Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

Embed Size (px)

Citation preview

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    1/60

    VENTILATION FOR URBAN BUILDINGS

    Natural and Hybrid Ventilation in the Urban Environment

    March 2006

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    2/60

    CALCULATION OF THE OPTIMAL OPENING....................43

    VENTILATION CONFIGURATION....................................53

    Introduction to Module 2

    Natural and hybrid ventilation are used in urban buildings to provide good air

    quality and acceptable thermal comfort while reducing energy consumption of

    buildings.

    Natural ventilation has many advantages compared to air-conditioned buildings;

    however it remains an uncontrollable system and depends on the ambient

    conditions.

    Hybrid ventilation combines both natural and mechanical ventilation switching

    from one mode to another according to outdoor and indoor parameters. Hybrid

    ventilation may be a solution for naturally ventilated buildings in urban areas forextreme hot periods.

    The urban environment offers disadvantages in the application of natural and

    hybrid ventilation: the reduced wind speeds, the high ambient temperatures, the

    outdoor pollution and the increased noise levels decrease the cooling potential of

    natural and hybrid ventilation. The effective integration of both ventilation

    systems in the building design requires a good understanding of the urban climatic

    characteristics and the choice of the appropriate techniques in order to reduce the

    buildings exposure to the ambient constraints. Several design assisted tools have

    been developed for the design of naturally ventilated buildings. These include

    deterministic and empirical models for the prediction of wind speed at specific

    height in urban canyons and software for the calculation of optimal openings orairflows in naturally ventilated buildings.

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    3/60

    Alternative ventilation strategies can also be used in the urban environments to

    enhance the airflows in naturally ventilated buildings. Their function is based on

    the increased temperature difference of the inlet and exhaust air thus the increase

    of the buoyancy stack pressure. These strategies are appropriate for urban sites

    because the location of inlet and outlet of air is at high level, in an above roof

    position where the noise levels are reduced, the pollutant concentration lower and

    wind speed higher than inside the urban canyon.

    Evaluation of the performance of natural and hybrid ventilation has been carried

    out through experiments and monitoring of buildings in real urban canyons. The

    assessment of both ventilation systems aims to identify the parameters that affect

    the indoor air quality in naturally ventilated buildings, to present the advantages of

    hybrid ventilation versus natural ventilation and to examine the parameters that

    affect the operation of hybrid ventilation systems. It can be concluded that the

    indoor air quality in naturally ventilated buildings depends on the air change rates,

    the concentration of indoor pollutants, the use of buildings and the different

    configurations of natural ventilation. Hybrid ventilation has high cooling potentialwhile keeping the energy consumption of buildings at low levels; it has advantage

    over natural ventilation under windless conditions. The operation of the hybrid

    system depends on various outdoor and indoor parameters: the canyon geometry,

    the ambient air, the indoor pollutants concentration, the building leakage and the

    control strategy.

    The choice of the ventilation system of urban buildings and the application of

    the appropriate design techniques should take into consideration the urban

    characteristics while maximizing the natural forces in the urban environment,

    optimizing the thermal comfort, saving energy and/or improving the indoor air

    quality.

    CHAPTER 1 Natural and Hybrid Ventilation inUrban Buildings

    Learning objectives

    After studying this section you should:

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    4/60

    1. Understand the principles of natural and hybrid ventilation systems used

    in urban buildings2. Understand the function and control strategies of hybrid ventilation

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    5/60

    Introduction

    This module presents the principles of natural and hybrid ventilation systems

    that are used in urban buildings. Natural ventilation remains an uncontrollable

    system depending on the ambient conditions i.e. wind direction and air velocity.

    Often in urban sites, where wind flows are reduced due to the heat island effect,

    natural ventilation is inadequate.

    Hybrid ventilation system may be a solution for naturally ventilated buildings as

    it combines the advantages of natural and mechanical ventilation. The system

    combines both modes switching from one to another depending on outdoor and

    indoor conditions; the optimum function of the system uses natural ventilation as

    much as possible.

    Both natural and hybrid ventilation systems use the outdoor environment to

    create good indoor air quality and thermal comfort while reducing energy

    consumption of buildings.

    1.1 Natural Ventilation

    Natural ventilation is caused by naturally produced pressure differences due to

    wind, temperature difference or both. Natural ventilation is achieved by allowing

    air to flow in and out of the building by opening windows and doors or specific

    ventilation components like chimneys. The effectiveness of natural ventilation

    depends on the wind speed and direction, temperature difference, the size and

    characteristics of the openings. (See module 1)

    The main configurations for natural ventilation in urban climate are the same as

    for open area location: Single sided Cross ventilation Stack ventilation Combinations of these strategies and enhancement of the airflows make

    them more suitable to urban climates

    When it is used for free-cooling, natural ventilation can replace air-conditioning

    systems for large periods of time during a year. The potential of natural ventilation

    is related to the energy saved for cooling if natural ventilation is used instead of

    cooling. However, urban environment presents disadvantages for the applicationof natural ventilation: lower wind speeds, higher temperatures due to the effect of

    urban heat island, high levels of noise and air pollution.

    1.2 Hybrid Ventilation

    Hybrid ventilation is a two mode system combining of natural ventilation and

    mechanical ventilation. (De Gids 2004) Mechanical ventilation is used when

    natural driving forces cannot fulfill the required ventilation level, a case very often

    met in the urban context (Figure 1.1).

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    6/60

    Figure 1.1: Definition ofHybrid Ventilation (De Gids, 2004)

    Hybrid ventilation is a new ventilation concept that combines the best features ofnatural and mechanical ventilation at different times of the day or season of theyear. It is a ventilation system where mechanical and natural forces are combined

    in a two mode system. The operating mode varies according to the season andwithin individual days, thus the current mode reflects the external environment

    and takes maximum advantage of ambient conditions at any point in time

    (Heiselbeg, 2002).

    The main difference between conventional ventilation systems and hybrid systems

    is the fact that the latter are intelligent systems with control systems thatautomatically can switch between natural and mechanical mode in order to

    minimize energy consumption and maintain a satisfactory indoor environment

    (RESHYVENT research programme, WP8)

    The aim of the strategy is to reduce energy, cost and the environmental side

    effects of year-round air conditioning while optimizing indoor air quality and

    thermal comfort by combining the two modes of ventilation.

    The operating mode performs according to seasons and depends on external

    ambient conditions.

    Figure 1.2 shows the combination of a balanced ventilation system with natural

    ventilation in a dwelling. When the ambient conditions allow it, the dwelling is

    naturally ventilated. In extreme weather conditions, natural ventilation is shut

    down and the mode is switched to mechanical ventilation.

    Figure 1.2: Example ofHybrid Ventilation in a Dwelling (RESHYVENT,WP8)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    7/60

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    8/60

    1.2.4 Control Strategies for Hybrid Ventilation

    The control strategy is a key role for the function of hybrid ventilation systems as

    it switches from natural to mechanical mode depending on the driving forces and

    the required airflows. Control strategies can be distinguished in spatial and

    temporal.

    Spatial Control

    Spatial strategy is related to the design system and should be taken into

    consideration at an early stage. It is linked with outdoor air entering the habitable

    rooms living rooms and bedrooms, and being extracted from the service rooms

    kitchen and bathrooms.

    The aim of this strategy is

    to control the air change rates that have an impact on the energyconsumption. These are linked to the presence of occupants since it islimited into the service rooms than into the habitable areas

    to limit the diffusion of short term pollutants from the service rooms to thehabitable rooms.

    The drawback of this strategy is the excessive increase of airflows rates into the

    habitable rooms when high air rates are required in some of the service rooms.

    Temporal Control

    Temporal strategy is related to the presence of occupants, thus emissions from

    metabolism and activities; and to the climatic conditions. It is linked to demandcontrol ventilation.

    Flows can be controlled by:

    Presence: movement, switching on/off lighting Metabolism: CO2 emissions, water vapour, odours Activities: cooking, shower (this applies mainly to residential buildings) Climatic conditions: outdoor/indoor temperature, wind speed and wind

    direction

    Temporal strategy is based mainly on control/monitoring of CO2, VOC,

    humidity and temperature parameters.

    Summary

    Hybrid ventilation systems use both natural and mechanical ventilation aiming

    at reducing energy consumption of buildings and enhancing indoor air quality and

    thermal comfort. The optimized operation of the system uses natural ventilation as

    much as possible; the mechanical part is used when due to ambient conditions

    natural ventilation cannot provide adequate airflows.

