96
Description 538929 1411c [8025816] VTIA Valve manifold

Valve manifold VTIA - Festo...The manifold sub-bases of the valve manifold provide the common ducts for the supply and exhaust air. Working lines 2 and 4 are provided for each valve

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

  • Description

    538929

    1411c

    [8025816]

    VTIA

    Valve manifold

  • VTIA

    2 Festo – P.BE-VTIA-EN – 1411c – English

    Translation of the original instructions

    P.BE-VTIA-EN

    Identification of hazards and instructions on how to prevent them:

    Warning

    Hazards that can cause death or serious injuries.

    Caution

    Hazards that can cause minor injuries or serious material damage.

    Other symbols:

    Note

    Material damage or loss of function.

    Recommendations, tips, references to other documentation.

    Essential or useful accessories.

    Information on environmentally sound usage.

    Text designations:

    � Activities that may be carried out in any order.

    1. Activities that should be carried out in the order stated.

    – General lists.

  • VTIA

    Festo – P.BE-VTIA-EN – 1411c – English 3

    Table of Contents – VTIA

    1 Safety and requirements for product use 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1 Safety 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1.1 General safety information 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1.2 Intended use 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2 Requirements for product use 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 Technical prerequisites 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.2 Qualification of the specialized personnel (requirements for the personnel) 8. . .

    1.2.3 Range of application and certifications 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2 Overview 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1 Product overview 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2 Overview of variants 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3 Description of components 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.1 Valves 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.2 Pilot control of the solenoid coils 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.3 Pressure zone separation 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.4 Vertical stacking 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.5 Pneumatic connection and control elements of the valve manifold 20. . . . . . . . . .

    2.3.6 Pneumatic connection and control elements of the vertical stacking

    components 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.7 Electrical components of the valve manifold 23. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3 Mounting and installation 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 Notes on mounting and dismounting 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2 Mounting variants 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2.1 Mounting/dismounting on an H-rail 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2.2 Wall mounting and dismounting 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3 Mounting the inscription labels (optional) 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4 Compressed air preparation 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.1 Operation with unlubricated compressed air 30. . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.2 Operation with lubricated compressed air 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5 General instructions on installation 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6 Installation of the tubing lines 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.1 Connecting 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.2 Removing 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • VTIA

    4 Festo – P.BE-VTIA-EN – 1411c – English

    3.7 Pneumatic connection of the valve manifold 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.1 Ducted exhaust of control air and venting air 33. . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.2 Pilot control (pilot air supply) 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.3 Valve manifold with pressure zone separation 35. . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.4 Reversibly operated valve manifold 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.5 Operation of the valve manifold with reversible 2x 3/2-way valves 37. . . . . . . . . .

    3.7.6 Operation of the valve manifold with reversible pressure regulator plates 37. . . .

    3.7.7 Adjusting the pressure regulator plates 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.8 Vacuum / low-pressure operation: 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7.9 Connecting the pneumatic lines 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.8 Power supply 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.8.1 Earthing the valve manifold 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.9 Address assignment of the valves 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.9.1 Recommended address allocation 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4 Commissioning 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.1 Prior to commissioning 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2 Pressure build-up in the overall supply 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3 Manual override (MO) 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4 Testing the valves and the valve/actuator combination 52. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.5 LED display of the valves 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6 Troubleshooting 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.1 Signal status display of the solenoid coils 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.2 Impairment of functions 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.3 Operating statuses of the pneumatic system 57. . . . . . . . . . . . . . . . . . . . . . . . . . .

    5 Conversion and maintenance 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.1 General preventive action 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.1.1 Repair 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2 Dismounting the valve manifold 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2.1 Disconnect the electrical connections 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2.2 Disconnecting the pneumatic connections 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2.3 Dismounting the valve manifold 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.3 Replacing valve manifold components 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.3.1 Replacing valves or cover plates 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.3.2 Replacing/adding vertical stacking components 61. . . . . . . . . . . . . . . . . . . . . . . .

    5.3.3 Replacing manifold sub-bases or end plates 64. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.4 Conversion of the valve manifold 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.4.1 Conversion to ducted pilot exhaust and venting air 66. . . . . . . . . . . . . . . . . . . . . .

    5.4.2 Conversion of the valve manifold to two or three pressure zones 67. . . . . . . . . . . .

    5.4.3 Adding valve positions 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.5 De-commissioning and disposal 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • VTIA

    Festo – P.BE-VTIA-EN – 1411c – English 5

    A Technical appendix 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1 Technical data 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1.1 General 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1.2 Operating and environmental conditions 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1.3 Pneumatics 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1.4 Electrical data 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.2 Accessories 82. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B Overview of valve position components 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1 Valves with internal pilot air supply 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.2 Valves with external pilot air supply 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.3 Vertical stacking components 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    C Glossary 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • VTIA

    6 Festo – P.BE-VTIA-EN – 1411c – English

    Notes on this documentation

    This documentation is intended to help you safely work with the valve manifold. It includes specific

    information on mounting, installing, commissioning, servicing and modification of the valve manifold.

    Product identification, versions

    This documentation refers to the following versions:

    – Valve manifold VTIA with valves with common connector type VSVA-B-...-R...

    – Valve manifold VTIA with valves with square plugs (individual connection) type

    VSVA-B-...- C1

    Service

    Please consult your regional Festo contact if you have any technical problems.

  • 1 Safety and requirements for product use

    Festo – P.BE-VTIA-EN – 1411c – English 7

    1 Safety and requirements for product use

    1.1 Safety

    1.1.1 General safety information

    � Observe the general safety information in the corresponding chapters.

    Specific safety regulations can be found immediately before the task instructions.

    Note

    Damage to the product from incorrect handling.

    � Switch off the supply voltage before mounting and installation work. Switch on sup

    ply voltage only when mounting and installation work are completely finished.

    � Never unplug or plug in a product when powered!

    � Observe the handling specifications for electrostatically sensitive devices.

    1.1.2 Intended use

    The valve manifold VTIA is intended for installation in machines or automated systems and may be used

    only as follows:

    – in excellent technical condition

    – in original status, without unauthorised modifications

    – within the limits of the product defined by the technical data (� Appendix A.1)

    – in an industrial environment

    Note

    In the event of damage caused by unauthorised manipulation or other than intended

    use, the guarantee is invalidated and the manufacturer is not liable for damages.

  • 1 Safety and requirements for product use

    8 Festo – P.BE-VTIA-EN – 1411c – English

    1.2 Requirements for product use

    � Make this documentation available to the design engineer, installer and personnel responsible for

    commissioning the machine or system in which this product is used.

    � Make sure that the specifications of the documentation are always complied with.

    � Take into consideration the legal regulations applicable for the destination, as well as:

    – regulations and standards,

    – regulations of the testing organizations and insurers,

    – national specifications.

    1.2.1 Technical prerequisites

    General conditions for the correct and safe use of the product, which must be observed at all times:

    � Comply with the connection and environmental conditions of the product (� Appendix A.1) and all

    connected components specified in the technical data.

    Only compliance with the limit values or load limits permits operation of the product in accordance

    with the relevant safety regulations.

    � Observe the instructions and warnings in this documentation.

    1.2.2 Qualification of the specialized personnel (requirements for the personnel)

    The product may only be commissioned by trained control and automation technology professionals,

    who are familiar with:

    – installation and operation of control and automation systems,

    – the applicable regulations for accident prevention and industrial safety, and

    – the documentation for the product.

    1.2.3 Range of application and certifications

    Standards and test values, which the product complies with and fulfils, can be found in the “Technical

    data” section (� Appendix A.1). The product-relevant EU directives can be found in the declaration of

    conformity.

    Certificates and the declaration of conformity for this product are found on the Festo Internetpage (� www.festo.com).

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 9

    2 Overview

    2.1 Product overview

    The modular structure of the valve manifold enables you to match it optimally in your machine or sys

    tem.

    The manifold sub-bases of the valve manifold provide the common ducts for the supply and exhaust air.

    Working lines 2 and 4 are provided for each valve position on the individual manifold sub-bases. The

    valves are supplied with operating pressure and the valve exhaust air is dissipated via the common

    ducts of the manifold sub-bases and the ports in the end plates.

    The pilot pressure is supplied via port 14 of the left end plate.

    The function range at each valve position can be extended by means of additional vertical stacking

    components (e.g. exhaust air flow control or pressure regulation).

    Depending on the manifold sub-bases used, the valve manifold is available with 1, 2, 3 … 16 valve posi

    tions (� Section 2.3).

    2.2 Overview of variants

    The valve manifold is available in the sizes 18 mm und 26 mm. An intermediate plate is required to com

    bine the two widths on one valve manifold.

    Electrical connection variants of the valves

    Valve manifold with valves with common

    connectors, valve type VSVA-B-...-R...

