27
VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 kA price and order entry guide

VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

  • Upload
    others

  • View
    240

  • Download
    9

Embed Size (px)

Citation preview

Page 1: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

VersaRupter MV indoor switch5-38 kV, 200-1200 A, 40 & 61 kAprice and order entry guide

Page 2: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

3

Table of Contents

VersaRupter Overview

General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

VersaRupter Switch Selection Guide

Style Number Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Operating Mechanism

Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Snap Action Mechanisms (K-mechanism) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Stored Energy Mechanisms (A-mechanism) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Electrical Control Options

Shunt Trip or Shunt Close & Auxiliary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Operating Handles

Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Chain Drive Handles without Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Chain Drive Handles with Mechanical Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Direct Drive Handle & Type HE Shaft Drive Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Motor Operator Option

Type NM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Grounding Switches

Type E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Fuse Options

Fuse Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Type CEF Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Miscellaneous Accessories and Renewal Parts

Back Connection Kit, Shaft Extensions, & Splined Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Appendix

Smart Style Number Code Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20VersaRupter Price and Order Entry Worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Renewal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Notes

Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Page 3: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

4

VersaRupter OverviewGeneral Description

VersaRupter is a general purpose, three-pole,loadbreak switch that offers switchgear owners andassemblers the advantages of an advanced interruptingtechnology and proven, dependable performance in acompact design. The switch is available to switchgearassemblers as a building block for metal-enclosed andpad-mounted switchgear applications in ratings from 5– 38 kV.

The standard VersaRupter switch includes a heavy-dutysteel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanismand current-carrying components, including blade-typeinterrupters with cast hinges and jaw connectors.

Optional accessories and features include a variety ofoperating handles, a motor operator, auxiliary switches,a shunt trip device, fuse bases, mechanical fuse tripping,grounding switches, mechanical door interlocking andkey interlocking.

5 – 38 kV VersaRupter

VersaRupter at a Glance...

Applications Metal-enclosed and padmount switchgear for utility distribution, capacitor switching, industrial, mining and commercial installations

Ratings Voltage Loadbreak Current Momentary5 – 27 kV 200, 600 & 1200 A 40 kA momentary / 40 kA fault close38 kV 600 & 800 A 40 kA momentary / 30 kA fault close15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

Standards ANSI C37.20.4IEC199, 265 (100 close/open at 630 A), 420, 694For UL listings see Tables 1A and 1B.

Experience Over 500,000 switches installed in over 50 countries worldwide

Actuators Manual operation with choice of direct side drive, front chain or front shaft driveOptional motor operation, optional shunt tripLeft or right side mounting available with most options

Options Grounding switch, fuse base, mechanical fuse tripping, auxiliary switches, key interlocks

Quality ISO-9001Complete ANSI design test reports100% production testing

Page 4: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

5

Weights and Dimensions

Dimensions (Inches)

Width* Height Depth Optional Weight Ref.Switch Max kV/ Phase Spacing (W) (H2) (A3) Shaft Ext. (N) Lbs. Drawing

8 kV K-mechanism 22.6822.68 15.51 4.80 71 S-20183

P = 5.91" (150 mm) A-mechanism 22.41

15 kV K-mechanism 24.2523.62 20.12 4.80 75 S-20184

P = 6.69" (170 mm) A-mechanism 23.98

15 kV (61 kA) K-mechanism 29.3724.17 21.55 7.32 110 S-20346

P = 9.25" (235 mm) A-mechanism 29.10

17 kV K-mechanism 29.3723.62 20.12 7.32 93 S-20348

P = 9.25" (235 mm) A-mechanism 29.10

27 kV K-mechanism 32.5223.62 20.12 7.32 95 S-20347

P = 10.8" (275 mm) A-mechanism 32.25

38 kV K-mechanism 46.6134.25 33.46 10.08 220 NHP 241285

P = 14.1" (360 mm) A-mechanism 46.34

* Width for K-mechanism based on standard shaft (K3) where Y dimension = 3.77"Other options are: K2 snap action mechanism where Y = 2.69"

K5 snap action mechanism where Y = 5.26"

* Width for A-mechanism based on standard shaft (A3) where Y dimension = 3.50"Other options are: A4 stored energy mechanism where Y = 4.80"

A6 stored energy mechanism where Y = 6.90"

Note: See definitions for K&A mechanisms on page 7.

Page 5: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

6

VersaRupter Switch Selection GuideStyle Number Reference

The VersaRupter switch product line has a structured, smart style number ordering system. Thecomplete style number is built up of 18 customer selection characters. Each character identifies fea-tures or functions than can be incorporated into the switch application.

The first nine characters of the style number define the basic switch. The next two characters defineelectrical control options. Four characters are used to define handle operator options and the finalfour define motor operator requirements. See page 20 for a complete list of code selections.

How To Order

Select the required option codes to fill in the smart style number. The total list price is computed by adding the individual list prices for each of the selections.

Step 1: Select basic switch (characters 1 – 9)Study the mechanism selection guide on page 7 to determine which mechanism is compatible with the features you require. Then select the 9 character switch smart style number code from Table 1A (K-mechanism) or Table 1B (A-mechanism).

Step 2: Select shunt trip and auxiliary switch options (characters 10 & 11)Select codes for the desired electrical control options from Tables 2 and 3 (page 10).

Step 3: Select handle operator options (characters 12 – 15)Study the handle operator guide on page 11 to review features offered and compatibility.Select the smart style number code for the desired handle operator and location from the appropriate tables on pages 12, 13 and 14.Note: If no handle is required this field is filled with zeros “0000”.

Step 4: Select motor operator options (characters 16 – 18)Select the desired motor operator and location code from Table 8 on page 15.Note: If no motor is required this field is filled with zeros “000”.

Step 5: Identify other optional accessories to be ordered as separate itemsSee Table 9 for ground switches.See Tables 10 – 14 for fuse bases.See Table 15 for CEF fuses.See page 19 for back connection kit and other accessories.

