Ventilation Sizing Summary for AHU-E1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2004 Design Condition Minimum flow (heating) Occupant Diversity 0.750 Uncorrected Ventilation Airflow Rate 1720 CFM System Ventilation Efficiency 0.641 Design Ventilation Airflow Rate 2682 CFM
2. Space Ventilation Analysis Table
Hourly Analysis Program v4.50 Page 1 of 4
Ventilation Sizing Summary for AHU-E1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (CFM) (ft²) (CFM/ft²) Occupancy (CFM/person) Effectiveness (CFM) (CFM) Efficiency
E1-025
025 - Perc Fac Studio 1 245 611.9 0.06 3.0 10.00 0.80 83 59 0.868
E1-027
027 - Perc Fac Studio 1 245 611.9 0.06 3.0 10.00 0.80 83 59 0.868
E1-029
029 - Perc Fac Studio 1 245 611.9 0.06 3.0 10.00 0.80 83 59 0.868
E1-031
031 - Perc Fac Studio 1 249 621.9 0.06 3.0 10.00 0.80 84 60 0.871
E1-026
026 - Perc AI Studio 1 108 269.8 0.06 3.0 10.00 0.80 58 39 0.674
E1-028
028 - Perc AI Studio 1 108 269.9 0.06 3.0 10.00 0.80 58 39 0.674
E1-030
030 - Perc AI Studio 1 111 277.3 0.06 3.0 10.00 0.80 58 39 0.683
E1-032
032 - Perc AI Studio 1 116 289.0 0.06 3.0 10.00 0.80 59 40 0.697
E1-034
034 - File Archives Rm 1 250 624.6 0.12 0.0 0.00 0.80 94 75 0.834
E1-099A
099B - Corridor 1 292 730.5 0.06 0.0 0.00 0.80 55 44 1.021
099A - Corridor 1 679 1696.3 0.06 0.0 0.00 0.80 127 102 1.021
099G - Stairs 1 209 522.0 0.00 0.0 0.00 0.80 0 0 1.209
099H - Stairs 1 111 276.6 0.00 0.0 0.00 0.80 0 0 1.209
099E - Corridor 1 79 198.0 0.06 0.0 0.00 0.80 15 12 1.021
000 - Perc Storage Rm 1 160 399.7 0.06 0.0 0.00 0.80 30 24 1.021
099D - Corridor 1 37 91.3 0.06 0.0 0.00 0.80 7 5 1.021
E1-023
023 - Locker Area 1 136 339.7 0.06 0.0 0.00 0.80 25 20 1.021
E1-111
111 - Conf Rm 1 167 418.4 0.06 8.0 5.00 0.80 81 55 0.723
E1-113
113 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-115
115 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-117
117 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-119
119 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-121
121 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-123
Hourly Analysis Program v4.50 Page 2 of 4
Ventilation Sizing Summary for AHU-E1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
123 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.785
E1-127
127 - Lounge 1 93 232.2 0.06 5.0 5.00 0.80 49 33 0.685
E1-114
114 - Work Room 1 113 282.0 0.06 0.0 5.00 0.80 21 17 1.021
E1-120B
120B - Ugrad Director 1 102 253.9 0.06 1.0 5.00 0.80 25 19 0.960
120C - Ugrad Advisor 1 75 188.0 0.06 1.0 5.00 0.80 20 15 0.938
120D - Ugrad Recorder 1 74 183.9 0.06 1.0 5.00 0.80 20 15 0.936
E1-120A
120A - Ugrad Stud File R 1 109 272.7 0.06 1.0 5.00 0.80 27 20 0.964
E1-120
120 - Reception Area 1 245 612.5 0.06 14.0 5.00 0.80 133 89 0.664
E1-120E
120E - Work Area 1 146 365.7 0.06 0.0 5.00 0.80 27 22 1.021
120F - Grad Recorder 1 76 189.1 0.06 1.0 5.00 0.80 20 15 0.939
120G - Doctoral Clerk 1 74 184.9 0.06 1.0 5.00 0.80 20 15 0.937
E1-120N
120R - Grad Stud File Rm 1 115 288.6 0.06 1.0 5.00 0.80 28 21 0.967
120P - Grad Exam 1 37 93.2 0.06 2.0 5.00 0.80 19 13 0.686
120N - Grad Exam 1 43 107.1 0.06 2.0 5.00 0.80 21 14 0.730
E1-120H
120H - Grad Advisor 1 74 183.8 0.06 1.0 5.00 0.80 20 15 0.936
120J - Grad Director 1 95 238.4 0.06 1.0 5.00 0.80 24 18 0.956
100 - Storage 1 24 61.0 0.12 0.0 0.00 0.80 9 7 0.834
E1-120K
