General Details Product Description General Product Use Properties Evaluated Code Compliance Meets requirements for Suspended Ceilings in accordance with: Seismic Classification ver 2.0 Page 1 of 7 3. All construction, wood or steel framing, beams, joist, stringers and associated connections needed to support the Donn ® AdvanceSpan Ceiling System are outside the scope of this PER. All construction shall follow applicable codes or be designed by a licensed Engineer. 4. Finish is not UV-resistant. All USG Donn Brand Suspension Grid Systems should not be installed where directly exposed to sun or weather. Approved Manufacturing Locations Evaluation Report Information The Donn AdvanceSpan Systems described in this report, are assemblies used in interior general-use areas only. The suspended ceiling systems consist of DXASHRC & DXTASHRC Main Tees, US44 Channel Molding with US44CC Channel Clips, ASMTSP Splice Plates, and ASCBC Cross Brace Clips. All steel framing members (Main Tees, Cross Tees, & Wall Molding) have a minimum Type G30 hot- dipped galvanized coating and are manufactured using ASTM A653 steel with a minimum yield strength of 30-ksi. US44CC Channel Clips and ASMTSP Splice Plates are manufactured from minimum 30-ksi steel conforming to ASTM A653 with a minimum G90 galvanized coating. Report Owner USG Interiors, LLC [email protected] USG Support: 800.USG4YOU USG Interiors, LLC Plant # 601 1000 Crocker Rd. Westlake, OH 44145 Donn AdvanceSpan Ceiling System shall be installed in accordance with the provisions of ASTM C636 and ASTM E580 unless otherwise qualified through testing. This suspension system has been uniform load tested in accordance with the methods outlined in ASTM C635 with modifications for longer spans. This report covers the USG Donn AdvanceSpan Suspension System. USG Interiors, LLC has a Product Evaluation Service Agreement with Pei Evaluation Service ® (Pei ES) / Follow-up Inspection Service Agreement with Progressive Engineering Inc. (Pei ). The manufacturing location shown in this PER has an approved Quality Control Manual and is audited Quarterly by Pei . Meets the requirements of ASTM C635 (modified) and installation requirements of ASTM C636 as required in the 2012/2015 IBC. 1. Donn AdvanceSpan Systems shall be installed in accordance with the Donn AdvanceSpan Installation Guide (AC3325) and are subject to the conditions of this PER. A copy of the installation guide shall be made easily available to the installer. 2. Complies with ASTM C635 and must be installed in accordance with ASTM C636, ASTM E580, CISCA, and standard industry practices, within applicable code requirements. Product USG Donn ® AdvanceSpan Suspension System 550 West Adams Street Chicago, Illinois 60661 October, 2017 Pei Evaluation Service ® is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Product Evaluation Report represents a product that Pei ES has Evaluated. This product has a Product Evaluation Service Agreement & Follow-up Inspection Service Agreement. This Product Evaluation Report in no way implies warranty for this product or relieves USG Interiors, LLC of their liability for this product. This PER is an official document if it is within one year of the initial or re- approval date. Initial Approval October, 2016 Re-Approved See all Pei ES Listings at: www.p-e-i.com PER-16100 Table 1 - Seismic Design Classification Seimsic Design Category A, B Seimsic Design Category C Seimsic Design Category D, E, F No Requirement Intermediate Duty Heavy Duty 2012 / 2015 International Residential Code Section R302.9 2012 / 2015 International Building Code Section 2506.2.1 Section 1613 Section 808 Section 803.1.1

USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

General Details

Product Description

General Product Use

Properties Evaluated

Code Compliance Meets requirements for Suspended Ceilings in accordance with:

Seismic Classification

ver 2.0 Page 1 of 7

3. All construction, wood or steel framing, beams, joist, stringers and associated connections needed to support the Donn® AdvanceSpanCeiling System are outside the scope of this PER. All construction shall follow applicable codes or be designed by a licensed Engineer.

4. Finish is not UV-resistant. All USG Donn Brand Suspension Grid Systems should not be installed where directly exposed to sun orweather.