    The control strategy is a key parameter for the function of the system and may

    be connected to the outdoor parameters, the indoor conditions or the usage of the

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    9/60

    building. Both natural and hybrid ventilation systems are influenced by the

    outdoor climate and take maximum advantage of ambient conditions at any time.

    1.3 Questions for self assessment

    1. How hybrid ventilation is connected to outdoor parameters?

    2. Which parameters that are connected to the presence of people can

    be controlled using hybrid ventilation?

    3. What are the benefits of hybrid ventilation compared to other

    ventilation systems

    Problem(s)

    1. Describe using a sketch a simple hybrid ventilation scheme integrated in a

    dwelling switching from mechanical to natural ventilation

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    10/60

    CHAPTER 2 Impact of the Urban Environment on

    Natural and Hybrid Ventilation

    Learning Objectives

    After studying this section you should:

    1. Understand the conditions under which the urban environment presents

    constraints to the use of natural and hybrid ventilation2. Be able to provide design solutions to enhance the use of natural andhybrid ventilation in urban buildings

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    11/60

    Introduction

    The chapter aims to discuss the most important constraints of the urban

    environment on the ventilation efficiency of natural and hybrid ventilation systems

    and to suggest several solutions to overcome these barriers.

    The urban environment presents disadvantages for the application of natural and

    hybrid ventilation. Because of the specific urban characteristics, the potential of

    natural and hybrid ventilation can be seriously decreased in the urban environment

    mainly due to:

    Reduced wind speeds High ambient temperatures due to urban heat island Increased external pollutant Increased noise levels

    2.1 Wind speed

    The urban wind pattern is complicated. Compared to the undistributed wind in

    rural areas, wind in the urban context is characterized by irregular flows because

    of the built landscape, building geometry, street orientation, arrangement of built

    structures and streets. As a result, wind speeds within the urban canopy are usually

    reduced in comparison with rural winds at the same height: the wind speed u at

    any heightzis lower in the urban area, and much lower within the obstructed area.

    As a result, wind induced pressure on building surface is also reduced.

    Figure2.1: Wind Velocity and Wind Induced Pressure are Reduced inUrban Environment

    [Pa]

    4m/s

    Length [m]

    4m/s

    4m/s

    2.1.2 Direction of airflows with respect to canyon axis

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    12/60

    The wind distribution in urban canyons is determined by the prevailing airflow

    direction with respect to the canyon axis. The following wind incidence angles can

    be observed:

    Perpendicular WindWhen the predominant direction of the airflow is approximately normal (say 20 degrees), to the long axis of the street canyon.

    Parallel wind (say 20 degrees)When the airflow is along the canyon axis.

    Oblique windWhen the airflow is at an angle to the canyon axis.

    Additionally, different types of air flow regimes are observed as a function of

    wind incident angle, building (L/W) and canyon (H/W) geometry. (See foundation

    module)

    2.1.3 Model to Predict Wind Speed

    Knowledge of the air speed inside urban canyons is of high importance for

    passive cooling applications and especially for hybrid and naturally ventilated

    buildings. Various methods, simplified or detailed have been proposed to calculate

    the wind speed inside a canyon. However, air flow in canyons is not always a

    deterministic problem and prediction algorithms may not be appropriate for any

    case. Additionally, the boundary conditions are difficult to be defined and are

    rarely known. Thus, a complete methodology to predict and estimate wind speeds

    in canyons should be a combination of deterministic and empirical methods.

    This section describes a new model that predicts wind speed inside canyons at

    any height above ground level. This model is an algorithm based on existing

    experimental knowledge and has been developed within the framework of

    URBVENT European Project (2000).This model operates as a function of the

    geometrical characteristics of the canyon, the undisturbed wind speed and other

    boundary conditions.

    The inputs of the model are:

    The orientation of the canyon

    The geometrical characteristics (width, height and length of the canyon

    without intersections) and

    Undisturbed wind speed (wind speed and direction outside canyon).

    The output is:

    Wind speed value at any specific point inside the canyon which is definedby coordinates (x, y, z).

    2.1.4 Description of the proposed model

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    13/60

    Figure 2.2: Flow-Chart ofThe Algorithms and The Empirical ValuesUsed in The Empirical Model forEstimating Wind Speed Inside Street

    Canyons (Georgakis and Santamouris, 2005a).

    Source: Final report of the URBVENT project, European Commission,

    Directorate General for Research, Brussels, June 2004

    The proposed model to predict wind speeds can be described by the following

    chart:

    2.1.5 Sequence ofCalculations

    Based on the input data, the model carries out the following sequence of

    calculations:

    Calculations to check if a canyon situation exists

    Aspect ratio (H/W): If the aspect ratio of the canyon (H/W) is greater than0.7 then there is a canyon situation. Otherwise the space between the buildingsis not a street canyon.

    1. Aspect ratio

    H/W>0.7Not a street canyon

    Dominant end effects. Use wind

    speed close to 0.5m/s

    3.Wind speed

    v>4m/s

    2. Aspect ratio

    L/W>20

    5.Wind flow

    along canyon

    4.Wind flowperpendicular/

    oblique to thecanyon axis

    Use Exponential Law.Use Hotchikiss-Harlow and Yamartino-

    Wiegand model.

    Use empirical

    values

    Yes

    No

    Yes

    Yes

    Yes

    Yes

    No

    No

    No

    No

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    14/60

    Calculations to check if there is wind circulation inside the urban canyon

    Ratio of length and width between the buildings: the ratio of the buildinglength between main intersections and the width between buildings (L/W) is

    greater than 20 then there is a wind circulation in the canyon and the

    calculations continue. If the ratio L/W is less than 20 then, the end effects

    dominate inside the canyon and extended experimental analysis indicated that

    a wind speed value of 0.5 m/s could be considered as mean (Georgakis and

    Santamouris, 2005b).

    Calculations of wind speed

    Consequently, if the wind speed outside the canyon is less than 4 m/s butgreater than 0.5m/sec and its direction is perpendicular or oblique to the

    canyon, the values from Table 2.1 (Empirical Values) can be used.

    Table 2.1: Empirical Values for Perpendicular/Oblique Canyon WindSpeed Inside the Canyon (Georgakis and Santamouris, 2005a)

    Wind Speed Outside

    The Canyon (U)

    Wind Speed Inside The Canyon

    Near The Windward Facade ofThe Canyon Near The Leeward

    FacadeLowest Part Highest Part

    U=0 0 m/s 0 m/s 0 m/s

    0

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    15/60

    and

    0

    2

    2 /1.0 zhz b= (2)

    Where:Uo is the constant reference speed, (outside the canyon)

    y is the height from the ground in which we want to calculate the upup is the calculated wind speed inside the canyonz2 is the roughness length for the obstructed sub-layer

    zo is the aerodynamic roughness length

    Typical values of zo are given by Oke, (1987) in Table 2.2.

    Table 2.2: Typical Roughness Length Values zo, forUrbanized Terrain(Oke, 1987)

    Terrain zo (m)

    Scattered Settlement(farms, villages, trees, hedges) 0.2-0.6

    Suburban

    Low density residences and gardens

    High Density0.4-1.2

    0.8-1.8

    Urban

    High Density, < 5 story row and block buildings

    Urban high density plus multi - story blocks

    1.5-2.5

    2.5-10

    For example, for the centre of the city of Athens where the mean buildings height

    is close to 30 meters, we considered 0z equal to the value 3.

    If the wind incidence angle is perpendicular/oblique to the canyon mainaxis and the wind velocity is greater than 4 m/s, the following algorithms are

    used:

    In this case the proposed algorithms are based on the study of Hotchkiss and

    Harlow (1973) and permit the calculation of the cross and vertical wind speed

    components ( u ,v ). The algorithms consider incompressible flow, absence ofsources or sinks of vorticity within the canyon, and appropriate boundaryconditions for the simple two-dimensional rectangular notch of depth H and width

    W.

    The proposed algorithms are the following:

    ( ) ( )[ ] ( )kxkyekyek

    u kyky sin11 +

    =

    (3)

    and

    ( ) ( )kxeeyvkyky

    cos

    =

    (4)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    16/60

    Where

    Wk /= (5)

    ( )kH2exp =

    (6)

    ( )= 1/0ku (7)

    Hzy = (8)

    And 0u is the wind speed above the canyon and at point x=W/2, z=H.

    The above-mentioned algorithms were tested and approved by Yamartino andWiegard (1986).

    Additionally, the along canyon wind speed component, ( )zw is calculated by thefollowing equation:

    [ ] [ ]0000 /)(log//)(log)( zzzzzzwzw rr ++= (9)

    Where rw was the wind speed values measured outside the canyon at rz meters

    above the ground and 0z was the surface roughness.

