-phase voltage or currents,

expressed in percentage. Voltage unbalance can be the result of blown fuses in one phase of a three-

phase capacitor bank. Severe voltage unbalance greater than 5% can cause damage to sensitive

equipments.

14.2.2 SHORT-DURATION VOLTAGE VARIATION

There are three types of short-duration voltage variations, namely, instantaneous, momentary and

temporary, depending on its duration. Short-duration voltage variations are caused by fault conditions,

energization of large loads, which require high starting currents or loose connections in power wiring.

Depending on the fault location and the system conditions, the fault can generate sags, swells or

interruptions. The fault condition can be close to or remote from the point of interest. During the actual

Item Range Def. Step Unit Comment

Voltage Unbalance

Detection Level 0~100 30 1 %

Detection Time 0.1~60.0 1.0 0.1 sec

Current Unbalance

Detection Level 0~100 30 1 %

Detection Time 0.1~60.0 1.0 0.1 sec

Page 82: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 82

ISO 9001 certified Jin Kwang E & C Corp.

fault condition, the effect of the voltage is of short-duration variation until protective devices operate to

clear the fault.

14.2.2.1 SAG

A sag (also known as dip) is a reduction to between 0.5 and 0.99 pu in RMS voltage or current at the

power frequency for a short period of time from 0.5 to 10 cycle. A 10% sag is considered an event

during which the RMS voltage decreased by 10% to 0.9 pu. Voltage sags are widely recorgnized as

among the most common and inportant aspects of power quality problems affecting industrial and

commercial customers. They are particularly troublesome. Since they occur randomly and are difficult to

predict.

Volatge sags are normally associated with system faults on the distribution system, sudden increase in

system loads, lightning strikes or starting of large load like induction motors. It is not possible to

eliminate faults on a system. One of the most common causes of faults

occuring on high-volatage transmission systems is a lightning strike. When there is a fault caused by a

lightning strike, the voltage can sag to 50% of the standard range and can last from four to seven cycles.

Most loads will be tripped off when encounter this type of voltage level. Possible effect of voltage sags

would be system shutdown or reduce effciency and life span of electrical equipment, particularly motors.

Equipment sensitivity to voltage sag occurs randomly and has become the most serious power quality

problem affecting many industries and commercial customers presently. An industrial monitoring

program determined an 87% voltage disturbances could be associate to voltage sags. Most of the fault

on the utility transmission and distribution system are single line-to-ground faults (SLGF).

Item Range Def. Step Unit Comment

Detection Level 0.50~0.99 0.90 0.01 PU

Detection Time 0.5~10.0 2.0 0.5 Cycle

14.2.2.2 SWELL

A swell (also known as momentary overvoltage) is an increase in RMS voltage or current at the power

frequency to between 1.01 and 1.5 Pu for duration from 0.5 to 10 cycles. Swells are commonly caused

by system conditions, switching off a large load or energizing a large capacitor bank. A swell can occur

during a single line-to-ground fault (SLGF) with a temporary voltage rise on the unfaulted phases. They

are not as common as voltage sags and are characterized also by both the magnitude and duration.

During a fault condition, the severity of a voltage swell is very much dependent on the system

Page 83: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 83

ISO 9001 certified Jin Kwang E & C Corp.

impedance, location of the fault and grounding. The effect of this type of disturbance would be

hardware failure in the equipment due to overheating.

Item Range Def. Step Unit Comment

Detection Level 1.01~1.50 1.20 0.01 PU

Detection Time 0.5~10.0 2.0 0.5 Cycle

14.2.2.3 INTERRUPTION

An interruption occurs when there is a reduction of the supply voltage or load current to between 0.1

and 0.49 pu for duration from 0.5 to 10 cycle. Possible causes would be circuit breakers responding to

overload, lightning and faults. Interruptions are the result of equipment failures, power system faults and

control malfunctions. They are characterized by their duration as the voltage magnitude is always less

than 10% of the nominal. The duration of an interruption can be irregular when due to equipment

malfuctions or loose connections.

The duration of an interruption due to a fault on the utility system is determined by the utility

protective devices operating time.

Item Range Def. Step Unit Comment

Detection Level 0.10~0.49 0.10 0.01 PU

Detection Time 0.5~10.0 2.0 0.5 Cycle

14.2.3 VOLTAGE & CURRENT ALARM

The Total Harmonic Distortion, or THD, of a sigmal is a measurement of the harmonic distortion present

and is defined as the ratio of the sum of the powers of all harmonic components to the power of the

fundamental frequency.

Item Range Def. Step Unit Comment

Voltage

Alarm Level 0.5~100.0 0.0 0.1 %

Detection Time 0.2~60.0 0.4 0.2 sec

Page 84: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 84

ISO 9001 certified Jin Kwang E & C Corp.

Current

Alarm Level 0.5~100.0 0.0 0.1 %

Detection Time 0.2~60.0 0.4 0.2 sec

14.3 COMMUNICATION

14.3.1 PORT PARAMETERS

SERIAL PORT

Item Range Def. Step Unit

Speed 1200/2400/4800/9600/19200 1200

Slave Adderss 1~65534 1 1

Protocol DNP/IEC101/IEC104 DNP

Port RS232C/RS485 RS232C

DIAL UP

Item Range Def. Step Unit

Dial-up Mode DISABLE/ENABLE DISABLE

Phone Number 20 Digit 1

Auto Hang-up Time 0~255 5 1 sec

TCP/IP PORT

Range Def. Step Unit

IP Address - 0.0.0.0

Subnet Mask - 255.255.255.

0

Gateway - 0.0.0.0

DNP Port 0~65535 20000 1

IEC Port 0~65535 2404 1

Page 85: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 85

ISO 9001 certified Jin Kwang E & C Corp.

MODEM CONTROL

Item Range Def. Step Unit

Line 2-WIRE/4-WIRE 4-WIRE

RTS Off Delay 10~500 50 10 ms

CTS Timeout 1~255 2 1 sec

DCD Timeout 0.1~30.0 5.0 0.1 sec

14.3.2 DNP 3.0 PARAMETERS

Item Range Def. Step Unit

D/L Retries 0~2 0 1

D/L Timeout 1~255 30 1 sec

D/L Confirm NO/YES/SOMETIMES SOMETIMES

A/L Retries 0~2 1 1

A/L Timeout 1~255 40 1 sec

Initial Unsolicited MSG NO/YES NO

Unsolicited Class 1

Delay Time 0~60 5 1 sec

Unsolicited Class 2

Delay Time 0~60 5 1 sec

Unsolicited Class 3

Delay Time 0~60 5 1 sec

Arm Timeout 1~255 15 1 sec

Unsolicited Address 0~65534 65534 1

Multi Frame Interval 10~500 100 10 ms

Unsolicited Class 1 DISABLE/ENABLE DISABLE

Unsolicited Class 2 DISABLE/ENABLE DISABLE

Unsolicited Class 3 DISABLE/ENABLE DISABLE

Page 86: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 86

ISO 9001 certified Jin Kwang E & C Corp.

14.3.3 IEC PARAMETERS

EC Parameters Range Def. Step Unit

Cyclic Period 0~60 0 1 sec

Arm Timeout 1~255 15 1 sec

Single Point Class CLASS1/CLASS2 CLASS1

Double Point Class CLASS1/CLASS2 CLASS1

Measured Point Class CLASS1/CLASS2 CLASS2

IEC101 PARAMETERS

Link Address Size 0~2 2 1

Common Address Size 1~2 2 1

Object Address Size 1~3 2 1

COT Address Size 1~2 1 1

Time Marker NONE/CP24/CP56 CP56

Single NACK Control NO/YES YES

IEC104 PARAMETERS

t0 Off Line Poll Period 1~255 30 1 sec

t1 Ack Period 1~255 15 1 sec

t2 SFrame Period 1~255 10 1 sec

t3 Test Period 1~255 20 1 sec

Page 87: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 87

ISO 9001 certified Jin Kwang E & C Corp.

15. STATUS MONITORING & CONTROL

15.1 SWITHCH CONTROL

Recloser can be controlled from remote or local operator place. Operator place can be changed only at

local front panel. ‘REMOTE CONTROL’ push button is to select the operator place. Operator place is

toggled between local and remote by pushing button. LED is lit if remote position is selected. FTU-R200

begins with remote position at power-up. Control is allowed only at the position selected.

Local switch control requires two-step operation. It’s for security of operation. ‘SELECT’ button should be

pushed before ‘CLOSE’ or ‘OPEN’. SELECT LED is lit if SELECT operation is valid. SELECT can be canceled

by pushing SELECT button again or automatically after SBO timeout without operation. CLOSE or OPEN

operation is valid while this LED is lit. Pushing CLOSE or OPEN button outputs switch control signal with

fixed time pulse which is configurable. Switch status change input which is auxiliary contacts of switch

stops continuing to output pulse. There are some interlock conditions to inhibit FTU from outputting

pulse signal.

Gas low, Switch handle lock, same status of switch auxiliary contacts ‘a’, ‘b’ are those. Close or open

pulse width shall be set longer than switch operating time.

Remote switch control is possible by using SCADA protocol DNP3.0 or IEC60870-5-101, IEC60870-5-104

FTU-R200 supports SBO (Select Before Operate) or Direct operate. If the operator place is set to ‘Local’,

remote control commands are refused. Pulse width of remote control command shorter than setting will

be overridden by local configuration

15.2 SWITCH STATUS MONITORING

FTU monitors switch open/close, gas and lock status through auxiliary contacts. FTU scans these

contacts input every 5 milliseconds. Switch open/close status is determined by double binary input,

normally open and closed contacts. Changes of all input status are saved as events with time tag in

history buffer. For each contact input, on-delay time can be applied. It’s adjustable within 10~500ms by

5ms step.

15.3 BATTERY MONITORING

FTU monitors external Lead-acid battery through the control unit, which are mounted on inner back-side

of control box. Battery voltage is supervised continuously during external AC supply loss. If over-

discharge condition occurred, the control unit sends alarm signal to RTU and disconnect battery in order

Page 88: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 88

ISO 9001 certified Jin Kwang E & C Corp.

to protect battery cell damage after 1-minute delay. The delay enables RTU to send alarm state to

remote station via communication. Also while AC supply is applied, battery test control activates this

function with connecting dummy battery load during test pulse, which is configurable. The test control

command can be ordered at local or remote.

16. MEASUREMENT

16.1 BASIC ELECTRIC QUANTITIES

FTU has 3-phase currents and 6 voltages input. DSP digitizes these signals and calculates various electric

quantities. These are basically based on fundamental frequency components. DSP use FFT (Fast Fourier

Transform) algorithm to get the components. Also DSP calculates true RMS of 3-phase currents and

voltages which include system frequency components and 2nd~31th harmonics. Actually harmonic

components over than 31th are attenuated by analog filters. Electric quantities calculated are listed in

the following.

l Currents (Ia, Ib, Ic, In) RMS, Phase Angle, True RMS

l Voltage (Va, Vb, Vc, Vr, Vs,

Vt)

RMS, Phase Angle, True RMS

l Apparent Power A-Phase, B-Phase, C-Phase, 3-Phase Total,

l Active Power A-Phase, B-Phase, C-Phase, 3-Phase Total,

l Reactive Power A-Phase, B-Phase, C-Phase, 3-Phase Total,

l Power Factor A-Phase, B-Phase, C-Phase, 3-Phase Total,

l Va-Vr Phase Angle Difference

l Current, Voltage Unbalance

l Frequency, Temporature

In the above items listed, active power, reactive power values are signed integer. Sign represents power

flow or if loads are inductive or capacitive. Also power factor has lead/lag state value separately.

Currents and voltages have phase angles, which are relative phase angles compared to the reference Va.

These angles are useful to monitor the phase sequence and imbalance of distribution line.

16.2 SEQUENCE COMPONENTS

FTU provides the sequence components of 3-phase currents and voltages. They are positive sequence

current (I1) and voltage (V1), negative sequence current (I2) and voltage (V2), and zero sequence voltage

(V0) which are calculated by 3-phase phasor quantities. This information can be used to monitor

imbalance of distribution line.

Page 89: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 89

ISO 9001 certified Jin Kwang E & C Corp.

16.3 HARMONICS

FTU extracts harmonic components from 3-phase current and voltage signals by using FFT (Fast Fourier

Transform). It provides 2nd to 31st harmonic magnitudes and THDs (Total Harmonic Distortion) for each

phase. THD is the total harmonic percentage to the fundamental frequency component. FTU also

calculates and provides 3-phase THD. These values may be used to monitor the power quality of

distribution line.

16.4 ENERGY

FTU provides active energy, reactive energy for each phase or 3-phase total. Also import, export energy

are accumulated on separate register. Units of energy are kWh, kVarh, which represent primary

distribution line energy flow. The values are represented by 16-bit rollovers kWh, kVarh counters which

are available at remote or local. Power calculation for energy is based on the fundamental frequency

component. It’s not for billing purpose, but for load management. Proper energy accumulation needs

that SCADA read energy counter with reset from FTU and accumulate it on SCADA’s local register by

periods shorter than the expected rollover time of the counter.

[Four-quadrant power flow directions ]

16.5 DEMAND CURRENTS AND POWER

FTU calculates and stores average of currents and active, reactive powers during the demand interval,

which is configurable as 5, 10, or 15 minutes. The buffer has 1023 demands. Also FTU stores daily peak

demand up to 1023.

Page 90: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 90

ISO 9001 certified Jin Kwang E & C Corp.

17. MAINTENANCE SOFTWARE

17.1 OVERVIEW

FTU-R200 has a dedicated setting and operation tool, FTUMan. This tool is operated on PC or

Notebook, and through RS232C port on front panel of FTU-R200. For this communication, MODBUS

protocol is used.

It supports the follwing features.

ü Setting & Configuration changes

ü Event & Waveform load

ü Measurement & Status display

ü Waveform File upload and convert

ü SCADA monitors protocol data frame between devices

[ Overview of FTUMans ]

Page 91: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 91

ISO 9001 certified Jin Kwang E & C Corp.

17.2 OPERATION OF FTUMan

17.2.1 MENU

n File

New Closes the current file and allows the creation of a new file

Open Closes the current file and opens a standard window file selection dialog. An

existing FTU File (*.f2s) can be selected and opened.

Save Saves the current file to the hard drive. If the file is new and this is the first

time it has been saved, the Save As dialog will be opened allowing the user

to type in a name before saving.

Save As Opens a standard Windows Save As dialog box. This allows an existing file to

be saved under a new name.

Exit Closes the current file and exits the tool.

n Comm

Comm.Config Opens a window for communication configuration dialog.

Comm.Connection Starts communication with FTU-R200

Comm.Disconnection Stops connecting with FTU-R200

[ Comm. Configuration Window ]

Port Select a serial Port of Laptop

Baud Rate Make to the transmission medium per second of in a digitally signal

Retry Set up the count if it failed to connect

Timeout Set up the time to connect

Page 92: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 92

ISO 9001 certified Jin Kwang E & C Corp.

n Command

Clock Setting Set RTC Time of FTU-R200

[ Clock Setting Window ]

Device Time Gets the current time per 1 second from FTU-R200.

Setting Time The operator can set aside time.

Use System Time The operator can use PC’s time.

Write Write RTC time to FTU-R200

Close Close this window

Factory Initialization Reset to factory defaults.

Warning: Restoring FTU-R200 to factory defaults will erase

all previous setting, configuration and event.

[ Factory Initialization Message Window ]

Page 93: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 93

ISO 9001 certified Jin Kwang E & C Corp.

n Tools

n View

Toolbar Show or hide the toolbar.

Status Bar Show or hide the status bar.

Monitoring Bar Show or hide the monitoring bar. The monitoring bar shows

communication status with FTU-R200.

n Help

The Help Menu opens a window for FTUMan’s program version and information.

17.2.2 TOOLBAR

Below the menu is a toolbar with 9 buttons.