Sample Style Number

V K3 B 15 6 4 U 0 6 CDLB 000

Switch Mechanism Type

Switch Frame Size

Switch Max kV Rating

Switch Current Rating

Switch Momentary Rating

Motor Operator

Handle Operator

Auxiliary Switch

Shunt Trip

UL Listed

Page 6: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

7

Operating MechanismSelection Guide

Snap Action K-mechanism

The K-mechanism is a single spring snap action device.The switch opens or closes by charging the spring pastdead center using one of the manual operating handles.The K-mechanism may be used with all handle optionsas well as with type NM motor operators. The K-mecha-nism cannot be used for shunt trip applications.

n Use K-mechanism if you need chain drive handles

Stored Energy A-mechanism

The A-mechanism is a dual spring stored energy devicethat is well suited for remote tripping applications. When shunt tripping or mechanical fusetripping is specified, the type A-mechanism must beused. In normal operation, the opening spring ischarged and latched by an operating handle or by a motor operator. The VersaRupter is thenopened by any or several methods:

n Movement of the operating handlen Motor operatorn Electrical signal to a shunt trip devicen Mechanical fuse tripping linkage

1 Shunt trip option provides for operation by local push button or remote signal. Shunt trip requires stored energy type A-mechanism.

2 The HE drive must be used if manual operation is needed in conjunction with motor operator.3 Chain drive handles cannot be used with motor operators.4 This feature provides for the switch to open if a fuse operates.

Mechanism Type

Snap Action K-mech Stored Energy A-mech

40 kA 61 kA 40 kA 61 kA

UL recognized X X X

Electrical Remote shunt trip1 X X

Control Options Auxiliary switch available X X X X

Fuse Auxiliary switch X X

Operating Side direct drive X X X X

Handles Front shaft drive—Type HE2 X X X X

Front chain drive X X

Motor Operator(optional)

NM—side or shaft mounted3 X X X X

Interlocks Mechanical door interlock X X X X

Key Interlock X X X X

Grounding Type E ground switch X X

Switch Ground switch interlock with VersaRupter X X

Fuse Options Fuse bases available X X

Mechanical fuse tripping4 X

Operating Features and Functions

Page 7: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

8

Operating Mechanism (Continued)Snap Action Mechanisms (K-mechanism)

Table 1A: VersaRupters with Snap Action Mechanisms (K-mechanism)

System Rated FaultRating Voltage Rated Continuous Momentary Close Old Smart

Nominal Max. BIL & Loadbreak Rating Rating Catalog Style List(kV) (kV) (kV) (A) (RMS kA) (RMS kA) Number Code Price

200 244-040-502 VK3A0824N $1081

4.73 200 244-040-512 VK3A0824U $1181

(5.9” (150mm) 8.25 75 600 40 40 244-040-506 VK3A0864N $1215pole spacing) 600 244-040-515 VK3A0864U $1315

1200 244-040-510 VK3A0814N $1575

200 244-041-502 VK3B1524N $1245

12 – 13.8 200 244-041-512 VK3B1524U $1345

(6.69" (170mm) 15.00 95 600 40 40 244-041-506 VK3B1564N $1391pole spacing) 600 244-041-515 VK3B1564U $1491

1200 244-041-510 VK3B1514N $1658

13.8 600 245-881-506 VK3C1566U $1607(9.25" (235 mm) 15.00 95 61 61

pole spacing) 1200 245-881-510 VK3C1516U $2139

14.4 600 245-881-522 VK3C1666U $1641(9.25" (235 mm) 15.50 110 61 61

pole spacing) 1200 245-881-526 VK3C1616U $2630

12 – 16.8 200 244-042-502 VK3C1724N $1283

(9.25" (235 mm) 17.00 110 600 40 40 244-042-506 VK3C1764N $1414pole spacing) 1200 244-042-510 VK3C1714N $1755

22.9 – 24.9 200 244-043-502 VK3D2724N $1510

(10.8" (275mm) 27.00 125 600 40 40 244-043-506 VK3D2764N $1724pole spacing) 1200 244-043-510 VK3D2714N $2105

34.5 600 244-005-501 VK3E3864N $3178(14.1" (360mm) 38.00 150 40 30pole spacing) 800 244-005-502 VK3E3884N $3354

Bold catalog numbers are UL recognized when used with chain drive handles and no motor operator.

Smart style codes for UL recognized designs have “U” in the 9th digit position. Smart stylecodes for non-UL designs end with “N”.

K-mechanism switches must be selected when chain drive handles are required.

Page 8: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

9

Stored Energy Mechanisms (A-mechanism)

Bold catalog numbers are UL recognized.

Smart style codes for UL recognized designs have “U” in the 9th digit position. Smart stylecodes for non-UL designs end with “N”.

A-mechanism switches must be selected when shunt trip or mechanical fuse tripping is required.

Switches with A-mechanisms cannot be used with chain drive handles.

Table 1B: VersaRupters with Stored Energy Mechanisms (A-mechanism)

System Rated FaultRating Voltage Rated Continuous Momentary Close Old Smart

Nominal Max. BIL & Loadbreak Rating Rating Catalog Style List(kV) (kV) (kV) (A) (Asym kA) (Asym kA) Number Code Price

4.73 200 245-864-501 VA3A0824N $1311

(5.9" (150mm) 8.25 75 600 40 40 245-864-502 VA3A0864N $1444pole spacing) 1200 245-864-503 VA3A0814N $1814

12 – 13.8 200 245-864-504 VA3B1524N $1485

(6.69" (170mm) 15.00 95 600 40 40 245-864-505 VA3B1564N $1621pole spacing) 1200 245-864-506 VA2B1514N $1971

13.8 600 245-881-514 VA3C1566U $1772(9.25" (235mm) 15.00 95

120061 61

245-881-515 VA3C1516U $2452pole spacing)

14.4 600 245-881-530 VA3C1666U $2280(9.25" (235mm) 15.50 110

120061 61

245-881-531 VA3C1616U $2868pole spacing)

