Easy to Use, Available in 3, 6, or 12 Dry-Contact InputsThe Model CT-6500 Series 2 is a stand-alone, microcomputer-driven EHV Circuit-Breaker Analyzer. It is inexpensive and easy to use. The CT-6500 is available inmodels with either 3 dry contacts (CT-6500-3); 6 dry-contacts (CT-6500-6); or 12dry-contact inputs (CT-6500-12). The CT-6500 fully analyzes circuit-breaker per-formance: contact time, stroke, velocity, over-travel, and contact wipe. Contact-motion analysis includes: Open, Close, Open-Close, Close-Open, and Open-Close-Open. The CT-6500 timing window is selectable: 1-second, 10-second, or 20-sec-ond periods. The 10 and 20-second timing windows allow timing the long durationevents (Circuit-Switcher contacts).

Contact Timing InputsBreaker contact timing uses dry-contact input channels. Each contact-input chan-nel can detect main contact and insertion-resistor contact times (milliseconds andcycles).

Voltage Monitoring InputsOne analog voltage input channel is dedicated to monitoring circuit-breaker dcpower supply or coil voltages 0 to 300 volts, dc or peak ac. One digital voltageinput channel allows users to monitor voltage on/off status of an A/B switch.

Trip/Close Current MonitoringA built-in Hall-effect current sensor records Trip/Close current level and duration.The breaker’s operate-coil current waveform duration (effectively, a performance"fingerprint" or "current profile") can be used as a diagnostic tool for analysis ofa breaker’s performance.

Breaker Stroke and VelocityThree travel transducer digital channels let the CT-6500 measure stroke, over-trav-el, and bounce-back. Unlike other types of transducers, the digital transducerrequires neither calibration nor setup.

Slow-Close TestWhen a cable-connected travel transducer is attached to a circuit breaker (formeasuring contact velocity), the Analyzer can also print out a table of "slow-close" test results. This Analyzer’s feature is a tool for accurately measuring con-tact-travel during circuit-breaker maintenance (when the circuit-breaker con-tact motion is slowly jacked through the stroke by manual operation i.e., ahand-operated "slow-close" test).

Timing Record Storage CapabilitiesThe CT-6500 uses Electrically Erasable PROMs (EEPROMs) to store timing-records data. Unlike other storage media, EEPROMs are immune to shock, tem-perature, and humidity. Stored timing records can be recalled by users to re-analyze test data, to print copies, or to transfer data to an IBM-compatible PCfor record keeping. Up to 200 timing records can be stored in EEPROMs.

Breaker Initiate FeaturesA built-in solid-state initiate device lets users operate the breaker from the CT-6500. The operational modes include: Open, Close, Open-Close, Close-Open,and Open-Close-Open. Multiple operations (e.g., Open-Close, Open-Close-Open) can be initiated by using programmable delay time or by sensing break-er’s contact condition.

Diagnostic CapabilitiesThe CT-6500 can perform diagnostics on its internal electronics. Self testing oftransducer and contact-test cables lets users check out the Timer whenever ver-ification is required.

Computer InterfaceThe CT-6500 can be used in the stand-alone mode or computer controlledmode. USB and RS-232C Ports allow an IBM-PC compatible computer to con-trol the CT-6500. From the PC, circuit breakers can be timed and users canretrieve timing shots saved in the CT-7500 flash EEPROM. A Windows® XP-basedBreaker-Analysis software lets users time circuit breakers, retrieve test-shotdata stored in the computer’s hard-drive, re-analyze the stored data, and gener-ate reports in the office. Test reports can be exported to Excel, allowing the userto generate customized test-result reports. Users may also create a circuit-breaker database library.

User InterfaceAn alpha-numeric keypad lets users enter breaker ID and control functions. A 4-line by 20-character LCD readout displays user messages. The LCD is back lightedso messages can be viewed in low light levels. A display contrast control is locatedon the front panel.

Built-in Thermal PrinterA built-in thermal printer prints the breaker contact analysis results in both tabu-lar and graphic formats on 4.5-inch-wide thermal paper.

CT-6500

Digital Circuit Breaker Analyzer

Rapidly Analyze

Vanguard Instruments CompanyReliability Through Instrumentation

OCB, Vacuum, and SF6 CircuitBreakers with Vanguard’s CT-6500alyze

Voltage Input Channels

Trigger Input Connector

Travel TransducerConnector

Breaker Initiate Output

Thermal Printer

Breaker InitiateArm Switch

Contact Timing Channel

RS-232C Port

USB Port

4x20 Backlit LCD Display

16-Key MembraneKeyboard

RVFeb07

Digital Circuit Breaker Analyzer

PC Printer Output

Built-in Thermal Printer Output

t

t

Graphic andTabulated Printouts

Microcomputer Accuracy in an Inexpensive Digital Circuit Breaker Tester

CT-6500, 3 Contact Channels, Cables, PC Software Part No: CT-6500-3 S2CT-6500, 6 Contact Channels, Cables, PC Software Part No: CT-6500-6 S2CT-6500,12 Contact Channels, Cables, PC Software Part No: CT-6500-12 S2CT-6500 Shipping Case Part No: CT-6500-CASE4.5-inch Printer Paper Part No: Paper-TP4