    Valve manifold with valves with square plugs

    (individual connection), valve type VSVA-B-...- C1

    Tab. 2.1 Electrical connection variants of the valves

  • 2 Overview

    10 Festo – P.BE-VTIA-EN – 1411c – English

    2.3 Description of components

    The valve manifold consists of the following pneumatic components:

    1 22

    3

    3

    1

    3 4

    5

    6

    7

    899

    1 Right/left end plate2 Blanking plate for valve position (optional)3 Valves4 Intermediate plate (optional)5 Pressure regulator plate (optional)

    6 Flow control plate (optional)7 Vertical pressure shut-off plate (optional)8 Vertical pressure supply plate (optional)9 Manifold sub-base

    Fig. 2.1 Pneumatic components of the valve manifold

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 11

    2.3.1 Valves

    The valve manifold can be equipped with 2x 3/2-way valves (standard and reversible), 5/2-way valves

    (monostable and bistable) and 5/3-way mid-position valves.

    All 5/2-way valves and 5/3-way mid-position valves can be used in all operating modes:

    – standard operation

    – reversible operation

    – low pressure operation

    – vacuum operation

    Identification of the valves

    The valves on the valve manifold are labelled with type codes. The type codes are printed on the re

    verse sides of the valves. An identifier within the type code indicates the valve function. For example,

    the identifier T32C in the type code VSVA-B-T32C-AZH-A1-1-R2 means that this valve consists of two,

    normally closed monostable 3/2-way valves. You can identify the valve function with the aid of the fol

    lowing table (� Tab. 2.2). In the sales documentation and in the Festo Configurator, the valves are

    marked with an ID code.

  • 2 Overview

    12 Festo – P.BE-VTIA-EN – 1411c – English

    Identifier in

    the type code

    ID

    code

    Valves

    3/2-way valves:

    T32C-A K Two monostable 3/2-way valves, normally closed

    T32H-A H Two monostable 3/2-way valves, control side 12 normally open, control

    side 14 normally closed

    T32U-A N Two monostable 3/2-way valves, normally open

    Reversible 3/2-way valves:

    T32F-A P Two monostable reversible 3/2-way valves, normally open

    T32N-A Q Two monostable reversible 3/2-way valves, normally closed

    T32W-A R Two monostable reversible 3/2-way valves, control side 14 normally open,

    control side 12 normally closed

    5/2-way valves:

    B52 J 5/2-way impulse directional control valve, bistable

    D52 D 5/2-way impulse directional control valve, bistable, dominant

    M52-A M Monostable 5/2-way valve, pneumatic reset

    M52-M O Monostable 5/2-way valve, mechanical reset

    M52-M SO Monostable 5/2-way valve, mechanically reset with switching position

    sensing via inductive sensor with PNP output

    M52-M SQ Monostable 5/2-way valve, mechanically reset with switching position

    sensing via inductive sensor with NPN output

    5/3-way valves:

    P53C-M G 5/3-way valve, mid-position closed

    P53E-M E 5/3-way valve, mid-position exhausted

    P53U-M B 5/3-way valve, mid-position open

    Tab. 2.2 Identification of the valve function in the type code

    5/2-way valves with switching position sensing

    The monostable 5/2-way valves with ID code SO or SQ (width 26 mm) have switching position sensing.

    An inductive sensor (N/C contact) monitors the neutral position of the piston spool. The sensor has a

    PNP or an NPN output.

    Manual override (MO)

    The manual override is mainly used when commissioning the pneumatic system in order to check the

    functionality and mode of action of the valve or the valve-actuator combination.

    The manual override enables the valve to be switched in a not electrically activated, de-energised

    status. Only the compressed air supply needs to be switched on.

    There are different MO variants, dependent on the valve type.

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 13

    MO variant Valves with common connector Valves with square plugs form C

    Only non-detenting X X

    Non-detenting/detenting – X

    Covered1) – X

    1) The MO is covered by a plastic sheet and so secured against undesired actuation.

    Tab. 2.3 Manual override variants

    Operation of the manual override � Chapter 4.3.

    Further information on the valves � Appendix B.

    2.3.2 Pilot control of the solenoid coils

    The type of pilot control (internal or external pilot air) depends on the type of valve. Valves for operation

    with external pilot air are identified with a Z in the type code, e.g. VSVA-B-T32C-AZH-A1-1-R2.

    2.3.3 Pressure zone separation

    The valve manifold can be fitted with pressure zones:

    – A maximum of 2 pressure zones can be implemented if only one size is used.

    – If sizes 18 mm and 26 mm are combined, a maximum of 3 pressure zones can be implemented.

    The pressure zones are formed via special seal plates, which are inserted in the ducts (� Fig. 2.2).

    The following ducts can be separated with the seal plates:

    – supply duct (1)

    – exhaust duct (3)

    – exhaust duct (5)

    In the valve manifold, external pilot air is fed in via the end plates. Pressure zone separa

    tion of pilot ducts 12 and 14 is not possible.

  • 2 Overview

    14 Festo – P.BE-VTIA-EN – 1411c – English

    1 1

    1

    22 23 3 34 4

    1 Duct 52 Duct 3

    3 Duct 14 Seal plate

    Fig. 2.2 Seal plates

    2.3.4 Vertical stacking

    Additional pneumatic components can be mounted in each location between the manifold sub-base

    and the valve. This vertical stacking will enable you to implement certain additional modes of action, as

    desired. The following tables show the available components.

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 15

    Valve or blanking plate

    Valve with central plug

    type VSVA-B-...-R...

    Valve with square plug

    type VSVA-B-...-C1

    Cover plate, for sealing an un

    used valve position

    type NDV-...-VDMA

    Tab. 2.4 Components for valve positions

    Vertical stacking (optional)

    Pressure regulator plate

    type VABF-S3-1R...

    (with or without pressure

    gauge)

    Flow control plate

    type VABF-S4-...F1B1-...

    This plate is used for exhaust air

    flow control in ducts 3 and 5 of a

    valve in order to adjust the

    speed of the actuator.

    Vertical pressure shut-off plate

    type VABF-S3-...L1D1...

    This plate cuts a valve off from

    the operating pressure of the

    valve manifold. This means that

    the valve can be removed

    without shutting off the pres

    sure to the valve manifold.

    Vertical pressure supply plate, type VABF-S3-...P1A3...

    This plate supplies individual operating pressure to a valve irrespective of the operating pressure of

    the valve manifold.

    Tab. 2.5 Components for vertical stacking components

  • 2 Overview

    16 Festo – P.BE-VTIA-EN – 1411c – English

    Manifold sub-base

    Manifold sub-base type NAW-...

    Tab. 2.6 Manifold sub-base

    Instructions on installing the vertical stacking components � Chapter 3.

    The vertical stacking components are labelled with type codes on the valve manifold. Identification

    within the type code indicates the function of the components, e.g. identification R1 in the type code

    VABF-S3-1-R1C2-C-10 indicates that this component is a P pressure regulator plate with a control range

    of 0 … 10 bar. You can identify the vertical stacking components with the aid of the following table. In

    the sales documentation and in the Festo Configurator, the valves are marked with an ID code.

    Identification in

    the type code

    ID

    code

    Vertical stacking component

    R1-...-6 ZF Pressure regulator plate for connection 1, control range 0 … 6 bar

    R2-...-6 ZH Pressure regulator plate for connection 2, control range 0 … 6 bar

    R3-...-6 ZG Pressure regulator plate for connection 4, control range 0 … 6 bar

    R4-...-6 ZI Pressure regulator plate for connection 2 and 4, control range 0 … 6 bar

    R6-...-6 ZM Pressure regulator plate for connection 2, control range 0 … 6 bar,

    reversible

    R7-...-6 ZN Pressure regulator plate for connection 4, control range 0 … 6 bar,

    reversible

    R5-...-6 ZJ Pressure regulator plate for connection 2 and 4, control range 0 … 6 bar,

    reversible

    R1-...-10 ZA Pressure regulator plate for connection 1, control range 0 … 10 bar

    R2-...-10 ZC Pressure regulator plate for connection 2, control range 0 … 10 bar

    R3-...-10 ZB Pressure regulator plate for connection 4, control range 0 … 10 bar

    R4-...-10 ZD Pressure regulator plate for ports 2 and 4, control range 0 … 10 bar

    R6-...-10 ZK Pressure regulator plate for connection 2, control range 0 … 10 bar,

    reversible

    R7-...-10 ZL Pressure regulator plate for connection 4, control range 0 … 10 bar,

    reversible

    R5-...-10 ZE Pressure regulator plate for connection 2 and 4, control range 0 … 10 bar,

    reversible

    F1B1 X Flow control plate for restricting the exhaust in ducts 3 and 5

    Tab. 2.7 Identification of the vertical stacking component in the type code

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 17

    Pressure regulator plates

    P pressure regulator

    ID code ZF, ZA

    Mode of operation The pneumatic pressure regulator regulates the pressure in front of

    the valve in channel 1 (P). This means that ducts 2 and 4 have the

    same regulated pressure. During venting, the exhaust flow in the

    valve is from duct 2 to duct 3 and from duct 4 to duct 5

    Advantages – The pressure regulator is not affected by exhausting, since the

    pressure is regulated upstream of the valve.