12 – 16.8 200 245-864-507 VA3C1724N $1511

(9.25" (235mm) 17.00 110 600 40 40 245-864-508 VA3C1764N $1645pole spacing) 1200 245-864-511 VA3C1714N $1993

22.9 – 24.9 200 245-864-515 VA3D2724N $1738

(10.8" (275mm) 27.00 125 600 40 40 245-864-516 VA3D2764N $1955pole spacing) 1200 245-864-518 VA3D2714N $2343

34.5 600 245-864-519 VA3E3864N $3521(14.1" (360mm) 38.00 150

80040 30

245-864-520 VA3E3884N $3693pole spacing)

Page 9: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

10

Electrical Control OptionsShunt Trip or Shunt Close / Auxiliary Switches

The shunt trip option is available for local push but-ton or remote switching applications. The shunt tripcan be installed only on VersaRupters with storedenergy (A-mechanism) mechanisms. The shunt triputilizes a solenoid to actuate the A-mechanism trip latch. An auxiliary switch isrequired with shunt trip option.

Shunt trip/close coils are intermittent duty coils. AVersaRupter switch-operated auxiliary contact mustbe in series with the trip coil so that power isremoved from the coil after VersaRupter change-of-state. See Table 3 for auxiliary switch selection.

VersaRupter switches do not include any auxiliary contacts unless specified as an option fromTable 3.

The auxiliary switch contacts change state when the VersaRupter contacts change state. Theauxiliary switch can be installed on all VersaRupterswitches and all grounding switches. Auxiliary switch-es are shipped with an equal number of normallyopen and normally closed contacts, which may bereconfigured in the field as needed.

An optional fuse auxiliary switch is available to indicate an open fuse condition. This switch hastwo contacts, one normally open and one normallyclosed, and is actuated by the tie rod linkage con-nected to the Type CEF fuse base.

Table 2: Shunt Trip Device

Control Catalog Digit List Voltage Number Position 10 Price

No Shunt Trip 0

24 VDC 186-873-006 1 $410

48 VDC 186-873-005 2 $410

110 VDC 186-873-004 3 $410

220 VDC 186-873-003 4 $410

110 VAC 186-873-002 5 $410

220 VAC 186-873-001 6 $410

Price includes shunt trip device, mounting brackets andhardware.

Table 3: Auxiliary Switches

Catalog Number DigitPosition List

Description 5 – 27 kV 38 kV 11 Price

No Auxiliary Contacts 0 $0

6 Contact244-006-516 244-006-514 6 $197

Switch

8 Contact244-006-515 244-006-517 8 $207

Switch

Open Fuse244-006-518 244-006-518 — $84

Aux. Switch

Price includes auxiliary switch, linkage and mounting bracket.

Shunt Trip or Shunt Close

Auxiliary Switches

Page 10: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

11

The VersaRupter switch can be operated with a variety of handles as well as a motor operator. Operators may bemounted in a variety of positions and offer various features. Some operators are not compatible with all mechanismsand features. The chart below provides compatibility guidance.

Operating HandlesSelection Guide

Selection Guide — Operators vs Feature Compatibility

MechanicalUse with Use with Door Key Shunt Motor

Handle Operator Location K-mech A-mech Interlock Interlock Trip Operator1

Chain Drive without Front mounted withDoor Interlock left or right side drive X X(see Table 4)

Chain Drive with Front mounted withDoor Interlock left or right side drive X X X(see Table 5)

Direct Drive Shaft mounted with(see Table 6) left or right side drive

X X X

Manual Shaft Drive Front mounted withType HE2 right side drive

X X X

(see Table 7)– Manual with

X X X X– NM motor

– Manual with X X X X

– door interlock

1If manual operator is required in conjunction with NM motor operator, a type HE shaft drive with removable handle should be selected.

2The HE operator does not provide for key interlocking. However it does have provisions for padlocking the handlespline, which prohibits installation of the removable handle.

Handle Options with Type K SnapAction Mechanism

Handle Operator

Front MountedChain Drive

Handle WithoutMechanical Door

Interlock

Right side mounting

Left side mounting

Front MountedChain DriveHandle With

Mechanical DoorInterlock

Right side mounting

Left side mounting

Direct Drive Handle

Right side mounting

Left side mounting

HE Shaft operator

Handle Options with Type A StoredEnergy Mechanism

Handle Operator

Direct DriveHandle

Right side mounting

Left side mounting

HE ShaftOperator

Page 11: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

12

Operating Handles (Continued)Chain Drive Handles without Door Interlock

The following chain drive handles are for use with K-mechanism snap actionswitches that do not require a door interlock.

Front-mounted right side chain drive handles are for attachment directly tothe type K-mechanism on the right side of the VersaRupter.The “spreader bar” spans the distance from the front door flange where the han-dle is located to the center-line of the switch shaft, maintaining tension on thedrive chain.

Front-mounted left side chain drive handles connect to the VersaRupter usinga left hand shaft extension. These handles do not utilize a spreader bar. Left side catalog numbers below include all the chain drive handle parts, plus the left hand shaft extension. Select left side chain drive handles in accordance with the voltage rating of the VersaRuptersfrom Table 1A so that the proper left hand shaft extension will be provided withthis handle.

Chain drive handles have provisions for two key interlocks.Do not use these handles with A-mechanism stored energy mechanisms.

