    Preface

    Thank you for choosing DELTAs high-performance VFD-E Series. The VFD-E Series is

    manufactured with high-quality components and materials and incorporate the latest microprocessor

    technology available.

    This manual is to be used for the installation, parameter setting, troubleshooting, and daily

    maintenance of the AC motor drive. To guarantee safe operation of the equipment, read the following

    safety guidelines before connecting power to the AC motor drive. Keep this operating manual at

    hand and distribute to all users for reference.

    To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor

    drive are to do installation, start-up and maintenance. Always read this manual thoroughly before

    using VFD-E series AC Motor Drive, especially the WARNING, DANGER and CAUTION notes.

    Failure to comply may result in personal injury and equipment damage. If you have any questions,

    please contact your dealer.

    PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.

    DANGER!

    1. AC input power must be disconnected before any wiring to the AC motor drive is made.

    2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power

    has been turned off. To prevent personal injury, please ensure that power has turned off before

    opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe voltage

    levels.

    3. Never reassemble internal components or wiring.

    4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the

    input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and

    W/T3 directly to the AC mains circuit power supply.

    5. Ground the VFD-E using the ground terminal. The grounding method must comply with the laws

    of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.

    6. VFD-E series is used only to control variable speed of 3-phase induction motors, NOT for 1-

    phase motors or other purpose.

    7. VFD-E series shall NOT be used for life support equipment or any life safety situation.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    3/398

    WARNING!

    1. DO NOT use Hi-pot test for internal components. The semi-conductor used in AC motor drive

    easily damage by high-voltage.

    2. There are highly sensitive MOS components on the printed circuit boards. These components

    are especially sensitive to static electricity. To prevent damage to these components, do not

    touch these components or the circuit boards with metal objects or your bare hands.

    3. Only qualified persons are allowed to install, wire and maintain AC motor drives.

    CAUTION!

    1. Some parameters settings can cause the motor to run immediately after applying power.

    2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,

    high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic

    particles.

    3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or

    electric shock.

    4. To prevent personal injury, please keep children and unqualified people away from the

    equipment.

    5. When the motor cable between AC motor drive and motor is too long, the layer insulation of the

    motor may be damaged. Please use a frequency inverter duty motor or add an AC output

    reactor to prevent damage to the motor. Refer to appendix B Reactor for details.

    6. The rated voltage for AC motor drive must be 240V (480V for 460V models) and the short

    circuit must be 5000A RMS (10000A RMS for the 40hp (30kW) models).

    DeviceNet is a registered trademark of the Open DeviceNet Vendor Association, Inc. Lonwork is a

    registered trademark of Echelon Corporation. Profibus is a registered trademark of Profibus

    International. CANopen is a registered trademark of CAN in Automation (CiA). Other trademarks

    belong to their respective owners.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    4/398

    Table of Contents

    Preface ............................................................................................................. i

    Table of Contents .......................................................................................... iii

    Chapter 1 Introduction................................................................................ 1-1

    1.1 Receiving and Inspection ................................................................... 1-2

    1.1.1 Nameplate Information................................................................ 1-2

    1.1.2 Model Explanation ...................................................................... 1-2

    1.1.3 Series Number Explanation ........................................................ 1-3

    1.1.4 Drive Frames and Appearances ................................................. 1-3

    1.1.5 Remove Instructions ................................................................... 1-7

    1.2 Preparation for Installation and Wiring ............................................... 1-9

    1.2.1 Ambient Conditions..................................................................... 1-9

    1.2.2 DC-bus Sharing: Connecting the DC-bus of the AC Motor Drives inParallel............................................................................................... 1-12

    1.3 Dimensions....................................................................................... 1-13

    Chapter 2 Installation and Wiring .............................................................. 2-1

    2.1 Wiring ................................................................................................. 2-2

    2.2 External Wiring................................................................................. 2-12

    2.3 Main Circuit ...................................................................................... 2-13

    2.3.1 Main Circuit Connection............................................................ 2-13

    2.3.2 Main Circuit Terminals .............................................................. 2-16

    2.4 Control Terminals ............................................................................. 2-17

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    5/398

    Chapter 3 Keypad and Start Up .................................................................. 3-1

    3.1 Keypad ............................................................................................... 3-1

    3.2 Operation Method ............................................................................... 3-2

    3.3 Trial Run ............................................................................................. 3-3

    Chapter 4 Parameters.................................................................................. 4-1

    4.1 Summary of Parameter Settings......................................................... 4-2

    4.2 Parameter Settings for Applications.................................................. 4-33

    4.3 Description of Parameter Settings .................................................... 4-38

    4.4 Different Parameters for VFD*E*C Models ..................................... 4-182

    Chapter 5 Troubleshooting......................................................................... 5-1

    5.1 Over Current (OC) .............................................................................. 5-1

    5.2 Ground Fault....................................................................................... 5-2

    5.3 Over Voltage (OV) .............................................................................. 5-2

    5.4 Low Voltage (Lv)................................................................................. 5-3

    5.5 Over Heat (OH)................................................................................... 5-4

    5.6 Overload ............................................................................................. 5-4

    5.7 Keypad Display is Abnormal............................................................... 5-5

    5.8 Phase Loss (PHL)............................................................................... 5-5

    5.9 Motor cannot Run ............................................................................... 5-6

    5.10 Motor Speed cannot be Changed..................................................... 5-7

    5.11 Motor Stalls during Acceleration ....................................................... 5-8

    5.12 The Motor does not Run as Expected .............................................. 5-8

    5.13 Electromagnetic/Induction Noise ...................................................... 5-9

    5.14 Environmental Condition................................................................... 5-9

    5.15 Affecting Other Machines................................................................ 5-10

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    6/398

    Chapter 6 Fault Code Information and Maintenance................................ 6-1

    6.1 Fault Code Information....................................................................... 6-1

    6.1.1 Common Problems and Solutions............................................... 6-1

    6.1.2 Reset .......................................................................................... 6-6

    6.2 Maintenance and Inspections............................................................. 6-6

    Appendix A Specifications ........................................................................ A-1

    Appendix B Accessories ........................................................................... B-1

    B.1 All Brake Resistors & Brake Units Used in AC Motor Drives..............B-1B.1.1 Dimensions and Weights for Brake Resistors ............................ B-4

    B.1.2 Specifications for Brake Unit ...................................................... B-7

    B.1.3 Dimensions for Brake Unit.......................................................... B-8

    B.1.4 DIN Rail Installation .................................................................... B-9

    B.2 No-fuse Circuit Breaker Chart .......................................................... B-10B.3 Fuse Specification Chart .................................................................. B-11

    B.4 AC Reactor ...................................................................................... B-12

    B.4.1 AC Input Reactor Recommended Value................................... B-12

    B.4.2 AC Output Reactor Recommended Value................................ B-13

    B.4.3 Applications .............................................................................. B-14B.5 Zero Phase Reactor (RF220X00A) .................................................. B-17

    B.6 Remote Controller RC-01................................................................. B-18

    B.7 PU06................................................................................................ B-19

    B.7.1 Description of the Digital Keypad VFD-PU06 ........................... B-19

    B.7.2 Explanation of Display Message............................................... B-19B.7.3 Operation Flow Chart ............................................................... B-20

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    7/398

    B.8 KPE-LE02........................................................................................ B-21

    B.8.1 Description of the Digital Keypad KPE-LE02 ............................B-21

    B.8.2 How to Operate the Digital Keypad...........................................B-23

    B.8.3 Reference Table for the 7-segment LED Display of the DigitalKeypad............................................................................................... B-24

    B.8.4 Keypad Dimensions.................................................................. B-24

    B.9 Extension Card................................................................................ B-25

    B.9.1 Relay Card................................................................................ B-25

    B.9.2 Digital I/O Card ......................................................................... B-26

    B.9.3 Analog I/O Card ........................................................................ B-26

    B.9.4 Communication Card ................................................................ B-26

    B.9.5 Speed Feedback Card.............................................................. B-27

    B.10 Fieldbus Modules .......................................................................... B-27

    B.10.1 DeviceNet Communication Module (CME-DN01) ...................B-27B.10.1.1 Panel Appearance and Dimensions ................................B-27

    B.10.1.2 Wiring and Settings ......................................................... B-28

    B.10.1.3 Mounting Method ............................................................ B-28

    B.10.1.4 Power Supply .................................................................. B-29

    B.10.1.5 LEDs Display................................................................... B-29B.10.2 LonWorks Communication Module (CME-LW01) ...................B-30

    B.10.2.1 Introduction ..................................................................... B-30

    B.10.2.2 Dimensions ..................................................................... B-30

    B.10.2.3 Specifications .................................................................. B-30

    B.10.2.4 Wiring.............................................................................. B-31B.10.2.5 LED Indications ............................................................... B-31

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    8/398

    B.10.3 Profibus Communication Module (CME-PD01) ...................... B-31

    B.10.3.1 Panel Appearance .......................................................... B-32

    B.10.3.2 Dimensions ..................................................................... B-33

    B.10.3.3 Parameters Settings in VFD-E........................................ B-33

    B.10.3.4 Power Supply.................................................................. B-33