    – The pressure regulator can always be adjusted, because the

    pressure from the valve manifold is always present.

    Application examples – An equal initial pressure is required at working lines 2 and 4.

    – A lower initial pressure (e.g. 3 bar) is required than the operating

    pressure present at the valve manifold (e.g. 8 bar).

    Tab. 2.8 P pressure regulator

    AB pressure regulator

    ID code ZI, ZD

    Mode of operation The AB pressure regulator regulates the air pressure in ducts 2 (B)

    and 4 (A) after the pressure medium has passed through the valve.

    During venting, the exhaust flow is from duct 2 to duct 3 and from

    duct 4 to duct 5 via the valve and the pressure regulator.

    Restrictions – The exhaust flow is restricted by the pressure regulating valve.

    – The pressure regulator cannot be adjusted in the exhaust posi

    tion. For example, the pressure regulator for duct 4 cannot be

    adjusted when the valve is pressurised in the switching position

    from duct 1 to duct 2 and exhausted from duct 4 to duct 5.

    Application examples – Two different initial pressures are required at connections 2 and

    4 instead of the operating pressure of the valve manifold.

    – Use of the reversible pressure regulator is not possible. For ex

    ample, when 2x 3/2-way valves with ducted pilot exhaust air

    82/84 or a flow control plate is used.

    Tab. 2.9 AB pressure regulator

    The following example shows the following switching position:

    The supply air is passed from duct 1 through the pressure regulator plate and the valve to the pressure

    regulator B, where it is regulated and then passed to port 2 of the manifold sub-base. The exhaust air is

    passed via duct 4 to pressure regulator A and then via the valve to duct 5.

  • 2 Overview

    18 Festo – P.BE-VTIA-EN – 1411c – English

    Example:

    Port

    connection

    123

    1 Duct 5 (exhaust)2 Duct 1 (supply air)

    3 Duct 3 (exhaust)

    Fig. 2.3 AB-pressure regulator

    Reversible AB pressure regulator

    ID code ZJ, ZE

    Mode of operation With the reversible pressure regulator, the supply air (duct 1) is split

    and routed directly to both pressure regulators. In each case the

    regulated air is present in ducts 3 and 5 on the valve. The valve is

    thus operated reversibly (� Fig. 2.4).

    This means:

    – Duct 3 routes the initial pressure to port 2

    – Duct 5 routes the initial pressure to port 4.

    Advantages compared to the

    AB pressure regulator

    – Faster cycle times

    – 50% higher exhaust flow rate, as air is not vented via the

    pressure regulator. The load on the pressure regulator is also

    reduced.

    – No quick exhaust valves are required. The exhaust air is ducted

    completely via the valve manifold.

    – Operating pressure is always present at the pressure regulator,

    as the pressure is regulated upstream of the valve. That is, both

    pressure regulators can always be adjusted simultaneously and

    independently of the valve switching position. For the AB

    pressure regulator, the valve must switch for this

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 19

    Reversible AB pressure regulator

    Disadvantages compared to

    the AB pressure regulator

    – No use of 2x 3/2-way valves (ID code H, K and N) is possible in

    combination with ducted pilot exhaust air 82/84, since reversible

    pressure is present at the valve interface.

    – No practical combination with an intermediate throttle plate

    possible.

    Application examples – If, instead of the operating pressure of the valve manifold, two

    additional different pressures are required in ducts 2 and 4.

    – When fast venting is required.

    – When the pressure regulator for both sides must always be

    adjustable.

    Tab. 2.10 Reversible AB-pressure regulator

    The subsequent example shows the following switching position:

    The supply air in duct 1 is passed in the pressure regulator plate to pressure regulators A and B, regu

    lated there and then passed to ports 3 and 5 on the valve. In the valve, the supply air is routed to port 2

    of the manifold sub-base. The exhaust air is conducted via duct 4 into the pressure regulator plate,

    split there to ducts 3 and 5 and exhausted.

    Example:

    Port

    Port

    123

    1 Duct 5 (exhaust)2 Duct 1 (supply air)

    3 Duct 3 (exhaust)

    Fig. 2.4 Reversible AB-pressure regulator

  • 2 Overview

    20 Festo – P.BE-VTIA-EN – 1411c – English

    Notes on the installation of the pressure regulator plates � Section 3.7.7

    2.3.5 Pneumatic connection and control elements of the valve manifold

    You will find the following pneumatic connecting and control elements on the valve manifold without

    vertical stacking:

    1

    1

    12

    2

    3

    3

    4

    4

    5

    6

    7

    8

    1 Manual override (MO), per pilot control2 Exhaust port (3) “Valve”3 Supply port (1) “Operating pressure”4 Exhaust port (5) “Valves”5 Working lines (2), per valve position6 Working lines (4), per valve position

    7 Pilot air port (14), for feeding the externalpilot air

    8 Pilot exhaust air port (12) for ductedexhausting of the pilot exhaust air (not

    ISO-compliant) for valves configured

    accordingly

    Fig. 2.5 Pneumatic connection and control elements of the valve manifold

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 21

    2.3.6 Pneumatic connection and control elements of the vertical stacking components

    You will find the following connection and control elements on the vertical stacking components:

    Pressure regulator plate

    1

    1

    2

    2

    3

    3

    1 Port for pressure gauge (can beswivelled 90°)

    2 Pressure gauge (optional)

    3 Adjusting knob with free-wheeling andsnap-in locking

    Fig. 2.6 Operation and connection elements

    Flow control plate

    1

    1

    1 Adjusting screw for controlled flow

    Fig. 2.7 Operation and connection elements

  • 2 Overview

    22 Festo – P.BE-VTIA-EN – 1411c – English

    Vertical pressure shut-off plate

    1

    1 Operating pressure plug screw for one valveposition

    Fig. 2.8 Operation and connection elements

    Vertical pressure supply plate

    1

    1 Supply port 1 (individual operating pressurefor one valve position)

    Fig. 2.9 Operation and connection elements

  • 2 Overview

    Festo – P.BE-VTIA-EN – 1411c – English 23

    2.3.7 Electrical components of the valve manifold

    Valve manifold with common connector

    1

    1 Central plug

    Fig. 2.10 Electrical components of the valve manifold

    Valve manifold with square plug

    1 2

    1 Electrical connection 14 in accordance withEN 175301-803

    2 Electrical connection 12 in accordance withEN 175301-803

    Fig. 2.11 Electrical components of the valve manifold

  • 2 Overview

    24 Festo – P.BE-VTIA-EN – 1411c – English

    Connection and display components

    1

    2

    3

    4

    1 Signal status display (yellow LED) for pilotcontrol in the plug socket with cable type

    KMEB-1-24-...-LED or KMEB-3-...-LED

    2 Square plug in accordance withEN 175301-803 on valves of type

    VSVA-B-...-C1

    3 M8/M12 common connector4 Signal status displays (yellow LEDs) of the

    pilot control

    Fig. 2.12 Electrical connection and display components of the valve manifold

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 25

    3 Mounting and installation

    3.1 Notes on mounting and dismounting

    Warning

    Risk of injury to people, damage to the machine and system resulting from uncontrolled

    movements of the actuators

    � Switch off the operating voltage and the load voltage supplies.

    � Switch off the compressed air supply.

    � Vent the pneumatics.

    Note

    Malfunction or damage to the electronics

    Electrostatically sensitive devices

    � Do not touch contact surfaces.

    3.2 Mounting variants

    H-rail mounting Wall mounting

    The valve manifold is suitable for mounting on an

    H-rail (mounting rail in accordance with EN

    60715). Follow the safety instructions in the

    following chapter. A guide groove on the reverse

    side of the valve manifold is used to hold the

    H-rail.

    The end plates and the manifold sub-bases have

    holes for wall mounting. For wall-mounting, Festo

    recommends using the holes in every fourth

    manifold sub-base in addition to the holes in the

    end plates (� Specifications on vibrations and

    shock in appendix A, Tab. A.4).

    Tab. 3.1 Mounting variants of the manifold assembly

    Note

    Damage to the valve manifold due to ambient temperature that is too high

    � Mount the valve manifold so that there is sufficient space for heat dissipation and

    ensure that the maximum limits for temperatures are observed (� Appendix A,

    section A.1.2).

  • 3 Mounting and installation

    26 Festo – P.BE-VTIA-EN – 1411c – English

    3.2.1 Mounting/dismounting on an H-rail

    Caution

    Risk of injury and material damage due to incorrect mounting

    � Make sure that the H-rail can support the weight of the valve manifold and can ab

    sorb torsion (e.g. through the vertical stacking).

    � When mounting the valve terminal onto an H-rail, note the specifications in standard

    EN 60715 and the specifications on vibration and shock in the technical data (� A).

    � Perform H-rail mounting only horizontally.

    � Mount the H-rail clamping unit.

    – Secure the clamping component of the H-rail clamping with the retaining screw

    of the H-rail clamping (� Fig. 3.2, number 3).

    H-rail mounting without an H-rail clamping unit is not permitted.

