54
http://www.alnor.com.pl/produkty_pl/Kanaly-i-ksztaltki-okragle.html 547 Ventilation dampers ALNOR reserves the right to modify technical specifications in line with the policy of continuous product improvement. ALNOR ® ventilation systems is a registered trademark protected by a technical patent. All modification rights reserved. Download Wentyle Download AlnorCAM B2B ordering

Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

http://www.alnor.com.pl/produkty_pl/Kanaly-i-ksztaltki-okragle.html

547

Ventilation dampers

ALNOR reserves the right to modify technical specifications in line with the policy of continuous product improvement.

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Download WentyleDownload AlnorCAM

B2B ordering

Page 2: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

548

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Damper tolerance limits

Damper sizing

Diameter Ødnom

(mm)

min. - max. diameterØdmin- Ødmax

(mm)

Sheet thicknesstnom

(mm)

80 78.8 - 79.3 0.5

100 98.8 - 99.3 0.5

125 123.8 - 124.3 0.5

140 138.7 - 139.3 0.5

150 148.7 - 149.3 0.5

160 158.7 - 159.3 0.5

180 178.6 - 179.3 0.5

200 198.6 - 199.3 0.5

224 222.5 - 223.3 0.5

250 248.5 - 249.3 0.5

280 278.4 - 279.3 0.5

300 298.4 - 299.3 0.5

315 313.4 - 314.3 0.5

355 353.3 - 354.3 0.5

400 398.3 - 399.3 0.5

450 448.2 - 449.3 0.5

500 498.2 - 499.3 0.5

560 558.1 - 559.3 0.6

600 598.2 - 599.3 0.6

630 628.1 - 629.3 0.6

Dimensions

System descriptionTogether with matching fittings and ducts, ventilation dampers offer a complete system for building ventilation ductwork. The wide range of types and versions allows adapting the damper solution to virtually all design requirements.

All diameter sizes of round dampers match the SPIRAL®system round fittings. Rectangular damper sizes need to be adjusted to the dimensions of the ductwork and fittings installed. All other sizes are shown in the tables and specifications in the individual Product Data Sheets.

Installation instructionsRound dampers are fastened with self-drilling screws or blind rivets, either of which are driven through the ductwork length overlapping the connection flange inside. Rectangular dampers are fastened with screws at the steel corner straps and with the KLQ G-clamp which couples two flange frames. Both round and rectangular dampers can be provided with actuators for operation of the closure.

MarkingALNOR products carry the Polish conformity mark B for construction products and product codes as shown in the technical specifications listed in this catalogue.The SPIRAL®system round dampers made from galvanized steel sheet are provided with the PZH-NIH Hygiene Certificate No. HK/B/0867/01/2009. Rectangular dampers are provided with the PZH-NIH Hygiene Certificate No.:HK/B/0100/02/2009 (version in galvanized steel sheet);HK/B/0101/01/2009 (version in stainless steel sheet).

Ventilation dampers

TECHNICAL INFORMATION

MaterialsThe dampers are made from galvanized steel sheet. Other materials are available on request (see the details below for specific damper types):1.4301/304 stainless steel sheet 1.4404/316L stainless steel sheet, molybdenum enriched

Always indicate the material code in your purchase order. If no material code is specified in the order, the default material will be used, i.e. galvanized steel sheet.

Examples of material codes:DARH-K-… — 1.4301 / 304DARH-K-…..-…..-316L — 1.4404 / 316L

Components made from stainless steel have to be inspected at least every 6 months.

The SPIRAL®system meets the tolerance limits given in the table below to provide the required sealing performance.

Ødnom

(mm)e

(mm)tolerance

(mm)

80-315 36 +0 -6

355-400 55 +0 -6

450-630 75 +0 -10

Page 3: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

549

Przeciek powietrza q v [l/(s*m

2)]

0,1 1 10 100 1000

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Ventilation dampers

TECHNICAL INFORMATIONAir tightness chartA leak-proof damper system

The DATL damper system was laboratory-tested. The tests included measurements of the air leak through a closed damper installed in a ductwork, with the test air flow matching the correct air flow direction designed for the damper. All dampers have the correct air flow direction marked on the housing.The purpose of the laboratory tests was to determine the air tightness class of the dampers.The measurement method followed the EN 1751 standard test method for DATL-315 dampers.

Air leak test results for the DATL-315 damper:

Item

No.

Pduct (Pa) qVLBA (l/sm2) Trend line

1 140 0.25

Pduct = 527.9 (qVLBA)0.8989

2 249 0.44

3 311 0.53

4 443 0.81

5 514 1.04

6 853 1.59

7 960 1.73

8 1220 2.30

9 1364 2.72

10 1570 3.51

11 1744 4.06

12 2085 5.15

Pduct — air pressure in the ductqVLBA — air flow rate

The table below shows the air leak rates through a closed DATL-315 damper at tot = 26.1˚C and Pat = 1010.6 hPa.

Air tightness classes 4 3 2 1

Air leak rate gv (l/(sm2))

2000

1000

100

Duc

t pr

essu

re P

s (Pa

)

Page 4: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

550

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Damper tolerance limits for versions in stainless steel, copper sheet and aluminium sheet

Dampers made from 304 or 316L stainless steel are designed for ventilation systems operated in environments involving harsh temperature, humidity or air contaminants inside or outside the ductwork. The compatible damper mechanisms include CV or PVC with the pivot rods made from plastic. The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured from the specified type of material. All non-return dampers are supplied with the pivot rod(s) made from stainless steel, irrespective of the material code specified. Large dampers, i.e. of diameter 315 mm or greater, can be made with the KKS-KWS damper mechanism if the material ordered is 1.4301 stainless steel sheet.

1.4301/304 components made from sheet metal

1.4404/316L components made from sheet metal

Diameter Ødnom (mm)

Sheet thickness tnom (mm)

Diameter Ødnom

(mm)Sheet thickness

tnom (mm)

80 0.5 80 0.6

100 0.5 100 0.6

112 0.5 112 0.6

125 0.5 125 0.6

140 0.5 140 0.6

150 0.5 150 0.6

160 0.5 160 0.6

180 0.5 180 0.6

200 0.5 200 0.6

224 0.5 224 0.6

250 0.5 250 0.6

280 0.5 280 0.6

300 0.5 300 0.6

315 0.5 315 0.6

355 0.5 355 0.6

400 0.5 400 0.6

450 0.5 450 0.6

500 0.5 500 0.6

560 0.5 560 0.6

600 0.5 600 0.6

630 0.5 630 0.6

Dampers made from copper sheet and aluminium sheet are designed for use as shutoff or regulating dampers in ventilation systems. It is best to order and operate the dampers with a PVC or CV damper mechanism and plastic parts only (without any parts made from galvanized steel). Given the specifics of the damper mechanisms, it is recommended that dampers should have diameters up to 315 mm. If the damper diameter is to be greater than 355 mm, order the DSQW-A aluminium-sheet damper with adapters for connecting with round ducts.

AW-1050A H24 compo-nents made from sheet

metal

M1-E components made from sheet metal

Diameter Ødnom (mm)

Sheet thickness tnom (mm)

Diameter Ødnom

(mm)Sheet thickness

tnom (mm)

80 0.8

100 0.8

112 0.8

125 0.8

140 0.8

150 0.8

160 0.8

180 0.8

200 0.8

224 0.8

250 0.8

280 0.8

300 0.8

315 0.8

355 0.8

400 0.8

450 0.8

500 0.8

560 0.8

600 0.8

630 0.8

Page 5: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

551

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-315

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

315

190

70

30

Ø

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-250

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

70

30

128

250Ø

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-200

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

74

30

200

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-160

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

76

30

160Ø

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-150

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

70

28

150

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-125

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

125

46

18

Ø

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-100

krzysztof.pietras 05.06.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

1948

100

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

DAT-AKU-080

krzysztof.pietras 30.05.2018Zaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

1 / 1 Wydanie Arkusz

Data

52

4618

80Ø

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Plastic foam damper

DAT-AKUDimensions

DescriptionThe DAT-AKU is an economical and an easy-to-install foam damper/silencer designed for central ventilation systems with attenuating properties. The design and the material the foam damper is made of - namely - non-flammable flexible polyurethane foam (class B2 according to DIN 4102-1) lead to its double function - a damper with an attenuating properties. Installation instructions: Insert the damper into the circular duct (e.g. before the air valve), then adjust pressure and airflow by removing the number of open holes. In order to obtain better attenuation, install several DAT-AKU foam dampers in series.