Table 4: Chain Drive Handles without Door Interlock

Digit PositionDescription Catalog Number 12-15 List Price

Right Side Options

Front mounted, right side operation,244-037-510 CCR1 $295

spreader bar: 29.625 to 34.0"

Front mounted, right side operation,244-037-511 CCR2 $325

spreader bar: 34.625 to 39.0"

Front mounted, right side operation,244-037-512 CCR3 $365

spreader bar: 39.625 to 44.0"

Front mounted, right side operation,244-037-514 CCR4 $425

spreader bar: 61.625 to 66.0"

Left Side Options

Front mounted, left side operation244-037-501 CCLA $295

for 8.25 kV switch (5.9" pole spacing)

Front mounted, left side operation244-037-502 CCLB $315

for 15.0 kV switch (6.69" pole spacing)

Front mounted, left side operation244-037-503 CCLC $340

for 15 – 17.0 kV switch (9.25" pole spacing)

Front mounted, left side operation 244-037-504 CCLD $385

for 27.0 kV switch (10.8" pole spacing)

Front mounted, left side operation 244-037-505 CCLE $415

for 38.0 kV switch (14.1" pole spacing)

Page 12: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

13

Chain Drive Handles with Mechanical Door Interlock

The following chain drive handles are for both right and left side operation, utilizing amechanical door interlock. They automatically latch the switchgear door when theVersaRupter is closed. Each assembly includes all parts required to actuate theVersaRupter switch, while interlocking the switchgear door. The mechanical doorinterlock is pre-installed on the chain drive handle assembly and includes the catchplate that fastens to the door to be automatically latched. Two styles are offered: stan-dard and offset. Standard doors close against the front of the switchgear frame andproject forward from the switchgear frame a dimension equal to the door depth.Offset doors are those that close into a recess in the switchgear frame so that the dooris flush with the switchgear front when closed. Select the chain drive handle assemblyaccording to the type of door used. Right hand chain drive handles include a spreaderbar of various lengths from which to select. Left hand chain drive handles include the left hand shaft extension sized to the voltage rating of the switch.

Do not use these handles with type A-mechanism stored energy mechanisms.

Table 5: Chain Drive Handles with Mechanical Door Interlock

Catalog Digit Position ListDescription Door Type Number 12-15 Price

Front mounted, right side operation, Standard 244-037-517 CDR1$415

spreader bar: 29.625 to 34.0" Offset 244-037-521 CFR1

Front mounted, right side operation, Standard 244-037-518 CDR2$445

spreader bar: 34.625 to 39.0" Offset 244-037-522 CFR2

Front mounted, right side operation, Standard 244-037-519 CDR3$485

spreader bar: 39.625 to 44.0" Offset 244-037-523 CFR3

Front mounted, right side operation, Standard 244-037-520 CDR4$545

spreader bar: 61.625 to 66.0" Offset 244-037-524 CFR4

Front mounted, left side operation Standard 244-037-525 CDLA$415

for 8.25 kV switch (5.9" pole spacing) Offset 244-037-530 CFLA

Front mounted, left side operation Standard 244-037-526 CDLB$435

for 15.0 kV switch (6.69" pole spacing) Offset 244-037-531 CFLB

Front mounted, left side operation Standard 244-037-527 CDLC$460

for 15 – 17.0 kV switch (9.25" pole spacing) Offset 244-037-532 CFLC

Front mounted, left side operation Standard 244-037-528 CDLD$505

for 27.0 kV switch (10.8" pole spacing) Offset 244-037-533 CFLD

Front mounted, left side operation Standard 244-037-529 CDLE$535

for 38.0 kV switch (14.1" pole spacing) Offset 244-037-534 CFLE

Page 13: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

14

Operating Handles (Continued)Direct Drive Handle / Type HE Shaft Drive Operator

Table 6: Direct Drive Operating Handles (side-mounted)

Catalog Digit Position ListDescription Number 12-15 Price

Side mounted, right side operation for switches of all voltage ratings 244-063-501 DDRR $120

Side mounted, left side operation for 8.25 kV switches (5.9" pole spacing) 244-063-505 DDLA $165

Side mounted, left side operation for 15.0 kV switches (6.69" pole spacing) 244-063-506 DDLB $170

Side mounted, left side operation for 15 – 17.0 kV switches (9.25" pole spacing) 244-063-507 DDLC $175

Side mounted, left side operation for 27.0 kV switches (10.8" pole spacing) 244-063-508 DDLD $180

Side mounted, left side operation for 38.0 kV switches (14.1" pole spacing) 244-063-509 DDLE $215

Table 7: Type HE Shaft Drive (front-mounted)

Catalog Digit Position List Digit Position List PriceDescription Number1 12-131 Price1 12-13 w/Handle

Manual 186-023-301 GE $235 HE $290

Manual for use with 186-023-304 GM $320 HM $375

type NM motor operator

Removable handle 183-786-001 $55

1A removable handle is required for manual HE operators. The removable handle should be ordered as a separate item.

Type HE Shaft Drive Operator

The “HE” operator provides front-mounted direct drive connection to theswitch main shaft. A bevel gear is provided for connection to the switchshaft, and a universal joint linkage is provided at the handle. These compo-nents accept a 0.75 inch galvanized pipe (not provided) which allows theVersaRupter to be positioned up to five feet from the front of the enclosure(special 1 inch fittings are required for greater distances). The type HEoperator is available in a locking coupled style for manual operation, and ade-coupled style for motor operation. Neither a mechanical door interlocknor key interlock provisions are available for the HE operators. However,the handle spline may be padlocked to prohibit installation of the removablehandle.

Direct Drive Handle

A manual operator handle is available for shaft-mounted direct operation of the VersaRupter fromeither side of the switchgear cabinet. The handles are available for fixed-mount or removable applica-tions. The left side handle includes the appropriate left-hand shaft extension kit. Padlocking is availablewith the fixed mount handle.

Page 14: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

Motor Operator OptionType NM

15

The compact lightweight NMmotor operator provides forremote electrical opening andclosing of the VersaRupter.

The NM motor operator isinstalled on the splined shaft ofthe VersaRupter mechanism(either K-mechanism or A-mechanism) or on a left-hand shaft extension.