[ Toolbar of FTUMan ]

Upload Read input or ouput data from FTU-R200.

Download Write input or ouput data to FTU-R200.

About Opens a window for FTUMan’s program version and information.

Protocol Monitoring Protocol monitoring command activation or deactivation.

IO Configuration Run the IOConfig program for I/O setting.

The IOConfig is explained in the Section 10.

DNP3.0

Index Configuration

Run the DNPConfig program for DNP index configuration.

The DNPConfig is explained in the Section 11.

Waveform

Evaluation Tool

Run the EvalTool program for analysis waveform data.

The EvalTool is explained in the Section 12.

Page 94: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 94

ISO 9001 certified Jin Kwang E & C Corp.

17.2.3 STATUS BAR

[ Status Bar ]

MODEL Model Name

F/W Firmware Version

PORT Serial Port Number and Speed

MODE Communication Status

17.2.4 MONITORING BAR

[ Monitoring Bar ]

Some performance is finished

Reads data from FTU-R200

Wirtes the setting value on FTU-R200

When Factory Initialization occurs.

Error of connection or operation

Connect or Disconnect between PC and FTU-R200

When the time set is completed

17.2.5 FUNCTION AND CONFIGURATION SETTING

In Function and Configuration window, existing setting values of FTU-R200 can be viewed through

‘Upload’ button, or setting values are edited and downloaded to FTU-R200 by clicking ‘Download’

button to apply new setting values to FTU-R200.

In some cases, operators require to save and reuse these edited setting values. To satisfy this request,

FTUMan tool has ‘New’, ‘Open’ and ‘Save’ menu items in File Menu. The file extension name is ‘f2s’.

Page 95: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 95

ISO 9001 certified Jin Kwang E & C Corp.

If you set up the ADGS (Auto Detection Group Setting) Function ‘ON’, you can check the current

direction ‘Forward’ or ‘Reverse’.

[ Tree View for function and configuration ]

Function has 5 contents, 4 setting groups and

active group setting. Each group has protection

setting value for FTU-R200.

Configuration has 3 contents for I/O, PQM and

communication. Communication seperated 3

contens, for Port, DNP3.0 and IEC protocol

parameter to communication for SCADA.

In tree view, if you choose some content, icon will

be replaced with a red icon from a blue icon. And

show setting parameters related content.

How to edit the setting value? Click the content in tree view and editing value using double-click or

Enter-Key. If you changed value, the text color is changed in red.

[ before the Change ]

[ after the Change ]

Page 96: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 96

ISO 9001 certified Jin Kwang E & C Corp.

And, in event window has a following pop-up menu. In the Tree View, select ‘FUNCTION’or

‘CONFIGURATION’ or all sub contens, and press the right-click pop-up menu is avaliable.

[ Pop-up Menu for Event Window ]

If you click ‘Upload’ Button, the setting

parameters related selected contents in the

tree view reads from FTU-R200.

Also, if you click ‘Download’ Button, the

setting parameters related selected contents

in the tree view writes to FTU-R200.

[ Input Password Dialog ]

When the Factory Initialization or all of information are changed, Input Password Window will be

appeared.

Note: Default Password is ‘ftuman’.

17.2.6 EVENT

In Event window, operators can list up all the event records, which are stored in the memory of FTU-

R200 by clicking ‘Upload’ button. Also 8 kinds of events are stored. Each event type of event can be

separately uploaded from FTU-R200 and can save to CSV format file. Time Resolution for event

recording is 5 msec and scanning interval is 1 msec.

And, in event window has a following pop-up menu. In the Tree View, select ‘EVENT’ and press the

right-click pop-up menu is avaliable.

Page 97: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 97

ISO 9001 certified Jin Kwang E & C Corp.

[ Pop-up Menu for Event Window ]

Upload Reads the selected events in the tree view.

Clear All Events Delete all event stored.

Clear Fault Events Delete only fault events.

Save to CSV File Current event saves to CSV (Comma-Saperated Values file) file

format.

ü CSV File

A Comma-Seperated Values (CSV) file is used for the digital storage of data structed in a table of lists

form, where each associated item (member) in a group is in association with others also seperated by

the commas of its set.

Each line in the CSV file corresponds to a row in the table. Within a line, fields are seperated by

commas, each field belonging to one table column. Since it is a common and simple file format, CSV

files are often used for moving tabular data between two different computer programs, for example

between a database program and a spreadsheet program.

Page 98: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 98

ISO 9001 certified Jin Kwang E & C Corp.

n I/O Event

[ I/O Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

Description Information of generated binary event.

Status Occured contact points and binary status, OFF/ON/AUTO

Page 99: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 99

ISO 9001 certified Jin Kwang E & C Corp.

n FUNCTION EVENT

[ Function Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

Description Operation of protection functions.

Status Occurred function event status, OFF/ON.

Page 100: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 100

ISO 9001 certified Jin Kwang E & C Corp.

n SYSTEM EVENT

[ System Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

Description Information of generated event like set value changed, triggered by

power reset and system error or self-diagnosis.

Status Occurred event position and detailed description of system error or self-

diagnosis.

Page 101: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 101

ISO 9001 certified Jin Kwang E & C Corp.

n FAULT EVENT

[ Fault Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

OC Detecting over-current.

SEF Detecting Sensitive Earth Fault.

UFR Detecting Under Frequency.

DIR Fault current direction.

Inrush Detecting inrush restraint.

Ia, Ib, Ic, In, V0 Fault current and zero-sequency voltage

Group Current setting group

Page 102: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 102

ISO 9001 certified Jin Kwang E & C Corp.

n PQM EVENT

[ PQM Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

Description The occurance history of power quality function change.

Value RMS value of voltage when moment voltage change occurs.

Unit: kV

Duration Duration time of moment voltage change by msec.

Unit: msec

Page 103: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 103

ISO 9001 certified Jin Kwang E & C Corp.

n DEMAND CURRENT EVENT

[ Demand Current Event Window ]

Index Event sequence number, the recent events that occurred is displayed on

top.

Date & Time Event occurred time.

Ia, Ib, Ic, In Demand current of each phase and neutral.

Page 104: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 104

ISO 9001 certified Jin Kwang E & C Corp.

n DEMAND POWER EVENT

[ Demand Power Event Window ]

Index Event sequence number, the recent events that occurred is

displayed on top.

Date & Time Event occurred time.

kWa, kWb, kWc, kW3ph 3-phase total and each phase kW.

kVARa, kVARb,

kVARc, kVAR3ph

3-phase total and each phase kVAR.

Page 105: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 105

ISO 9001 certified Jin Kwang E & C Corp.

n DAILY MAXIMUM CURRENT EVENT

For more details, refer to Demand Current Event.

n DAILY MAXIMUM POWER EVENT

For more details, refer to Demand Power Event.

17.2.7 MEASUREMENT

Operators can monitor all kinds of measurement values such as current, voltage, sequence value, power

and energy, etc. And, FTU-R200 has the function of Harmonic Analysis, therefore up to 31st harmonics

RMS value and THD for current and voltage are measured and displayed. Lastly, counter values and

accumulation data are displayed.

FTUMan has 6 kinds of Mesurement window. The measurement value updates per 1 second.

n BASIC VALUE

Operators can check the basic value like load or source volatage, current including RMS, Phase Angle

and True RMS also apparent, active and reactive power. And it shows unbalance frequency, temperature

and so on.

[ Basic Mesurement Window ]

Page 106: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 106

ISO 9001 certified Jin Kwang E & C Corp.

n SEQUENCE VALUE

It shows zero, positive and negative sequence of source or load voltage and current.

[ Sequence Value Window ]

Page 107: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 107

ISO 9001 certified Jin Kwang E & C Corp.

n POWER

You can check active, reactive and apparent power of each phase or 3-phase. It also shows lag of each

phase or lead.

[ Power Winodw ]

Page 108: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 108

ISO 9001 certified Jin Kwang E & C Corp.

n ENERGY

FTU-R200 provies imported or exported energy according to conductive, inductive energy of each phase

or 3-phase total.

[ Energy Window ]

Page 109: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 109

ISO 9001 certified Jin Kwang E & C Corp.

n RMONICS

It displays THD and each harmonics value of voltage and current. It shows from 2nd to 31st per 1 second.

[ Harmonics Window ]

Page 110: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 110

ISO 9001 certified Jin Kwang E & C Corp.

n COUNTER

It basically shows restart, fault, PQM and THD counter and total interruption time.

[ Counter Window ]

Restart Show restarts time and its count.

Fault Counter Show the total fault count of each, neutral phase and Switch

Trip.

PQM Counter Show the short-duration voltage variation event count.

Total Interruption Time Show the total interruption time.

THD Counter Show the each or total phase’s current and voltage THD

counts.

Page 111: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 111

ISO 9001 certified Jin Kwang E & C Corp.

17.2.8 STATUS

In status window, all the status indications and command are displayed.

[ Status Window ]

When operator supervises some command in status window, this window generated. Upper box shows

device name, bottom box displays command name. If you click the ‘OK’ button, command will be

operated and window will be disappeared.

[ Commnad Window ]

Page 112: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 112

ISO 9001 certified Jin Kwang E & C Corp.

17.2.9 WAVEFORM

In waveform window displays Fault and PQM waveforms list stored in FTU-R200.

FTU-R200 can record and store the data for up to 8 faults, up to 6 PQM and 1 waveform by manual

triggering. And each waveform has the data of 20 cycles at 128 samples.

How to upload waveforms are as follow. First, by using the ‘Upload’ command reads a list of stored

waveforms on the FTU-R200.

[ Waveform List Uploaded ]

To import the waveform from FTU-R200, select a row and double click, you upload the following

message window appears.

Page 113: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 113

ISO 9001 certified Jin Kwang E & C Corp.

[ Message Window ]

If you click the ‘OK’ button, opens standard Windows Save As dialog box and enter the file name, and

click the Save button. And then will start uploading waveform.

The follwing window shows the progress for uploading.

[ Progress Window ]

The file is stored in the COMTRADE file format by converting. The stored file is avalilable the waveform

analysis by EvalTool. The EvalTool is explained in the Section 12. And, in waveform window has a

following pop-up menu. In the Tree View, select ‘WAVEFORM’ and press the right-click pop-up menu is

avaliable.

[Pop-up Menu for Waveform Window ]

Upload Read waveform list from FTU-R200.

Manual Trigger Capture current waveform by manual triggerring.

Clear Fault Waveforms Delete all fault waveform stored.

Clear PQM Waveforms Delete all PQM waveform stored.

Page 114: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 114

ISO 9001 certified Jin Kwang E & C Corp.

18. I/O CONFIGURATION TOOL

18.1 OVERVIEW

The ‘IO Config’ tool allows FTU users to custom I/O mappings.

[ Overview of IOConfig Tool ]

The I/O mapping is created using the tool and saved to an IO File (*.iom). Once a valid file has been

created, it is linked to the Recloser device.

The IOConfig tool is intended to be used off-line only. Mappings are created, saved and linked to

FTUMan while disconnected from the FTU. Once these tasks have been completed the user connects to

the device and writes the new mapping into the Recloser.

Warning: Make sure the IOConfig Tool is closed after a mapping has been edited. If the Tool is left

open while the Automatic Data Retriaval feature is running it may attempt to update a mapping file that

Page 115: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 115

ISO 9001 certified Jin Kwang E & C Corp.

is already open in the Tool. This will either cause the read operation to fail or result in a situation where

the newly read file differs from the file open within the Tool.

18.2 OPERATION OF IOConfig

To start the IOConfig Tool selects ‘Tools – IO Configration’ from the FTUMan menu. When you run the

IOConfig Tool, main screen is displayed as show in following figure. There are two tabbed pages in the

IOConfig Tool.

[ Main Screen of IOConfig Tool ]

Page 116: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 116

ISO 9001 certified Jin Kwang E & C Corp.

18.2.1 MENU

The File Menu has the following options.

New Closes the current file and allows the creation of a new file

Open Closes the current file and opens a standard window file selection dialog. An

existing IO File (*.iom) can be selected and opened.

Save Saves the current file to the hard drive. If the file is new and this is the first time

it has been saved, the Save As dialog will be opened allowing the user to type in

a name before saving.

Save As Opens a standard Windows Save As dialog box. This allows an existing file to be

saved under a new name.

Exit Closes the current file and exits the tool.

The Comm Menu is explained in the Section 17.2.1 Comm.

The View Menu is explained in the Section 17.2.1 View.

The Help Menu opens a window for IOConfig’s program version and information.

18.2.2 TOOLBAR

Below the menu is a toolbar with 9 buttons.

[ Toolbar of IOConfig ]

Upload Read input or ouput data from FTU-R200.

Download Write input or ouput data to FTU-R200.

About Opens a window for IOConfig’s program version and

information.

Once you Press the Upload or Download button, the follwing window appears. This window determines

the types of data read or write.

Page 117: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 117

ISO 9001 certified Jin Kwang E & C Corp.

[ Select Widow ]

18.2.3 INPUT

FTU-R200 has 10 inputs. Input is created by filling the fields on the Input tab. Each column is defined as

follows.

[ Input Tab ]

Name Input name is defined.

Type of the characters is limited to 11 characters.

Note: 0~3 of 4 input points is fixed.

Debounce Time The minimum time to retain status change.

Like, it prevents making useless information against chattering

in the point

Invert Specifies whether the point will be inverted.

Blk.Open To open blocked

Blk.Close To close blocked

Ext.Trip To trip using external input

Ext. Close To close using external input

Page 118: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 118

ISO 9001 certified Jin Kwang E & C Corp.

18.2.4 OUTPUT

FTU-R200 has 4 relay outputs and 2 photoMOS relay outs. Output is created by filling the fields on the

Output tab. Eash column is defined as follows.

[ Output Tab ]

Name Output name is defined.

Type characters are limited to 11 characters.

Only index number of 3 is changed.

Pulse Time Set a pulse command.

Control Output Select type of PhotoMOS or Contact Relay for OPEN and CLOSE

Page 119: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 119

ISO 9001 certified Jin Kwang E & C Corp.

19. DNP 3.0 INDEX CONFIGURATION TOOL

19.1 OVERVIEW

Custom DNP3.0 point index maps can now be created and loaded into FTU directly from DNPConfig.

The mappings is created using the tool and saved to a DNP3.0 mapping file (*.d3m).

[ Overview of DNPConfig ]

The DNPConfig tool is intended to be used off-line only. Mappings are created, saved and linked to

FTUMan while disconnected from the FTU. Once these tasks have been completed the user connects to

the device and writes the new mapping into the Recloser.

Warning: Make sure the DNPConfig Tool is closed after a mapping has been edited. If the Tool is left

open while the Automatic Data Retriaval feature is running it may attempt to update a mapping file that

is already open in the Tool. This will either cause the read operation to fail or result in a situation where

the newly read file differs from the file open within the Tool.

Page 120: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 120

ISO 9001 certified Jin Kwang E & C Corp.

19.2 OPERATION OF DNPCONFIG.

To start the DNPConfig Tool selects ‘Tools - DNP3.0 Index Configration’ from the FTUMan menu.

When you run the DNPConfig Tool, main screen is displayed as show in following figure. There are 4

tabbed pages, Binaty Input, Binary Output, Analog Input and Counter, in the DNPConfig Tool.

[ Main Screen of DNPConfig ]

The DNPConfig tool allows the user to build custom mapplings to suit their own application. Points are

added by selecting a row in PID Columns on one of the tabbed pages then double clicking point from

the Configuration Tool Box or entering index number in configuration tool box defined. Points are

deleted by selecting a row and pressing ‘Delete’ on the keyboard or entering ‘0’. The PID Number ‘0’

means is not used anymore. You can choose to either shift all the rows below up one, or leave the

entire row blank.

Page 121: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 121

ISO 9001 certified Jin Kwang E & C Corp.

The DNPConfig tool allows the following.