Available materials - Product code examplesDAT-AKU-…-50 - 50 mm thick polyurethane foam DAT-AKU-…-75 - 75mm thick polyurethane foam

Product code exampleProduct code: DAT-AKU - 100 - 50

typeØdthickness

Product code ød [mm]

Thickness [mm]

Number of holes

DAT-AKU-80 80 50 / 75 3

DAT-AKU-100 100 50 / 75 5

DAT-AKU-125 125 50 / 75 8

DAT-AKU-160 160 50 / 75 5

DAT-AKU-200 200 50 / 75 8

DAT-AKU-250 250 50 / 75 10

DAT-AKU-315 315 50 / 75 14

Page 6: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

552

10

20

40

80

160

320

10 20 40 80 160

Δp[P

a]

Q [m3/h]

DAT-AKU-100-50

5432

liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320

Δp [

Pa]

Q [m3/h]

DAT-AKU-160-50

5

432liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320

Δp [

Pa]

Q [m3/h]

DAT-AKU-160-75

5

432liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320 640

Δp [

Pa]

Q [m3/h]

DAT-AKU-200-50

876543

liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320 640

Δp [

Pa]

Q [m3/h]

DAT-AKU-200-75

876543

liczba otworów

10

20

40

80

160

320

10 20 40 80 160

Δp [

Pa]

Q [m3/h]

DAT-AKU-100-755432

liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320

Δp [

Pa]

Q [m3/h]

DAT-AKU-125-50

8

7654liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320

Δp [

Pa]

Q [m3/h]

DAT-AKU-125-75

87654

liczba otworów

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Plastic foam damper

DAT-AKUAir flow charts DAT-AKU-100-50 DAT-AKU-160-50

DAT-AKU-160-75

DAT-AKU-200-50

DAT-AKU-200-75

DAT-AKU-100-75

DAT-AKU-125-75

Number of holes Number of holes

Number of holes

Number of holes

Number of holes

Number of holes

Number of holes

Number of holes

DAT-AKU-125-50

Page 7: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

553

10

20

40

80

160

320

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DAT-AKU-250-50

10

6

9

875321liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DAT-AKU-250-75

10

98765321

liczba otworów

10

20

40

80

160

320

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DAT-AKU-315-75

1412641 100

liczba otworów

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Plastic foam damper

DAT-AKUAir flow charts DAT-AKU-250-50

DAT-AKU-250-75

DAT-AKU-315-75

Number of holes

Number of holes

Number of holes

Page 8: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

554

80

140

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Regulating damper with air tightness class D joints

DARLDimensions

DescriptionThe DARL regulating damper with EPDM gaskets at both flange connections has been designed for cladding with up to 50 mm thick insulation.The damper closure is pivoted on separate square rods. The square rod pivots are replaced with a single solid bar in regulating dampers of diameter 450 mm.The damper closure position can be read on the 0° to 90° dial of the control handle. Closing the damper closure allows 20% of the rated air flow to pass. The damper closure opening ratio can be fixed with a screw.All the DARL regulating dampers of diameter 450 mm or greater are supplied complete with the KIT-DS-H damper mechanism control lever.

Available materials — Product code examplesDARL-... — galvanized steel sheetDAR-PVC-... — galvanized steel sheet

For d1 < 450, the damper closure pivot is mounted on two short rods;For d1 ≥ 450, the damper closure pivot is mounted on a single long bar.

for d1< 355

for d1 ≥ 355

Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

355 2.00

400 2.40

450 3.50

500 4.00

560 4.60

600 5.00

630 5.40

If the damper diameter is greater than 630 mm, order the DASQL multi-blade damper.

Product code exampleProduct code: DARL - aaa

typeØd1

Page 9: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

555

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Regulating damper

DAR

The DAR dampers for round ducts are available in the diameters of 80 mm to 630 mm. The damper closure has two chord-cut edges to provide 20% of the rated air flow in the closed position. The dampers 450 mm in diameter and larger have the damper closure pivot braced additionally with a single steel bar across the opening. The damper mechanism can be provided with up 50 mm thick insulation and features a control dial to show the opening ratio. The dampers of diameter 450 mm or greater also feature the KIT-DS-H damper mechanism control lever for easier operation.

Available materials — Product code examplesDAR-... — galvanized steel sheet

DAR-K-... — 1.4301/304 stainless steel sheet

Description

For d1 < 450, the damper closure pivot is mounted on two short rods;For d1 ≥ 450, the damper closure pivot is mounted on a single long bar.

Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

355 2.00

400 2.40

450 3.50

500 4.00

560 4.60

600 5.00

630 5.40

If the damper diameter is to be greater than 630 mm, order the DASQL multi-blade damper.

Product code exampleProduct code: DAR - aaa

typeØd1

Page 10: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

556

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round damper

DARHDimensions

DescriptionThe DARH dampers regulate the air flow rate in ventilation systems. The damper closure has two chord-cut edges to provide 20% of the rated air flow in the closed position. This damper model is the easiest to install and operate, and the most budget-friendly solution for air flow control in round ductwork systems.

Available materials — Product code examplesDARH-... — galvanized steel sheet

DARH-K-... — 1.4301/304 stainless steel sheet

Ød1 nom (mm)

Weight

(kg)

80 0.4

100 0.4

125 0.5

140 0.6

150 0.6

160 0.7

180 0.7

200 0.8

224 0.9

250 1.2

280 1.4

300 1.5

315 1.6

Product code exampleProduct code: DARH - aaa

typeØd1

Page 11: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

557

50

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Regulating dampers

DAR-CV

The DAR-CV regulating damper has been designed for cladding with up to 50 mm thick insulation.The DAR-CV damper closure position can be read on the 0° to 90° dial of the control handle. Closing the damper closure allows 20% of the rated air flow to pass. The damper closure opening ratio can be fixed with a screw.

Available materials — Product code examplesDAR-CV-... — galvanized steel sheet

Description Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

355 2.00

400 2.60

Product code exampleProduct code: DAR-CV - aaa

typeØd1

Page 12: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

558

30

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Regulating dampers

DAR-PVCDimensions

DescriptionThe DAR-PVC regulating damper has been designed for cladding with up to 30 mm thick insulation.The DAR-PVC damper closure position can be read on the 0° to 90° dial of the control handle. Closing the damper closure allows 20% of the rated air flow to pass. The damper closure opening ratio can be fixed with a screw.

Available materials — Product code examplesDAR-PVC-... — galvanized steel sheet

DAR-PVC-K-... — 1.4301/304 stainless steel sheet

Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

Product code exampleProduct code: DAR-PVC - aaa

typeØd1

Page 13: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

559

Æ100Æ80

Æ160Æ125

Æ100Æ80

Æ160Æ125

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Technical specificationsPressure loss and sound level charts to help with the product selection.

Solid lines show the overall pressure loss across a damper vs. the air flow rate and the damper closure opening angle. The curve shows the A-weighed sound level value, Lw (A), in dB, inside a connected duct.

Example:Diameter Ø: 100Air flow rate: 60 l/sPressure loss: 200 Pa

The following information can be read from the charts:Opening angle: 40°Sound level: 62 dB(A)

Regulating dampers

DARL/DAR/DARH

Page 14: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

560

Æ200 Æ250

Æ315

Æ500 Æ630

Æ400

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Regulating dampers

DARL/DAR/DARH

Technical specifications

Page 15: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

561

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Technical specificationsSound performance specifications for DARL dampersSound level Lw (dB) in 63-8000 Hz octave bands vs. diameter, air flow rate and pressure loss.

Regulating dampers

DARL/DAR/DARH

diameter(mm)

pressureloss (Pa)

mean velocity: 3 m/sfrequency (Hz)

mean velocity: 6 m/sfrequency (Hz)

mean velocity: 9 m/sfrequency (Hz)

mean velocity: 12 m/sfrequency (Hz)

mean velocity: 15 m/sfrequency (Hz)

63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

air flow rate: 15 l/s air flow rate: 30 l/s air flow rate: 45 l/s air flow rate: 60 l/s air flow rate: 75 l/s

80

500 65 65 65 65 59 55 49 46 67 67 67 67 60 57 50 47 70 70 70 70 63 60 53 49 75 75 75 75 68 64 56 53 80 80 80 80 72 68 60 56

300 63 63 60 60 54 48 42 36 66 66 63 63 56 50 44 38 70 70 67 67 60 54 47 40 75 75 71 71 64 57 50 43 79 79 75 75 68 60 53 45

200 63 63 60 54 51 43 34 29 65 65 62 56 53 44 35 30 70 70 67 60 57 48 38 32 75 75 71 65 61 51 41 34 – – – – – – – –

100 55 60 53 48 43 30 23 15 59 65 57 51 46 32 24 16 66 72 63 57 51 36 27 18 – – – – – – – – – – – – – – – –

50 56 54 47 43 36 25 16 9 59 59 52 47 40 27 17 10 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 25 l/s air flow rate: 50 l/s air flow rate: 75 l/s air flow rate: 100 l/s air flow rate: 120 l/s

100

500 67 64 64 57 54 48 48 48 72 68 68 62 59 52 52 52 78 75 75 67 64 57 57 57 84 81 80 72 68 62 61 61 88 85 84 76 72 65 64 64

300 62 61 60 54 51 45 42 42 68 68 68 59 56 50 47 47 75 74 73 65 61 54 51 51 81 80 79 70 67 59 56 55 86 85 84 74 70 62 59 58

200 58 58 58 50 48 40 37 37 65 65 64 57 54 45 42 42 74 73 73 64 59 50 47 46 80 80 79 69 66 55 51 51 – – – – – – – –

100 58 55 53 46 41 34 26 24 68 66 62 54 48 40 31 29 79 75 71 62 56 46 36 33 – – – – – – – – – – – – – – – –

50 55 53 48 42 35 26 22 18 69 67 60 53 44 33 28 22 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 40 l/s air flow rate: 80 l/s air flow rate: 120 l/s air flow rate: 160 l/s air flow rate: 180 l/s

125

500 71 68 65 59 56 50 50 47 76 73 70 63 60 53 53 50 83 79 76 68 65 58 58 54 89 85 81 73 69 62 62 58 91 87 83 75 71 63 63 59

300 66 66 60 55 52 46 43 40 73 73 67 60 57 51 48 44 79 79 72 66 62 55 52 48 86 86 79 71 68 60 56 53 89 88 81 73 69 62 58 54

