    08 71 0008 71 0008 71 0008 71 00 Door HardwareDoor HardwareDoor HardwareDoor Hardware Master Schedule

    PROJECTPROJECTPROJECTPROJECT VA M C Oncology Relocation/Renovation

    Veterans Affairs Medical Center4100 W Third StDayton OH 45428

    ARCHITECTARCHITECTARCHITECTARCHITECT CB LH Design

    (440) 243-2000

    Fax 243-3305

    7850 Freeway Circle

    Cleveland OH 44130

    CONTRACTORCONTRACTORCONTRACTORCONTRACTOR Leeward Construction Corp

    (817) 236-0016Fax 236-8564

    5748 Boat Club RdFort Worth TX 76179

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 1/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    2/26

    Door Index and NotesDoor Index and NotesDoor Index and NotesDoor Index and Notes by schedule opening

    MarkMarkMarkMark SetsSetsSetsSets KeyingKeyingKeyingKeying NotesNotesNotesNotes

    1-1-RR-100 1.0 passage See set for all notes

    1-1-S-103 9.0 privacy

    1-1-S-112-1 7.1

    1-1-S-112-2 7.2

    1-1-S-401 9.0 privacy

    1-1-S-402-1 3.1 See set for all notes

    1-1-S-407 5.11-1-S-408 8.0

    1-1-S-409-1 3.2 See set for all notes

    1-1-S-417 10.0 privacy

    1-1-S-419 5.1

    1-1-S-420 5.1

    1-1-S-422 10.0 privacy

    1-1-S-C1-29 2.0 exit only See set for all notes

    1-1-U-404 14.0 passage

    1-1-U-405 14.0 passage

    1-1-U-406 14.0 passage

    1-1-U-410-1 14.0 passage

    1-1-U-411 14.0 passage

    1-1-U-415 16.0

    1-1-U-416 13.0

    1-1-X-409-2 17.0

    1-1-X-413 15.0

    1-1-X-414A-1 18.2 See set for all notes

    1-1-X-414A-2 18.2 See set for all notes

    1-X-410-2 18.1 See set for all notes

    1A-1-S-101 5.2

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 2/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    3/26

    Door Index and NotesDoor Index and NotesDoor Index and NotesDoor Index and Notes by schedule opening

    MarkMarkMarkMark SetsSetsSetsSets KeyingKeyingKeyingKeying NotesNotesNotesNotes

    1A-1-S-105 5.2

    1A-1-U-108 12.0

    1A-1-U-1E-145 12.0

    2-1-S-402-2 6.0

    2-1-U-403 11.0

    3-3-S-109 4.0 See set for all notes

    4-1-U-110 12.05-5-NX-106 19.0 passage See set for all notes

    5-5-S-104 20.0 passage See set for all notes

    5-5-S-107 21.0 privacy See set for all notes

    Scheduling and Procurement AdvisoryScheduling and Procurement AdvisoryScheduling and Procurement AdvisoryScheduling and Procurement Advisory IMPORTANTIMPORTANTIMPORTANTIMPORTANT

    Unless otherwise noted: each opening is configured with regard to project planningas quoted, all minimum and maximum references are identified without regard foraesthetics, and individual protection plates are intended for push side installation

    Ancillary details MUST be validated and subordinating attributes such as function,trim design, material or finish will be regarded accurate as detailed if not otherwiseformally revised prior to initializing production or procurement. Approvals forwarded

    with questions, provisions or other conditional markings are not actionable until eachparticular reservation is resolved to CMS satisfaction

    Project analysis and scheduling is non-refundable and invoiced at 3% of the scopedvalue plus $200.00. Prior to initializing either production or procurement or prior toimplementing a change to one or the other formal approval MUST be provided withan indemnification recap. ONCE PRODUCTION, PROCUREMENT OR A CHANGEIS INITIATED, COMPONENTS CAN BE NEITHER CANCELED NOR RETURNED

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 3/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    4/26

    Set 1.0Set 1.0Set 1.0Set 1.0 Clarify keying

    1 Pr Doors 1-1-RR-1001-1-RR-1001-1-RR-1001-1-RR-100 Existing Corridor --from-- Corridor 100LHRRHR

    Opening 7870 310 SCW doors HMHS frame B-Label

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    6 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    2 ea DOR Power transfers ES105 625