    B.10.3.5 PROFIBUS Address ....................................................... B-33

    B.10.4 CME-COP01 (CANopen)........................................................ B-34

    B.10.4.1 Product Profile ................................................................ B-34B.10.4.2 Specifications.................................................................. B-34

    B.10.4.3 Components ................................................................... B-35

    B.10.4.4 LED Indicator Explanation & Troubleshooting ................ B-36

    B.11 DIN Rail.......................................................................................... B-38

    B.11.1 MKE-DRA............................................................................... B-38B.11.2 MKE-DRB............................................................................... B-39

    B.11.3 MKE-EP.................................................................................. B-39

    B.12 EMI Filter........................................................................................ B-40

    Appendix C How to Select the Right AC Motor Drive.............................. C-1

    C.1 Capacity Formulas............................................................................. C-2C.2 General Precaution............................................................................ C-4

    C.3 How to Choose a Suitable Motor .......................................................C-5

    Appendix D How to Use PLC Function..................................................... D-1

    D.1 PLC Overview.................................................................................... D-1

    D.1.1 Introduction ................................................................................ D-1D.1.2 Ladder Diagram Editor WPLSoft ............................................. D-1

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    9/398

  • 8/13/2019 VFD E User Manual

    10/398

    D.4.11 Function Code (only for PLC2 mode) .....................................D-27

    D.5 Commands ......................................................................................D-27

    D.5.1 Basic Commands .....................................................................D-27

    D.5.2 Output Commands ...................................................................D-28

    D.5.3 Timer and Counters..................................................................D-28

    D.5.4 Main Control Commands..........................................................D-28

    D.5.5 Rising-edge/falling-edge Detection Commands of Contact ......D-28

    D.5.6 Rising-edge/falling-edge Output Commands............................D-29D.5.7 End Command .........................................................................D-29

    D.5.8 Explanation for the Commands ................................................D-29

    D.5.9 Description of the Application Commands................................D-44

    D.5.10 Explanation for the Application Commands............................D-45

    D.5.11 Special Application Commands for the AC Motor Drive .........D-57D.6 Error Code .......................................................................................D-64

    Appendix E CANopen Function .................................................................E-1

    E.1 Overview............................................................................................E-2

    E.1.1 CANopen Protocol......................................................................E-2

    E.1.2 RJ-45 Pin Definition....................................................................E-3E.1.3 Pre-Defined Connection Set.......................................................E-3

    E.1.4 CANopen Communication Protocol............................................E-4

    E.1.4.1 NMT (Network Management Object) ..................................E-4

    E.1.4.2 SDO (Service Data Object).................................................E-6

    E.1.4.3 PDO (Process Data Object)................................................E-7E.1.4.4 EMCY (Emergency Object).................................................E-9

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    11/398

    E.2 How to Control by CANopen ........................................................... E-13

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    12/398

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-1

    Chapter 1 Introduction

    The AC motor drive should be kept in the shipping carton or crate before installation. In order to retain

    the warranty coverage, the AC motor drive should be stored properly when it is not to be used for an

    extended period of time. Storage conditions are:

    CAUTION!

    1. Store in a clean and dry location free from direct sunlight or corrosive fumes.

    2. Store within an ambient temperature range of -20

    C to +60

    C.

    3. Store within a relative humidity range of 0% to 90% and non-condensing environment.

    4. Store within an air pressure range of 86 kPA to 106kPA.

    5. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding

    environment is humid, you should put exsiccator in the package.

    6. DO NOT store in an area with rapid changes in temperature. It may cause condensation and

    frost.

    7. If the AC motor drive is stored for more than 3 months, the temperature should not be higher

    than 30 C. Storage longer than one year is not recommended, it could result in the degradation

    of the electrolytic capacitors.

    8. When the AC motor drive is not used for longer time after installation on building sites or places

    with humidity and dust, its best to move the AC motor drive to an environment as stated above.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    13/398

    Chapter 1 Introduction

    1-2 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    1.1 Receiving and Inspection

    This VFD-E AC motor drive has gone through rigorous quality control tests at the factory before

    shipment. After receiving the AC motor drive, please check for the following:

    Check to make sure that the package includes an AC motor drive, the User Manual/Quick

    Start and CD.

    Inspect the unit to assure it was not damaged during shipment.

    Make sure that the part number indicated on the nameplate corresponds with the part

    number of your order.

    1.1.1 Nameplate Information

    Example for 1HP/0.75kW 3-phase 230V AC motor drive

    MODEL VFD007E23A:INPUT :3PH 200-240V 50/60Hz 5. 1AOUTPUT :3PH 0- 240V 4.2 A 1.6kVA 0.75kW/1 HPFREQUEN CY RANGE : 0.1~400Hz

    Seria l Nu mber & Bar Co de

    AC Dri ve Mod elInput Spec.

    Output Spec.

    Output Frequency Ra nge

    007E23A0T801123001.0302.03

    Software VersionPower BoardControl Board

    1.1.2 Model Explanation

    VFD A

    Version Type

    23

    Mains Input Voltage11:115 Single phaseV 21: phase230V Single

    23:230 Three phaseV

    E

    E Series

    007

    Applicable motor capa city

    Series Name ( ariable requency rive)V F D

    43:460 Three phaseV

    A: Standard driveC: CANopenP: Cold plate drive ( frame A only)T: Frame A, buil t-in brake chopper

    004: 0.5 HP(0.4kW)007: 1 HP(0.75kW)015: 2 HP(1.5kW)022: 3 HP(2.2kW)

    002: 0.25 HP(0.2kW)055: 7.5 HP(5.5kW)075: 10 HP(7 .5kW)110: 15 HP(11kW)

    037: 5 HP(3.7kW)

    150: 20 HP(15kW)

    220: 30 HP(22kW) 185: 25 HP(18.5kW)

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    14/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-3

    1.1.3 Series Number Explanation

    12300180T007E23A

    Production number

    Production year 2008

    Production factory

    Production week

    T: Taoyuan, W: Wuj iang

    Model230V 3-phase 1HP(0.75kW )

    If the nameplate information does not correspond to your purchase order or if there areany problems, please contact your distributor.

    1.1.4 Drive Frames and Appearances

    0.25-2HP/0.2-1.5kW (Frame A)

    Input terminals(R/L1, S/L2, T/L3)

    Keypad cover

    Output terminals(U/T1, V/T2, W/T3)

    Control board cover

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    15/398

    Chapter 1 Introduction

    1-4 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    1-5HP/0.75-3.7kW (Frame B)

    Input terminals(R/L1, S/L2, T/L3)

    Keypad cover

    Case body

    Contro l board cover

    Output terminals(U/T1, V/T2, W/T3)

    7.5-15HP/5.5-11kW (Frame C)

    Input terminals(R/L1, S/L2, T/L3)

    Case body

    Keypad cover

    Control board cover

    Output terminals(U/T1, V/T2, W/T3)

    20-30HP/15-22kW (Frame D)

    Input terminals(R/L1, S/L2, T/L3)

    Case body

    Keypad cover

    Control board cover

    Output terminals(U/T1, V/T2, W/T3)

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    16/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-5

    Internal Structure

    1.

    2.

    3.

    READY: power indicator

    RUN: status indicator

    FAULT: fault indicator

    NPN/PNP

    RS485 port (RJ-45)

    Switch to ON for 50Hz, refer toP 01.00 to P01.02 for details

    Switch to ON for free run to stoprefer to P02.02

    Switch to ON for setting frequencysource to ACI (P 02.00=2)

    ACI terminal (ACI/AVI2 switch )

    Mounting port for extension card

    NOTE The LED READY will light up after applying power. The light wont be off until the capacitors are

    discharged to safe voltage levels after power off.

    RFI Jumper Location

    Frame A: near the output terminals (U/T1, V/T2, W/T3)

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    17/398

  • 8/13/2019 VFD E User Manual

    18/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-7

    RFI Jumper

    RFI Jumper: The AC motor drive may emit the electrical noise. The RFI jumper is used to suppress

    the interference (Radio Frequency Interference) on the power line.

    Main power isolated from earth:If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off.

    Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage

    (according to IEC 61800-3) and reduce earth leakage current.

    CAUTION!

    1. After applying power to the AC motor drive, do not cut off the RFI jumper. Therefore,

    please make sure that main power has been switched off before cutting the RFI jumper.

    2. The gap discharge may occur when the transient voltage is higher than 1,000V. Besides,

    electro-magnetic compatibility of the AC motor drives will be lower after cutting the RFI

    jumper.

    3. Do NOT cut the RFI jumper when main power is connected to earth.

    4. The RFI jumper cannot be cut when Hi-pot tests are performed. The mains power and

    motor must be separated if high voltage test is performed and the leakage currents are

    too high.

    5. To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC

    motor drive is installed on an ungrounded power system or a high resistance-grounded

    (over 30 ohms) power system or a corner grounded TN system.