200 65 62 57 51 46 41 38 38 74 71 65 59 53 47 43 43 82 78 71 65 58 51 48 48 89 85 78 70 63 56 52 52 – – – – – – – –

100 64 59 53 47 39 34 29 27 77 70 63 55 47 40 35 32 84 78 70 61 51 45 39 35 – – – – – – – – – – – – – – – –

50 63 54 50 41 36 27 25 20 80 68 60 51 43 34 32 26 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 60 l/s air flow rate: 120 l/s air flow rate: 180 l/s air flow rate: 240 l/s air flow rate: 300 l/s

160

500 68 67 64 59 55 53 52 51 72 71 68 62 59 55 54 53 78 77 74 67 63 60 59 58 84 84 80 72 68 65 65 65 89 89 85 77 73 69 69 69

300 63 62 59 55 52 49 46 45 67 66 64 58 55 52 49 48 75 75 71 65 61 58 54 54 81 81 78 70 67 63 59 59 87 87 83 76 72 68 64 64

200 58 56 50 48 42 40 40 68 65 62 56 53 47 44 44 76 73 69 63 59 53 50 50 84 80 77 69 66 58 55 55 – – – – – – – –

100 59 54 50 45 40 35 33 31 70 64 60 53 48 42 39 38 77 73 69 61 54 48 45 44 – – – – – – – – – – – – – – – –

50 54 50 46 37 33 29 25 25 69 64 58 48 42 37 32 32 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 100 l/s air flow rate: 200 l/s air flow rate: 300 l/s air flow rate: 400 l/s air flow rate: 450 l/s

200

500 70 64 61 55 52 52 55 55 75 68 65 59 55 55 59 59 83 76 72 65 61 61 65 65 90 82 78 72 67 66 71 70 93 85 81 73 71 70 74 73

300 67 62 56 50 48 45 48 48 74 68 62 55 52 51 53 52 84 78 71 64 61 57 60 60 92 84 78 71 67 63 67 66 95 87 81 72 68 66 69 68

200 62 57 55 47 44 42 42 42 71 65 62 53 50 48 47 47 83 76 71 62 58 55 54 54 90 83 79 69 65 62 61 60 – – – – – – – –

100 57 52 48 41 39 36 34 34 69 64 58 50 47 44 42 42 83 76 69 59 56 53 50 50 – – – – – – – – – – – – – – – –

50 51 45 41 36 32 32 28 28 63 56 51 44 39 39 34 34 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 150 l/s air flow rate: 300 l/s air flow rate: 450 l/s air flow rate: 600 l/s air flow rate: 750 l/s

250

500 69 66 59 53 50 54 53 52 71 67 61 56 53 56 55 54 78 75 68 61 58 61 60 59 87 83 76 68 64 68 68 68 94 90 82 74 70 74 74 74

300 63 61 55 50 47 46 48 47 66 63 57 51 48 47 51 48 75 72 65 59 55 55 59 55 84 80 73 67 65 64 62 61 91 87 80 72 70 69 72 68

200 59 57 52 46 44 41 44 44 63 60 55 49 46 44 46 46 72 69 63 57 55 54 54 53 82 79 72 64 63 63 62 61 – – – – – – – –

100 56 52 45 41 38 36 34 31 63 57 51 45 43 40 38 35 75 69 60 56 52 49 45 42 – – – – – – – – – – – – – – – –

50 52 48 40 38 34 30 28 24 61 56 47 45 40 38 33 28 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 250 l/s air flow rate: 500 l/s air flow rate: 750 l/s air flow rate: 1000 l/s air flow rate: 1200 l/s

315

500 68 65 59 53 50 50 53 50 74 71 65 58 55 55 58 55 82 78 71 64 60 60 54 60 89 85 77 69 68 67 69 65 92 88 80 72 71 70 72 68

300 62 59 54 49 46 45 49 43 69 66 60 54 51 51 54 48 78 74 68 61 57 57 61 54 85 81 74 66 64 64 66 59 89 85 78 70 68 68 70 62

200 60 55 50 45 43 40 43 40 70 64 58 52 49 48 49 46 79 72 66 59 58 57 56 52 86 79 72 65 63 62 64 58 – – – – – – – –

100 54 52 45 41 38 36 36 31 66 63 55 50 47 46 44 39 76 72 64 57 54 52 50 44 – – – – – – – – – – – – – – – –

50 49 49 43 38 34 32 30 24 64 64 56 49 45 42 40 32 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 400 l/s air flow rate: 800 l/s air flow rate: 1200 l/s air flow rate: 1600 l/s air flow rate: 1800 l/s

400

500 79 73 67 62 57 60 59 58 82 75 68 65 59 62 61 60 88 81 74 70 62 66 65 64 95 87 79 75 67 71 70 69 98 90 82 78 70 74 73 72

300 72 66 60 54 51 51 51 51 77 70 64 58 56 55 54 54 84 77 70 63 62 61 60 60 91 83 76 69 67 66 65 64 94 86 79 71 70 69 68 67

200 67 62 56 50 48 48 48 45 74 68 62 56 53 52 52 49 82 75 68 61 60 59 58 54 89 82 75 69 67 64 63 60 – – – – – – – –

100 61 56 49 44 42 39 39 34 72 66 58 53 49 47 46 40 83 76 67 60 58 55 53 47 – – – – – – – – – – – – – – – –

50 57 52 44 39 37 35 34 26 72 67 56 50 47 44 44 33 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 600 l/s air flow rate: 1200 l/s air flow rate: 1800 l/s air flow rate: 2400 l/s air flow rate: 3000 l/s

500

500 84 77 70 64 63 62 61 60 85 78 71 65 64 63 62 61 91 84 76 68 67 68 68 67 96 88 80 72 70 73 72 71 102 94 85 78 75 77 77 76

300 77 70 64 58 54 54 58 58 80 74 67 60 57 57 60 60 88 80 73 66 62 62 66 66 93 85 78 70 66 66 70 70 99 91 83 74 70 70 74 74

200 71 65 59 53 50 50 50 47 77 70 64 58 56 55 54 51 85 78 72 65 63 61 60 57 91 84 76 70 68 66 65 61 – – – – – – – –

100 63 58 53 47 46 44 42 37 72 66 60 55 53 51 49 43 82 75 70 63 60 57 55 50 – – – – – – – – – – – – – – – –

50 59 52 47 44 42 38 38 31 71 63 57 54 51 46 46 37 – – – – – – – – – – – – – – – – – – – – – – – –

air flow rate: 1000 l/s air flow rate: 2000 l/s air flow rate: 3000 l/s air flow rate: 4000 l/s air flow rate: 4500 l/s

630

500 88 80 73 69 66 64 63 62 90 83 75 71 68 67 65 64 96 88 80 76 72 72 70 68 103 95 86 82 77 77 76 73 107 98 90 85 81 81 80 76

300 82 75 69 65 62 61 58 55 84 77 70 67 63 62 61 56 92 84 77 73 69 68 68 61 100 91 83 79 75 75 74 66 105 96 88 83 79 79 79 70

200 78 72 65 62 59 55 55 49 80 74 67 64 60 57 57 50 89 82 75 71 67 63 63 56 98 90 82 78 74 70 70 62 – – – – – – – –

100 71 66 59 54 50 46 45 40 78 71 66 59 56 49 47 44 90 82 76 68 63 58 55 50 – – – – – – – – – – – – – – – –

50 66 58 53 48 43 40 39 30 77 68 62 57 51 45 48 36 – – – – – – – – – – – – – – – – – – – – – – – –

Page 16: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

562

85

dd

1

2

d3140

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round shutoff damper

DASLDimensions

DescriptionThe DASL shutoff damper with EPDM gaskets at both flange connections is designed for cladding with up to 50 mm thick insulation.The DASL shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw.All the DASL dampers of diameter 355 mm or greater have the damper closure pivot provided with extra bracing.All the DASL dampers of diameter 450 mm or greater are supplied with the KIT-DS-H damper mechanism control lever.Standard dampers are made from galvanized steel sheet.

Available materials - Product code examplesDASL-... - galvanized steel sheetDASL-K-... - 1.4301/304 stainless steel sheet

Ød nom (mm)

Ød1 nom (mm)

Ød2 nom (mm)

Ød3 nom (mm)

Weight

(kg)

80* – – – 0.40

100* – – – 0.45

125* – – – 0.55

140* – – 0.60

150* – – – 0.65

160* – – – 0.70

180* – – – 0.75

200* – – – 0.80

224* – – – 0.90

250* – – – 1.20

280* – – – 1.40

300* – – – 1.50

315* – – – 1.60

355** 330 295 263 2.70

400** 330 295 263 3.30

450** 370 337 293 4.50

500** 370 337 293 5.00

560** 490 457 413 6.30

600** 490 457 413 6.70

630** 490 457 413 7.20

For d1 < 355, the damper closure pivot is mounted on two short rods.

For d1 ≥ 355, the damper closure pivot is mounted a single long bar.

*with a press-formed damper closure** with a damper closure & pivot bracingIf the damper diameter is to be greater than 630 mm, order the DASQL multi-blade damper.

Product code exampleProduct code: DASL - aaa

typeØd1

Page 17: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

563

Raport – DARL‐DASL  

1 Stanowisko pomiarowe

1 – wentylator

2 – prostownica przepływu

3,8 – przewód

4 – pomiar prędkości przepływu

5,7 – pomiar ciśnienia

6 – przepustnica

Stopnie przy krzywych oznaczają poziom zamknięcia przepustnicy zgodnie z rysunkiem.