ü Up to 128 Binary Input

ü Up to 32 Binary Output

ü Up to 512 Analog Input

ü Up to 128 Counter

19.2.1 MENU

The File Menu has the following options.

New Closes the current file and allows the creation of a new file

Open Closes the current file and opens a standard window file selection dialog.

An existing DNP File (*.d3m) can be selected and opened.

Save Saves the current file to the hard drive. If the file is new and this is the first

time it has been saved, the Save As dialog will be opened allowing the user

to type in a name before saving.

Save As Opens a standard Windows Save As dialog box. This allows an existing file

to be saved under a new name.

Exit Closes the current file and exits the tool.

The Comm Menu is explained in the Section 17.2.1 Comm.

The View Menu is explained in the Section 17.2.1 View.

The Help Menu opens a window for DNPConfig’s program version and information.

19.2.2 TOOLBAR

[ Toolbar of DNPConfig ]

Tool Shows or hides a window the DNP3.0 Configuration tool box.

Upload Read input or ouput data from FTU-R200.

Download Write input or ouput data to FTU-R200.

About Opens a window for DNPConfig’s program version and information.

Page 122: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 122

ISO 9001 certified Jin Kwang E & C Corp.

Pressing Upload or Download button, the follwing window appears. This window determines the types

of data read or write.

[ Select Widow]

19.2.3 CONFIGURATION TOOL BOX

The configutation tool box panel is launched by clicking the Tool button.

[ Configuration Tool Box ]

Page 123: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 123

ISO 9001 certified Jin Kwang E & C Corp.

The toolbox contains every available point for FTU-R200. The toolbox displays different points depends

on which tab selected. For example, if the Counters tab is selected then only accumulators will be

displayed on the list.

19.2.4 BINARY INPUT

Binary inputs are used to report the status of binary points.

[ Binary Input Tab ]

Index Specifies the DNP ID Number of the point

Range : 0 to 127

PID Specifies number as defiend in the configuration tool box.

The PID Number’s ‘0’ meaning is not used anymore. Range : 0 to 59

Name The name of the points as defiend in the configuration tool box.

Page 124: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 124

ISO 9001 certified Jin Kwang E & C Corp.

This field can be changed in two ways:

Selecting the cell then double clicking a point in the configuration tool

box.

Entering PID number as defiend in configuration tool box.

Class 0~3 The DNP3.0 class of the point. The default class can be modified by

checking from the checkbox.

COS Select event type, COS(Change of state) or SOE(Sequence of Events)

Invert Specifies whether the point will be inverted. If the point is inverted it will

be transmitted when the condition is false than true.

n DNP3.0 Classes

There are four classes in DNP3.0. These are defined as follows:

0 Class 0 is not an event class. It is used when reporting current (static) data values and

not changes of state events.

Note: Setting a point to Class 0 will prevent the controller’s protocol handler from

reporting change of state events for that point to the master station. The point still

remains accessible through static data polls.

1 Class 1 used to report high priority events. Events in this class take precedence.

2 Class 2 used to report medium priority events.

3 Class 3 used to report low priority events.

Page 125: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 125

ISO 9001 certified Jin Kwang E & C Corp.

19.2.5 BINARY OUTPUT

Binary Outputs are used to perform operations on the Recloser device and change setting.

[ Binary Output Tab ]

Index Specifies the DNP ID Number of the point

Range : 0 to 31

PID Specifies number as defiend in the configuration tool box.

The PID Number ‘0’ means is not used anymore.

Range : 0 to 10

Name The name of the points as defiend in the configuration tool box.

This field can be changed in two ways:

Selecting the cell then double clicking a point in the configuration tool

box.

Entering PID number as defiend in configuration tool box.

Page 126: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 126

ISO 9001 certified Jin Kwang E & C Corp.

19.2.6 ANALOG INPUT

Analog Points are used to transmit analog data such as line currents, voltages and contact life. Analog

intputs are created by adding points as required, then modifying the parameters from defaults if

necessary.

[ Analog Input Tab ]

Index Specifies the DNP ID Number of the point

Range : 0 to 511

PID Specifies number as defiend in the configuration tool box.

The PID Number ‘0’ means is not used anymore.

Range : 0 to 331

Name The name of the points as defiend in the configuration tool box.

This field can be changed in two ways:

Selecting the cell then double clicking a point in the configuration tool box.

Page 127: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 127

ISO 9001 certified Jin Kwang E & C Corp.

Entering PID number as defiend in configuration tool box.

Class 0~3 The DNP3.0 class of the point. The default class can be modified by checking

from the checkbox.

COS Select event type, COS(Change of state) or SOE(Sequence of Events)

Scale The scale is used to multiply the reported analog value by the amount

enterd. For example, scaling the Ia RMS value by a multiple of ten will

change the reported value from zero decimal points to one decimal point

(i.e:9 to 9.0)

Default Value: 1, Range: 1,10,100,1000

Deadband Display the deadband value for the point. The analog point value must change

by more than the deadband amount before it is reported.

19.2.7 COUNTER

Counters are used to count data and events such as Trips, Protection Pickups, Faults and Accumulated

kWh.

[ Counter Tab ]

Page 128: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 128

ISO 9001 certified Jin Kwang E & C Corp.

Index Specifies the DNP ID Number of the point

Range : 0 to 127

PID Specifies number as defiend in the configuration tool box.

The PID Number’s ‘0’ means are not used anymore.

Range : 0 to 66

Name

The name of the points as defiend in the configuration tool box.

This field can be changed in two ways:

Selecting the cell then double clicking a point in the configuration tool box.

Entering PID number as defiend in configuration tool box.

Class 0~3 The DNP3.0 class of the point. The default class can be modified by checking

from the checkbox.

COS Select event type, COS(Change of state) or SOE(Sequence of Events)

Page 129: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 129

ISO 9001 certified Jin Kwang E & C Corp.

20. WAVEFORM EVALUATION TOOL

20.1 OVERVIEW

The Waveform data upload from FTU-R200 through the above setting program are analyzed in this

evaluation tool. Graphs of currents/voltages and operation of protection elements are displayed, and

instantaneous/RMS current and voltage values, phase angles and time information at tracker position

are presented. If 2 trackter one is moving with left mouse button and the other with right mouse button

are used, time difference between two points is presented and it becomes the ruler for correct

operation of protection element as setting. And, harmonics up to 31st and THD (Total Harmonic

Distortion) also show up.

Recorded waveforms can be uploaded to FTUMan in local site. After uploading stored to the

COMTRADE file format. These waveform data saved as COMTRADE file format and compatible with

other analyzing tool.

n COMTRADE file

Comtrade (COMmon format for Transient Data Exchange for power systems) is a file format for

oscilloscops data. It is used by many leading coñpanies for the oscilloscops used in high voltage

substations. It has been standardised by the IEEE.

[ Overview of EvalTool ]

Page 130: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 130

ISO 9001 certified Jin Kwang E & C Corp.

20.2 OPERATION OF EvalTool

To start the EvalTool selects ‘Tools – Waveform Evaluation Tool’ from the FTUMan menu. The tool

has meter view and scroll view for graph.

[ Main Screen of EvalTool ]

20.2.1 MENU

The File Menu has the following options.

Open Closes the current file and opens a standard window file selection dialog. An

existing Data File (*.dat) can be selected and opened.

Exit Closes the current file and exits the tool.

Page 131: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 131

ISO 9001 certified Jin Kwang E & C Corp.

The Option Menu has the following options.

Graph Opens analog and digital graph select window..

[ Graph Select Window ]

Harmonic Open a window for voltage and current harmonics.

[ List Window ]

Move Change the position of the screen.

Zoom The screen to yellow line center to shrink or enlarge the size.

The Help Menu opens a window for EvalTool’s program version and information.

Page 132: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 132

ISO 9001 certified Jin Kwang E & C Corp.

20.2.2 TOOLBAR

[ Toolbar of EvalTool ]

Graph Show the entire graph

Harmonic List Check the harmonic list

Move-First Move to the beginning graph

Move-Double left Show the prior 2-step

Move-Left Show the prior 1-step

Move-Right Show the posterior 1-step

Move-Double right Show the posterior 2-step

Move-End Move to the last graph

Zoom In Enlarged image

Zoom out Shirink image

Zoom All Enlarge all image

Page 133: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 133

ISO 9001 certified Jin Kwang E & C Corp.

APPENDIX 1.TC (Time-Current) Characteristic Curves

[ A, B, C, D curves ]

Page 134: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 134

ISO 9001 certified Jin Kwang E & C Corp.

[ EI, NI, VI, LI, SI curves ]

Page 135: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 135

ISO 9001 certified Jin Kwang E & C Corp.

[ E, L, M, N curves ]

Page 136: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 136

ISO 9001 certified Jin Kwang E & C Corp.

[ KP, P, R, T curves ]

Page 137: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 137

ISO 9001 certified Jin Kwang E & C Corp.

[ V, W, Y, Z curves ]

Page 138: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 138

ISO 9001 certified Jin Kwang E & C Corp.

[ 1, 2, 3, 4 curves ]

Page 139: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 139

ISO 9001 certified Jin Kwang E & C Corp.

[ 5, 6, 7, 8 curves ]

Page 140: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 140

ISO 9001 certified Jin Kwang E & C Corp.

[ 8*, 9 , 11, 13 curves ]

Page 141: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 141

ISO 9001 certified Jin Kwang E & C Corp.

[ 14, 15, 16, 18 curves ]

Page 142: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 142

ISO 9001 certified Jin Kwang E & C Corp.

[ N1, N2, N3, N4 curves ]

Page 143: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 143

ISO 9001 certified Jin Kwang E & C Corp.

[ F, G, H, J curves ]

Page 144: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 144

ISO 9001 certified Jin Kwang E & C Corp.

[ 8+, 17, K-G, A* curves ]

Page 145: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 145

ISO 9001 certified Jin Kwang E & C Corp.

[ IM, IV, IE, ES-NI, ES-VI curves ]

Page 146: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 146

ISO 9001 certified Jin Kwang E & C Corp.

APPENDIX 2. DNP3.0 PROTOCOL OBJECT & INDEX TABLE

Index

No. Description

Defau

lt

Class

Object/Variation Remark

Binary Inputs

0 Switch Status 1 01/01,01/02,02/02 Closed = 1

1 Ext. AC Power Loss 1 01/01,01/02,02/02

2 Battery Discharged 1 01/01,01/02,02/02

3 DI Spare #5 1 01/01,01/02,02/02 Contact closed = 1

4 DI Spare #6 1 01/01,01/02,02/02 Contact closed = 1

5 DI Spare #7 1 01/01,01/02,02/02 Contact closed = 1

6 DI Spare #8 1 01/01,01/02,02/02 Contact closed = 1

7 DI Spare #9 1 01/01,01/02,02/02 Contact closed = 1

8 DI Spare #10 1 01/01,01/02,02/02 Contact closed = 1

9 Control Mode 1 01/01,01/02,02/02 Local = 1

10 Fault Indicator (A) 3 01/01,01/02,02/02

11 Fault Indicator (B) 3 01/01,01/02,02/02

12 Fault Indicator (C) 3 01/01,01/02,02/02

13 Fault Indicator (N) 3 01/01,01/02,02/02

14 Fault Indicator (SEF) 3 01/01,01/02,02/02

15 Reverse Direction Fault 3 01/01,01/02,02/02

16 Live Source 0 01/01,01/02,02/02

17 Live Load 0 01/01,01/02,02/02

18 Open Line Detection A 3 01/01,01/02,02/02

19 Open Line Detection B 3 01/01,01/02,02/02

20 Open Line Detection C 3 01/01,01/02,02/02

21 Open Line Detection R 3 01/01,01/02,02/02

22 Open Line Detection S 3 01/01,01/02,02/02

23 Open Line Detection T 3 01/01,01/02,02/02

24 Sync. Fail A 3 01/01,01/02,02/02

25 Sync. Fail B 3 01/01,01/02,02/02

26 Sync. Fail C 3 01/01,01/02,02/02

27 Under Frequency Op. 0 01/01,01/02,02/02

28 Under Voltage A 0 01/01,01/02,02/02

Page 147: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 147

ISO 9001 certified Jin Kwang E & C Corp.

29 Under Voltage B 0 01/01,01/02,02/02

30 Under Voltage C 0 01/01,01/02,02/02

31 Over Voltage A 0 01/01,01/02,02/02

32 Over Voltage B 0 01/01,01/02,02/02

33 Over Voltage C 0 01/01,01/02,02/02

34 Source Voltage Unbalance 0 01/01,01/02,02/02

35 Current Unbalance 0 01/01,01/02,02/02

36 Sag Detection A 0 01/01,01/02,02/02

37 Sag Detection B 0 01/01,01/02,02/02

38 Sag Detection C 0 01/01,01/02,02/02

39 Swell Detection A 0 01/01,01/02,02/02

40 Swell Detection B 0 01/01,01/02,02/02

41 Swell Detection C 0 01/01,01/02,02/02

42 Interruption Detection A 0 01/01,01/02,02/02

43 Interruption Detection B 0 01/01,01/02,02/02

44 Interruption Detection C 0 01/01,01/02,02/02

45 Voltage THD A 0 01/01,01/02,02/02

46 Voltage THD B 0 01/01,01/02,02/02

47 Voltage THD C 0 01/01,01/02,02/02

48 Current THD A 0 01/01,01/02,02/02

49 Current THD B 0 01/01,01/02,02/02

50 Current THD C 0 01/01,01/02,02/02

51 System Error 3 01/01,01/02,02/02

52 Inrush Detected 3 01/01,01/02,02/02

53 Mode Lock 1 01/01,01/02,02/02

54 Reclosing Blocked 1 01/01,01/02,02/02

55 Protection Blocked 1 01/01,01/02,02/02

56 Ground Protection Blocked 1 01/01,01/02,02/02

57 High Current Trip 3 01/01,01/02,02/02

58 Sequence Lockout 3 01/01,01/02,02/02

Binary Outputs

0 Switch Open/Close Control Pulse 12/01 CLOSE=Close, TRIP=Open

1 Battery Test Pulse 12/01 CLOSE

2 DO spare Output Pulse 12/01 CLOSE

3 DO Photo1 Output Pulse 12/01 CLOSE

4 DO Photo2 Output Pulse 12/01 CLOSE

5 Annunciator Manual Reset Pulse 12/01 CLOSE

Page 148: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 148

ISO 9001 certified Jin Kwang E & C Corp.

6 Control Lock Pulse 12/01 CLOSE

7 Enable/Disable Reclosing Pulse 12/01 CLOSE=En.,TRIP=Dis.

8 Enable/Disable Protection Pulse 12/01 CLOSE=En.,TRIP=Dis.

9 Enable/Disable Ground Protection Pulse 12/01 CLOSE=En.,TRIP=Dis.

Analog Inputs

0 Ia RMS 2 30/02,30/04,32/

02 A

1 Ib RMS 2 30/02,30/04,32/

02 A

2 Ic RMS 2 30/02,30/04,32/

02 A

3 In RMS 0 30/02,30/04,32/

02 A

4 Source side Va RMS 0 30/02,30/04,32/

02 V

5 Source side Vb RMS 0 30/02,30/04,32/

02 V

6 Source side Vc RMS 0 30/02,30/04,32/

02 V

7 Source side Vo RMS 0 30/02,30/04,32/

02 V

8 Load side Va RMS 0 30/02,30/04,32/

02 V

9 Load side Vb RMS 0 30/02,30/04,32/

02 V

10 Load side Vc RMS 0 30/02,30/04,32/

02 V

11 Load side Vo RMS 0 30/02,30/04,32/

02 V

12 KVAa 0 30/02,30/04,32/

02 kVA

13 KVAb 0 30/02,30/04,32/

02 kVA

14 KVAc 0 30/02,30/04,32/

02 kVA

15 kVA3ph 0 30/02,30/04,32/

02 kVA

16 KWa 0 30/02,30/04,32/

02 kW

17 KWb 0 30/02,30/04,32/

02 kW

Page 149: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 149

ISO 9001 certified Jin Kwang E & C Corp.