    2 ea DOR E-latch VR devs+lev trim ESF9400B-LBR-YC23 with door/door popper 630AM

    1 ea DOR E-latch power supply PS501 1a@120VAC 6934 ea DON Kick plates 90 10 door width less 2 630

    2 ea DON Convex wall stops 1412 626

    1 ea NGP Astragal seal 5070C door/door height COAL

    1 ea NGP Perimeter seal set 5020C doors/frame perimeter COAL

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by othersBalances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via device trims with passage levers

    Basic powered operation:

    Free egress at all timesAccess via device trims with passage levers OR via latch retraction of each device in concert

    with access/security controls and door operators by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 4/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    5/26

    Set 2.0Set 2.0Set 2.0Set 2.0 Clarify keying

    1 Sgl Door 1-1-S-C1-291-1-S-C1-291-1-S-C1-291-1-S-C1-29 Existing Wait Area --from-- Corridor C1-29 ~100O RHR

    Opening 3070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB74545 41/2x 41/2 652

    1 ea DOR Rim exit only device 9300B 630AM

    1 ea DOR Closer+stop 8616FMC-DS parallel 689

    1 ea DON Kick plate 90 10 door width less 2 630

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 5/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    6/26

    Set 3.1Set 3.1Set 3.1Set 3.1 Core & keying by others

    1 Sgl Door 1-1-S-402-11-1-S-402-11-1-S-402-11-1-S-402-1 Wait Area 400 --to-- Consult 402 RH

    Opening 3070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB74545 41/2x 41/2 652

    1 ea DOR Power transfer ES105 625

    1 ea DOR E-unlock leverset M9080EUL-LCM .21a@24VDC 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea ALT E-unlock power supply AL125UL .6a@115VAC 693

    1 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by others

    Balances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via keyed latch retraction

    Basic powered operation:

    Free egress at all timesAccess via keyed latch retraction OR via electric unlocking of the lever in concert with

    access/security controls by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 6/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    7/26

    Set 3.2Set 3.2Set 3.2Set 3.2 Core & keying by others

    1 Sgl Door 1-1-S-409-11-1-S-409-11-1-S-409-11-1-S-409-1 Wait Area 400 --from-- Corridor 409 LHR

    Opening 3670 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Power transfer ES105 625

    1 ea DOR E-unlock leverset M9080EUL-LCM .21a@24VDC 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea ALT E-unlock power supply AL125UL .6a@115VAC 693

    1 ea DOR Closer 616FMC-SPA parallel 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by others

    Balances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via keyed latch retraction

    Basic powered operation:

    Free egress at all timesAccess via keyed latch retraction OR via electric unlocking of the lever in concert with

    access/security controls by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 7/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    8/26

    Set 4.0Set 4.0Set 4.0Set 4.0 Core & keying by others

    1 Sgl Door 3-3-S-1093-3-S-1093-3-S-1093-3-S-109 Existing Corridor --to-- Agent Cashier 109 LH

    Opening 3070 310 HM door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB74545TX 41/2x 41/2 652

    1 ea DOR Power transfer ES105 625

    1 ea DOR E-unlock leverset M9080EUTXL-LCM .21a@24VDC 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea ALT E-unlock power supply AL125UL .6a@115VAC 693

    1 ea DOR Closer 8616FMCTX-AF regular 689

    1 ea DON Kick plate 90TX 10 door width less 2 630

    1 ea DON Mop plate 90TX 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by others

    Balances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via keyed latch retraction

    Basic powered operation:

    Free egress at all timesAccess via keyed latch retraction OR via electric unlocking of the lever in concert with

    access/security controls by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 8/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    9/26

    Set 5.1Set 5.1Set 5.1Set 5.1 Core & keying by others

    1 Sgl Door 1-1-S-4071-1-S-4071-1-S-4071-1-S-407 Existing Corridor --to-- Clean Utility 407 LH

    1 Sgl Door 1-1-S-4191-1-S-4191-1-S-4191-1-S-419 Infusion 414 --to-- Meds 419 LH

    1 Sgl Door 1-1-S-4201-1-S-4201-1-S-4201-1-S-420 Infusion 414 --to-- Clean Utility 407 RH

    Opening 3070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Storeroom leverset M9080L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 9/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    10/26