Q [m3/h] – przepływ obliczony ze zmierzonej prędkości przepływu (4) oraz pola przekroju przewodu

Δp [Pa] – różnica pomiędzy pomiarami ciśnienia przed (5) i za (7) przepustnicą

0° 30° 60° 90°

`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°

`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°

`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280Δp

[Pa

]Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°

`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°`

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-1000°

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-125

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-200 60° 30°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-250

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280 2560

Δp [

Pa]

Q [m3/h]

DASL-315

30°60°

10

20

40

80

160

320

640

10 20 40 80 160 320 640 1280

Δp [

Pa]

Q [m3/h]

DASL-160

30°60°

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round shutoff damper

DASLTechnical specificationsNumbers shown on the diagrams represent the damper blade position according to pictures below:

Q [m3/h] - air flow calculated form air velocity and a duct cross-section

Dp [Pa] - pressure loss measured before and after the damper

DASL 100

Q [m3/h]

Dp

[Pa

]

DASL 125

Q [m3/h]

Dp

[Pa

]

DASL 160

Q [m3/h]

Dp

[Pa

]

DASL 200

Q [m3/h]

Dp

[Pa

]

DASL 250

Q [m3/h]

Dp

[Pa

]

DASL 315

Q [m3/h]

Dp

[Pa

]

Page 18: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

564

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Reinforced round shutoff damper

DASL-B / DAS-BDimensions

DescriptionThe DASL-B shutoff damper with EPDM gaskets is designed for cladding with up to 50 mm thick insulation. The damper closure angle range is 0˚ to 90˚ and can be read on the handle dial. The differences in design regarding a standard DASL are: additional folding in the housing, reinforcements on the damper blade, thicker hinge rod (12x12mm), brass bearings. Used materials provide temperature resistance up to 110 C̊ (200 C̊ for DAS-B without gasket).

Available materials - Product code examplesDASL-B-... - galvanized steel sheetDASL-B-K-... - 1.4404 / 316L stainless steel sheet

Ød(mm)

L(mm)

Weight

(kg)

100 200 1.00

125 200 1.08

140 200 1.14

160 200 1.24

200 200 1.40

224 200 1.49

250 200 1.61

280 200 1.77

315 265 2.21

355 265 2.47

400* 265 4.58

450* 305 5.85

500* 400 7.78

560* 400 8.76

630* 500 11.62

710* 600 15.39

800* 600 17.50

900* 600 19.96

1000* 600 22.49

*bumpers added

Product code exampleProduct code: DASL-B - aaa

typeØd

Page 19: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

565

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Shutoff damper with actuator mounting

DASL-CV

The DASL-CV shutoff damper with EPDM gaskets at both flange connections is designed for cladding with up to 50 mm thick insulation.The DASL-CV shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw.The DASL-CV shutoff damper can be easily adapted for mounting Belimo power actuators. The power actuator must be compatible with the 8x8 mm square bar. The product has safe edges.

Available materials - Product code examplesDASL-CV-... - galvanized steel sheet

DASL-CV-K-... - 1.4301/304 stainless steel sheet

DASL-CV-K-...-316L - 1.4404/316L stainless steel sheetDASL-CV-A-... - aluminium sheet*

DASL-CV-CU-... - copper sheet

*KIT-DS.-CV-K damper mechanism

Description Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.45

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.20

280 1.40

300 1.50

315 1.60

355 2.00

400 2.60

Product code exampleProduct code: DASL-CV - aaa

typeØd1

Page 20: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

566

85

dd

1

2

d3100

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round damper for Lamella Mat cladding

DASDimensions

DescriptionThe DAS dampers are designed for cladding with up to 50 mm thick insulation.The DAS damper is a good choice when the ductwork closure does not have to be fully airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw. The product has safe edges.All the DAS dampers of diameter 355 mm or greater have the damper closure pivot provided with extra bracing.All the DAS dampers of diameter 450 mm or greater are supplied with the KIT-DS-H damper mechanism control lever.Standard dampers are made from galvanized steel sheet.

Available materials — Product code examplesDAS-... — galvanized steel sheetDAS-K-... — 1.4301/304 stainless steel sheet

Ød nom (mm)

Ød1 nom (mm)

Ød2 nom (mm)

Ød3 nom (mm)

Weight

(kg)

80* – – – 0.40

100* – – – 0.45

125* – – – 0.55

140* – – 0.60

150* – – – 0.65

160* – – – 0.70

180* – – – 0.75

200* – – – 0.80

224* – – – 0.90

250* – – – 1.20

280* – – – 1.40

300* – – – 1.50

315* – – – 1.60

355** 330 295 263 2.70

400** 330 295 263 3.30

450** 370 337 293 4.50

500** 370 337 293 5.00

560** 490 457 413 6.30

600** 490 457 413 6.70

630** 490 457 413 7.20

For d1 < 355, the damper closure pivot is mounted on two short rods.

For d1 ≥ 355, the damper closure pivot is mounted on a single long bar.

*with a press-formed damper closure** with a damper closure & pivot bracingIf the damper diameter is to be greater than 630 mm, order the DASQ multi-blade damper.

Product code exampleProduct code: DAS - aaa

typeØd1

Page 21: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

567

50

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

SPIRAL duct shutoff damper

DAS-CV

The DAS-CV dampers are designed for cladding with up to 50 mm thick insulation.The DAS-CV shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw.The DAS-CV shutoff damper can be easily adapted for mounting Belimo power actuators. The power actuator must be compatible with the 8x8 mm square bar.The product has safe edges.

Available materials - Product code examplesDAS-CV-... - galvanized steel sheetDAS-CV-K-... - 1.4301/304 stainless steel sheetDAS-CV-K-...-316L - 1.4404/316L stainless steel sheetDAS-CV-A-... - aluminum sheet*

DAS-CV-CU-... - copper sheet

*KIT-DS-CV-K damper mechanism

Description Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

355 2.00

400 2.60

Product code exampleProduct code: DAS-CV - aaa

typeØd1

Page 22: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

568

30

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round ventilation damper w/o gaskets

DAS-PVCDimensions

DescriptionThe DAS-PVC dampers are designed for cladding with up to 30 mm thick insulation.The DAS-PVC shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw. The product has safe edges.

Available materials — Product code examplesDAS-PVC-... — galvanized steel sheet

DAS-PVC-K-... — 1.4301/304 stainless steel sheet

DAS-PVC-K-...-316L — 1.4404/316L stainless steel sheetDAS-PVC-A-... — aluminium sheetDAS-PVC-CU-... — copper sheet

Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50Product code exampleProduct code: DAS-PVC - aaa

typeØd1

Page 23: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

569

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Hand-operated damper

DASH

The DASH dampers are among the most budget-efficient solutions for air flow control in round ductwork systems. The safe edges at the damper ends protect against accidental injury during the installation process. The wing nut can be tightened to set the control lever in place at a specific opening angle. The dial of the control handle shows the damper closure / opening ratio. This damper is designed for air ducts in diameters of 80 to 315 mm and made from galvanized steel sheet.

Available materials - Product code examplesDASH-... - galvanized steel sheetDASH-K-... - 1.4301/304 stainless steel sheet

Description Ød1 nom (mm)

Weight

(kg)

80 0.4

100 0.4

125 0.5

140 0.6

150 0.6

160 0.7

180 0.7

200 0.8

224 0.9

250 1.2

280 1.4

300 1.5

315 1.6Product code exampleProduct code: DASH - aaa

typeØd1

Page 24: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

570

85

dd

1

2

d3140

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Airtight shutoff dampers

DATL/DATDimensions

DescriptionThe DATL/DAT dampers are designed for cladding with up to 50 mm thick insulation.The DATL/DAT dampers are a good choice when the ductwork closure must be airtight. The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw.

DAT — airtight shutoff damperDATL — airtight shutoff damper with gaskets at

flanged endsAll DATL/DAT dampers of diameter 355 mm or greater have the damper closure pivot provided with extra bracing.All DATL/DAT dampers of diameter 450 mm or greater are supplied with the KIT-DS-H damper mechanism control lever.Standard dampers are made from galvanized steel sheet.

Available materials — Product code examplesDATL-... — galvanized steel sheet

DATL/DAT-... — 1.4301/304 stainless steel sheet

Ød nom (mm)

Ød1 nom (mm)

Ød2 nom (mm)

Ød3 nom (mm)

Weight

(kg)

80 – – – 0.40

100 – – – 0.45

125 – – – 0.55

140 – – 0.60

150 – – – 0.65

160 – – – 0.70

180 – – – 0.75

200 – – – 0.80

224 – – – 0.90

250 – – – 1.20

280 – – – 1.40

300 – – – 1.50

315 – – – 1.60

355* 330 295 295 2.70

400* 330 295 295 3.30

450* 370 337 293 4.50

500* 370 337 293 5.00

560* 490 457 413 6.30

600* 490 457 413 6.70

630* 490 457 413 7.20

For d1 < 355, the damper closure pivot is mounted on two short rods.

For d1 ≥ 355, the damper closure pivot is mounted on a single long bar.

* with a damper closure & pivot bracing

Product code exampleProduct code: DATL - aaa

typeØd1

Page 25: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

571

Przeciek powietrza q v [l/(s*m2)]

Ciśn

ieni

e w

kan

ale

p s

[Pa]

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Airtight shutoff dampers

DATL/DATAir tightness testingBased on the tests and the calculation results shown in Chart 1, the DATL-315 damper was found to meet air tightness class 4. The EN 1751 test method was applied.