    For H-rail mounting of the valve manifold, you need the mounting kit VTIA-…-A1 (part

    number 533995) for the width 26 mm, and VTIA-…A2 (part number 533996) for the width

    18 mm. These mounting kits each consist of 2 M4 screws and 2 clamping components.

    11

    1 Drill hole for H-rail clamping unit

    Fig. 3.1 Position of the drill holes for H-rail clamping unit

    Mounting

    1. Make sure that the mounting surface can support the weight of the valve manifold (for weights

    � Appendix A, Tab. A.1).

    2. Mount H-rail (DIN mounting rail EN 60715 - 35x7.5; width 35 mm, height 7.5 mm). Be sure to leave

    sufficient space for connecting the supply cables and tubes.

    3. Fasten the H-rail to the mounting surface at intervals of approx. every 100 mm.

    4. Mount the H-rail clamping units (� Fig. 3.1).

    5. Attach the valve manifold to the H-rail (� Fig. 3.2, arrow (A)).

    6. Swivel the valve manifold onto the H-rail (� Fig. 3.2, arrow (B)). Make sure that the clamping com

    ponent is horizontal to the H-rail.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 27

    (A)

    (B)

    1

    2

    3

    1 H-rail2 Clamping component of the H-rail clamping

    unit

    3 Retaining screw of the H-rail clamping unit

    Fig. 3.2 H-rail mounting of the valve manifold

    7. Secure the valve manifold against tilting or sliding by tightening the retaining screw to 1.3 Nm.

    1

    2 2

    1 H-rail 2 Clamping component of the H-rail clampingunit

    Fig. 3.3 Rear view: H-rail mounting

    Dismounting

    1. Loosen the retaining screw from the H-rail clamping unit (position of the screws � Fig. 3.1). Make

    sure that the clamping component is horizontal to the H-rail.

    2. Swivel the valve manifold forwards from the H-rail (� Fig. 3.4, arrow (B)).

    3. Lift manifold assembly from the H-rail (� Fig. 3.4, arrow (A)).

  • 3 Mounting and installation

    28 Festo – P.BE-VTIA-EN – 1411c – English

    (A)

    (B)

    1

    23

    1 H-rail2 Clamping component of the H-rail clamping

    unit

    3 Retaining screw of the H-rail clamping unit

    Fig. 3.4 Dismounting the valve manifold from the H-rail

    3.2.2 Wall mounting and dismounting

    The end plates and the manifold sub-bases have holes for wall mounting.

    Caution

    Risk of injury and material damage due to incorrect mounting

    � Mount the valve manifold only on a flat rigid surface.

    � In addition to the holes in the end plates, use the holes in every fourth manifold

    sub-base.

    � Observe the specifications on vibration and shock in appendix A.

    � Make sure that the mounting surface can support the weight of the valve manifold

    (weights � Appendix A, Tab. A.1).

    Mounting

    Be sure to leave sufficient space for connecting the supply cables and tubes.

    1. Drill mounting holes in the mounting surface.

    2. Secure the valve manifold to the mounting surface with screws of sufficient length (� Fig. 3.5).

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 29

    1 1

    2 2

    1 In the end plates: four drill holes for M4screws

    2 For each manifold sub-base: one drill hole forM3 screw for width 18 mm or one drill hole

    for M4 screw for width 26 mm

    Fig. 3.5 Options for mounting the valve manifold on a wall

    Dismounting

    1. Secure a suspended mounted valve manifold to prevent it falling down.

    2. Loosen mounting screws (� Fig. 3.5).

    3. Remove the valve manifold from the mounting surface.

    3.3 Mounting the inscription labels (optional)

    Inscription labels can be mounted as shown in the table below to identify the solenoid coils.

    � Clip the inscription labels to the recesses of the valve or connecting cable (� Fig. 3.6).

    1 2

    1 Valve with common connector, typeVSVA-B-...-R...

    2 Connecting cable KMEB-1-... and KMEB-3-...to the valve with square plug, type

    VSVA-B-...-C1

    Fig. 3.6 Mounting the inscription labels

  • 3 Mounting and installation

    30 Festo – P.BE-VTIA-EN – 1411c – English

    3.4 Compressed air preparation

    Note

    Unfiltered or incorrectly lubricated compressed air will reduce the service life of the

    valve manifold.

    3.4.1 Operation with unlubricated compressed air

    Note

    Too much residual oil content in the compressed air will reduce the service life of the

    valve manifold and result in malfunctions of the valves.

    – When using bio-oils (oils that are based on synthetic ester or native ester, e.g. rape

    seed oil methyl ester), the maximum residual oil content of 0.1 mg/m³ must not be

    exceeded (� ISO 3-8573-1 class 2)

    – When using mineral oils (e.g. HLP oils in accordance with DIN 51524 Part 1 to 3) or

    corresponding oils based on polyalphaolefin (PAO), the maximum residual oil con

    tent of 5 mg/m3 should not be exceeded (� ISO 8573-1-2010 class 4).

    Excessive residual oil content is not permissible, independent of the compressor oil, as otherwise the

    basic lubrication will be washed out with time.

    3.4.2 Operation with lubricated compressed air

    Operate the system with unlubricated air, if possible, in order to protect the environment.

    Festo pneumatic valves and actuators have been designed so that, if used as intended,

    they will not require additional lubrication and will still achieve a long service life.

    Note

    Operation with lubricated compressed air will cause the life-time lubrication, which is

    necessary for unlubricated operation, to be “washed out”.

    Observe the following notes if lubricated compressed air must be used.

    The quality of compressed air downstream of the compressor must correspond to that of

    unlubricated compressed air.

    � If possible, do not operate the entire system with lubricated compressed air.

    � If possible, always install the lubricators directly upstream of the consuming actuator.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 31

    Note

    Incorrect supplemental oil and too much oil content in the compressed air will reduce

    the service life of the valve manifold and result in malfunctions of the valves.

    � Use Festo special oil OFSW-32 or the other oils listed in the Festo catalogue (con

    forming to DIN 51524-HLP32, basic viscosity 32 CST at 40 °C).

    � Check the correct lubricator setting (� Section)

    The additional lubrication must not exceed 25 mg/m3 (ISO 8573-1 class 5).

    Adjusting the lubricator

    With the machine running (typical operating status) 0.2 to max. 1 drop/min. or 0.5 to 5 drops/1000 l of

    air.

    The procedure described subsequently can be used to check the lubricator setting.

    � Check the service units for condensate and lubricator setting twice a week.

    1. Determine the actuator which is furthest from the lubricator.

    2. Determine the valve manifold which controls this actuator.

    3. Remove the silencer, if present, from port 3/5.

    4. Hold a piece of white cardboard at a distance of 10 cm from the exhaust port.

    5. Let the system run for some time.

    � There must be only a slight yellow colouring on the cardboard. If oil droplets appear, this is an

    indication that too much oil has been used.

    Another indicator of over-lubrication is the coloration or status of the exhaust air silencer. A distinctly

    yellow colouring of the filter element or drops of oil on the silencer indicate that the lubricator setting is

    too high.

    3.5 General instructions on installation

    Warning

    Risk of injury to people, damage to the machine and system resulting from uncontrolled

    movements of the actuators

    � Switch off the operating voltage and the load voltage supplies.

    � Switch off the compressed air supply.

    � Exhaust the valve manifold pneumatics.

    Note

    Malfunction or damage to the electronics

    Components of the valve manifolds contain electrostatically sensitive components.

    � Do not touch any contact surfaces.

    � Observe the handling specifications for electrostatically sensitive devices.

  • 3 Mounting and installation

    32 Festo – P.BE-VTIA-EN – 1411c – English

    3.6 Installation of the tubing lines

    If angled connectors or multiple distributors are used, the air flow will usually be reduced.

    3.6.1 Connecting

    1. Push the tubing as far as possible into or over the tube connection of the fitting.

    2. Tighten the clamping screw 1 or, if applicable, pull the locking ring 2 over the tubing connection.

    3. Seal unused connections with blanking plugs 3.

    4. For a better overview of the system, bundle the installed tubes with a tubing strap or multiple hose

    holder.

    1

    2

    3

    1 Clamping screw2 Locking ring

    3 Blanking plug

    Fig. 3.7 Mounting the tubing connections

    3.6.2 Removing

    Warning

    If the pneumatic tubing is under pressure when dismounted, it may perform sudden

    unexpected movements, causing injury to persons.

    Before disconnecting the pneumatic tubing on the valve manifold:

    � Switch off the compressed air supply.

    � Make sure that all pneumatic tubing is unpressurized.

    � Exhaust all actuators controlled by valves that are blocked in the neutral or middle

    positions.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 33

    1. Mark all pneumatic tubing.

    2. Loosen the clamping screw 1 of the fitting or, if necessary, press down the locking ring of the fit

    ting 2 (e.g. with the loosening tool QSO from Festo).