    1.1.5 Remove Instructions

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    19/398

  • 8/13/2019 VFD E User Manual

    20/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-9

    1.2 Preparation for Installation and Wiring

    1.2.1 Ambient Conditions

    Install the AC motor drive in an environment with the following conditions:Air Temperature:

    -10 ~ +50C (14 ~ 122F) for UL & cUL-10 ~ +40C (14 ~ 104F) for side-by-side mounting

    Relative Humidity:

  • 8/13/2019 VFD E User Manual

    21/398

    Chapter 1 Introduction

    1-10 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Frame B, C and D Mounting Clearances

    Single drive Side-by-side installation Air flow

    150mm

    150mm

    50

    mm

    50

    mm

    150mm

    150mm

    50

    mm

    50

    mm

    Air Flow

    For VFD-E-P series: heat sink system example

    Duct temperatureAir flow speed

    40 2m/sec

    C

    User

    1. Flatness

  • 8/13/2019 VFD E User Manual

    22/398

  • 8/13/2019 VFD E User Manual

    23/398

  • 8/13/2019 VFD E User Manual

    24/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-13

    1.3 Dimensions

    (Dimensions are in millimeter and [inch])

    Frame AD

    H1

    H

    WW1

    S2S1

    D1D2

    Unit: mm [inch]

    Frame W W1 H H1 D D1 D2 S1 S2

    A (A1)72.0

    [2.83]

    60.0

    [2.36]

    142.0

    [5.59]

    120.0

    [4.72]

    152.0

    [5.98]

    50.0

    [1.97]

    4.5

    [0.18]

    5.2

    [0.20]

    5.2

    [0.20]

    A (A2)

    72.0

    [2.83]

    56.0

    [2.20]

    155.0

    [6.10]

    143.0

    [5.63]

    111.5

    [4.39]

    9.5

    [0.37]

    - 5.3

    [0.21]

    -

    NOTE

    Frame A (A1): VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A,

    VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C, VFD007E21C/23C/43C,

    VFD015E23C/43C, VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T,

    VFD015E23T/43TFrame A (A2): VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, VFD007E21P/23P/43P,

    VFD015E23P/43P

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    25/398

    Chapter 1 Introduction

    1-14 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Frame BD

    H

    S2

    H1

    WW1

    D1D2

    S1

    Unit: mm [inch]

    Frame W W1 H H1 D D1 D2 S1 S2

    B1100.0

    [3.94]

    89.0

    [3.50]

    174.0

    [6.86]

    162.0

    [6.38]

    152.0

    [5.98]

    50.0

    [1.97]

    4.0

    [0.16]

    5.5

    [0.22]

    5.5

    [0.22]

    NOTE

    Frame B (B1): VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A,

    VFD007E11C, VFD015E21C, VFD022E21C/23C/43C, VFD037E23C/43C

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    26/398

    Chapter 1 Introduction

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-15

    Frame C

    HH1

    W1W

    S1

    S2

    DD1

    D2

    Unit: mm [inch]

    Frame W W1 H H1 D D1 D2 S1 S2

    C1130.0

    [5.12]

    116.0

    [4.57]

    260.0

    [10.24]

    246.5

    [9.70]

    169.2

    [6.66]

    78.5

    [3.09]

    8.0

    [0.31]

    6.5

    [0.26]

    5.5

    [0.22]

    NOTE

    Frame C (C1): VFD055E23A/43A, VFD075E23A/43A, VFD110E23A/43A, VFD055E23C/43C,

    VFD075E23C/43C, VFD110E23C/43C

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    27/398

    Chapter 1 Introduction

    1-16 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Frame D

    W1

    W

    D2

    D1

    D

    H1

    H

    S1

    S2

    Unit: mm [inch]Frame W W1 H H1 D D1 D2 S1 S2

    D200.0

    [7.87]

    180.0

    [7.09]

    310.0

    [12.20]

    290.0

    [11.42]

    190.0

    [7.48]

    92.0

    [3.62]

    10.0

    [0.39]

    10.0

    [0.39]

    9.0

    [0.35]

    NOTE

    Frame D (D1): VFD150E23A/23C, VFD150E43A/43C, VFD185E43A/43C, VFD220E43A/43C

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    28/398

  • 8/13/2019 VFD E User Manual

    29/398

    Chapter 2 Installation and Wiring

    2-2 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    DANGER!

    1. A charge may still remain in the DC bus capacitors with hazardous voltages even if the power

    has been turned off. To prevent personal injury, please ensure that the power is turned off and

    wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC

    motor drive.

    2. Only qualified personnel familiar with AC motor drives is allowed to perform installation, wiring

    and commissioning.

    3. Make sure that the power is off before doing any wiring to prevent electric shock.

    2.1 Wiring

    Users must connect wires according to the circuit diagrams on the following pages. Do not plug a

    modem or telephone line to the RS-485 communication port or permanent damage may result. The

    pins 1 & 2 are the power supply for the optional copy keypad only and should not be used for RS-485

    communication.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    30/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-3

    Figure 1 for models of VFD-E SeriesVFD002E11A/21A, VFD004E11A/21A, VFD007E21A, VFD002E11C/21C, VFD004E11C/21C,VFD007E21C, VFD002E11P/21P, VFD004E11P/21P, VFD007E21P

    AVI

    ACI

    ACM

    +

    +10V

    5K

    3

    2

    1

    Power supply

    +10V 20m A

    Master Frequency

    0 to 10V 47K

    Analog S ignal Com mo n E

    Main circuit (power) terminals Control circuit term inals Shielded leads & Cable

    E

    R(L1)

    S(L2)

    Fuse/NFB(None Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommen ded Circuit

    when pow er supplyis turne d OFF by a

    fault outputIf the fault occurs, the

    contact will be ON to

    turn off the power a ndprotect the power system.

    R(L1)

    S(L2)

    E

    An alog M ul t i- func tion Outpu t

    Terminalfactory setting: Analog freq.

    / current meter 0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    ACM

    RA

    RB

    RC

    Motor

    Factory setting:

    Drive is in operation48V50mA Max.

    Multi-function

    Photocoulpe r Output

    An alog S ignal comm on

    E

    E

    MO1

    MCM

    MI1

    MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Commo n

    Factory

    setting

    Sw2

    AVI

    ACI

    Factory setting:

    ACI Mode

    ACI/AVI switch

    Whe n switching to AVI,it indicates AVI2

    -

    8 1

    Sw1

    NPN

    PNP

    Factory setting:

    NPN Mode

    Please refer to Figure 7

    for wiring of NPNmode and PNPmode.

    BUEbrake unit

    (optional)

    BR brake resistor (optional)

    Multi-functio n contact output

    Refer to chapter 2.4 for details.Factory setting is

    malfunction indication

    Factory setting: output frequency

    4-20mA/0-10V

    RS-485 serial interface

    (NOT for VFD*E*C models)

    1: Reserved

    2: EV

    5: SG +

    6: Reserved

    7: Reserved8: Reserved

    3: G ND

    4: SG -

    For VFD*E*C models,

    pleas e ref er to figure 8.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    31/398

    Chapter 2 Installation and Wiring

    2-4 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Figure 2 for models of VFD-E SeriesVFD002E23A, VFD004E23A/43A, VFD007E23A/43A, VFD015E23A/43A, VFD002E23C,VFD004E23C/43C, VFD007E23C/43C, VFD015E23C/43C, VFD002E23P, VFD004E23P/43P,VFD007E23P/43P, VFD015E23P/43P

    AVI

    ACI

    ACM

    +

    +10V

    5K

    3

    2

    1

    Power supply

    +10V 20mA

    Master Frequency

    0 to 10V 47K

    An alog S ignal Com mo n E

    Main circuit (power) terminals Control circuit term inals Shielded leads & Cable

    E

    R(L1)

    S(L2)

    Fuse/NFB(No Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommended Circuitwhen pow er supplyis turne d OFF by a

    fault outputIf the fault occurs, the

    contact will be O N to

    turn off the power a ndprotect the power system.

    R(L1)

    S(L2)

    E

    An alog M ul t i- func tion Outpu t

    Terminalfactory setting: Analog freq.

    / current meter 0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    ACM

    RA

    RB

    RC

    Motor

    Factory setting:

    Drive is in operation48V50mA Max.

    Multi-function

    Photocoulpe r Output

    An alog S ignal commo n

    E

    E

    MO1

    MCM

    MI1

    MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Common

    Factory

    setting

    Sw2

    AVI

    ACI

    Factory setting:

    ACI Mode

    ACI/AVI switch

    Whe n switching to AVI,it indicates AVI2

    -

    8 1

    Sw1

    NPN

    PNP

    Factory setting:

    NPN Mode

    Please refer to Figure 7for wiring of NPNmode and PNPmode.

    BUEbrake unit

    (optional)

    BR brake resistor (optional)

    Multi-functio n contact output

    Refer to chapter 2.4 for details.

    Factory setting ismalfun ction indication

    Factory setting: output frequency

    4-20mA/0-10V

    T(L3)T(L3)

    RS-485 serial interface

    (NOT for VFD*E*C models)

    1: Reserved

    2: EV

    5: SG +

    6: Reserved

    7: Reserved

    8: Reserved

    3: G ND

    4: SG -

    For VFD*E*C models,

    pleas e ref er to figure 8.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    32/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-5

    Figure 3 for models of VFD-E SeriesVFD007E11A, VFD015E21A, VFD022E21A, VFD007E11C, VFD015E21C, VFD022E21C

    AVI

    AC I

    AC M

    +/B1

    +10V

    5K

    3

    2

    1

    Power supply+10V 20mA

    Master Frequency0 to 10V 47K

    Analog S ignal Co mmon E

    Main circuit (power) terminals Control circuit term inals Shielded leads & Cable

    E

    R(L1)

    S(L2)

    Fuse/NFB(No Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommended Circuit

    when powe r su pplyis turned OFF by a

    fault outputIf the fault occurs, thecontact will be O N toturn off the powe r andprotect the power system.