Chart 1. Air flow leaks through a closed DATL-315 damper. Vacuum deformation:

The damper closure deformation test was done at 2,000 Pa. The test duration was 120 seconds. The DATL-315 damper closure deflection was 2 cm. After the test, when the damper was opened and closed again, the damper closure returned to the original, non-deflected shape.

Overpressure deformation:

Page 26: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

572

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Round smooth-flow perforated damper

DAP-CV

The DAP-CV dampers are designed for cladding with up to 50 mm thick insulation.The DAP-CV shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The perforated closure provides an even air flow without turbulence.The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw.The DAP-CV shutoff damper can be easily adapted for mounting Belimo power actuators. The power actuator must be compatible with the 8x8 mm square bar.The product has safe edges.Closing the damper closure allows 35% of the rated air flow to pass.

Available materials — Product code examplesDAP-CV-... — galvanized steel sheet

DAP-CV-K-... — 1.4301/304 stainless steel sheet

DAP-CV-K-...-316L — 1.4404/316L stainless steel sheetDAP-CV-A-... — aluminium sheet*

DAS-PVC-CU-... — copper sheet

*KIT-DS-CV-K damper mechanism

Description Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.46

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.10

280 1.30

300 1.45

315 1.50

355 2.00

400 2.60

Product code exampleProduct code: DAP-CV - aaa

typeØd1

Page 27: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

573

50

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Regulating damper with perforated closure

DAPL-CVDimensions

DescriptionThe DAPL-CV damper with EPDM gaskets at both flange connections is designed for cladding with up to 50 mm thick insulation. The DAPL-CV shutoff damper is a good choice when the ductwork closure does not have to be fully airtight. The perforated closure provides an even air flow without turbulence.The damper closure position can be read on the 0° to 90° dial of the control handle. The damper closure opening ratio can be fixed with a screw. The DAPL-CV shutoff damper can be easily adapted for mounting Belimo power actuators. The power actuator must be compatible with the 8x8 mm square bar. The product has safe edges.Closing the damper closure allows 35% of the rated air flow to pass.

Available materials — Product code examplesDAPL-CV-... — galvanized steel sheet

DAPL-CV-K-... — 1.4301/304 stainless steel sheet

DAPL-CV-K-...-316L — 1.4404/316L stainless steel sheetDAPL-CV-A-... — aluminium sheet*DAS-PVC-CU-... — copper sheet

*KIT-DS.-CV-K damper mechanism

Ød1 nom (mm)

Weight

(kg)

80 0.40

100 0.45

125 0.55

140 0.60

150 0.65

160 0.70

180 0.75

200 0.80

224 0.90

250 1.20

280 1.40

300 1.50

315 1.60

355 2.00

400 2.60

Product code exampleProduct code: DATL-CV - aaa

typeØd1

Page 28: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

574

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Round non-return damper - inside duct

DAOSL-IN

The DAOSL-IN dampers feature a split flap closure and are designed as non-return dampers which allows a single air flow direction only.Both closure flaps are made of light-weight aluminium sheet and hinged on a steel bar with springs which keep the flaps closed when there is no air flow. This damper is often installed upstream of an air intake or an air exhaust unit to prevent the air backflow. The DAOSL-IN dampers are designed for inline duct installation.This saves time and space, and requires fewer installation accessories.

Available materials — Product code examplesDAOSL-IN-... — galvanized steel sheet

DAOSL-K-IN-... — 1.4301/304 stainless steel sheet

DAOSL-A-IN-... — aluminium sheet

Description Ød1 nom (mm)

L(mm)

Weight

(kg)

80 130 0.15

100 130 0.2

125 130 0.25

150 130 0.3

160 130 0.32

200 130 0.4

250 190 0.7

Installation method

Caution!When pressing the male ends into the ducts, hold the damp-er around its housing.

Product code exampleProduct code: DAOSL-IN - aaa

typeØd1

Page 29: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

575

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Round non-return damper - airtightness class D

DAOSL

The DAOSL dampers are designed for ventilation ductwork systems which require air tightness class D according to EN 12237 requirements. These dampers feature a split flap closure and are designed as non-return dampers which allows a single air flow direction only. The damper closure has approximately air tightness class 2 as per EN 1751:2002, without full class compliance. Both closure flaps are made of light-weight aluminium sheet and hinged on a steel bar with springs which keep the flaps closed when there is no air flow. This damper is often installed upstream of an air intake or an air exhaust unit to prevent the air backflow.

Available materials - Product code examplesDAOSL-... - galvanized steel sheetDAOSL-K-... - 1.4301/304 stainless steel sheetDAOSL-A-... - aluminium sheet

Description Ød1 nom (mm)

L(mm)

Weight

(kg)

80 130 0.2

100 130 0.2

125 130 0.3

150 130 0.4

160 130 0.4

180 130 0.4

200 130 0.5

250 190 0.8

300 190 0.9

315 190 1.0

355 270 1.5

400 270 1.7

450 270 1.9

500 270 2.1

Diameter sizes up to Ød 560 mm are available on request.Product code exampleProduct code: DAOSL - aaa

typeØd1

Page 30: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

576

0

25

50

75

100

125

150

175

200

225

250

275

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250

Spad

ek c

iśni

enia

[Pa]

Wydatek powietrza [m^3/h]

100

125

160

200

250

315

0

25

50

75

100

125

150

175

200

225

250

275

300

325

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250Sp

adek

ciś

nien

ia [P

a]Wydatek powietrza [m^3/h]

100

125

160

200

250

315

50

100

200

400

800

1600

1 2 4 8 16 32 64 128 256 512 1024 2048

Klasa 4

Klasa 3

Klasa 2

Klasa 1

DAOSL

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round non-return damper - airtightness class D

DAOSLTechnical specificationsPressure loss chart for DAOSL Pressure loss chart for DAOSL-K

Ø100

Ø125

Ø160Ø200

Ø250

Ø315

Pres

sure

loss

(Pa

)

Air output (m3/h)Pr

essu

re lo

ss (

Pa)

Air output (m3/h)

Ø100

Ø125

Ø160

Ø200Ø250

Ø315

Air tightness chart for DAOSL

Clas

s IV

Clas

s III

Clas

s II

DAO

SLCl

ass

I

Pres

sure

(Pa

)

Air leak rate (l/s*m2)

Page 31: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

577

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round non-return damper

DAOSDimensions

The DAOS dampers feature a split flap closure and allow the air flow to pass in one direction only. The aluminium closure flaps are pressed against a foam seal when closed to reduce the operating noise in the ductwork. The split flap closure is held closed with a spring gear, which makes it also possible to use the damper in vertical installations. A version intended for a full-male insertion into the ductwork ends is available on special request.

Available materials - Product code examplesDAOS-... - galvanized steel sheetDAOS-K-... - 1.4301/304 stainless steel sheetDAOS-A-... - aluminium sheet

Description Ød1 nom (mm)

L(mm)

Weight

(kg)

80 81 0.1

100 81 0.1

125 81 0.2

150 81 0.2

160 81 0.2

180 81 0.3

200 81 0.3

250 190 0.8

300 190 0.9

315 190 1.0

355 270 1.5

400 270 1.7

450 270 1.9

500 270 2.1

Diameter sizes up to Ød 560 mm are available on request.

Product code exampleProduct code: DAOS - aaa

typeØd1

Page 32: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

578

0

25

50

75

100

125

150

175

200

225

250

275

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250

Spad

ek c

iśni

enia

[Pa]

Wydatek powietrza [m^3/h]

100

125

160

200

250

315

0

25

50

75

100

125

150

175

200

225

250

275

300

325

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250Sp

adek

ciś

nien

ia [P

a]Wydatek powietrza [m^3/h]

100

125

160

200

250

315

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round non-return damper

DAOSTechnical specificationsPressure loss chart for DAOS Pressure loss chart for DAOS-K

Ø100

Ø125

Ø160Ø200

Ø250

Ø315

Pres

sure

loss

(Pa

)

Air output (m3/h)Pr

essu

re lo

ss (

Pa)

Air output (m3/h)

Ø100

Ø125

Ø160

Ø200Ø250

Ø315

Page 33: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

579

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Reinforced backdraft damper

DAOSL-B / DAOS-BDimensions

The DAOSL-B / DAOS-B ventilation damper is a new version of DAOS (L) backdraft dampers. In addition, it is reinforced with a reinforcing rods, making it possible to manufacture large diameters up to Ø630mm, while maintaining the rigidity of the construction and correct operation of the blades. The DAOSL-B damper with seals is used in installations that meet airtightness class D according to DIN EN 12237. The DAOS-B-FLS version with flanges is suitable for mounting on axial fans.

Available materials — Product code examplesDAOS-B-... - galvanized steel sheetDAOSL-B-… - galvanized steel sheet, with seals

DAOS-B-K-... - 1.4301/304 stainless steel sheetDAOSL-B-K-... - 1.4301/304 stainless steel sheet, with seals

DAOS-B-A-... - aluminium sheet (stainless steel rod)DAOSL-B-A-... - aluminium sheet (stainless steel rod),

with sealsDAOSLI-B-… - galvanized steel sheet, insulated, with seals DAOS-B-FLS-… - galvanized steel sheet, with flanges

Description Ød(mm)

L(mm)

355 285

400 285

450 285

500 285

560 285

630 285

Product code exampleProduct code: DAOSL-B - aaa

typeØd

Page 34: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

580

L

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Duct gate damper for air ventilation and dust extraction systems

GKL/GK

The hand-operated duct gate damper is designed for air ventilation and dust extraction systems which carry particulates of sawdust, EPS debris, or other light air fractions of solids. An advantage is the sliding gate which opens the passage to full clearance, without any obstruction by closure edges or pivot rods. The gate damper is a rigid structure made of 1-mm thick galvanized steel sheet, to which ILS flanges (GK gate damper) or ILSL flanges with gaskets (GKL gate damper) are attached. Gate dampers can be requested with FLS steel flanges or upturns for use with quick clamps.