    Set 5.2Set 5.2Set 5.2Set 5.2 Core & keying by others

    1 Sgl Door 1A-1-S-1011A-1-S-1011A-1-S-1011A-1-S-101 Existing Corridor --from-- HAC 101 RHR

    1 Sgl Door 1A-1-S-1051A-1-S-1051A-1-S-1051A-1-S-105 Corridor 100 --from-- Equipment 105 RHR

    Opening 3070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Storeroom leverset M9080L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DOR Closer 8616FMC-SPA parallel 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Set 6.0Set 6.0Set 6.0Set 6.0 Core & keying by others

    1 Sgl Door 2-1-S-402-22-1-S-402-22-1-S-402-22-1-S-402-2 Corridor 409 --to-- Consult 402 RH

    Opening 3070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 10/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    11/26

    Set 7.1Set 7.1Set 7.1Set 7.1 Core & keying by others

    1 Sgl Door 1-1-S-112-11-1-S-112-11-1-S-112-11-1-S-112-1 Existing Wait --to-- Patient Advocate 112 RH

    Opening 3070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Set 7.2Set 7.2Set 7.2Set 7.2 Core & keying by others

    1 Sgl Door 1-1-S-112-21-1-S-112-21-1-S-112-21-1-S-112-2 Existing Corridor --to-- Patient Advocate 112 LH

    Opening 3870 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 6261 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 11/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    12/26

    Set 8.0Set 8.0Set 8.0Set 8.0 Core & keying by others

    1 Sgl Door 1-1-S-4081-1-S-4081-1-S-4081-1-S-408 Existing Corridor --to-- Break Room 408 ~90O RH

    Opening 3070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Classroom leverset M9070L-LCM 630AM

    1 ea COR Mortise housing 1070-A01 626

    1 ea DOR Closer+track stop 8616FMC-JT jamb track 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    3 ea DON Silencers 1608 COAL

    Set 9.0Set 9.0Set 9.0Set 9.0 Core & keying by others

    1 Sgl Door 1-1-S-1031-1-S-1031-1-S-1031-1-S-103 Corridor 100 --from-- Toilet 103 LHR

    1 Sgl Door 1-1-S-4011-1-S-4011-1-S-4011-1-S-401 Waiting 400 --from-- Toilet 401 RHR

    Opening 3070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Privacy leverset M9040-LCM 630AM

    1 ea DOR Closer 8616FMC-SPA parallel 6891 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 12/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    13/26

    Set 10.0Set 10.0Set 10.0Set 10.0 Core & keying by others

    1 Sgl Door 1-1-S-4171-1-S-4171-1-S-4171-1-S-417 Infusion 414 --from-- Toilet 417 ~95O RHR

    1 Sgl Door 1-1-S-4221-1-S-4221-1-S-4221-1-S-422 Infusion 414 --from-- Toilet 422 ~95O LHR

    Opening 3070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Privacy leverset M9040-LCM 630AM

    1 ea DOR Closer+stop 8616FMC-DS parallel 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    3 ea DON Silencers 1608 COAL

    Set 11.0Set 11.0Set 11.0Set 11.0 Core & keying by others

    1 Sgl Door 2-1-U-4032-1-U-4032-1-U-4032-1-U-403 Corridor 409 --to-- Precept 403 LH

    Opening 3870 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 13/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    14/26

    Set 12.0Set 12.0Set 12.0Set 12.0 Core & keying by others

    1 Sgl Door 1A-1-U-1081A-1-U-1081A-1-U-1081A-1-U-108 Existing Corridor --to-- Exam 108 LH

    1 Sgl Door 1A-1-U-1E-1451A-1-U-1E-1451A-1-U-1E-1451A-1-U-1E-145 Existing Corridor --to-- Exam 1E-145 RH

    1 Sgl Door 4-1-U-1104-1-U-1104-1-U-1104-1-U-110 Existing Corridor --to-- Exam 110 RH

    Opening 3870 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Coat hook 302 626