Ordering InformationCT-6500 Series 2 Digital Circuit Breaker Timer

SeePage 87for Travel

TransducerOrdering Info

CT-6500 S2Digital Circuit Breaker Analyzer

Vanguard Instruments CompanyReliability Through Instrumentation

pensive Digital Circuit Breaker TesterFE

ATU

RE

S

TYPE

PHYSICAL SPECIFICATIONS

INPUT POWER

DRY-CONTACT INPUTS

TIMING WINDOWS

TIMING RESOLUTION

TIMING ACCURACY

DRY CONTACT CHANNEL PROTECTION

DRY CONTACT DETECTION RANGE

RESISTOR DETECTION RANGE

TRIGGER INPUT VOLTAGE

VOLTAGE SENSING INPUT RANGE

BREAKER OPERATION

BREAKER INITIATE CAPACITY

INITIATE CURRENT READING RANGE

TRAVEL TRANSDUCER INPUT

CONTACT TRAVEL POINT DIFFERENCE

DISPLAY

PRINTOUT

TEST RECORD STORAGE

COMPUTE INTERFACE

PC SOFTWARE

SAFETY

ENVIRONMENT

OPTIONS

WARRANTY

Special purpose test equipment, portable circuit breaker analyzer

16” W by 11” H by 14” D (40.6 cm x 29.9 cm x 35.6 cm); Weight, less than 25 lbs (11.3 kg)

90-130 Vac or 200-240 Vac (selectable), 50/60Hz

3, 6 or 12 dry-input channels. Each channel detects Main and Insertion-Resistor Contacts

Selectable: 1-second, 10-seconds, 20-seconds

±50 microseconds at 1-second duration, ±500 microseconds at 10-second duration,

±1.0 milliseconds at 20-second duration

0.05% of reading, ±0.05 ms at 1-second duration

Fuses protect all isolated power supplies. All contact inputs are grounded until test.

TVS and Zener-diode protected.

Closed: <20 ohm, Open:> 5,000 ohm

50 to 5,000 Ohm

Open/Close: 30-300V dc or peak ac

V1: analog input; 0-255V dc or peak ac, Sensitivity ±1V; V2: voltage detector (present/absent) input;

30-300V cd or peak ac

Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open

30A/250V ac/dc max

One, Non-contact, Hall-Effect sensor, 0-20A, dc to 5Khz

3 digital travel transducer channel; Linear range, 0.0-60.0 in (±0.01 in); Rotary range 0-360° (±0.36°)

Measures “Slow-Close” contact-point distances (hard copy)

4 lines by 20 character back-lit LCD, sunlight viewable

Both graphic contact and travel waveforms & tabulated results are printed on 4.5-inch thermal printer

Store up to 200 timing records

USB and RS-232C port

Furnished Circuit breaker analysis software running under Windows XP; features graphic display,

numerical reports, and data base utility for use at shop or office.

Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92

Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)

Hard case for shipping; available for both Travel Transducers and CT-6500

One-year warranty on parts and labor

SPECIFICATIONS

• Full Breaker Tabulated & Graphic Data Printout• Built-in thermal printer • Initiate Breaker Operation• Digital Travel Transducer; no setup or calibration required• Detect Main Contact and Insertion Resistor Contact on the same input channel• On-Board EEPROM Shot Storage • Computer Interface • Diagnostic Capabilities

Note: The above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice.

RVFeb07

Vanguard Instruments Company, Inc.

Vanguard Instruments Co., (VIC), was founded in 1991.Currently, our 28,000 square-foot facility housesAdministration, Design & Engineering, and Manufacturingoperations. From its inception, VIC’s vision was, and is todevelop and manufacture innovative test equipment foruse in testing substation EHV circuit breakers and otherelectrical apparatus.

The first VIC product was a computerized circuit-breaker analyzer, which was a resounding success. Itbecame the forerunner of an entire series of circuit-breaker test equipment. Since its beginning, VIC’sproduct line has expanded to include microcomputer-based, precision micro-ohmmeters, single and three-phase transformer winding turns-ratio testers, wind-ing-resistance meters, transformer tap-changing con-trollers, megaohm resistance meters, and a variety ofother electrical utility maintenance support products.

VIC’s performance-oriented products are well suitedfor the utility industry. They are rugged, reliable, accu-rate, user friendly, and most are computer controlled.Computer control, with innovative programming, pro-vides many automated testing functions. VIC’s instru-ments eliminate tedious and time-consuming opera-tions, while providing fast, complex, test-result calcu-lations. Errors are reduced and the need to memorizelong sequences of procedural steps is eliminated.Every VIC instrument is competitively priced and iscovered by a liberal warranty.

Vanguard Instruments Company, Inc.1520 S. Hellman Ave. • Ontario, California 91761 USA • P 909-923-9390 • F 909-923-9391