Part Numbers for Brackets

Motor Controllers

NM Motor Operator

Table 8: Type NM Motor Operator

Catalog Digit Position ListControl Voltage Number 16-18 Price

Mounted on Right Side of Switch Splined Shaft (includes motor controllerboard) - spacer bracket to be ordered separately

24 VAC or VDC 245-869-001 1RR $1985

48 VAC or VDC 245-869-002 2RR $1985

110 VAC or VDC 245-869-003 3RR $1985

220 VAC or VDC 245-869-004 4RR $1985

Mounted on Left Side of Switch (includes left hand shaft extension and motorcontroller board) - spacer bracket to be ordered separately

5.9" pole spacing 1LA $20876.69" pole spacing 1LB $2096

24 VAC or VDC 9.25" pole spacing 1LC $209610.8" pole spacing 1LD $210414.1" pole spacing 1LE $2141

5.9" pole spacing 2LA $20876.69" pole spacing 2LB $2096

48 VAC or VDC 9.25" pole spacing 2LC $209610.8" pole spacing 2LD $210414.1" pole spacing 2LE $2141

5.9" pole spacing 3LA $20876.69" pole spacing 3LB $2096

110 VAC or VDC 9.25" pole spacing 3LC $209610.8" pole spacing 3LD $210414.1" pole spacing 3LE $2141

5.9" pole spacing 4LA $20876.69" pole spacing 4LB $2096

220 VAC or VDC 9.25" pole spacing 4LC $209610.8" pole spacing 4LD $210414.1" pole spacing 4LE $2141

Part Number Description List Price

For use on switcheswith K-Mech

245-870-011NM spacer bracket, right side mounting, for use withall switches, 39mm

$30

245-870-012NM spacer bracket, left hand mounting, for use withswitches up to 17 kV, 55mm

$30

245-870-013NM spacer bracket, right side mounting, for use with38 kV switches, 85mm

$30

245-870-014NM spacer bracket, left hand mounting, for use with27 kV swithces, 105mm

$30

For use on switcheswith A-Mech

245-870-015 NM spacer bracket, 39mm $90

245-870-016 NM spacer bracket, 70mm $90

Page 15: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

16

Grounding SwitchesType E

Grounding switches are available forconnection to the lower terminals of theVersaRupter or the VersaRupter fusebase. Grounding switches require theirown operating handle.

Note: It is required that mechanicalinterlocks be used in conjunctionwith ground switches. Interlocks pre-vent closing of the VersaRupterwhen the ground switch is closed.Please select an appropriate interlockfrom one of the lower sections intable 9.

The mechanical interlock prevents theVersaRupter from being closed when theType E grounding switch is closed.Mechanical interlocks are available invarious lengths to accommodate ground-ing switches mounted on the hinged sideof the VersaRupter or at the bottom ofthe fuse base.

Note: Mechanical interlocking is mount-ed on the left hand side and requires aleft hand shaft extension for theVersaRupter (see Table A2).

Table 9: Grounding Switches for Connection to VersaRupterLower Terminal (40 kA switches only)

NominalRated Catalog List

System Rating (kV) Current (A) Number Price

Ground Switches for Connection to VersaRupter Lower Terminal

4.6 – 7.2 200, 600 323-026-010 $445

[5.9" (150 mm) pole spacing] 1200 323-026-001 $449

12.0 – 13.8 200, 600 323-026-012 $452

[6.69" (170 mm) pole spacing] 1200 323-026-003 $457

12.0 – 16.5 200, 600 323-026-013 $461

[9.25" (235 mm) pole spacing] 1200 323-026-004 $461

22.9 – 24.9 200, 600 323-026-014 $465

[10.82" (275 mm) pole spacing] 1200 323-026-005 $465

34.5 [14.17" (360 mm) pole spacing] 600, 800 323-026-025 $2237

Ground Switches for Connection to VersaRupter Fuse Base

4.6 – 7.2 200,600 323-026-015 $429

[5.9" (150 mm) pole spacing] 1200 323-026-020 $848

12.0 – 13.8 200, 600 323-026-017 $438

[6.69" (170 mm) pole spacing] 1200 323-026-022 $915

12.0 – 16.5 200, 600 323-026-018 $448

[9.25" (235 mm) pole spacing] 1200 323-026-023 $1005

22.9 – 24.9 200, 600 323-026-019 $448

[10.82" (275 mm) pole spacing] 1200 323-026-024 $1005

34.5 [14.17" (360 mm) pole spacing] 600, 800 323-026-025 $2237

Mechanical Interlocks for VersaRupter w/o Fuse Base (40 kA VersaRupter only)

4.6–7.2 [5.9" (150 mm) pole spacing] 200 – 1200 186-856-001 $60

12.0–13.8 [6.69" (170 mm) pole spacing] 200 – 1200 186-856-002 $70

12.0–16.5 [9.25" (235 mm) pole spacing] 200 – 1200 186-856-002 $70

22.9–24.9 [10.82" (275 mm) pole spacing] 200 – 1200 186-856-002 $70

34.5 [14.17" (360 mm) pole spacing] 600 – 800 186-856-010 $244

Mechanical Interlocks for VersaRupter with Fuse Base (40 kA VersaRupter only)

CEF FuseLength Catalog List

System Rating (kV) (inches) Number Price

7.5 186-856-004 $974.6–7.211.5 186-856-003 $97[5.9" (150 mm) pole spacing]17.4 186-856-005 $109

12.0–13.8 [6.69" (170 mm) pole spacing] 11.5 186-856-006 $109

12.0–16.5 [9.25" (235 mm) pole spacing] 17.4 186-856-007 $116

22.9–24.9 17.4 186-856-008 $120

[10.82" (275 mm) pole spacing] 21.1 186-856-009 $192

34.5 [14.17" (360 mm) pole spacing] 21.1 186-856-012 $244

Page 16: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

17

Fuse OptionsFuse Bases

Fuse bases are offered for mounting type CEF fuses, with or without fuse tripping, on theupper or lower terminals of the VersaRupter switch. Use the fuse bases with fuse tripping onlywith the latching stored energy mechanism (A-mechanism) found on the switches in Table 1B.Fuse bases in Tables 11-14 use special CEF fuses, which must be ordered separately from Table15. Contact the factory for availability of fuse bases, fuse base options or part identification for61 kA switches. (Prices include fuse clamps.)