    The horizontal wind speed inside the canyon is:

    5.022 )( vuvh += (10)

    The total wind speed inside canyon at any point ( x, y, z) is:

    5.022

    )( wvvht +=

    (11)

    2.2 Temperature Distribution

    The temperature distribution in the urban canopy layer is greatly affected by the

    radiation balance: the temperature of the canyon surfaces depend on the heat

    exchange processes between the buildings surfaces and the environment through:

    radiation, convection and conduction

    Surfaces absorb short-wave radiation and absorb/emit long wave radiation

    depending on:

    Thermal and optical characteristics of the materials-materialsabsorptivity. This is defined by the albedo; the albedo being a measure of the

    solar energy amount that is reflected by the surfaces. The use of high albedomaterials, thus high reflectivity results in cooler surface temperatures whereas

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    17/60

    low albedo implies higher surface temperatures since the larger amounts of

    solar energy is absorbed (Santamouris, 2001).

    Surfaces exposure to solar radiation and buildings orientation.Because of the cities characteristics, canyon geometry, buildings thermal

    properties and anthropogenic heat rate ambient temperatures in the urban

    contexts are higher than their surroundings. This results in the urban heatisland effect that is the best documented example of inadverted climate

    modification (Oke, 1987).

    2.2.1 Analysis ofThe Air and Surface Temperature in Urban Canyons

    Analysis of temperature distribution in several deep urban canyons showed that:

    The surface temperatures are higher than the air temperatures in urbancanyons.

    Surface temperatures vary according to their orientation: Southerly, south-easterly and south westerly orientated facades during the day may result inhigher temperatures than northerly, north-westerly and north-easterly

    orientated facades. Additionally, the surface temperature stratification

    observed during the day period of the analysis was between 300C to 500 on the

    South-East wall and 270C to 410C on the North-West wall.

    Surface temperature depend on inclination and materials: Comparison ofthe maximum difference of daily temperatures of the building facades and the

    surface temperatures of the street shows that at street level the temperature is

    20C and 50 C higher than the lower and the highest parts of the canyon.

    Horizontal surfaces during the summer period receive more solar radiation

    than vertical ones. Additionally slabs used in the pedestrian streets absorb

    more radiation than materials used fro the building walls

    Surface temperatures vary according to the surface height: maximumsimultaneous difference of the two facades was up to 10-20C at the middle

    and at the highest measured levels of the canyon.

    It should be noted that the air temperature outside the canyon was during the

    experimental period about 5C higher than the temperature inside the canyon. This

    can be explained by the canopy geometry as most of the canyons that were used

    were deep. Additionally, the street orientation prevented the solar radiation for a

    long period and a very good airflow was observed due to the big aspect ratio

    (H/W=3.3)Figure 2.1: Box-Plots ofTemperature Distribution in a Street Canyon:

    a) Vertical Distribution in The Centre ofThe Canyon; b) WallsTemperature (Georkakis and Santamouris 2003).

    1 2 3 4 523

    25

    27

    29

    31

    Temperature[C]

    utsde

    canyon

    At3.5m

    At7.5m

    At11.5m

    At15.5m

    25

    30

    35

    40

    45

    South-West

    facade

    Ground North-Eastfacade

    Tem

    perature[C]

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    18/60

    2.3 OutdoorPollution

    Outdoor air pollution is a serious limitation for natural and hybrid ventilation in

    urban areas. The relative importance of different air pollutants and sources has

    changed with time and culture in the different geographical areas. Nowadays, the

    dominant sources of atmospheric pollution, in certain European cities, are motor

    vehicles and combustions of gaseous fuels.

    Outdoor pollution is associated with:

    Poor indoor air quality in buildings if combined with inadequateventilation. Health problems may occur if a space is not properly ventilated

    and indoors pollutants concentration is high.All pollutants can cause serious

    health problems to the occupants like as respiratory and cardiovascular problems, dermal irritations, infections and intoxication that result in

    occupants discomfort and to a poor quality life. High humidity levels indoors

    may also provoke allergies and are linked to an increased concentration of

    micro organisms, mould and bacteria. In developed countries concentrations of

    indoor pollutants are very similar to those outdoors with the ratio of indoor to

    outdoor concentration (I/O) falling in the range of 0.7-1.3

    Poor life quality. If identical health problems are experienced by a bigpercentage of the inhabitants, then we could speak about the sick building

    syndrome. Sick building syndrome is usually met in air-conditioned buildings

    but also observed in naturally ventilated buildings. It is a frequent

    phenomenon of all major cities of the western countries.

    In the case of sickbuilding syndrome the peoples productivity is seriously affected.

    Damages to buildings and historic monuments. They can causedeterioration of materials and serious damage to equipment resulting in loss of

    services provided by the equipment or even release of harmful substances into

    the environment.

    According to World Health Organisation, the predominant outdoor pollutants are:

    sulphur dioxide, nitrogen dioxide, carbon monoxide, ozone, particulate matter, and

    lead. Guideline values are given for these pollutants (WHO 2000). Indoor

    pollutants include environmental tobacco smoke, particles (biological and non-

    biological), volatile organic compounds, nitrogen oxides, lead, radon, carbon

    monoxide, asbestos, various synthetic chemicals and others.

    2.3.1 Analysis of the outdoor & indoor pollutants concentration

    Indoor air quality in developing countries is an extremely serious problem.

    Experimental measurements of the indoor-outdoor pollutant transfer showed that

    the indoor pollutants concentration depends on several parameters:

    Outdoor pollutant concentration and ambient particle distributions

    Buildings openings Faade air tightness Ventilation rates

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    19/60

    Wind speeds and wind angles

    Figure 2.2: The Variation ofIndoor perOutdoorOzone Ratio as aFunction of: a) Air Changes perHour (CW Closed Window, POW

    Partially Opened Window, OW Open Window); b) OutdoorConcentration.

    Source: Natural ventilation in the urban environment, Series Editor M.

    Santamouris

    0.0

    0.10.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1.0

    0 50 100 150 200 250 300 350 400 450

    Outdoor concentration, Co (ppb)

    I/O at 0,6 (vol./h) Weschler et al. 1989I/O at 4,0 (vol./h) Weschler et al. 1989I/O Shair et Heitner 1974

    I/O=1-exp(-0.027*Co.

    )

    I/O=exp(-0,379*Co,

    )

    I/O=1-exp(-0,027*Co.

    )

    0.0

    0.10.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1.0

    0 2 4 6 8 10 12

    Air changes per hour, ach (h-1

    )

    OWPOWCW

    Hayes1991

    Weschler et al. 1989Iordache 2003

    Monitoring of the main outdoor pollutants (SO2, NO2, CO, O3, suspended particle

    matter, and lead) in large cities shows that:

    The mean level of sulphur dioxide and lead are equal indoor and outdoor. Ozone and nitrogen dioxide react with the building material and the

    building airtight ness: their concentration is lower indoors than outdoors when

    the building is airtight.

    The particle matter transfer depends on the particle size and the outdoorconcentration of the pollutant.

    The indoor - outdoor pollutant transfer depends also on the windowsopening, thus the building air-tightness; in the case of closing windows the

    transfer becomes more complex.

    2.3.2 Ventilation strategies and guidelines to reduce exposure to outdoor

    pollutants

    Many guidelines have been developed to propose interactive design tools andventilation strategies for naturally ventilated buildings in polluted urban areas.

    Pollution avoidance strategies in the building design that should be taken into

    consideration include:

    Location of vents on sheltered facades and positioning of central inlets at asufficient height from emissions.

    Alternative solutions to natural ventilation as supply ventilation withfiltration or exhaust ventilation, filtration

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    20/60

    2.4 Noise Levels Ventilation Potential in Urban Areas

    Noise is one of the most important considerations when designing openable

    windows thus for the potential of natural ventilation in urban sites. Noise is often

    considered as a restrictive parameter for the use of natural ventilation and the

    selection of air-conditioning systems instead.

    It is suggested that acceptable noise levels should not exceed 65 dB (A). High

    levels of noise and continuous background noise may provoke sleep disturbance,

    and have impact on peoples health, productivity and social life. Moreover, areas

    with noise levels more than 75 dB(A) are considered harmful as these can lead to

    hearing loss.

    Studies showed that inhabitants of the most urban areas are exposed to high

    noise pollution. Within the frames of the Fifth Programme it was stated that about

    8% of the urban population is exposed to outdoor noise at a level 70 dB(A), while

    11% is exposed at levels greater than 65 dB(A).