GK — plain end flange gate damperGSL — gate damper with EPDM gaskets at the flanges, air

tightness class D according to EN 12237

Available materials — Product code examplesGKL-... — galvanized steel sheet

GKL-K-... — 1.4301/304 stainless steel sheet

GKL-K-...-316L — 1.4404/316L stainless steel sheetGKL-A-... — aluminium sheet

Description

Ød1 (mm)

A(mm)

B(mm)

C(mm)

D(mm)

Weight

(kg)

100 184 210 320 455 3.15

125 209 290 400 555 4.35

150 244 300 405 590 5.05

160 244 300 405 600 5.15

200 315 370 515 750 7.05

400 484 675 915 1355 18.20

Product code exampleProduct code: GKL - aaa

typeØd1

Page 35: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

581

L

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round gate damper with pneumatic actuator

GKML/GKMDimensions

Description

Ød1 (mm)

A(mm)

B(mm)

C(mm)

D(mm)

Weight

(kg)

100 184 210 320 455 3.15

125 209 290 400 555 4.35

150 244 300 405 590 5.05

160 244 300 405 600 5.15

200 315 370 515 750 7.05

400 484 675 915 1355 18.20

Product code exampleProduct code: GKML - aaa

typeØd1

The GKML/GKM round gate dampers with pneumatic actuators are designed for air ventilation and dust extraction systems.The design of the gate damper makes it easier to clean the ductwork as there are no elements within the clear opening. The gate damper provides a tight seal when closed and enables remote control of the opening ratio which can be set in infinitely variable steps. The solenoid valve of the pneumatic actuator is available for 230 V AC, 24 V AC or 24 V DC power supply - to be specified when ordering.

Recommended installation options: - GKML/GKM sized ≤ 200 mm in diameter: use 1 actuator - GKML/GKM sized > 200 mm in diameter: use 2 actuatorsGKM — gate damper with actuator and bare flangesGKML — gate damper with actuator and EPDM gaskets at

the flanges, air tightness class D acc. to EN12237

Technical parametersAir cylinder: control pressure: 0,6 MPa (6 bar) max. ambient temp: -20oC to 80oC operating medium: treated airSolenoid valve: control pressure: max 7bar ambient temperature: max 50˚C supply voltage: 230V Ingress protection: IP65

Available materials — Product code examplesGKML-... - galvanized steel sheetGKML-K-... - 1.4301/304 stainless steel sheetGKML-K-...-316L - 1.4404/316L stainless steel sheetGKML-A-... - aluminium sheet

Page 36: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

582

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

T-piece damper for GCHX (ground-coupled heat exchangers)

DATVTL

The DATVTL T-piece damper is an air distribution units which can replace two separate ventilation dampers. The easy adjustment control can divert the air flow to either of the two 90°-spaced legs, with the other leg automatically closed. The damper can also be used for supplying air via either of the two legs from an external air supply valve, a ground-coupled heat exchanger, or a fireplace hot air hood. All damper sizes come with the KIT-DS-H damper mechanism control handle for easier operation. The ends of the damper are provided with EPDM gaskets to ensure air tightness class D.

Available materials — Product code examplesDATVTL-... — galvanized steel sheet

Description Ød1 nom (mm)

Ød3 nom (mm)

L(mm)

H(mm)

Weight

(kg)

100 100 151 65 0.8

125 125 184 83 1.1

160 160 229 105 1.7

200 200 281 125 2.2

250 250 307 150 3.4

315 315 390 182 4.9

Air flow directions

Product code exampleProduct code: DATVTL - aaa

typeØd1

Page 37: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

583

100

125

160

200

250

315

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

T-piece damper for GCHX (ground-coupled heat exchangers)

DATVTLTechnical specifications

(Pa) 300

200

100

50

10

5

Dimension (mm)

Pre

ssur

e lo

ss D

pt

1

50 100 500 1000 5000 (m3/h)

10 50 100 500 1000 2000 (I/s)

Flow rate

Page 38: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

584

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

T-piece double damper for SPIRAL ducts

DATASL

The DATASL T-piece double regulating dampers for round ductwork systems can replace two standard DASL dampers. The alternate-opening link which couples both closures of the damper helps close one closure and at the same time open the other closure using a single damper mechanism. This design can save approximately 20 to 30% of installation space and helps avoid coupling two separate dampers with T-pieces and MSF couplings. The double EDPM gasket at each flange provides the best air tightness class D as per EN 12237:2005.

Available materials — Product code examplesDATASL-... — galvanized steel sheet

Description

Ød1 nom (mm)

Ød3 nom (mm)

L(mm)

H(mm)

Weight

(kg)

100 100 280 65 1.1

125 125 345 83 1.5

160 160 385 105 2.0

200 200 425 125 2.8

250 250 520 150 4.1

315 315 585 182 5.9

400 400 645 225 8.3

Product code exampleProduct code: DATASL - aaa - bbb

typeØd1Ød3

Page 39: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

585

[Pa]

300

100

200

50

10

5

110 50 100 500 1000 2000

50 100 500 1000 5000

100

125

160

200

250

315

400

[l/s]

[m3/h]

[Pa]

300

100

200

50

10

5

110 50 100 500 1000 2000

50 100 500 1000 5000

100

125

160

200

250

315

400

[l/s]

[m3/h]

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Bypass dampers

DATASLTechnical specifications

Dimension (mm)

Pre

ssur

e lo

ss D

pt

Flow rate

Page 40: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

586

90 90

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-S-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

BC

AH

1 2 3

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

A

C

H

B

1 3 42

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

A

C

H

B

1 3 42

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Regulating dampers with actuator mounting

DASML / DASM

Description

Product code exampleProduct code: DASML - aaa - bbb

typeØd1orientation of the actuator mounting

Dampers with actuator mounting are available in diameters of Ø80 to Ø630 mm, including intermediate sizes. The actuator mounting is designed to enable cladding with up to 50 mm thick insulation. The standard version permits a lengthwise actuator orientation

For fast assembly of actuators, we recommend specially designed DA-SUP-S and DA-SUP-M mounting plates.

Actuators matching DA-SUP-S mountig plate

Actuators matching DA-SUP-Mmountig plate

Alnor DM-LM-06 Alnor DM-LM-06

Belimo CM Alnor DM-LM-08

Belimo LM Belimo CM

Belimo NM

UWAGA! Podstawki DA-SUP występują tylko w wersji wzdłużnej!

The DASML/DASM dampers are a good choice when the ductwork closure does not have to be fully airtight. The opening angle can be fixed with a mechanical limiter installed directly on the actuator.For outdoor installations, the actuator must be protected from UV light and weather.All dampers can be provided with various types of actuators on request.

DASM — shutoff damper with actuator mountingDASML — airtight shutoff damper with gaskets at flanges and actuator mounting

Available materials — Product code examplesDASML-...-... — galvanized steel sheet

Ød1 nom (mm)

Weight

(kg)Ød1 nom (mm)

Weight

(kg)

80 0.6 355 2.2

100 0.7 400 2.7

125 0.8 450 3.7

160 0.9 500 4.3

200 1.1 560 5.0

250 1.4 630 5.8

315 1.7

Standard: lengthwise actuator orientation

P — crosswise actuator orientation

DA-SUP-S mounting plate DA-SUP-M mounting plate

DA-SUP-S mounting plate DA-SUP-M mounting plate

A (mm)

B (mm)

C (mm)

A (mm)

B (mm)

C (mm)

94 135 182 104 145 190

DA-SUP-S/M mounting plate is mounted lengthwise only!

Page 41: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

587

90 90

155

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-S-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

BC

AH

1 2 3

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

AC

H

B

1 3 42

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

AC

HB

1 3 42

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Airtight shutoff dampers with actuator mounting

DATML/DATMDimensions

Description

Product code exampleProduct code: DATML - aaa - bbb

typeØd1orientation of the actuator mounting

Dampers with actuator mounting are available in diameters of Ø80 to Ø630 mm, including intermediate sizes. The actuator mounting is designed to enable cladding with up to 50 mm thick insulation. The standard version permits a lengthwise actuator orientation

For fast assembly of actuators, we recommend specially designed DA-SUP-S and DA-SUP-M mounting plates.

Actuators matching DA-SUP-S mountig plate

Actuators matching DA-SUP-Mmountig plat

Alnor DM-LM-06 Alnor DM-LM-06

Belimo CM Alnor DM-LM-08

Belimo LM Belimo CM

Belimo NM

NOTE! DA-SUP mounting plates are available only in lengthwise version!The standard version permits a lengthwise actuator orientation.The DATML/DATM dampers are a good choice when the ductwork closure must be airtight. The opening angle can be fixed with a mechanical limiter installed directly on the actuator. The damper closure can be deflected by up to 2 cm when the air pressure exceeds 2,000 Pa. For outdoor installations, the actuator must be protected from UV light and weather.All dampers can be provided with various types of actuators on request.