    R(L1)

    S(L2)

    E

    Analog Mul t i- fun c tionOutput Terminalfactory set ting: Analog

    freq./ cur rent meter0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    ACM

    RA

    RB

    RC

    Motor

    Factory setting:Drive is in operation48V50m A Max.

    Multi-functionPhotocou lper Ou tput

    Analog S ignal common

    E

    E

    MO 1

    MCM

    MI1

    MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Common

    Factorysetting

    Sw2

    AVI

    ACI

    Factory setting:ACI Mode

    ACI/AVI switchWhen switch ing to AVI,it indicates AVI2

    -

    8 1

    Sw1

    NPN

    PNP

    Factory setting:NPN Mode

    Please refer to Figure 7for wiring of NPNmode and PNPmode.

    brake resistor

    (optional)

    Multi-function contact output

    Refer to chapter2.4 for details.Factory setting ismalfunction indication

    Factory setting: outputfrequency

    4-20mA/0-10V

    BR

    B2

    RS-485 serial interface(NO T for VFD*E*C models)

    1: Reserved2: EV

    5: SG+6: Reserved7: Reserved8: Reserved

    3: GND4: SG -

    For VFD*E*C models,

    please refer to figure 8.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    33/398

    Chapter 2 Installation and Wiring

    2-6 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Figure 4 for models of VFD-E SeriesVFD022E23A/43A, VFD037E23A/43A, VFD055E23A/43A, VFD075E23A/43A, VFD110E23A/43A,VFD022E23C/43C, VFD037E23C/43C, VFD055E23C/43C, VFD075E23C/43C, VFD110E23C/43C,VFD150E23A/23C, VFD150E43A/43C, VFD185E43A/43C, VFD220E43A/43C

    AVI

    ACI

    ACM

    +/B1

    +10V

    5K

    3

    2

    1

    Power supply+10V 20m A

    Master Frequency

    0 to 10V 4 7K

    An alog S ignal Co mm on E

    Main circuit (power) terminals Control circuit terminals Shielded leads & Cable

    E

    R(L1)

    S(L2)

    Fuse/NFB(No Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommen ded Circuit

    when power supplyis turn ed OFF by a

    fault outputIf the fault occurs, the

    contact will be ON to

    turn off the powe r andprotect the power system.

    R(L1)

    S(L2)

    E

    An alog Mul ti - func ti on

    Output Terminalfactory setting: Analog

    freq./ cur rent meter0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    AC M

    RA

    RBRC

    Motor

    Factory setting:

    Drive is in operation48V50mA Max.

    Multi-function

    Photocoulper Output

    Analog S ignal comm on

    E

    E

    MO 1

    MC M

    MI 1

    MI 2

    MI 3

    MI 4

    MI 6

    MI 5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Common

    Factorysetting

    Sw2

    AVI

    ACI

    Factory setting:ACI Mode

    ACI/AVI sw itchWhen switch ing to AVI,

    it indicates AVI2

    -

    8 1

    Sw1

    NPN

    PNP

    Factory setting:NPN Mode

    Please refer to Figu re 7for wiring of NPNmode and PNP

    mode.

    brake resistor

    (optional)

    Multi-function contact output

    Refer to chapter2.4 for deta ils.

    Factory setting ismalfunction indication

    Factory setting: output

    frequency

    4-20mA/0-10V

    T(L3)T(L3)

    BR

    B2

    RS-485 serial interface(NO T for VFD *E*C mod els)

    1: Reserved

    2: EV

    5: SG+6: Reserved

    7: Reserved8: Reserved

    3: GND

    4: SG -

    For VFD*E*C models,pleas e ref er to figu re 8.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    34/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-7

    Figure 5 for models of VFD-E SeriesVFD002E11T/21T, VFD004E11A/21T, VFD007E21T

    AVI

    AC I

    AC M

    B1

    +10V

    5K

    3

    2

    1

    Power supply+10V 20mA

    Master Frequency0 to 10V 47K

    Analog S ignal Co mmon E

    Main circuit (power) terminals Control circuit term inals Shielded leads & Cable

    E

    R(L1)S(L2)

    Fuse/NFB(No Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommended Circuitwhen powe r su pply

    is turned OFF by afault outputIf the fault occurs, thecontact will be O N toturn off the powe r andprotect the power system.

    R(L1)

    S(L2)

    E

    Analog Mul t i- fun c tionOutput Terminalfactory set ting: Analogfreq./ current meter0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    ACM

    RA

    RB

    RC

    Motor

    Factory setting:Drive is in operation48V50m A Max.

    Multi-function

    Photocou lper Ou tput

    Analog S ignal common

    E

    E

    MO 1

    MCM

    MI1MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Common

    Factorysetting

    Sw2

    AVI

    ACI

    Factory setting:ACI Mode

    ACI/AVI switchWhen switch ing to AVI,it indicates AVI2

    B2

    RS-485Serial interface

    1: Reserved

    2: EV

    5: SG+

    6: Reserved7: Reserved8: Reserved

    3: GND4: SG -

    8 1

    Sw1

    NPN

    PNP

    Factory setting:NPN Mode

    Please refer to Figure 7for wiring of NPNmode and PNP

    mode.

    BRbrake resistor

    (optional)

    Multi-function contact output

    Refer to chapter2.4 for details.Factory setting ismalfunction indication

    Factory setting: output

    frequency

    4-20mA/0-10V

    NOTE For VFD-E- T series, the braking resist or can be used by connect ing terminals ( B1 and B2) direct ly. B ut

    it can't connect DC-BUS in parallel.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    35/398

    Chapter 2 Installation and Wiring

    2-8 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Figure 6 for models of VFD-E SeriesVFD002E23T, VFD004E23T/43T, VFD007E23T/43T, VFD015E23T/43T

    AVI

    ACI

    ACM

    B1

    +10V

    5K

    3

    2

    1

    Power supply+10V 20mA

    Master Frequency0 to 10V 4 7K

    Analog S ignal Com mo n E

    Main circui t (powe r) terminals Control circuit terminals Shielded leads & Cable

    E

    R(L1)

    S(L2)

    Fuse/NFB(No Fuse Breaker)

    SA

    OF F ON

    MC

    MC

    RB

    RC

    Recommended Circuitwhen powe r s upply

    is tu rned OFF by afault outputIf the fault occurs, the

    contact will b e ON toturn off the powe r andprotect the power system.

    R(L1)

    S(L2)

    E

    Analog Mul t i- fun c tionOutput Terminalfactory set ting: Analogfreq./ current me ter0~10VDC/2mA

    U(T1)

    V(T2)

    W(T3)

    IM3~

    AFM

    ACM

    RA

    RB

    RC

    Motor

    Factory setting:Drive is in operation48V50mA Max.

    Multi-function

    Photocou lper Out put

    Analog S ignal common

    E

    E

    MO1

    MCM

    MI1MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Comm on

    Factorysetting

    Sw2

    AVI

    ACI

    Factory setting:ACI Mode

    ACI/AVI switch

    When switching to AVI,it indicates AVI2

    B2

    RS-485Serial interface

    1: Reserved

    2: EV

    5: SG +6: Reserved7: Reserved8: Reserved

    3: GND4: SG-

    8 1

    Sw1

    NPN

    PNP

    Factory setting:NPN Mode

    Please refer to Figure 7for wiring of NPNmode and PNP

    mode.

    BRbrake resistor

    (optional)

    Multi-function contact output

    Refer to chapter2.4 for details.Factory setting ismalfunction indication

    Factory setting: output

    frequency

    4-20mA/0-10V

    T(L3)T(L3)

    NOTE For VFD-E- T series, the braking resistor can be used by conne cting termin als (B1 and B2) dire ctly. But

    it can't connec t DC-BUS i n parallel.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    36/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-9

    Figure 7 Wiring for NPN mode and PNP mode

    A. NPN mode without external power

    Factorysetting

    NPN

    PN P

    B. NPN mode with external power

    Factorysetting

    NPN

    PN P

    24Vdc

    -

    +

    C. PNP mode without external power

    Sw1

    Factory

    setting

    NPN

    PN P

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    37/398

    Chapter 2 Installation and Wiring

    2-10 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    D. PNP mode with external power

    Sw1

    Factorysetting

    NP N

    PN P

    24Vdc -

    +

    Figure 8 RJ-45 pin definition for VFD*E*C models

    PIN Signal Description

    1 CAN_H CAN_H bus line (dominant high)

    2 CAN_L CAN_L bus line (dominant low)

    3 CAN_GND Ground / 0V /V-

    4 SG+ 485 communication

    5 SG- 485 communication

    7 CAN_GND Ground / 0V /V-

    CAUTION!