Approved Manufacturing Locations

Evaluation Report Information

The Donn AdvanceSpan Systems described in this report, are assemblies used in interior general-use areas only. The suspended ceilingsystems consist of DXASHRC & DXTASHRC Main Tees, US44 Channel Molding with US44CC Channel Clips, ASMTSP Splice Plates,and ASCBC Cross Brace Clips. All steel framing members (Main Tees, Cross Tees, & Wall Molding) have a minimum Type G30 hot-dipped galvanized coating and are manufactured using ASTM A653 steel with a minimum yield strength of 30-ksi. US44CC Channel Clipsand ASMTSP Splice Plates are manufactured from minimum 30-ksi steel conforming to ASTM A653 with a minimum G90 galvanizedcoating.

Report OwnerUSG Interiors, LLC

[email protected] Support: 800.USG4YOU

USG Interiors, LLCPlant # 601

1000 Crocker Rd.Westlake, OH 44145

Donn AdvanceSpan Ceiling System shall be installed in accordance with the provisions of ASTM C636 and ASTM E580 unless otherwisequalified through testing. This suspension system has been uniform load tested in accordance with the methods outlined in ASTM C635with modifications for longer spans.

This report covers the USG Donn AdvanceSpan Suspension System. USG Interiors, LLC has a Product Evaluation Service Agreementwith Pei Evaluation Service® (Pei ES) / Follow-up Inspection Service Agreement with Progressive Engineering Inc. (Pei ). Themanufacturing location shown in this PER has an approved Quality Control Manual and is audited Quarterly by Pei .

Meets the requirements of ASTM C635 (modified) and installation requirements of ASTM C636 as required in the 2012/2015 IBC.

1. Donn AdvanceSpan Systems shall be installed in accordance with the Donn AdvanceSpan Installation Guide (AC3325) and aresubject to the conditions of this PER. A copy of the installation guide shall be made easily available to the installer.2. Complies with ASTM C635 and must be installed in accordance with ASTM C636, ASTM E580, CISCA, and standard industry practices,within applicable code requirements.

Product

USG Donn® AdvanceSpan Suspension System

550 West Adams StreetChicago, Illinois 60661

October, 2017

Pei Evaluation Service® is an accredited ISO Standard 17065 Product Certifier,accredited by the IAS. This Product Evaluation Report represents a product thatPei ES has Evaluated. This product has a Product Evaluation Service Agreement &Follow-up Inspection Service Agreement. This Product Evaluation Report in noway implies warranty for this product or relieves USG Interiors, LLC of their liability forthis product. This PER is an official document if it is within one year of the initial or re-approval date.

Initial ApprovalOctober, 2016

Re-Approved

See all Pei ES Listings at: www.p-e-i.com

PER-16100

Table 1 - Seismic Design Classification

Seimsic Design Category A, B Seimsic Design Category C Seimsic Design Category D, E, F

No Requirement Intermediate Duty Heavy Duty

2012 / 2015 International Residential Code

Section R302.9

2012 / 2015 International Building Code

Section 2506.2.1Section 1613Section 808Section 803.1.1

Page 2: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Standard Load Ratings

Shaketable Qualified Installations

Product Labeling

1. USG Interior, LLC Name and Address2. Product name3. Plant identifier & date code4. Pei ES Information: See Pei Evaluation Report at p-e-i.com

Acceptable Evaluation Marks

Product Documentation

Page 2 of 7

USG Interiors, LLC Quality Control Manual for Donn Brand Suspension Systems and USG Drywall Suspension Systems - Dated:September 18, 2017

Each Grid system shipment assembly, that is covered by this Product Evaluation Report, must have a label attached with at least thefollowing information:

A Follow-up Inspection Service Agreement between Progressive Engineering Inc. and USG Interiors, LLCA Product Evaluation Service Agreement between Pei Evaluation Service® and USG Interiors, LLC

USG Donn AdvanceSpan Installation Guide (AC3325) - Dated: May, 2016USG Donn AdvanceSpan Data Submittal Sheet (AC3324) - Dated: August, 2017SDS for USG Donn® DX®/DXL™ Acoustical Suspension System - Version #3 - Dated: September 15, 2016

PER-16100

DX216 4'-0"DX424 4'-0"DX216 2'-0"DX424 2'-0"DX216 2'-0"DX424 2'-0"

DXT222 4'-0"DXT424 4'-0"DXT222 2'-0"DXT424 2'-0"DXT222 2'-0"DXT424 2'-0"

Notes:

Figure 7(3/8" Gap)

Figure 7 (3/8" Gap)

Figure 7(3/8" Gap)