Accessory: Open fuse AUX switch (244-006-518) $84

Table 12: Bottom Mounted Fuse Base with Fuse Tripping — (Use with type CEF Fuses only)

System Rating kV, Nominal Pole Spacing (mm) Rated Current (A) Catalog Number List Price

4.6 – 7.2 5.9” (150) 200 186-899-001 $412

12.0 – 13.8 6.69” (170) 200 186-899-003 $460

12.0 – 16.5 9.25” (235) 200 186-899-004 $558

22.9 – 24.9 10.82” (275) 200 186-899-005 $558

34.5 14.17” (360) 200 186-899-006 $1079

Table 13: Top Mounted Fuse Base with Fuse Tripping — (Use with type CEF Fuses only)

System Rating kV, Nominal Pole Spacing (mm) Rated Current (A) Catalog Number List Price

4.6 – 7.2 5.9” (150) 200 186-899-007 $412

12.0 – 13.8 6.69” (170) 200 186-899-009 $460

12.0 – 16.5 9.25” (235) 200 186-899-010 $558

22.9 – 24.9 10.82” (275) 200 186-899-011 $558

Table 11: Top Mounted Fuse Base without Fuse Tripping — (Use with type CEF Fuses only)

System Rating kV, Nominal Pole Spacing (mm) Rated Current (A) Catalog Number List Price

4.6 – 7.2 5.9” (150) 200 186-900-007 $370

12.0 – 13.8 6.69” (170) 200 186-900-009 $395

12.0 – 16.5 9.25” (235) 200 186-900-010 $509

22.9 – 24.9 10.82” (275) 200 186-900-011 $509

34.5 14.17” (360) 200 186-900-012 $1058

Table 10: Bottom Mounted Fuse Base without Fuse Tripping — (Use with type CEF Fuses only)

System Rating kV, Nominal Pole Spacing (mm) Rated Current (A) Catalog Number List Price

4.6 – 7.2 5.9” (150) 200 186-900-001 $370

12.0 – 13.8 6.69” (170) 200 186-900-003 $395

12.0 – 16.5 9.25” (235) 200 186-900-004 $509

22.9 – 24.9 10.82” (275) 200 186-900-005 $509

34.5 14.17” (360) 200 186-900-006 $1058

Page 17: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

18

Table 15: Type CEF Fuses

Rating Rated Fuse Dimensions Catalog ListVoltage (kV) Current (A) Length/Diameter (inches) Number Price

6 186-904-048 $8910 186-904-049 $8916 186-904-050 $9325 7.55/2.55 186-904-051 $9940 186-904-052 $108

3.6/7.2 50 186-904-053 $11463 186-904-054 $11980

7.55/3.4186-904-055 $135

100 186-904-056 $155125 186-904-057 $169160 11.5/3.4 186-904-058 $201200 186-904-059 $261

6 186-904-001 $9210 186-904-002 $9216 186-904-003 $9525 11.5/2.55 186-904-004 $10240 186-904-005 $111

12 50 186-904-006 $12163 186-904-007 $12780

11.5/3.4186-904-008 $166

100 186-904-009 $190125 186-904-010 $190160 17.4/3.4 186-904-011 $213200 186-904-012 $273

6 186-904-013 $10010

11.5/2.55186-904-014 $100

16 186-904-015 $10225 186-904-016 $110

17.5 40 186-904-017 $13050 11.5/3.4 186-904-018 $14863 186-904-019 $15780 186-904-020 $213

100 17.4/3.4 186-904-021 $242125 186-904-022 $282

6 186-904-023 $11010 186-904-024 $11016 17.4/2.55 186-904-025 $11325 186-904-026 $13540 186-904-027 $153

24 50 186-904-028 $17963 17.4/3.4 186-904-029 $19480 186-904-030 $30180 186-904-031 $223

100 21.1/3.4 186-904-032 $252125 186-904-033 $293

6 186-904-034 $11410 17.4/2.55 186-904-035 $11416 186-904-036 $12125 186-904-037 $145

27 4017.4/3.4

186-904-038 $20650 186-904-039 $23563 186-904-040 $23580

21.1/3.4186-904-041 $271

100 186-904-042 $2776 186-904-043 $157

10 21.1/2.55 186-904-044 $15736 16 186-904-045 $185

2521.1/3.4

186-904-046 $20340 186-904-047 $261

Fuse Options (Continued)Type CEF Fuses

Use with fuse bases in Tables 11-14. Consult the factory for CMF style fuses, which may be used in fusebases in Tables 11-14 for medium-voltage motor applications. (Price shown is per fuse.)

Page 18: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

19

Miscellaneous Accessories and Renewal PartsBack Connection Kit / Shaft Extensions / Splined Tubes

Back Connection Kits

Back connect kits are available for positioning the line and load con-nections of the VersaRupter to the rearfor dead front applications.

Left Side Shaft Extensions

Optional shaft extensions are available for left-hand operation using motor operatorsor manual operator handles. Some shaft extensions may be grooved for cutoff to theprecise extension required. Catalog numbers include shaft mounting hardware.

Splined Tube

Optional splined tube provides the ability to create shaft extensions, customize operatorhandles or link the mechanical actuation of the switch together.