    1. The wiring of main circuit and control circuit should be separated to prevent erroneous actions.

    2. Please use shield wire for the control wiring and not to expose the peeled-off net in front of the

    terminal.

    3. Please use the shield wire or tube for the power wiring and ground the two ends of the shield

    wire or tube.

    4. Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it

    comes in contact with high voltage.

    5. The AC motor drive, motor and wiring may cause interference. To prevent the equipment

    damage, please take care of the erroneous actions of the surrounding sensors and the

    equipment.

    6. When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor terminalsU/T1, V/T2, and W/T3, respectively. To permanently reverse the direction of motor rotation,

    switch over any of the two motor leads.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    38/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-11

    7. With long motor cables, high capacitive switching current peaks can cause over-current, high

    leakage current or lower current readout accuracy. To prevent this, the motor cable should be

    less than 20m for 3.7kW models and below. And the cable should be less than 50m for 5.5kW

    models and above. For longer motor cables use an AC output reactor.

    8. The AC motor drive, electric welding machine and the greater horsepower motor should begrounded separately.

    9. Use ground leads that comply with local regulations and keep them as short as possible.

    10. No brake resistor is built in the VFD-E series, it can install brake resistor for those occasions

    that use higher load inertia or frequent start/stop. Refer to Appendix B for details.

    11. Multiple VFD-E units can be installed in one location. All the units should be grounded directly

    to a common ground terminal, as shown in the figure below.Ensure there are no ground

    loops.

    Excellent

    Good

    Not allowed

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    39/398

    Chapter 2 Installation and Wiring

    2-12 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    2.2 External Wiring

    Motor

    Output ACLine Reactor

    Power Supply

    Magneticcontactor

    Input ACLine Reactor

    EMI Filter

    R/L1 S/L2 T/L3

    U/T1 V/T2 W/T3

    +/B1

    B2

    Zero-phaseReactor

    Zero-phaseReactor

    FUSE/NFB

    -

    BR

    BUE

    Brake

    resistor

    Brakeunit

    Items Explanations

    Powersupply

    Please follow the specific power

    supply requirements shown inAppendix A.

    Fuse/NFB

    (Optional)

    There may be an inrush currentduring power up. Please check thechart of Appendix B and select thecorrect fuse with rated current. Use ofan NFB is optional.

    Magneticcontactor(Optional)

    Please do not use a Magneticcontactor as the I/O switch of the ACmotor drive, as it will reduce the

    operating life cycle of the AC drive.

    Input ACLine Reactor(Optional)

    Used to improve the input powerfactor, to reduce harmonics andprovide protection from AC linedisturbances. (surges, switchingspikes, short interruptions, etc.). ACline reactor should be installed whenthe power supply capacity is 500kVAor more or advanced capacity isactivated .The wiring distance shouldbe 10m. Refer to appendix B for

    details.

    Zero-phaseReactor(Ferrite CoreCommonChoke)(Optional)

    Zero phase reactors are used toreduce radio noise especially whenaudio equipment is installed near theinverter. Effective for noise reductionon both the input and output sides.Attenuation quality is good for a widerange from AM band to 10MHz.Appendix B specifies the zero phasereactor. (RF220X00A)

    EMI filter To reduce electromagneticinterference.

    Brakeresistor andBrake unit(Optional)

    Used to reduce the deceleration timeof the motor. Please refer to the chartin Appendix B for specific Brakeresistors.

    Output ACLine Reactor

    (Optional)

    Motor surge voltage amplitudedepends on motor cable length. Forapplications with long motor cable

    (>20m), it is necessary to install a

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    40/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-13

    2.3 Main Circuit

    2.3.1 Main Circuit Connection

    Figure 1For frame A: VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A,

    VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C,

    VFD007E21C/23C/43C, VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P,

    VFD007E11P/21P/23P/43P, VFD015E23P/43P

    R(L1)S(L2)

    T(L3)

    R

    S

    T

    U(T1)V(T2)

    W(T3)

    IM

    3~

    MC

    EE

    + -

    No fuse breaker (NFB)

    Brake Resistor(Optional)

    Motor

    BUE

    BRBrake Unit(Optional)

    Figure 2

    For frame B: VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A,

    VFD007E11C, VFD015E21C, VFD022E21C/23C/43C, VFD037E23C/43C

    For frame C: VFD055E23A/43A, VFD075E23A/43A, VFD110E23A/43A, VFD055E23C/43C,

    VFD075E23C/43C, VFD110E23C/43C

    For frame D: VFD150E23A/23C, VFD150E43A/43C, VFD185E43A/43C, VFD220E43A/43C

    R(L1)

    S(L2)

    T(L3)

    R

    S

    T

    U(T1)

    V(T2)

    W(T3)

    IM

    3~

    MC

    E

    E

    B2 -

    No fuse brea ker (NFB)

    Brake Resistor(Optional)

    Motor+/B1

    BR

    Figure 3

    For Frame A: VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T,

    VFD015E23T/43T

    R(L1)

    S(L2)

    T(L3)

    R

    S

    T

    U(T1)

    V(T2)

    W(T3)

    IM

    3~

    MC

    EE

    B1 B2

    No fuse breaker (NFB)

    Brake Resistor(Optional)

    Motor

    BR

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    41/398

  • 8/13/2019 VFD E User Manual

    42/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-15

    to the group 9 for details. Method2, control by the optional keypad KPE-LE02. Refer to

    Appendix B for details.

    When it needs to install the filter at the output side of terminals U/T1, V/T2, W/T3 on the

    AC motor drive. Please use inductance filter. Do not use phase-compensation capacitors

    or L-C (Inductance-Capacitance) or R-C (Resistance-Capacitance), unless approved byDelta.

    DO NOT connect phase-compensation capacitors or surge absorbers at the output

    terminals of AC motor drives.

    Use well-insulated motor, suitable for inverter operation.

    Terminals [+/B1, B2] for connecting brake resistor

    BR

    B2

    BR

    +/B1 B2

    BR

    B1 -

    BUE

    +/B1

    Brake resistor (optional)

    Brake unit (optional)Refer to Appendix B for details.

    Connect a brake resistor or brake unit in applications with frequent deceleration ramps,

    short deceleration time, too low brake torque or requiring increased brake torque.

    If the AC motor drive has a built-in brake chopper (frame B, frame C and VFDxxxExxT

    models), connect the external brake resistor to the terminals [+/B1, B2] or [B1, B2].

    Models of frame A dont have a built-in brake chopper. Please connect an external

    optional brake unit (BUE-series) and brake resistor. Refer to BUE series user manual for

    details.

    Connect the terminals [+(P), -(N)] of the brake unit to the AC motor drive terminals [+/B1, -

    ]. The length of wiring should be less than 5m with cable.

    When not used, please leave the terminals [+/B1, -] open.

    WARNING!

    Short-circuiting [B2] or [-] to [+/B1] can damage the AC motor drive.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    43/398

    Chapter 2 Installation and Wiring

    2-16 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    2.3.2 Main Circuit Terminals

    Frame A Main circuit terminals:

    R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , +, -

    Models Wire Torque Wire type

    VFD002E11A/21A/23A

    VFD004E11A/21A/23A/43A

    VFD007E21A/23A/43A

    VFD015E23A/43A

    VFD002E11C/21C/23C

    VFD004E11C/21C/23C/43C

    VFD007E21C/23C/43C

    VFD015E23C/43C

    VFD002E11T/21T/23T

    VFD004E11T/21T/23T/43T

    VFD007E21T/23T/43T

    VFD015E23T/43T

    VFD002E11P/21P/23P

    VFD004E11P/21P/23P/43P

    VFD007E21P/23P/43P

    VFD015E23P/43P

    12-14 AWG.(3.3-

    2.1mm2)

    14kgf-cm(12in-lbf)

    StrandedcopperOnly,

    75

    Frame B Main circuit terminals:

    R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , +/B1, B2, -

    Models Wire Torque Wire type

    VFD007E11A,

    VFD015E21A,

    VFD022E21A/23A/43A,

    VFD037E23A/43A,

    VFD007E11C,

    VFD015E21C,

    VFD022E21C/23C/43C,

    VFD037E23C/43C,

    8-18 AWG.(8.4-0.8mm

    2)

    18kgf-cm(15.6in-lbf)

    StrandedcopperOnly,75

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    44/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-17

    Frame C Main circuit terminals:

    R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , +/B1, B2, -

    Models Wire Torque Wire type

    VFD055E23A/43A,

    VFD075E23A/43A,

    VFD110E23A/43A,

    VFD055E23C/43C,

    VFD075E23C/43C,

    VFD110E23C/43C

    6-16 AWG.(13.3-1.3mm

    2)

    30kgf-cm

    (26in-lbf)

    Strandedcopper

    Only, 75

    NOTETo connect 6 AWG (13.3 mm2) wires, use Recognized Ring

    Terminals

    Frame D Main circuit terminals:

    R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , B1, B2, +, -

    Models Wire Torque Wire type

    VFD150E23A/23C,

    VFD150E43A/43C,

    VFD185E43A/43C,

    VFD220E43A/43C

    4-14 AWG.(21.2-

    2.1mm2)

    57kgf-cm

    (49.5in-lbf)

    Strandedcopper

    Only, 75

    2.4 Control Terminals

    Circuit diagram for digital inputs (NPN current 16mA.)