3.0 Figure 7 (3/8" Gap)

4.0 Figure 6Figure 5 (3/4" Gap)

Maximum System

Weight5 (psf)

Figures for Adjacent "Floating" Sides

(Clearance)

Figures for Adjacent Fixed

Sides6

2'-0"

4'-0"

4'-0"

4.0 Figure 6Figure 5 (3/4" Gap)

4.0 Figure 6Figure 5 (3/4" Gap)

4.0 Figure 6Figure 5 (3/4" Gap)

3.0

4'-0"

Wall

Molding3

US44

US44

US44

US44

US44

US44

2'-0"

4'-0"

DXTAS

8'-6"

7'-0"

8'-0"

ASDXT Suspension

System

3.0

3.0

2.75

D, E, F

D, E, F

C

6. Systems approved as Intermediate Duty (Seismic Design Category C) were tested with all sides "floating" and a 3/8" gap on all sides.

Table 3 - USG Donn AdvanceSpan AC156 Seismic Qualified Installations

4. See Figure 4 for referenced cross tee details.3. See Figure 1 for main tee and wall molding details.

Main Tee3

USG System ID

Passed AC156 @

Ss (g)

Approved Seismic

Category1

Cross Tee4

ASDX Suspension

System

3.0

1. All systems are approved for use in Seismic Design Category A, B, and C. Systems approved for Seismic Design Category C may be considered IntermediateDuty installations, and systems approved for Seismic Design Category D,E, & F may be considered Heavy Duty installations in accordance with the definition from 2. Systems from Table 3 are limited to use with the maximum unsupported length shown. Unsupported length is maximum main tee span between wall moldingsupports without the use of hanger wires, perimeter wires, or splay wires.

3.0

2.75

D, E, F

5. Maximum system weight was achieved by using two layers of Gypsum Lay-in Panels (GLIP) for Heavy Duty installations and one layer of GLIP with 1 layer ofRadar panels for Intermediate Duty installations. Alternative lay-in panels of equivalent plan dimensions (2'x2' or 2'x4' as applicable) may be utilized as long as thesystem weight does not exceed that shown in Table 3 for the respective system.

USG Model

Unsupported

Length2 SpacingUSG Model

OptionsMaximum Spacing

D, E, F

C

DXAS

DXAS

DXAS

8'-6"

7'-0"

8'-0"

DXTAS

DXTAS

8' Max Span 7' Max Span3 7' Max Span 8' Max SpanDXASHRC 0.021 Intermediate Duty Heavy Duty 16.0 12.0

DXTASHRC 0.021 Intermediate Duty Heavy Duty 16.0 12.0Notes:

Table 2 - Rated Loads5

Main TeeMetal Thickness

(in)ASTM Class4

1. ASTM Class is valid when the ceiling grid is installed in accordance with ASTM C636 and/or ASTM E580.2. Rated loads are based upon the load at a deflection limit of L/360.3. All spans of 7-feet or less meet the requirements of Heavy Duty in accordance with the ASTM C635.4. ASTM C635 Class: Intermediate Duty ≥ 12 lb/ft; Heavy Duty ≥ 16 lb/ft

5. Refer to Table 3 for alternative system installations approved for use in Seismic Design Category C and/or D, E, & F when tested inaccordance with AC156.

Page 3: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Page 3 of 7

PER-16100

Page 4: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Page 4 of 7

PER-16100

Page 5: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Page 5 of 7

PER-16100

Page 6: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Page 6 of 7

PER-16100

Page 7: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

Page 7 of 7

PER-16100

Page 8: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

General Details

CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with:

2016 CBC Chapter 8 (BSC, SFM, HCD 1, HCD 2, DSA SS, DSA SS/CC, OSHPD 1, OSHPD 2, & OSHPD 4):

2016 CBC Chapter 16 (BSC, HCD 1, HCD 2, DSA SS/CC, OSHPD 2, & OSHPD 3):

ver 2.0 Page 1 of 2

2. Expansion joints are required at all corridor intersections and junctions of corridors at lobbies or other similar areas.

13.5.6.2.2 - Modifications to ASTM E5801. When installed in exitways of hospitals and essential service buildings, each lay-in tile/board/panel and lightfixture or grille shall be installed with either a main tee or cross tee surrounding all sides. Lateral force diagonalbracing may be omitted in the transverse direction for spans between braced partition walls of less than 8 feetassuming perimeter support is provided in accordance with ASTM E580 Sections 5.2.2 and 5.2.3. Connectionsmust be designed to resist the ceiling lateral forces.