DATM — airtight shutoff damper with actuator mountingDATML — airtight shutoff damper with gaskets at flanges and actuator mounting

Available materials — Product code examplesDATML-... — galvanized steel sheet

Ød1 nom (mm)

Weight

(kg)Ød1 nom (mm)

Weight

(kg)

80 0.6 355 2.3

100 0.7 400 2.8

125 0.8 450 3.8

160 0.9 500 4.5

200 1.2 560 5.2

250 1.5 630 6.0

315 1.8

Standard: lengthwiseactuator orientation

P — crosswise actuator orientation

DA-SUP-S mounting plate DA-SUP-M mounting plate

DA-SUP-S mounting plate DA-SUP-M mounting plate

A [mm]

B [mm]

C [mm]

A [mm]

B [mm]

C [mm]

94 135 182 104 145 190

DA-SUP-S/M mounting plate is mounted lengthwise only!

Page 42: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

588

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-S-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

BC

AH

1 2 3

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

A

C

H

B

1 3 42

mateusz.kazimierukZaprojektowany przez Sprawdzony przez Zatwierdzony przez Data

Materiał

Ogólny

Skala

1 : 1,5

A3

Nazwa części

DA-SUP-M-marketingFormatMasa

DataData

2016-11-09

Niedotyczy

A

C

H

B

1 3 42

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Bypass dampers with actuator mounting

DATVTML

Description Ød1 nom (mm)

Ød3 nom (mm)

L(mm)

H(mm)

Weight

(kg)

100 100 150 65 0.8

125 125 184 83 1.1

160 160 229 105 1.7

200 200 281 125 2.2

250 250 307 150 3.4

315 315 390 182 4.9

Product code exampleProduct code: DATVTML - aaa - bbb

typeØd1type of actuator

The bypass dampers can replace a set of two standard dampers with a T-piece and couplings, which makes the entire assembly 20 to 30% shorter.

The DATVTML damper has a motor operator.

For fast assembly of actuators, we recommend specially designed DA-SUP-S and DA-SUP-M mounting plates.

Actuators matching DA-SUP-S mountig plate

Actuators matching DA-SUP-Mmountig plate

Alnor DM-LM-06 Alnor DM-LM-06

Belimo CM Alnor DM-LM-08

Belimo LM Belimo CM

Belimo NM

NOTE! DA-SUP mounting plates are available only in lengthwise version!

Available materials — Product code examplesDATVTML-...-... — galvanized steel sheet

Air flow directions

DA-SUP-S mounting plate DA-SUP-M mounting plate

DA-SUP-S mouting plate DA-SUP-M mouting plate

A [mm]

B [mm]

C [mm]

A [mm]

B [mm]

C [mm]

94 135 182 104 145 190

DA-SUP-S/M mounting plate is mounted lengthwise only!

Page 43: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

589

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Iris damper

GBLDimensions

The GBL iris dampers are essential for smooth control of the duct air pressure. The lever and the iris blade mechanism allows changing the clear opening diameter in infinitely variable steps. The iris-type closure allows choking the air flow without turbulence or in-duct noise. The GBL iris damper can be installed both in air supply and air exhaust ducts.This product features two output ports as an interface for an air flow meter.The GBL can be opened to the full clear diameter for easier cleaning of the ductwork. The iris dampers, however, cannot be sealed shut (the maximum closing ratio is ca. 25% of the nominal clear diameter).

Available materials — Product code examplesGBL-... — galvanized steel sheet

Description

Technical specifications

Ød1 nom (mm)

ØD (mm)

L(mm)

A(mm)

B(mm)

Weight

(kg)

80 125 120 35 22 0.5

100 165 110 30 32 0.5

125 188 110 30 32 0.7

150 230 110 30 40 1.3

160 230 110 30 35 0.9

200 285 110 30 42 1.4

250 335 135 40 42 2.1

315 410 135 40 47 3.5

400 525 150 50 62 6.4

500 655 150 50 77 9.6

630 815 150 50 92 15.6

800 1015 285 100 107 25.0

k

Item 1 2 3 4 5 6 7 8

GBL 80 6.1 4.1 3.2 2.3 1.4 0.9 0.6 –

GBL 100 10.4 7.5 6.0 4.5 3.4 2.5 1.7 0.9

GBL 125 13.8 8.8 6.5 4.7 3.5 2.7 1.5 –

GBL 150 24.1 16.5 13.4 11.0 8.9 6.9 5.2 3.7

GBL 160 22.1 14.8 12.5 10.7 8.5 6.8 4.9 3.5

GBL 200 44.2 30.9 23.2 18.2 14.0 11.0 8.4 5.0

GBL 250 64.4 45.6 38.7 30.7 24.1 18.4 12.8 8.9

GBL 315 118.0 70.0 58.7 45.1 37.0 30.0 21.8 15.8

GBL 400 131.0 102.0 88.3 67.3 52.7 38.5 28.4 15.5

GBL 500 230.0 177.0 146.0 112.0 88.5 66.6 48.0 30.0

GBL 630 451.0 297.0 238.0 169.0 127.0 91.6 62.8 35.1

GBL 800 489.0 402.0 344.0 267.0 217.0 170.0 122.0 73.7

K-value for various damper settingsProduct code exampleProduct code: GBL - aaa

typeØd1

Page 44: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

590

10,8 14,4 18 36 72 108 146 252

704030201054310

20

304050

100

200

300

5007 6 5 4 3

2

1

21,6 25,2 36 72 144 216 360 504

10

20

304050

100

200

300

500

10040 6030201076 140

108

8 7 6 5 4 3

2

1

36 72 144 216 360 720

10

20

304050

100

200

300

500

60 10040302010 200

108

7 6 5 4 3 2

1

54 108 720144 1080

10

20

304050

100

200

300

500

60 10040302015 300

72

1

3

2

216

45678

200

360

54 72 144 216 360 720

10

20

304050

100

200

300

500

60 10040302015 300

108

1

8 7 6 5 3

200

4

2

1080 108 144 252 360 720 1800

10

20

304050

100

200

300

500

100 20070504030 500

180

1

8 7 6 53

300

4

2

1080

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Technical specifications

Iris damper

GBL

GBL 80

(l/s)

(m3/h)

Item k

1 6.1

2 4.1

3 3.2

4 2.3

5 1.4

6 0.9

7 0.6

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 100

(l/s)

(m3/h)

Item k

1 10.4

2 7.5

3 6.0

4 4.5

5 3.4

6 2.5

7 1.7

8 0.9

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 125

(l/s)

(m3/h)

Item k

1 13.8

2 8.8

3 6.5

4 4.7

5 3.5

6 2.7

7 1.5

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 150

(l/s)

(m3/h)

Item k

1 24.1

2 16.5

3 13.4

4 11.0

5 8.9

6 6.9

7 5.2

8 3.7

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 160

(l/s)

(m3/h)

Item k

1 22.1

2 14.8

3 12.5

4 10.7

5 8.5

6 6.8

7 4.9

8 3.5

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 200

(l/s)

(m3/h)

Item k

1 44.2

2 30.9

3 23.2

4 18.2

5 14.0

6 11.0

7 8.4

8 5.0

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

Page 45: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

591

180 216 720 1080 2520

10

20

304050

100

200

300

500

300 4002001006050 700

360

1

8 7 6 5

3

4

2

1440 288 720 36001080 5400

10

20

304050

100

200

300

500

500 100030020010080 1500

360

1

3

2

1800

45678

360 1080 3600 9000

10

20

304050

100

200

300

500

1000500300200100 2500

720

1

2

1800

345678

720 1800 7200 14400

10

20

304050

100

200

300

500

20001000500300200 4000

1080

1

2

3600

345678

1080 1800 7200 21600

10

20

304050

100

200

300

500

20001000500300 6000

1

2

3600

345678

1800 3600 18000 36000

10

20

304050

100

200

300

500

500020001000500 10000

1

2

7200

345678

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Iris damper

GBLTechnical specificationsGBL 250

(l/s)

(m3/h)

Item k

1 64.4

2 45.6

3 38.7

4 30.7

5 24.1

6 18.4

7 12.8

8 8.9

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 315

(l/s)

(m3/h)

Item k

1 118.0

2 70.0

3 58.7

4 45.1

5 37.0

6 30.0

7 21.8

8 15.8

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 400

(l/s)

(m3/h)

Item k

1 131.0

2 102.0

3 88.3

4 67.3

5 52.7

6 38.5

7 28.4

8 15.5

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 500

(l/s)

(m3/h)

Item k

1 230.0

2 177.0

3 146.0

4 112.0

5 88.5

6 66.6

7 48.0

8 30.0

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 630

(l/s)

(m3/h)

Item k

1 451.0

2 297.0

3 238.0

4 169.0

5 127.0

6 91.6

7 62.8

8 35.1

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

GBL 800

(l/s)

(m3/h)

Item k

1 489.0

2 402.0

3 344.0

4 267.0

5 217.0

6 170.0

7 122.0

8 73.7

Item

Pres

sure

loss

∆p

m (P

a)

Air flow rate qv

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

qv = k√∆pm (l/s)

Page 46: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

592

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Iris damper

GBLM

The GBLM iris dampers can be provided with actuators.The GBLM iris dampers are used for smooth control of the duct air pressure. The lever and the iris blade mechanism allow changing the clear opening diameter in infinitely variable steps. The iris-type closure allows choking the air flow without turbulence or in-duct noise.The GBLM iris damper can be installed both in air supply and air exhaust ducts. It also features two output ports as an interface for an air flow meter. The full-clear opening of the iris damper helps with cleaning internal surfaces of the ductwork.