    +24

    NPN Mode

    multi-inputterminal

    Internal CircuitDCM +24V

    Multi-Input Terminal

    DCM

    Internal Circuit

    PNP Mode

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    45/398

    Chapter 2 Installation and Wiring

    2-18 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    The position of the control terminals

    RS-485

    10VMI1 MI2 MI3 MI4 MI5 MI6 DCM 24VDCM ACM AVI ACI

    AFM MCM MO1

    RA RB RC

    Terminal symbols and functions

    TerminalSymbol

    Terminal FunctionFactory Settings (NPN mode)

    ON: Connect to DCM

    MI1 Forward-Stop commandON: Run in MI1 direction

    OFF: Stop acc. to Stop Method

    MI2 Reverse-Stop commandON: Run in MI2 direction

    OFF: Stop acc. to Stop Method

    MI3 Multi-function Input 3

    MI4 Multi-function Input 4

    MI5 Multi-function Input 5

    MI6 Multi-function Input 6

    Refer to Pr.04.05 to Pr.04.08 for programming theMulti-function Inputs.

    ON: the activation current is 16mA.

    OFF: leakage current tolerance is 10A.

    +24V DC Voltage Source +24VDC, 20mA used for PNP mode.

    DCM Digital Signal CommonCommon for digital inputs and used for NPN

    mode.

    RAMulti-function Relay output(N.O.) a

    RBMulti-function Relay output(N.C.) b

    RC Multi-function Relay common

    Resistive Load:

    5A(N.O.)/3A(N.C.) 240VAC

    5A(N.O.)/3A(N.C.) 24VDC

    Inductive Load:

    1.5A(N.O.)/0.5A(N.C.) 240VAC

    1.5A(N.O.)/0.5A(N.C.) 24VDC

    Refer to Pr.03.00 for programming

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    46/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-19

    TerminalSymbol

    Terminal FunctionFactory Settings (NPN mode)

    ON: Connect to DCM

    MO1Multi-function Output 1(Photocoupler)

    Maximum 48VDC, 50mA

    Refer to Pr.03.01 for programming

    MO1-DCM

    Mo1

    MCM

    Max: 48Vdc 50mA

    internal circuit

    MCM Multi-function output common Common for Multi-function Outputs

    +10V Potentiometer power supply +10VDC 3mA

    AVI

    Analog voltage Input

    ACM

    AVI

    +10V

    internal circuit

    AVI circuit

    Impedance: 47k

    Resolution: 10 bits

    Range: 0 ~ 10VDC =

    0 ~ Max. Output Frequency(Pr.01.00)

    Selection: Pr.02.00, Pr.02.09, Pr.10.00Set-up: Pr.04.11 ~ Pr.04.14, 04.19~04.23

    ACMAnalog control signal(common)

    Common for AVI, ACI, AFM

    ACI

    Analog current Input

    ACM

    ACI

    internal circuit

    ACI ci rcuit

    Impedance: 250/100k

    Resolution: 10 bits

    Range: 4 ~ 20mA =

    0 ~ Max. Output Frequency

    (Pr.01.00)

    Selection: Pr.02.00, Pr.02.09, Pr.10.00

    Set-up: Pr.04.15 ~ Pr.04.18

    AFM

    Analog output meter

    AFM

    ACM

    0~10V

    Max. 2mApotentiometer

    ACM c ircu it

    internal circuit

    0 to 10V, 2mA

    Impedance: 100k

    Output current 2mA max

    Resolution: 8 bits

    Range: 0 ~ 10VDC

    Function: Pr.03.03 to Pr.03.04

    NOTE: Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    47/398

    Chapter 2 Installation and Wiring

    2-20 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Analog inputs (AVI, ACI, ACM)

    Analog input signals are easily affected by external noise. Use shielded wiring and keep it

    as short as possible (

  • 8/13/2019 VFD E User Manual

    48/398

    Chapter 2 Installation and Wiring

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 2-21

    RS-485 port

    10VMI1 MI2 MI3 MI4 MI5 MI6 DCM 24VDCM ACM AVI ACI

    AFM MCM MO1

    RA RB RC

    The position of the control terminals

    Terminals 2

    Terminals 1

    Frame Control Terminals Torque Wire

    Terminals 1 5 kgf-cm (4.4 in-lbf) 12-24 AWG (3.3-0.2mm2)

    A, B, CTerminals 2 2 kgf-cm (1.7 in-lbf) 16-24 AWG (1.3-0.2mm

    2)

    NOTE

    Frame A:VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A,

    VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C, VFD007E21C/23C/43C,

    VFD015E23C/43C, VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T,

    VFD015E23T/43T, VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, VFD007E21P/23P/43P,

    VFD015E23P/43P

    Frame B:VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A, VFD007E11C,

    VFD015E21C, VFD022E21C/23C/43C, VFD037E23C/43C

    Frame C:VFD055E23A/43A, VFD075E23A/43A, VFD110E23A/43A, VFD055E23C/43C,

    VFD075E23C/43C, VFD110E23C/43C

    Frame D: VFD150E23A/43A, VFD150E23C/43C, VFD185E43A/43C, VFD220E43A/43C

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    49/398

    Chapter 2 Installation and Wiring

    2-22 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    This page intentionally left blank

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    50/398

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 3-1

    Chapter 3 Keypad and Start Up

    Make sure that the wiring is correct. In particular, check that the

    output terminals U/T1, V/T2, W/T3. are NOT connected to power

    and that the drive is well grounded.

    Verify that no other equipment is connected to the AC motor drive

    Do NOT operate the AC motor drive with humid hands.

    Please check if READY LED is ON when power is applied. Check

    if the connection is well when option from the digital keypad KPE-

    LE02.

    It should be stopped when fault occurs during running and refer to

    Fault Code Information and Maintenance for solution. Please do

    NOT touch output terminals U, V, W when power is still applied to

    L1/R, L2/S, L3/T even when the AC motor drive has stopped. The

    DC-link capacitors may still be charged to hazardous voltage

    levels, even if the power has been turned off.

    3.1 Keypad

    There are three LEDs on the keypad:

    LED READY: It will light up after applying power. The light wont be off until the capacitors are

    discharged to safe voltage levels after power off.

    LED RUN: It will light up when the motor is running.

    LED FAULT: It will light up when fault occurs.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    51/398

    Chapter 3 Keypad and Start Up

    3-2 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    3.2 Operation Method

    The operation method can be set via communication, control terminals and optional keypad KPE-

    LE02.

    RS485 port (RJ-45)It needs to use VFD-USB01 orIFD8500 converter to connectto the PC.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    52/398

    Chapter 3 Keypad and Start Up

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 3-3

    3.3 Trial Run

    The factory setting of the operation source is from the external terminal (Pr.02.01=2).

    1. Both MI1-DCM and MI2-DCM need to connect a switch for switching FWD/STOP and

    REV/STOP.

    2. Please connect a potentiometer among AVI, 10V and DCM or apply power 0-10Vdc to

    AVI-DCM (as shown in figure 3-1)

    OperationMethod

    Frequency SourceOperation Command

    Source

    Operate from thecommunication

    When setting communication by the PC, it needs to use VFD-USB01 orIFD8500 converter to connect to the PC.

    Refer to the communication address 2000H and 2101H setting for details.

    * Don't apply the mains voltage directl y to above terminals.

    E

    MI1

    MI2

    MI3

    MI4

    MI6

    MI5

    DCM

    +24VFWD/Stop

    REV/Stop

    Multi-step 1

    Multi-step 2

    Multi-step 3

    Multi-step 4

    Digital Signal Common

    FactorysettingSw1

    NPN

    PNP

    Factory setting:NPN Mode

    AVI

    ACI

    ACM

    +10V

    5K

    3

    2

    1

    Power supply+10V 3mA

    Master Frequency0 to 10V 47K

    Analog Signal Common E

    Sw2

    AVI

    ACI

    Factory setting:ACI Mode

    ACI/AVI switchWhen switching to AVI,it indicates AVI2

    4-20mA/0-10V

    Figure 3-1

    Operate fromexternal signal

    MI3-DCM (Set Pr.04.05=10)

    MI4-DCM (Set Pr.04.06=11)

    External terminals input:

    MI1-DCM

    MI2-DCM

    Operate from theoptional keypad

    (KPE-LE02)

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    53/398

    Chapter 3 Keypad and Start Up

    3-4 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    3. Setting the potentiometer or AVI-DCM 0-10Vdc power to less than 1V.

    4. Setting MI1=On for forward running. And if you want to change to reverse running, you

    should set MI2=On. And if you want to decelerate to stop, please set MI1/MI2=Off.

    5. Check following items:

    Check if the motor direction of rotation is correct.

    Check if the motor runs steadily without abnormal noise and vibration.

    Check if acceleration and deceleration are smooth.

    If you want to perform a trial run by using optional digital keypad, please operate by the following

    steps.

    1. Connect digital keypad to AC motor drive

    correctly.

    2. After applying the power, verify that LED

    display shows F 0.0Hz.