18 KWc 0 30/02,30/04,32/

02 kW

19 kW3ph 0 30/02,30/04,32/

02 kW

20 KVARa 0 30/02,30/04,32/

02 kVAR

21 KVARb 0 30/02,30/04,32/

02 kVAR

22 KVARc 0 30/02,30/04,32/

02 kVAR

23 kVAR3ph 0 30/02,30/04,32/

02 kVAR

24 PFa 0 30/02,30/04,32/

02 X100

25 PFb 0 30/02,30/04,32/

02 X100

26 PFc 0 30/02,30/04,32/

02 X100

27 PF3ph 0 30/02,30/04,32/

02 X100

28 Va-Vr Phase Angle Diff 0 30/02,30/04,32/

02 o 10

29 Frequency 0 30/02,30/04,32/

02 HZ100

30 Temperature 0 30/02,30/04,32/

02

31 Ia phase angle 0 30/02,30/04 o 10

32 Ib phase angle 0 30/02,30/04 o 10

33 Ic phase angle 0 30/02,30/04 o 10

34 In phase angle 0 30/02,30/04 o 10

35 Source side Va phase angle 0 30/02,30/04 o 10

36 Source side Vb phase angle 0 30/02,30/04 o 10

37 Source side Vc phase angle 0 30/02,30/04 o 10

38 Source side Vo phase angle 0 30/02,30/04 o 10

39 Load side Va phase angle 0 30/02,30/04 o 10

40 Load side Vb phase angle 0 30/02,30/04 o 10

41 Load side Vc phase angle 0 30/02,30/04 o 10

42 Load side Vo phase angle 0 30/02,30/04 o 10

43 I1 RMS 0 30/02,30/04 A

44 I1 phase angle 0 30/02,30/04 o 10

Page 150: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 150

ISO 9001 certified Jin Kwang E & C Corp.

45 I2 RMS 0 30/02,30/04 A

46 I2 phase angle 0 30/02,30/04 o 10

47 Source side V1 RMS 0 30/02,30/04 V

48 Source side V1 phase angle 0 30/02,30/04 o 10

49 Source side V2 RMS 0 30/02,30/04 V

50 Source side V2 phase angle 0 30/02,30/04 o 10

51 Load side V1 RMS 0 30/02,30/04 A

52 Load side V1 phase angle 0 30/02,30/04 o 10

53 Load side V2 RMS 0 30/02,30/04 A

54 Load side V2 phase angle 0 30/02,30/04 o 10

55 Source side Voltage Unbalance

ratio 0 30/02,30/04 %

56 Load side Voltage Unbalance ratio 0 30/02,30/04 %

57 Current Unbalance ratio 0 30/02,30/04 %

58 PFa lead 0 30/02,30/04 Leading = 1

59 PFb lead 0 30/02,30/04 Leading = 1

60 PFc lead 0 30/02,30/04 Leading = 1

61 PF3ph lead 0 30/02,30/04 Leading = 1

62 Last Fault Ia 3 30/02,30/04,32/

04 A

63 Last Fault Ib 3 30/02,30/04,32/

04 A

64 Last Fault Ic 3 30/02,30/04,32/

04 A

65 Last Fault In 3 30/02,30/04,32/

04 A

66 Last Fault vo 0 30/02,30/04 A

67 Last Fault location 0 30/02,30/04 km

68 Last Fault I2t 0 30/02,30/04

69 Demand I Ia 2 30/02,30/04,32/

04 A

70 Demand I Ib 2 30/02,30/04,32/

04 A

71 Demand I Ic 2 30/02,30/04,32/

04 A

72 Demand I In 2 30/02,30/04,32/

04 A

73 Demand P kWa 2 30/02,30/04,32/

04 kW

Page 151: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 151

ISO 9001 certified Jin Kwang E & C Corp.

74 Demand P kWb 2 30/02,30/04,32/

04 kW

75 Demand P kWc 2 30/02,30/04,32/

04 kW

76 Demand P kW3ph 2 30/02,30/04,32/

04 kW

77 Demand P kVARa 2 30/02,30/04,32/

04 kVAR

78 Demand P kVARb 2 30/02,30/04,32/

04 kVAR

79 Demand P kVARc 2 30/02,30/04,32/

04 kVAR

80 Demand P kVAR3ph 2 30/02,30/04,32/

04 kVAR

81 Max. I Ia 2 30/02,30/04,32/

04 A

82 Max. I Ib 2 30/02,30/04,32/

04 A

83 Max. I Ic 2 30/02,30/04,32/

04 A

84 Max. I In 2 30/02,30/04,32/

04 A

85 Max. P1 kWa 2 30/02,30/04,32/

04 kW

86 Max. P1 kWb 2 30/02,30/04,32/

04 kW

87 Max. P1 kWc 2 30/02,30/04,32/

04 kW

88 Max. P1 kW3ph 2 30/02,30/04,32/

04 kW

89 Max. P1 kVARa 2 30/02,30/04,32/

04 kVAR

90 Max. P1 kVARb 2 30/02,30/04,32/

04 kVAR

91 Max. P1 kVARc 2 30/02,30/04,32/

04 kVAR

92 Max. P1 kVAR3ph 2 30/02,30/04,32/

04 kVAR

93 3-phase currents THD 0 30/02,30/04 %

94 Ia THD 0 30/02,30/04 %

95 Ib THD 0 30/02,30/04 %

Page 152: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 152

ISO 9001 certified Jin Kwang E & C Corp.

96 Ic THD 0 30/02,30/04 %

97 In THD 0 30/02,30/04 %

98 Source side 3-phase voltages

THD 0 30/02,30/04 %

99 Source side Va THD 0 30/02,30/04 %

100 Source side Vb THD 0 30/02,30/04 %

101 Source side Vc THD 0 30/02,30/04 %

102 Ia true RMS 0 30/02,30/04 A

103 Ib true RMS 0 30/02,30/04 A

104 Ic true RMS 0 30/02,30/04 A

105 In true RMS 0 30/02,30/04 A

106 Va true RMS 0 30/02,30/04 V

107 Vb true RMS 0 30/02,30/04 V

108 Vc true RMS 0 30/02,30/04 V

109 Vr true RMS 0 30/02,30/04 V

110 Vs true RMS 0 30/02,30/04 V

111 Vt true RMS 0 30/02,30/04 V

112 Vab true RMS 0 30/02,30/04 V

113 Vbc true RMS 0 30/02,30/04 V

114 Vca true RMS 0 30/02,30/04 V

115 Vrs true RMS 0 30/02,30/04 V

116 Vst true RMS 0 30/02,30/04 V

117 Vtr true RMS 0 30/02,30/04 V

118 Active Group 0 30/02,30/04

119 TD #1 0 30/02,30/04 mA1000

120 TD #2 0 30/02,30/04 mA1000

121 Va 2nd harmonic RMS 0 30/02,30/04 V

122 Vb 2nd harmonic RMS 0 30/02,30/04 V

123 Vc 2nd harmonic RMS 0 30/02,30/04 V

124 Ia 2nd harmonic RMS 0 30/02,30/04 A

125 Ib 2nd harmonic RMS 0 30/02,30/04 A

126 Ic 2nd harmonic RMS 0 30/02,30/04 A

127 In 2nd harmonic RMS 0 30/02,30/04 A

128 Va 3rd harmonic RMS 0 30/02,30/04 V

129 Vb 3rd harmonic RMS 0 30/02,30/04 V

130 Vc 3rd harmonic RMS 0 30/02,30/04 V

131 Ia 3rd harmonic RMS 0 30/02,30/04 A

Page 153: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 153

ISO 9001 certified Jin Kwang E & C Corp.

132 Ib 3rd harmonic RMS 0 30/02,30/04 A

133 Ic 3rd harmonic RMS 0 30/02,30/04 A

134 In 3rd harmonic RMS 0 30/02,30/04 A

135 Va 4th harmonic RMS 0 30/02,30/04 V

136 Vb 4th harmonic RMS 0 30/02,30/04 V

137 Vc 4th harmonic RMS 0 30/02,30/04 V

138 Ia 4th harmonic RMS 0 30/02,30/04 A

139 Ib 4th harmonic RMS 0 30/02,30/04 A

140 Ic 4th harmonic RMS 0 30/02,30/04 A

141 In 4th harmonic RMS 0 30/02,30/04 A

324 Va 31th harmonic RMS 0 30/02,30/04 V

325 Vb 31th harmonic RMS 0 30/02,30/04 V

326 Vc 31th harmonic RMS 0 30/02,30/04 V

327 Ia 31th harmonic RMS 0 30/02,30/04 A

328 Ib 31th harmonic RMS 0 30/02,30/04 A

329 Ic 31th harmonic RMS 0 30/02,30/04 A

330 In 31th harmonic RMS 0 30/02,30/04 A

Counters

0 Restart Count 0 20/02,20/06 --

1 Switch Trip (or Open) Count 0 20/02,20/06 --

2 All Faults Count 0 20/02,20/06 --

3 A-phase Fault Count 0 20/02,20/06 --

4 B-phase Fault Count 0 20/02,20/06 --

5 C-phase Fault Count 0 20/02,20/06 --

6 N-phase Fault Count 0 20/02,20/06 --

7 kWattHour-a (Positive) 0 20/02,20/06,22/

08 kWh

8 kWattHour-b (Positive) 0 20/02,20/06,22/

08 kWh

9 kWattHour-c (Positive) 0 20/02,20/06,22/

08 kWh

10 kWattHour-3ph (Positive) 0 20/02,20/06,22/

08 kWh

11 kWattHour-a (Negative) 0 20/02,20/06,22/

08 kWh

12 kWattHour-b (Negative) 0 20/02,20/06,22/

08 kWh

Page 154: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 154

ISO 9001 certified Jin Kwang E & C Corp.

13 kWattHour-c (Negative) 0 20/02,20/06,22/

08 kWh

14 kWattHour-3ph (Negative) 0 20/02,20/06,22/

08 kWh

15 kVarHour-a (Inductive Positive) 0 20/02,20/06,22/

08 kVarh

16 kVarHour-b (Inductive Positive) 0 20/02,20/06,22/

08 kVarh

17 kVarHour-c (Inductive Positive) 0 20/02,20/06,22/

08 kVarh

18 kVarHour-3ph (Inductive Positive) 0 20/02,20/06,22/

08 kVarh

19 kVarHour-a (Capacitive Positive) 0 20/02,20/06,22/

08 kVarh

20 kVarHour-b (Capacitive Positive) 0 20/02,20/06,22/

08 kVarh

21 kVarHour-c (Capacitive Positive) 0 20/02,20/06,22/

08 kVarh

22 kVarHour-3ph

(Capacitive Positive) 0

20/02,20/06,22/

08 kVarh

23 kVarHour-a (Inductive Negative) 0 20/02,20/06,22/

08 kVarh

24 kVarHour-b (Inductive Negative) 0 20/02,20/06,22/

08 kVarh

25 kVarHour-c (Inductive Negative) 0 20/02,20/06,22/

08 kVarh

26 kVarHour-3ph (Inductive

Negative) 0

20/02,20/06,22/

08 kVarh

27 kVarHour-a (Capacitive Negative) 0 20/02,20/06,22/

08 kVarh

28 kVarHour-b (Capacitive Negative) 0 20/02,20/06,22/

08 kVarh

29 kVarHour-c (Capacitive Negative) 0 20/02,20/06,22/

08 kVarh

30 kVarHour-3ph (Capacitive

Negative) 0

20/02,20/06,22/

08 kVarh

31 Sag Counts 0 20/02,20/06 --

32 Sag A Counts 0 20/02,20/06 --

33 Sag B Counts 0 20/02,20/06 --

34 Sag C Counts 0 20/02,20/06 --

35 Sag Instantaneous Counts 0 20/02,20/06 --

Page 155: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 155

ISO 9001 certified Jin Kwang E & C Corp.

36 Sag Momentary Counts 0 20/02,20/06 --

37 Sag Temporary Counts 0 20/02,20/06 --

38 Sag Long-time Counts 0 20/02,20/06 --

39 Swell Counts 0 20/02,20/06 --

40 Swell A Counts 0 20/02,20/06 --

41 Swell B Counts 0 20/02,20/06 --

42 Swell C Counts 0 20/02,20/06 --

43 Swell Instantaneous Counts 0 20/02,20/06 --

44 Swell Momentary Counts 0 20/02,20/06 --

45 Swell Temporary Counts 0 20/02,20/06 --

46 Swell Long-time Counts 0 20/02,20/06 --

47 Interruption Counts 0 20/02,20/06 --

48 Interruption A Counts 0 20/02,20/06 --

49 Interruption B Counts 0 20/02,20/06 --

50 Interruption C Counts 0 20/02,20/06 --

51 Interruption Momentary Counts 0 20/02,20/06 --

52 Interruption Temporary Counts 0 20/02,20/06 --

53 Interruption Sustained Counts 0 20/02,20/06 --

54 Interruption Total Time 0 20/02,20/06 --

55 Interruption A Total Time 0 20/02,20/06 --

56 Interruption B Total Time 0 20/02,20/06 --

57 Interruption C Total Time 0 20/02,20/06 --

58 Source Voltage THD Counts 0 20/02,20/06 --

59 Source Voltage THD A Counts 0 20/02,20/06 --

60 Source Voltage THD B Counts 0 20/02,20/06 --

61 Source Voltage THD C Counts 0 20/02,20/06 --

62 Current THD Counts 0 20/02,20/06 --

63 Current THD A Counts 0 20/02,20/06 --

64 Current THD B Counts 0 20/02,20/06 --

65 Current THD C Counts 0 20/02,20/06 --

Analog outputs

Setting Group1

0 Phase Pickup Current 40/02,41/02 10~1260A

1 Phase Fast TCC type 40/02,41/02 1~48

2 Phase Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

3 Phase Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

4 Phase Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

Page 156: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 156

ISO 9001 certified Jin Kwang E & C Corp.

5 Phase Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

6 Phase Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

7 Phase Delay TCC type 40/02,41/02 1~48

8 Phase Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

9 Phase Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

10 Phase Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

11 Phase Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

12 Phase Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

13 Phase Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

14 Phase Definite Time O/C Level 40/02,41/02 50~10000A

15 Phase Definite Time O/C

Response Time 40/02,41/02 0.00~1.00sec,step:0.01

16 Phase High Current Pickup 40/02,41/02 50~10000A

17 Phase High Current Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

18 Phase 2nd harmonic restraint 40/02,41/02 0(No),1(Yes)

19 Phase Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

20 Ground Pickup Current 40/02,41/02 5~900A

21 Ground Fast TCC type 40/02,41/02 1~48

22 Ground Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

23 Ground Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

24 Ground Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

25 Ground Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

26 Ground Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

27 Ground Delay TCC type 40/02,41/02 1~48

28 Ground Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

29 Ground Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

30 Ground Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

31 Ground Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

32 Ground Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

33 Ground Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

34 Ground Definite Time O/C Level 40/02,41/02 50~10000A

35 Ground Definite Time Response

Time 40/02,41/02 0.00~1.00sec,step:0.01

36 Ground High Current Pickup 40/02,41/02 50~10000A

37 Ground High Current Time Adder 40/02,41/02 0.00~1.00,step:0.01

38 Ground 2nd harmonic Restraint 40/02,41/02 0(No),1(Yes)

Page 157: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 157

ISO 9001 certified Jin Kwang E & C Corp.