    3. Remove the tubing from the fitting.

    1

    2

    1 Clamping screw 2 Locking ring

    Fig. 3.8 Removing the tubing connection

    3.7 Pneumatic connection of the valve manifold

    Seal working lines (2 or 4) on non-assigned valve positions (valve positions equipped with

    blanking plates) with blanking plugs or threaded blanking plugs to protect them from dirt.

    In order to guarantee the optimum capacity of the valve manifold, we recommend that more than one

    supply or exhaust line be used in the following cases:

    – When large volume cylinders are operated at high speeds,

    – When several valves (e.g. 10 valves) are switched simultaneously to the flow position.

    Valve manifolds equipped with size 18 mm and 26 mm valves can also be supplied via the intermediate

    plate.

    3.7.1 Ducted exhaust of control air and venting air

    In accordance with the standard ISO 15407-1, ports 12 and 14 are intended for supplying the valve

    manifold with external pilot air. Festo valves for the valve manifold require pilot air supply via duct 14

    only.

    In the case of the Festo reversible 2x 3/2-way valves, additional operating pressure is also required at

    duct 12 for the internal pneumatic spring. This pressure must correspond to the pilot pressure in duct

    14.

    If the valve manifold is equipped with valves for ducted pilot and venting air via duct 12, duct 12 must

    not be pressurized. Otherwise, the valves cannot reverse.

    Therefore, please observe the following points if you wish to use duct 12 for ducted pilot and venting

    air:

    – The valve manifold is not equipped with reversible 2x 3/2-way valves.

    – The valve manifold is not equipped with valves from other manufacturers.

    – The seals between the manifold sub-bases and the valves must be mounted in the corresponding

    position (� Section 5.4.1).

  • 3 Mounting and installation

    34 Festo – P.BE-VTIA-EN – 1411c – English

    3.7.2 Pilot control (pilot air supply)

    Except for the reversible valves, there are all valve types both for internal and external pilot air. Valves

    for external pilot air are identified with the indicator Z in the type code.

    Festo recommends using valves with the same pilot control variant (either internal or

    external pilot air) on the valve manifold.

    Note

    If the valve manifold is also equipped with reversible 2x 3/2-way valves (ID code P, Q

    and R), pilot air must also be fed via port 12. The pneumatic spring of these valves is

    supplied via this port.

    Internal pilot air supply

    If the operating pressure is within the range of the required pilot pressure (see appendix A, Tab. A.8),

    you can use valves for internal pilot air. In these valves, the pilot air is branched from supply duct 1.

    External pilot air supply

    If the operating pressure is not within the required pilot pressure range for the valves (� Appendix A,

    Tab. A.8 and Fig. A.1 … Fig. A.2), you must use valves for external pilot air supply.

    Supply the external pilot air via port 14. Under certain conditions (� Section 3.7.1), you can exhaust

    the pilot and venting air via port 12.

    If you use regulated external pilot air, the valve manifold can be operated safely without

    trouble even if the operating pressure fluctuates.

    The external pilot air is supplied centrally for all solenoid coils via pilot port 14 on the left

    or right end plate. This also applies if the valve manifold is operated with different pres

    sure zones (� Fig. 3.9).

    � Set the pilot pressure according to the specifications in appendix A, Tab. A.8 or the corresponding

    diagrams Fig. A.1 … Fig. A.2.

    Note

    In a valve position with vertical pressure shut-off plate, duct 14 is blocked by the vertic

    al pressure shut-off plate (� Appendix B, Tab. B.10). The valve is supplied with internal

    pilot air.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 35

    3.7.3 Valve manifold with pressure zone separation

    Note

    Note the following in the case of valve manifolds which are operated with internal pilot

    air and have several pressure zones:

    – The pilot air for all solenoid coils is branched centrally from supply connection 1 in

    the right end plate.

    – The pressure zone which is supplied via port 1 on the right end plate must be oper

    ated at a pressure which corresponds at least to the pilot pressure required for the

    valve manifold (� Appendix A, corresponding diagrams Fig. A.1 … Fig. A.2).

    The pressure zones are formed via isolating discs mounted in ducts 1, 3 and 5. Valve man

    ifolds which are equipped solely with valves of the same size can have a maximum of two

    pressure zones. Valve manifolds equipped with sizes 18 mm and 26 mm can have a max

    imum of three pressure zones.

    The following figure shows the assignment of the supply and exhaust ports to the valves using a valve

    manifold with blocked ducts 1, 3 and 5 as an example.

    The individual pressure zones are supplied as follows (ports 1 or 3 and 5):

    – The left outer pressure zone via the left end plate

    – The middle pressure zone via the intermediate plate

    – The right outer pressure zone via the right end plate.

    External pilot air can be supplied for the entire valve manifold via port 14 on the left or right end plate.

  • 3 Mounting and installation

    36 Festo – P.BE-VTIA-EN – 1411c – English

    5 55 33 3114 11

    1 2 3

    456

    1 Pressure zone 12 Pressure zone 23 Pressure zone 34 Supply of pressure zone 3 via the right end

    plate

    5 Supply of pressure zone 2 (middle pressurezone) via the intermediate plate

    (requirement: the valve manifold is equipped

    with both sizes)

    6 Supply of pressure zone 1 via the left endplate

    Fig. 3.9 Valve manifold with 3 pressure zones and pilot control with external pilot air

    3.7.4 Reversibly operated valve manifold

    With reversible operation of the valve manifold, the operating pressure is supplied via ports 3 and 5

    and the exhaust is vented via port 1.

    Note

    Operate a reversible valve manifold only with an external pilot air supply.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 37

    3.7.5 Operation of the valve manifold with reversible 2x 3/2-way valves

    Note

    If reversible 2x 3/2-way valves (ID code P, Q and R) are operated together with standard

    2x 3/2-way valves (ID code H, K and N) on the valve manifold, the reversible valves must

    be operated in a separate pressure zone.

    Exception:

    If the reversible 2x 3/2-way valves are operated with reversible pressure regulator

    plates (ID code ZJ and ZE) (circuit diagrams � Section B, Tab. B.4 and Tab. B.8), a separ

    ate pressure zone is not required.

    The valve manifold can be operated with reversible 2x 3/2-way valves (ID code P, Q and R) under the

    following conditions:

    – The pilot exhaust air and venting air must not be exhausted in a common duct.

    The reversible 2x 3/2-way valves require compressed air at duct 12 for the pneumatic spring. Duct 12 is

    therefore no longer available for removing the ducted pilot air and venting air. Valves which are con

    figured for exhausting via duct 12 can then no longer switch (� Section 5.4.1).

    3.7.6 Operation of the valve manifold with reversible pressure regulator plates

    Note

    Operation of the valve manifold with reversible pressure regulator plates (ID code ZM,

    ZN, ZJ, ZK, ZL and ZE):

    – Reversible pressure regulator plates must not be used on reversibly operated valve

    manifolds.

    – Standard 2x 3/2-way valves with ID code H, K and N (non-reversible valves) may not

    be operated with reversible pressure regulator plates.

    – If 2x 3/2-way valves (ID code P, Q and R) are combined with reversible pressure

    regulator plates, no separate pressure zone is required. In this combination, pres

    sure is supplied via duct 1 and the exhaust is vented via ducts 3 and 5. The pilot

    pressure must be supplied via the ducts 12 and 14.

    3.7.7 Adjusting the pressure regulator plates

    You can adjust the pressure regulator plates in two ways:

    – using the adjusting knob

    – using the socket head screw in the adjusting knob.

  • 3 Mounting and installation

    38 Festo – P.BE-VTIA-EN – 1411c – English

    Adjusting the pressure regulator plate with the adjusting knob

    1. Pull the adjusting knob 1 out of the locking level 4 into the setting level 2 up to the stop

    (� Fig. 3.10).

    2. In the setting level, turn the adjusting knob to set the desired controlled variable (� “Flow dia

    grams of the pressure regulator plates” in appendix A).

    3. Press the adjusting knob into the free-running level 3. In this position you can turn the adjusting

    knob without modifying the controlled variable.

    4. Turn the adjusting knob in the free-running level longitudinally to the pressure regulator plate.

    5. Press the adjusting knob in this position into the snap-in locking of the locking level 4.

    2

    1

    34

    4

    1. 2. 3. 4.

    1 Adjusting knob2 Adjusting knob in the setting level

    3 Adjusting knob in the free-running level4 Adjusting knob in the locking level

    Fig. 3.10 Setting the pressure regulator plates with the aid of the adjusting knob

    If the space around the adjusting knob is not sufficient for setting the pressure regulator

    plate, use the adjusting screw (socket head screw) in the adjusting knob.

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 39

    Adjusting the pressure regulator plate with the adjusting screw

    � Set the desired controlled variable by turning the adjusting screw (� “Flow diagrams of the pres

    sure regulator plates” in appendix A).

    1

    1 Adjusting screw, internal hexagon socket(spanner size 2.0)

    Fig. 3.11 Setting the pressure regulator plates with the adjusting screw

    3.7.8 Vacuum / low-pressure operation:

    Note

    Standard 2x 3/2-way valves (ID code H, K and N) are not suitable for use with vacuums

    or low pressure in case of supply via port 1.