Description Catalog Number List Price

8.5 kV switch, 5.9" (150mm) pole spacing 244-044-501 $52

15.0 kV switch, 6.69" (170mm) pole spacing 244-044-502 $61

17.0 kV switch, 9.25" (235 mm) pole spacing 244-044-504 $61

27.0 kV switch, 10.8" (275 mm) pole spacing 244-044-505 $68

38.0 kV switch, 14.1" (360mm) pole spacing 244-044-506 $105

Table A2: Handle Accessories

Table A1: Back Connect Kits

Momentary200 – 600 Rating Catalog List

(A) Configuration (kA) Number Price

Upper & lower 245-901-501 $520

5 kV Lower only 40 245-901-502 $345

Upper only 245-901-503 $180

Upper & lower 245-902-501 $520

15 kV Lower only 40 245-902-502 $345

Upper only 245-902-503 $180

Upper & lower 245-903-501 $575

17 kV Lower only 40 245-903-502 $396

Upper only 245-903-503 $190

Upper & lower 245-904-501 $625

27 kV Lower only 40 245-904-502 $435

Upper only 245-904-503 $205

5 & Upper & lower 245-906-501 $800

15 kV Lower only 61 245-906-502 $455

Upper only 245-906-503 $410

Type Catalog Number Length (inches) List Price

Splined tube (1.125”) 186-851-001 1.125 $30

Splined tube (2.880”) 186-851-002 2.880 $40

Description Catalog Number List Price

Right side shaft extension, 14.96” (380mm) 1YMX053349M0001 $70

Right side shaft extension, 18.50” (470mm) 1YMX053348M0001 $79

Joint Link for right side shaft extension 1YMX053350M0001 $35

Right Side Shaft Extensions

Optional shaft extensions are available for right-hand operation. To order, select the desired shaft extension and thenselect the joint link.

Page 19: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

20

AppendixSmart Style Number Code Sheet

Mechanism Type Code

Snap action K-mech—std. 3.77" shaft K3

Snap action K-mech—2.69" shaft K2

Snap action K-mech—5.26" shaft K5

Stored energy A-mech—std. 3.5" shaft A3

Stored energy A-mech—std. 4.80" shaft A4

Stored energy A-mech—std. 6.90" shaft A6

Frame Size Code

5.9" pole spacing (150mm) A

6.69" pole spacing (170 mm) B

9.25" pole spacing (235 mm) C

10.8" pole spacing (275 mm) D

14.1" pole spacing (360 mm) E

Max kV / BIL Rating Code

8.5 kV / 75 kV BIL 08

15 kV / 95 kV BIL 15

15.5 kV / 110 kV BIL 16

17 kV / 110 kV BIL 17

27 kV / 125 kV BIL 27

38 kV / 150 kV BIL 38

Current / Loadbreak Rating Code

200 A 2

600 A 6

800 A 8

1200 A 1

Momentary Rating Code

40 kA 4

61 kA 6

UL Code

Not UL listed N

UL listed U

Shunt Trip Options Code

None 0

24 VDC control voltage 1

48 VDC control voltage 2

110 VDC control voltage 3

220 VDC control voltage 4

110 VAC control voltage 5

220 VAC control voltage 6

Switch Mech Frame Max Current Momen. UL ShuntType Type Size kV Rating Rating Listed Trip

V K3 B 15 6 4 U 0

Page 20: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

21

Motor Drive Location Choices Code

No motor 00

Right side RR

Left with frame A shaft extension LA

Left with frame B shaft extension LB

Left with frame C shaft extension LC

Left with frame D shaft extension LD

Left with frame E shaft extension LE

NM Motor Choices Code

No motor 0

NM motor 24 VDC, 24 VAC control 1

NM motor 48 VDC, 48 VAC control 2

NM motor 110 VDC, 110 VAC control 3

NM motor 220 VDC, 220 VAC control 4

Handle Drive Location Choices Code

No handle 00

Right side RR

Right with spreader bar 29.625 – 34.0" (chain drive only) R1

Right with spreader bar 34.625 – 39.0" (chain drive only) R2

Right with spreader bar 39.625 – 44.0" (chain drive only) R3

Right with spreader bar 61.625 – 66.0" (chain drive only) R4

Left w/shaft extension for 8.25 kV switches, 5.9" pole spacing LA

Left w/shaft extension for 15.0 kV switches, 6.69" pole spacing LB

Left w/shaft extension for 15 – 17.0 kV switches, 9.25" pole spacing LC

Left w/shaft extension for 27.0 kV switches, 10.8" pole spacing LD

Left w/shaft extension for 38.0 kV switches, 14.1" pole spacing LE

Handle Types Code

No handle 00

Chain w/o door interlock (use w/K-mech only) CC

Chain with door interlock—standard door (use w/K-mech only) CD

Chain with door interlock—offset door (use w/K-mech only) CF

Direct Drive DD

HE Shaft Drive Options Code1 Code2

Shaft type HE manual GE HE

Shaft type HE manual for use with NM motor GM HM1 This code does not include removable handle.2 This code includes removable handle.

Auxiliary Switch Choices Code

None 0

6 contact auxiliary switch 6

8 contact auxiliary switch 8

Aux. Handle MotorSwitch Operator Operator

6 CDLB 000

Page 21: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

22

VersaRupter Price and Order Entry Worksheet

Complete Switch

Switch Smart Style Number

V

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Smart Code List Price

Step 1: Select basic switch with operating mechanism from tables 1A or 1B (Required)Enter 9 character smart number (digits 2 – 9) & list price.

Step 2: Select shunt trip option from table 2. (Optional) Enter “0” if none required. (digit 10)

Step 3: Select auxiliary switch option from table 3. (Optional) Enter “0” if none required. (digit 11)

Step 4: Select 4 character handle operator from tables 4, 5, 6, or 7.(Optional) Enter “0000” if none required. (digits 12 – 15)

Step 5: Select 4 character number for motor operator from table 8.(Optional) Enter “0000” if none required. (digits 16 – 19)

Step 6: Total list prices and apply multiplier to calculate net price. Enter complete smart switch style number to top of page.