39 Ground Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

40 SEF - Pickup Current(3Io) 40/02,41/02 0.1~20.0A

41 SEF - Pickup Voltage(-3Vo) 40/02,41/02 10~80%

42 SEF - Max. Torque Angle 40/02,41/02 0~345,step:15 DEG

43 SEF - Detection Time 40/02,41/02 0.1~30.0 step:0.1 Sec

44 SEF - 2nd harmonic restraint 40/02,41/02 No(0),Yes(1)

45 SEF - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

46 2nd Inrush - harmonic level 40/02,41/02 5~50%

47 2nd Inrush - Detection Time 40/02,41/02 0.02~1.00,step:0.01

48 2nd Inrush - Function Select 40/02,41/02 0(Off),1(On)

49 Direction – 3I1 Threshold 40/02,41/02 0.00~1.00, step:0.01

50 Direction – 3V1 Threshold 40/02,41/02 0.00~1.00, step:0.01

51 Direction – 3I1 Max Torque Angle 40/02,41/02 0~355, step:5

52 Direction – 3Io Max Torque Angle 40/02,41/02 0~355, step:5

53 Direction – 3Io Threshold 40/02,41/02 0.00~1.00, step:0.01

54 Direction – -3Vo Threshold 40/02,41/02 0.00~1.00, step:0.01

55 Phase Loss - Volt On level 40/02,41/02 50~90,step:5

56 Phase Loss - Volt Off level 40/02,41/02 35~75,step:5

57 Phase Loss - Detection Time 40/02,41/02 0.1~30.0 step:0.1

58 Phase Loss - Function Select 40/02,41/02 0(Off),1(On)

59 Under voltage - Detection level 40/02,41/02 0.30~0.95, step:0.01

60 Under voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

61 Under voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

62 Over voltage - Detection level 40/02,41/02 1.05~1.50, step:0.01

63 Over voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

64 Over voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

65 Under Frequency - Detection

Level 40/02,41/02 47.00~59.98,step:0.01

66 Under Frequency - Detection

Delay Time 40/02,41/02 0.03~10.00, step:0.01

67 Under Frequency - Function

Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

68 Sync Fail - Phase difference 40/02,41/02 5~60

69 Sync Fail - Delay Time 40/02,41/02 0.1~30.0 step:0.1

70 Sync Fail - Function Select 40/02,41/02 0(Off),1(On)

71 Phase Cold Load Pickup Multiplier 40/02,41/02 0(Off), 1~10

72 Phase Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

Page 158: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 158

ISO 9001 certified Jin Kwang E & C Corp.

73 Ground Cold Load Pickup

Multiplier 40/02,41/02 0(Off), 1~10

74 Ground Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

75 Oper. To Lockout Phase 40/02,41/02 1~4

76 Oper. To Lockout Ground 40/02,41/02 1~4

77 Oper. Fast Curve Phase 40/02,41/02 0~4

78 Oper. Fast Curve Ground 40/02,41/02 0~4

79 High Current Phase Active 40/02,41/02 0~4

80 High Current Ground Active 40/02,41/02 0~4

81 Phase/Ground Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

82 Phase/Ground Reclose Interval 2nd 40/02,41/02 1~180

83 Phase/Ground Reclose Interval 3rd 40/02,41/02 1~180

84 Phase/Ground Reclose Interval 4th 40/02,41/02 1~180

85 Phase/Ground Reset Time 40/02,41/02 3~180

86 Oper. To Lockout SEF 40/02,41/02 1~4

87 SEF Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

88 SEF Reclose Interval 2nd 40/02,41/02 1~180

89 SEF Reclose Interval 3rd 40/02,41/02 1~180

90 SEF Reclose Interval 4th 40/02,41/02 1~180

91 SEF Reset Time 40/02,41/02 3~180

92 Single Shot Time 40/02,41/02 0~180

93 Seq. Coordination Active 40/02,41/02 0(Off),1(On)

Setting Group2

94 Phase Pickup Current 40/02,41/02 10~1260A

95 Phase Fast TCC type 40/02,41/02 1~48

96 Phase Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

97 Phase Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

98 Phase Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

99 Phase Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

100 Phase Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

101 Phase Delay TCC type 40/02,41/02 1~48

102 Phase Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

103 Phase Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

104 Phase Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

105 Phase Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

106 Phase Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

107 Phase Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

Page 159: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 159

ISO 9001 certified Jin Kwang E & C Corp.

108 Phase Definite Time O/C Level 40/02,41/02 50~10000A

109 Phase Definite Time O/C

Response Time 40/02,41/02 0.00~1.00sec,step:0.01

110 Phase High Current Pickup 40/02,41/02 50~10000A

111 Phase High Current Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

112 Phase 2nd harmonic restraint 40/02,41/02 0(No),1(Yes)

113 Phase Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

114 Ground Pickup Current 40/02,41/02 5~900A

115 Ground Fast TCC type 40/02,41/02 1~48

116 Ground Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

117 Ground Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

118 Ground Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

119 Ground Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

120 Ground Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

121 Ground Delay TCC type 40/02,41/02 1~48

122 Ground Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

123 Ground Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

124 Ground Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

125 Ground Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

126 Ground Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

127 Ground Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

128 Ground Definite Time O/C Level 40/02,41/02 50~10000A

129 Ground Definite Time Response

Time 40/02,41/02 0.00~1.00sec,step:0.01

130 Ground High Current Pickup 40/02,41/02 50~10000A

131 Ground High Current Time Adder 40/02,41/02 0.00~1.00,step:0.01

132 Ground 2nd harmonic Restraint 40/02,41/02 0(No),1(Yes)

133 Ground Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

134 SEF - Pickup Current(3Io) 40/02,41/02 0.1~20.0A

135 SEF - Pickup Voltage(-3Vo) 40/02,41/02 10~80%

136 SEF - Max. Torque Angle 40/02,41/02 0~345,step:15 DEG

137 SEF - Detection Time 40/02,41/02 0.1~30.0 step:0.1 Sec

138 SEF - 2nd harmonic restraint 40/02,41/02 No(0),Yes(1)

139 SEF - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

140 2nd Inrush - harmonic level 40/02,41/02 5~50%

141 2nd Inrush - Detection Time 40/02,41/02 0.02~1.00,step:0.01

Page 160: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 160

ISO 9001 certified Jin Kwang E & C Corp.

142 2nd Inrush - Function Select 40/02,41/02 0(Off),1(On)

143 Direction – 3I1 Threshold 40/02,41/02 0.00~1.00, step:0.01

144 Direction – 3V1 Threshold 40/02,41/02 0.00~1.00, step:0.01

145 Direction – 3I1 Max Torque Angle 40/02,41/02 0~355, step:5

146 Direction – 3Io Max Torque Angle 40/02,41/02 0~355, step:5

147 Direction – 3Io Threshold 40/02,41/02 0.00~1.00, step:0.01

148 Direction – -3Vo Threshold 40/02,41/02 0.00~1.00, step:0.01

149 Phase Loss - Volt On level 40/02,41/02 50~90,step:5

150 Phase Loss - Volt Off level 40/02,41/02 35~75,step:5

151 Phase Loss - Detection Time 40/02,41/02 0.1~30.0 step:0.1

152 Phase Loss - Function Select 40/02,41/02 0(Off),1(On)

153 Under voltage - Detection level 40/02,41/02 0.30~0.95, step:0.01

154 Under voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

155 Under voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

156 Over voltage - Detection level 40/02,41/02 1.05~1.50, step:0.01

157 Over voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

158 Over voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

159 Under Frequency - Detection

Level 40/02,41/02 47.00~59.98,step:0.01

160 Under Frequency - Detection

Delay Time 40/02,41/02 0.03~10.00, step:0.01

161 Under Frequency - Function

Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

162 Sync Fail - Phase difference 40/02,41/02 5~60

163 Sync Fail - Delay Time 40/02,41/02 0.1~30.0 step:0.1

164 Sync Fail - Function Select 40/02,41/02 0(Off),1(On)

165 Phase Cold Load Pickup Multiplier 40/02,41/02 0(Off), 1~10

166 Phase Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

167 Ground Cold Load Pickup

Multiplier 40/02,41/02 0(Off), 1~10

168 Ground Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

169 Oper. To Lockout Phase 40/02,41/02 1~4

170 Oper. To Lockout Ground 40/02,41/02 1~4

171 Oper. Fast Curve Phase 40/02,41/02 0~4

172 Oper. Fast Curve Ground 40/02,41/02 0~4

173 High Current Phase Active 40/02,41/02 0~4

174 High Current Ground Active 40/02,41/02 0~4

175 Phase/Ground Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

Page 161: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 161

ISO 9001 certified Jin Kwang E & C Corp.

176 Phase/Ground Reclose Interval 2nd 40/02,41/02 1~180

177 Phase/Ground Reclose Interval 3rd 40/02,41/02 1~180

178 Phase/Ground Reclose Interval 4th 40/02,41/02 1~180

179 Phase/Ground Reset Time 40/02,41/02 3~180

180 Oper. To Lockout SEF 40/02,41/02 1~4

181 SEF Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

182 SEF Reclose Interval 2nd 40/02,41/02 1~180

183 SEF Reclose Interval 3rd 40/02,41/02 1~180

184 SEF Reclose Interval 4th 40/02,41/02 1~180

185 SEF Reset Time 40/02,41/02 3~180

186 Single Shot Time 40/02,41/02 0~180

187 Seq. Coordination Active 40/02,41/02 0(Off),1(On)

Setting Group3

188 Phase Pickup Current 40/02,41/02 10~1260A

189 Phase Fast TCC type 40/02,41/02 1~48

190 Phase Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

191 Phase Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

192 Phase Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

193 Phase Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

194 Phase Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

195 Phase Delay TCC type 40/02,41/02 1~48

196 Phase Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

197 Phase Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

198 Phase Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

199 Phase Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

200 Phase Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

201 Phase Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

202 Phase Definite Time O/C Level 40/02,41/02 50~10000A

203 Phase Definite Time O/C

Response Time 40/02,41/02 0.00~1.00sec,step:0.01

204 Phase High Current Pickup 40/02,41/02 50~10000A

205 Phase High Current Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

206 Phase 2nd harmonic restraint 40/02,41/02 0(No),1(Yes)

207 Phase Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

208 Ground Pickup Current 40/02,41/02 5~900A

209 Ground Fast TCC type 40/02,41/02 1~48

Page 162: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 162

ISO 9001 certified Jin Kwang E & C Corp.

210 Ground Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

211 Ground Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

212 Ground Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

213 Ground Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

214 Ground Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

215 Ground Delay TCC type 40/02,41/02 1~48

216 Ground Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

217 Ground Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

218 Ground Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

219 Ground Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

220 Ground Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

221 Ground Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

222 Ground Definite Time O/C Level 40/02,41/02 50~10000A

223 Ground Definite Time Response

Time 40/02,41/02 0.00~1.00sec,step:0.01

224 Ground High Current Pickup 40/02,41/02 50~10000A

225 Ground High Current Time Adder 40/02,41/02 0.00~1.00,step:0.01

226 Ground 2nd harmonic Restraint 40/02,41/02 0(No),1(Yes)

227 Ground Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

228 SEF - Pickup Current(3Io) 40/02,41/02 0.1~20.0A

229 SEF - Pickup Voltage(-3Vo) 40/02,41/02 10~80%

230 SEF - Max. Torque Angle 40/02,41/02 0~345,step:15 DEG

231 SEF - Detection Time 40/02,41/02 0.1~30.0 step:0.1 Sec

232 SEF - 2nd harmonic restraint 40/02,41/02 No(0),Yes(1)

233 SEF - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

234 2nd Inrush - harmonic level 40/02,41/02 5~50%

235 2nd Inrush - Detection Time 40/02,41/02 0.02~1.00,step:0.01

236 2nd Inrush - Function Select 40/02,41/02 0(Off),1(On)

237 Direction – 3I1 Threshold 40/02,41/02 0.00~1.00, step:0.01

238 Direction – 3V1 Threshold 40/02,41/02 0.00~1.00, step:0.01

239 Direction – 3I1 Max Torque Angle 40/02,41/02 0~355, step:5

240 Direction – 3Io Max Torque Angle 40/02,41/02 0~355, step:5

241 Direction – 3Io Threshold 40/02,41/02 0.00~1.00, step:0.01

242 Direction – -3Vo Threshold 40/02,41/02 0.00~1.00, step:0.01

243 Phase Loss - Volt On level 40/02,41/02 50~90,step:5

244 Phase Loss - Volt Off level 40/02,41/02 35~75,step:5

Page 163: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 163

ISO 9001 certified Jin Kwang E & C Corp.

245 Phase Loss - Detection Time 40/02,41/02 0.1~30.0 step:0.1

246 Phase Loss - Function Select 40/02,41/02 0(Off),1(On)

247 Under voltage - Detection level 40/02,41/02 0.30~0.95, step:0.01

248 Under voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

249 Under voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

250 Over voltage - Detection level 40/02,41/02 1.05~1.50, step:0.01

251 Over voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

252 Over voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

253 Under Frequency - Detection

Level 40/02,41/02 47.00~59.98,step:0.01

254 Under Frequency - Detection

Delay Time 40/02,41/02 0.03~10.00, step:0.01

255 Under Frequency - Function

Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

256 Sync Fail - Phase difference 40/02,41/02 5~60

257 Sync Fail - Delay Time 40/02,41/02 0.1~30.0 step:0.1

258 Sync Fail - Function Select 40/02,41/02 0(Off),1(On)

259 Phase Cold Load Pickup Multiplier 40/02,41/02 0(Off), 1~10

260 Phase Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

261 Ground Cold Load Pickup

Multiplier 40/02,41/02 0(Off), 1~10

262 Ground Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

263 Oper. To Lockout Phase 40/02,41/02 1~4

264 Oper. To Lockout Ground 40/02,41/02 1~4

265 Oper. Fast Curve Phase 40/02,41/02 0~4

266 Oper. Fast Curve Ground 40/02,41/02 0~4

267 High Current Phase Active 40/02,41/02 0~4

268 High Current Ground Active 40/02,41/02 0~4

269 Phase/Ground Reclose Interval 1st 40/02,41/02 0.1~180.0,step:0.1

270 Phase/Ground Reclose Interval 2nd 40/02,41/02 0.1~180

271 Phase/Ground Reclose Interval 3rd 40/02,41/02 0.1~180

272 Phase/Ground Reclose Interval 4th 40/02,41/02 0.1~180

273 Phase/Ground Reset Time 40/02,41/02 3~180

274 Oper. To Lockout SEF 40/02,41/02 1~4

275 SEF Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

276 SEF Reclose Interval 2nd 40/02,41/02 1~180

277 SEF Reclose Interval 3rd 40/02,41/02 1~180

278 SEF Reclose Interval 4th 40/02,41/02 1~180

Page 164: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 164

ISO 9001 certified Jin Kwang E & C Corp.

279 SEF Reset Time 40/02,41/02 3~180

280 Single Shot Time 40/02,41/02 0~180

281 Seq. Coordination Active 40/02,41/02 0(Off),1(On)

Setting Group4

282 Phase Pickup Current 40/02,41/02 10~1260A

283 Phase Fast TCC type 40/02,41/02 1~48

284 Phase Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

285 Phase Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

286 Phase Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

287 Phase Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

288 Phase Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

289 Phase Delay TCC type 40/02,41/02 1~48

290 Phase Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

291 Phase Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

292 Phase Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

293 Phase Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

294 Phase Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

295 Phase Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

296 Phase Definite Time O/C Level 40/02,41/02 50~10000A

297 Phase Definite Time O/C

Response Time 40/02,41/02 0.00~1.00sec,step:0.01

298 Phase High Current Pickup 40/02,41/02 50~10000A

299 Phase High Current Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

300 Phase 2nd harmonic restraint 40/02,41/02 0(No),1(Yes)

301 Phase Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

302 Ground Pickup Current 40/02,41/02 5~900A

303 Ground Fast TCC type 40/02,41/02 1~48

304 Ground Fast Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

305 Ground Fast Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

306 Ground Fast Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

307 Ground Fast Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

308 Ground Fast RDMT 40/02,41/02 0.00~100.00,step:0.01

309 Ground Delay TCC type 40/02,41/02 1~48

310 Ground Delay Time Multiplier 40/02,41/02 0.05~2.00,step:0.01

311 Ground Delay Time Adder 40/02,41/02 0.00~1.00sec,step:0.01

312 Ground Delay Min Response Time 40/02,41/02 0.00~1.00sec,step:0.01

Page 165: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 165

ISO 9001 certified Jin Kwang E & C Corp.

