Using SF Using SF 6 6 Analysis for Analysis for Condition Based Maintenance of Condition Based Maintenance of Circuit Breakers and Circuit Breakers and Gas Insulated Substation Gas Insulated Substation Antony Giacomin TJ|H2b Analytical Services, Pty. Ltd.

Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

  • Upload
    vanphuc

  • View
    231

  • Download
    7

Embed Size (px)

Citation preview

Page 1: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Using SFUsing SF66 Analysis forAnalysis forCondition Based Maintenance ofCondition Based Maintenance of

Circuit Breakers andCircuit Breakers andGas Insulated SubstationGas Insulated Substation

Antony GiacominTJ|H2b Analytical Services, Pty. Ltd.

Page 2: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Reasons for TestingReasons for Testing

Acceptance testing (purity)Acceptance testing (purity)SafetySafetyHandling & processingHandling & processingFault identification/failure mode processesFault identification/failure mode processesWear outWear out

Page 3: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

AACCEPTANCE TESTINGCCEPTANCE TESTING

Numerous new suppliers have entered Numerous new suppliers have entered marketmarketSF6 is manufactured for different SF6 is manufactured for different applicationsapplications

Page 4: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

ASTM SFASTM SF66 SpecificationSpecification

Moisture 8.0 ppm w/w

Air 500 ppm w/w

CF4 500 ppm w/w

Assay 99.8% wt

Page 5: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

IEC SFIEC SF66 SpecificationSpecification

Moisture 15 ppm w/w

Air 500 ppm w/w

CF4 500 ppm w/w

Page 6: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

SAFETYSAFETY

Numerous decomposition products formed Numerous decomposition products formed –– many toxicmany toxic

Page 7: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Threshold Limit Values in Threshold Limit Values in ppmppm of SFof SF66Gaseous Decomposition ProductsGaseous Decomposition Products

SF6 Sulfur hexafluoride 1000SO2 Sulfur dioxide 3SF4 Sulfur tetrafluoride 0.1SOF2 Thionyl fluoride 1SO2F2 Sulfuryl fluoride 5SOF4 Thionyl tetrafluoride 0.5WF6 Tungsten hexafluoride 0.1CF4 Carbon tetrafluoride 1000

Page 8: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Threshold Limit Values in Threshold Limit Values in ppmppm of SFof SF66Solid Decomposition ProductsSolid Decomposition Products

AlF3 Aluminum fluoride 2.5CuF2 Cupric fluoride 1CuF Cuprous fluoride 1

Page 9: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Handling & ProcessingHandling & Processing

Uncontaminated SFUncontaminated SF66

SFSF66 slightly contaminated with SFslightly contaminated with SF66breakdown productsbreakdown productsSFSF66 severely contaminated with SFseverely contaminated with SF66breakdown productsbreakdown productsSFSF66 contaminated with moisturecontaminated with moistureSFSF66 slightly contaminated with airslightly contaminated with airSFSF66 severely contaminated with airseverely contaminated with air

Page 10: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

UncontaminatedSF6

Slightlycontaminated

SF6 with breakdownproducts

Severelycontaminated

SF6 with breakdownproducts

Slightlycontaminated

With air

Severelycontaminated

With air

ContaminatedWith moisture

AssessSF6

condition

Collect SF6Sample

Store and reuse

As needed

Filter and retest until

acceptable, then reuse

Reprocess SF6

Filter and retest until

acceptable, then reuse

Add new SF6 untilresidual air acceptable.

Reuse as needed

Reprocess SF6

Page 11: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

CigreCigre SF6 Recycling GuideSF6 Recycling Guide

50 50 ppmvppmv totaltotalReactive ComponentsReactive Components

160 Pa @ 0ºC 160 Pa @ 0ºC Equivalent to120 Equivalent to120 ppmvppmv ((liqliq))320 320 ppmvppmv @ 500 @ 500 kPakPa1600 1600 ppmvppmv @ 100 @ 100 kPakPa

H2OH2O

2% 2% volvol totaltotalAir and CF4Air and CF4

Proposed LevelsProposed LevelsComponentsComponents

Page 12: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

CIGRE 23.10 CIGRE 23.10 -- “SF6 Guidelines” “SF6 Guidelines” ELECTRA No. 173 (1997)ELECTRA No. 173 (1997)

InIn--service service guidelinesguidelines..

Total Air (O2 & N2): Total Air (O2 & N2): 30,000 ppm30,000 ppmWater content: 200 Water content: 200 ppmv.

Recycling or reRecycling or re--use use guidelines.guidelines.Total Air (O2 & N2): Total Air (O2 & N2): 20,000 ppm20,000 ppmWater content: 120 Water content: 120 ppmvppmv.ppmv. .

Page 13: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Comparison of Australian and NZ Comparison of Australian and NZ data against these guidelinesdata against these guidelines

59% of equipment tested met the 59% of equipment tested met the recycling guidelines of CIGRE 23.10 for recycling guidelines of CIGRE 23.10 for both air and water content.both air and water content.76% of equipment the CIGRE 23.10 76% of equipment the CIGRE 23.10 inin--service guidelines.service guidelines.Correct and careful sampling is required Correct and careful sampling is required to meet these specifications.to meet these specifications.