    In the case of naturally ventilated buildings or buildings with hybrid ventilation,noise is an important parameter to consider. Window opening provides the

    minimal sound insulation, thus many times noise exclusion and provision of

    adequate ventilation consist of two controversial functions.

    2.4.1 Noise Levels in Street Canyons and Potential ofNatural Ventilation

    Several studies have been undertaken to estimate noise levels in urban areas and

    their impact on the choice of ventilation strategies for buildings. Noise

    measurements were undertaken in the canyon streets in Athens with aspect ratios

    (height/width) varying from 1.0 to 5.0 and with a variety of traffic load, during

    September 2001. The aim of the analysis is to assess the vertical variation of noiselevels along the building facades and the cooling potential of natural ventilation.

    The analysis comprises two parts, measured data of daytime traffic noise and

    simulations using a noise-level simulation package.

    Part 1 - Measurement data: The study of the measured data uses a linear regression

    analysis and shows that the noise levels in the urban areas depend on the canyon

    geometry and the traffic density;

    Attenuation of noise levels is noted with floor height above the street level

    The maximum value of noise attenuation is almost entirely a function ofaspect ratio

    Traffic density thus noise levels increase with reduced street width

    Balconies may contribute to a noise reduction of 2-4 dB depending onfloor height.

    Part 2 - Simulations: Three simulations were made and the simulation results were

    compared to the measured data. For the study, different street widths were

    assumed of 5m, 10m and15m respectively for a five storey building. The aim of

    the analysis was to assess the impact of the balconies to the reduction of the traffic

    noise levels at the four building levels: first floor, second, third and fourth floor

    for the three different street widths. The results showed that:

    The noise attenuation due to the balconies is around 2dB at first floor and

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    21/60

    more than 3dB for the top floor.

    The geometry of the balcony, width and distance of the building faade aswell as the solidity of the front of the balcony has an impact on the noise

    attenuation: for example narrower balconies do not have great impact on the

    noise levels as larger balconies may have.

    2.4.1 Analysis ofNoise Levels in Office Buildings

    Within the frames of the Research programme Smart Controls and Thermal

    Comfort (SCATS), surveys were undertaken in 25 office buildings of 5 European

    countries to assess the use of natural ventilation and noise limitations in urban

    areas. The results show that:

    Noise levels of 55-60dB can be accepted, though greater tolerance isobserved in areas with open windows.

    The noise attenuation at an open window is accepted at 10-15dB, thusoutdoor levels for acceptable comfort indoor conditions should be around

    70dB.

    Window design is very critical when providing natural ventilation: Specialglazing may contribute to a further 3-5dB reduction.

    Figure 2.7: Potential forNatural Ventilation ofOffices as a Function ofStreet Width and Height Above the Street.

    Configurations in which natural ventilation is possible are indicated (ok), as arethose in which it is ruled out (not ok). Between these two extremes is a region in

    which there are possibilities for design solutions. Source Natural Ventilation in

    the urban environment

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    22/60

    0 5 10 15 20 25 30 35 405

    10

    15

    20

    25

    dB

    Height above street (m)

    Streetw

    idth(m)

    OK

    NOT OKDesign

    possibilities?

    74 dB

    70 dB

    7276

    68

    2.4.2 Noise Control Strategies for Natural Ventilation

    A number of noise control strategies for natural ventilation systems can be

    implemented in the building design. It is suggested that:

    With careful design, adequate airflow rates can be provided in buildingsfor good indoor quality and noise insulation

    The use of hybrid ventilation can convert the natural ventilation strategy areal possibility in areas where noise levels have previously prohibited such

    an approach.

    SummaryThe urban characteristics influence the cooling potential and efficiency of

    natural and hybrid ventilation: the reduced wind speeds, the high ambient

    temperatures, the increased noise levels and the outdoor pollution are restrictive

    parameters for the use of natural and hybrid ventilation in urban buildings.

    Knowledge of the air speed in urban sites is of high importance for the

    application of passive cooling techniques. The use of an algorithm that was

    developed within the frames of the URBVENT research programme is suggested

    for the prediction of wind speed in canyons at specific coordinates. Additionally,

    the careful location of vents and inlets, the use of filtration or the replacement of

    natural ventilation with hybrid ventilation offer solutions for naturally ventilatedbuildings that are located in high polluted areas.

    Noise levels in urban areas depend on the canyon geometry and the traffic

    density; additionally the building geometry i.e. number of floors, presence of

    balconies can contribute significantly to the noise attenuation. However, hybrid

    ventilation can be a solution for areas with increased noise levels: natural

    ventilation should not be used in sites with noise levels higher than 74 dB.

    2.5 Self assessment Questions

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    23/60

    1. Describe the sequence of calculations carried out by the algorithm

    in order to predict wind speed inside urban canyons. In which case the

    mean wind speed can be considered 0.5 m/sec?

    2. Which parameters affect temperature distribution in urban areas?

    3. Give the threshold lines of noise levels in urban areas where natural

    ventilation can be applied

    Problems

    1. What are the consequences of badly selected and located air inlets in

    naturally ventilated buildings in the urban environment? What is the

    optimum location of air inlets?

    2. The wind speed (Vo) is measured 4.2 m/sec at 15m above ground.

    The orientation of the wind speed and urban canyon are given:

    Canyon orientation = 50Wind (V0) incidence angle = 40It is also calculated that L/W >20. Explain why there is wind circulation

    inside the urban canyon.

    Assuming that z0 is equal to 3 and the roughness length is given by the

    equation: 02

    2 /1.0 zhz b= , calculate the wind speed up at the faade of the

    fifth floor (at height 1.5m from floor level of the fifth floor)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    24/60

    CHAPTER 3 Natural Ventilation Strategies to

    EnhanceAirflows in Urban Environments

    Learning Objectives

    After studying this section you should:

    1. Understand the principles of the strategies that can be used to enhance

    airflows in naturally ventilated buildings in urban areas

    2. Use equations to calculate airflows in different ventilation strategies whenincreasing the buoyancy stack pressure

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    25/60

    Introduction

    This chapter focuses on several alternative ventilation strategies and building

    constructions that can be used to enhance airflows in naturally ventilated buildings

    in urban areas.

    The use of natural ventilation in urban environment should take into account the

    lower wind velocity but also the noise and outdoor pollution. It is very important

    to consider other techniques than windows to enhance airflow in buildings. In

    many cases, the ventilation systems cannot rely on low-level inlets as these may

    be close to external pollutant sources i.e. traffic.

    3.1 Balanced stack ventilation

    The balanced stack ventilation schemes use both inlets and exhausts of air at

    different temperature: air is supplied in a cold stack (i.e., with air temperatures

    maintained close to outdoor conditions through proper insulation of the stack) andexhausted through a warm stack. This strategy is met in the traditional Iranian

    wind towers (bagdir) and the Arabian Asian wind catchers (malkaf) comprise

    examples of balanced stack ventilation.

    Figure 3.1: Top-down or balanced stack natural ventilation systemsuse high level supply inlets to access less contaminated air and to

    place both inlet and outlets in higher wind velocity exposures.

    Top-Down or Balanced Stack Ventilation

    v ref

    nlet

    nternal

    exhaust

    w-inlet

    w-outlet1 2

    3

    4

    5 6

    warm

    stackcool

    stack

    The equation for the pressure loop for example through the second floor of the

    figure above will be similar in form to the case of combined wind and buoyancy-

    driven ventilation:

    exhausternalinletws ppppp ++=+ int . (1)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    26/60

    If air temperatures within the cold stack can be maintained close to outdoor

    levels, the stack pressure is determined by the indoor-to-outdoor air density

    difference and the height difference from the stack exhaust and the floor level inlet

    locations is given by the equation:

    ( ) s o ip g z = (2)

    Airflow through each floor level will, therefore, be identical to that expected in

    the simpler single stack scheme if the airflow resistance of the supply stack (and

    its inlet and outlet devices) is similar to that provided by the air inlet devices in

    this scheme.

    The driving wind pressure is determined by the difference between inlet and

    exhaust wind pressure coefficients and the kinetic energy content of the approach

    wind velocity

    2/)( 2refexhaustpinletpw vCCp = . (3)

    The high location of the inlet assures a higher inlet wind pressure and

    insensitivity to wind direction. The location of the air-intakes in an above-roof

    position where the pollutant concentration is lower than the street level and the

    independency from air velocity and wind direction thus wind patterns remain

    independent from surrounding buildings, make this strategy very attractive for the

    urban areas.

    Balanced stack systems have been used in the UK for, apparently, over a century

    (Axley, 2001) although these commercially available systems have, until recently,

    been designed to serve single rooms rather than whole buildings.