    3. Set Pr.02.00=0 and Pr.02.01=0. (Refer to

    Appendix B operation flow for detail)

    4. Press key to set frequency toaround 5Hz.

    5. Press key for forward running.And if you want to change to reverse

    running, you should press in

    page. And if you want to

    decelerate to stop, please presskey.

    6. Check following items:

    Check if the motor direction of rotation

    is correct.

    Check if the motor runs steadily

    without abnormal noise and vibration.

    Check if acceleration and

    deceleration are smooth.

    If the results of trial run are normal, please start the formal run.

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    54/398

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-1

    Chapter 4 Parameters

    The VFD-E parameters are divided into 14 groups by property for easy setting. In most applications,

    the user can finish all parameter settings before start-up without the need for re-adjustment during

    operation.

    The 14 groups are as follows:

    Group 0: User Parameters

    Group 1: Basic Parameters

    Group 2: Operation Method Parameters

    Group 3: Output Function Parameters

    Group 4: Input Function Parameters

    Group 5: Multi-Step Speed Parameters

    Group 6: Protection Parameters

    Group 7: Motor ParametersGroup 8: Special Parameters

    Group 9: Communication Parameters

    Group 10: PID Control Parameters

    Group 11: Multi-function Input/Output Parameters for Extension Card

    Group 12: Analog Input/Output Parameters for Extension Card

    Group 13: PG function Parameters for Extension Card

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    55/398

    Chapter 4 Parameters

    4-2 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    4.1 Summary of Parameter Settings

    : The parameter can be set during operation.

    Group 0 User Parameters

    Parameter Explanation SettingsFactorySetting

    Customer

    00.00 Identity Code of theAC motor drive

    Read-only ##

    00.01 Rated CurrentDisplay of the ACmotor drive

    Read-only #.#

    0: Parameter can be read/written

    1: All parameters are read only

    6: Clear PLC program (NOT for VFD*E*Cmodels)

    9: All parameters are reset to factory settings(50Hz, 230V/400V or 220V/380V depends onPr.00.12)

    00.02 Parameter Reset

    10: All parameters are reset to factorysettings (60Hz, 220V/440V)

    0

    0: Display the frequency command value(Fxxx)

    1: Display the actual output frequency (Hxxx)

    2: Display the content of user-defined unit(Uxxx)

    3: Multifunction display, see Pr.00.04

    4: FWD/REV command

    00.03Start-up DisplaySelection

    5: PLCx (PLC selections: PLC0/PLC1/PLC2)

    (NOT for VFD*E*C models)

    0

    0: Display the content of user-defined unit(Uxxx)

    1: Display the counter value (c)

    2: Display PLC D1043 value (C) (NOT forVFD*E*C models)

    3: Display DC-BUS voltage (u)

    00.04Content of Multi-function Display

    4: Display output voltage (E)

    0

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    56/398

  • 8/13/2019 VFD E User Manual

    57/398

    Chapter 4 Parameters

    4-4 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Parameter Explanation SettingsFactorySetting

    Customer

    01.01Maximum VoltageFrequency (Fbase)(Motor 0)

    0.10 to 600.0 Hz 60.00

    115V/230V series: 0.1V to 255.0V 220.001.02 Maximum OutputVoltage (Vmax)(Motor 0) 460V series: 0.1V to 510.0V 440.0

    01.03Mid-Point Frequency(Fmid) (Motor 0)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.04

    Mid-Point Voltage(Vmid) (Motor 0)

    460V series: 0.1V to 510.0V 20.0

    01.05

    Minimum Output

    Frequency (Fmin)(Motor 0)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.06

    Minimum OutputVoltage (Vmin)(Motor 0) 460V series: 0.1V to 510.0V 20.0

    01.07Output FrequencyUpper Limit

    0.1 to 120.0%110.0

    01.08Output FrequencyLower Limit

    0.0 to100.0 %0.0

    01.09 Accel Time 1 0.1 to 600.0 / 0.01 to 600.0 sec 10.0

    01.10 Decel Time 1 0.1 to 600.0 / 0.01 to 600.0 sec 10.0

    01.11 Accel Time 2 0.1 to 600.0 / 0.01 to 600.0 sec 10.0

    01.12 Decel Time 2 0.1 to 600.0 / 0.01 to 600.0 sec 10.0

    01.13 Jog AccelerationTime

    0.1 to 600.0 / 0.01 to 600.0 sec1.0

    01.14 Jog DecelerationTime

    0.1 to 600.0 / 0.01 to 600.0 sec 1.0

    01.15 Jog Frequency 0.10 Hz to Fmax (Pr.01.00) Hz 6.00

    0: Linear Accel/Decel

    1: Auto Accel, Linear Decel

    2: Linear Accel, Auto Decel

    3: Auto Accel/Decel (Set by load)

    01.16

    Auto acceleration /deceleration (referto Accel/Decel timesetting)

    4: Auto Accel/Decel (set by Accel/DecelTime setting)

    0

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    58/398

    Chapter 4 Parameters

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-5

    Parameter Explanation SettingsFactorySetting

    Customer

    5: Linear Accel. controlled by current, linearDecel.

    01.16

    Auto acceleration /deceleration (referto Accel/Decel timesetting) 6: Linear Accel. controlled by current, auto

    Decel.

    0

    01.17Acceleration S-Curve

    0.0 to 10.0 / 0.00 to 10.00 sec 0.0

    01.18Deceleration S-Curve

    0.0 to 10.0 / 0.00 to 10.00 sec 0.0

    0: Unit: 0.1 sec01.19

    Accel/Decel TimeUnit

    1: Unit: 0.01 sec0

    01.20Delay Time at 0Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.21Delay Time at 10Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.22Delay Time at 20Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.23Delay Time at 30Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.24 Delay Time at 40Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.25Delay Time at 50Hzfor Simple Position

    0.00 to 600.00 sec0.00

    01.26Maximum VoltageFrequency (Fbase)(Motor 1)

    0.10 to 600.0 Hz 60.00

    115V/230V series: 0.1V to 255.0V 220.001.27

    Maximum OutputVoltage (Vmax)

    (Motor 1) 460V series: 0.1V to 510.0V 440.0

    01.28Mid-PointFrequency (Fmid)(Motor 1)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.29

    Mid-Point Voltage(Vmid) (Motor 1)

    460V series: 0.1V to 510.0V 20.0

    01.30Minimum OutputFrequency (Fmin)

    (Motor 1)

    0.10 to 600.0 Hz 1.50

    01.31 Minimum Output 115V/230V series: 0.1V to 255.0V 10.0

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    59/398

    Chapter 4 Parameters

    4-6 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Parameter Explanation SettingsFactorySetting

    Customer

    460V series: 0.1V to 510.0V 20.0

    01.32Maximum VoltageFrequency (Fbase)

    (Motor 2)

    0.10 to 600.0 Hz 60.00

    115V/230V series: 0.1V to 255.0V 220.001.33

    Maximum OutputVoltage (Vmax)(Motor 2) 460V series: 0.1V to 510.0V 440.0

    01.34Mid-PointFrequency (Fmid)(Motor 2)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.35

    Mid-Point Voltage

    (Vmid) (Motor 2) 460V series: 0.1V to 510.0V 20.0

    01.36Minimum OutputFrequency (Fmin)(Motor 2)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.37

    Minimum OutputVoltage (Vmin)(Motor 2) 460V series: 0.1V to 510.0V 20.0

    01.38

    Maximum Voltage

    Frequency (Fbase)(Motor 3) 0.10 to 600.0 Hz 60.00

    115V/230V series: 0.1V to 255.0V 220.001.39

    Maximum OutputVoltage (Vmax)(Motor 3) 460V series: 0.1V to 510.0V 440.0

    01.40Mid-PointFrequency (Fmid)(Motor 3)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.0

    01.41

    Mid-Point Voltage

    (Vmid) (Motor 3) 460V series: 0.1V to 510.0V 20.0

    01.42Minimum OutputFrequency (Fmin)(Motor 3)

    0.10 to 600.0 Hz 1.50

    115V/230V series: 0.1V to 255.0V 10.001.43

    Minimum OutputVoltage (Vmin)(Motor 3) 460V series: 0.1V to 510.0V 20.0

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    60/398

    Chapter 4 Parameters

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-7

    Group 2 Operation Method Parameters

    Parameter Explanation SettingsFactorySetting

    Customer

    02.00Source of FirstMaster FrequencyCommand

    0: Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN. Last used

    frequency saved.

    1: 0 to +10V from AVI

    2: 4 to 20mA from ACI or 0 to +10V fromAVI2

    3: RS-485 (RJ-45)/USB communication

    4: Digital keypad potentiometer

    5: CANopen communication

    1

    0: Digital keypad

    1: External terminals. Keypad STOP/RESETenabled.

    2: External terminals. Keypad STOP/RESETdisabled.

    3: RS-485 (RJ-45)/USB communication.Keypad STOP/RESET enabled.

    4: RS-485 (RJ-45)/USB communication.Keypad STOP/RESET disabled.

    02.01Source of FirstOperationCommand

    5: CANopen communication. KeypadSTOP/RESET disabled.