Page 14: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

DIAGNOSTIC TESTINGDIAGNOSTIC TESTING

Measuring various levels of Measuring various levels of decomposition products enables decomposition products enables detection of failure modes, faults and detection of failure modes, faults and wear activity.wear activity.

Page 15: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

SFSF66 ChemistryChemistry

Page 16: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

ChemistryChemistry

Page 17: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

S

F

F

F

F F

F

Page 18: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

F

S

F

F

F F

F

Page 19: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

FF

F S FFSF

F

SF FF

FF FF SF S

F

FF

Page 20: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

SF6

SF5

SF4

SF3

SF2

SF

S

F

F

F

F

F

e

e

e

e

e

F

e

Page 21: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Population DistributionPopulation Distribution

05

1015202530354045

SF6 SF5 SF4 SF3 SF2 SF S

Page 22: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

ELECTRIC DISCHARGESELECTRIC DISCHARGES

Type Occurrence Characteristics

Partial Discharge Electrically floating component Free conducting particles 0.01 – 0.010 J

102 – 104 Hz

Spark Capacitive discharge Disconnect switch 0.010 – 100 J

a few µs duration

Arc Breaker switch In-service fault 105 – 107 J

50 – 150 ms

Page 23: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Contamination with AirContamination with Air

Residual OResidual O22, N, N22, H, H22O from fillingO from fillingAbsorbed & Adsorbed OAbsorbed & Adsorbed O22, N, N22, H, H22OOIngress of OIngress of O22, N, N22, H, H22O through leaksO through leaks

Page 24: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Graham’s Law of EffusionGraham’s Law of Effusion

Vacuum

H2O

O2

N2

1 atm <0.001 atmp ≈ 1 atm

Page 25: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Graham’s Law of EffusionGraham’s Law of Effusion

SF6 @ 5 atm

p ≈ 5 atm<0.001 atm 5.0 atm

Page 26: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Graham’s Law of EffusionGraham’s Law of EffusionZWA0=pA0/(2πmkT)1/2

SF6

H2O

O2

N2

Page 27: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 28: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 29: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 30: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

SF6

SF5

SF4

SF3

SF2

SF

S

OH SOF4

SOF3

SOF2

SOF

SO

OH SO2F2

O

SOF4

SOF2

SO2F2

SO2F2

SO2F2SOF2

SO2F

SO2

SO2

OH

OH

OH

OH

H 2O

H 2O

H 2O

O2

O2O

O

O

O

O

F

F

F

F

F

e

Fe

O

e

O

e

e

F

e

Page 31: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Materials of ConstructionMaterials of Construction

Cu

(copper) CuF2 (solid)

W

(tu

ngste

n)

WF6

C

(c

arbo

n)H2O

CF4

WO3 (solid)

SF6

Al(aluminum)

Al, O

2 , C

SOF2 + AlF3 (solid) + CF4

AlF3 (solid)

Page 32: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Key SFKey SF6 6 GasesGases

ActivityActivitySOFSOF22

SOFSOF44

SOSO22FF22

SOSO2

Wear OutWear OutCFCF44

WFWF66

2

Page 33: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 34: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

CasesCases

Page 35: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Case 1 Case 1 -- Circuit BreakerCircuit Breaker161 kV, 2000 amp161 kV, 2000 amp

Compound Pole 1 Pole 2 Pole 3SF6 Sulfur hexafluoride 998191 995848 996190N2 Nitrogen 964 649 2917O2 Oxygen 341 136 638CF4 Carbon tetrafluoride 504 3365 255SOF2 Thionyl Fluoride ND 1 NDCO2 Carbon dioxide ND 1 ND

Page 36: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Case 2 Case 2 -- Gas Insulated Gas Insulated SubstationSubstation

Compound Segment 26 Segment 31SF6 Sulfur hexafluoride 825686 820579N2 Nitrogen 173657 178674CF4 Carbon tetrafluoride 184 329CO2 Carbon dioxide 255 254SOF4 Thionyl tetrafluoride 8 17H2 Hydrogen 210 146

Page 37: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Case 3 Case 3 –– 245kV Live Tank CB245kV Live Tank CB Compound SF6 Sulfur hexafluoride 670011N2 Nitrogen 144898O2 Oxygen 44409CF4 Carbon tetrafluoride 8719CO2 Carbon dioxide 18174SO2F2 Sulfuryl fluoride 3445SO2 Sulfur dioxide 109812COS Carbonyl Sulfide 533

Moisture 180 ppm

Page 38: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 39: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 40: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 41: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 42: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

SamplingSampling

Page 43: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Sampling IssuesSampling Issues

AirAirMoistureMoistureReactive surfacesReactive surfacesSample pressureSample pressure

Page 44: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Sampling SFSampling SF66

Page 45: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation

Sampling SFSampling SF66

Page 46: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation
Page 47: Using SF6 Analysis for Condition Based Maintenance of Circuit … - SF6 Testing.pdf · 6 Analysis for Condition Based Maintenance of Circuit Breakers and Gas Insulated Substation