    3.2 Passive Downdraught Evaporative Cooling

    The passive downdraught evaporative cooling (PDEC) scheme is the same

    scheme with the balanced stack ventilation system with the addition of

    evaporative cooling to the supply stack. Traditionally, evaporative cooling was

    achieved through water-filled porous pots within the supply air stream or the use

    of a pool of water at the base of the supply stack. In more recent developments,

    water sprayed high into the supply air stream cools the air stream and increases the

    supply air density thereby augmenting the buoyancy induced pressure differences

    that drive airflow.

    In the loop analysis of thepassive downdraught evaporative coolingscheme, the

    increased moisture content must be accounted for. Two height differences must

    now be distinguished:za - the height above the room inlet location of the moist air

    column in the supply stack and zb - the height of the exhaust above this moist

    column.

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    27/60

    Figure 3.2: Passive Downdraught Evaporative Cooling StackVentilation.

    The air density in the moist air supply column, s , will approach the saturation

    density corresponding to the outdoor air wet bulb temperature more specifically,

    experiments indicate these supply air conditions will be within 2 C of the wet

    bulb temperature. Hence the loop equation describing the (time-averaged)

    ventilation airflow in this system becomes:

    ( )inlet internal exhaust s wp p p p p + + = + (4)

    where:

    [ ]gzzzzp baiasbos )( ++= (5)

    ( )2

    2r

    exhaustpinletpw

    vCCp

    = . (6)

    For a quantitative measure of the impact of this strategy, let us consider a case

    similar to that one discussed above for wind and buoyancy induced natural

    ventilation, but with a cool moist column height that equals the stack height of 10

    m (i.e., mza 0 and mzb 10 ). If the outdoor air having the temperatures of 25

    C and humidity of 20 % RH (i.e., with a density of approximately 1.18 kg/m3) is

    evaporatively cooled to within 2 C of its wet bulb temperature (12.5 C), its dry

    bulb temperature will drop to 14.5 C while its density will increase to

    approximately 1.21 kg/m3 and relative humidity to 77%. If internal conditions are

    kept just within the thermal comfort zone for these outdoor conditions (i.e., 28 C

    and 60 % RH), using an appropriate ventilation flow rate given internal gains, then

    internal air density will be approximately 1.15 kg/m3. Consequently the buoyancy

    pressure difference that will result will be:

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    28/60

    3 3 3 2

    kg kg kg m1.18 (0 m) 1.21 (10 m) 1.15 (0 10 m) 9.8 6.4 Pa

    m m m ssp

    = + + =

    (7)

    Without the evaporative cooling (i.e., with 10az and 0 mbz ):

    3 3 3 2

    kg kg kg m1.18 (10 m) 1.21 (0 m) 1.15 (10 0 m) 9.8 2.9 Pa

    m m m ss

    p = + + =

    (8)

    Thus, in this representative example, evaporative cooling more than doubles the

    buoyancy pressure difference while, at the same time, providing adiabatic cooling.

    3.2.1 Example

    The School of Slavonic and East European Studies (SSEES) building of

    University College London comprises an example where passive dowdraughtcooling is used. The building is located in a central area of London with high

    ambient temperatures and increased noise levels and pollution. Initial studies

    showed that natural ventilation strategy would not achieve acceptable thermal

    comfort and the night time ventilation efficiency was reduced due to the urban

    aspects. Therefore, the natural ventilation cooling capacity was enhanced with

    chilled water coils for extreme weather conditions.

    The air is entering the building to all floors through a three sided light well in

    the centre of the building. The air is cooled by chilled water coils that are located

    around the top of the light well. The air is exhausted through stacks on the curved

    and double faade sides of the building (figure 3.3)

    Figure 3.3: The School of Slavonic and East European Studies(SSEES) Building of University College London.Example ofPassiveDowndraught Evaporative Cooling (Source: IJV Volume 3, 4 March

    2005)

    3.3 Double Skin Faade

    The double skin faade system consists of two glass skins placed in distance sothat air flows in the intermediate cavity. The ventilation of the cavity can be

    neutral, fan supported or mechanical. Apart from the type of the ventilation inside

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    29/60

    the cavity, the origin and destination of the air can differ depending mostly on

    climatic conditions, the use, the location, the occupational hours of the building

    and the HVAC strategy. The glass skins can be single or double glazing units with

    a distance from 15cm up to 2 metres.Usually, solar shading devices are placed

    inside the cavity. (Haris Poirazis, 2004)

    Potential advantages and disadvantages of the application of double skin facades,

    typologies of the system and technical description of the systems components are

    studied within the research programme BESTFACADE.

    Compared to conventional office buildings with large glazed facades, this system

    provides the follows advantages:

    Thermal buffer zone that reduces heat losses and enables passive thermalgain from solar radiation

    Solar preheating of ventilation air, thus reduced heating demands

    Sound protection e.g. at locations with heavy traffic mainly during windowventilation Additional shading and protection of shading devices Energy savings if the design is well adapted to the climatic conditions Enables natural ventilation. Individual window ventilation is almostindependent of wind and weather conditions mainly during sunny winter days

    and the intermediate season

    Night cooling of the building by opening the inner windows

    Potential disadvantages of double skin facades can be:

    Poorer cross ventilation and insufficient removal of heat from the officesduring windless periods when ventilation is provided mainly by natural

    ventilation

    Overheating in the occupied spaces during the summer months Higher investment and cleaning costs Risk of noise-cross talk via the faade from one office to the other and/orfrom one level to the other.

    It is very important the double skin faade to be well designed with the correct

    type of ventilation and adapted to the climatic region; otherwise overheating or

    energy inefficiency may be experienced.The space within the skin two skinsshould be well ventilated either by natural, mechanical or hybrid ventilation.

    According to the origin and destination of the supplied air into the cavity the

    double skin facades can follow into the following sections:

    Outdoor air curtain, when the air comes from the outside and isimmediately rejected to the outside - Figure 3.3 (1)

    Indoor air curtain, when the air circulates from the inside and returns to theinside- Figure 3.3 (2)

    Air supply, where fresh air is supplied into the building throug the externalskin- Figure 3.3 (3)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    30/60

    Air exhaust, the air is comes from the inside of the room and is exhaustedfrom the building faade - Figure 3.3 (4)

    Buffer zone, the faade is made airtight. The cavity comprises a bufferzone between the internal and external skin. - Figure 3.3 (5)

    Figure 3.3: Configurations ofDouble Skin Facades According to TheOrigin and Destination ofThe Supplied AirInto The Cavity

    Source: Double Skin Facades for Office Buildings-Literature Review, Division of

    Energy and Building Design, Department of Construction and Architecture, LundUniversity, 2004, Harris Poirazis

    Double faades can be used for solar assisted stack ventilation or balanced stack

    ventilation.

    3.4 Solar-Assisted Ventilation

    The solar assisted ventilation technique increases the difference between the

    internal and external temperature by heating the air in the ventilation stack, thus it

    increases the buoyancy-stack pressure. Solar energy is used to heat the air usually

    stored into hot air solar collectors. This technique is very useful for naturally

    ventilated buildings in urban areas where the wind speed thus the corresponding

    airflows into the occupied areas are reduced.

    The pressure losses for a solar collector depend on the inlet (pi) distributed (pd),and exit (pe) pressure losses:

    edis pppp++=

    (9)

    Depending on the position of the control damper, ip or ep include the

    control damper pressure losses. The stack pressure is:

    zgTTTp ies = ]/1/1[00 , (10)

    Where

    Ti is the inlet air temperature of the collector, usually equal to the indoor

    temperature,

    Te is the exit temperature of the collector (Awbi 1998):

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    31/60

    )]/(exp[)/(/ vpeie qcBwHBATBAT += , (11)

    2211 ww ThThA += (12)

    21 hhB += (13)

    Whereh1, h2 are surface heat transfer coefficients for internal surfaces of the collectorW/m

    2KTw1, Tw2 are surface temperatures of internal surfaces of the collector (C)

    w is the collector width (m)

    H is the height between inlet and outlet openings (m)

    e is the air density at exit, (kg/m3)

    cp is the specific heat of air (J/(kg.K))

    qv is the volumetric air flow rate. (m3/s)

    Figure 3.4: SolarCollectorUsed as: a) Ventilator, b) Heater.

    Tw1h1

    Tw2h2

    Ti

    Te

    Ti

    Glass

    Wall

    Outdoor

    airTo

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    32/60

    ventilation is supported by fans. Such fans may be installed either on stack ducts,

    in walls or windows.