120K - Kinchenette/Loung 1 161 401.3 0.06 7.0 5.00 0.80 74 50 0.749
120L - Storage 1 65 163.0 0.12 0.0 0.00 0.80 24 20 0.834
120M - Grad Oral Exam Rm 1 164 411.2 0.06 10.0 5.00 0.80 93 62 0.641
E1-199A
199A - Corridor 1 863 2156.6 0.06 0.0 0.00 0.80 162 129 1.021
199K - Stairs 1 222 555.4 0.00 0.0 0.00 0.80 0 0 1.209
199L - Stairs 1 125 313.6 0.00 0.0 0.00 0.80 0 0 1.209
191 - Mop Closet 1 16 40.4 0.00 0.0 0.00 0.80 0 0 1.209
199B - Corridor 1 86 215.5 0.06 0.0 0.00 0.80 16 13 1.021
199C - Corridor 1 23 58.3 0.06 0.0 0.00 0.80 4 3 1.021
E1-120T
120T - Corridor 1 252 629.0 0.06 0.0 0.00 0.80 47 38 1.021
199G - Corridor 1 43 106.6 0.06 0.0 0.00 0.80 8 6 1.021
E1-033
033 - CFS Rm 1 137 343.6 0.12 0.0 0.00 0.80 52 41 0.834
091 - Mop Closet 1 20 51.1 0.00 0.0 0.00 0.80 0 0 1.209
E1-190
190 - Elec Closet 1 67 168.7 0.00 0.0 0.00 0.80 0 0 1.209
Hourly Analysis Program v4.50 Page 3 of 4
Ventilation Sizing Summary for AHU-E1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
Totals (incl. Space Multipliers) 8237 1720 0.641
Hourly Analysis Program v4.50 Page 4 of 4
Ventilation Sizing Summary for AHU-E2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2004 Design Condition Minimum flow (heating) Occupant Diversity 0.750 Uncorrected Ventilation Airflow Rate 2781 CFM System Ventilation Efficiency 0.768 Design Ventilation Airflow Rate 3619 CFM
2. Space Ventilation Analysis Table
Hourly Analysis Program v4.50 Page 1 of 5
Ventilation Sizing Summary for AHU-E2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (CFM) (ft²) (CFM/ft²) Occupancy (CFM/person) Effectiveness (CFM) (CFM) Efficiency
E2-219
219 - Faculty Studio 1 138 346.0 0.06 3.0 10.00 0.80 63 43 0.778
E2-221
221 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-223
223 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-225
225 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-227
227 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-229
229 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-231
231 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-233
233 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-235
235 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-222
222 - Faculty Studio 1 138 346.2 0.06 3.0 10.00 0.80 63 43 0.779
E2-224
224 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-226
226 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-228
228 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-230
230 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-232
232 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-234
234 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-236
236 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-238
238 - Faculty Studio 1 178 444.2 0.06 3.0 10.00 0.80 71 49 0.838
E2-237
237 - Lounge 1 93 231.9 0.06 3.0 5.00 0.80 36 25 0.847
E2-299A
299A - Corridor 1 717 1791.8 0.06 0.0 0.00 0.80 134 108 1.049
299F - Stairs 1 214 533.9 0.00 0.0 0.00 0.80 0 0 1.237
Hourly Analysis Program v4.50 Page 2 of 5
Ventilation Sizing Summary for AHU-E2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
299G - Stairs 1 130 324.0 0.00 0.0 0.00 0.80 0 0 1.237
291 - Mop Closet 1 16 40.4 0.00 0.0 0.00 0.80 0 0 1.237
299B - Corridor 1 30 74.0 0.06 0.0 0.00 0.80 6 4 1.049
E2-319
319 - Faculty Studio 1 138 346.0 0.06 3.0 10.00 0.80 63 43 0.778
E2-321
