2
Technical Data Ice Qube, Inc., 141 Wilson Ave., Greensburg, PA 15601 Call: 724.837.7600 Fax: 724.837.3386 www.iceqube.com Email: [email protected] 2-15-17 Rev 6 Model BTU/Watts Volts/Hz Max Amps Max Temp ºF/ºC Weight (lbs/Kg) Dimensions (In/mm) IQ5000EV 5600/1641 120/60 8.29 140/60 97.5 / 44.2 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 220/50 3.73 140/60 97.5 / 44.2 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 230/60 4.31 140/60 97.5 / 44.2 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 400/50 2.29 140/60 117.5 / 53.3 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 400/60 2.49 140/60 117.5 / 53.3 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 480/50 2.00 140/60 117.5 / 53.3 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) IQ5000EV 5600/1641 480/60 2.09 140/60 117.5 / 53.3 H 28.58”(726 mm) x W 11.31”(287mm) x D 14.15”(359mm) 5000 BTU EV Series 0 2000 4000 6000 8000 10000 20 25 30 35 40 45 50 55 60 Capacity (BTU/hr) Return Air Temperature - ° C IQ5000EV 60Hz Capacity Chart 25º C Ambient 35º C Ambient 45º C Ambient 55º C Ambient Conditioned Enclosed Air Flow Internal Cabinet Air Flow Enclosure Air Flow The next evolution of cutting edge design is here now. The EV Evolution Series from Ice Qube is a certified for general purpose and hazardous locations Class I Division 2 Groups A, B, C, & D air conditioner taking our Ice Qube product line to new levels. Vertical Mount Evolution Series Certified for General Purpose & Hazardous Locations Class I Division 2 Groups A, B, C, & D 5,000 BTUH - 1641 Watt Cooling Capacity Air Conditioner Standard Features Options Technical Data Cooling Solutions Standard Features Compact 11” (287mm) width to fit on smaller cabinets. Three position condenser air flow with the option to direct hot discharge air in different directions. Standard Digital Controller with programmable temperatures and alarm. Controller can be installed on either front or rear of the unit (inside or outside of enclosure). Can be used with or without purge system. UL Listed, (third party certified). Outdoor model operating temperature range from -40 O F/-40 O C to 140 O F/60 O C. Environment friendly refrigerant. Efficient, quiet, and long lasting rotary compressor. Powder Coat finish on durable 16 gauge welded steel. Easy pull out cleanable, reusable electrostatic 10 micron filter. Every unit 100% factory tested before shipping. Minimal visible fasteners. NEMA type 12, 3R, 4, 4X available. Options & Accessories Custom finishes. 304 or 316 Stainless steel. Ethernet controller (ETHR). Low ambient (LA). Alarm output (XO3). 4 Micron condenser filter. Total corrosive e-coating (CP3). 120V 60Hz. 220/230V 50/60Hz. 400V 50/60Hz. 480V 50/60Hz. Class I Division 2 Groups A, B, C, & D

Vertical Mount Evolution Series - iceqube.com · IQ5000EV 5600/1641 480/50 2.00 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm) IQ5000EV 5600/1641

  • Upload
    lyhanh

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

Technical Data

Ice Qube, Inc., 141 Wilson Ave., Greensburg, PA 15601 Call: 724.837.7600 Fax: 724.837.3386www.iceqube.com Email: [email protected] Rev 6

Model BTU/Watts Volts/Hz Max Amps Max Temp ºF/ºC Weight (lbs/Kg) Dimensions (In/mm)

IQ5000EV 5600/1641 120/60 8.29 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 220/50 3.73 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 230/60 4.31 140/60 97.5 / 44.2 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 400/50 2.29 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 400/60 2.49 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 480/50 2.00 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

IQ5000EV 5600/1641 480/60 2.09 140/60 117.5 / 53.3 H 28.58” (726 mm) x W 11.31” (287mm) x D 14.15” (359mm)

5000

BTU

EV

Ser

ies

0

2000

4000

6000

8000

10000

20 25 30 35 40 45 50 55 60

Cap

acity

(BTU

/hr)

Return Air Temperature - ° C

IQ5000EV 60Hz Capacity Chart

25º C Ambient

35º C Ambient

45º C Ambient

55º C AmbientConditioned EnclosedAir Flow

Internal CabinetAir Flow

Enclosure Air Flow

The next evolution of cutting edge design is here now. The EV Evolution Series fromIce Qube is a certified for general purpose and hazardous locations Class I Division2 Groups A, B, C, & D air conditioner taking our Ice Qube product line to new levels.