    Summary

    This chapter describes five alternative strategies that can be used in the urban

    context to enhance airflows in naturally ventilated buildings and cope with

    increased levels of noise and outdoor pollution. These techniques include the

    following schemes: balanced stack ventilation, passive downdraught evaporative

    cooling, double skin faade, solar assisted ventilation and fan assisted ventilation.

    All strategies are based on the increased temperature difference of the inlet and

    exhaust air thus the increase of the buoyancy stack pressure. When natural

    ventilation cannot be provided by stack effect, then natural ventilation can be

    supported by fans.

    Usually in these techniques, the inlets of air are located at high level where

    outdoor pollutant concentration is low and wind pressure is increased. Double skin

    facades can also provide extra sound insulation in indoor areas.

    3.6 SelfAssessment Questions

    1. Describe 3 ventilation strategies that are used to enhance airflows in

    naturally ventilated buildings and are based on the stack effect.

    2. Why the use of the balanced stack ventilation system offers advantages

    in urban areas?

    3. Describe the main advantages that double skin facades offer as a

    solution to the constraints of the urban environment

    Problems

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    33/60

    1. Describe using sketches two methods by which natural ventilation can

    be enhanced in the urban environment

    2. Using the basic equations for the calculations of the buoyancy

    pressure difference ps in the case of balanced stack ventilation and

    evaporative cooling explain the increase of the stack pressure in the

    second methodology

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    34/60

    CHAPTER 4 Evaluation of the Natural & HybridVentilation Potential in Urban Environments

    Learning Objectives

    After studying this section you should understand:

    1. The potential of natural ventilation in urban areas2. The impact of natural ventilation on IAQ according to the external pollutants

    concentration3. The potential of night ventilation in urban areas

    4. The efficiency of hybrid ventilation systems in urban areas

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    35/60

    Introduction

    This chapter evaluates the use of natural and hybrid ventilation in urban

    buildings. The evaluation of the different ventilation configurations is based on

    studies that have been carried out in real urban canyons with different

    characteristics.

    This section is split into 2 parts: the first part is focused on the potential of

    natural ventilation and indoor air quality of urban buildings versus the external

    pollutants concentration. This part also presents the night cooling capacity with

    regard to the heat island effect and the reduced wind speeds in urban areas.

    The second part describes the potential of hybrid ventilation in urban sites.

    However, only a minor number of real urban buildings with hybrid ventilation

    systems are known in the literature.

    4.1 Natural Ventilation and IAQ

    Indoor air quality was studied in several office and school buildings. All

    buildings are naturally ventilated and the analysis showed that:

    The air change rate is the determining factor for air quality in naturallyventilated buildings. The greater the supply of external air, the greater the

    presence of external pollutant indoors in the urban environment.

    Concentration of indoor pollutants (sulphur dioxide, nitrogen oxides,carbon monoxide and carbon dioxide) is higher in naturally ventilated

    buildings in polluted urban areas than in air-conditioned ones. In some cases

    though, indoor pollutants concentration may be higher in air-conditioned buildings if transfer of combustion products from heating boilers in the

    occupied spaces occurs via the ventilation system.

    Apart from the ventilation strategy used, the indoor air quality depends onthe use of the building. For example, in school buildingsthe indoor air quality

    inside the classrooms is strongly related to the number of occupants and their

    activities.

    In the case of reduced wind speeds cross ventilation with two or more

    windows into the occupied space can provide adequate airflows and betterindoor air quality. Cross ventilation seems more efficient than single sided

    ventilation under calm conditions (very low wind speed).

    Night ventilation can result in daytime temperature reduction up to 2.5Cunder free floating conditions and 1C under air conditioned operation in

    buildings of the urban context. However, the cooling potential of night

    ventilation for a specific building is a function of many parameters: the

    building design and materials, climatic conditions, site layout, applied air flow

    rate, efficient coupling of air flow with the thermal mass of the building and

    assumed operational conditions.

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    36/60

    4.1.1 Evaluation ofNatural Ventilation and Night Cooling in Urban Areas

    The performance of natural ventilation in the urban environment was assessed in

    real urban canyons through field measurements. The measurements included

    simulations of the air flow processes for ten different canyons in which wind

    speed and temperature data were collected in a number of field measurements in

    the framework of the POLISEuropean research project. The analysis focused on

    single-sided and cross-ventilation configurations for a typical building zone with a

    window opening in each canyon facade. Additionally the performance of night-

    ventilation techniques in urban areas was simulated for the same reference

    building, various simulations have been performed under controlled and free-

    floating operation, when single-sided and cross ventilation are considered, during

    the night period.

    It has been found that:

    The potential of natural ventilation techniques in urban canyons isseriously reduced with the decreased wind speed inside the canyons. Air flow

    reduction may be up to 10 times than the flow that corresponds to undisturbed

    ambient wind conditions.

    The potential of night techniques is significantly reduced due to theincrease of air temperature and the decrease of wind velocity inside canyons

    Figure 4.1: Air Change Rate for Single Sided and Cross Ventilated

    Buildings in Ten Urban Canyons (Geros et al., 2001).

    The effect of the increased ambient temperatures of London due to the heat

    island effect on the effectiveness of stack night ventilation strategies for office

    buildings were also studied by Kolokotroni et al. (2005).

    Real air temperature measurements, carried out in London in 1999/2000 toquantify the London Urban Heat Island Intensity, were used to perform a

    0.2 0.43.0 2.5 2.2

    10.0

    2.9 1.6 2.63.

    12.6

    17.8

    34.6

    4.2

    34.9

    60.0

    52.9

    27.4

    69.3

    10

    20

    30

    40

    50

    60

    70

    80

    Urban Canyon

    Differenceofthea

    irflow

    (inACH)

    Single Sided Ventilati

    Cross Ventilation

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    37/60

    parametric analysis on the cooling demand and potential for night cooling

    ventilation for typical offices. The study was applied by using a thermal and air

    flow simulation tool specifically designed for London office in SE England. Two

    representative weeks were studied, one with extreme hot weather and one with

    typical hot weather in the centre of the London heat island as well as in a rural

    reference site.

    The results showed that the increased urban temperatures due to the heat island

    effect can be taken into account for night cooling as they result in significant

    deviations.

    4.2 Evaluation ofHybrid Ventilation

    Hybrid ventilation in urban areas is highly affected by a number of urban

    parameters like as canyon geometry and layout, wind and temperature distribution

    inside canyons, pollutant concentrations, external noise, and solar access.

    Therefore, effective design of hybrid ventilation in urban buildings requires a

    good understanding of the urban climate characteristics. However, a fewexperimental and theoretical studies on urban buildings with hybrid ventilation are

    known in the literature.

    Some measurements of hybrid systems were carried out in office and educational

    buildings within the frames of the research programme Annex 35 (Hybrid

    Ventilation in New and Retrofitted Office Buildings, IEA)

    The buildings are located in urban areas with moderate levels of air and noise

    pollution and the main ventilation strategy is stack effect with fan assistance. The

    analysis shows that the strategy has very high cooling potential providing good

    indoor air quality and thermal comfort. Additionally the building energy

    consumption was kept in satisfactory levels.

    Other monitoring in residential buildings in the streets canyons of Athens under

    the RESHYVENT European project shows that under calm conditions with wind

    speed lower than 0.5m/sec hybrid ventilation is more efficient than natural

    ventilation with regard to ACH values.

    4.2.1 Performance ofHybrid Ventilation Systems

    The performance of two different hybrid ventilation systems was examined

    within the research programme RESHYVENT: the first configuration comprised a

    mechanical exhaust system and the second one a hybrid ventilation system thatwas developed for the purposes of the European project RESHYVENT. Two

    demand controlled strategies were developed for the RESYVENT hybrid system,

    the first one was based on occupant detection and the second one on CO2 levels.

    The analysis included yearly simulations for four European climates (Athens,

    Nice, Stokholm and Trappes) building and HVAC toolbox.

    The analysis showed that both control strategies have better performance

    regarding the indoor air quality and electrical consumptions of the fan compared

    to the mechanical exhaust system because they optimize the use of natural

    ventilation mode. Detailed description of the analysis of the two hybrid ventilation

    systems is included in chapter 6.

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    38/60

    Summary

    The evaluation of the natural ventilation performance in real urban canyons

    shows that indoor air quality in naturally ventilated buildings depends on various

    parameters like as: the air change rates, the concentration of indoor pollutants, the

    use of buildings and the different configurations of natural ventilation. The

    potential of natural ventilation and night cooling is reduced in urban areas due to

    the increased ambient temperatures and the reduced wind speeds. However,

    studies in the London area showed that the increased urban temperatures due to

    the heat island effect can be taken into account for night cooling as they result in

    significant deviations.