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 14/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    15/26

    Set 13.0Set 13.0Set 13.0Set 13.0 Core & keying by others

    1 Sgl Door 1-1-U-4161-1-U-4161-1-U-4161-1-U-416 Infusion 414 --to-- Nurse Office 416 ~95O LH

    Opening 3870 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Office leverset M9050L-LCM 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea DOR Closer+track stop 8616FMC-JT jamb track 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 15/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    16/26

    Set 14.0Set 14.0Set 14.0Set 14.0 Core & keying by others

    1 Sgl Door 1-1-U-4041-1-U-4041-1-U-4041-1-U-404 Corridor 409 --to-- Exam 404 LH

    1 Sgl Door 1-1-U-4051-1-U-4051-1-U-4051-1-U-405 Corridor 409 --to-- Exam 405 RH

    1 Sgl Door 1-1-U-4061-1-U-4061-1-U-4061-1-U-406 Corridor 409 --to-- Exam 406 LH

    1 Sgl Door 1-1-U-410-11-1-U-410-11-1-U-410-11-1-U-410-1 Corridor 409 --to-- Exam 410 RH

    1 Sgl Door 1-1-U-4111-1-U-4111-1-U-4111-1-U-411 Corridor 409 --to-- Exam 411 LH

    Opening 3870 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Passage leverset M9010-LCM 630AM

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Coat hook 302 626

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 16/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    17/26

    Set 15.0Set 15.0Set 15.0Set 15.0 Core & keying by others

    1 Sgl Door 1-1-X-4131-1-X-4131-1-X-4131-1-X-413 Corridor 409 --to-- Reception 413 LH

    Opening 3070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Standard weight hinges BB74545 41/2x 41/2 652

    1 ea DOR Classroom leverset M9070L-LCM 630AM

    1 ea COR Mortise housing 1070-A01 626

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Set 16.0Set 16.0Set 16.0Set 16.0 Core & keying by others

    1 Sgl Door 1-1-U-4151-1-U-4151-1-U-4151-1-U-415 Infusion 414 --to-- Infusion Exam 415 ~95O RH

    Opening 3870 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Classroom leverset M9070L-LCM 630AM

    1 ea COR Mortise housing 1070-A01 626

    1 ea DOR Closer+track stop 8616FMC-JT jamb track 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 17/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    18/26

    Set 17.0Set 17.0Set 17.0Set 17.0 Core & keying by others

    1 Sgl Door 1-1-X-409-21-1-X-409-21-1-X-409-21-1-X-409-2 Existing Corridor --to-- Corridor 409 RH

    Opening 3870 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Classroom leverset M9070L-LCM 630AM

    1 ea COR Mortise housing 1070-A01 626

    1 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 18/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    19/26

    Set 18.1Set 18.1Set 18.1Set 18.1 Core & keying by others

    1 Sgl Door 1-X-410-21-X-410-21-X-410-21-X-410-2 Existing Corridor --to-- Exam 410 LH

    Opening 4070 310 SCW door HMHS frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Power transfer ES105 625

    1 ea DOR E-unlock leverset M9080EUL-LCM .21a@24VDC 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea ALT E-unlock power supply AL125UL .6a@115VAC 693

    1 ea DOR Closer 8616FMC-AF regular 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by others

    Balances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via keyed latch retraction

    Basic powered operation:

    Free egress at all timesAccess via keyed latch retraction OR via electric unlocking of the lever in concert with

    access/security controls by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 19/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    20/26

    Set 18.2Set 18.2Set 18.2Set 18.2 Core & keying by others

    1 Sgl Door 1-1-X-414A-11-1-X-414A-11-1-X-414A-11-1-X-414A-1 Existing Corridor --from-- Infusion 414 RHR

    1 Sgl Door 1-1-X-414A-21-1-X-414A-21-1-X-414A-21-1-X-414A-2 Existing Corridor --from-- Infusion 414 LHR

    Opening 4070 310 SCW door HMHS frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    3 ea DON Heavy weight hinges HWBB75045 5x 41/2 652