Pei Evaluation Service® is an accredited ISO Standard 17065 Product Certifier,accredited by the IAS. This Product Evaluation Report represents a product thatPei ES has Evaluated. This product has a Product Evaluation Service Agreement &Follow-up Inspection Service Agreement. This Product Evaluation Report in noway implies warranty for this product or relieves USG Interiors, LLC of their liability forthis product. This PER supplement is an official document if it is within one year of theinitial or re-approval date of the master PER.

Initial Approval Re-ApprovedJune, 2017 October, 2017

See all Pei ES Listings at: www.p-e-i.com

Report Owner Approved Manufacturing LocationsUSG Interiors, LLC USG Interiors, LLC

Plant # 6011000 Crocker Rd.

Westlake, OH 44145

550 West Adams StreetChicago, Illinois 60661

Product Evaluation Report Information

USG Donn® AdvanceSpan Suspension System

[email protected] Support: 800.USG4YOU

This PER supplement provides details of California Building Code (CBC) compliance for the USG Donn AdvanceSpan suspension systemdescribed in PER-16100.

803.1.1 - Lay-in ceiling panels and other finish material shall be classified in accordance with ASTM E84 or UL 723. Refer to 2016 CBCTable 803.11 for classification requirements based on occupancy.808 - The USG Donn AdvanceSpan suspension system meets the requirements of acoustical ceiling systems when installed in accordance with ASTM C635 and ASTM C636. All acoustical finish materials used in combination with the grid system shall meet the requirements of CBC Section 803. Fire-resistance rated construction has not been evaluated.

1616.10.16 - Modifications to ASCE 7, Section 13.5.6

Exception - Lateral force diagonal bracing and ASTM E580 perimeter installation requirementsmay be omitted as applicable for seismically qualified designs described in PER -16100 Table 3.See PER -16100 Figures 5 and Figure 6 for alternative perimeter installation options in SeismicDesign Category D, E, & F.

13.5.6.1 - When determining seismic forces, the weight of the ceiling (Wp) shall not be taken less than 4 psf and the calculated seismic force (Fp) shall be transmitted through the ceiling attachments to the building structural elements. Connections to the building structural elements and the ceiling-structure boundary shall be evaluated by a registered design professional.

Exception - The USG Donn AdvanceSpan system has been evaluated for the longer spans as indicated in Table 2 of PER -16100 when otherwise installed in accordance with ASTM C635 and ASTM C636.

13.5.6.2 - USG AdvanceSpan grid system may be designed in accordance with ASTM E580 Section 5.2.8, seismic qualified in accordance with ASCE 7 Sections 13.2.5 or 13.2.6 (See PER-16100 Table 3), or otherwise designed and constructed in accordance with CBC modifications to ASCE 7 Sections 13.5.6.2.1 and 13.5.6.2.2.

Exception - The USG Donn AdvanceSpan system has been evaluated for the longer spans indicated in Table 2 of PER -16100 when otherwise installed in accordance with ASTM E580 with CBC modifications.

13.5.6.2.1 - For Seismic Design Categories D, E, and F, the USG Donn AdvanceSpan grid system described in PER-16100 Table 2 shall be designed and installed in accordance with ASTM C635, ASTM C636, and ASTM E580 with CBC modifications and exception for longer spans evaluated. Exceptions to lateral bracing of partition walls supporting the perimeter of the suspended ceiling system (see ASCE 7 Section 13.5.8.1) shall not be used in Seismic Design Categories D, E, or F.