313 Ground Delay Reset Type 40/02,41/02 RDMT(0)/RIDMT(1)

314 Ground Delay RDMT 40/02,41/02 0.00~100.00,step:0.01

315 Ground Definite Time O/C Active 40/02,41/02 ON(1),OFF(0)

316 Ground Definite Time O/C Level 40/02,41/02 50~10000A

317 Ground Definite Time Response

Time 40/02,41/02 0.00~1.00sec,step:0.01

318 Ground High Current Pickup 40/02,41/02 50~10000A

319 Ground High Current Time Adder 40/02,41/02 0.00~1.00,step:0.01

320 Ground 2nd harmonic Restraint 40/02,41/02 0(No),1(Yes)

321 Ground Fault Trip Direction 40/02,41/02 0(off),1(fwd),2(rev),3(fwd or

rev)

322 SEF - Pickup Current(3Io) 40/02,41/02 0.1~20.0A

323 SEF - Pickup Voltage(-3Vo) 40/02,41/02 10~80%

324 SEF - Max. Torque Angle 40/02,41/02 0~345,step:15 DEG

325 SEF - Detection Time 40/02,41/02 0.1~30.0 step:0.1 Sec

326 SEF - 2nd harmonic restraint 40/02,41/02 No(0),Yes(1)

327 SEF - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

328 2nd Inrush - harmonic level 40/02,41/02 5~50%

329 2nd Inrush - Detection Time 40/02,41/02 0.02~1.00,step:0.01

330 2nd Inrush - Function Select 40/02,41/02 0(Off),1(On)

331 Direction – 3I1 Threshold 40/02,41/02 0.00~1.00, step:0.01

332 Direction – 3V1 Threshold 40/02,41/02 0.00~1.00, step:0.01

333 Direction – 3I1 Max Torque Angle 40/02,41/02 0~355, step:5

334 Direction – 3Io Max Torque Angle 40/02,41/02 0~355, step:5

335 Direction – 3Io Threshold 40/02,41/02 0.00~1.00, step:0.01

336 Direction – -3Vo Threshold 40/02,41/02 0.00~1.00, step:0.01

337 Phase Loss - Volt On level 40/02,41/02 50~90,step:5

338 Phase Loss - Volt Off level 40/02,41/02 35~75,step:5

339 Phase Loss - Detection Time 40/02,41/02 0.1~30.0 step:0.1

340 Phase Loss - Function Select 40/02,41/02 0(Off),1(On)

341 Under voltage - Detection level 40/02,41/02 0.30~0.95, step:0.01

342 Under voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

343 Under voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

344 Over voltage - Detection level 40/02,41/02 1.05~1.50, step:0.01

345 Over voltage - Detection Time 40/02,41/02 0~180.0, step:0.1

346 Over voltage - Function Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

347 Under Frequency - Detection

Level 40/02,41/02 47.00~59.98,step:0.01

Page 166: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 166

ISO 9001 certified Jin Kwang E & C Corp.

348 Under Frequency - Detection

Delay Time 40/02,41/02 0.03~10.00, step:0.01

349 Under Frequency - Function

Select 40/02,41/02 0(Off),1(Alarm),2(Trip)

350 Sync Fail - Phase difference 40/02,41/02 5~60

351 Sync Fail - Delay Time 40/02,41/02 0.1~30.0 step:0.1

352 Sync Fail - Function Select 40/02,41/02 0(Off),1(On)

353 Phase Cold Load Pickup Multiplier 40/02,41/02 0(Off), 1~10

354 Phase Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

355 Ground Cold Load Pickup

Multiplier 40/02,41/02 0(Off), 1~10

356 Ground Cold Load Duration 40/02,41/02 0.00~60.00 step:0.01

357 Oper. To Lockout Phase 40/02,41/02 1~4

358 Oper. To Lockout Ground 40/02,41/02 1~4

359 Oper. Fast Curve Phase 40/02,41/02 0~4

360 Oper. Fast Curve Ground 40/02,41/02 0~4

361 High Current Phase Active 40/02,41/02 0~4

362 High Current Ground Active 40/02,41/02 0~4

363 Phase/Ground Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

364 Phase/Ground Reclose Interval 2nd 40/02,41/02 1~180

365 Phase/Ground Reclose Interval 3rd 40/02,41/02 1~180

366 Phase/Ground Reclose Interval 4th 40/02,41/02 1~180

367 Phase/Ground Reset Time 40/02,41/02 3~180

368 Oper. To Lockout SEF 40/02,41/02 1~4

369 SEF Reclose Interval 1st 40/02,41/02 0.5~180.0,step:0.1

370 SEF Reclose Interval 2nd 40/02,41/02 1~180

371 SEF Reclose Interval 3rd 40/02,41/02 1~180

372 SEF Reclose Interval 4th 40/02,41/02 1~180

373 SEF Reset Time 40/02,41/02 3~180

374 Single Shot Time 40/02,41/02 0~180

375 Seq. Coordination Active 40/02,41/02 0(Off),1(On)

Common Setting

376 Default setting group 40/02,41/02 1~4

377 Automation Detection Group

Selection 40/02,41/02 0(Off),1(On)

378 Reverse power flow setting group 40/02,41/02 1~4

File Transfer

“EV_BIO” 70/01 I/O Event history

Page 167: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 167

ISO 9001 certified Jin Kwang E & C Corp.

“EV_FUNC” 70/01 Function Event History

“EV_SYS” 70/01 System Event History

“EV_FAULT” 70/01 Fault Event History

:EV_PQM” 70/01 Pqm Event History

“EV_DMD_I” 70/01 Demand I History

“EV_DMD_P” 70/01 Demand P History

“EV_MAX_I” 70/01 Max. I History

“EV_MAX_P” 70/01 Max. P History

“WAVE_INFO” 70/01 Wave Info

“FI_WAVE_1” 70/01 Fault Waveform (Recent)

“FI_WAVE_2” 70/01 Fault Waveform

“FI_WAVE_3” 70/01 Fault Waveform

“FI_WAVE_4” 70/01 Fault Waveform

“FI_WAVE_5” 70/01 Fault Waveform

“FI_WAVE_6” 70/01 Fault Waveform

“FI_WAVE_7” 70/01 Fault Waveform

“FI_WAVE_8” 70/01 Fault Waveform (Oldest)

“PQ_WAVE_1” 70/01 Pqm Waveform (Recent)

“PQ_WAVE_2” 70/01 Pqm Waveform

“PQ_WAVE_3” 70/01 Pqm Waveform

“PQ_WAVE_4” 70/01 Pqm Waveform

“PQ_WAVE_5” 70/01 Pqm Waveform

“PQ_WAVE_6” 70/01 Pqm Waveform (Oldest)

“PQ_WAVE_0” 70/01 Manual Waveform

I/O Event File Record Format

I/O Event ID

Unsigned short

I/O Event Date & Time DNP Time

I/O Event Status Flags Unsigned short

Function Event File Record Format

Function Event ID

Unsigned short

Function Event Date & Time DNP Time

Function Event Status Flags Unsigned short

System Event File Record Format

System Event ID

Unsigned short

System Event Date & Time DNP Time

System Event Status Flags Unsigned short

Fault Event File Record Format

Page 168: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 168

ISO 9001 certified Jin Kwang E & C Corp.

Fault Event Date & Time

DNP Time

Fault Event Status Unsigned short

Fault Event Ia Unsigned short

Fault Event Ib Unsigned short

Fault Event Ic Unsigned short

Fault Event In Unsigned short

Fault Event Vo Unsigned short

Fault Event Active Group Unsigned short

Reserved Unsigned short

Reserved Unsigned short

Reserved Unsigned short

PQM Event File Record Format

PQM event # ID

Unsigned short

PQM event # Date & Time DNP Time

PQM event # Duration Unsigned short

PQM event # Value Unsigned short

Demand I Event File Record Format

Demand I Date & Time

DNP Time

Demand I Ia Unsigned short

Demand I Ib Unsigned short

Demand I Ic Unsigned short

Demand I In Unsigned short

Demand P Event File Record Format

Demand P Date & Time

DNP Time

Demand P kWa short

Demand P kWb short

Demand P kWc short

Demand P kW3ph short

Demand P kVARa short

Demand P kVARb short

Demand P kVARc short

Demand P kVAR3ph short

Max. I Event File Record Format

Max. I Date & Time

DNP Time

Max. I Ia Unsigned short

Max. I Ib Unsigned short

Max. I Ic Unsigned short

Page 169: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 169

ISO 9001 certified Jin Kwang E & C Corp.

Max. I In Unsigned short

Max. P Event File Record Format

Max. P Date & Time

DNP Time

Max. P kWa short

Max. P kWb short

Max. P kWc short

Max. P kW3ph short

Max. P kVARa short

Max. P kVARb short

Max. P kVARc short

Max. P kVAR3ph short

Wave Info File Record Format

FI_WAVE _1 Date & Time

DNP Time

FI_WAVE _1 frequency Unsigned char

FI_WAVE _1 Type Unsigned char

FI_WAVE _1 Cycle Unsigned char

FI_WAVE _1 Sampling Unsigned char

FI_WAVE _8 Date & Time DNP Time

FI_WAVE _8 frequency Unsigned char

FI_WAVE _8 Type Unsigned char

FI_WAVE _8 Cycle Unsigned char

FI_WAVE _8 Sampling Unsigned char

PQ_WAVE _1 Date & Time DNP Time

PQ_WAVE _1 frequency Unsigned char

PQ_WAVE _1 Type Unsigned char

PQ_WAVE _1 Cycle Unsigned char

PQ_WAVE _1 Sampling Unsigned char

PQ_WAVE _6 Date & Time DNP Time

PQ_WAVE _6 frequency Unsigned char

PQ_WAVE _6 Type Unsigned char

PQ_WAVE _6 Cycle Unsigned char

PQ_WAVE _6 Sampling Unsigned char

PQ_WAVE _0 Date & Time DNP Time

PQ_WAVE _0 frequency Unsigned char

PQ_WAVE _0 Type Unsigned char

PQ_WAVE _0 Cycle Unsigned char

Page 170: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 170

ISO 9001 certified Jin Kwang E & C Corp.

PQ_WAVE _0 Sampling Unsigned char

Sample waveform File Record Format

Sample Waveform Date & Time

Record

0

DNP Time

Fault Status Unsigned short

Sampling Rate = 128 Unsigned short

Reserved 10 Bytes

Sample Va[0]

Record

1~2560

-32768 ~ +32767

Sample Vb[0] -32768 ~ +32767

Sample Vc[0] -32768 ~ +32767

Sample Ia[0] -32768 ~ +32767

Sample Ib[0] -32768 ~ +32767

Sample Ic[0] -32768 ~ +32767

Sample In[0] -32768 ~ +32767

Sample Op. Status[] Unsigned short

Page 171: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 171

ISO 9001 certified Jin Kwang E & C Corp.

APPENDIX 3. IEC 60870-5-101 PROTOCOL OBJECT & INDEX TABLE

Point

Address Description Remark

M_SP_NA_1 points

100 Reserved

101 Ext. AC Power Loss

102 Battery Discharged

103 DI Spare #5 Contact closed = 1

104 DI Spare #6 Contact closed = 1

105 DI Spare #7 Contact closed = 1

106 DI Spare #8 Contact closed = 1

107 DI Spare #9 Contact closed = 1

108 DI Spare #10 Contact closed = 1

109 Control Mode Local = 1

110 Fault Indicator (A)

111 Fault Indicator (B)

112 Fault Indicator (C)

113 Fault Indicator (N)

114 Fault Indicator (SEF)

115 Reverse Direction Fault

116 Live Source

117 Live Load

118 Open Line Detection A

119 Open Line Detection B

120 Open Line Detection C

121 Open Line Detection R

122 Open Line Detection S

123 Open Line Detection T

124 Sync. Fail A

125 Sync. Fail B

126 Sync. Fail C

127 Under Frequency Op.

128 Under Voltage A

129 Under Voltage B

Page 172: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 172

ISO 9001 certified Jin Kwang E & C Corp.

130 Under Voltage C

131 Over Voltage A

132 Over Voltage B

133 Over Voltage C

134 Source Voltage Unbalance

135 Current Unbalance

136 Sag Detection A

137 Sag Detection B

138 Sag Detection C

139 Swell Detection A

140 Swell Detection B

141 Swell Detection C

142 Interruption Detection A

143 Interruption Detection B

144 Interruption Detection C

145 Voltage THD A

146 Voltage THD B

147 Voltage THD C

148 Current THD A

149 Current THD B

150 Current THD C

151 System Error

152 Inrush Detected

153 Mode Lock

154 Reclosing Blocked

155 Protection Blocked

156 Ground Protection Blocked

157 High Current Trip

158 Sequence Lockout

C_SC_NA_1 points

200 Annunciator Manual Reset No Select Required

201 Battery Test Output No Select Required

M_DP_NA_1 points

300 Switch Status

C_DC_NA_1 points

400 Switch Open/Close Control Select Required Before Execute

M_ME_NB_1 points

Page 173: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 173

ISO 9001 certified Jin Kwang E & C Corp.

1000 Ia RMS A

1001 Ib RMS A

1002 Ic RMS A

1003 In RMS A

1004 Source side Va RMS V

1005 Source side Vb RMS V

1006 Source side Vc RMS V

1007 Source side Vo RMS V

1008 Load side Va RMS V

1009 Load side Vb RMS V

1010 Load side Vc RMS V

1011 Load side Vo RMS V

1012 KVAa kVA

1013 KVAb kVA

1014 KVAc kVA

1015 kVA3ph kVA

1016 KWa kW

1017 KWb kW

1018 KWc kW

1019 kW3ph kW

1020 KVARa kVAR

1021 KVARb kVAR

1022 KVARc kVAR

1023 kVAR3ph kVAR

1024 PFa X100

1025 PFb X100

1026 PFc X100

1027 PF3ph X100

1028 Va-Vr Phase Angle Diff o 10

1029 Frequency HZ100

1030 Temperature

1031 Ia phase angle o 10

1032 Ib phase angle o 10

1033 Ic phase angle o 10

1034 In phase angle o 10

1035 Source side Va phase angle o 10

1036 Source side Vb phase angle o 10

Page 174: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 174

ISO 9001 certified Jin Kwang E & C Corp.

1037 Source side Vc phase angle o 10

1038 Source side Vo phase angle o 10

1039 Load side Va phase angle o 10

1040 Load side Vb phase angle o 10

1041 Load side Vc phase angle o 10

1042 Load side Vo phase angle o 10

1043 I1 RMS A

1044 I1 phase angle o 10

1045 I2 RMS A

1046 I2 phase angle o 10

1047 Source side V1 RMS V

1048 Source side V1 phase angle o 10

1049 Source side V2 RMS V

1050 Source side V2 phase angle o 10

1051 Load side V1 RMS A

1052 Load side V1 phase angle o 10

1053 Load side V2 RMS A

1054 Load side V2 phase angle o 10

1055 Source side Voltage Unbalance ratio %

1056 Load side Voltage Unbalance ratio %

1057 Current Unbalance ratio %

1058 PFa lead Leading = 1

1059 PFb lead Leading = 1

1060 PFc lead Leading = 1

1061 PF3ph lead Leading = 1

1062 Last Fault Ia A

1063 Last Fault Ib A

1064 Last Fault Ic A

1065 Last Fault In A

1066 Last Fault vo A

1067 Last Fault location km

1068 Last Fault I2t

1069 Demand I Ia A

1070 Demand I Ib A

1071 Demand I Ic A

1072 Demand I In A

1073 Demand P kWa kW

Page 175: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 175

ISO 9001 certified Jin Kwang E & C Corp.