321 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-323
323 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-325
325 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-327
327 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-329
329 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-331
331 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-333
333 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-335
335 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-322
322 - Faculty Studio 1 134 335.7 0.06 3.0 10.00 0.80 63 43 0.770
E2-324
324 - Faculty Studio 1 152 380.7 0.06 3.0 10.00 0.80 66 45 0.803
E2-326
326 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-328
328 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-330
330 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-332
332 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-334
334 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-336
336 - Faculty Studio 1 159 396.7 0.06 3.0 10.00 0.80 67 46 0.813
E2-338
338 - Faculty Studio 1 173 431.8 0.06 3.0 10.00 0.80 70 48 0.832
E2-337
337 - Lounge 1 93 232.2 0.06 4.0 5.00 0.80 42 29 0.780
E2-399A
399A - Corridor 1 717 1791.8 0.06 0.0 0.00 0.80 134 108 1.049
399F - Stairs 1 210 524.4 0.00 0.0 0.00 0.80 0 0 1.237
Hourly Analysis Program v4.50 Page 3 of 5
Ventilation Sizing Summary for AHU-E2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
399G - Stairs 1 121 301.4 0.00 0.0 0.00 0.80 0 0 1.237
391 - Mop Closet 1 16 40.4 0.00 0.0 0.00 0.80 0 0 1.237
399B - Corridor 1 30 74.0 0.06 0.0 0.00 0.80 6 4 1.049
E2-419
419 - Faculty Studio 1 136 340.7 0.06 3.0 10.00 0.80 63 43 0.774
E2-421
421 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-423
423 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-425
425 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-427
427 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-429
429 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-431
431 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-433
433 - Faculty Studio 1 143 356.7 0.06 3.0 10.00 0.80 64 44 0.787
E2-422
422 - Faculty Studio 1 133 333.7 0.06 3.0 10.00 0.80 63 43 0.768
E2-424
424 - Faculty Studio 1 145 362.7 0.06 3.0 10.00 0.80 65 44 0.791
E2-426
426 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-428
428 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-430
430 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-432
432 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-434
434 - Faculty Studio 1 155 388.7 0.06 3.0 10.00 0.80 67 46 0.808
E2-436
436 - Faculty Studio 1 169 423.1 0.06 3.0 10.00 0.80 69 48 0.828
E2-437
437 - Lounge 1 90 224.0 0.06 4.0 5.00 0.80 42 28 0.770
E2-499A
499A - Corridor 1 575 1438.4 0.06 0.0 0.00 0.80 108 86 1.049
499F - Stairs 1 219 546.3 0.00 0.0 0.00 0.80 0 0 1.237
499G - Stairs 1 132 329.8 0.00 0.0 0.00 0.80 0 0 1.237
491 - Mop Closet 1 16 40.4 0.00 0.0 0.00 0.80 0 0 1.237
499B - Corridor 1 30 74.0 0.06 0.0 0.00 0.80 6 4 1.049
E2-290
Hourly Analysis Program v4.50 Page 4 of 5
Ventilation Sizing Summary for AHU-E2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
290 - Elec Closet 1 68 170.0 0.00 0.0 0.00 0.80 0 0 1.237
E2-390
390 - Elec Closet 1 67 166.6 0.00 0.0 0.00 0.80 0 0 1.237
E2-490
490 - Elec Closet 1 67 167.7 0.00 0.0 0.00 0.80 0 0 1.237
Totals (incl. Space Multipliers) 11738 2781 0.768