    Limited data on real buildings with hybrid ventilation systems exists in the

    literature. Studies on various urban canyons show that hybrid ventilation can have

    high cooling potential providing good indoor air quality and thermal comfortalthough the urban constraints.

    4.3 Self Assessment Questions

    1. Which natural ventilation configuration is more appropriate in urban

    buildings under calm wind conditions

    2. What parameters affect indoor air quality in naturally ventilatedbuildings?

    3. How the urban environment influences the cooling potential of night

    ventilation

    Problems

    1. What are the advantages of hybrid ventilation in urban buildings

    when compared a. to natural ventilation and b. to mechanical ventilation

    2. Describe techniques to reduce peak air temperatures in naturally

    ventilated buildings

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    39/60

    CHAPTER 5 A Methodology to Calculate The

    Optimum Openings for Naturally Ventilated BuildingsLocated in UrbanCanyons

    Learning Objectives

    After studying this section you should:

    1. Be able to understand and describe the function and principles of themethodology developed for the best practice design of naturally ventilated

    buildings in urban areas

    2. Be able to use the methodology in order to calculate optimal openings innaturally ventilated buildings

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    40/60

    Introduction

    When designing naturally ventilated buildings, it is very important to be able to

    calculate optimal openings to achieve the required airflows for acceptable comfort

    levels. Several tools have been developed to estimate the natural ventilation

    potential and the passive cooling potential of urban buildings versus the climatic

    characteristics of a location.

    This chapter presents a methodology for the best practice design of naturally

    ventilated buildings in urban canyons. This methodology was developed within

    the frames of the research European programme URBVENT and is based on the

    principle of a recurrent neural network model. The designer can use this tool for

    the calculation of airflows in buildings, alternatively with a given database of

    airflows; the tool can be used for the calculation of the optimum opening.

    5.1 Description ofThe Methodology

    The methodology is based on the principle of a recurrent neural network model;

    it provides the designers with database of different parameters and then an

    interpolation of the results is required.

    For example, the tool calculates the airflows in naturally ventilated buildings

    under specific:

    - canyon characteristics

    - openings of a building

    - geometrical and operational characteristics of the building.

    Alternatively, the designer can obtain a large database of airflows for buildings

    configurations and search the database for the corresponding optimum openings.

    Neural network model

    A neural network model is based on establishment of empirical laws obtained

    starting from an experimental data base. Practically this model can be seen as a

    black box establishing the link between input variables which influence the

    studied phenomenon, and an output variable corresponding to the value that we

    seek to predict.

    Figure 5.1: General Outline ofThe Model

    INPUT

    S

    ACH

    Neural

    network

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    41/60

    5.2 Architecture Scenario and Databases

    The models used in the methodology are based on two architectural

    configurations: the single-sided ventilation scenario and the stack-induced

    ventilation scenario. The scenarios were supplied by the Instituto de Engeharia

    Mecnica and obtained from simulations on AIOLOS and COMIS softwares.

    A database of air change rates is obtained through simulations using the validatedtools: AIOLOS and COMIS. Two databases have been created, one for single-

    sided and another for stack induced ventilation by varying the size, location of the

    openings, wind speed and temperature difference between the indoor and outdoor

    environment. The databases are included into the library of the developed model.

    Single Sided Ventilation

    A matrix of 15 million values formed the database for single sided ventilated

    rooms. The model is represented by a small room with one external opening on

    one faade.

    Figure 5.2: Single-Sided Ventilation Room

    StackInduced Ventilation

    A matrix containing 2.6 million values is used as the database for stack induced

    ventilated rooms. The model is represented by the same small room shown in

    figure 5.2, but it was inserted into a multi-storey building and the stack effect was

    induced by a single external opening in the faade and a chimney linking the room

    the roof of the building.

    Figure 5.3: Multi-Storey Building with Stack Induced Ventilated

    Rooms.

    LW

    M

    h

    X

    H

    Number of

    stories : 1-5

    Chimney

    External

    Opening

    Room under

    study

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    42/60

    .

    5.3 Tool forCalculations ofACH orOpenings

    5.3.1 Single Sided Scenario

    In the case of a single sided ventilated room the tool can be used as follows:

    Calculation of ACH

    For the calculation of air change rates the network requires as inputs the values

    of external temperature, the wind velocity, the room volume, the height of the

    opening top of the window, the height of the opening bottom of the window and

    the width of the window. After been trained according to correspondent values of

    air change per hour for the rooms, it can simulate new inputs and predict the value

    the air change rate per hour for the single sided ventilated room (figure 5.1,4).

    Figure5.4: Architecture of the model of calculation of ACH for single sidedventilation.

    Then a graphical interface was developed in order to make it easy for users to use

    the model (figure 5.5).

    Figure 5.5: Graphical Interface to Calculate ACH.

    ACH

    Neuralnetwork

    Externaltemperature Wind speed

    Roomvolume X, H, W

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    43/60

    Calculation ofThe Optimal Opening

    For the calculation of optimal openings the network requires as inputs the values

    of external temperature, the wind velocity, the room volume, the height of the

    opening bottom of the window, the height of the opening top of the window and

    the value of the Air Change Rate per hour. After been trained according to

    correspondent values of air change per hour for the rooms, it can simulate new

    inputs and predict the width of the window for the single sided ventilated room

    (figure 5.6).

    Figure 5.6: Architecture ofThe Model ofCalculation of W forSingleSided Ventilation.

    Figure 5.7 Graphical Interface to Optimise The Opening.

    W

    Neural network

    Externaltemperature Wind speed

    Room

    volume H, X ACH

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    44/60

    5.3.2 StackInduced Scenario

    In the case of stack induced ventilation the tool can be used as follows:

    Calculation of ACHThe techniques used are identical to these for single-sided ventilation:

    For the calculation of the air change rate the network has inputs the values of

    external temperature, the room volume, the height of the opening top, the height of

    the opening bottom of the window and the width of the window, the diameter of

    the chimney, the useful area and the floor level of the room in the building. Then

    the network can predict the value the Air Change Rate per hour for the natural

    ventilated room with stack effect.

    Calculation of the Optimal OpeningFor the calculation of the optimal opening, the network has as inputs the values

    of external temperature, wind velocity, room volume, the height of the opening

    bottom, the height of the opening top of the window, the value of the air change

    rate per hour, the diameter of the chimney, the useful area and the floor level of

    the room in the building. Then the network can predict the width of the window

    for the natural ventilated room with stack effect

    Figure 5.8: Graphical Interface to Calculate ACH.

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    45/60

    Validation ofThe Software

    The airflows that were predicted by the developed tool were compared with real

    experimental data in order to compare the models accuracy.

    The comparison was carried out for both architectural scenarios that are used in

    the model; the single sided case and the stack induced configuration; the

    calculated values are very close to the experimental values.

    Therefore the model can be considered reliable and can be used by designers to

    predict airflow rates or to size openings for naturally ventilated buildings in urban

    areas.

    Summary

    The size of openings or the calculation of airflows is of high importance when

    designing naturally ventilated buildings in urban areas. A methodology for the

    best practice design of naturally ventilated buildings in urban canyons was

    developed within the frames of the research European programme URBVENT. Itis based on the principle of a recurrent neural network model; it provides the

    designers with database of different parameters and then an interpolation of the

    results is required.

    The methodology is based on two architectural configurations: the single-sided

    ventilation scenario and the stack-induced ventilation scenario. The database of

    the air change rates that is included in the tool is obtained through simulations

    using the validated tools: AIOLOS and COMIS. For both architectural scenarios,

    and inputs as the values of external temperature, the wind velocity, the room

    volume, the height of the opening bottom of the window, the height of the opening

    top of the window and the value of the air change rates, the network calculates the

    optimum size of openings. Alternatively, when the size of openings is known the

    methodology can be used for the calculation of the required airflows.

    5.4 SelfAssessment Questions

    1. Describe the principle on which the methodology for the best practice

    design of naturally ventilated buildings is based

    2.