    � Operate these valves in a separate pressure zone.

    � The operating pressure for this pressure zone in accordance with Fig. A.1 in ap

    pendix A.

    The following conditions must be fulfilled so that you can operate the valve manifold at supply port 1

    with vacuum or low pressure between –0.9 … 2 bar.

    – Only the following valves are used for controlled external pilot air supply:

    – Monostable 5/2-way valves (identifier M52-AZ / M52-MZ)

    – 5/2-way bistable valves (identifier B52-Z / D52-Z)

    – 5/3-way mid-position valves (identifier P53C-Z / P53E-Z / P53U-Z)

    – Reversible 2x 3/2-way valves (identifier T32F-AZ / T32N-AZ / T32W-AZ). These valves must be

    operated via ports 3 and 5 in a separate pressure zone with vacuum or low pressure.

    3.7.9 Connecting the pneumatic lines

    Note

    � Use blanking plugs to seal all ports not required for the functioning of the valve man

    ifold.

  • 3 Mounting and installation

    40 Festo – P.BE-VTIA-EN – 1411c – English

    1. Mount the fitting or the silencers in accordance with the following table (� Tab. 3.2). The position

    of the pneumatic ports is shown in Fig. 3.12.

    2. Then lay the tubing lines.

    Line Connection

    code

    (ISO 5599)

    Connection size

    (ISO 228)

    Connection1)

    Compressed air or vacuum 1 Size 26 mm: G½”

    Size 18 mm: GÅ”

    Fitting in the end

    plates

    G½” Fitting in the in

    termediate plate

    Size 26 mm: G¼”

    Size 18 mm: GÁ”

    Fitting in the

    vertical pressure

    supply plate

    Ducted exhaust air from the valves 3 or 5 Size 26 mm: G½”

    Size 18 mm: GÅ”

    Fitting in the end

    plates.

    G½” Fitting in the in

    termediate plate

    Pilot air supply (external pilot air)2) 14 GÁ” Fitting in the end

    platesComplies with ISO standard:

    – Pilot air supply (external pilot air)

    – Supply air for the pneumatic springs of

    the reversible 2x 3/2-way valves

    Does not comply with ISO standard:3)

    – Ducted pilot exhaust of the pilot con

    trol4)

    12

    Air or vacuum 2 or 4 Size 26 mm: G¼”

    Size 18 mm: GÁ”

    Fitting in the man

    ifold sub-bases

    1) Depending on what you have ordered, the valve manifold will already be equipped with fittings.

    2) The external pilot air is supplied as standard via port 14.

    3) Requirement: The valve manifold must be equipped with Festo valves (except reversible 2x 3/2-way valves).

    4) Note the following if you wish to exhaust the pilot air ducted.

    Tab. 3.2 Pneumatic ports of the valve manifold

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 41

    Note

    If the valve manifold is to be operated in conformity with the ISO standard, the pilot

    exhaust air will be vented non-ducted directly at the valve.

    If the pilot air is to be vented ducted via port 12, the valve manifold can, under certain

    circumstances, no longer be operated with ISO valves from other manufacturers. Ob

    serve the instructions from the valve manufacturer in this case.

    Conversion of the valve manifold to ducted pilot exhaust air is described in sec

    tion 5.4.1.

    12

    35

    14

    1

    41 13

    5

    4 22

    Note: Position of the pneumatic ports on the right end plate equivalent to the left end plate

    Fig. 3.12 Position of the pneumatic ports

  • 3 Mounting and installation

    42 Festo – P.BE-VTIA-EN – 1411c – English

    Note

    If there are several systems with centrally ducted exhaust air:

    � Use non-return valves in the exhaust tubing or pilot air tubing in order to prevent

    functional impairment due to back pressures.

    1 2 3 4

    5

    5

    6

    6

    7

    7

    1 Valve manifold 12 Central pilot air exhaust tubing 82/843 Central exhaust line 3/54 Valve manifold 2

    5 Exhaust line 56 Pilot exhaust line 12 (82/84)7 Exhaust line 3

    Fig. 3.13 Centrally ducted exhaust air with non-return valves

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 43

    3.8 Power supply

    Warning

    Valve manifolds with 12 V DC or 24 V DC control voltage:

    Danger of electric shock from voltage sources without protective measures.

    � For the electrical power supply, use only PELV circuits in accordance with

    IEC/EN 60204-1 (Protective Extra-Low Voltage, PELV).

    � Observe the general requirements of IEC/EN 60204-1 for PELV circuits.

    � Use only voltage sources that ensure a reliable electric separation of operating

    voltage in accordance with IEC/EN 60204-1.

    Valve manifolds with 24 V AC, 110 V AC and 230 V AC:

    Danger of electric shock

    � Observe the applicable safety regulations for working with 110 V AC or 230 V AC

    control voltage.

    � Make sure that the earth connection of the valve manifold is connected to the pro

    tective earth.

    Through the use of PELV circuits, protection against electric shock (protection against direct and indir

    ect contact) is ensured in accordance with EN 60204-1.

    Note

    � Check which measures are required in your EMERGENCY OFF procedures for putting

    your machine/system into a safe state in the event of an EMERGENCY OFF (e.g.

    switching off the operating voltage for the valves and output modules, switching off

    pressure).

  • 3 Mounting and installation

    44 Festo – P.BE-VTIA-EN – 1411c – English

    The valve manifold can be equipped with the following electrical connection and voltage variants

    (� Tab. 3.3).

    Valve Type of electrical connection Voltage variants

    Type:VSVA-B-...-R...

    The solenoid coils of the valve

    are supplied via a port.

    – Common connector on the

    valve, 4-pin, M8 or

    – Common connector on the

    valve, 3-pin, M12

    – 24 V DC

    Type VSVA-B-...-C1

    Each solenoid coil is connected

    separately.

    – 3-pin square plug on the

    solenoid coil

    – 24 V DC

    Special voltages:

    – 12 V DC

    – 24 V AC

    – 110 V AC

    – 230 V AC

    5)

    Tab. 3.3

    Note

    Ensuring degree of protection IP65

    � Use the connecting cables from the Festo accessories to connect the manifold as

    sembly.

    Use a uniform method of control. Preferably all control signals should be positive-switching (1-switch

    ing), otherwise all control signals negative-switching (0-switching).

    Square plug, 2-pin1)

    1

    2

    PIN Description2) Wire colour3)

    1 Power supply BK

    2 Power supply BK

    1) Solenoid coils for 12 V DC, 24 V DC and 24 V AC voltage

    2) Pin allocation in accordance with EN 175301-803

    3) When using the socket with cable from the Festo accessories

    Tab. 3.4 Pin allocations for electric square plugs

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 45

    Square plug, 3-pin1)

    1

    32

    PIN Description 2) Wire colour3)

    1 Power supply BK

    2 Protective earth YE/GN

    3 Power supply BK

    1) Solenoid coils for 110 V AC and 230 V AC voltage

    2) Pin allocation in accordance with EN 175301-803

    3) When using the socket with cable from the Festo accessories

    Tab. 3.5 Pin allocations for electric square plugs

    M8 common connector, 4-pin

    3

    2

    4

    PIN Description Wire colour1) Comments

    – – BN Unused

    2 Signal solenoid coil 12 WH PIN 2 is not used for valves

    with only one solenoid coil

    3 com BU 0 V or 24 V2)

    4 Signal solenoid coil 14 BK –

    1) When using the socket with cable from the Festo accessories

    2) Connect 0 V with positive-switching control signals, 24 V with negative-switching control signals.

    Tab. 3.6 Pin allocations for electrical M8 common connector

  • 3 Mounting and installation

    46 Festo – P.BE-VTIA-EN – 1411c – English

    M12 common connector, 3-pin

    3

    42

    PIN Description Wire colour1) Comments

    – – BN Unused

    2 Signal solenoid coil 12 WH PIN 2 is not used for valves

    with only one solenoid coil

    3 com BU 0 V or 24 V2)

    4 Signal solenoid coil 14 BK –

    – – GY3) –

    1) When using the socket with cable from the Festo accessories

    2) Connect 0 V with positive-switching control signals, 24 V with negative-switching control signals.

    3) Only for a socket with cable of type SIM-M12-5...

    Tab. 3.7 Pin allocations for electrical M12 common connector

  • 3 Mounting and installation

    Festo – P.BE-VTIA-EN – 1411c – English 47

    3.8.1 Earthing the valve manifold

    Warning

    Danger of electric shock when using solenoid coils for 110 and 230 V DC

    � Connect the earth terminal of the valve manifold to the protective earth.

    Note

    Electromagnetic interference

    � Connect the valve manifold to the earth potential with low-impedance (short line

    with a large cross-section), e.g. via a mounting hole in an end plate.

    This prevents malfunctions from electromagnetic interference and ensures electromag

    netic compatibility in accordance with EMC directives.