1074 Demand P kWb kW

1075 Demand P kWc kW

1076 Demand P kW3ph kW

1077 Demand P kVARa kVAR

1078 Demand P kVARb kVAR

1079 Demand P kVARc kVAR

1080 Demand P kVAR3ph kVAR

1081 Max. I Ia A

1082 Max. I Ib A

1083 Max. I Ic A

1084 Max. I In A

1085 Max. P1 kWa kW

1086 Max. P1 kWb kW

1087 Max. P1 kWc kW

1088 Max. P1 kW3ph kW

1089 Max. P1 kVARa kVAR

1090 Max. P1 kVARb kVAR

1091 Max. P1 kVARc kVAR

1092 Max. P1 kVAR3ph kVAR

1093 3-phase currents THD %

1094 Ia THD %

1095 Ib THD %

1096 Ic THD %

1097 In THD %

1098 Source side 3-phase voltages THD %

1099 Source side Va THD %

1100 Source side Vb THD %

1101 Source side Vc THD %

1102 Ia true RMS A

1103 Ib true RMS A

1104 Ic true RMS A

1105 In true RMS A

1106 Va true RMS V

1107 Vb true RMS V

1108 Vc true RMS V

1109 Vr true RMS V

1110 Vs true RMS V

Page 176: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 176

ISO 9001 certified Jin Kwang E & C Corp.

1111 Vt true RMS V

1112 Vab true RMS V

1113 Vbc true RMS V

1114 Vca true RMS V

1115 Vrs true RMS V

1116 Vst true RMS V

1117 Vtr true RMS V

1118 Active Group

1119 TD #1 mA1000

1120 TD #2 mA1000

1121 Va 2nd harmonic RMS V

1122 Vb 2nd harmonic RMS V

1123 Vc 2nd harmonic RMS V

1124 Ia 2nd harmonic RMS A

1125 Ib 2nd harmonic RMS A

1126 Ic 2nd harmonic RMS A

1127 In 2nd harmonic RMS A

1128 Va 3rd harmonic RMS V

1129 Vb 3rd harmonic RMS V

1130 Vc 3rd harmonic RMS V

1131 Ia 3rd harmonic RMS A

1132 Ib 3rd harmonic RMS A

1133 Ic 3rd harmonic RMS A

1134 In 3rd harmonic RMS A

1135 Va 4th harmonic RMS V

1136 Vb 4th harmonic RMS V

1137 Vc 4th harmonic RMS V

1138 Ia 4th harmonic RMS A

1139 Ib 4th harmonic RMS A

1140 Ic 4th harmonic RMS A

1141 In 4th harmonic RMS A

1324 Va 31th harmonic RMS V

1325 Vb 31th harmonic RMS V

1326 Vc 31th harmonic RMS V

1327 Ia 31th harmonic RMS A

1328 Ib 31th harmonic RMS A

Page 177: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 177

ISO 9001 certified Jin Kwang E & C Corp.

1329 Ic 31th harmonic RMS A

1330 In 31th harmonic RMS A

M_IT_NA_1 points

4000 Restart Count --

4001 Switch Trip (or Open) Count --

4002 All Faults Count --

4003 A-phase Fault Count --

4004 B-phase Fault Count --

4005 C-phase Fault Count --

4006 N-phase Fault Count --

4007 kWattHour-a (Positive) kWh

4008 kWattHour-b (Positive) kWh

4009 kWattHour-c (Positive) kWh

4010 kWattHour-3ph (Positive) kWh

4011 kWattHour-a (Negative) kWh

4012 kWattHour-b (Negative) kWh

4013 kWattHour-c (Negative) kWh

4014 kWattHour-3ph (Negative) kWh

4015 kVarHour-a (Inductive Positive) kVarh

4016 kVarHour-b (Inductive Positive) kVarh

4017 kVarHour-c (Inductive Positive) kVarh

4018 kVarHour-3ph (Inductive Positive) kVarh

4019 kVarHour-a (Capacitive Positive) kVarh

4020 kVarHour-b (Capacitive Positive) kVarh

4021 kVarHour-c (Capacitive Positive) kVarh

4022 kVarHour-3ph (Capacitive Positive) kVarh

4023 kVarHour-a (Inductive Negative) kVarh

4024 kVarHour-b (Inductive Negative) kVarh

4025 kVarHour-c (Inductive Negative) kVarh

4026 kVarHour-3ph (Inductive Negative) kVarh

4027 kVarHour-a (Capacitive Negative) kVarh

4028 kVarHour-b (Capacitive Negative) kVarh

4029 kVarHour-c (Capacitive Negative) kVarh

4030 kVarHour-3ph (Capacitive Negative) kVarh

4031 Sag Counts --

4032 Sag A Counts --

4033 Sag B Counts --

Page 178: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 178

ISO 9001 certified Jin Kwang E & C Corp.

4034 Sag C Counts --

4035 Sag Instantaneous Counts --

4036 Sag Momentary Counts --

4037 Sag Temporary Counts --

4038 Sag Long-time Counts --

4039 Swell Counts --

4040 Swell A Counts --

4041 Swell B Counts --

4042 Swell C Counts --

4043 Swell Instantaneous Counts --

4044 Swell Momentary Counts --

4045 Swell Temporary Counts --

4046 Swell Long-time Counts --

4047 Interruption Counts --

4048 Interruption A Counts --

4049 Interruption B Counts --

4050 Interruption C Counts --

4051 Interruption Momentary Counts --

4052 Interruption Temporary Counts --

4053 Interruption Sustained Counts --

4054 Interruption Total Time --

4055 Interruption A Total Time --

4056 Interruption B Total Time --

4057 Interruption C Total Time --

4058 Source Voltage THD Counts --

4059 Source Voltage THD A Counts --

4060 Source Voltage THD B Counts --

4061 Source Voltage THD C Counts --

4062 Current THD Counts --

4063 Current THD A Counts --

4064 Current THD B Counts --

4065 Current THD C Counts --

C_SE_NB_1 points

Setting Group1

2000 Phase Pickup Current 10~1260A

2001 Phase Fast TCC type 1~48

2002 Phase Fast Time Multiplier 0.05~2.00,step:0.01

Page 179: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 179

ISO 9001 certified Jin Kwang E & C Corp.

2003 Phase Fast Time Adder 0.00~1.00sec,step:0.01

2004 Phase Fast Min Response Time 0.00~1.00sec,step:0.01

2005 Phase Fast Reset Type RDMT(0)/RIDMT(1)

2006 Phase Fast RDMT 0.00~100.00,step:0.01

2007 Phase Delay TCC type 1~48

2008 Phase Delay Time Multiplier 0.05~2.00,step:0.01

2009 Phase Delay Time Adder 0.00~1.00sec,step:0.01

2010 Phase Delay Min Response Time 0.00~1.00sec,step:0.01

2011 Phase Delay Reset Type RDMT(0)/RIDMT(1)

2012 Phase Delay RDMT 0.00~100.00,step:0.01

2013 Phase Definite Time O/C Active ON(1),OFF(0)

2014 Phase Definite Time O/C Level 50~10000A

2015 Phase Definite Time O/C Response Time 0.00~1.00sec,step:0.01

2016 Phase High Current Pickup 50~10000A

2017 Phase High Current Time Adder 0.00~1.00sec,step:0.01

2018 Phase 2nd harmonic restraint 0(No),1(Yes)

2019 Phase Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2020 Ground Pickup Current 5~900A

2021 Ground Fast TCC type 1~48

2022 Ground Fast Time Multiplier 0.05~2.00,step:0.01

2023 Ground Fast Time Adder 0.00~1.00sec,step:0.01

2024 Ground Fast Min Response Time 0.00~1.00sec,step:0.01

2025 Ground Fast Reset Type RDMT(0)/RIDMT(1)

2026 Ground Fast RDMT 0.00~100.00,step:0.01

2027 Ground Delay TCC type 1~48

2028 Ground Delay Time Multiplier 0.05~2.00,step:0.01

2029 Ground Delay Time Adder 0.00~1.00sec,step:0.01

2030 Ground Delay Min Response Time 0.00~1.00sec,step:0.01

2031 Ground Delay Reset Type RDMT(0)/RIDMT(1)

2032 Ground Delay RDMT 0.00~100.00,step:0.01

2033 Ground Definite Time O/C Active ON(1),OFF(0)

2034 Ground Definite Time O/C Level 50~10000A

2035 Ground Definite Time Response Time 0.00~1.00sec,step:0.01

2036 Ground High Current Pickup 50~10000A

2037 Ground High Current Time Adder 0.00~1.00,step:0.01

2038 Ground 2nd harmonic Restraint 0(No),1(Yes)

2039 Ground Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

Page 180: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 180

ISO 9001 certified Jin Kwang E & C Corp.

2040 SEF - Pickup Current(3Io) 0.1~20.0A

2041 SEF - Pickup Voltage(-3Vo) 10~80%

2042 SEF - Max. Torque Angle 0~345,step:15 DEG

2043 SEF - Detection Time 0.1~30.0 step:0.1 Sec

2044 SEF - 2nd harmonic restraint No(0),Yes(1)

2045 SEF - Function Select 0(Off),1(Alarm),2(Trip)

2046 2nd Inrush - harmonic level 5~50%

2047 2nd Inrush - Detection Time 0.02~1.00,step:0.01

2048 2nd Inrush - Function Select 0(Off),1(On)

2049 Direction – 3I1 Threshold 0.00~1.00, step:0.01

2050 Direction – 3V1 Threshold 0.00~1.00, step:0.01

2051 Direction – 3I1 Max Torque Angle 0~355, step:5

2052 Direction – 3Io Max Torque Angle 0~355, step:5

2053 Direction – 3Io Threshold 0.00~1.00, step:0.01

2054 Direction – -3Vo Threshold 0.00~1.00, step:0.01

2055 Phase Loss - Volt On level 50~90,step:5

2056 Phase Loss - Volt Off level 35~75,step:5

2057 Phase Loss - Detection Time 0.1~30.0 step:0.1

2058 Phase Loss - Function Select 0(Off),1(On)

2059 Under voltage - Detection level 0.30~0.95, step:0.01

2060 Under voltage - Detection Time 0~180.0, step:0.1

2061 Under voltage - Function Select 0(Off),1(Alarm),2(Trip)

2062 Over voltage - Detection level 1.05~1.50, step:0.01

2063 Over voltage - Detection Time 0~180.0, step:0.1

2064 Over voltage - Function Select 0(Off),1(Alarm),2(Trip)

2065 Under Frequency - Detection Level 47.00~59.98,step:0.01

2066 Under Frequency - Detection Delay Time 0.03~10.00, step:0.01

2067 Under Frequency - Function Select 0(Off),1(Alarm),2(Trip)

2068 Sync Fail - Phase difference 5~60

2069 Sync Fail - Delay Time 0.1~30.0 step:0.1

2070 Sync Fail - Function Select 0(Off),1(On)

2071 Phase Cold Load Pickup Multiplier 0(Off), 1~10

2072 Phase Cold Load Duration 0.00~60.00 step:0.01

2073 Ground Cold Load Pickup Multiplier 0(Off), 1~10

2074 Ground Cold Load Duration 0.00~60.00 step:0.01

2075 Oper. To Lockout Phase 1~4

2076 Oper. To Lockout Ground 1~4

Page 181: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 181

ISO 9001 certified Jin Kwang E & C Corp.

2077 Oper. Fast Curve Phase 0~4

2078 Oper. Fast Curve Ground 0~4

2079 High Current Phase Active 0~4

2080 High Current Ground Active 0~4

2081 Phase/Ground Reclose Interval 1st 0.5~180.0,step:0.1

2082 Phase/Ground Reclose Interval 2nd 1~180

2083 Phase/Ground Reclose Interval 3rd 1~180

2084 Phase/Ground Reclose Interval 4th 1~180

2085 Phase/Ground Reset Time 3~180

2086 Oper. To Lockout SEF 1~4

2087 SEF Reclose Interval 1st 0.5~180.0,step:0.1

2088 SEF Reclose Interval 2nd 1~180

2089 SEF Reclose Interval 3rd 1~180

2090 SEF Reclose Interval 4th 1~180

2091 SEF Reset Time 3~180

2092 Single Shot Time 0~180

2093 Seq. Coordination Active 0(Off),1(On)

Setting Group2

2094 Phase Pickup Current 10~1260A

2095 Phase Fast TCC type 1~48

2096 Phase Fast Time Multiplier 0.05~2.00,step:0.01

2097 Phase Fast Time Adder 0.00~1.00sec,step:0.01

2098 Phase Fast Min Response Time 0.00~1.00sec,step:0.01

2099 Phase Fast Reset Type RDMT(0)/RIDMT(1)

2100 Phase Fast RDMT 0.00~100.00,step:0.01

2101 Phase Delay TCC type 1~48

2102 Phase Delay Time Multiplier 0.05~2.00,step:0.01

2103 Phase Delay Time Adder 0.00~1.00sec,step:0.01

2104 Phase Delay Min Response Time 0.00~1.00sec,step:0.01

2105 Phase Delay Reset Type RDMT(0)/RIDMT(1)

2106 Phase Delay RDMT 0.00~100.00,step:0.01

2107 Phase Definite Time O/C Active ON(1),OFF(0)

2108 Phase Definite Time O/C Level 50~10000A

2109 Phase Definite Time O/C Response Time 0.00~1.00sec,step:0.01

2110 Phase High Current Pickup 50~10000A

2111 Phase High Current Time Adder 0.00~1.00sec,step:0.01

2112 Phase 2nd harmonic restraint 0(No),1(Yes)

Page 182: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 182

ISO 9001 certified Jin Kwang E & C Corp.

2113 Phase Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2114 Ground Pickup Current 5~900A

2115 Ground Fast TCC type 1~48

2116 Ground Fast Time Multiplier 0.05~2.00,step:0.01

2117 Ground Fast Time Adder 0.00~1.00sec,step:0.01

2118 Ground Fast Min Response Time 0.00~1.00sec,step:0.01

2119 Ground Fast Reset Type RDMT(0)/RIDMT(1)

2120 Ground Fast RDMT 0.00~100.00,step:0.01

2121 Ground Delay TCC type 1~48

2122 Ground Delay Time Multiplier 0.05~2.00,step:0.01

2123 Ground Delay Time Adder 0.00~1.00sec,step:0.01

2124 Ground Delay Min Response Time 0.00~1.00sec,step:0.01

2125 Ground Delay Reset Type RDMT(0)/RIDMT(1)

2126 Ground Delay RDMT 0.00~100.00,step:0.01

2127 Ground Definite Time O/C Active ON(1),OFF(0)

2128 Ground Definite Time O/C Level 50~10000A

2129 Ground Definite Time Response Time 0.00~1.00sec,step:0.01

2130 Ground High Current Pickup 50~10000A

2131 Ground High Current Time Adder 0.00~1.00,step:0.01

2132 Ground 2nd harmonic Restraint 0(No),1(Yes)

2133 Ground Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2134 SEF - Pickup Current(3Io) 0.1~20.0A

2135 SEF - Pickup Voltage(-3Vo) 10~80%

2136 SEF - Max. Torque Angle 0~345,step:15 DEG

2137 SEF - Detection Time 0.1~30.0 step:0.1 Sec

2138 SEF - 2nd harmonic restraint No(0),Yes(1)

2139 SEF - Function Select 0(Off),1(Alarm),2(Trip)

2140 2nd Inrush - harmonic level 5~50%

2141 2nd Inrush - Detection Time 0.02~1.00,step:0.01

2142 2nd Inrush - Function Select 0(Off),1(On)

2143 Direction – 3I1 Threshold 0.00~1.00, step:0.01

2144 Direction – 3V1 Threshold 0.00~1.00, step:0.01

2145 Direction – 3I1 Max Torque Angle 0~355, step:5

2146 Direction – 3Io Max Torque Angle 0~355, step:5

2147 Direction – 3Io Threshold 0.00~1.00, step:0.01

2148 Direction – -3Vo Threshold 0.00~1.00, step:0.01

2149 Phase Loss - Volt On level 50~90,step:5

Page 183: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 183

ISO 9001 certified Jin Kwang E & C Corp.