Compatible actuators:CM24 or CM230 — open/close control

Available materials — Product code examplesGBLM-... — galvanized steel sheet

Description Ød1 nom (mm)

ØD (mm)

L(mm)

A(mm)

B(mm)

Weight

(kg)

80 125 110 30 22 0.5

100 165 110 30 32 0.5

125 188 110 30 32 0.7

Product code exampleProduct code: GBLM - aaa

typeØd1

Page 47: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

593

AB

ød

Mechanizmręczny

A

B

ød

Podstawka pod siłownik

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Round multi-blade damper

DASQ/DASQL/DASQM/DASQML

Dimensions

The round multi-blade damper can be used to control and isolate air flow in round ductwork.The round multi-blade damper design is based on the DSQW model. This model, however, features a housing with a branch at each end, sized to match the SPR ducts.Operating temperature range: -20˚ to +80˚ C.The DASQ / DASQL dampers are hand-operated. The DASQM / DASQML dampers are designed for use with actuators.All dampers have the blade angle (and the opening ratio) controlled with a system of gears driven by a hand lever or an actuator. The damper mechanism is installed on the outer surface of the housing.The dampers meet air tightness class B.

Available materials — Product code examplesDASQL-... — galvanized steel sheet

Description

Ød(mm)

A(mm)

B(mm)

400 505 505

450 505 505

500 605 605

560 605 605

630 705 705

710 805 805

800 905 905

900 1005 1005

1000 1105 1105

1120 1205 1205

1250 1305 1305

DASQ, DASQL

DASQM, DASQML

Product code exampleProduct code: DASQL - 800

typeØd

mounting plate

manualmechanism

Page 48: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

594

b

aL

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Rectangular single-blade damper

DSQ

Rectangular single-blade dampers can be used to control and isolate air flow in rectangular ductwork. The damper blade is reinforced by transverse embossing which depends on the product’s size.The damper can have a hand-operated damper mechanism, an externally-mounted actuator, or an actuator mounting.The hand operation requires turning the control handle, and the damper blade opening angle can be read on the control handle's bezel. The damper blade opening angle can be fixed with two stop screws.The standard version has a hand-operated damper mechanism.

The dimension A and B s izes ≤ 300 have the KIT-DS-PVC damper mechanism installed. Other dimensions have the KIT-DS damper mechanism installed.

Standard length sizes available:L = 200 at B ≤ 300L = 250 at 300 < B ≤ 500L = 300 at 500 < B ≤ 700

Available materials — Product code examplesDSQ-...-... — galvanized steel sheet

DescriptionThe damper mechanism is installed at the side of length b.

Product code exampleProduct code: DSQ - 600 - 400

typeab

Page 49: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

595

165

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Rectangular multi-blade damper

DSQWDimensions

The DSQW rectangular multi-blade dampers can be used to control and isolate air flow in rectangular ductwork. The dampers can be installed in ventilation ducts, as wall-mounted air flow regulators, or AHU air flow regulating and shutoff units.All dampers have a housing made of 4 galvanized steel sheet profiles framed with PQ angles, and a closure consisting of aluminium blades. The blade height is the same for all product sizes.The DSQW damper can have a hand-operated damper mechanism, an externally-mounted actuator, or an actuator mounting. The damper mechanism is installed on the outer surface of the housing. The damper blade rotation mechanism features short and long shafts rotating by intermeshed gears installed on bearings. The gears are installed on the outer surface of the housing.If B is between 1000 and 2000 and A ≥ 1000, two separate hand-operated damper mechanisms are provided. The versions with vertical partitions are available for A ≥ 1400.

The DSQW-C version is a special design of the damper that ensures airtightness class C (housing ) according to EN 1751:2014-03 standard. The frame is additionally sealed, the gears are placed on the inner side and the bearing mechanisms are sealed with plugs.

Operating temperature: -20˚C to +80˚C.

Available materials - Product code examplesDSQW-...-... - steel housing, galvanized steel sheet blades,

mechanism: external mountingDSQW-C-...-... - steel housing, galvanized steel sheet blades,

mechanism: internal mounting, airtightness class C according to EN 1751:2014-03

Description a (mm)

b (mm)

300-2000 300-2000

Product code exampleProduct code: DSQW - 600 - 300

typeab

Page 50: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

596

115

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Rectangular multi-blade damper

DSQW-A

The DSQW-A rectangular multi-blade aluminium dampers can be used to control and isolate air flow in rectangular ductwork.The dampers can be installed in ventilation ducts, as wall-mounted air flow regulators, or AHU air flow regulating and shutoff units.All dampers have a housing made of 4 aluminium profiles and a closure consisting of aluminium blades. The blade height is the same for all product sizes. The blades are fitted with gaskets to provide air tightness class 2 as per EN 1751:2003.The DSQW-A damper can have a hand-operated damper mechanism, an externally-mounted actuator, or an actuator mounting. The damper mechanism is installed on the outer surface of the housing. The damper blade rotation mechanism features short and long shafts rotating by intermeshed gears installed on bearings. The gears are installed on the outer surface of the housing.If B is between 1000 and 2000 and A ≥ 1000, two separate hand-operated damper mechanisms are provided. The versions with vertical partitions are available for A ≥ 1400.

Operating temperature: -20˚C to +80˚C

Note:It is recommended that the b dimension size should be chosen as a multiple of 100 mm. Otherwise, DSQW-A will not meet air tightness class 2.

Available materials — Product code examplesDSQW-...-... — aluminium housing, press-formed aluminium blades, 6063-T5 alloy, no surface finish

Description a (mm)

b (mm)

300-2000 300-2000

Product code exampleProduct code: DSQW-A - 600 - 300

typeab

Page 51: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

597

Positive pressureNegative pressure

10000

1000

100

100 1

class 0class 1class 2class 3class 4

10 100 1000 10000

2

stra

ty c

iśni

enia

[Pa]

nieszczelność [l/s*m ]

www

0,0

10,0

20,0

30,0

40,0

50,0

60,0

70,0

80,0

90,0

100,0

0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6

30° open45° open90° open

prędkość [m/s]

stra

ty c

iśni

enia

[Pa]

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Rectangular multi-blade damper

DSQW-ATechnical specifications

Air tightness chart according to EN 1751:2003

Pressure loss chart

speed (m/s)

pres

sure

loss

(Pa

)pr

essu

re lo

ss (

Pa)

Page 52: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

598

115

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Steel non-return air dampers

DSQOW

The self-closing multi-blade non-return steel dampers with aluminium blades are designed for air pressure control in the ventilation system. The blade design and mounting allow automatic air flow exhaust under the incoming pressure. This prevents overpressurizing the ductwork. The housing is made of galvanized steel angles. The blades are made of aluminium sections. The air damper is provided with a housing made of 4 angles of the same type as those used in the fabrication of the DSQW air dampers. All blades are provided with sealing gaskets.

The DSQOW air damper features moving aluminium blades, each 80 mm high. The blade height is the same for all product sizes. The blade bearings are fitted inside the upright sections. The versions with vertical partitions are available for A ≥ 1400 mm and according to these conditions: for 1400 mm < A ≤ 2100 mm, a single partition is installed; for A > 2100 mm, multiple partitions are installed.

Operating temperature range: -20˚C to +80˚C

Available materials — Product code examplesDSQOW-...-... — galvanized steel sheet housing

with aluminium sheet blades

Description a (mm)

b (mm)

300-2000 300-2000

Product code exampleProduct code: DSQOW - 600 - 300

typeab

Page 53: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

599

115

Ven

tilation

dam

pers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Dimensions

Self-closing rectangular multi-blade aluminium damper

DSQOW-A

The self-closing multi-blade non-return aluminium dampers are designed for air pressure control in the ventilation system. The blade design and mounting allow automatic air flow exhaust under the incoming pressure. This prevents overpressurizing the ductwork. The housing and the blades are made of aluminium sections.The air damper is provided a housing made of 4 angles of the same type as those used in the fabrication of the DSQW-A air dampers. EPDM gaskets are installed in the top and bottom housing walls.The DSQOW-A air damper features moving aluminium blades, each 80 mm high. The blade height is the same for all product sizes. The blade bearings are fitted inside the upright sections.The versions with vertical partitions are available for A ≥ 1400 mm and according to these conditions:for 1400 mm < A ≤ 2100 mm, a single partition is installed;for A > 2100 mm, multiple partitions are installed.

Operating temperature range: -20˚C to +80˚C

Available materials — Product code examplesDSQOW-A...-... — aluminium sheet

Description a (mm)

b (mm)

300-2000 300-2000

Product code exampleProduct code: DSQOW-A - 600 - 300

typeab

Page 54: Ventilation dampers · The dampers can be manufactured with any of the available damper mechanisms; however, only the housing and the damper closure (without the pivot rods) are manufactured

600

0

20

40

60

80

100

120

0 1 2 3 4 5 6 7 8

stra

ty c

iśni

enia

[Pa

]

prędkość [m/s]

Ven

tila

tio

n d

amp

ers

ALNOR® ventilation systemsis a registered trademark protected by a technical patent. All modification rights reserved.

Self-closing rectangular multi-blade aluminium damper

DSQOW-ATechnical specifications

Pressure loss chart

speed (m/s)

pres

sure