Hourly Analysis Program v4.50 Page 5 of 5
Ventilation Sizing Summary for AHU-N1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2004 Design Condition Minimum flow (heating) Occupant Diversity 0.750 Uncorrected Ventilation Airflow Rate 1806 CFM System Ventilation Efficiency 0.707 Design Ventilation Airflow Rate 2555 CFM
2. Space Ventilation Analysis Table
Hourly Analysis Program v4.50 Page 1 of 4
Ventilation Sizing Summary for AHU-N1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (CFM) (ft²) (CFM/ft²) Occupancy (CFM/person) Effectiveness (CFM) (CFM) Efficiency
N1-013
013 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-011
011 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-009
009 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-007
007 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-005
005 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-003
003 - Perc Prac Rm 1 40 202.5 0.06 2.0 10.00 0.80 40 27 0.707
N1-012
012 - Perc Prac Rm 1 41 206.8 0.06 2.0 10.00 0.80 41 27 0.707
N1-010
010 - Perc Prac Rm 1 41 206.8 0.06 2.0 10.00 0.80 41 27 0.707
N1-008
008 - Perc Prac Rm 1 41 206.8 0.06 2.0 10.00 0.80 41 27 0.707
N1-002
002 - Perc Prac Rm 1 41 208.3 0.06 2.0 10.00 0.80 41 27 0.707
N1-004
004 - Perc Prac Rm 1 41 208.3 0.06 2.0 10.00 0.80 41 27 0.707
N1-006
006 - Perc Prac Rm 1 41 208.3 0.06 2.0 10.00 0.80 41 27 0.707
N1-001
001 - Lounge 1 55 314.2 0.06 5.0 5.00 0.80 55 38 0.707
N1-014
014 - Building Serv Rm 1 51 512.0 0.06 2.0 5.00 0.80 51 38 0.707
N1-015
015 - Lounge 1 105 903.2 0.06 6.0 5.00 0.80 105 77 0.707
N1-017
017 - Perc. Prac Rm 1 39 182.3 0.06 2.0 10.00 0.80 39 26 0.707
N1-019
019 - Perc. Prac Rm 1 39 187.8 0.06 2.0 10.00 0.80 39 26 0.707
N1-021
021 - Perc. Prac Rm 1 38 179.2 0.06 2.0 10.00 0.80 38 26 0.707
N1-099
099 - Corridor 1 49 650.2 0.06 0.0 0.00 0.80 49 39 0.707
099C - Corridor 1 21 281.7 0.06 0.0 0.00 0.80 21 17 0.707
N1-105
105 - Lounge 1 136 819.0 0.06 12.0 5.00 0.80 136 94 0.707
Hourly Analysis Program v4.50 Page 2 of 4
Ventilation Sizing Summary for AHU-N1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
N1-100
100 - Reception Area 1 109 618.9 0.06 10.0 5.00 0.80 109 75 0.707
100L - Corridor 1 6 85.7 0.06 0.0 0.00 0.80 6 5 0.707
N1-100F
100F - Director 1 25 253.9 0.06 1.0 5.00 0.80 25 19 0.707
100G - Assoc Director 1 21 191.2 0.06 1.0 5.00 0.80 21 15 0.707
N1-100A
100A - Video/Conf Rm 1 97 461.5 0.06 10.0 5.00 0.80 97 65 0.707
N1-101
101 - Lobby 1 172 1716.0 0.06 7.0 5.00 0.80 172 129 0.707
N1-100B
100B - File Rm/Staff 1 56 491.6 0.06 3.0 5.00 0.80 56 41 0.707
N1-100K
100K - Corridor 1 25 331.2 0.06 0.0 0.00 0.80 25 20 0.707
N1-100C
100C - Work Area 1 22 292.3 0.06 0.0 5.00 0.80 22 18 0.707
100D - Staff Work Area 1 15 120.9 0.06 1.0 5.00 0.80 15 11 0.707
100E - Staff Work Area 1 16 129.5 0.06 1.0 5.00 0.80 16 12 0.707
N1-208
208 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-206
206 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-204
204 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-202
202 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-211
211 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-209
209 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-207
207 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-205
205 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-203