2150 Phase Loss - Volt Off level 35~75,step:5

2151 Phase Loss - Detection Time 0.1~30.0 step:0.1

2152 Phase Loss - Function Select 0(Off),1(On)

2153 Under voltage - Detection level 0.30~0.95, step:0.01

2154 Under voltage - Detection Time 0~180.0, step:0.1

2155 Under voltage - Function Select 0(Off),1(Alarm),2(Trip)

2156 Over voltage - Detection level 1.05~1.50, step:0.01

2157 Over voltage - Detection Time 0~180.0, step:0.1

2158 Over voltage - Function Select 0(Off),1(Alarm),2(Trip)

2159 Under Frequency - Detection Level 47.00~59.98,step:0.01

2160 Under Frequency - Detection Delay Time 0.03~10.00, step:0.01

2161 Under Frequency - Function Select 0(Off),1(Alarm),2(Trip)

2162 Sync Fail - Phase difference 5~60

2163 Sync Fail - Delay Time 0.1~30.0 step:0.1

2164 Sync Fail - Function Select 0(Off),1(On)

2165 Phase Cold Load Pickup Multiplier 0(Off), 1~10

2166 Phase Cold Load Duration 0.00~60.00 step:0.01

2167 Ground Cold Load Pickup Multiplier 0(Off), 1~10

2168 Ground Cold Load Duration 0.00~60.00 step:0.01

2169 Oper. To Lockout Phase 1~4

2170 Oper. To Lockout Ground 1~4

2171 Oper. Fast Curve Phase 0~4

2172 Oper. Fast Curve Ground 0~4

2173 High Current Phase Active 0~4

2174 High Current Ground Active 0~4

2175 Phase/Ground Reclose Interval 1st 0.5~180.0,step:0.1

2176 Phase/Ground Reclose Interval 2nd 1~180

2177 Phase/Ground Reclose Interval 3rd 1~180

2178 Phase/Ground Reclose Interval 4th 1~180

2179 Phase/Ground Reset Time 3~180

2180 Oper. To Lockout SEF 1~4

2181 SEF Reclose Interval 1st 0.5~180.0,step:0.1

2182 SEF Reclose Interval 2nd 1~180

2183 SEF Reclose Interval 3rd 1~180

2184 SEF Reclose Interval 4th 1~180

2185 SEF Reset Time 3~180

2186 Single Shot Time 0~180

Page 184: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 184

ISO 9001 certified Jin Kwang E & C Corp.

2187 Seq. Coordination Active 0(Off),1(On)

Setting Group3

2188 Phase Pickup Current 10~1260A

2189 Phase Fast TCC type 1~48

2190 Phase Fast Time Multiplier 0.05~2.00,step:0.01

2191 Phase Fast Time Adder 0.00~1.00sec,step:0.01

2192 Phase Fast Min Response Time 0.00~1.00sec,step:0.01

2193 Phase Fast Reset Type RDMT(0)/RIDMT(1)

2194 Phase Fast RDMT 0.00~100.00,step:0.01

2195 Phase Delay TCC type 1~48

2196 Phase Delay Time Multiplier 0.05~2.00,step:0.01

2197 Phase Delay Time Adder 0.00~1.00sec,step:0.01

2198 Phase Delay Min Response Time 0.00~1.00sec,step:0.01

2199 Phase Delay Reset Type RDMT(0)/RIDMT(1)

2200 Phase Delay RDMT 0.00~100.00,step:0.01

2201 Phase Definite Time O/C Active ON(1),OFF(0)

2202 Phase Definite Time O/C Level 50~10000A

2203 Phase Definite Time O/C Response Time 0.00~1.00sec,step:0.01

2204 Phase High Current Pickup 50~10000A

2205 Phase High Current Time Adder 0.00~1.00sec,step:0.01

2206 Phase 2nd harmonic restraint 0(No),1(Yes)

2207 Phase Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2208 Ground Pickup Current 5~900A

2209 Ground Fast TCC type 1~48

2210 Ground Fast Time Multiplier 0.05~2.00,step:0.01

2211 Ground Fast Time Adder 0.00~1.00sec,step:0.01

2212 Ground Fast Min Response Time 0.00~1.00sec,step:0.01

2213 Ground Fast Reset Type RDMT(0)/RIDMT(1)

2214 Ground Fast RDMT 0.00~100.00,step:0.01

2215 Ground Delay TCC type 1~48

2216 Ground Delay Time Multiplier 0.05~2.00,step:0.01

2217 Ground Delay Time Adder 0.00~1.00sec,step:0.01

2218 Ground Delay Min Response Time 0.00~1.00sec,step:0.01

2219 Ground Delay Reset Type RDMT(0)/RIDMT(1)

2220 Ground Delay RDMT 0.00~100.00,step:0.01

2221 Ground Definite Time O/C Active ON(1),OFF(0)

2222 Ground Definite Time O/C Level 50~10000A

Page 185: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 185

ISO 9001 certified Jin Kwang E & C Corp.

2223 Ground Definite Time Response Time 0.00~1.00sec,step:0.01

2224 Ground High Current Pickup 50~10000A

2225 Ground High Current Time Adder 0.00~1.00,step:0.01

2226 Ground 2nd harmonic Restraint 0(No),1(Yes)

2227 Ground Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2228 SEF - Pickup Current(3Io) 0.1~20.0A

2229 SEF - Pickup Voltage(-3Vo) 10~80%

2230 SEF - Max. Torque Angle 0~345,step:15 DEG

2231 SEF - Detection Time 0.1~30.0 step:0.1 Sec

2232 SEF - 2nd harmonic restraint No(0),Yes(1)

2233 SEF - Function Select 0(Off),1(Alarm),2(Trip)

2234 2nd Inrush - harmonic level 5~50%

2235 2nd Inrush - Detection Time 0.02~1.00,step:0.01

2236 2nd Inrush - Function Select 0(Off),1(On)

2237 Direction – 3I1 Threshold 0.00~1.00, step:0.01

2238 Direction – 3V1 Threshold 0.00~1.00, step:0.01

2239 Direction – 3I1 Max Torque Angle 0~355, step:5

2240 Direction – 3Io Max Torque Angle 0~355, step:5

2241 Direction – 3Io Threshold 0.00~1.00, step:0.01

2242 Direction – -3Vo Threshold 0.00~1.00, step:0.01

2243 Phase Loss - Volt On level 50~90,step:5

2244 Phase Loss - Volt Off level 35~75,step:5

2245 Phase Loss - Detection Time 0.1~30.0 step:0.1

2246 Phase Loss - Function Select 0(Off),1(On)

2247 Under voltage - Detection level 0.30~0.95, step:0.01

2248 Under voltage - Detection Time 0~180.0, step:0.1

2249 Under voltage - Function Select 0(Off),1(Alarm),2(Trip)

2250 Over voltage - Detection level 1.05~1.50, step:0.01

2251 Over voltage - Detection Time 0~180.0, step:0.1

2252 Over voltage - Function Select 0(Off),1(Alarm),2(Trip)

2253 Under Frequency - Detection Level 47.00~59.98,step:0.01

2254 Under Frequency - Detection Delay Time 0.03~10.00, step:0.01

2255 Under Frequency - Function Select 0(Off),1(Alarm),2(Trip)

2256 Sync Fail - Phase difference 5~60

2257 Sync Fail - Delay Time 0.1~30.0 step:0.1

2258 Sync Fail - Function Select 0(Off),1(On)

2259 Phase Cold Load Pickup Multiplier 0(Off), 1~10

Page 186: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 186

ISO 9001 certified Jin Kwang E & C Corp.

2260 Phase Cold Load Duration 0.00~60.00 step:0.01

2261 Ground Cold Load Pickup Multiplier 0(Off), 1~10

2262 Ground Cold Load Duration 0.00~60.00 step:0.01

2263 Oper. To Lockout Phase 1~4

2264 Oper. To Lockout Ground 1~4

2265 Oper. Fast Curve Phase 0~4

2266 Oper. Fast Curve Ground 0~4

2267 High Current Phase Active 0~4

2268 High Current Ground Active 0~4

2269 Phase/Ground Reclose Interval 1st 0.5~180.0,step:0.1

2270 Phase/Ground Reclose Interval 2nd 1~180

2271 Phase/Ground Reclose Interval 3rd 1~180

2272 Phase/Ground Reclose Interval 4th 1~180

2273 Phase/Ground Reset Time 3~180

2274 Oper. To Lockout SEF 1~4

2275 SEF Reclose Interval 1st 0.5~180.0,step:0.1

2276 SEF Reclose Interval 2nd 1~180

2277 SEF Reclose Interval 3rd 1~180

2278 SEF Reclose Interval 4th 1~180

2279 SEF Reset Time 3~180

2280 Single Shot Time 0~180

2281 Seq. Coordination Active 0(Off),1(On)

Setting Group4

2282 Phase Pickup Current 10~1260A

2283 Phase Fast TCC type 1~48

2284 Phase Fast Time Multiplier 0.05~2.00,step:0.01

2285 Phase Fast Time Adder 0.00~1.00sec,step:0.01

2286 Phase Fast Min Response Time 0.00~1.00sec,step:0.01

2287 Phase Fast Reset Type RDMT(0)/RIDMT(1)

2288 Phase Fast RDMT 0.00~100.00,step:0.01

2289 Phase Delay TCC type 1~48

2290 Phase Delay Time Multiplier 0.05~2.00,step:0.01

2291 Phase Delay Time Adder 0.00~1.00sec,step:0.01

2292 Phase Delay Min Response Time 0.00~1.00sec,step:0.01

2293 Phase Delay Reset Type RDMT(0)/RIDMT(1)

2294 Phase Delay RDMT 0.00~100.00,step:0.01

2295 Phase Definite Time O/C Active ON(1),OFF(0)

Page 187: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 187

ISO 9001 certified Jin Kwang E & C Corp.

2296 Phase Definite Time O/C Level 50~10000A

2297 Phase Definite Time O/C Response Time 0.00~1.00sec,step:0.01

2298 Phase High Current Pickup 50~10000A

2299 Phase High Current Time Adder 0.00~1.00sec,step:0.01

2300 Phase 2nd harmonic restraint 0(No),1(Yes)

2301 Phase Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2302 Ground Pickup Current 5~900A

2303 Ground Fast TCC type 1~48

2304 Ground Fast Time Multiplier 0.05~2.00,step:0.01

2305 Ground Fast Time Adder 0.00~1.00sec,step:0.01

2306 Ground Fast Min Response Time 0.00~1.00sec,step:0.01

2307 Ground Fast Reset Type RDMT(0)/RIDMT(1)

2308 Ground Fast RDMT 0.00~100.00,step:0.01

2309 Ground Delay TCC type 1~48

2310 Ground Delay Time Multiplier 0.05~2.00,step:0.01

2311 Ground Delay Time Adder 0.00~1.00sec,step:0.01

2312 Ground Delay Min Response Time 0.00~1.00sec,step:0.01

2313 Ground Delay Reset Type RDMT(0)/RIDMT(1)

2314 Ground Delay RDMT 0.00~100.00,step:0.01

2315 Ground Definite Time O/C Active ON(1),OFF(0)

2316 Ground Definite Time O/C Level 50~10000A

2317 Ground Definite Time Response Time 0.00~1.00sec,step:0.01

2318 Ground High Current Pickup 50~10000A

2319 Ground High Current Time Adder 0.00~1.00,step:0.01

2320 Ground 2nd harmonic Restraint 0(No),1(Yes)

2321 Ground Fault Trip Direction 0(off),1(fwd),2(rev),3(fwd or rev)

2322 SEF - Pickup Current(3Io) 0.1~20.0A

2323 SEF - Pickup Voltage(-3Vo) 10~80%

2324 SEF - Max. Torque Angle 0~345,step:15 DEG

2325 SEF - Detection Time 0.1~30.0 step:0.1 Sec

2326 SEF - 2nd harmonic restraint No(0),Yes(1)

2327 SEF - Function Select 0(Off),1(Alarm),2(Trip)

2328 2nd Inrush - harmonic level 5~50%

2329 2nd Inrush - Detection Time 0.02~1.00,step:0.01

2330 2nd Inrush - Function Select 0(Off),1(On)

2331 Direction – 3I1 Threshold 0.00~1.00, step:0.01

2332 Direction – 3V1 Threshold 0.00~1.00, step:0.01

Page 188: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 188

ISO 9001 certified Jin Kwang E & C Corp.

2333 Direction – 3I1 Max Torque Angle 0~355, step:5

2334 Direction – 3Io Max Torque Angle 0~355, step:5

2335 Direction – 3Io Threshold 0.00~1.00, step:0.01

2336 Direction – -3Vo Threshold 0.00~1.00, step:0.01

2337 Phase Loss - Volt On level 50~90,step:5

2338 Phase Loss - Volt Off level 35~75,step:5

2339 Phase Loss - Detection Time 0.1~30.0 step:0.1

2340 Phase Loss - Function Select 0(Off),1(On)

2341 Under voltage - Detection level 0.30~0.95, step:0.01

2342 Under voltage - Detection Time 0~180.0, step:0.1

2343 Under voltage - Function Select 0(Off),1(Alarm),2(Trip)

2344 Over voltage - Detection level 1.05~1.50, step:0.01

2345 Over voltage - Detection Time 0~180.0, step:0.1

2346 Over voltage - Function Select 0(Off),1(Alarm),2(Trip)

2347 Under Frequency - Detection Level 47.00~59.98,step:0.01

2348 Under Frequency - Detection Delay Time 0.03~10.00, step:0.01

2349 Under Frequency - Function Select 0(Off),1(Alarm),2(Trip)

2350 Sync Fail - Phase difference 5~60

2351 Sync Fail - Delay Time 0.1~30.0 step:0.1

2352 Sync Fail - Function Select 0(Off),1(On)

2353 Phase Cold Load Pickup Multiplier 0(Off), 1~10

2354 Phase Cold Load Duration 0.00~60.00 step:0.01

2355 Ground Cold Load Pickup Multiplier 0(Off), 1~10

2356 Ground Cold Load Duration 0.00~60.00 step:0.01

2357 Oper. To Lockout Phase 1~4

2358 Oper. To Lockout Ground 1~4

2359 Oper. Fast Curve Phase 0~4

2360 Oper. Fast Curve Ground 0~4

2361 High Current Phase Active 0~4

2362 High Current Ground Active 0~4

2363 Phase/Ground Reclose Interval 1st 0.5~180.0,step:0.1

2364 Phase/Ground Reclose Interval 2nd 1~180

2365 Phase/Ground Reclose Interval 3rd 1~180

2366 Phase/Ground Reclose Interval 4th 1~180

2367 Phase/Ground Reset Time 3~180

2368 Oper. To Lockout SEF 1~4

2369 SEF Reclose Interval 1st 0.5~180.0,step:0.1

Page 189: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)

Instruction manual of SF6 recloser with FTU-R200 control unit 189

ISO 9001 certified Jin Kwang E & C Corp.

2370 SEF Reclose Interval 2nd 1~180

2371 SEF Reclose Interval 3rd 1~180

2372 SEF Reclose Interval 4th 1~180

2373 SEF Reset Time 3~180

2374 Single Shot Time 0~180

2375 Seq. Coordination Active 0(Off),1(On)

Common Setting

2376 Default setting group 1~4

2377 Automation Detection Group Selection 0(Off),1(On)

2378 Reverse power flow setting group 1~4

Page 190: User's Guide & Manual of Sf6 Recloser With FTU-R200_1203 (1)