    1 ea DOR Power transfer ES105 625

    1 ea DOR E-unlock leverset M9080EUL-LCM .21a@24VDC 630AM

    1 ea COR Mortise housing 1070-A02 626

    1 ea ALT E-unlock power supply AL125UL .6a@115VAC 693

    1 ea DOR Closer 8616FMC-SPA parallel 689

    1 ea DON Kick plate 90 10 door width less 2 630

    1 ea DON Mop plate 90 6 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    3 ea DON Silencers 1608 COAL

    Components wiring diagram produced ONLY after all details are clarified and approved

    Clarify if incompatible with conditions or components by othersBalances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via keyed latch retraction

    Basic powered operation:

    Free egress at all timesAccess via keyed latch retraction OR via electric unlocking of the lever in concert with

    access/security controls by others

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 20/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    21/26

    Set 19.0Set 19.0Set 19.0Set 19.0 Clarify keying

    1 Pr Doors 5-5-NX-1065-5-NX-1065-5-NX-1065-5-NX-106 Corridor 100 --to-- Procedure 106LHARH

    Opening 6070 40

    20SCWLL active doorSCWLL inactive door

    HMLL frame

    QtyQtyQtyQty MfgrMfgrMfgrMfgr DescriptionDescriptionDescriptionDescription ModelModelModelModel FinishFinishFinishFinish

    2 ea DOR Pivot sets+intermediate OP440+75220 652

    2 ea DON Flush bolts 1557 inactive door leaf 626

    1 ea DOR Passage leverset M9010-LCM lead lined 630AM1 ea DOR Top-jamb maglock EML3081M-TJ81 .440a@12VDC 628

    1 ea ALT Maglock power supply AL125UL .600a@115VAC 693

    1 ea DOR Closer+hold-open 8616FMC-FH regular, lead lined 689

    2 ea DON Armor plates, push side 90SM 30 door width less 2 630

    2 ea DON Kick plates, pull side 90SM 10 door width less 1 630

    2 ea DON Convex wall stops 1412 626

    Components wiring diagram produced ONLY after all details are clarified and approvedAstragal by the doors provider, and balances of components by othersClarify if incompatible with conditions or components by others

    Basic unpowered operation:

    Free egress at all timesAccess via passage leverset at all times

    Basic powered operation:

    Egress halted via maglock whenever energizedAccess halted via maglock whenever energized

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 21/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    22/26

    Set 20.0Set 20.0Set 20.0Set 20.0 Clarify keying

    1 Sgl Door 5-5-S-1045-5-S-1045-5-S-1045-5-S-104 Scrub Alcove 104 --to-- Procedure 106 RH

    Opening 3070 40 SCWLL door HMLL frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    1 ea DOR Pivot set+intermediate OP440+75220 652

    1 ea DOR Passage leverset M9010-LCM lead lined 630AM

    1 ea DOR Top-jamb maglock EML3081M-TJ81 .440a@12VDC 628

    1 ea ALT Maglock power supply AL125UL .600a@115VAC 693

    1 ea DOR Closer+hold-open 8616FMC-FH regular, lead lined 689

    1 ea DON Armor plate, push side 90SM 30 door width less 2 630

    1 ea DON Kick plate, pull side 90SM 10 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by othersBalances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via passage leverset at all times

    Basic powered operation:

    Egress halted via maglock whenever energizedAccess halted via maglock whenever energized

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 22/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    23/26

    Set 21.0Set 21.0Set 21.0Set 21.0 Clarify keying

    1 Sgl Door 5-5-S-1075-5-S-1075-5-S-1075-5-S-107 Procedure 106 --from-- Toilet 107 RHR

    Opening 3070 40 SCWLL door HMLL frame

    QtyQtQtQty MfgrMf rMf rMfgr DescriptionDescri tionDescri tionDescription ModelModelModelModel FinishFinishFinishFinish

    1 ea DOR Pivot set+intermediate OP440+75220 652

    1 ea DOR Privacy leverset M9040-LCM lead lined 630AM

    1 ea DOR Maglock EML3081M .440a@12VDC 628

    1 ea ALT Maglock power supply AL125UL .600a@115VAC 693

    1 ea DOR Closer+hold-open 8616FMC-FHP parallel, lead lined 689

    1 ea DON Armor plate, push side 90SM 30 door width less 2 630

    1 ea DON Kick plate, pull side 90SM 10 door width less 1 630

    1 ea DON Convex wall stop 1412 626

    Components wiring diagram produced ONLY after all details are clarified and approvedClarify if incompatible with conditions or components by othersBalances of components by others