203 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.707
N1-199D
199D - Vestibule 1 20 263.0 0.06 0.0 0.00 0.80 20 16 0.707
N1-199E
199E - Vestibule 1 10 128.6 0.06 0.0 0.00 0.80 10 8 0.707
N1-215
215 - Lounge 1 159 869.1 0.06 15.0 5.00 0.80 159 108 0.707
N1-299
299 - Corridor 1 64 847.9 0.06 0.0 0.00 0.80 64 51 0.707
Hourly Analysis Program v4.50 Page 3 of 4
Ventilation Sizing Summary for AHU-N1Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
N1-016
016 - Security Room 1 12 158.1 0.06 0.0 5.00 0.80 12 9 0.707
N1-018
018 - Recycling 1 26 175.0 0.12 0.0 0.00 0.80 26 21 0.707
N1-100H
100H - Assoc Director 1 21 200.5 0.06 1.0 5.00 0.80 21 16 0.707
100 - Office 1 18 150.6 0.06 1.0 5.00 0.80 18 13 0.707
N1-090
090 - Elec Closet 1 11 142.9 0.06 0.0 0.00 0.80 11 9 0.707
N1-201
201 - Lounge 1 27 366.3 0.06 0.0 5.00 0.80 27 22 0.707
Totals (incl. Space Multipliers) 2555 1806 0.707
Hourly Analysis Program v4.50 Page 4 of 4
Ventilation Sizing Summary for AHU-N2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2004 Design Condition Minimum flow (heating) Occupant Diversity 0.750 Uncorrected Ventilation Airflow Rate 1138 CFM System Ventilation Efficiency 0.704 Design Ventilation Airflow Rate 1616 CFM
2. Space Ventilation Analysis Table
Hourly Analysis Program v4.50 Page 1 of 3
Ventilation Sizing Summary for AHU-N2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (CFM) (ft²) (CFM/ft²) Occupancy (CFM/person) Effectiveness (CFM) (CFM) Efficiency
N2-308
308 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-306
306 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-304
304 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-302
302 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-311
311 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-309
309 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-307
307 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-305
305 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-303
303 - Faculty Studio 1 67 396.7 0.06 3.0 10.00 0.80 67 46 0.704
N2-301
301 - Lounge 1 59 370.4 0.06 5.0 5.00 0.80 59 41 0.704
N2-313
313- Lounge 1 92 480.0 0.06 9.0 5.00 0.80 92 63 0.704
N2-315
315 - Faculty Lounge 1 154 797.8 0.06 15.0 5.00 0.80 154 104 0.704
N2-399
399 - Corridor 1 61 807.5 0.06 0.0 0.00 0.80 61 48 0.704
N2-408
408 - ADI Admin Secr 1 22 210.4 0.06 1.0 5.00 0.80 22 16 0.704
N2-406
406 - File/Stor/RevArea 1 34 455.5 0.06 0.0 5.00 0.80 34 27 0.704
N2-404
404 - Work Area/Kitchen 1 22 291.2 0.06 0.0 5.00 0.80 22 17 0.704
N2-402
402 - Small Conf Rm 1 93 413.3 0.06 10.0 5.00 0.80 93 62 0.704
N2-401
401 - Dean's Office 1 41 456.9 0.06 1.0 5.00 0.80 41 31 0.704
N2-403
403 - Dean's AdminAssis 1 23 218.7 0.06 1.0 5.00 0.80 23 17 0.704
N2-405
405 - EAD Admin Secr 1 22 211.1 0.06 1.0 5.00 0.80 22 16 0.704
N2-407
Hourly Analysis Program v4.50 Page 2 of 3
Ventilation Sizing Summary for AHU-N2Project Name: 10-058 IU Jacobs - ESB (Load Design) 07/19/2012 Prepared by: Applied Engineering 04:29PM
407 - Exec Assoc Dean 1 36 396.2 0.06 1.0 5.00 0.80 36 28 0.704
N2-409
409 - Assoc Dean for In 1 34 364.4 0.06 1.0 5.00 0.80 34 26 0.704
N2-499
499 - Corridor 1 65 872.3 0.06 0.0 0.00 0.80 65 52 0.704
099F - Stairs 1 0 331.1 0.00 0.0 0.00 0.80 0 0 0.704
199J - Stairs 1 0 485.0 0.00 0.0 0.00 0.80 0 0 0.704