    3. Which two ventilation configurations the methodology uses?

    4. What are the inputs required from the tool when calculating the optimal

    openings of a building

    Problems

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    46/60

    1. Describe using a sketch the procedure of the tool to calculate the airflows

    in naturally ventilated buildings

    2. Calculation of optimal opening of a naturally ventilated room (single

    sided) using the software

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    47/60

    CHAPTER 6 Performance ofHybrid Ventilation in

    Urban Environments Through Experimental Data

    Learning Objectives

    After studying this section you should:

    1. Be able to provide advantages or disadvantages of hybrid ventilation

    systems against natural ventilation in urban buildings2. Describe principles and components of hybrid ventilation systems used in

    urban buildings3. Understand the performance of hybrid ventilation systems versus indoor

    parameters, outdoor parameters and different control strategies

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    48/60

    Introduction

    This chapter presents the impact of the urban environment on hybrid ventilation

    systems. The analysis is based on the results of experimental and theoretical

    analysis in real urban buildings.

    It consists of two parts: the first part gives the comparison among different

    ventilation configurations: natural ventilation, hybrid ventilation and mechanical

    ventilation through monitoring in real urban canyons. The comparison examines

    the different methodologies in terms of air change rates and shows the advantages

    of hybrid ventilation over natural ventilation under specific climatic conditions.

    The second part describes two hybrid ventilation systems; the pilot system and the

    RESHYVENT system that was developed during the unanimous research

    programme. This part presents the performance of the systems against indoor

    parameters, outdoor parameters and different control strategies.

    6.1 Comparison ofHybrid Ventilation, Natural Ventilationand Mechanical Ventilation

    Air-exchange rates and air exchange efficiency were monitored and compared

    for different ventilation systems, under two specific urban canyons of Athens,

    during summer 2002. The compared ventilation systems comprised natural

    ventilation, infiltration, mechanical and hybrid systems.

    Natural ventilation comprised single-sided and cross ventilation configurations.In

    case of single-sided ventilation, openings were considered either, from the canyon

    or, the rear canyon facade. Cross ventilation experiments were studied with two or

    more openings placed at the front and back canyon side.

    Mechanical systems comprised one or two fans in inlet or extract modes.Hybrid ventilation systems focused on fan-assisted natural ventilation, where

    supply and extract fans were used to enhance pressure differences by mechanical

    fan assistance. The fans were installed in the facades adjacent to the canyon or the

    rear facades operating in inlet or extract mode in conjunction with natural

    ventilation. The configurations that were monitored during the analysis are

    described in the following table:

    Figure 6.1: Hybrid Ventilation Systems Monitored During Summer2002 In Athens (Where (a) Refers To Canyon Faade And (b) To Rear Canyon

    Faade)(Niachou et al., 2005)

    1. Mechanical Exhaust (a) and

    Natural Ventilation (b).

    2. Mechanical Inlet (a) and

    Natural Ventilation (b).

    (a)(b) (a)(b)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    49/60

    3.Natural Ventilation (a) andMechanical Exhaust (b).

    4. Natural Ventilation (a) andMechanical Inlet (b).

    5. Mechanical Exhaust (a) and

    Natural Ventilation (a).

    6. Mechanical Inlet (a) and

    Natural Ventilation (a).

    7.Natural Ventilation (a) and

    Mechanical Exhaust (a).

    8.Natural Ventilation (a) and

    Mechanical Inlet (a).

    9.Natural Ventilation with more than one

    windows (a,b) and Mechanical Exhaust (b).

    10. Mechanical Exhaust (a) and Natural

    Ventilation with more than one windows (b).

    11. Mechanical Exhaust (a,b) and

    Natural Ventilation (b).12. Mechanical Exhaust (a), Mechanical Inlet

    (b) and Natural Ventilation (b).

    The experiment was conducted along the tracer gas method during which tracer

    was injected inside the rooms, with internal fans used to homogenize its internal

    concentration and when the internal fans were turned off the tracer gas decay was

    measured.

    (a)(b)(a)(b)

    (a)(b) (a)(b)

    (a)(b) (a)(b)

    (b)(a) (b)(a)

    (b)(a)(b)(a)

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    50/60

    Results & Conclusions

    The comparison of the different ventilation systems showed that:

    Natural cross ventilation results in higher ACH values than single-sidednatural ventilation.

    Hybrid ventilation is associated with rather lower ACH than natural cross-ventilation, but slightly higher ACH under single-sided ventilation or calm

    conditions. However this does not mean that hybrid ventilation may not be of

    use during the summer days when natural ventilation is not an effective means

    of cooling, either due to low winds or due to high ambient temperatures.

    Hybrid ventilation has an advantage over natural under windlessconditions

    Hybrid ventilation provides higher air-exchange rates in comparison withsingle-sided ventilation.In most cases, there is also an improvement relative to

    natural cross ventilation.

    Figure 6.2: Estimated Air Exchange Rates (h-1) for Natural (Single-Sided) And Hybrid Ventilation Experiments at A3 apartment, Under

    Calm Conditions Based on Single-Zone (1,2) And Multi-Zone (3)Methods (Niachou et al., 2005)

    6.2 Performance ofTwo Different Hybrid VentilationSystems

    Within the RESHYVENT research programme, the performance of two hybrid

    ventilation systems was assessed: the pilot ventilation system and the

    RESHYVENT hybrid ventilation system.

    The analysis of the systems efficiency was performed for different urban

    situations, having aspect ratio (H/W) equal to 1, 1.5, 2, 2.5 and 3, and for climates

    of eleven different European cities.

    0

    2

    4

    6

    8

    10

    1 2 3 1 2 3

    AirExchangeR

    ates(h-1)

    Natural Hybrid

    min

    75th percentile

    25th percentile

    average

    max

    Methdologies

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    51/60

    6.2.1 Pilot Ventilation System

    The pilot ventilation system consists of:

    Demand control strategy based on the indoor air quality levels. Differentcontrol functions have been introduced and are based either on the indoor CO 2or on the TVOCs concentrations.

    Low-pressure system supported by wind and buoyancy: An asymmetricand non-ideal flow controller is used. Non-ideal means that no compensation

    for other faade leaks is included in the flow controller model. Only the actual

    characteristic of the controller is considered. The asymmetric controller has a

    separate flow rate for negative flow-directions. The resulting flow is

    temperature compensated according the relation of air densities at actual and

    test conditions.

    Balancing Supply and Exhaust: Two supply/exhaust fans have been usedwith a corresponding performance of 795m3/h at 0 Pa pressure difference. Thefans are installed on the zone external walls facing the rear and the front

    canyon faade. The fans are reversible and they operate on both extract and

    intake mode according to the specific case study.

    Figure 6.3: A representation of the pilot hybrid ventilation systemwith two inlet/extract fans installed at the two external building walls.

    An inverse operation of the fans is considered on the right photo(Niachou and Santamouris, 2005)

    6.2.2 RESHYVENT Hybrid Ventilation System

    The system consists of self-regulating air inlets, DC fan, motorized damper,

    flow meter, central control unit, CO2 sensors and ductwork. The demand control

    of the ventilation system is based on monitoring of CO2 in rooms. There is a CO2sensor and a self-regulating air inlet in each room. The self-regulating inlets are

    usually positioned above windows. These inlets are able to maintain a constant

    flow rate for the pressure difference across the facade higher than 1 Pa.

    The hybrid ventilation system was simulated to operate when the CO2concentration in the apartment increased to 1200 ppm. The exhaust fan is used

    when the air exhaust through the duct is lower than the demanded flow.

    Supply fan

    Exhaust fan

    Supply fan

    Exhaust fan Supply fan

    Exhaust fan

    Supply fan

    Exhaust fan

  • 8/3/2019 Ventilation for URBAN BUILDINGS.. Natural and Hybrid Ventilation in the Urban Environment March 2006

    52/60

    Pressure-dependent grilles of the system were also simulated in order to realize

    better the canyon effect.

    The pressure-dependent inlet grilles have the following characteristics, when the

    pressure difference is above 1Pa:

    Qv=CP

    n

    and C=25.96dm

    3

    /s per 1 Pa , n=0.50

    The inlet grilles are considered full open between 0 Pa and 0.5 Pa. Above 0.5 Pa

    the inlet grilles start to control and there is not longer a standard relation between

    pressure and airflow. The ventilation system is examined either with natural or

    hybrid exhaust mode. In the natural ventilation exhaust mode, the exhaust airflow

    rate from the duct is affected by the natural driving forces. When the exhaust flow

    rate through the duct is lower than the demanded flow rate, then the fan starts to

    operate. A minimum of 21dm3/s is considered for the air exhaustion through the

    duct.

    Figure 6.4: Representation ofThe RESHYVENT Hybrid VentilationSystem For Moderate Climates (Niachou and Santamouris, 2005)

    6.2.3 Results & Conclusions

    The performance of the two hybrid system was assessed considering the following

    parameters:

    Canyon Geometry Canyon Layout Outdoor Urban Air Characteristics Indoor Pollutant Emissions Buildi