    Basic unpowered operation:

    Free egress at all timesAccess via privacy leverset at all times

    Basic powered operation:

    Egress halted via maglock whenever energizedAccess halted via maglock whenever energized

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 23/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    24/26

    Components ReferenceComponents ReferenceComponents ReferenceComponents Reference by schedule annotation

    Manufacturer Description Model

    ALT Altronix Power supply, filtered and regulated AL125ULaltronix.com

    COR Corbin Russwin Hardware Mortise housings, less 7-pin core 1070[-cam]corbinrusswin.com

    DON Don-Jo Manufacturing Armor/kick/mop plates, sized 90don-jo.com Self-adhesive mount option ...SM

    With torx security fasteners ...TXCoat hooks 302Wall stops, convex 1412Manual flush bolts 1557Silencers 1608

    Standard ball bearing hinges, sized BB7[size]Heavy ball bearing hinges, sized HWBB7[size]

    Non-removable pin option (standard NRP...feature for heavy weight)

    DOR Dorma Architectural Hardware Offset pivot sets OP440dorma-usa.com Intermediate pivot 75220

    Grade 1 surface closers 8600 SeriesBarrier free, size adjustable 1~6 ...16Full metal cover configuration ...FMC

    With torx security fasteners ...TXStandard/top-jamb flat arm -AFRugged door stop parallel arm -DSFriction hold-open arm option -FHTrack arm with stop option -JTRugged parallel arm -SPAParallel~mount adapter option ...PTop jamb long reveal option ...J

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 24/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    25/26

    Components ReferenceComponents ReferenceComponents ReferenceComponents Reference by schedule annotation

    Manufacturer Description Model

    DOR Dorma Architectural Hardware Grade 1 exit devices 9000 Seriesdorma-usa.com Rim type, standard 9300

    Vertical rod type, standard 9400Electric latch retraction option ES...Fire rated configuration F...For 34~48 nominal door, standard ...AFor 28~36 nominal door, standard ...BWith torx security fasteners ...TXPopper aka less bottom rod option -LBRPassage function lever trim -YC23

    Grade 1 mortise leversets ML9000 SeriesPassage function F01 ...9010Privacy function F22 ...9040Office function F04 ...9050Classroom function F05 ...9070Storeroom function F07 ...9080Electric unlock aka fail secure config ...9080EULess cylinder ...LWith torx security fasteners ...TX

    Curved ADA lever escutcheon trim -LCMAntimicrobial finish options [finish]AMPower transfers ES105Dedicated e-latch power supplies PS501Grade 1 maglock, standard mount EML3081MTop-jamb aka inswing option -TJ81

    NGP National Guard Products Perimeter seal sets, sized 5020C

    ngpinc.com Astragal seals, sized 5070C

    11/14/12 VAMC Dayton Oncology Relocation 121114.pdf 25/26 [ less cut sh

    2828 W Riverview AveDayton OH 45402

    (937) 278-0706 Phone(937) 278-7604 Fax

    CONSOLIDATED

    MILLWORK SUPPLY

    Mark [email protected]

    cmsi.webs.co

  • 7/30/2019 VAMC Dayton Oncology Relocation Door Hardware Scheduling

    26/26

    AAAANNNNSSSSIIII////BBBBHHHHMMMMAAAA Base Materials and Finishes ReferenceBase Materials and Finishes ReferenceBase Materials and Finishes ReferenceBase Materials and Finishes Reference by schedule annotation

    ANSI US Finish Description Base Material Related sim

    626 26D Satin chromium plated Brass/Bronze 630 652 628 6

    628 28 Satin, clear anodized Aluminum 689

    630 32D Satin stainless steel Stainless 300 626 652 628 6

    652 26D Satin chromium plated Steel 626 630 628 6

    689 Paint/coated to match 628 Any 628

    719 Mill or natural Aluminum 628 6