299E - Stairs 1 0 365.4 0.00 0.0 0.00 0.80 0 0 0.704
399E - Stairs 1 0 359.5 0.00 0.0 0.00 0.80 0 0 0.704
499E - Stairs 1 0 358.1 0.00 0.0 0.00 0.80 0 0 0.704
N2-413
413 - Reception Area 1 105 646.5 0.06 9.0 5.00 0.80 105 73 0.704
N2-415
415 - Large Conf Rm 1 149 655.8 0.06 16.0 5.00 0.80 149 99 0.704
Totals (incl. Space Multipliers) 1616 1138 0.704
Hourly Analysis Program v4.50 Page 3 of 3
EQp1 LEED Review Response 07/20/12 Project Jacobs School of Music North Studio Building By Applied Engineering Services (AES) Question 1: Please provide a detailed narrative and calculations or resubmit the Submittal Template to include a detailed narrative and calculations describing the procedure employed by the project in the IAQ analysis (Ventilation Rate Procedure). Include in this detailed narrative specific information regarding the design outside air intake volumes for each air handling unit. Additionally, provide Ventilation Rate Procedure calculations for each air handling unit. For systems with multiple ventilation zones, the calculations should be sufficient to show that the critical zone was correctly determined, and that the peak occupancies predicted are aligned with those reported in other credits, and should include corrections for zone air distribution effectiveness (Ez) according to ASHRAE 62.1 Section 6.2.2.2, and ventilation efficiency (Ev) according to Section 6.2.5 Keep in mind that Ev can be determined according to Table 6-3 using the maximum zone primary outdoor air fraction (Zp) among all the zones served by the system, or according to Appendix A. Also note that the calculations must be conducted for the wort-case conditions (generally heating mode), and the Ez is most commonly 0.8 during heating mode. If the value for Ez is great than 0.8 for this project, please include a short description in the narrative supporting the use of the Ez value used. AES Response 1: The ventilation airflows were determined in Carrier’s design program, HAP 4.50. A copy of these calculations for each of the four AHUs serving the building are included in the attached file, “EQp1 - Attached Ventilation Calculations”. The design ventilation rates are summarized in the following table.
Table 1: Ventilation Airflow Rates AHU-E1 2700 CFM AHU-E2 3600 CFM AHU-N1 2550 CFM AHU-N2 1600 CFM
HAP follows ASHRAE 62.1 procedures to determine the ventilation rate for each AHU. All ventilation is introduced via the dedicated outside air system (DOAS). This unit preconditions the outside air before supplying the four distribution air handlers. The DOAS unit is a variable volume unit which varies from 5,700 cfm to 10,450 cfm. The DOAS responds to CO2 monitors in variable occupancy spaces and common return ducts throughout the building. On a call for increased ventilation by a CO2 monitor, the percentage of outside air is increased by 5% to the associated air handler. After 20 minutes, the monitor is polled again and the air volume is increased again if required. After the air handler is at it’s maximum ventilation rate, a further call from the CO2 monitor signals an alarm at the campus monitoring station. In spaces without variable occupancy, offices, studios, practice rooms etc, the minimum VAV box air flows are designed to provide required ventilation at minimum (normal) air handler ventilation percentage.