    1

    1

    1 Earthing the valve manifold via a mountinghole in the end plate

    Fig. 3.14 Earthing the valve manifold

  • 3 Mounting and installation

    48 Festo – P.BE-VTIA-EN – 1411c – English

    3.9 Address assignment of the valves

    3.9.1 Recommended address allocation

    – Assign addresses on the valve manifold ascending from left to right

    – For valves with 2 solenoid coils:

    – Assign the less significant address to solenoid coil 14

    – Assign the higher-value address to solenoid coil 12.

    0

    1

    2

    3

    4 5

    6

    7 9

    8 10 11

    11

    22

    1 Addresses of the solenoid coils 12 2 Addresses of the solenoid coils 14

    Fig. 3.15 Address allocation for valve manifold (example)

  • 4 Commissioning

    Festo – P.BE-VTIA-EN – 1411c – English 49

    4 Commissioning

    4.1 Prior to commissioning

    � Switch off voltage before plugging together or disconnecting plug connectors (damage to function

    ing).

    � Only commission a valve manifold that has been mounted and wired completely.

    � Make sure that there is a sufficient supply of fresh air (cooling) for the following operating condi

    tions:

    – Maximum number of valves

    – Maximum operating voltage

    – When the solenoid coils are constantly under stress.

    � Observe the following notes on building up pressure in the overall supply.

    4.2 Pressure build-up in the overall supply

    Warning

    Risk of injury to people, damage to the machine and system resulting from sudden

    movements of the actuators

    If the build-up of pilot air is too slow or delayed, this may lead to sudden unexpected

    movements of the actuators under the following conditions:

    – When the compressed air is connected via a safety start-up valve (gradual pressure

    build-up) and

    – If there are electric signals (e.g. after EMERGENCY OFF switching).

    � Operate the valve manifold with external pilot air with the pressure listed in ap

    pendix A, Fig. A.1 … Fig. A.2.

    � Branch off the pilot air in front of the safety start-up valve (� Fig. 4.1).

  • 4 Commissioning

    50 Festo – P.BE-VTIA-EN – 1411c – English

    The pilot air must be applied immediately after it is switched on at the minimum pressure specified in

    appendix A, Fig. A.1 … Fig. A.2 for the corresponding valves. Otherwise there is no guarantee that the

    valve will reverse directly (� Fig. 4.1).

    If the pressure is less than the minimum specified, there may be a delay before the valve is switched, in

    spite of an electric signal being present. The gradual pressure build-up of the overall supply does not

    affect the actuator in that case. The actuator would react suddenly (e.g. a cylinder would extend or

    retract suddenly, depending on the valve function).

    1

    4 2

    5 3

    14 12

    1

    12/14

    12/14

    3

    82/84

    2

    1

    2

    1 Externally supplied pilot air, branchedupstream of the safety start-up valve

    2 Safety start-up valve (gradual pressurebuild-up of the complete supply)

    Fig. 4.1 Example: valve-cylinder combination with gradual pressure build-up of the overall supply

    The table below shows the effects of gradual start-up pressurisation when electric signals are present:

    External pilot air Pressure rise in

    the overall

    supply

    Pressure rise in

    the pilot air

    supply (12/14)

    Time when a

    valve reverses

    Movement of the

    actuator

    Branched downstream

    of the safety start-up

    valve

    Slow Slow After pressure

    rise at (1)

    Fast

    Branched upstream of

    the safety start-up

    valve

    Slow Fast Before pressure

    rise at (1)

    Slow

    Tab. 4.1 Effects of slow start-up pressurisation

  • 4 Commissioning

    Festo – P.BE-VTIA-EN – 1411c – English 51

    4.3 Manual override (MO)

    The manual override enables the valve to be switched in a not electrically activated, de-energised

    status. Only the compressed air supply needs to be switched on. You should use the manual override

    mainly when commissioning the pneumatic system in order to check the function and operation of the

    valve or the valve-actuator combination. The valve is activated by pressing the manual override.

    Depending on the manual override variant, there are the following actuation types:

    Actuation type Mode of operation

    Non-detenting After actuation, the manual override is reset

    automatically by spring force.

    Turning with detent The manual override remains actuated until it is

    reset by hand.

    Tab. 4.2 Actuation types of the manual override

    The assignment of the manual overrides to the solenoid coils is as follows.

    1

    2

    1 Manual override for solenoid coils 12 2 Manual override for solenoid coils 14

    Fig. 4.2 Position of the manual overrides on the valve manifold (top view)

  • 4 Commissioning

    52 Festo – P.BE-VTIA-EN – 1411c – English

    4.4 Testing the valves and the valve/actuator combination

    The valve manifold can be commissioned as follows:

    Commissioning variants Activity

    Preliminary test of the pneumatic tubing

    connection

    Test the valve-actuator combination by means of

    the manual override

    Complete commissioning of the overall system Installing and connecting the overall system.

    Program control via PLC/industrial PC.

    Tab. 4.3 Commissioning variants

    Commissioning the pneumatic components by means of the manual override is described below.

    Before actuating the MO:

    Warning

    Risk of injury to people, damage to the machine and system resulting from uncontrolled

    movements of the actuators

    � Disconnect the operating voltage supply to prevent accidental actuation of the

    solenoid coils.

    Note

    A valve that has been switched by an electric signal cannot be reset by the manual over

    ride. The electric signal is dominant in this case.

    � Before actuating the manual override, reset the electric signal.

    Before testing the valve-actuator combination:

    Warning

    Risk of injury due to uncontrolled movements of the actuators

    � Make sure that nobody is in the danger zone.

    Testing the valve-actuator combination:

    1. Switch on the compressed air supply

    Note

    Incorrect actuation of the non-detenting manual override can lead to malfunctioning or

    damage to the manual override

    � Use a screwdriver (blade width max. 4 mm) to actuate the manual override.

    � Actuate the manual override with a maximum of 25 N.

    2. Test the functioning and effect of each valve-actuator combination by actuating the corresponding

    manual override (� Tab. 4.4 and Tab. 4.5 ).

    3. Switch off the compressed air supply after testing the valves.

  • 4 Commissioning

    Festo – P.BE-VTIA-EN – 1411c – English 53

    Non-detenting operation of manual override (automatic reset)

    Valve with common

    connector

    Type VSVA-B-...-R...

    Valve with square plug

    Type VSVA-B-...-C1

    Operation Valve response

    � Use a screwdriver

    (max. blade width

    4 mm) to press

    down the plunger of

    the manual override

    until the valve

    switches.

    � The valve re

    verts to the

    switching posi

    tion.

    � Keep the plunger of

    the MO pressed.

    � The valve re

    mains in switch

    ing position.

    � Release the plunger

    (the spring resets

    the plunger of the

    manual override to

    the initial position).

    � The valve returns

    to the normal po

    sition (not with

    bistable valve,

    identifier in the

    type code B52 /

    D52).

    Tab. 4.4 Non-detenting operation of the manual override

  • 4 Commissioning

    54 Festo – P.BE-VTIA-EN – 1411c – English

    Detenting actuation of the manual override (manual reset)

    Valve with square plug

    Type VSVA-B-...-C1

    Operation Valve response

    1. Use a screwdriver (max.

    blade width 4 mm) to press

    down the plunger of the

    manual override until the

    valve switches.

    2. Then turn the plunger of the

    MO in a clockwise direction

    up to the stop.

    � The valve reverts to the

    switching position.

    � Leave the plunger of the MO

    in position.

    � The valve remains in

    switching position.

    1. Then turn the plunger of the

    MO in an anti-clockwise dir

    ection up to the stop.

    2. Release the plunger of the MO.

    � The valve returns to the

    normal position (not with

    bistable valve, identifier in

    the type code B52 / D52).

    Tab. 4.5 Locking actuation of the manual override

    Before switching on the operating voltage:

    Warning

    Risk of injury to people, damage to the machine and system resulting from uncontrolled

    movements of the actuators

    � Before commissioning, make sure that none of the manual overrides are actuated or

    engaged.

  • 4 Commissioning

    Festo – P.BE-VTIA-EN – 1411c – English 55

    4.5 LED display of the valves

    There is a manual override (MO) for every solenoid valve and an LED, depending on the valve type. The

    positions of the LED and MO for the corresponding solenoid valve are as follows:

    1

    2

    3

    4

    2

    1

    1 LED and manual override for valve solenoidcoil 14

    2 LED and manual override for solenoid coil 12

    3 Valve with square plug type VSVA-B...-C1 andplug socket with cable type KMEB-...LED

    4 Valve with common connector typeVSVA-B...-R...

    Fig. 4.3 The assignment of LEDs and manual overrides to the solenoid coils of the valve manifold

    The LEDs indicate the signal status of the solenoid coils.