PER-16100-CBC

Page 9: USG Donn® Brand AdvanceSpan™ PEI Report (English) - 16100 · General Details CBC Code Compliance Meets requirements for Suspended Ceilings in accordance with: 2016 CBC Chapter

2016 CBC Chapter 16A (DSA SS, OSHPD 1, & OSHPD 4):

2016 CBC Chapter 25 (BSC, HCD 1, HCD 2, DSA SS, DSA SS/CC, OSHPD 1, OSHPD 2, & OSHPD 3):

Page 2 of 2

3. Metal panels and non-acoustical panels weighing more than 0.5 pounds per square foot shall be positively attached to the ceiling suspension grid unless otherwise seismically qualified in accordance with Table 3 of PER-16100.4. Lateral force bracing is required for all ceiling areas greater than 144 square feet when the perimeter support in accordance with ASTM E580 Sections 5.2.2 and 5.2.3 are provided. Perimeter walls must be designed to resist the ceiling lateral forces and horizontal restraint point spacing shall not exceed a spacing of 12 feet by 12 feet. Bracing wires must be secured with four tight twists in 1.5 inches.5. A minimum 6" clearance is required between ceiling support/bracing and all pipes, ducts, conduits, and equipment that are not braced for horizontal forces, unless approved by the building official.

2506.2.1 - USG Donn AdvanceSpan has been evaluated in accordance with ASTM C635 and Section 13.5.6 of ASCE 7. Table 2 of PER-16100 provides details of approved spans longer than the standard 4 feet for both Heavy Duty and Intermediate Duty use. See CBC Sections 1616.10.16 and 1616A.1.21 for modifications to ASCE 7 Section 13.5.6 and ASTM E580. Refer to Table 3 of PER-16100 for designs that have been seismically qualified through AC156 shake table testing.

3. Metal panels and non-acoustical panels weighing more than 0.5 pounds per square foot shall be positively attached to the ceiling suspension grid unless otherwise seismically qualified in accordance with Table 3 of PER-16100.4. Lateral force bracing is required for all ceiling areas greater than 144 square feet when the perimeter support in accordance with ASTM E580 Sections 5.2.2 and 5.2.3 are provided. Perimeter walls must be designed to resist the ceiling lateral forces and horizontal restraint point spacing shall not exceed a spacing of 12 feet by 12 feet. Bracing wires must be secured with four tight twists in 1.5 inches.5. A minimum 6" clearance is required between ceiling support/bracing and all pipes, ducts, conduits, and equipment that are not braced for horizontal forces, unless approved by the building official.

1616A.1.21 - Modifications to ASCE 7, Section 13.5.613.5.6.1 - When determining seismic forces, the weight of the ceiling and all components (Wp) shall not be taken less than 4 psf and the calculated seismic force (Fp) shall be transmitted through the ceiling attachments to the building structural elements. Connections to the building structural elements and the ceiling-structure boundary shall be evaluated by a registered design professional.

13.5.6.2 - USG AdvanceSpan grid system may be designed in accordance with ASTM E580 Section 5.2.8, seismic qualified in accordance with ASCE 7 Sections 13.2.5 or 13.2.6 (See PER-16100 Table 3), or otherwise designed and constructed in accordance with CBC modifications to ASCE 7 Sections 13.5.6.2.1 and 13.5.6.2.2.

Exception - The USG Donn AdvanceSpan system has been evaluated for the longer spans indicated in Table 2 of PER -16100 when otherwise installed in accordance with ASTM E580 with CBC modifications.

13.5.6.2.1 - For Seismic Design Categories D, E, and F, the USG Donn AdvanceSpan grid system described in PER-16100 Table 2 shall be designed and installed in accordance with ASTM C635, ASTM C636, and ASTM E580 with CBC modifications and exception for longer spans evaluated. Exceptions to lateral bracing of partition walls supporting the perimeter of the suspended ceiling system (see ASCE 7 Section 13.5.8.1) shall not be used in Seismic Design Categories D, E, or F.13.5.6.2.2 - Modifications to ASTM E580

1. When installed in exitways of hospitals and essential service buildings, each lay-in tile/board/panel and lightfixture or grille shall be installed with either a main tee or cross tee surrounding all sides. Lateral force diagonalbracing may be omitted in the transverse direction for spans between braced partition walls of less than 8 feetassuming perimeter support is provided in accordance with ASTM E580 Sections 5.2.2 and 5.2.3. Connectionsmust be designed to resist the ceiling lateral forces.

Exception - Lateral force diagonal bracing and ASTM E580 perimeter installation requirementsmay be omitted as applicable for seismically qualified designs described in PER -16100 Table 3.See PER -16100 Figures 5 and Figure 6 for alternative perimeter installation options in SeismicDesign Category D, E, & F.

2. Expansion joints are required at all corridor intersections and junctions of corridors at lobbies or other similar areas.

13.5.6.2.2 - Modifications to ASTM E580 continued….