A diversity factor of 75% was applied during the ventilation calculation to account for people moving from room to room in the building but not necessarily occupying every space in the building. The CO2 monitors coupled with demand ventilation in the building allow us to take advantage of this diversity. The FTE occupancy number was divided by the number of people in the ventilation summary to determine the diversity fraction.
G
C.8
K.9
M.8M
H
J
N
E
K
D.3
H.6
K.6
D.8
ML
P
H
F
15.9 24.820191817161514 2210 121187
D.3
H.6
K.6
D.8
ML
P
H
F
10 121187 15.9 24.820191817161514 22
G
C.8
K.9
M.8M
H
J
N
E
K
G
C.8
K.9
M.8M
H
J
N
E
K
15.9 24.820191817161514 2210 121187
D.3
H.6
K.6
D.8
ML
P
H
F
M-402MECHANICAL ROOM PLANSPENTHOUSE
PENTHOUSE MECHANICAL ROOM DUCTWORK PLAN
PENTHOUSE MECHANICAL ROOM PIPING PLAN
CERTIFICATION
08031
February 14, 2011
Browning Day Mullins Dierdorf ArchitectsArchitectureLandscape ArchitecturePlanning
626 North Illinois StreetIndianapolis, Indiana 46204P: 317.635.5030F: 317.634.5409W: www.bdmd.com
Checked By:Scale:Issue Date:Revision # - Date of Issue:
Drawn By:Project No.:
ISSUED FORCONSTRUCTION
INDIANA UNIVERSITY:JACOBS SCHOOL OFMUSIC - EAST STUDIOBUILDINGBloomington, IN 47405
See Drawing
P:F:W:
Flad ArchitectsAssociate Architect / Structural Engineer
644 Science DriveMadison, WI 53711
608.238.2661608.238.6727 www.flad.com
P:F:W:
Bledsoe Riggert GuerrettazCivil Engineer
1351 West Tapp RoadSuite 300Bloomington, IN 47403
812.336.8277812.336.0817 www.brgcivil.com
P:F:W:
Applied Engineering ServicesUtility Relocation / M.E.P. Engineer
9100 Keystone CrossingSuite 200Indianapolis, IN 46240
317.810.4141317.810.4140 www.applied-e-s.com
P:F:W:
Kirkegaard AssociatesAcoustical Consultant
954 Pearl StreetBoulder, CO 80302
303.442.1706303.442.0714 www.kirkegaard.com
PENTHOUSE MECHANICAL ROOM EQUIPMENT PLAN
M-602HVAC SCHEDULES
CERTIFICATION
08031
February 14, 2011
Browning Day Mullins Dierdorf ArchitectsArchitectureLandscape ArchitecturePlanning
626 North Illinois StreetIndianapolis, Indiana 46204P: 317.635.5030F: 317.634.5409W: www.bdmd.com
Checked By:Scale:Issue Date:Revision # - Date of Issue:
Drawn By:Project No.:
CONSTRUCTION DOCUMENTS
INDIANA UNIVERSITY:JACOBS SCHOOL OFMUSIC - EAST STUDIOBUILDINGBloomington, IN 47405
See Drawing
P:F:W:
Flad ArchitectsAssociate Architect / Structural Engineer
644 Science DriveMadison, WI 53711
608.238.2661608.238.6727 www.flad.com
P:F:W:
Bledsoe Riggert GuerrettazCivil Engineer
1351 West Tapp RoadSuite 300Bloomington, IN 47403
812.336.8277812.336.0817 www.brgcivil.com
P:F:W:
Applied Engineering ServicesUtility Relocation / M.E.P. Engineer
9100 Keystone CrossingSuite 200Indianapolis, IN 46240
317.810.4141317.810.4140 www.applied-e-s.com