Total List Price

Enter Multiplier

Calculate Net Price

Step 7: Other Accessories (Order as separate line items)

Description Catalog Number List Price Multiplier Net Price

Removable Handle (table 7)

Grounding Switch (table 9)

Grounding Switch Interlock (table 9)

Fuse Base (tables 10 – 14)

Fuses (table 15)

Back Connection Kit (table A1)

Shaft Extensions (table A2)

Splined Tubes (table A2)

Page 22: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

23

Appendix ERenewal Parts

1

2

3

4

56 7

8

Item Part # Description List Price

1 245-823-5015 kV Main Blade assembly 200,600 A with link & hinge contact (3req’d)

Contact factory

1 245-823-502 5 kV Main Blade assembly 1200 A with link & hinge contact (3 req’d) Contact factory

1 245-847-501 15,17,27 kV Main Blade assembly 200,600 A (3 req’d) Contact factory

1 245-847-502 15,17,27 kV Main Blade assembly 1200 A (3 req’d) Contact factory

2 323-057-502 5 kV Upper Insulator w/Contact 200,600 A (3 req’d) Contact factory

2 323-057-503 5 kV Upper Insulator w/Contact 1200 A (3 req’d) Contact factory

2 323-083-502 15,17,27 kV Upper Insulator w/Contact 200,600 A (3 req’d) Contact factory

2 323-083-503 15,17,27 kV Upper Insulator w/Contact 1200 A (3 req’d) Contact factory

3 323-058-502 5 kV Lower Support Insulator 200,600,1200 (3 req’d) Contact factory

3 323-082-502 15,17,27 kV Lower Support Insulator 200,600,1200 (3 req’d) Contact factory

4 245-824-501 5 kV Air Piston w/O-ring 200,600,1200 (3 req’d) Contact factory

4 245-844-501 15,17,27 kV Air Piston w/O-ring 200,600,1200 (3 req’d) Contact factory

5 186-041-001 Snap action “K” mechanism with 3.77” shaft Contact factory

5 186-872-001 Stored energy latched “A” mechanism with 3.5” shaft Contact factory

7 245-865-301 5 kV Jack shaft Contact factory

7 245-829-301 15 kV Jack shaft Contact factory

7 245-835-301 17 kV Jack shaft Contact factory

7 245-841-301 27 kV Jack shaft Contact factory

8 245-842-001 5,15,17,27 Jack shaft bearing Contact factory

9 186-928-001 5,15,17,27 Eccentric bolt (3 req’d) Contact factory

- 244-044-001 5 kV LH shaft extension and mounting hardware Contact factory

- 244-044-002 15 kV LH shaft extension and mounting hardware Contact factory

- 244-044-004 17kV LH shaft extension and mounting hardware Contact factory

- 244-044-005 27 kV LH shaft extension and mounting hardware Contact factory

- 183-786-001 Removable operating handle Contact factory

- 1YMX001131M0002 NM controller board 110VAC/DC Contact factory

Page 23: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

24

Appendix FTechnical Data

VersaRupter Switch—Technical Details

Rated Phase 60 HzMaximum Spacing Withstand Rated FaultVoltage Center-Center BIL 1 minute Current Momentary Closing

(kV) (inches) (kV) (kV) (A) (kA @ sec) (kA)

200

8.25 5.90 75 26 600 40 @ 3 40

1200

200

15.00 6.69 95 36 600 40 @ 3 40

1200

15.00 9.25 95 36600

61 @ 3 611200

200

15.50 9.25 110 50 600 61 @ 3 61

1200

200

17.00 9.25 110 50 600 40 @ 2 40

1200

200

27.00 10.80 125 60 600 40 @ 2 40

1200

38.00 14.10 150 80600

40 @ 2 40800

Capacitor bank switching for 15 kV switches (kVar): 2500

Maximum torque at closing (ft-lbs): 85-89

Maximum torque at opening K-mech. (ft-lbs): 89

Maximum torque at opening A-mech. (ft-lbs): 2.2

Operating rotation of shaft (degrees): 130

Arc time (ms): 10-20

Opening time (ms): 40-60

Page 24: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

25

Appendix FTechnical Data

Manual Operation with NM Motor

The NM motor operator allows manual operation of the VersaRupter via a direct shaft drive HE operator with remov-able handle (chain drive handles cannot be used). The NM motor operator does not have to be electrically cycled aftera manual operation of the VersaRupter; it will automatically resume proper electrical operation in the proper position.The NM motor operator requires a motor contactor/relay assembly (3" x 3" x 8"), which may be mounted in theswitch enclosure or an adjacent vertical section.

Voltage AC/DC ±10% 24 V 48 V 60 V 110 V 220 V

Current, I (A) 3 3 0.8 0.8 0.4

Power consumption (W) 70 140 45 85 90

Operating time (sec.) ~4 ~2 ~8 ~4 ~4

Operating temperature (°C) -40 to +55 -40 to +55 -40 to +55 -40 to +55 -40 to +55

Signaling time (sec.) 0.5 – 2.0 0.3 – 1.0 1.0 – 4.0 0.5 – 2.0 0.5 – 2.0

Weight (kg) 6 6 6 6 6

Technical Data Shunt Trip Device

NominalAverage

Coil VoltageCurrent

PowerVoltage Range (VA)IN IStart

24 VDC –15% to +10% 10.0 10.0 240

48 VDC –15% to +10% 2.4 2.4 115

110 VDC –15% to +10% 1.4 1.4 155

220 VDC –15% to +10% 1.5 0.5 110

110 VAC –15% to +10% 2.7 5.0 300

220 VAC –15% to +10% 1.5 2.8 320

Page 25: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

26

Notes

Page 26: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

27

Notes

Page 27: VersaRupter MV indoor switch 5-38 kV, 200-1200 A, 40 & 61 ... · 38 kV 600 & 800 A 40 kA momentary / 30 kA fault close 15 – 15.5 kV 600 & 1200 A 61 kA momentary / 61 kA fault close

1VA

F206

001-

PL

Rev

. J O

ctob

er 2

009

(Rep

lace

s P

S 2

.1.3

.5C

)Components in this catalog are intendedfor use by assemblers engaged in originalequipment manufacturing. All sales aresubject to ABB Inc. General Terms andConditions of Sale, ABBGTC073101.

While every effort has been made toassure the accuracy of technical specifica-tions and pricing, the information in thiscatalog is subject to change withoutnotice.

ADVAC is a registered trademark of ABBInc.

© Copyright 2004, 2009 ABB. All rightsreserved.

Contact Us