  • 4 Commissioning

    56 Festo – P.BE-VTIA-EN – 1411c – English

    4.6 Troubleshooting

    4.6.1 Signal status display of the solenoid coils

    LED Switching position of the valve Significance

    Dark Normal position Logic 0 (signal not present)

    Lights up

    yellow

    Switching position (normal case) Logic 1 (signal is present)

    Normal position (error) Logic 1 (signal is present, valve has not

    switched):

    – Operating voltage of the valves lies be

    low the permitted tolerance range

    – Compressed air supply not OK

    – Pilot exhaust air blocked

    – Servicing required

    Tab. 4.6 Meaning of the LED display

    4.6.2 Impairment of functions

    After switching on the compressed air supply or when subsequently testing the individual valves, you

    can learn the following about the operating status of the pneumatic system:

    Operating status of the

    pneumatic system

    Error handling when the compressed air supply has been

    switched off

    Air flows out at common-line or

    working-line connections.

    � Check tube assembly

    Valve or pneumatic system

    does not react as expected.

    � Check the installation of the tubing lines

    � Check the electric cables

    Valve or pneumatic system

    does not react.

    � Bring the detenting manual override into the basic position

    � After switching on again, check the operating pressure (if

    necessary for each pressure zone). Set operating pressure in

    accordance with instructions in chapter 3.

    � Servicing required

    For valve manifolds which must be operated with closed-loop

    regulated external pilot air supply:

    � After they are switched on again, check the pilot pressure (set

    dependent on the operating pressure, if necessary, � Chapter 3)

    Tab. 4.7 Function impairments of the pneumatic system

  • 4 Commissioning

    Festo – P.BE-VTIA-EN – 1411c – English 57

    4.6.3 Operating statuses of the pneumatic system

    The following requirements should be fulfilled in order to achieve the desired pneumatic operating

    statuses listed below:

    Desired pneumatic

    operating status

    Requirement Comment

    Zero leakage – Tubing connected with care

    – Regulated pilot air supply

    Fast reaction Sufficient pressure supply by means

    of compressed air supply

    � Exhaust the valve manifold via all

    exhaust plates or flat plate

    silencers.

    Trouble-free Non-return valves in common

    exhaust line

    This applies when several systems

    with centrally ducted exhaust air are

    used

    Two or three

    pressure zones

    Restriction of the pressure zones via

    seal plate in the corresponding duct

    Subsequent conversion possible

    (� Chapter 5)

    Vacuum or

    low-pressure

    operation

    Regulated external pilot air (pressure

    range � Appendix A, Fig. A.1 …

    Fig. A.2)

    � Observe the requirements for

    operating the valve manifold with

    vacuum or low-pressure

    (� Section 3.7.8).

    EMERGENCY STOP of

    pressure zones

    Guarantees the functioning of the

    pressure regulating valve for the pilot

    air despite the overall supply being

    switched off

    The regulator regulates the pilot air

    of all the valves on a valve manifold.

    Slow switch-on after

    EMERGENCY OFF

    If control signals are present, the

    pilot air must be applied immediately

    after being switched on with at least

    the minimum pressure specified in

    appendix A, Fig. A.1 … Fig. A.2.

    Tab. 4.8 Pneumatic operating statuses

  • 5 Conversion and maintenance

    58 Festo – P.BE-VTIA-EN – 1411c – English

    5 Conversion and maintenance

    5.1 General preventive action

    5.1.1 Repair

    Warning

    Risk of injury to people, damage to the machine and system resulting from uncontrolled

    movements of the actuators

    Before carrying out installation and maintenance work:

    � Switch off the operating voltage and the load voltage supplies.

    � Switch off the compressed air supply.

    � Exhaust the valve manifold pneumatics.

    Note

    Handle all modules and components of the valve manifold with great care. Note espe

    cially the following when mounting components:

    � Screws inserted exactly (prevents damage to threads).

    � Screws must be turned by hand only and inserted so that the self-cutting threads

    can be used.

    � Comply with the specified torques.

    � Threaded fittings must be free of distortion and mechanical tension.

    � Check seals for damage (to maintain IP degree of protection).

    � The contact surfaces must be dry and clean (sealing effect, avoidance of leakage

    and contact errors).

    5.2 Dismounting the valve manifold

    Provided the valve manifold is easily accessible, it need not be dismounted when the following compon

    ents are replaced or removed:

    Components

    in valve positions: in vertical stacking:

    – Valves

    – Blanking plates

    – Pressure regulators

    – Flow control valves

    – Vertical pressure shut-off plates

    – Vertical pressure supply plates

    Tab. 5.1 Pneumatic components

  • 5 Conversion and maintenance

    Festo – P.BE-VTIA-EN – 1411c – English 59

    5.2.1 Disconnect the electrical connections

    Alternative connections Procedure

    Valve with common con

    nector type VSVA-B-...-R...

    � Loosen the union nut on the M8 or M12 common connector and

    remove common connector.

    Valve with square plug

    type VSVA-B-...-C1

    � Loosen the mounting screws of the square plug.

    � Pull out plug connector.

    Tab. 5.2 Disconnect the electrical connections

    5.2.2 Disconnecting the pneumatic connections

    Disconnecting the pneumatic ports is described in chapter 3.

    5.2.3 Dismounting the valve manifold

    Dismounting of the valve manifold is described in chapter 3.

  • 5 Conversion and maintenance

    60 Festo – P.BE-VTIA-EN – 1411c – English

    5.3 Replacing valve manifold components

    Components on the manifold sub-bases of the valve manifold can easily be replaced for maintenance

    and conversion work.

    5.3.1 Replacing valves or cover plates

    Dismounting

    � Loosen the mounting screws and remove the component from the manifold sub-base (� Fig. 5.1).

    Fig. 5.1 Removing valves or cover plates

    Mounting

    1. Check seals for damage and replace damaged seals.

    2. Make sure that the seals between the manifold sub-base and component are in the correct position.

    – For blanking plates, the seal must be in the recess of the blanking plate.

    – With valves, the seal must sit in the recess in accordance with the exhaust variant

    (� Section 5.4.1).

    3. Place component onto the manifold sub-base.

    4. Screw the component on at first only slightly and then tighten with the following tightening torque:

    – Valves of width 18 mm: 1.0 Nm ±10 %

    – Valves of width 26 mm: 2.0 Nm ±10 %

  • 5 Conversion and maintenance

    Festo – P.BE-VTIA-EN – 1411c – English 61

    5.3.2 Replacing/adding vertical stacking components

    The valve manifold can be equipped with the following vertical stacking components:

    – Pressure regulator plate

    – Flow control plate

    – Vertical pressure shut-off plate

    – Vertical pressure supply plate

    Note

    No valve function

    � Do not combine a standard 2x 3/2-way valve (identifier T32C-A / T32H-A / T32U-A)

    with reversible pressure regulator plates (identifier R5-..., R6-..., R7-...).

    If this combination is used, the pneumatic spring of the valves does not function. The

    valves cannot return from the switching position to the neutral position.

    Vertical stacking with pressure regulator plate:

    � Always mount the pressure regulator plate as the highest component of the vertical

    stacking.

    � This guarantees free access to adjusting screws or connections (� Tab. 5.3).

  • 5 Conversion and maintenance

    62 Festo – P.BE-VTIA-EN – 1411c – English

    The following component sequence is recommended for valve positions with vertical stacking:

    (� Fig. 5.2):

    1

    2

    3

    4

    5

    6

    1 Valve2 Optional pressure regulator plate3 Optional flow control plate

    4 Optional vertical pressure shut-off plate5 Optional vertical pressure supply plate6 Manifold sub-base

    Fig. 5.2 Recommended sequence of valve position components

  • 5 Conversion and maintenance

    Festo – P.BE-VTIA-EN – 1411c – English 63

    Note

    – Reversible pressure regulator plates should only be combined with valves that can

    be operated in reverse mode.

    – Valve position with vertical pressure shut-off plate:

    The pilot air supply for the valve is branched internally from duct 1 in the vertical

    pressure shut-off plate, even if the valve manifold is operated with external pilot air

    (� Appendix B, section B.1). If the valve manifold is equipped with vertical pressure

    shut-off plates at all valve positions, supplying the valve manifold with external pilot

    air is not required. In this case, the operating pressure at which the valve manifold is

    operated must be within the range of the required pilot pressure (� Appendix A,

    Fig. A.1 … Fig. A.2).

    – The combination of reversibly operated valve manifolds with the following vertical

    stacking components is not permitted:

    – Reversible pressure regulator plates

    – Flow control plates

    – Vertical pressure shut-off plates

    – Vertical pressure supply plates

    Removing the components

    1. Unscrew mounting screws of all components above the relevant position.

    2. Remove these components from the valve position.

    Mounting new components

    1. Check seals for damage. Replace damaged seals.

    2. When mounting the valve:

    Insert seal between the valve and the vertical stacking component according to the desired exhaust

    variant (� Section 5.4.1).

    3. Place the new component on the valve position, possibly onto a component already mounted.

    4. Fasten new component. Spanner size of the hexagon socket wrench � Tab. 5.3.

  • 5 Conversion and maintenance

    64 Festo – P.BE-VTIA-EN – 1411c – English

    Vertical stacking with pressure regulator plate

    1

    2

    Valve size 18 mm Valve size 26 mm

    1 H