    1

    0: STOP: ramp to stop; E.F.: coast to stop

    1: STOP: coast to stop; E.F.: coast to stop

    2: STOP: ramp to stop; E.F.: ramp to stop02.02 Stop Method

    3: STOP: coast to stop; E.F.: ramp to stop

    0

    02.03

    PWM Carrier

    FrequencySelections

    1 to 15kHz 8

    0: Enable forward/reverse operation

    1: Disable reverse operation02.04Motor DirectionControl

    2: Disabled forward operation

    0

    0: Disable. Operation status is not changedeven if operation command source Pr.02.01is changed.

    02.05 Line Start Lockout

    1: Enable. Operation status is not changedeven if operation command source Pr.02.01is changed.

    1

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    61/398

    Chapter 4 Parameters

    4-8 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Parameter Explanation SettingsFactorySetting

    Customer

    2: Disable. Operation status will change ifoperation command source Pr.02.01 ischanged.

    3: Enable. Operation status will change ifoperation command source Pr.02.01 ischanged.

    0: Decelerate to 0 Hz

    1: Coast to stop and display AErr02.06

    Loss of ACI Signal(4-20mA)

    2: Continue operation by last frequencycommand

    1

    0: by UP/DOWN Key

    1: Based on accel/decel time

    2: Constant speed (Pr.02.08)02.07 Up/Down Mode

    3: Pulse input unit (Pr.02.08)

    0

    02.08

    Accel/Decel Rate ofChange ofUP/DOWNOperation withConstant Speed

    0.01~10.00 Hz 0.01

    02.09Source of SecondFrequencyCommand

    0: Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN. Last usedfrequency saved.

    1: 0 to +10V from AVI

    2: 4 to 20mA from ACI or 0 to +10V fromAVI2

    3: RS-485 (RJ-45)/USB communication

    4: Digital keypad potentiometer

    5: CANopen communication

    0

    02.10

    Combination of theFirst and SecondMaster FrequencyCommand

    0: First Master Frequency Command

    1: First Master Frequency Command+Second Master Frequency Command

    2: First Master Frequency Command -Second Master Frequency Command

    0

    02.11Keypad FrequencyCommand

    0.00 to 600.0Hz60.00

    02.12CommunicationFrequencyCommand

    0.00 to 600.0Hz60.00

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    62/398

    Chapter 4 Parameters

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-9

    Parameter Explanation SettingsFactorySetting

    Customer

    0: Save Keypad & CommunicationFrequency

    1: Save Keypad Frequency only02.13

    The Selections forSaving Keypad orCommunication

    FrequencyCommand

    2: Save Communication Frequency only

    0

    0: by Current Freq Command

    1: by Zero Freq Command02.14

    Initial FrequencySelection (forkeypad &RS485/USB) 2: by Frequency Display at Stop

    0

    02.15Initial FrequencySetpoint (for keypad

    & RS485/USB)

    0.00 ~ 600.0Hz 60.00

    02.16Display the MasterFreq CommandSource

    Read Only

    Bit0=1: by First Freq Source (Pr.02.00)

    Bit1=1: by Second Freq Source (Pr.02.09)

    Bit2=1: by Multi-input function

    Bit3=1: by PLC Freq command (NOT forVFD*E*C models)

    ##

    02.17Display theOperationCommand Source

    Read Only

    Bit0=1: by Digital Keypad

    Bit1=1: by RS485 communication

    Bit2=1: by External Terminal 2/3 wire mode

    Bit3=1: by Multi-input function

    Bit4=1: by PLC Operation Command (NOTfor VFD*E*C models)

    Bit5=1: by CANopen communication

    ##

    02.18Selection of CarrierModulation

    0: by carrier modulation of load current and

    temperature1: by carrier modulation of load current

    0

    Group 3 Output Function Parameters

    Parameter Explanation SettingsFactorySetting

    Customer

    0: No function

    1: AC drive operational

    2: Master frequency attained

    03.00Multi-functionOutput Relay (RA1,

    RB1, RC1)

    3: Zero speed

    8

    4: Over torque detection

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    63/398

    Chapter 4 Parameters

    4-10 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Parameter Explanation SettingsFactorySetting

    Customer

    5: Base-Block (B.B.) indication 1

    6: Low-voltage indication03.01Multi-functionOutput TerminalMO1

    7: Operation mode indication8: Fault indication

    9: Desired frequency 1 attained

    10: Terminal count value attained

    11: Preliminary count value attained

    12: Over Voltage Stall supervision

    13: Over Current Stall supervision

    14: Heat sink overheat warning

    15: Over Voltage supervision

    16: PID supervision

    17: Forward command

    18: Reverse command

    19: Zero speed output signal

    20: Warning(FbE,Cexx, AoL2, AUE, SAvE)

    21: Brake control (Desired frequencyattained)

    22: Drive ready

    23: Desired frequency 2 attained

    03.02 Desired Frequency1 Attained

    0.00 to 600.0Hz 0.00

    0: Analog frequency meter03.03

    Analog OutputSignal Selection

    (AFM) 1: Analog current meter

    0

    03.04 Analog Output Gain 1 to 200% 100

    03.05 Terminal CountValue

    0 to 9999 0

    03.06Preliminary CountValue

    0 to 9999 0

    0: Terminal count value attained, no EFdisplay

    03.07EF Active WhenTerminal CountValue Attained 1: Terminal count value attained, EF active

    0

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    64/398

    Chapter 4 Parameters

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-11

    Parameter Explanation SettingsFactorySetting

    Customer

    0: Fan always ON

    1: 1 minute after AC motor drive stops, fanwill be OFF

    2: Fan ON when AC motor drive runs, fanOFF when AC motor drive stops

    03.08 Fan Control

    3: Fan ON when preliminary heatsinktemperature attained

    0

    Read only

    Bit0=1:RLY used by PLC

    Bit1=1:MO1 used by PLC

    Bit2=1:MO2/RA2 used by PLC

    Bit3=1:MO3/RA3 used by PLC

    Bit4=1:MO4/RA4 used by PLC

    Bit5=1:MO5/RA5 used by PLC

    Bit6=1:MO6/RA6 used by PLC

    03.09

    The Digital OutputUsed by PLC

    (NOT for VFD*E*Cmodels)

    Bit7=1:MO7/RA7 used by PLC

    ##

    Read only

    Bit0=1:AFM used by PLC

    Bit1=1: AO1 used by PLC03.10

    The Analog OutputUsed by PLC

    (NOT for VFD*E*Cmodels)

    Bit2=1: AO2 used by PLC

    ##

    03.11Brake ReleaseFrequency

    0.00 to 20.00Hz 0.00

    03.12

    Brake Engage

    Frequency 0.00 to 20.00Hz 0.00

    03.13Display the Status ofMulti-functionOutput Terminals

    Read only

    Bit0: RLY Status

    Bit1: MO1 Status

    Bit2: MO2/RA2 Status

    Bit3: MO3/RA3 Status

    Bit4: MO4/RA4 Status

    Bit5: MO5/RA5 Status

    Bit6: MO6/RA6 Status

    Bit7: MO7/RA7 Status

    ##

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    65/398

    Chapter 4 Parameters

    4-12 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14

    Parameter Explanation SettingsFactorySetting

    Customer

    03.14Desired Frequency2 Attained

    0.00 to 600.0Hz 0.00

    Group 4 Input Function Parameters

    Parameter Explanation SettingsFactorySetting

    Customer

    04.00KeypadPotentiometer Bias

    0.0 to 200.0 % 0.0

    04.01KeypadPotentiometer BiasPolarity

    0: Positive bias

    1: Negative bias00

    04.02KeypadPotentiometer Gain

    0.1 to 200.0 % 100.0

    0: No negative bias command

    04.03

    KeypadPotentiometerNegative Bias,Reverse MotionEnable/Disable

    1: Negative bias: REV motion enabled

    0

    0: 2-wire: FWD/STOP, REV/STOP

    1: 2-wire: FWD/REV, RUN/STOP

    04.04 2-wire/3-wireOperation ControlModes

    2: 3-wire operation

    0

    0: No function 1

    1: Multi-Step speed command 1

    04.05 Multi-function InputTerminal (MI3)

    2: Multi-Step speed command 2

    3: Multi-Step speed command 3 2

    4: Multi-Step speed command 4

    04.06 Multi-function InputTerminal (MI4)

    5: External reset

    6: Accel/Decel inhibit 3

    7: Accel/Decel time selection command

    04.07 Multi-function InputTerminal (MI5)

    8: Jog Operation

    9: External base block 4

    10: Up: Increment master frequency

    04.08 Multi-function Input

    Terminal (MI6)

    11: Down: Decrement master frequency

    CALL NOW 800-985-6929 http://www.automatedpt.com

    CALL NOW 800-985-6929 http://www.automatedpt.com

  • 8/13/2019 VFD E User Manual

    66/398

    Chapter 4 Parameters

    Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 4-13

    Parameter Explanation SettingsFactorySetting

    Customer

    12: Counter Trigger Signal

    13: Counter reset

    14: E.F. External Fault Input15: PID function disabled

    16: Output shutoff stop

    17: Parameter lock enable

    18: Operation command selection (externalterminals)

    19: O