Vertical Mount Evolution SeriesCertified for General Purpose & Hazardous LocationsClass I Division 2 Groups A, B, C, & D5,000 BTUH - 1641 Watt Cooling Capacity Air Conditioner

Standard FeaturesOptionsTechnical Data

Cooling Solutions

Standard Features• Compact 11” (287mm) width to fit on smaller cabinets.• Three position condenser air flow with the option to direct hot discharge air

in different directions.• Standard Digital Controller with programmable temperatures and alarm.• Controller can be installed on either front or rear of the unit (inside or outside of enclosure).• Can be used with or without purge system.• UL Listed, (third party certified).• Outdoor model operating temperature range from -40O F/-40O C to 140O F/60O C.• Environment friendly refrigerant.• Efficient, quiet, and long lasting rotary compressor.• Powder Coat finish on durable 16 gauge welded steel.• Easy pull out cleanable, reusable electrostatic 10 micron filter.• Every unit 100% factory tested before shipping.• Minimal visible fasteners.• NEMA type 12, 3R, 4, 4X available.

Options & Accessories• Custom finishes.• 304 or 316 Stainless steel.• Ethernet controller (ETHR).

• Low ambient (LA).• Alarm output (XO3).• 4 Micron condenser filter.• Total corrosive e-coating (CP3).

• 120V 60Hz.• 220/230V 50/60Hz.• 400V 50/60Hz.• 480V 50/60Hz.

Class I Division 2Groups A, B, C, & D

Ice Qube, Inc., 141 Wilson Ave., Greensburg, PA 15601 Call: 724.837.7600 Fax: 724.837.3386www.iceqube.com Email: [email protected] Rev 6

Drawings depict all voltages. Data is subject tochange.

Specification Drawings

Vertical Mount Evolution SeriesCertified for General Purpose & Hazardous LocationsClass I Division 2 Groups A, B, C, & D5,000 BTUH - 120V 60Hz, 220/230V 50/60Hz, 400V 50/60Hz, &480V 50 & 60 Hz Air Conditioners

Cooling Solutions

11.309287.26

14.150359.40

DATE

U

T

REV 0

LOCATION

INTAKEENCLOSURE

EXHAUST(6) PEM, NUT, #1/4-20 ENCLOSURE

OPTIONAL CONTROLLER (2) PEM, STUD, 1/4"-20, 1"LG

179.47

203.208.000

7.066

5.500139.70

WITH GUARD

AMBIENT EXHAUST

28.584726.04

IQ5000EV

AMBIENT EXHAUSTIQ5000EVNOMINAL COOLING CAPACITY:5600 BTUH @ 140-140 F5300 BTUH @ 95-95 FINTERNAL HEAT OPTION: 400W MAXIMUMMAXIMUM AMPS: 8.29 @ 120V/60Hz w/ INTERNAL HEAT 4.00AMAXIMUM AMPS: 3.73 @ 220V/50Hz w/ INTERNAL HEAT 2.20AMAXIMUM AMPS: 4.31 @ 230V/60Hz w/ INTERNAL HEAT 2.10AMAXIMUM AMPS: 2.00 @ 480V/50Hz w/ INTERNAL HEAT 2.20AMAXIMUM AMPS: 2.09 @ 480V/60Hz w/ INTERNAL HEAT 2.10AMAXIMUM AMPS: 2.29 @ 400V/50Hz w/ INTERNAL HEAT 2.21AM

STANDARD CONTROLLER

LOCATION

52.122.052

9.046229.77

AMBIENT INTAKE FILTER

8.000203.20

14.000355.60

DRAIN TUBE .375" [9.53] O.D.